Do~ket No. 50-237 Commonwealth Edison Company ATTN:
Mr. Cordell Reed Senior Vice President Post Office Box 767 Chicago, IL 60690 JANZ It*
SUBJECT:
CONFIRMATORY-ACTION LETTER (C.AL) RIII-90-001
Reference:
January 17, 1990 Confirm,atory Action Letter from A. Bert Davis to Cordell Reed
- Gent 1 emen:
In response to the Dresden Unit 2 reactor scram caused by the loss of the 20 condensate/condensate booster pump, an Augmented Inspection Team (AIT) was established to review your investigation of the equipment failures associated with. the reactor scram.
Our understanding of the elements of your investigative process were outlined in the referenced CAL.
This letter confirms the conversation between Mr. R. Cooper, NRC Branch Chief, Division of Reactor Safety and Mr. J. Eenigenburg, Commonwealth Edison Company Plant Manager, Dresden on January 22, 1990.
Based on this conversation, we*
agreed that the actions you were taking satisfy the requirements of the CAL and therefore, concurred with your decision to restart Unit 2.
We further understand that you will provide a written report of the results of your investigation including root causes and corrective actions for the problems listed iri the CAL within 30 days of the receipt of this letter.
Accordingly, the referenced CAL (RIII-90-001) is terminated.
Sincerely,
- ~;...
"f~; ~** *..
A. Bert Davis*
Regional Administrator See Attached Distribution RII I.
RIII RIII
- RIII RIII NRR Hinds/jp_ Shafer Coopet Miller Grobe Zwolinski 01/ /90 SEE ATTACHED SHEET Rill Greenman RI II Paperiello
Docket No. 50-237 Cormnonwealth Edison Company ATTN:-
Mr. Cordell Reed Senior Vice President Post Office Box 767*
. Chicago, IL 6069~
JAN t *g 1900
SUBJECT:
CONFIRMATORY ACTION LETTER (CAL) RilI-90-001
Reference:
January 17, 1990 Confirmatory Action Letter from A. Bert Davis to Corde 11 Reed Gentlemen:
...I In response to the Dresden Unit 2 reactor scram caused by the loss of the 2D condensate/condensate booster pump, an Augmented Insp~ction Team (AIT) was establi~hed to review your investigation of the equipment failures ass6ciated with the reactor scram.
Our understanding of the elem~nts of your investigative process were outlined in the referenced CAL *
. This letter confirms the conversation between Mr. R. Cooper, NRC Branch Chief, Division of Reactor Safety and Mr. J. Eenigenburg, Cormnonwealth Edison Company.
Plant Manager, Dresden on January 22, 1990.
Based on this conversation, we agreed, that the actions you were taking satisfy the requirements of the CAL and therefore, concurred with your decision to restart Unit 2..
We further understand that you will provide a written report of the results of your investigation including root causes and corrective actions for the problems listed in the CAL within 30 days of the receipt of this letter.
Accordingly, the referenced CAL (RIII-90-001) is terminated.
A. Bert Davis
- Regiona 1 Administrator See Attached Distribution
'-'~II
-t'R~
RIII
. RIII RIII
~u..~>\\
\\\\)* -
r~c1;{
~.tt.\\
.~t.4;{
(.. _ _)f;nds_ljp s'hr*.t.~.r,\\ ',
- per~~ ler',
obe Olh'c>/90 I *J.*'.ltt
~.c
~"'
- RI I I Davis
- Commonwealth Edison Company 2
Distribution cc:
T. Kovach, Nuclear Licensing Manager E. D. Eenigenburg, Station Manager DCD/DCB (RIDS)
Licensing Fee Management Branch Resident Inspector, RIII Richard Hubbard J. W. Mccaffrey, Chief, Public Utilities Division J. Lieberman, OE J. M. Taylor, EDO T. E. Murley, NRR E. L. Jordan, AEOD G. M. Holahan, NRR J. A. Zwolinski, NRR
.J. W. Craig, NRR J. R. Goldberg, OGC H. L. Thompson, DEDS J. W. Clifford, OEDO
. J. G. Partlow, NRR R. J. Strasma, Rill JAN-! _-5 1900