RS-13-207, License Amendment Request to Revise Loss of Voltage Relay Settings for 4.16 Kv ESF Buses
| ML13266A107 | |
| Person / Time | |
|---|---|
| Site: | LaSalle |
| Issue date: | 09/20/2013 |
| From: | Gullott D Exelon Generation Co |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| RS-13-207 | |
| Download: ML13266A107 (92) | |
Text
1 Exelon Generation, RS-13-207 September 20,2013 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 LaSalle County Station, Units 1 and 2 Facility Operating License Nos. N PF-1 1 and N PF-18 NRC Docket Nos. 50-373 and 50-374 4300 Winfield Road Warrenville. IL 60555 6306572000 Office 10 CFR 50.90
Subject:
License Amendment Request to Revise Loss of Voltage Relay Settings for 4.16 kV ESF Buses
Reference:
NRC Letter from A. M. Stone to M. J. Pacilio, "LaSalle County Station, Units 1 and 2 Component Design Bases Inspection (CDBI) 05000373/2010006(DRS);
05000374/2010006(DRS)," February 15, 2011 In accordance with 10 CFR 50.90, "Application for amendment of license, construction permit, or early site permit," Exelon Generation Company, LLC (EGG) requests an amendment to Facility Operating License Nos. NPF-11 and NPF-18 for LaSalle County Station (LSCS), Units 1 and 2.
This amendment request proposes to revise allowable values for certain Functions in Technical Specifications (TS) Table 3.3.8.1 -1, "Loss of Power Instrumentation." The changes to the allowable values are necessary to address the discovery of a non-conservative TS. As documented in the Referenced letter, EGC had not established the adequacy of the setpoints for degraded voltage relay time delay and the loss of voltage relay trip function described in TS 3.3.8.1, and the EGC analysis of record did not account for the potential worst case, non-accident degraded voltage condition, and, therefore, did not demonstrate the operability of permanently connected safety-related loads under those conditions.
Increasing the 4.16 kV ESF bus loss of voltage relay settings will provide assurance that, under non-accident conditions, normally operating safety related motors will not be damaged in the event of sustained degraded bus voltage during the time delay before initiation of the loss of voltage trip function. This change will involve alteration of nominal trip set points in the field, which will also be reflected in revisions to the calibration procedures.
Plant operations in TS 3.3.8.1 are currently administratively controlled under the provisions of NRC Administrative Letter (AL) 98-10, "Dispositioning of Technical SpeCifications that are Insufficient to Assure Plant Safety," to assure that plant safety is maintained. This license amendment request is submitted in accordance with the guidance in AL 98-10. In accordance with the guidance of AL 98-10, EGC submits the proposed change as a required license amendment request to resolve a non-conservative TS. As such, this is not a "voluntary request from a licensee to change its licensing basis" and should not be subject to "forward fit" considerations.
September 20,2013 U. S. Nuclear Regulatory Commission Page 2 The attached request is subdivided as follows:
- provides a description and evaluation of the proposed changes.
- provides the markup of the affected TS page.
- provides Design Analysis L-002588.
The proposed changes have been reviewed by the LSCS Plant Operations Review Committee and approved by the Nuclear Safety Review Board in accordance with the requirements of the EGC Quality Assurance Program.
EGC requests approval of the proposed license amendment request by September 20, 2014, to support implementation activities during the LSCS Unit 2 spring 2015 refueling outage (L2R15) and LSCS Unit 1 spring 2016 refueling outage (L 1 R16) as changes to the loss of voltage relay settings cannot be completed online. Once approved, the amendment will be implemented for LSCS Unit 2 prior to entering MODE 4 following implementation of the revisions to the loss of voltage relay settings for the 4.16 kV ESF buses during the LSCS Unit 2 spring 2015 refueling outage (L2R15), and the amendment will be implemented for LSCS Unit 1 prior to entering MODE 4 following implementation of the revisions to the loss of voltage relay settings for the 4.16 kV ESF buses during the LSCS Unit 1 spring 2016 refueling outage (L 1 R16).
In accordance with 10 CFR 50.91, "Notice for public comment; State consultation," paragraph (b),
EGC is notifying the State of Illinois of this application for license amendment by transmitting a copy of this letter and its attachments to the designated State Official.
There are no regulatory commitments contained within this letter. Should you have any questions concerning this letter, please contact Ms. Lisa A. Simpson at (630) 657-2815.
I declare under penalty of perjury that the foregoing is true and correct. Executed on the 20th day of September 2013.
Respectfully, David M. Gullott Manager - Licensing Exelon Generation Company, LLC Attachments:
- 1) Evaluation of Proposed Changes
- 2) Markup of Technical Specifications Page
- 3) Design Analysis L-002588
September 20,2013 U. S. Nuclear Regulatory Commission Page 3 cc:
NRC Regional Administrator, Region III NRC Senior Resident Inspector, LaSalle County Station Illinois Emergency Management Agency - Division of Nuclear Safety
ATTACHMENT 1 Evaluation of Proposed Changes
Subject:
License Amendment Request to Revise Loss of Voltage Relay Settings for 4.16 kV ESF Buses 1.0
SUMMARY
DESCRIPTION 2.0 DETAILED DESCRIPTION
3.0 TECHNICAL EVALUATION
4.0 REGULATORY EVALUATION
4.1 Applicable Regulatory Requirements/Criteria 4.2 No Significant Hazards Consideration 4.3 Conclusions
5.0 ENVIRONMENTAL CONSIDERATION
6.0 REFERENCES
1 of 10
AlTACHMENT1 Evaluation of Proposed Changes 1.0
SUMMARY
DESCRIPTION This evaluation supports a request to amend Facility Operating License Nos. NPF-11 and NPF-18 for LaSalle County Station (LSCS), Units 1 and 2.
Exelon Generation Company, LLC, (EGC) proposes to revise allowable values for certain Functions in Technical Specifications (TS) Table 3.3.8.1-1, "Loss of Power Instrumentation."
The changes to the allowable values are necessary to address the discovery of a non-conservative TS. As documented in NRC Inspection Report issued February 15, 2011, for the LaSalle Component Design Bases Inspection (CDBI), EGC had not established the adequacy of the setpoints for degraded voltage relay time delay and the loss of voltage relay trip function described in TS 3.3.8.1, and the EGC analysis of record did not account for the potential worst case, non-accident degraded voltage condition, and, therefore, did not demonstrate the operability of permanently connected safety-related loads under those conditions.
Increasing the 4.16 kV engineered safety feature (ESF) bus loss of voltage relay settings will provide assurance that, under non-accident conditions, normally operating safety related motors will not be damaged in the event of sustained degraded bus voltage during the time delay before initiation of the loss of voltage trip function. This change will involve alteration of nominal trip setpoints in the field, which will also be reflected in revisions to the calibration procedures.
In accordance with NRC Administrative Letter (AL) 98-10, "Dispositioning of Technical SpeCifications that are Insufficient to Assure Plant Safety," (Reference 1), administrative controls implemented under EGC Operability Evaluation OE 10-006 (Reference 2) assure that plant safety is maintained. In accordance with the guidance of AL 98-10, EGC submits the proposed change as a required license amendment request to resolve a non-conservative TS.
As such, this is not a "voluntary request from a licensee to change its licensing basis" and should not be subject to forward fit" considerations.
Approval of this amendment application is requested by September 20, 2014, to support implementation activities during the LSCS Unit 2 spring 2015 refueling outage (L2R15) and LSCS Unit 1 spring 2016 refueling outage (L 1 R16) as revision of the loss of voltage relay settings cannot be completed online. Once approved, the amendment will be implemented for LSCS Unit 2 prior to entering MODE 4 following implementation of the revisions to the loss of voltage relay settings for the 4.16 kV ESF buses during the LSCS Unit 2 spring 2015 refueling outage (L2R15), and the amendment will be implemented for LSCS Unit 1 prior to entering MODE 4 following implementation of the revisions to the loss of voltage relay settings for the 4.16 kV ESF buses du ring the LSCS Unit 1 spring 2016 refueling outage (L 1 R16).
2.0 DETAILED DESCRIPTION The requested amendment will revise the allowable values in TS Table 3.3.8.1-1, "Loss of Power Instrumentation," for the following Functions:
- 1) Function 1.a, Divisions 1, 2 and Opposite Unit Division 2 - 4.16 kV ESF Bus Undervoltage, Loss of Voltage - 4.16 kV Basis 2 of 10
ATTACHMENT 1 Evaluation of Proposed Changes
- 2) Function 2.a, Division 3 - 4.16 kV ESF Bus Undervoltage, Loss of Voltage - 4.16 kV Basis Current TS Table 3.3.8.1-1, Function 1.a Allowable Value states: ;:: 2422 V and S 3091 V Revised TS Table 3.3.8.1-1, Function 1.a Allowable Value states: ;:: 2870 V and S 3127 V Current TS Table 3.3.8.1-1, Function 2.a Allowable Value states: ;:: 2596 V and S 3137 V Revised TS Table 3.3.8.1-1, Function 2.a Allowable Value states: ;:: 2725 V and s 3172 V provides mark-ups of the affected TS page for the proposed change.
3.0 TECHNICAL EVALUATION
Offsite power is supplied to LSCS by the Commonwealth Edison 345 kV system. There are four incoming lines, two for each unit. The 345 kV switchyard is arranged in a double ring bus.
Each unit's auxiliary electric system is served from two 6.9 kV and five 4.16 kV buses. The ESF loads are fed from the 4.16 kV buses (buses 141Y, 142Y, 143, 241Y, 242Y, and 243). Each 4.16 kV ESF bus has its own independent LOP instrumentation and associated trip logic. The voltage for the Division 1, 2, and 3 buses is monitored at two levels, which are considered as two different undervoltage functions: loss of voltage and degraded voltage.
Loss of voltage on a 4.16 kV ESF bus indicates that offsite power may be completely lost to the respective ESF bus, and the bus is unable to supply sufficient voltage for proper operation of the applicable equipment. Therefore, the power supply to the bus is transferred from the offsite power supply to onsite diesel generator. Undervoltage relays are provided for each ESF bus to initiate load shedding and transfer the ESF load to the onsite diesel generator in case offsite power is lost or degraded. The transfer is initiated prior to when the voltage on the bus drops below the minimum loss of voltage function allowable value but after the voltage drops below the maximum loss of voltage function allowable value. A short time delay of the undervoltage trip prevents inadvertent relay actuations due to momentary voltage transients. Because the minimum expected voltage during normal or emergency operation is well above the relay setting, transfer to the onsite power supply should not occur. The undervoltage relays incorporate sufficient time delay so that short circuits are cleared without undervoltage relay operation.
A degraded voltage condition on a 4.16 kV ESF bus indicates that while offsite power may not be completely lost to the respective ESF bus, voltage may be insufficient for starting large motors without risking damage to the motors that could disable the ECCS function. Therefore, power supply to the bus is transferred from offsite power to onsite diesel generator when the voltage on the bus drops below the degraded voltage function allowable values. The system also includes a timer that is initiated by the degraded voltage relays. If the degraded voltage is not corrected within the approximate 5-minute period of the timer, the bus will automatically transfer from the offsite power source to an onsite diesel generator. This ensures that adequate power will be available to the required equipment.
3 of 10
ATTACHMENT 1 Evaluation of Proposed Changes A loss of voltage signal or degraded voltage signal results in the start of the associated diesel generator, the trip of the normal and alternate offsite power supply breakers to the associated 4.16 kV ESF bus, and (for Divisions 1 and 2 only) the shedding of the appropriate 4.16 kV bus loads.
The bus undervoltage allowable values are low enough to prevent inadvertent power supply transfer, but high enough to ensure that sufficient power is available to the required equipment.
The time delay allowable values are long enough to provide time for the offsite power supply to recover to normal voltages following short system or grid perturbations, but short enough to ensure that sufficient power is available to the required equipment when a significant grid disturbance occurs.
LSCS TS Table 3.3.8.1-1 specifies the 4.16 kV ESF bus undervoltage allowable values as summarized in the following table:
Function Allowable Value (current values)
- 1.
Division 1, 2 and Opposite Unit Division 2 - 4.16 kV Emergency Bus Undervoltage
- a.
Loss of Voltage - 4.16 kV Basis
~ 2422 V and S 3091 V
- b.
Loss of Voltage - Time Delay
~ 3.1 seconds and s 10.9 seconds
- c.
Degraded Voltage - 4.16 kV Sasis
~ 3814 V and S 3900 V
- d.
Degraded Voltage - Time
~ 270.1 seconds and Delay, No LOCA S 329.9 seconds
- e.
Degraded Voltage - Time
~ 9.4 seconds and S 10.9 seconds Delay, LOCA
- 2.
Division 3 - 4.16 kV Emergency Bus Undervoltage
- a.
Loss of Voltage - 4.16 kV Basis
~ 2596 V and S 3137 V
- b.
Loss of Voltage - Time Delay S 10.9 seconds
- c.
DeQraded Voltage - 4.16 kV Basis
~ 3814 V and S 3900 V
- d.
Degraded Voltage - Time
~ 270.1 seconds and Delay, No LOCA S 329.9 seconds
- e.
Degraded Voltage - Time
~ 9.4 seconds and s 10.9 seconds Delay, LOCA Based on TS 3.3.8.1, the 4.16 kV buses for Division 1, 2 can remain above 2422 V for 340.8 seconds (Le., 10.9 seconds for the loss of voltage relay time delay and 329.9 seconds for Degraded Voltage relay time delay for non loss-of-coolant accident (LOCA) case), with no action taken to rectify this condition. Under this condition of the 4.16 kV buses, the constant kilovolt-ampere (KVA) loads running on these buses (such as motors) may experience stall conditions and the over load protection may trip the load. Similarly, based on TS 3.3.8.1, the 4.16 kV buses for Division 3 can remain above 2596 V for 340.8 seconds (Le., 10.9 seconds for the loss of voltage relay time delay and 329.9 seconds for Degraded Voltage relay time delay for non-LOCA case), and no action may be taken to rectify this condition. Under this condition 4 of 10
ATTACHMENT 1 Evaluation of Proposed Changes of the 4.16 kV buses, the constant KVA loads running on these buses (such as motors) may experience stall condition and/or the over load protection may trip these loads.
On February 15, 2011, the NRC issued an Inspection Report for the laSalle Component Design Bases Inspection (CDBI) (Reference 3). The report describes a finding of very low safety significance (Green) and an associated non-cited violation (NCV) of 10 CFR Part 50, Appendix B, Criterion III, "Design Control," involving "[EGC's] failure to have appropriate analyses for the loss of voltage relay setpoints and the second level undervoltage [degraded voltage] relay timer settings. Specifically, [EGC's] analysis and technical basis for the auxiliary power system (AP) second level undervoltage relay time delay settings failed to demonstrate the ability of the permanently connected safety-related loads to continue to operate during the 5.5 minutes relay time delay without sustaining damage during a worst case, non-accident degraded voltage condition (when voltage was still above the setpoint of the loss of voltage relay setpoint)."
Exelon performed an analysis of the relay setpoints to address the CDSI NCV issued in 2011.
The degraded voltage relay timer is set to trip in 300 +/- 29.9 seconds time delay following the 10.9 seconds time delay of the degraded voltage relay before transfer of all the loads to the diesel generators. The maximum time delay to trip the offsite source due to degraded bus voltage is therefore 340.8 seconds (5.7 minutes) (Reference TS Table 3.3.8.1-1). As documented in Exelon Design Analysis L-002588 (Reference 4), the purpose of the calculation was to evaluate relay setpoints to ensure that all safety related motors normally running from power supplied from the SAT would not trip in less than 5.7 minutes under a degraded voltage condition of the 4.16 kV ESF bus.
The upper analytical limit for Division 1, 2 and 3 bus loss of voltage relays was chosen to ensure that the minimum expected voltage during LOCA block start of all safety related loads remains above this value. This ensures that the loss of voltage relays do not trip the SAT feeder breaker when the SAT voltage is adequate to supply the power to the safety related loads. The minimum voltage at 4.16 kV buses for Division 1, 2 and 3 is more than 3190 V, when all the safety related loads were started at the same time. This voltage improves to a higher value in 2.5 seconds as the motors accelerate. Therefore, the upper analytical limit was chosen to be 3185 V to provide margin.
The lower analytical limit for Division 1, 2 and 3 bus loss of voltage relays are such that none of the safety related, normally running motors stall when subjected to this voltage for the entire time delay. The minimum bus voltage that ensures none of the safety related motors running in Division 1 and 2 will stall is 65.5% of 4.16 kV or 2725 V and for Division 3 is 65% of 4.16 kV or 2704 V. The analysis determined that for these analytical values, none of the safety related motors stalled. Therefore, the lower limit of the analytical limit for Division 1 and 2 is chosen as 2812 V to provide margin. Similarly, the lower analytical limit for Division 3 is chosen as 2712 V to provide margin.
Based on the upper and lower analytical limits provided in the two preceding paragraphs, Design Analysis L-002488 (Reference 4) provides a calculation that determines the new upper and lower allowable values for Loss of Voltage - 4.16 kV Basis Functions in accordance with the EGC setpoint methodology.
5 of 10
ATTACHMENT 1 Evaluation of Proposed Changes The following table provides the new upper and lower allowable values for Loss of Voltage -
4.16 kV Basis Functions:
Divisions 1 and 2:
TS Specification Existing Revised Allowable Values Allowable Values TS Table 3.3.8.1-1, Function 1.a
~ 2422 V and s 3091 V
~ 2870 V and s 3127 V Division 3' TS Specification Existing Revised Allowable Values Allowable Values TS Table 3.3.8.1-1, Function 2.a
~ 2596 V and s 3137 V
~ 2725 V and s 3172 V The analysis shows that the auxiliary distribution system at LSCS has the capability to adequately handle worst case loading and maintain all voltages well within equipment ratings under the postulated most severe contingency conditions.
Design Analysis L-002588, included as Attachment 3 to this amendment request, is provided as a reference for additional information.
4.0 REGULATORY EVALUATION
4.1 Applicable Requlatorv Requirements/Criteria The proposed change has been evaluated to determine whether applicable regulations and requirements continue to be met.
General Design Criterion 5, "Sharing of structures, systems, and components," states that no safety-related systems, structures, or components are shared unless such sharing has been evaluated to ensure that there will be no significant adverse impact on safety functions.
General Design Criterion 17, "Electric power systems," states that provisions shall be included to minimize the probability of losing electric power from any of the remaining supplies as a result of, or coincident with, the loss of power generated by the nuclear power unit, the loss of power from the transmission network, or the loss of power from the onsite electric power supplies.
Regulatory Guide 1.81, Revision 1, "Shared Emergency and Shutdown Electric Systems for Multi-Unit Nuclear Power Plants," states that, because of the low probability of a major reactor accident, a suitable design basis for multi-unit nuclear power plants is the assumption that an accident occurs in only one unit at a time, with all remaining units proceeding to an orderly shutdown and a maintained cooldown condition.
6 of 10
ATTACHMENT 1 Evaluation of Proposed Changes NUREG-0800, "Standard Review Plan for the Review of Safety Analysis Reports for Nuclear Power Plants," Branch Technical Position (BTP) 8-6, "Adequacy of Station Electric Distribution System Voltages," March 2007, states, in part, as follows:
The technical specifications should include limiting conditions for operations, surveillance requirements, trip setpoints, and maximum and minimum allowable values for the first level of undervoltage protection (LOOP (loss of offsite power])
relays and the second-level (degraded voltage) protection sensors and associated time delay devices.
Based on the considerations above, (1) there is reasonable assurance that the health and safety of the public will not be endangered by operation in the proposed manner; (2) such activities will continue to be conducted in accordance with the site licensing basis; and (3) the approval of the proposed change will not be inimical to the common defense and security or to the health and safety of the public.
In conclusion, EGC has determined that the proposed change does not require any exemptions or relief from regulatory requirements, other than the TS, and does not affect conformance with any regulatory requirements or criteria.
4.2 No Significant Hazards Consideration In accordance with 10 CFR 50.90, "Application for amendment of license, construction permit, or early site permit," Exelon Generation Company, LLC (EGG) requests an amendment to Facility Operating License Nos. NPF-11 and NPF-18 for laSalle County Station (LSCS), Units 1 and 2. The proposed change would revise allowable values for certain Functions in Technical Specifications (TS) Table 3.3.8.1-1, "Loss of Power Instrumentation." The changes to the allowable values are necessary to address the discovery of a non-conservative value in the affected TS.
As documented in NRC Inspection Report issued February 15, 2011, for the LaSalle Component Design Bases Inspection (CDBI), EGC had not established the adequacy of the setpoints for degraded voltage relay time delay and the loss of voltage relay trip function described in TS 3.3.8.1, and the EGC analysis of record did not account for the potential worst case, non-accident degraded voltage condition, and, therefore, did not demonstrate the operability of permanently connected safety-related loads under those conditions.
Increasing the 4.16 kV engineered safety feature (ESF) bus loss of voltage relay settings will provide assurance that, under non-accident conditions, normally operating safety related motors will not be damaged in the event of sustained degraded bus voltage during the time delay before initiation of the loss of voltage trip function.
7 of 10
ATTACHMENT 1 Evaluation of Proposed Changes According to 10 CFR 50.92, "Issuance of amendment," paragraph (c), a proposed amendment to an operating license involves no significant hazards consideration if operation of the facility in accordance with the proposed amendment would not:
(1)
Involve a significant increase in the probability or consequences of an accident previously evaluated; or (2)
Create the possibility of a new or different kind of accident from any accident previously evaluated; or (3)
Involve a significant reduction in a margin of safety.
EGC has evaluated the proposed change for LSCS, using the criteria in 10 CFR 50.92, and has determined that the proposed change does not involve a significant hazards consideration. The following information is provided to support a finding of no significant hazards consideration.
Criteria
- 1.
Does the proposed change involve a significant increase in the probability or consequences of an accident previously evaluated?
Response: No.
The proposed change to the 4.16 kV ESF bus loss of voltage allowable values allow the protection scheme to function as originally designed. (This change will involve alteration of nominal trip setpoints in the field and will also be reflected in revisions to the calibration procedures.) The proposed change does not affect the probability or consequences of any accident. Analysis was conducted and demonstrates that the proposed allowable values will allow the normally operating safety-related 'motors to continue to operate without sustaining damage or tripping during the worst-case, non-accident degraded voltage condition for the maximum possible time-delay of 5.7 minutes. Thus, these safety-related loads will be available to perform their safety function if a loss-of-coolant accident (LOCA) concurrent with a loss-of-offsite power (LOOP) occurs following the degraded voltage condition.
The proposed changes do not adversely affect accident initiators or precursors, and do not alter the design assumptions, conditions, or configuration or the plant or the manner in which the plant is operated or maintained. The proposed allowable values ensure that the 4.16 kV distribution system remains connected to the offsite power system when adequate offsite voltage is available and motor starting transients are considered. The diesel start due to a LOCA signal is not adversely affected by this change. During an actual loss of voltage condition, the loss of voltage time delay will continue to isolate the 4.16 kV distribution system from offsite power before the diesel is ready to assume the emergency loads, which is the limiting time basis for mitigating system responses to the accident.
For this reason, the existing loss of power / LOCA analysis continues to be valid.
8 of 10
ATTACHMENT 1 Evaluation of Proposed Changes Therefore, the proposed change does not involve a significant increase in the probability or consequences of an accident previously evaluated.
- 2.
Does the proposed change create the possibility of a new or different kind of accident from any accident previously evaluated?
Response: No.
The proposed change involves the revision of 4.16 kV ESF bus loss of voltage allowable values to satisfy existing design requirements. The proposed change does not introduce any changes or mechanisms that create the possibility of a new or different kind of accident. The proposed change does not install any new or different type of equipment, and installed equipment is not being operated in a new or different manner. No new effects on existing equipment are created nor are any new malfunctions introduced.
Therefore, the proposed change does not create the possibility of a new or different kind of accident from any previously evaluated.
- 3.
Does the proposed change involve a significant reduction in a margin of safety?
Response: No.
The proposed protection voltage allowable values are low enough to prevent inadvertent power supply transfer, but high enough to ensure that sufficient power is available to the required equipment. The diesel start due to a LOCA signal is not adversely affected by this change. During an actual loss of voltage condition, the loss of voltage time delays will continue to isolate the 4.16 kV distribution system from offsite power before the diesel is ready to assume the emergency loads.
Therefore, the proposed change does not involve a significant reduction in a margin of safety.
Based on the above, EGC concludes that the proposed amendments do not involve a Significant hazards consideration under the standards set forth in 10 CFR 50.92(c), and, accordingly, a finding of "no significant hazards consideration" is justified.
4.3 Conclusions In conclusion, based on the considerations discussed above, (1) there is reasonable assurance that the health and safety of the public will not be endangered by operation in the proposed manner, (2) such activities will be conducted in compliance with the Commission's regulations, and (3) the issuance of the amendment will not be inimical to the common defense and security or to the health and safety of the public.
9 of 10
ATTACHMENT 1 Evaluation of Proposed Changes
5.0 ENVIRONMENTAL CONSIDERATION
EGC has evaluated the proposed amendment for environmental considerations. The review has resulted in the determination that the proposed amendment would change a requirement with respect to installation or use of a facility component located within the restricted area, as defined in 10 CFR 20, and would change an inspection or surveillance requirement. However, the proposed amendment does not involve (i) a significant hazards consideration, (ii) a significant change in the types or significant increase in the amounts of any effluent that may be released offsite, or (iii) a significant increase in individual or cumulative occupational radiation exposure. Accordingly, the proposed amendment meets the eligibility criterion for categorical exclusion set forth in 10 CFR 51.22(c)(9). Therefore, pursuant to 10 CFR 51.22(b), no environmental impact statement or environmental assessment need be prepared in connection with the proposed amendment.
6.0 REFERENCES
- 1)
NRC Administrative Letter 98-10, "Dispositioning of Technical Specifications that are I nsufficient to Assure Plant Safety," December 29, 1998
- 2)
Operability Evaluation DE 10-006, Revision 3, "Non-Conservative Tech Spec Value for Loss of Voltage and Degraded Voltage," October 8, 2012
- 3)
NRC Letter from A. M. Stone to M. J. Pacilio, "LaSalle County Station, Units 1 and 2 Component Design Bases Inspection (CDBI) 05OO0373/2010006(DRS);
05000374/201 0006(DRS)," February 15, 2011
- 4)
Design Analysis L-002588, Loss of Voltage Relay Setpoint for 4.16 kV Buses 141 Y, 142Y, 143, 241 Y, 242Y, 243 - Undervoltage Function," Revision 1 E, September 5,2012 10 of 10
ATTACHMENT 2 Markup of Technical Specifications Page LASALLE COUNTY STATION UNITS 1 AND 2 Docket Nos. 50-373 and 50-374 Facility Operating License Nos. NPF-11 and NPF-18 REVISED TS PAGE 3.3.8.1-3
FUNCTION
- 1.
Divisions 1, 2 and Opposite Unit Division 2 - 4. 16 kV Emergency Bus Undervoltage
- a.
Loss of Vo ltage - 4.16 kV Basis
- b.
Loss of Voltage - Time Delay
- c.
Degraded Voltage - 4. 16 kV Basi s
- d.
Degraded Voltage - Time Del ay, No LDCA e.
Degraded Voltage - Time Del ay. LDCA
- 2.
Di visi on 3* 4. 16 kV Emergency Bus UndervD tage
- a.
Loss of Voltage - 4.16 kV Basis
- b.
Loss of Voltage - Time Del ay c. Degraded Voltage - 4.16 kV Bas is
- d.
Degraded Vol tage - Time Del ay, No l oeA
- e.
Degraded Vol t age - Time Oel ay, LOCA
, able 3.3.8.1
- 1 (page 1 of IJ Loss of Power Instrumentation REQUIRED CHANNELS PER 01 V I SION SURVEIllANCE REQUIREMENTS I::: 2870 V and S 3127 V 2
SR 3.3.8.1.3 SR 3.3.8.1.4 SR 3.3.8.1.5 2
SR 3.3.8.1.3 SR 3.3.8.1.4 SR 3.3.8. 1. 5 2
SR 3.3.8.1.1 SR 3.3.8. 1. 2 SR 3.3.8. 1. 5 2
SR 3.3.8. 1.1 SR 3.3.8. 1. 2 SR 3.3.8.1.5 2,.. Hb l SR 3.3.8. 1. 1 SR 3.3.8.1.2 SR 3.3.8. 1. 5 LOP Instrumentation 3.3.8.1 ALLOWABLE VALUE
~ 3.1 seconds and s 10. 9 seconds
~ 3814 V and s 3900 V
~ 27 0. 1 seconds and s 329.9 seconds
~ 9.4 seconds and s 10. 9 seconds I::: 2725 Vand s 3172 V ~
~
'i' aAd s 3137 '/
SR 3.3.8.1.4 SR 3.3.8.1.5 2
SR 3.3.8.1.3 s 10.9 seconds SR 3.3.8.1.4 SR 3.3.8.1.5 2
SR
- 3. 3.8.1.1
~ 3814 V and s 3900 V SR 3.3.8. 1.2 SR 3.3.8.1.5 2
SR 3.3.8. 1.1 it 270. 1 seconds and SR 3.3.8. 1. 2 s 329. 9 seconds SR 3.3.8.1.5 2,,'10' SR 3.3.8.1.1
~ 9. 4 seconds and s 10.9 seconds SR 3.3.8.1. 2 SR 3.3.8. 1. 5 (a)
In MODES 4 and 5, when associa ted ECCS subsystem (s ) are requ i red to be OPERABLE per LCD 3.5. 2, "ECCS-Shutdown."
(b ) Wi t h no fuel 1n tne react or ves sel, not requi red to be OPERABLE.
LaSa ll e 1 and 2
- 3. 3.8. 1-3 Amendment No. 155 /141
ATTACHMENT 3 Design Analysis L-002588 LASALLE COUNTY STATION UNITS 1 AND 2 Docket Nos. 50-373 and 50-374 Facility Operating License Nos. NPF-11 and NPF-18 Design Analysis L-002588, Revision 1 E, "Loss of Voltage Relay Setpoint for 4.16 kV Buses 141Y, 142Y, 143, 241Y, 242Y, 243 - Undervoltage Function"
CC-AA-309 Revision 0 Page 14 of 17 ATTACHMENT 1 DESIGN ANALYSIS APPROVAL Page 1 of 2 CALCULATION NO:
L-002588 REV: 01 Page No.1 of 28
[
] BRAIDWOOD STATION BYRON STATION
(
] DRESDEN STATION X ] LASALLE CO. STATION
(
) QUAD CITIES STATION
[ ] Unit 0
[X] Unit 1
[X] Unit 2
] Unit 3 DESCRIPTION CODE:
E07 (cola)
DISCIPLINE CODE: (Coil)
E SYSTEM CODE:
(CO1l)
AP ELEVATION CODE: (co16) 687, 710, 731 TITLE:
Loss of Voltage Relay Setpoint for 4.16 kV Buses 141Y, 142Y, 143, 241Y, 242Y, 243 --
Undervoltage Function P
] Safety Related
[
] Augmented Quality
[
] Non-Safety Related REFERENCE NUMBERS: (Coil Panel)
Type Number Type COMPONENT EPN: (CO14 Panel)
EPN Component Type DOCUMENT NUMBERS: (CO12 Panel)
(Calculation References)
Doc Type/
Document Number Sub Type 1(2)AP037A R19 PROC I jR LES-OA-101 1(2)AP037B R19 PROC&\\
LES-OA-201 1(2)AP040A R19 DWGC I See Section 5.3 1(2)AP040B R19 CALC I ENG See Section 5.6 1(2)AP041A R19 1(2)AP041 B R19 REMARKS:
E-FORM
CALCULATION TITLE PAGE NEP-12-02.01 Effective Date:
01/07/00 CALCULATION NO:
L-002588 Page No.
1.
[
] BRAIDWOOD STATION
[
I BYRON STATION
(
] DRESDEN STATION
[ X ) LASALLE CO. STATION
[
I QUAD CITIES STATION Unit 0
[X] Unit 1
[X] Unit 2
(] Unit 3 DESCRIPTION CODE:
E07 (Cola)
DISCIPLINE CODE:
(Coll)
E SYSTEM CODE:
(CO41)
AP ELEVATION CODE: (cols) 687, 710, 731 TITLE:
Loss of Voltage Relay Setpoint for 4.16 kV Buses 141Y, 142Y, 143, 241Y, 242Y, 243 -
Undervoltage Function
[ XX ] Safety Related
[
] Augmented Quality
[
] Non-Safety Related REFERENCE NUMBERS: (Coll Panel)
Type Number COMPONENT EPN: (0014 Panel)
EPN Component Type 1(2)AP037A R19 DOCUMENT NUMBERS: (CO12 Panel)
(Calculation R eferences)
Doc Type/
Document Number Sub Type PROC lrr LES-OA-101 1(2)AP037B R19 PROC /6 c..
LES-OA-201 1(2)AP040A R19 DWGC /
See Section 5.3 1(2)AP040B R19 CALC / ENG See Section -5:4 5.
1(2)AP041 B R19 REMARKS:
Revision Initiated 4/7/00.
REV. No.
REVISING ORGANIZATION APPROVED (P nt & Sign)
DATE 0
Sargent & Lundy W. A. Barasa 7-z 7-90 IPEPP-E FORM
REVISION
SUMMARY
N E P-12-02.02 Effective Date-01/07/00 PEPP-E FORM
ATTACHMENT I DESIGN ANALYSIS APPROVAL Page 2 of 2 CC-AA-309 Revision 0 Page 15 of 17 DESIGN ANALYSIS NO.
L-002588 REV:
01 PAGE NO. 7' C29 Revision Summary:
Revised CakeIstioe Sections 2.7 to address negligible uncertainties doe to seismic effects. The Calculation was transferred to new forms in accordance with the requirements of CC-4.A-309 and. FMS-C;-1d.
° It t.
t +c Electronic Calculation Data Files:
^
i h
our m n)
(Program Name, Version. File Name c%tensionisi date:
`
Design mpactreview completed?
(X 1 Yes
(
I No Significant clesign impact from results' I 1 Yes 1 X 1 No (!f }mss, attach impact review sheet)
Prepared by:
WW duo prft late prim s
Method of Review:
I X 1 Detailed
[
1 Alternate 1
1 Test Tiri Design Analysis supersedes:
Su pte^et Review Required?
1 1 Yes 1 X I Addkiesal Review i
i Special RMew Teatrt Meal Reviewer or Special Review Tess Leader 1
1 Y^rlnt t
Spa" Review Tee: (N/A for Addkkmti Review)
Reviewer
- }
1 1
Print S^lff Ewe hint tiwga Oat (Tracked Hv, A Tr-,. etc.)
I 3}
1 1
4}
1 Prim p
DOW Prom Si,a1 Oar Suppitmoutaf Review Results:
Approved by:
t1lr__
External Design Analysis Review(Attachment 3 Attached)
Reviewed 1w:
P" 4r n etc Approved by:
praru 5i^tn F3ate Do a srr,4.S,SViIPTIO'
/ ENGLYEl 11`!SG Jt' GE:%IE.YT require l^rttr r cnjkmi>>r' I
Yes I X I No E-FORM
NES-G-14.01 Effective Date:
04/14/00 CALCULATION TABLE OF CONTENTS CALCULATION NO.
L-002588 REV. NO. 01 PAGE NO. 3 SECTION:
PAGE NO.
SUB-PAGE NO.
TITLE PAGE 1
REVISION
SUMMARY
2 TABLE OF CONTENTS 3
PURPOSE / OBJECTIVE 4
METHODOLOGY AND ACCEPTANCE CRITERIA 5-7 ASSUMPTIONS / ENGINEERING JUDGMENT 8
DESIGN INPUT 9-12 REFERENCES 13-15 CALCULATIONS 16-25
SUMMARY
AND CONCLUSIONS 26-27 ATTACHMENTS 28 Attachment A - ABB Instructions, IB 18.4.7-2 Issue E, A1-A16 for Single Phase Voltage Relays, Types 27, 27D, 27H, 59D, and 59H (16 pages)
Attachment B - GE Instruction Manual GEI-90805J for B1-B14 Voltage Relay types NGV11A, B, 12A, B, C and 13A, B, Forms 21 and up. (14 pages)
Attachment C - Relay Setting Orders (6 pages)
C1-C6 Attachment D - LaSalle NDIT LS-1202 -
D1-D9 Transmittal of Improved Technical Specification (ITS) Analytical Limits (9 pages)
Attachment E - Telecon confirming RSO data (1 El of El page)
E-FORM J
CALC. NO. L-002588 CALCULATION PAGE REVISION NO. 01 N ES-G-14.02 Effective Date:
04/14/00 PAGE NO. 4 of 28 1.
PURPOSE/OBJECTIVE The purpose of this calculation is to evaluate relay setpoint errors associated with an extended 24 month calibration interval, to ensure adequate margin between the Analytical Limit (AL) and the setpoint. The analytical limits are based on LaSalle NDIT LS-1202 (Ref.
5.5.2).
In addition, a calculation is performed to determine an allowable value. It should be noted that an expanded tolerance calculation is NOT performed. No expanded tolerance evaluation is performed because the calibration of the device is a check to ensure the relay will actuate when voltage is removed.
This calculation is applicable for both normal and accident operating conditions.
This calculation is applicable for the following undervoltage relays that perform the Loss of Voltage identification function and initiate load shedding at Emergency Safe Shutdown (ESS) buses 141Y, 142Y, 241Y, 242Y, 143, and 243:
Relay Bus Relay Type 1(2)AP037A & B 141Y(241Y)
Inverse Time UV Relay 1(2)AP040A & B 142Y(242Y)
Inverse Time UV Relay 1(2)AP041A & B 143(243)
Undervoltage Relay Based on the component classification for the subject equipment (Ref. 5.5.1), this calculation is classified as safety-related.
For analysis of the time delay functions of these relays, refer to LaSalle calculation L-002589.
FORM
CALC. NO. L-002588 CALCULATION PAGE REVISION NO. 01 NES-G-14.02 Effective Date:
04114/00 PAGE NO. 5 of 28 2.
METHODOLOGY AND ACCEPTANCE CRITERIA 2.1 Basic Methodology This calculation is performed in accordance with NES-EIC-20.04 (Ref. 5.1.2) and the main body of Reference 5.1.3 with the clarifications and additions identified below. Appendix I of Reference 5.1.3 does not apply to this calculation because the Appendix is a documentation of guidelines for the ComEd calculations prepared under a different scope of work.
2.2 Classification Level A Level 1 evaluation is performed which provides the highest level of confidence as defined in Appendix D of NES-EIC-20.04 (Ref. 5.1.2). As a Level 1 evaluation, the random errors (6) are converted to a 2: value and added to the non-random errors (se).
Thus, the total error (Z) is Z=2a+Ze 2.3 Vendor Specifications Published instrument vendor specifications are considered to be based on sufficiently large samples so that the probability and confidence level meets the 2a criteria, unless stated otherwise by the vendor.
2.4 Negligible Uncertainties Per Appendix I of NES-EIC-20.04 (Ref. 5.1.2), the effects of radiation (eR), humidity (eH),
power supply (eV), calibration standard equipment (STD), and seismic (eS) under normal operating conditions may typically be considered negligible. For the evaluation of normal operating conditions, these errors are considered negligible unless otherwise noted.
2.5 Other Environmental Effects For environmental effects not considered negligible (Section 2.4), if the vendor does not provide a separate specification but the environmental limits are bounded by the vendor operating limits, then the effect is considered included in the reference accuracy.
2.6 Drift Specifications The calculated drift specification (Drift Tolerance Interval - DTIc) based on As-Left / As-Found data is used in place of the specifications for reference accuracy (RA), calibration error (CAL), setting tolerance (ST) and drift (DR).
E-FORM
CALC. NO. L-002588 I
CALCULATION PAGE REVISION NO. 01 NES-G-14.02 Effective Date:
04/14/00 PAGE NO. 6 of 28 2.7 Seismic Based on NES-EIC-20.04, Appendix I, Section 3.1, the combined seismic and environmental errors for all the instrument types during normal operation are assumed accounted for in the published reference accuracy for the device unless specifically stated by the vendor. The under voltage relays are all installed in a mild environment.
Therefore, the only accident of consequence is a design basis earthquake. These relays are installed in Class 1E switchgear (1,2AP04E, 1,2AP06E, and 1,2AP07E) and are seismically qualified (EWCS D030 panel component data). The vendor specifications do not provide separate error effects for a seismic event, therefore, the error due to seismic effects is considered encompassed and included in the published reference accuracy (References 5.7.1 and 5.7.2).
2.8 Calculated Setpoint A calculated setpoint will be determined utilizing the following equations from Appendix C of Reference 5.1.2 where applicable:
SPc
[lower limit]
SPc
<_ AL -
I Z" 1-MAR
[upper limit]
where, SPc: is the calculated setpoint AL: is the Analytical Limit Z+, Z': is the total error (positive, negative) for the device including all estimated effects-MAR: is a selected margin used to provide additional conservatism Note: The names of the terms in the generic equations shown above may be modified in accordance with specific loop designations.
The errors (Z) included in the determination of the calculated setpoint are all applicable instrument errors and environmental effects The calculated setpoint is determined using DTlc(See Section 2.6).
E-FO RM
CALC. NO. L-002588 CALCULATION PAGE REVISION NO. 01 NES-G-14.02 Effective Date:
04/14/00 PAGE NO. 7 of 28 2.9 Allowable Value An allowable value will be determined utilizing the following equations from Appendix C of 5.1.2 as applicable:
_ SPc - IZav+I AV
_SPc+IZav I
[lower limit]
[upper limit]
where, AV: is the allowable value SPc: is the calculated setpoint Zav+, Zav-: is the total error (positive, negative) applicable during calibration Note: The names of the terms in the generic equations shown above may be modified in accordance with specific loop designations.
The errors that are included for the determination of the allowable values (Zav) are only those applicable during calibration.
Thus, only reference accuracy (RA), calibration errors (CAL), setting tolerance (ST), drift (DR) and if applicable, the input error (bin) are included.
If DTIc is available, RA, CAL, ST and DR errors are replaced by the calculated drift (DTIc).
2.10 Acceptance Criteria The acceptance criteria for this calculation is that the field calibration setpoints (SPf) associated with the subject instrument loops are set such that the UV analytical limits are not exceeded.
There are no acceptance criteria for the allowable value determination. The allowable value is calculated in accordance with the methodology and the results are provided for use.
2.11 Minimum / Maximum Calculated Values The minimum/maximum operating voltage taking into account the field setpoint and the total negative/positive error will be calculated. These calculations are for information only.
These values will be calculated as follows:
MaxVal = SPf + Z-Upper Limit MinVal = SPf - I Z+
Lower Limit E-FORM
CALCULATION PAGE NES-G-14.02 Effective Date:
04/14/00 CALC. NO. L-002588 REVISION NO. 01 PAGE NO. 8 of 28 3.
ASSUMPTIONS 3.1It is assumed that the burden on the PT is within the standard test burden of the PT. Per engineering judgement documented in LaSalle calculation 4266/19AN71 (Ref 5.6.4), the expected variation in burden connected to the PT over time will be less than half of the rated burden, and the expected error associated with the PT was determined to be +/-0.175%. Therefore, use of the standard published error of
+/-0.3% for the PT is conservative. This assumption does not require verification.
3.2 To determine the temperature error associated with the Division 1 & 2 undervoltage relays, it is assumed that the relays are calibrated at the minimum and maximum normal ambient temperatures for the zone they are located in. This assumption is conservative and does not require verification.
3.3 To determine the control voltage error associated with the Division 1 & 2 undervoltage relays, it is assumed that the relays are calibrated at the minimum and maximum control voltage variation specified for the relay by the vendor. This assumption is conservative and does not require verification.
E-FORM
CALCULATION PAGE NES-G-14.02 Effective Date:
04/14/00 CALC. NO. L-002588 REVISION NO. 01 PAGE NO. 9 of 28 4
DESIGN INPUT 4.1 Instrument Channel Configuration Per Reference 5,3.1, the under voltage relay is used to detect a loss of voltage at the 4kV ESS buses (141Y, 142Y, 143, 241Y, 242Y, and 243). Hence, the under voltage relay is considered the first and only module in the loop making this a single module bistable loop.
Loss of Voltage at 4kV ESS Buses Under Voltage Relay 1(2)AP037A & B 1(2)AP040A & B 1(2)AP041A & B Initiate Load Shedding 4.2 Loop Element Data Unit 1 & 2, Division 1 & 2 Inverse Time Under Voltage Relay EPN 1(2)AP037A & B
[Ref. 5.5.1]
1(2)AP040A & B Manufacturer ABB
[Ref. 5.6.1]
Model No.
ITE-27 (211 R1175)
[Ref. 5.6.1]
Voltage Tap Range 60 - 110V
[Ref. 5.7.1 ]
Available Voltage Taps 60, 70, 80, 80, 100, 11 OV
[Ref. 57, ]
Differential Between Operate and Reset Voltage
< 0.5%
[Ref. 5.7. 11 Setting Tolerance - Operating Voltage
+/- 5% (Based on printed dial markings)
[Ref. 5.7.1]
Setting Tolerance - Operating Time
+/- 10% (Based on printed dial markings)
[Ref. 5.7.1]
Control Voltage Allowable Variation (125V Nominal) 100-140V
[Ref. 5.7.1]
Repeatability - Control Voltage Affects 0.2V for a 10V variation in control voltage
[Ref. 5.7.1 ]
Repeatability - Temperature Affects 0.5V over temperature range of 20-40°C (68°F - 104°F)
[Ref. 5.7.1]
Unit 1 & 2, Division 3 Under Voltage Relay EPN 1(2)AP041A & B
[Ref. 5.5.1]
Manufacturer General Electric
[Ref. 5.6.2]
Model No.
NGV-13A
[Ref. 5.6.2]
Dropout Voltage Adjustment Range 70 - 100V
[Ref. 5.7.2]
Pick-up Voltage s 110% of dropout voltage
[Ref. 5.7.2]
E-FORM
CALC. NO. L-002588 CALCULATION PAGE REVISION NO. 01 NES-G-14.02 Effective Date:
04/14/00 PAGE NO. 10of28 Unit I & 2, Division I & 2 Potential Transformer EPN Not assigned EPNs Manufacturer/Model No.
(See engineering judgement below)
Voltage Ratio 4200-120
[Ref. 5.6.4]
Accuracy Class 0.3 W,X,Y; 1.2 Z.
[Ref. 5.6.4]
(See engineering judgement below)
Frequency 60 Hz
[Ref. 5.6.4]
Engineering Judgement (Taken from Reference 5.6.4 and restated here for clarification)
The 4200/120 V PT at 4 kV SWGR 141 X for Unit 1 is a Westinghouse PC-60, 4200-120 V Style No. 2780A99GO2, 0.3 W, X, Y; 1.2 Z Accuracy Class. Because all 4 kV SWGR at LaSalle Station were purchased from the same manufacturer using one specification, it is expected that the 4200-120 V PTs at Unit 1 4kV SWGR 141Y and 142Y and Unit 2 4kV SWGR 241 Y and 242Y have an accuracy class equal to or better than that of the 4kV PTs at SWGR 141X.
Unit I & 2, Division 3 Potential Transformer EPN Not assigned EPNs Manufacturer GE
[Ref. 5.6.4]
Model No.
Type JVM-3; Model 763X21G18
[Ref. 5.6.41 Voltage Ratio 4200-120
[Ref. 5.6.4]
Accuracy Class 0.3 W,X,M,Y ; 1.2 Z
[Ref. 5.6.4]
Frequency 60 Hz
[Ref. 5.6.4]
E-FORM
CALC. NO. L-002588 CALCULATION PAGE REVISION NO. 01 NES-G-14.02 Effective Date:
04/14/00 PAGE NO. 11 of 28 4.3 Local Service Environments Per References 5.3.1, 5.3.3 and 5.5.1, the Loss of Voltage Relays 1AP037A & B, 1 AP040A & B, 2AP037A & B, and 2AP040A & B are located at Buses 141 Y. 142Y, 241 Y, and 242Y, respectively. Also per References 5.3.1, 5.3.3 and 5.5.1, the Loss of Voltage Relays for Buses 143 and 243 are located at their respective SWGR. Both normal and accident operating conditions are evaluated.
The conditions that are evaluated are summarized below based on References 5.4.1,2,3, and 4 for normal and worst case environmental conditions.
Panel Bus 143 / 243 Bus 141 Y 1 142Y Bus 241 Y / 242Y Location (Row-Column)
L-10 / L-20 N-10 N-20 Elevation 687' 710'/ 731' 710' 1731' EQ Zone Zone C3 Zone C2 Operating Conditions Ambient Temperature 80-119°F 70-104°F Range (40-119°F during maintenance or plant shutdown)
Ambient Pressure
+0.5" W.G.
+0.125" W.G.
Humidity 21 to 38% RH 36 to 57% RH (10 to 90% during maintenance or plant shutdown)
Radiation 1.0E03 RADS gamma (integrated) 4.4 Calibration Procedure Data Per the most recent Relay Setting Order [Ref. 5.8.1], the present settings for the Division 1
& 2 Loss of Voltage relays are provided below. The ratio for the P.T. supplying these relays is 35:1.
Relay Tap 70V
[Ref 5.8.1]
Relay Setting 75V min pickup (2625V on primary)
[Ref 5.8.1]
Surveillance Interval 24 months
[Ref 5.1.3]
Late Factor (LF) 25°/0
[Ref 5.1.31 Per the most recent Relay Setting Order [Ref. 5.8.1], the present settings for the Division 3 Loss of Voltage relays are provided below. The ratio for the P.T. supplying these relays is 35:1.
LRelay Setting Surveillance Interval Late Factor (LF) 82V Dropout (2870V on primary)
[Ref 5.8.1]
24 months 25%
[Ref 5.1.3]
[Ref 5.1.3]
I E-FORM
CALC. NO. L-002588 CALCULATION PAGE REVISION NO. 01 NES-G-14.02 Effective Date:
04/14/00 PAGE NO. 12 of 28 4.5 Analytical Limit (AL)
Per Reference 5.5.2, the Division 1 and 2 Loss of Voltage relay Analytical Limit (AL) is 2363 Vs AL <_ 3150 V at the bus. Also, per reference 5.5.2, the Division 3 Loss of Voltage relay Analytical Limit (AL) is 2583 V < AL s 3150 V at the bus. These voltages are transformed to a control voltage through a PT with a turns ration of 35:1 (Ref. 5.8.1).
Control Voltage = Bus Voltage / 35 Thus, the transformed control voltage AL bands are as shown below:
Control Voltage AL Division 67.52V<ALs90.00V 1 &2 73.80VsAL<90.00V 3
4.6 Calculated Drift Specifications Per Calculation L-002470 (Ref. 5.6.1), the 2a drift for 24 months surveillance interval (30 months with late factor) for the BBC/ABB ITE-27 4. 16kV Bus Undervoltage Relays is a random +/- 1.389 V with a bias of +0.460 / -0.791 Vac.
Per Calculation L-002472 (Ref. 5.6.2), the 2a drift for 24 months surveillance interval (30 months with late factor) for the GE model NGV-1 3A Undervoltage Relays is a random +/-
3.608 V with a bias of +0 / -0.190 Vac.
The bias drift is the drift determined by subtracting the as-left value from the as-found value per Section 2.2.2 of calculations L-002470 and L-002472 [Ref. 5.6.1 and 5.6.2].
Therefore, a positive drift implies that the actual trip value (as-found) is higher than the previously indicated trip value (as-left). This would reflect a negative bias instrument error effect, since bias is defined as indicated value minus actual value. Conversely, a negative bias drift implies a positive bias instrument error effect. Therefore, the bias drift effect is re-stated for use in this calculation as follows:
Division 1&2 Undervoltage drift bias
= +0.791 Vac / -0.460 Vac Division 3 Undervoltage drift bias
= +0.190 Vac / -0.000 Vac I
E-FORM
CALC. NO. L-002588 CALCULATION PAGE REVISION NO. 01 NES-G-14.02 Effective Date:
04/14/00 PAGE NO. 13 of 28 REFERENCES 5.1 METHODOLOGY 5.1.1 ANSI/ISA-S67.04-1994, "Setpoints for Nuclear Safety Related Instrumentation."
5.1.2 NES-EIC-20.04, Rev.2, "Analysis of Instrument Channel Setpoint Error and Instrument Loop Accuracy."
5.1.3 "Improved Technical Specifications (ITS) and 24-Month Technical Specifications Project Technical Plan.", Revision 2 dated 04 /28/2000.
5.2 PROCEDURES 5.2.1 NEP 12-02, Rev. 9, "Preparation, Review, and Approval of Calculations."
5.2.2 LES-OA-101, Revision 2, "Unit 1, Emergency Bus "Loss of Voltage" Relay Calibrations by OAD" 5.2.3 LES-OA-201, Revision 0, "Unit 2, Emergency Bus "Loss of Voltage" Relay Calibrations by OAD" 5.3 DRAWINGS 5.3.1 LaSalle Schematic Drawings 1 E-1-4005AM, Rev. L, "4160V Switchgear 141 Y Auxiliary Compartment System "AP" Part 12" 1 E-1-4005AT, Rev. N, "4160V Switchgear 142Y Auxiliary Compartment System "AP" Part 18" 1 E-1-4223AC, Rev. S, "4160V Switchgear 143 Auxiliary Compartment System "HP" (E22B) Part 3" 1 E-2-4005AM, Rev. K, "4160V SWGR 241 Y Auxiliary Compt. System AP Pt. 12" 1 E-2-4005AT, Rev. K, "4160V SWGR 242Y Auxiliary Compt. System AP Pt. 18" 1 E-2-4223AC, Rev. Q, "4160V Switchgear 243 Auxiliary Compartment System "HP" (E22B) Part 3" 5.3.2 LaSalle Single Line Drawings 1E-1-40008, Rev. N, "Part 2 Standby Generators and 4160V Buses" 1 E-2-4000B, Rev. L, "Stand-by Generators & 4160V Buses Part 2" 5.3.3 LaSalle Relaying and Metering Diagram 1 E-1-4000PG, Rev. N, "4160V Switchgear 141 Y" 1E-1-4000PJ, Rev. L, "4160V Switchgear 142Y" 1E-1-4000PK, Rev. N, "4160V Switchgear 143" 1 E-2-4000PG, Rev. L, "4160V Switchgear 241 Y" E-FORM
CALCULATION PAGE NES-G-14.02 Effective Date:
04/14/00 CALC. NO. L-002588 REVISION NO. 01 PAGE NO. 14 of 28 1 E-2-4000PJ, Rev. K, "4160V Switchgear 242Y" 1 E-2-4000PK, Rev. K, "4160V Switchgear 243" 5.4 ENVIRONMENTAL PARAMETERS 5.4.1 LaSalle UFSAR, Revision 13, Section 3.11, "Environmental Design of Mechanical and Electrical Equipment" 5.4.2 LaSalle UFSAR, Revision 13, Table 3.11-26, "Controlled Environment Zone C2 -
Conditions Inside the Essential Switchgear Rooms" 5.4.3 LaSalle UFSAR, Revision 13, Table -3.11-27, "Controlled Environment Zone C3 -
Conditions Inside the Diesel Generator Rooms, RHR Service Water Pump Rooms and HPCS DG Cooling Water Pump Rooms" 5.4.4 LaSalle UFSAR, Revision 13, Figure 3.11-5, Sheets 1 through 5.
5.5 OTHER STATION DOCUMENTS 5.5.1 ComEd EWCS Records 1AP037A
[002]
2AP037A
[002]
1AP037B
[002]
2AP037B
[002]
1 AP040A
[002]
2AP040A
[002]
1AP040B
[002]
2AP040B
[002]
1AP041A
[002]
2AP041A
[002]
1 AP041 B
[002]
2AP041 B
[002]
1AP04E
[002]
2AP04E
[003]
1AP06E
[002]
2AP06E
[002]
1AP07E
[002]
2AP07E
[002]
Note: The number in the brackets that follows the Equipment Part Number (EPN) is the EWCS record revision.
5.5.2 LaSalle NDIT LS-1202 - Transmittal of Improved Technical Specification (ITS) Analytical Limits. (Attachment D).
5.5.3 LaSalle UFSAR, Revision 13, Section 8.2.3.3, "Undervoltage Relays" 5.5.4 Telecon between M.C. Warpehoski of Sargent & Lundy and L. Cabrera of ComEd dated 7/25/00 verifying the relay setting orders for the loss of voltage relays (Attachment E).
5.6 CALCULATIONS 5.6.1 L-002470, Revision 0; "Instrument Drift Analysis for BBC/ABB Model ITE-27 4.16kV Bus Undervoltage Time Delay Relays - Undervoltage Function" 5.6.2 L-002472, Revision 0, "Instrument Drift Analysis for General Electric Model NGV-13A Undervoltage Relays" 5.6.3 4266-EAD6, Revision 3; "Voltage Relay Settings for 4160V and 480V ESF Buses" 5.6.4 4266/19AN71, Revision 1; "Second Level Undervoltage Relay Setpoint" IL E-FORM
CALL. NO. L-002588 CALCULATION PAGE REVISION NO. 01 NES-G-14.02 Effective Date:
04/14/00 PAGE NO. 15 of 28 5.7 VENDOR DOCUMENTS 5.7.1 ABB Instructions, IB 18.4.7-2 Issue E, Single Phase Voltage Relays, Types 27, 27D, 27H, 590, and 59H (Attachment A).
5.7.2 General Electric Instructions, GEI-90805J, for Voltage Relay Types NGV-1 1A & B, 12A,B,
& C, and 13A & B, Forms 21 and Up. (Attachment B).
5.8 MISCELLANEOUS REFERENCES 5.8.1 Present Relay Setting Orders for relays 1(2)AP037A & B, 1(2)AP040A & B, and 1(2)AP041A & B. (Attachment C).
E-FORM
CALC. NO. L-002588 CALCULATION PAGE REVISION NO. 01 N ES-G-14.02 Effective Date:
04/14/00 PAGE NO. 16 of 28 6
CALCULATIONS 6.1 Process / Input Error Evaluation The potential transformer (PT) has a standard published error of +/- 0.3% [Ref. 5.6.4].
Per assumption 3.1, the burden on the PT is within the standard test burden of the PT.
Therefore, the maximum error of +/-0.3% will be considered in this calculation.
Therefore, elp
=120V*0.003 el p1)1v1a2
= +/-0.36V el porv3
= +/-0.36V 6.2 Loss of Voltage Relay (Module 1) Errors 6.2.1 Module 1 - Random Errors 6.2.1.1 Standard Specifications (RA, CAL, ST, DR)
The Loss of Voltage relay's standard specifications of reference accuracy (RA),
calibration errors (CAL), setting tolerances (ST), and drift (DR) are considered included in the calculated drift (DTIc) per Section 2.6. Thus, these errors are not included in the errors evaluated by this calculation.
6.2.1.2 As-Left / As-Found Drift Data (DTI 1 c)
Per Section 4.6, the 26 calculated drift for Division 1 & 2 is +/- 1.389 V. Thus, DTI1 CD,vl&2
= +/- 1.389 V / 2 DTI 1 corv1 a2
= +/- 0.695 V Per Section 4.6, the 26 calculated drift for Division 3 is +/- 3.608 V. Thus, DT 11 cprv3
= +/- 3.608 V / 2 DTI 1 torus
=+/-1,804V 11 E-FORM
CALC. NO. L-002588 CALCULATION PAGE REVISION NO. 01 NES-G-14.02 Effective Date:
04/14/00 PAGE NO. 17 of 28 6.2.1.3 Random Input Errors (al in)
There are no random input errors for this instrument (Ref. 5.1.2). Thus, al inD,v1&2
=0V a11nD1v3
= 0 V 6.2.1.4 Total Random Errors (al)
Per Section 2.8, all potential errors are used in calculating the setpoint. Per Section 6.2.1.2, the calculated drift DTI1c is used in place of RA, CAL, ST, and DR. Therefore, the total random errors for the calculation of the setpoint are:
cs 1
= +/- [ DTI1 c2 + c 1 in2 1 1/2 61 DIV1&2
= +/- [ (0.695 V)2 + (0 V)2 ]1f2 01 DIV1&2
= +/- 0.695 V
[1 a]
61Dw3
=+/-[ (1.804V)2+(0 V)2 ]112 61 DIV3 1.804 V Per Section 2.9, DTI1 c is used for the allowable value random errors for single module loops. Thus, c1av
= DTI1c 61 avDIV1&2
('51 aVDIV3
= +/- 0.695 V
= +/- 1.804 V
[1a]
[1cr]
6.2.2 Module 1 - Non-Random Errors 6.2.2.1 Temperature Effects (e1T)
For the Division 1 & 2 relays, the temperature error associated with the undervoltage function as taken from Section 4.2 is 0.5 V over a temperature range of 20°C to 40°C (68°F to 104°F). Per section 4.3, the local environment in which the relays are located has an ambient temperature range of 70 °F to 104°F. Therefore, assuming that the relays are calibrated at their maximum or minimum ambient temperature (Assumption 3.2), the published error of +/- 0.5V will be used.
el TDIV3&2
= +/- 0.5 V E-FORM
CALC. NO. L-002588 CALCULATION PAGE REVISION NO. 01 NES-G-14.02 Effective Date:
04/14/00 PAGE NO. 18 of 28 For the Division 3 relays, there is no specific temperature errors or operating temperature range described in the vendor's specification for the undervoltage relay.
From Section 4.3, these relays are installed in a controlled environment with an ambient temperature of 80°F to 119°F under normal operating conditions. Per Appendix I of Ref 5.1.2, environmental errors such as those associated with Temperature Effects are assumed to be accounted for in the published reference accuracy of the device. Additionally, as these type relays are typically installed in a controlled environment and expected to perform their function under normal operating conditions, the effect of temperature related errors is considered negligible. Therefore, temperature related error associated with the Division 3 relays is considered to be included in the reference accuracy specification.
el Toiv3 = 0 V 6.2.2.2 Ambient Pressure Effects (el P)
The voltage relay is an electrical device and as such is not affected by ambient pressure changes (Ref. 5.1.2). Therefore, el PDIVIR2 el Pp,v3
=0V
=0V 6.2.2.3 Humidity Effects (e1H)
Appendix I of NES-EIC-20.04 (Ref. 5.1.2) recommends consideration of humidity effects in a condensing environment. Therefore, since the environment is non-condensing in this situation, humidity effects are considered negligible unless specifications by the vendor indicate otherwise.
There is no humidity errors described in the vendor's specification for the devices. As discussed above, the humidity effects are considered to be negligible. Therefore, e1Ho,v,&2
=0V elHD,V3
=0V E-FORM
CALC. NO. L-002588 CALCULATION PAGE REVISION NO. 01 NES-G-14,02 Effective Date:
04/14/00 PAGE NO. 19 of 28 I
6.2.2.4 Power Supply Effects (e IV)
For the Division 1 & 2 undervoltage relays, the variation in operating voltage for a 1 OV variation in control voltage is 0.2V (typical) per Section 4.2. Also per section 4.2, the control voltage is 125Vdc nominal with an allowable variation of 100V to 140V. As documented in LaSalle calculation 4266119AN71 (Ref 5.6.4), there is a maximum dc system voltage of 135.1 Vdc during the battery equalization period and the minimum calculated voltage at the relays will be greater than 100V when using a minimum voltage of 105V at the battery. Therefore, the voltage at the relays will be within the upper and lower limits of the range identified above. Therefore, assuming that the relays are calibrated at their maximum or minimum allowable control voltage (Assumption 3.3), the relay control voltage effect is as follows:
e1 VDIV1&2
= +/- [0.2V * (140V -100V)]
el VDIV1&2
= +/- 0.8V There are no power supply errors specified in the vendor specification for the Division 3 undervoltage relays. Per Section 2.4, these errors are considered negligible with respect to other errors terms. Therefore, e1 VDIV3 0 V 6.2.2.5 Radiation Effects (e1 R)
There are no radiation effects described in the vendor's specifications for the undervoltage relays. Per Section 2.4, radiation effects are considered included in the reference accuracy or capable of being calibrated out for normal conditions. Per Section 4.3, the total integrated dose the undervoltage relays will be exposed to is the same for accident and normal operating conditions. Thus, per Section 2.4, radiation effects for normal and accident conditions are considered to be negligible. Thus, e1RDlvl&2
= 0 V e1RDlv3
= 0 V 6.2.2.6 Seismic Effects (el S)
Per Section 2.7, seismic effects are not included in this calculation. Thus, e1SDIV1&2
=0V e1SDIV3
= 0 V E-FORM
CALC. NO. L-002588 CALCULATION PAGE REVISION NO. 01 NES-G-14.02 Effective Date:
04/14/00 PAGE NO. 20 of 28 6.2.2.7 Insulation Resistance Effects (elIR)
Per Section 4.1, this is a single module bistable loop and IR leakage errors are not applicable. Therefore, el IRD,vl&2 elIRDIV3 6.2.2.8 Process Error Effects (elp)
Per Section 6.1, the process error effects are:
el PDIV1&2
= +/-0.36 V e1p DIV3
= +/-0.36V 6.2.2.9 As-Found / As-Left Drift Bias Effects (e1 DTlc)
Per Section 4.6, the bias drift effect is:
el DTIcDIV1&2
= +0.791 V
/
-0.460 V e1DTIcDIV3
= +0.190 V
/
-0.000 V 6.2.2.10 Non-Random Input Errors (el in)
There are no input errors associated with the voltage relays. Thus,
=0V
=0V el inD,v,&2 el ino,v3
=0V
=0V 6.2.2.11 Total Non-Random Errors (Ze1)
In accordance with Section 2.8, the total positive and negative bias non-random errors for determining the calculated setpoint are Ee1+
=e1T+e1P+e1H+e1V+e1R+e1S+ellR+e1p++elDTlc++elin
_ +(0.5V + OV + OV + 0,8V + OV + OV + OV + 0.36V + Q.791V + OV)
_ +2.451 V
= +(OV + OV + OV + OV + OV + OV + OV + 0.36V + 0.190V + OV)
= +0.550 V 11 E-FORM rel DIV1 &2+
Eel DIV1 &2+
Ee l DIV3+
Ee l DIV3
CALC. NO. L-002588 CALCULATION PAGE REVISION NO. 01 NES-G-14.02 Effective Date:
04/14100 PAGE NO. 21 of 28 Eel'
=elT+elP+elH+elV+elR+elS+ellR+elp'+eIDT[c -+elin e1 Diw&2'
- v. el DIV1&2'
-(0.5V+OV+OV+0.8V+OV+OV+OV+0.36V+0.460V+OV)
-2.12V 7-e1Dry3'
= -(OV + OV + OV + OV + OV + OV + OV + 0.36V + OV + OV)
Eel DIV3-
= -0.36 V In accordance with Section 2.9, only the drift bias effect is included as a non-random error applicable for the determination of the allowable value. Thus, Eel av = el DTIc Eel avDIV1&2
= +0.791 V
/
-0.460 V Ee 1 avDIV3
= +0.190 V
/
-0.000 V E-FORM
CALC. NO. L-002588 CALCULATION PAGE REVISION NO. 01 NES-G-14.02 Effective Date:
04/14/00 PAGE NO. 22 of 28 E
6.3 Total Errors In accordance with Section 2.2, the total errors for determining the calculated setpoint are:
Z+
= 2*61 + set' ZDIV1&2+= 2
- 0.695 V + 2.451 V ZDIV1&2+= +3.841 V ZDIV3+
= 2
- 1.804 V + 0.550 V ZDIV3+
= +4.1 58 V Z
2*cr1 + ^e1" ZDIV1&2 = 2 * (-0.695 V) + (-2.12 V)
ZDIV1&2 = -3.51 V ZDIV3-
= 2 * (-1.804 V) + (-0.36 V)
ZDIV3
= -3.968 V In accordance with Section 2.9, the total errors for determining the Allowable Value are Zav*
= 2*c1 av + ref av+
.ZavD[Vl&2+
= 2
- 0.695 V + 0.791 V ZavDIV1 &2+
= +2.181 V ZavDIV3 ZavDIV3+
= 2
- 1.804 V + 0.190 V
= +3.798 V Zav'
= 2*alav + ref av ZaVDIV1&2 ZaVDIV1&2 ZaVDIV3
= 2 * (-0.695 V) + (-0.460 V)
= -1.85 V
= 2 * (-1.804 V) + (-0.000 V)
ZavDIV3-
= -3.608 V 6.4 Calculated Setpoint The values calculated for the parameters associated with the calculated setpoint are ALDIV,&2
<_ 90.00 V ALDIVl&2 67.52 V
[Section 4.5]
E-FORM
CALC. NO. L-002588 CALCULATION PAGE REVISION NO. 01 NES-G-14.02 Effective Date:
04/14/00 PAGE NO. 23 of 28 ALDIV3 s 90.00 V ALDIV3 73.80 V
[Section 4.5]
ZDIVI&2 = +3.841 V
/
-3.51 V ZDIV3
= +4.158 V
/
-3.968 V
[Section 6.3)
[Section 6.3]
Per References 5.6.1 and 5.6.2, the DTI1c is calculated based on a sufficiently large historical data, and per Reference 5.1.2, additional margin may be omitted in calculating the setpoint. Thus, MAR = 0 V Therefore, in accordance with Section 2.8, the calculated setpoints for upper and lower limits are:
SPc(UL) s AL(UL) - ( Z-I - MAR
[upper limit]
SPc(UL)Dlv1 2 <- 90.00 V - 3.51 V - 0 V SPC(UL)DIv,&2 < 86.49 V SPc(UL)DIV3 s 90.00 V-3.968 V- 0 V SPC(UL)DIV3
^ 86.032 V,,z86.03 V SPc(LL)
[lower limit]
SPc(LL)DIV1&2 > 67.52 V + 3.841 V + 0 V SPc(LL)Dlv1 2 ? 71.361 V, 71.37 V SPc(LL)DIV3
> 73.80 V + 4.158 V + 0 V SPc(LL)DIV3
>_ 77.958 V 77.96 V Division 1&2: Per Section 4.4, the field calibration setpoint (SPf) for this loop is 75 V [Ref.
5.8.1]. The field calibration setpoint value is within the calculated setpoint limits of > 71.37 V and < 86.49 V. Therefore, as the field calibration setpoint is bounded by the calculated setpoint limits, the field setpoint is acceptable.
Division 3: Per Section 4.4, the field calibration setpoint (SPf) for this loop is 82 V [Ref.
5.8.1 ]. The field calibration setpoint value is within the calculated setpoint limits of ^L 77.96 V and < 86.03 V. Therefore, as the field calibration setpoint is bounded by the calculated setpoint limits, the field setpoint is acceptable.
E-FORM 11
CALC. NO, L-002588 CALCULATION PAGE REVISION NO. 01 NES-G-14.02 Effective Date:
04/14/00 PAGE NO. 24 of 28 6.5 Allowable Value The values calculated for the parameters associated with the allowable value are SPc(UL)DIV1&2 s 86.49 V SPc(LL)DIV1&2? 71.37 V
[Section 6.4]
Zav01V1&2
= +2.181 V
/
-1.85 V
[Section 6.3]
SPc(UL)Dlv3 < 86.03 V SPC(LL)DIV3? 77.96 V
[Section 6.4]
ZavDIV3 = +3.798 V
/
-3.608 V
[Section 6.3]
Therefore, in accordance with Section 2.9, the calculated allowable value is AV(UL)
^ SPc(UL) + I Zav" AV(UL)01vl&2 5 86.49 V + 1.85 V AV(UL)01v12 c 88.34 V AV(UL)DIV3 86.03 V + 3.608 V AV(UL)Dlv3 s 89.638 V 89.63 V AV(LL)
>_ SPc(LL) - Zav+
? 71.37 V - 2.181 V AV(LL) DIVI&2
? 69.189 V z 69:19 V AV(LL)Dlv3
? 77. 96 V - 3.798 V AV(LL)Div3
? 74.162V z 74.17 V 6.6 Expanded Tolerances Expanded Tolerances are not calculated for these Loss of Voltage relays because the calibration of these devices is to check to ensure the relay will actuate when voltage is removed.
E-FORM
[upper limit]
[lower limit]
CALCULATION PAGE NES-G-14.02 Effective Date:
04/14/00 CALC. NO. L-002588 I REVISION NO. 01 PAGE NO. 25 of 28 6.7 Minimum / Maximum Calculated Values The minimum/maximum calculated values define the minimum/maximum operating values based on the recommended field settings. These values are calculated as follows (See Section 2.11):
MaxVal MinVal SPf+Z-I SPf - IZ+
MaxVaIDIV1&2 SPf DIV1&2 +I ZDIV182 I 75V + 3. 51V = 78.51V (2748V on primary side)
MinVaID1V1 2 SPf DIV1&2 -I ZDIV1&2+ I 75V - 3.841 V = 71. 159V (2490V on primary side)
MaxValDIV3
=
SPf DIV3
+
I ZDIV3 I
=
82V + 3.968V = 85.968V (3009V on primary side)
MinVaIDIV3
=
SPf DIV3 - I ZDIV3+ I
=
82V - 4,158V = 77.842V (2724V on primary side)
E-FORM
CALC. NO. L-002588 CALCULATION PAGE REVISION NO. 01 NES-G-14.02 Effective Date:
04/14/00 PAGE NO. 26 of 28
SUMMARY
AND CONCLUSIONS The results summarized below are applicable for normal and accident operating conditions.
7.1 Calculated Values Summary Calculated Setpoint:
71.37V <_ SPco,v,&2 s 86.49V 77,96V s: SPcDiv3 86.03V Allowable Value:
69.19V :5 AVDIV1&2 88.34V 74.17V 's AVDN3 5 89.63V Analytical Limit 67.52V<;
AVD,v1&2 :590-00V 73.80V s AVD,v3 s 90.OOV The minimum and maximum operating voltage values based on the recommended (existing) field settings are as follows:
Min/MaxD,v,&2 =
Min/MaxDiv3 7.2 Calibration Summary 71.16 / 78.51 V (2490V / 2748V) 77.84 / 85.97 V (2724V / 3009V)
The calibration information used to support the results of this calculation is defined below.
Calibration Setpoint / Allowable Value:
EPN Parameter Process Units Div 1 & 2 Field Calibration 75 V 1AP037A & B Setpoint 1AP040A & B Allowable Value
> 69.19 V and 2AP037A & B 88.34 V 2AP040A & B Analytical Limit
> 67.52 V and
<_ 90.OOV Div 3 Field Calibration 82 V 1AP041A & B Setpoint 2AP041A & B Allowable Value 74.17 V and
^89.63V Analytical Limit
> 73.80 V and 5 90.OOV PEPP-E FORM
CALL, NO, L-002588 CALCULATION PAGE REVISION NO. 01 N ES-G-14.02 Effective Date:
04/14/00 PAGE NO. 27 of 28 Calibration Frequency, Setting Tolerances and Expanded Tolerances (Div 1,2,3):
Surveillance Interval Setting Tolerance Expanded Tolerance Channel Calibration 24 months N/A N/A 7.3 Acceptance Criteria The acceptance criteria (Section 2.10) associated with the setpoints are met since the field calibration setpoint (SPf) is within the enveloping calculated setpoints (SPc) and therefore ensures that the analytical limits will not be exceeded.
There are no acceptance criteria for the allowable value determination.
PEPP-E FORM
I CALC, NO. L-002588 CALCULATION PAGE REVISION NO. 01 N ES-G-14.02 Effective Date:
04/14/00 PAGE NO. 28 of 28 8
ATTACHMENTS Attachment A: ABB Instructions, IB 18.4.7-2 Issue E, for Single Phase Voltage Relays, Types 27, 27D, 27H, 59D, and 59H Attachment B: GE Instruction Manual GEI-90805J, for Voltage Relay types NGV1 1A, B, 12A, B, C and 13A, B, Forms 21 and up.
Attachment C: Present Relay Setting Orders for Loss of Voltage Relays 1(2)AP037A&B, 1(2)AP04OA7B, and 1(2)AP041A&B.
Attachment D: LaSalle NDIT LS-1202 - Transmittal of Improved Technical Specification (ITS) Analytical Limits Attachment E: Telecon confirming RSO data - see Ref 5.5.4 Final
[Last Page]
PEPP-E FORM
CC-AA-309 - ATTACHMENT I - DESIGN ANALYSIS APPROVAL Page 1 of 2 GN ANALYS CLINTON STATION DROSt" STATION LASALLE CO. STATION STATION OUAD CITIES Wated BRAIIA BYRON Page 1 of 2 (Printed 12/18/01 7:13 AM E-Form CC-AA-309-1 v1.1 for use with CC-AA-309 Revision 1 and above.
CC-AA-309 - ATTACHMENT 1 - DESIGN ANALYSIS APPROVAL Page 2 of 2 SIGN
- Y Nt e L-0025M REV:
A PAGE NO. 2 E
Revision S
. (inctuding EC's incorporaw):
This minor durnge was prepared t being kWa#ed in the Class 1E 4160V swk;hgear buses (141Y 178 installs these new PTs install ftso e
s three on remi^n#V
(
of new ASS rnodel M
, 142Y. 241Y e 242Y on sw#dVm bus 1 141 Y, 241 Y & 242Y).
Y
) by various engneering 42Y. 06W sim#ar EECs will Electronic Calculation Data FRes-(Ptogram
, Version, File N
' `
's eo
- NSA,
/min)
Per E 3341 78 (If yes, attach Wripact review sheet)
P. McCarthy PIVA of Reviewed by-Scott R. Shwhard Prot Date Mathod of t
0 supersedes:
This D"I" Arwityift LVI In its orttirety.
Approved by.
aa-t 0Z onto External De"n I
fieview (Attachment 3Attached)
Reviewed by-E_ k ^
Poof
^
Approved by-.
A4 1 Date I
Do any A 9 I ENGWEERWG.tt Tr, By, A°T. etc.)
0 Y
- M Page 2 of 2 (Printed 12/18/01 7
- 13 AM E-Form CC-AA-309-1 v1.1 for use with CC-AA-309 Revision 1 and above.
NES-G-14.01 Effective Date:
04/14/00 i
CALCULATION PAGE NES-G-14.02 Effective Date:
04/14/00 CALCULATION NO. L-002588 REVISION 001A PAGE NO. 4 of 6 1.
PURPOSEIOBJECTIVE:
This minor revision is being prepared to determine the adequacy of new ABB model MY-60 potential transformers being installed in the Class 1E 4160V switchgear buses (141Y, 142Y, 241Y & 242Y) by various engineering changes. Engineering change EC 334178 installs these new PTs on switchgear bus 142Y. Other similar ECs will install these same PTs on remaining three switchgear buses (141Y, 241Y & 242Y). The ratings of the new PTs will be compared to those previously evaluated in this calculation to determine if the new PT ratings are acceptable.
The vendor information for the new PTs will be included as an attachment to this calculation minor revision.
2.
METHODOLOGYIACCEPTANCE CRITERIA:
Methodology This EC replaces the bus 142Y, Westinghouse model PC-60, PTs with new ABB model MY-60 PTs. The methodology used for this minor calculation revision is to compare the ratings of the new PTs with those previously analyzed and document this comparison. Any differences in ratings will be addressed.
Acceptance Criteria The acceptance criteria for the new PTs are as follows:
The new PTs must have the same voltage ratio as the existing PTs.
The new PTs must have the same accuracy class or better for a given burden as the existing PTs.
The new PTs must be rated for the same frequency as the existing PTs.
The power rating of the new PTs must be at least as high as the existing PTs.
3.
REFERENCES:
In addition to the references established in the current revision of this calculation, the following references apply to this pending revision:
3.1.
Calculation L-002588, Revision 001, "Loss of Voltage Relay Setpoint for 4.16 kV Buses 141Y, 142Y, 143, 241Y, 242Y, 243 - Undervoltage Function" 3.2.
Calculation AN71, Revision 001, "Second Level Undervoltage Relay Setpoint" 3.3.
EC 334178 3.4.
Asea Brown Boveri, Product Bulletin 42-951, dated Sept 1991, "Type MY-60 Voltage Transformer" (see Attachment A).
4.
ASSUMPTIONS:
4.1.
none
CALCULATION PAGE NES-G-14.02 Effective Date:
0411410© CALCULATION NO. L-002588 REVISION 001A PAGE NO. 5 of 6 5.
INPUT DATA:
5.1.
The ratings of the new ABB PTs are as follows (see reference 3.4):
ANSI metering accuracy (60Hz)
Accuracy Class:
0.3 W, X, Y and 1. 2 Z burdens at 120VAC Voltage Ratio:
4200-120V (35:1)
VA rating:
1000VA thermal at 30°C 6.
CALCULATION RESULTS:
Based on page 10 of reference 3.1, and page A6 of reference 3.2, the calculation was performed using the following PT information for bus 142Y.
Voltage Ratio:
4200-120V (35:1)
Accuracy Class:
0.3 W, X, Y and 1.2 Z burdens at 120VAC Frequency:
60 Hz VA rating:
1000VA thermal at 30°C A comparison of the existing PT information with the Input Data from reference 3.4 for the new ABB PTs, shows that the ratings for these two types of PTs are the same. Therefore, all of the acceptance criteria were met:
The new PTs have the same voltage ratio as the existing PTs.
The new PTs have the same accuracy class for a given burden as the existing PTs.
The new PTs are rated for the same frequency as the existing PTs.
The power rating of the new PTs is the same as the existing PTs.
CALCULATION PAGE NES-G-14.02 Effective Date:
04/14/00 CALCULATION NO. L-002588 REVISION 001A PAGE NO. 6 of 6 (final) I 7.
SUMMARY
AND CONCLUSIONS:
The comparison of rating information for the existing Westinghouse model (PC-60) PTs in the Class 1 E 4160V switchgear buses (141 Y, 142Y, 241 Y & 242Y) and new ABB model, MY-60, PTs has determined that the two types of PTs have equivalent ratings. Since the PT rating information is the same, there is no effect on the remaining calculations performed in Calculation L-002588.
The new ABB model MY-60 rating information is included in Attachment A of this minor revision.
This PT information should become an attachment to Calculation L-002588 when the next formal revision is performed.
CC-AA-309 - ATTACHMENT I - Design Analysis Approval Page 1 of 2 DESIGN ANALYSIS NO.:
L-002588 PAGE NO.1 Major REV Number:001 Minor Rev Number: B II BRAIDWOOD STATION
[
] BYRON STATION
[
] CLINTON STATION
[
] DRESDEN STATION
[ X] LASALLE CO. STATION
[
] QUAD CITIES STATION Unit:[ 10 [X]1
[X]2 TITLE: `-off Q'
[ Y ] Safety Related DESCRIPTION CODE:(c018) 103 DISCIPLINE CODE: (Coil)
I SYSTEM CODE: (CO11)
&.tb V ^'i
.5s \\4t.\\y, tjQL1, t`t3,.?
] Augmented Quality
[ ] Non-Safety Related TYPE Elevation Software VALUE ATTRIBUTES (C016)
PE VALUE COMPONENT EPN: (C014 Panel)
EPN TYPE DOCUMENT NUMBERS:
(C012 Panel) (Design Analyses References)
Type/Sub Document Number Input (YIN)
See Rev I CAC/ENG L-002589 Revision 1A Y
REMARKS:
Page 1 of 2 (Printed: 05/15/02 11;31 AM)
E-Form CC-AA-309-1 v1.1 for use with CC-AA-309 Revision 1 and abov?.
CC-AA-309 - ATTACHMENT I - Design Analysis Approval Paae 2 of 2 DESIGN ANALYSIS N.
L4)02588 R:
11B PAGE N.
2 Revision Summary (including EC's (`
-d o dmdqx*ft fbrDv 1&2. Reviumt or added s 2A,, 2-8 2 9 7,1.7,2.7,3 and 7A t
o R
to to
.3.4,
, F 4 8,5A.2, &&5. 5.6,5, 6*
2, 555, 585, 64,6 8, 67,S 8, Electronic
'u u Data Files, (Pmgram Name, Vers=, Re Nam z
r/rein)
Design irnpact review
?
[
Y z) : A Pe - E (If yes, attach impact r Prepared by:
R. F ck t
p ir m Reviewed 1
E. Sed^
PrOd c
Metttod R
[
Alternate This Design supersede*:
in its entirety.
I
j b
E 7
{ass-',
Y,+'
} Z OR 01
£
^r u
y'
'+
h S 3^>'" ^y x?
.'=`
Y^'^L^ :
'ff^'^^(4u^1 1
am
^
S^"'
'u At^.f#°nhUFst
^.'^
Y d.
3 Yi'{°^^ §^
3:4°vz.X'
.3 r` /f
£
`:
L?K 4"'.'
E`* ` "x s.l
£ ak 3f° w'
s R
{
`F
{
..4 JA Pared
.^
°.
/
,.^.
° External aAnalysis Olview Attachment 3 Attach NOW ed)
Ftevkmed by, Sign DWe Approved by:
p pmd
/
3-Date D o any ASSU
/ O S / ENGWEERNGJU OG EM E ' N T S requke b w
[
] Y e s [ X I Tracked AT#, EC# etc.) -
Page 2 of 2 (Printed: 05/15/02 11:31 AM)
E-Form CC-AA-309-1 v1.1 for use with CC-AA-309 Revision 1 and above.
NES-G-14.01 Effective Date:
04/14/00 CALCULATION TABLE OF CONTENTS CALCULATION NO.
L-002588 REV. NO. 001B PAGE NO. 3 SECTION:
PAGE NO.
SUB-PAGE NO.
TABLE OF CONTENTS PURPOSE / OBJECTIVE METHODOLOGY AND ACCEPTANCE CRITERIA ASSUMPTIONS / ENGINEERING JUDGEMENTS DESIGN INPUT REFERENCES CALCULATIONS
SUMMARY
AND CONCLUSIONS ATTACHMENTS:
Attachment F-Acceptance Regions for Calibration Checkpoints for ITE-27 Relays 3
4 4-6 6
6-7 7
7-9 9-10 11-12 E-FORM Page 3 of I2
CALCULATION PAGE NES-G-14.02 Effective Date:
04/14/00 Purpose/Objective The purpose of this revision to the calculation is to revise the computed values to provide a set of acceptance criteria such that the calibration of the ITE-27 type inverse time low voltage trip relay will better coordinate with the requirements of the design and still meet Technical Specification requirements.
Methodology and Acceptance Criteria Replace paragraph 2.1 with the following:
2.1 Basic Methodology The settings of the ITE-27 Inverse Time Delay Low Voltage Relays consist of a pickup voltage tap setting and a time delay tap setting, both of which can be slightly adjusted.
The determination of where these taps are set is made by T&D Protection Engineering and this calculation will provide this group with the required acceptance criteria for these relays for the purpose of compliance with Technical Specifications.
This calculation of uncertainty for the instrument is performed in accordance with NES-EIC-20.04 (Ref. 5.1.2) and the main body of Reference 5.1.3 with the clarifications and additions identified below.
Once the uncertainties are known, then, using the time delay requirements of Reference 5.6.5, the following will be determined:
1.
The maximum pickup voltage setting for the relay that would ensure that the relay is energized before the voltage reaches the minimum expected bus voltage during a transient will be determined.
Determining this point will be done by subtracting the uncertainty of the ITE-27 voltage setting as computed in the uncertainty section of the calculation from the analytical limit for the high voltage.
2.
The acceptance criteria for calibration of the ITE-27 relays will be determined, to ensure that the requirements of Technical Specifications are met. This will be done by providing a range of times vs. voltages, in a graphical form, that will ensure that the relay meets it's technical specification requirements if it is set to pass through these ranges.
This will be done by taking two points, one near the high end of the technical specification voltage range and one near the low end of the technical specification range and looking at the expected results considering the uncertainties in the relays. Both voltage and time delay uncertainties will be considered, causing a range of acceptable results that can be plotted.
CALCULATION PAGE NES-G-14.02 Effective Date:
04/14/00 I CALCULATION NO. L-002588 REVISION NO. 1B PAGE NO. 5 of 12 3.
The minimum time delay that can be accepted at a voltage that corresponds to 60% of bus voltage.
Revise paragraph 2.8 with the following:
2.8 Nominal Setpoint A nominal setpoint will be determined utilizing the following equations from Appendix C of Reference 5.1.2 where applicable:
SPc
<_ AL -
I Z° # - MAR
[lower limit]
[upper limit]
Where,SPc: is the nominal setpoint AL: is the Analytical Limit Z+, Z': is the total error (positive, negative) for the device including all estimated effects MAR: is a selected margin used to provide additional conservatism Note: The names of the terms in the generic equations shown above may be modified in accordance with specific loop designations.
The errors (Z) included in the determination of.the calculated setpoint are all applicable instrument errors and environmental effects This nominal setpoint is determined using DTIc(See Section 2.6).
These setpoints are not values that will be set into the ITE-27 relay as discrete values but will be used as the basis for the acceptance criteria for calibration.
Revise paragraph 2.9 as follows:
2.9 Allowable Value An allowable value will be determined utilizing the following equations from Appendix C of 5.1.2 as applicable:
>_ SPc -
C Zav+ I
[lower limit]
AV SPc+IZav I
[upper limit]
E-FORM Pace 5 of 12
CALCULATION PAGE NES-G-14.02 Effective Date:
04/14/00 CALCULATION NO. L-002588 REVISION NO. 113 PAGE Nth, 6 of 12 where, AV: is the allowable value SPc: is the calculated nominal setpoint Zav+, Zav : is the total error (positive, negative) applicable during calibration Note: The names of the terms in the generic equations shown above may be modified in accordance with specific loop designations.
The errors that are included for the determination of the allowable values (Zav) are only those applicable during calibration. Thus, only reference accuracy (RA), calibration errors (CAL), setting tolerance (ST), drift (DR) and if applicable, the input error (bin) are included. If DTIc is available, RA, CAL, ST and DR errors are replaced by the calculated drift (DTIc).
The computed AV will provide a sufficient safety margin because it is computed from the developed nominal setpoint, and the setpoint is being checked with an acceptance criteria that ensures that the relay follows it's expected curve.
Assumptions / Engineering Judgments Add the following assumption/engineering judgement:
3.4 The ITE-27 is an inverse time delay low voltage trip relay. The relay follows a set inverse function based on a time tap and voltage tap setting. If two points on this curve are verified to be within a given tolerance, then the curve is assumed to be "true" within those tolerances throughout the range of concern. These points are close enough to each other that there is little probability that the curve could deviate enough to fall outside the desired region if the calibration checkpoints are within their ranges.
Design Inputs Add the following design input:
4.7 The time delays associated with these relays are computed in Reference 5.6.5 and the values for Division 1 and 2 are as specified below:
E-FORM Page 6 of 12
NES-G-14.02 Effective Date:
04/14/00 CALCULATION PAGE CALCULATION NO. L-002588 REVISION NO. 1B PAGE NO. 7 of 12 Calculated Upper Allowable Value (AV1 u)
< 10.9 seconds Calculated Setpoint (SP1 cu) 8.3 seconds Calculated Lower Limit Setpoint (SP1 CL)
>_ 4.3 seconds Calculated Lower Allowable Value (AV1 L)
? 3.1 seconds Calibration Frequency and Tolerances Surveillance Interval Setting Tolerance Expanded Tolerance 24 months Point!:
+/- 10% (+/- 0.83 seconds)
Point 2:
+/- 10% (+/- 0.43 seconds)
Point!:
+/- 25.5% (+/-2.12 seconds)
Point 2:
+/- 23.9% (+/- 1.03 seconds) 4.8 Calibration checkpoints will be at or near the high and low technical specification range when setting tolerance is included. From Design Input 4.2 the setting tolerance for voltage is +/- 5.0 % The low checkpoint is approximately 75 Volts computed from the value in section 6.4 of 71.37 volts adjusted up by 5% tolerance. The high checkpoint is approximately 82 volts computed from the value in section 6.4 of 86.49 V when adjusted down by 5% tolerance. These two voltages, 75 Volts and 82 Volts, will be used for calibration checkpoints. These adjusted calibration points will provide some additional conservatism in that the inverse voltage curve that will fit them will meet tighter constraints.
References Revise Reference 5.1.2 to Revision 3.
Add the following references:
5.5.5 LaSalle Technical Specification 3.3.8.1 5.6.5 L-002589, Instrument Setpoint Analysis for 4.16KV Undervoltage (Loss of Voltage) Relay
- Time Delay Function, Revision 1A Calculations Revise section 6.4 as follows:
Change title to 6.4 Nominal Calculated Setpoint E-FORM Page7of 12
IVES-G-14.02 Effective Date:
04/14/00 CALCULATION PAGE CALCULATIO N NO. L-002688 REVISION NO. 113 PAGE NO. 8 of 12 After the calculations:
SPc(LL)D,v3
? 73.80 V
+ 4.158 V + 0 V SPc(LL)D,,
>_ 77.958 V 77.96 V Revise the Division I & 2 statement to read:
Division 1 & 2:
The upper setpoint, SPc(UL)¢,V,8,2 : 86.49 V, is the maximum value that the pickup voltage of the relay can be set at. This is the maximum voltage as the uncertainty of the relay voltage setting is taken into account.
The lower setpoint, SPC(LL)DIV1a2
? 71.361 V 71.37 V, is representative of the voltage value that will be above the lower analytical limit but will be used to check for compliance with the expected values near the low end of the voltage range.
Revise paragraph 6.6 to read as follows:
6.6 Expanded Tolerances Expanded Tolerances are not calculated for these relays because the calibration of these devices does not check to ensure the relay will actuate at a specific setpoint.
In paragraph 6.7 delete the MinVal and MaxVal equations for division 1 and 2.
Add paragraph 6.8 as follows:
6.8 Acceptance Criteria for Calibration Testing The acceptance points that should be tested are for PT Secondary voltages as specified in Design Input 4.8.
For the 82 Volt checkpoint the upper time delay limit from design input 4.7 will be used.
Thus for a simulated bus voltage that generates 82, within the range of the 5% setting tolerance of +/- 4.1 Volts, at the PT secondary, the time delay should be 8.3 +/- 0.83 seconds.
For the 75 Volt checkpoint the lower time delay limit from design input 4.7 will be used.
Thus for a simulated bus voltage that generates 75, within the range of the 5% setting E-FORM Page 8 of 12
CALCULATION PAGE NES-G-14.02 Effective Date:
04/14/00 I CALCULATION NO. L-002588 REVISION NO. 1B PAGE NO. 9 of 12 tolerance of t 3.75 Volts, at the PT secondary, the time delay should be 4.3 +/- 0.43 seconds.
SUMMARY
AND CONCLUSIONS In paragraph 7.1 delete the MinVal/MaxVal Values for Division 1 and 2.
Revise the table in 7.2 as shown below:
EPN Parameter Process Units Div 1 & 2 Field Calibration 75 V IAP037A & B Checkpoints 82 V 1AP040A & B Allowable Value
>_ 69.19 V and 2AP037A&8 s88.34V 2AP040A & B Analytical Limit
> 67.52 V and
< 90.OOV Div 3 Field Calibration 82 V 1AP041A & B Setpoint 2AP041A & B Allowable Value
? 74.17 V and
<_ 89.63 V Analytical Limit z 73.80 V and 90.OOV Calibration Frequency, Setting Tolerances and Expanded Tolerances (Div 1,2,3):
Surveillance Interval Setting Tolerance Expanded Tolerance Channel Calibration 24 months
+/- 10%
N/A Replace 7.3 with the following:
7.3 Acceptance Criteria for Division 3 The acceptance criteria (Section 2.10) associated with the setpoints for Division 3 are met since the field calibration setpoint (SPf) is within the enveloping calculated setpoints (SPc) and therefore ensures that the analytical limits will not be exceeded.
There are no acceptance criteria for the allowable value determination.
E-FORM CE i
Page 9of 12
CALCULATION. PAGE NES-G-14;02.
Effective Date:
04/14/00 Add a new paragraph 7.4 as follows:
7.4 Calibration Checkpoint Acceptance Criteria for division I and 2 The verification that the ITE-27 inverse voltage curve will meet the requirements of this calculation for Division I and 2 is to test the relay to ensure that:
A.
The pickup voltage is not set higher than 86.49 V.
B.
That, when the relay trips with a simulated bus voltage that equals 60% of the normal bus voltage that the time delay is greater than the minimum allowable value of 3.1 seconds.'
C.
That when the relay trips with simulated bus voltages of 75 and 82 +/- 10% Volts the time delays will be within expected zones as shown on Attachment F pages 1 and 2.
ATTACHMENTS Attachment F: Acceptance Regions for Calibration Checkpoints for ITE-27 Relays, Final
[Last Page]
E-FORM Page 10 of 12
NES-G-14..
Effective Date:
04114/00 CALCULATION PAGE I
CALCULATION NO. L-002688 REVISION NO. 9 B PAGE NO. I I of 12 Attachment F:
Acceptance Regions for Calibration Checkpoints for ITE-27 Relays Page F1 of F2 Low Calibration Check Point 11.1__I_
1-A 1 11 1 1 I 1__T _1 -F-I TA - [ -- I --
a a
4.25 I
4 Boundary 0-- Lo Cal Point I
a 3.75 71 73 72 74 75 PT Secondary Voltage E-FORM Page llof 12 77 76 79 78
CALCULATION PAGE NES-G-14.,
Effective Date:
04/14/00 CALCULATION NO. L-002588 REVISION NO. 1B PAGE NO.
12 of 12 Attachment F:
Acceptance Regions for Calibration Checkpoints for ITE-27 Relays Page F2 of F2 High Calibration Check Point PT Secondary Voltage E-FORM Page 12 of 12
CC-AA-309 - ATTACHMENT I - Design Analysis Approval Page 1 of 2 DESIGN ANALYSIS NO.:
L-002588 PAGE NO.
Major REV Number: 001 Minor Rev Number: C 3
] BRAIDWOOD STATION
] BYRON STATION
] CLINTON STATION
} DRESDEN STATION LASALLE CO. STATION I QUAD CITIES STATION Unit:[ 10
[Xj1 (X]2 DESCRIPTION CODE:(co/a) 103 DISCIPLINE CODE: (0011)
I SYSTEM CODE: (C011)
AP TITLE: Loss of Voltage Relay Setpoint for 4.16 kV Buses 141Y, 142Y, 143, 241Y, 242Y and 243 - Undervoltage Function X ] Safety Related
(
] Augmented Quality
[
] Non-Safety Related ATTRIBUTES (C016)
TYPE Elevation Software VALUE TYPE VALUE COMPONENT EPN: (0014 Panel)
EPN TYPE (2)AP037A R
1(2)AP037B R19 1(2)AP040A R19 2)AP040B R19 (2)AP04IA R19 1(2)AP041 B RI 9(R20)
REMARKS:
Page 1 of 2 (Printed: 08116102 5:34 PM)
.E-Form CC-AA-309-1 v1.1 for use with CC-AA-309 Revision 1 and above.
DOCUMENT NUMBERS:
(0012 Panel) (Design Analyses References)
Type/Sub Document Number Input (YIN) i
/
/
CC-AA-309 - ATTACHMENT I - Design Analysis Approval Page2of2 DESIGN ANALYSIS WWISW REV: ODIC PAGE NO.
Revhdon Summary (OmkxWV EC's b d - The purpose of aft revision is to correct an saw Ow was made in n*w remon 18 of mmorrectly identifying #* Se voltage for the n
Surntnary a section 4.
ftV Tolerance nd ConcAmons Table
.2 and c n f?
E y
I WA, E-(If yes, attach Wnpad review sheet 1
14 i
Pft Sir
.01 DOW P^ft so*
WOW of Rmdew-ii Detailed I i Ahm%ale i
Test Daft TW*
e Anah"ft supersedes:
in its or r
p 43 Lsi "X.^w
+?.
Y`
k;"£
^'4 2^
JF a.%A,
^
- ^
3^'
^b
'ff
'?
^'
^t^F'1*°'^f' x
1.
3
^
^4r 1
A 6^^k^
. t`.
u
{
31 P:,
Y_"
yjly 3
F -s 41 y
3 Appwed
+
n s
rrt Attached) 3RD
°
{
p g
F t
m Approved by:
Date any ASSUMP?ZONS / ENGWSEM NG later a Tracked
- AT*o C e I Yes [XI No Page 2 of 2 (Printed: 08/16/02 5:34 PM)
E-Form CC-AA-309-1 y1.1 for use with CC-AA-309 Reyisk,r, 1 and above.
NES-G-14.01 Effective Date:
04/14/00 CALCULATION TABLE OF CONTENTS CALCULATION NO.
REV. NO.
PAGE NO.
SECTION:
PAGE NO.
SUB-PAGE NO.
TITLE PAGE:
REVISION
SUMMARY
TABLE OF CONTENTS PURPOSE / OBJECTIVE METHODOLOGY AND ACCEPTANCE CRITERIA ASSUMPTIONS i ENGINEERING JUDGEMENTS DESIGN INPUT REFERENCES CALCULATIONS
SUMMARY
AND CONCLUSIONS ATTACHMENTS 2
N/A N/A N/A N/A N/A 4
N/A II E-FORM
Purpose/Objective The purpose of this revision is to correct an error that was made in minor revision 1B of incorrectly identifying the Setting Tolerance of the checkpoint voltage for the undervoltage relays; Calibration Frequency, Setting Tolerances and Expanded Tolerances (Div 1,2,3);
Surveillance Interval Setting Tolerance Expanded Tolerance Channel Calibration 24 months
+/- 5°10 NIA Revise the Setting Tolerance of voltages in Table 7.2 and section 7.4 to a value of t 5% to Table 7.2 changes:
agree with section 4.8 and Design Input 4.2.
7.4.C is changed to:
C.
That when the relay trips with simulated bus voltages of 75 and 82 +/- 5% Volts the time delays will be within expected zones as shown on Attachment F pages 1 and 2.
Final
[Last Page]
CC-AA-309-1001 Revision 4 ATTACHMENT 2 Design Analysis Minor Revision Cover Sheet Design Analysis (Minor Revision)
Last Page No. ° 3 Analysis No.:
L-002588 Revision: 2 001 D
Title:
Lose of Voltage Relay Setpoint for 4.16 ikV Buses 141 Y,142Y,143, 241 Y, 242Y, 243-Undervoitage Function EC/ECR No.:
369973 Revision: a 000 Station(s):
LaSalle Unit No.: a
- 0. 1 &2 Safety/QA Class: ° SR System Code(s):
10 AP is this Design Analysis Safeguards Information?
Yes E] No o If yes, see SY-AA-101-106 Does this Design Analysis contain Unverified Assumptions? 1' Yes El No 0 If yes, ATI/AR#:
N/A This Design Analysis SUPERCEDES: "
N/A In its entirety.
Description of Changes (list affected pages): "
1 `
(s1 The seismic uncertainty in Section 2.7 is clarified by adding a paragraph describing that actual test data from seismic qualification testing v da+ the time delay settings not affected.
Added Acton Labs Test Report 18333-T W9as Re erence 5.7.3 and Attachment G.
Added direct References for Analytical Limits (currently NDIT LS-1202 is referenced).
Disposition of Changes:,,,
All changes are clarification of existing information or deletion of unnecessary information, so there is no impact on any calculated values or conclusions.
Add Calculations L-000295 and L-001561 as cross-references in to this calculation.
Preparer:
1e E. Zacharias 6-&A-LeAA" Print Name Sl Name Date Method of Review:
Detailed Review 0 Alternate 11 Ic lation 0 Testing 0 Reviewer:
T. J. Van Wyk t S Print Name Sign Name D
Review Independent review Peer review C1 Notes:
12 (For External Analyses Only)
External Approver:
Prim Name Sign Name Date Exelon Reviewer 81 Print Name SI Name Date Exelon Approver: 21 1ffit^RA^
CA
]
=
^ Print Narnri 5i Date
CALCULATION TABLE OF CONTENTS CALCULATION NO. L-002588 REV. NO. 0010 PAGE NO.2 SECTION:
PAGE NO.
SUB-PAGE NO.
a NA NA NA NA NA NA NA NA NA N/A TABLE OF CONTENTS 1.0 PURPOSE / OBJECTIVE 2.0 METHODOLOGY AND ACCEPTANCE CRITERIA 3.0 ASSUMPTIONS / ENGINEERING JUDGEMENTS 4.0 DESIGN INPUT
5.0 REFERENCES
6.0 CALCULATIONS 7.0
SUMMARY
AND CONCLUSIONS 8.0 ATTACHMENTS 9
2 3
3.
N/A 3
3 N/A N/A 3
GI -G8 G: Acton Test Report 18333-8,N (Partial - Seismic test data pages only).
CALCULATION PAGE CALCULATION NO. L-002588 REVISION NO. 001 D Page No. 3 of 3 1.0 _
PURPOSEIOB]ECTIVE The purpose of this minor revision is to correct several minor discrepancies noted during review of the calculation. (These discrepancies were documented in IRs 672166)
Revise Calculation 1-002588 as ollows:
2.0 METHODOLOGY AND ACCEPTANCE CRITERIA Add the following raph to the end of Section 2.7 Seismic:
Seismic qualification testing performed at Acton Labs validated that there was no change detected in the time delay settings of the ITE-27N relay during seismic testing. (Reference 5.7.3) 4.0 DESIGN INPUT Revise first sentence in 4.5 Analytical Limit (AL) as follows:
"Per References 5.5.2, 5.6.5, and 5.6.6, the Analytical Limits (AL) are as follows:"
5.0 REFERENCES
Add References 5.6.5. 5.6.6. and 5.7.3 as follows:
"5.6.5 LaSalle Calculation L-000295, Rev. 2C, "Analysis of Safety Related Loads During LOCA Block Start for LaSalle Unit 2" 5.6.6 LaSalle Calculation L-001561, Rev. 4C, "Analysis of Safety Related Loads During LOCA Block Start for LaSalle Unit 1"
- 1
- I I I 5.7.3 Acton Test Report 18333 -8fN (Attachment G)"
13 4 44A, I "G. Acton Test Report 18333-8 N (Partial - Seismic test data pages only)"
This minor revision to L-002588 is for clarification of minor discrepancies and does not affect any calculated values, 4
8.0 ATTA NTS Add Attachment G as follows:
Exek,n..
ATTACHMENT I Design Analysis Cover Sheet Design Analysis
( Last Page No. 8, Attachment B, Page B2 Analysis No.: t L-002588 Revision: Z 001E Major
Minor Z
Title:
3 Loss of Voltage Relay Setpoint for 4.16 kV Buses 141Y, 142Y, 143, 241Y, 242Y, 243 -
Undervoltage Function EC/ECR No.:
390578, 390579 Revision: '
000, 000 Station(s): '
LaSalle Component(s): '.
Unit No.: '
01 and 02 1427-AP037A 2427-AP037A Discipline: ° ELDC 1427-AP0376 2427-AP037B Descrip. Code/Keyword:
E07 1427-AP040A 2427-AP040A Safety/QA Class: "
SR 1427-AP040B 2427-AP040B System Code:
AP 1427-AP041A 2427-AP041A Structure:
REACTOR BUILDING 1427-AP041 B 2427-AP041 B CONTROLLED DOCUMENT REFERENCES Document No.:
From/To Document No.:
From/To From Is this Design Analysis Safeguards Information? "
Yes El No E If yes, see SY-AA-101.106 Does this Design Analysis contain Unverified Assumptions? "
Yes No [0 If yes, ATI/AR#:
This Design Analysis SUPERCEDES: "
N/A in its entirety.
Description of Revision (list changed pages when all pages of original analysis were not changed): 19 Calculation L-002588 is a Key calculation and approval for to use a Minor revision was obtained from Mr. Richard Meyer on June 05, 2103.
This minor revision addresses Loss of Voltage (LOV) relay setpoint change to address a NRC 2010 CDBI: NCV.
Preparer:
Anup Behera (KCI)
!13 Print Name S'
Name Data Method of Review: 21 Detailed Review Alternate Calcula 'on ttach
)
Testing Reviewer:
Tom VanWyk (KCI)
/13 Pint Name Sign Name Date Review Notes: 2' independent review Z Peer review Q Reviewed per Attachment 4 of CC-AA-309-1001.
(Far Extemat Mayses linty)
External Approver:
24 Badar Hussain (KCI)
!1 3 fi Print Name SF.
Date Exelon Reviewer: 2$
. L.
e, 6 {t'irtaa Print S`
N ate Independent 3`d Party Review Reqd?
Yes No
)
I Fl-t Exelon Approver:
27 t?ue' -
`° r
Print I
S+
Nan.
Data CC-AA-309-1001 Revision 8 Paqe 1
CC-AA-103-1003 Revision 9 ATTACHMENT 2 Owner's Acceptance Review Checklist for External Design Analyses DESIGN ANALYSIS NO. L-002588 REV. 001 E PAGE: la No Question Instructions and Guidance Yes No / N/A 1
Do assumptions have All Assumptions should be stated in clear terms with enough C1 El sufficient documented justification to confirm that the assumption is conservative.
rationale?
For example, 1) the exact value of a particular parameter may not be known or that parameter may be known to vary over the range of conditions covered by the Calculation. It is appropriate to represent or bound the parameter with an assumed value. 2) The predicted performance of a specific piece of equipment in lieu of actual test data.
It is appropriate to use the documented opinion/position of a recognized expert on that equipment to represent predicted equipment performance.
Consideration should also be given as to any qualification testing that may be needed to validate the Assumptions. Ask yourself, would you provide more justification if you were performing this analysis? If yes, the rationale is likely incomplete.
2 Are assumptions Ensure the documentation for source and rationale for the assumption compatible with the way supports the way the plant is currently or will be operated post change the plant is operated and and they are not in conflict with any design parameters. If the Analysis with the licensing basis?
purpose is to establish a new licensing basis, this question can be answered yes, if the assum ption supports p
that new basis.
3 Do all unverified If there are unverified assumptions without a tracking mechanism assumptions have a indicated, then create the tracking item either through an ATI or a work tracking and closure order attached to the implementing WO. Due dates for these actions mechanism in place?
need to support verification prior to the analysis becoming operational or the resultant plant chane being op authorized.
4 Do the design inputs The origin of the Input, or the source should be identified and be readily 11 El have sufficient rationale?
retrievable within Exelon's documentation system. If not, then the source should be attached to the analysis. Ask yourself, would you provide more justification if you were performing this analysis? If yes, the rationale is likely incomplete.
5 Are design inputs correct The expectation is that an Exelon Engineer should be able to clearly and reasonable with understand which input parameters are critical to the outcome of the critical parameters analysis. That is, what is the impact of a change in the parameter to the identified, if appropriate?
results of the analysis? If the impact is large, then that parameter is critical.
6 Are design inputs Ensure the documentation for source and rationale for the inputs compatible with the way supports the way the plant is currently or will be operated post change the plant is operated and and they are not in conflict with any design parameters.
with the licensing basis?
7 Are Engineering See Section 2.13 in CC-AA-309 for the attributes that are sufficient to Judgments clearly justify Engineering Judgment. Ask yourself, would you provide more documented and justification if you were performing this analysis? If yes, the rationale is justified?
like!
incom lete.
S Are Engineering Ensure the justification for the engineering judgment supports Judgments compatible the way the plant is currently or will be operated post change with the way the plant and is not in conflict with any design parameters. If the Analysis is operated and with purpose is to establish a new licensing basis, then this question the licensing basis?
can be answered yes, if the judgment supports that new basis.
9 Do the results and Why was the analysis being performed? Does the stated conclusions satisfy the purpose match the expectation from Exelon on the proposed purpose and objective application of the results? If yes, then the analysis meets the of the Design needs of the contract.
Analysis?
CC-AA-103-1003 Revision 9 ATTACHMENT 2 Owner's Acceptance Review Checklist for External Design Analyses DESIGN ANALYSIS NO. L-002588 REV.
001 E PAGE:
1 b No Question Instructions and Guidance Yes I No f NIA 10 Are the results and Make sure that the results support the UFSAR defined system conclusions compatible with the wa lant the design and operating conditions, or they support a proposed ch t
th diti If h y
p ange o ose con ons.
t e analysis supports a change, is operated and with are all of the other changing documents included on the cover the licensing basis?
sheet as impacted documents?
11 Have any limitations on Does the analysis support a temporary condition or procedure the use of the results change? Make sure that any other documents needing to be been identified and updated are included and clearly delineated in the design transmitted to the analysis. Make sure that the cover sheet includes the other appropriate documents where the results of this analysis provide the input.
organizations?
1,t I Ya
_^;ee EC 12 Have margin impacts Make sure that the impacts to margin are clearly shown within been identified and the body of the analysis. If the analysis results in reduced documented margins ensure that this has been appropriately dispositioned in appropriately for any the EC being used to issue the analysis.
negative impacts (Reference ER-AA-2007).
13 Does the Design Are there sufficient documents included to support the sources
- 3 El El Analysis include the of input, and other reference material that Is not readily applicable design basis retrievable in Exelon controlled Documents?
documentation?
14 Have all affected Determine if sufficient searches have been performed to identify design analyses been any related analyses that need to be revised along with the base documented on the analysis. It may be necessary to perform some basic searches Affected Documents to validate this.
List (AOL) for the associated Configuration Change?
15 Do the sources of Compare any referenced codes and standards to the current inputs and analysis design basis and ensure that any differences are reconciled. If methodology used the input sources or analysis methodology are based on an out-meet committed of-date methodology or code, additional reconciliation may be technical and required if the site has since committed to a more recent code regulatory requirements?
16 Have vendor Based on the risk assessment performed during the pre-job brief
supporting technical for the analysis (per HU-AA-1212), ensure that sufficient reviews documents and of any supporting documents not provided with the final analysis references (including are performed.
GE DRFs) been reviewed when necessary?
17 Do operational limits I Ensure the Tech Specs, Operating Procedures, etc. contain support-assumptions operational limits that support the analysis assumptions and and inputs?
inputs.
Create an SFMS entry as required by CC-AA-4008. SFMS Number:
/ 3.5
DESIGN ANALYSIS TABLE OF CONTENTS ANALYSIS NO. L-002588 REV. NO. 001E PAGE NO.2 SECTION:
PAGE NO.
SUB-PAGE NO.
I DESIGN ANALYSIS COVER SHEET OWNER'S ACCEPTANCE REVIEW CHECKLIST FOR EXTERNAL DESIGN ANALYSES TABLE OF CONTENTS PURPOSE/SCOPE DESIGN INPUTS REFERENCES CALCULATION RESULTS/CONCLUSION ATTACHMENTS Attachment A: System Protection Department - Relay Setting Order (Nuclear) for Division 1, 2 and 3 Loss of Voltage relay I(2)AP037A & B, 1(2)AP040A & B and 1(2)AP041A & B Attachment B: Acceptance Regions for Calibration Checkpoints for ITE-27 Relays la, lb 2
3 3
4 5
7 8
Al-A9 131-132
Analysis No: L-002588 Revision No: 001E Page No:
PURPOSE/SCOPE The purpose of this calculation is to evaluate relay setpoints so that all the safety related motors normally running from power supplied from the SAT would not trip in less than 5.7 minutes under a degraded voltage condition of the 4kV ESF bus. The degraded voltage relay timer is set to trip in 300 29.9 seconds time delay following the 10.9 seconds time delay of the degraded voltage relay before transfer of all the loads to the diesel generators. The maximum time delay to trip the offsite source due to degraded bus voltage is therefore 340.8 seconds (5.7 minutes) [Reference Technical Specification Table 3.3.8.1.1 ]. This evaluation of the relay setpoints is done to address a NRC 2010 CDBI NCV, Specifically, the NRC concern was that adequate basis was not documented to demonstrate the ability of the permanently connected safety-related loads to continue to operate during the 5.7 minutes relay time delay without sustaining damage or tripping during a worst case, non-accident degraded voltage condition (when voltage was still above the setpoint of the loss of voltage relay setpoint).
This calculation is applicable for the following undervoltage relays that perform the Loss of Voltage identification function and initiate load shedding at Emergency Safe Shutdown (ESS) buses 141Y, 142Y, 241Y, 242Y, 143, and 243:
Relay Bus Relay Type 1(2)427AP037A & B 141Y(24IY)
Inverse Time UV Relay 1(2)427AP040A & B 142Y(242Y)
Inverse Time UV Relay 1(2)427AP041A & B 143(243)
Undervoltage Relay DESIGN INPUTS Revise the first two rows of the table in Section 4.4 Calibration Procedure Data for Divisions I & 2 as follows:
Per the most recent Relay Setting Order [Ref. 5.8.1] (included as Attachment A to this minor revision), the present settings for the Division I & 2 Loss of Voltage relays are as follows. The ratio for the Potential Transformer (PT) supplying these relays is 35:1.
Relay Tap and Time Dial Relay Setting 80V, TD = 3 86.49 Dropout (3027V on primary)
Revise Section 4.5 Analytical Limit (AL) as follows:
Per Reference 5.5.2, the Division 1 and 2 Loss of Voltage relay Analytical Limit (AL) is 2363 Volts :s AL _<
3150 Volts at the relay bus and the Division 3 Loss of Voltage relay Analytical Limit (AL) is 2583 Volts S AL _< 3150 Volts at the relay bus. These voltages are transformed to a control voltage using a PT with a turns ratio of 35:1 (Ref. 5.8.1).
Control Voltage = Bus Voltage / 35 Thus, the transformed control voltage AL bands are as shown below:
Control Voltage AL Division 67.52V <_AL<_90.00 V 1 &2 73.80V<_AL<_90.00V 3
The above upper limit of AL for Division 1, 2 and 3 bus voltage was chosen to ensure that the minimum expected voltage during LOCA Block Start of all safety related loads is above this
Analysis No: L-002588 Revision No: 001 E Page No:
value. This would ensure that the Loss of Voltage relays do not trip the SAT feeder breaker when the SAT voltage is adequate to supply the power to the safety related loads. Reference 5.6.6 analyzed the 4160 SWGR degraded voltage relays [l(2)427-AP270A(B), 1(2)427-AP271A(B) and l(2)427-AP272A(B)i during a LOCA Block Start with a minimum switchyard voltage, The minimum voltage at 4160 SWGR busses for Division 1, 2 and 3 is more than 3190 Volts (Reference 5.6.6, Attachments F and AL), when the all the safety related loads were started at the same time (i.e., T = 0.0). This voltage improves to a higher value in 2.5 seconds as the motors accelerate. Therefore, the upper limit of AL is less than 3190 and therefore can be chosen to be 3185 Volts. This is equivalent to 91 Volts on the PT secondary side.
There is no technical basis for the existing lower limit of the AL for Division 1, 2 and 3 bus voltages. The lower limit of AL for Division 1, 2 and 3 bus voltages should be such that none of the safety related normally running motors stalls at this voltage. The minimum bus voltage that ensures none of the safety related motors running in Division I and 2 will stall is 65.5% of 4160 Volts or 2725 Volts (Reference 5.6.6, Attachment AN) and for Division 3 will stall is 65% of 4160 Volts or 2704 Volts (Reference 5.6.6, Attachment AN). Therefore, the lower limit of AL for Division I and 2 is chosen as 2812 Volts to provide margin, This is equivalent to 80.34 Volts on the PT secondary side. Similarly, the lower limit of AL for Division 3 is chosen as 2712 Volts to provide margin. This is equivalent to 77.48 Volts on the PT secondary side. Note that tripping the SAT at higher bus voltage is desirable since the motors will be protected against overloading as would be in a lower terminal voltage condition.
Therefore, the revised transformed control voltage AL bands are as follows:
Control Voltage AL Division 80.34 Volts S AL 5 91,00 Volts 1 & 2 77.48 Volts 5 AL :5 91.00 Volts 3
Replace Section 4.8 with the following:
Calibration checkpoints will be at or near the high and low technical specification range when setting tolerance is included. The setting tolerance for voltage is +/- 5.0 % (Design Input 4.2). The low checkpoint is approximately 75 Volts computed from the value in section 6.4 of 71.314 Volts adjusted up by 5% tolerance. The high checkpoint is approximately 83 volts computed from the value in Section 6.4 of 87.49 V when adjusted down by 5% tolerance. These two voltages, 75 Volts and 83 Volts, will be used for calibration checkpoints. These adjusted calibration points will provide some additional conservatism in that the inverse voltage curve that will fit them will meet tighter constraints.
REFERENCES Add the following reference:
5.6.6 L-003364, Auxiliary Power Analysis, Revision 002.
Update the following references:
5.6.5 L-002589, Instrument Setpoint Analysis For 4.16 kV Undervoltage (Loss of Voltage) Relay -
Time Delay Function, Rev. 00 l D
Analysis No: L-002588 Revision No: 001E Pa=
No-.
wMrrw^iiw^rsirrwrn CALCULATION Replace Section 6.4 with the following:
6.4 Nominal Calculated Setpoint The values calculated for the parameters associated with the calculated setpoint are ALDIVI&2
< 91.00 Volts ALotvl&2
? 80.34 Volts
[Section 4.5]
ALDIV3 5 91.00 Volts ALDIV3
> 77.48 Volts
[Section 4.5]
ZDIVI&2 - +3.841 Volts 1
-3.51 Volts
[Section 6.3]
ZDIV3
= +4.158 Volts /
-3.968 Volts
[Section 6.3]
Per References 5.6.1 and 5.6.2, the DTI I c is calculated based on a sufficiently large historical data, and per Reference 5.1.2, additional margin may be omitted in calculating the setpoint. Thus, MAR = 0 V.
Therefore, in accordance with Section 2.8, the calculated setpoints for upper and lower limits are:
SPc(UL)
[upper limit]
SPc(UL)DIVI&2 91.00 Volts - 3.51 V - 0 Volts SPc(UL)DIVI&2 87.49 Volts SPc(UL)DIV3 91.00 Volts - 3.968 V - 0 Volts SPc(UL)o1V3
^ 87,032 Volts = 87.03 Volts SPc(LL)
[lower limit]
SPc(LL)DIVI8c2
? 80.34 Volts + 3.841 Volts + 0 Volts SPc(LL)DIVI&Z
> 84.181 Volts u 84.18 Volts SPc(LL)DIV3
? 77.48 Volts + 4. 158 Volts + 0 Volts SPc(LL) DIV3
?
81.638 Volts 81.64 Volts Division I & 2: The upper setpoint, SPc(UL)orvl&2 < 87.49 Volts, is the maximum value that the pickup voltage of the relay can be set at. This is the maximum voltage that accounts for the uncertainty of the relay voltage setting, The lower setpoint, SPc(LL)olvl&2 ? 84.181 Volts a 84,18 Volts, is representative of the voltage value that will be above the lower analytical limit In order to meet the calibration requirements at the lower end of the voltage range, (See Section 7.4, Item B), a 60% of normal bus voltage (71,314 Volts) will be used to check for compliance with the expected values near the low end of the voltage range.
Division 3: Per Section 4,4, the field calibration setpoint (SPf) for this loop is 82 Volts. The field calibration setpoint value is within the calculated setpoint limits of ? 81.64 Volts and <_ 87.03 Volts.
Although the field calibration setpoint is bounded by the calculated setpoint limits, field calibration setpoint (SPf) is recommended to be at 84 Volts.
Analysis No: L-002588 Revision No: 001E Pa=
NW.
Replace Section 6.5 with the following:
6.5 Allowable Value The values calculated for the parameters associated with the allowable value are SPc(UL)DLV &2 S 87.49 Volts SPc(LL)D1v1&22! 84.18 Volts
[Section 6.4]
ZavDIV1&2
= +2.181 Volts /
-1.85 Volts
[Section 6.3]
SPc(UL)D1v3 < 87.03 Volts SPc(LL)Dtv3>t 81.64 Volts
[Section 6.41 ZaVDIV3 = +3.798 Volts /
-3.608 Volts
[Section 6.3]
Therefore, in accordance with Section 2.9, the calculated allowable value is AV(UL)
SPc(UL) + I Zav {
AV(UL)D1v1&2 87.49 Volts + 1.85 Volts AV(UL)DIVI&2 5 89.34 Volts AV(UL)D1v3
< 87.03 Volts + 3.608 Volts AV(UL)D1V3 90.638 Volts 90.64 Volts AV(LL)
? SPc(LL) - Zav+
? 84.18 Volts - 2.181 Volts AV(LL)DWVI&2
? 81.999 Volts 82.0 Volts AV(LL)DIV3
> 81,64 Volts - 3.798 Volts AV(LL)D1v3
? 77.842 Volts z 77.84 Volts Replace Section 6.7 with the following:
6.7 Minimum / Maximum Calculated Values Deleted.
Replace Section 6.8 with the following:
6.8 Acceptance Criteria for Calibration Testing The acceptance points that should be tested are for PT Secondary voltages for Division 1 and 2 as specified in Design Input 4.8.
For the 83 Volt check point the upper time delay limit from design input 4.7 will be used, Thus for a simulated bus voltage that generates 83, within the range of the 5% setting tolerance of +/- 4.15 Volts, at the PT secondary, the time delay should be 8.3 +/- 0.83 seconds.
For the 75 Volt check point the lower time delay limit from design input 4.7 will be used. Thus for a simulated bus voltage that generates 75, within the range of the 5% setting tolerance of+ 3.75 Volts, at the PT secondary, the time delay should be 4.3 +/- 0.43 seconds.
[upper lim
[lower limit]
[Analysis No: L-002588 Revision No: 001 E Page No: 7 RESULTS/CONCLUSION Replace Section 7.0 with the following:
7
SUMMARY
AND CONCLUSIONS The results summarized below are applicable for normal and accident operating conditions.
7.1 Calculated Values Summary Calculated Setpoint:
84.18Volts <_ SPcDIVI&z S 87.49Volts 81.64Volts S SPCDIV3 S 87.03Volts Allowable Value:
82.OOVolts S AVDIVI&2 S 89,34Volts 77.84Volts S AVDlV3
<_ 90.64Volts Analytical Limit 80.34Volts S ALDIVI&z S 91.OOVolts 77.48Volts S ALDIV3
<_ 91.00Volts 7.2 Calibration Summary The calibration information used to support the results of this calculation is defined below.
Calibration Setpoint / Allowable Value:
EPN Parameter Process Units Div 1 &2 Field Calibration 75 Volts Checkpoints 83 Volts 7A & B 1 AP03 Allowable Value
? 82.00 Volts and 1 AP040A & B 5 89.34 Volts 2AP037A & B Analytical Limit
? 80.34 Volts and
< 9l.OOVolts 2AP040A & B Div 3 Field Calibration 84 Volts Setpoint A & B 041 I AP Allowable Value
> 77.84 Volts and 2AP041 A & B S 90.64 Volts Analytical Limit
? 77.48 Volts and
<_ 91.00Volts Calibration Frequency, Setting Tolerances and Expanded Tolerances (Div 1,2,3):
Surveillance Interval Setting Tolerance Expanded Tolerance Channel Calibration 24 months
+/- 2%
N/A
Analysis No: L-002588 Revision No: 001E Page No:
7.3Acceptance Criteria for Division 3 The acceptance criteria (Section 2.10) associated with the setpoints for Division 3 are met since the field calibration setpoint (SFf) is within the enveloping calculated setpoints (SPc) and therefore ensures that the analytical limits will not be exceeded.
There are no acceptance criteria for the allowable value determination.
7.4 Calibration Checkpoint Acceptance Criteria for Division 1 and 2 The verification that the ITE-27 inverse voltage curve will meet the requirements of this calculation for Division I and 2 is to test the relay to ensure that:
A.
The pickup voltage is not set higher than 87.49 Volts or lower than 84.18 volts.
B.
That, when the relay trips with a simulated bus voltage that equals 60% of the normal bus voltage that the time delay is greater than the minimum allowable value of 3.1 seconds.
C.
That when the relay trips with simulated bus voltages of 75 Volts and 83 +/- 5% Volts the time delays will be within expected zones as shown on Attachment F pages I and 2.
ATTACHMENTS Replace Attachment C with the contents of Attachment A of this minor revision.
Replace Attachment F with the contents of Attachment B of this minor revision.
Analysis No: L-002588 Revision No: (}01E Attachment A Pane No: Al of A9 System Protection Department - Relay Setting Order (Nuclear) for Division 1, 2 and 3 Loss of Voltage relay 1(2)AP037A & B, 1(2)AP040A & B and 1(2)AP041 A & B
System Protection Department - Relay Setting Order (Nuclear)
STATION:
101, LaSalle Co.
EQUIPMENT:
(
6US 141Y RELAY NO:
1427-AP037A(8)
POTENTIAL TRANSFORMER RATIO:
TARGET TAPS:
IIIWA EXISTING:
UNIT:
4.18 RELAY TYPE:
ITE-27 SAFETY-RELATED?*
Bus Loss of Voltage INSTALL:
REPLACE:
DEACTIVATE:
PICKUP (UV RESET) TAPS RANGE:
DROPOUT (UV TRIP) RANGE:
TIME DELAY RANGE:
Tap I to 8 (0.4-12 seconds)
NIEW:
PRIMARY RELAY Less than ar DROPOUT (UV TRIP):
equal to 3027.15 V V
SECONDARY RELAY DROPOUT (UV TRIP):
lass than ar equal to 88.49 V 1 v TIME IME DELAY GREATER THAN 3, 1 SEC 42 71.3 V (80% of normal)
DELAY: Calibration Checkpoints Si see,+/- 10% 0 82 V+/-5%
14.3 sec +/- 10% 4%l 75 V+1-5%
TIME DIAL/TAP:
SECONDARY RELAY DROPOUT (UV TRIP):
V 75 PRIMARY RELAY DROPOUT (UV TRIP):
2625 V
A:
B:
C.
f9 N:
Q RES:
Cubicle No.:
I APPLICATION:
`Yes AP CODE:
CHANGE:
L kid-I10V Approx. 97% Of Pickup TIME DELAY:
120-OV @ 1.5 seconds, TIME DIALI TAP:
FIELD 13 TO DETERMINE AND RECORD BELOW PICKUP TAP 70 V
(UV RESET) :
RELAY PICKUP WI
-A (UV RESET):
I RECOMMENDED TIME TAP I
T k ACTUAL TIME TAP' PICKUP VOLTS FIELD IS TO DETERMINE AND RECORD BELOW TAP (UV RESET):
RECOMMENDED VOLT TAP:
80 ACTUAL VOLT TAP:
RELAY PICKUP (UV RESET): W TOLERANCES:
Checkpoint voltages tolerances are +/-5%. The relay dropout DROPOUT UV (UV TRIP) setpotnt tolerance is also
+1-5% with the added
(
resvlction that the UV TRIP seipoint must be less than or equal TRIP)
TOLERANCE: !to5849 Volts.
TIMING TOLERANCE:
L SOURCE:
[Cato Nos, L-002888, Rev IC and L-002589, rev IIA.
+/.10%
SOURCE: ICatculation Nos. L-002588, Rev IC and L-002589, Rev 1A PICKUP (UV REST TOLERANCE IN/A I SOURCE :
`DCP No. EC 33837 ISSUE DATE:
8/23/
COMPL DATE:
RETURN DATE:
COMMENTS:
SUPERSEDES RSO DATED:
ISSUED BY:
T.J. ISAeno (y,R.
()04t-797ja.©/
COMPLETED BY.
RETURNED TO:
1/0 FOR SAFETY-RELATED RELAYS ONLY, THE FOLLOWING INFORMATION MUST BE INCLUDED:
INDICATE THE BASIS FOR THE PROTECTIVE RELAY SETTINGS CONTAINED IN THIS RELAY SETTING ORDER:
REVIEWED BY: I`j'. Chow 1 INITIAL:
DATE: 6F%237,2, CONCURRENCEWITHA/ERECOMMENOATIONS Q SETTINGS PER SYSTEM PROTECTION SETTINGS GUIDE SPD-RPS-TG3 REV #
DATED: '
---t OTHER BASIS
.EXPLAIN:
Calculation Nos. L-002588, Rev 1C and L-002589, Rev 1A and (3CP No. EC 338375.
APPROVED BY:
j4V. J. (Miller tTIAL:
DATE:
'? -o L.
Analysis No. L-002588 System Protection Department - Relay Setting Order (Nuclear STATION:
- 01, LaSalle Co.
UNIT: ( 1 KV: { 4,1g RELAYTYPE:
ITE-27 EOUIPMENT:
RELAY NO:
Sus 142Y 1427-AP04OA(B}
SAFETY-RELATED7:
=
Yes But Lose of Voltage AP CODE:
27 2
Cubicle No.:
APPLICATION:
A.
l e:
f9l G:
IR N:
RES:
Q INSTALL; CHANGEI 1I REPLACE:
DEACTIVATE:
35 POTENTIAL TRANSFORMER RATIO:
TARGET TAPS:
jN/A PICKUP (UV RESET) TAPS RANGE:
DROPOUT (UV TRIP) RANGE:
TIME DELAY RANGE:
Tap 1 60-11GV 8 (0.4-12 seconds)
TIME DELAY:
EXISTING:
12"V to 1.5 seconds PICKUP TAP (UV RESET) ;
70 V
SECONDARY RELAY DROPOUT (UV TRIP):
TIME DIPd1TAP: 3 V
75 PRIMARY RELAY DROPOUT (UV TRIP):
2625 V
V V
NEW:
PRIMARY RELAY DROPOUT (UV TRIP):
SECONDARY RELAY DROPOUT (UV TRIP):
TIME (TIME DELAY GREATER THAN 3.1 SEC 9 71.3 V (60% of normal)
DELAY: (CaGbratton Checkpoints: 8.3 sec +1-10% Q 82 V +1-6%
r4.3sec+/-10%Q75V+A5%
TIME DIAL+TAP:
FIELD 13 TO DETERMINE AND RECORD BELOW RECOMMENDED TIME TAP:
3 ACTUAL, TIME TAP:
PICKUP VOLTS FIELD IS TO DETERMINE AND RECORD BELOW TAP (UV RESEn RECOMMEN[?ED VOLT TAP 80 ACTUAL VOLT TAP:
RELAY PICKUP (UV RESET):
NIA Less than or equal to 3027.15 V Less than or equal to 88.49 V TOLERANCES!
Checkpoint voltages tolerances are +1-5%. the relay dropout DROPOUT (UV (UV TRIP) setpoint tolerance is also +/- 5% with the added
(
restriction that the UV TRIP setpoint must be lest than or equal TRIP)
TOLERANCE: Ito 89.49 Volts.
SOURCE:
Cato Nos. L-002588, Rev I C and L-002589,
!Rev tA.
DCP EC 338375 TIMING TOLERANCE:
+1-10%
SOURCE: Cakulatiot: Naa. L-002588, Rev 1C and L-402589, Rev to PICKUP (UV RESET) TOLERANCE I JA SOURCE: N/A COMMENTS: I DCP No. EC 338378 SUPERSEDES RSO DATED:
5/31/01 FOR SAFETY-RELATED RELAYS ONLY. THE FOLLOWING INFORMATION MUST BE INCLUDED:
INDICATE THE BASIS FOR THE PROTECTIVE RELAY SETTINGS CONTAINED IN THIS RELAY SETTING ORDER:
17 CONCURRENCE NRTh A/E RECOMMENDATIONS El SETTINGS PER SYSTEM PROTECTION SETTINGS GUIDE SPD-RPS-TG3 REV 0 0 DATED:
Q OTHER BASIS
!Calculation Nos. L-0O2588, Rev IC and L-0025 89, Rev 1A and DCP No. EC 338375.
.EXPLAIN:
I ISSUED BY:
T.J. Meno ISSUE DATE:
8/23/02 COMPLETED BY:
RETURNED TO:
L COMPL DATE:
r: f -
12^
RETURN DATE:
REVIEWED BY: IT. Chow INITIAL:
DATE:
APPROVED BY:
LN, J Muter INITIAL:
j(
DATE: 1-7-7-O7-
(KELAY ITT(KG'Ott"t-m"
} '
Ya*.
z GORE gig
,.rte r
DNr7E IMO May.
r 1
IAI o-V
'O EUONATION$ NOT COVERED ABOVE OR OEI.OV. SUCH AS UNE NO., NN W OR OLD f!
TY IN D^ ITC.
cul U4on nxlrq 1
S^^
- N6v T h i n Th u SAM r fttz 1 olruo SPd-01 -01*Oo3 i
mfachmenl B-Pg.7. Or L
Revision Ito: 0010 Attachment A Analysis No: L-002588 Page No: A5 of A9
- teat Protection Department - Relay Setting Order (Nuclear) n_RELAY TYPE
01, LaS '4 County
^{
}
EQUIPMENT:
Rue I33 Less Of Voltage Timar__^ _..
_ e KY:
'4.18 CB Nt 102 f
AP CODE:
2 RELAY P40:
1427*APQ41A(B)X SAFETY.RELATEO?:
`res(
REASON FOR R50; INSTALL:
CHANGE:
REIfLACE:
f_i DEACTIVATE:
]
EXISTING:
TIME DELAY RANGE:
05 33 B sec TIME DIAL:
TIME DELAY:
2,0 sec, TO BE:
TIME DELAY RANGE:
0.05 *3.0 se J!
TIME DIAL
'-^
TIME DELAY:
20 SEC RELAY TIMING TOLERANCE:
see comments TARGET TAPS:
INIA COMMENTS:
Revised to document settings basis and to show toierancs of
(+1-0.0B sec.)
per Cate, No. L-002589, Rev. 1, SAMI1 A Relay is timer for NGV Relay SUPERSEDES RSO DATED:
^- t PREPARED BY; RETURN TO:
'L, R, Cabrera COMPLETED BY; ISSUE DATE:
3124101 COMPL DATE:O RETURN DATE:
Y!rdr1QA M2 7L AIfA fM 4,4,= 4^/_4__^_
FOR SAFETY-RELATED RELAYS ONLY, THE FOLLOWING INFORMATION MUST BE INCLUDED:rS tNOICATE THE BASIS FOR THE PROTECTIVE RELAY SETTINGS CONTAINED IN THIS RELAY SETTING ORDER:
_. CONCURRENCE WITH A/E RECOMMENDATION PER SPO RIPS TG3 SETTING GUIDE REV At; DATED:
v OTHER BASIS EXPLAIN :
CsIC. No. L-QQ2588. Rev. i REVIEWED BY:
Mann INITIAL:
DATE:
APPROVED BY; W,
Miller SHfTtA1:
DATE:
ym I.-d WWI ^a rr^Wa s ^ra`an to speGyrq rant' rxtzanp wom tJpa eo^nr
^--__^m DIT No, SPIMI.01-+303 Attachment Q, Pg. _!Cof By:
Attachment A alysis No: L-002588 Revision No; 001E Page No: A6 of A9 System Protection Department - Relay Setting Order (Nuclear)
STATION:
,01, LaSalle CO.
f UNIT:
F 2-1 KV:
4.16 RELAY TYPE:
IT--
E-27 EQUIPMENT:
t BUS 241Y..
]
Cublcle No.:
(1 SAFETY-RELATED7:
RELAY NO:
2427-AP037A{8)-7 APPLICATION:
Bus Loss of Voltage
=Yes 27 AP CODE:
At l
B:
r C:
LR N:
Q RES.Q INSTALL.:
REPLACE:
CHANGE:
DEACTIVATE:
- 1 POTENTIAL TRANSFORMER RATIO:
TARGET TAPS:
iN/A PICKUP (W RESET) TAPS RANGE:
DROPOUT (UV TRIP) RANGE:
TIME DELAY RANGE:
Tap 1 to 6 (0.4-12 seco 80-110V EXISTING:
PRIMARY RELAY DROPOUT (UV TRIP):
SECONDARY RELAY DROPOUT (W TRIP):
TIME OIAL/TAP:
75 V
2825 TIME DELAY.
PICKUP TAP (UV RESET):
120-OV Q 1.5 secondsl 7a V
RELAY PICKUP N/A (UV RESET):
I PRIMARY RELAY DROPOUT (UV TRIP):
SECONDARY RELAY DROPOUT (W TRIP):
i IME DELAY GREATER THAN 3.1 SEC M 71.3 V (60% at normal)
Calibratlon Checkpoints: 8,3 sea +1-10% a 82 V +/-5%
4.3 sec +/-10% fg 75 V +/. 5%
TIME DIAL/TAP:
FIELD 13 TO DETERMINE AND RECORD BELOW RECOMMENDED TIME TAP, ACTUAL TIME TAP:
PICKUP VOLTS TOLERANCES:
ChedlpoIntvollagee tolerances are +/ 5%. The relay dropout POUT (UV
!(UV TRIP) setpoirrt tolerance Is also +1-5% with the added DROOTOLERANCE: Irestrictlon that the UV TRIP satpokrt must he rase than or equal TRIP) 3a 86.49 Volts.
TIME DELAY:
TAP (W RESET) :
FIELD IS TO DETERMINE AND RECORD BELOW RECOMMENDED VOLT TAP: L J 80 ACTUAL. VOLT TAP:
RELAY PICKUP (W RESET): IN/A SOURCE:
ICalc Nos. L-002588, Rev 1C and L-002589, Rev 1A.
- NEW, Less than or equal to 3027.15 V Less than or equal to 88,49 V V
TIMING TOLERANCE:
PICKUP (UV RESET) TOLERANCE 'N/A SOURCE: (Calculation Nos. L-002588, Rev IC and L-002589, Rev to SOURCE : s /A
-771 T-1-074 CP No. EC COMMENTS: (
SUPERSEDES RSO DATED:
ISSUED BY:
ISSUE DATE:
1 9 s
^a COMPLETED BY:
RETURNED TO:
w,R it C6 14 7 71 RETURN DATE:
COMPL DATE:
4 5131/01 T.J. Marto 8/23/02 FOR SAFETY-RELATED RELAYS ONLY, THE FOLLOWING INFORMATION MUST BE INCLUDED:
INDICATE THE BASIS FOR THE PROTECTIVE RELAY SETTINGS CONTAINED IN THIS RELAY SETTING ORDER:
Q CONCURRENCE WITH Alin RECOMMENDATIONS Q SETTINGS PER SYSTEM PROTECTION SETTINGS GUIDE SPD-RPS-TG3 C
OTHER BASIS
REVIEWED BY:
fT. Chow t INITIAL:
DATE:
dz^
APPROVED BY: i/1/. J. Miller I iNITlAL DATE: ^* Zj°rJL REV # E DATED:
Attachment A Analysis No: L-002588 Revision No: 041E Pa. se No: A7 of A9 Systel STATION:
Protection Department - Relay Setting Order (Nuclear)
UNIT:
KV:
48 RELAY TYPE:
Y ITE-27 LaSalle Co.
EQUIPMENT:
Bus 242Y RELAY NO:
2427-APO4OA(81 A:
UR B:
Cubicle No.:
1 SAFETY-RELATED?
APPLICAT Nt Bus Loss of Voltage AP CODE:
L27 N:
17 R e.34 El INSTALL CHANGE:
Q REPLACE:
DEACTIVATE:
Q C:
POTENTIAL TRANSFORMER RATIO:
TARGET TAPS:
PICKUP (IN RESET) TAPS RANGE, DROPOUT (UV TRIP) RANGE.-
TIME DELAY RANGE:
Go-11oV Approx. 97% Of Pickup 12 seconds) 35 Tap Ito 6 (0.
V 75 EXISTING:
PRIMARY RELAY 2^5 DROPOUT (UV TRIP):
SECONDARY RELAY DROPOUT (UV TRIP):
TIME DIAUTAP.
N PRIMARY RELAY DROPOUT (UV TRIP):
SECONDARY RELAY DROPOUT (UV TRIP):
TIME JTIME DELAY GREATER THAN 3.1 SEC (9 71.3 V (80% of no DELAY: CaWxad n CheekpohNs; 9.3 sec +/. 10% a 82 V +1.5%
141 sec +/. i0% Q 75 V +1-5%
Less than or equal to 3027.1 5V Less than or equal is 88.49 V TIME DELAY:
120-W a 1.5 second TOME DIAUTAP:
FIELD IS TO DETERMINE AND RECORD BELOW V
70 PICKUP TAP (UV RESET) :
RELAY PICKUP N/
(UV RESET):
RECOMMENDED TIME TAP: 1 3 1 ACTUAL TIME TAP:
PICKUP VOLTS TAP (t7V RESET)
FIELD IS TO DETERMINE AND RECORD BELOW RECOMMENDED VOLT TAP; 80 ACTUAL VOLT TAP:
RELAY PICKUP (LIV RESET);
$a TOLERANCES:
Checkpoint vokages toterahces ant +1-5%, The relay dropout DROPOUT (UV (UV TRIP) setpoint talerance is also +A 5% with the added restdctlon that the UV TRIP setpoint must be less than or equal TRIP)
TOLERANCE: 4. 86,49 Volts.
SOURCE; Cale Nos. L-002588, Rev IC and L-002589, Rev IA.
DCP No. EC 338414 TIMING TOLERANCE:
+1-1-0%
PICKUP (tN RESET) TOLERANCE >N No. EC 338414 SOURCE:
[Cak:ulation Nos. L-002588, Rev IC and L-002589, Rev to OIJRCE :
NIA COMMENTS:
SUPERSEDES RSO DATED:
ISSUED BY:
T.J. Mena ISSUE DATE:
COMPLETED BY:
M 4 Z CoMet. DATE:
RETURNED TO:
R. 3rhvea RETURN DATE:
0 3 t
^ I a
/31/01 FOR SAFETY-RELATED RELAYS ONLY, THE FOLLOW NG INFORMATION MUST BE INCLUDED:
NDICATE THE BASIS FOR THE PROTECTIVE RELAY SETTINGS CONTAINED IN THIS RELAY SETTING ORDER:
0 CONCURRENCE V`ATH A/E RECOMMENDATIONS Q SETTINGS PER SYSTEM PROTECTION SETTINGS GUIDE SPO-RPS-TG3 REV t DATED:
R OThER BASIS
`Calculation Nos. L-002588, Rev IC and L-002589, Rev 1A and OCP No. EC 338414
.EXPLAIN:
REVIEWED BY' T Chow.
INIT'IAAL:
CJ_.
DATE:
APPROVED BY:
W. J. Miller INITIAL:
U DATE: p_ 2,7-az
nalysis No:
02588 Revision No: 001E Attachment A Page No: A8 of A9 RELAY SETTING ORDER C.r.CO. 14-4404 1a!
PROM OMIT. ENO.
LA ^M1LLE- ^,0
'^ri tT. pilkM.
STATfpN 0
V X. POVA KV
/
WAY reap Q
IL^ 0 fAuN uL C7 cm m 13 2c3.
Cv 9. 102 UNfl^^tvotT^t a' 1016 Aq
^ N TGIF Z y.
0 Et.
7QIP,c 7uar.
Qa.. y
-r--.^ Div. nts.
0 OR
)55U4 Dart/ -^-7$ tyVEM itui t1
'aC314Ma 71QNS NOT COVERrO ACaVt OR A LOW, SUCH A S LINT NO., Nrr OR OL4 StTTINO, [
Lrrc TC.
D IT ia..SPt?-0j.9{-403 i
itt:^ehmcntg, P. L n L
Attachment A Analysis No: L-002588 Revision No: 001E Page No: A9 of A9 tern Protection Department - Relay Setting Order (Nuclear) 2 EQUIPMENT:
Bus 243 Less Of Vo329e T'wner E:
62 RELAY NO, 242?-APGItA
- 01. LaSalle County RELAY TYPE.,
KV:
4t8 Ca P.
?G2 SAFETY*RELATED?:
Yes; SAMI IA...
REASON FOR RIO:
INSTALL:
CHANGE:
REPLACE:
DEACTIVATE:
r EXISTING:
- 3. 0 sst:^I TIME DELAY RANGE:
05 TIME DIAL:
TIME DELAY:
2.0 sea TO BE:
TIME DELAY RANGE:,0`O5 -3, 0
ec.
TIME DIAL:
TIME DELAY: 12.0 SEC 1
RELAY TIMING TOLERANCE:
sae Comments TARGET TAPS:
N/A COMMENTS:
Revised to document settings basis and to show toteranea of +/. 3% {.0.06 sac.)
per Cab, No. L-00258E, Rev, 1. SAMI 1A Relay is tarter for NGV Relay.
SUPERSEDES RSO DATED:
N/A^
PREPARED BY!
- 1. R,'Cib4ia COMPLETED BY:
ISSUE DATE:
3129/01 COMPL DATE:
RETURN TO:
^retr^3.D ^ d RETURN DATE:
FOR SAFETY-RELATED RELAYS ONLY, THE FOLLOWING INFORMATION MUST BE INCLUDED:
---1S
!NOICATE THE BASIS FOR THE PROTECTIVE RELAY SETTINGS CONTAINED IN THIS RELAY SETTING ORDER:
CONCURRENCE WITH ACE RECCMMENOATION PER SPO RPS TG3 SETTING GUIDE REV A:
DATED:
OTHER BASIS EXPLAIN :
Calf. No. 1-002589. 90v. -l REVIEWED BY:
T.
INITIAL:
J^
DATE:
r+
a^..._
APPROVED BY:
W J. Hitter _
INITIAL:
c.
Fmm n.,ae YSOt m t¢a tr.jersrxt frw sC^^vd`9 "^Y ^fl c,rt "q t.gw vps cm^
U ST No. SPD-014)t-003 Attad mere 11 Pg..
-r-(A Br:
FLAT NIOO LCUION 4.75 REVISION NO. 001E Attachment B PAGE NO. BI of B2 I
Acceptance Regions for Calibration Checkpoints for ITE-27 Relays Low Calibration Check Point 74 75 PT Secondary Voltage 3.75 3.75 4.5 71 72 73 76 77 78 79
I CALCULATION NO. L-002588 REVISION NO. OO1E Attachment B PAGE NO.B2of132 High Calibration Check Point 111111 lilt 11111 11 9.50 9.00
- 8. 50 f
7.50 8.00
--r^-- Boundary
!a Hi Cal Point 7.00 78 79 80 81 82 83 84 85 86 87 PT Secondary Voltage