ML19256F548
| ML19256F548 | |
| Person / Time | |
|---|---|
| Site: | Mcguire, Catawba |
| Issue date: | 11/30/1979 |
| From: | James O'Reilly NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II) |
| To: | Parker W DUKE POWER CO. |
| References | |
| NUDOCS 7912190392 | |
| Download: ML19256F548 (1) | |
Text
,
o ano
/C
/
UNITED STATES 8"3, 7,
NUCLEAR REGULATORY COMMISSION f j(, #
E REGION ll o
101 MARIETTA ST., N.W., SUITE 3100 g"
ATLANTA, G EoRGIA 30303 NOV 3 01979 In Reply Refer To:
RII C
~
rYU Duke Power Company Attn:
W. O. Parker, Jr.
Vice President, Steam Production P. O.
Box 2178 Charlotte, North Carolina 28242 Gentlemen:
The enclosed IE Bulletin No. 79-27, is forwarded to you for information.
Although no written response is required at this time, these concerns will be addressed as part of the licensing process for your plent.
If you desire sdditional information regarding this matter, please contact this office.
Sincerely,
/-
James P. O'R ly Director
Enclosures:
1.
List of Recently Issued IE Bulletins 1857 227 7 912190 M
NOV 3 01979 Duke Power Company,
cc w/ encl:
D. G. Beam, Project Manager Post Office Box 223 Clover, South Carolina 29710 M. D. McIntosh, Plant Manager Post Office Box 488 Cornelius, North Ca olina 28031 J. C. Rogers, Project Manager Post Office Box 33189 Charlotte, North Carolina 28242 1857 228
UNITED STATES SSINS No.:
6820 NUCLEAR REGULATORY COMMISSION Accession No.:
OFFICE OF INSPECTION AND ENFORCEMENT 7910250499 WASHINGTON, D.C.
20555 November 30, 1979 IE Bulletin No. 79-27 LOSS OF NON-CLASS 1E INSTRUMENTATION AND CONTROL POWER SYSTEM BUS DURING OPERATION Description of Circumstances:
On November 10, 1979, an event occurred at the Oconee Power Station, Unit 3, that resulted in loss of power to a non-class IE 120 Vac single phase power panel that supplied power to the Integrated Control System (ICS) and the Non-Nuclear Instrumentation (NNI) System. This loss of power resulted in control system malfunctions and significant loss of information to the control room operator.
Specifically, at 3:16 p.m.,
with Unit 3 at 100 percent power, the main condensate pumps tripped, apparently as a result of a technician performing maintenance on the hotwell level control system. This led to reduced feedwater flow to the steam generators, which resulted in a reactor trip due to high coolant system pressure and simultaneous turbine trip at 3:16:57 p.m.
At 3:17:15 p.m.,
the non-class IE inverter power supply feeding all power to the integrated control system (which provides proper coordination of the reactor, steam generator feedwater control, and turbine) and to one NNI channel tripped and failed to automatically transfer its loads from the DC power source to the regulated AC power source.
The inverter tripped due to blown fuses.
Loss of power to the NNI rendered control room indicators and recorders for the reactor coolant system (except for one wide-range RCS pressure recorder) and most of the secondary plant systems inoperable, causing loss of indication for systems used for decay heat removal and water addition to the reactor vessel and steam generators. Upon loss of power, all valves controlled by the ICS assumed their respective failure positions.
The loss of power existed for approximately three minutes, until
.a operator could reach the equipment room and manually switch the inverter to the regulated AC source.
The above event was discussed in IE Information Notice No. 79-29, issued November 16, 1979.
NUREG 0600 " Investigation into the March 28, 1979 TMI Accident" also discusses TMI LER 78-021-03L whereby the RCS depressurized and Safety Injection occured on loss of a vital bus due to inverter failure.
Actions to Be Taken by Licensees For all power reactor facilities with an DUPLICATE DOCUMENT completion of construction (North Anna 2 Sequoyah, and Zimmer):
Entire document previously
}[
entered into system under:
ANO No. of pages: