1 NRR-PMDAPEm Resource From:

Lyon, Fred Sent:

Thursday, November 14, 2013 8:35 AM To:

'JHiller@ameren.com' Cc:

'Elwood, Thomas B'; 'Maglio, Scott A'

Subject:

FW: Callaway NFPA 805 LAR, FPE RAI 20 (TAC No. ME7046)

Attachments:

ME7046 Callaway AFPB FPE RAI 20 NFPA 805 LAR.docx Importance:

High From: Robinson, Jay Sent: Thursday, November 14, 2013 7:54 AM To: Lyon, Fred Cc: Pearson, Alayna; Barrett, Harold; Klein, Alex; Dinh, Thinh; Kichline, Michelle; Wall, Scott; Fields, Leslie; Wu, Angela

Subject:

Callaway NFPA 805 LAR, FPE RAI 20 (TAC No. ME7046)

Fred, Attached is the RAI discussed at the meeting earlier this week. The RAI has been reviewed and approved by the AFPB Branch Chief Alex Klein.

Also be advised that a Sensitive Unclassified Non-Safeguards Information (SUNSI) review of this RAI against the criteria of SECY-04-0191 has been performed and it was concluded that the RAI does not contain any sensitive unclassified (non-safeguards) information to be withheld from public disclosure.

Please forward this RAI to the licensee. A response is needed as soon as possible. If you have any questions or need any additional information, please let me know. Thanks. Jay.

Hearing Identifier:

NRR_PMDA Email Number:

921 Mail Envelope Properties (A56E37EC1CBC8045910287CEF5E7AE6C01D6E858A720)

Subject:

FW: Callaway NFPA 805 LAR, FPE RAI 20 (TAC No. ME7046)

Sent Date:

11/14/2013 8:35:01 AM Received Date:

11/14/2013 8:34:00 AM From:

Lyon, Fred Created By:

Fred.Lyon@nrc.gov Recipients:

"'Elwood, Thomas B'" <TElwood@ameren.com>

Tracking Status: None

"'Maglio, Scott A'" <SMaglio@ameren.com>

Tracking Status: None

"'JHiller@ameren.com'" <JHiller@ameren.com>

Tracking Status: None Post Office:

HQCLSTR01.nrc.gov Files Size Date & Time MESSAGE 939 11/14/2013 8:34:00 AM ME7046 Callaway AFPB FPE RAI 20 NFPA 805 LAR.docx 30725 Options Priority:

High Return Notification:

No Reply Requested:

No Sensitivity:

Normal Expiration Date:

Recipients Received:

1 REQUEST FOR ADDITIONAL INFORMATION LICENSE AMENDMENT REQUEST TO ADOPT NATIONAL FIRE PROTECTION ASSOCIATION STANDARD 805 PERFORMANCE-BASED STANDARD FOR FIRE PROTECTION FOR LIGHT WATER REACTOR GENERATING PLANTS CALLAWAY PLANT (TAC NO. ME7046)

Office of Nuclear Reactor Regulation Division of Risk Assessment Fire Protection Branch Fire Protection Engineering RAI 20 In Attachment X of the License Amendment Request (LAR) dated August 29, 2011, (ADAMS Accession No. ML112420048), Approval Request 1 requests the elimination of the requirement to enter Technical Specification 3.0.3 for an inoperable fire suppression water system coupled with inability to establish a backup fire protection water system within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. The request indicates that the procedure that is currently used to address compensatory actions, does not address the National Fire Protection Association Standard 805 (NFPA 805), "Performance-Based Standard for Fire Protection for Light Water Reactor Electric Generating Plants - 2001 Edition," requirements. The request states that the procedure...will be used to establish the required compensatory actions and impairment durations following the transition to NFPA 805.

However, there is no implementation item associated with the revision of this procedure to meet the requirements of NFPA 805 Section 3.2.3(2). Describe the actions needed to bring the procedure into compliance with these requirements and update LAR Attachment S, Table S-3 as necessary.