- Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance
- Meeting, Meeting
|
MONTHYEARGNRO-2009/00022, 2009-03 - NRC Written Examination Grade Report in Accordance with NUREG 1021, Revision 92009-03-0909 March 2009 2009-03 - NRC Written Examination Grade Report in Accordance with NUREG 1021, Revision 9 Project stage: Request ML0931404632009-11-0303 November 2009 License Amendment Request Regarding Power Range Neutron Monitoring System Upgrade Project stage: Request ML0934100662009-12-10010 December 2009 Acceptance Review of License Amendment Request for Power Range Neutron Monitoring System - Includes Revised Schedule for Completion Based on Late Submittal Project stage: Acceptance Review ML0931707702009-12-10010 December 2009 Request for Withholding Information from Public Disclosure - 10/1/2009 Affidavit Executed by E. Schrull, GE-Hitachi Nuclear Energy Americas LLC Project stage: Withholding Request Acceptance ML1000703852010-01-15015 January 2010 Request for Additional Information, License Amendment Request for Power Range Neutron Monitoring System Project stage: RAI ML1004308252010-02-0808 February 2010 Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI ML1010902452010-04-22022 April 2010 Request for Additional Information Power Range Neutron Monitoring System Project stage: RAI ML1011901252010-05-0404 May 2010 Request for Additional Information, Round 3, License Amendment Request for Power Range Neutron Monitoring System Project stage: RAI ML1013805412010-05-17017 May 2010 Entergy Operations, Inc. - E-mail Attaching EOI and GE-Hitachi Nuclear Energy Presentation Slides and Affidavit Related to Meeting on May 25, 2010 Regarding Grand Gulf Nuclear Station, Unit 1 Project stage: Meeting ML1013805152010-05-17017 May 2010 GE-Hitachi Nuclear Energy Americas LLC Affidavit of Edward Schrull Request to Withhold from Public Disclosure, Enclosure 1 to GEH Letter GG-PRNM-168777-EC065, Grand Gulf Prnm Upgrade Project - Presentation for May 25, 2010, NRC Meeting Project stage: Meeting ML1014100942010-05-18018 May 2010 Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI ML1013805592010-05-24024 May 2010 Request for Withholding Information from Public Disclosure Project stage: Withholding Request Acceptance ML1013804212010-05-25025 May 2010 Entergy Operations, Inc. and GE-Hitachi Nuclear Energy Slide Presentation for May 25, 2010 - NRC RAIs Regarding GGNS Prnm System LAR (Non-Proprietary) Project stage: Other ML1014703852010-05-25025 May 2010 Licensee Slides from 5/25/10 Meeting to Discuss Response to Requests for Additional Information on License Amendment Request for Digital Power Range Neutron Monitoring System (Nonproprietary Version) Project stage: Response to RAI ML1014704032010-05-25025 May 2010 Affidavit for 5/25/10 NRC Meeting to Discuss Response to Requests for Additional Information on License Amendment Request for Digital Power Range Neutron Monitoring System Project stage: Response to RAI GNRO-2010/00040, Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2010-06-0303 June 2010 Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI ML1015202692010-06-0909 June 2010 5/25/2010 Summary of Meeting with Entergy Operations, Inc., to Discuss the Licensees Response to NRC Staffs Request for Additional Information Dated 5/4/2010 Installation of a Digital Power Range Neutron Monitoring System Project stage: RAI ML1018001492010-06-18018 June 2010 Schedule for Responding to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Request ML1017904372010-06-30030 June 2010 0000-0102-0888-RI, Plant-Specific Responses Required by Numac Prnm Retrofit Plus Option III Stability Trip Function Topical Report, (NEDC-3241OP-A) Project stage: Other ML1016703442010-07-0202 July 2010 Request for Withholding Information from Public Disclosure - GE-Hitachi Nuclear Energy Americas LLC Affidavit Dated 6/2/2010 Project stage: Withholding Request Acceptance ML1021500292010-07-29029 July 2010 Responses to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI ML1021404062010-08-10010 August 2010 Request for Withholding Information from Public Disclosure, E. Schrull, GE-Hitachi Nuclear Energy Americas LLC Affidavit Dated 7/23/2010 Project stage: Withholding Request Acceptance GNRO-2010/00064, Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2010-09-29029 September 2010 Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI ML1027307312010-10-14014 October 2010 Request for Withholding Information from Public Disclosure, 9/28/2010 Affidavit Executed by J. Harrison, GE-Hitachi Nuclear Energy Americas LLC Project stage: Withholding Request Acceptance GNRO-2010/00075, Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2010-12-13013 December 2010 Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI GNRO-2010/00070, Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2010-12-14014 December 2010 Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI ML1111704242011-04-27027 April 2011 E-mail, Request for Additional Information, Round 4, License Amendment Request for Power Range Neutron Monitoring System Project stage: RAI ML1111704322011-04-27027 April 2011 Request for Additional Information, Round 4, License Amendment Request for Power Range Neutron Monitoring System Project stage: RAI GNRO-2011/00032, Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2011-05-0303 May 2011 Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI ML1113204932011-05-12012 May 2011 E-mail, Request for Additional Information, Round 5, License Amendment Request for Power Range Neutron Monitoring System Project stage: RAI GNRO-2011/00038, Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2011-05-16016 May 2011 Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI GNRO-2011/00039, Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2011-05-26026 May 2011 Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI GNRO-2011/00042, Responses to NRC Requests for Additional Information Re License Amendment Request for Power Range Neutron Monitoring System2011-05-31031 May 2011 Responses to NRC Requests for Additional Information Re License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI ML1113905962011-06-0202 June 2011 Request for Withholding Information from Public Disclosure, 4/28/2011 Affidavit Executed by E. Schrull, GE-Hitachi Nuclear Energy Americas LLC, Attachment 1 to GNRO-2011/00032 Project stage: Withholding Request Acceptance ML1113906562011-06-0202 June 2011 Request for Withholding Information from Public Disclosure, 5/11/2011 Affidavit Executed by J. Harrison, GE-Hitachi Nuclear Energy Americas LLC, Attachment 1 to GNRO-2011/00038 Project stage: Withholding Request Acceptance GNRO-2011/00044, Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2011-06-13013 June 2011 Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI ML1117402132011-06-23023 June 2011 Email, Request for Additional Information, Round 6, License Amendment Request for Power Range Neutron Monitoring System Project stage: RAI GNRO-2011/00045, Supplemental Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2011-06-28028 June 2011 Supplemental Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Supplement GNRO-2011/00057, Response to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2011-07-22022 July 2011 Response to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI GNRO-2011/00066, Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2011-09-28028 September 2011 Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI GNRO-2011/00089, Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2011-10-18018 October 2011 Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI GNRO-2011/00090, Supplemental Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System (TAC No. ME2531) - Software Evaluation Report2011-10-26026 October 2011 Supplemental Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System (TAC No. ME2531) - Software Evaluation Report Project stage: Supplement GNRO-2011/00091, Supplemental Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System (TAC No. ME2531) – V&V Summary Test Report2011-11-0808 November 2011 Supplemental Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System (TAC No. ME2531) – V&V Summary Test Report Project stage: Supplement GNRO-2011/00110, Supplemental Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System (TAC No. ME2531) – V&V Summary Test Report2011-12-0101 December 2011 Supplemental Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System (TAC No. ME2531) – V&V Summary Test Report Project stage: Supplement ML1204406022012-02-27027 February 2012 Request for Withholding Information from Public Disclosure, 5/19/2011 Affidavit Executed by J. Harrison, GE-Hitachi Nuclear Energy Americas LLC, Attachment 1 to GNRO-2011/00039 Project stage: Withholding Request Acceptance ML1204406602012-02-27027 February 2012 Request for Withholding Information from Public Disclosure, 11/29/2011 Affidavit Executed by J. Harrison, GE-Hitachi Nuclear Energy Americas LLC, Attachment 1 to GNRO-2011/00110 Project stage: Withholding Request Acceptance ML1204406532012-02-27027 February 2012 Request for Withholding Information from Public Disclosure, 11/3/2011 Affidavit Executed by E. Schrull, GE-Hitachi Nuclear Energy Americas LLC, Attachment 1 to GNRO-2011/00091 Project stage: Withholding Request Acceptance ML1204406462012-02-27027 February 2012 Request for Withholding Information from Public Disclosure, 10/20/2011 Affidavit Executed by E. Schrull, GE-Hitachi Nuclear Energy Americas LLC, Attachment 1 to GNRO-2011/00090 Project stage: Withholding Request Acceptance ML1204406382012-02-27027 February 2012 Request for Withholding Information from Public Disclosure, 9/22/2011 Affidavit Executed by J. Harrison, GE-Hitachi Nuclear Energy Americas LLC, Attachment 1 to GNRO-2011/00066 Project stage: Withholding Request Acceptance ML1204406272012-02-27027 February 2012 Request for Withholding Information from Public Disclosure, 7/21/2011 Affidavit Executed by E. Schrull, GE-Hitachi Nuclear Energy Americas LLC, Attachment 1 to GNRO-2011/00057 Project stage: Withholding Request Acceptance 2010-07-29
[Table View] |
Text
When Attachment 1 is removed from this letter, the entire document is NON-PROPRIETARY.
contains PROPRIETARY information.
GNRO-2013/00031 May 22, 2013 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555
SUBJECT:
Corrected Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System (TAC No. ME2531)
Grand Gulf Nuclear Station, Unit 1 Docket No. 50-416 License No. NPF-29
REFERENCE:
Entergy Operations, Inc. letter to the NRC (GNRO-2011/00039),
Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System (TAC No. ME2531), May 26, 2011
Dear Sir or Madam:
In the referenced letter, Entergy Operations, Inc. (Entergy) submitted to the NRC responses to Requests for Additional Information (RAIs) pertaining to a license amendment request (LAR), which proposed to revise the Grand Gulf Nuclear Station (GGNS) Technical Specifications (TS) to reflect the installation of the digital General Electric-Hitachi (GEH)
Nuclear Measurement Analysis and Control (NUMAC) Power Range Neutron Monitoring System (PRNMS). Included in this submittal was a response to RAI 18, which asked for a description of testing performed to ensure PRNMS safety functions met the requirements of NRC Staff Positions 1.19 and 1.20 of NRC Digital Instrumentation and Control Interim Staff Guidance DI&C-ISG-04, Highly-Integrated Control Rooms Communications Issues (HICRc).
On April 9, 2013, General Electric - Hitachi (GEH) informed Entergy via letter they had identified errors in the response to RAI 18. Entergy has reviewed the errors and has determined that the original conclusion, that Staff Positions 1.19 and 1.20 are met, is not affected and remains valid. Entergy has discussed these errors with GGNS NRC project manager.
As requested by the NRC project manager, Entergy is providing in Attachment 1 a corrected response to RAI 18. GEH considers certain information contained in the attachment to be proprietary and, therefore, requests they be withheld from public disclosure in accordance Entergy Operations, Inc.
P. O. Box 756 Port Gibson, MS 39150 Kevin J. Mulligan Site Vice President Grand Gulf Nuclear Station Tel. (601) 437-6409
ATTACHMENT 2 GRAND GULF NUCLEAR STATION GNRO-2013/00031 CORRECTED RESPONSE TO NRC RAI 18 (NON-PROPRIETARY VERSION) to GNRO-2013/00031 Page 1 of 6 NON-PROPRIETARY INFORMATION CORRECTED RESPONSE TO NRC RAI 18 NRC RAI 18 Staff Positions 1.19 and 1.20 of DI&C-ISG-04 address the potential impact of data throughput and data error rates on worst-case response time.
Describe in detail the testing performed to ensure proper performance of all safety functions to satisfy the above criteria or to determine the proposed approach is an acceptable alternative.
The following further clarifies the rationale for this RAI but does not include additional information requests. The RAI response DI&C-ISG-04 compliance matrix in Attachment 3 to GNRO-2010/00040, items 64 and 65, did not address throughput and error rates observed through design and qualification testing on system response time calculations.
Response
Supporting Information:
((
{3}))
Staff Position 1.19:
If data rates exceed the capacity of a communications link or the ability of nodes to handle traffic, the system will suffer congestion. All links and nodes should have sufficient capacity to support all functions. The applicant should identify the true data rate, including overhead, to ensure that communication bandwidth is sufficient to ensure proper performance of all safety functions. Communications throughput thresholds and safety system sensitivity to communications throughput issues should be confirmed by testing.
The following response explains how PRNMS satisfies the criteria of Staff Position 1.19. This response:
Discusses the features used to ensure sufficient link capacity, Identifies link capacity, and Details testing performed to ensure communication links have sufficient capacity to ensure proper performance of safety functions.
to GNRO-2013/00031 Page 2 of 6 NON-PROPRIETARY INFORMATION
((
{3}))
to GNRO-2013/00031 Page 3 of 6 NON-PROPRIETARY INFORMATION Table 18-1 FDDI Link Capacity Usage
((
{3}))
((
to GNRO-2013/00031 Page 4 of 6 NON-PROPRIETARY INFORMATION
{3}))
Based on the above information, the PRNMS system communication link features, capacity usage information, and testing described in the response satisfy the criteria of Staff Position 1.19.
Staff Position 1.20:
The safety system response time calculations should assume a data error rate that is greater than or equal to the design basis error rate and is supported by the error rate observed in design and qualification testing.
The following response explains how PRNMS satisfies the criteria of Staff Position 1.20.
((
{3}))
to GNRO-2013/00031 Page 5 of 6 NON-PROPRIETARY INFORMATION Table 18-2 Data Error Rate Impact to PRNM System Response Time
((
{3}))
((
{3}))
Table 18-3 Maximum Expected PRNMS Response Time
((
{3}))
((
{3}))
to GNRO-2013/00031 Page 6 of 6 NON-PROPRIETARY INFORMATION The data error rate for each safety-related communication link was established and used to determine the impact of data errors on safety system response time. The established data error rates are supported by testing during the development of PRNMS. Therefore, the criteria of Staff Position 1.20 are met.
ATTACHMENT 3 GRAND GULF NUCLEAR STATION GNRO-2013/00031 GEH AFFIDAVIT SUPPORTING PROPRIETARY INFORMATION PROVIDED IN ATTACHMENT 1