ML17223B108

From kanterella
Jump to navigation Jump to search
Monthly Operating Repts for Jan 1991 for St Lucie Units 1 & 2
ML17223B108
Person / Time
Site: Saint Lucie  
Issue date: 01/31/1991
From: Breen J
FLORIDA POWER & LIGHT CO.
To:
Shared Package
ML17223B107 List:
References
NUDOCS 9102260043
Download: ML17223B108 (8)


Text

AVERAGE DAILY UNIT POWER LEVEL DOCKET NOe 50-335 UNIT St. Lucre 1

DATE FEB 1

COMPLETED BY Z.Z. Breen TELEPHONE 407 465-3550 MONTH Januar 1991 DAY AVERAGE DAILY POWER LEVEL (MWe-Net) 1/ 1/91 1/ 2/91 il 3/91 1/ 4/91.

1/ 5/91 1/ 6/91 1/ 7/91 1/ 8/91 1/ 9/91 1/10/91 1/il/91 1/12/91 1/13/91 1/14/91 1/15/91 1/16/91 1/17/91 i/18/91 1/19/91 1/20/91 1/21/91 1/22/91 1/23/91 1/24/91 1/25/91 1/26/91 1/27/91 1/28/91 1/29/91 1/30/'91 1/31/91 859 858 857 858 857 858 860 858 855 857 857 856 857 833 710 860 864 866 865 866 866 867 866 864 863 865 866 1,05 625 780 785 9102260043 910214 PDR ADOCK 05000335 R

PDR

OPERATTNG STATUS OPF RATING DATA REPORT OQCrET NQ 5()

335 DATE PPg 1 4 199t COMPLETED BY J. J.

BREEN TELEPHONE 407/465/3550 1

~

UNIT NAME:

ST i LUCXE UNIT 2 i REPORTING PERIOD i JANUARY 1991 3,

LICENSED THERMAL POWER (MWT):

27ee NAMEPLATE RATING (GROSS MWE) i 858 5+

DESIGN ELECTRXCAL RATING (NET MWE) i 830 6.

MAXIMUM DEPENDABLE CAPACXTY (GROSS MWE):

872 7

MAXIMUM DEPENDABLE CAPACXTY (NET MWE):

$39 8, IF 'HANGES OCCUR IN CAPACXTY RATINGS (ITEMS NUMBER 3 THROUGH 7)

SINCE LAST REPORT

~

GIVE REASONS+

9i POWER LEVEL TO WHICH RESTRICTED~ IF ANY (NET MWE) le REASONS FOR RESTRXCTIONS IF ANY:

MONTHLY

-YTD-CUMULATIVE lii HOURS XN REPORT PERIODS 12 i NUMBER OF HOURS REACTOR WAS CRITXCAL 13'EACTOR RESERVE SHUTDOWN HOURS 14.

HOURS GENERATOR ON-LINE 15'NIT RESERVE SHUTDOWN HOURS 16+

GROSS, THERMAL ENERGY GENERATED (MWH) 17.

GROSS ELECTRICAL ENERGY GENERATED (MWH) 18'ET ELECTRICAL ENERGY GENERATED (MWH) 19 o

UNXT SERVICE FACTOR 28.

UNIT AVAXLABXLITYFACTOR Zii CAPACITY FACTOR (USING MDC NET) 22 CAPACXTY.FACTOR (USING DER NET) 23.

UNIT FORCED OUTAGE RATE 24'HUTDOWNS SCHEDULED OVER NFXT 6 MONTHS 744 725(5 0.0 721.8 eiO 191637Z 641890 608700 97iO 97' 97' 98o6 OiO 744 725 5

8+0 721 i8 OiO 1916372 641890 6087ee 97ie 97' 97' 98i6 OiO 123720.0 93684iO 205.3 92826il 39i3 239158426 78850530 74501442 75 i 0 750 1 73.6 4i3 25'F SHUT DOWN AT END OF REPORT PERIODr ESTXMATED DATE OF STARTUP:

UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO.

UNIT NAME DATE COMPLETED BY TELEPHONE R8PORTMONTH~JA ARY I 1]

50-335 STLU IE NIT 1

~

FEB f 4 last J. J. BREEN 407 46 -3 50 No.

Date Type Duration (Hours)

Reasons Method of Shutting Down Reactor Licensee Event Report

¹ System Code'omponent Code Cause &Corrective Action to Prevent Recurrence 910128 910128 910129 0.0 B

22.2 B

0.0 F

N/A N/A N/A RC CONROD CONROD ZZZZZZ Reducing power for control rod testing.

Shutdown for control rod testing.

Unit 1 held at 20Fo power for nuclear differential temperature calibration.

F Forced S

Shutdown Reason A - Equipmcnt failure (explain)

B - Maintenance or Test C - Refueling D - Regulatory restriction E - Operator Training dc License Examination F - Administrative G - Operational Error (Expalin)

H - Other (Explain)

Method 1 - Manual 2-Manual Scram 3 - Automatic Scram 4 - Continued 5 - Load Reduction 9 - Other (Explain)

Exhibit G - Instructions for Preparation ofData Entry Sheets Liccnscc Event Report (LER) File (NUREG4161)

Exhibit 1 - Same Source

8UMMARY OF OPERATING EXPERIENCE DOCKET NO ~

50-335 UNIT 8t. Lucie 1

~E COMPLETED BY J.J.

Breen TELEPHONE 407 465-3550 REPORT MONTH JANUARY 1991 On January 28,

1991, Unit 1

commenced a reactor shutdown for control rod testing.

Unit 1 was shutdown for control rod testing from January 28, 1991 until January 29, 1991.

On January 29, 1991, Unit 1 was started back up, but was held at approximately 20% power for nuclear differential temperature instrument calibration.

As of January 31, 1991, Unit 1 was increasing power and was just short of 1004 power.

In accordance with the requirements of Technical Specification 6.9.1.6, there were no challenges to the PORVs or safety valves during the report period.

AVERAGE DAILY UNIT POSER LEVEL DOCKET N00 50-389 UNIT St. Lucre 2

DATE 4

19 COMPLETED BY J.J.

Breen TELEPHONE 407 465-3550 MONTH Januar 1991 DAY AVERAGE DAILY POWER LEVEL (NReqNet):

1/ 1/91 1/ 2/91 1/ 3/91 1/ 0/91 1/ 5/91 1/ 6/91 1/ 7/91 1/ 8/91 1/ 9/91 1/10/91 1/11/91 1/12/91 1/13/91 1/14/91 1/15/91 1/ib/91 1/17/91 1/18/91 1/19/91 1/28/91 1/21/91 1/22/91 1/23/91 1/24/91 1/25/91 1/26/91 1/27/91 1/28/91 1/29/91 1/30/91 1/31/91 868 866 867 867 868 867 868 86T 866 868 868 868 868 869 870 869 869 869 868 869 859 868 868 870 865 869 871 872 869 869 867

OPERATING DATA REPORT OPERATING STATUS DOCI(ET NO 50 389 DATE FEB 1 4 1991 CQMPLETED BY J

~ Ji BREEN TELEPHONE 407/465/3550

i. UNIT NAMEo STi LUCIE UNXT 2 2,

REPORTING PERIOD:

JANUARY 1991 3.

LICENSED THERMAL POHER

< MAT):

~788 4.

NAMEPLATE RATING (GROSS MME) f 850 5.

DESIGN ELECTRICAL RATXNG (NET MHE):

838 6,

MAXIMUM DEPENDABLE CAPACXTY (GROSS MHE> l 882 7.

M*XIMUM DEPENDABLE CAPACXTY <NET MHE)l 839 8,

XF CHANGES OCCUI'N CAPACXTY R*TXNGS <ITEMS NUMBER 3 THROUGH 7)

SINCE LAST REPOli T ~

GXVE REASONS i Vi POWER LEVEL TQ HHICH RESTRICTED'F ANY (NET MHE) 10.

REASONS FOR RESTRICTIONS ~

XF ANYi MONTHLY

-YTD-CUMULATIVE ilo HOURS IN REPORT PERIOD+

12.

NUMBER OF HOURS REACTOR HAS CRITICAL 13.

REACTOR RESERVE SHUTDOHN HOURS 14.

HOURS GENERATOR ON-LXNE 15'NIT RESERVE SHUTDOHN HOURS 16, GROSS THERMAL ENERGY GENERATED (MHH) 17+

GROSS ELECTRIC*L ENERGY GENERATED (MHH) 18'ET ELECTRICAL ENERGY GENERATED (MHH) 19.

UNIT SERVICE F*CTOR 20 UNIT AVAIIABXLXTY FACTOR 21.

CAPACXTY FACTOR (USING MDC NET) 22'AF'ACITY FACTOR (USING DER NET) 23, UNIT FORCED OUTAGE RATE 24'HUTDOWNS SCHEDULED OVER NEXT 6 MONTI.IS 744 744i8 0.8 744i8 8i8 2807740 679688 645780 188i8 100.0 183 5

184i6 0.0 744 744+8 8o8 744.0 0.0 2007740 679688 645780 188i8 188i8 183+5 184i6 8i8 65617i8 55604.3 0.0 54588i3 8i8 142796821 47576600 44979'883 83.2 83i2 83i3 83.4 25 o XF SHUT DOHN AT END OF REPORT PERIOD ~

ESTIMATED DATE OF STARTUF':

UNIT SHUTDOWNS AI'G) POWER REDUCTIONS DOCKET NO.

50-389 UNITNAME ST LUCIE UNIT2 DATE FEB 1 4 1991 COMPLETED BY J. J. BREEN Pi!LEPHQIIE 566065-550 REPORT MONTH JA ARY I I

No.

Date Type Duration (Hours)

Reasons Method of Shutting Down Reactor Licensee Event Report System Code4 Component Codes Cause &Corrective Action to Prevent Recurrence Unit 2 remained at fullpower for the month of January.

F Forced S

Shutdown Reason A - Equipment failure (explain)

B - Maintenance or Test C - Refueling D - Regulatory restriction E - Operator Training 8c Liernse Examination F - Administrative G - Operational Error (Expalin)

H - Other (Explain)

Method 1 - Manual 2-Manual Scram 3 - Automatic Scram 4 - Continued 5 - Load Reduction 9 - Other (Explain)

Exhibit G - Instructions for preparation ofData Entry Sheets Licensee Event Report (LER) File (NUREG4161)

Exhibit 1 - Same Source

SUMMARY

OF OPERATING EXPERIENCE DOCKET NO ~

50-389 UNIT St. Lucie 2

DATE FEB 1

COMPLETED BY J.J.

Breen TELEPHONE 407 465-3550 REPORT MONTH JANUARY 1991 For the month of January Unit 2 remained at full power.

In accordance with the requirements of Technical Specification 6.9.1.6, there were no challenges to the PORVs or safety valves during the report period.