UNITED STATES o
NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-4001 DUKE POWER COMPANY DOCKET NO. 50-269 OCONEE NUCLEAR STATION, UNIT 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 226 License No. DPR-38
- 1.
The Nuclear Regulatory Commission (the Commission) has found that:
A.
The application for amendment to the Oconee Nuclear Station, Unit 1 (the facility) Facility Operating License No. DPR-38 filed by the Duke Power Company (the licensee) dated June 12, 1997, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations as set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations set forth in 10 CFR Chapter I; D.
The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.
- 2.
Accordingly, the license is hereby amended by page changes to the license, Appendix C of the license, and the Technical Specifications as indicated in the attachment to this license amendment, and Paragraph 3.B of Facility Operating License No. DPR-38 is hereby amended to read as follows:
9709260248 970916 PDR ADOCK 05000269 P
_j J
-2 B. Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 226 are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.
- 3.
This license amendment is effective as of its date of issuance and shall be implemented within 30 days of issuance.
FOR THE NUCLEAR REGULATORY COMMISSION erbert N. Berkow, Director Project Directorate 11-2 Division of Reactor Projects - I/Il Office of Nuclear Reactor Regulation Attachments:
- 1. Pages 1 and 8 to the License (remove page 8a)
- 2. Appendix C of the License
- 3. Changes to the Technical Specifications Date of Issuance: September 16, 1997
UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 DUKE ENERGY CORPORATION DOCKET NO. 50-269 OCONEE NUCLEAR STATION, UNIT 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 3 License No. DPR-38 The Atomic Energy Commission (the Commission) has found that:
- a.
The application for amendment by Duke Energy Corporation (the licensee) dated June 19, 1974, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I;
- b. The facility will operate in conformity with the license, the provisions of the Act, and the rules and regulations of the Commission;
- c.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations;
- d. The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and
- e.
Prior public notice of this amendment is not required since the amendment does not involve a significant hazards consideration.
Accordingly, Facility Operating License No. DPR-38 is hereby amended in its entirety to read as follows:
- 1.
This license applies to Oconee Nuclear Station, Unit 1, a pressurized water reactor and associated equipment (the facility) owned by the Duke Energy Corporation. The facility is located in eastern Oconee County, about eight miles northeast of Seneca, South Carolina, and is described in the "Final Safety Analysis Report" as supplemented and amended (Amendments 1 through 47) and the Environmental Report as supplemented and amended (Supplement 1).
- 2.
Subject to the conditions and requirements incorporated herein, the Commission hereby licenses Duke Energy Corporation (the licensee):
Amendment No. 226
-8 properly raised at the Federal Power Commission concerning such commitments, including allocation of costs or the rates to be charged. Applicant will negotiate (including the execution of a contingent statement of intent) with respect to the foregoing commitments with any neighboring entity including distribution systems where applicable engaging in or proposing to engage in bulk power supply transactions, but applicant shall not be required to enter into any final arrangement prior to resolution of any substantial questions as to the lawful authority of an entity to engage in the transactions. In addition, applicant shall not be obligated to enter into a given bulk power supply transaction if: (1) to do so would violate, or incapacitate it from performing any existing lawful contract it has with a third party; (2) there is contemporaneously available to it, a competing or alternative arrangement which affords it greater benefits which would be mutually exclusive of such arrangement; (3) to do so would adversely affect its system operations or the reliability of power supply to its customers, or (4) if to do so would jeopardize applicant's ability to finance or construct on reasonable terms facilities needed to meet its own anticipated system requirements.
3.E. Fire Protection Duke Energy Corporation shall implement and maintain in effect all provisions of the approved fire protection program as described in the Final Safety Analysis Report for the facility and as approved in the SERs dated August 11, 1978, and April 28, 1983; October 5, 1978 and June 9, 1981 Supplements to the SER dated August 11, 1978; and Exemptions dated February 2, 1982; August 31, 1983; December 27, 1984; December 5, 1988; and August 21, 1989 subject to the following provision:
The licensee may make changes to the approved fire protection program without prior approval of the Commission only if those changes would not adversely affect the ability to achieve and maintain safe shutdown in the event of a fire.
3.F Physical Protection Duke Energy Corporation shall fully implement and maintain in effect all provisions of the Commission-approved physical security, guard training and qualification, and safeguards contingency plans including amendments made pursuant to provisions of the Miscellaneous Amendments and Search Requirements revisions to 10 CFR 73.55 (51 FR 27817 and 27822) and to the authority of 10 CFR 50.90 and 10 CFR 50.54(p). The plans, which contain Safeguards Information protected under 10 CFR 73.21, are entitled: "Oconee Nuclear Station Security Plan," with revisions submitted through January 15, 1988; "Oconee Nuclear Station Training and Qualification Plan," with revisions submitted through May 16, 1986; and "Oconee Nuclear Station Safeguards Contingency Plan," with revisions submitted through March 18, 1987. Changes made in accordance with 10 CFR 73.55 shall be implemented in accordance with the schedule set forth therein.
Amendment No. 226
APPENDIX C ADDITIONAL CONDITIONS FACILITY OPERATING LICENSE NO. DPR-38 Duke Energy Corporation shall comply with the following conditions on the schedules noted below:
Amendment Implementation Number Additional Conditions Date 224 This amendment authorizes the licensee to May 16,1997 incorporate in the Updated Final Safety Analysis Report certain changes to the main turbine-generated missile protection criteria. Implementation of this amendment is the incorporation of these changes as described in the licensee's application dated April 29, 1997, and evaluated in the staffs Safety Evaluation dated May 16, 1997.
225 Prior to performing the seventh tendon September 15, 1997 surveillance for Unit 1, the licensee will modify the Oconee Updated Final Safety Analysis Report (specifically the Selected Licensee Commitment Manual) to incorporate the prescribed lower limit and the minimum required value of tendon forces for each group of Reactor Building Post-Tensioning System tendons. In addition, the portion of the Selected Licensee Commitment Manual related to the establishment of these limits will be submitted as soon as available.
Implementation of this amendment includes the incorporation of these commitments as described in the licensee's application dated October 30, 1996, as supplemented by letters dated April 22 and July 2, 1997, evaluated in the staffs Safety Evaluation attached to this amendment, and acknowledged by letter dated September 4, 1997.
Amendment No 226
UNITED STATES 0
NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 DUKE POWER COMPANY DOCKET NO. 50-270 OCONEE NUCLEAR STATION, UNIT 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 226 License No. DPR-47
- 1.
The Nuclear Regulatory Commission (the Commission) has found that:
A.
The application for amendment to the Oconee Nuclear Station, Unit 1 (the facility) Facility Operating License No. DPR-47 filed by the Duke Power Company (the licensee) dated June 12, 1997, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations as set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations set forth in 10 CFR Chapter I; D.
The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.
- 2.
Accordingly, the license is hereby amended by page changes to the license, Appendix C of the license, and the Technical Specifications as indicated in the attachment to this license amendment, and Paragraph 3.8 of Facility Operating License No. DPR-47 is hereby amended to read as follows:
-2 B. Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No.226, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.
- 3.
This license amendment is effective as of its date of issuance and shall be implemented within 30 days of issuance.
FOR THE NUCLEAR REGULATORY COMMISSION erbert N. Berkow, Director Project Directorate 11-2 Division of Reactor Projects - I/Il Office of Nuclear Reactor Regulation Attachments:
- 1. Pages 1 and 8 to the License (remove page 8a)
- 2. Appendix C of the License
- 3. Changes to the Technical Specifications Date of Issuance:
September 16, 1997
1$
A UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-M001 DUKE ENERGY CORPORATION DOCKET NO. 50-270 OCONEE NUCLEAR STATION, UNIT 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 3 License No. DPR-47 The Atomic Energy Commission (the Commission) has found that:
- a.
The application for amendment by Duke Energy Corporation (the licensee) dated June 19, 1974, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I;
- b. The facility will operate in conformity with the license, the provisions of the Act, and the rules and regulations of the Commission;
- c.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations;
- d. The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and
- e.
Prior public notice of this amendment is not required since the amendment does not involve a significant hazards consideration.
Accordingly, Facility Operating License No. DPR-47 is hereby amended in its entirety to read as follows:
- 1.
This license applies to Oconee Nuclear Station, Unit 2, a pressurized water reactor and associated equipment (the facility) owned by the Duke Energy Corporation. The facility is located in eastern Oconee County, about eight miles northeast of Seneca, South Carolina, and is described in the Final Safety Analysis Report" as supplemented and amended (Amendments 1 through 47) and the Environmental Report as supplemented and amended (Supplement 1).
- 2.
Subject to the conditions and requirements incorporated herein, the Commission hereby licenses Duke Energy Corporation (the licensee):
Amendment No.
226
-8 properly raised at the.Federal Power Commission concerning such commitments, including allocation of costs or the rates to be charged. Applicant will negotiate (including the execution of a contingent statement of intent) with respect to the foregoing commitments with any neighboring entity including distribution systems where applicable engaging in or proposing to engage in bulk power supply transactions, but applicant shall not be required to enter into any final arrangement prior to resolution of any substantial questions as to the lawful authority of an entity to engage in the transactions. In addition, applicant shall' not be obligated to enter into a given bulk power supply transaction if: (1) to do so would violate, or incapacitate it from performing any existing lawful contract it has with a third party; (2) there is contemporaneously available to it, a competing or alternative arrangement which affords it greater benefits which would be mutually exclusive of such arrangement; (3) to do so would adversely affect its system operations or the reliability of power supply to its customers, or (4) if to do so would jeopardize applicant's ability to finance or construct on reasonable terms facilities needed to meet its own anticipated system requirements.
3.E. Fire Protection Duke Energy Corporation shall implement and maintain in effect all provisions of the approved fire protection program as described in the Final Safety Analysis Report for the facility and as approved in the SERs dated August 11, 1978, and April 28, 1983; October 5, 1978 and June 9, 1981 Supplements to the SER dated August 11, 1978; and Exemptions dated February 2, 1982; August 31, 1983; December 27, 1984; December 5, 1988; and August 21, 1989 subject to the following provision:
The licensee may make changes to the approved fire protection program without prior approval of the Commission only if those changes would not adversely affect the ability to achieve and maintain safe shutdown in the event of a fire.
3.F Physical Protection Duke Energy Corporation shall fully implement and maintain in effect all provisions of the Commission-approved physical security, guard training and qualification, and safeguards contingency plans including amendments made pursuant to provisions of the Miscellaneous Amendments and Search Requirements revisions to 10 CFR 73.55 (51 FR 27817 and 27822) and to the authority of 10 CFR 50.90 and 10 CFR 50.54(p). The plans, which contain Safeguards Information protected under 10 CFR 73.21, are entitled: "Oconee Nuclear Station Security Plan," with revisions submitted through January 15, 1988; "Oconee Nuclear Station Training and Qualification Plan," with revisions submitted through May 16, 1986; and "Oconee Nuclear Station Safeguards Contingency Plan," with revisions submitted through March 18, 1987. Changes made in accordance with 10 CFR 73.55 shall be implemented in accordance with the schedule set forth therein.
Amendment No. 226
APPENDIX C ADDITIONAL CONDITIONS FACILITY OPERATING LICENSE NO. DPR-47 Duke Energy Corporation shall comply with the following conditions on the schedules noted below:
Amendment Implementation Number Additional Conditions Date 224 This amendment authorizes the licensee to May 16, 1997 incorporate in the Updated Final Safety Analysis Report certain changes to the main turbine-generated missile protection criteria. Implementation of this amendment is the incorporation of these changes as described in the licensee's application dated April 29, 1997, and evaluated in the staffs Safety Evaluation dated May 16, 1997.
225 Prior to performing the seventh tendon September 15, 1997 surveillance for Unit 1, the licensee will modify the Oconee Updated Final Safety Analysis Report (specifically the Selected Licensee Commitment Manual) to incorporate the prescribed lower limit and the minimum required value of tendon forces for each group of Reactor Building Post-Tensioning System tendons. In addition, the portion of the Selected Licensee Commitment Manual related to the establishment of these limits will be submitted as soon as available.
Implementation of this amendment includes the incorporation of these commitments as described in the licensee's application dated October 30, 1996, as supplemented by letters dated April 22 and July 2, 1997, evaluated in the staffs Safety Evaluation attached to this amendment, and acknowledged by letter dated September 4, 1997.
Amendment No. 226
UNITED STATES NUCLEAR REGULATORY COMMISSION Z
WASHINGTON, D.C. 20555-0001 DUKE POWER COMPANY DOCKET NO. 50-287 OCONEE NUCLEAR STATION, UNIT 3 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 223 License No. DPR-55
- 1.
The Nuclear Regulatory Commission (the Commission) has found that:
A.
The application for amendment to the Oconee Nuclear Station, Unit 1 (the facility) Facility Operating License No. DPR-55 filed by the Duke Power Company (the licensee) dated June 12, 1997, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations as set forth in 10 CFR Chapter 1; B.
The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations set forth in 10 CFR Chapter I; D.
The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.
- 2.
Accordingly, the license is hereby amended by page changes to the license, Appendix C of the license, and the Technical Specifications as indicated in the attachment to this license amendment, and Paragraph 3.B of Facility Operating License No. DPR-55 is hereby amended to read as follows:
-2 B. Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 223are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.
- 3.
This license amendment is effective as of its date of issuance and shall be implemented within 30 days of issuance.
FOR THE NUCLEAR REGULATORY COMMISSION erbert N. Berkow, Director Project Directorate 11-2 Division of Reactor Projects - 1/11 Office of Nuclear Reactor Regulation Attachments:
- 1. Pages 1, 2, and 9 to the License
- 2. Appendix C of the License
- 3. Changes to the Technical Specifications Date of Issuance:
September 16, 1997
UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-4001 DUKE ENERGY CORPORATION (Oconee Nuclear Station, Unit 3)
DOCKET NO. 50-287 FACILITY OPERATING LICENSE License No. DPR-55 The Atomic Energy Commission (the Commission) having found that:
- a.
The application for license filed by Duke Energy Corporation (the licensee) complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I and all required notifications to other agencies or bodies have been duly made;
- b. Construction of the Oconee Nuclear Station, Unit 3 (the facility) has been substantially completed in conformity with Construction Permit No. CPPR-35 and the application, as amended, the provisions of the Act and the rules and regulations of the Commission;
- c.
The facility will operate in conformity with the application, as amended, the provisions of the Act, and the rules and regulations of the Commission;
- d. There is reasonable assurance: (i) that the activities authorized by this operating license can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the rules and regulations of the Commission;
- e.
The licensee is technically and financially qualified to engage in the activities authorized by this operating license in accordance with the rules and regulations of the Commission;
- f.
The licensee has satisfied the applicable provisions of 10 CFR Part 140, "Financial Protection Requirements and Indemnity Agreements", of the Commission's regulations;
- g. The issuance of this operating license will not be inimical to the common defense and security or the health and safety of the public;
- h. After weighing the environmental, economic, technical, and other benefits of the facility against environmental costs and considering available alternatives, the issuance of Facility Operating License No. DPR-55 (subject to the conditions for Amendment No. 223
-2 protection of the environment as set forth herein) is in accordance with 10 CFR Part 50, Appendix D, of the Commission's regulations and all applicable requirements of said Appendix D have been satisfied;
- i.
Pursuant to Section 105c(8) of the Act, the Commission has consulted with the Attorney General regarding the issuance of this operating license. After said consultation, the Commission has determined that the issuance of this license, subject to the conditions set forth in this subparagraph i, in advance of consideration of and findings with respect to matters covered in Section 105c of the Act, is necessary in the public interest to avoid unnecessary delay in the operation of the facility. At the time this operating license is being issued an antitrust proceeding has been noticed but antitrust hearings have not been concluded. The Commission, accordingly, has made no determination with respect to matters covered in Section 105c of the Act, except to the extent of the conditions noted herein which the Atomic Safety Licensing Board has ordered be included herein after said conditions were negotiated and agreed to by the applicant, the Department of Justice, and the Regulatory staff. On the basis of its findings made as a result of the conclusion of the antitrust proceeding, the Commission may continue this license as issued, rescind this license or amend this license to include such additional conditions as the Commission deems appropriate., Duke Energy Corporation and others who may be affected hereby are accordingly on notice that the granting of this license is without prejudice to any subsequent licensing action, including the imposition of additional appropriate conditions, which may be taken by the Commission as a result of the outcome of any antitrust proceeding. In the course of its planning and other activities, Duke Energy Corporation will be expected to conduct itself accordingly; and
- j.
The receipt, possession, and use of source, byproduct and special nuclear material as authorized by this license will be in accordance with the Commission's regulations in 10 CFR Part 30, 40 and 70, including 10 CFR Section 30.33, 40.32, 70.23 and 70.31.
Facility Operating License No. DPR-55 is hereby issued to the Duke Energy Corporation (the licensee) to read as follows:
- 1.
This license applies to the Oconee Nuclear Station, Unit 3, a pressurized water reactor and associated equipment (the facility) owned by the Duke Energy Corporation. The facility is located in eastern Oconee County, about eight miles northeast of Seneca, South Carolina, and is described in the "Final Safety Analysis Report" as supplemented and amended (Amendments 1 through 47) and the Environmental Report as supplemented and amended (Supplement 1).
- 2.
Subject to the conditons and requirements incorporated herein, the Commission hereby licenses Duke Energy Corporation (the licensee):
Amendment No. 223
-9 any neighboring entity including distribution systems where applicable engaging in or proposing to engage in bulk power supply transactions, but applicant shall not be required to enter into any final arrangement prior to resolution of any substantial questions as to the lawful authority of an entity to engage in the transactions. In addition, applicant shall not be obligated to enter into a given bulk power supply transaction if: (1) to do so would violate, or incapacitate it from performing any existing lawful contract it has with a third party; (2) there is contemporaneously available to it, a competing or alternative arrangement which affords it greater benefits which would be mutually exclusive of such arrangement; (3) to do so would adversely affect its system operations or the reliability of power supply to its customers, or (4) if to do so would jeopardize applicant's ability to finance or construct on reasonable terms facilities needed to meet its own anticipated system requirements.
3.E. Fire Protection Duke Energy Corporation shall implement and maintain in effect all provisions of the approved fire protection program as described in the Final Safety Analysis Report for the facility and as approved in the SERs dated August 11, 1978, and April 28, 1983; October 5, 1978 and June 9, 1981 Supplements to the SER dated August 11, 1978; and Exemptions dated February 2, 1982; August 31, 1983; December 27, 1984; December 5, 1988; and August 21, 1989 subject to the following provision:
The licensee may make changes to the approved fire protection program without prior approval of the Commission only if those changes would not adversely affect the ability to achieve and maintain safe shutdown in the event of a fire.
3.F Physical Protection Duke Energy Corporation shall fully implement and maintain in effect all provisions of the Commission-approved physical security, guard training and qualification, and safeguards contingency plans including amendments made pursuant to provisions of the Miscellaneous Amendments and Search Requirements revisions to 10 CFR 73.55 (51 FR 27817 and 27822) and to the authority of 10 CFR 50.90 and 10 CFR 50.54(p). The plans, which contain Safeguards Information protected under 10 CFR 73.21, are entitled: "Oconee Nuclear Station Security Plan," with revisions submitted through January 15, 1988; "Oconee Nuclear Station Training and Qualification Plan," with revisions submitted through May 16, 1986; and "Oconee Nuclear Station Safeguards Contingency Plan," with revisions submitted through March 18, 1987. Changes made in accordance with 10 CFR 73.55 shall be implemented in accordance with the schedule set forth therein.
Amendment No.
223
APPENDIX C ADDITIONAL CONDITIONS FACILITY OPERATING LICENSE NO. DPR-55 Duke Energy Corporation shall comply with the following conditions on the schedules noted below:
Amendment Implementation Number Additional Conditions Date 221 This amendment authorizes the licensee to May 16,1997 incorporate in the Updated Final Safety Analysis Report certain changes to the main turbine-generated missile protection criteria. Implementation of this amendment is the incorporation of these changes as described in the licensee's application dated April 29, 1997, and evaluated in the staffs Safety Evaluation dated May 16, 1997.
222 Prior to performing the seventh tendon September 15, 1997 surveillance for Unit 1, the licensee will modify the Oconee Updated Final Safety Analysis Report (specifically the Selected Licensee Commitment Manual) to incorporate the prescribed lower limit and the minimum required value of tendon forces for each group of Reactor Building Post-Tensioning System tendons. In addition, the portion of the Selected Licensee Commitment Manual related to the establishment of these limits will be submitted as soon as available.
Implementation of this amendment includes the incorporation of these commitments as described in the licensee's application dated October 30, 1996, as supplemented by letters dated April 22 and July 2,
.1997, evaluated in the staffs Safety Evaluation attached to this amendment, and acknowledged by letter dated September 4, 1997.
Amendment No.223
ATTACHMENT TO LICENSE AMENDMENT NO. 226 FACILITY OPERATING LICENSE NO. DPR-38 DOCKET NO. 50-269 AND TO LICENSE AMENDMENT NO. 226 FACILITY OPERATING LICENSE NO. DPR-47 DOCKET NO. 50-270 AND TO LICENSE AMENDMENT NO. 223 FACILITY OPERATING LICENSE NO. DPR-55 DOCKET NO. 50-287 Replace the following pages of the Appendix "A" Technical Specifications with the enclosed pages. The revised pages are identified by Amendment number and contain vertical lines indicating the areas of change.
Remove Insert 3.7-8 3.7-8 3.7-10 3.7-10 3.7-11 3.7-11 3.7-12 3.7-12*
3.7-13 3.7-13 3.7-14 3.7-14*
4.6-3 4.6-3 4.6-4 4.6-4 6.1-1 6.1-1 6.1-la 6.1-1 a*
- overflow page - no change
the reactor may be heated above 200 0 F if previously shutdown or be permitted to remain critical or be restarted provided the following restrictions are observed:
(a)
Prior to heating the reactor above 200F or prior to the restart of a shutdown reactor or within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> of the loss of any one of the following:
- 1)
Keowee Main Step-up Transformer (including both Keowee Auxiliary Transformers);
- 2)
Both Keowee Auxiliary Transformers (lX and 2X);
- 3)
Keowee Backup Auxiliary Transformer (CX);
the 4160 volt standby buses shall be energized by a Lee gas turbine through the 100kV circuit.
The Lee gas turbine and 100kv transmis sion circuit shall be electrically separate from the system grid and off-site non-safety related loads.
(b)
A Keowee hydro unit shall be connected to the underground feeder circuit and this path shall be verified operable within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and weekly thereafter.
(c)
The remaining Keowee Hydro Unit shall be available to the overhead if using this Specification due to Keowee Backup Transformer (CX) unavailability. Generation to the system grid shall be prohibited except for periods of test.
If the overhead path is unavailable, the remaining Keowee Hydro Unit must be operable and shall be available to the underground feeder circuit.
(d)
Operating in this mode is restricted to periods not to exceed 28 days and the provisions of this specification may be utilized without prior NRC approval.
The U.S. NRC Regional Office Region II, will be notified within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
3.7.9 Any degradation beyond Specifications 3.7.2, 3.7.4, 3.7.5, 3.7.6, 3.7.7, and 3.7.8 above shall be reported to the U.S. NRC Regional Office, Region II, within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
A safety evaluation shall be performed by Duke Energy Corporation for the specific situation involved which justifies the safest course of action to be taken.
The results of this evaluation together with plans for expediting the return to the unrestricted operating conditions of Specification 3.7.1 above shall be submitted in a written report to the Office of Nuclear Reactor Regulation with a copy to the U.S.
NRC Regional Office, Region II, within five days.
Bases The auxiliary electrical power systems are designed to supply the required Engineered.Safeguards loads in one unit and safe shutdown loads of the other two units and are so arranged that no single contingency* can inactivate enough engineered safety features to jeopardize plant safety. These systems were designed to meet the following criteria:
Oconee -Units 1, 2, and 3 3.7-8 Amendment No. 226(Unjt 1)
Amendment No. 226(Unit 2)
Amendment No. 223(Unit 3)
In addition to the service test, the battery performance test may be conducted every 5 years (per IEEE standard 450), unless there are signs of degradation.
Degradation is indicated when the battery capacity drops more than 10 percent of rated capacity from its average on previous performance tests, or is below 90 percent of manufacturer's rating. If there is degradation per above de finition, the test should be conducted annually until the battery is replaced or until tests prove the battery is not in a degraded state.
Redundancy of AC Systems There are three 4160 V engineered safety feature switchgear buses per unit.
Each bus can receive power from either of the two 4160 V main feeder buses per unit. Each feeder bus in turn can receive power from the 230 kV switchyard through the start-up transformers, through the unit auxiliary transformer by backfeeding through the main step-up transformer, or from the 4160 V standby buses. Another unit's start-up transformer serving as an alternate supply can be placed in service in one hour.
Under normal unit auxiliary power system alignment, the main feeder buses shall be capable of receiving power automatically from:
- 1.
The Keowee Unit aligned to the underground, through transformer CT-4, and through both standby buses; and
- 2.
The redundant Keowee Unit, aligned through the overhead path; and through the respective Unit's startup transformer.
The standby buses can receive power from the hydro station through the under ground feeder circuit or from a combustion turbine generator at the Lee Steam Station over an isolated 100 kV transmission line. The 230 kV switchyard can receive power from the on-site Keowee hydro station or from several off-site sources via transmission lines which connect the Oconee Station with the Duke Energy Corporation system power distribution network.
In order to meet the single failure criteria for certain design basis sce narios, both standby buses (for the underground flow path), and both El and E2 breakers (for the overhead path) must be operable for the respective flow path to be considered operable.
Redundancy of DC System A.
125 VDC Instrumentation and Control Power System The 125 VDC Instrumentation and Control (I&C) Power System consists of two batteries, three battery chargers, and two I&C distribution centers per unit. All reactor protection and engineered safety features loads on this system can be powered from either the Unit 1 and Unit 2 or Unit 2 and Unit 3 or Unit 3 and Unit 1 125 VDC I&C distribution centers. The 125 VDC I&C distribution centers are normally supplied from their associ ated battery and charger. For one unit, in the event that only one of its batteries and associated chargers are operable, both I&C distribution centers will be tied together.allowing operation of the DC loads from the unit's operable battery and charger. As shown above, one I&C battery (e.g., ICA) can supply both I&C distribution centers (e.g., IDCA and IDCB) and their associated panelboard loads. Also, one of the three battery chargers for each unit can supply all connected ESF and reactor protection loads.
Oconee -
Units 1, 2, and 3 3.7-10 Amendment No.226 (Unit 1)
Amendment No-226 (Unit 2)
Amendment No. 223 (Unit 3)
In order to find and correct a DC ground on the 125 VDC Instrumentation and Control system each unit's DC system must be separated from the other two units. This is due to the interconnected design of the system. With the backup function disabled, the units would be in a degraded mode but would in fact have all of its own DC system available if needed. Each unit's batteries either XCA or XCB is capable of carrying all the 125 VDC Instrumentation and Control loads on that unit.
B.
125 VDC Switching Station Power System There are two essentially independent subsystems each complete with an AC/DC power supply (battery charger), a battery bank, a battery charger bus, motor control center (distribution panel).
All safety-related equipment and the relay house in which it is located are seismic Category I design. Each sub-system provides the necessary DC power to:
- a.
Continuously monitor operations of the protective relaying,
- b.
Isolate Oconee (including Keowee) from all external 230 kV grid
- faults,
- c.
Connect on-site power to Oconee from a Keowee hydro unit or,
- d.
Restore off-site power to Oconee from non-faulted portions of the external 230 kV grid.
Provisions are included to manually connect a standby battery charger to either battery/charger bus.
C.
125 VDC Keowee Station Power System There are essentially two independent physically separated seismic Category I subsystems, each complete with an AC/DC power supply (charg er), a battery bank, a battery/charger bus and a DC distribution center.
Each subsystem provides the necessary power to automatically or manually start, control and protect one of the hydro units.
An open or short in any one battery, charger, or DC distribution center, cannot cause loss of both hydro units.
The 230 KV sources, while expected to have excellent availability, are not under the direct control of the Oconee station and, based on past experience, cannot be assumed to be available at all times. However, the operation of the onsite hydro-station is under the direct control of the Oconee Station and requires no offsite power to start up. Therefore, an onsite backup source of auxiliary power is provided in the form of twin hydro-electric turbine genera tors powered through a common penstock by water taken from Lake Keowee. The use of a common penstock is justified on the basis of past hydro plant ex perience of the Duke Energy Corporation (since 1919) which indicates that the cumulative need to dewater the penstock can be expected to be limited to about one day a year, principally for inspection, plus perhaps four days every tenth year.
Operation with one Keowee Hydro unit out of service for periods less than 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> is permitted. The operability of the remaining Keowee hydro unit is verified within one hour by starting the unit and energizing the standby buses through the underground feeder circuit. This action is repeated once every eight hours thereafter until the Keowee hydro unit is restored to service and Oconee - Units 1, 2, and 3 3.7-11 Amendment No. 226 (Unit 1)
Amendment No. 226 (Unit 2)
Amendment No. 223(Unit 3)
will provide additional assurance of the operability of the remaining unit.
Provisions have been established for those conditions in which long term pre ventative maintenance of a Keowee Hydro unit are necessary. The primary long term maintenance items are expected to be hydro turbine runner and discharge ring welding repairs which are estimated to be necessary every six to eight years. Also, generator thrust and guide bearing replacements will be neces sary. Other items which manifest as failures are expected to be extremely rare and could possibly be performed during the permitted maintenance periods. Time periods of up to 45 days for each Keowee Hydro unit are permitted every three years. During these outages the remaining Keowee Hydro unit will be verified to be operable within one hour and weekly thereafter by starting the unit and energizing the underground feeder circuit to CT-4.
Credit can be taken for the operability of the SK and S breakers per the routine surveillance test.
The remaining Keowee hydro unit will also be available through the overhead transmission path and will not be used for system peaking. Additionally, the standby buses will be energized continuously by one of the Lee gas turbines through the 100 kV transmission circuits.
This transmission circuit would be electrically separated from the system grid and all off-site non-safety-related loads. This arrangement provides a high degree of reliability for the emergency power systems.
Operation with both Keowee Hydro units out of service is permitted for planned or unplanned outages for periods of 72 or 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> respectively. Planned out ages are necessary for the inspection of common underwater areas such as the penstock and to enable the removal of one Keowee unit from service. This would be a controlled evolution in which the availability and condition of the offsite grid, startup transformers and weather would be evaluated and a Lee gas turbine would be placed in operation on the isolated 100 kV transmission line prior to commencement of the outage.
A time period of 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> for unplanned outages of both Keowee units is ac ceptable since a Lee gas turbine will be started within one hour and will energize the standby buses through the dedicated 100 kV transmission line.
This period of time is reasonable to determine and rectify the situation which caused the loss of both Keowee units.
If the overhead power path from Keowee is inoperable for more than 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> due to an extended outage of the Keowee main step-up transformer, both Keowee Auxiliary Transformers (lX and 2X), or Keowee Backup Auxiliary Transformer (CX) operation is permitted provided that certain actions are taken to ensure the quick availability of emergency power. These actions include:
continuous energization of the standby buses by a Lee gas turbine through the 100kV trans mission circuits; connection of a Keowee unit to the underground feeder path and periodic verification of its operability; and, availability of the remaining Keowee unit to the underground feeder path. Operation in this mode is permitted for a maximum of 28 days, which allows a reasonable period of time to remove the existing transformer and install a replacement.
In the event that none of the sources of off-site power are available and it is considered important to continue to maintain an Oconee reactor critical or return it to criticality from a hot shutdown condition, one of the Lee gas turbines can be made available as an additional backup source of power, thus assuring continued availability as an auxiliary power to perform an orderly shutdown of a unit should a problem develop.requiring shutdown of both hydro units.
Oconee -
Units 1, 2, and 3 3.7-12 Amendment No. 226(Unit 1)
Amendment No.
2 2 6 (Unit 2)
Amendment No. 223 (Unit 3)
The power system of the Keowee Hydro station is designed to allow the alignment of each of the two units to the Oconee emergency power systems through either the underground feeder or the overhead path via the main step-up transformer.
During an emergency start one of the Keowee units will be aligned to the underground feeder and the other to the overhead path. Each Keowee unit's 600 VAC auxiliaries are powered from the unit's generator through a 750KVA auxiliary transformer. Each auxiliary transformer is capable of handling auxiliary loads of both units. Unit's auxiliaries can be aligned to receive power from either transformer by a manual transfer capability at the load center level. A backup 750KVA auxiliary transformer (CX) is provided and powered from Oconee 4KV switchgear ITC through an underground feeder.
Transformer CX is capable of backing up one or both unit's auxiliary trans formers.
Each Keowee unit has a generation capacity of 87.5 MVA and the main step up transformer is rated for 230 MVA. This power capacity exceeds the Oconee emergency power requirements.
In addition to supplying emergency power for Oconee, the Keowee Hydro units provide peaking power to the Duke Energy Corporation system. During periods of commercial power generation, the Keowee Hydro units are operated within the acceptable region of the Keowee Hydro operating restrictions. This will ensure that the Keowee Hydro units will be able to perform their emergency power functions from an initial condition of commercial power generation. The Keowee Hydro operating restrictions for commercial power generation are contained in the Selected Licensee Commitment manual.
Changes to these operating restrictions would be performed in accordance with 10 CFR 50.59, which would include an evaluation to determine if any unreviewed safety questions exist.
Emergency Power Switching Logic Circuits The Emergency Power Switching Logic (EPSL) in conjunction with its associated circuits, is designed with sufficient redundancy to assure that power is supplied to the unit Main Feeder Buses and, hence, to the unit's essential loads, under accident conditions. The logic system monitors the normal and emergency power sources and, upon loss of the normal power source (the unit auxiliary transformer), the logic will seek an alternate source of power.
Operation of the unit with certain circuits or channels of the EPSL inoperable for test or maintenance is permitted for periods of up to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, provided that the inoperable circuits/channels are in only one portion, or functional unit, of the EPSL and provided that a sufficient number of circuits/channels in the affected functional unit remain operable such that the functional unit does not lose its ability to perform its designed safety function. These provisions ensure that only one portion of the EPSL is degraded at a time for test or maintenance on the EPSL and that the affected portion remains operable although degraded.
Emergency power system components.(transformers, buses, Keowee Hydro Units, etc.) which become inoperable for testing or maintenance cause their associated circuitry (functional units) of the EPSL to become ineffective. Therefore, the operability of these associated functional units is irrelevant and not required. In these cases the controlling Technical Specification for the LCO will be the one associated with the inoperability of the emergency power system component(s).
However,.all other functional units unaffected by the inoperability of the emergency power system component(s) must meet the re quirements of Table 3.7-1 to ensure the operability of the remaining emergency power system.
Oconee -
Units 1, 2, and 3 3.7-13 Amendment No.226 (Unit 1)
Amendment No.226 (Unit 2)
Amendment No.223 (Unit 3)
In the event a 125 VDC instrumentation and control power panelboard becomes inoperable (for planned or unplanned reasons) as allowed by Technical Speci fication 3.7.2(e) (4), circuits or channels of more than one functional unit of EPSL may become inoperable. In this case, continued operation is allowed under the LCO of T.S. 3.7.2(e) (4), provided that no functional units' circuits, etc., addressed by Table 3.7.1 are out of service, which would not have been out of service due to inoperability of the panelboard. This assures that no functional unit of Table 3.7.1 is degraded beyond the requirements for degraded operation, and that the EPSL is capable of performing its intended function.
Oconee -
Units 1, 2, and 3 3.7-14 Amendment No. 226(Unit 1)
Amendment No. 226(Unit 2)
Amendment No. 223(Unit 3)
>2.12 VDC.
(3)
The electrolyte level of each connected cell is between the minimum and maximum level indication marks.
- c.
Annually verify that:
(1) The cells, end-cell plates and battery racks show no visual indication of structural damage or degradation.
(2) The cell to cell and terminal connections are
- clean, tight and coated with anti-corrosion grease.
4.6.10 Annually, a one hour discharge service test at the required maximum load shall be made on the instrument and control batteries, the Keowee batteries, and the switching station batteries.
4.6.11
- Monthly, the operability of the individual diode monitors in the Instrument and Control Power System shall be verified by imposing a simulated diode failure signal on the monitor.
I 4.6.12 Semiannually, the peak inverse voltage capability of each auctioneering diode in the 125 VDC Instrument and Control Power System shall be measured and recorded.
4.6.13 At lease once every 18 months, the ability of the Keowee Hydro units to supply emergency power from an initial condition of commercial power generation shall be verified.
4.6.14 At lease once every 18 months, the Keowee Hydro units load rejection response will be verified to be bounded by the design criteria used to develop the Keowee operating restrictions.
Bases The Keowee Hydro units, in addition to serving as the emergency power sources for the Oconee Nuclear Station, are power generating sources for the Duke Energy Corporation system requirements.
As power generating units, they are operated frequently, normally on a daily basis at loads equal to or greater than required by Table 8.1-1 of the FSAR for ESF bus loads. Normal as well as emergency Oconee 1, 2, and 3 4.6-3 Amendment No.226(Unit 1)
Amendment No.226(Unit 2)
Amendment No.223(Unit 3)
startup and operation of these units will be from the Oconee Unit 1 and 2 Control Room. The frequent starting and loading of these units to meet Duke Energy Corporation system power requirements assures the continuous availability for emergency power for the Oconee auxiliaries and engineered safety features equipment.
it will be verified that these units will carry the equipment of the maximum safeguards load within 25
- seconds, including instrumentation lag, after a simulated requirement for engineered safety features. To further assure the reliability of these units as emergency power sources, they will be, as specified, tested for automatic start on a monthly basis from the Oconee control room.
These tests will include verification that each unit can be synchronized to the 230 kV bus and that each unit can energize the 13.8 kV underground feeder. Also, the verification of the ability of the Keowee Unit ACBs to automatically close to the underground power path will be performed by the annual tests.
In order to ensure that the Keowee Hydro units are operable during periods of commercial power generation, the protection circuitry will be tested at least once every 18 months.
This surveillance will ensure that the adverse effects of overspeed following a load rejection will be precluded and the appropriate emergency power paths will be aligned.
In addition, the speed sensing governor failure logic will be verified during this surveillance.
Failure to meet the acceptance criteria will be evaluated in the corrective action program to determine the impact on the operability of the emergency power paths.
The Keowee Watt/Var meter, frequency relays, and governor magnetic speed switch will be calibrated prior to the performance of this surveillance.
A maximum power dual unit load rejection will be performed at least once every 18 months.
This surveillance will verify that the Keowee Hydro units response to a load rejection is bounded by the design criteria used to develop the Keowee operating restrictions.
The design criteria are defined in the calculation that determines the Keowee operating restrictions. A power level for the dual unit load rejection will be defined based on the operating conditions for the day of the test.
In addition, a
revision of the operating restrictions for simultaneous operation of both Keowee units will require that a maximum power dual unit load rejection test be performed prior to implementing the revision.
A revision of the operating restrictions for a single Keowee unit will require only a maximum power single unit load rejection as defined by the conditions for the day of the test.
However, if a load rejection test is performed to support a revision to the operating restrictions, then no additional load rejection test will be required until the next surveillance.
The Keowee Watt/Var meter. and frequency relays will be calibrated prior to the performance of this surveillance.
Oconee 1, 2, and 3 4.6-4 Amendment No.226(Unit 1)
Amendment No. 22 6 (Unit 2)
Amendment No.223(Unit 3)
6.0 ADMINISTRATIVE CONTROLS 6.1 ORGANIZATION, REVIEW, AND AUDIT 6.1.1 Organization Onsite and offsite organizations shall be established for unit operation and corporate management, respectively. The onsite and offset organizations shall include the positions for activities affecting the safety of the nuclear power plant.
6.1.1.1 Lines of authority, responsibility, and communication shall be established and defined for the highest management levels through intermediate levels to and including all operating organization positions.
These relationships shall be documented and updated, as appropriate, in the form of organization charts, functional descriptions of departmental responsibilities and relationships, and job descriptions for key personnel positions, or in equivalent forms of documentation. These requirements shall be documented in the FSAR.
6.1.1.2 The Station Manager shall be responsible for overall plant safe operation and shall have control over those onsite activities necessary for safe operation and maintenance of the plant and shall delegate in writing the succession to this responsibility during his absence.
6.1.1.3 The Vice President, Oconee Nuclear Site, shall have corporate responsibility for overall plant nuclear safety and shall take any measures needed to ensure acceptable performance of the staff in operating, maintaining, and providing technical support to the plant to ensure nuclear safety.
The Senior Vice President, Nuclear Generation Department will be the Senior Nuclear Executive and have corporate responsibility for overall nuclear safety.
6.1.1.4 Incorporated in the staff of the station shall be personnel meeting the minimum requirements encompassing the training and experience described in Section 4 of ANSI/ANS-3.1-1978, "Selection and Training of Nuclear Power Plant Personnel" except for the Radiation Protection Manager, the Operations Superintendent and the Shift Operations Manager.
The Radiation Protection Manager shall have a bachelor's degree in a science or engineering subject or the equivalent in experience, including some formal training in radiation protection, and shall have at least five years of professional experience in applied radiation protection of which three years shall be in applied radiation protection work in one of Duke Energy Corporation's nuclear stations.
A qualified individual who does not meet the above requirements, but who has demonstrated the required radiation protection management capabilities and professional experience in applied radiation protection work at one of Duke Energy Corporation's multi-unit nuclear stations, may be appointed to the position of Radiation Protection Manager by the Station Manager, based on the recommendations of the Nuclear Technical Services Manager and as approved by the Site Vice President, Nuclear Operations.
The Operations Superintendent shall have a minimum of eight years of responsible nuclear or fossil station experience, of which a minimum of three years shall be nuclear station experience. A maximum of two years of the remaining five years of experience may be fulfilled by academic training, or related technical training, on a one-for-one time basis. The Operations Superintendent shall hold or have held a Senior Reactor Operator license.
Oconee - Units 1, 2, 3 6.1-1 Amendment No. 226(Unit 1)
Amendment No226(Unit 2)
Amendment No. 22 3Unit 3)
The Shift Operations Manager shall have a minimum of eight years of responsible nuclear or fossil station experience, of which a minimum of three years shall be nuclear station experience. A maximum of two years of the remaining five years of experience may be fulfilled by academic training, or related technical training on a one-for-one time basis. The Shift Operations Manager shall hold a Senior Reactor Operator license.
6.1.1.5 The individuals who train the operating staff and those who carry out radiation protection and quality assurance functions may report to the appropriate onsite manager; however, they shall have sufficient organizational freedom to ensure their independence from operating pressures.
6.1.1.6 Minimum operating shift crew requirements shall be as specified in Table 6.1-1.
6.1.1.7 Retraining and replacement of station personnel shall be in accordance with Section 5.5 of the ANSI/ANS-3.1-1978, "Selection and Training of Nuclear Power Plant Personnel."
6.1.1.8 A training program for the fire brigade shall meet or exceed the requirements of Section 27 of the NFPA Code-1975, except that training sessions may be held quarterly.
6.1.1.9 The Shift Manager is an experienced SRO, who has been instructed in additional academic subjects, and will be assigned on-shift to provide the accident assessment capability.
The operating experience assessment function will be provided by the Station Safety Review Group.
Oconee - Units 1, 2, 3 6.1-1 a Amendment No. 226(Unit 1)