September 24, 1990 Docket Nos. 50-237 and 50-249 Mr. Thomas J. Kovach Nuclear Licensing Manager Commonwealth Edison Company-Suite 300 OPUS West III 1400 OPUS Place Downers Grove, Illinois 60515
Dear Mr. Kovach:
SUBJECT:
INSTALLATION OF HARDENED WETWELL VENT - DRESDEN NUCLEAR POWER STATION, UNITS 2 AND 3 (TAC NOS. 74864 AND 74865)
By letters dated September 4, 1990 and September 17, 1990, Commonwealth Edison Company (CECo) committed to install hardened wetwell vents prior to January 1, 1993 on Dresden, Units 2 and 3.
As per the guidance in Generic Letter 89-16, installation of these hardened vents will be completed under the
. provisions of 10 CFR 50.59.
If you 1dentify any reason to reconsider your commitment to install these vents, or if your schedule for installation should change, the staff should be promptly notified, s i nee any change to your commitment must be approved by the NRC staff..
Sincerely, Original Signed By:
Richard J. Barrett, Director Project Directorate III-2 Division of Reactor Projects - III, IV, V and Special Projects Office of Nuclear Reactor Regulation cc:
See next page
- *.
- 01s1R1B u:r-rn N1
.i L~~~2L~-;*~:__J
- 'JZwolinski
/ijBSiegel 1
- ~~~g: 1 1
- EJordan MS MNBB 3701
- ~,f!::"-:t Plant File*
1*-*1-1 I
,otn MThadani i'-:F-C*
b::.::
OFFICIAL RECORD COPY NRC & Local PDRs DCrutchfield MS 13A2 CMoore OGC ACRS (10)
WShafer Riii
'o-.u
'-MC*
bQ DOCUMENT NAME:[KOVACH 74864/65]
',*r,,,.,.
1:..:'-1..
1'-'
- c*
- ~cc:
tSEE PREVIOUS CONCURRENCE
'*-*O 1
'*5-:o..o.. j
- PDIII-2:LA 11 CMoore 1
!I
- 09/14/90 I
- PD1-2:PM MThadani 09/14/90
Docket Nos. 50-237 and 50-249 Mr. Thomas J. Kovach Nuclear Licensing Manager Conunonwealth Edison Company-Suite 300 OPUS West I II
- 1400 OPUS Place
.Downers Grove, Illinois 60515
Dear Mr. Kovach:
SUBJECT:
- INSTALLATION OF HARDENED WETWELL VENT - DRESDEN flUCLEAR
.. *POWER STATION, UNITS 2 AND 3 (TAC.NOS. 74864 AND 74.865)
By letter dated September 4, 1990, Commonwealth Edison Company (CECo) committed to install a hardened wetwell vent for Dresden, Units 2 and 3. The installatiori of the hardened wetwell vent for both units i~ exp~cted tQ be completed no later than the first calendar quarter of 1993. This project will be completed under the p.ro.visions of*10 CFR 50.59.
If yqu identify any reason to re.consider you*r commitment the staff should be
'promptly notified,- since any.change to your conuni.tment must be approved by the NRC staff.
cc:
See next page
- OISTRiBUTION Docket File".
- PDIII-2 r/f.
-J Zwo l ins k i
- BSiegel EJordan MS MNBB 3701
- Plant File MThadani Sincere)y, Rtchard:J. Barrett,_ Director
.*Project Directorate III-2 Division of.Reactor Projects - III,
. IV, V. and Special Projects Office of Nuclear Reactor Regulation NRC & Local PDRs DCrutchfield MS 13A2 CMoore
.OGC
- ACRS (10)
WShaf er RI II OFFICIAL RECORD COPY CUMENT NAME:[KOVACH 74864/65] -~~-
2
~.P~M-PDIII-~:P BSiege :t
- Thadani
. PDIII-2:PD RBarrett 1 //} /9
'1111190.
I /90
- ~._:
Docket Nos. 50-237 a.nd 50-249 Mr.. Thomas J. Kovach*
UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 September 24, 1990 Nuclear Licensing Manager Commonwealth Edistin Comp~ny-Suite 300 OPUS West III 1400 OPUS Place Downers Grove, Illinois 60515
Dear Mr. Kovach:
SUBJECT:
INSTALLATION OF HARDENED WETWELL VENT *- DRESDEN NUCLEAR POWER STATION, UNITS 2 AND 3 (TAC NOS. 74864 AND 74~65).
By letters d'cttd Sf:'ptemb~r 4, 1990 and September 17~ 1990, Commonwealth Edison.Comp.any (CECo.) con.1nritted to install-hardened wetwell vents prior to January.1; 1993 on Dresden, µnits 2 and 3.
As per the guidance in Generic Letter 89-16, installation of these hardened vents will be completed under the provisions of 10 CFR 50.59.
If.you identify any reason to reconsider your commitment to iristall these.
ve~ts, or if your schedule for installation should chan~e,. the staff should be promptly.notified, since any,.change to -your commitmeri"t must be approved by.the*
NRC staff.
cc:
See next ~~ge Sincerely,
-~*
1 :dlr '
-~*.
Richard
. B~r~ett, Direcio~
Project Directorate III-2 Division of* Reactor Projects ~.rI*I, IV, V and Special Projects Office of' Nuclear Reactor.Regula~ion
".i**
-==--
~
- Mr_~-,Thomas J. Kovach Commonwealth Edison Company cc:
Michael. I. Miller, Esq.
Sidley and Austin One First National Plaza Chicago, Illinois 60690_
Mr. J. Eenigeriburg Plant Superintendent
- Dresden Nuclear Power Station Rura 1 Route #1 Morris, Illinois 60450 U. S. Nuclear Regulatory Corrmission
- Resident Inspectors Office Dresden Station Rural Route #1 Morris, Illinois 60450
- Chairman Board of Supervisors of*
Grundy County..
Grundy County Courthouse
- Morris, Illinois 604?0 Regional Administrator Nuclear*Regulatory Commission, Region III 799 Roosevelt Road, Bldg. #4 G*len-Ellyn, Illinois 60137 Illinois Department of Nuclear Safety.
. Office of Nuclear Facility Safety 1035 Outer Park Drive
- Springfield, Illinois ~2704.
Robert Neumann Office of Public Counsel State of Illinois Cente~
100 W
~** Randolph Suite 11-300
- Chicago, Illinois 60601.
Dresden Nuclear Power Station Unit Nos. 2 and 3