Forwards IE Info Notice 79-29, Loss of Nonsafety-Related Reactor Coolant Sys Instrumentation During Operation. No Specific Action or Response Required
ML19262B047
Person / Time
Site: Ginna 
Issue date: 11/19/1979
From: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: White L
ROCHESTER GAS & ELECTRIC CORP.
References
NUDOCS 7912110473
Download: ML19262B047 (1)


Text

%

to gjv..c%g, UNITED STATES

{ i ) y, g

NUCLEAR REGULATORY COMMISSION REGION I 3 ?'

j 0, '.

631 PAR % AVENUE

%, ' b#

,o' KING OF PRUSN, PENNSYLVANIA 19406

+....

Docket No. 50-244 D I 91977 Rochester Gas and Electric Corporation ATTN:

Mr. Leon D. White, Jr.

Vice President Electric and Steam Production 89 East Avenue Rochester, New York 14649 Gentlemen:

This Information Notice is provided as an early notification of a possibly significant matter.

It is expected that recipients will distribute this Notice to their operating personnel and will review the information for pos-sible applicability to their facilities.

No specific action or response is requested at this tune.

However, we anticipate that further NRC evaluations will result in issuance of an IE Circular, Bulletin, or NRR Generic Letter in the near future which will recomuend or request specific applicant or licensee actions.

If you have questions regarding the matter, please contact this office.

Sincerely,

/ s/ceVJ'.

ca ~

Boyce H. Grier Director

Enclosures:

1.

IE Information M1tice No. 79-29 2.

List of Recently Issued Information Notices CONTACT:

W. H. Baunack (215-337-5253) cc w/encls:

B. A. Snow, Plant Superintendent S. Bullock, QC Engineer Harry Voigt, Esquire 1530 283 1912t j g YS$

ENCLOSURE 1 SSINS No.: 6300 Accession No.:

79102504W 667 UNITED STATES NUCLEAR REGULATORY COMMISSION 0FFICE OF INSPECTION AND ENFORCEMENT

,1 D

q [ c, WASHINGTON, D. C.

20555 Jo 2J IE Information Notice No. 79-29 Date:

November 19, 1979 Page 1 of 2 LOSS OF NONSAFETY-RELATED REACTOR COOLANT SYSTEM INSTRUMENTATION DURING OPERATION This notice contains information regarding a loss of reactor coolant system instrumentation as a consequence of a failure of a static transfer switch to transfer to an alternate supply.

At 3:15 p.m. on November 10 with Unit 3 of the Oconee Station at 100 percent power, the main condensate pumps tripped, apparently as a result of a techni-cian performing maintenance bn the botwell level control system.

This led to reduced feedwater flow to the steam generators, which resulted in a high reactor coolant system (RCS) pressure reactor trip and simultaneous turbine trip at 3:16:57 p.m.

At 3:17:15 p.m., the inverter power supply, nonsafety-related, feeding all power to the integrated control system (ICS) tripped and failed to automatically transfer its loads from the DC power source to the regulated AC power source.

The inverter had tripped due to blown fuses, resulting in loss of RCS indicators and recorders in the control room, except one wide range RCS pressure recorder.

This condition existed for approximately three minutes, until an operator could reach the equipment room and switch the inverter manually to the regu-lated AC source.

As a result of the power failure to the ICS, all valves controlled by the system assumed their respective fail positions.

This resulted in a cool down of the RCS to 1635 psi and 530 degrees F.

The opera-tor, expecting this condition, started all makeup pumps and opened the asso-ciated high pressure injection valves to the RCS which limited the rate of RCS pressure reduction and associated reduction in pressurizer level.

At 3:20:42 p.m., power was restored to the ICS and RCS conditions were restored.

Although RCS cooldown limits were exceeded, the pressurizer and steam genera-tors did not go dry, and at least 79 degrees F subcooling was maintained during this event.

No engineered safety features actuation setpoints were reached, and, except for the components discussed above, no component malfunc-tions occurred.

The licensee has installed a redundant electromechanical transf9r switch between the loads and the regulated supply.

This switch will actuate and power the loads from the regulated supply should the original static switch fail to transfer.

Longer term resolution of the need or desirability to separate these instru-ments onto diverse electrical supplies or to provide redundant instrumentation display channels for operatur use from essential power supplies are also under 1530 284 IE Information Notice No. 79-29 Date:

November 19, 1979 Page 2 of 2 consideration.

It is anticipated that further NRC evaluations will result in issuance of an IE Circular, Bulletin, or NRR Generic letter in the near future which will recommend or request specific applicant or licensee actions.

This Information Notice is provided to inform licensees of a possibly signifi-cant matter.

It is expected that recipients will disseminate the information to all operational personnel working at their licensed facilities.

If you have questions regarding this matter, please contact the Director of the appropriate NRC Regional Office.

No written response to this Information Notice is required.

1530 2%

ENCLOSURE 2 IE Infcrmation Notice No. 79-29 Date:

lovember 19, 1979 Page 1 of 1 REC 5NTLY ISSUED IE INFORMATI0F NOTICES Informatie n Subject Date Issued to Notice No.

Issued 79-20 Same Title as 79-20 9/7/79 Same as 79-20 (Revision No. 1) 79-21 Transportation and Com-9/7/79 All Power and Research mercial Burial of Radio-Reactors with OLs active Material 79-22 Qualification of Control 9/14/79 All Power Reactor Faci-Systems lities with an OL or CP 79-23 Emergency Diesel Generator 9/26/79 All Power Reactor Faci-Lube Oil Coolers lities with an OL or CP 79-24 Overpressurization of Con-10/1/79 All Power Reactor Faci-tainment of a PWR Plant lities with an OL or CP After a Main Steam Line Break 79-25 Reactor Trips at Turkey 10/1/79 All Power Reactor Faci-Point Unit 3 and 4 lities with an OL or CP 79-26 Breach of Containment 11/5/79 All Power Reactor Facil-Integrity ities with an OL or CP 79-12A Attempted Damage to New 11/9/79 All Fuel Facilities, Fuel Assemblies Research Reactors and Power Reactors with an OL or CP 79-27 Steam Generator Tube 11/16/79 All Power Reactor Faci-Ruptures at Two PWR lities with an OL or CP Facilities 79-28 Overloading of Structural 11/16/79 All Power Reactor Faci-Elements Due to Pipe Support lities with an OL or CP Loads 1530 286