EOP:

AP-RCS

~ 3 HIGH REACTOR COOLANT ACTIVITY REV' PAGE 1 of 6 ROCHESTER GAS AND ELECTRIC CORPORATION GINNA STATION CONTROLLED COPY NUMBER TECHNICAL REVIEW PORC REVIEW DATE PLANT SUPERINTENDENT EFFECTIVE DATE CATEGORY 1.0 REVIEWED BY:

9305140024

'730505 PDR ADQCK 05000244 PDR

AP-RCS.3 HIGH REACTOR COOLANT ACTIVITY REV 6

PAGE 2 of 6

A.

PURPOSE This procedure provides guidance necessary to operate the plant with indication of high reactor coolant activity.

B.

ENTRY CONDITIONS/SYMPTOMS 1.

SYMPTOMS The symptoms of. HIGH REACTOR COOLANT ACTIVITY are; a.

Unexplained increase in letdown line monitor, R-9, or b.

Sampling indicates I-131 equivalent GREATER THAN 0.2 uCi/gm, or c.

Sampling indicates gross degassed activity GREATER THAN 20 uCi/gm, or d.

Sampling indicates that total specific activity exceeds 84/E.

EOP:

AP-RCS-3 TITLE:

HIGH REACTOR COOLANT ACTIVITY REV' PAGE 3 of 6 STEP ACTION/EXPECTED RESPONSE

RESPONSE

NOT OBTAINED CAUTION o

IF LETDOWN FLOW EXCEEDS 60

GPM, THEN LOCALLY MONITOR D/P ACROSS THE CVCS DI(S)

TO VERIFY THAT FLOW IS CONTINUING AND THAT RELIEF VALVE, V-209, HAS NOT LIFTED.

o LETDOWN FLOW THROUGH THE DI'S SHOULD BE LIMITED TO 90 GPM.

NOTE:

Conditions should be evaluated for site contingency reporting (Refer to EPIP-1.0, GINNA STATION EVENT EVALUATION AND CLASSIFICATION.

1 Verify RCS Activity:

a. Direct HP to sample RCS for activity b.

RCS activity -

GREATER THAN NORMAL (Check with HP Department for normal activity)

b. IF normal activity verified, THEN direct I&C to check operability of R-9, letdown line
monitor, AND return to normal operations.

EOP:

AP-RCS.3 HIGH REACTOR COOLANT ACTIVITY REV:

6 PAGE 4 of 6

STEP ACTION/EXPECTED RESPONSE

RESPONSE

NOT OBTAINED 2

Increase Letdown Flow To 60 GPM'.

Verify deborating DI isolated DIVERT VLV CATION DEBOR DI AOV-244 IN BYPASS POSITION a.

Place AOV-244 in bypass position.

b. Place letdown controllers in HANUAL at 40%

~ TCV-130

~ PCV-135

c. Increase letdown flow as follows:
1) Close letdown orifice valve (AOV-200A or AOV-200B)
2) Immediately open 60 gpm letdown orifice valve, AOV-202
d. Adjust low pressure letdown pressure to approximateiy 250 psig e.

Place TCV-130 in AUTO at 105'F

f. Place PCV-135 in AUTO at 250 psig g.. Adjust charging pump speed and HCV-142 as necessary

AP-RCS

~ 3 HIGH REACTOR COOLANT ACTIVITY REV:

6 PAGE 5 of 6 STEP ACTION/EXPECTED RESPONSE

RESPONSE

NOT OBTAINED 3

Check Letdown Line Monitor, R-9 LESS THAN 200 MR/HR ABOVE BACKGROUND Evaluate conditions to determine whether local radiation emergency exists (Refer to EPIP 1-13, LOCAL RADIATION EMERGENCY).

CAUTION PLACING A NEW DI IN SERVICE MAY RESULT IN A POSITIVE OR NEGATIVE REACTIVITY ADDITION DUE TO A BORON CHANGE.

4 Direct HP Tech To Sample Letdown DI Efficiency DECONTAMINATION FACTOR GREATER THAN 10 IF DI efficiency is NOT acceptable, THEN place a new mixed bed in service (Refer to S-3.2B, PLACING A MIXED BED DEMINERALIZER IN SERVICE BORON CONCENTRATION DIFFERENT THAN RCS).

5 Evaluate AUX BLDG Radiation Levels:

a. Direct HP to survey AUX BLDG
b. Check AUX BLDG radiation monitors NORMAL

~ R-4

~ R-9

~ R-10B

~ R-13

~ R-14

1) Direct HP Tech to survey AUX BLDG areas as necessary.
2) Evaluate conditions to determine whether local radiation emergency exists (Refer to EPIP 1-13, LOCAL RADIATION EMERGENCY).

EOP:

AP-RCS.3 HIGH REACTOR COOLANT ACTIVITY REV:

6 PAGE 6 of 6

STEP ACTION/EXPECTED RESPONSE

RESPONSE

NOT OBTAINED 6

Determine If Plant Operation Can Continue (Consult Plant staff if necessary)

OPERATION CAN CONTINUE IF plant shutdown is required, THEN refer to 0-2.1, NORMAL SHUTDOWN TO HOT SHUTDOWN.

NOTE:

Refer to 0-9.3, NRC IMMEDIATE NOTIFICATION, for reporting requirements.

7 Notify Higher Supervision