Forwards Identification of Equipment Installed in Mild Environs for TMI Mods,Per NUREG-0578,supplementing Util Re Environ Qualification of Electrical Equipment. Updated Schedule for Documentation & Testing Provided
ML13317A316
Person / Time
Site: San Onofre 
Issue date: 09/07/1982
From: Baskin K
Southern California Edison Co
To: Crutchfield D
Office of Nuclear Reactor Regulation
References
RTR-NUREG-0578, RTR-NUREG-578 NUDOCS 8209100110
Download: ML13317A316 (28)


Text

Southern California Edison Company P. 0. BOX Boo 2244 WALNUT GROVE AVENUE ROSEMEAD, CALIFORNIA 91770 K. P. BASKIN TELEPHONE MANAGER OF NUCLEAR ENGINEERING, September 7, 1982 (213) 572.1401 SAFETY, AND LICENSING Director of Nuclear Reactor Regulation Attention: D. M. Crutchfield, Chief Operating Reactors Branch No. 5 Division of Licensing U.S. Nuclear Regulatory Commission Washington, D.C. 20555 Gentlemen:

Subject:

Docket No. 50-206 Environmental Qualification of Electrical Equipment San Onofre Nuclear Generating Station Unit 1 By letter dated July 2, 1982, we provided you with the environmental qualification documentation for the electrical equipment installed in potentially harsh environments for TMI requirements.

The letter indicated that we would be providing the identification of the equipment installed in mild environments for TMI modifications. Provided as an enclosure is the listing of the TMI equipment installed in mild environments. The listing identifies the equipment, provides its location in the plant, and provides the reference for the TMI requirement.

Our July 2, 1982 letter also indicated that qualification documents and qualification test schedules for some items would be provided at a later date.

Specifically:

1. The review of qualification documentation for the Reactor Coolant Temperature Detectors would be completed and the documents submitted by July 30, 1982. The qualification documentation is still under review. We are in the process of resolving comments with the manufacturer. This effort is scheduled to be completed by October, 1982.
2. The review of qualification documentation for Namco Limit Switches was scheduled to be completed by July 30, 1982. This documentation is still under review and should be completed by the end of October, 1982.

AOY 8209100110 820907 PDR ADOCK 05000206 P

PDR

Mr. D.

September 7, 1982

3. It was expected that we would have a firm schedule for testing of the containment hydrogen monitors by July 30, 1982.

The qualification testing and the associated test reports are scheduled to be completed by January, 1983.

If you have any questions regarding this matter, please let me know.

Very truly yours, K. P. Baskin Manager of Nuclear Engineering, Safety, and Licensing Enclosure cc:

Cyril J. Crane.

Franklin Research Center Parkway at Twentieth Philadelphia, PA 19103

SONGS 1 EQIPM4ENT QUALIFICATION

SUMMARY

TMI EQUIFlENT-MILD ENVIRONMENTS NUREG 0578 Section:

2.1.1 COMPONENT CONTROL MODIFICATIONS -

FEEDWATER BYPASS VALVES Page 1 of 26 NUREG INSTL.

0737 PLANT MFG.

INSTL.

BEFORE REF.

ITEM NO.

TAG NO.

EQUIPMENT MODEL NO.

LOCATION DATE 1/1/81 SEC.

1 PB 142, Momentary Action Master Specialties 10 2/20/81 No IIE3.1 PB 143, Switch-Lite 1OH7A1C5F4 PB 144 J 14L (W)N1

SONGS 1 EQUIPMENT QUALIFICATION

SUMMARY

TMI EQUIPMENT-MILD ENVIRONMENTS NUREG 0578 Section:

2.1.3b-1 SUBCOOLING MONITORING SYSTEM Page 2 of 26 NUREG INSTL.

0737 PLANT MFG. &

INSTL.

BEFORE REF.

ITEM NO.

TAG NO.

EQUIPMENT MODEL NO.

LOCATION DATE 1/1/81 SEC.

1 TS-2001, Thermocouple Honeywell, Inc.

10 3/13/81 No IIF2 2002, 2003, Switch 300172-83-7 2004 2

TI-2402A/

Dual Temperature Sigma Instruments 10 3/13/81 No IIF2 TI-2412A

'Indicators 9270-02-D-V-B TI-2422A/

(Dual)

TI-2009 TI-2425X2/

TI-2010 TI-3401A/

TI-3411A TI-3421A/

TI-3009 TI-3425X1/

TI-3010 3

TYV-2001 & 2 EMF to Voltage Foxboro N-2Al-T2V 10 3/13/81 No IIF2 TYV-2003 & 4 Converter TYV-3001 & 2 TYV-3003 & 4

SONGS 1 EQUIPMENT QUALIFICATION

SUMMARY

TMI EQUIPMENT-MILD ENVIRONMENTS NUREG 0578 Section:

2.1.3b-1 SUBCOOLING MONITORING SYSTEM Page 3 of 26 NUREG INSTL.

0737 PLANT MFG. &

INSTL.

BEFORE REF.

ITEM NO.

TAG NO.

EQUIPMENT MODEL NO.

LOCATION DATE 1/1/81 SEC.

4 TYV-2402A Resistance to Foxboro N-2Al-P2V 10 3/13/81 No IIF2 TYV-2412A Voltage Converter TYV-2422A TYV-3401A TYV-3411A TYV-3421A 5

TYA-2008 Signal Selector Foxboro N-2AP+SSL 10 3/13/81 No IIF2 TYA-2009 Hi/Lo TYA-3008 TYA-3009 PYA-2425X2 6

TYB-2010 Dual Absolute Alarm Foxboro N-2AP 10 3/13/81 No IIF2 TYB-3010

+ ALM-AR 7

TYC-2001 Contact Output Foxboro N-2AO-L2C-R 10 3/13/81 No IIF2 TYC-2010 Isolator Relay TYC-3001 Switch TYC-3010

SONGS 1 EQUIPMENT QUALIFICATION

SUMMARY

TMI EQUIPMENT-MILD ENVIRONMENTS NUREG 0578 Section:

2.1.3b-1 SUBCOOLING MONITORING SYSTEM Page 4 of 26 NUREG INSTL.

0737 PLANT MFG.

INSTL.

BEFORE REF.

ITEM NO.

TAG NO.

EQUIPMENT MODEL NO.

LOCATION DATE 1/1/81 SEC.

8 TYL-2001 Contact Input Foxboro N-2Al-C2L 10 3/13/81 No IIF2 TYL-3001 Isolator 9

PYV-425 Current-to-Voltage Foxboro-N-2Al-I3V 10 3/13/81 No IIF2 Converter ECEP 9003 10 TYS-2008 Dual Linear Foxboro N-2AP 10 3/13/81 No IIF2 TYS-3008 Scaler

& DLS 11 TQ-2009 Summer Foxboro N-2AP & Sum 10 3/13/81 No IIF2 TQ-3009 12 PYG-2425X2 Signal Foxboro N-2AP & SGC 10 3/13/81 No IIF2 PYG-3425X1 Characterizer

SONGS 1 EQUIPMENT QUALIFICATION

SUMMARY

TMI EQUIPMENT-MILD ENVIRONMENTS NUREG 0578 Section:

2.1.4 CONTAINMENT ISOLATION UPGRADING Page 5 of 26 NUREG INSTL.

0737 PLANT MFG. &

INSTL.

BEFORE REF.

ITEM NO.

TAG NO.

EQUIPMENT MODEL NO.

LOCATION DATE 1/1/81 SEC.

p 1

Connector Plug (Note 3) 10 4/1/81 No IIE4.2 MS-24266R22B12SN 2

Connector Receptacle (Note 3) 10 4/1/81 No IIE4.2 MS-24264R22B12 3

Snap Lock Switch NAMCO Controls, 10 4/1/81 No IIE4.2 EA 170-11302 4

Snap Lock Switch NAMCO Controls 10 4/1/81 No IIE4.2 EA 170-12302 5

Momentary Action Master Specialties 10 4/1/81 No IIE4.2 Switch-Lite 1OH7A1C5F1 J14L(R)N1 6

Momentary Action Master Specialties 10 4/1/81 No IIE4.2 Switch-Lite 10H7A1C5F1 J14L(G)N1 7

Alternate Action Master Specialties 10 4/1/81 No IIE4.2 Switch-Lite 10H7A1C5F4 J14L(R)N1

SONGS 1 EQUIPMENT QUALIFICATION

SUMMARY

TMI EQUIPMENT-MILD ENVIRONMENTS NUREG 0578 Section:

2.1.4 CONTAINMENT ISOLATION UPGRADING Page 6 of 26 NUREG INSTL.

0737 PLANT MFG. &

INSTL.

BEFORE REF.

ITEM NO.

TAG NO.

EQUIPMENT MODEL NO.

LOCATION DATE 1/1/81 SEC.

8 PY 1120 Current-to-Voltage Foxboro N-2Al-I2V 10 4/1/81 No IIE4.2 A, B, C Converter PY 1121 A, B, C PYV 3000

.A, B, C PYV 3459 B 9

PA 1120 Dual Aboslute Alarm Foxboro N-2AP+ALM-AR 10 4/1/81 No IIE4.2 A, B, C PA 1121 A, B, C PYB 3000 A, B, C 10 PY1120 Solid State Logic Foxboro N-2AX+DSS 10 4/1/81 No IIE4.2 PY1121 Card 11 PC1120-1,-2 Contact Output Foxboro N-2AO-L2C-R 10 4/1/81 No IIE4.2 PC1121-1,-2 Isolator Relay PYC 3000 A, B, C 12 YE-1120 Power Supply Foxboro N-2AX+PS9A 10 4/1/81 No IIE4.2 YE-1121

SONGS 1 EQUIPMENT QUALIFICATION

SUMMARY

TI EQUIPMENT-MILD ENVIRONMENTS NUREG 0578 Section:

2.1.5a.

POST-ACCIDENT HYDROGEN CONTROL-HYDROGEN RECOMBINERS Page 7 of 26 NUREG INSTL.

0737 PLANT MFG. &

INSTL.

BEFORE REF.

ITEM NO.

TAG NO.

EQUIPMENT MODEL NO.

LOCATION DATE 1/1/81 SEC.

1 C73, C74 Control Panel Westinghouse, 10 3/6/81 No IIE4.1 Model B 2

C75, C76 Power Supply Panel Westinghouse, 16 & 17 3/6/81 No IIE4.1 Model B

SONGS 1 EQUIPMENT QUALIFICATION

SUMMARY

TMI EQUIPMENT-MILD ENVIRONMENTS NUREG 0578 Section:

2.1.7 AUXILIARY FEEDWATER Page 8 of 26 NUREG INSTL.

0737 PLANT MFG. &

INSTL.

BEFORE REF.

ITEM NO.

TAG NO.

EQUIPMENT MODEL NO.

LOCATION DATE 1/1/81 SEC.

1 LLL-3400A,B, Switch/Indicating Master Specialties, 10 4/17/81 No C,D,E Light-Red 10H7A1C-5F1-J14L (R)N1R1V14 2 11-2012 Indicator Westinghouse, V-252 10 4/17/81 No 3 LT-2400A,B,C Indicator-Single Sigma, 9270-01-D-VB 10 4/17/81 No LT-3400A,B,C FI-3453 FI-3454 FI-3455 4 LI-6A Indicator-Single Sigma, 9270-20-D-VB 10 4/17/A1 No LI-6B with Alarm Switch 5 PI-2010A/2011 Indicator-Dual Sigma, 9270-02-D-VB 10 4/17/81 No PI-3010A/3011

SONGS 1 EQUIPMENT QUALIFICATION

SUMMARY

TMI EQUIPMENT-MILD ENVIRONMENTS NUREG 0578 Section: 2.1.7 AUXILIARY FEEDWATER Page 9 of 26 NUREG INSTL.

0737 PLANT MFG. &

INSTL.

BEFORE REF.

ITEM NO.

TAG NO.

EQUIPMENT MODEL NO.

LOCATION DATE 1/1/81 SEC.

6 LYC-2400A, Logic to Contact Foxboro N-2AO-L2C-R 10 4/17/81 No B, C, D, E, F Output Converter PYC-2010A Logic to Contact Foxboro N-2AO-L2C-R 10 4/17/81 No PYC-2011A,B Output Converter LYC-2400G, Logic to Contact Foxboro N-2AO-L2C-R 10 4/17/81 No H, I Output Converter PYC-2010B Logic to Contact Foxboro N-2AO-L2C-R 10 4/17/81 No Output Converter ZYC-2533D, C Logic to Contact Foxboro N-2AO-L2C-R 10 4/17/81 No Output Converter LYC-3400A, Logic to Contact Foxboro N-2AO-L2C-R 10 4/17/81 No B, C, D, E, F Output Converter

)

PYC-3010A Logic to'Contact Foxboro N-2AO-L2C-R 10 4/17/81 No Output Converter LYC-3400G, Logic to Contact Foxboro N-2AO-L2C-R 10 4/17/81 No H, I, J Output Converter PYC-3010B Logic to Contact Foxboro N-2AO-L2C-R 10 4/17/81 No Output Converter ZYC-3531, Logic to Contact Foxboro N-2AO-L2C-R 10 4/17/81 No 3545 Output Converter

SONGS 1 EQUIPMENT QUALIFICATION

SUMMARY

TMI EQUIPMENT-MILD ENVIRONMENTS NUREG 0578 Section:

2.1.7 AUXILIARY FEEDWATER Page 10 of 26 NUREG INSTL.

0737 PLANT MFG. &

INSTL.

BEFORE REF.

ITEM NO.

TAG NO.

EQUIPMENT MODEL NO.

LOCATION DATE 1/1/81 SEC.

7 PYY-2010 Solid State Logic Foxboro N-2AX + DSS 10 4/17/81 No LYY-2400B Module LYY-2400A PYY-3010 LYY-3400B LYY-3400A 8

FYS-3453A Dual Linear Scaler Foxboro N-2AP + DLS 10 4/17/81 No FYS-3454A FYS-3455A 9

LYL-2400A, B Contact to Logic Foxboro N-2Al-C2L 10 4/17/81 No LYL-3400A, B Converter 10 FYQ-3453A Square Root Foxboro N-2AP+SQE 10 4/17/81 No FYQ-3454A Extractor FYQ-3455A 11 FYI-2300 Voltage to Current Foxboro N-2AO-V2I 10 4/17/81 No FYI-2301 Converter FYI-3300 FYI-3301 12 FYI-3454 Voltage to Current Foxboro N-2AO-VAI FYI-3455 Converter (ECEP 9206)

FYI-3453 (Isolator)

SONGS 1 EQUIPMENT QUALIFICATION

SUMMARY

TMI EQUIPMENT-MILD ENVIRONMENTS NUREG 0578 Section:

2.1.7 AUXILIARY FEEDWATER Page 11 of 26 NUREG INSTL.

0737 PLANT MFG. &

INSTL.

BEFORE REF.

ITEM NO.

TAG NO.

EQUIPMENT MODEL NO.

LOCATION DATE 1/1/81 SEC.

13 FC-2300 Dual Manual Foxboro N-2AC+M3 10 4/17/81 No FC-2301 Controller

+ MO + MO FC-3300 FC-3301 14 HC-2300 Manual Output Foxboro N-2AX + M2NH 10 4/17/81 No HC-2301 HC-3300 HC-3301 15 PYB-2010 Alarm Module Foxboro N-2AP+ALM-AR 10 4/17/81 No LYB-2400C LYB-2400A LYB-2400B LYB-3400A LYB-3400B PYB-3010 LYB-3400C PYB-2011 16 FYA-3453 Hi/Lo Signal Foxboro N-2AP+SSL 10 4/17/81 No FYA-3454 Selector FYA-3455

SONGS 1 EQUIPMENT QUALIFICATION

SUMMARY

TMI EQUIPMENT-MILD ENVIRONMENTS NUREG 0578 Section:

2.1.7 AUXILIARY FEEDWATER Page 12 of 26 NUREG INSTL.

0737 PLANT MFG. &

INSTL.

BEFORE REF.

ITEM NO.

TAG NO.

EQUIPMENT MODEL NO.

LOCATION DATE 1/1/81 SEC.

17 (PYV-2001)

Current to Voltage Foxboro N-2Al-I2V 10 4/17/81 No PYV-2011 Converter PYV-2010 LYV-2400C LYV-2400A,B (FYV-3114A)

PYV-3011 LYV-3400C,B,A FYV-3453A FYV-3453B FYV-3454A, B FYV-3455A, B PYV-3010 18 FYQ-3453B Square Root Foxboro N-2AP+SQE 10 4/17/81 No FYQ-3454B (Modified)

(8735)

FYQ-3455B 19 PYT-3010 Timer Unit Foxboro N-2AP+TIM 10 4/17/81 PYT-2010

SONGS 1 EQUIPMENT QUALIFICATION

SUMMARY

TMI EQUIPMENT-MILD ENVIRONMENTS NUREG 0578 Section:

2.1.8b-1 CONTAINMENT HIGH RANGE MONITOR Page 13 of 26 NUREG INSTL.

0737 PLANT MFG. &

INSTL.

BEFORE REF.

ITEM NO.

TAG NO.

EQUIPMENT MODEL NO.

LOCATION DATE 1/1/81 SEC.

1 RI-1255 Readout Module General Atomic 10 (5/4/82)

No II.F.1 RI-1257 RP-2C 2

RR-1256, 1257 2 Pen Recorder L&N 430 10 (5/4/82)

No II.F.1 3

Signal Converter Action Pak 10 (5/4/82)

No II.F.1 4

RYV-1255 EMF.to Voltage Foxboro Spec. 200 10 (5/4/82)

No II.F.1 RYV-1257 Converter Mod.

No. N-2Al-T2V 5

RYI-1255 Voltage to Current Foxboro Spec. 200 10 (5/4/82)

No II.F.1 RYI-1257 Converter Mod. No. N-2AO-VAI Excep. 9206

SONGS 1 EQUIPMENT QUALIFICATION

SUMMARY

TMI EQUIPMENT-MILD ENVIRONMENTS NUREG 0578 Section:

2.1.8b-2 VENT STACK RADIATION MONITOR Page 14 of 26 NUREG INSTL.

0737 PLANT MFG. &

INSTL.

BEFORE REF.

ITEM NO.

TAG NO.

EQUIPMENT MODEL NO.

LOCATION DATE 1/1/81 SEC.

1 RE-1254, Wide Range Gas General Atomic WRGM 3, 10 (5/4/82)

No II.F.1 RX-1254, Monitor (WRGM)

RT-1254, RIC-1254, PE-1254, TE-1254 2

RT-1254 Microprocessor General Atomic 10 (5/4/82)

No II.F.1 Control & J. Box RM-80 3

RR-1254A,B Recorder L&N 430 3

(5/4/82)

No II.F.1 0I

SONGS 1 EQUIPMENT QUALIFICATION

SUMMARY

TMI EQUIPMENT-MILD ENVIRONMENTS NUREG 0578 Section:. 2.1.8b-3 STEAM DUMP HEADER RADIATION MONITOR Page 15 of 26 NUREG INSTL.

0737 PLANT MFG. &

INSTL.

BEFORE REF.

ITEM NO.

TAG NO.

EQUIPMENT MODEL NO.

LOCATION DATE 1/1/81 SEC.

1 RI-1256A, Readout G.A. Co., RP-1A, 10 (2/11/82)

No II.F.1 RI-1258A 2

RI-1256B, Readout G.A. Co., RP-2A 10 (2/11/82)

II.F.1 RI-1258B 3

RR-1254B, Recorder L&N 430 10 (2/11/82)

No II.F.1 RR-1258 4

RYV-1256A,B EMF to Voltage Foxboro, Spec. 200 10 (2/11/82)

II.F.1 RYV-1258A,B Converter N2AI-T2V 5

RYI-1256A,B Voltage to Current Foxboro Spec. 200 10 (2/11/82)

II.F.1 RYI-1258A,B Converter N-2AO-VAI (Excep. 9206)

SONGS 1 EQUIPMENT QUALIFICATION

SUMMARY

TMI EQUIPMENT-MILD ENVIRONMENTS NUREG 0578 Section:

3.1.1 CONTAINMENT WIDE RANGE PRESSURE Page 16 of 26 NUREG INSTL.

0737 PLANT MFG. &

INSTL.

BEFORE REF.

ITEM NO.

TAG NO.

EQUIPMENT MODEL NO.

LOCATION DATE 1/1/81 SEC.

1 PIS-2001 Electronic Signma 9270-20-DVB 10 5/2/81 No II.F.1.4 PIS-3001 Indicator 2

PYV-2001 Current to Voltage Foxboro Spec. 200, 10 5/2/81 No II.F.1.4 PYV-3001 Converter (I/E)

Mod. No. N2AI-I2V 3

PYI-3001 Voltage to Voltage Foxboro Spec. 200, 10 5/2/81 No II.F.1.4 Converter (Isolator) Mod. No. N2AO-VAI (Excep. 9206)

SONGS 1 EQUIPMENT QUALIFICATION

SUMMARY

TMI EQUIPMENT-MILD ENVIRONMENTS NUREG 0578 Section:

3.1.2 CONTAINMENT HYDROGEN INDICATION Page 17 of 26 NUREG INSTL.

0737 PLANT MFG. &

INSTL.

BEFORE REF.

ITEM NO.

TAG NO.

EQUIPMENT MODEL NO.

LOCATION DATE 1/1/81 SEC.

1 AI-H2-2001 Electronic Sigma 9270 10 (4/7/82)

No IIF.1 AI-H2-3001 Indicator, 0-10%,

0-10 VDC Input 2

AIT-H2-2001 Microprocessor Exo 10 (4/7/82)

II.F.1 AIT-H2-3001 and Relay Tray Sensors

SONGS 1 EQUIPMENT QUALIFICATION

SUMMARY

TMI EQUIPMENT-MILD ENVIRONMENTS NUREG 0578 Section:

3.1.3 CONTAINMENT WATER LEVEL MONITORING Page 18 of 26 NUREG INSTL.

0737 PLANT MFG. &

INSTL.

BEFORE REF.

ITEM NO.

TAG NO.

EQUIPMENT MODEL NO.

LOCATION DATE 1/1/81 SEC.

1 LT-2001, Level Receiver GEMS RE-36562 10 (3/25/82)

No II.F.1.5 LT-3001, (Transmitter)

LT-2002, LT-3002 2

LYV-2001 Current to.Voltage Foxboro Spec. 200, 10 (3/25/82)

No II.F.1.5 LYV-2002 Converter (I/E)

Mod. No. N2AI-I2V LYV-3001 LYV-3002 3

LYI-3001 Voltage to Voltage Foxboro Spec. 200, 10 (3/25/82)

No II.F.1.5 LYI-3020 Converter (Isolator) N2AO-VAI (Excep. 9206) 4 LIS-2001 Level Indicators Sigma 9270 10 3/25/82 No II.F.1.5 LIS-3001 (0-110%)

5 LIS-2002 Level Indicators Sigma 9270 10 3/25/82 No II.F.1.5 LIS-3002

( + 12)

SONGS 1 EQUIPMENT QUALIFICATION

SUMMARY

TMI EQUIPMENT-MILD ENVIRONMENTS NUREG 0578 Section:

3.2 REACTOR COOLANT SYSTEM VENTING Page 19 of 26 NUREG INSTL.

0737 PLANT MFG. &

INSTL.

BEFORE REF.

ITEM NO.

TAG NO.

EQUIPMENT MODEL NO.

LOCATION DATE 1/1/81 SEC.

1 HS2210A, 2214A Open Pushbutton Master Specialties 10 4/30/82 No 2401A-2404A, Switch 10H7A Series 3212A, 3216A, 3401A-3404A 2 HS2210B,2214B, Closed Pushbutton Master Specialties 10 4/30/82 No 2401B-2404B, Switch 1OH7A Series

3212B, 3401B-3404B

SONGS 1 EQUIPMENT QUALIFICATION

SUMMARY

TMI EQUIPMENT-MILD ENVIRONMENTS NUREG 0578 Section:

ALL TMI ELECTRICAL Page 20 of 26 NUREG INSTL.

0737 PLANT MFG. &

INSTL.

BEFORE REF.

ITEM NO.

TAG NO.

EQUIPMENT MODEL NO.

LOCATION DATE 1/1/81 SEC.

1 Heat Trace Strip Raychem 1OPTV1-M 3

1981-No

IIB3, 1983
IID3, IIE1.2.,

IIE3.1 2

Power Connection Raychem AM-BC6 3

1981-No IIE4.1, Kit 1983 IIE4.2 IIF2 3

Thermocouples Raychem (Type J) 3 1981-No IIE4.1, 1983 IIE4.2 IIF2 4

Relays Amerace (Typical 10 1981-No

IIB3, (Non-:Latching)

EGP-I-001, E7012PD-001, 1983

IID3, Control, On Delay EML-D-001)

IIE1.2.

Timing, Latching IIE3.1, Control)

IIE4.1, IIE4.2, IIF2 5

-Relays (Isolation)

Consolidated Controls 10 1981-No

IIB3, (Typical 8N13-1) 1983
IID3, IIE1.2, IIE3.1, IIE4.1, IIE4.2, IIF2

SONGS 1 EQUIPMENT QUALIFICATION

SUMMARY

TMI EQUIPMENT-MILD ENVIRONMENTS NUREG 0578 Section:

ALL TMI ELECTRICAL Page 21 of 26 NUREG INSTL.

0737 PLANT MFG. &

INSTL.

BEFORE REF.

ITEM NO.

TAG NO.

EQUIPMENT MODEL NO.

LOCATION DATE 1/1/81 SEC.

6---

Relay, Multicontact, GE 12HFA 151A2H 10 1981-No

IIB3, Nonlatching 1983
IID3, IIE1.2, IIE3.1, IIE4.1, IIE4.2, IIF2 7

600 V Switchboard Haveg 10 1981-No

IIB3, Wire 1-Conductor, 1983
IID3,
  1. 20 AWG IIE1.2, IIE3.1, IIE4.1, IIE4.2, IIF2 8

AC Ammeter Westinghouse VX-252 10 1981-No

IIB3, 1983
IID3, IIE1.2, IIE3.1, IIE4.1, IIE4.2, IIF2

SONGS 1 EQUIPMENT QUALIFICATION

SUMMARY

TMI EQUIPMENT-MILD ENVIRONMENTS NUREG 0578 Section:

ALL TMI ELECTRICAL Page 22 of 26 NUREG INSTL.

0737 PLANT MFG. &

INSTL.

BEFORE REF.

ITEM NO.

TAG NO.

EQUIPMENT MODEL NO.

LOCATION DATE 1/1/81 SEC.

9 Terminal Block Buchanan 10 1981-No

IIB3, 1983
IID3, IIE1.2, IIE3.1, IIE4.1, IIE4.2, IIF2 10 Fuse, 20 amp, Bussman Non 20 10 1981-No
IIB3, 250 Volt 1983
IID3, IIE1.2, IIE3.1, IIE4.1, IIE4.2, IIF2 11 Indicating Light Master Specialties 10 1981-No
IIB3, 10HA2C5 J3L(W)N1 1983
IID3, R1V13120 VAC IIE1.2, IIE3.1, IIE4.1, IIE4.2, IIF2

SONGS 1 EQUIPMENT QUALIFICATION

SUMMARY

TMI EQUIPMENT-MILD ENVIRONMENTS NUREG 0578 Section:

ALL TMI ELECTRICAL Page 23 of 26 NUREG INSTL.

0737 PLANT MFG. &

INSTL.

BEFORE REF.

ITEM NO.

TAG NO.

EQUIPMENT MODEL NO.

LOCATION DATE 1/1/81 SEC.

12 Momentary Action Master Specialties 10 1981-No

IIB3, Switch-Lite 10H Series 1983
IID3, IIE1.2, IIE3.1, IIE4.1, IIE4.2, IIF2 13 Inverter and Elgar 3

1981-No

IIB3, Transfer Switch 1 1983
IID3, Phase, 120 VAC, IIE1.2, 7-1/2 KVA Output, IIE3.1, 60 Hz IIE4.1, IIE4.2, IIF2 14 Circuit Breaker Square D, KHL 36125 3

1981-No

IIB3, 1983
IID3, IIE1.2, IIE3.1, IIE4.1, IIE4.2, IIF2

SONGS 1 EQUIPMENT QUALIFICATION

SUMMARY

TMI EQUIPMENT-MILD ENVIRONMENTS Work Package:

ALL TMI ELECTRICAL Page 24 of 26 NUREG INSTL.

0737 PLANT MFG. &

INSTL.

BEFORE REF.

ITEM NO.

TAG NO.

EQUIPMENT MODEL NO.

LOCATION DATE 1/1/81 SEC.

15 15 KVA Transformer Square D, BCE 214 3

1981-No

IIB3, YQT2 1983
IID3, IIE1.2, IIE3.1, IIE4.1, IIE4.2, IIF2 16 480 Volt Motor Westinghouse 3

1981-No

IIB3, Starter Full FB3015PL 1983
IID3, Voltage Reversing IIE1.2, NEMA Size 1 IIE3.1, IIE4.1, IIE4.2, IIF2 17 Circuit Breakers Westinghouse 3

1981-No

IIB3, (Thermal Magnetic, 1983
IID3, Switchgear)

IIE1.2, IIE3.1, IIE4.1, IIE4.2, IIF2

SONGS 1 EQUIPMENT QUALIFICATION

SUMMARY

TMI EQUIPMENT-MILD ENVIRONMENTS NUREG 0578 Section:

ALL TMI ELECTRICAL Page 25 of 26 NUREG INSTL.

0737 PLANT MFG. &

INSTL.

BEFORE REF.

ITEM NO.

TAG NO.

EQUIPMENT MODEL NO.

LOCATION DATE 1/1/81 SEC.

18 Resistor, 3,000 Ohmite 10 1981-No

IIB3, Ohm, 25 Watt 0379 1983
IID3, IIE1.2, IIE3.1, IIE4.1, IIE4.2, IIF2 19 120/240 VAC Square D 10 1981-No
IIB3, Panelboards 1983
IID3, IIE1,2, IIE3.1, IIE4.1, IIE4.2, IIF2 20 Solistrand Butt AMP Special 1981-No
IIB3, and Parallel Industries 1983
IID3, Splice IIE1.2, (Uninsulated)

IIE3.1, IIE4.1, IIE4.2, IIF2

SONGS 1 EQUIPMENT QUALIFICATION

SUMMARY

TMI EQUIPMENT-MILD ENVIRONMENTS NUREG 0578 Section:

ALL TMI ELECTRICAL Page 26 of 26 NUREG INSTL.

0737 PLANT MFG. &

INSTL.

BEFORE REF.

ITEM NO.

TAG NO.

EQUIPMENT MODEL NO.

LOCATION DATE 1/1/81 SEC.

21 Connector, Right Burndy-Hylug, 1981-No

IIB3, Angle Compression type YAV.

1983

IID3, (Uninsulated)

IIE1.2, IIE3.1, IIE4.1, IIE4.2, IIF2 HClay:npc