05000255/LER-1996-005-01, Forwards LER 96-005-01 Re DC Panels Breaker/Fuse Coordinate Issue.Ltr Contains No New Commitments

From kanterella
(Redirected from ML18065A879)
Jump to navigation Jump to search
Forwards LER 96-005-01 Re DC Panels Breaker/Fuse Coordinate Issue.Ltr Contains No New Commitments
ML18065A879
Person / Time
Site: Palisades 
Issue date: 08/20/1996
From: Bordine T
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML18065A880 List:
References
NUDOCS 9608280259
Download: ML18065A879 (2)


LER-1996-005, Forwards LER 96-005-01 Re DC Panels Breaker/Fuse Coordinate Issue.Ltr Contains No New Commitments
Event date:
Report date:
2551996005R01 - NRC Website

text

consumers Power POWERING MICHIGAN'S PROGRESS Palisades Nuclear Plant: 27780 Blue Star Memorial Highway, Covert, Ml 49043 August20, 1996 U S Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 DOCKET 50-255 - LICENSE DPR PALISADES PLANT LICENSEE EVENT REPORT 96-005 APPENDIX R ENHANCEMENT ANALYSIS -

DC PANELS BREAKER/FUSE COORDINATION ISSUE - SUPPLEMENTAL REPORT Licensee Event Report (LER) 96-005-01, Supplemental Report is attached. This event is reportable to the NRC in accordance with 10 CFR 50. 73(a)(2)(ii)(B) as a condition outside the plant design basis.

This supplemental report contains corrected information concerning the safety significance portion of the event report and other minor editoral corrections.

SUMMARY OF COMMITMENTS This letter contains no new commitments. The commitments that were previously committed on LER 96-005 are:

1.

Replace main supply fuse to DC Panels ED-11-1 and ED-21-1 with a size and type that coordinate with panel circuit breakers.

- 2. -

Review the settings on branch circuit breakers and adjust as required to coordinate with the newly installed main supply fuses for DC Panels ED-11-1 and ED-21-1.

9608280259 960820 PDR ADOCK 05000255 S

PDR A CMS ENERGY COMPANY

2

3.

Continue hourly fire tours in the 1 F & 1 G Bus Switchgear House, 1 C Switchgear Room, and the Turbine Building until permanent corrective actions are complete for the fuse coordination issue on DC Panels ED-11-1 and ED-21-1.

~~~)..;,

Thomas C. Berdine Manager, Licensing CC Administrator, Region 111, USNRC Project Manager, NRR, USNRC NRC Resident Inspector - Palisades Attachment