LER 80-021/03L-0:on 800506,during Routine Testing to Prove Diesel operability,13U Diesel Generator Breaker Closed After Manual Opening.Caused by Loose Bolt in Generator Spring Charging Sys Causing Latch to Fail.Bolt Tightened
ML19323H068
Person / Time
Site: Millstone Dominion icon.png
Issue date: 06/04/1980
From: Foster E
NORTHEAST NUCLEAR ENERGY CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML19323H059 List:
References
LER-80-021-03L, LER-80-21-3L, NUDOCS 8006110256
Download: ML19323H068 (1)


Text

LICENSEE EVENI HEmHT

'cor717IOt ntt K: l l l l l l j (PtrASE PRINT On TYPE Att REQUIRED INFORMATION) i o@

~S

~ s 9

[c l T l rul1 sl 2l@[ 0 ] 01 -l 0 l OLICiIfdSt0 nut.9HE L 8 CENSE E CODE 14 1:n l 0 l 0 l - l 0101@l 4 j 1 11 l 1 L1_J@[ l l@

H 25 20 I "L F45 E 1YPE JD 57 LA1b8 orrT i j 1_] ) "5E $ ( l}@l 0l 5 l 0l 0 l 0 ] 3 ] 3 l 6 l@l 0 l 5 l 0 l 6 l 8 l 0 l@[0 l 6 l 0 l 4 l 8_LO_j@

8'v 00 61 DOCKET NUMHER EG 63 LVEtJT DAT E 74 75 HEPORT DATE 60

- EVENT DESCRIPTION AND PROBAutE CONSEQUENCES @

>T21 l Durina routine testina to prove Diesel operability, the 13U Diesel Generator Breaker I

,j3j j was opened manually per procedure. The Diesel Generator Breaker (General Electric I gg [ Magne-blast Type AM-4.16-250-9H) reclosed itself thereby returnino the Generator l y l on line out of phase. Operability surveillances for the other Facility were completedl gg l and operations continued per Technical Specification 3.8.1.1.a. I dlj l .

I m il i I 8 9 EO C D CODE SUBC E COMPONENT CODE SUBC dE Sb DE ijoj l Ej El@ l E l@ l B l@ l Cl Kl Tl Bl Rl Kl@ l Al@ [ Z j @

8 9 10 11 12 13 19 19 20_

_ SE QUE NTI AL OCCU R R E tJCE REPORT REVISION LE R EVE rJT YE AR REPOR T NO. CODE TYPE 00.

@ rg/RO

_ 21

[8 l0 l 22 l_l 23 l0 l2 l1 26l 24 l/] l 0l 3l lLl l-l [320]

27 29 29 30 31 T KEf A T O PL Ar T ET O HOURS 22 S Bf I k FO . SUR. SUPPLIE M Af ACTURER l33E lgl34Z l g l5Zlg 3

l Z l@

36 l0 l0 l0 lY l 31 l N[ g 41 lY l g l Al g l Gl 0] 8j 0l{

40 42 43 44 47 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS h 3;Oj l A loose bolt in the 13U Diesel Generator Breaker's Sprino Charoino Svstem caused the I

, ;i ; l closing latch to fail. The bolt was retightened and the breaker tested and returned _j y [ to service. Total time out of service was 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />. Other similar breakers were 1 l

l g l inspected and found satisfactory. There are no known similar incidents. I l 14 I I I 8 9 80 STA S  % POWER OTH F R STATUS ISCOV RY DISCOVERY DESCRIPTION I 5 l I E l@ l1 l 0 l 0 jgl f1A l l Algl Operator observation l i2 n 44 4s 4c e0 "JTiviTY CO TENT SELE Or RrLE ASE LOCATION OF RELEASE @