ML19312E886

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 800219-22
ML19312E886
Person / Time
Site: Hartsville  
Issue date: 03/11/1980
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML19312E876 List:
References
50-518-80-04, 50-518-80-4, 50-519-80-04, 50-519-80-4, 50-520-80-04, 50-521-80-04, NUDOCS 8006180083
Download: ML19312E886 (1)


Text

T

?

"'N

(/

APPENDIX A NOTICE OF VIOLATION Tennessee Valley Authority License No. CPPR-150 Hartsville Nuclear Plant Based on the NRC inspection February 19-22, 1980, certain of your activities were apparently not conducted in full compliance with NRC requirements as indi-cated below. These items have been categorized as described in correspondence to you dated December 31, 1974.

As required by Criterion V of Appendix B to 10 CFR 50, and as implemented by PSAR Section 17.1A.5, " Activities affecting quality shall be prescribed by documented instructions, procedures,...and shall be accomplished in accordance with those instructions, procedures,...".

TVA Procedure for Hartsville Nuclear Site SOP-34, R-1, " Weld Inspection Documentation",

Paragraph 6.2, requires the inspector at the time of weld joint fit-up to verify that the tack welder had stamped the work with his symbol prefixed by the letter "T" and that the joint has been stamped with the correct weld number in accordance with SOP-17, " Welder Identification of Welds".

Contrary to the above, on February 21, 1980, the following examples were noted:

1.

A welded butt joint in the Low Pressure Coolant Core Spray System, where welding was past.the root, was not marked with joint identifi-cation or welder symbol.

2.

One completed welded butt joint in the Low Pressure Core Spray System and the High Pressure Coolant Injection System did not have "T" pre-fixing the welder symbol.

3.

SOP-17 had not been issued.

This is an infraction.

8006180083

.