Forwards LER 79-033/03L-0
Date released: 10/14/2019 Download: ML19273B920


LER 79-033/03L-0 on 790518:HPCI Turbine Tripped on Mechanical Overspeed at 3,500 Rpm.Caused by Spring Adjusting Screw Being Approx Five Turns Out of Position.Set Screw for Securing Spring Adjusting Screw Was Approx Six Turns Out
ML19273B921
Person / Time
Site: Brunswick 
Issue date: 06/13/1979
From: Tollison A
CAROLINA POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19273B921 (2)
Forwards LER 79-033/03L-0
ML19273B919
Person / Time
Site: Brunswick 
Issue date: 06/13/1979
From: Banks H
CAROLINA POWER & LIGHT CO.
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19273B919 (1)