$O Report on C?.DCS 3reaker Cabinet Seis=ic Qualification jv
-l O )
Thir report, pursuant to 10 CFR 50.53(e) on 'Significant Deficiencies, is to S
document the investigation of the significant deficiency 'in the seis=ic qual-U ification on the Control Rod Drive Control Syste= Trip Breaker Cabinets.
t f
Identification of Proble=s A reevaluation of the seis=ic qualification of the control rod drive control i
system AC breaker cabinets has found that the attach =ent of the cabinet to the i,
floor is inadequate to withstand the SSE acceleration levels.
1 Analysis l
The. Control Rod Drives are trippad by Loss of Power to the Drive Stators.
Pcwer is interrupted by disengaging either the AC or DC CRD breakers.
Should the I
f f.
breaker function be disabled in some =anner, the Control Rods would have to be driven into the core to shut the reactor down.
t O
j In the event of an SSE, the AC Breaker Cabinets could, as per the analysis, i
break loose fco= the floor =ounting. With the cabinets unattached, the rando:
i motion of dancing, bouncing, and even falling over could cause accelerations of the breakers that have not been analyzed or damage to the breakers, wiring, or I
connections which could conpro=ise the ability of the breakers to trip the f
control rods. Analyses cannot show that the failure will always be fail safe.
i l
Therefore, the deficiency in the design of the structural attach =ent of the AC l
Breakers Cabinets to the floor could adversely affect safety.
This i. roble: is t
thus considered to be a Significant Deficiency as par 10 CFR 50.55 (e).
i Corrective Acticn l
'Ihe attach =ent of the AC Breaker Cabinet to the. floor has been redesigned.
De-l I
Pending upen the arrange =ent at the particular site, either additional bolts
[
will be included or a fillet veld will be added to increase the attachnent strength, l
)a ]
l' Each plant is being evaluated on an individual basis.
l' j