Notice of Deviation from Insp on 811207-11
ML18139B763
Person / Time
Site: Surry  
Issue date: 01/04/1982
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML18139B757 List:
References
50-280-81-32, 50-281-81-32, NUDOCS 8203020347
Download: ML18139B763 (1)


Text

APPENDIX B NOTICE OF DEVIATION Virginia Electric and Power Company Surry Units 1 and 2 Docket Nos. 50-280 & 50-281 License Noi. DPR-32 & DPR-37 Based on the results of the inspection conducted on December 7-11, 1981, certain of your activities appear to deviate from your commitments to the Commission as indicated below:

Date:

Virginia Electric and Power Company* s Fire Protection Systems Review of July 1, 1977 Section III.C Fire Area 28C (Page III-147) states that initi-ation of the carbon dioxide system pneumatically closes the ventilation dampers in the fire walls enclosing the oil tank room.

Contrary to the above, initiation of the carbon dioxide system will not pneumatically close the ventilation fire dampers.

J~N* cr4* 198!>

~*

8203020347 820223 PDR ADOCK 05000280 Q

PDR I