ML18241A124
| ML18241A124 | |
| Person / Time | |
|---|---|
| Site: | NuScale |
| Issue date: | 08/30/2018 |
| From: | Getachew Tesfaye NRC/NRO/DLSE/LB1 |
| To: | Samson Lee NRC/NRO/DLSE/LB1 |
| Tesfaye G / 415-8013 | |
| References | |
| Download: ML18241A124 (6) | |
Text
August 30, 2018 MEMORANDUM TO:
Samuel S. Lee, Chief Licensing Branch 1 Division of Licensing, Siting, and Environmental Analysis Office of New Reactors FROM:
Getachew Tesfaye, Senior Project Manager
/RA/
Licensing Branch 1 Division of Licensing, Siting, and Environmental Analysis Office of New Reactors
SUBJECT:
SUMMARY
OF THE AUGUST 2, 2018, CATEGORY 1 PUBLIC TELECONFERENCE TO DISCUSS NUSCALE POWER, LLC RESPONSES TO REQUESTS FOR ADDITIONAL INFORMATION ASSOCIATED WITH THE NUSCALE DESIGN CERTIFICATION APPLICATION The U.S. Nuclear Regulatory Commission (NRC) held a Category 1 public teleconference on August 2, 2018, to discuss responses to the NRC staff requests for additional information associated with the NuScale Power, LLC (NuScale) design certification application. Participants included personnel from NuScale. Members of the general public did not participate.
The public meeting notice dated August 2, 2018, can be found in the NRCs Agencywide Documents Access and Management Systems under Accession No. ML18212A023. This meeting notice was also posted on the NRC public website.
Enclosed is the meeting agenda (Enclosure 1), list of participants (Enclosure 2), and overview (Enclosure 3).
Docket No.52-048
Enclosures:
- 1. Meeting Agenda
- 2. List of Attendees
- 3. Meeting Overview cc w/encl.: DC NuScale Power, LLC Listserv CONTACT: Getachew Tesfaye NRO/DLSE 301-415-8013
ML18241A124 NRO-002 OFFICE DLSE/LB1:PM DLSE /LB1:LA DLSE/RPAC DNRL/LB1:PM NAME GTesfaye MMoore SMeighan*
GTesfaye (signed)
DATE 8/28/2018 8/29/2018 8/30/2018 8/30/2018
U.S. NUCLEAR REGULATORY COMMISSION CATEGORY 1 PUBLIC TELECONFERENCE TO DISCUSS NUSCALE POWER, LLC RESPONSES TO REQUESTS FOR ADDITIONAL INFORMATION ASSOCIATED WITH THE NUSCALE DESIGN CERTIFICATION APPLICATION MEETING AGENDA August 2, 2018 1:00 - 1:15 PM Introductions and Identification of topics 1:15 - 2:30 PM Discussion of U.S. Nuclear Regulatory Commission Staffs Questions regarding NuScale Power LLCs Responses to Requests Additional Information 9295, 9255, 9263, and 9267.
2:30 - 2:45 PM Public Comments/Questions 2:45 Meeting Closure
U.S. NUCLEAR REGULATORY COMMISSION CATEGORY 1 PUBLIC TELECONFERENCE TO DISCUSS NUSCALE POWER, LLC RESPONSES TO REQUESTS FOR ADDITIONAL INFORMATION ASSOCIATED WITH THE NUSCALE DESIGN CERTIFICATION APPLICATION LIST OF ATTENDEES August 2, 2018 Name Organization Getachew Tesfaye U.S. Nuclear Regulatory Commission (NRC)
Sean Meighan NRC Edward Stutzcage NRC Ronald LaVera NRC Carrie Fosaaen NuScale Power, LLC (NuScale)
Jon Bristol NuScale Jim Osborn NuScale Mark Shaver NuScale
1 U.S. NUCLEAR REGULATORY COMMISSION OVERVIEW OF THE AUGUST 2, 2018, TELECONFERENCE TO DISCUSS THE NUSCALE POWER, LLC RESPONSES TO REQUESTS FOR ADDITIONAL INFORMATION ASSOCIATED WITH THE NUSCALE DESIGN CERTIFICATION APPLICATION The purpose of this teleconference was to discuss the results of the U.S. Nuclear Regulatory Commission (NRC) staffs review of NuScale Power, LLCs (NuScale) Responses to Requests for Additional Information (RAI) 9295, 9255, 9263, and 9267.
The following is the summary of the NRC staffs feedback and agreed upon next steps for the resolution of the remaining issues.
- 1. RAI No. 9295, Question 12.03-55, Steam Galleries streaming radiation:
- a. NRC Feedback: In response to this RAI, NuScale indicated that this issue will be finalized during a future design phase. In subsequent conversations, NuScale indicated that consideration would be given to including this issue in Table 1.8-1, Summary of NuScale Certified Design Interfaces with Remainder of Plant. Has NuScale made a determination on inclusion of this item in the list of Design Interfaces? If not, what does NuScale see as path forward/resolution of this item?
- b. Next Step: NuScale understood the NRC staffs question and will submit a supplemantal response that will add a Combined License information item.
However, NuScale will not include it in Table 1.8-1 as a design interface requirement. Both NRC and NuScale took action to further review this request.
NuScale would consider the matter for major penetrations as reccommeded by the NRC staff but made no commitment.
- 2. RAI No. 9255, Question 12.02-31, Inclusion of Transuranic (TRU) nuclides in Airborne Sources:
- a. NRC Staff Feedback: In a follow-up discussions on this issue with a previous NuScale Senior Manager of Regulatory Affairs, it was suggested that inclusion of the limited list of TRUs supplied in the RAI would be considered for inclusion into Section 12.2.2, Airborne Radioactive Material Sources. Has a decision been made on this item?
- b. Next Step: NuScale will not include the limited list of TRUs supplied in the RAI into Section 12.2.2, Airborne Radioactive Material Sources. The NRC staff took action to further evaluate this request and take appropriate action.
- 3. RAI No. 9263, Question 12.02-06, Low Reactor Coolant System (RCS) flow rate:
- a. NRC Staff Feedback: During a public teleconference conducted on July 19, 2018, the NRC took an action to review interlocks associated with the refueling
2 bridge. It was determined that there were no interlocks on bridge movement associated with direct dose measurement. The NRC would like to reengage on this RAI, to include discussion on NuScales ability to meet the ANSI-ANS 57.2 guideline of 2.5mr/hr due to pool water activity shortly after disassembly of the nuclear power module (NPM), prior to adequate mixing of refueling pool area.
- b. Next Step: NuScale acknowledged that the information regarding the possible provision of interlocks in DCD Chapter 9 associated with restricting the movement of the refueling bridge when dose rates are high was incorrect.
However, they retirated that their original response to this RAI where they explained that the post-crud burst cleanup of the primary coolant in the NPM until the projected dose rate at one meter above the ultimate heat sink water is less than 5 mR/hr is consistent with ANSI-ANS guidelines and addresses this issue.
The NRC staff took action to further evaluate this request and take appropriate action.
- 4. RAI 9267, Q12.2-7 and Q12.2-8:
- a. NRC Staff Feedback: Using the information available in the Gaseous and Liquid Effluent (GALE) Audit, the staff attempted to correct the DCD R1 Table 11.1-4 Design Basis Reactor Coolant Activity concentration for the new Design Basis Failed Fuel Fraction (6.6E-4) and the new reactor coolant system mass (103000 lbm). However, the staff calculated activity concentration was greater than the Table 11.1-4, Primary Coolant Design Basis Source Term, Primary Coolant Concentrations provided in the response to RAI 9270. The change in activity appears to be due to a change to Ub (the name of a user defined variable) that is not understood by the staff. The staff request that NuScale describe the changes made to Ub and the basis for those changes.
- b. Next Step: NuScale understood the NRC staffs question and provided further explanation for their calculation. The NRC staff thanked NuScale for the additional clarification and took action to go back and check their numbers.