05000339/LER-1980-050-03, /03L-0:on 800902,during Mode 5,pressurizer power- Operated Relief Valve Was Inoperable When Nitrogen Supply Dropped.Caused by Low Nitrogen Pressure.Pressure Was Restored in 12-h by Renewing Supply & Pressurizing Tanks

From kanterella
(Redirected from ML19338F089)
Jump to navigation Jump to search
/03L-0:on 800902,during Mode 5,pressurizer power- Operated Relief Valve Was Inoperable When Nitrogen Supply Dropped.Caused by Low Nitrogen Pressure.Pressure Was Restored in 12-h by Renewing Supply & Pressurizing Tanks
ML19338F089
Person / Time
Site: North Anna 
Issue date: 10/01/1980
From: Cartwright W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML19338F076 List:
References
LER-80-050-03L-02, LER-80-50-3L-2, NUDOCS 8010070512
Download: ML19338F089 (2)


LER-1980-050, /03L-0:on 800902,during Mode 5,pressurizer power- Operated Relief Valve Was Inoperable When Nitrogen Supply Dropped.Caused by Low Nitrogen Pressure.Pressure Was Restored in 12-h by Renewing Supply & Pressurizing Tanks
Event date:
Report date:
3391980050R03 - NRC Website

text

o a

g U.S. NUCLEAR REGULATORY COMMISSION LICENSEE EVENT REPORT CONTROL BLOCK / / / / / / / (1) (PLEAiE PRINT OR TYPE ALL REQUIRED INFORMATION)

/0/1/

/V/A/N/A/S/2/ (2)

/0/0/-/0/0/0/0/0/-/0/0/ (3)

/4/1/1/1/1 (4)

/ / / (5)

LICENSEE CODE LICENSE NUMBER LICENSE TYPE CAT

/

(6)

/0/5/0/0/0/3/3/9/ (7)

/0/9/0/2/8/0/ (8) hhhhMN/ M OUR DOCKET NUMBER EVENT DATE REPORT DATE EVENT DESCRIPTION AND PROBABLE CONSEQUENCES (10)

/0/2/

/

During Mode 5 operation, a pressurizer power operated relief valve was declared /

/0/3/

/

inoperable when the nitrogen gas supply dropped below 1750 psig.

The nitrogen /

/0/4/

/

pressure was restored within seven days in accordance with T.S. 3.4.9.3. There-/

/0/5/

/

fore, the health and safety of the public were not affected. This item is

/

/0/6/

/

reportable pursuant to T.S. 6.9.1.9.b.

__ _ /

/0/7/

/

/

/0/8/

/

/

SYSTEM

CAUSE

CAUSE COMP.

VALVE CODE CODE SUBCODE COMPONENT CODE SUBCODE SUBCODE

/0/9/

/C/J/ (11) /B/ (12) /A/ (13) /Z/Z/Z/Z/Z/2/ (14) g/ (15) g/ (16)

SEQUENTIAL OCCURRENCE REPORT REVISION LER/R0 EVENT YEAR REPORT NO.

CODE TYPE NO.

(17) REPORT NUMBER

/8/0/

/-/ /0/5/0/

/\\/

/0/3/

/L/

/-/

g/

ACTION FUTURE EFFECT SHUTDOWN ATTACHMENT NPRD-4 PRIME COMP. COMPONENT TAKEN ACTION ON PLANT METHOD HOURS SUBMITTED FORM SUB. SUPPLIER MANUFACTURER

/X/ (18) /F/ (19) /C/ (20) /Z/ (21) /0/0/0/0/ (22) g/ (23) /N/ (24) /A/ (25) /S/4/2/0/ (26 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS (27)

/1/0/

/

The PORV was made inoperable due to low nitrogen pressure. Nitrogen is re-

/

/1/1/

/

quired to cycle the valve during conditions wherein overpressure protection is /

/1/2/

/

required. The nitrogen pressure was restored in about 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> by renewing

/

/1/3/

/

the supply and pressurizing the PORV nitrogen tanks.

/

/1/4/

/

/

FACILITY METHOD OF STATUS

% POWER OTHER STATUS DISCOVERY DESCRIPTION (32)

/ (30) DISCOVERY

/1/5/

/B/ (28)

/0/0/0/ (29) /

NA

/A/ (31)

/ Operator Observation /

ACTIVITY CONTENT RELEASED OF RELEASE AMOUNT OF ACTIVITY (35)

LOCATION OF RELEASE (36)

/1/6/

g/_(33)

[Zf (34) /

NA

/

/

NA

/

PERSONNEL EXPOSURES NUMBER TYPE DESCRIPTION (39)

[1/ 7/. /0/0/0f (37) [Z[ (38) /

NA

/

PERSONNEL INJURIES NUMBER DESCRIPTION (41)

)

/1/8/ /0/0/0/ (40) /

NA

/

1 LOSS OF OR DAMAGE TO FACILITY b3)

TYPE

DESCRIPTION

/1/9/,

LZf (42) /

NA

/

Z PUBLICITY ISSUED DESCRIPTION (45)

NRC USE ONLY

/2/0/

/N/ (44) /

NA

/////////////

NAME OF PREPARER W. R. CARTWRIGHT PHONE (703) 894-5151 8 010070 Q g

^s I

Virginia Electric and Power Company North Anna Power Station, Unit #2 Attachment: Page 1 of 1 Docket No. 50-339 Attachment to LER 80-050/03L-0

Description of Event

On September 2, 1980, during Mode 5 operation, the pressurizer power operated relief valves (PORV's) were required to be operable for overpressure protection in accordance with T.S. 3.4.9.3.

In this condition, nitrogen is used as the cycling medium for the PORV's.

The nitrogen supply pressure dropped to below the pressure necessary to maintain the PORV's in an operable status.

4 Probable Consequences of Event Overpressure protection for cold shutdown condition is required to prevent pressurization in the non-ductile range of the materials used in the reactor coolant system. Since the nitrogen pressure was restored d

within seven days as requried by T.S. 3.4.9.3, there was no affect on the health and safety of the public.

1

Cause of Event

The cause of the PORV becoming inoperable was the nitrogen supply tank pressure dropping below the pressure necessary to provide this J

protection function. The low nitrogen supply in this system was created by excessive usage of nitrogen throughout the station and an inadequate method for replenishing this supply.

Immediate Corrective Action

The nitrogen supply tanks were recharged and the system returned to normal.

)

Scheduled Corrective Action The nitrogen supply system has been investigated and recommended corrective actions have been proposed. Future corrective action will be taken based on the review and acceptability of these proposals.

Actions Taken to Prevent Recurrence No further actions are required.

Generic Implications There are no generic implications associated with this event.

l t

Y