ML19309C495
| ML19309C495 | |
| Person / Time | |
|---|---|
| Site: | Fort Calhoun |
| Issue date: | 04/01/1980 |
| From: | Seyfrit K NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV) |
| To: | William Jones OMAHA PUBLIC POWER DISTRICT |
| References | |
| NUDOCS 8004080670 | |
| Download: ML19309C495 (1) | |
Text
-
bec to DAC:ADM:
CENTRAL FILES PDR:HQ e "%,
UNITED STATES a
LPDR
- p NUCLEAR REGULATORY COMMISSION o
2 Il 3%
H EGloN IV
~
3 _p., "
C 611 RYAN PLAZA DRIVE, SulTE 1000 N31C f
ARLINGTON, TEXAS 76012
'v e
April 1, 1980
- - - ~ ~ -
Docket No.
50-285 Omaha Public Power District ATTN:
W. C. Jones, Division Manager -
Production Operations 1623 Harney Street omaha, Nebraska 68102 Gentlemen:
The enclosed IE Circular No. 80-05 is forwarded to you for information.
No wri'.: ten response is required.
Should you have any questions related to your un.ferstanding of the recommendations on this matter, please contact this office.
Sincerely, j
r1 V. Seyfri Director
Enclosures:
1.
IE Circular No. 80-05 2.
List of IE Circulars Recently Issued cc:
S. C. Stevens, Manager Fort Calhoun Station Post Office Box 98 Fort Calhoun, Nebraska 68102 5
8 004080 b7C) 1
SSINS No.: 6830 Accession No.:
UNITED STATES 7912190691 NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT Dhc3 WASHINGTON, D.C.
20555 O
as wo
- 2. e0%
IE Circular No. 80-05 Date: April 1, 1980 Page 1 of 3 EMERGENCY DIESEL-GENERATOR LUBRICATING OIL ADDITION AND ONSITE SUPPLY Descrip; ion of Circumstances:
On January 17, 1980, the Kewaunee Nuclear Power Plant experienced a partial loss of offsite power which resulted in a turbine trip, reactor trip, and one emergency diesel engine driven generator (diesel generator or D/G) supplying power to one engineered safeguards bus.
Offsite power continued to supply the other engineered safegeards bus.
During the day before, on January 16, 1980, this D/G had succestfully completed a 24-hour loaded test run but had a low Dfae oil alarm condition with oil level 1/2-inch low.
The D/G was fully oper:61onal in this conditio9.
Before oil could be added on January 17, 1980, the D/G was required for emergency power following the failure of the reserve auxiliary transformer.
The normal oil fill location could not be used while the D/G was operating.
The D/G Technical Manual (TM) indicated that oil could be added with the engine running, but did not describe the method to be used. Lube oil was added by pumping into the engine through a pipe that was assumed to be a lube oil line; this line was color coded in the TM and painted with the lube oil system color code. Three barrels of oil were added via this line while the D/G was operating. After transferring the emergency bus to off-site power through the tertiary auxiliary transformer, the D/G was shut down. With the D/G shut down, two more barrels of oil were added through this line without increasing the sump level.
Then two more barrels of oil were added through a different addition point and the level was restored to normal.
The following day, a factory representative determined that the first five barrels of oil had been added to the engine air box through a mismarked drain connection (should have been color coded as an air line).
Four and one-half barrels of oil were drained out after which the D/G was satisfactorily test operated.
It is believed that the diesel engine could have been damaged had an engine start been attempted while the five barrels of oil were in the air box.
Further, it is noted that procedures for adding oil to the operating diesel engine were not available and that the personnel performing the addition were not fcafliar.with, nor trained on, how to add oil to a running engine or how to verify that oil had been properly added.
i i
l l-1 I
IE Circular No. 80-05 Date:
April 1, 1980
> ~
Page 2 of'3' Tids event brought to light an additional problem which may be generic.
During the previous day's test run of the D/G, lube oil consumption was approximately 3 gal /hr. During the loss of power event, the licensee had three barrels (165 gallons) of lube oil available onsite.
The licensee's Technical Specifications require a seven day supply of fuel oil for one D/G be available onsite. To meet the intent of the Technical Specifications, a seven day supply of lube oil should also be available onsite.
The diesel engines are model 999-20 manufactured by the Electro-Motive Division of General Motors Corporation. These diesel engines use a 2-stroke cycle and lube oil consumption is normally higher than for the 4-stroke cycle diesel engines. Vendor representatives and NRC consultants indicate that lube oil consumption rate varies with engine condition and load.
Further, the 3 8al/hr consumption rate is considered to be in the normal range.
Recommended Action for Licensee's Consideration:
All holders of operating licenses for nuclear power reactor facilities should be aware of the potential problems described above.
Because of the generic nature of these matters, it is recommended that the considerations identified above be resiewed at your facility in the following respects:
1.
Verify the existence and adequacy of procedures or instructions for adding lubricating oil to safety-related equipment. This should include the following:
a)
Whether or not, how and where lube oil can be added while the equipment is in operation, DJ F.:*1cular assurance that the wrong kind of oil is not inadvertently added to the lubricating oil system, and c)
That the expected rise in level occurs for each unit of lube oil added.
These operating procedures or instructions should be available locally in the area of the affected equipment.
2.
Verify that personnel are trained-in such approved procedures and demonstrate an ability for using these procedures to add oil while j
the D/G is operating and that they understand how to verify that the proper amount of oil has been added.
j 3.
Verify that the color coded, or otherwise marked, lines associated with i
the D/G are correct and that the line or point for adding lube oil has been clearly identified.
i 1
IE Circular No. 80-05 Date: April 1, 1980
. i. '.
' - Page 3 of 3
~ "
4.
Verify that appropriate procedures or instructions exist, and personnel are trained, on the proper addition of tube oil and the performance of maintenance during operation of other similar vital equipment.
5.
Determine the lube oil usage rate for each diesel engine under full load conditions including the rates considered to be excessive.
Provide adequate inventory of lubricating oil of the proper grade consistent with the highest usage emergency D/G's operating for the time period specified in the plant Technical Specifications for fuel oil supply.
When lube oil consumption rates become excessive, provisions should be included for overhaul of the diesel engine.
All holders of construction permits for nuclear power reactor facilities should be aware of the potential problems identified above and initiate appropriate procedures prior to initial fuel loading.
No written response to this Circular is required.
If you require additional information regarding these matters, contact the Director of the appropriate NRC Regional Office.
I e
IE Circular No. 80-05 April 1, 1980 RECENTLY ISSUED IE CIRCULARS Circular Subject Date Issued To No.
Issued 79-24 Proper Installation and 11/26/79 All Holders of a Calibration of Core Spray Power Reactor Operating Pipe Break Detection License (OL) or Equipment on BWRs.
Construction Permits (cps) 79-25 Shock Arrestor Strut 12/20/79 All licensees and Assembly Interference holders of power reactor construction Permit (CP) 80-01 Service Advice for GE 1/17/80 All licensees of nuclear Induction Disc Relays power reactor operating facilities and holders of nuclear power reactor Construction Permits (cps) 80-02 Nuclear Power Plant Staff 2/1/80 All holders of Reactor Work Hours Operating Licenses (OLs),
including research and test reactors, and Construction Permits (cps) 80-03 Protection from Toxic Gas 3/6/80 All holders of a power Hazards reactor Operating License (OL) 80-04 Securing of Threaded 3/14/80 All holders of a power Locking Devices on Safety-reactor Operating License Related Equipment (OL) or Construction Permit (CP)
Enclosure
.