04/11/2014 U.S. Nuclear Regulatory Commission Operations Center Event Report Page I Part 21 (PAR)

Event#

50020 Rep Org: ROSEMOUNT NUCLEAR INSTUMENTS, INC Notification Date I Time: 04110/2014 11:50 (EDT)

Supplier: ROSEMOUNT NUCLEAR INSTUMENTS, INC Event Date I Time: 04/10/2014 (CDT)

Last Modification: 04/10/2014 Region:

3 Docket #:

City: CHANHASSEN Agreement State:

Yes County:

License #:

State:

MN NRC Notified by: DUYEN PHAM Notifications: PATTY PELKE R3DO HQ Ops Officer: CHARLES TEAL PART 21 GROUP EMAIL Emergency Class: NON EMERGENCY 10 CFR Section:

21.21(d)(3)(i)

DEFECTS AND NONCOMPLIANCE PART 21 - MODEL 1154HP TRANSMITTERS WITH INTEGRAL 1159 REMOTE DIAPHRAGM SEALS MAY EXHIBIT DEGRADED FUNCTIONAL RELIABILITY "Pursuant to 10 CFR Part 21, section 21.21(b), Rosemount Nuclear Instruments, Inc. (RNII) is writing to inform you that certain Model 1154HP transmitters with integral 1159 Remote Diaphragm Seals may exhibit degraded functional reliability.

"The standard maximum working pressure for Model 1154 transmitters with integral 1159 Remote Diaphragm Seals is 2000 psi.

"Per the unique requirements of Point Beach Nuclear Generating Station, Model 11 54HP5RAGN0080 pressure transmitters with integral 11 59A50AS0 111 Remote Diaphragm Seals were manufactured to operate at a non-standard maximum working pressure of 2750 psi.

"Once installed in the field, two transmitters exhibited unexpected drift in the output signal when operated at line pressures of approximately 2235 psi.

"To date there are no known additional reported functional reliability issues with other Model 11 5x Series transmitters with integral 1159 Remote Diaphragm Seals in a similar configuration.

"RNII does not have complete information relating to specific plant applications and therefore cannot determine the potential effects of the condition on plant operation.

"This notification affects seven Model 1154HP transmitters with integral 1159 Remote Diaphragm Seals shipped to Point Beach Nuclear Generating Station since March 2013."

04/11/2014 U.S. Nuclear Regulatory Commission Operations Center Event Report Page 2 Name and address of the individual providing the information:

Mr. Marc D. Bumgarner Vice President & General Manager Rosemount Nuclear Instruments, Inc.

8200 Market Boulevard Chanhassen, MN 55317

'Apr/10/2014 10:50:16 AM EPM OUT RMT NUCLEAR 952-949-5201 1/4 EMERSON.

Process Management ROSEMOUNT" Nuclear 8200 Market Boulevard Chanhasaen, MN 55317 USA Tel 1 (952) 949-5210 Fax 1 (952) 949-5201 Facsimile

/NO. of Pages:4 Including cover page To:

NRC Operations Center Fax Number:

(301) 816-5151 Date:

From:

E-Mail:

Subject:

Thursday, April 10, 2014 Duyen Pham, Quality Manager Duyen.Phamt&Emerson.com Phone:

(952) 949-5383 Notification under 10 CFR Part 21 on certain Rosemount Model 1154HP transmitters with Integral 1159 Remote Diaphragm Seals shipped to Point Beach Nuclear Generating Station Rosemount Nuclear Instruments, Inc. is submitting the attached notification as required by 10 CFR Part 21. Please contact me If you have any questions, Sincerely, Duyen Pham Quality Manager Rosemount Nuclear Instruments, Inc.

www.RossrnountNuclear.com RNIl.lnfod1EmepsonProceus.com

Apr/10/2014 10:50:16 AM EPM OUT RMT NUCLEAR 952-949-5201 2/4 Rosemount Nuclear Instruments, Inc.

8200 Market Boulevard ROSEMOUNTI Chanhassen, MN 85317 USA Nuclear Tl (952) 94M21 0 Fax 1 (952) 94M-201 www.RosemountN uclear.com 10 April 2014 U.S. Nuclear Regulatory Commission Washington, DC 20555-0001 Attn: Document Control Desk Re: Notification under 10 CFR Part 21 on certain Rosemount Model 1154HP transmitters with Integral 1159 Remote Diaphragm Seals shipped to Point Beach Nuclear Generating Station Pursuant to 10 CFR Part 21, section 21.21(b), Rosemount Nuclear Instruments, Inc. (RNII) is writing to inform you that certain Model 11 54HP transmitters with integral 1159 Remote Diaphragm Seals may exhibit degraded functional reliability.

  • The standard maximum working pressure for Model 1154 transmitters with Integral 1159 Remote Diaphragm Seals is 2000 psi.
  • Per the unique requirements of Point Beach Nuclear Generating Station, Model I I54HPSRAGN0080 pressure transmitters with integral 11 59A5ASO0111 Remote Diaphragm Seals were manufactured to operate at a non-standard maximum working pressure of 2750 psi.
  • Once Installed in the field, two transmitters exhibited unexpected drift In the output signal when operated at line pressures of approximately 2235 psi.

To date there are no known additional reported functional reliability issues with other Model 11 5x Series transmitters with integral 1159 Remote Diaphragm Seals in a similar configuration.

RNII does not have complete information relating to specific plant applications and therefore cannot determine the potential effects of the condition on plant operation.

This notification affects seven Model 1154HP transmitters with integral 1159 Remote Diaphragm Seals shipped to Point Beach Nuclear Generating Station since March 2013.

1.0 Name and address of the individual providing the Information:

Mr. Marc D. Bumgarner Vice President & General Manager Rosemount Nuclear Instruments, Inc.

8200 Market Boulevard Chanhassen, MN 55317 2.0 Identification of Items supplied:

Seven 1154HP transmitters with integral 1159 Remote Diaphragm Seals shipped from; RNII to Point Beach Nuclear Generating Station since March 2013.

Page 1 of 2

'Apr/10/2014 10:50:16 AM EPM OUT RMT NUCLEAR 952-949-5201 3/4 3.0 Identification of firm supplying the Item:

Rosemount Nuclear Instruments, Inc.

8200 Market Boulevard Chanhassen, MN 55317 4.0 Nature of the failure and potential safety hazard:

Technical Overview:

Failure analysis efforts have demonstrated the output drift is due to a slow loss of fill fluid in one of the 1159 Remote Diaphragm Seal systems. The loss of fill fluid is due to a leak in the system, however failure analysis efforts to date have not determined the leak path.

Testing suggests the leak may be related to non-standard processing associated 1159 applications requiring maximum working pressures in excess of 2000 psi.

Potential Safety Hazard:

A leak in 1159 capillary fill fluid can cause the output to slowly drift over time. Excessive loss of fill fluid, over time, may result in a loss of transmitter functionality.

On April 4, 2014, RNI1 concluded that a substantial safety hazard may exist.

5.0 The corrective action which is taken, the name of the Individual or organization responsible for that action, and the length of time taken to complete that action:

Existing and new orders for Model 1I54HP transmitters with Integral 1159 Remote Diaphragm Seals with a maximum working pressure above 2000 psi will undergo extended production drift testing to verify performance prior to shipment.

Mr. Marc Bumgarner, VP & GM of Rosemount Nuclear Instruments, Inc. is responsible for any further action related to this issue.

6.0 Any advice related to the potential failure of the item:

RNII recommends implementing appropriate drift monitoring of the seven affected Model 1154HP transmitters with integral 1159 Remote Diaphragm Seals.

RNII is committed to the nuclear Industry and remains dedicated to the supply of high quality products to our customers. If you have any questions, or require additional information related to this Issue, please contact: Mike Dougherty (208) 865-1112.

Sincerely, Marc DBugrne Vice President & General Manager Rosemount Nuclear Instruments, Inc.

Enc.: Appendix A - List of Affected Transmitters by Serial Number

-O" Nuclear Page 2 of 2

Apr/10/2014 10:50,16 AM EPM OUT RMT NUCLEAR 952-949-5201 4/4 Appendix A: List of Affected Transmitters by Serial Number 10 CFR Part 21 Notification - 10 APRIL 2014 NEXTERA ENERGY, POINT BEACH LLC Sales Order Purchase Order Model Number Serial Number Ship Date Number 3492435 2300727 REV 003 1154HPSRGN0080 w/1159ASOAS0111 548595 Mar-13 REL 00001 3492435 2300727 REV 003 1154HPSRGN0080 w/ 1159ASOAS0111 548596 Mar-13 REL 00001 3492435 2300727 REV 003 1154HPSRGNOOBO w/II SA50AS01II 548597 Mar-13 REL 00001 3492435 2300727 REV 003 1154HP5RGN0080 w/1159A50AS0111 548615 Mar-13 REL 00001 3737832 02300727 REV 001 1154HPbRGN0080 w/1159A50AS0111 551728 Jan-14 REL 00005 3737829 02300727 REV 001 1154HPSRGN0OBO w/1159A50AS0111 551742 Feb-14 REL 00004 I

t 1

3737829 02300727 REV 001 1154HP*SRGN'080 w/1159A50A80111 551743 Feb-14 REL 00004 Page I of I