05000339/LER-1981-013-03, /03L-0:on 810126,containment Hi & hi-hi Pressure Channel III Annunciator Energized.Caused by Instrument Drift in Nonisolated Power Supply Card S/N 5088,increasing Output Voltage.Card Replaced & Channel Calibr

From kanterella
(Redirected from ML19341C244)
Jump to navigation Jump to search
/03L-0:on 810126,containment Hi & hi-hi Pressure Channel III Annunciator Energized.Caused by Instrument Drift in Nonisolated Power Supply Card S/N 5088,increasing Output Voltage.Card Replaced & Channel Calibr
ML19341C244
Person / Time
Site: North Anna Dominion icon.png
Issue date: 02/25/1981
From: Cartwright W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML19341C243 List:
References
LER-81-013-03L-01, LER-81-13-3L-1, NUDOCS 8103020522
Download: ML19341C244 (2)


LER-1981-013, /03L-0:on 810126,containment Hi & hi-hi Pressure Channel III Annunciator Energized.Caused by Instrument Drift in Nonisolated Power Supply Card S/N 5088,increasing Output Voltage.Card Replaced & Channel Calibr
Event date:
Report date:
3391981013R03 - NRC Website

text

,

7 U.S. NUCLEAR REGULATORY COMMISSION O

LICENSEE EVENT REPORT CONTROL BLOCK / / / / / / / (1)

(PLEASE PRINT OR TYPE ALL REQUIRED INFORMATION)

/0/1/

/V/A/N/A/S/2/ (2)

/0/0/-/0/0/0/0/0/-/0/0/ (3)

/4/1/1/1/1 (4)

/ / / (5)

LICENSEE CODE LICENSE NUMBER LICENSE TYPE CAT

/0/1/

REP 0R

/L/ (6)

/0/5/0/0/0/3/3/9/

(7)

/0/1/2/6/8/1/

(8) / / / / / / / (9) g DOCKET NUMBER EVENT DATE REPORT DATE EVENT DESCRIPTION AND PROBABLE CONSEQUENCES (10)

/0/2/

/ On January 26, 1981, the containment Hi and Hi-Hi channel III annunciator became /

/0/3/

/ energized. After ensuring that a high pressure did not exist, the channel was /

/0/4/

/ placed in the tripped condition and declared inoperable. Containment pressure

/

/0/5/

/ channels I, II and IV remained operational to initiate a CDA if required, there- /

-/0/6/

/ fore the health and safety of the public were not affected. This event is

/

/0/7/

/ reportable pursuant to T.S. 6.9.1.9.b.

/

/0/8/

/

/

SYSTEM

CAUSE

CAUSE COMP.

VALVE CODE CODE SUBCODE COMPONENT CODE SUBCODE SUBCODE

'/0/9/

/I/B/ (11) [EL (12) /G/ (13) /I/N/S/T/R/U/ (14) /C/ (15)

/Z/ (16)

SEQUENTIAL OCCURRENCE REPORT REVISION LER/R0 EVENT YEAR REPORT NO.

CODE TYPE NO.

(17) REPORT NUMBER

/8/1/

/-/ /0/1/3/

/\\/

/0/3/

/L/

/-/

/0/

ACTION FUTURE EFFECT SHUTDOWN ATTACHMENT NPRD-4 PRIME COMP. COMPONENT TAKEN

. ACTION ON PLANT METHOD HOURS SUBMITTED FORM SUB. SUPPLIER MANUFACTURER [A/ (18) /Z/ (19) /Z/ (20) /Z/_(21) /0/0/0/0/ (22) /Y/ (23) /N/ (24) /A/ (25) /W/1/2/0/ (26)

CAUSE DESCRIPTION AND CORRECTIVE ACTIONS (27)

/1/0/

/ The power supply card (S/N 5088) drifted high causing an increase in output

/

-/1/1/

/ voltage. The faulty card was replaced, the channel calibrated and declared

/

/1/2/

/ operable.

/

/1/3/

/

/

/1/4/

/

/

FACILITY METHOD OF STATUS

% POWER OTHER STATUS DISCOVERY DISCOVERY DESCRIPTION (32)

/1/5/

/E/ (28)

/1/0/0/ (29) /

NA

/ (30) [AL (31) / Operator Observation /

ACTIVITY CONTENT RELEASED OF RELEASE AMOUNT OF ACTIVITY (35)

LOCATION OF RELEASE (36)

./1/6/

/Z/-(33)

/Z/ (34) /

NA

/

/

NA

/

PERSONNEL EXPOSURES NUMBER TYPE

. DESCRIPTION,(39)

/1/7/ /0/0/0/ (37) /Z/ (38) /

' NA

/

- PERSONNEL INJURTES NUMBER DESCRIPTION (41)

/1/8/ /0/0/0/ (40) /

NA

/

LOSS OF OR DAMAGE TO FACILITY (43)

TYPE

DESCRIPTION

L/1/9/ _[Z[ (42) /

NA

/

PUBLICITY ISSUED DESCRIPTION (45)

NRC USE ONLY

/2/0/-

[NL(44) /

NA

/////////////

NAME OF PREPARER W. R. CARTWRIGHT PHONE (703) 894-5151

'81030 2 0$$3-

^

N Virginia Electric and Power Company North Anna Power Station, Unit 2 Attachment: Page 1 of 1 Docket No. 50-339 Report No. LER 81-013/03L-0

Description of Event

On January 26, 1981, during steady state operation, the Containment Hi and Hi-Hi pressure channel III annunciator energized. After determining

. that an actual high pressure did not exist, the channel was placed in the trip condition and declared inoperable.

- Probable Consequences of Occurrence The consequences of this event were limited because three out of the four containment pressure channels remained operable to initiate a
- Containment Depressurization Actuation if required. Therefore, the health and safety of the general public were not affected.

Cause of Event

This event was caused by instrument drift in the non-isolated power supply. card.

Immediate Corrective Action

The-affected channel was placed in the trip position within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> as required by T.S. 3.3.2.1.

The affected power supply was' replaced,

- the channel was calibrated and returned to service.

' Scheduled Cctrective Action

~ No 'further action required.'

Actions Taken to Prevent Recurrence No further action required.