ML19257D505

From kanterella
Jump to navigation Jump to search
Mod to Change Request 33 for Tech Specs 15.3 Re Radiological Effluent Releases
ML19257D505
Person / Time
Site: Point Beach  NextEra Energy icon.png
Issue date: 01/28/1980
From:
WISCONSIN ELECTRIC POWER CO.
To:
Shared Package
ML19257D501 List:
References
RTR-NUREG-0472, RTR-NUREG-472 NUDOCS 8002040497
Download: ML19257D505 (32)


Text

s s

2)

Logic Channel A logic channel is a group of relay contact matrices which operate in response to the analog channels signals to generate a protective action signal.

f.

Ins trumentation surveillance 1)

Channel Check Channel check is a qualitativo determination of acceptable operability by observation of channel behavior during operation.

Where other channels are provided, this determination shall include comparison of the channel indication with indications from other independent instrumentation channels measuring the same parameter.

2)

Channel Functional Test A channel functional test consists of injecting a simulated signal irto the channel to verify that it is operable, including alarm and/or trip initiating action.

3) 01annel Calibration Channel calibration consists of the adjustment of channel output such that it responds, with acceptable range and accuracy, to known values of the parameter which the channel measures.

Calibration shall encompass the entire channel, including equipront action, alarm, or trip, and shall be deemed to include the channel functional test.

1866 020 g.

Shutdown 1) flot Shutdown I

The reactor is in the hot shutdown condition when the reactor is 1

i subcritical, by an amount greater than or equal to the margin as specified in Technical Specifications 15.3.10 and T is at or greater avg than 540 P.

15.3.9 Radioactive Effluent Releases Applicability Applies to the controlled releases of radioactive gases or liquids from the plant on a total plant or site basis.

Obiective To define the limits and conditions for the controlled release of radioactive materials in liquid and gaseous effluents to the environs to ensure that these releases are as low as is reasonably achievable in conformance with 10 CFR Parts 50.34a and 50.36a, to ensure that these releases result in concentrations of radioactive materials in liquid and gaseous effluents released to unrestricted areas that are within the limits specified in 10 CFR Part 20, and to ensure that the releases of radioactive material above background to unrestricted areas are as low as is reasonably achievable, the following design objectives as defined in Appendix I to 10 CFR Part 50 apply:

A.

The annual total quantity of all radioactive material above background that may be released from each light-water-cooled nuclear power reactor to unrestricted areas should not result in an annual dose or dose commitment from liquid effluents for any individual in an unrestricted area from all pathways of exposure in excess of 3 millirems to the total body or 10 millirems to any organ.

B.

The annual total quantity of all radioactive material above background that may be released from each light-water-cooled nuclear power reactor to the atmosphere should not result in an annual air dose from qaseous ef fluents at any location near ground level which could be occupied by individuals in unrestricted areas in excess of 10 millirads for gamma radiation or 20 uillirads for beta radiation, or that this quantity should not result in an annual external dose from gasecus effluen ts to any individual 11366 '021 15.3.9-1

in unrestricted areas in excess of 5 millirems to the total body or 15 millirems to the skin.

C.

The annual total quantity of all radioactive iodine and radioactive material in particulate form above background that may be released from each light-water-coo'ed nuclear power reactor in effluents to the atn osphere should not result in an annual dose or dose commitment from such radioactive iodine and radioactive material in particulate form for any individual in an unrestricted area from all pathways of exposure in excess of 15 millirems to any organ.

SPECIPICATIONS A.

Radioactive Licuid Effluent Monitorino Instrumentation The radioactive liquid effluent monitoring instrumentation channels listed in Table 15.3.9-1 shall be operable with their alarm or trip setpoints set to ensure that the limits of Specification 15.3.9.C are not exceeded.

In the event that a radioactive effluent monitoring instrumentation channel alarm or trip setpoint is less conservative than required by this Specification, the release of radioactive liquid effluents monitored by the affected channel shall be immediately suspended or the channel shall be declared inoperable.

If a radioactive liquid effluent monitoring instrumentation channel is inoperable, the action statement listed in Table 15.3.9-1 opposite the channel shall be taken.

B.

Radioactive Gaseous Effluent Monitoring Instrumentation The radioactive gaseous ef fluent monitoring instrumentation channels listed in Table 15.3.9-1 shall be operable with their alarm or trip setpoint set to ensure that the limits of Specification 15.3.9.D are not exceeded.

In the event that a radioactive gaseous effluent monitoring instrumentation channel alarm or trip setpoint is less conservative than required by this Specification, the release of radioactive gaseous effluents monitore<1 by the affected channel shall be immediately suspended or the channel shall 15,3.9-2

be declared inoperable.

If radioactive gaseous effluent monitoring instrumentation channels are inoperable, the action statement listed in Table 15.3.9-1 opposite that channel shall be taken.

C.

Liquid Waste Release Rates 1.

The release rate of radioactive liquid effluents shall be such that the annual average concentration of radionuclides in the circulating water discharge does not exceed the limits specified in 10 CFR 20, Appendix B, for unrestricted areas.

2 Prior to release of liquid waste tank contents, a sample shall be taken and analyzed.

3.

During release of liquid radioactivity wastes, at least one condenser circulating water purp shall be in operation and the service water return header shall be lined up only to the unit whose circulating water pump is operating.

4.

The maximum release rate for any ei ght hour period shall not exceed ten tires the yearly average limit.

D.

Gaseous Waste Release Rates 1.

The annual average release rates of gaseous and airborne particulate wastes shall be limited as follows:

-6 1.5 x 10 sec pi

< 1.0 m#

(!4PC)i is the annual release rate (Ci/sec) of any radioisotope, Where Qi i, and (tiPC)i in units of pCi/cc are defined in Column 1, Table II of Appendix B to 10 CFR 20.

For purposes of calculating permissible releases by the above formula (MPC)1 for isotopes of iodine and 15.3.9-3

particulates with half-lives longer than 8 days shall be reduced by a factor of 700 from the listed value in 10CFR20, Appendix B, December 22, 1965, edition.

2 The maximum release rate for any 60 minute period shall not exceed ten times the yearly average limit.

3.

Gascous wastes shall have as a minimum 7 days of decay time, except for low radioactivity gaseous wastes resulting from purge and fill operations associated with refueling and reactor startup or main-tenance and surveillance activities on the gas stripper system.

Prior to release of gaseous wastes, the contents of the gas decay tank shall be sampled and analyzed to determine compliance with 1 and 2 above.

4.

During release of gaseous wastes to the plant vent, at least one auxiliary building exhaust fan shall be in operation.

E.

Radioactive Liquid Effluent Releases 1.

Definitions:

Ceij = Ci x DFi DFj Ceij = number of curies of isotope i expressed in terms of an equivalent number of curies of isotope j.

Ci

= actual number of curies of isotope i.

DFi = dose factor for isotope i as given in Regulatory Guide 1.109, Revision 1, October 1977 DFj = dose factor for reference isotope j as given in Regulatory Guide 1.109, Revision.1, October 1977.

The design objective annual releases in liquid effluents shall be as follows:

1866'024 2.

Tritium: Ci { 2.15E+03 curies 15.3.9-4

~

3.

Radiciodines: I Ceij = 2.82E+01 equivalent curies where (1) the reference isotope, j, is I-131; (2) DFi is the thyroid dose factor for isotope i given in Table E-13 of Regulatory Guide 1.109, Revision 1, October 1977; thyroid dose factors for isotopes not given in Table E-13 are obtained from Table E-ll.

(3) DFj is the thyroid dose factor for the reference isotope, I-131, as given in Table E-13 of Regulatory Guide 1.109, Revision 1, October 1977.

4.

Others (isotopes other than tritium, nob'e gases, or radiciodines):

E Ceij = 3.49E+01 equivalent curies where (1) the reference isotope, j, is Co-60; (2) DFi is the highest dose factor for isotope i in any column of Table E-12 of Regulatory Guide 1.109, Revision 1, October 1977; dose factors for isotopes not given in Table E-12 are obtained from Table E-ll.

Dose i

factors for isotopes not given in either Table E-13 or Table E-ll are obtained from 'he dose factor for any isotope of the same element, modified by the ratio of their respective maximum permissible concentrations (MPCs) as giver in 10 CFR Part 20.

(3) DFj is the highest dose factor for the reference isotope, Co-60, given in any column of Table E-l? of Regulatory Guide 1.109, Revision 1, October 1977 5.

Noble gases released in liquid effluents are to be included with noble 1

l qases released in gaseous effluents.

1866 025 F.

Annual Radioactive Gaseous Effluent Releases 1.

Definitions of terms are as listed in Specification 15.3.9.C.

above.

15.3.9-5

The design objective annual releases in gaseous efiluents shall be as follows:

2.

Tritium: Ci 5 2.90E+04 curies E Ceij $ 9.21E405 equivalent curies 3.

Noble Gases:

where (1) the reference isotope, j, is Xe-133; (2) DFi is the dose factor for isotope i given as DFBi in Table B-1 of Regulatory Guide 1.109, Revision 1, October 1977; and (3) DFj is the dose factor for the re ference isotope, Xe-133, given under DFBi in Table B-1 of Regulatory Guide 1.109, Revision 1, October 1977 4.

Radiciodines: E Ceij < 3.72E-01 equivalent curies where (1) the reference isotope, j, is I-131; (2) DFi is the thyroid dose factor for isotope i given in Table E-14 of Regulatory Guide 1.109, Revision 1, October 1977; thyroid dose factors for isotopes not given in Table A-6 are obtained from Table E-ll.

(3) DFj is the thyroid dose factor for the reference isotope, I-131, as given in Table E-14 of Regulatory Guide 1.109, Revision 1, October 1977.

5.

Particulates (isotopes other than tritium, noble gases, or radioiodines):

4 E Ceij 1.80E400 equivalent curies

=

where (1) the reference isotope, j, is Co-60; (2) DFj is the highest dose factor for isotope i in any column of Table E-13 of Regulatory Guide 1.109, Revision 1, October 1977; dose factors for isotopes not given in Tabl^ E-13 are obtained from Table E-ll.

Dose factors for isotopes not given in either Table E-13 or Table E-ll are obtained from the dose fa,ctor for 1866 026 15.3.9-6

any isotope of the same element, modified by the ratio of their respective maximum permissible concentrations (MPCs) as given in 10 CPR Part 20.

(3) DFj is the highest dose factor for the reference isotope, Co-60, given in any column of Table E-13 of Regulctory Guide 1.109, Revision 1, October 1977.

G.

Tritium The design objective release for tritium in liquid effluents may be increased, provided it is accompanied by a proportional decrease in the design objective release for tritium in gaseous effluents.

Similarly, the design objective release for tritium in gaseous effluents may be increased, provide it is accompanied by a proportional decrease in the design objective release for tritium in liquid effluents.

H.

Quarterly Summary A summary of effluent release shall be made on a quarterly basis to demonstrate compliance with this section.

In the event that actual quantities of radio-active materials released in liquid and gaseous effluents exceed twice the quantities corresponding to the annual dose design objectives of Appendix I to 10 CFR Part 50, a special report will ta prepared and submitted to the U. S. Nuclear Regulatory Commission.

I.

Radioactive Effluent Waste Treatment The liquid radwaste treatment system shall be operable. The appropriate portions of the system shall be used to reduce the radioactive materials in liquid wastes prior to their discharge whenever such effluents require treatment to meet the design objectives set forth in Appendix I to 10 CFR 50.

If such treatment is required, and the liquid radwaste treatment system is inoperable for more than 31 days or radioactive liquid waste is being discharged without treatment, a special report shall be prepared and sent to the U. S. Nuclear Regulatory Commission which includes the following 1866 027 information:

15.3.9-7

Identification of the inoperable equipment or subsystems and a.

the reason for inoperability; b.

Actions taken to restore the inoperable equipment to operable status; and c.

Summary description of actions taken to prevent a recurrence.

2.

The gaseous radwaste treatment system and the ventilation exhaust treatment system shall be operable.

The appropriate portions of the gaseous radwaste treatment and ventilation exhaust treatment systems shall be used to reduce radioactive materials in gasecus wastes prior to their discharge, whenever such effluents require treatment to meet the design cbjectives set forth in Appendix I to 10 CPR 50.

If such treatment is required, and the gaseous radwaste treatment system or the ventilation exhaust treatment system is inoperable for more than 31 days or gaseous waste is being discharged without treatment, a special report shall be prepared and sent to the U.

S.

Nuclear Regulatory Commisnion which includes the following information:

a.

Identification of the inoperable equipment or subsystems and the reason for inoperability; b.

Actions taken to restore the inoperable equipment to operable status; and c.

Summary description of actions taken to prevent a recurrence.

Bases:

Liquid wastes from the radioactive Waste Disposal Sys*em are diluted in the Circulating Water System discharge prior to release to the lake (l)

With two pumps operating per unit, the rated flow of the circulating water system is approximately 356,000 gpm per unit.

Operation of a single circulating water pump per unit reduces the nominal flow rate by about 40%.

Liquid waste from the waste disposal system may be discharged to the circulating water discharge of either unit via'the service water return header.

Because of the low radioactivity 1866 028 1s.3.e-n

levels in the circulating water discharge, the concentrations of liquid radio-active effluents at this point are not measured directly. The concentrations in the circulating water discharge are calculated from the measured concen-tration in the waste condensate tank, the flow rate of the waste condensate pumps, and the nominal flow in the circulating water system.

If the annual average concentration of liquid wastes in the circulating water discharge should equal MPC as specified in C-1, the average concentration at the intake of the nearest public water supply at Two Rivers would be well below MPC(2).

Th2s, discharge of liquid wastes at the specified annual average concentrations would not result in significant exposure to members of the public as a result of consumption of drinking water from the lake, even if the effect of potable water treatment systems on reducing radioactive concentrations of the water supply is neglected.

Prior to re] ease to the atmosphere, gaseous wastes from the radioactive waste aisposal system are mixed in the auxiliary building vent with the flow from i

at least one of two auxiliary building exhaust fans.

Further dilution then occurs in the atmosphere.

Startups involving heavy boration of a main coolant system can result in a substantial increase in rejected dilution water to the holdup tanks and a net increase in the volume of gas makeup to the gas blanket system.

These startups involve a power outage and considerabic decay time has already occurred for the residual radioactive gases; hence, almost no radioactive gases exist.

Since the gases are predominantly hydrogen and nitrogen with low or trace radioactive, and since volumes can be large, monitoring and bypassing these low radioactivity, gases-866 029 directly to the vent discharge is allowed.

The formula prescribed in Specification D-1 takes >r.ao spheric dilution into account and ensures that at the point of maximum ground concentration at the 15.3.9-9

site boundary the requirements of 10 CFR 20 will not be exceeded.

The limit is based on the highest long term value of X/Q, which occurs at the nearest site boundary.

The release of radioactive materials in liquid offluents to unrestricted areas shall not exceed the limits set forth in Section 15.3.9 and should be as low as is reasonably achievable in accordance with the requirements of 10 CFR Part 50.34a and 50.36a.

These Specifications provide reasonable assurance that the resulting average annual dose or done commitnent from liquid effluents from each radioactive waste producing reactor for any individual in an unrestricted area from all pathways of exposure will not exceed 3 mrcm to the total body or 10 mrem to any organ.

Further, these Specifications provide reasonable assurance that the resulting annual air dose due to gamma radiation will not exceed 10 mrad and that the resulting annual air done due to beta radiation will not excced 20 mrad from the gaseous waste effluents from each radioactive waste producing reactor at the site.

These Specifications also provide reasonable assurance that no individual in an unrestricted area will receive an annual dose to the total body greater than 5 mrem or an annual dose to the skin greater than 15 mrem from these gaseous effluents, and tr.at the annual dose to any organ of an in-lividual from radioiodines and radioactive material in particulate form will not exceed 15 mrem from each radioactive waste producing reactor at the site.

At the same time, these specifications pormit the flexibility of operation, compat ible with considerations of health and safet'f, to assure that the public is provided with a dependable source of power even undet unusual operating 5

i conditions which may temporarily result in releases higher than such numerical guiden for design objectives but still within levels that assuro that the average population exposure is equivalent to small fractions of doses from natural background radiation.

15.3.9-10

The design objective releases set forth in this Specification are derived from the dose evaluation performed in accordance with Appendix I to 10 CFR part 50 In the evaluation, certain maximum calculate doses to an individual result from the calculated effluent releases.

Design objective releases are defined by scaling calculated releases upward to the point at which corresponding doses reach the applicable limit specified in Appendix I to 10 CFR part 50 Design objective releases are calculated in terms of " equivalent curies",

referenced to an appropriate single isotope within each release group, to allow for minor shifts in the distribution of actual effluent releases.

Dose factors used in the calculation of equivalent curies are selected for the age group in which the dose limit is most closely approached.

From the Appendix I evaluation, it is observed that ingestion is generally the most significant dose pathway for both gaseous and liquid effluent types, except for nobic gases; hence, ingestion dose factors ar e used in evaluating effluent releases except when noted otherwise. Conservatively, the highest dose factor listed for each isotope within the applicable age group is used for calculating equivalent curies, regardless of organ of applicability. For each effluent category, the design objective release is as follows:

EDCeijk = E ACeiik x LkX 2 Dk where EDCoijk = Dose objective release in total equivalent curies for all isotopes of effluent type k.

EACoijk = Calculated release in. total equivalcut curies for all isotopes of effluent type k.

1866 031 two units per plant.

2

=

Dk

= calculated dose resulting from release of EACeijk curies.

1.

The following notes apply to the calculation of design objective releases for gaseous effluents:

15.3.9-11

a)

For noble gases, the gamma air dose is limiting; b)

For radioiodines, the thyroid dose to the infant is limiting; the dose contribution from other isotopes is negligibic.

c)

For remaining isotopes, the liver dose to the child is limiting; the dose contribution from radiciodines '.s negligible for all organs other than the thyroid.

2 The following notes apply to the calculation of design objective releases for liquid effluents:

a)

For radiciodines, the thyroid dose to a child is limiting; for scaling purposen, the dose contribution from other isotopes is negligible.

b) For remaining isotopes, the total body dose to the adult is limiting; the dose contribution from radiciodines is negligibic for all organs other than the thyroid.

Dose factors for the teenager are conservatively used, since the liver dose for teenagers is the next limiting case after total body dose for adults.

Design objective releases calculated in the manner described above are quantir'ae of radioactivity in effluents which, for the particular environmental parameters and conditions at point Beach Iuclear Plant, would result in maximum doses to an individual corresponding to the limits set forth in Appeniix I to 10 CFR Part 50.

Actual plant releases are expected to be well within the design objective release quantities.

The periodic review required by this section ensures that plant releases remain as low as is reasonably achievable.

1866 4132 The radioactive liquid and gaseous effluent instrumentation is provided to monitor and control as applicabic, the releases of radioactive materials in liquid and gaseous ef fluents during actual or potential releases of these ef fluents.

The alarm / trip setpointo for these instruments shall be calculated in accordance 15.3.9-12

with the procedures in the offsite dose calculation manual to ensure that the alarm / trip will occur prior to exceeding the limits of 10 CPR part 20 The operability of the liquid and gaseous radwaste treatment systems and the ventilation exhaust treatment system ensures that the systems will be available for use whenever' liquid or gaseous effluents require treatment prior to release to the environment.

The requirement that the appropriate portions of these systems be used when specified provides assurance that the releases of radio-active materials in liquid and gaseous effluents will be kept "as low as is reasonably achievable".

Compliance with the provisions of Appendix I to 10 CFR part 50 is adequate demonstration of conformance to the standards set forth in 40 CPR part 190 regarding the dose com:nitment to individuals from the uranium fuel cycle.

The Specifications direct that i actual quantities of radioactive materials released exceed twice the quantities associated with the design dose objective of Appendix I to 10 CFR part 50, a special report will be submitted.

1 1866 033 References (1)

FSAR, Section 10.2 (2)

FSAR, Section 2, Appendix 2A (3)

FSAR, Sections 2.6 and 2.7 15.3.9-13

TABLP 15.3.9-1 RADIOACTIVE EFFLUE'IT MO!!ITORIf1G It!STRUMENTATICN MINIMU'1 CilANNELS INSTRUME!1T OPERABLE ACTION A.

Radioactive Liquid Effluent Monitoring 1.

LW16, Waste Distillate Tank 1

Note 1 Discharge 2.

R18, Waste Condensate Tank 1

Note 1 Discharge 3.

IR19, Unit 1 Steam Generator 1

fote 2 Blowdown Liquid 4,

2R19, Unit 2 Steam Generator 1

Note 2 Blowdown Liquid 5

R16, Containment Cooling 1

Note 3 Fan Service Water heturn 6

R2 0, S;>ent Puel Fool IIcat 1

Note 3 Exchanger Service Water Outlet 7.

FRC-LW15, Waste Distillate 1

Note 4 Tank Discharge Flow Recorder i

8.

FI-1064, Waste Condensate 1

Note 4 Tank Discharge Flow Meter B.

Radioactive Gaseous Effluent Monitoring 1.

Gas Decay Tank System a.

Noble Gas-R14, Auxiliary 1

Note 5 Building Vent Stack b.

Iodine and Particulate -

1 Note 6 Portable Continuous Air Sampler c.

FI-014, Gas Decay Tank 1

Note 7 Flow Measuring Device i

d.

Sampler Flow Rate Measuring 1

Noto 6 f

Device 1866 034

TABLE 15.3.9-1 (Continued)

MINIMUM CIIANNELS INSTRUMENT OPERABLE ACTION 2.

Auxiliary Building Ventilation System a.

Noble Gas-R14, Auxiliary 1

Note 8 Building Vent Stack b.

Iodine and Particulate -

1 Note 6 Portable Continuous Air Sampler c.

Sampler Flow Rate Measuring 1

Note 6 Device 3.

Condenser Air Ejection System a.

Noble Gas-CR9, Combined 1

Note 8 Air Ejector Discharge Monitor and R15, Air Ejector Monitors (one per unit) b.

Flow Rate Monitor - Air 1

Note 7 Ejectors (one per unit) 4.

Containment Purge and Continuous Vent System a.

Noble Gas-R12 Monitors, 1

Note 8 (one per unit) b.

Iodine and Particulate -

1 Note 6 Portable Co-Finuous Air Sampler c.

10CFM Vent Path Flow 1

Note 7 Monitor d.

Sampler Flow Rate Measuring 1

Note 6 Device 5.

Fuel Storage and Drumming Area Ventilation System a.

Noble Gas-R21, Drumming 1

Note 8 Area Stack b.

Iodine and Particulate -

1 Note 6 Portable Continuous Air Sampler c.

Sampler Flow Rate Measuring 1

Note 6 Device 1866 035

TABLE 15.3.9-1 (Continued)

MINIMUM CHANNELS INSTRUMEDT OPERADLE ACTION 6.

Gas Stripper Building Ventilation a.

Noble Gas - GW112 Monitor 1

Note 8 b.

Iodine and Particulate -

1 Note 6 Portable Continuous Air Sampler c.

Sampler Flow Rate Measuring 1

Note 6 Device Note 1: With the number of channels operable less than required by the minimum channels operable requirement, ef fluent releases may continue for up to 14 days provided that prior to initiating a release, two separate samples are analyzed i?

ccordance with the applicable part of Specification 15.4.6 and the release rate calculation is reviewed.

Note 2: With the number of channels operable less than required by the minimum channels operable requirement, effluent releases via this pathway may continue for up to 30 days provided grab camples are ar.alyzed for gamma radioactivity at least once every 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> when the R-15 Air Ejector Monitor is operable or at least once every 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> if the R-15 monitor is not operable.

Note 3: With the number of channels operable less than required by the mir.. mum channels operable requirement, effluent releases via this pathway may continue for up to 30 days provided that at least once every 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> grab samples are collected and analyzed for gamma radioactivity.

Note 4:

With the number of channels operable less than required by the minimum channels operable requirement, effluent releases via this pathway may continue for up to 30 days provided the flow rate is estimated at least once per 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> during actual releases.

Note 5: With the number of channels operable less than required by the minimum channels operable requirement, the contents of the tanks may be released to the environment for up to 14 days provided that prior to initiating the release two separate sample, of the tank's contents are analyzed in accordance with the applicable part of Specification 15.4.16 and the release rate calculation is reviewed.

Note 6: With the number of channels operable less than required by the minimum channels operable requirement, e f fluent releases via the affected pathway may continue for up to 30 days provide samples are continuously collected with auxiliary sampling equipment.

Note 7: With the number of channels operable less than required by the minimum channels operoole requirement, effluent releases via this pathway may continue for up to 30 days provided the flow rate is estimated at least once every 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> or determined with auxiliary indication.

Note 8: With the number of channels operable less than required by the minimum channels operable requirement, e f fluent releases via this pathway may continue for up to 30 days provided grab sam-les are taken at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> and these samples are analyzed for gamma radioactivity within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

1866 036

TABLE 15.4.1-1 (CONTINUED)

Channel Des crip tion Check Calibrate Test Remarks 10.

Rod Position Sank Counters S (1) *

  • N.A.

N.A.

1) With analog rod position 11.

Steam Generator Level S **

R M**

12.

Steam Generator Flow Mis:stch 5 **

R M**

13.

Charging Flow N.A.

R N.A.

14.

Residual Heat Removal Pu:T Flow N.A.

R N.A.

15.

Boric Acid Tank Level D

R N.A.

16.

Refueling Water Storage Tank N.A.

R N.A.

Level 17.

Volume Control Tank Level N.A.

R N.A.

18.

Reactor Containm2nt Pressure D

R B/W (1) *

  • 1) Isolation Valve signal 19.

Radiation Monitoring System D

R M

Radioactive Effluent Monitor Instrumen-tation Requirements are covered in 15.4.16.

20.

Boric Acid Control N.A.

R N.A.

21.

Containment Sump Level N.A.

R N.A.

22.

Turbine Overspeed Tdp*

N.A.

R M (1) * *

1) Block Trip 23.

Accumulator Level ar d Pressure S

R N.A.

Overspeed Trip Mechanism, and Independent Turbine Speed Detection and Valve Trip System.

    • Not required during periods of refueling shutdown, but must be performed prior to starting up if it has not been performed during the previous surveillance period.

CD U

N

TABLE 15.4.10 OPERATIONAL RADIOLOGICAL ENVIRONMENTAL MONITORING Sample Type Locations Frequency Analysis Comments Vegetation 1-Re fe re nce (20) 3x/y r.

Gross Beta Vegetation sarples 4-Site Boundary (1,2,3,4) as available Gamma Scan are general grasses and weeds.

3-Within 5 miles (6,8,9)

Shoreline Silt 1-Discharge Flume (12) 2x/yr.

Gross Beta 2-N of Discharge (5,9)

Gamma Scan 2-S of Discharge (1,6)

Soil 1-Re fe re nce (20) 2x/yr.

Gross Beta 4-Site Boundary (1,2,3,4)

Gamma Scan 3-Within 5 miles (6,8,9)

TLD's 1-Re fe rence (20)

Quarte rly Gamma Dose Control TL is

-Site Vicinity (1,2,3,4,5,14,15,16,22) used for roind ll-Within 3 to 6 miles (6,7,8,9,17,18,23,24,25,26,27) trip transporta :.is 1-PENP Pier (12) 1-Transportation Control (20)

Lake Water 1-Di:[ charge Flume (12)

Monthly Gross Beta Gross Beta and Gamma 2-N of Discharge (5,9)

(Sarple at Gama Scan Scan done monthly on 2-S of Discharge (1,6) flume is com-total solids; Tritium posited weekly and Radiostrontium for monthly Tritium done quarterly on analysis.)

Strontium-89 composites for each S trontium-90 location.

Air Filters 1-Reference (20)

Weekly Gross Beta Gross Beta analysis 4-Site Boundary (1,2,3,4)

Radioiodine done weekly on parti-1-Within 5 miles (8)

Gamma Scan culate filters; Radio-iodine done weekly on charcoal cannisters; gamma scan done quarterly on particulate filter CO composites for each location.

O tr4 CD*

Page 1 of 2

TABLE 15.4.10-1 (CONTINUED)

Sample Type Locations ^'

Freq uency Analysis Comments Well Water 1-Cnsite Well (10)

Quarterly Gross Beta Gross Beta and Gamma Gamma Scan Scan done on total solids.

Tritium Strontium-89 Strontium-90 Milk 1-Dairy Farm, W (11)

Monthly Garna Scan Radioiodine analysis 1-Dairy Farm, NNW (19)

Radioiodine done by the resin 1-Dairy Farm, SSE (21)

S trontium-89 extraction technique.

Strontium-90 Algae 1-North of Discharge (5) 2x/yr.

Gross Beta 1-Discharge of Flume (12) as available Gamma Scan Fish 1-Travelling Screens (13) 2 x/y r.

Gross Beta Analysis of edible as available Gamma Scan portions only.

Food Products 1-Onsite (3)

At Harvest Gross Beta Analysis of food Gamma Scan crop produced onsite.

(a)

Reference location is chosen well in excess of 10 miles from the plant in a lot? X/Q sector to p rovide an estimate of background levels.

(b)

Numbers given under location correspond to sampling locations shown in Figure 15.4.10-1.

CO CB CB OW Page 2 of 2

FM @MM

)j A

i 4

l e

3

  • J a /*
E

,t b q

.J i/:

j.

O b *

5. c h

. t J.

~

-.,g

,, [. i 3w -

+

/

'4.,

u h

2 a

I d

f

/-

t I t '

s v

[

's g

4t s 3,

' 2..

I,(. c. a

}

g< /'

l 3

(

i g[

~ -

t

-5

.g.

i h '. ' <.. I'

~ ^ i'-

  • '/

~

' ' ~

,tr

-+ +-** *j e r- *,"*,., e /

- g -,

i ',

x i-r j

,s.

.f.

o

_ f Id

/

/h,/s.

,/

y y

) -/ * )

y,'** ~ ~ ~*"f.. i[.

l.k #

/e' '}, 4 g g

iv 7

,'c 93 i i-

  1. f

( f 1

/, & f.

t s.

t r*

g,9 i

~

- V 3 -.t

-= g-h.\\

p i

t*

ic

f. il -

O.,

  • ,r

>l 1

S-W d

i I,

k4 i

24

'h < 8 y,..

c

- 3

, f !, H' '

I. ' j 8

..a, ),'A'> _C.p,

l'( '

$3 h

'I

g. ~
  • q.'i, -= y,l 1+

1 po j, jo s

a' J;-)<

i.

4._

g w r--,

'p

.,, // l g--

, ;f Q

f vt n-4 i

,e e t, j'i

}

5, W%

,[

  1. y' "

[t

!.f.

y

, h, d;'

M.y

--Q(.

\\ 1 -l 5;

. 4,.

a. <.,.

s p p-s.

,3 i

e

,. -m 2 - A,

}'.'l x 5

f ys x wN.

s.a 4 )?. ':,'f[1,

t. *) p

., ' "W)g. A,., O,.%.,1[

q

,) -

g

("'

. t i

' :;,- L v

A.

+ ss 9-g i.

ql. 4*9, % g.g i, ',-

.j3s i,

,A r

v.,

y_

(, J f.,..

-v

~

r

?'

ya f

1 i

.o..

_m

,c,u..

,t6-..

t.

5 4

g J,

e 3

"j j?

  • g- !

-A-

[

t

'+

{

'l I. '.

s' i J r s

r

'(j 9 5],h l

  • i@'

s

'.,l

.,. ~ i V

l'

'~ /~d

  • }.? 1

-Q

~

~

- A t

I

- A, _ n. -.- -, q m-g

,J r 1

f' I, _ p 6 -

t.

.-,O;

_ p _,_ _

o y_

1 t

j 4 - I ( '.. h 4ia pf.

6,

,w t.,;

s. - e -

s f '. e,'

x 6

t

  • ** l g,,
m. )e a m'y - A e{.n4 -~i.
  • h...

. f E-i o

- - t,#v.p. -

t e

', e,u;7.

i y

e

. ~.

_y

-A

,. #J.,

2 3

[

s..,

.%- g

'. I i

m,

./.,,

s

'l.-

s-t l

s

<~m 4.,

c.,

/., > - ' ' -

t"'i j,.e..

t'

.-.c,d

./

,u

-.e

<-t y :;

N ^ *,y ' -*i -

, g _. -

q I'#d '

e t

q

%, e,M i

(

t u

~

,G -

a I

,s

. ' I t

',. ;4 )

._-L._-,_L.-_.

/. )

,a

')

9 i.,,.fy*

s

'?

- :i-p qi-M3 I

w e'.

~I,x i

/

3 i

.: i,

/

,/

/ t.

N b

3

r,;

t

,/ c q,.,/m-

t. s ).

/l3

~.

3.,-

i t

s

/

__A iI f

%sa.L. --y q

I t,

r b

l

_- +

~/

/.

,_,y_..,.

_.4

. *p.

w y

4

/

..w*-

\\

l

,.& t 5

) N'

  • ka. t

_? l,Y

^

Z m.e s.

4 g,\\

e'

.L l ";

f [/

~

e_.

+

a, --

I

).-../

j 8

j j

y

d. s 3

a

.e l.

2

/

JI x

,i i'.. t.,*

h

.a'

  • j l

/

g -..

t'.-

s

( = s>"r.

e j,-

lt 4~

.r y

' x 2

a

..(c f.

'"3

~.

t

~s e; 4

x

/

' ' +,

4

. I 2,.

e

.1 4

/

4 3 l

li.,,'..c:

  • ... ht.d. \\-

~

r

. u, g l t, I

1r-

'--t

'A -- - -

t

.p

...r o n t s t i4 t i" y,-

,, ' v, as

.\\ 'e '

)

.1...

~',-

44 ->

st g,o a

,. ?,

m e

un 'pW.'

,_'4)

, jlf * '

M

8I' g

%, '*? !

4

?

? 'k 's

?

{ '.

..u i

1 t

1 y

J j

J J

.J-4 1

E ic;se 15.4.10-1 San;' ling locatices 186~6 040

9 15.4.16 RADIOACTIVE EFPLUENT MONITORING AND CONTROL SYSTEMS Applicability Applies to the periodic inspection, testing calibration and verification of operability requirements for the radioactive liquid and gaseous effluent monitoring instrumentation and waste processing systems.

Obje ctive To verify that radioactive liquid and gaseous effluent monitoring instrumentation channels and liquid and gaseous radwaste treatment systens are periodically demonstrated to be operable and to verify that the concentrations of raefoactive material released from the site do not exceed the limits specified in Specification 15.3.9.

Specifications A.

Radioactive Effluent Monitoring Instrumentation Channel Surveillance Requirer.unts Ecch radioactive liquid effluent monitoring instrumentation channel and each ra.oactive gaseous effluent monitoring instrumentation channel shall be demonstrated operable by performance of the channel check, channel calibration and channel functional tert operations at the frequencies shown in Table 15.4.16-1.

B.

Radioactive Liquid Waste Sarpling and Analysis 1.

The radioactivity content of each batch of radioactive liquid waste shall be determined prior to release by sampling and analysis in accordance with Tabic 15.4.16-2.

The results of pre 2 - 2ase analyses shall be used with the calculational methods in the Offsite Dose Calculation Manual (ODCM) to assure that the concentration at the point of releases is maintained within the limits of Specification 15.3.9.

2.

Post-release analyses of samples corposited f rom batch releases shall be performed in accordance with Table 15.4.16-2.

The results of the previous post-release analyses shall be used with the calculational 1866 041 15.4.16-1

methods in the ODC4 to assure that the concentrations at the point of release were maintained within the limits of Specification 15.3.9.

3.

The radioactivity concentration of liquids discharged from continuous release points shall be determined by collection and analysis of samples in accordance with Table 15.4.6-2.

The results of the analyses shall be used with the calculational methods in the ODCM to assure that the concentrations at the point of release are maintained within the limits of Specification 15. 3.9 C.

Radioactive Gaseous Waste Sampling and Analysis 1.

The radicactivitiy concentration of radioactive gaseous wastes shall be determined by sampling and analyses in accordance with Table 15.4.16-3.

The results of the analyses shall be used with the calculation methods in the ODCM to assure tuat concentrations are maintained within the limits of specification 15.3.9.

D.

Radioactive Waste processing System Operability 1.

The liquid radwaste treatment systems shall be demonstrated operable by the following reans:

a. The blowdown evaporator and one of two redundant boric acid evaporators together with their associated equipment shall be operated at least once a quarter with a demonstrated minimum Decontamination Factor (DF) for soluble gamma isotopes of 10.
b. The waste evaporator and associated equipment, while not normally used, shall be demonstrated. operable with a minimum DF for soluble gamma isotopes of 10 prior to each use,
c. The polishing condensate demineralizers shall be checked to verify a minimum DF of 10 for soluble gamma isotopes at least once a quarter.

2.

The ventilation and gaseous waste processing systems shall be demonstrated operable by the following means.

1866 042 15.4. 16-2

a.

For the Auxiliary Building Ventilation, Containment Purge and Continuous Vent (one system per unit), and Chemistry Laboratory Ventilation Systens, the !! EPA filters and charcoal absorbers shall be inspected for damage or ndsalignment and verified in place once a quarter.

b.

For the Spent Fuel Pool - Drumming Area, Service Building and Auxiliary Building - (low radiation areas) ventilation systems,, the llEPA filters shall be inspected for damage or rdsalignment and verified in place once a quarter.

c.

The Charcoal Decay Tanks shall be checked for operability once a quarter by verifying with appropriate beta-gamma survey instruments a reduction in gross radioactivity between the inlet and outlet flow stream.

d.

The Condenser Air Ejector decay duct valve lineup shall be checked end the charcoal absorber inspected for damage and verified in place ence a quarter.

1866 043 15.4.16-3

TABLE 15.4.16-1 Radioactive Effluent Monitorina Instrumentation Surveillance Requirements Channel Description Check Calibrate Test

  • Remarks A.

Radioactive Liquid Monitors 1.

LW16, Waste Distillate Tank Discharge D

R M

2.

R18, Waste Condensate Tank Discharge D

R M

3.

R19, Unit 1, Steam Generator Blowdown Liquid D

R M

4.

R19, Unit 2, Steam Generator Blowdown Liquid D

R M

5.

R16, Containment Cooling Fan Service Water D

R M

Return 6.

R20, Spent Fuel Pool Heat Exchanger Service D

R M

The test for this channel Water Outlet is satisfied by a source response check only.

B.

Flow Rate Measurement Devices - Liquid Effluents 1.

FRC-LWl5, Waste Distillate Tank Discharge P

R NA Flow Recorder 2

FI-1064, Naste Condensate Tank Discharge P

R NA Flow Meter

__, 12.

Radioactivity Recorders - Liquid Effluents CO 1.

R19, Steam Generator B]owdown D

R NA 2

LW16, Wasta Distillate Tank Discharge D

R NA CD J5-3.

R18, Waste Condensate Tank Discharge D

R NA

-C=

D.

Radioactive Gaseous Monitors 1.

Gas Decay Tank System and Auxiliary Building Ventilation System a.

Noble Gas - R14, Auxiliary Building D

R M

Vent Stack

TAB LE 15.4.16-1 (Continued)

Channel Description Check Calibrate Test

  • Remarks b.

Iodine and Particulate - Portable P/W R

NA Continuous Air Sampler c.

FI-014, Gas Decay Tank Flow Measuring r

R NA Device d.

Sampler Flow Rate Measuring Device W

R NA 2.

Condenser Air Ejector System a.

Noble Gas - CR9, Combined Air Ejector D

R M

Discharge b.

Moble Gas - R15, Air Ejector, (one per D

R M

unit) c.

Flow Rate Measuring Device - Air D

NA NA Ejectors (one per unit) 3.

Containment Purge and Continuous Vent System a.

Noble Gas - R12, one per unit D

R M

b.

Iodine and Particulate - Portable P/W R

NA Continuous Air Sampler c.

lOCFM Vent Path Flow Monitor P/D**

R NA d.

Sampler Flow Rate Measuring Device P/W R

NA 4

Fuel Storage and Drumming Area Ventilation C33 System C7N C7N a.

Noble Gas - R21, Drumming Area Stack D

R M

jf b.

Iodine and Particulate - Portable W

R NA Continuous Air Sampler ty) c.

Sampler Flow Rate Measuring Device W

R NA

TABLE.15.4.16-1 (Continued)

Channel Description Check Calibrate Test *

Remarks, 5.

Gas Stripper Building Ventilation a.

Noble Gas - GWil2 D

R M

b.

Iodine and Particulate - Portable W

R NA Continuous Air Sampler c.

Sampler Flow Rate Measuring Device W

R NA

  • The channel functional tests identified in this table include a source check response test.

D = Daily M = Monthly P = Prior to or during a release W = Weekly R = One each refueling cycle

    • When in use.

CX CB C

b Ch

e TABLE 15.4.16-2 Radioactive Liquid Waste Sampling and Analysis Proaram Sampling Analysis Type of Liquid Release Type Frequency Frequency Activity Analysis

1. Waste Condensate Tank, Prior to Prior to Gamma Emitters, Waste Distillate Tank Release Release Tritium Monthly on Gross Alpha Composite Sr-89, Sr-90 Sample
2. Continuous Releases Twice Weekly Twice Weekly Gamma Emitters, Grab Samples Tritium Monthly on Gross Alpha Composite Sr-89, Sr-90 Sampler TABLE 15.4.16-3 Radioactive Gaseous Waste Sampling and Analysis Program Sampling Analysis Type of Gaseous Release Type Frequency Frequency Activity Analysis
1. Gas Decay Tank Prior to Prior to Gamma Emitters Release Release
2. Containment Purge or Prior to Prior to Gamma Emitters, Continuous Vent Purge or Vent Purge or Vent Tritium
3. All Continuous Releases Continuous Weekly Analysis Gamma Emitters, of Charcoal and I-131, I-133 Particulate Samples Continuous Monthly Composite Gross Alpha Particulate Sample Continuous Quarterly Com-Sr-89, Sr-90 posite Particulate Sample Weekly Weekly Noble Gases (Grab) 1866 047

15.5 DESIGN FEA'IURES 15.5.1 SITE Applicability Applies to the location and extent of the reactor site.

Objective To define those aspects of the site which affect the overall safety of the installation.

Specification The Point Beach Nuclear Power Plant is located on property owned by the Wisconsin Electric Power Company at a site on tne shore of Lake Michigan, approximately 30 miles southeast of the city of Green Bay.

The minimum distance from the reactor containment center line to the site exclusion boundary as defined in 10 CPR 100.3 is 1200 meters. Tlw site boundary is identical with the exclusion area boundary. The site exclusion area boundary is identified on Figure 15.5.1-1.

f866 048 15.5.1-1

11

~

,f h.

((n f'

A y

e i

i

- 2 6

.c 9

i...,.

i

.y oJ

)

  • . T1.Lt

\\

/

A r

,m

,2 t,. t

- gi.

(

)

a

, L. -

t.

\\

.1 a

\\

h

\\

(

l!

) l.

4A.\\

i 1

s

(

.;(i.,S

  • 'bs f

(

M-g,

f T l

(

V\\

d.uks l

x

\\.

C,.g \\

ss s1 T,,

s,g

i. f, j '

\\.

']

i.

=

d k

  • o

'g j

(

g A

s

, g,. -.

\\

3

,s

- s A.

g i

s c.' -. i. s i,

s s

., i g,

~

~.

W r

's i

(

t

}%'j'___'

~ N

x -

,9

'p,M

\\

= (.

.,b. -

_----2--L5

1- --q* h s\\

w.,,,... a t.,

-= =

.;q, __

J.

  • %y w%

k_,'/./, cfp.. c_

(

~..

g. ~ ' '
  • ~ ~L

~

3

.. ~

w w, p ].

x w-

-3*,

s, j

A1

\\

\\

Q SLW' hb kb I T

p s

i

~. JT Z_-d[d ~[~=.-my+Fr= :sw./ k._

L-e S%{VyNN& '~e I

E

~T 1-l l.

w}

-..r " y [_..,,\\.

= = =-

-7 sy y'

3h*'

e' i

l s

lu M.

s

/

\\ -)

l s

\\>

_ q'. sx q

-x

/

t, y

' 7,, x"

(

N

  1. ,.;:~.

x

,l

"(

\\

.,f l

.s l.

q-

. _.._ 'A f

g

~q-j!

s q) r y

j s

t l

l g

::~~ -

2

~

v

\\

k.

,/

,A,\\

s.

e 5

g ' i*g - - - -. - -

->. - e s-4 3

===e g y ___.

.\\

~

l FIGURE 15.5.1-1 SITE PLAtl i&,

SITE LiUUUJARY = PROPERTY LIflE 1866 049 SCALE: 1" = 400' m

..m.

b)

Review all proposed tests and experiments related to safety and the results thereof when applicable.

c)

Review all proposed changes to Technical Specifications, d)

Review all proposed changes or modifications to plant systems or equipment where changes would require a change in operating or emergency procedures or that affect nuclear safety.

e)

Periodically review plant operations for industrial and nuclear safety hazards.

f)

Investigate violations or suspected violations of Technical Specifications, such investigations to include reports, evaluations, and recommendations to prevent recurrence, to the Vice President - Nuclear Plant and to the Chairman of the Off-Site Review Committee.

g) Perform special reviews and investigations and prepare reports thereon as requested by the Chairman of the off-Site Review Committe e.

l h)

Investigate, review, and report on all reportable occurrences.

1) Cause to be conducted periodic drills on emergency procedures, including evaccation (partial or complete) of the site and check adequacy of communications with off-site support groups.

j)

Review the Facility Fire Protection Program and implementing procedures at least once per 24 months.

k)

Review every unplanned onsite release of radioactive material to the environs which exceeds the pernissibic release concen-trations specified in Specification 15.3.9.

Such review will f

include the preparation and forwarding of reports c_vering e valuation, recommendation and disposition to prevent recurrence to the Director - Nuclear Power Department and the Executive Vice President.

bf)i 15.6.5-3

P 9.

Performance of structures, systems, or compone.nts that requires remedial action or corrective measures to prevert operation in a manner less conservative than that assumed in the accident analyses in the safety analysis report or technical specifications bases; or discovery during plant life of conditions not specifically considered in the safety analysis report or technical specification that require remedial action or corrective measures to prevent the existence or development of an unsafe condition.

10.

offsite Releases of radioactive materials in liquid or gaseous effluents which exceed twice the quantities corresponding to the dose design objectives of Appendix I to 10 CFR Part 50.

11.

An unplanned offsite release of 1) more than 1 curie of radioactive material in liquid effluents, 2) more than 150 curies of noble gas in gaseous ef fluents, or 3) rrre than 0.05 curies of Iodine 131 in gaseous effluents.

12.

Confirmed measured levels of radioactivity in an environmental sampling medium determined to exceed the notification levels shown in Table 15.4.10-2 when averaged over any calendar quarter sampling period.

B.

Thirty-Day Written Reports The types of events listed in iters 1 through 4 below have lesser immediate importance.

These events shall be the subject of written reports to the Director, Regulatory Operations, Region III within 30 days of the occurrence of the event.

The written report shall include, as a minimun, a completed copy of the licensee event report form, and may be supplemented, as needed to provide complete explanation of the circumstances surrounding the event.

1866'051 15.6.9-6

~M=

--.w-y w--

,