- Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance, Withholding Request Acceptance
- Meeting, Meeting
|
MONTHYEARGNRO-2009/00022, 2009-03 - NRC Written Examination Grade Report in Accordance with NUREG 1021, Revision 92009-03-0909 March 2009 2009-03 - NRC Written Examination Grade Report in Accordance with NUREG 1021, Revision 9 Project stage: Request ML0931404632009-11-0303 November 2009 License Amendment Request Regarding Power Range Neutron Monitoring System Upgrade Project stage: Request ML0934100662009-12-10010 December 2009 Acceptance Review of License Amendment Request for Power Range Neutron Monitoring System - Includes Revised Schedule for Completion Based on Late Submittal Project stage: Acceptance Review ML0931707702009-12-10010 December 2009 Request for Withholding Information from Public Disclosure - 10/1/2009 Affidavit Executed by E. Schrull, GE-Hitachi Nuclear Energy Americas LLC Project stage: Withholding Request Acceptance ML1000703852010-01-15015 January 2010 Request for Additional Information, License Amendment Request for Power Range Neutron Monitoring System Project stage: RAI ML1004308252010-02-0808 February 2010 Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI ML1010902452010-04-22022 April 2010 Request for Additional Information Power Range Neutron Monitoring System Project stage: RAI ML1011901252010-05-0404 May 2010 Request for Additional Information, Round 3, License Amendment Request for Power Range Neutron Monitoring System Project stage: RAI ML1013805412010-05-17017 May 2010 Entergy Operations, Inc. - E-mail Attaching EOI and GE-Hitachi Nuclear Energy Presentation Slides and Affidavit Related to Meeting on May 25, 2010 Regarding Grand Gulf Nuclear Station, Unit 1 Project stage: Meeting ML1013805152010-05-17017 May 2010 GE-Hitachi Nuclear Energy Americas LLC Affidavit of Edward Schrull Request to Withhold from Public Disclosure, Enclosure 1 to GEH Letter GG-PRNM-168777-EC065, Grand Gulf Prnm Upgrade Project - Presentation for May 25, 2010, NRC Meeting Project stage: Meeting ML1014100942010-05-18018 May 2010 Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI ML1013805592010-05-24024 May 2010 Request for Withholding Information from Public Disclosure Project stage: Withholding Request Acceptance ML1013804212010-05-25025 May 2010 Entergy Operations, Inc. and GE-Hitachi Nuclear Energy Slide Presentation for May 25, 2010 - NRC RAIs Regarding GGNS Prnm System LAR (Non-Proprietary) Project stage: Other ML1014703852010-05-25025 May 2010 Licensee Slides from 5/25/10 Meeting to Discuss Response to Requests for Additional Information on License Amendment Request for Digital Power Range Neutron Monitoring System (Nonproprietary Version) Project stage: Response to RAI ML1014704032010-05-25025 May 2010 Affidavit for 5/25/10 NRC Meeting to Discuss Response to Requests for Additional Information on License Amendment Request for Digital Power Range Neutron Monitoring System Project stage: Response to RAI GNRO-2010/00040, Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2010-06-0303 June 2010 Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI ML1015202692010-06-0909 June 2010 5/25/2010 Summary of Meeting with Entergy Operations, Inc., to Discuss the Licensees Response to NRC Staffs Request for Additional Information Dated 5/4/2010 Installation of a Digital Power Range Neutron Monitoring System Project stage: RAI ML1018001492010-06-18018 June 2010 Schedule for Responding to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Request ML1017904372010-06-30030 June 2010 0000-0102-0888-RI, Plant-Specific Responses Required by Numac Prnm Retrofit Plus Option III Stability Trip Function Topical Report, (NEDC-3241OP-A) Project stage: Other ML1016703442010-07-0202 July 2010 Request for Withholding Information from Public Disclosure - GE-Hitachi Nuclear Energy Americas LLC Affidavit Dated 6/2/2010 Project stage: Withholding Request Acceptance ML1021500292010-07-29029 July 2010 Responses to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI ML1021404062010-08-10010 August 2010 Request for Withholding Information from Public Disclosure, E. Schrull, GE-Hitachi Nuclear Energy Americas LLC Affidavit Dated 7/23/2010 Project stage: Withholding Request Acceptance GNRO-2010/00064, Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2010-09-29029 September 2010 Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI ML1027307312010-10-14014 October 2010 Request for Withholding Information from Public Disclosure, 9/28/2010 Affidavit Executed by J. Harrison, GE-Hitachi Nuclear Energy Americas LLC Project stage: Withholding Request Acceptance GNRO-2010/00075, Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2010-12-13013 December 2010 Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI GNRO-2010/00070, Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2010-12-14014 December 2010 Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI ML1111704242011-04-27027 April 2011 E-mail, Request for Additional Information, Round 4, License Amendment Request for Power Range Neutron Monitoring System Project stage: RAI ML1111704322011-04-27027 April 2011 Request for Additional Information, Round 4, License Amendment Request for Power Range Neutron Monitoring System Project stage: RAI GNRO-2011/00032, Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2011-05-0303 May 2011 Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI ML1113204932011-05-12012 May 2011 E-mail, Request for Additional Information, Round 5, License Amendment Request for Power Range Neutron Monitoring System Project stage: RAI GNRO-2011/00038, Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2011-05-16016 May 2011 Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI GNRO-2011/00039, Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2011-05-26026 May 2011 Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI GNRO-2011/00042, Responses to NRC Requests for Additional Information Re License Amendment Request for Power Range Neutron Monitoring System2011-05-31031 May 2011 Responses to NRC Requests for Additional Information Re License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI ML1113905962011-06-0202 June 2011 Request for Withholding Information from Public Disclosure, 4/28/2011 Affidavit Executed by E. Schrull, GE-Hitachi Nuclear Energy Americas LLC, Attachment 1 to GNRO-2011/00032 Project stage: Withholding Request Acceptance ML1113906562011-06-0202 June 2011 Request for Withholding Information from Public Disclosure, 5/11/2011 Affidavit Executed by J. Harrison, GE-Hitachi Nuclear Energy Americas LLC, Attachment 1 to GNRO-2011/00038 Project stage: Withholding Request Acceptance GNRO-2011/00044, Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2011-06-13013 June 2011 Responses to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI ML1117402132011-06-23023 June 2011 Email, Request for Additional Information, Round 6, License Amendment Request for Power Range Neutron Monitoring System Project stage: RAI GNRO-2011/00045, Supplemental Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2011-06-28028 June 2011 Supplemental Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Supplement GNRO-2011/00057, Response to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2011-07-22022 July 2011 Response to NRC Requests for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI GNRO-2011/00066, Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2011-09-28028 September 2011 Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI GNRO-2011/00089, Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System2011-10-18018 October 2011 Response to NRC Request for Additional Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System Project stage: Response to RAI GNRO-2011/00090, Supplemental Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System (TAC No. ME2531) - Software Evaluation Report2011-10-26026 October 2011 Supplemental Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System (TAC No. ME2531) - Software Evaluation Report Project stage: Supplement GNRO-2011/00091, Supplemental Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System (TAC No. ME2531) – V&V Summary Test Report2011-11-0808 November 2011 Supplemental Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System (TAC No. ME2531) – V&V Summary Test Report Project stage: Supplement GNRO-2011/00110, Supplemental Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System (TAC No. ME2531) – V&V Summary Test Report2011-12-0101 December 2011 Supplemental Information Pertaining to License Amendment Request for Power Range Neutron Monitoring System (TAC No. ME2531) – V&V Summary Test Report Project stage: Supplement ML1204406022012-02-27027 February 2012 Request for Withholding Information from Public Disclosure, 5/19/2011 Affidavit Executed by J. Harrison, GE-Hitachi Nuclear Energy Americas LLC, Attachment 1 to GNRO-2011/00039 Project stage: Withholding Request Acceptance ML1204406602012-02-27027 February 2012 Request for Withholding Information from Public Disclosure, 11/29/2011 Affidavit Executed by J. Harrison, GE-Hitachi Nuclear Energy Americas LLC, Attachment 1 to GNRO-2011/00110 Project stage: Withholding Request Acceptance ML1204406532012-02-27027 February 2012 Request for Withholding Information from Public Disclosure, 11/3/2011 Affidavit Executed by E. Schrull, GE-Hitachi Nuclear Energy Americas LLC, Attachment 1 to GNRO-2011/00091 Project stage: Withholding Request Acceptance ML1204406462012-02-27027 February 2012 Request for Withholding Information from Public Disclosure, 10/20/2011 Affidavit Executed by E. Schrull, GE-Hitachi Nuclear Energy Americas LLC, Attachment 1 to GNRO-2011/00090 Project stage: Withholding Request Acceptance ML1204406382012-02-27027 February 2012 Request for Withholding Information from Public Disclosure, 9/22/2011 Affidavit Executed by J. Harrison, GE-Hitachi Nuclear Energy Americas LLC, Attachment 1 to GNRO-2011/00066 Project stage: Withholding Request Acceptance ML1204406272012-02-27027 February 2012 Request for Withholding Information from Public Disclosure, 7/21/2011 Affidavit Executed by E. Schrull, GE-Hitachi Nuclear Energy Americas LLC, Attachment 1 to GNRO-2011/00057 Project stage: Withholding Request Acceptance 2010-07-29
[Table View] |
Text
UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 January 15, 2010 Vice President, Operations Entergy Operations, Inc.
Grand Gulf Nuclear Station P.O. Box 756 Port Gibson, MS 39150
SUBJECT:
GRAND GULF NUCLEAR STATION, UNIT 1 - REQUEST FOR ADDITIONAL INFORMATION RE: POWER RANGE NEUTRON MONITORING SYSTEM (TAC NO. ME2531)
Dear Sir or Madam:
By application dated November 3,2009 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML093140430), Entergy Operations, Inc. (Entergy, the licensee), requested U.S. Nuclear Regulatory Commission (NRC) staff approval of an amendment to the Grand Gulf Nuclear Station, Unit 1, technical specifications to reflect installation of the digital General Electric - Hitachi (GEH) Nuclear Measurement Analysis and Control (NUMAC) Power Range Neutron Monitoring (PRNM) System.
The NRC staff reviewed the information provided in your application and determined that additional information is required in order to complete its review. The enclosed questions were discussed with Mr. G. Davant of your staff on January 7,2010. Please provide a response to the enclosed questions within 45 days of the date of this letter.
The NRC staff considers that timely responses to requests for additional information help ensure sufficient time is available for NRC staff review and contribute toward the NRC's goal of efficient and effective use of NRC staff resources. If circumstances result in the need to revise the requested response date, please contact me at 301-415-2296 or via e-mail at fred.lyon@nrc.gov.
Sincerely, Carl. F. Lyon, Project Manager Plant Licensing Branch IV Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-416
Enclosure:
Request for Additional Information cc w/encl: Distribution via Listserv
REQUEST FOR ADDITIONAL INFORMATION POWER RANGE NUCLEAR MONITORING SYSTEM UPGRADE GRAND GULF NUCLEAR STATION, UNIT 1 DOCKET NO. 50-416 By application dated November 3,2009 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML093140430), Entergy Operations, Inc. (Entergy, the licensee), requested U.S. Nuclear Regulatory Commission (NRC) staff approval of an amendment to the Grand Gulf Nuclear Station (GGNS), Unit 1, technical specifications (TS) to reflect installation of the digital General Electric - Hitachi (GEH) Nuclear Measurement Analysis and Control (NUMAC) Power Range Neutron Monitoring (PRNM) System. The NRC staff requests the following additional information (RAI) from the licensee to complete its review of the proposed application.
RAI No.1 Please explain how a unit restart is allowed by adding the note, "LCO 3.0A.b is not applicable" to new Required Action J.2., page 14 of the application letter states, "Entergy also proposes a note that states LCO 3.0A.b is not applicable to new Required Action J.2. This note allows unit restart in the event of a shutdown during the 120-day completion time." However, Limiting Condition for Operation (LCO) 3.0A.a and LCO 3.0A.c remain applicable.
LCO 3.0A.a allows entry into a MODE or other specified condition in the Applicability, when an LCO is not met, only when the associated ACTIONS to be entered permit continued operation in the MODE or other specified condition in the Applicability for an unlimited period oftime. Condition J is referenced in Table 3.3.1.1-1 and entered as required by Required Action D.1. Condition J Required Action J.1 requires initiating an alternate method to detect and suppress thermal hydraulic instability oscillations within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and J.2 requires restoring the required channels to operable status within 120 days. Condition J does not permit continued operation for an unlimited period of time. LCO 3.0A.c allows entry into a MODE or other specified condition in the Applicability, when an LCO is not met, only when an allowance is stated in the individual value, parameter, or other Specification. LCO 3.0A.c is not allowed in any condition in GGNS TS 3.3.1.1.
RAI No.2 Please provide revised proposed TS Bases changes that are consistent with Technical Specification Task Force (TSTF)-493, Revision 4, or justify deviations.
The applicability section in Federal Register (74 FR 58065; November 10, 2009), "Notice of Opportunity for Public Comment on the Proposed Model Safety Evaluation for Plant Specific Adoption of Technical Specification Task Force Traveler-493, Revision 4, Enclosure
- 2 "Clarify Application of Setpoint Methodology for LSSS [Limited Safety System Settings]
Functions" stated, "The licensee must add footnotes to all the functions identified in TSTF Traveler-493, Revision 4, Appendix A, and must incorporate the related TS Bases changes" for any licensee wishing to adopt TSTF-493, option A, without changes to setpoint values. The NRC staff considers the changes made by TSTF-493, Revision 4 to TS 3.3.1.1 Bases sections: (1) background; (2) applicable safety analyses, LCO, and applicability; (3) actions; and (4) surveillance requirements (SRs), to be related to GGNS proposed amendment.
RAI No.3 Please state which SRs verify trip setpoint settings for functions 2.a, 2.b, 2.c, 2.d, 2.e, and 2.f in TS Table 3.3.1.1-1, and provide a revised TS Table 3.3.1.1-1 with the addition of notes (d) and (e) for these functions as needed.
The proposed change revises GGNS TSs to incorporate NRC-approved TSTF Traveler-493, Revision 4, to be consistent with Option A. Option A, without changes to setpoint values, adds two Notes to the SRs in the Surveillance Requirements column of TSs Instrumentation Function Tables. Specifically, Notes are added to TS 3.3.1.1 SRs that require verifying trip setpoint setting values (i.e., Channel Calibration and Channel Functional Test SRs) for NUREG-1434.
The first Surveillance Note requires evaluation of channel performance for the condition where the As-Found setting for the channel setpoint is outside its As-Found Tolerance but conservative with respect to the allowable value. This is proposed note (d) to TS Table 3.3.1.1-1. The second Surveillance Note requires that the As-Left setting for the channel be returned to within the As-Left Tolerance of the Nominal Trip Setpoint. This is proposed note (e) to TS Table 3.3.1.1-1.
RAI No.4 In its application, the licensee proposed the following new operating license condition (OLC):
During Cycle 19, GGNS may conduct monitoring of the Oscillation Power Range Monitor (OPRM). During this time, the OPRM Upscale function (Function 2.f of Technical Specification Table 3.3.1.1-1) may be disabled and operated in an "indicate only" mode at which time technical specification requirements would not apply. During such time, Backup Stability Protection measures will be implemented via GGNS procedures to provide an alternate method to detect and suppress reactor core thermal hydraulic instability oscillations.
In the application, the licensee stated that it would review the operating data, setpoints, and margins at the end of the OPRM monitoring period. Once it determines that the results are acceptable, the licensee will enable the OPRM (with applicable SRs met) by connecting it to the reactor protection system trip relays, completing implementation of the hardware changes, and notifying the NRC.
- 3 However, the proposed OLC wording does not restrict GGNS from returning the OPRM into "indicate only" mode, once the OPRM has been enabled during Cycle 19. Also, the proposed "may" wording in the OLC suggests that GGNS has the option to disable the OPRM and conduct monitoring of the OPRM. Please revise the proposed OLC to address these concerns or provide further justification for the proposed wording.
January 15, 2010 Vice President, Operations Entergy Operations, Inc.
Grand Gulf Nuclear Station P.O. Box 756 Port Gibson, MS 39150
SUBJECT:
GRAND GULF NUCLEAR STATION, UNIT 1 - REQUEST FOR ADDITIONAL INFORMATION RE: POWER RANGE NEUTRON MONITORING SYSTEM (TAC NO. ME2531)
Dear Sir or Madam:
By application dated November 3, 2009 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML093140430), Entergy Operations, Inc. (Entergy, the licensee), requested U.S. Nuclear Regulatory Commission (NRC) staff approval of an amendment to the Grand Gulf Nuclear Station, Unit 1, technical specifications to reflect installation of the digital General Electric - Hitachi (GEH) Nuclear Measurement Analysis and Control (NUMAC) Power Range Neutron Monitoring (PRNM) System.
The NRC staff reviewed the information provided in your application and determined that additional information is required in order to complete its review. The enclosed questions were discussed with Mr. G. Davant of your staff on January 7, 2010. Please provide a response to the enclosed questions within 45 days of the date of this letter.
The NRC staff considers that timely responses to requests for additional information help ensure sufficient time is available for NRC staff review and contribute toward the NRC's goal of efficient and effective use of NRC staff resources. If circumstances result in the need to revise the requested response date, please contact me at 301-415-2296 or via e-mail at fred.lyon@nrc.gov.
Sincerely, IRA!
Carl. F. Lyon, Project Manager Plant Licensing Branch IV Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-416
Enclosure:
Request for Additional Information cc w/encl: Distribution via Listserv DISTRIBUTION:
PUBLIC LPLIV r/f RidsAcrsAcnw_MailCTR Resource RidsNrrDorlLpl4 Resource RidsNrrLAJBurkhardt Resource RidsNrrPMGrandGulf Resource RidsOgcRp Resource RidsRgn4MailCenter Resource RidsNrrDirsltsb Resource KBucholtz, NRRlDIRS/ITSB ADAMS Accession No' ML100070385 "memo dated OFFICE NRRlLPL4/PM NRRlLPL4/LA DIRSIITSB/BC NRRlLPL4/BC NRRlLPL4/PM NAME FLyon JBurkhardt RElliott" MMarkley MThadani for FLyon DATE 1/15/10 1/14/10 12/15/09 1/15/10 1/15/10