ML16293A748
| ML16293A748 | |
| Person / Time | |
|---|---|
| Site: | Oconee (DPR-38-A-179, DPR-47-A-179, DPR-55-A-176) |
| Issue date: | 12/13/1989 |
| From: | Matthews D Office of Nuclear Reactor Regulation |
| To: | |
| Shared Package | |
| ML16138A687 | List: |
| References | |
| NUDOCS 8912190401 | |
| Download: ML16293A748 (8) | |
Text
k REGUZ 0
UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 DUKE POWER COMPANY DOCKET NO. 50-269 OCONEE NUCLEAR STATION, UNIT 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 179 License No. DPR-38
- 1. The Nuclear Regulatory Commission (the Commission) has found that:
A. The application for amendment to the Oconee Nuclear Station, Unit I (the facility) Facility Operating License No. DPR-38 filed by the Duke Power Company (the licensee) dated July 14, 1989, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I;
- 6. The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C. There is reasonable assurance (i) that the activities authorized by this anendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulaticrs set forth in 10 CFR Chapter I; D. The issuance of this license amendment will not be inimical to the common defense and security or to the health and safety of the public; and E. The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations, and all applicable requirements have been satisfied.
- 2. Accordingly, the license is hereby amended by page changes to the Technical Specifications as indicated in the attachment to this license amendment, and Paragraph 3.B. of Facility Operating License No. DPR-38 is hereby amended to read as follows:
8912190401 691213 PDR ADOCK 05000269 P
PNU
Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 179, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.
- 3. This license amendment is effective as of its date of issuance.
FOR THE NUCLEAR REGULATORY COMMISSION David B. Matthews, Director Project Directorate 11-3 Division of Reactor Projects -
I/11 Office of Nuclear Reactor Regulation
Attachment:
Technical Specification Changes Date of Issuance: December 13, 1989
UNITED STATES I
l NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 DUKE POWER COMPANY DOCKET NO. 50-270 OCONEE NUCLEAR STATION, UNIT 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 179 License No. DPR-47
- 1. The Nuclear Regulatory Commission (the Comission) has found that:
A.
The application for amendment to the Oconee Nuclear Station, Unit 2 (the facility) Facility Operating License No. DPP-47 filed by the Duke Power Company (the licensee) dated July 14, 1989, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; B. The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C. There is reasonable assurance (i) that the activities authorized by this amendment car be conducted without endangering the health and satety of the public, and (ii) that such activities will be conducted in compliance with the Comirission's regulations set forth in 10 CFR Chapter I; U. The issuance of this license amendment will not be inimical to the comrrmon defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations, and all applicable requirements have been satisfied.
- 2. Accordingly, the license is hereby amended by page changes to the Technical Specifications as indicated in the attachment to this license amendment, and Paragraph 3.B. of Facility Operating License No. DPR-47 is hereby amended to read as follows:
-2 Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 179, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.
- 3. This license amendment is effective as of its date of issuance.
FOR THE NUCLEAR REGULATORY COMMISSION ka46A AJ. J~eA David B. Matthews, Director Project Directorate 11-3 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation
Attachment:
Technical Specification Changes Date of Issuance: December 13, 1989
o REj UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 DUKE POWER COMPANY DOCKET NO.
50-287 OCONEE NUCLEAR STATION, UNIT 3 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 176 License No. DPR-55
- 1. The Nuclear Regulatory Commission (the Commission) has found that:
A. The application for amendment to the Oconee Nuclear Station, Unit 3 (the facility) Facility Operating License No. DPR-55 filed by the Duke Power Company (the licensee) dated July 14, 1989, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; C. The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C. There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations set forth in 10 CFR Chapter I; D. The issuance of this license amendment will not be inimical to the common defense and security or to the health and safety of the public; and E. The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations, and all applicable requirements have been satisfied.
- 2. Accordingly, the license is hereby amended by page changes to the Technical Specifications as indicated in the attachment to this license amendment, and Paragraph 3.B. of Facility Operating License No. DPR-55 is hereby amended to read as follows:
-2 Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 176, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.
- 3. This license amendment is effective as of its date of issuance.
FOR THE NUCLEAR REGULATORY COMMISSION David B. Matthews, Director Project Directorate 11-3 Division of Reactor Projects -
I/Il Office of Nuclear Reactor Regulation
Attachment:
Technical Specification Changes Date of Issuance: December 13, 1989
ATTACHMENT TO LICENSE AMENDMENT NO. 179 FACILITY OPERATING LICENSE NO. DPR-38 DOCKET NO. 50-269 AND TO LICENSE AMENDMENT NO. 179 FACILITY OPERATING LICENSE NO. DPR-47 DOCKET NO.
50-270 AND TO LICENSE AMENDMENT NO. 176 FACILITY OPERATING LICENSE NO. DPR-55 DOCKET NO. 50-287 Replace the following page of the Appendix "A" Technical Specifications with the enclosed page. The revised page is identified by Amendment number and contains vertical lines indicating the areas of change.
Amended Page 4.8-1
4.8 MAIN STEAM STOP VALVES Applicability Applies to the main steam stop valves.
Objective To verify the ability of the main steam stop valves to close upon signal.
Specification 4.8 Using Channels A and B, the operation of each of the main steam stop valves shall be tested during each refueling outage to demon strate a closure time of one second or less in Channel A and a clo sure time of 15 seconds or less for Channel B.
I Bases The main steam stop valves limit the Reactor Coolant System cooldown rate and resultant reactivity insertion following a main steam line break accident.
Their ability to promptly close upon redundant signals will be verified during each refueling outage.
Channel A solenoid valves are designed to close all four turbine stop valves in 240 milliseconds.
The backup Channel B solenoid valves are designed to close the turbine stop valves in approximately 12 seconds.
Using the maximum 15 second stop valve closing time, the fouled steam generator inventories and the minimum tripped rod worth with the maximum stuck rod worth, an analysis similar to that presented in FSAR Section 15.13, (but considering a blowdown of both steam generators) shows that the reactor will remain sub critical after reactor trip following a double-ended steam line break.
REFERENCES (1) FSAR, Section 10.3.4, and 15.13 OCONEE -
UNITS 1, 2, & 3 4.8-1 Amendment No.
179 (Unit 1)
Amendment No.
179 (Unit 2)
Amendment No.
176 (Unit 3)