ML13018A140

From kanterella
Jump to navigation Jump to search

Issuance of Amendments to Adopt Technical Specification Task Force 510, Revision 2, Revision to Steam Generator Program Inspection Frequencies and Tube Sample Selection
ML13018A140
Person / Time
Site: North Anna  Dominion icon.png
Issue date: 01/28/2013
From: V Sreenivas
Plant Licensing Branch II
To: Heacock D
Virginia Electric & Power Co (VEPCO)
Sreenivas V
References
TAC ME9156, TAC ME9157
Download: ML13018A140 (37)


Text

UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 January 28, 2013 Mr. David A. Heacock President and Chief Nuclear Officer Virginia Electric and Power Company Innsbrook Technical Center 5000 Dominion Boulevard Glen Allen, VA 23060-6711

SUBJECT:

NORTH ANNA POWER STATION, UNITS 1 AND 2, ISSUANCE OF AMENDMENTS TO ADOPT TECHNICAL SPECIFICATION TASK FORCE (TSTF) 510, REVISION 2, REVISION TO STEAM GENERATOR PROGRAM INSPECTION FREQUENCIES AND TUBE SAMPLE SELECTION (TAC NOS.

ME9156 AND ME9157)

Dear Mr. Heacock:

The U.S. Nuclear Regulatory Commission has issued the enclosed Amendment Nos. 269 and 250 to Renewed Facility Operating License Nos. NPF-4 and NPF-7 for the North Anna Power Station, Units 1 and 2. The amendment consists of changes to the Technical Specifications (TSs) in response to your application dated July 30, 2012.

The amendments revise the TSs requirements regarding steam generator tube inspections and reporting as described in TSTF-510, Revision 2, "Revision to Steam Generator Program Inspection Frequencies and Tube Sample Selection." The changes are consistent with NRC-approved Industry TSTF Standard Technical Specifications change TSTF-510, Revision 2.

A copy of our related safety evaluation is also enclosed. The Notice of Issuance will be included in the Commission's biweekly Federal Register notice.

Sincerely,

! JI tQ if,. ",-y_____.___7 ' )

Dr . Sreenivas, Project Manager Plant Licensing Branch 1/-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket Nos. 50-338 and 50-339

Enclosures:

1. Amendment No. 269 to NPF-4
2. Amendment No.250 to NPF-7
3. Safety Evaluation cc w/encls: Distribution via Listserv

UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 VIRGINIA ELECTRIC AND POWER COMPANY DOCKET NO. 50-338 NORTH ANNA POWER STATION, UNIT NO.1 AMENDMENT TO RENEWED FACILITY OPERATING LICENSE Amendment No. 269 Renewed License No. NPF-4

1. The Nuclear Regulatory Commission (the Commission) has found that:

A. The application for amendment by Virginia Electric and Power Company et aI., (the licensee) dated July 30, 2012, as supplemented by letter dated December 13, 2012, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; B. The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C. There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D. The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E. The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

-2

2. Accordingly, the license is amended by changes to Paragraph 2.C.(2) of Renewed Facility Operating License No. NPF-4, as indicated in the attachment to this license amendment, and is hereby amended to read as follows:

(2) Technical Specifications The Technical Specifications contained in Appendix A, as revised through Amendment N0269 ,are hereby incorporated in the renewed license. The licensee shall operate the facility in accordance with the Technical Specifications.

3. This license amendment is effective as of its date of issuance and shall be implemented within 60 days of issuance.

FOR THE NUCLEAR REGULATORY COMMISSION Robert J. Pascarelli, Chief Plant Licensing Branch 11-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation

Attachment:

Changes to License No. NPF-4 and the Technical Specifications Date of Issuance: January 28, 2013

UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 VIRGINIA ELECTRIC AND POWER COMPANY DOCKET NO. 50-339 NORTH ANNA POWER STATION, UNIT NO.2 AMENDMENT TO RENEWED FACILITY OPERATING LICENSE Amendment No. 250 Renewed License No. NPF-7

1. The Nuclear Regulatory Commission (the Commission) has found that:

A. The application for amendment by Virginia Electric and Power Company et al., (the licensee) dated July 30,2012, as supplemented by letter dated December 13, 2012, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; B. The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C. There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D. The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E. The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

-2

2. Accordingly, the license is amended by changes to Paragraph 2.C.(2) of Renewed Facility Operating License No. NPF-7, as indicated in the attachment to this license amendment, and is hereby amended to read as follows:

(2) Technical Specifications The Technical Specifications contained in Appendix A, as revised through Amendment No. 250 , are hereby incorporated in the renewed license. The licensee shall operate the facility in accordance with the Technical Specifications.

3. This license amendment is effective as of its date of issuance and shall be implemented within 60 days of issuance.

FOR THE NUCLEAR REGULATORY COMMISSION Robert J. Pascarelli, Chief Plant Licensing Branch 11-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation

Attachment:

Changes to License No. NPF-7 and the Technical Specifications Date of Issuance: January 28, 2013

UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 ATTACHMENT TO LICENSE AMENDMENT NO. 269 RENEWED FACILITY OPERATING LICENSE NO. NPF-4 DOCKET NO. 50-338 AND TO LICENSE AMENDMENT NO. 250 RENEWED FACILITY OPERATING LICENSE NO. NPF-7 DOCKET NO. 50-339 Replace the following pages of the Licenses and the Appendix "A" Technical Specifications (TSs) with the enclosed pages as indicated. The revised pages are identified by amendment number and contain vertical lines indicating the areas of change.

Remove Pages Insert Pages Licenses Licenses License No. NPF-4, page 3 License No. NPF-4, page 3 License No. NPF-7, page 3 License No. NPF-7, page 3 3.4.20-1 3.4.20-1 3.4.20-2 3.4.20-2 5.5-5 5.5-5 5.5-6 5.5-6 5.5-7 5.5-7 5.5-8 5.5-9 5.5-10 5.5-11 5.5-12 5.5-13 5.5-14 5.5-15 5.5-16 5.5-17 5.5-18 5.6-5 5.6-5

-3 (2) Pursuant to the Act and 10 CFR Part 70, VEPCO to receive, possess, and use at any time special nuclear material as reactor fuel, in accordance with the limitations for storage and amounts required for reactor operation, as described in the Updated Final Safety Analysis Report; (3) Pursuant to the Act and 10 CFR Parts 30, 40, and 70, VEPCO to receive, possess, and use at any time any byproduct, source, and special nuclear material as sealed neutron sources for reactor startup, sealed sources for reactor instrumentation and radiation monitoring equipment calibration, and as fission detectors in amounts as required; (4) Pursuant to the Act and 10 CFR Parts 30,40, and 70, VEPCO to receive, possess, and use in amounts as required any byproduct, source, or special nuclear material, without restriction to chemical or physical form, for sample analysis or instrument calibration or associated with radioactive apparatus or component; and (5) Pursuant to the Act and 10 CFR Parts 30 and 70, VEPCO to possess, but not separate, such byproduct and special nuclear materials as may be produced by the operation of the facility.

C. This renewed operating license shall be deemed to contain and is subject to the conditions specified in the following Commission regulations in 10 CFR Chapter I:

Part 20, Section 30.34 of Part 30, Section 40.41 of Part 40, Sections 50.54 and 50.59 of Part 50, and Section 70.32 of Part 70; is subject to all applicable provisions of the Act and to the rules, regulations, and orders of the Commission now or hereafter in effect; and is subject to the additional conditions specified or incorporated below:

(1) Maximum Power Level VEPCO is authorized to operate the North Anna Power Station, Unit No.1, at reactor core power levels not in excess of 2940 megawatts (thermal).

(2) Technical Specifications The Technical Specifications contained in Appendix A, as revised through Amendment No. 269 are hereby incorporated in the renewed license. The licensee shall operate the facility in accordance with the Technical Specifications.

NORTH ANNA - UNIT 1 Renewed License No. NPF-4 Amendment No. 269

-3 (3) Pursuant to the Act and 10 CFR Parts 30, 40, and 70, VEPCO to receive, possess, and use at any time any byproduct, source, and special nuclear material as sealed neutron sources for reactor startup, sealed sources for reactor instrumentation and radiation monitoring equipment calibration, and as fission detectors in amounts as required; (4) Pursuant to the Act and 10 CFR Parts 30,40, and 70, VEPCO to receive, possess, and use in amounts as required any byproduct, source, or special nuclear material, without restriction to chemical or physical form, for sample analysis or instrument calibration or associated with radioactive apparatus or components; and (5) Pursuant to the Act and 10 CFR Parts 30, 40, and 70, VEPCO to possess, but not separate, such byproduct and special nuclear materials as may be produced by the operation of the facility.

C. This renewed license shall be deemed to contain and is subject to the conditions specified in the Commission's regulations as set forth in 10 CFR Chapter I and is subject to all applicable provisions of the Act and to the rules, regulations, and orders of the Commission now or hereafter in effect; and is subject to the additional conditions specified or incorporated below:

(1) Maximum Power Level VEPCO is authorized to operate the facility at steady state reactor core power levels not in excess of 2940 megawatts (thermal).

(2) Technical Specifications The Technical Specifications contained in Appendix A, as revised through Amendment No. 250 ate hereby incorporated in the renewed license. The licensee shall operate the facility in accordance with the Technical Specifications.

(3) Additional Conditions The matters specified in the following conditions shall be completed to the satisfaction of the Commission within the stated time periods following the issuance of the condition or within the operational restrictions indicated. The removal of these conditions shall be made by an amendment to the renewed license supported by a favorable evaluation by the Commission:

a. If VEPCO plans to remove or to make significant changes in the normal operation of eqUipment that controls the amount of radioactivity in effluents from the North Anna Power Station, the NORTH ANNA - UNIT 2 Renewed License No. NPF-7 Amendment No. 250

SG Tube Integrity 3.4.20 3.4 REACTOR COOLANT SYSTEM (RCS) 3.4.20 Steam Generator (SG) Tube Integrity LCO 3.4.20 SG tube integrity shall be maintained.

AND All SG tubes satisfying the tube plugging criteria shall be plugged in accordance with the Steam Generator Program.

APPLICABILITY: MODES 1, 2. 3, and 4.

ACTIONS

- - - - - - - - - - - - - - - NOTE - - - -

Separate Condition entry is allowed for each SG tube.

CONDITION REQUIRED ACTION COMPLETION TIME A. One or more SG tubes A.I Verify tube integrity 7 days satisfying the tube of the affected plugging criteria and tube(s) ;s maintained not plugged in until the next accordance with the refueling outage or SG Steam Generator tube inspection.

Program.

AND A.2 Plug the affected Prior to tube(s) in accordance entering MODE 4 with the Steam following the Generator Program. next refuel i ng outage or SG

. tube inspection North Anna Units 1 and 2 3.4.20-1 Amendments 269, 250

SG Tube Integrity 3.4.20 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME B. Required Action and B.1 Be in MODE 3. 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> associated Completion Time of Condition A AND not met.

B.2 Be in MODE 5. 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> OR SG tube integrity not maintained.

SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.20.1 Verify SG tube integrity in accordance with In accordance the Steam Generator Program. with the Steam Generator Program SR 3.4.20.2 Verify that each inspected SG tube that Prior to satisfies the tube plugging criteria is entering MODE 4 plugged in accordance with the Steam fo 11 ow; ng a SG Generator Program. tube inspection North Anna Units 1 and 2 3.4.20-2 Amendments 269, 250

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.7 Inservice Testing Program This program provides controls for inservice testing of ASME Code Class I, 2, and 3 components. The program shall include the foll owi ng:

a. Testing frequencies specified in the ASME Code for Operation and Maintenance of Nuclear Power Plants and applicable Addenda as follows:

ASME Code for Operation and Maintenance of Nuclear Power Plants and applicable Addenda Required Frequencies for terminology for inservice performing inservice testing activities testing activities Weekly At least once per 7 days Monthly At least once per 31 days Quarterly or every 3 months At least once per 92 days Semiannually or every 6 months At least once per 184 days Every 9 months At least once per 276 days Yearly or annually At least once per 366 days Biennially or every 2 years At least once per 731 days

b. The provisions of SR 3.0.2 are applicable to the above required Frequencies for performing inservice testing activities;
c. The provisions of SR 3.0.3 are applicable to inservice testing activities; and
d. Nothing in the ASME Code for Operation and Maintenance of Nuclear Power Plants shall be construed to supersede the requirements of any TS.

5.5.8 Steam Generator (SG) Program A Steam Generator Program shall be established and implemented to ensure that SG tube integrity is maintained. In addition, the Steam Generator Program shall include the following:

a. Provisions for condition monitoring assessments. Condition monitoring assessment means an evaluation of the lias found" condition of the tubing with respect to the performance criteria for structural integrity and accident induced leakage. The "as found" condition refers to the condition of the tubing during a SG inspection outage, as determined from the inservice (continued)

North Anna Units 1 and 2 5.5-5 Amendments 269, 250

Programs and Manuals 5.5 5.5 P and Manuals 5.5.8 Steam Generator (SG) Program

a. (continued) inspection results or by other means, prior to the plugging of tubes. Condition monitoring assessments shall be conducted during each outage during which the SG tubes are inspected or plugged to confirm that the performance criteria are being met.
b. Performance criteria for SG tube integrity. SG tube integrity shall be maintained by meeting the performance criteria for tube structural integrity, accident induced leakage, and operational LEAKAGE.
1. Structural integrity performance criterion: All in-service steam generator tubes shall retain structural integrity over the full range of normal operating conditions (including startup, operation in the power range, hot standby, and cool down), and all anticipated transients included in the design specification, design basis accidents. This includes retaining a safety factor of 3.0 against burst under normal steady state full power operation primary to secondary pressure differential and a safety factor of 1.4 against burst applied to the design basis accident primary to secondary pressure differentials. Apart from the above requirements, additional loading conditions associated with the design basis accidents, or combination of accidents in accordance with the design and licensing basis, shall also be evaluated to determine if the associated loads contribute significantly to burst or collapse. In the assessment of tube integrity, those loads that do significantly affect burst or collapse shall be determined and assessed in combination with the loads due to pressure with a safety factor of 1.2 on the combined primary loads and 1.0 on axial secondary loads.
2. Accident induced leakage performance criterion: The primary to secondary accident induced leakage rate for any design basis accident, other than a SG tube rupture, shall not exceed the leakage rate assumed in the accident analysis in terms of total leakage rate for all SGs and leakage rate for an individual SG. Leakage is not to exceed 1 gpm for all SGs.
3. The operational LEAKAGE performance criterion is specified in LCO 3.4.13, "RCS Operational LEAKAGE."

North Anna Units 1 and 2 5.5-6 Amendments 269, 250

Programs and Manuals 5.5 5.5 and Manuals 5.5.8 Steam Generator (SG) Program (continued)

c. Provisions for SG tube plugging criteria. Tubes found by inservice inspection to contain flaws with a depth equal to or exceeding 40% of the nominal tube wall thickness shall be plugged.
d. Provisions for SG tube inspections. Periodic SG tube inspections shall be performed. The number and portions of the tubes inspected and methods of inspection shall be performed with the objective of detecting flaws of any type (e.g., volumetric flaws. axial and circumferential cracks) that may be present along the length of the tube, from the tube-to-tubesheet weld at the tube inlet to the tube-to-tubesheet weld at the tube outlet, and that may satisfy the applicable tube plugging criteria. The tube-to-tubesheet weld is not part of the tube. In addition to meeting the requirements of d.1, d.2, and d.3 below, the inspection scope, inspection methods, and inspection intervals shall be such as to ensure that SG tube integrity is maintained until the next SG inspection. A degradation assessment shall be performed to determine the type and location of flaws to which the tubes may be susceptible and, based on this assessment, to determine which inspection methods need to be employed and at what locations.
1. Inspect 100% of the tubes in each SG during the first refueling outage following SG installation.
2. After the first refueling outage following SG installation, inspect each SG at least every 72 effective full power months or at least every third refueling outage (whichever results in more frequent inspections). In addition, the minimum number of tubes inspected at each scheduled inspection shall be the number of tubes in all SGs divided by the number of SG inspection outages scheduled in each inspection period as defined in a, b, c and d below. If a degradation assessment indicates the potential for a type of degradation to occur at a location not previously inspected with a technique capable of detecting this type of degradation at this location and that may satisfy the applicable plugging criteria, the minimum number of locations inspected with such a capable inspection technique during the remainder of the inspection period may be prorated. The fraction of locations to be inspected for this potential type of degradation at this location at the end of the inspection period shall be no less than the ratio of the number of times the SG is scheduled to (continued)

North Anna Units 1 and 2 5.5-7 Amendments 269, 250

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.8 Steam Generator (SG) Program (continued)

2. (continued)

. be inspected in the inspection period after the determination that a new form of degradation could potentially be occurring at this location divided by the total number of times the SG ;s scheduled to be inspected in the inspection period. Each inspection period defined below may be extended up to 3 effective full power months to include a SG inspection outage in an inspection period and the subsequent inspection period begins at the conclusion of the included SG inspection outage.

a. After the first refueling outage following SG installation, inspect 100% of the tubes during the next 144 effective full power months. This constitutes the' first inspection period; .
b. During the next 120 effective full power months, inspect 100% of the tubes. This constitutes the second inspection period;
c. During the next 96 effective full power months, inspect 100% of the tubes. This constitutes the third inspection period; and
d. During the remaining life of the SGs, inspect 100% of the tubes every 72 effective full power months. This constitutes the fourth and subsequent in~pection periods.
3. If crack indications are found in any SG tube, then the next inspection for each affected and potentially affected SG for the degradation mechanism that caused the crack indication shall not exceed 24 effective full power months or one refueling outage (whichever results in more frequent inspections). If definitive information, such as from examination of a pulled tube, diagnostic non-destructive testing, or engineering evaluation indicates that a crack-like indication is not associated with a crack(s),

then the indication need not be treated as a crack.

North Anna Units 1 and 2 5.5-8 Amendments 269, 250

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.8 Steam Genera tor (SG) Program (continued)

e. Provisions for monitoring operational primary to secondary LEAKAGE.

5.5.9 Secondary Water Chemistry Program This program provides controls for monitoring secondary water chemistry to inhibit SG tube degradation and low pressure turbine disc stress corrosion cracking. The program shall include:

a. Identification of a sampling schedule for the critical variables and control points for these variables;
b. Identification of the procedures used to measure the values of the critical variables;
c. Identification of process sampling points, which shall include monitoring the discharge of the condensate pumps for evidence of condenser in leakage;
d. Procedures for the recording and management of data;
e. Procedures defining corrective actions for all off control point chemistry conditions; and
f. A procedure identifying the authority responsible for the interpretation of the data and the sequence and timing of administrative events, which is required to initiate corrective action.

5.5.10 Ventilation Filter Testing Program (VFTP)

A program shall be established to implement the following required testing of Engineered Safety Feature (ESF) filter ventilation systems in general conformance with the frequencies and requirements of Regulatory Positions C.5.a, C.5.c, C.5.d, and C.6.b of Regulatory Guide 1.52, Revision 2, March 1978, and ANSI N510-1975.

a. Demonstrate for each of the ESF systems that an inplace test of the high efficiency particulate air (HEPA) filters shows a penetration and system bypass < 1.0% when tested in accordance (continued)

North Anna Units 1 and 2 5.5-9 Amendments 269, 250

Programs and Manuals 5.5 5.5 Programs and Manual 5.5.10 Ventilation Filter Testing Program (VFTP)

a. (continued) with Regulatory Positions C.5.a and C.5.c of Regulatory Guide 1.52, Revision 2. March 1978, and ANSI N510-1975 at the system flowrate specified below.

ESF Ventilation System Flowrate Main Control Room/Emergency Switchgear 1000 +/- 10% cfm Room (MCR/ESGR) Emergency Ventilation System (EVS)

Emergency Core Cooling System (ECCS) Nominal Pump Room Exhaust Air Cleanup System accident flow (PREACS) for a single train actuation Nominal accident flow for a single train actuation is greater than the minimum required cooling flow for ECCS equipment operation, and ~ 39,200 cfm. which is the maximum flow rate providing an adequate residence time within the charcoal adsorber.

b. Demonstrate for each of the ESF systems that an inplace test of the charcoal adsorber shows a penetration and system bypass

< 1.0% when tested in accordance with Regulatory Positions C.5.a and C.5.d of Regulatory Guide 1.52. Revision 2, March 1978, and ANSI N510-1975 at the system flowrate specified below.

ESF Ventilation System Flowrate MCR/ESGR EVS 1000 +/- 10% cfm Nominal accident flow for a ECCS PREACS single train actuation Nominal accident flow for a single train actuation is greater than the minimum required cooling flow for ECCS equipment operation. and ~ 39.200 cfm. which is the maximum flow rate providing an adequate residence time within the charcoal adsorber.

c. Demonstrate for each of the ESF systems that a laboratory test of a sample of the charcoal adsorber. when obtained as described in Regulatory Position C.6.b of Regulatory Guide 1.52. Revision 2, March 1978. shows the methyl iodide penetration less than the (continued)

North Anna Units 1 and 2 5.5-10 Amendments 269, 250

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.10 Ventilation Filter Testing Program (VFTP)

c. (continued) value specified below when tested in accordance with ASTM 03803-1989 at a temperature of 30°C (86°F) and relative humidity specified below.

ESF Ventilation System Penetration RH MCR/ESGR EVS 2.5% 70%

ECeS PREACS 5% 70%

d. Demonstrate for each of the ESF systems that the pressure drop across the combined HEPA filters, the prefilters, and the charcoal adsorbers is less than the value specified below when tested in accordance with ANSI N510-1975 at the system flowrate specified below.

ESF Ventilation System De lta P Flowrate MCR/ESGR EVS 4 inches W.G. 1000 +/- 10% cfm ECCS PREACS 5 inches W.G. ~ 39,200 cfm

e. Demonstrate that the heaters for each of the ESF systems dissipate ~ the value specified below when tested in accordance with ASME N510-1975.

ESF Ventilation System Wattage MCR/ESGR EVS 3.5 kW The provisions of SR 3.0.2 and SR 3.0.3 are applicable to the VFTP test frequencies.

5.5.11 Explosive Gas and Storage Tank Radioactivity Monitoring Program This program provides controls for potentially explosive gas mixtures contained in the Gaseous Waste System, the quantity of radioactivity contained in gas storage tanks, and the quantity of radioactivity contained in unprotected outdoor liquid storage tanks.

The gaseous radioactivity quantities shall be determined following the methodology in Branch Technical Position (BTP) ETSB 11-5.

"Postulated Radioactive Release due to Waste Gas System Leak or (continued)

North Anna Units 1 and 2 5.5-11 Amendments 269, 250

Programs and Manuals 5.5 5.5 and Manuals 5.5.11 Stora e Tank Radioactivit Monitorin Pro ram Failure". The liquid radwaste quantities shall be determined in accordance with Standard Review Plan, Section 15.7.3, "Postulated Radioactive Release due to Tank Failures".

The program shall include:

a. The limits for concentrations of hydrogen and oxygen in the Gaseous Waste System and a surveillance program to ensure the limits are maintained. Such limits shall be appropriate to the system1s design criteria (i .e., whether or not the system is designed to withstand a hydrogen explosion);
b. A surveillance program to ensure that the quantity of radioactivity contained in each gas storage tank is less than the amount that would result in a whole body exposure of ~ 0.5 rem to any individual in an unrestricted area, in the event of an uncontrolled release of the tanks contents; and l
c. A surveillance program to ensure that the quantity of radioactivity contained in each of the following outdoor tanks that are not surrounded by liners, dikes, or walls, capable of holding the tanks contents and that do not have tank overflows l

and surrounding area drains liquid radwaste ion exchanger system is less than the amount that would result in concentrations greater than the limits of 10 CFR 20, Appendix S, Table 2, Column 2, excluding tritium, at the nearest potable water supply and the nearest surface water supply in an unrestricted area, in the event of an uncontrolled release of the tanks* contents:

1. Refueling Water Storage Tank;
2. Casing Cooling Storage Tank;
3. PG Water Storage Tank;
4. Boron Recovery Test Tank; and
5. Any Outside Temporary Tank.

The provisions of SR 3.0.2 and SR 3.0.3 are applicable to the Explosive Gas and Storage Tank Radioactivity Monitoring Program surveillance frequencies.

North Anna Units 1 and 2 5.5-12 Amendments 269, 250

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.12 Diesel Fuel Oil Testing Program.

A diesel fuel oil testing program to implement required testing of both new fuel oil and stored fuel oil shall be established. The program shall include sampling and testing requirements, and acceptance criteria, all in accordance with applicable ASTM Standards. The purpose of the program is to establish the following:

a. Acceptability of new fuel oil for use prior to addition to storage tanks by determining that the fuel oil has:
1. an API gravity or an absolute specific gravity within limits,
2. a flash pOint and kinematic viscosity within limits for ASTM 2D fuel oil, and
3. water and sediment ~ 0.05%.
b. Within 31 days following addition of the new fuel oil to storage tanks verify that the properties of the new fuel oil, other than those addressed in a. above, are within limits for ASTM 2D fuel oi 1;
c. Total particulate concentration of the stored fuel oil is

~ 10 mg/l when tested every 92 days; and

d. The provisions of SR 3.0.2 and SR 3.0.3 are applicable to the Diesel Fuel Oil Testing Program testing Frequencies.

5.5.13 Technical Specifications (TS) Bases Control Program This program provides a means for processing changes to the Bases of these Technical SpeCifications.

a. Changes to the Bases of the TS shall be made under appropriate administrative controls and reviews.
b. Licensees may make changes to Bases without prior NRC approval provided the changes do not require either of the following:
1. a change in the TS incorporated in the license; or (continued)

North Anna Units 1 and 2 5.5-13 Amendments 269, 250

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.13 Technical Specifications (TS) Bases Control Program (continued)

b. (continued)
2. a change to the UFSAR or Bases that requires NRC approval pursuant to 10 CFR 50.59.
c. The Bases Control Program shall contain provlslons to ensure that the Bases are maintained consistent with the UFSAR.
d. Proposed changes that meet the criteria of Specification 5.5.13b above shall be reviewed and approved by the NRC prior to implementation. Changes to the Bases implemented without prior NRC approval shall be provided to the NRC on a frequency consistent with 10 CFR 50.71(e).

5.5.14 Safety Function Determination Program (SFDP)

This program ensures loss of safety function is detected and appropriate actions taken. Upon entry into LCO 3.0.6, an evaluation shall be made to determine if loss of safety function exists.

Additionally, other appropriate actions may be taken as a result of the support system inoperability and corresponding exception to entering supported system Condition and Required Actions. This program implements the requirements of LCO 3.0.6. The SFDP shall contain the following:

a. Provisions for cross train checks to ensure a loss of the capability to perform the safety function assumed in the accident analysis does not go undetected;
b. Provisions for ensuring the plant is maintained in a safe condition if a loss of function condition exists;
c. Provisions to ensure that an inoperable supported system's Completion Time is not inappropriately extended as a result of multiple support system inoperabilities; and
d. Other appropriate limitations and remedial or compensatory actions.

A loss of safety function exists when, assuming no concurrent single failure, no concurrent loss of offsite power or loss of onsite diesel generator{s), a safety function assumed in the accident (continued)

North Anna Units 1 and 2 5.5-14 Amendments 269, 250

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.14 Safety Function Determination Program (SFDP) (continued) analysis cannot be performed. For the purpose of this program, a loss of safety function may exist when a support system is inoperable, and:

a. A required system redundant to the system(s) supported by the inoperable support system is also inoperable; or
b. A required system redundant to the system(s) in turn supported by the inoperable supported system is also inoperable; or
c. A required system redundant to the support system(s) for the supported systems (a) and (b) above is also inoperable.

The SFOP identifies where a loss of safety function exists. If a loss of safety function is determined to exist by this program, the appropriate Conditions and Required Actions of the LCO in which the loss of safety function exists are required to be entered. When a loss of safety function is caused by the inoperabi1ity of a single Technical Specification support system, the appropriate Conditions and Required Actions to enter are those of the support system.

5.5.15 Containment Leakage Rate Testing Program

a. A program shall establish the leakage rate testing of the containment as required by 10 CFR 50.54(0) and 10 CFR 50, Appendix J, Option B, as modified by approved exemptions. This program shall be in accordance with the guidelines contained in Regulatory Guide 1.163, "Performance-Based Containment Leak-Test Program." dated September 1995 as modified by the following exception:

NEI 94-01-1995, Section 9.2.3: The first Unit 2 Type A test performed after the October 9, 1999 Type A test shall be performed no later than October 9. 2014.

b. The calculated peak containment internal pressure for the design basis loss of coolant accident. Pat is 42.7 ps;g. The containment design pressure is 45 psig.
c. The maximum allowable containment leakage rate. La. at Pas shall be 0.1% of containment air weight per day.

(continued)

North Anna Units 1 and 2 5.5-15 Amendments 269, 250

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.15 Containment Leakage Rate Testing Program (continued)

d. Leakage Rate acceptance criteria are:
1. Prior to entering a MODE where containment OPERABILITY is required, the containment leakage rate acceptance criteria are:

~ 0.60 La for the Type B and Type C tests on a Maximum Path Basis and ~ 0.75 La for Type A tests.

During operation where containment OPERABILITY is required, the containment leakage rate acceptance criteria are:

~ 1.0 La for overall containment leakage rate and ~ 0.60 La for the Type B and Type C tests on a Minimum Path Basis.

2. Overall air lock leakage rate testing acceptance criterion is ~ 0.05 La when tested at ~ Pa.
e. The provisions of SR 3.0.3 are applicable to the Containment Leakage Rate Testing Program.
f. Nothing in these Technical Specifications shall be construed to modify the testing Frequencies required by 10 CFR 50, Appendix J.

5.5.16 Main Control Room/Emergency Switchgear Room (MCR/ESGR) Envelope Habitability Program A MCR/ESGR Envelope Habitability Program shall be established and implemented to ensure that MCR/ESGR envelope habitability is maintained such that, with an OPERABLE MCR/ESGR EVS, MCR/ESGR envelope occupants can control the reactor safely under normal conditions and maintain it in a safe condition following a radiological event, hazardous chemical release, or a smoke challenge. The program shall ensure that adequate radiation protection is provided to permit access and occupancy of the MCR/ESGR envelope under design basis accident conditions without (continued)

North Anna Units 1 and 2 5.5-16 Amendments 269, 250

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.16 personnel receiving radiation exposures in excess of 5 rem total effective dose equivalent for the duration of the accident. The program shall include the following elements:

a. The definition of the MCR/ESGR envelope and the MCR/ESGR envelope boundary.
b. Requirements for maintaining the MCR/ESGR envelope boundary in its design condition including configuration control and preventive maintenance.
c. Requirements for (i) determining the unfiltered air inleakage past the MCR/ESGR envelope into the MCR/ESGR envelope in accordance with the testing methods and at the Frequencies specified in Sections C.1 and C.2 of Regulatory Guide 1.197, "Demonstrating Control Room Envelope Integrity at Nuclear Power Reactors," Revision 0, May 2003. and (11) assessing MCR/ESGR envelope habitability at the Frequencies specified in Sections C.1 and C.2 of Regulatory Guide 1.197, Revision O.

The following is an exception to Section C.2 of Regulatory Guide 1.197, Revision 0:

  • 2.C.l Licensing Bases - Vulnerability assessments for radiological, hazardous chemical and smoke. and emergency ventilation system testing were completed as documented in the UFSAR. The exceptions to the Regulatory Guides (RG) referenced in RG 1.196 (i.e., RG 1.52. RG 1.78, and RG 1.183), which were considered in completing the vulnerability assessments, are documented in the UFSAR/current licensing basis. Compliance with these RGs is consistent with the current licensing basis as described in the UFSAR.
d. Measurement, at designated locations, of the MCR/ESGR envelope pressure relative to all external areas adjacent to the MCR/ESGR envelope boundary during the pressurization mode of operation by one train of the MCR/ESGR EVS, operating at the flow rate required by the VFTP, at a Frequency of 18 months on a STAGGERED TEST BASIS. The results shall be trended and used as part of the assessment of the MCR/ESGR envelope boundary.

(continued)

North Anna Units 1 and 2 5.5-17 Amendments 269, 250

Programs and Manuals 5.5 5.5 and Manuals 5.5.16 Habitability

e. The quantitative limits on unfiltered air inleakage into the MCR/ESGR envelope. These limits shall be stated in a manner to allow direct comparison to the unfiltered air inleakage measured by the testing described in paragraph c. The unfiltered air inleakage limit for radiological challenges is the inleakage flow rate assumed in the licensing basis analyses of design basis accident consequences. Unfiltered air inleakage limits for hazardous chemicals must ensure that exposure of MCR/ESGR envelope occupants to these hazards will be within the assumptions in the licensing basis.
f. The provisions of SR 3.0.2 are applicable to the Frequencies for assessing MCR/ESGR envelope habitability. determining MCR/ESGR envelope unfiltered inleakage. and measuring MCR/ESGR envelope pressure and assessing the MCR/ESGR envelope boundary as required by paragraphs c and d, respectively.

5.5.17 Surveillance Frequency Control Program This program provides controls for Surveillance Frequencies. The program shall ensure that Surveillance Requirements specified in the Technical Specification are performed at interval sufficient to assure the associated Limiting Conditions for Operation are met.

a. The Survei Hance Frequency Control Program shall contai n ali st of Frequencies of those Surveillance Requirements for which the Frequency is controlled by the program.
b. Changes to the Frequencies listed in the Surveillance Frequency Control Program shall be made in accordance with NEI 04-10, "Risk-Informed Method for Control of Surveillance Frequencies,"

Revision 1.

c. The provisions of Surveillance Requirements 3.0.2 and 3.0.3 are applicable to the Frequencies established in the Surveillance Frequency Control Program.

North Anna Units 1 and 2 5.5-18 Amendments 269, 250

Reporting Requirements 5.6 5.6 Reporting Requirements 5.6.7 Steam Generator Tube Inspection Report A report shall be submitted within 180 days after the initial entry into MODE 4 following completion of an inspection performed in accordance with the Specification 5.5.8. "Steam Generator (SG)

Program." The report shall include:

a. The scope of inspections performed on each SG,
b. Degradation mechanisms found,
c. Nondestructive examination techniques utilized for each degradation mechanism,
d. Location, orientation (if linear). and measured sizes (if available) of service induced indications,
e. Number of tubes plugged during the inspection outage for each degradation mechanism,
f. The number and percentage of tubes plugged to date, and the effective plugging percentage in each steam generator, and
g. The results of condition monitoring, including the results of tube pulls and in-situ testing.

North Anna Units 1 and 2 5.6-5 Amendments 269, 250

UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 20555-0001 SAFETY EVALUATION BY THE OFFICE OF NUCLEAR REACTOR REGULATION RELATED TO AMENDMENT NO. 269 TO RENEWED FACILITY OPERATING LICENSE NO. NPF-4 AND AMENDMENT NO. 250 TO RENEWED FACILITY OPERATING LICENSE NO. NPF-7 VIRGINIA ELECTRIC AND POWER COMPANY NORTH ANNA POWER STATION, UNITS 1 AND 2 DOCKET NOS. 50-338 AND 50-339

1.0 INTRODUCTION

By application dated July 30, 2012, as supplemented by letter dated December 13, 2012 (Agencywide Documents and Management System (ADAMS) Accession Nos. ML12219A072 and ML12356A298, respectively), Virginia Electric and Power Company (Dominion, the licensee) proposed changes to the Technical Specifications (TSs) for North Anna Power Station, Unit Nos.

1 and 2 (North Anna), to adopt the U.S. Nuclear Regulatory Commission (NRC)-approved Revision 2 to Technical Specifications Task Force (TSTF) Standard Technical Specifications (STS) Change Traveler TSTF-510, "Revision to Steam Generator Program Inspection Frequencies and Tube Sample Selection."

The proposed changes revise TS Limiting Condition for Operation (LCO) 3.4.20, "Steam Generator (SG) Tube Integrity," TS 5.5.8, "Steam Generator (SG) Program," and TS 5.6.7, "Steam Generator Tube Inspection Report," and include TS Bases changes that summarize and clarify the purpose of the TS. The specific changes concern SG inspection periods, and address applicable administrative changes and clarifications. Per the licensee, its license amendment request (LAR) is consistent with the Notice of Availability of TSTF-51 0, Revision 2, announced in the Federal Register on October 27, 2011 (76 FR 66763), as part of the consolidated line item improvement process (CLlIP).

Enclosure

-2 TSTF-510

Background:

The SG tubes in PWRs have a number of important safety functions. These tubes are an integral part of the reactor coolant pressure boundary (RCPB) and, as such, are relied upon to maintain primary system pressure and inventory. As part of the RCPB, the SG tubes are unique in that they are also relied upon as a heat transfer surface between the primary and secondary systems such that residual heat can be removed from the primary system and are relied upon to isolate the radioactive fission products in the primary coolant from the secondary system. In addition, the SG tubes are relied upon to maintain their integrity to be consistent with the containment objectives of preventing uncontrolled fission product release under conditions resulting from core damage during severe accidents.

The current STS requirements in the above specifications were established in May 2005 with the NRC staffs approval of TSTF-449, Revision 4, "Steam Generator Tube Integrity" (NRC Federal Register Notice of Availability (70 FR 24126>>. The TSTF-449 changes to the STS incorporated a new, largely performance-based approach for ensuring the integrity of the SG tubes is maintained. The performance-based requirements were supplemented by prescriptive requirements relating to tube inspections and tube repair limits to ensure that conditions adverse to quality are detected and corrected on a timely basis. As of September 2007, the TSTF-449, Revision 4, changes were adopted in the plant TS for all pressurized water reactors (PWRs).

2.0 REGULATORY EVALUATION

Title 10 of the Code of Federal Regulations (10 CFR) establishes the requirements with respect to the integrity of the SG tubing. Specifically, the General Design Criteria (GDC) in Appendix A to 10 CFR Part 50 state that the RCPB shall have "an extremely low probability of abnormal leakage...and of gross rupture" (GDC 14), "shall be designed with sufficient margin" (GDC 15 and 31), shall be of "the highest quality standards practical" (GDC 30), and shall be designed to permit "periodic inspection and testing ...to assess ...structural and leaktight integrity" (GDC 32).

Although both of North Anna's units were issued construction permits based on the draft GDC (published by the Atomic Energy Commission), the licensee demonstrates conformance to the 1971 GDC to facilitate review. The following sections of North Anna's Updated Final Safety Analysis Report (UFSAR), revision 47, discuss compliance with the RCPB design criteria:

  • 3.1.27, "Fracture Prevention of Reactor Coolant Pressure Boundary, Criterion 31"
  • 3.1.28, "Inspection of Reactor Coolant Pressure Boundary, Criterion 32" Section 50.55a of 10 CFR, specifies that components which are part of the RCPB must meet the requirements for Class 1 components in Section 11\ of the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code (Code). Section 50.55a further requires, in part, that throughout the service life of a PWR facility, ASME Code Class 1 components meet the requirements, except design and access provisions and pre-service examination requirements, in

- 3 Section XI, "Rules for Inservice Inspection [(lSI)] of Nuclear Power Plant Components," of the ASME Code, to the extent practical. This requirement includes the inspection and repair criteria of Section XI of the ASME Code.

Section 50.36 of 10 CFR, "Technical Specifications," establishes the requirements related to the content of the TS. Pursuant to 10 CFR 50.36, TSs are required to include items in the following five categories related to station operation: (1) safety limits, limiting safety system settings, and limiting control settings; (2) LCOs; (3) SRs; (4) design features; and (5) administrative controls.

LCOs and accompanying action statements and SRs in the STS relevant to SG tube integrity are in TS 3.4.13 "RCS [reactor coolant system] Operational Leakage," and TS 3.4.17 (SR 3.4.17.2),

"Steam Generator (SG) Tube Integrity." The SRs in the "Steam Generator (SG) Tube Integrity" specification reference the SG Program which is defined in the STS administrative controls. North Anna's TSs 3.4.13, "RCS Operational Leakage," and 3.4.20, "Steam Generator (SG) Tube Integrity," address requirements similar to those specified in STS sections above.

Section 50.36(c)(5) of 10 CFR, defines administrative controls as "the provisions relating to organization and management, procedures, recordkeeping, review and audit, and reporting necessary to assure the operation of the facility in a safe manner." Programs established by the licensee to operate the facility in a safe manner, including the SG Program, are listed in the administrative controls section of the TS. The SG Program is defined in TS 5.5.B, while the reporting requirements relating to implementation of the SG Program are in TS 5.6.7.

TS 5.5.B requires that an SG Program be established and implemented to ensure that SG tube integrity is maintained. TS 5.5.B.a requires that a condition monitoring assessment be performed during each outage in which the SG tubes are inspected, to confirm that the performance criteria are being met. SG tube integrity is maintained by meeting the performance criteria specified in TS 5.5.B.b for structural and leakage integrity, consistent with the plant design and licensing basis.

The applicable tube repair criteria, specified in TS 5.5.B.c, are that tubes found during lSI to contain flaws with a depth equal to or exceeding 40 percent of the nominal wall thickness shall be plugged. TS 5.5.B.d includes provisions regarding the scope, frequency, and methods of SG tube inspections. These provisions require that the inspections be performed with the objective of detecting flaws of any type that (1) may be present along the length of a tube, from the tube-to-tubesheet weld at the tube inlet to the tube-to-tubesheet weld at the tube outlet, and (2) may satisfy the applicable tube repair criteria.

3.0 TECHNICAL EVALUATION

Each proposed change to the TS is described individually below, followed by the NRC staffs assessment of the change.

3.1 TS 5.5.B, "Steam Generator (SG) Program" The last sentence in the introductory paragraph currently states, "In addition, the Steam Generator Program shall include the following provisions."

Proposed Change: The sentence is revised to say "In addition, the Steam Generator Program shall include the following." The subsequent paragraph starts with "Provisions for ... " and stating "provisions" in the introductory paragraph is duplicative.

- 4 Assessment: The NRC staff has reviewed the licensee's proposed change to TS 5.5.8 and agrees that the word, "provisions," in the introductory paragraph is duplicative. The NRC staff agrees that the change is administrative in nature, and therefore is acceptable.

3.2 TS 5.5.8. Paragraph 5.5.8 b.1, "Structural integrity performance criterion" The first sentence currently states:

All in-service steam generator tubes shall retain structural integrity over the full range of normal operating conditions (including startup, operation in the power range, hot standby, and cool down, and all anticipated transients included in the design specification) and design basis accidents.

Proposed Change: Revise the sentence as follows:

All in-service steam generator tubes shall retain structural integrity over the full range of normal operating conditions (including startup, operation in the power range, hot standby, and cool down), all antiCipated transients included in the design specification, and design-basis accidents.

The basis for the change is that the sentence inappropriately includes anticipated transients in the description of normal operating conditions.

Assessment: The NRC staff agrees the current wording is incorrect and that anticipated transients should be differentiated from normal operating conditions. Therefore, the NRC staff finds the change acceptable.

3.3. Paragraph 5.5.8.c, "Provisions for SG tube repair criteria," Paragraph 5.5.8.d, "Provisions for SG tube inspections," LCO 3.4.20, "Steam Generator (SG) Tube Integrity" Proposed Change: Change all references to "tube repair criteria" to "tube plugging criteria."

This change is intended to be consistent with the treatment of SG tube repair throughout TS 5.5.8.

Assessment: The NRC staff finds that the proposed change provides a more accurate label of the criteria and, therefore, adds clarity to the specification. This is because only one action must be taken when the criteria are exceeded. There are no alternative SG tube repair actions in North Anna's TSs. Therefore, the NRC staff finds the change acceptable.

3.4 Paragraph 5.5.8.d, "Provisions for SG tube inspections" Proposed Change: Change the term "an assessment of degradation" to "a degradation assessment" to be consistent with the terminology used in industry program documents.

Assessment: The NRC staff agrees that the terminology should be consistent and finds the change acceptable.

- 5 3.5 Paragraph 5.5.B.d.1 The paragraph currently states: "Inspect 100% of the tubes in each SG during the first refueling outage following SG replacement."

Proposed change The change would replace "SG replacement" with "SG installation." The basis for the change is that it will allow the SG Program to apply to both existing plants and new plants.

Assessment The NRC staff agrees the SG Program can apply to both existing and new plants.

Therefore, the NRC staff finds the change acceptable.

3.6 Paragraph 5.5.B.d.2 for plants with SGs with alloy 690 thermally-treated (TT) tubes NOTE: Per North Anna's UFSAR Revision 47, Table 5.2-22, "Reactor Coolant Pressure Boundary Materials," both Unit 1 and Unit 2 use steam generator tubes made of "ASME SB-163, Alloy 690 TT" material.

The paragraph currently states:

Inspect 100% of the tubes at sequential periods of 144, 10B, 72, and, thereafter, 60 effective full power months. The first sequential period shall be considered to begin after the first inservice inspection of the SGs. In addition, inspect 50% of the tubes by the refueling outage nearest the midpoint of the period and the remaining 50% by the refueling outage nearest the end of the period.

No SG shall operate for more than 72 effective full power months or three refueling outages (whichever is less) without being inspected.

Proposed Change: Revise paragraph 5.5.B.d.2 as follows:

After the first refueling outage following SG installation. inspect each SG at least every 72 effective full power months or at least every third refueling outage (whichever results in more frequent inspections). In addition. the minimum number of tubes inspected at each scheduled inspection shall be the number of tubes in all SGs divided by the number of SG inspection outages scheduled in each inspection period as defined in a. b. c, and d below. If a degradation assessment indicates the potential for a type of degradation to occur at a location not previously inspected with a technique capable of detecting this type of degradation at this location and that may satisfy the applicable tube plugging criteria, the minimum number of locations inspected with such a capable inspection technique during the remainder of the inspection period may be prorated. The fraction of locations to be inspected for this potential type of degradation at this location at the end of the inspection period shall be no less than the ratio of the number of times the SG is scheduled to be inspected in the inspection period after the determination that a new form of degradation could potentially be occurring at this location divided by the total number of times the SG is scheduled to be inspected in the inspection period.

Each inspection period defined below may be extended up to 3 effective full power months to include a SG inspection outage in an inspection period and the

-6 subsequent inspection period begins at the conclusion of the included SG inspection outage.

a) After the first refueling outage following SG installation, inspect 100% of the tubes during the next 144 effective full power months. This constitutes the first inspection period; b) During the next 120 effective full power months, inspect 100% of the tubes.

This constitutes the second inspection period; c) During the next 96 effective full power months, inspect 100% of the tubes.

This constitutes the third inspection period; and d) During the remaining life of the SGs, inspect 100% of the tubes every 72 effective full power months. This constitutes the fourth and subsequent inspection periods.

Assessment:

Paragraph 5.5.8.d.2 in its current form and with the proposed changes is similar for each of the tube alloy types used in domestic steam generators, but with differences that reflect the improved resistance of alloy 690 TT to stress corrosion cracking relative to both alloy 600 mill annealed (MA) and alloy 600 TT. These differences include progressively larger maximum inspection interval requirements and sequential inspection periods (during which 100 percent of the tubes must be inspected) for alloy 600 MA, 600 TT, and alloy 690 TT tubes, respectively. In addition, because of the longer maximum inspection intervals allowed for alloy 600 TT and 690 TT tubes, Paragraph 5.5.8.d.2 includes a restriction on the distribution of sampling over each sequential inspection period for alloy 600 TT and 690 TT tubes that is not included for alloy 600 MA tubes.

The licensee proposes to move the first two sentences of Paragraph 5.5.8.d.2 to the end of the paragraph and make editorial changes to improve clarity. The NRC staff finds these changes to be of a clarifying nature, not changing the current intent of these two sentences. However, the LAR also includes three changes to when inspections are performed as follows:

  • The second inspection period would be revised from 108 to 120 EFPM.
  • The third inspection period would be revised from 72 to 96 EFPM.
  • The fourth and subsequent inspection periods would be revised from 60 to 72 EFPM.

The licensee characterizes these changes as marginal increases for consistency with typical fuel cycle lengths that better accommodate the scheduling of inspections. The NRC staff observes that this is clearly the case for plants operating with 18- or 36-month inspection intervals (one or two fuel cycles, respectively). With these intervals, the last scheduled inspection during the first inspection period would coincide with the end of the first, third, and subsequent inspection periods.

The NRC staff finds that for plants operating with 54-month inspection intervals (three fuel cycles);

the end of each inspection period will not generally coincide with a scheduled inspection outage.

-7 The proposed changes would generally increase the number of inspections in each of the third and subsequent inspection periods by up to one additional inspection. This could reduce the required average minimum sample size during these periods. For plants operating with 54-month inspection intervals, the proposed changes will usually have no effect on the required average minimum sample size during these periods. However, inspection sample sizes will continue to be subject to Paragraph 5.5.B.d.2 which states that in addition to meeting the requirements of Paragraph 5.5.B.d.2, the inspection scope, inspection methods, and inspection intervals shall be such as to ensure SG tube integrity is maintained until the next scheduled inspection. Therefore, the NRC staff concludes that with the proposed changes to the length of the second and subsequent inspection periods, compliance with the SG program requirements in TS 5.5.B.d.2 will continue to ensure both adequate inspection scopes and tube integrity.

For each inspection period, Paragraph 5.5.B.d.2 currently requires that at least 50 percent of the tubes be inspected by the refueling outage nearest to the mid-point of the inspection period and the remaining 50 percent by the refueling outage nearest the end of the inspection period. The NRC staff notes that if there are not an equal number of inspections in the first half and second half of the inspection period, the average minimum sampling requirement may be markedly different for inspections in the first half of the inspection period compared to those in the second half, even when there are uniform intervals between each inspection.

For example, a plant in the second (120 EFPM) inspection period with a scheduled 36-month interval (two fuel cycles) between each inspection would currently be required to inspect 50 percent of the tubes by the refueling outage nearest the midpoint of the inspection which would be the third refueling outage in the period, six months before the mid-point (assuming an inspection was performed at the very end of the 144 EPFM inspection period). However, since no inspection is scheduled for that outage, then the full 50 percent sample must be performed during the inspection scheduled for the second refueling outage in the period. Two inspections would be scheduled to occur in the second half of the inspection period, at 72 and 10B months into the inspection period. Thus, the current sampling requirement could be satisfied by performing a 25 percent sample during each of these inspections or other combinations of sampling (e.g., 10 percent during one and 40 percent in the other) totaling 50 percent.

The NRC staff finds there is no basis to require the minimum initial sample size to vary so much from inspection to inspection. The licensee proposes to revise this requirement such that the minimum sample size for a given inspection in a given inspection period is 100 percent divided by the number of scheduled inspections during that inspection period. For the above example, the proposed change would result in a uniform initial minimum sample size of 33.3 percent for each of the three scheduled inspections during the inspection period. The NRC staff concludes this proposed revision to be an improvement to the existing requirement since it provides a more consistent minimum initial sampling requirement.

The proposed changes to Paragraph 5.5.B.d.2 include two new sentences addressing the prorating of required tube sample sizes if a degradation assessment indicates the potential for a type of degradation to occur at a location not previously inspected with a technique capable of detecting this type of degradation at this location and that may satisfy the applicable tube plugging criteria. For example, new information from another similar plant becomes available indicating the potential for circumferential cracking at a specific location on the tube. Previous degradation assessments had not identified the potential for this type of degradation at this location. Thus, previous inspections of this location had not been performed with a technique capable of detecting

-8 circumferential cracks. However, now that the potential for circumferential cracking has been identified at this location, Paragraph 5.5.8.d.2 requires a method of inspection to be performed with the objective of detecting circumferential cracks which may be present at this location and that may satisfy the applicable tube repair criteria.

Furthermore, suppose this inspection is performed for the first time during the third of four SG inspections scheduled for the 144 EFPM inspection period, Paragraph 5.5.8.d.2 currently does not specifically specify whether this location needs to be 100 percent inspected by the end of the 144 EFPM inspection period, or whether a prorated approach may be taken. The NRC staff addressed this question in Issue 1 of NRC Regulatory Information Summary (RIS) 2009-04, "Steam Generator Tube Inspection Requirements," dated April 3, 2009 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML083470557), as follows:

Issue 1: A licensee may identify a new potential degradation mechanism after the first inspection in a sequential period. If this occurs, what are the expectations concerning the scope of examinations for this new potential degradation mechanism for the remainder of the period (e.g., do 100 percent of the tubes have to be inspected by the end of the period or can the sample be prorated for the remaining part of the period)?

[NRC Staff Position:] The TS contain requirements that are a mixture of prescriptive and performance-based elements. Paragraph I'd" of these requirements indicates that the inspection scope, inspection methods, and inspection intervals shall be sufficient to ensure that SG tube integrity is maintained until the next SG inspection. Paragraph lid" is a performance-based element because it describes the goal of the inspections but does not specify how to achieve the goal. However, Paragraph "d.2" is a prescriptive element because it specifies that the licensee must inspect 100 percent of the tubes at specified periods.

If an assessment of degradation performed after the first inspection in a sequential period results in a licensee concluding that a new degradation mechanism (not anticipated during the prior inspections in that period) may potentially occur, the scope of inspections in the remaining portion of the period should be sufficient to ensure SG tube integrity for the period between inspections.

In addition, to satisfy the prescriptive requirements of Paragraph "d.2" that the licensee must inspect 100 percent of the tubes within a specified period, a prorated sample for the remaining portion of the period is appropriate for this potentially new degradation mechanism. This prorated sample should be such that if the licensee had implemented it at the beginning of the period, the TS requirement for the 100 percent inspection in the entire period (for this degradation mechanism) would have been met. A prorated sample is appropriate because (1) the licensee would have performed the prior inspections in this sequential period consistently with the requirements, and (2) the scope of inspections must be sufficient to ensure that the licensee maintains SG tube integrity for the period between inspections.

-9 The NRC staff finds that relocation of information in sentences 3 and 4 as described above clarifies the existing requirement consistent with the NRC staffs position from RIS 2009-04 quoted above and are, therefore, acceptable.

The proposed fifth sentence in Paragraph S.S.B.d.2 states, "Each inspection period defined below may be extended up to 3 effective full power months to include a SG inspection outage in an inspection period and the subsequent inspection period begins at the conclusion of the included SG inspection outage." Allowing extension of the inspection periods by up to an additional 3 EFPMs potentially impacts the average tube inspection sample size to be implemented during a given inspection in that period. For example, if four SG inspections are scheduled to occur within the nominal 144-EFPM period, then the minimum sample size for each of the four inspections could average as little as 2S percent of the tube population. If a fifth inspection can be included within the period by extending the period by 3 EFPM, then the minimum sample size for each of the five inspections could average as little as 20 percent of the tube population. Therefore, the proposed change does not impact the required frequency of SG inspection.

Required tube inspection sample sizes are also subject to the performance-based requirement in Paragraph S.S.B.d.2, which states, in part, that in addition to meeting the requirements of Paragraph S.S.B.d.2, "the inspection scope, inspection methods, and inspection intervals shall be such as to ensure that SG tube integrity is maintained until the next scheduled SG inspection."

This requirement remains unchanged underthe proposal. The NRC staff concludes the proposed fifth sentence involves only a relatively minor relaxation to the existing sampling requirements in Paragraph S.S.B.d.2. However, the performance-based requirements in S.S.B.d.2 ensure that adequate inspection sampling will be performed to ensure tube integrity is maintained. The NRC staff concludes that the proposed change is acceptable.

Finally, the first sentence of the proposed revision to Paragraph S.S.B.d.2 replaces the last sentence of the current Paragraph S.S.B.d.2. This sentence establishes the minimum allowable SG inspection frequency as at least every 72 EFPM or at least every third refueling outage (whichever results in more frequent inspections). This minimum inspection frequency is unchanged from the current requirement in North Anna's technical specifications. The NRC staff finds that the wording changes in the sentence are of an editorial and clarifying nature and are not material, such that the current intent of the requirement is unchanged. Thus, the NRC staff concludes the first sentence of proposed Paragraph S.S.B.d.2 is acceptable.

3.7 Paragraph S.S.8.d.3 for plants with SGs with alloy 690 TT tubes The first sentence of Paragraph S.S.B.d.3 currently states:

If crack indications are found in any SG tube, then the next inspection for each SG for the degradation mechanism that caused the crack indication shall not exceed 24 effective full power months or one refueling outage (whichever is less).

- 10 Proposed Change: Revise this sentence as follows:

If crack indications are found in any SG tube, then the next inspection for each affected and potentially affected SG for the degradation mechanism that caused the crack indication shall not exceed 24 effective full power months or one refueling outage (whichever results in more frequent inspections).

The proposed change is replacing the words "for each SG" with words "for each affected and potentially affected SG." The licensee states that the existing wording can be misinterpreted. The licensee further states that the intent is that those SGs that are affected and those SGs that are potentially affected must be inspected for the degradation mechanism that caused the crack indication. However, some licensees have questioned whether the current reference to "each SG" requires only the SGs that are affected to be inspected for the degradation mechanism. The proposed revision is intended to clarify the intent of the requirement.

Assessment: Proposed changes in Paragraph 5.5.B.d.2 (Section 3.6) permits SG inspection intervals to extend over multiple fuel cycles for SGs with alloy 690 TT tubing, assuming that such intervals can be implemented while ensuring tube integrity is maintained in accordance with Paragraph 5.5.B.d. However, stress corrosion cracks may not become detectable by inspection until the crack depth approaches the tube repair limit. In addition, stress corrosion cracks may exhibit high growth rates. For these reasons, once cracks have been found in any SG tube, Paragraph 5.5.B.d.3 restricts the allowable interval to the next scheduled inspection to 24 EFPM or one refueling outage (whichever is less). The intent of this requirement is that it applies to the affected SG and to any other SG which may be potentially affected by the degradation mechanism that caused the known crack(s). For example, a root cause analysis in response to the initial finding of one or more cracks might reveal that the crack(s) are associated with a manufacturing anomaly which causes locally high residual stress which in turn caused the early initiation of cracks at the affected locations. If it can be established that the extent of condition of the manufacturing anomaly applies only to one SG and not the others, then the NRC staff agrees that only the affected SG needs to be inspected within 24 EFPM or one refueling cycle in accordance with Paragraph 5.5.B.d.3. The next scheduled inspections of the other SGs will continue to be subject to all other provisions of Paragraph 5.5.B.d. The NRC staff finds the proposed change to Paragraph 5.5.B.d.3 acceptable, because it clarifies the intent the paragraph.

3.B TS 5.6.7, "Steam Generator Tube Inspection Report" This specification lists items a. through h. to be included in a report which shall be submitted within 1BO days after the initial entry into MODE 4 following completion of an inspection performed in accordance with the TS 5.5.B, "Steam Generator (SG) Program."

Proposed Changes: Item b. currently reads: "Active degradation mechanisms found ... " to be revised to read: "Degradation mechanisms found ... "

Item e. currently reads: "Number of tubes plugged during the inspection outage for each active degradation mechanism ... " to be revised to read: "Number of tubes plugged during the inspection outage for each degradation mechanism ... "

- 11 Item f. currently reads, "Total number and percentage of tubes plugged to date ... " to be revised to read: "The number and percentage of tubes plugged to date, and the effective plugging percentage in each steam generator... "

Item g. currently reads, "The results of condition monitoring, including the results of tube pulls and in-situ testing, and ... " The proposed change makes this item the final of the list, replacing ", and" with a period.

Item h. currently reads: "The effective plugging percentage for all plugging in each SG," which will be deleted.

Assessment: This proposal would delete the word "Active" in items b. and e. above. Thus, all degradation mechanisms found, whether deemed to be active or not, would now be reportable.

The NRC staff finds the proposed change acceptable. The change in item g, and proposal to combine items f. and h. are editorial changes that do not materially change the reporting requirements. The NRC staff finds this change acceptable.

4.0 STATE CONSULTATION

In accordance with the Commission's regulations, the Virginia State official was notified of the proposed issuance of the amendment. The State official had no comments.

5.0 ENVIRONMENTAL CONSIDERATION

The amendments change a requirement with respect to installation or use of a facility component located within the restricted area as defined in 10 CFR Part 20. The NRC staff has determined that the amendments involve no significant increase in the amounts, and no significant change in the types, of any effluents that may be released offsite, and that there is no significant increase in individual or cumulative occupational radiation exposure.

The Commission has previously issued a proposed finding that the amendments involve no Significant hazards consideration, and there has been no public comment on such finding (77 FR 60155). Accordingly, the amendments meet the eligibility criteria for categorical exclusion set forth in 10 CFR 51.22(c)(9). Pursuant to 10 CFR 51.22(b) no environmental impact statement or environmental assessment need be prepared in connection with the issuance of the amendments.

6.0 CONCLUSION

The Commission has concluded, based on the considerations discussed above, that: (1) there is reasonable assurance that the health and safety of the public will not be endangered by operation in the proposed manner, (2) such activities will be conducted in compliance with the Commission's regulations, and (3) the issuance of the amendments will not be inimical to the common defense and security or to the health and safety of the public.

Principal Contributors: K. Hemphill, NRR R. Grover, NRR Date: January 28, 2013

'.. ML13018A140

~E LPL2-1IPM LPL2-11LA DIRS/ITSBlBC OGC NLO LPL2-1/BC LPL2-1/PM VSreenivas SFigueroa RElliolt BHarris RPascarelli VSreenivas IDATE 1/17/13 1/18/13 1/4113 1124/13 1/28/13 1128113