05000302/LER-1978-009-04, /04X-0:on 780223-24,biomass of Fish & Shellfish Impinged on Intake Screens Exceeding 50 kg/24-h Reporting Level of Ets.Caused by Two Coal Barges Exiting & Coal Barge Entering Intake Canal During Sampling

From kanterella
(Redirected from ML19308D949)
Jump to navigation Jump to search
/04X-0:on 780223-24,biomass of Fish & Shellfish Impinged on Intake Screens Exceeding 50 kg/24-h Reporting Level of Ets.Caused by Two Coal Barges Exiting & Coal Barge Entering Intake Canal During Sampling
ML19308D949
Person / Time
Site: Crystal River 
Issue date: 03/16/1978
From:
FLORIDA POWER CORP.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML19308D947 List:
References
LER-78-009-04X, LER-78-9-4X, NUDOCS 8003200696
Download: ML19308D949 (1)


LER-1978-009, /04X-0:on 780223-24,biomass of Fish & Shellfish Impinged on Intake Screens Exceeding 50 kg/24-h Reporting Level of Ets.Caused by Two Coal Barges Exiting & Coal Barge Entering Intake Canal During Sampling
Event date:
Report date:
3021978009R04 - NRC Website

text

-.

m k)

~

ENVIRONMENTAL LICENSEE EVENT REPORT (# 78-009/04X-0) 1.

Facility: Crystal River Unit #3 2.

Report Date:

16 March 1978 3.

Occurrence Date:

February 23-24,1978 (determined at planc 15 March '1978) 4.

Identification of Occurrence:

Biomass of fish and shellfish impinged on the intake screens

~

of Units 1, 2 and 3 exceeded the 50 kg/24 hr. reporting level of Section 3.1.3 of the Environmental Technical Specifications.

5.

Conditions prior to Occurrence:

Unit #1 - All water ci.rculation pumps operational.

Unit #2 - All water circulation pumps operational.

Unit #3 - All water circulation pumps operational.

6.

Description of Occurrence:

During the period 0900 February 23,1978 to 0900 February 24, 1978.

185.96 kg of fish and shellfish were impinged on the intake screens -

of Crystal River Units 1, 2 and 3.

Of the 185.96 kg impinged, Unit 3 accounted for.123.49 kg (66% of total).

Four finfish species accounted for 142.13 kg (76% of total); pinfish 28%, Atlantic sting-ray '27%, bay anchovy 12%, silver perch 9%.

Two commercially utilized shellfish species, the pink ' shrimp and blue crab accounted for 11.08 kg (6% of total).

The remaining biomass impinged was distributed among several species of fish and shellfish.

7.

Designation of Aoparent Cause of Occurrence:

The following unusual or periodic events were noted prior to or during the occurrence:

Two coal barges exited the intake canal during sampling.

One additional coal barge entered the intake canal during sampling.

These events may have been partially responsible for the impingement observed.