gnRfCyg Q

o UNITED STATES

[f

[ 'y)[.f.,

~'

NUCLEAR REGULATORY COMMISSION c

REGION V rn ir.

199u N. CAllFORNIA BOULEVARD o,'.ftp q

b SulTE 202, WALNUT CREEK PLAZA

%/

o 4,,,,

WALNUT CR EE K. CALIF ORNI A 94596 October 19, 1979 Docket 110. 50-344 Portland General Electric Company 121 S. W. Salmon Street Portland, Oregon 97204 Attention: Mr. Charles Goodwin, Jr.

Assistant Vice President Gentlemen:

Enclosed is IE Circular No. 79-21, " Prevention of Unplanned Releases of Radioactivity," which provides infonaation on inadvertent releases and on-site spills of radioactivity. Should you have any questions related to the enclosed suggested preventive measures, please contact this office.

Sincerely,

. +N

~

R. H. Engelken Director

Enclosures:

1.

IE Circular flo. 79-21 2.

IE Circulars Issued in the Last Six Months cc w/ enclosures:

C. P. Yundt, PGE F. C. Gaidos, PGE 1270 744 7911050 2J

Accession No.:

7908220128 SSINS:

6830 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 October 19, 1979 IE Circular No. 79-21 PREVENTION OF UNPLANNED RELEASES OF RADI0 ACTIVITY Numerous incidents of unplanned releases of radioactivity have been reported to the NRC within the past few months. These incidents of leaks, overflows and spills have resulted in contamination of areas outside of plant buildings.

The attached table provides you with summary information on these events, their apparent causes, the radiological consequences and the corrective actions.

We believe that a number of these incidents could have been avoided and preven-tive actions for these types of unplanned releases should be instituted by all reactor licensees.

Based on the reported incidents, the following preventive measures can minimize the occurrence of such events.

1.

Review of procedures for transfer of radioactive liquids.

Errors in written procedures have led to mistakes in valve line-ups and tank overflows. Written procedures, including check lists for valve line-ups, should be developed and followed for operations which could cause spills of radioactivity. Management controls, including audits, should be employed to assure verbatim compliance with such procedures.

2.

Review of "as built" systems having the potential of inadvertent releases because of design or construction errors. Consider items such as:

a.

Tank overflows should be routed to liquid radwaste tanks.

b.

Storm drains should be located away from areas with a high potential for spills.

c.

Consideration should be given to drip pans under equipment, such as pumps and valves, from which leakage is expected.

d.

Cofferdams should be installed under doors to areas with a potential for radioactive spills, e.

Preoperational testing should verify that crossconnects do not exist that would permit radioactivity to flow from operating unit (s) to unit (s) unde? construction.

3.

Periodically functionally test and perform inspections to verify integrity of systems that could cause an inadvertent release.

Excessive wear and corrosion du;radation have occurred in valves, seals and piping systems to cause leaks. New permanent and temporary piping systerrs should be 1270 '45

IE Circular flo. 79-21 October 19, 1979 Page 2 of 2 hydrostatically tested prior to first use. Underground piping should be periodically hydrosta.'ically tested.

Preventive maintenance programs should c

be implemented and identified problems, such as leaking equipment and plugged floor drains, should be promptly repaired.

No written response to this Circular is recuired.

If you require additional information regarding this subject, contact the Director of the appropriate flRC Regional Office

Enclosure:

Recent Events of Radicactive Centamination 12/0 ":46

RECENT EVD!TS OF RADI0 ACTIVE CONTAMIllhTION OUTSIDE BUILDINGS Plant Date Apparent cause Radiological Consequence Licensee followup Action Turkey Point 3/4 G/11/79 Operator Error 900 gallons of water processed Total of 0.01 mci of Co-58 Procedure reviewed by radwaste system overflowed Co-60 released to storn with operator, from vaste processing tank because drain of error in valve line-up. The Aux.

Bldg. floor drain backed up to the on-site storm drain.

The drain system discharged to an on-site underground tile bed.

Palisades 6/9/79 Inadequate Procedures

-5 Contaminated secondary system Resins activity at 10 The nonitoring procedure spent powdered resins were trans-pCi/cc; total release to determine the routing ferred to an outside storage bin about 10 pCi of Co-60 of the secondary spent without. monitoring.

Rain storm resins has been replaced caused resins to overflow the by a procedure requiring storage bin and be washed to Lake all spent secondary systtm Michigan via storm drain, resins to be handled and shipped as solid waste.

Surry 2 5/21/79 Equipment Failure.

Core spray pump isolation 5 gallons spiTled; 2 gallons Leak' repaired.Three 55-g valve leaked during RWST outside of b1dg.

gallon drums of con-transfer to Spent Fuel Pit.

0.02 pCi/cc, Co-58 taminated dirt removed cp Water leaked to Safeguards 0.035 pCi/cc, Il-3.

Bldg. floor.

Floor drain iJ plugged; resulted in water 1

Q flow out of building.

Enclosure IE Circular flo. 79-21 Page 1 of 3

Plant Date Apparent Cause Radiological Consequence Licensee Follow-up Action Ocence 3 5/15/79 Operational Error.

5/17/79 7

Normally closed valve left 2000 gallons overflowed; Procedure reviewed with open during pumping of fuel 200-300 gallens out of operating personnel.

Areas transfer canal water to GWST.

building 4 outside of Aux. Bldg. decon-Water overflowed the BWST to 3.1 x 10 pCi/cc, I-131.

taminated.

Aux. Bldg. penetration room, dowa a stairway to area outside Aux. Bldg.

Farley 1/2 5/14/79 Design Error.

Decontamination drains 1860 gallons of contar.-

Review all drains from from Unit I routed to Uqit inated water discharged Unit I and Unit 2.

Six such 2 sump and released to to pond.

Estf=ated max-drains were located and flush pond via tendon imun activity of 10 raci

plugged, access area.

Those drains Co-58.

Pond mud activity should have been routed

< 500 pCi/Kg. No pond to Unit 1 floor drain water activity detected.

system.

Oyster Creek 4/17/79 Equipment Failure.

Leakage from a Drywell Water in pipe tunnel DEDT line repaired.

Equipment Drain Tank (DEDT) 0 0.3 pCi/cc and soil Structure to enclose pipe line.

in vicinity of penetra-from Rx. Bldg. to main tion to the reactor pipe tunnel to be con-building were found to structed.

be contaminated.

N N

cz)

Enclosure IE Circular No. 79-21 J

Page 2 of 3 n

CO

Plant Date Apparent Cause Radiological Consequence Licensee Follow-up Action Brunswick 1 5/8-3/79 Operator Error and Equipment Failure.

Air mixing vc!ve o'f RWCU Total release of 12 mci Tank transfer procedure backwash tank left open of corrosion product.

reviewed.

Caution tag af ter liquid transfer.

on valve installed.

Dried tank residue released Loose access cover re-to building ventilation paired.

system via loose access cover.

Hatch 1/2 3/20/79 Construction Error.

Buried temporary line for Highest on-sitc gr und Temporary line broken 5

N, tank in yard for feed-water of 3 x 10 pCi/1 -

inside turbine building water heaters was not capped H Highest qtr. avg. off-and capped.

sYteoutfal.1ofsubsugface after tank removal.

Rx steam released into ground from drainage was 1.8 x 10 buried line, pCi/1.

North Anna e/25/79 Construction Error Relief valve on the volume Airborne radicactivity Still under investigation control tank lifted thus trans-levelt in the Auxiliary ferring reactor coolant to the Building reached 150 X high level waste drain tank and HPCs.

Auxiliary Beiiding releasing dissolved noble gases was evacuated.

to the auxiliary building via the waste system vent.

An incorrectly connected vont line allowed venting directly to the auxiliary building.

N N

t ca Enclosure IE Circular No. 79-21 J

Page 3 of 3 s

G i

IE Circular No. 79-21 Enclosure Octob'er 19,1979 Page 1 of 2 LISTING OF IE CIRCULARS ISSUED IN LAST SIX MONTHS Circular Subject Date of Issued to No.

Issue 79-07 Unexpected Speed Increase 5/2/79 All Holders of of Reactor Recirculation BWR OL's or CP's MG Set Resulted in Reactor Power Increase 79-08 Attempted Extortion - Low 5/18/79 All Fuel Facilities Enriched Uranium Licensed by NRC 79-09 Occurrences of Split or 6/22/79 All Materials Punctured Regulator Diaphragms Priority I, Fuel In Certain Self Contained Cycle and Operating Breathing Apparatus Reactor Licensees 79-10 Pipefittings Manufactured 6/26/79 All Power Reactor from Unacceptable Material Licensees with a CP and/or OL 79-11 Design / Construction 6/27/79 All Applicants Interface Problem for, and Holders of Power Reactor cps 79-12 Potential Diesel Generator 6/28/79 All Power Reactors Turbocharger Problem Operating Facilities and all Utilities having a CP 79-13 Replacement of Diesel 7/10/79 All Power Reactor Fire Pump Starting Operating Facilities Contactors and all Utilities having a CP 79-14 Unauthorized Procurement and 7/13/79 All Medical Licensees Distribution of XE-133 except Teletheraphy Medical Licensees and to all Radiopharmaceu-tical Suppliers 79-15 Bursting of High Pressure Hose 8/8/79 All Materials Priority I, and Malfunction of Relief Fuel Cycle and Operating Valve "0" Ring in Certain Self-Power Reactor Licensees Contained Breathing Apparatus 1270

?50

IE Circular No. 79-21 Enclosure October 19, 1979 Page 2 of 2 LISTING 0F IE CIRCULARS ISSUED IN LAST SIX MONTHS Circular Subject Date of Issued to No.

Issued 79-16 Excessive Radiation Exposures 8/16/79 All Radiography To Members Of The General Public Licensees And A Radiographer 79-17 Contact Problem in SB-12 8/14/79 All Power Reactor Switches on General Electric Licensees with a CP Company Metalclad Circuit and/or OL Breakers 79-18 Proper Installation of 9/10/79 All Holders of a Target Rock Safety-Relief Power Reactor OL Valves or CP 79-19 Loose Locking Devices on 9'/13/79 All Power Reactor Ingersoll-Rand Pumps Operating facilities and all utilities having a CP 79-20 Failure Of GTE Sylvania Relay 9/24/79 All utilities having a Type PM Bulletin 7305, Catalog CP SU12-11-AC With A 120V AC Coil 1270 251

.