ML15152A310

From kanterella
Jump to navigation Jump to search

NRR E-mail Capture - for Your Review - Draft Second Round RAI - Revised - Seabrook Radiation Monitor LAR (MF4572)
ML15152A310
Person / Time
Site: Seabrook 
Issue date: 06/01/2015
From: John Lamb
Plant Licensing Branch 1
To: Ossing M
NextEra Energy Seabrook
References
TAC MF4572
Download: ML15152A310 (4)


Text

1 NRR-PMDAPEm Resource From:

Lamb, John Sent:

Monday, June 01, 2015 10:05 AM To:

Ossing, Michael (Michael.Ossing@nexteraenergy.com)

Cc:

Kilby, Gary (Gary.Kilby@nexteraenergy.com); Blumberg, Mark; Shoop, Undine; Broaddus, Doug; Wilson, George

Subject:

For Your Review - DRAFT Second Round RAI - Revised - Seabrook Radiation Monitor LAR (MF4572)

Attachments:

RAI - Second Round - Revised - Seabrook Rad Monitor LAR.docx Importance:

High

Mike, Attached, for your review, is a Revised DRAFT second round RAI regarding the Seabrook Radiation Monitor License Amendment Request (LAR).

Please review to ensure that the questions are understandable, the regulatory basis is clear, there is no proprietary information contained in the Revised DRAFT RAI, and to determine if the information was previously docketed.

There is a conference call scheduled for June 3 to clarify the Revised DRAFT RAI, and how much time NextEra needs to respond to the RAI.

Thanks.

John

Hearing Identifier:

NRR_PMDA Email Number:

2125 Mail Envelope Properties (John.Lamb@nrc.gov20150601100400)

Subject:

For Your Review - DRAFT Second Round RAI - Revised - Seabrook Radiation Monitor LAR (MF4572)

Sent Date:

6/1/2015 10:04:39 AM Received Date:

6/1/2015 10:04:00 AM From:

Lamb, John Created By:

John.Lamb@nrc.gov Recipients:

"Kilby, Gary (Gary.Kilby@nexteraenergy.com)" <Gary.Kilby@nexteraenergy.com>

Tracking Status: None "Blumberg, Mark" <Mark.Blumberg@nrc.gov>

Tracking Status: None "Shoop, Undine" <Undine.Shoop@nrc.gov>

Tracking Status: None "Broaddus, Doug" <Doug.Broaddus@nrc.gov>

Tracking Status: None "Wilson, George" <George.Wilson@nrc.gov>

Tracking Status: None "Ossing, Michael (Michael.Ossing@nexteraenergy.com)" <Michael.Ossing@nexteraenergy.com>

Tracking Status: None Post Office:

Files Size Date & Time MESSAGE 565 6/1/2015 10:04:00 AM RAI - Second Round - Revised - Seabrook Rad Monitor LAR.docx 40595 Options Priority:

High Return Notification:

No Reply Requested:

No Sensitivity:

Normal Expiration Date:

Recipients Received:

ENCLOSURE OFFICE OF NUCLEAR REACTOR REGULATION REQUEST FOR ADDITIONAL INFORMATION FOR A LICENSE AMENDMENT REQUEST TO CHANGE TECHNICAL SPECIFICATION 3.3.3.1, RADIATION MONITORING FOR PLANTOPERATIONS NEXTERA ENERGY SEABROOK SEABROOK STATION DOCKET NOS. 50-443 TAC NO. MF4572 By application dated July 24, 2014, (Agencywide Documents Access and Management System (ADAMS) Accession Number ML14209A919), as supplemented by a letter dated December 11, 2014 (ADAMS Accession Number ML14349A644), NextEra Energy Seabrook, LLC (NextEra) submitted a license amendment (LAR) for Seabrook Station.The LAR, in part, proposes to modify the applicability of Technical Specification 3.3.3.1, Radiation Monitoring for Plant Operations, by adding a requirement for the control room air intake radiation monitors to be operable during the movement of irradiated fuel.

The Nuclear Regulatory Commission(NRC) Staff completed our review and determined that the enclosed additional information is required to complete the evaluation.

ARCB2-RAI-3 NUREG-0800, Standard Review Plan (SRP) 15.0.1, Radiological Consequence Analyses Using Alternative Source Terms, dated July 2000 (ADAMS Accession Number ML003734190),states, in part that:

The methodology and assumptions for calculating theradiological consequences should reflect the regulatory positions of RG[Regulatory Guide] -1.183.

Appendix B of RG-1.183, Alternative Radiological Source Terms for Evaluating Design Basis Accidents at Nuclear Power Reactors, dated July 2000 (ADAMS Accession Number ML003716792), Regulatory Position 1.1 states, in part that:

The number of fuel rods damaged during the accident should be based on a conservative analysis that considers the most limiting case. This analysis should consider parameterssuch as the weight of the dropped heavy load or the weight of a dropped fuel assembly(plus any attached handling grapples), the height of the drop, and the compression,torsion, and shear stresses on the irradiated fuel rods. Damage to adjacent fuelassemblies, if applicable (e.g., events over the reactor vessel), should be considered.

Updated Final Safety Analysis Report Section 15.7.4.3 states:

The FHA [fuel handling accident analysis]dose consequence analysis is consistent with the guidance provided in RG 1.183 Appendix B, Assumptions for Evaluating the Radiological Consequences of a Fuel Handling Accident.

The proposed change to the applicability of Technical Specification 3.3.3.1, Radiation Monitoring for Plant Operations, (i.e. Table 3-6, Functional Units 5.a.1 and 5.a.2) from requiring the operability of the control room air intake radiation monitors from All Modes to include during movement of irradiated fuel does not address movement of loads other than irradiated fuel assemblies over the spent fuel pool. For example, Section 15.7.4.1 of the Updated Final Safety Analysis Report considers dropping new fuel assemblies. Section 15.7.4.1 states that:

Dropping or damaging an assembly [not an irradiated assembly] within the Fuel Storage Building (FSB) is another postulated accident addressed in this analysis.

It is unclear how the proposed revised applicability for Functional Units 5.a.1 and 5.a.2 are derived from the Seabrook fuel handling accident analysis and how the fuel handling analysis bounds Regulatory Guide 1.183, Regulatory Position 1.1. To clarify, how does the fuel handling analysis determine the most limiting control room dose and how does the fuel handling analysis show that the limiting control room dose is not the drop of a new fuel assembly or object1 other than a recently irradiated fuel assemblyassuming no credit2 for the control room intake monitors? Please provide enough detail (inputs, assumptions and methodology) so that the NRC staff can independently verify the results of the fuel handling accident. Alternatively, change the Applicable Modes of Technical Specification 3.3.3.1, Table 3.3-6, Functional Units 5.a.1 and 5.a.2 to include during movement of fuel assemblies and objects3 over irradiated fuel.

1Object rather than load is consistent with the terminology in the current Seabrook technical specifications (See Technical Specifications 3.8.1.2).

2Regulatory Guide 1.183, Regulatory Position 5.1.2 states that credit may be taken for accident mitigation features that are classified as safety-related and are required to be operable by technical specifications.

The control room intake monitors are not required to be operable by technical specifications during the movement of new fuel assemblies and other loads and, therefore, would not be credited in the fuel handling accident safety analysis.

3Objects not covered under the Heavy Loads program.