Discusses Min Fire Brigade Shift Size.Approves five-member Fire Brigade.Forwards Generic Evaluation,Specific Comments & Guidance on Training Fire Brigade Personnel.Requests Application for Appropriate Tech Spec Change
ML19208A636
Person / Time
Site: Point Beach  
Issue date: 08/21/1979
From: Eisenhut D
Office of Nuclear Reactor Regulation
To: Burstein S
WISCONSIN ELECTRIC POWER CO.
References
NUDOCS 7909170121
Download: ML19208A636 (38)


Text

TnA

-p pR NEGg o

UNITED STATES g

y t s, g

NUCLEAR REGULATORY COMMISSION 33 -

.E WASHINGTON, D. C. 20555

\\.v,o#

August 21, 1979 Docket Nos. 50-266 and 50-301 Mr. Sol Burstein Executive Vice President Wisconsin Electric Power Company 231 West Michigan Street k

Milwaukee, Wisconsin 53201

Dear Mr. Burstein:

SUBJECT:

MINIMUM FIRE BRIGADE SHIFT SIZE By letter dated November 23, 1977, you were sent sample Technical Specifications and our position regarding the minimum size of the fire brigade for each operating shift at Point Beach Nuclear Plant. Our position was that a minimum of five members, fully trained for fire fighting, is necessary.

You responded by letter dated December 12, 1977, and proposed a smaller brigade of four members and pro-vided a justification therefor. After reviewing fire protection at your facilities and other operating facilities, we have concluded, based on the possible demands that may be placed on the brigade and the consequent actions that may be required of the brigade to fight fires, that five members constitute the minimum accept-able fire brigade size. Our generic evaluation is enclosed to this letter as and addresses the major points you raised to justify a smaller brigade size.

In addition, we have included comments specific to your position (Enclosure 2).

By letter dated June 5,1978, we sent you a document entitled, " Manpower Requirements for Operating Reactors." That document provided the bases for allowing the sharing of duties to meet minimum staffing requirements for fire brigades at nuclear power plants. July 3, 1978, you responded by letter in which you concluded that your position remained the same, namely that a four member fire brigade was adequate.

In performing our evaluations of the use of personnel who are not. members of the operations staff, an issue was raised as to the amount of training to be given these personnel. We are, therefore, enclosing for your guidance our position on minimum fire brigade training (Enclosure 3) whica modifies, for up to two members of the brigade, the previous guidance given in " Nuclear Plant Fire Protection Functional Responsibilities, Administrative Controls and Quality Assurance," June 14, 1977.

Of the seventy plants presently licensed to operate,all but eighteen have a requirement on their Technical Specifications for a minimum fire brigade shift size of five persons.

Discussions held with licensees of those eighteen plants have resulted in a commitment by the licensee to propose sucn a Technical Specification except for six utilities who are the licensees for twelve plants.

Ob100,"{

7 0 0017 0(p

Because the staff believes that the fire brigade at each facility should consist of a minimum of five persons, we are preparing a proposed change to 10 CFR Part 50 which would incorporate this minimum fire brigade shift size into the Commission's regulations as a requirement for each operating licensee.

Until this is completed, we feel that it is prudent for you to have such a requirement in the Technical Specifications for your plants. We request that within 30 days of your receipt of this letter, you propose an amendment to Facility Operating License Nos. OPR-24/27 to change the minimum size of the fire brigade contained in the Technical Specifications for Point Beach Unit Nos. 1 and 2 to five members. We intend to make this Technical Specification effective within 90 days of the issuance of the amendment.

incerely, i

ar

.Esnu, ct g Director Division of Operating Reactors

Enclosures:

1.

NRC Evaluation of Minimum Fire Brigade Shift Size 2.

Evaluation of Fire Protection SER Open Item 3.

NRC Staff Position - Minimum Fire Brigade Training cc: w/ enclosure See next page 351300

ENCLOSURE 1

EVALUATION OF MINIMUM FIRE BRIGADE SHIFT SIZE JUNE 8, 1979 bd.l.UCf5

EVALUATION OF MINIMUM FIRE BRIGADE SH FT SIZE Table of Contents I.

Introduction II.

Background

III.

Discussion A. Defense-in-Depth Principle B. Fire Brigade Performance Objective C. Fire Brigade Actions D. Typical Response to a Postulated Fire in a Nuclear Plant IV.

Conclusion Appendix A - Staff Response to Licensee's Arguments

1. Historical Fires
2. Offsite Personnel
3. Availability of Onsite Personnel 331306

EVALUATION OF MINIMUM FIRE BRIGADE SHIFT SIZE I.

INTRODUCTION Criterion 3 of the General Design Criteria (GDC) for Nuclear Power Plants (Appendix A to 10 CFR 50) reads as follows:

" Fire protection.

Structures, systems and components important to safety shall be designed and located to minimize, consistent with other safety requirements, the probability and effect of fires and explosions.

Noncombustible and heat resistant materials shall be used wherever practical throughout the unit, particularly in locations such as the containment and control room.

Fire detection and fighting systems of appropriate capacity and capability shall be provided and designed to minimize the adverse effects of fires on structures, systems and components important to safety.

Fire fighting systems shall be designed to assure that their rupture or inadvertent operation does not significantly impair the safety capability of these structures, systems, and components."

The above mentioned fire fighting systems consist of both automatic and manual systems. The minimum fire brigade shift is an essential part of the manual fire fighting system (i.e., detectors, portable extinguishers, hose stations and fire brigade) which must function to

" minimize the adverse effects of fires on structures, systems and components important to safety."

This evaluation summarizes the staff's and its consultant's evaluation of the factors that establish the minimum fire brigade shift size.

We have concluded that all operating plant sites should have an onsite fire brigade shif t of at least five members appropriately trained for fire fighting.

The fire brigade shift should be capable of perfonning a spectrum of actions that may be necessary to cope with a variety of fire situations.

One member should be assigned as fire brigade leader to assess the situation and direct fire fighting activities.

Four members should be available to transport equipment to the fire, operate suppression equipment, or perform rescue work as required by the specific fire.

II. BACKGROUND The need for and the role of the fire brigade as part of the fire protection program for operating plants has been under evaluation by the staff since the Brown's Ferry Fire in March 1975.

Following its study of the Brown's Ferry Fire, the Nuclear Regulatory Comission's Special Review Group Report, dated February 1976, stated the need for an adequate fire brigade:

'jf}0/0 "In addition to adequate equipment design, successfu' fire fighting requires testing and maintenance of the equipment and training and practice as teams under realistic conditions for the onsite and offsite personnel who must fight the fire. Onsite and offsite equipment should be compatible. Emergency plans should recognize the need for fire fighting concurrent with other activities.

They should provide for division of available personnel into preassigned, trained teams responsible for the various activities needed with proper utilization of offsite fire-fighters." (NUREG-0050 p.6).

"While the Review Group believes that such basic training is a necessary element in effective preparation for fire fighting, such training alone does not assure smooth operaticn of fire fighting personnel during a fire.

Emergency plans should recognize the need for fire fighting concurrent with other activities. There must be a clear understanding of the dut.es of the onsite personnel, with preassigned and trained teams for each needed function. The degree of dependency upon trained onsite fire fighting personnel must be related to the availability of support personnel from professional fire fighting units (city or county fire departments, military fire control units, etc.) or trained personnel in the licensee's organization who are available for such emergency service.

In general, the onsite personnel should have sufficient training and practice to handle all small fires, and to contain larger fires until the offsite units arrive. When it is deemed prudent to call in the offsite units, their capabilities should be used to the greatest extent possible.

Periodic drills, involving all onsite and offsite organizations which may be expected to respond to a fire, should be held to enable the groups to train as a team, permit the offsite personnel to become failar with the plant layout, and to permit evaluation of the effectiveness of communication among all those involved.

These drills should include operations personnel, those specifically assigned to fire fighting, any offsite emergency control centers involved in the plan, and all those other organizations that would normally respond to such emergencies."

(NUREG-0050 p.27).

At Brown's Ferry Nuclear Station, a five man site fire Brigade was established to fight fires in any of the three units on this site.

To assure the presence of this fire brigade at all times, a requirement for such a fire brigade organization was incorporated into the Fire Protection Program for these units.

Subsequent.ly, in furtherance of the objective of GDC.3 the NRC reflected this need at all plants for an adequate fire brigade in all guidelines issued on fire protection (i.e., Branch Technical Position (BTP) 9.5-1, Appendix A to BTP 9.5-1 and Regulatory Guide (R.G.

1.120.)

These NRC guidelines gave criteria for determining the size of the fire brigade:

<3'd M U O "The plant should be self-sufficient with re;pect to fire fighting activities and rely on public response only for supplemental or backup capability" (Appendix A p.7).

" Guidance is contained in the following publications :... National Fire Protection Association (NFPA) 27 - Private Fire Brigades" (Appendix A p.4).

Regarding the size of the fire brigade, NFPA 27 states:

"The eqaipment that must be put into service at a fire will determine the number of men required for each operating unit or company into which the brigade is organized and the total number needed in the brigade.

Each company should have a leader and each brigade should have a chief." (NFPA p.27-3, Vol.12) (Note that the site fire brigade on each shift corresponds to the company of NFPA 27; the organization of all shif t fire brigades corresponds to the brigade of NFPA 27.)

In November 1977, the NRC issued additional guidance indicating that the fire brigade size should be detennined by the functions the fire brigade must perform after consid ration of several factors:

(1) plant geometry and size; (2) quant'ty M quality of detection and suppression systems; (3) fire fig'iting strategies for postulated fires; (4) fire brigade traininr, (5) fire t,-igade equipment; and (6) fire brigade supplements b; plant personnel ;nu bal fire depart-ments. At that time, the staff established an interim fir,. brigade size of five oersons until a site specific n! view could be completed.

In November 1977, the NRC ent licensees of operating facilities proposed interim Techn'.al R.racifications for fire protection which included the requirement for a five man fire brigade.

The NRC position on Minimum Fire Brigade Shift Size was included with the Safety Evaluation supporting this requiremnt.

The licensees' response on the requirement for a five nan fire brigade was divided.

Of 70 operating facilities, 51 accepted a five man brigade and 19 presented arguments for a smaller fire brigade shift size.

To effect expeditious implementation of interim Technical Specifications requirements for fire protection, license amendments were issued which added Fire Protection Technical Specificatior:s requiring the minimum fire brigade shif t size as proposed by the licensees.

Where the licensee proposed a fire brigade of fewer than five persons, the amendments contained the condition that the staff's evaluation of the licensee's basis for the smaller fire brigade size would be included in the site specific review of the licensee's fire protection program.

In April 1978, the NRC issued additional guidance regarding the sharing of personnel required onsite for the purpose of plant operation, industrial security and fire fighting.

These guidelines recognized that:

(1) the plant requires a minimum number of personnel to be on the site to cope with either an operating, security or fire emergency; (2) the probability of an event which requires entire minimum shift of each discipline during the first 30 minutes of the event is low; and (3) the shift supervisor should be able to use available site personnel

.9hi103 as the specific emergency demands.

Since October 22, 1976, the NRC fire protection review teams have visited all operating facilities.

At each site, the staff evaluated the factors identified in its November 1977 guidance.*

III.

DISCUSSION We found that variations in plant geometry and size were not a determining factor for minimum fire brigade shift size because at all of the plants we found combinations of hazards, conditions of access, and physical arrangement of safety mlated equipment that would require immediate actions by at least five persons.

In all but a few plants, the detection and suppression systems and fire brigade strategies, training, equipment, and supplementation by off-shift personnel are about equal because they met or comitted to meet staff guidelines.

In some cases, our site evaluation concluded that more than five persons were required for eacF shift; however, in these cases, prompt modifications were made by licensees to reduce the need for the additional manpower.

None of the plants had support from local fire departments which was adequate to reduce the size of the fire brigade below five persons. All of the plants had sufficient support from local fire departmant and off shif t personnel such that the minimum fire bt igade shift size need not be increased above five.

We also found that the major factors in determining the shif t size of the fire brigade were (1) the need for leadership of the brigade by a person who is relatively free of other duties, including actively fighting the fire; (2) the equipment to be obtained and used for fighting the fire; and (3) the actions to be performed by the fire brigade for a variety of fire situations.

A.

De fen se-In-Death.

The concept of " defense-in-depth" which has been utilized throughout the site specific evaluations contains three major areas of protection, i.e.,

prevention, detection and suppression.

First, administrative controls are required to limit the t,uantity of combus'tible and potential ignition sources.

Second, detection systems are required to inform the plant staff in the event of a fire. Third, suppression systems, automatic and manual, are required to extinguish the fire rapidly and successfully.

Functions pertaining to each of these areas requires a minimum level of performance to be accepted, e.g., the fire brigade must have a minimum acceptable size to be given credit for being able to perform its function under a broad spectrum of conditions.

The fire brigade is but one element of the" defense-in-depth" fire protec-tion program which contributes to the adequacy of the fire protection that assures that the public health and safety is not endangered due to potential consequences of fire at an operating facility. To consider this issue in perspective, it is necessary to remember that if a severe fire occurs, the plant conditions which lead to or result from the fire cannot be

  • Some of the licensees' arguments for a smaller shif t size are discussed in Appendix A.

33.1.310 precisely defined and that no single echelon of fire protection can be perfect or c.omplete in itself.

The demands on the manual fire fighting capability and resources will vary depending on their degree of involvement:

1. If the automatic detection and suppression system functions as designed, the combustibles involved in the fire are limited to those evaluated in the design, and all other conditions for the fire are the same as for the design evaluation, the fire will probably be controlled and possibly extinguished by the installed system. The fire brigade will be needed to enter the involved a.ea to conduct final " mop-up" actions and inspection to ensure the fire is completely extingished.
2. If the fire is of a larger magnitude than the design assumption of the automatic systems or the fire spreads beyond the coverage of the automatic system because of the deterioration of design conditions, the fire brigade will be required to assist in the extinguishment operation and possibly in the protection of adjacent safety related equipment which may be jeopardized by the fire.
3. If the automatic systems do not actuate, the fire brigade will be required to independently contain and extinguish the fire in the involved zone.

Similar action is required in all areas that de not have automatic suppression systems.

When detemining the minimum fire brigade size.each of the above three levels of performance must be considered and evaluated, with the third level bounding the brigade size since it places the largest burden on the team.

Further, the specific fire brigade actions that will be required will vary from area to area within the plant, and with the construction, maintenance or normal operation activities that may be ongoing at the time of the fire.

Because the specific fire brigade actions cannot be precisely defined,

'he fire brigade must be capable of a spectrum of actions that may be required.

The minimum fire brigade and the available manual equipment is the only fire suppression system in many areas of the plant.

Thus, the brigade and their equipment must satisfy the requirements of the General Design Criteria to minimize the adverse effects of fire on systems impor-tant to safety for these areas as well as provide its contribution to the defense-in-depth features in other areas which also have automatic suppression systems.

The fire brigade offers the flexibility to perform actions to mitigate the consequences of fires for the event that may exceed the limits of fixed fire protection systems and, with early warnino fire detection, to extinguish fires before automatic systems actuate.

Even though the fire brigade is only one aspect of the " defense-in-depth",

it requ'.res a minimum operating size to successfully fulfill its perfor-mance cojectives as defined in the following section of this document.

To reduce the size below the needed level will result in the loss of brigade flexibility and the potential that all performance objectives will not be achieved.

W5IUE.

B. Fire Brigade Performance Objectives The performance objectives of the fire brigade at a nuclear power plant are the same as those in any fire situation. There are three major performance objectives:

(1) rescue; (2) extinguish; and (3) confine, control and extinguish. Wnich of these objectives are to be perfonned depends upon the specific factors that are present at the fire; however, the orderof performance of these objectives never changes. Where there is no need for rescue, the first objective can be " extinguish".

In all cases, even the most extreme, the final objective always is to extinguish the fire:.

This is true even where it is first necessary to confine the fire, then bring it under control and finally extinguish it.

In extremely rare and unusual circumstances, a fire may be allowed to burn itself out as a last resort.

We have not endorsed this alternative as the design condition because of the potential deleterious effects on plant operation associated with the toxic and corrosive effects of the smoke and additional system failures that may occur.

To achieve any one, or all of the major objectives, the fire brigade must perform several functions.

Some of these are:

(a) Locate the fire and ascertain its potential; (b) localize the fire, alleviate smoke and heat conditions, improve visibility, and facilitate the advance of hose lines; (c) Extinguish the fire by application of a sufficient amount of the correct extinguishing medium; (d) Minimize damage by the judicious use of water or other extinguishing agent;

  • (e) Protect personnel, provide ventilation, self-contained breathing equipment and protective backup capability;
  • (f) Coordinate activities through adequate supervision and communication.

To ascertain the potential of each specific fire, and to determine the required ft actions, there are certain prima.y factors that must be evaluated ty the fire brigade leader at that time.

Some of these primary factors are:

life hazard for occupants and for personnel, location of fire, extent of fire on arrival, shutdown equipment and fixed suppression systems in the fire building, construction of fire building, construction of exposures, area of exposures, proxiraity of exposures, structural collapse of fire building, beat conditions, smoke conditions, visibility, exposure hazard, and class of fire.

  • These are objectives from the beginning to the end of every fire suppression operation.

dO12 Some of these factors interact and the combination of effects of such factors also require the consideration of the fire brigade leader.

C.

Fire Brigade Actions The actions required of the fire brigade to achieve the performance objectives depend largely on the complexity of the fire; however, the shift fire brigade should be capabh of performing a spectrum of actions for any fire.

If a fire alarm sounds for any area of the plant the following actions should be taken by the fire brigade:

(a) The fire brigade leader and all brigede members should immediately respond to the fire area.

(b) The brigade leader should respond directly to the fire area, with an extinguisher that he obtains on the way, and with adequate equipment for communications and a portable handlight.

(c) The other brigade members should respond to the fire area with a personal self-contained breathing apparatus and a portable extinguisher.

If on arrival at the fire area, an incipient fire is in progress, the following actions should be taken by the fire brigade:

(a) An immediate attack should be made on the fire in an attempt to extinguish.

(b) Additional extinguishers should be obtained from the immediate area.

(c) A hose line should be stretched to the fire area as a precaution.

(d) Additional self-contained breathing apparatus and spare cylinders should be obtained immediately to be ready for use if necessary.

If the fire is not extinguished in its incipient stage, the following actions may be required:

(a) Place the necessary calls for off-site assistance.

(b)

If ladders are required to reach the fire, fire ladders should be obtained.

(c)

If the fire involves electrical equipment, the equipment should be de-energized. This action requires coordination with operating personnel to assure it will not affect the continued safe operation of the plant.

351313 (d)

If smoke conditions are such that visibility is impaired, ventilation may be required either in tha form of activation of fixed systems or by the use of portable smoke ejectors.

(e)

If it becomes necessary to use water fog, precautions should be taken to prevent water damage to electrical equipment not involved in the fire.

This may recuire the use of protective water shielding.

(f)

If it becomes necessary to use water fog, a second nose line, from a standpipe or exterior hose station should be prepared to serve as a back up to the initial hose line.

(g)

If the fire area is one that contains a special hazard such as a flammable or combustible liquids, some of the brigade members should obtain and prepare the special equipment necessary for that type of operation, i.e., foam in 5 gallon cans, pick up tube, foam applicator and hose lines.

(h)

If the fire is in a confined space and its exact location cannot readily be determined, the fire brigade leader may commit all his personnel to the attempt to locate the fire, but should do so only after all other required preparatory actions have been carried out.

(i)

If any of the brioade members, who are actively extinguishing the fire or attempting to locate the fire, become trapped or incapacitated in anyway, other brigade members would be required to rescue.

If the injury were such that the injured party were overcome by smoke or severely injured, at least one of the other members would be required to attend the injured to attempt to safe his life.

(j)

If the fire has not been extinguished when offsite assistance arrives at the fire location, the offsite people should be divided into teams to assist the fire fighting operation with each team having a member of the plant brigade assigned as leader.

For any given area or fire, the initial actions of the brigade require sufficient personnel to extinguish the incipient fire and to prepare for the fire that may occur if the incipient fire is not extinguished.

Therefore, the brigade should be adequately staffed so that the above actions can be performed if required by a particular fire.

Table 1 inoicates how these required actions would be carried out by a five member fire brigade. Not all actions assigned to each member will necessarily be carried out for every fire; however, for the spectrum of fires that may reasonably be expected to occur, the brigade should be capable of performing the actions as shown. The five member fire brigade is the minimum complement that can provide sufficient personnel sc that these actions may be carried out.

C'2$31' D.

Typical Response to a Postulated Fire in a Nuclear Plant The following outline describes how a brigade would respond tu a postulated fire and carry out the actions discussed in the previous sections.

The outline illustrates the need for some actions simultaneously and some sequentially.

It also illustrates that the specific circumstances that determines the course of the fire will determine the specific actions required.

The actions being performed by the fire brigade leader and the fire brigade members are summarized in Table 1.

1.

The fire brigade leader and all brigade members should initiate their response to the announced fire area.

2.

The fire brigade leader should respond directly to the announced fire area with pt table connunication equipment. He evaluates the situation, and advises the control room and formulates an action plan.

3.

Each member cf the fire brigade including the fire brigade leader obtains a fire extinguisher from a location along the way and bring it to the fire area.

These should be brought from a remote location to assure that sufficient extinguishers will be available. Those in the immediate fire area may have been used by the discoverer af the fire.

4.

Ea, h member of the fire brigade should also bring a self-cor lined breathing apparatus for use by the brigade members.

5.

If conditions are such that self-contained breathing apparatus masks will have to be worn by the brigade members, no member should enter the fire area without a mask.

If necessary one or more, depending on the need, brigade members should be sent to obtain additional self-contained breathing apparatus in sufficient number so that each brigade member and the fire brigade leader will have a unit.

At least one man should be sent to obtain spare air cylinders, at least one per self-contained breathing apparatus being used.

(NOTE:

Recent tests at Syracuse Fire Dept. Training Academy showed that the 1/2 hour rated mask, pressure demand type, was breathed down in as little as 7 to 15 minutes during fire fighting activities).

6.

If the brigade members will pass by the personnel protective clothing storage area, they should obtain their fire fighting gear and bring it to the fire scene.

If such clothing is needed but is not brought to the scene, at least one man should be sent to obtain such clothino.

Ob$.Olb

- lU -

7.

If the source of the fire or smoke can be readily determined, the brigade leader should order the following simultaneous actions:

(a) At least two (2) man to begin a direct attack on the fire with suitable extinguishers and, (b) the remaining two (2) men to prepare to assist with additional extinguishers and/or to stretch at least one 1-1/2" tandpipe hose line to be used as a back up to the extinguishe. r.

If the fire is readily extinguished by the initial extinguisher application, the brigade leader should make a careful examina-tion of the fire area to insure that the fire has been completely extinguished and to try to determine the point of origin and the cause of the fire. He would be assisted by at least one brigade member. Consiceration should be given for the ne.ed "or a fire watch in the area for a period of up to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

The remaining brigade members would be directed to return the fire fighting equipment brought to the fire location to its proper storage area ensuring that it is in proper working order and in readiness for another fire.

A critique of the fire fiahting operation should be held immediately after the fire to evaluate the pre-fire strategies for the fire area and to determine the efficiency of the fire brigade and the effectiveness of the operation.

8.

If the smoke conditions are such that the '.ocation of the source of the fire and smoke cannot readily be determined, the brigade leader should order the following simultaneous actions:

(a)

The control room to notify the off-site fire department and plant on-call personnel.

(b)

Two brigade members and the leader to put on self-contained breathing apparatus, take suitable extinguishers and enter the fire area to attempt to locate the fire.

(c) The remaining brigade members to put on self-contained breathing apparatus and stretch a 1-1/2" hose line from the closest standpipe location and assure that the hose has sufficient length to effectively reach the fire area.

(d)

Af ter the hose line is stretched and ready to be operated, at least one roember should remain with the line while the other(s) go to obtain additional equipment usch as smoke ejectors, ladders if necessary, spare air cylinders, protective covers for water sensitive equipment, and any other items that would be of need in the fire and damage control effort.

(e)

If while the above activity is going on-the fire source is located by the leader and the two brigade members, they would innediately attempt to extinguish the fire with their extinguishers.

(If successful, the steps subsequent to extinguish-ment outlined in 7 above would be followed).

3S$U$$

9.

If the fire is not readily extinguished by the use of extinguishers, the following actions should be undertaken by the fire brigade as ordered by the fire brigade leader.

(a)

The 1-1/2" hose line that has been stretched as a pre-cauthionary measure should be advanced into the fire area by at least two brigade members and; (b) The remaining brigade members should simultaneously stretch an additional 1-1/2" hose line from the closest available standpipe location to the area imediately outside or adjacent to the fire area and be prepared to use this line to provide protective spray and/or as a backup attack line if the fire severity demands.

(NOTE:

It is likely that the second 1-1/2" hose line will have to have additional hose added to reach the fire area).

(c)

Once the second line is readied for use and if its imediate use is not required, the fire brigade leader may direct one or more of the back up men to take steps to pro-vide protection for electrical equipment or to set up portable ventilation equipment to evacuate smoke and heat, or to obtain additional special equipment that may be required if the fire is not controlled and extinguished in a short time.

(d)

If the brigade leader and the men attacking the fire with the 1-1/2" hose line are successful in extinguishing the fire, the steps subsequent to extinguishment contained in 7 arave should be followed.

10.

If the fire is not extinguished by the r attack with 1-1/2" hose lines, the area may become untenable as a result of either heat or smoke or both.

In this situation the fire brigade leader should ceder the following actions by the fire brigade.

(a) All personnel should back out of the fire area and take positions where they can either keep the fire contained by the use of the hose lines from the perimeter openings or (b)

The area should be sealed off, if possible, by closing the fire doors and the hose lines should be used by brigade members to attempt to keep the fire from passing through any penetrations or ducts or fire doors or the exterior walls by spraying water on the potentially dangerous areas to keep it cooled down.

(c)

If the situation develops to this extent in a relatively short time period (less than 15-20 minutes) it may be necessary for the brigade leader to direct that one individual hold the 1-1/2" hose line from a suitable braced position while the other members are sent for additional back up hose lines, additional air supply, and to check surrounding areas and floors above the fire for possible extension of the fire.

% ))5 0

. (d) The fire fighting objective would now become a matter of confine, control and extinguish (or allow to burn out). When this occurs there will be a very serious problem of smoke and heat removal which will require the efforts of all available personnel as they arrive from off-site.

(e)

Decisions will have to be made regarding the direction the smoke and heat is to be routed with serious consideration given to the possible damage the smoke and/or heat might cause to equipment that is relatively remote from the fire.

IV. CONCLUSION On the basis of its onsite evaluations of the fire protection program for 70 operating facilities, the NRC staff has found that:

1.

The specific actions for the control and extinguishment of potential fires vary greatly from area to area Pithin a given plant; 2.

The specific actions which the fire brigade may be required cannot be precisely defined prior to the fire; 3.

Although the fire fighting actions as described previously in this report may not be applicable to each and every plant area, all plants contain areas important to plant safety which require consideration of these fire fighting actions.

4.

Abnormal events cannot be precluded for each and every potential fire situation, some margin in brigade size is warranted to compensate for the potential unanticipated events such as.

a.

Failure of detection systems to promptly alert plant personnel of the onset of a fire condition.

b.

Failure of automatic suppression systems to actuate to limit fi re damage.

c.

Personnel injury in the act of fire fighting.

d.

Failure of admiristrative controls of combustible materials in situations wh,ich could impact systems important to safety.

5.

The minimum fire brigade shift size cannot be based only upon the potential fire consequences and their apparent impact on the capability to safely shutdown because this is contradictory to both the philosophy of defense-in-depth and the general design criterion requirement to minimize the adverse effects of fires.

Based on the above, we conclude that:

1.

All operating plant sites should have an onsite fire briagde shift complement of at least five trained persons.

Ob.'s b.$O 2.

One member should be assigned as fire brigade leader and at the time of the fire, he should be free of all duties so that he can devote his attention to assessment of the fire situation and direction of fire fighting activities.

3.

Four members should be capable of acting individually or as teams to perform the spectrum of basic fire fighting action which may be required e.g., locating the fire, operation of portable extinguisher or hose lines, transporting equipment to the fire scene, or rescue work.

Oa1319

TABLE 1 MANPOWER REQUIRED FOR FIRE FIGHTING ACTIONS FIRST & SECOND BRIGADE THIRD & FOURTH BRIGADE LEADER MEHliERS MEMBERS A.

ACTIONS REQUIRED FOR FIRE NOT EXTINGUISHED BY PERSON (s) WHO DISCOVERED FIRE.

Respond to fire with portable Respond to fire with portable fire Respond to fire with portabl-fire extinguisher extinguishe rs.

fire extinguishers.

Respond to fire wi th sel f-Respond to fire with self-Respond to fire with self-contained breating apparatus.

contained breathing apparatus.

contained breathing apparatt.

Locate fire or source of smoke Locate fire or source of smoke.

Locate fire or source of smoe.

Evaluate the fire situation and Operate fire extinguishers on the Operate fire extinguishers o. the the area involved to determine the fire (if fire location is deter-fire (if fire location is desr-effective actions to be taken and mined).

mined).

maintain communication with control room.

(Required for all Stretch at least one 1-1/2' fires.

hose line to be used as backsp to extinguishers.

Dire'.t fire fighting activities by.he fire brigade members.

(O Cil ON C)

TABLE I (cont.)

B.

ADDITIONAL ACTIONS REQUIRED FOR FIRE NOT EXTINGUISHED WITH PORTABLE EXTINGUISHERS At the scene of the fire, continuously Extend and prepare Obtain fire fighting protective evaluate the fire condition as it to operate a 1-1/2" hose line or a clothing for fire brigade develops.

Direct the activities of single 2-1/2" hose line from an members.

(If not brought on the other members and observe the fire exterior hose house.

Ist response).

fighting operation and judge its ef fectiveness and safety.

Consider Attempt fire extinguishment as a Obtain special equipmer.tfor fire alternative actions that may be two person team using one fire hose.

fighting operations - ladder, required as a result of changing foam, ventilation, breathing air.

conditions. Consider the consequences of actions being taken in regard to Take steps to cover electrical their impact on the overall safe slsutdown equipment to prevent water damage.

capability of the plant.

When necessary, extend and The fire team leader should not be-prepare to operate a 1-1/2" hose come involved in the actual fire line or a single 2-1/2" hose fightinj process to the extent that line from an exterior hose house.

he is unable to carry out the responsibilities of continuous Perform relief and rescue duties evaluation and decision making.

as required.

Communicate with control room regarding fire status, equipment that may become disabled, need for of f-si te assis tance, etc.

(O C/:

s :.

v.,

TABLE 1 (cont.)

C.

ADDITIONAL ACTIONS REQUIRED FOR FIRE THAT DEMANDS ASSISTANCE BY OFF-SITE PERSONNEL All actions required in B:

Be prepared to provide rescue of en-Be prepared to provide rescue of en-Be prepared to provide rescue dangered personnel or tire brigade dangered personnel or fire brigade of endangered personnel or fire nenbers if necessary.

nenbers i f necessary.

brigade members if necessary.

Provide off-site fire fighting with Serve as guide, coordinator and Serve as guide, coordinator and suf ficient information so they under-control person for off-site fire control person for off-site fire stand the situation as it exists on department.

department.

their arrival, the objective of the operation, ti.e actions being taken to Isolate and confine fire.

Isolate and confine fire.

achieve the objective, advice and supervision of their actions in use hoses to cool and protect Use hoses to cool and protect coordination with the fire brigade.

barriers.

barriers.

Survey barriers for possible Survey barriers for possible break through and extention of fire break through and extention of fire.

FOOTNOTES: Operations in fire areas should always be a team effort of at least two If these two members are not nenters for the purpose of improved operation and personal safety.

fully trained fire brigade members, they would be replaced by the off-shift personnel when taey arrive.

(O C,

p..

e.

I.')

APPENDIX A STAFF RESPONSE TO SELECTED LICENSEE'S ARGUMENTS 1.

Historical Fires Some licensees argue that the rajority of historical fires in nuclear power plants were either self-extinguished or were extinguished by a small response force.

Further, a large number of these fires occurred during the construction phase of the plants.

The NRC does not deem the size of historical fires a significant factor in determining the size of the minimum fire brigade. The small fires that self-extinguish or the fires that are easily extinguished present little, if any, threat to public health and safety.

Further, the circumstances that lead to fires in the construction phase are not precluded after the plant goes into operation.

New construction at the site, major plant modifications and maintenance activities produce similar circumstances at an operating plant.

It is the fires that do not.self-extinguish because of "off-design" conditions or are not promptly extinguished at operating plant sites which may present a threat to the plants capability to achieve and maintain safe shutdown conditions.

For example, a temporary breakdown in the administrative controls over the use of combustibles and ignition source, a failure to detect a fire early, or adverse unanticipated events which either delay prompt extinguishment or lead to rapid fire development may lead toward the development of a severe fire.

Because of the possibility of these fires, the staff deems it prudent to maintain a site fire brigade which can promptly extinguish such fires in safety related areas with sufficient margin in size to account for adverse conditions and events.

2.

Offsite Assistance Some licensees argue that the minimum fire brigade may be less than five persons because of substantial offsite assistance.

The NRC concludes that the delay in prompt fire extinguishment incurred by reliance upon support from offsite fire departments or the call back of plant personnel does not provide an acceptable alternative to meeting the minimum manpower requirements for an onsite fire brigade.

Offsite fire departments could be committed to fighting fire elsewhere when a call goes out for their assistance.

In many areas weather conditions could delay the response of offsite fire departments as well as operating personnel called back for additional assistance.

While the NRC recognizes the importance of a preplanned utilization of offsite fire departments and' call back personnel, such assistance does not justify a reduction of an adequate onsite fire brigade to provide an immediate initial attack on a fi re.

AU23

- 3.

Availability of Onsite Personnel Some licensees argue that the potential for fire is greater during times when there is more than the minimum complement of plant operating personnel on onsite.

In general, this is the period from about 8 to 5 on normal work days.

It is during these periods during which normal maintenance operations are performed.

While the NRC recognizes the greater potential for fire during such time, this does not alleviate the need for an adequate fire brigade on the other shif ts.

It ap%ars tha there are sufficient personnel on site on all shif ts to provide a five man fire brigade.

In its position paper on " Manpower Requirements for Operating Reactors" the NRC addressed the sharing of available onsite personnel such as the security forces as a means of meeting the manpower require-The issue is not the availability ments for a five man fire brigade.

of onsite personnel who could be utilized to combat fires; but rather the effective utilization of manpower resources to establish a trained team that responds to a fire and effectively performs those action which are essential to fire fighting.

3513.'@

y.

y ENCLOSURE 2 POINT SEACH NUCLEAR PLANT, UNITS 1 AND 2 f

EVALUATION OF FIRE PROTECTION SER OPEN ITEM 3.2.3 Fire Bricade Size 12, 1977 and July 3, 1978, the licensee pro-By letters dated Decemberposed to maintain a trained fire brigade of four provided his justification therefore.

(1)

The licensee's bases for a four man fire brigade are as follows:

during day shif t of the week days of normal operations fire brigade members; (2) the potential for fires is significantly reduced because during back, holiday, and weekend shifts, only activities associated with the direct operation of the plants ant conducted; (3) should a fire occur, assistance would be requested from the offsite volunteer fire department, and from the off ' duty fire brigade members; and (4) the licensee expects that the fire brigade to either extinguish the fire or to confine it to a single fire area for

'the 15 minutes required to bring the offsite assistance into action.

The staff and its consultants evaluated the licensee's bases and foun that the plant specific justifications were not sufficient to support the proposal for the following reasons:

Although the potential for fires may be reduced during back, holiday, and weekend shifts as a result of limited work activities, 1.

the potential for fire will not be eliminated.

The onsite fire brigade must have the capability to promptly 2.

extinguish fires, whenever they occur.

At the many fire zones which are not bounded by fire barriers, it is essenti.a1 that the fire brigade be capdle of extinguishing 3.

fire in such zones promptly because of the proximity of redundant safe shutdown systems.

29, 1978, the licensee provided a plant specific By letter dated December analysis to demenstrate that the proposed four man fire brigadeThe analysis d will be self sufficient in suppressing fires.

the plant's prefire strategies for the cable spreading roo feed pumo areas, and the turbine lube oil storage room to dencnstrate the capability of the four man fire brigade to accomplish all functions The functions necessary in the event of a fire in each of these areas.

described for each scea were:

transport support equipment to the scene of the fire.

assess fire conditions; comand, and direct the fire fighting 1.

2.

i activit es.

comunicate with the centrol room or remote shutdown panels.

3.

lay and maneuver fire hose.

locate fire and apply the extinguishment to the fire E.

.% IU.~.'.J

... 6.

set up and operate portable ventilation equipment.

7.

charge and replace respirator air bottles.

- /[

8.

direct and coordinate offsite fire department.

9.

set up and operate emergency lights.

10. set up and operate emergency communications equipment,
11. rescue injured personnel.
12. maintain fire fighting activities if supporting personnel are delayed.

The postulated fire scenarios included the obscure fire that requires a significant time to locate, and the well-developed fire that will require a sustained effort to extinguish; fires in areas where the auto-matic suppression system has failed to operate; injury and resc :e of at least one brigade member; and rotation of the men handling the hese and other fire fightdrs exposed to heat and/or products of combustion.

As described therein, the Point Beach Nuclear Plant minimum shift crew is comprised of:

Shift Title Fire Briaade Status 1

Shift Supervisor (SR0 Licensed)

Chief 1

Operations Supervisor (SRO or R0 Licensed) Assistant Chief 2

Control Operators (R0 Licensed)

Member 3

Auxiliary Operators Member 8

Security Guards Non-Member The seven operations personnel are fully trained members of the Point Beach fire brigade.

The Shift Supervisor and the three Auxiliary Operators are the basic four-man fire brigade attack team.

The Operations Supervisor is a backup to the brigade chief.

The two Control Operators are backup to the brigade attack members.

The Point Beach Nuclear Plant Technical Specifications allow the Operations Supervisor and one control roperator to leave the control room.

Present plant practice requires one supervisor to remain in the control room unless an emergency situation develops which requires his presence elsewhere in the plant.

Therefore, one of the three operating personnel who normally remain in the control roon could become part of the attack team in an injury emergency.

Three security personnel will be available for activities which support the four man fire brigade.

Security personnel are not required to have fire fighting training, they cannot be expected to :erform effectively as fire attack personr.el.

We have reviewed the licensee's arguments for having a four man fire brigade shift size supported by an untrained three man su::: ort team.

W-deem this organization deficient in the folicwing areas.

SS13?iG

j[p.[NNA

.j.,

4?

I 1.

The Shift Supervisor is designated as the fire brigade leader.

This is unacceptable because he may be required to leave the fire scene to carry out his responsibility for the overall operation and safety of the plant.

2.

The fire brigade leader has only three trained members supporting him.

Therefore, he is required to perforn fire fighting actions.

Because he is not free of such duties, he cannot continuously assess the situation and direct the activities of other fire brigade members and the support team.

3.

If operators performing fire fighting stions are required to leave the fire scene should a safety threat occur as a result of the fire before the fire is extinguished, the support team is not trained in fire fighting such that at least a minimum fire fighting action of one hose line could be sustained.

Staff Position The Shift Supervisor should not be designated as the fire brigade leader. He should be free to carry out his overall responsibility as as shift supervisor.

The Operations Supervisor, presently designated as assistant fire brigade chief should be designated as fire brigade chief.

The use of three of the remaining five operations personnel on the fire brigade is acceptable.

The security support people should be adequately trained in the basic fire fighting procedures.

At least one of the trained support pecple should be required to respond directly to the fire location and take an active part in the fire suppression activity.

This will free the fire brigade leader to fulfill his responsibility as fire brigade leader.

t W n J.a

ENCLOSURE 3 STAFF POSITION MINIMUM FIRE BRIGADE TRAINING CONCERN During our evaluation of the training given to fire brigade members, the issue of whether all members of a five man fire brigade need be given identical training has been considered.

In several instances licensees These have proposed two levels of training for fire brigade members.

evaluations have established the minimum acceptable level of training.

STAFF POSITION W? prefer that all fire brigade members receive training in accordance with the staff guidelines set forth in " Nuclear Plant Fire Protection Functional Responsibilities, Administrative Controls and Quality Assurance," June 14, 1977:.

Fire Protection Organization.

Fire Brigade Training.

Fire Fighting Procedures (Note: Copies of these attachments are enclosed)

Where the five man fire brigade has two levels of training, at least three members shall have training which fully conforms to the staff guidelines; however, two members may be excepted from the training require-ments listed below:

1. :

1.0a (6) The direction and coordination of the fire fighting activi ties.

1.0a (9) Detailed review of fire fighting procedures and procedure changes.*

1.0a (10)

Review of latest plant modifications and changes in fire fighting plans.

The excepted personnel should have general training in these subjects.

  • The only portion of this item excepted is that associated with the fire fighting strategies which have been developed to conform with attachment 5,

'The strategies established for fighting fires in all safety-item d.

related areas and areas presenting a hazard to safety-related equip-ment."

s

.$bb

Excerpts from:

" Nuclear Plant Fire Protection Functional Responsibilities, Administrative Controls, and Quality Assurance" (June 14,1977)..

Fire Protection beganization.

Fire Brigade Training Attachaent 5.

Fire Fighting Procedures

~

t s

Attachment No.1

'f FIRE PROTECTION ORGANIIATION s

1.0 The organizational responsibilities and lines of comunication per-taining to fire protection should be defined between the various positions through the use of organizational charts and functional descriptions of eacn position's responsibilities. As a minimum the positions / organizations responsible for the following should be designated:

a.

The upper level offsite management position which has management res:ensioility for the formulation. ir.clementation, and assess-e4nt of the effectiveness of the nuclear plant fire protection program.

b.

The offsite management position (s) directif responsible for (1) for ulating, implementing, and periodically assessing the effectiveness of the fire protect on program for the licensee's nuclear power plant including fire drills and training con-ducted by the fire brigade and plant personnel. The results of these assessments 5hould be recorted to the upper level management position responsicle for fire protection with reco mendations for improvements or corrective actions as deemed necessary.

(2) Using the following NFPA Publications for guidance to dev-elop tne fire protection program:

"Organi:ation for Fire Services" No. 4 "Organi:ation of a Fire Department" No. 4A

" Industrial Fire Loss Prevention" No. 6

" Management of Fire Emerganctes" No. 7

" Management Responsibilities for Effects of No. 8 Fire on Operations"

" Private Fire Brigades" No. 27 c.

The onsite maragement position res;cnsible for the overall acministration of the plant operations and emergency plans which include the fire protection and prevention program and which provides a single point of control and contact for all contingencies.

g..

  • k *x)
  • fa 5O

~

9000

^

d.

The onsite postd o @ 7 %hich:

(1) implements periodic inspections to: minimize the arount of combustibles in safety related areas; detemine the ef#ectiveness of housekeeping practices; assure the avail-ability and acceptable condition of all fire protection systems /equipeent, emergency breathing apparatus, emergency lighting, comunication equipment, fire stops, penetration seals anc fire retardant coatings; and assures prompt and effective corrective actions are taken to correct conditions acverse to fire protection and preclude their recurrence.

(2) is responsible for the fire fighting training for operating plant personnel and the plant's fire brigade; design and selection of ecui: ment; periodic inspection and testing of fire protection systems and equipment in accordance with established procedures and evaluate test results and deter-mine the acceptability of the systems under test.

(3) assists in the critique of all fire drills to detemine how well the training objectives have been met.

(4) reviews and evaluates proposed work activities to identify potential transient fire loads.

(5) imclements a program for indoctrination of all planc contractor personnel in appropriate administrative pro-cedures which implement the fire protection program, and the emergency procedures relative to fire protection.

(6) implements a program for instruction of personnel on the proper handling of accidental events such as leaks or spills of flar.mable materials that are related to fire p rotec tion.

l e.

The onsite position responsible for fire protection quality assurance.

1 This position should be responsible for assuring the effective implementation of the fire protection program by planned in-spections and scheduled audits. He should assure and verify that results of these inspections or audits are premptly re-ported to cogni: ant management personnel, s

351'XiO

3

[

f The positions which are part of the plant fire brigade (1) The plant fire brigade positions snould be responsible for fignting fires. The authority and responsibility of each fire brigade position relative to fire protection should be clearly defined.

(2) The responsibilities of each fire brigade position should correspond with tne actions required by the fire fignting procedures.

(3) The responsibilities of the fire brigade members uncer normal plant conoitions, should not conflict witn tneir responsibilities during a fire emergency.

(O The minimum numoe* of trained fire brigade memoers avail-able onsite for each operating shift should be consistent with tne activities required to combat the most significant fire. The si:e of the fire brigade should be based upon the functions required to fight fires with adequate allow-ance for injuries.

(5) The recomendations for organization, training, and equip-ment of " PRIVATE FIRE BRIGACE5" as s;ecified in NFPA No. 27-1975, including the applicable NF2A publications listed in tne Appendix to NFPA No. 27. are considered aporocriate criteria for organi:ing, training, and operating a plant fire brigade.

2.0 Qualifications a.

Tne position resconsible for for ulation and implementation of the Fire Protection Program should have, within his organ-1:ation, or as a consultant, a Fire Protection Engineer is a graduate of an engineering curriculum of accepted standing and shall have completed not less than six years of engineering attainment indicative of growth in engineering competercy and acnievement, three of which shall have been in responsible charge of fire protection engineering work. These requirements are the eligibility requirements as a Member in the Society of Fire Protection Engineers.

Q) d d}A-

  • q

"%E

(.

.1 The fire brigade memcees cualifications should include satis-b.

f actory completion of a pnysical examination for perfoming strenuous activity, and of the fire brigade taining described in At:achment No. 2.

The personnel responsible for the maintenance and testing of the c.

Fire Protection Systems should be qualified by training and ex;erience for sucn work.

The personnel res::ensible for the t.aining of the fire brigade d.

should be qualified by training and experience for such work.

k

... - ~

~

Attachmant No. 2 FIRE BRIG,01 TRAINING The training pro, cam should assure that the ca: ability to fignt potential fires is estac11sned and maintained. The progran shoald consist of an initial classroom instruction program followed by periodic classroom instruction, practice in fire fignting and fire drills:

1.0 Classroem Instruction The initial classroom instruction shculd include:

a.

(1)

Identification of the fire ha:ards and associated types of fires that could occur in the plant, and an icenti-fication of the 1ccation of sucr. hacards.

Identification of ne location of fire fighting equ'ip-(2) cent for eacn fire area, anc familiarization with layout of ne plan; including access and egress routes to each area.

(3) The proper u of available fire fighting equipment, and the correct metnod of fignting each type of fire. The types of fires covered snould include electrical fires, fires in cables and cable trays, hydrogen fires, flam-mable liquid, waste /detris fires, and record file fires.

(a)

Indcctrination of the clant fire fighting plan with soecific coverage of eacn individual's res;cnsibilities.

(5) The pr:per u:e of ccmunication, lignting, ventilation and emergency breatning equi; ment.

(6) The direction and coordina:icn of the fire fignting activities (fire brigade leaders only).

(7) The toxic characteristics of expected products of combus tion.

(8) The peccer method for fighting fires inside butidings and tunnels.

(9) Cetailed review of fire fighting precedures and procedure changes.

(10)

Review of lates plant ecdificatiens and changes in fire fign:ing plans.

.N

2 3.

The instruction should be provided by Qualified individuals knewledgeable, ex:erienced, and suitably trained in fighting the types of fires that could occur in the plant and in using the types of equipment available in the nuclear power plant.

Members of the " Fire Protection Staff" and Fire Brigade Leaders may conduct this training.

c.

Instruction should be provided to all fire brigade members and fire brigade leaders.

d.

Regular planned meetings held every 3 months should repeat tne classroem instruction program over a two year period.

2.0 practice practice sessions should be held for fire brigade members on the pro:er metnod of fighting various types of fires of similar mag-nitude, corplexity, and dif ficulty as tnose which could occur in a nuclear power plant. These sessions shculd provide brigade members with experience in actual fire extinguishment and the use of em-ergency breatning ap;aratus under strenuous conditions. These practice sessions snould be provided at regular intervals but not to exceed 1 year for eacn fire brigace memoer.

3.0 Drills Fire brigade drills should be perfor.r a in the plant so that the fire brigade can practice as a team. Orills should include the following:

Assessrent of fire alarm effectiveness, time required to notify a.

and asseroly fire brigade, and selection, placement and use of equi pme'1 t.

b.

Assess eacn brigade member's knowledge of his role in the fire fighting stentegy for the area assu-ed to contain tne fire:

Assess the brigade members conformance with established plant fire fighting procedures and use of fire fighting equipment, including self-contained emergency breathing apparatus, comuni-cation e:uipment, and ventilation equipment, to tne extent practicable.

1 swm

3 The simulated use of fire fignting equipment required tc co;e c.

with the situation and type of fire selected for the drill.

The area and ty:e of fire chosen for the drill should be varied sucn that brigade mesters are trained in fignting fires in all safety related areas containing significant fire hazards. The situation selected should simulate the size and arrangement of a fire wnich coulo reasonably occur in the area selected, allowing for fire development due to the time required to re-spond. to obtain equipment, and organize for the fire, assuming loss of automatic suppression capability.

d.

Assessment of brigade leader's direction of the fire fighting ef# ort, as to tnercugnness, accuracy, and effectiveness.

The drills should be perfomed at regular intervals but-not e.

to exceed 3 months for each fire brigade. At least one drill pea year snould be perforced on a "back shift" for each fire brigade. A sufficient number of these dr1115, not less than one fcr eacn fire brigace per year, shall be unannouncec, to de-te-mine the fire readiness of the plant fire brigade leader, brigade, fire protection systems and equipment, f.

The drills should be pre-planned to establish the training ocjectives of :ne drill. The drills should be critived.:o cete-mine new well the training objectives have been met.

Unannounced drills snould have their critiques perfomed by mercers of tne tranage en: staff res;onsible for plant safety and securi ty.

At three year intervals, drills should be critiqued by qualifiec incividuals independent of the utility's staff.

4.0 Records Recores of training provided to each fire brigade memcer including delli criti::ves should be maintained to assure that each member receives training in all parts of the training program. These reccccs of training snoul.d be available for review.

s

Attachment No. 5

&s, y

h

/

} j; b[

FIRE FIGHT:NG PRCCE URE5 V af Fire fighting Orecedures snould be estaclished to cover such items as notification of a fire, fire emergency prececures, and c orcination of fire fignt'e; activities wita of fsite fire ce; art.ments.

The fire fignt-ing p mcecures sneule icentify:

K.

Acti0ns t: ::e taken by indivicual discovering the fire, suen as, nc.i'icaticn of c:ntrol recm, attem:t to extinguish fire, anc actua.icn of local fire su ressicr. systems.

b.

Actices to te take, :y the c:ntrol room c:e ater an: the neec for triga:e assistance u:en re: Ort of a fire er recei:t of ala n on c:n.r:1 r:cm a9nenciat:r panel, sucn as:

anncuncing loca-icn of fire ever PA system, scuncing fire alarms and notifying tne shift su erviser and the fire brigace lea:er of the ty e, si:e, and iccation of the fire.

c.

Acti:ns t: :e taken :y the fire brigade af er notification'by the cor r:1 re:m ::e ater of a fire, including:

locati:n to assem:le; ci e:ttens given by fire trigade leacer; and res:ensi-Oilities of Origa:e mem:ers such as selection of fire fignting e:.i:eemt anc trans; rtation to fire locatien, selection of pr:tective ecuipment, use of fire su::ression systems c erating instruc-i:.s, anc t.se of pre lannec strategies for fighting fires in 5:e:ific areas.

The st. atagies esta:lished for fighting fires in all safety-d.

relate: areas and a eas presenting a ha:ar to safety-related ecui: ment. As a minimum the following su:jects shoulc be c: vere::

(1) Icentificati:n of ccm:vstibles in each :lant :ene c:vered by the s:ecific fire fignti,ng prececures.

(2) Fire extinguismants best suited for controlling the fires asscciatec with the c:moustible Icadings in that zone and the nearest 1ccati:n of these extinguisnants.

(3) Idest f avera:le directi:n frem whien to attack a fire in eacn area, in view of the ventilation direction, ac:ess hallways, stairs and ::Ps nica are mes. likely to e fire-free, anc the test station er elevation f r fignting

  • ne " e.

A s:ecific ice-tification system shall cesignate all hallways, stairs, d:crs, fire ecui:.ent and system c:ntrol 1:ca.i:ns, an: Other items descricec in tne fire fignting pr:cac res.

Inis icentificatien should be used c~.

v 4.4 %LUvo

in the er:cedures anc the cerrasconding plant items should be pr:minently ma-ked so that they can be rec:gnizac in dim light. All access anc egress routes that involve lockec doces shoulc be specifically identified in the procecure with the a:pr:priate precautions and metnces for access specified.

(*)

Oesigrati:n of plant syste?.s that should be managed to recuce tne camage cetential during a local fire; location e' local anc remote c:ntrols for such management (e.g.,

ary hycraulic cc electrical systems in the zone C3vered by the specific fire fighting Dr cedure that c uld increase the ha:n-Os in the area because of overpres-suri:ation er electrical ha: arcs).

(~)

Cesignation of vital heat-sensitive system c:e:cnents tha*. shoulc ce ke:t cc 1 while fignting a local fire.

Critical ecui: ment wnich are particularly ha:arceus c:e:wstible s urces shcule be designatec to receive c: cling.

(')

Organi:atien c' fire fighting brigades and the assig ant of s:ecial cut es acc:rcing to je: title so that all fire fighting functions are covered by any c e:lete shift per-scnnel com;lement. These duties should include c:mmand centrol of tne tr*gade, fire hose laying, a; plying the extinguisnant to tne fire, advancing su; ort supplies to the fire scene, c:mmunication with ne c:ntrol recm, c:crcination with outsica fire depart:;ents.

(7)

Ideatificatien raciclogical and toxic ha:ards in fire

cres.

(3) Veatilation system c:eration that assures cesired plant pressure cistrit utien wrnen the ventilation flew is

=ccified for fire c:ntainrent or smoke clearing operations.

(9) 0:erations requiring control reem and shif t engineer coordination or authorization.

(10)

Instructi:ns fer plant operat:rs anc general plant per-sonnel curing fire.

a.

The valicity of the ; replanning strategies should be tested by a::r::riate fuli-cress crills to check the logic of the strate;y, the acecuacy of the ecuipment, persennel unce--

stancing, anc to unc:ver unf reseen pr:blems.

O p < q

-3,....;

e3Q. LOO ;

O&

Actions to be taken by Plant Sucerintencent and his staff, and f.

Security Guarcs after notification of a fire.

Actions to be taken that will coordinate fire fighting activities identification of 9

with offsite fire de:artments, including:

incivicual res:ensible for assessing fituation and calling in outsice fire de:artment assistance when neecec; identification of incivicual who will direct fire fighting activities when aidec by offsite fire fighting assistance; provisions for inclucing offsite fire fignting organitations in fire brigace cr'115 at least once :er year; and provisions for training of f site fire ce:a-tment personnel in basic radiation principles, tyD cal rac'ation ha:ards, anc precau*. ions to be taken in. a i

The pro-fire involving racicactive materials in the plant.also cescrite the of fsite Cecures snoul resources arc es-imatec rescense time by the offsite fire ce: art. ment to provict assistance to the station.

O C. *.j.- 0.e.. y,ata

Mr. Sol Burstein Wisconsin Electric Power Company cc: Mr. Bruce Churchill, Esquire Shaw, Pittman, Potts and Trowbridge 1800 M Street, N.W.

Washington, D. C.

20036 Document Department University of Wisconsin Stevens Point Library Stevens Point, Wisconsin 54481 Mr. Glen Reed, Manager Nuclear Power Division Point Beach Nuclear Plant Wisconsin Electric Power Company 231 West Michigan Street Milwaukee, Wisconsin 43201