ML17046A483

From kanterella
Jump to navigation Jump to search
9 to Updated Final Safety Analysis Report, Section 10.2, Turbine Generator
ML17046A483
Person / Time
Site: Salem  PSEG icon.png
Issue date: 01/30/2017
From:
Public Service Enterprise Group
To:
Office of Nuclear Reactor Regulation
Shared Package
ML17046A230 List: ... further results
References
LR-N17-0034
Download: ML17046A483 (15)


Text

10.2 TURBINE GENERATOR 10.2.1 Design Bases The Steam and Power Conversion System is designed to convert the heat produced in the reactor to electrical energy.

Heat absorbed by the Reactor Coolant System (RCS) is transferred to the feedwater in four steam generators.

The Feedwater System provides sufficient feedwater flow to the four steam generators where removal of heat from the RCS results in sufficient steam formation to drive the turbine units as follows:

Plant PEPSE)

Gross Output, MWe Net Output, MWe (Power Plant PEPSE)

Gross Output, MWe Anticipated Net Output, MWe 1214 1195 1234 1215 1225 1213 1249 1237 Generator output is limited to 1232 MWe per Artificial Island Operating Guidelines and Documents A-5-500-EEE-1686.

10.2.2 System 10.2.2.1 The turbine is a four-casing, tandem-compound, six flow exhaust, 1800 rpm unit.

The Unit 1 last stage blades are 46 inches long.

The Unit 2 last stage blades are 47 inches long.

The turbine shaft is directly connected to the ac generator.

A brushless exciter (Unit 1) or alternator-exciter (Unit 2) is The is hydrogen cooled with water-cooled coupled to the stator windings.

It is rated at 1, 300, 000 KVA at 7 5 hydrogen pressure, 0. 90 PF, 0. 4 8 SCR, 3

60 cps, 25 KV, and 1800 rpm.

Generator rise, and insulation class are in accordance with the latest ANSI standards.

The voltage regulator has automatic and manual controllers.

The automatically transfers to manual regulation upon an automatic controller problem or circuit initiation.

to manual regulation, the voltage regulation when available.

SGS-UFSAR 10.2-1 After automatic or manual transfer may be transferred to automatic Revision 26 May 21, 2012

The turbine consists of one double-flow high pressure (HP) element in tandem with three double-flow low pressure (LP) elements.

Moisture separation and two stage reheating of the steam is provided between the HP and LP elements utilizing six horizontal-axis, cylindrical-shell, combined moisture separator-reheater assemblies.

Three of these assemblies are located on each side of the LP turbine elements.

Additional moisture removal is accomplished inside the turbine by use of blades constructed with slingers.

The slingers direct the moisture radially to the turbine casing drain passages.

A diagram of the Lubricating Oil System is shown on Plant Drawing 205218. The turbine generator bearings are lubricated by a conventional oil system.

The main lubricating oil pump, a centrifugal volute type, is mounted on the end of the turbine shaft and supplies all of the lubricating oil requirements for the Lubrication System during normal operation.

The ac rnotor-dri ven auxiliary centrifugal lubricating oil pump supplies bearing oil when operating the unit on turning gear during startup and shutdown.

The de rnotor-dri ven emergency lubricating oil pump operates in the event of loss of ac power or failure of the ac rnotor-dri ven pump, to protect the turbine generator bearings during coastdown. The hydraulic lift pump supplies a small quantity of high pressure oil to selected turbine bearings during startup.

The seal oil backup pump provides oil to the Hydrogen Seal System upon loss of the seal oil pump in the Hydrogen Seal System.

Part of the oil in the reservoir is continuously bypassed to an oil purification system.

Lubricating oil is received in the makeup tank and is pumped by the positive displacement pump to either the lubricating oil storage tanks, reservoir or lubricating oil purifier.

10.2.2.2 Stearn Cycle Stearn from each of the four steam generators supplies the tandem-compound turbine generator unit.

The steam enters the HP 10.2-2 SGS-UFSAR Revision 27 November 25, 2013

turbine through four stop valves and four governor control valves.

One stop valve and one control valve form a single assembly.

After expanding through the HP turbine, steam flows through moisture separators and two-stage reheaters to three LP turbines.

A stop valve and an intercept valve are provided at the discharge of each moisture separator-reheater.

feedwater heating are provided.

Six stages of extraction for Stearn from the exhaust of the HP turbine element enters each moisture separator-reheater assembly at one end.

Internal manifolds in the lower section distribute the wet steam.

The steam then rises through chevron plate moisture separators where the moisture is removed and drained to a drain tank from which it is pumped to the main feed pump suction.

The steam leaving the chevron plate separators flows over two tube bundles where it is reheated in two stages.

The moisture separator-reheater of the Stearn and Drains System is shown diagrammatically on Plant Drawings 205245 and 205345. This reheated steam leaves through nozzles in the top of the assemblies and flows to the LP turbines through a stop valve and an interceptor valve located in each reheated steam line.

Two moisture separator-reheater assemblies furnish steam to each of the three LP turbines.

The first stage bundle in the reheater is supplied with extraction steam from the HP turbine and the second stage tube bundle is supplied with main steam (steam generator outlet).

The heating steam condenses in the tubes and the condensate from both reheaters flows to the HP feedwater heater.

10.2.2.3 Turbine Electro-Hydraulic Control System The turbine is equipped with an Electro-Hydraulic Control System to control turbine valve movement.

The system regulates turbine speed prior to the time that the generator is synchronized and controls unit output when the generator is connected to the power grid.

of steam through the turbine.

SGS-UFSAR Control is accomplished by regulating the flow 10.2-3 Revision 27 November 25, 2013

The cont.rol of the main steam at the turbine inlet is accomplished through the use of four stop valves and four control valves.

A hydraulic actuator controls each stop valve so that it is either in the fully open or fully closed position.

The prime function of these stop valves is to shut off the flow of steam to the turbine.

The stop valves are closed immediately by actuation of trip devices (see Section 10.2. 2. 4 below), which are independent of the controller.

The turbine control valves are positioned by a servo-c:.Ictualor which rcc-~sponds to a signal from the cont.roller.

'l'he controller signal po.si tions the control valves for wide-range speed control during startup and for load control after the unit is synchronized on the grid.

1~he reheat stop valves and the reheat interceptor valves control the flow of steam to the LP sections of the turbine.

These valves are closed immediately by actuation of the emergency trip devices.

Overspeed Protection Controller (OPC) is a turbine trip.

See 10.2.2.4.

10.2.2.4 Turbine Protection The following protective devj.ces are independent of the electronic controller and, when initiated, will cause tripping of all turbine valves:

1.

Mechanical overspeed trip

2.

Low bearing oil pressure trip

3.

Low vacuum trip tJ.

Thrust bearing trip 10.2-4 SGS-UE'SAR Revision 23 October 17, 2007

5.

Electrical solenoid trip actuated by:

a.

Reactor trip

b.

Generator electrical trips

c.

Manual trip from Control Room

d.

Loss of electro-hydraulic system control voltage

e.

EHC Overspeed Setpoint (108% or 110%)

f.

Loss of EHC speed signals

g.

Fail to accelerate signals

h.

EHC Power Up

i.

Load Drop Anticipator (LDA)

6.

Manual trip lever located at the turbine

7.

Loss of primary/secondary 24 V de power

8.

High-high steam generator water level or safety injection

9.

Overspeed Protection Controller (OPC) solenoids actuated by:

a.

EHC Overspeed Setpoint (108%)

b.

Load Drop Anticipator (LDA)

The mechanical overspeed trip mechanism consists of an eccentric weight mounted on the end of the turbine shaft, which is balanced in position by a spring until the speed reaches approximately 108 percent of rated speed. Centrifugal force then overcomes the spring force and the weight flies out striking a trigger which actuates the overspeed trip valve and releases the protection system fluid (autostop oil) to drain.

The resulting decrease in autos top pressure causes the governor emergency trip valve to dump the hydraulic fluid to a drain, thereby closing the turbine stop and control valves and the reheat stop and interceptor valves.

The autostop dump valve is also tripped when any one of the previously mentioned protective devices is actuated.

In addition to these devices, other protective features of the Turbine and Stearn System are:

1.

Turbine trip following a reactor trip

2.

Automatic load runback initiated by overpower or overternperature ~T

3.

MSIV in each steam generator steam line

4.

Safety and relief valves in each steam generator steam line

5.

Safety valves mounted on the moisture separator-reheater vessels 10.2-5 SGS-UFSAR Revision 27 November 25, 2013

/

I

6.

Extraction line nonreturn valves

7.

Automatic load runback initiated by generator stator water turbine runback (Unit 2).

8.

Automatic load runback initiated by main feedwater pump trip.

A trip of the turbine generator, when unit load is than a

limit, initiates a

reactor trip to prevent excessive reactor coolant temperature and pressure.

Automatic turbine load runback is initiated by an approach to an overpower or overtemperature condition.

lead to an overpower or Thls will prevent high power which might

~T For Unit 2, an automatic turbine load runback can also be initiated by an input from the stator water turbine runback schemes. Generator runback is initiated by 2 out of 3 logic for low water pressure, 2 out of 3 for outlet water 2 out of 3

, 2 out of 3 for low stator winding water flow or for low bushing water flow when the No. 2 voltage is in the automatic for runback condition.

Stator current is monitored during this runback.

Stator current must less than 79% of rated load at the 2 minute mark and less than 23% of rated load at the 3.5 minute mark or a main turbine winding.

will be initiated.

This will prevent to the Generator An automatic turbine load, runback can also be initiated by a main feedwater pump when turbine power is greater than 69%.

of either The extraction nonreturn valves are closed through an air pilot valve which is actuated by the loss of autostop oil pressure when the turbine generator is tripped.

Overspeed Protection Control (OPC) is a turbine See 10.2.2.4.

To prevent damage to the turbine due to the generator motoring, an electrical reverse power device interlocked with the turbine trip signal is incorporated.

This protective measure ensures that the turbine is before the generator circuit breakers are open, and provides the 30 seconds delay between the turbine trip and the upon detection of condition.

SGS-UFSAR 10.2-6 Revision 26 May 21, 2012

10.2.2.5 Instrumentation Instrumentation is provided to continuously monitor and/or alarm such turbine generator parameters as the following:

1.

Generator load

2.

Shaft vibration at bearings

3.

Shaft eccentricity

4.

Shell expansion

5.

Differential expansion between turbine shell and rotor

6.

Turbine speed

7.

Turbine casing temperatures

8.

Bearing temperatures

9.

Hydrogen gas and stator cooling water temperatures

10.

Generator frequency

11.

Exhaust hood temperature

12.

Condenser vacuum

13.

Stator winding temperatures

14.

Hydrogen pressure and purity

15.

Bearing lube oil and hydraulic oil pressure 10.2.2.6 TURBINE OVERSPEED PROTECTION Turbine Overspeed Protection is provided to protect the turbine from excessive overspeed1 and is required since excessive overspeed of the turbine could generate potentially damaging missiles, which could impact and damage safety-related components, equipment or structures.

The overspeed protection instrumentation consists of five solenoid valves and one trip mechanism, which can be grouped into three independent systems.

These are:

1. Mechanical Overspeed Trip The mechanical overspeed trip valve will dump the autostop oil.

The dump of the autos top oil will open the oil operated interface valve to dump the emergency electro-hydraulic trip fluid.

2. Electrical Overspeed Trip The electrically sensed overspeed will trip two solenoid valves in the turbine trip regular circuit, either of which will dump the autostop oil.

Also, it will trip one solenoid in the turbine trip backup circuit, which I will dump the emergency trip header.

The dump of the autostop oil will open the oil operated interface valve to dump the emergency electro-hydraulic trip fluid.

The solenoid valves associated with the electrical overspeed are also energized by the various generator protection trips.

10.2-6a SGS-OFSAR Revision 23 October 17, 2007

The dump of the autostop oil will actuate a solenoid to dump the emergency elec*tro-hydraulic trip fluid.

This solenoid serves as a backup for both the mechanical and electrical overspeed trips.

The backup solenoid is also energized by the various generator protection trips.

When the F.HC controller receives an input (Auto Stop Oil Pressure Low or 4 I 4 stop valvc,:s closed) that the turbine has been tripped by some external means, it l:oo will issue a turbine trip in order to put the system in a tripped state.

3. Overspeed ProtectJ.on Controller E::i.ther of the two overspeed protection control solenoid dump valves will dump the control electro-hydraulic trip fluid from the main steam governor and stop valves and the reheat intercept valves and stop valves, resulting in a turbine trip.

Limiting Condition for Operation

a. At least one lm~bine over speed protection system shall be operable in Modes l, 2 and 3.

With one stop valve~ or one control valve per h:i.gh pressure turbine steam lead inoperable and/or with one reheat stop valve or one reheat intercept valve per low pressure turbine steam lead inoperable, it is necessary to restore the inoperable valve(s} to operable status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or close at least one valve in the affected steam lead; otherwise isolate the turbine from the steam supply within the next six hours.

b. With the above required turbine overspeed protection system otherwise inoperable, within six hours either restore the system to operable status or isolate the turbine :from the steam supply.

10.2-6b SGS-UFSAR Revision 23 October 17, 2007

Surveillance Requirements

a. Each of the following valves in the Turbine Overspeed Protection System must be demonstrated operable by the direct observation of movement through at least one complete cycle from running position:

Four high-pressure turbine stop valves Four high-pressure turbine control valves Six low-pressure hot reheat stop valves Six low-pressure hot reheat intercept valves

b. The operability testing shall be performed for each of the following conditions~
1. Prior to admitting steam to the turbine during each startup unless performed within the past seven days, unless the requirements have been met by one of the following within the past seven days:

For a planned turbine trip, the requirements may be satisfied by direct visual inspection of each valve during the trip, or For an unplanned shutdown, the requirements may be satisfied by visual inspection of each turbine valve shortly after the trip.

2. Following a startup, within 24 hrs. of attaining manufacturer's recommended power level for performing Turbine Valve Testing.

3, At a frequency not to exceed six months.

Note:

The above valves are to be tested at a frequency and methodology consistent with that presented in WCAP-11525, "Probabilistic Evaluation of Reduction in Turbine Valve Testing Frequency" and WCAP-16054-P, "Probabilistic Analysis Of Reduction In Turbine Valve Tes.t Frequency For Nuclear Plants With Siemens-Westinghouse BB-95/96 Turbines," dated April, 2003, and in accordance with the established NRC acceptance criteria for the probability of a missile ejection incident of l.OE-5 per year, in no case shall the test interval for the above valves exceed six months.

c. The Turbine Overspeed Protection System shall be demonstrated operable:
1. at least once every 18 months by performance of a channel calibration on the Turbine Overspeed Protection Systems, and
2. at least one of the above valves shall be disassembled each 40 months to perform a visual and surface inspection of the valve seats, disks, and stems to verify no unacceptable flaws or corrosion.

If unacceptable flaws or excessive corrosion are found, all other valves of that type shall be inspected.

10.2-7 SGS-UFSAR Revision 23 October 17, 2007

d. The Turbine Overspeed Protection System test frequency must also be verified such that the testing frequency maintains the probability of a missile ejection incident within NRC guidelines.

This verification must be accomplished every two refueling outages or after modifications to the main turbine or turbine overspeed protection valves.

10.2.3 Turbine Missiles The subject of turbine missile characteristics, probability of occurrence and protection of essential safety equipment is covered in Section 3.5.

Section 3. 5 also deals with characteristics of the turbine discs, blades 1 and rot01:s as they relate to the subject of turbine missile formation.

10.?..4 Evaluation Automatic control actions, alarms and trips ar:e initiated by deviations of system variables from preset values.

In every instance automatic control functions are programmed such that appropriate corrective action is taken to protect the RCS as well as the Steam and Power Conversion Systems.

10.2.5 Turbine Generator Test and Inspection

10. 2. 5. 1

'l'urbine Genera tor Mon:L taring Each turbine generator is equipped with supervisory instrumentation that monitor such variables as pressure, temperatures,

flows, speed, vibration, eccentricity, rotor position, casing differential and rotating differential expansion.

In the event that abnormal readings are being receiv(~d, investigations will be made to ascertain the cause of the abnormal readin9s and, if necessary, the unit will be shut down.

Investigations made may consist of nondestructive tests, such as visual 1 magnetic particle, liquid penetrant, ultrasonic and radiographic, where deemed possible.

Periodic inspections will be made as recommended by the turbine generator manufacturer.

10.2-8 SGS-UFSAR Revision 23 October 17, 2007

Detectable flaws will be evaluated by both the turbine generator manufacturer's and owner's technical staff to determine the severity of removal and repair of the flaw.

Relationship to the critical flaw size is a part of this evaluation.

10.2.5.2 Turbine Generator Inspection and Repair Base loaded units are usually operated for a number of years between overhauls, unless operating parameters (such as unusual vibration, pressure and temperature variations throughout the steam path, or bearing temperature indications) indicate the need for an earlier inspection.

The outline of typical procedures for performing turbine and generator repair and inspection is provided below.

If any crack is found in the blading, the blade must either be replaced or cut off in the cracked section or at the blade root section.

Depending upon the physical arrangement of the blading and the contour surfaces that are to be inspected, any of the following nondestructive techniques might be used:

visual magnaflux, magnaglo, liquid penetrant, or ultrasonic.

10.2.5.3 Outline of Typical Procedures for Turbine and Generator Repair and Inspection Prior to Outage The following would be performed prior to shutting down the unit:

1.

Stop and control valves shall be exercised.

2.

Readings shall be taken of temperatures and pressures on oil, water, steam and hydrogen systems.

3.

Inspection of operating equipment will be performed.

10.2-9 SGS-UFSAR Revision 6 February 15, 1987

Outage Competent personnel would maintain schedules of the work to be performed on the turbine generator unit, which would include required replacement parts, rigging requirements, tools, special services (such as air, electric power, etc.).

Schedules would also be maintained for disassembly of component sections of the

unit, such as lagging, cylinder and pedestal covers, piping, thermocouples, wiring, etc.

Coupling alignments would be checked prior to complete disassembly.

Axial and radial clearances would also be checked.

Inspection would be made of pedestals, oil reservoir, seals,

rotors, blading, journals, thrust collars, bearings, spindle, support keys, nozzle blocks, bolting, oil pumps, turning gear, lift pumps, stop and control valves, steam strainers, joints, castings and forgings, cylinder and blade rings and diaphragms.

Grout under the pedestals would also be inspected.

Inspection would also be made of generator parts such as windings, retaining rings, stud assemblies, slot coils, end winding coils, hydrogen ventilating systems, core and magnetic end shields, bushings, gland seal rings, bearings, blower blades and hydrogen coolers.

Such inspections could result in replacements, adjustments, machining, cleaning, realignment, nondestructive testing, etc., as deemed necessary prior to assembly of each part.

Various measurements would be made of journal and bearing bores.

Overspeed mechanism would be exercised by hand.

Balance weight holes would be checked.

Weight locations would be recorded.

Electrical tests would be made as deemed necessary.

Such tests would include air leakage, insulation resistance, impedance and overpotential tests.

In addition to visual inspection of components, nondestructive testing of field retaining rings and blower blades would be conducted as deemed necessary.

10.2-10 SGS-UFSAR Revision 6 February 15, 1987

The following equipment associated with the turbine generator unit would be inspected, cleaned, repaired when necessary, and tested in cooperation with the manufacturer:

1.

Brushless Excitation System

2.

E-H Control System

3.

Lubrication System

4.

Gland Stearn Supply and Exhaust System

5.

Seal Oil and Hydrogen Gas System

6.

Supervisory instruments

7.

Protective devices Records of significant changes, additions, replacements, deviations would be maintained during reassembly of the turbine generator unit. Reassembly of the unit would be in accordance with the manufacturer's accepted practices.

10.2.6 Hydrogen Supply Three banks of storage tubes supply hydrogen through pressure reducing stations to a header, which is pipe sleeve protected.

The header is run underground into the Turbine Building.

Within the building, the header divides to supply hydrogen to each generator through individual pressure regulators.

An emergency header supplies hydrogen individually to each generator through a pressure reducing station.

Hydrogen storage tubes are located in the yard on a concrete pad.

The ground is covered with crushed stone. The Hydrogen Supply System is shown on Plant Drawing 205220.

10.2-11 SGS-UFSAR Revision 27 November 25, 2013

The following protective measures are used to prevent fires and explosions:

1.

Carbon dioxide is used as an intermediate gas when changing from hydrogen to air or air to hydrogen.

2.

Each generator is vented when changing from one gas to another.

3.

Gas changing operations are performed with the generator at standstill or on turning gear.

4.

For Unit 1, a line blind flange, in individual hydrogen piping to the generator, is placed in the blind position to isolate the generator from the hydrogen supply whenever hydrogen is not needed in the generator.

For Unit 2, a spool piece is removed from the hydrogen supply line and blank flanges are installed to isolate the generator from the hydrogen supply whenever hydrogen is not needed in the generator.

10.2.7 Turbine Auxiliaries Cooling System The Turbine Auxiliaries Cooling System, shown on Plant Drawing 205210, provides the cooling water for the following turbine generator auxiliary components:

1.

Generator hydrogen coolers

2.

Generator stator water coolers

3.

Generator exciter coolers

4.

Generator seal oil coolers

5.

Turbine electro-hydraulic control fluid coolers

6.

Gland seal steam condenser

7.

Main bus air cooler 10.2-12 SGS-UFSAR Revision 27 November 25, 2013

8.

Feedwater sample coolers

9.

Bleed steam coil drain pump mechanical seal coolers

10.

Heater drain pump stuffing box water jacket

11.

Condensate and heater drain pump motor upper/lower bearing coolers

12.

Bleed steam coil drain tank pump lube oil coolers

13.

Vacuum pump seal water coolers The system consists of a single closed loop employing condensate quality water as a coolant with the following major components:

1.

Makeup and expansion tank

2.

Main heat exchangers

3.

Pumps The pumps are used to circulate the coolant through the shell side of the main heat exchangers where its heat is given up to service water on the tube side.

The tank provides a makeup water source for the system from the main condensate cycle.

10.2-13 SGS-UFSAR Revision 6 February 15, 1987