ML19256B527
| ML19256B527 | |
| Person / Time | |
|---|---|
| Site: | Oyster Creek |
| Issue date: | 07/11/1979 |
| From: | Grier B NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I) |
| To: | Finfrock I JERSEY CENTRAL POWER & LIGHT CO. |
| References | |
| NUDOCS 7907270333 | |
| Download: ML19256B527 (1) | |
Text
aarco y_
f,,
UNITED STATES yn y'p g
NUCLEAR REGULATORY COMMISSION l
REGION I 3 g; S'
631 PARK AVENUE
,e KING OF PRUSSIA, PENNSYLVANI A 19406 July 11, 1979 Docket No. 50-219 Jersey Central Power and Light Company ATTN:
Mr. Ivan R. Finfrock, Jr.
Vice President Madison Avenue at Punch Bowl Road Morristown, New Jersey 07960 Gentlemen:
The enclosed Bulletin No. 79-15 is forwarded to you for action.
A written res onse is required.
If you desire additional information regarding r
this matter, please contact this office.
Sincerely,
/
b Boyce H. Grier Director
Enclosures:
1.
IE Bulletin No. 79-15 w/ Attachments 2.
Listing of IE Bulletins Issued in Last Twelve Months cc w/encls:
J. T. Carroll, Station Superintendent A. Z. Roisman, Natural Resources Defense Council I
7907270J77
ENCLOSURE 1 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.
20555 IE Bulletin No. 79-15 Date:
July 11, 1979 Page 1 of 3 DEEP DRAFT PUMP DEFICIENCIES Description of Circumstances:
On October 20, 1978, Commonwealth Edison Company reported that manufacturing deficiencies had been identified in new high nressure core spray, low pressure core spray, and residual heat removal pumps manufactured by Ingersoll-Rand (I-R)
Company, Cameron Pump Division.
Ee
" these pumps is a vertical turbine pump with impellers located in bowls in a sump or a self contained barrel.
The motor (prime mover) is located at the highest pump elevation to take into account maximum flooding at the site or space considerations.
The suction is at the lower end of the pump while the discharge head is just below the driver.
Bearings supporting the vertical shaft segments (usually 5 to 10 segments) are either self lubricated, force fed (lubricated by fluid being pumped), or oil lubricated and maintained within their own isolated system.
These pumps are designated as " Deep Draft".
Figures 1&2 show typical outlines of such pumps.
The internal deficiencies, identified through dimensional and visual inspections were as follows:
Low Pressure Core Spray Pumps (I-R Model No. 29APKD-5) (Date of Manufacture -
Feburary 1973)
Loose impeller bolts and bolts improperly staked Loose key - keyway fit Excessive runout on pump shaft Bearing showed wear Bearing clearance exceeded recommended tolerance Coupling thread galled Wear ring clearance out-of-specification Impeller-to-shaft clearance out of specification Cracks found in second-and-third-stage impellers Stuffing box bushings were severely galled High Pressure Core Spray Pumps (I-R Mode September 1972)
DUPLICATE DOCUMENT Bearing clearance exceeded recommend Wear ring clearance out-of-specifica Entire document previously Bearings showed wear entered into system under:
ANO 77d 7 / 96 /,,7 g N o.
of pages:
9