9 to Updated Final Safety Analysis Report, Tables 7.3-1 Through 7.3-9
ML17046A416
Person / Time
Site: Salem  
Issue date: 01/30/2017
From:
Public Service Enterprise Group
To:
Office of Nuclear Reactor Regulation
Shared Package
ML17046A230 List: ... further results
References
LR-N17-0034
Download: ML17046A416 (86)


Text

Parameter Reactor Coolant Temperature Pressurizer Pressure Pressurizer Level Steam Flow Steam Pressure SGS-UFSAR TABLE 7.3-1 PROCESS INSTRUMENTATION FOR RPS AND ESF ACTUATION Transmitter Sensors 8 RTDs 4 Transmitters 3 AP Transmitters 8 AP Transmitters 12 Transmitters Read-out c.B. Meter c.s. Meter c.s. Meter c.s. Meter c.a. Meter 1 of 2 Ext.

Ext.

Ext.

Ext.

Ext.

Prot/Safeguards Use 11 trips, T avg permissives Hi/Lo Pressure Trips, SIS R. T.

SIS SIS, Steam Line Isolation Taps 1 each 3 (Top Level) one Shared 3 (Top Level) 3 (Bottom Level) 1 Pair Each 1 Each Revision 17 October 16, 1998

Parameter Steam Generator Level Reactor Coolant Flow Containment Pressure Turbine Steamline Inlet Pressure

  • C.B~ is Control Board SGS-UFSAR TABLE 7.3-1 (Cant)

Transmitter Sensors 12 LlP Transmitters 12 LlP Transmitters 4 Transmitters 2 Transmitters Read-out C.B. Meter C.B. Meter C.B. Meter C.B. Meter 2 of 2 Power Ext.

Ext.

Ext.

Prot /!:)afeguards Use Low Level trip Low Flow Trip SIS (3)

Spray (4)

Cont. Isol.

Set Point Programs and Turbine Power Permissives 1 Pair Each 1 High Pressure Shared/Loop 1 Low Pressure Each 4

1 Each Revision 21 December 6, 2004 I

TABLE 7.3-2 POST-ACCIDENT EQUIPMENT (INSIDE CONTAINMENT)

OPERATIONAL AND TESTING REQUIREMENTS Equipment Name and Tag Number CATEGORY I -

INSTRUMENTATION Pressurizer pressure channels:

PT-455, 456, 457, 474 Pressurizer level channels:

LT-459, 460, 461 Accumulator pressure channels:

PT-936A,B,C,D, 937A,B,C,D Containment sump level channels:

LT-938, 939 Containment sump level channels:

LD-20255 and LD-20256 CATEGORY II - VALVES Containment sump isolation valves:

MOV-8982A,B (11SJ44, 12SJ44}

Accumulator isolation valves:

MOV-8808A,B,C,D (11SJ54, 12SJ54, 13SJ54, 14SJ54)

Fan cooler motors Safeguard equipment power, control, and instrument cable SGS-UFSAR Operating Mode Continuous Continuous During injec-tion phase Continuous Continuous Continuous Duration of Operation 1/2 hr (SI initiation) 1/2 hr 1 hr Available to 1 year Available to 1 year Environmental Testing Required Required Required Not required Required Within 1/2 hr Required after accident During injec-1/2 hr Required tion phase minimum Continuous Available 1 year Continuous Available 1 year 1 of 1 for Required for.

Required Revision 24 May 11, 2009

TABLE 7. 3-3 POSTULATED SUBMERGED ELECTRICAL COMPONENTS IN THE CONTAINMENT FOLLOWING A LOCA Vital Circuits

1.

Motor-operated Valves 1CV284, 1CC187, 1CC190, 1RB2, 1RB26, 12SJ54, 13SJS4, 14SJS4 2

  • Panel Mounted Instruments Panel 232 - PT187, LT470, PT472, SV421, SV422, SV424 Panel 233 - P'l'936A, PT937A, LT934A, LT935A, SV229, SV230, SV231, SV232, SV233 Panel 234 -

PT936B, PT9378, L'l'934B, LT93SB, SV234, SV235, SV236, SV237, SV238 Panel 235 - PT936C, PT937C, LT934C, LT93SC, SV239, SV240, SV241, SV242, SV243 Panel 236 - PT936D, PT937D, LT934D, LT93SD, SV244, SV245, SV246, SV247, SV248 Panel 237 - PTlBB Panel 238 - SV486, SV487, SV488, SV489, SV490, SV491, SV492, SV493 Panel 240 - PT183, SV444 Panel 241 - PT186, PT121, SVllS, SV751, SV757, SV758, SV772, SV773, SV774, SV399, SV397, SV394, SV401, SV518 SV519, SV520, SV521, SV498, SV499, SV500, SV442, E/P(IN'l'JS),

E/P(ICV132)

SGS-UFSAR 1 of 2 Nonvital Circuits Panel 232 - FIC616, SV439, SV931 Panel 233 -

SVS30 Panel 234 -

SVS31 Panel 235 -

SV532 Panel 236 -

SVS33 Panel 237 - FIC613, SV437 Panel 240 - FIC622 Panel 241 - PIC619, SV441, SV528, SV526, SVS23, SV522, SV529, SV527, SVS25, SV524 Revision 16 January 31, 1998

Table 7.3-3 {Cont)

Vital Circuits

3.

Valve Limit Switches Control Valves -

lSJ63, 1SJ123, 1SJ158, lSJlS9, lSJl63, 1SJ166, 11SJ20, 11SJ27, llSJSO, 11SJ57, 11SJ162, l2SJ20, 12SJ27, 12SJSO, 12SJ57, 12SJ162, 13SJ20, 13SJ27, 13SJ57, 13SJ58, 14SJ20, 14SJ27, 14SJ162 1SS103, 1SS104, 1SS107, 1SS110, 1PR14, 1PR17, 1WL7, 1WL98, 1CV2, lCV3 1 lCV4, 1CV5, 1CV75, lCV77, 1CV79, 1CV114, lCV131, 1CV132, 1CV134, 1CV277, 1CV278 Motor-operated Valves -

lCV284, lCC187, 1CC190, 1RH2, 1RH26, 12SJS4, 13SJ54, 14SJ54 Nonvital Circuits Control Valves-1RC4, 11SS93, 125593, l3SS93, 14SS93, 11SS26, 12SS26, 13SS26 14SS26, 11SS32, l3SS32, 1FP85, 1FP90 1FP91, 1FP94

4.

Miscellaneous and Local Mounted Instruments No. 11-14 Reactor Nozzle Support Fans, Triaxial Accelerometer (Seismic Instrument -

Unit 1 only)

FIT159A, FIT159B, FIT158A, FIT158B, FIT157A, FIT157B, FIT156A, FIT156B, SV506, PA7693 No. 11 Containment sump Pump No. 12 Containment sump Pump No. 1 Reactor Sump Pump No. 11 Reactor Coolant Drain Pump No. 12 Reactor Coolant Drain Tank Tank Pump

FIC166, LD-2067, TA-0134, TA-4325,
FIC171, FIC172,
FIC176, TA-0129, TA-2868, TA-0133, TA-1521, TA-4315, TA-4321, LD-7749, LD-7750, LD-7751
5.

Terminal/Junction Boxes *.. Unit 1 (Unit 2)

JTll (JT96), JT12 (JT97), JT13 (JT98),

JT14 (JT99), JT122 (JT123), EJT-210 (EJT-211), JT212 (JT213), EJN-140 {JN148) 2 of 2 SGS-UFSAR JN41 {JT470), JT144, JT420 (JT473),

JT423 (JT424), JT425 (JT426), JS7 (JS8) I JS93 (JS521), JS94 (JS522) I JS95 (JS523),

JS96 (JS524),

JS131 (JS370) I JS132 (JS371) I JS133 (JS372}, JS134 (JS373), JS289, JS290, JS291, JS293, JS29S, JS288, JS292,

JS294, JN31 (JN170),

JN36 (J.N37) 1 JN63 (JS657),

JN64 (JS658),

JN143 (JN144}, JN616 Revision 16 January 31, 1998

TABLE 7.3-4 SAFETY EVALUATION

  • ELECTRICAL COMPONENTS AND CIRCUITS THAT ARE AFFECTED BY THE FLOODING OF COMPONENTS WITHIN THE CONTAINMENT DURING POST*LOCA CONDITIONS*

SUBMERGED ELECTRICAL COMPONENTS IN CONTAINMENT CO!!pOflent Limit Switches eva, eve <1RH2 Motor Operated)

Function Position Indication circuitry for valve 1RH2 NONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS CO!!I)Onent lux Relays 33X/CSV1 33Y/CSV1 Aux Relays l3Z1 SGS-UFSAR Function Position Indication circuitry for valve 1RH2 11SJ45, 11CS36 interlock 125 V DC Distribution Cabinet 1AAOC - Clrcuft 5 Accident/Safety Requirements None Accident/Safety Requirements None Open Permissive 1 of 47 Ar!alvsfs Breaker trip due to submerged component wi ll cause loss of position indication Results IE f facts N/A Analysis Results/Effects Breaker trip due None to submerged CllllflOI"'e!t wf ll cause loss of position indication 11SJ45 safety Safety Function function c~leted will be performed prior to flooding.

11CS36 safety function c~leted by installing Jumpers around interlock Revision 16 January 31, 1998

SUBMERGED ELECTRICAL COMPONENTS IN CONTAINMENT C9!!1!011!0t Function SV*487 Control for valve (Panel 238) 1CV77 (Charging Line to Reactor Coolant Cold Leg)

SV-442 Control for valve (Panel 241) 1CV114 (Reactor Coolant P~ Seal Bypass flow)

Lfmft Switches Position frdtcatfon cvo, eve C1CV77>

circuitry for valve 1CV77 Lfml t Switches Position indication cvo, eve circuitry for valve C1CV114>

1CV114 NONSUBMERGEO ASSOCIATED ELECTRICAL COMPONENTS Conpcm!nt Function Aux Relays valve position irdicatfon for 33X/1Cl 1CV77 and 1CV114 33Y/1CI 33X/SBF 33\\'/SBF SGS*UFSAR TABLE 7.3*4 (Cont) 125 V DC Distribution Cabinet 1AAOC - Circuit 6

~cf9!n~lS&f!tl R~i[~I~S Analvsis None N/A None N/A None II/A None N/A AccfdeotlSafet~ Rsgytrements Analvsfs None N/A 2 of 47 B!!Yl~!leff!!:~s None None None None Besultslfffects None Revision 16 January 31, 1998

TABLE 7.3*4 (Cant) 125 V DC Distribution Cabinet 1AADC

  • Circuit 9 SUBMERGED ELECTRICAL COMPONENTS IN CONTAINMENT Conponent SV*492 (Panel 238)

Lfmft Switches cw, eve <1CV4>

function Control for valve 1CV4 (Containment Isolation Valve)

RG 1.97 Posftfon indication circuitry for valve 1CV4 (lsol Valve)

IONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS Conponent 41\\ux Relays 33X/LOB 33Y/LOB Relay 740C/LOB SGS*UFSAR Function Valve position indication for 1CV4

(!sol Valve)

Provides loss of 125V DC Alarm for 1CV4 control circuit Accident/Safety Requirements Valve 1CV4 closes for an accident (T signal) solenoid valve deenergizes Indicate Containment Isolation Accjd!nt/Safety Requirements None None 3 of 47 Analvsjs Fail close circuitry

  • function performed prior to sl.tlmergence, ftrlCtfon still performed when s!J:nerged s i nee breaker will trip open Breaker trip due to st.bnerged c~nt will cause loss of position indication Analvsis N/A Breaker trip due to submerged COIIflOnents will alarm loss of voltage for this circuit Results/Effects Safety ftrlCtion will be performed Valve 1CV4 safety function wfll be performed. Redundant valve 1CV7 RG 1.97 position indication will indicate containment isolation.

Results/Effects None None Revision 16 January 31, 1998

NONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS CO!!I!O!"!e!lt fii!CtfO!l Aux Relay Provides indication 43LX/LOB of local control Local CMC Provide local Indicating indication of valve Lights (213) posftion, etc SGS*UFSAR TABLE 7.3*4 (Cont) 125 V DC Distribution Cabinet 1AADC

  • Circuit 9 AceidentlSafetl Rsgyfrements Analnis None N/A None N/A

. 4 of 47 Results/Effects None None Revfsfon 16 January 31, 1998

TABLE 7.3-4 (Cont) 125 V DC Distribution Cabinet 1AADC - Circuit 11 SUBMERGED ELECTRICAL CCIIPONENTS JN CONTAINMENT Conponent SY-427 (Panel 245)

Lfml t Switches cvo, eve c1sJ123)

SGS*UFSAR Function Control for valve 1SJ123 (Containment Isolation Valve)

Accid!nt/Safety Requirements Valve 1SJ123 closes for an accident (T signal) solenoid valve deenergizes RG 1.97 Position indication circuitry for valve Indicate Containment isolation 1SJ123 (lsol Valve) 5 of 47 Analysis Fatl close circuitry

  • function performed prior to submergence, function still performed when submerged since breaker will trip open Breaker trip due to submerged COIIJIOI"'eft wi ll cause loss of position fndfcation Results/Effects Safety function will be performed Valve 1SJ123 safety funct ton wt U be performed. Redundant valves 1SJ53, 1SJ60, RG 1.97 position indication will indicate containment isolation.

Revision 16 January 31, 1998

NONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS CO!!J)Onent SV-249 limit Switches cvo, eve C1NT32)

Aux. Relays 33X/1NT32 33Y/1NT32 33X/1SJ123 33Y/1SJ123 Limit Switches cvo, eve C11SJ54 motor operated)

SGS*UFSAR Function control for valve 1NT32 (Containment Isolation Valve)

Position indication circuitry for valve 1NT32 (lsol Valve)

Valve position indication for 1NT32 and 1SJ123 (lsol Valves)

Also 33Y/ *** aux relays provide toss of 125 V DC control voltage or valve out of position alarm Position indication circuitry for valve

-11SJ54 (Ace Discharge)

TABLE 7.3*4 (Cont) 125 V DC Distribution Cabinet 1AADC - Circuit 11 Accid!nt/Safety Requirements Valve 1NT32 closes for an accident (T signal) solenoid valve deenergizes None None None 6 of 47 Analysis Fail close circuit design whether breaker trips or not due to submerged c~nents, solenoid will deenergize (check valve is redundant Isol valve)

Breaker trip due to submerged c~nents wilt alarm loss of control voltage or valve out of position Valve 11SJ54 in position for safety injection with power locked out Results/Effects Safety function will be performed None None None Revision 16 January 31, 1998

NONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS (Cont) conponent Aux Relays 33K/11SJ54 33Y!11SJ54 SGS-UFSAR f\\fiCtion Valve position indication for 11SJ54 (Motor Operated)

TABLE 7.3-4 (Cont) 125 V DC Distribution Cabinet 1AADC - Circuit 11 Accident/Safety Requirements None 7 of 47 Analysis Valve 11SJS4 In position for aafety injection wfth power locked out.

Results/Effects None Revision 16 January 31, 1998

TABLE 7.3-4 (Cont) 125 V DC Distribution Cabinet 1AADC - Circuit 12 SUBMERGED ELECTRICAL COMPONENTS IN CONTAINMENT Conponent SV-506 (MTD on Valve)

Limit Switches eva, eve C1PR17)

SGS*UFSAR Function Control for valve 1PR17 (Containment Isol Valve)

RG 1.97 Position indication circuitry for valve 1PR17 (Isol Valve)

Accfd!nt/Safetx Requfrements Valve 1PR17 closes for an accident (T signal) solenoid valve deenergizes Indicate containment isolation 8 of 47 Analxsis Fail close circuitry -

function performed prior to submergence, function stn l performed when submerged s I nee breaker will trip open Breaker trip due to subnerged c~t wfll cause loss of position indication Results/Effects Safety function will be performed Valve 1PR17 safety function wi ll be performed. Redundant valves 1PR18 RG 1.97 position indication will indicate contain*

ment isolation.

Revision 16 January 31, 1998

NONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS Conponent Aux Relays 95/GAX 96/CIX Relay 74/0C Awe Relays 33X/AV 33Y/AV SGS*UFSAR fli!Ctfon Associated with auto**nual circuitry for valve 1PR17 Provides loss of 125 V DC alarm for circuit 12 Valve position Indication for 1PR17

(!sol Valve)

TABLE 7.3*4 (Cont) 125 v DC Distribution cabinet 1AADC

  • Circuit 12 Accident/Safety Requirements None None None 9 of 47 N/A Breaker trip due to submerged conponents will alarm toss of voltage for this circuit N/A Results/Effects None None None Revision 16 January 31, 1998

TABLE 7.3-4 (Cont) 125 V DC Distribution Cabinet 1AADC - Circuit 41 SUBMERGED ELECTRICAL COMPONENTS IN CONTAINMENT CO!IJ)Onent SV-115 (Panel 241)

Limit switches cvo, eve (1SJ63)

Function Control for valve 1SJ63 (Sl Accumulator Fill)

Position indication circuitry for valve 1SJ63 NONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS CO!IJ)Onent Aux Relays 33X/1SJ63 33Y/1SJ63 SGS*UFSAR Function Valve position indication for valve 1SJ63 Accident/Safety Requirements None None Accident/Safety Requirements None 10 of 47 Analysis N/A N/A Analysis N/A Results/Effects None None Results/Effects None Revision 16 January 31, 1998

SUBMERGED ELECTRICAL COMPONENTS IN CONTAINMENT Component SV*229 (Panel 2l3)

SV-230 (Panel 233)

SV-231 (Panel 233)

SV-232 (Panel 233)

SV-233 (Panel 233)

SV*110 (Panel 245)

  • SGS-UFSAR Function Control for valve 11SJ58 (No. 11 Accumulator Test Line Valve)

Control for valve 11SJ57 (NO. 11 Accumulator Test line Valve)

Control for valve 11SJ20 (No. 11 Accumulator Fill Line Valve)

Control for valve 11SJ27 (No. 11 Accumulator to Reactor Coolant Drain Tank)

Control for valve 11SJ93 (No. 11 Accumulator Nitrogen Supply)

Control for valve 12SJ50 (SI Test Valves)

TABLE 7.3-4 (Cont) 125 V OC Distribution Cabinet 1AADC

  • Circuit 15 Accident/Safety Requirements None None None None None None 11 of 47 Analysis Fail close circuitry Fail close circuitry Fail close circuitry Fail close circuitry Fail close circuitry N/A Results/Effects None None None None None None Revision 14 December 29, 1995

SUBHERGED ELECTRICAl COMPONENTS IN CONTAINHENT Cogponent FLI'ICtion SV-111 control for valve (Panel 245) -

11SJ50 (SI Test Valves)

SV*421 Control for valve (Panel 232) -

1PR15 (Pressurizer Relief Tank Vent Valve)

Limit Switches Position indication cvo, eve <11SJ20, circuitry for valves 11SJ27, 11SJ50, 11SJ20, 11SJ27, 11SJ57 & 12SJ50) 11SJSO, 11SJ57 & 12SJ50 SGS*UFSAR TABLE 7.3*4 (Cant) 125 V DC Distribution Cabinet 1AADC

  • Circuit 15 accjS!Dt£Safetx Rsgyirements Anelvsfs None N/A None N/A None N/A 12 of 47 Results£Effects None None None Revision 16 January 31, 1998

TABLE 7.3*4 (Cont) 125 V DC Distribution cabinet 1AADC - Circuit 15 NONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS (Cont) comonent f\\!letion Accfdent/Safetv Requirements Limit Switches Position indication None cvo, eve (11SJ58 and circuitry for valves 11SJ93) 11SJ58 and 11SJ93 limit Switches Position indication None cvo, eve <1PR15>

circuitry for valve 1Pit15 Aux Relays Valve position None 33X/W indication for 3lY/W 1PR15 Aux Relays Valve position None 33X/11SJ93 indication for 33Y/11SJ93 11SJ93, 11SJ58, 11SJ27, 33X/11SJ58 11SJ57, and 11SJ20 33Y/11SJ58 33X/11SJ27 Also 337/ *** aux 33Y/11SJ27 relays provide atann 33X/11SJ57 either loss of 33Y/11SJ57 control power or 33X/11SJ20 valves out of 33Y/11SJZO position 13 of 47 SGS*UFSAR Analysis N/A N/A N/A Breaker trip due to submerged con-ponents wi ll alarm loss of control voltage or valves out of position Results/Effects None None None None Revision 16 Jal'll.lery 31, 1998

TABLE 7.3-4 (Cont}

125 v DC Distribution Cabinet lAADC - Circuit 15 NONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS (Cont}

Component Results/Effects Limit Switches cvo, eve (1PR15)

Unit 2 only Limit switches cvo, eve (llSJSO and 12SJ50)

Unit 2 only Aux Relays 33X/VV 33'!/VV Unit 2 only AUX Relays 33X/DMV 33Y/DMV SV-1200

{Mounted on valve)

Limit Switches eve, cvo !1DR107)

SGS-UFSAR Function Position Indication Circuitry for valve 1PR15 Position indication circuitry for valves 11SJ50 and 12SJ50 Valve position indication for 1PR15 Valve position indication for 1DR107 Control for valve 1DR107 (demineralized water to component cooling system surge tank inlet)

Position indication circuitry for valve 1DR107 Accident/Safety Requirements

'None N/A None N/A None N/A None N/A None N/A None N/A 14 of 47 Analysis None None None None None None Revision 23 October 17, 2007

TABLE 7.3~4 (Cont) 125 DC Distribution Cabinet 1AADC

  • Circuit Z9 SUBMERGED ELECTRICAL COMPONENTS IN CONTAINMENT Cgmonent SV-518 (Panel 241)

SV*519 (Panel 241)

SV-520 (Panel 241)

SV*521 (Panel 241)

Limft Switches cvo, eve c1ss11o, 1SS107, 1SS104, and 1SS103)

SGS*UFSAR fi.I'ICtion Control for valve 1SS110 (Containment Isolation Valve)

Control for valve 1SS107 (Containment Isolation Valve)

Control for valve 1SS104 (Containment Isolation Valve)

Control for valve 1SS103 (Containment Isolation Valve)

RG 1.97 Position indication circuitry for valves 1SS110, 1SS107, 1SS104 and 1SS103 (Isolation Valves)

Accident/Safety Requirements Valve 1SS110 closes for an accident (T signal) solenoid valve deenergizes Valve 1SS107 closes for an accident (T signal) solenoid valve deenergizes Valve 1SS104 closes for an accident (T signal) solenoid valve deenergizes Valve 1SS103 closes for an accident CT signal) solenoid valve deenergizes Indicate containment isolation 15 of 47 Analysis Fail close circuitry

  • function performed prior to submergence, function still performed when submerged s i nee breaker will trip open Same as above for valve 1SS110 Same as above for valve 1SS110 Same as above for valve 1SS110 Breaker trfp due to submerged C:OIIliOMnt wt ll cause toss of posUion indication Results/Effects Safety function wfll be performed Safety function will be performed Safety function wf l t be performed Safety function will be performed Valves 1SS110, 1SS107, 1SS104 &

1SS103 safety function wi tl be performed.

Redundant valves 1SS64, 1SS49, 1SS33 &

1SS27 RG 1.97 posi*

tfon indication will Indicate containment isolation Revision 16 January 31, 1998

NONSUBMERGEO ASSOCIATED ELECTRICAL COMPONENTS Ccnponent Aux Relays 33X/1 33Y/1 33X/2 33Y/2 33X/3 33YI3 33Xf4 33YI4 SGS*UFSAR Function Valve position indication for 1SS110, 1SS107, 1SS104, and 1SS103 (Isolation valves)

Also for off nonmal alarm or loss of 125 V DC voltage alarm TABlE 7.3*4 (Cont) 125 DC Distribution Cabinet 1AADC

  • Cfrcuit 29 Accid!ot/Safetv Requirements None 16 of 47 Analysis Breelter trip u to sWllerged c~ts will alarm loss of control voltage or valve out of position Results/Effects None Revision 16 Jarwary 31, 1998

SUBMERGED ELECTRICAL COMPONENTS IN CONTAINMENT C9!'11'.!0fle0t SV-486 (Panel 238)

Limit Switches cvo, eve c 1tV75)

Limit Switches CVO, eve C1CV132)

Function Control for valve 1CV15 (Auxtlfary Spray to Pressurizer)

Position indication circuitry for valve 1CV15 Position Indication circuitry for valve 1CV132 (Excess Letdown IIX)

NONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS CCl!!J'.!On(!!!t Aux Relays 33X/CAS 33Y/CAS SGS*UFSAR Function Valve position indication for 1CV75 TABLE 7.3-4 (Cont) 125 V DC Distribution Cabinet 1BBOC - Circuit 7 Accident/Safety Requirements None None None Accident/SafetY Requirements None 17 of 47 Analvsjs N/A N/A N/A Analvsis N/A Results/Effects None None None Results/Effects None Revfsfon 16 January 31, 1998

SUBMERGED ELECTRICAL COMPONENTS IN CONTAINMENT Component SV*244 (Panel 236)

SV-245 (Panel 236}

SV-246 (Panel 236)

SV*247 (Panel 236)

SV-248 (Panel 236) limit Switches cvo, eve <14SJ27, 14SJ20}

SGS*UFSAR Function Control for valve 14SJ93 (No. 14 Accumulator Nitrogen Supply)

Control for valve 14SJ27 (No. 14 Accumulator to Reactor Coolant Orain Tank)

Control for valve 14SJ20 (No. 14 Accumulator Fill Line Valve)

Control for valve 14SJ57 (No. 14 Accwnulator Test Line Valve)

Control for valve 14SJ58 {No. 14 Accumulator Test Line Valve)

Position indication circuitry for valves 14SJ27 and 14SJ20 TABLE 7.3*4 (Cont}

125 V OC Distribution Cabinet 1BBDC Circuit 11 Accident/Safety Requirements None None None None None None 18 of 47 Analysis Fail close circuitry Fail close circuitry Fail close circuitry Fail close circuitry Fail close circuitry N/A Results/Effects None None None None None None Revision 14 December 29, 1995

NONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS Cogponent Aux Relays 33X/14SJ93 33Y/14SJ93 33X/14SJ58 33Y/14SJ58 33lC/14SJ27 33Y/14SJZ7 33lC/14SJ57 33Y/14SJ57 33X/14SJ20 33Y/14SJ20 Limit Switches cvo, eve C14SJ93, 14SJ57, 14SJ58)

SGS*UFSAR fi.I"'Ction Valve position indication for 14SJ93, 14SJ58, 14SJ27 I 14SJ57, and 14SJ20 Also 33Y/ *** aux relays provide alarm either loss of control power or valves out of position Position indication circuitry for valves, 14SJ93, 14SJ57, 14SJ58 TABLE 7.3*4 (Cont) 125 V DC Distribution Cabinet 1BBDC - Circuit 11 Accident/Safety Requirements None None 19 of 47 Analvsis Breaker trip due to submerged c~nts will alarm toss of control voltage or valves out of position N/A ResuUs/Effects None None Revision 14 December 29, 1995

SUBMERGED ELECTRICAL COMPONENTS IN CONTAINMENT Conponent SV*424 (Panel 232)

SV-422 (Panel 232)

Lfmit switches cvo, eve (1PR14>

SGS*UFSAR Function Control for valve 1PR14 (Pressurizer Relief Tank to Coolant Drain Tank Pumps>

Control for valve 1WR82 (Primary Water to Pressurizer Relief Tank Spray Header)

Position indication circuitry for valve 1PR14 TABLE 7.3*4 (Cont) 125 V DC Distribution Cabinet 1BBDC

  • Circuit 16 Accident/Safety Requirements None None None 20 of 47 Af!alnis N/A N/A N/A Results/Effects None None None Revision 14 December 29, 1995

TABLE 7.3-4 (Cent) 125 v DC Distribution Cabinet 1BBDC Circuit 16 NONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS Component Aux Relays 33X/DV 33Y/DV 33X/SV 33Y/SV Aux Relay 33X-1/DV SV413, SV415 SV417, SV419 (Panel 108}

SV414, SV416 SV418, SV420 (Panel 108)

SV1027, SV1028 and SV1055 (Mounted on valve)

{Unit 2 only)

Limit Switches CDO, CDC (1CBV35, 1CBV36)

SGS-UFSAR Function Valve position indication for 1PR14 and 1WR82 Interlock with reactor coolant drain tank pump control circuit Control for valves 11WG42, 12WG42, 13WG42, 14WG42 (Gas decay tank sampling valves)

Control for valves 11WG29, 12WG29, 13WG29, 14WG29 (Gas decay tank inlet valves)

Control for valves HS49 and HS293 (Heating steam condensate return valves) and HS920 (Sampler bypass valve)

Position indication circuitry for dampers 1CBV35, 1CBV36 Accident/Safety Requirements Analysis None N/A None N/A None N/A None N/A None N/A None N/A 21 of 47 Results/Effects None None None None None None Revision 23 October 17, 2007

TABLE 7.3-4 (Cont) 125 V DC Distribution Cabinet 1BBDC - Circuit 16 NONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS (Cont)

Component Relay 74/DC Limit Switches cvo, eve (1WR82)

SV929 (Panel 317)

SV930 (Panel 317)

SV580 (Panel 212)

SV611 (Panel 108)

Limit switches CVO, eve (1WL51)

Limit Switches cvo, eve (1WG41)

SGS-OFSAR Function Provides loss of 125 V DC alarm for circuit 16 Position indication circuitry for valve 1WR82 Control for damper 1CBV35 (Containment Ventilation Vacuum Relief Prefilter Damper)

Control for damper 1CBV36 (Containment Ventilation Pressure Relief Damper)

Control for valve 1WL51 (Liquid Waste Discharge Valve)

Control for valve 1WG41 (Radiation waste gas decay tanks to plant vent}

Position indication circuitry for valve 1WL51 Position indication circuitry for valve 1WG41 Accident/Safety Requirements None None None None None None None None 22 of 47 Analysis Breaker trip due to submerged components will alarm loss of voltage for this circuit N/A N/A N/A N/A N/A N/A N/A Results/Effects None None None None None None None None Revision 23 October 17, 2007

TABLE 7.3-4 (Cont) 125 V DC Distribution Cabinet lBBDC - Circuit 16 NONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS (Cont)

Component Limit Switches CVO, CVC (11WG29, 12WG29, 13WG29, 14WG29)

Limit Switches CDO, CDC (1ABV20)

Aux Relays 33X/PR 33Y/PR 33X/VR 33Y/VR Aux Relay 33X/10 33Y/10 Aux Relay 33X/7 33Y/7 Aux Relay 33X/DD 33Y/DD SGS-UFSAR Function Position indication circuitry for valves 11WG29, 12WG29, 13WG29 and 14WG29 Position indication circuitry for damper 1ABV20 Valve position indication for 1CBV35, 1CBV36 (Containment ventilation vacuum relief prefilter damper and pressure relief damper)

Valve position indication for 1WL51

{Liquid waste discharge valve)

Valve position indication for 1WG41 (Radiation waste gas decay tanks to plant vent)

Valve position indication for 1ABV20 (Diversion damper)

Accident/Safety Requirements Analysis None N/A None N/A None N/A None N/A None N/A None N/A 22a of 47 Results/Effects None None None None None None Revision 23 October 17, 2007

TABLE 7.3*4 (eont) 125 V DC Distribution Cabinet 1BBDC

  • Circuit 17 SUBMERGED ELECTRICAL COMPONENTS IN CONTAINMENT C9!!1X!nent SV*234 (Panel 234)

SV*235 (Panel 234)

SV-236 (Panel 234)

SV*237 (Panel 234)

SV-238 (Panel 234) l f mf t Switches cvo, eve C12SJ57, 12SJ20, 12SJ27) limit Switches cvo, eve C14SJ54>

Motor Operated SGS*UfSAR Func;tfon Control for valve 12SJ58 (No. 12 Accumulator Test Line Valve)

Control for valve 12SJ57 (No. 12 Accumulator Test Line Valve)

Control for valve 12SJZO (No. 12 Accumulator Test Lfne Valve)

Control for valve 12SJ27 (No. 12 Accumulator to Reactor Coolant Drain Tank)

Control for valve 12SJ93 (No. 12 Acc~.~~Ulator Nitrogen Supply)

Position indication circuitry for valves 12SJ57, 12SJ20, and 12SJ27 Position indication circuitry for valve 14SJ54 (Accumulator discharge) ftcc!dent/Safety Requirements None None None None None None None 23 of 47 Analvsis fail close circuitry faiL close circuitry fail close circuitry Fail close circuitry N/A N/A Valve 14SJ54 In position for safety injection with power locked out Results/Effects None None None None None None None Revision 16 January 31, 1998

NONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS CQ!!IX!nent SV-575 (Panel 311)

Aux Relays 33X/1SJ60 33Y/1SJ60 Limit switches cvo, eve (1SJ60)

Aux Relays 33X/12SJ54 33Y/12SJ54 SV-423 (Panel 311)

SGS-UFSAR Function Control for valve 1SJ60 (Contafnnent Isolation Valve)

Valve position indication for 1SJ60 also 33Y/1SJ60 provides alanm either loss of control power or valves out of position Position indication circuitry for valve 1SJ60 Valve position Indication for 12SJ54 (Motor Operated)

Control for valve 1NT25 (Containment lsolatfon Valve)

TABLE 7.3*4 (Cont) 125 V DC Distribution Cabinet 18BOC

  • Circuit 17 Accfd!nt/Safety Requirements Valve 1SJ60 closes for accident (T signal) solenoid valve deenergfles None None None Valve 1NT25 closes for accident (T signal) solenoid valve deenergtzes 24 of 47 Analvsis Fail close circuitry design Nhether breaker trips or not due to submerged c~ts solenof d will deenergi:r.e Breaker trip due to submerged CoqMlN!ntS Wi ll alarm loss of control power or valve out of position N/A Valve 12SJ54 fn position for safety injection Nf th po~~er locked out Fait close circuitry design Nhether breaker trips or not due to submerged c~ts solenoid will deenergize Results/Effects Safety function will be performed None None None Safety function will be performed whether breaker trfps or not due to sl.bnerged CCiq)OI'WltS solenoid wf ll deenergfze Revision 16 January 31, 1998

TABLE 7.3-4 (cont) 125 V DC Distribution Cabinet 1BBOC - Circuit 17 NONSUBMERGED ASSOCIATED ElECTRICAL COMPONENTS (Cont) conponent Function Aux Relays Valve position 33X/12SJ93 indication for 12SJ93, 33Y/12SJ93 12SJ58, 12SJ27, 33X/12SJ58 12SJ57, end 12SJ20 33Y/12SJ58 Also 33Y/ *** eux 33X/12SJ27 relays provide alann 33Y/12SJ27 either loss of control 33X/12SJ57 power or valves out 33Y/12SJ57 of position 33X/12SJ20 33Y/12SJ20 Limit Switches Position indication cvo, eve c12SJ58 circuitry for valves and 12SJ93) 12SJ58 and 12SJ93 SV-505 Control for valve (Mounted on 1PR18 (Containment valve)

Isolation Valve)

SV-507 Control for valve (Mounted on 1WR80 (Containment valve)

Isolation Valve)

Aux Relays Valve position 33X/PWS indication for 33Y/PWS 1NT25, 1PR18, and 33X/NZS 1WR80 33Y/N2S (Isolation Valves) 33X/AV 33Y/AV Limit Switches Position indication cvo, eve, C1NT25, circuitry for valves 1PR18 and 1WR80 1NT25,1PR18, and 1WR80 (Isolation Valves)

SGS*UFSAR Accident/SafetY Requirements None None Valve 1PR18 closes for an accident (T signal) solenoid valve deenergizes Valve 1WR80 closes for an accident (T signal) solenoid valve deenergizes None None 25 of 47 Analysis Breaker trip due to aubnerged cOIJf)OilentS Nill atann loss of control voltage or valves out of positfon N/A Similar analysis as above for SV423 Similar analysis as above for SV423 N/A N/A Results/Effects Nona None Safety Fl.l"lc::tion will be performed Safety Fl.l"lction will be performed None None Revision 16 January 31, 1998

TABLE 7.3-4 (Cont) 125 V DC Distribution Cabinet 188DC - Circuit 17 NONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS (Cont.)

Conponent F~Ntion Accident/Safety Requirements Aux. Relays Valve position indication None 33X/14SJ54 for 14SJ54 (Motor Operated>

33Y/14SJ54 95/GAX Associated with None 96/Cll(

auto-manual circuitry for valve 1PR18 74-1/DC Provides loss of 125V DC None alarm for circuit 17 26 of 47 SGS*UFSAR Analvsjs Valve 14SJ54 fn position for safety injection with power locked out N/A Breaker trip due to submerged cl.:lq)Onents MIll alarm loss of voltage for this circuit Results/Effects None None None Revfsion 16 January 31, 1998

TABLE 7.3-4 (Cant) 125 V DC Distribution Cabinet 1BBDC

  • Circuits 5 & 19 SUBMERGED ASSOCIATED ELECTRICAL COMPONENTS (Cont.)

Conponent 1BBDC BKR 5 SV-489 (Panel 238) 1BBDC BKR 5 SV-490 (Panel 238) 1BBDC BKR 19 SV-491 (Panel 238) 1BBDC BKR 5 Limit Switches cvo, eve c1cv2 and 1CV277) 1BBDC BKR 19 Limit SWitches cvo, eve c1cv3>

SGS*UFSAR Function Control for valve 1CV2 (CVCS Letdown Valve) control for valve 1CV277 (CVCS Letdown Valve)

Control for valve 1CV3 (Containment Isolation Valve)

Position indication circuitry for valves 1CV2 and 1CV277 RG 1.97 Position indication circuitry for valve 1CV3 (lsol Valve)

Accident/Safety Requirements None None Valve 1CV3 closes for accident (T signal) solenoid valve deenergizes None Indicate containment isolation 27 of 47 Analysis N/A N/A Fail close circuitry function performed prior to submergence, function still performed when submerged since breaker will trip open N/A Breaker trip due to submerged component will cause loss of position indication Results/Effects None None Safety function will be performed None Valve 1CV3 safety function will be performed. Redundant valve 1CV7 RG 1.97 position indication wilt indicate containment isolation.

Revision 16 January 31, 1998

NONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS CC!!'I!!O!'!e!Jt SV-425 (Panel 311)

Isolation Valve)

Limit Switches cvo, eve c1cvn Aux Relays 33X/LIC 33Y/LIC SGS*UFSAR Function Control for valve 1CV7 (Contahnent deenerg i zes Position Indication circuitry for valve 1CV7 (Isol Valve)

Valve position indication for 1CV7 (lsol Valve)

TABLE 7.3*4 (Cont) 125 V DC Oistr;butlon Cabinet 1BBDC - Circuit 19 Accident/Safety Requirements Valve 1CV7 closes for accident CT signal) solenoid valve None None 28 of 47 AnaLwis Fail close circuitry design whether breaker trips or not due to submerged c~ts solenoid will deenergize N/A N/A Results/Effects Safety function will be performed None None Revision 16 January 31, 1998

NONSUBMERGEO ASSOCIATED ELECTRICAL COMPONENTS CO!!p:!f!!Ot Function Aux Relays Valve position 33X/LOA indication for 1CV3 33YJLOA (lsol Valve)

Aux Relays Associated with auto*

43X/LOA manuel circuitry for valve 1CV3 Local CMC Provide local Indicating Lights indication of valve (213) posftton, etc Relay Provides loss of 74DC/LTV 125 V DC alarm for circuit 19 SGS*UFSAR TABLE 7.3-4 (Cont) 125 v DC Distribution Cabinet 1BBDC

  • Circuit 19

~ccj~tlSafetx Rsgyirements Analysis None N/A None N/A None N/A None Breaker trip due to subnerged coq:10nents will alarm loss of voltage for this circuit 29 of 47 Resultslgffects None None None None Revision 16 January 31, 1998

TABLE 7.3*4 (Cont) 125 V DC Distribution Cabinet 1BBOC - Circuit 5 NONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS (Cont)

CC!I!!i!9nent Aux Relays 33X1/459 33X2/459 33X3/459 33Y/459 33X1/460 33X2/460 33X3/460 33Y/460 SGS*UFSAR Function Valve position indication for 1CY2 1CV277 Also 33X1/ ***

33X2/ ***

Awe 3313 ***

Relays provide open interlocks for letdown orifice valves 1CV3, 1CV4, and 1CVS 6ccid!nt/Safetv Requirements None 30 of 47 Analvsis N/A Results/Effects None Revision 16 January 31, 1998

SUBMERGED ELECTRICAL COMPONENTS IN CONTAINMENT CO!!I)O!!!!Jt sv~488 (Panel 238) lImit Switches CYO, CVC (1CV79)

F~n:tton Control for valve 1CV79 (Charging l tne to reactor coolant cold leg)

Position indication circuitry for valve 1CV79 NONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS Conponent Awe Relays 33)(/2Ct 33Y/2Ct SGS-UFSAR FU1Ction Valve position indication for 1CV79 TABLE 7.3-4 (Cont) 125 V DC Distribution Cabinet 1CCOC - Circuit 10 Acci4ent/Safety Requirements None None Accident/Safety Requirements None 31 of 47 Analvsis N/A N/A Analvsis N/A Results/Effects None None Results/Effects None Revision 16 January 31, 1998

SUBMERGED ELECTRICAL COMPONENTS IN CONTAINMENT CQ!!I)()nent sv-401 (Panel 241)

SV-394 (Panel 241)

SV*399

<Penel 241) sv~397 (Panel 241)

SV-403 (Panel 246) limit Switches Function Control for valve 1Wl96 (Containment Isolation Valve)

Control for valve 1WL16 (Containment Isolation Valve)

Control for valve 1WL98 (Containment Isolation Valve)

Control for valve 1WL12 (Containment Isolation Valve)

Control for valve 1WL7 (Reactor Coolant Drain Tank Valve)

Position indication TABLE 7.3*4 (Cent) 125 V DC Distribution Cabinet 1CCDC

  • Circuit 13 Accident/Safety Requirements Valve 1WL96 closes for an accident CT signal) solenoid valve deenergfzes Valve 1WL16 closes for an accident (T signal) solenoid valve deenergizes Valve 1WL98 closes for an accident (T signal) solenoid valve deenergizes Valve 1WL1Z closes for an accident (T signal) solenoid valve deenergizes None None Malvafs Fail close circuitry -

function performed prior to sullmergence, fi.A'IC tf on at fl t performed when submerged since breaker will trip open Same as above for valve Ull96 Same as above for valve 1Wl96 same as above for valve 1WL96 N/A cvo, eve C1WL7 circuitry for valves 1WL7

& 1WL98)

N/A

& 1WL98 32 of 47 SGS-UFSAR Results/Effects Safety function wt ll be performed safety function wi ll be performed Safety f1.11ction wi ll be performed Safety function wi ll be performed None None Revision 16 January 31, 1998

NONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS CO!fiX!I'!ef)t Awe Relays 33X/3 33Y/3 33X/4 33Y/4 33X/1 33Y/1 33X/2 33Y/2 Aux Relay 33X/14 Aux Relay 95/1 Aux Relay 95*3 SGS-UFSAR F~n:tion Valve position indication for 1WL98, 1WL12, 1WL96, 1WL16 (lsol Valves)

Valve 1WL12 position Interlock with reactor coolant drain tank pumps Valve 1WL96 isolation function relay Reactor coolant drain tank sampling control via 1WL96 TABLE 7.3-4 (Cont) 125 V DC Distribution Cabinet 1CCDC - Circuit 13 Accident/Safety Requirements None None Relay deenergizes on accident signal to close valve None 33 of 47 Allalvsis N/A N/A Fail safe circuitry design relay will deenergize whether breaker trips or not due to subllerged components N/A Results/Effects None None Safety function wi ll be performed None Revision 16 January 31, 1998

TABLE 7.3-4 (Cont) 125 V DC Distribution Cabinet 1CCOC

  • Circuit 13 NONSUBMERGEO ASSOCIATED ELECTRICAL COMPONENTS (Cont)

C9!!1X!!leDt Relay 74/0C Aux Relay 20/X, 20X1 Aux Relay 20Y, 95/2, end 43/LIC Local Indicating Lights Limit swi tches cvo, eve (1WL96, 1WL 12, and 1WL16)*

SGS*UFSAR F!.!1Ction Provides loss of 125 V DC alann for circuit 13 COIIJIOnCmtS wf ll alann loss of voltage for this circuit Vatve 1WL12 isolation f!.!1Ction relay Part of valve 1WL12 auto-manual circuit Local position indication for valves 1WL98, 1WL12, 1WL96, 1WL7, and 1Wl16 Position indication circuitry for valves 1WL98, 1WL96, 1WL12, and 1WL16 (!sol Valves)

Accident/Safety Requirements None Relay deenergfzes on accident signal to close valve None None None 34 of 47 Analvsfs Breaker trip ct.e to siA:merged Fail safe circuitry design relay wfll deenergbe

..t\\ether breaker trips or not due to submerged c~nents N/A N/A N/A Results/Effects None Safety f!.!1Ct ton wi ll be performed None None None Revision 16 January 31, 1998

TABLE 7.3-4 (Cont) 125 V DC Distribution Cabinet 1CCDC - Circuits 15 & 22 SUBMERGED ELECTRICAL COMPONENTS IN CONTAINMENT 1CCDC CKT 15:

SV-493 (Panel 238) 1CCDC CKT 22:

SV-498 (Panel 241)

SV-499 (Panel 241)

SV-500 (Panel 241>

Limit Switches cvo, eve C1CV134, 1CV131 & 1CV278)

SGS*UFSAR Fli!Ction Control for valve 1CV5 (Containment Isolation Valve control for valve 1CV134 (Excess Letdown HX valve)

Control for valve 1CV131 (Excess Letdown HX valve>

Control for valve 1CV278 (Excess Letdown HX valve)

Position indication circuitry for valves 1CV134, 1CV131 & 1CV278

&ccfd!nt/Safety Requirements Valve 1CV5 closes for an accident (T signal) solenoid deenergizes None None None None 35 of 47 Analvsis Fail close circuitry -

performed prior to submergence, function still performed when st.bnerged since breaker will trip cpen N/A N/A N/A N/A Rnults/Effects Safety fLI"'Ct ion wi ll be performed function None None None None Revision 16 January 31, 1998

TABLE 7.3*4 (Cont) 125 V DC Distribution cabinet 1CCDC

  • Circuits 15 & 22 NONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS Conponent 1CCDC CKT 15:

Aux Relays 33X/LOC 33Y/LOC AUX Relays 43U(/LOC Local CMC Indicating Lights (213)

Relay 74DC 11CCOC CKT 22:

Aux Relays 33X/ELO 33Y/ELD 33X/ELIB 33Y/ELIB 33X/ELIA 33Y/ELIA SGS*UFSAR Function Valve position indication for 1CV5 (lsol Valve)

Associated with auto-manual circuitry for valve 1CV5 Provide local indication of valve position, etc Provides loss of 125V DC alarm Valve position indication for 1CV134, 1CV131, 1CV278 Accident/Safety Requirements None None None None None 36 of 47 Analysis Results/Effects N/A None N/A None N/A None Breaker trip due None to submerged c~nents will alarm loss of voltage for this circuit N/A None Revision 16 January 31, 1998

SUBMERGED ELECTRICAL COMPONENTS IN CONTAINMENT CC!!!)Of'!ent SV-240 (Panel 235)

SV*241

{Panel 235)

SV*242

<Panel 235)

SV*243 (Panel 235) limit switches cvo, eve C13SJ20, 13SJ27, 13SJ57 & 13SJ58)

Lfmft switches cvo. eve (13SJ54 Motor Operated)

SGS*UFSAR Function Control for valve 13SJ93 (No. 13 Accumulator Nitrogen Supply)

Control for valve 13SJ27 (No. 13 Accumulator to Reactor Coolant Drain Tanlt>

Control for valve 13SJ20 (No. 13 Accumulator Fill line Valve)

Control for valve 13SJ57 (No. 13 Accumulator Test Line Valve)

Control for valve 13SJ58 (No. 13 Accumulator Test Line Valve)

Position indication circuitry for valve f3SJ20, 13SJ27, 13SJ57 & 13SJ58 Position indication circuitry for valve 13SJ54 (Ace Discharge)

TABLE 7.3-4 (Cont) 125 V DC Distribution Cabinet 1CCOC

  • Circuit 17 Accid!nt/Safety Requirements None None None None None None None 37 of 47 Analysis Faf l close circuitry Fail close circuitry Fail close circuitry Fall close circuitry Fail close circuitry N/A Valve 13SJ54 in position for safety injectfon with power locked out Resul tstEffects None None None None None None None Revision 16 January 31, 1998

NONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS CQ!!I)Onent Aux Relays 33X/13SJ93 33Y/13SJ93 33X/13SJ58 33Y/13SJ58 33X/13SJ27 33Y/13SJ27 33X/13SJ57 33Y/13SJ57 33X/13SJ20 33Y/13SJ20 Aux Relays 33X/13SJ54 33Y/13SJ54 Limit Switches cvo, eve (13SJ93>

SGS*UFSAR F!!JCtfon Valve position indication for 13SJ93, 13SJ58, 13SJ27, 13SJ57, and 13SJ20 Also 33Y/ *** aux.

relays provide alarm either loss of control power or valves out of position Valve position indication for 13SJ54 (Motor Operated)

Position indication circuitry for valve 13SJ93 TABLE 7.3*4 (Cont) 125 V DC Distribution Cabinet 1CCDC

  • Circuit 17 Accident/Safetv Requirements None None None 38 of 47 Analvsis Breaker trip due to sltlmerged COIJflOI"M!fltS Will alarm loss of control voltage or valve out of position Valve 13SJ54 in position for safety injection with power locked out N/A Resul tstEffects None None None Revision 16 January 31, 1998

TABLE 7.3*4 (Cont) 125 V DC Distribution Cabinet 1CCOC

  • Circuits 20 & 22 SUBMERGED ELECTRICAl COMPONENTS IN CONTAINMENT CO!!pOnent 1CCDC CKT 20:

Limit Switches cov, eve <1RH26>

1CCDC CICT 22:

SV*116 (Panel 245)

SGS*UFSAR Function Position indication circuitry for valve 1RH26 (Motor Operated)

Control for valve 1SJ19 (Accumulator Fltl Valve>

Accjd!nttsafety Requirements Analvsis None N/A None N/A 39 of 47 Results/Effects None None Revision 16 January 31, 1998

TABLE 7.3~4 (Cont) 125 V DC Distribution Cabinet 1CCOC - Circuit 22 NONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS (Cont)

C!!!I!)Onent Relay 74/DC Aux Relays 33X/1SJ19 33YJ1SJ19 F~.r~etion Provides loss of 125 DC alann for circuit Valve position indication for 1SJ19 Accident/Safety Requirements None None 40 of 47 Analvsis Breaker trip clJe to submerged c~ts will alann loss of voltage for this circuit N/A Results/Effects None None Revision 16 January 31, 1998

TABLE 7.3*4 (Cont) 125 V DC Dfstribution Cabinet 1CCOC

  • Circuit 20 NONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS (Cont)

Conponent Limit Switches eva, eve c1sJJO,

1SJ40, 1SJ69)

Aux Relays 33X/1SJ30 33Y/1SJ30 33X/12SJ40 33Y/12SJ40 33X/RSTV 33Y/RSTV 33X/CLIV 33Y/CLIV SGS-UFSAR Function Position indication circuitry for valves 1SJ30, 1SJ40, and 1SJ69 (Motor Operated Valve position indication for 1SJ30, 12SJ40, 1SJ69, and 1RH26 (Motor Operated)

Accfdent/Safetv Requirements None None 41 of 47 Analysis Valves 1SJ30 and 1SJ40 in position for safety injection with power locked out

  • loss of indication will not affect need to operate at some time during recfrc phase of accident
  • position alarm in aux annunciator not affected so that position infonmation is provided Same as above Results/Effects None None Revision 16 January 31, 1998

TABLE 7.3-4 (Cont) 125 V DC Distribution Cabinets 1CCDC Circuit 22 & 1DDC - Circuit 16 NONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS (Cont)

Cqnponent 1CCDC CKT 22:

l fmt t Switches cvo, eve <1SJ19>

F~.R:tion Position indication circuitry for valve 1SJ19 SUBMERGED ELECTRICAL COMPONENTS lN CONTAINMENT 1DDC CICT 16:

sv-m (Panel 241)

SV-773 (Panel 241)

SV-774 (Panel 241)

Limit switches cvo, eve

{1SJ163, 14SJ162)

Function Control for valve 1SJ163 (SI Test Valve)

Control for valve 14SJ162 (SI Test Valve)

Control for valve 13SJ162 (SI Test Valve)

Position indication circuitry for valves 1SJ163, 14SJ162 NONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS CO!!!)Onent AUX Relays 33X/TLVC 331'/TLVC 33X/TLV3 33T/TLV3 33X/TLV4 33f/TLY4 SGS*UFSAR fi.I'ICtion Valve position indication for 1SJ163, 13SJ162, and 14SJ162.

Also 33\\' *** aux relays provide off normal position alarm or loss of 125 V DC control voltage Accident/Safety Requirements None Accident/Safety Requirements None None None None Accfdent/Safetv Requirements None 42 of 47 Analvsfs N/A Analvsis N/A (fall close circuit)

N/A (fail close circuit)

N/A (fail close circuit)

N/A Analysis None Breaker trip due to submerged components will alarm loss of control power or valve out of position Results/Effect!

None Results/Effects None None None None Results/Effects None Revision 16 January 31, 1998

TABLE 7.3*4 (Cont) 125 v DC Distribution cabinet 10DC

  • Circuit 16 NONSUBMERGED ASSOCtATED ELECTRtCAL COMPONENTS (Cont)

Component Limit Switches cvo, eve 13SJ162 SGS*UFSAR Function Position indication circuitry for valve 13SJ162 Accident/Safety Requirements None 43 of 47 Analvsis N/A Results/E1fects None Revision 16 January 31, 1998

SUBMERGED ELECTRICAL COMPONENTS IN CONTAINMENT C0!'!1!9!'1!nt F!.!!Ction SV-757 control for valve (Panel 241) 1SJ163 (SI Test Valve)

SV*771 Control for valve (Panel 245) 1SJ166 (SI Test Valve)

SV*751 Control for valve (Panel 241) 1SJ159 (Sl Test Valve)

SV*75B Control for valve (Panel 241) 12SJ162 (SI Test Valve)

SV*753 Control for valve (Panel 245) 1SJ158 (SJ Test Valve)

L lmf t Switches Position indication cvo, eve circuitry for valves (11SJ162, 11SJ162, 1SJ166, 1SJ166, 1SJ159, 1SJ159, 12SJ162 12SJ162 & 1SJ158)

& 1SJ158 SGS*UFSAR TABLE 7.3*4 (Cont) 125 V OC Distribution Cabinet 1DDC

  • Circuit 28 AccidentlSifetl RggyiremM*ts

!nalxsis None N/A (fail close circuit)

None N/A (fail close ctrcuit)

None N/A (fail close circuit}

None N/A (fail close cfrcutt)

None N/A (faH close circuit)

None N/A 44 of 47 BesultslEff~tl None None None None None None Revision 16 Jai"'UUIry 31, 1998

TABLE 7.3*4 (Cont)

THIS PAGE INTENTIONALLY BLANK 45 of 47 SGS*UFSAR Revision 16 January 31, 1998

NONSUBMERGEO ASSOCIATED ELECTRICAL COMPONENTS CC!!J!Onent Aux Relays 33X/11SJ162 33Y/11SJ162 33X/tSJ166 33Y/1SJ166 33X/1SJ159 33Y/1SJ159 33K/12SJ162 33Y/12SJ162 33K/1SJ158 33Y/1SJ15B SGS*UFSAR F111ction Valve position indication for 11SJ162, 1SJ159, 12SJ162, 1SJ166, and 1SJ158.

Also 33Y/ *** aux relays provide out of position alarm includes 33Y/1SJ53 TABLE 7.3~4 (Cont) 125 V De Distribution Cabinet 10DC - Circuit 28 Accident/Safety Requirements None 46 of 47 Analvsfs Breaker trip due to stilmerged c~ents will alarm loss of control voltage or valve out of position ResultstEffects None Revision 16 January 31, 1998

SUBMERGED ELECTRICAL COMPONENTS IN CONTAINMENT CC!!!I!O!"!e!!t sv-444 (Panel 240)

Function Control for valve 14CV104 (RCP Seal Leak Off)

NONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS CCl!IJ!90!!nt SV-443 (Panel 355)

Limit switches cvo, eve C14WR62, 14CV104)

Aux Relays 33X/SSV 33Y/SSV 33X/SLV 33Y/SLV Function Control for valve 14WR62 (Standpipe Supply)

Position indication circuitry for valve 14WR62 and 14CV104 Valve position Indication for 14CV104 and 14WR62 TABLE 7.3-4 (Cont) 125 V DC Distribution Cabinet 1DDC - Circuit 35 AccfdentiSafety Requirements None Accident/Safety Requirements None None None Analysis N/A Analvsis N/A N/A N/A

  • Circuit protection - entire 125 V de circuit protected by Class tE 15 amp circuit breaker.

47 of 47 SGS*UFSAR Results/Effects None Results/Effects None None None Revision 16 January 31, 1998

TABLE 7.3*5 SAFETY EVALUATION

  • SUBMERGED ELECTRICAL COMPONENTS IN THE CONTAINMENT DURING POST-LOCA CONDITIONS 115 V AC Vital Instrument Bus 1A
  • Circuit 19 SUBMERGED ELECTRICAL COMPONENTS IN CONTAINMENT COII'f)Onent PT-936A (Panel 233)

LT*934A (Panel 233)

PT*937B (Panel 234)

LT-9358 (Panel 234)

SGS*UFSAR FIIICtion AccU~MJlator Pressure No. 11 Acc1.0.1lator level No. 11 Accllll.llator Pressure No. 12 Accllll.llator level No. 12 Control Gr.

Affiliation Process Gr.

Rack 21 Process Gr.

Rack 21 Process Gr.

Rack 21 Process Gr.

Rack 21 Accident/Safety Requt rements Requf red ri.trlng injection phase for Yp to 5 minutes following an accident RG 1.97 Category 3 (EQ not required)

Required ri.tring Injection phase for up to 5 minutes following an accident RG 1.97 Category 3 (EQ not required) 1 of 15 Analysts Instrument wl L l function for the requf red tiM period prior to any flooding - Panel 233 is located at E1. 7811 with the instrument approx. 4

  • up from the bottom Instrument will fi.I'ICtfon for the required time period prior to any flooding Instrument will function for the required ti 11e per1od prior to any flooding
  • Panel 234 is located at £1.78 1 with the instrument approx.

4 1 up from the bottom Instrument wfll function for the required time period prior to any flooding Results/Effects Safety function wilt be performed None Safety function wf U be performed None Revision 16 January 31, 1998

Conponent PT-188 (Panel 237)

FIT-159A (local>

FIT*159B (Local)

SGS-UFSAR Function No. 11 Reactor Coolant PI.I!Jl Seal Water Diff.

Pressure No. 11 Reactor Coolant PI.I!Jl Seal Leakoff Flow No. 11 Reactor Coolant PI.I!Jl Seal Leakoff Flow Control Gr.

Affiliation Process Gr.

Rack 21 Process Gr.

Rack 21 Process Gr.

Rack 21 TABLE 7.3-5 (Cont)

Accident/Safety Requirements None None None Analvsis N/A N/A N/A CIRCUIT PROTECTION - ENTIRE 115V AC CIRCUIT PROTECTED BY CLASS 1E 15 AMP CIRCUIT BREAKER.

Results/Effects None None None INDIVIDUAL PROCESS/PROTECTION CONTROL AND INDICATION LOOPS PROVIDED WITH THEIR OWN FUSE PROTECTED POWER SUPPLY.

2 of 15 Revision 17 October 16, 1998

SUBMERGED ELECTRICAL COMPONENTS IN CONTAINMENT C~t FT414 (Panel 447-1A)

FT*424 (Panel 447*

1D)

FT-434 (Panel 447*

1G)

SGS*UFSAR Function No. 11 Reactor Coolant Loop Flow No. 12 Reactor Coolant Loop Flow No. 13 Reactor Coolant Loop Flow control Gr.

Affiliation Protection Channel I Rack 3 Protection Channel I Rack 3 Protection channel 1 Rack 3 TABLE 7.3*5 (Cont) 115V AC Vital Instrument Bus 1A

  • Circuit 20 Accident/Safety Requirements Provides input to re*

actor trip logic, not requl red for long term accident conditions Provides input to re*

actor trip logic, not required for long term accident conditions Provides input to re-actor trip logic, not required for long term accident conditions 3 of 15 Analysis Instrument is provided for loss of flow pro*

tection. Reactor will trip on safety injection sfgnsl for a Loss*

of-coolant accident.

The loss of the instru-ment due to flooding is acceptable Same analysis as for FT-414 above Same analysis as for FT*414 above Results/Effects Ncne

  • Safety fU'ICtfon is performed None
  • Safety func*

is performed None

  • Safety func*

is performed Revision 16 January 31, 1998

Conponent FT-444 (Panel 447-1K)

SGS-UFSAR Function No. 14 Reactor Coolant Loop Flow Control Gr.

Affiliation Protection Channel I Rack 3 TABLE 7.3-5 (Cont)

Accident/Safety Reaui rements Provides input to re-actor trip logic, not required for long term accident conditions Analysis Same analysis as for PT-414 above CIRCUIT PROTECTION - ENTIRE 115V AC CIRCUIT PROTECTED BY CLASS 1E 15 AMP CIRCUIT BREAKER.

Results/Effects Hone - Safety func-is performed INDIVIDUAL PROCESS/PROTECTION CONTROL AND INDICATION LOOPS PROVIDED WITH THEIR OWN FUSE PROTECTED POWER SUPPLY.

4 of 15 Revision 17 October 16, 1998

TABLE 7.3*5 (Cont)

SAFETY EVALUATION

  • SUBMERGED ELECTRICAL COMPONENTS IN THE CONTAINMENT BUILDING DURING POST LDCA CONDITIONS 115 V AC Vital Instrument Bus 1B
  • Circuit 15 SUBMERGED ElECTRICAL COMPONENTS IN CONTAINMENT Ccqxlnent PT*472 (Panel 232)

LT*470 (Panel 232) level PT*187 (Panel 232)

PT*937A (Panel 233)

LT*935A

<Panel 233)

SGS*UFSAR function Pressurf zer Relief Tank Pressure Pressurizer Relief Tank No. 12 Reactor Coolant Seal Water Dlff.

Pressure ACCUIIAlator Pressure No. 11 AccliiULator level No. 11 Control Gr.

Affi l iatfon Process Gr. 2 Rack 20 Process Gr. 2 Rack 20 Process Gr. 2 Rack 16 Process Gr. 2 Rack 16 Process Gr. 2 Rack 16 Accf dent/Safety Requirements None None None Required during injection phase for up to 5 minutes following an aced dent RG 1.97 Category 3 (EQ not required) 5 of 15 Analysis N/A N/A N/A tnstr~.~~~ent wit l function for the required time period prior to any flooding

  • Panel 233 is located at E1. 78' with the instrument approx. 4 1 up from the bottom Instrument wi ll function for the required time period prior to any flooding Results/Effects None None None Safety function wi ll be performed None Revision 16 January 31, 1998

Component PT-9368 (Panel 234)

LT-9348 (Panel 234)

PT-121 (Panel 241)

E/P Conver-ter(Panet 241)

FIT-158A (Local)

F IT-1588 (Local)

SGS*UFSAR TABLE 7.3-5 (Cont) control Gr.

Accident/Safety Function Affiliation Requirements Analysis Results/Effects AcctJnUlator Process Gr. 2 Required during injection Instrunent will safety function Pressure Rack 16 phase for up to 5 function for the wi ll be performed No. 12 minutes following an required time accident period prior to flooding -

Panel 234 is located at E1.78' with the instrument approx.

4' up from the bottom J

Accllll.llator Process Gr. 2 RG 1.97 Category Ins tr1.111e11t will None Level No. 12 Rack 16 3 (EQ not required) function for the required time period prior to any flooding Excess Let*

Process Gr. 2 None N/A None down Pressure Rack 16 Control for Process Gr. 2 None N/A None Valve 1CV132 Rack 16 No. 12 Reactor Process Gr. 2 None N/A None Coolant P~

Rack 16 Seal Leakoff Flow No. 12 Reactor Process Gr. 2 None N/A None Coolant P~

Rack 16 Seal Leakoff Flow CIRCUIT PROTECTION

  • ENTIRE 115V AC CIRCUIT PROTECTED BY CLASS 1E 15 AMP CIRCUIT BREAKER.

INDIVIDUAL PROCESS/PROTECTION CONTROL AND INDICATION LOOPS PROVIDED WITH THEIR OWN FUSE PROTECTED POWER SUPPLY.

6 of 15 Revision 17 October 16, 1998

TABLE 7.3-5 (Cont.)

115V AC Vital Instrument Bus 18

  • Circuit 16 SUBMERGED ELECTRICAL COMPONENTS IN CONTAINMENT COIIflOfl8nt PT-415 (Panel 447-
18) n-425 (Panel 447-1E)

FT*435

{Panel 447-1H)

Function No. 11 Reactor Coolant Loop Flow No. 12 Reactor coolant Loop Flow No. 13 Reactor Coolant Loop Flow Control Gr.

Afffl fatfon Protection Channel II Rack 7 Protection Channel II Rack 7 Protection Channel II Rack 7 Accident/Safety Requirements Provides input to re*

actor trip Logie, not required for long term accident conditions Provides input to re-actor trip logic, not requf red for long term accident conditions Provides input to re-actor trip logic, not required for long term accident conditions 7 of 15 Analysts Instrument is provided for loss of flow pro-tection. A reactor trip will be inftfated by a safety injectf on signal for the loss-of*

coolant accident. The loss of the instrument due to flooding acceptable Same anal ys f s as for PT-415 above same analysis as for PT-415 above Results/Effects None

  • Safety func*

f s performed None - Safety func*

is performed llone - Safety ftB:*

is performed Revfsfon 16 January 31, 1998

Comoonent FT-445 (Panel 447)

SGS-UFSAR

E\\:nct~ on No. 14 Reactor Coolant Loop Flow Control Gr.

Affiliation Protection Channe: II Rack 7 TPBLE 7.3-5 (Cont.)

Accident/Safety Reauirements re-

10t term conditions Same PT-415 CIRCUIT PROTECTION ENTIRE 115V AC CIRCUIT PROTECTED BY CLIISS lE l5 AMP CIRCUIT BREAKER.

as for INDIVIDUAL PROCESS/PROTECTION CONTROL A.>JD lNDICAT:ON LOOPS PROVIDED WITH THEIR Ol'IN FUSE ?ROTECTED PO\\-IER SUPPLY.

of 15 Revision 25 October 26, 2010 I

TABLE 7.3*5 (Cont.)

115 V AC Vital Instrument Ius 1C - Circuit 12 SUBMERGED ELECTRICAL COMPONENTS IN CONTAINMENT Coqlonent PT*936C (Panel 235)

LT*934C (Panel 235)

PT-9310 (Panel 236)

LT*935D (Panel 236)

SGS-UFSAR FI.I'ICt I on Acc~.~~~o~lator Pressure No. 13 Acc~.~~~o~lator Level No. 13 Acc~.~~~o~lator Pressure No. 14 Acc~.~~~o~tator Level No. 14 Control Gr.

Afftl iatfon Process Gr. 3 Rack 24 Process Gr. 3 Rack 24 Process Gr. 3 Rack 24 Process Gr. 3 Rack 24 Accident/Safety Requirements Required durfng Injection f)hase for up to 5 minutes following an accident RG 1.97 category 3 (EQ not required)

Required during injection phase for up to 5 minutes following an accident RG 1.97 Category 3 (EQ not requl red) 9 of 15 Analysts Instrument wfll function for the required time period prior to any flooding

  • Panel 235 fs located at E1. 78 1 with the Instrument approx. 4
  • up from the bottom Instrument wfll function for the required time period prior to any flooding Instrument wfll function for the required time period prior to any flooding - Panel 236 is located at E1. 781 with the Instrument approx. 41 up from the bottom Instrument will function for the required time period prior to any flooding Results/Effects Safety function wi ll be performed None Safety fl.W'!Ctton wi ll be performed None Revision 16 January 31, 1998

COIII)Onent PT-186 (Panel 241)

FIT*157A (local)

FIT-1578 (local)

SGS-UFSAR Control Gr.

Function Affiliation No. 13 Reactor Process Gr.

Coolant PI.IJ1)

Rack 24 Seal Water Diff. Pressure No. 13 Reactor Process Gr.

Cool ant P1.111>

Rack 24 Seat Leakoff Flow No. 13 Reactor Process Gr.

Coolant P~

Rack 24 Seal Leakoff Flow 3

3 3

TABLE 7.3*5 (Cont.)

Accident/Safety Requirements None None None Analysis N/A N/A N/A CIRCUIT PROTECTION

  • ENTIRE 115V AC CIRCUIT PROTECTED BY CLASS 1E 15 AMP CIRCUIT BREAKER.

Results/Effects None None None INDIVIDUAL PROCESS/PROTECTION CONTROL AND INDICATlON LOOPS PROVIDED WITH THEIR OWN FUSE PROTECTED POWER SUPPLY.

10 of 15 Revision 17 October 16, 1998

TABLE 7.3-5 (Cont)

SAFETY EVALUATION - SUBMERGED ELECTRICAL COMPONENTS IN THE CONTAINMENT DURING POST LOCA CONDITIONS 115 V AC Vital Instrument Bus 1C - Circuit 13 SUBMERGED ELECTRICAL COMPONENTS IN CONTAINMENT Component FT-416 (Panel 447-lC)

FT-426 (Panel 447-1F)

FT-436 (Panel 447-1J)

SGS-UFSAR Function No. 11 Reactor Coolant Loop Flow No. 12 Reactor Coolant Loop Flow No. 13 Reactor Coolant Loop Flow Control Gr.

Affiliation Protection Channel III Rack 12 Protection Channel III Rack 12 Protection Channel III Rack 12 Accident/Safety Requirements Provides input to reactor trip logic, not required for long term accident conditions Provides input to reactor trip logic, not required for long term accident conditions Provides input to reactor trip logic, not required for long term accident conditions 11 of 15 Analysis Results/Effects Instrument is pro-None - Safety func-vided for loss of tion is performed flow protection.

A reactor trip will be initiated by a safety injection signal for the loss-of-coolant accident.

The loss of the instru-ment due to flooding is acceptable Same analysis as FT-416 above Same analysis as FT-416 above None - Safety func-tion is performed None - Safety func-tion is performed Revision 6 February 15, 1987

Conponents FT-446 (Panel 447-1M)

SGS-UFSAR Function No. 14 Reactor Coolant loop Flow Control Gr.

Affiliation Protection Channel I IJ Rack 12 TABLE 7.3-5 (Cont.)

Accident/Safety Requirements Provides input to reactor trip logic, not required for long term accident conditions Analysis Same analysis as FT-416 above CIRCUIT PROTECTION - ENTIRE 115V AC CIRCUIT PROTECTED BY CLASS 1E 15 AMP CIRCUIT BREAKER.

Results/Effects None - Safety func-tion is performed tNDIVIOUAL PROCESS/PROTECTION CONTROL AND INDICATION LOOPS PROVIDED WITH THEIR OWN FUSE PROTECTED POWER SUPPLY.

12 of 15 Revision 17 October 16, 1998

TABLE 7.3~5 (Cont.)

115V AC Vital Instrument Bus 1D - Circuit 7 SUBMERGED ELECTRICAL COMPONENTS JN CONTAINMENT control Gr.

Accident/Safety C~t Function Affiliation Requirements PT-937C AccUIIJlator Process Gr. 4 Required during Injection (Panel 235)

Pressure Rack 28 phase for up to S No. 13 minutes following an accident LT*935C AccUIIJlator Process Gr. 4 RG 1.97 Category (Panel 235)

Level No. 13 Reck 28 3 CEQ not required)

PT*9360 AccUIIJlator Process Gr. 4 Required during Injection (Panel 236)

Pressure Rack 28 phase for up to 5 No. 14 minutes following an accident LT*934D AccUIIJletor Process Gr. 4 RG 1.97 Category (Panel 236)

Level No. 14 Rack 27 3 (EQ not required) 13 of 15 SGS*UFSAR Analysis lnstrunent will function for the required time period prior to any flooding

  • Panel 235 fs located at E1. 78*

with the fnstrunent

  • r:rox. 4 1 up from t e bottom Instrument witt function for the required tfme prior to any flooding Instrument wf l L function for the required time period prfor to any flooding ~

Panel 236 is located at E1.78' with the instrument ~rox.

4 1 up from t e bottom Instrument wfll function for the required time prior to any flooding Results/Effects safety funetion will be performed None Safety function wi ll be performed None Revision 16 January 31, 1998

Component PT-183 (Panel 240)

E/P Converter

<Panel 241>

FIT-156A (local)

FIT-1568 (local)

SGS-UFSAR Function No. 14 Reactor Coolant P~ Seal Water Di ff.

Pressure Control for Valve INT35 No. 14 Reactor Coolant P~ Seal Leakoff Flow No. 14 Reactor Coolant P~ Seal Lealcoff Flow Control Gr.

Affiliation Process Gr. 4 Rack 27 Process Gr. 4 Rack 28 Process Gr. 4 Rack 28 Process Gr. 4 TABLE 7.3-5 (Cont.)

Accident/Safety Regui rements None None None None Analvsis N/A N/A N/A N/A CIRCUIT PROTECTION - ENTIRE 115V AC CIRCUIT PROTECTED BY CLASS 1E 15 AHP CIRCUIT BREAKER.

Results/Effects None None None None INDIVIDUAL PROCESS/PROTECTION CONTROL AND INDICATION LOOPS PROVIDED WITH THEIR OWN FUSE PROTECTED POWER SUPPLY.

14 of 15 Revision 17 october 16, 1998

TABLE 7.3-5 (Cont.)

115V AC Vital Instrument Bus 10

  • Circuit 13 SUBMERGED ELECTRICAL COMPONENTS IN CONTAINMENT Caq:Jonent Triaxial Accelero*

meter f~M~Ction Seismic lnstnnentatfon Control Gr.

Affiliation N/A Acchlent/Safety Requirements None Analysis N/A Results/Effects None CIRCUIT PROTECTION

  • ENTIRE 115V AC CIRCUIT PROTECTED BY CLASS 1E 15 AMP CIRCUIT BREAKER.

ONLY THE SEISMIC INSTRUMENTATION SYSTEM IS CONNECTED TO THIS CIRCUIT.

15 of 15 SGS*UFSAR Revision 16 January 31, 1998

TABLE 7.3-6 SAFETY EVALUATION

  • ELECTRICAL COMPONENTS AND CIRCUITS THAT ARE AFFECTED BY THE FLOODING OF COMPONENTS WITHIN THE CONTAiNMENT DURING POST*LOCA CDNDJTIDNS*

230V AC Vital Control Center 1A Ventilation - Circuit Section 1D SUBMERGED ELECTRIC COMPONENTS IN CONTAINMENT c~nt No. 11 Reactor No:u.le Support Fan SGS-UFSAR Function Nozzle Support Vent System Accident/Safety Requirements None 1 of 14 Analysis N/A Results/Effects None Revision 16 January 31, 1998

TABLE 7.3*6 (Cont) 230V AC Vital Control Center 1A Ventilation* Circuit Section 1D NONSUBMERGED ELECTRIC COMPONENTS IN CONTAtNMENT C~nent Aux. Relays 33X 63X 23X Aux. Relays 6X, 3X, 6Y and Starter Relay Relay 6 Relay 74/AC SV-912 (Panel 247*1A)

FD*7670 (local)

T0-7671 (Local)

Limit Switch coo for o....,er 1CBV34 SGS*UFSAR Function Alarm Circuitry forD~ Posi*

tfon, Low Air Flow, HI Air T ~rature for No. 11 Reactor Nozzle s~rt Vent System Fan and D&ll'per Operation Control Provides Loss of 115V AC Control Voltage for No. 11 Circuit Control for Damper 1CBV34 (No. 11 Reactor Nozzle Support Fan)

Low Flow Alarm for No. 11 Reactor support Vent System Ki Temperature Alarm for No.

Reactor support Vent System Position Indication Circuitry for Damper Accident/safety Requirements None None None None None 11 None None 2 of 14 Analysis N/A N/A 23DV Breaker/

Control Cf rcuft fuse trip due to slbnerged CafiJIO*

nents will alarm loss of control voltage for this circuit N/A N/A N/A N/A Resut ts/Effects None None None None None None Revision 16 January 31, 1998

TABLE 7.3-6 (Cont) 230V AC Vital Control Center 1B Ventilation* Circuit Section 1D SUBMERGE~ ELECTRIC COMPONENTS IN CONTAINMENT c~nt No. 12 Reactor Nozzle Support Fan SGS*UFSAR FlWICtion Nozzle support Vent System Accident/Safety Requirements None 3 of 14 Analysis N/A Results/Effects None Revision 16 January 31, 1998

TABLE 7.3-6 (Cont) 230V AC Vital Control Center 18 Ventilation

  • Circuit Section 1D NONSUBMERGED ELECTRIC COMPONENTS IN CONTAINMENT CCIIJf)Oflent Aux. Relays 33X 63X 23X Aux. Relays 6X, 3X, 6Y, and Starter Relay 6 Relay 74/AC SV-913 (Panel 247*1A)

FD-7672 (local)

TD*7613 (local)

Limit Switch CDO for Damper 1CBV32 SGS*UFSAR FI.M1Ctf on Alarm Circuitry for D~r Posi-tion, low Afr Flow, Hi Air T~rature for No. 12 Reactor Nozzle Support Vent System Fan and D~r Operation Control Provides Loss of 115V AC Voltage for No. 12 Fan Control Circuit Control for Damper 1CBV32 (No. 12 Reactor Nozzle support Fan) low Flow Alanm for No. 12 Reactor Support Vent System Hi Temperature Alarm for No.

Reactor Support Vent System Position Indication Circuitry for Damper Accident/Safety Requirements None None None None None 12 None None 4 of 14 Analysis N/A N/A 230V Breaker/

control circuit fuse trip due to submerged c~nts wilt alarm loss of control voltage for this circuit H/A N/"

N/A N/A Results/Effects None None None None None None Revision 16 January 31, 1998

TABLE 7.3-6 (Cont) 230V AC Vital Control Center 1C Ventilation - Circuit Section 1A SUBMERGED ELECTRIC COMPONENTS IN CONTAlNMENT COIIp)nent No. 13 Reactor Nozzle Support Fan SGS*UFSAit Function Nozzle Support Vent System Accident/Safety Requirements None 5 of 14 Analysis N/A Resut ts/Effects None Revision 16 January 31, 1998

TABLE 7.3-6 (Cont) 230V AC Vital Control Center 1C Ventilation

  • Circuit Section 1A NONSUBMERGEO ELECTRIC COMPONENTS IN CONTAINMENT COI'J1)0nent Aux. Relays 33X 63X 23X Aux. Relays 6X, 3X, 6Y, and Starter Relay 6 Relay 74/AC SV*914

<Panel 247-1A)

F0-7674 (Local)

T0*7615 (local)

Limit Switch coo for Damper 1CBV33 SGS*UFSAR F~.W~Ction Alarm Circuitry for Danper Posi-tion, Low Air Flow, Hi Air Tenperature for No. 13 Reactor Nozzle Support Vent System Fan and D~

Operation Control Provides loss of 115V AC Voltage for No. 13 Fan Control CircuU Control for Damper 1CBV33 (No. 13 Reactor Nozzle Support Fan)

Low Flow Alarm for No. 13 Reactor Support Vent System Hi Temperature Alarm for No.

Reactor Support Vent System Position lndfcation Circuitry for Damper Accident/Safety Requirements None None None None None 13 None None 6 of 14 Analysis N/A N/A 230V Breaker/

Control Circuit fuse trip due to sl.bnerged COIIJ.IO*

nents will alarm loss of control voltage for this circuit MIA N/A N/A N/A Results/Effects None None None None None None Revision 16 January 31, 1998

TABLE 7.3*6 (Cont) 230V AC Vital Control Center 1C Ventilation-Circuit Section 2A SUBMERGED ELECTRJC COMPONENTS IN CONTAINMENT Coqxment No. 14 Reactor Nozzle Support Fan Function Nozzle Support Vent System Accident/Safety Requirements None 7 of 14 Analysis N/A Results/Effects None Revision 16 January 31, 1998

TABLE 7.3-6 CCont) 230V AC Vital Control Center 1C Ventilation-Circuit Section 2A (Cont.)

NONSUBMERGED ELECTRIC COMPONENTS IN CONTAINMENT Coq10nent Aux. Relays 33X 63X 23X Aux. Relays 6X, 3X, 6Y, and Starter Relay 6 Relay 74/AC SV-915 (Panel 247*1A)

FD*7676 (local)

FC*7677 (local)

Limit Switch coo for Damper 1CBV31 SGS*UFSAR Function Alarm Circuitry for Damper Posi-tion, Low Air Flow, Hf Air Ten.,erature for No. 14 Reactor Nozzle Support Vent System Fan and Damper Operation/Control Provides Loss of 115V AC Voltage for No. 14 Fan Control Circuit Control for Damper 1CBV31 (No, 14 Reactor Nozzle Support Fan) low Flow Alarm for No. 14 Reactor Support Vent System Hf Temperature Alarm for No.

Reactor Support Vent System Position Indication Circuitry for Damper Accident/Safety Requirements None None None None None 14 None None 8 of 14 Analysis N/A N/A 230V Breaker/

Control circuit fuse trip due to submerged coq10nents will alarm loss of control voltage for this circuit N/A N/A N/A N/A Results/Effects None None None None None None Revisfon 16 January 31, 1998

TABLE 7.3-6 (Cont) 230V AC Vital Control Center 1A East Valves - Circuit Section 4A SUBMERGED ELECTRIC COMPONENTS IN CONTAINMENT Component 1RH2 (Motor operated) limit and Torque Swl tches for Valve 1RH2 Function RHR Common Suction Isolation Valve Control and position Indications for valve 1RH2 Accident/Safety Requirements RHR SUCtion RHR Suction Analysis Valve Is adminis-tratively locked closed.

Circuit breaker trip could prevent operator opening S811le analysis as above for the valve itself Results/Effects 1RH1 available as alternate, also steam generators can provide cooling Same analysis as above for the valve itself 230V AC Vital control center 1A East Valves - Circuit section 4A NONSUBMERGED ELECTRIC COMPONENTS IN CONTAINMENT c~nt Relay 74X/AC Function Indicate control circuit energized for 2RH1 Accident/Safety Requirements None 9 of 14 Analysis Results/Effects 230V Breaker/Control None circuit fuse trip due to submerged conponents will alarm loss of control voltage for this circuit Revision 16 January 31, 1998

TABLE 7.3-6 (Cont) 230V AC Vital Control center 1A East Valves

  • Circuit Section 41 SUBMERGED ELECTRIC COMPONENTS IN CONTAINMENT C011p011ent 1CC190 (Motor operated) limit and Torque Switches for Valve 1CC190 Function Reactor Coolant Pump Thermal Barrier Component Cooling Water Return (Containment Isolation Valve)

Control and position position indications for Valve 1CC190 NONSUBMERGED ELECTRIC COMPONENTS IN CONTAINMENT C~ent Aux. Relays 33)(

33Y Relay 74AC/TSV Aux. Relays 9XJO, 9X/C and starter 9/0 9/C SGS*UFSAR Function Valve position indication for 1CC190 Provides loss of 115V AC control voltage for 1CC190 control circuft Valve Operation Control Accident/Safety Requirements Valve closes for an accident (P signal)

Control portion of function needed until valve operates as required Accident/Safety Requirements None None Needed until valve operates as required 10 of 14 Analysis Valve closes on signal prior to valve becoming submerged (located at approx. El 79 1)

Same analysis as above for the valve itself Analysis N/A 230 V Breaker/

Control circu;t fuse trip due to submerged coq:10*

nents will alarm loss of control voltage for this circuit Will operate as required Results/Effects Safety function will be performed Safety function will be performed Results/Effects None None Safety function will be performed Revision 16 January 31, 1998

TABLE 7.3-6 (Cont) 230V AC Vital Control Center lA East Valves - Circuit Section SE SUBMERGED ELECTRIC COMPONENTS IN CONTAINMENT Component 1CC187 (Motor operated)

Limit and Torque Switches for Valve 1CC187 SGS-UFSAR Function Reactor Coolant Pump Component Cooling Water Return (Con-tainment Iso-lation Valve)

Control and position indi-cations for valve 1CC187 Accident/Safety Requirements Valve closes for an accident (P signal)

Analysis Valve closes on signal prior to valve becoming submerged (loc-ated at approx.

El. 79')

Control portion of function Same analysis as needed until valve operates as above for the required valve itself 11 of 14 Results/Effects Safety function will be performed Safety function will be performed Revision 6 February 15, 1987

TABLE 7.3-6 (Cont) 230V AC Vital Control Center lA East Valves - Circuit Section SE NONSUBMERGED ASSOCIATED ELECTRICAL COMPONENTS Component Aux. Relays 33X/14B 33Y/14B Relay 74AC/14B Aux. Relays 9X/O, 9X/C and starter 9/0 9/C SGS-UFSAR Function Valve position indications for 1CC187 Provides loss of 115V AC control voltage for 1CC187 control circuit Valve Operation Control Accident/Safety Requirements None None Needed until valve operates as required 12 of 14 Analysis N/A 230 Breaker/

Control circuit fuse trip due to submerge compo-nents will alarm loss of control voltage for this circuit Will operate as required Results/Effects None None Safety function will be performed Revision 6 February 15, 1987

TABLE 7.3-6 (Cont) 230V AC Vital Control Center 1B East Valves - Circuit section 5A SUBMERGED ELECTRIC COMPONENTS IN CONTAINMENT COftl)Onent 1CV284 (Motor operated)

Limit and Torque Switches for Valve 1CV184 SGS*UFSAR Function Reactor Coolant P~.Seal Water Return (Con-tairrnent Iso-lation Valve)

Control and position indi

  • cations for valve 1CV184 Accident/Safety Requirements Valve closes for an accident (P signal)

Control portion of function needed until valve operates as required 13 of 14 Amtlysis Valve closes on signal prior to valve becoming submerged <loc*

ated at approx.

eL.79*>

Same analysis as above for the valve itself Results/Effects Safety function wfll be performed Safety function will be performed Revision 16 January 31, 1998

TABLE 7.3*6 (Cont) 230V AC Vital Control Center 18 East Valves

  • Circuit Section SA NONSUBNERGED ELECTRIC COMPONENTS lN CONTAINMENT Conponent Aux. Relays 33X/SWB 33V/SWB Relay 74AC/SWB Aux. Relays

'IX/0, 9X/C n starter 910 9/C Function Valve position indications for 1CC284 Provides loss of 115V AC control voltage for 1CC284 control circuit Valve Operation Control Accident/Safety Requirements Indicate containment Isolation None Needed untfl valve operates as required Analysis Breaker trip COIIIpOI'Itf'lts w I ll cause loss of position fndfcatfon 230 Breaker/

Control circuit fuse trip due to sul!merged conpo*

nents will alarm loss of control voltage for this circuit Vi lt operate as required Results/Effects Redl.rldant valve position Indication will indicate containment isolation None Safety function will be performed

~ircuit Protection

  • Motor control Center cfrcuft provided with manual Class 1E circuit breaker. Vent fan motor power circuit protected by open MOtor starter contactor. Control circuit (developed from a 230/115V transformer) fs protected by 15 amp fuses, SGS*UFSAR 14 of 14 Revision 16 January 31, 1998

TABLE 7.3*7 SAFETY EVALUATION

  • ELECTRICAL COMPONENTS AND CIRCUITS THAT ARE AFFECTED BY THE FLOODING OF COMPONENTS WITKIN THE CONTAINMENT DURING POST*LOCA CONDITIONS JUNCTION/TERMINAL BOXES SUBMERGED ELECTRICAL COMPONENTS IN CONTAINMENT Jun/Ter Box EJN-140 (Unit 2 EJN*148)

JT 11 (Unit 2 JT-96)

JT 12 (Unit 2 JT-97)

JT 13 (Unit 2 JT*98)

JT 14 (Unit 2 JT-99)

SGS*UFSAR FI.A"'Ctions Circuit Affiliation Terminations for Limit Switches 1AADC

  • No. 12 for valve 1PR17 Terminations for Limit Switches 1AADC
  • No. 15 for Valves 11SJ20, 11SJZ7, 11SJ57! 11SJ58, 11SJ93 (Positlon Indication)

Terminations for Limit Switches 1BBDC - No. 17 for Valves 12SJ20, 12SJ27, 12SJ57, 12SJ58, 12SJ93 (Position Indication)

Terminations for Limit Switches 1CCDC

  • No. 17 for Valves 13SJ20, 13SJ27, 13SJ57, 13SJ58, 13SJ93 (Position Indication)

Terminations for Limit Switches 188DC

  • No. 11 for Valves 14SJ20, 14SJ27, 14SJ57, 14SJ58, 14SJ93 (Position Indication) 1 of 2 Accident/Safety Requirements Indicate containment isolation None None None None Analysis Breaker trip due to c~ts wt ll cause loss of position indication N/A N/A N/A N/A Results/

Effects Valve 1PR17 safety fi.A"'Ctton will be valve 1PR18 RG 1.97 position hdfcatlon will indicate containment isolation None None None None Revision 16 January 31, 1998

,Jun/Ter Box EJT 210 JT 212 (Unit 2 JT-213)

JT (Unit 2 JT-123)

SGS-UFSAR t'unctlons Terminations for Limit Switches for Valves lCV2, 1CV3,

1CV75, (Position Indication)

Terminations for Limit Switches for Valves lCV278, 1CV131, 1CV134 (Position Indication)

Terminations for Limit Switches for Valves llSJ162, 12SJ162, 13SJ162, 14S,"Tl62, (Position Indication)

TABLE 7.3-7 (Conti rcul Affiliation lEBDC No. 5,.,, 19 lCCDC No. 22 lDDC No. 16, 2 of 2 Requj re~ents Indicate containrr,ent isolation None None Analys.is Breaker trip due to submerged v-.~i.::.l N/11.

N/A Valve 1CV3 safety function will be valve 1CV7 RG will ind~cate contaiP~ent lsola-:ion None

.'lone Revisic!1 25 October 26, 2010

SGS -

UFSAR TABLE 7.3-8 ENGINEERED SAFETY FEATURES RESPONSE TIMES THE INFO:RMATION CONTAINED IN THIS TABLE WAS RELOCATED TO THE SALEM TECHNICAL REQUIREMENTS MANUAL 1 of 1 Revision 25 October 26, 2010

SGS UFSAR SALEM UNIT 2 THE INFORMATION CONTAINED IN THIS TABLE WAS RELOCATED TO THE SALEM TECHNICAL REQUIREMENTS MANUAL 1 of 1 Revision 25 October 26, 2010