Watts Bar Nuclear Plant Pre-Submittal Meeting for Proposed License Amendment Request Regarding 120 V AC Vital Buses December 20, 2017
Opening Remarks System Overview Overview of the 120 volt (V) Alternating Current (AC) Vital Distribution Board and Associated Maintenance Common Load Evaluation Technical Evaluation Highlights Current Vital Bus Testing Requirements Proposed TS 3.8.9 Changes and Basis for Changes Regulatory Precedent Schedule for Submittal Summary and Closing Remarks Agenda l 2
Opening Remarks WBN has transitioned to a two-unit operating site.
Due to the commonality of the vital bus loads, performing maintenance on 120V AC vital buses for a shutdown unit affects operability on the operating unit.
Due to the unique design of the 120V AC vital buses, performing maintenance with one unit operating and the other unit shutdown the current two-hour completion time poses challenges to performing the maintenance of the vital buses within the current two-hour completion of TS 3.8.9 Condition B.
The LAR will extend the completion time from two to eight hours when maintenance is performed on a vital bus on a shutdown unit when the opposite unit is in operation.
l 3
System Overview The onsite Class 1E AC electrical distribution system supplies electrical power to two power trains shared between the two units.
Some safety-related system loads are shared between the units.
Shared loads are distributed across both units 120V AC vital buses.
The core cooling and containment cooling system (ESF) loads are unitized to the respective units shutdown boards and 120V AC vital buses.
l 4
System Overview l 5
120V Vital Distribution Board l 6 Each row bus on the board is seismically supported by the cover. Removal of the cover to access the breakers renders the board inoperable, but available.
Current Vital Bus Testing Requirements Technical Requirement Manual (TRM) Surveillance Requirement (SR) 3.8.1 requires an 18-month functional test on > 10% population of breakers. Some of these breakers are located on the 120V AC vital boards.
FSAR 8.3.1.4.2 states that a 72-month testing is performed of 100% of the Class 1E Molded Case Circuit Breakers (MCCBs) and a 96-month testing is performed of 100% of the non-Class1E MCCBs. Those breakers not impacted by the TRM requirement are impacted by this FSAR requirement.
MCCB panel covers are required for seismic integrity and, therefore operability. MCCBs are not individually bolted, rather held in place by panel covers.
l 7
120V Vital Distribution Board Maintenance l 8 Replace 120V AC Breakers 1.
Replace local panel top bolts and washers with temporary studs.
Remove bottom bolts and washers and slide local panel out along studs. Remove panel as necessary for access to breakers.
2.
Adjust or replace tie-wrap to temporarily support electrical bus bar, as needed.
3.
Remove existing breaker and install replacement breaker, as required.
4.
Torque replacement breaker/ instrument wire connector
120V Vital Distribution Board Load Breaker Access l 9
120V Vital Distribution Board Maintenance (contd) l 10 Maintenance activity on a 120 V AC vital bus necessitates removal of a panel cover that is required to be in place for the seismic integrity of the bus.
There will be less impact to both the vital bus segment and plant LCO if multiple MCCBs may be replaced with each panel cover removal.
Replacing multiple MCCBs or encountering problems with a replacement may jeopardize the current two-hour completion time for a 120V AC vital board, that could result in an unwarranted down power based on the plant configuration and associated load impact.
Technical Evaluation Highlights The eight-hour completion time takes into consideration:
- 1) TS 3.8.9 is in effect for the unit not under outage. The opposite units 120V AC vital boards only supply power to some shared features. The TS LCOs of these shared feature systems are greater than eight hours.
- 2) TS 3.8.10 is in effect for the unit under outage. This TS requires support features of the AC vital bus which is inoperable are to be declared inoperable when in Mode 5 and 6, during movement or irradiated fuel assemblies.
For individual MCCB preventive maintenance requirements, a vital board may remain energized, yet not qualified due to seismic limitations when access cover is removed.
The limited application of the new eight-hour completion to the non-operating unit prevents unnecessary operating plant transients while allowing for performance of maintenance.
This additional flexibility for maintenance increases reliability for both units.
Common System TS Evaluation l 12 TS LCO Applicability LCO Impact 3.3.7 Control Room Emergency Ventilation System (CREVS) Actuation Instrumentation 7 Days 3.3.8 Auxiliary Building Gas Treatment System (ABGTS) Actuation Instrumentation 7 Days 3.6.9 Emergency Gas Treatment System (EGTS) 7 Days 3.7.4 Atmospheric Dump Valves 72 Hours 3.7.7 Component Cooling System (CCS) 72 Hours 3.7.8 Essential Raw Cooling Water (ERCW)
System 72 Hours 3.7.10 Control Room Emergency Ventilation System (CREVS) 7 Days 3.7.11 Control Room Emergency Air Temperature Control System (CREATCS) 30 Days 3.7.12 Auxiliary Building Gas Treatment System (ABGTS) 7 Days
Current TS Requirements l 13 WBN Units 1 and 2 TS 3.8.9, Distribution Systems - Operating, applies when the units are in Modes 1 through 4.
Condition B of TS 3.8.9 requires that when one or more AC vital buses in one channel are inoperable to restore the inoperable AC vital bus(es) to operable status within two hours.
Single unit operation currently requires the eight 120V AC busses to be operable when in Modes 1 through 4 such that a dual unit outage would be required for any maintenance activity extending more than two hours.
As noted in TS Bases 3.9.9.B.1, the current two-hour limit is more conservative than Completion Times allowed for the vast majority of components that are without adequate vital AC power.
Proposed TS 3.8.9 Changes and Basis for Changes The proposed TS 3.8.9 changes will:
Add a new Condition C to increase the completion time for an inoperable AC vital bus channel fed from the opposite unit that is in Modes 4, 5, or defueled from two hours to eight hours.
This change will allow sufficient time for MCCB breaker preventive maintenance.
Board is still energized and operating but it is inoperable from a seismic qualification standpoint.
Recognize the dual unit common load effect by adding this new, separate completion time for the opposite units Vital 120V AC.
As noted previously, the proposed eight-hour completion time is more conservative than the completion times associated with the shared vital loads.
l 14
Proposed TS 3.8.9 Changes and Basis for Changes The proposed TS 3.8.9 changes will also:
Add a new Condition D when one or more Unit 2 AC vital bus in one channel inoperable for reasons other than Condition C with the same completion times as current Condition B l 15
Proposed WBN 1 TS 3.8.9 Changes l 16
Proposed WBN 2 TS 3.8.9 Changes l 17
Proposed WBN 1 TS 3.8.9 Bases Changes l 18
Proposed WBN 2 TS 3.8.9 Bases Changes l 19
Regulatory Precedent While there is no an exact precedent for the proposed change, the eight-hour completion time for the proposed TS 3.8.9 Condition C for an inoperable vital bus is also consistent with other operating nuclear plants TS [e.g., Sequoyah (SQN), Arkansas, Davis-Besse, Farley, River Bend].
The Notes associated with the proposed TS 3.8.9 Condition C are also similar to those in SQN TS 3.8.9, Condition D.
l 20
Schedule for Submittal 12/20/18 - Pre-submittal meeting with NRC 1/31/18 - Submit LAR to NRC Request NRC approval by 1/31/19 with a 60-day implementation date to support the WBN Unit 2 outage scheduled for Spring 2019 (U2R2).
March 2018 - Telecon or meeting to discuss any NRC questions l 21
Summary l 22 Unit Independence Dual Unit Dependence The proposed two to eight-hour completion time increase for an in-operable 120V Vital Board considers the impact of common loads required for an operating unit while providing a window for maximizing maintenance for the opposite unit when under outage conditions.
Closing Remarks Proposed LAR is needed to support a two-unit operating site at WBN.
Due to the commonality of the vital bus loads, performing maintenance on 120V AC Vital buses for a shutdown unit affects operability on the operating unit.
The LAR will extend the completion time from two to eight hours when maintenance is performed on a shutdown unit when the opposite unit is in operation This LAR is needed to support the WBN Unit 1 outage scheduled for Fall 2018.
l 23