Forwards Amend Applications 23 & 9 to Licenses NPF-10 & NPF-15,respectively,revising Tech Spec 3/4.3.2 Re ESF Actuation Instrumentation to Require Testing of Certain Relays at 6-month Intervals.Amend Fee Encl
ML13302A633
Person / Time
Site: San Onofre  
Issue date: 01/25/1984
From: Baskin K
Southern California Edison Co
To: Harold Denton
Office of Nuclear Reactor Regulation
Shared Package
ML13302A634 List:
References
TAC-51613, TAC-54708, TAC-54709, TAC-54710, TAC-54711, TAC-55119, NUDOCS 8401270266
Download: ML13302A633 (5)


Text

REGULATORY IORMATION DISTRIBUTION SYS (RIDS)

ACCESSION NBR:8401270266 DOC.DATE: 84/01/25 NOTARIZED: NO DOCKET #

FACIL:50-361 San'Onofre Nuclear Station, Unit 2, Southern Californ 05000361 50-362 San Onofre Nuclear Station, Unit 3, Southern Californ 05000362 AUTH,NAME AUTHOR AFFILIATION

8ASKINKP, Southern California Ed4son Co.

RECIP.NAME RECIPIENT AFFILIATION DENTONH,R.

Office of Nuclear Reactor Regulation, Director

SUBJECT:

Forwards Amend Applicatons

&9 to Licenses NPF-10 &

NPF-15,respectively -revising Tech Spec 3/4,3.2 re ESF actuation-instrumentation to require testing of certain relays at 6-month intervals.Amend fee encl.

DISTRIBUTION CODE: 80018 COPIES RECEIVED:LTR..3 ENCL SI Z E-..

TITLE: Licensing Submittal: PSAR/FSAR Amdts & Related Correspondence, NOTES:J Hanchett Icy PDR Documents. ELD Chandler icy, 05000361

-J Iianchett icy PDR DocUments. ELD Chandler Icy.

05000362 RECIPIENT COPIES' RECIPIENT-COPIES ID CODE/NAME LTTR ENCL 1D CODE/NAME LTTR.ENCL NRR/DL/ADL 1

0 NRR L83 BC 1

0 NRR LB3 LA 1

0 ROODH.

01 1-1 INTERNAL? ELD/HDS2 1

0 IE FILE 1

1 IE/DEPER/EPB 36 3

IE/DEPER/IR8 -35 1

1 IE/DEQA/QA8 2 1

1

-NRR/DE/AEAB 1

0 NRR/DE/CEB 11 1

1 NRR/DE/EHEB 1

1 NRR/DE/EQB 13 2

1t NRR/DE/GB 28 2

2 NRR/DE/MEB 18 1

1 NRR/0E/MTEB 17 1

1 NRR/DE/SAB 24 1-1 NRR/DE/SGEB 25 1

1 NRR/DHFS/HFEB40 1

1 NRR/DHFS/LQB 32 1

1 NRR/DHFS/PSRB

-1 1

NRR/DL/SSPB 1

0 NRR/DSI/AE8 26 1

1 NRR/DSI/ASB 1

1 NRR/DSI/CPB 10 1

1-NRR/DSI/CSB 09 1

1 NRR/DSI/ICSB 16 1

1 NRR/DSI/METB 12 1

1 NRR/DSI/PSB 19 1

1 NRR DSI/RAB 22 1

1 NRR/DSI/RSB 23 1

1 0

1 1

RGN5 3

/ DAMI/MIB 1

0 EXTERNAL: ACRS 41 6

t BNL-(AMDTS ONLY) 1 1

DMB/DSS (AMDTS) 1 1

FEMA-REP DIV 39 1

1 LPDR 03 1

1 NRC PDR 02 1

1 NSIC 05 1

1 NTIS 1

1 NOTES:

.2 2

TOTAL NUMBER OF COPIES REQUIRED:- LTTR 55-ENCL-48

0p Southern California Edison Company P. 0. BOX 800 2244 WALNUT GROVE AVENUE KENNETH P. BASKIN ROSEMEAD, CALIFORNIA 91770 TELEPHONE VCEa PRESIDENT January 25, 1984 818-572-1401 Director, Office of Nuclear Reactor Regulation Attention: Mr. H. R. Denton U.S. Nuclear Regulatory Commission Washington, D. C. 20555 Gentlemen:

Subject; Docket Nos. 50-361 and 50-362 San Onofre Nuclear Generating Station, Units 2&3 Enclosed are three executed and forty conformed copies of Amendment Application No. 23 to Operating License NPF-10 and Amendment Application No. 9 to Operating License NPF-15 for San Onofre Nuclear Generating Station, Units 2 and 3, respectively.

Amendment Application No. 23 far Unit 2.consists of the following proposed changes:

1. Proposed Change NPF-10-4, Revision 1, is a request to revise Technical Specification 3/4.3.2, Engineered Safety Features Actuation (ESFAS) Instrumentation, to not require testing of certain ESFAS relays at six month intervals necessitating a plant shutdown. The proposed change will require testing of these relays at each cold shutd6wn of sufficient duration, unless they had been tested within the previous six months.

This revision of Proposed Change NPF-10-4 replaces the original version submitted by Southern California Edison Company's (SCE) letter dated July 23, 1982.

2. Proposed Change NPF-10-41 is a request to revise Technical Specification 3.2.8, Pressurizer Pressure, to clarify the meaning of the phrase "average pressurizer pressure'.
3. Proposed Change NPF-10-84 is a request to revise License Condition 2.C(5), Environmental Qualification, to reflect the current requirements of 10 CFR 50.49.
4. Proposed Change NPF-10-91 -is a request to delete Technical Specification 4.8.1.1.2.d.6, a.diesel generator surveillance requirement, in accordance with-Generic Letter 83-30.
5. Proposed Change NPF-10-97 is a request to revise Technical Specification 3/4.6.4.1, Hydrogen Monitors, to clarify the surveillance requirements to be in accordance with manufacturer's recommendations and to improve containment integrity by reducing the amount of time containment isol tion valves are open for instrument calibration.

P 4OiR1A 04 j

&0(2~

~9 PR ADQ3cj'j05000361 P

~~PDR

.~/'

Mr. H..

January 25, 1984 FE

6. Proposed Change NPF-10-98 is a request to revise License Condition 2.C.(14)a, relating to fire protection to clarify reporting requirements, with respect to License Condition 2.G, for deviations from the Fire Hazards Analysis. This proposed change was informally submitted by SCE's letter dated December 2, 1983.
7. Proposed Change NPF-10-144 is a request to revise Technical Specification 3/4.6.1.7, Containment Ventilation System, to increase the limitation-on the use of the 8-inch containment purge system from 1000 hours0.0116 days <br />0.278 hours <br />0.00165 weeks <br />3.805e-4 months <br /> to 3000 hours0.0347 days <br />0.833 hours <br />0.00496 weeks <br />0.00114 months <br /> per 365 days. This proposed change was informally submitted by SCE's letter dated January 3, 1984..

Amendment Application No. 9 for Unit 3 consists of the following proposed changes:

1. Proposed Change NPF-15-4, Revision 1, is a request to revise Technical Specification 3/4.3.2, Engineered Safety Features Actuation (ESFAS) Instrumentation, to not require testing of certain ESFAS relays at sl* month intervals necessitating a plant shutdown. The proposed change will require testing of these relays at each cold shutdown of sufficient duration, unless they had been tested within the previous six months.
2. Proposed Change NPF-15-41 is a request to revise Technical Specification 3.2.8, Pressurizer Pressure, to clarify the meaning of the phrase "average pressurizer pressure".
3. Proposed Change NPF-15-84 is a.request to revise License Condition 2.C(5), Environmental Qualification., to reflect the current requirements of 10 CFR 50.49.
4. Proposed Change NPF-15-91 is a request to delete Technical Specification 4.8.1.1.2.d.6, a diesel generator surveillance requirement, in accordance with Generic Letter 83-30.
5. Proposed Change NPF-15-97 is a request to revise Technical Specification 3/4.6.4.1, Hydrogen Monitors, to clarify the surveillance requirements to be in accordance with manufacturer's recommendations and to improve containment integrity by reducing the amount of time containment isolation valves are open for instrument calibration.
6. Proposed Change NPF-15-98 is a request to revise License Condition 2.C.(12)a, relating to fire protection to clarify reporting requirements, with respect to License Condition 2.6, for deviations from the Fire Hazards Analysis. This proposed change was informally submitted by SCE's letter dated December 2, 1983.

Mr. H.

January 25, 1984=7'_'_

7. Proposed Change NPF-15-144 is a request to revise Technical Specification 3/4.6.1.7, Containment Ventilation System, to increase the limitation on the use of the 8-inch containment purge system from 1000 hours0.0116 days <br />0.278 hours <br />0.00165 weeks <br />3.805e-4 months <br /> to 3000 hours0.0347 days <br />0.833 hours <br />0.00496 weeks <br />0.00114 months <br /> per 365 days. This proposed change was informally submitted by SCE's letter dated January 3, 1984.

Direct distribution of Amendment Application No. 23 to Operating License NPF-10 and Amendment Application No. 9 to Operating License NPF-15 will be made in accordance with the service list provided in SCE's October 7, 1983 letter to the Commission. An affidavit attesting to the fact that distribution has been completed will be submitted within ten days of amendment docketing.

Pursuant to 10 CFR 170.22, the following determinations have been made regarding the class of license amendment constituted by each of the proposed changes:

Amendment Application No. 23 to NPF-10 Proposed Change Cass Fee NPF-10-4 III

$4,000.00 NPF-10-41 II

$1,200.00 NPF-10-84 II

$1,200.00 NPF-10-91 II

$1,200.00 NPF-10-97 II

$1,200.00 NPF-10-98 II

$1,200.00 NPF-10-144 II

$1,200.00 Amendment Application No. 9 to NPF-15 Proposed Change Class Fee NPF-15-4 I

$400.00 NPF-15-41 I

$400.00 NPF-15-84 I

$400.00 NPF-15-91 I

$400.00 NPF-15-97 1

$400.00 NPF-15-98 I

$400.00 NPF-15-144 1

$400.00 The fees for Proposed Changes WNPF-10-98 and NPF-15-98 were remitted with SCE's letter dated December 2, 1983.

The fees for Proposed Changes NPF-10-144 and NPF-15-144 were remitted with SCE's letter dated January 3, 1984.

Mr. H. R. Denton

-4 January 25, 1984 SCE's check in the amount of $10,800.00 corresponding to the remaining fees noted above is enclosed as required by 10 CFR 170.22.

If you have any questions regarding these license amendment requests, please call me.

Sincerely, Enclosures cc: H. Rood, NRC (to be opened by addressee only)

J. 0. Ward, California Department of Health Services A. E. Chaffee, NRC Resident Inspector