ML19291B983

From kanterella
Jump to navigation Jump to search
Forwards IE Bulletin 79-27, Loss of Non-Class IE Instrumentation & Control Power Sys Bus During Operation. Written Response Required
ML19291B983
Person / Time
Site: Fort Calhoun 
Issue date: 11/30/1979
From: Seyfrit K
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To: William Jones
OMAHA PUBLIC POWER DISTRICT
References
NUDOCS 7912190188
Download: ML19291B983 (1)


Text

CENTRAL FILES PDP.:HQ UNITED STATES LPDR

/ pato,%

NUCLEAR REGULATORY COMMISSION TIC v

3%

T,;

nEGloN IV y(

$ ! [

o 611 RYAN PLAZA DRIVE.SulTE 1000 g.,'

,j ARUNGTON, TEXAS 76012 ot E

%* + w '

z November 30, 1979 Docket No.

50-285 Omaha Public Power District ATTN:

W.. C. Jones, Division Manager -

Production Operations 1623 Harney Street Omaha, Nebraska 68102 Centlemen:

The enclosed IE Bulletin No. 79-27, is forwarded for action. A written response is required.

If you desire additional information regarding this matter, please contact this office.

Sincerely,

/

1 O wjwnt. J.ve.n Karl V. Seyfrit

~

Director

Enclosures:

1.

IE Bulletin No. 79-27 2.

List of Recently Issued IE Bulletins cc:

S. C. Stevens, Manager Fort Calhoun Station Post Office Box 98 Fort Calhoun, Nebraska 68102 g st 1790 $M 7912190/gf

UNITED STATES SSINS No.: 6820 NUCLEAR REGULATORY COMMISSION Accession No.:

OFFICE OF INSPECTION AND ENFORCEMENT 7910250499 WASHINGTON, D.C.

20555 IE Bulletin No. 79-27 Date: November 30, 1979 Page 1 of 3 LOSS OF NON-CLASS 1-E INSTRUMENTATION AND CONTROL POWER SYSTEM BUS DURING OPERATION Description of Circumstances:

On November 10, 1979, an event occurred at the Oconce Power Station, Unit 3, that resulted in loss of power to a non-class 1-E 120 Vac single phase power panel that supplied power to the Integrated Control System (ICS) and the Non-Nuclear Instrumentation (NNI) System.

This loss of power resulted in control system malfunctions and significant loss of information to the control room operator.

Specifically, at 3:16 p.m., with Unit 3 at 100 percent power, the main condensate pumps tripped, apparently as a result of a technician performing maintenance on the hotwell level control system. This led to reduced feedwater flow to the steam generators, which resulted in a reactor trip due to high coolant system pressure and simultaneous turbine trip at 3:16:57 p.m.

At 3:17:15 p.m., the non-class 1-E inverter power supply feeding all power to the integrated control system (which provides proper coordination of the reactor, steam generator feedwater control, and turbine) and to one NNI channel tripped and failed to automatically transfer its loads from the DC power source to the regulated AC power source. The inverter tripped due to blown fuses.

Loss of power to the NNI rendered control room indicators and recorders for the reactor coolant system

,(except for one wide-range RCS pressure recorder) and most of the secondary plant systems inoperable, causing loss of indication for systems used for decay heat removal and water addition to the reactor vessel and steam generators. Upon losn of power, all valves controlled by the ICS assumed their respective failure positions. The loss of power existed for approximately three minutes, until an operator could reach the equipment room and manually switch the inverter to the regulated AC source.

The above event was discussed in IE Information Notice No. 79-29, issued November 16, 1979.

NUREG 0600 "Investigatinn into the March 28, 1979 TMI Accident" also discusses TMI LER 78-021-03L whereby the RCS depressurized and Safety Injection occurred on loss of a vital bus due to inverter failure.

Actions to Be Taken by Licensees For all power reactor facilities w completion of constru.ction (North Entire document previously Sequoyah, and Zimmer):

entered into system der:

'Y ANO I

~'

"1790 317-N o.

of pages: