ML19291B987

From kanterella
Jump to navigation Jump to search
Forwards IE Bulletin 79-27, Loss of Non-Class IE Instrumentation & Control Power Sys Bus During Operation. No Written Response Required
ML19291B987
Person / Time
Site: Byron, Braidwood, LaSalle  Constellation icon.png
Issue date: 11/30/1979
From: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Reed C
COMMONWEALTH EDISON CO.
References
NUDOCS 7912190207
Download: ML19291B987 (1)


Text

b

/'e..,#'o, UNITED STATES E \\*

j NUCLEAR REGULATORY COMMISSION

,y s

REGION lit

.h' -

[

799 ROOSEVELT ROAD o,,

0

%..b' 0

GLEN ELLYN, ILLINOIS 60137 50-373, 50-374, 50-454, OV 3 " 1979 N

Docket Nos.

50-455, 50-456 and 50-457 Commonwealth Edison Company ATTN:

Mr. Cordell Reed Manager of Nuclear Operations Post Office Box 767 Chicago, IL 60690 Gentlemen:

The enclosed IE Bulletin No. 79-27, is forwarded to you for information.

Although no written response is required at this time, these concerns will be addressed as part of the licensing process for your plant.

If you desire additional information regarding this matter, please contact this office.

Sincerely, A

l

$ James G. Keppler Director

Enclosure:

IE Bulletin No. 79-27 cc w/ enc 1:

Mr. D. L. Peoples, Director Central Files of Nuclear Licensing Direc*or, NRR/DPM Mr. L. J. Burke, Site Director, NRR/ DOR Project Superintendent PDR Mr. T. E. Quaka, Quality Local PDR Assurance Supervisor NSIC Mr. R. H. Holyoak, Station TIC Superintendent Mr. Dean Hansell, Office of Mr. Gunner Sorensen, Site Assistant Attorney General Project Superintendent Mr. R. Cosaro, Project Superintendent T

7912190 20f

UNITED STATES SSINS No.:

6820 NUCLEAR REGULATORY COMMISSION Accession No.-

0FFICE OF INSPECTION AND EhTORCEMENT 7910250499 WASHINGTON, D.C.

20555 November 30, 1979 IE Bulletin No. 79-27 LOSS OF NON-CLASS-1-E INSTRUMENTATION AND CONTROL POWER SYSTEM BUS DURING OPERATION Description of Circumstances:

On November 10, 1979, an event occurred at tre Oconee Power Station, Unit 3, that resulted in loss of power to a non-class-1-E 120 Vac single phase power panel that supplied power to the Integrated Control System (ICS) and the Non-Nuclear Instrumentation (NNI) System. This loss of power resulted in control system malfunctions and significant loss of information to the control room operator.

Specifically, at 3:16 p.m., with Unit 3 at 100 percent power, the main condensate pumps tripped, apparently as a' result of a technician performing maintenance on the hotwell level control system. This led to reduced feedwater flow to the steam generators, which resulted in a reactor trip due to high coolant system pressure and simultaneous turbine trip at 3:16:57 p.m.

At 3:17:15 p.m., the non-class-1-E inverter power supply feeding all power to the integrated control system (which provides proper coordination of the reactor, steam generator feedwater control, and turbine) and to one NNI channel tripped and failed to automatically transfer its loads from the DC power source to the regulatei AC power source. The inverter tripped due to blown fuses.

Loss of power to the NNI rendered control room indicators and recorders for i he reactor coolant system (except for one wide-range RCS pressure recorder) and m6st of the secondasy plant systems taoperable, causing loss of indication for systems used for decay heat removal and water addition to the reactor vessel and steam generators. Upon loss of power, all valves controlled by the ICS assumec their respective failtre positions. The loss of power existed for approximately three minutes, urtil an operator could reach the equipment room and manually switch the inverter to the regulated AC source.

The above event was discussed in IE Information Notice No. 79-29, issued November 16, 1979.

NUREG 0600 " Investigation into the March 28, 1979 TMI Accident" also dis:usses TMI LER 78-021-03L whereby the RCS depressurized and Safety In,jection or cur'ed on loss of a vital bus due to inverter failure.

~1790 309 Actions to Be Taken by Licensees For all power reactor facilities with completion of construction (North Anna Sequoyah, and Zimmer):

DUPLICATE DOCUMENT Entire document previously entered into system under:

ANO No. of pages: