APPENDIX A NOTICE OF VIOLATION Duke Power Company License No. DPR-38 Oconee Unit 1 Based on the NRC insptction June 27-29, 1979, certain of your activities were apparently not conducted in full compliance with NRC requirements as indicated below. These items have been categorized as described in correspondence to you dated December 31, 1974.

As required by Technical Specification 4.18 all hydraulic snubbers listed in Table 4.18-1 shall be inspected, and this inspection shall include as a minimum hydraulic fluid reservoir fluid connections, and linkage connections to the piping and anchor to verify suppressor operability.

Contrary to the above, two snubbers in the reactor coolant system (RCS-50) were found by an inspector to be rotated such that fluid ports in reserviors were uncovered and one locknut on the cylinder extension tie rod end was loose. This finding occurred af ter these snubbers were identified in inspection procedure MP/1/A/3000/12 as being properly oriented with all nuts tight. These snubbers are considered to be inoperable.

This is an infraction.

- ( E.

2kb c

7 909190 3 f O