FORM NIS-1 OWNER'~ATA REPORT FOR INSERVICE 1&ECTIONS AS' REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1.

Owner Public Service Electric & Gas Co., 80 Park Plaza, Newark, NJ, 07101

2.

Plarit Salem Generating Station P.O. Box E, Hancock's Bridge, NJ 08038

3.

Plant Unit Unit 1 (Facility Operating License DPR-70)

4.

Owner's Certificate of Authorization (if Required) N/A

5.

Commercial Service Date 07/01/77

6. National Board Number for Unit 20757
7.

Components inspected (see page 1)

8.

Exam Dates February 2, 1994 to April 17, 1998

9.

Inspection Interval from February 27, 1988 to July 7, 2001

10. Applicable Edition of ASME Section XI, 1983, through 1983 Summer Addenda
11. Abstract of Examinations:

Component or Manufacturer Appurtenance or installer

  1. 11 Steam Westinghouse Tampa Div.

Generator P.O. Box 19218 Tampa, FL 33616

  1. 12 Steam II Generator
  1. 13 Steam II Generator
  1. 14 Steam II Generator Reactor Coolant II System Safety Injection United Engineers &

System Constructors (UE&C)

Residual Heat UE&C Removal System Boiler Feed System UE&C Main Steam System UE&C Chemical Volume UE&C and Control System Auxiliary Feedwater UE&C System Containment Spray UE&C System Service Water UE&C System Component Cooling UE&C System Sampling System UE&C

.~,ge: 1 (Rev. 1) 9901130104 990106 PDR ADOCK 05000272 G

PDR Manuf.

State or National or Province Board No.

Installer No.

Serial No.

2174 N/A N/A 2173 N/A N/A 2171 N/A N/A 2172 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

FORM NIS-1 OWNER'~ATA REPORT FOR INSERVICE 1&ECTIONS AS' REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1.

Owner Public Service Electric & Gas Co., 80 Park Plaza, Newark, NJ, 07101

2.

Plarit Salem Generating Station P.O. Box E, Hancock's Bridge, NJ 08038

3.

Plant Unit Unit 1 (Facility Operating License DPR-70)

4.

Owner's Certificate of Authorization (if Required) N/A

5.

Commercial Service Date 07/01/77

6. National Board Number for Unit 20757
7.

Components inspected (see page 1)

8.

Exam Dates February 2, 1994 to April 17, 1998

9.

Inspection Interval from February 27, 1988 to July 7, 2001

10. Applicable Edition of ASME Section XI, 1983, through 1983 Summer Addenda
11. Abstract of Examinations:

An inservice examination (ISi) of selected Class 1, Class 2 and Class 3 components of Public Service Electric and Gas Company's (PSE&G) Salem Generating Station, Unit 1, was performed by Public Service Electric & Gas (PSE&G), Magnaflux Quality Services (MQS), Southwest Research Institute (SwRI), Virginia Corporation of Richmond (VCR) and AEA Technology Engineering Services (AEA) personnel during the April 1995 - April 1998. These examinations-constituted the twelfth (2nd Period, 3rd Outage) at Salem 1 during the Second 10-year Inspection Interval of operation.

Exams were performed in accordance with the 1983 Edition through Summer 1993 Addenda of ASME Section XI and the Salem lnservice Inspection Program Long Term Plan.

ISi was performed utilizing visual (VT), magnetic particle (MT), liquid penetrant (PT), manual ultrasonic (UT), mechanized ultrasonic (M-UT) and radiography (RT) nondestructive examination techniques.

This report also contains augmented examinations required by the Salem Technical Specifications, Regulatory Guides, Circulars and Bulletins issued by the United States Nuclear Regulatory Commission.

Page: 2 (Rev. 1)

FORM NIS-1 OWNER'5'ATA REPORT FOR INSERVICE 1&ECTIONS AS' REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1.

Owner Public Service Electric & Gas Co., 80 Park Plaza, Newark, NJ, 07101

2.

Plant Salem Generating Station P.O. Box E, Hancock's Bridge, NJ 08038

3.

Plant Unit Unit 1 (Facility Operating License DPR-70)

4.

Owner's Certificate of Authorization (if Required) N/A

5.

Commercial Service Date 07/01/77

6. National Board Number for Unit 20757
7.

Components inspected (see page 1)

8.

Exam Dates February 2, 1994 to April 17, 1998

9.

Inspection Interval from February 27, 1988 to July 7, 2001

10. Applicable Edition of ASME Section XI, 1983, through 1983 Summer Addenda
11. Abstract of Examinations:

11.1 MQS, SwRI and VCR under the direction of the PSE&G ISi Group, conducted 13 manual ultrasonic, five liquid penetrant, two magnetic particle examinations.

There were no unacceptable indications identified.

Class 1 Vessels Piping Class 2 Vessels Piping Steam Generator Reactor Coolant Safety Injection Residual Heat Removal Steam Generator Boiler Feed Main Steam Chemical Volume Control Page: 3 (Rev. 1)

FORM NIS-1 OWNER'.ATA REPORT FOR INSERVICE l.PECTIONS AS' REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1.

Owner Public Service Electric & Gas Co., 80 Park Plaza, Newark, NJ, 07101

2.

Plant Salem Generating Station P.O. Box E, Hancock's Bridge, NJ 08038

3.

Plant Unit Unit 1 (Facility Operating License DPR-70)

4.

Owner's Certificate of Authorization (if Required) N/A

5.

Commercial Service Date 07/01fi7

6. National Board Number for Unit 20757
7.

Components inspected (see page 1)

8.

Exam Dates February 2, 1994 to April 17, 1998

9.

Inspection Interval from February 27, 1988 to July 7, 2001

10. Applicable Edition of ASME Section XI, 1983, through 1983 Summer Addenda
11. Abstract of Examinations:

11.2 ISi Section XI Visual examinations on valves and bolting PSE&G's ISi Group conducted eight Class 1 bolting exams and one Class 1 valve internal exam.

ISi Section XI examinations were conducted on the*following systems:

Safety Injection Residual Heat Removal The following was identified during the course of these examinations:

Valve 1 RH26 (WinlSI Sum# 193800) had a visual VT-3 internal examination, which revealed seating surface wear. The valve interior was resurfaced and an acceptable post rework VT-3 valve internal examination was performed. An additional sample was not required, since the valve is the only one identified in that valve group.

There were no other unacceptable indications identified.

11.3 ISi Section XI Visual examination of components supports PSE&G conducted four Class 1, 2 & 3 component support visual VT-3 and VT-3/4 examinations.

ISi Section XI examinations were conducted on the following systems:

Main Steam Safety Injection Reactor Coolant Chemical and Volume Control There were no unacceptable indications identified.

Page: 4 (Rev. 1)

FORM NIS-1 OWNER'.ATA REPORT FOR INSERVICE l.PECTIONS AS. REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1.

Owner Public Service Electric & Gas Co., 80 Park Plaza, Newark, NJ, 07101

2.

Plarit Salem Generating Station P.O. Box E, Hancock's Bridge, NJ 08038

3.

Plant Unit Unit 1 (Facility Operating License DPR-70)

4.

Owner's Certificate of Authorization (if Required) N/A

5.

Commercial Service Date 07/01/77

6. National Board Number for Unit 20757
7.

Components inspected (see page 1)

8.

Exam Dates February 2, 1994 to April 17, 1998

9.

Inspection Interval from February 27, 1988 to July 7, 2001

10. Applicable Edition of ASME Section XI, 1983, through 1983 Summer Addenda
11. Abstract of Examinations:

11.4 ISi Section XI System Leakage Examinations PSE&G's ISi Group conducted four System Pressure Tests during a System Functional or lnservice Test, on Nuclear Class 1, 2 and 3, in accordance with ASME Section XI.

A system Leakage exam was performed in accordance with ASME Section XI on all Class 1 Systems. The system leakage test was performed with the Reactor Coolant System in Mode 3 (normal operating temperature and pressure) with the insulation installed. No pressure boundary leakage was detected.

Work requests were initiated to correct minor mechanical leakage that was not corrected during the system walkdowns.

Class 2 and 3 System Pressure Tests were conducted on the following systems:

- Auxiliary Feedwater

- Sampling 11.5 RCP Flywheel Augmented Examinations per USNRC Regulatory Guide 1.14 SwRI under the direction of the ISi Group performed a Ten year exam (with the Flywheels removed from the motors) on all Salem Unit 1 & 2's RCP Flywheels at the Westinghouse Cheswick, PA facility as identified below by the Flywheel serial number:

2S-76P917 1S-88P318 1S-76P917 3S-76P917 1S-D003 1S-75P790 4S-75P790 There were no unacceptable indications identified.

Page: 5 (Rev. 1) 3S-75P790 2S-75P790

FORM NIS-1 OWNER'.ATA REPORT FOR INSERVICE l.PECTIONS AS. REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1.

Owner Public Service Electric & Gas Co., 80 Park Plaza, Newark, NJ, 07101

2.

Plant Salem Generating Station P.O. Box E, Hancock's Bridge, NJ 08038

3.

Plant Unit Unit 1 (Facility Operating License DPR-70)

4.

Owner's Certificate of Authorization (if Required) NIA

5.

Commercial Service Date 07/01/77

6. National Board Number for Unit 20757
7.

Components inspected (see page 1)

8.

Exam Dates February 2, 1994 to April 17, 1998

9.

Inspection Interval from February 27, 1988 to July 7, 2001

10. Applicable Edition of ASME Section XI, 1983, through 1983 Summer Addenda
11. Abstract of Examinations:

11.6 NRC Bulletin 88-08 "Thermal Stresses in Piping Connected to the Reactor Coolant System" Augmented Examinations VCR under the direction of PSE&G's ISi Group performed augmented ultrasonic and dye penetrant examinations on a total of 20 components, broken down as follows:

(15) 1.5 inch Safety Injection piping welds Two 2 inch Chemical and Volume Control piping welds Two 3 inch Chemical and Volume Control piping welds There are no unacceptable indications identified.

11.7 Augmented Exams per Branch Technical Position MEB 3-1 30 welds were volumetrically examined, to comply with the augmented requirements of NUREG 0800 Standard Review Plan, Section 3.6.2, Branch Technical Position MEB 3-1.

The UT was performed by VCR with no unacceptable indications identified.

11.8 NRC Bulletin 88-11 "Pressurizer Surge Line Thermal Stratification" Augmented Examinations PSE&G's ISi Group performed visual examinations on all existing surge line pipe supports I HEBA restraints and their associated insulation interfaces.

A total of ten supports were examined.

There were no unacceptable indications identified.

Page: 6 (Rev. 1)

FORM Nl*S-1 OWNER'.ATA REPORT FOR INSERVICE l.PECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1.

Owner Public Service Electric & Gas Co., 80 Park Plaza, Newark, NJ, 07101

2.

Plarit Salem Generating Station P.O. Box E, Hancock's Bridge, NJ 08038

3.

Plant Unit Unit 1 (Facility Operating License DPR-70)

4.

Owner's Certificate of Authorization (if Required) N/A

5.

Commercial Service Date 07/01/77

6. National Board Number for Unit 20757
7.

Components inspected (see page 1)

8.

Exam Dates February 2, 1994 to April 17, 1998

9.

Inspection Interval from February 27, 1988 to July 7, 2001

10. Applicable Edition of ASME Section XI, 1983, through 1983 Summer Addenda
11. Abstract of Examinations:

11.9 Augmented System Leakage tests per NUREG 0578 "TMI Lessons Learned" PSE&G's ISi Group conducted 27 System Leakage Tests in accordance with NUREG 0578 on the following systems:

Safety Injection, Residual Heat Removal, Chemical and Volume Control, Containment Spray, Sampling, Liquid Radwaste, Waste Gas, & Waste*

Liquid There were no unacceptabie indications identified.

11.10 PSE&G's Supplemental Ultrasonic Examinations on the old Steam Generator Feedwater Nozzle to Forging Expanders AEA ultrasonically examined the four Steam Generator Feedwater Nozzle inner radius and the barrel of the nozzle including the Feedwater thermal sleeves.

There were no unacceptable indications identified.

11.11 PSE&G Augmented Visual Examinations on the Reactor Coolant Pump Main Flange connection (R/T# 290049)

PSE&G's ISi Group performed a visual examination of the Reactor Coolant Pumps Main Flange connection for evidence of leakage in accordance with R/T# 290049.

Each of the four RCP's showed evidence of RCS leakage (dried boron on the main flange connection area and the bolting). All the RCP main flange studs were removed, several at a time, and visually VT-1 examined for damage and reinstalled and re-torqued. Several studs were found with unacceptable conditions and were replaced as required (See the following preservice examination descriptions for specific details)

Page: 7 (Rev. 1)

FORM Nl.S-1 OWNER'.ATA REPORT FOR INSERVICE.PECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1.

Owner Public Service Electric & Gas Co., 80 Park Plaza, Newark, NJ, 07101

2.

Plarit Salem Generating Station P.O. Box E, Hancock's Bridge, NJ 08038

3.
  • Plant Unit Unit 1 (Facility Operating License DPR-70)
4.

Owner's Certificate of Authorization (if Required) N/A

5.

Commercial Service Date 07/01177

6. National Board Number for Unit 20757
7.

Components inspected (see page 1)

8.

Exam Dates February 2, 1994 to April 17, 1998

9.

Inspection Interval from February 27, 1988 to July 7, 2001

10. Applicable Edition of ASME Section XI, 1983, through 1983 Summer Addenda 11. Abstract of Examinations:

11.12 Preservice Examinations on Various Bolting Material Replacements Several bolted connections were replaced as identified below:

ITEM PSE&G PSE&G PSE&G COMPONENT NO.

DCP NO.

CJP NO.

W.0.#

DESCRIPTION

1.

N/A S-93-036 920804179 Valve 1 PR1 Bonnet Bolting

2.

N/A S-94-048 950527023 Valve 1 PR4 Flange Bolting

3.

N/A S-94-052 940425148 Valve 1 PR5 Flange Bolting

4.

N/A S-94-051 940425145 Valve 1 PR3 Flange Bolting

5.

N/A S-94-073 940520130 Valve 1 PR3 Flange Bolting

6.

N/A S-95-288 950325019 Valve 13MS167

7.

N/A S-95-287 950325019 Valve 1CV78

8.

N/A S-95-254 950527006 Valve 1CV80

9.

N/A S-95-180 950505099 Valve 1CV75

10.

N/A S-95-176 950520006 Valve 1SJ150

11.

N/A S-95-026 941112125 Valve 1CV75

12.

N/A S-96-072 950811370 13 RCP Main Flange

13.

N/A S-96-071 950811362 11 RCP Main Flange

14.

N/A S-96-062 950811372 14 RCP Main Flange

15.

N/A S-96-059 950811368 12 RCP Main Flange

16.

N/A S-97-031 960921041 Valve 14MS167

17.

N/A S-97-077 960921040 Valve 12MS167

18.

N/A S-97-232 950527035 Valve 1 PR3 Inlet Flange

19.

N/A S-97-233 951104046 Valve 1 PR4 Inlet Flange

20.

N/A S-97-234 950608024 Valve 1 PR5 Inlet Flange

21.

N/A S-97-263 971107115 Valve 2PS25

22.

N/A N/A N/A Valve 1PR3, 4 & 5 (P.O. - P3-0933105-0630)

The applicable (PSI) examinations were performed with no unacceptable indications identified.

Page: 8 (Rev. 1)

FORM NIS-1 OWNER'.ATA REPORT FOR INSERVICE.PECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1.

Owner Public Service Electric & Gas Co., 80 Park Plaza, Newark, NJ, 07101

2.

Plant Salem Generating Station P.O. Box E, Hancock's Bridge, NJ 08038

3.

Plant Unit Unit 1 (Facility Operating License DPR-70)

4.

Owner's Certificate of Authorization (if Required) N/A

5.

Commercial Service Date 07/01/77

6. National Board Number for Unit 20757
7.

Components inspected (see page 1)

8.
  • Exam Dates February 2, 1994 to April 17, 1998
9.

Inspection Interval from February 27, 1988 to July 7, 2001

10. Applicable Edition of ASME Section XI, 1983, through 1983 Summer Addenda
11. Abstract of Examinations:

11.13 Preservice Examinations on Variuos Component Supports and their Associated Integral Attachments, due to Repair I Replacements Several component supports and their associated integral attachments were replaced I replaced or modified as identified below:

Preservice Examinations on Various Component Supports and their Associated Integral Attachments due to Repair/ Replacement I Modifications ITEM PSE&G DCP PSE&G CJP PSE&G COMPONENT NO.

NO.

NO.

W.0.#

DESCRIPTION

1.

1EC-3323-2 PS-94-036 940811077 MSWG-30

2.

1EC-3323-3 PS-95-033 950913228 S1-SWPG-49

3.

1EC-3396-4 PS-95-070 951114131 Various Aux. Feedwater supports

4.

1EC-3412-1 PS-95-037**

950823379 Various PZR Relief supports

5.

N/A S-95-210 950809300 MSWG-36A

6.

N/A S-95-171 950803107 MSWG-25

7.

1EC-3396-1 PS-95-028 950606218 Various SJ, RHR, & CS supports

8.

N/A S-95-105 950519222 13-FWLS-11

9.

N/A S-95-040 950215277 1 M-SWPS-029

10.

1EE-0102 PS-95-012 950206127 1C-PRH-155

11.

1 EC-3322-1 PS-95-033 940811073 Various Service Water supports

12.

1 EC-3323-1 PS-94-035 950914127 Various Service Water supports

13.

1 EC-3404-1 PS-95-010 950206095 1-PRG-2552

14.

1EC-3322-4 PS-95-035 940811075 Various Service Water supports

15.

1EC-3322-2 PS-94-034 940811076 Various Service Water supports

16.

1EC-3323-3 PS-95-032 950913288 Various Service Water supports

17.

1EC-3323-3 PS-95-050 950914129 Various Service Water supports

18.

1 EC-3476-1 PS-95-078 951001130 1C-13SIH-136 & 1C-11SIA-39

19.

1EE-0282-1 PS-96-142 960523251 Various Service Water supports

20.

1 EC-3525-1 PS-96-001 951212220 Various CVCS supports

21.

1EC-3668-8 PS-97-070 970318111 1 P-11 SWG-005 & 1 P-11 SWS-2 Page: 9 (Rev. 1)

FORM N~S-1 OWNER'.ATA REPORT FOR INSERVICE.PECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1.

Owner Public Service Electric & Gas Co., 80 Park Plaza, Newark, NJ, 07101

2.

Plant Salem Generating Station P.O. Box E, Hancock's Bridge, NJ 08038

3.

Plant Unit Unit 1 (Facility Operating License DPR-70)

4.

Owner's Certificate of Authorization (if Required) N/A

5.

Commercial Service Date 07/01/77

6. National Board Number for Unit 20757
7.

Components inspected (see page 1)

8.

Exam Dates February 2, 1994 to April 17, 1998

9.

Inspection Interval from February 27, 1988 to July 7, 2001

10. Applicable Edition of ASME Section XI, 1983, through 1983 Summer Addenda
11. Abstract of Examinations:

Preservice Examinations on Various Component Supports and their Associated Integral Attachments due to Repair/ Replacement I Modifications ITEM PSE&G DCP PSE&G CJP PSE&G COMPONENT NO.

NO.

NO.

W.0.#

DESCRIPTION

22.

1EC-3668-9 PS-97-071 970318121 Various Service Water supports

23.

1EC-3668-3 PS-97-085 970318099 Various SW (CFCU) supports

24.

1E0-2600-1 PS-97-039 961011186 1CCH-8

25.

1EC-3668-4 PS-97-090 970318103 Various SW (CFCU) supports

26.

1 EC-2668-15 PS-97-092 970318133 1C-13SWG-3A & 38

27.

1EC-3715-3 PS-97-125 970815174 Various CVCS supports

28.

1EC-3668-5 PS-97-091 970318104 Various SW (CFCU) supports

29.

1EC-3668-3 PS-97-084 970318099 Various SW (CFCU) supports

30.

1EC-3715-2 PS-97-116 970818173 Various CS supports

31.

1EC-3668-7 PS-97-129 970318108 Various SW (CFCU) supports

32.

1 EA-1240-1 PS-98-001 970620208 FWH-14-24

33.

1 EA-1240-1 PS-98-002 970525116 FWG-11-3065 & FWG-12-3066 970525067

34.

1EA-1240-1 PS-98-003 970526071 Various S/G Feedwater supports 970526068

35.

1 EC-3343-1 PS-97-049 950218096 S/G platform to S/G lower vertical support PS-97-050 950609102 attachment welds PS-97-051 PS-97-052

36.

N/A S-94-074 940426177 1A-CVCH-408A and 1 A-CVCH-407 A

37.

N/A S-94-049 940413245 1C-PRH-145 and 1C-PRH-149 940424126

38.

N/A S-97-224 970811072 1PRSN29

39.

N/A S-95-161 950523016 1 C-PRSN-401 Page: 10 (Rev. 1)

FORM NJS-1 OWNER'.ATA REPORT FOR INSERVICE.PECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1.

Owner Public Service Electric & Gas Co., 80 Park Plaza, Newark, NJ, 07101

2.

Plant Salem Generating Station P.O. Box E, Hancock's Bridge, NJ 08038

3.

Plant Unit Unit 1 (Facility Operating License DPR-70)

4.

Owner's Certificate of Authorization (if Required) N/A

5.

Commercial Service Date 07/01/77

6. National Board Number for Unit 20757
7.

Components inspected (see page 1)

8.

Exam Dates February 2, 1994 to April 17, 1998

9.

Inspection Interval from February 27, 1988 to July 7, 2001

10. Applicable Edition of ASME Section XI, 1983, through 1983 Summer Addenda
11. Abstract of Examinations:

Preservice Examinations on Various Component Supports and their Associated Integral Attachments due to Repair/ Replacement I Modifications ITEM PSE&G DCP PSE&G CJP PSE&G COMPONENT NO.

NO.

NO.

W.0.#

DESCRIPTION

40.

N/A S-95-220 950523016 1 C-CC-SN001

41.

N/A S-95-157 950523016 1A-CC-SN100B

42.

N/A S-95-159 950523016 1 C-CVCSSN900

43.

N/A S-95-248 950523016 1 C-SISN-501

44.

N/A S-95-221 950523016 1 C-PRSN-023

45.

N/A S-95-158 950523016 1A-SISN-101A

46.

N/A S-97-239 950815548 1 C-SISN-500

47.

N/A S-95-160 950523016 1A-MSASN-147A

48.

N/A S-95-195 950523016 1A-MSANS-147A The applicable (PSI) exams were performed with no unacceptable indications identified.

11.14 Preservice Examinations on Various Piping welds due to Repair/

Replacement I Modifications Several piping welds were repaired I replaced or modified as identified below:

Preservice Examinations on Various Piping welds due to Repair/ Replacement I Modifications ITEM PSE&G PSE&G PSE&G COMPONENT NO.

DCP CJP W.0.#

DESCRIPTION NO.

NO.

1.

NIA S-95-292 931002072 11SJ139 associated piping welds

2.

N/A S-95-349 950623083 11 RHR Pump piping replacement

3.

1EE-0152-1 PS-95-093 951120163 Valve 1 CV55 replacement welds

4.

1EC-3530 PS-96-029 960116178 Safety Injection System orifice addition, socket welds Page: 11 (Rev. 1)

FORM NIS-1 OWNER'~ATA REPORT FOR INSERVICE.PECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1.

Owner Public Service Electric & Gas Co., 80 Park Plaza, Newark, NJ, 07101

2.

Plant Salem Generating Station P.O. Box E, Hancock's Bridge, NJ 08038

3.

Plant Unit Unit 1 (Facility Operating License DPR-70)

4.

Owner's Certificate of Authorization (if Required) N/A

5.

Commercial Service Date 07/01/77

6. National Board Number for Unit 20757
7.

Components inspected (see page 1)

8.

Exam Dates February 2, 1994 to April 17, 1998

9.

Inspection Interval from February 27, 1988 to July 7, 2001

10. Applicable Edition of ASME Section XI, 1983, through 1983 Summer Addenda
11. Abstract of Examinations:

Preservice Examinations on Various Piping welds due to Repair/ Replacement I Modifications ITEM PSE&G PSE&G PSE&G COMPONENT NO.

DCP CJP W.0.#

DESCRIPTION NO.

NO.

5.

N/A S-96-084 960111096 Valve 13SJ143 replacement welds

6.

N/A S-96-398 960506124 Valve 11 RH 10 replacement welds

7.

1EC-3525-1 PS-96-001 951212220 Valves 1CV63 & 1CV141 relocation &

associated welds

8.

N/A S-96-049 951004102 Valve 1CV137 & associated welds

9.

1EC-3530-2 PS-97-029 970623168 Safety Injection System orifice addition, socket welds near valves 11-14SJ 16 The applicable (PSI) examinations were performed with no unacceptable indications identified.

11.15 Preservice Examinations per, DCP# MM-97-099, CJP# S-97-156, Work Order# 970613277 Replacement of the 11 Charging Pump Casing (1 CVE20).

The applicable (PSI) examinations were performed with no unacceptable indications identified.

11.16 Preservice Examinations per, CJP# S-97-257, Work Order# 971108157 Weld repairs to the 100' personnel airlock door seal knife edges.

The (PSI) examinations were performed with no unacceptable indications identified.

Page: 12 (Rev. 1)

FORM NIS-1 OWNER'AATA REPORT FOR INSERVICE.PECT.IONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1.

Owner Public Service Electric & Gas Co., 80 Park Plaza, Newark, NJ, 07101

2.

Plant Salem Generating Station P.O. Box E, Hancock's Bridge, NJ 08038

3.

Plant Unit Unit 1 (Facility Operating License DPR-70)

4.

Owner's Certificate of Authorization (if Required) N/A

5.

Commercial Service Date 07/01177

6. National Board Number for Unit 20757
7.

Components inspected (see page 1)

8.

Exam Dates February 2, 1994 to April 17, 1998

9.

Inspection Interval from February 27, 1988 to July 7, 2001

10. Applicable Edition of ASME Section XI, 1983, through 1983 Summer Addenda 11. Abstract of Examinations:

11.17 Preservice Examinations per, Work Order# 971129120 The 100' personnel airlock inside and outside door (inner and outer) rubber 0-ring seal replacement.

The (PSI) examinations were performed with no unacceptable indications identified.

11.18 Preservice Examinations on four Replacement Steam Generators and their Associated Feedwater, Main Steam and Reactor Coolant piping welds and component supports I integral attachments The Steam Generator Vessel welds, Steam Generator Primary Manway bolting, Reactor Coolant, Feedwater, and Main Steam piping welds and their associated component supports I integral attachments were replaced I repaired and I or modified as identified below:

Preservice Examinations on four Replacement Steam Generators and their Associated Feedwater, Main Steam and Reactor Coolant piping welds and component supports I integral attachments ITEM PSE&G DCP PSE&G REPAIR I REPLACEMENT I MODIFICATION NO.

NO.

P.O.#

DESCRIPTION

1.

N/A P3-0879959

  1. 11 - 14 Steam Generator (S/G) vessel welds were preservice (PSI) examined at the Sea Brook Facility by SwRI after the construction hydro was satisfactorily completed.
2.

EWP#SLM-N/A

  1. 11 - 14 new Steam Generators Primary Manway bolts MOD-04 were replaced with studs and nuts.

3.'

EWP#SLM-N/A

  1. 11 - 14 new Steam Generator Reactor Coolant hot and MOD-07 cold leg tie in welds.
4.

1 EA-1240-11 N/A

  1. 11 SIG Feedwater piping and component support I integral attachment modifications.

Page: 13 (Rev. 1)

FORM NIS-1 OWNER'.ATA REPORT FOR INSERVICE.PECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1.

Owner Public Service Electric & Gas Co., 80 Park Plaza, Newark, NJ, 07101

2.

Plant Salem Generating Station P.O. Box E, Hancock's Bridge, NJ 08038

3.

Plant Unit Unit 1 (Facility Operating License DPR-70)

4.

Owner's Certificate of Authorization (if Required) N/A

5.

Commercial Service Date 07/01/77

6. National Board Number for Unit 20757
7.

Components inspected (see page 1)

8.

Exam Dates February 2, 1994 to April 17, 1998

9.

Inspection Interval from February 27, 1988 to July 7, 2001

10. Applicable Edition of ASME Section XI, 1983, through 1983 Summer Addenda
11. Abstract of Examinations:

Preservice Examinations on four Replacement Steam Generators and their Associated Feedwater, Main Steam and Reactor Coolant piping welds and component supports I integral attachments ITEM NO.

5.
6.
7.
8.
9.
10.
11.
12.

PSE&G DCP PSE&G REPAIR I REPLACEMENT I MODIFICATION NO.

P.O.#

DESCRIPTION 1 EA-1240-12 NIA

  1. 12 SIG Feedwater piping and component support I integral attachment modifications.

1 EA-1240-13 NIA

  1. 13 SIG Feedwater piping and component support I integral attachment modifications.

1 EA-1240-14 NIA

  1. 14 SIG Feedwater piping and component support I integral attachment modifications.

1 EA-1241-11 NIA

  1. 11 SIG Main Steam piping and component support I integral attachment modifications.

1 EA-1241-12 NIA

  1. 12 SIG Main Steam piping and component support I integral attachment modifications.

1 EA-1241-13 NIA

  1. 13 SIG Main Steam piping and component support I integral attachment modifications.

1 EA-1241-14 NIA

  1. 14 SIG Main Steam piping and component support I integral attachment modifications.

EWP#SLM-01 NIA

  1. 11 - 14 new Steam Generator Lower Vertical support modifications SwRI found a rejectable PSI indication on the #14 Steam Generator (S/N 2172) Transition Cone to Shell C weld. The rejectable indication was located at the inside surface, approximately 301 inches clock wise from ISi vessel zero. The rejectable indication was reduced in size by mechanical blending to within acceptable limits.

There were no other unacceptable indications identified.

Page: 14 (Rev. 1)

FORM NIS-1 OWNER'AATA REPORT FOR INSERVICE IPECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1.

Owner Public Service Electric & Gas Co., 80 Park Plaza, Newark, NJ, 07101

2.

Plant Salem Generating Station P.O. Box E, Hancock's Bridge, NJ 08038

3.

Plant Unit Unit 1 (Facility Operating License DPR-70)

4.

Owner's Certificate of Authorization (if Required) N/A

5.

Commercial Service Date 07/01/77

6. National Board Number for Unit 20757
7.

Components inspected (see page 1)

8.

Exam Dates February 2, 1994 to April 17, 1998

9.

Inspection Interval from February 27, 1988 to July 7, 2001

10. Applicable Edition of ASME Section XI, 1983, through 1983 Summer Addenda
11. Abstract of Examinations:

ITEM NO.

1.
2.
3.
4.
5.
6.
7.
8.
9.

11.19 Erosion I Corrosion UT Thickness Program In response to NRC Bulletin 87-01 and Engineering Directive MEC-94-1071, 130 components were scheduled for UT thickness examinations The following Components were replaced, due to the results of the erosion I corrosion UT examinations performed.

SYSTEM COM COMPONENT PONE DESCRIPTION NTID Heater Drain A3 18" Orifice Heater Drain A29 18" X 16" X 12" Tee MSR (Reheat Drains)

C17 3"Tee MSR (Reheat Drains)

C18 3"Tee MSR (Reheat Drains)

C20 3"Tee MSR (Reheat Drains)

C30 3"Tee Misc. Drains H9 3" Orifice Condensate M1 20" Orifice Condensate M12 24" Elbow As a result of these repairs I replacements, and procedural requirements for readings less than 70% of nominal wall, an examination expansion of 35 components was performed. This increased the total number of examinations to 165 components. The following is a break down of these examinations.

a. Nine components were replaced.
b. 156 were acceptable for continued service, based on minimum wall design requirements
c. No components required a weld build-up.

There were no other unacceptable indications identified.

Page: 15 (Rev. 1)

FORM NIS-1 OWNER'IATA REPORT FOR INSERVICE.PECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1.

Owner Public Service Electric & Gas Co., 80 Park Plaza, Newark, NJ, 07101

2.

Plarit Salem Generating Station P.O. Box E, Hancock's Bridge, NJ 08038

3.

Plant Unit Unit 1 (Facility Operating License DPR-70)

4.

Owner's Certificate of Authorization (if Required) N/A

5.

Commercial Service Date 07/01/77

6. National Board Number for Unit 20757
7.

Components inspected (see page 1)

8.

Exam Dates February 2, 1994 to April 17, 1998

9.

Inspection Interval from February 27, 1988 to July 7, 2001

10. Applicable Edition of ASME Section XI, 1983, through 1983 Summer Addenda
11. Abstract of Examinations:

11.20 Technical Specification 4.7.9 (c) Functional Testing of Selected Hydraulic and Mechanical Snubbers HYDRAULIC SNUBBERS (FIRST TEST SAMPLE)

Hydraulic snubbers were tested using the Technical Specification 47.9(c),

10% sample plan by Wyle Laboratories using the API in-place snubber test machine and the Wyle Laboratories model 150 snubber test machine as follows:

Two SIG 1,000 Kip Rexnords One MSIV 200 Kip Paul Monroe One Lisega small hydraulic snubber All hydraulic snubbers tested satisfactorily, except for the one Lisega small snubber.

MECHANICAL SNUBBERS (FIRST TEST SAMPLE)

Mechanical snubbers were tested using the Technical Specification 4.7.9(c), 10% sample plan using the Wyle Laboratories model 150 snubber test machine as follows:

Two Mechanical large (PSA-35) 11 mechanical medium (PSA-1, 3 and 10)

Four mechanical small (PSA-1/4 and 1/2)

All mechanical snubbers tested satisfactorily, except for the two mechanical medium (PSA-1, 3 and 10) snubbers.

HYDRAULIC AND MECHANICAL EXPANDED SNUBBER TEST SAMPLES Due to Hydraulic and Mechanical snubbers test failures the following expanded snubber test samples were tested using the Wyle Laboratories model 150 snubber test machine.

Four snubbers (100% of the Lisega hydraulic snubbers)

Two expanded samples totaling 22 mechanical medium (PSA-1, 3 and 10)

PSE&G Engineering performed a stress evaluation on all failed snubber locations and concluded that the piping and components to which the snubbers were attached were not impaired due to in-operability of the snubbers.

Page: 16 (Rev. 1)

FQRM NtS-1 OWNER'IATA REPORT FOR INSERVICE.PECTIONS AS REQUIRED BY THE PROVISIONS OF THE ASME CODE RULES

1.

Owner Public Service Electric & Gas Co., 80 Park Plaza, Newark, NJ, 07101

2.

Plant Salem Generating Station P.O. Box E, Hancock's Bridge, NJ 08038

3.

Plant Unit Unit 1 (Facility Operating License DPR-70)

4.

Owner's Certificate of Authorization (if Required) NIA

5.

Commercial Service Date 07101177

6. National Board Number for Unit 20757
7.

Components inspected (see page 1)

8.

Exam Dates February 2, 1994 to April 17, 1998

9.

Inspection Interval from February 27, 1988 to July 7, 2001

10. Applicable Edition of ASME Section XI, 1983, through 1983 Summer Addenda
11. Abstract of Examinations:

11.20 Technical Specification 4.7.9 (c) Functional Testing of Selected Hydraulic and Mechanical Snubbers (cont'd)

STEAM GENERATOR REPLACEMENT, MSIV REFURBISHMENT &

MISC.

Sixteen SIG snubbers were removed during the SIG replacement and were returned their position, two SIG snubbers were retested satisfactorily, eight MSIV snubbers were removed for MSIV rebuild and were restored and one retested satisfactorily. Five none Code pre-NF snubbers were found in the Turbine area and tested and were replaced with new snubbers.

HYDRAULIC AND MECHANICAL SNUBBER EXTENDED OUTAGE SAMPLE Due to the extended outage greater than 18 months, the following hydraulic and mechanical snubbers were tested to comply with Technical Specification 4.7.9 (c) (10% sample):

One 1,000 Kip Paul Monroe One 1,000 Kip Rexnord One 200 Kip Paul Monroe snubbers One mechanical large (PSA-35) 11 mechanical medium (PSA-1, 3 and 10) 100% mechanical small (PSA-114 and 112) under a new random sample were previously tested satisfactorily. Thus, no additional testing was required.

Page: 17 (Rev. 1)

11.

Abstract of Examinations (see pages 2 -17)

12.

Abstract of Conditions Notes (see pages 2-17)

13.

A~stract_of Corrective Measures Recommended and Taken (see pages 2-17)

We certify that the statements made in this report are correct and the examinations and corrective measures taken conform to the rules of the ASME Code,Section XI.

Certificate of Authorization No. (if applicable)

~If\\.

Date dL 19 '1'r.Jl Signed PSE&G, Owner By ::...._/"L---::~~====:::s;;;;;;;;::------

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of New Jersey and employed by

. Protection Mutual Insurance Company, OBA Factory Mutual Engineering Association, have inspected the components described in this Owner's Report during the period February 2, 1994 to April 17, 1998, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Page: 18 (Rev. 1)

J