05000324/LER-1979-033-03, /03L-0 on 790518:HPCI Turbine Tripped on Mechanical Overspeed at 3,500 Rpm.Caused by Spring Adjusting Screw Being Approx Five Turns Out of Position.Set Screw for Securing Spring Adjusting Screw Was Approx Six Turns Out

From kanterella
(Redirected from ML19273B921)
Jump to navigation Jump to search
/03L-0 on 790518:HPCI Turbine Tripped on Mechanical Overspeed at 3,500 Rpm.Caused by Spring Adjusting Screw Being Approx Five Turns Out of Position.Set Screw for Securing Spring Adjusting Screw Was Approx Six Turns Out
ML19273B921
Person / Time
Site: Brunswick Duke Energy icon.png
Issue date: 06/13/1979
From: Tollison A
CAROLINA POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML19273B920 List:
References
LER-79-033-03L-01, LER-79-33-3L-1, NUDOCS 7906180514
Download: ML19273B921 (2)


LER-1979-033, /03L-0 on 790518:HPCI Turbine Tripped on Mechanical Overspeed at 3,500 Rpm.Caused by Spring Adjusting Screw Being Approx Five Turns Out of Position.Set Screw for Securing Spring Adjusting Screw Was Approx Six Turns Out
Event date:
Report date:
3241979033R03 - NRC Website

text

NRC FORM 366 U. S. NUCLEAR REGULATORY COMMISSION (7 77)

LICENSEE EVENT REPORT CON TROL DLOCK:

l l

l l

l lPLEASE I 11NT OR TYPE ALL HEOUIRED INFORMATION) 1 1l 1 lg l

0 l0 lg 4 gl 0 l0 l-l 0 l0 l0 0

0 f0 lN lC lB lE lP 2

1 8 9 LiC[NSEL CUhi 14 IS LICENSL f.UMt E H 25

/t)

LICE NSL T)PE JO Si LAT$8 4

CON'T

$$I I lhl 0 l 5 l 0 l - l 0 l 3 l 2 l 4 gl 0 l 5 l 1 l 8 l 7 [ 9 }@l 0l 6 l 1 3l 7 9

i0 1

U 60 61 LOCK E T NUYBEH M

63 EvlNT DATE 14 D

HtPOH T DAT E 80 EVENT DESCHiPTION AND PHOBABLE CONSEQUENCLS h lWhile testing HPCI to determine its operability on 2-19-79, prior to cancellation of o

2 l an LCO for a routine calibration, the HPCI turbine tripped on mechanical overspeed at l jo 3

jo 4

l3500 RPM.

The required overspeed trip setting is 5000 RPM.+2%.

This turbine trip was l fo S

inot reported under an additional LCO or other notification method.

l 6

l l

Lo 7

l Technical Srecifications 3.5.1, 6.9.1.9b, c l

[o l0 s l l

q 9 80 Si iI(

C /,a UE C#

s ' G t.a p g3tgL UE COLT UfMObi L OYPG'.L *.T CO Dt ABCODE SUECLE s

'a o

i Si Fl@ lX l@ l Zl@ l Tl U Ri Bl Il Nl@ l Z lQ ]Q 8

'J 13 11 1J 13 1ri l'e N

  • E OLT N il A.

th L;;H Hf NC[

hlfLHT H E ViSloN pf, L Vt N T v t all H E PvH T N O.

LODE TYPL NO

@ g(, y;g; I 71 91 l-10 13 13 I VI I o f 31 ILI l-l I 01

_._ J l

,J ll

/b JH 29 JO Jt JJ AC T ION F U Tt ie:E iftffT

.a H > t i t i

]

ATT A :r4ME N T

  • HD4 FHIVE Cr NP.

J.OY PO*. E N T T A r. L

  • A T I ON

(.,'4 r L A '. T t t lunt)

W;JHS..

SUBYt T T L D F OHf.i suu SUPPi l t h CANUFACTURFH lX Q Gl@

lZl@

lZlh l0l0l0l0 lY g l Yj g l Nl g lT l1l4l7lg JJ 34 30 J/

4a 41 al 43 44 47 ACflONSh CAUSE DE', CHIP TION A";D CORRECTivt Ii o l The spring adjusting screw was found approximately 5 turns out of position.

The set l

fi i

Iscrew used to lock the spring adjusting screu in place was found approximately 6 turnst laway from eni, aging the spring adjusting screw. With the assistance of a Terry Turbine l i

li 3

l representative, the spring adjusting screw and its set :; crew were placed in their j

[t 4

correct position, the mechanical setpoint trip was set per Section 10 of the (cont.) J 8 9 80 STAIUs PUAE4 o f H f H S T A T US '

  • *L TH OO ('er FACILtYY DMOL E HV Di' Job lHY DLLCsuP rioN l

W @ l0l6l5l@

NA l

l D l@l NRC PAB Team l

,i

'a 4

)

e9 e'

11 44 43 4r; g0 AC TIVI T Y i '" il N I H E l f A'.F D UF RE L E ast Aucp f *:T OF AC T ivi T Y J '

L et A i toa. cr HE L E A;E Lz_J @ lzl@ L N^

l I

N^

l i

c.

14 4

1J lt 41 45 80 ff H5 Ni L [ u VU'.i tif '

'It a TYrF n['St u m T! c a ; D 2e 354 004 I

i I Oi 0 OJ@lZi@i N^

8 9 11 11 1.1 80 F[PiONN{t i. i,H ' L 5 Ni vos H D L % H iP i + 0'.

l0 0 l0 l@l NA l

i a

IJ 5) 11 12 80 L O',% 06 C H D A.' A cil T( > F M r t I i v T N P{

Ist S L H le' t ION I

9 Nb H

'J 10 go L ooN O y.gg 9061 ao S/K 7

"c o e q to fa rM P0 ;

a 9

9 LER CONTINUATION -- RO # 2-79-33 Facility:

BSEP l'.it #2 Event Date 5-18_7,9 technical manual and the turbine mechanical overspeed trip was tested several times.

The Terry Turbine representative stated that if the set screw is correctly installed, it will lock with the threads of the spring adjusting screw and will not be able to back out.

The turbine has been run several times since with no problems.

The setscrew and the spring adjusting screw on both units were checked during the past refueling outages with no discrepancies found.

This is considered an isolated incident and no further action is required.

Through an administrative deficiency, this event was not detected until May 18, 1979.

The HPCI system was under an LCO for a non-reportable reason. When additional problems developed that were reportable, they were maintained under the same LC0; therefore, the reportable problen was not reviewed by management. An administrative procedure is being written to ensure that all such occurrences are identified, reported, and properly reviewed.

2354 005