ML14183A601

From kanterella
Jump to navigation Jump to search
Proposed TS 4.5.1.4,relaxing Surveillance Interval for Containment Spray Nozzles
ML14183A601
Person / Time
Site: Robinson 
Issue date: 12/12/1994
From:
CAROLINA POWER & LIGHT CO.
To:
Shared Package
ML14183A602 List:
References
NUDOCS 9412200074
Download: ML14183A601 (5)


Text

Enclosure 6 to Serial: RNP/94-1870 H. B. ROBINSON STEAM ELECTRIC PLANT, UNIT NO. 2 NRC DOCKET NO. 50-261/LICENSE NO. DPR-23 REQUEST FOR TECHNICAL SPECIFICATIONS CHANGE CONTAINMENT SPRAY SURVEILLANCE INTERVAL TECHNICAL SPECIFICATIONS PAGES 9412200074 941212 PDR ADOCK 05000261 P

PDR

Containment Spray System 4.5.1.3 System tests shall be performed at each refueling interval. The test shall be performed with the isolation valves in the spray supply lines at the containment and spray additive tank blocked closed. Operation of the system is initiated by tripping the normal actuation instrumentation.

4.5.1.4

-- Phe4-- spray nozzle/

f.nzotg at least every. fkf years.

4.5.1.5 The tests discussed in 4.5.1.3 and 4.5.1.4 will be considered satisfactory if visual observations indicate all components have operated satsifactorily.

Containment Fan Coolers 4.5.1.6 Each fan cooler unit shall be tested at intervals not to exceed one month to verify proper operation of all essential features including valves, dampers and piping.

4.5.2 Component Verification 4.5.2.1 When the reactor coolant pressure is in excess of 1,000 psi, it shall be verified at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> (from the RTGB indicators/controls) that the following valves are in their proper position with control power to the valve operators removed.

Valve Number Valve Position 1-MOV 862 A&B Open 2-MOV 863 A&B Closed 3-MOV 864 A&B Open 4-MOV 866 A&B Closed 4.5-2 Amendment No. 83

addition, the active components (pumps and signal valves) are to be tested quarterly to check the operation of the starting circuits and to verify that the pumps are in satisfactory running order.

The quarterly test interval is based on the judgment that more frequent testing would not significantly increase the reliability (i.e., the probability that the component would operate when required), and that more frequent testing would result in increased wear over a long period of time.

Quarterly testing of valves is consistent with the requirements of ASME Section XI.

Quarterly testing of the safety injection pumps, residual heat removal pumps, containment spray pumps and the boron injection tank isolation valves is not required when in the cold shutdown condition. These components are not required for plant safety when the reactor is in cold shutdown and testing during this condition will result in unnecessary wear on the equipment.

Other systems that are also important to the emergency cooling function are the accumulators, the Component Cooling System, the Service Water System and the containment fan coolers. The accumulators are a passive safeguard.

In accordance with Specification 4.1, the water volume and pressure in the accumulators are checked periodically. The other systems mentioned operate when the reactor is in operation and by these means are continuously monitored for satisfactory performance.

With the containment spray pump discharge valves closed and the spray headers drained of any solution, low pressure air or smoke can be blown through test connections. This surveillance requirement ensures that each spray nozzle is unobstructed and provides assurance that spray coverage of the containment during an accident is not degraded.

Due to the passive design of the nozzle, a test at 10 year intervals is considered adequate to detect obstruction of the nozzles.

References (1) FSAR Section 6.2 (2) FSAR Section 6.4 (3) FSAR Section 6.1 (4) CP&L report and supplemental letters of September 29, November 5, December 8, 1971, and March 20, 1972.

4.5-4 Amendment No.

83

Containment Spray System 4.5.1.3 System tests shall be performed at each refueling interval.

The test shall be performed with the isolation valves in the spray supply lines at the containment and spray additive tank blocked closed. Operation of the system is initiated by tripping the normal actuation instrumentation.

4.5.1.4 Verify each spray nozzle is unobstructed at least every 10 years.

4.5.1.5 The tests discussed in 4.5.1.3 and 4.5.1.4 will be considered satisfactory if visual observations indicate all components have operated satisfactorily.

Containment Fan Coolers 4.5.1.6 Each fan cooler unit shall be tested at intervals not to exceed one month to verify proper operation of all essential features including valves, dampers and piping.

4.5.2 Component Verification 4.5.2.1 When the reactor coolant pressure is in excess of 1,000 psi, it shall be verified at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> (from the RTGB indicators/controls) that the following valves are in their proper position with control power to the valve operators removed.

Valve Number Valve Position 1-MOV 862 A&B Open 2-MOV 863 A&B Closed 3-MOV 864 A&B Open 4-MOV 866 A&B Closed 4.5-2 Amendment No.

addition, the active components (pumps and signal valve are to be tested quarterly to check the operation of the starting circuits and to verify that the pumps are in satisfactory running order.

The quarterly test interval is based on the judgment that more frequent testing would not significantly increase the reliability (i.e., the probability that the component would operate when required), and that more frequent testing would result in increased wear over a long period of time.

Quarterly testing of valves is consistent with the requirements of ASME Section XI.

Quarterly testing of the safety injection pumps, residual heat removal pumps, containment spray pumps and the boron injection tank isolation valves is not required when in the cold shutdown condition. These components are not required for plant safety when the reactor is in cold shutdown and testing during this condition will result in unnecessary wear on the equipment.

With the containment spray pump discharge valves closed and the spray headers drained of any solution, low pressure air or smoke can be blown through test connections. This surveillance requirement ensures that each spray nozzle is unobstructed and provides assurance that spray coverage of the containment during an accident is not degraded. Due to the passive design of the nozzle, a teat at 10 year intervals is considered adequate to detect obstruction of the nozzles.

Other systems that are also important to the emergency cooling function are the accumulators, the Component Cooling System, the Service Water System and the containment fan coolers. The accumulators are a passive safeguard. In accordance with Specification 4.1, the water volume and pressure in the accumulators are checked periodically. The other systems mentioned operate when the reactor is in operation and by these means are continuously monitored for satisfactory performance.

References (1) FSAR Section 6.2 (2) FSAR Section 6.4 (3) FSAR Section 6.1 (4) CP&L report and supplemental letters of September 29, November 5, December 8, 1971, and March 20, 1972.

4.5-4 Amendment No.