ML18139B469

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 810501-29
ML18139B469
Person / Time
Site: Surry  Dominion icon.png
Issue date: 06/19/1981
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML18139B463 List:
References
50-280-81-17, 50-281-81-17, NUDOCS 8108040582
Download: ML18139B469 (1)


Text

e e

APPENDIX A NOTICE OF VIOLATION Virginia Electric and Power Company Surry 1 and 1 Docket Nos. 50-280, 50-281 License Nos. DPR-32, DPR-37 As a result of the inspection conducted on May 1-29, 1981, and in accordance with the Interim Enforcement Policy, 45 FR 66754 (October 7, 1980), the following violation was identified.

Technical Specification 3.21.G requires that all penetration fire barriers protecting safety related areas be functional, otherwise a continuous fire watch shall be established within one hour.

Fire doors serve as fire barriers and must be functional.

NFPA-80, Section 516.b requires that all swinging type fire doors be provided with approved positive latching devices to be functional.

Contrary to the above, on May 28, 1981, th*e following fire barriers (swinging type fire doors) were in access and not functional *due to inoperable latching devices, and a continuoui fire watch was not properly established:

Fire doors 37, 39, and 41 leading from the mezzanine into the three emergency diesel generator rooms, Fire door 21 between the turbine building and the emergency switchgear

room, Fire door 10 into the cable spreading room above the control rooms.

This is a Severity Leyel V Violation (Supp. I.E.).

Pursuant to the provisions of 10 CFR 2.201, you are hereby required to submit to this office within thirty days of the date of this Notice, a written statement or explanation in reply, including:

(1) admission or denial of the alleged viola-tion; (2) the reasons for the violation if admitted; (3) the corrective steps which have been taken and the results achieved; (4) corrective steps which will be taken to avoid further violations; and (5) the date when full compliance will be achieved.

Consideration may be given to extending your response time for good cause shown.

Under the authority of Section 182 of the Atomic Energy Act of 1954, as amended, this response shall be submitted under oath or affirmation.

Date: JUN 191S~1 8108040582 -810724~

PDR ADOCK 05000280' G

PDR.,

.....