Forwards LER 81-013/03L-0
Date released: 12/21/2019 Download: ML19341C243


LER 81-013/03L-0:on 810126,containment Hi & hi-hi Pressure Channel III Annunciator Energized.Caused by Instrument Drift in Nonisolated Power Supply Card S/N 5088,increasing Output Voltage.Card Replaced & Channel Calibr
ML19341C244
Person / Time
Site: North Anna 
Issue date: 02/25/1981
From: Cartwright W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19341C244 (2)
Forwards LER 81-013/03L-0
ML19341C242
Person / Time
Site: North Anna 
Issue date: 02/25/1981
From: Cartwright W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19341C242 (1)