Forwards IE Bulletin 79-27, Loss of Non-Class IE Instrumentation & Control Power Sys Bus During Operation. Written Response Required
ML19256F542
Person / Time
Site: Farley 
Issue date: 11/30/1979
From: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To: Clayton F
ALABAMA POWER CO.
References
NUDOCS 7912190374
Download: ML19256F542 (1)


Text

.

m

'o UNITED STATES 8'3 f *7, NUCLEAR REGULATORY COMMISSION I E REGION ll w

o

!^4 f

101 MARIETTA ST., N.W., SulTE 3100

/

ATLANTA, GEORGIA 30303 NOV 3 01979 In Reply Refer To:

RI -

50-348 Alabama Power Company Attn:

F. L. Clayton, Jr.

Senior Vice President Post Office Box 2641 Birmingham, Alabama 35291 Gentlemen:

The enclosed IE Bulletin No. 79-27, is forwarded for action.

A written response is required.

If you desire additional information regarding this matter, please contact this office.

Sincerely,

(

M'_)

%l James P. O'Re(11 Director

Enclosures:

1.

IE Bulletin No. 79-27 2.

List of Recently Issued IE Bulletins 1857 236 7912190 3 7 9

NOV 3 01979 Alabama Power Company.

cc w/ enc 1:

A. R. Barton Executive Vice President fost Office Box 2641 Birmingham, Alabama 35291 J. T. Young Vice President-Production Post Office E.x 2641 Birmingham, Alabama 35291 C. Biddinger, Jr.

Manager-Corporate Quality Assurance Post Office Box 2641 Birmingham, Alabama 35291 H. O. Thrash Manager-Nuclear Generation Post Office Box 2641 Birmingham, Alabama 35291 H. G. Hairston, III Plant Manager Drawer 470 Ashford, Alabama 36312 R. E. Hollands, Jr.

QA Supervisor Post Office Box U Ashford, Alabama 36312 iBSJ7 237

UNITED STATES SSINS No.:

6820 NUCLEAR REGULATORY COMMISSION Accession No.:

OFFICE OF INSPECTION AND ENFORCEMENT 7910250499 WASHINGTON, D.C.

20555 November 30, 1979 IE Bulletin No. 79-27 LOSS OF NON-CLASS 1E INSTRUMENTATION AND CONTROL POWER SYSTEM BUS DURING OPERATION Description of Circumstances:

On November 10, 1979, an event occurred at the Oconee Power Station, Unit 3, that resulted in loss of power to a non-class 1E 120 Vac single phase power panel that supplied power to the Integrated Control System (ICS) and the Non-Nuclear Instrumentation (NNI) System. This loss of power result _d in control system malfunctions and significant loss of information to the control room operator.

Specifically, at 3:16 p.m., with Unit 3 at 100 percent power, the main condensate pumps tripped, apparently as a result of a technician performing maintenance on the hotwell level control system. This led to reduced feedwater flow to the steam generators, which resulted in a reactor trip due to high coolant system pressure and simultaneous turbine trip at 3:16:57 p.m.

At 3: 17:15 p.m., the non-class 1E inverter power supply feeding all power to the integrated control system (which provides proper coordination of the reactor, steam generator feedwater control, and turbine) and to one NNI channel tripped and failed to automatically transfer its loads from the DC power source to the regulated AC power source. The inverter tripped due to blown fuses.

Loss of power to the NNI rendered control room indicators and recorders for the reactor coolant system (except for one wide-range RCS pressure recorder) and most of the secondary plant systems inoperable, causing loss of indication for systems used for decay heat removal and water addition to the reactor vessel and steam generators.

Upon loss of power, all valves controlled by the ICS assumed their respective failure positions. The loss of power existed for approximately three minutes, until an operator couF reach the equipment room and manually switch the invertcr to the regulated AC source.

The above event was discussed in IE Information Notice No. 79-29, issued November 16, 1979.

NUREG 0600 " Investigation into the March 28, 1979 TMI Accident" also discusses TMI LER 78-021-03L whereby the RCS depressurized and Safety Injection occured on loss of a vital bus due to inverter failure.

Actions to Be Taken by L censees For all power reactor f cilities with an DUPLICATE DOCUMENT completion of construct _on (North Anna 2 Sequayah, and Zimmer):

Entire document previously entered into system under:

ANO E

(

No. of pages: