- Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance
- Meeting, Meeting
|
MONTHYEARGNRO-2009/00022, 2009-03 - NRC Written Examination Grade Report in Accordance with NUREG 1021, Revision 92009-03-0909 March 2009 2009-03 - NRC Written Examination Grade Report in Accordance with NUREG 1021, Revision 9 Project stage: Request ML0931404632009-11-0303 November 2009 License Amendment Request Regarding Power Range Neutron Monitoring System Upgrade Project stage: Request ML0934100662009-12-10010 December 2009 Acceptance Review of License Amendment Request for Power Range Neutron Monitoring System - Includes Revised Schedule for Completion Based on Late Submittal Project stage: Acceptance Review ML0931707702009-12-10010 December 2009 Request for Withholding Information from Public Disclosure - 10/1/2009 Affidavit Executed by E. Schrull, GE-Hitachi Nuclear Energy Americas LLC Project stage: Withholding Request Acceptance ML1000703852010-01-15015 January 2010 Request for Additional Information, License Amendment Request for Power Range Neutron Monitoring System Project stage: RAI ML1004308252010-02-0808 February 2010 Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI ML1010902452010-04-22022 April 2010 Request for Additional Information Power Range Neutron Monitoring System Project stage: RAI ML1011901252010-05-0404 May 2010 Request for Additional Information, Round 3, License Amendment Request for Power Range Neutron Monitoring System Project stage: RAI ML1013805412010-05-17017 May 2010 Entergy Operations, Inc. - E-mail Attaching EOI and GE-Hitachi Nuclear Energy Presentation Slides and Affidavit Related to Meeting on May 25, 2010 Regarding Grand Gulf Nuclear Station, Unit 1 Project stage: Meeting ML1013805152010-05-17017 May 2010 GE-Hitachi Nuclear Energy Americas LLC Affidavit of Edward Schrull Request to Withhold from Public Disclosure, Enclosure 1 to GEH Letter GG-PRNM-168777-EC065, Grand Gulf Prnm Upgrade Project - Presentation for May 25, 2010, NRC Meeting Project stage: Meeting ML1014100942010-05-18018 May 2010 Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI ML1013805592010-05-24024 May 2010 Request for Withholding Information from Public Disclosure Project stage: Withholding Request Acceptance ML1013804212010-05-25025 May 2010 Entergy Operations, Inc. and GE-Hitachi Nuclear Energy Slide Presentation for May 25, 2010 - NRC RAIs Regarding GGNS Prnm System LAR (Non-Proprietary) Project stage: Other ML1014703852010-05-25025 May 2010 Licensee Slides from 5/25/10 Meeting to Discuss Response to Requests for Additional Information on License Amendment Request for Digital Power Range Neutron Monitoring System (Nonproprietary Version) Project stage: Response to RAI ML1014704032010-05-25025 May 2010 Affidavit for 5/25/10 NRC Meeting to Discuss Response to Requests for Additional Information on License Amendment Request for Digital Power Range Neutron Monitoring System Project stage: Response to RAI GNRO-2010/00040, Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2010-06-0303 June 2010 Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI ML1015202692010-06-0909 June 2010 5/25/2010 Summary of Meeting with Entergy Operations, Inc., to Discuss the Licensees Response to NRC Staffs Request for Additional Information Dated 5/4/2010 Installation of a Digital Power Range Neutron Monitoring System Project stage: RAI ML1018001492010-06-18018 June 2010 Schedule for Responding to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Request ML1017904372010-06-30030 June 2010 0000-0102-0888-RI, Plant-Specific Responses Required by Numac Prnm Retrofit Plus Option III Stability Trip Function Topical Report, (NEDC-3241OP-A) Project stage: Other ML1016703442010-07-0202 July 2010 Request for Withholding Information from Public Disclosure - GE-Hitachi Nuclear Energy Americas LLC Affidavit Dated 6/2/2010 Project stage: Withholding Request Acceptance ML1021500292010-07-29029 July 2010 Responses to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI ML1021404062010-08-10010 August 2010 Request for Withholding Information from Public Disclosure, E. Schrull, GE-Hitachi Nuclear Energy Americas LLC Affidavit Dated 7/23/2010 Project stage: Withholding Request Acceptance GNRO-2010/00064, Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2010-09-29029 September 2010 Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI ML1027307312010-10-14014 October 2010 Request for Withholding Information from Public Disclosure, 9/28/2010 Affidavit Executed by J. Harrison, GE-Hitachi Nuclear Energy Americas LLC Project stage: Withholding Request Acceptance GNRO-2010/00075, Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2010-12-13013 December 2010 Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI GNRO-2010/00070, Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2010-12-14014 December 2010 Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI ML1111704242011-04-27027 April 2011 E-mail, Request for Additional Information, Round 4, License Amendment Request for Power Range Neutron Monitoring System Project stage: RAI ML1111704322011-04-27027 April 2011 Request for Additional Information, Round 4, License Amendment Request for Power Range Neutron Monitoring System Project stage: RAI GNRO-2011/00032, Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2011-05-0303 May 2011 Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI ML1113204932011-05-12012 May 2011 E-mail, Request for Additional Information, Round 5, License Amendment Request for Power Range Neutron Monitoring System Project stage: RAI GNRO-2011/00038, Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2011-05-16016 May 2011 Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI GNRO-2011/00039, Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2011-05-26026 May 2011 Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI GNRO-2011/00042, Responses to NRC Requests for Additional Information Re License Amendment Request for Power Range Neutron Monitoring System2011-05-31031 May 2011 Responses to NRC Requests for Additional Information Re License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI ML1113905962011-06-0202 June 2011 Request for Withholding Information from Public Disclosure, 4/28/2011 Affidavit Executed by E. Schrull, GE-Hitachi Nuclear Energy Americas LLC, Attachment 1 to GNRO-2011/00032 Project stage: Withholding Request Acceptance ML1113906562011-06-0202 June 2011 Request for Withholding Information from Public Disclosure, 5/11/2011 Affidavit Executed by J. Harrison, GE-Hitachi Nuclear Energy Americas LLC, Attachment 1 to GNRO-2011/00038 Project stage: Withholding Request Acceptance GNRO-2011/00044, Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2011-06-13013 June 2011 Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI ML1117402132011-06-23023 June 2011 Email, Request for Additional Information, Round 6, License Amendment Request for Power Range Neutron Monitoring System Project stage: RAI GNRO-2011/00045, Supplemental Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2011-06-28028 June 2011 Supplemental Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Supplement GNRO-2011/00057, Response to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2011-07-22022 July 2011 Response to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI GNRO-2011/00066, Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2011-09-28028 September 2011 Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI GNRO-2011/00089, Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2011-10-18018 October 2011 Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI GNRO-2011/00090, Supplemental Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System (TAC No. ME2531) - Software Evaluation Report2011-10-26026 October 2011 Supplemental Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System (TAC No. ME2531) - Software Evaluation Report Project stage: Supplement GNRO-2011/00091, Supplemental Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System (TAC No. ME2531) – V&V Summary Test Report2011-11-0808 November 2011 Supplemental Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System (TAC No. ME2531) – V&V Summary Test Report Project stage: Supplement GNRO-2011/00110, Supplemental Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System (TAC No. ME2531) – V&V Summary Test Report2011-12-0101 December 2011 Supplemental Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System (TAC No. ME2531) – V&V Summary Test Report Project stage: Supplement ML1204406022012-02-27027 February 2012 Request for Withholding Information from Public Disclosure, 5/19/2011 Affidavit Executed by J. Harrison, GE-Hitachi Nuclear Energy Americas LLC, Attachment 1 to GNRO-2011/00039 Project stage: Withholding Request Acceptance ML1204406602012-02-27027 February 2012 Request for Withholding Information from Public Disclosure, 11/29/2011 Affidavit Executed by J. Harrison, GE-Hitachi Nuclear Energy Americas LLC, Attachment 1 to GNRO-2011/00110 Project stage: Withholding Request Acceptance ML1204406532012-02-27027 February 2012 Request for Withholding Information from Public Disclosure, 11/3/2011 Affidavit Executed by E. Schrull, GE-Hitachi Nuclear Energy Americas LLC, Attachment 1 to GNRO-2011/00091 Project stage: Withholding Request Acceptance ML1204406462012-02-27027 February 2012 Request for Withholding Information from Public Disclosure, 10/20/2011 Affidavit Executed by E. Schrull, GE-Hitachi Nuclear Energy Americas LLC, Attachment 1 to GNRO-2011/00090 Project stage: Withholding Request Acceptance ML1204406382012-02-27027 February 2012 Request for Withholding Information from Public Disclosure, 9/22/2011 Affidavit Executed by J. Harrison, GE-Hitachi Nuclear Energy Americas LLC, Attachment 1 to GNRO-2011/00066 Project stage: Withholding Request Acceptance ML1204406272012-02-27027 February 2012 Request for Withholding Information from Public Disclosure, 7/21/2011 Affidavit Executed by E. Schrull, GE-Hitachi Nuclear Energy Americas LLC, Attachment 1 to GNRO-2011/00057 Project stage: Withholding Request Acceptance 2010-07-29
[Table View] |
Text
UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 June 9, 2010 LICENSEE:
Entergy Operations, Inc.
FACILITY:
Grand Gulf Nuclear Station, Unit 1
SUBJECT:
SUMMARY
OF MEETING ON MAY 25, 2010, TO DISCUSS THE LICENSEE'S RESPONSE TO THE NRC STAFF'S REQUEST FOR ADDITIONAL INFORMATION DATED MAY 4,2010, REGARDING INSTALLATION OF A DIGITAL POWER RANGE NEUTRON MONITORING SYSTEM (TAC NO.
ME2531 )
On May 25, 2010, members of the U.S. Nuclear Regulatory Commission (NRC) staff met with representatives from Entergy Operations, Inc. (Entergy, the licensee), at NRC Headquarters, Two White Flint North, 11545 Rockville Pike, Rockville, MD. The licensee was accompanied by representatives from its contractor, General Electric - Hitachi Nuclear Energy (GEH). The meeting was a Category 1 public meeting; however, no members of the public attended.
Portions of the meeting were closed due to the proprietary nature of the information that was discussed.
The meeting was requested by the licensee to discuss its proposed responses to the NRC staff's request for additional information (RAI) dated May 4, 2010 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML101190125). The RAI was issued as part of the staff's review of the licensee's application dated November 3, 2009 (ADAMS Accession No. ML093140430), which requested staff approval of an amendment to the Grand Gulf Nuclear Station, Unit 1 technical specifications to reflect installation of the digital GEH Nuclear Measurement Analysis and Control Power Range Neutron Monitoring (NUMAC PRNM) System.
The licensee presented its understanding of the RAI and its proposed approach to responding to each of the questions.
The NRC staff provided comments for consideration by the licensee in the preparation of its RAI response, including the following:
For RAI No.2, the staff noted that system upgrades are reviewed using the guidance of the Standard Review Plan (SRP, or NUREG-0800). The staff expects the response will address changes that have occurred to the platform since the staff's approval of the NUMAC PRNM system topical report and supplement.
For RAI No.5, the licensee should provide the information in its response or provide the schedule to submit the information. As much as possible, the PRNM system application should be unlinked from the planned extended power uprate application.
- 2 For RAI No.8, the licensee should provide the schedule to submit the information.
For RAI No.3, the staff expects that the licensee will provide a diversity and defense-in-depth (0-3) analysis to demonstrate that the plant remains within its design basis for a common-cause failure of the PRNM system. Additionally, the 0-3 analysis should include sources of "programmable device" common-cause failures, including the tools and teams used to develop, synthesize, validate, and verify the resultant programmable logic.
For RAI No.7, the question is limited to changes made to the operator front and back panel screens as a result of the PRNM upgrade. If not yet available, the licensee should provide the schedule to submit the information.
For RAI No.9, the staff expects a description in the response describing the planned administrative controls and a proposed regulatory commitment or license condition that the controls will be in place before the PRNM system upgrade is implemented.
The staff notes that RAI Nos. 1 and 6 were written specifically to address "programmable devices" rather than "software," so that not just the most common/conventional microprocessor-executable software program would be addressed. Therefore, the licensee's response to RAJ NO.1 should address the voter/coincidence programmable logic, as well as all other platform programmable logic that has been modified, and the processes/procedures that govern these modifications. Similarly, the response to RAI NO.6 should address any application-specific programmable logic and the processes/procedures that govern these modifications.
The scope of RAI Nos. 1 and 2 was subsequently discussed during a telephone call between the meeting participants on June 1, 2010. As a general comment, the NRC staff notes that SRP Appendix 7.0-A, "Review Process for Oigital Instrumentation and Control Systems," provides an overview of the process for reviewing digital instrumentation and control (I&C) systems. Appendix 7.0-A refers to SRP Appendix 7.1-0, "Guidance for Evaluation of the Application of IEEE Std 7-4.3.2," for guidance on the use of IEEE Std 7-4.3.2-2003, as endorsed by Regulatory Guide 1.152, Revision 2. SRP Appendix 7.1-0 states, "The scope of IEEE Std 7-4.3.2-2003 and Regulatory Guide 1,152, Revision 2 includes all safety instrumentation and control (I&C) systems that are computer based. IEEE Std 7-4.3.2-2003 serves to amplify criteria in IEEE Std 603-1991 to address the use of computers as part of safety systems in nuclear power generating stations, systems covered by Sections 7.2 through 7.6 of the plant safety analysis report (SAR)." SRP Appendix 7.1-0 also states, "The criteria contained in IEEE Std 7-4.3.2-2003, in conjunction with requirements in IEEE Std 603-1991, establish minimum functional and design criteria for computers used as components of a safety system." Since there is no established relationship between IEEE Std 279-1971 and IEEE Std 7-4.3.2-2003, any new digitall&C systems or upgraded digital systems will be reviewed against IEEE Std 603
- 3 1991. A plant licensed to requirements that predated IEEE Std 603-1991 may not be able to meet all the requirements of IEEE Std 603-1991. In that case, the licensee should document and justify each deviation from the requirements of IEEE Std 603-1991.
No regulatory decisions were made at the meeting. The meeting agenda was provided with the meeting notice dated May 12, 2010 (ADAMS Accession No. ML101300509). The licensee's presentation slides have been placed in ADAMS (ADAMS Accession No. ML101470388, proprietary version; ML101470385, public version). A list of attendees is enclosed.
Carl F. Lyon, Project Manager Plant Licensing Branch IV Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-416
Enclosure:
Attendance List cc w/encl: Distribution via Listserv
ATTENDANCE LIST NRC MEETING WITH ENTERGY OPERATIONS, INC.
PROPOSED REQUEST FOR ADDITIONAL INFORMATION RESPONSE GRAND GULF NUCLEAR STATION, UNIT 1 MAY 25,2010 G. Davant, Entergy F. Lyon, NRR J. Langberg, Entergy W. Kemper, NRR T. Thornton, Entergy B. Marcus, NRR J. Brown, Entergy B. Dittman, NRR E. Cooper, GEH S. Rudy, GEH E. Mino, GEH S. Fitzsimmons, GEH T. Rogers, GEH E. Schmidt, GEH R. Miller, GEH A. Poulos, GEH Enclosure
ML101300509). The licensee's presentation slides have been placed in ADAMS (ADAMS Accession No. ML101470388, proprietary version; ML101470385, public version). A list of attendees is enclosed.
IRA by Kaly Kalyanam fori Carl F. Lyon, Project Manager Plant Licensing Branch IV Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-416
Enclosure:
Attendance List cc w/encl: Distribution via Listserv DISTRIBUTION:
PUBLIC RidsNrrDorlLpl4 Resource RidsRgn4MailCenler Resource LPLIV r/f RidsNrrLAJBurkhardl Resource BMarcus, NRR/DE/EICB RidsAcrsAcnw_MailCTR Resource RidsNrrPMGrandGulf Resource BDiUman, NRR/DE/EICB RidsNrrDeEicb Resource RidsOgcRp Resource LTrocine, EDO RIV ADAMS Accession Nos. MIg. Notice ML101300509, Mtg. Summary ML101520269 Licensee Slides ML101470388 via emal OFFICE NRR/LPL4/PM NRRlLPL4/LA DE/EICB/BC NRR/LP4/BC NRRlLPL4/PM NAME FLyon JBurkhardt' WKemper MMarkley FLyon KKalyanam for DATE 6/4/10 6/4/10 6/8/10 6/9/10 6/9/10