ML19323D193
| ML19323D193 | |
| Person / Time | |
|---|---|
| Site: | River Bend |
| Issue date: | 04/21/1980 |
| From: | Seyfrit K NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV) |
| To: | Weigand J GULF STATES UTILITIES CO. |
| References | |
| NUDOCS 8005210241 | |
| Download: ML19323D193 (1) | |
Text
'
PDR LPDR#
TIC UNITED STATES C
pa macu T q%,
NUCLEAR REGULATORY COMMISSION y
g%
REGloN IV 3
O 611 RYAN PLAZA DRIVE, SUITE 10uo 7 !! #I
" (r..
"j ARLINGTON, TEXAS 76012
.s ]
April 21, 1980 In Rtply Refer To:
RIV Dockst Nos.
50-458/IE Information Notice Nc. 80-15 50-459/IE Information Notice No. 80-15 Gulf States Utilities Attn:
Dr. J. G. Weigand, Vice President Operations and Technical Systems Post Office Box 2951 Beaumont, Texas 77704 Gentlemen:
This IE Information Notice is provided as an early notification of a possibly significant matter.
It is expected that recipients will review the information for possible applicability to their facilities.
No specific action or response is requested at this time. If further NRC evaluations so indicate, an IZ Circular or Bulletin will be issued to recommend or request specific licensee j
actions.
If you have questions regarding this matter, please contact the Director of the appropriate NRC Regional Office.
Sincerely,
/ /
t[
V.
/
Director
Enclosures:
1.
IE Information Notice No. 80-15 2.
List of Recently Issued IE Inform
- ton Notices
~
8 o 0s 1024//
o 9
IF SSINS No.:
6870 Accession No.
UNITED STATES 8002280660 NUCLEAR REGULATCRY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.
20555 IE Information Notice No. 60-15 Date:
April 21, 1980 Page 1 of 1 AXIALLY (LONGITUDINAL) ORIENTED CRACKING IN PIPING On March 8, 1980, the Commonwealth Edison Company reported to the NRC that slight leakage was observed from the "A" loop core spray injection piping during a reactor coolant system leakage test at their Quad-Cities Unit 2 Nuclear Power Station.
The source of leakage was subsequently identified to be located adjacent to a shop weld joining a 90* elbow and a wedge section of elbow material used to extend the elbow to 105.
Subsequent ultrasonic inspections revealed additional cracking in several other elbows in "A" and "B" core spray loops.
The cracks are located adjacent to welds and oriented transverse to the weld in the axial (longitudinal) piping direction.
The affected elbows have been removed, and failure analyses are in progress.
Preliminary results from liquid penetrant examinations of the elbow interior surface in the counter bore / weld root area revealed axially oriented cracks on both sides of the weld in the counter bores adjacent to the weld roots. From the limited metallography performed to date, the cracking mode appears to be intergranular stress corrosion cracking.
The cracking, however, only appears to be slightly branched. A determination as to whether or not the cracking extends into and across the welds cannot be made at this time.
It is significant to point out that these service sensitive lincs, as defined by NUREG 313, had been examined on an augmented basis per NUREG 313 requirements.
Two of the affected welds were inspected ultrasonically during the current outage, prior to the leakage being observed at the pressure test, with no indication of cracking reported. Further ultrasonic examinatioas, using standard ASME Section XI methods, performed after discovery of the leak clearly revealed the cracking (approximately 100% over the reference level).
Licensees are requested to inform NDE inspection personnel of the above stated information and to emphasize the need for care when performing circumferential UT scans of the weld and adjacent areas in piping components.
Particular importance should be stressed when the examinations are performed on BWR service sensitive 304 stainless steel piping and on PWR 304 stainless steel piping in stagnant systems.
This Information Notice is provided as an early notification of a possibly
]
significant matter that is still under review by the NRC staff.
It is expected that recipients will review the information for possible applicability to their facility. No specific action or response is requested at this time.
If you have any questions regarding this matter, please contact the Director of the appropriate NRC Regional Office.
l
5 Dr IE Information Notice No. 80-15 April 21, 1980 LISTING OF RECENTLY ISSUED IE INFORMATION NOTICES Information Subject Date Issued To Notice No.
Issued 80-10 Partial Loss of Non-Nuclear 3/7/80 All Power reactor Instrument System Power facilities holding Supply During Operation Operating Licenses (OLs) and Construction Permits (cps) 80-11 General Problems with ASCO 3/14/80 All holders of Reactor Valves in Nuclear Application Operating License (OL),
Including Fire Protection Construction Permit (CP),
Systems fuel fabrication and processing facilities 80-12 Instrument Failure Causes 3/31/80 All holders of Power Openirg of PORV and Block Reactor Operating Valve Licenses (OLs) and Construction Permits (cps) 80-13 General Electric Type SBM 4/2/80 All light water reactor Control Switches - Defective facilities holding power Cam Followers reactor Operating Licenses (OLs) and Construction Permits (cps) 80-14 Safety Saggestions From 4/2/80 All power reactor Employees facilities with an Operating License (OL) or Construction Permit (CP)
Enclosure
..-