t Procedure No.
Jersey Central 507.2 Page 1 or 4
ate issued EHective Date Power & Light Company 8/20/76 6/18/79-6/2s/79 Revision No.
Date 3
6/13/79 Suoject:
Tnrhim m41r14rg mg q Water Systan Failuro Authorized By Stai-4m Sumerinterrismt Approv Concu,ys Oyster Creek Generatire Statica v
LIST OE' t.ern;nVE PAGES DA'IE REVISION NUMBER 1
6/13/79....-.
3 2
5/10/79 2
3 6/13/79 3
4 6/13/i9 3
- Ihis s. Wiir u rrelam Section 507.2 of the old 507 r
- -iin per 507 Rev. 2.
(
- m. -
11 v..
"I
_.ji' },
- 4,'_
? l.3,;- ? - ;- s = - c
~.
em 7.
CONTRollyg
~~
OWMENT'senig,_ yWlON.. _ l s,;,'w
~
- -r.
I e
i'.B z,,
-h-
.4932040 3.N,
~
_f..
i
. ' is. p :.
- g. 7 2,5 M..
..v..,
. f,,'
OP 1_*I.
. < j
Subject:
Procedure No.
Turbine Dnilrling Closed Cooling 507.2 Page 2 of 4 Pages f
Water System Failure Revision No.
Date 2
5/10/79
1.0 Purpose
To provide a procedure for opezator action should the Turbine Btilding Closed Cboling Water Systs (TBCCWS) fail due to pump failure or pipe break.
2.0 Indications to the Operator:
2.1 Failure of 7ECCWS may be indicated by one or nore of the following ala-r Indications:
2.1.1 Panel 7F - Annunciator "Q".
2.1.1.1 GBCC Water Pump 1-1 Trip 2.1.1.2 180C Water Pump 1-2 Trip 2.1.1.3 2BCC Water Pump 1-3 Trip 2.1.1.4 TBCC Water Disch. Im Press.
2.1.1.5 TBOC Water Pump Auto Start C
2.2 Other abrms a-f ated with equipuent cooled by 1BCCW may be receivr1.
3.0 Autcuatic Actions:
3.1.The standby TBCCW purp will start upcn a Im discharge har%r pressure.
4.0 Irrmvlinte Ooerator 7cticn:
' ~
4.1 If cne TBCCW purrp fatis, verify that the starr!by 1BTW purrp starts.
4.2 If tm TJCCN purrps fail, at.br to mamally restart tse pumps.
~
4.2.1 If only one TBCCW purrp is available and TBOCN -- W ature is rising, reduce the reacter recirculation fim to minimum using the recircu-lation fim master controller.
Note: (1) If'a rMvwl TBZW flow is awrf anced through the stator cooling heat exchangers, the tine differential betwen the reduced ficw and I
receipt of the stator cooling high beature alarm is dependent cn generator 1rvv1 and 'mrTW heat exchanger capacity.
~
~
44.72 M
~
i..
..'.g,
~'
0921'.
Subject:
Procedure No.
Turbine Biilding Close:1 Ccolirq 507.2 Page, of Pages Water Systen Failure Revision No.
Date 3
6/13/79 (2) If stator cooling high te;.-ture is alarmed, the generator runback feature will ram generator load to about 20% of rated autmatically within 3 minutes and the bypass valves will open autmatically.
(3) Nhen turbine load is rdM to a point below the Icw load trip, reset the 25% load trip (green button) ha_ hind Panel 13R.
4.2.2 Dispatch an operator to itdjust the TK:CN supply to the etrhim lube oil coolers to reduce the turbine hanring oil *Prature.
4.2.3 If the H'rhim Wring high te hature alam is initiated, chedt the turbine haaring thm
> -ple recorder on Panel llR. If errhine bearing tercerature is > 185'F, raAm htrhine load manually to decrease bearing tu.gatures.
f 4.3 If all TBOCN pu=ps fail or a major pipe break occurs and no TBOCW pumps can be restarted and the break cannot be isolated:
4.3.1 Trip the etrhine. Manual'.y scram the reacten: if less than 45%
s.
Hirhim load.
~
,'p' p
.. -.. 7,.
4-4.3.2 Trip all recirculation pumps. Insure the suction and dieharge valves remain open until the ptrap start rw2are is impisnented.
4.3.3 Initiate transfer of air -gessor cooling to the Fire Water Systs. Isolate the 'lBCCW supply and return to the air meessors.
1 TT -t Prrvw'ivre 503 if a loss of air should occur.
4.3.4 Ftnitcr feedwater pump and condensate operation since pumps are utili ing TBCcf for cooling..
4.3.5 If feskater pumps h incperable at reactor pressure greater than 250 psig, isolate the reacter or 1 lace the isolaticn condmsers
' n service to maintain cooldcwn.
}
,k3-i t
~
,+
CP21 x,' -
r-
,7;
.i
~
.r
Subject:
Procedure No.
Page of Pam 507.2 4
Turbine nnilairs Closed Cooling Revision No.
Date Water System Failure g.
3 C/13/79 i
4.4 If a small 'IBCCW systan pipe break occurs such that the level in the TB00f surge tank can be maintained, locate and isolate the leak.
5.0 Subsmuent operator Acticn:
5.1 fenitor equipTent cooled by the TBcrW Systan for excessive tmperatures.
5.2 In the event only one TIC 07 purp is in service, adjust TBOCW flew to prevmt Pump rtrait.
5.3 If reactor scram was required, refe'r to energency g.
san e 532, "Autcmatic or Manual Reactor Scram", or g -are 514, " Reactor Isolaticn Scram" as afgu.vplate.
5.4 If nere than cne recirculatica pump is tripped, place the reactor in the cold shutdown conditicn within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
5.5 lbtify Supervisar - Staticn operaticns.
{'
h.0
References:
G.1 Reportable Occurrence 79--14.