FIGURE 3.5.1-1 4 KV BUSES 1C & 2.C UNDER-VOLTAGE TRIP SETTING LOSS OF BUS VOLTAGE ( CV-7) 100 12870 VOLTS (See note 3)

~10 0I III A.2870 VOLTS 00 13.1 SEONDS 4160 VOLTS TO 0 VOLT 1.0 SECOND 1

1600 2000 2400 2800 3200 3600 9102040279 9101:31 BUS VOLTAGE PDR ADOCK 05000206 P

PDR Notes: 1. Trip voltage tolerance: +/- 3 %

2. Trip time tolerance: +/- 10 %
3. Range for accurate relay operation: < 90 % of the tap voltage SAN ONOFRE -

UNIT 1 3.5-8 AMENDMENT NO: