FINAL IPEC QUARTERLY LONG-TERM GROUNDWATER MONITORING REPORT QUARTERS ONE THROUGH FOUR 2011 (REPORT NO. 13)

INDIAN POINT ENERGY CENTER BUCHANAN, NEW YORK PREPARED FOR:

ENTERGY NUCLEAR NORTHEAST, INC.

INDIAN POINT ENERGY CENTER 450 BROADWAY BUCHANAN, NEW YORK 10511 ON BEHALF OF:

ENTERGY SERVICES, INC.

INDIAN POINT ENERGY CENTER 295 BROADWAY, SUITE 3 P.O. BOX 308 BUCHANAN, NY 10511-0308 PREPARED BY:

GZA GEOENVIRONMENTAL OF NEW YORK 104 WEST 29 TH STREET 10 TH FLOOR NEW YORK, NEW YORK 10001 SEPTEMBER 26, 2012 FILE NO. 01.0017869.92 Copyright © 2012 GZA GeoEnvironmental of New York GZA GeoEnvironmental, Inc.

ENT00575A Submitted: October 2, 2012

GZA Engineers and GeoEnvironmental, Inc.

Scientists Copyright 2012 GZA GeoEnvironmental, Inc.

104 West 29th Street 10th Floor New York, New York 10001 212-594-8140 FAX 212-279-8180 http://www.gza.com September 26, 2012 File No. 01.0017869.92 Mr. John Doroski Indian Point Energy Center 450 Broadway, Suite 3 P.O. Box 249 Buchanan, NY 10511-0308 IP3 Chemistry Re:

FINAL IPEC Quarterly Groundwater Monitoring Report Quarters One through Four 2011 (Report No. 13)

Indian Point Energy Center 450 Broadway Buchanan, New York 11501

Dear Mr. Doroski:

GZA GeoEnvironmental of New York (GZA) is pleased to provide this 2011 Quarterly Groundwater Monitoring Report for Indian Point Energy Center located at 450 Broadway, Buchanan, NY.

We trust that this information satisfies your present needs. Should you need any additional information, please do not hesitate to call us at (781) 278-3805.

Very truly yours, GZA GEOENVIRONMENTAL OF NEW YORK Josh Simpson Michael Powers, PE Engineer I Consultant/Reviewer David Rusczyk, PE Matthew J. Barvenik, LSP Senior Project Manager Senior Principal Attachments: 3 Copies

FINAL QUARTERLY LONG-TERM GROUNDWATER MONITORING REPORT Q1 THROUGH Q4 2011 (REPORT NO. 13)

September 26, 2012 Table of Contents 1 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 TABLE OF CONTENTS Page 1.0 EXECUTIVE

SUMMARY

..................................................................................................1-1 2.0 SCOPE OF WORK...........................................................................................................2-1 2.1 Groundwater Elevation Measurement....................................................................2-1 2.2 Monitoring Installation Sampling............................................................................2-2 2.3 Additional Monitoring Location Installation.............................................................2-3 2.4 Vapor Containment Building Foundation Drain Sampling......................................2-4 2.5 Proactive Mid-Quarter and Confirmatory Sample Collection..................................2-4 2.6 Preventative Maintenance.....................................................................................2-4 3.0 DATA EVALUATION........................................................................................................3-1 3.1 Groundwater Mass Flux Computation....................................................................3-1 3.2 Groundwater Sampling..........................................................................................3-2 3.2.1 Groundwater Sampling Results..................................................................3-2 3.3 Radionuclide Release Rates.................................................................................3-3 3.4 SSCs and Property Boundary Monitoring..............................................................3-4 3.4.1 Proactive Mid Quarter Samples.................................................................3-6 3.4.2 Previous Q4-2010 Investigation Level Exceedances..................................3-6 3.4.3 Q1 through Q4 2011 Boundary Investigation Levels..................................3-6 3.4.4 Q1 through Q4 2011 SSC Investigation Levels..........................................3-7 3.5 Plume Natural Attenuation Monitoring................................................................. 3-18 3.5.1 Unit 2 Tritium Plume Attenuation.............................................................. 3-20 3.5.2 Unit 1 Strontium Plume Attenuation......................................................... 3-23

4.0 CONCLUSION

S AND PLANNED FUTURE WORK.........................................................4-1

FINAL QUARTERLY LONG-TERM GROUNDWATER MONITORING REPORT Q1 THROUGH Q4 2011 (REPORT NO. 13)

September 26, 2012 Table of Contents 2 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 TABLES Table 1 Groundwater Sampling Methods, Equipment, Frequency, and Depths Table 2 Historic Quarterly Low Tide Groundwater Elevations Table 3-Q1 First Quarter 2011 Groundwater Analytical Results and Averages Table 3-Q2 Second Quarter 2011 Groundwater Analytical Results and Averages Table 3-Q3 Third Quarter 2011 Groundwater Analytical Results and Averages Table 3-Q4 Fourth Quarter 2011 Groundwater Analytical Results and Averages Table 4-Q1 2011 1st Quarter Groundwater Analytical Results and I.L.s Table 4-Q2 2011 2nd Quarter Groundwater Analytical Results and I.L.s Table 4-Q3 2011 3rd Quarter Groundwater Analytical Results and I.L.s Table 4-Q4 2011 4th Quarter Groundwater Analytical Results and I.L.s Table 5 Historic Groundwater Analytical Results FIGURES Figure 1 Site Location Plan Figure 2 Site Plan Figure 3 Lower Hudson Valley Geologic Map Figure 4 4th Quarter 2011 Current and Potential Future SSC Source Locations Figure 5A-Q1 1st Quarter 2011 Longterm Transducer Monitoring Evaluation Map Figure 5A-Q2 2nd Quarter 2011 Longterm Transducer Monitoring Evaluation Map Figure 5A-Q3 3rd Quarter 2011 Longterm Transducer Monitoring Evaluation Map Figure 5A-Q4 4th Quarter 2011 Longterm Transducer Monitoring Evaluation Map Figure 6-Q1 1st Quarter 2011 Rolling Average Tritium Activity Map Figure 6-Q2 2nd Quarter 2011 Rolling Average Tritium Activity Map Figure 6-Q3 3rd Quarter 2011 Rolling Average Tritium Activity Map Figure 6-Q4 4th Quarter 2011 Rolling Average Tritium Activity Map Figure 6A Temporal Trends in Unit 2 Rolling Average Tritium Activity Maps Figure 6B Unit 2 Leak Collection Device Evaluation 4th Quarter 2011 Figure 7-Q1 1st Quarter 2011 Rolling Average Strontium-90 Activity Map Figure 7-Q2 2nd Quarter 2011 Rolling Average Strontium-90 Activity Map Figure 7-Q3 3rd Quarter 2011 Rolling Average Strontium-90 Activity Map Figure 7-Q4 4th Quarter 2011 Rolling Average Strontium-90 Activity Map

FINAL QUARTERLY LONG-TERM GROUNDWATER MONITORING REPORT Q1 THROUGH Q4 2011 (REPORT NO. 13)

September 26, 2012 Table of Contents 3 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 Figure 7A Sr-90 Baseline Analysis-Unit 1 Defueling Evaluation 4thQuarter 2011 Figure 8-Q1 1st Quarter 2011 Rolling Average Cesium, Cobalt, and Nickel Activity Map Figure 8-Q2 2nd Quarter 2011 Rolling Average Cesium, Cobalt, and Nickel Activity Map Figure 8-Q3 3rd Quarter 2011 Rolling Average Cesium, Cobalt, and Nickel Activity Map Figure 8-Q4 4th Quarter 2011 Rolling Average Cesium, Cobalt, and Nickel Activity Map APPENDICES Appendix A:

Limitations Appendix B:

2011 Transducer Installation Logs Appendix C:

2011 Chains of Custody Appendix D:

2011 Sampling Data Sheets Appendix E:

2011 Mid-Quarter Sampling Data Sheets Appendix F:

Q4 2011 Dose Calculations Appendix G:

Q4 2011 Unit 2 Tritium Plume Trend Analyses Appendix H:

Southern Boundary Wells Appendix I:

MW-68 Borehole, Well Completion and Geophysical Logs Appendix J:

Q4 2011 Unit 1 Strontium Plume Trend Analysis

FINAL QUARTERLY LONG-TERM GROUNDWATER MONITORING REPORT Q1 THROUGH Q4 2011 (REPORT NO. 13)

September 26, 2012 Page 1-1 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 1.0 EXECUTIVE

SUMMARY

On behalf of Entergy Nuclear Northeast, Inc., GZA GeoEnvironmental of New York (GZA) has completed the Q1 through Q4 2011 quarterly groundwater monitoring for the Indian Point Energy Center (IPEC), culminating in this report1. Interpretations of the monitoring data have been made in the context of the current Conceptual Site Model2 (CSM). Development of this model began at the outset of the site investigations and has been iteratively enhanced as subsequent data has become available, in part through quarterly monitoring. The report has been written with a focus on the subject four quarters of 2011 data. Relationships to prior data, more in-depth technical explanations and exceptions to generalized statements and conclusions have typically been explained in the footnotes. This report format was chosen to allow efficient assimilation of the most current data and analyses by those already familiar with the project.

The footnotes contain important information and should be carefully read by all, but particularly by those less familiar with the technologies involved and the project history. It is further noted that the analyses and conclusions presented in this report are based on the data and information available up to and including Q4 2011. Data that becomes available after the subject quarter (Q4 2011), but before the finalization date of the report, will be sequentially reflected in associated subsequent reports.

Consistent with our interpretation of earlier data, and based on the 2011 quarterly groundwater sampling data, GZA concludes that groundwater contaminants continue to migrate toward the Hudson River to the West, and have not migrated off the Site to the North, East or South.

Radionuclide activities measured during each 2011 quarter were combined with the four previous quarterly and post-quarterly data sets to compute yearly rolling average groundwater activities for each quarter. For Q4 2011, these data were multiplied by the associated individual zone-specific groundwater flux values, derived from the Precipitation Mass Balance Model3, to compute yearly average radionuclide release rates to the Discharge Canal and Hudson River.

The CSM, upon which this radionuclide dose computation is based, continues to be validated through: (1) groundwater elevation data downloaded quarterly from a focused set of transducer-monitored well installations; (2) the behavior of both the Unit 1 Strontium plume and the Unit 2 Tritium plume as evaluated each quarter; and (3) the behavior of the recent Unit 1 and Unit 3 Tritium plumes, as discussed further in this report. These data, in our opinion, continue to support the use of the current CSM as a basis for Long Term Monitoring Program design.

The 2011 quarterly data further support the conclusion that the overall Tritium activity in the Unit 2 plume is generally showing a historically decreasing trend, from both qualitative and quantitative perspectives4. These overall reductions are seen on Figure G-17, where the total 1The plume and data analyses discussed in this report reflect data available through the Q4 2011 quarterly monitoring round.

2The formulation and basis for the overall CSM and the Precipitation Mass Balance model are presented in the Hydrogeologic Site Investigation Report, January 7, 2008, prepared by GZA GeoEnvironmental, Inc, on behalf of Enercon Services, Inc., for Entergy Nuclear Northeast, Indian Point Energy Center, 450 Broadway, Buchanan, NY 10511.

3Refer to Appendix H of the Quarter 2 2009 Quarterly Long-Term Groundwater Monitoring Report for discussion of the recalibration of the Precipitation Mass Balance Model. Precipitation and groundwater elevation data were collected onsite between 2007 and 2009 and used to compute groundwater fluxes across the site. Based on analyses of these data, it was concluded that this data set sufficiently encompassed the historical variability in groundwater elevation and flux response to seasonal and yearly precipitation variability. Therefore, maximum onsite groundwater fluxes were calculated from the elevation data, and used to conservatively recalibrate the Precipitation Mass Balance Model, as discussed and employed in the Q2 2009 Quarterly LTM Report.

4A slightly increasing to stable trend in the overall Tritium activity was observed between Q4 2009 and Q2 2011 due to the Q4 2009 transient surface spill from the rented RWST/R.O. processing skid. The most recent quarterly data sets (Q3 2011 and Q4 2011) demonstrate a re-establishment of the overall historical decreasing trend of the total Unit 2 Tritium plume activity, with the dissipation of the R.O. skid spill (see Figure G-17). Further discussion on the transient RWST/R.O. skid spill can be found below and in the Q4 2009 Quarterly Monitoring Report.

Section 1.0 Executive Summary September 26, 2012 Page 1-2 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 Tritium activity has decreased by approximately 55% since Q2 2007, and by 91% when compared to the bounding level Tritium activities. This overall trend is also evident on Figures 6-Q1 through 6-Q4 and 6A, where the shaded plume5 no longer extends downgradient to the river, as first observed in the Q2 2009 data. It is further visually evident from Figure 6A that the core of the plume has also shown a marked decrease in activity and extent over time in the vicinity of MW-111. These findings are consistent with our CSM, which anticipates overall decreasing trends in Tritium activity.

Consistent with one of the purposes of this Report, we also point out and explain data which, when first considered, may initially appear inconsistent with the assumptions used to develop the CSM. Such examples, where Tritium has increased in recent quarters, include:

Beginning in Q2 2011, uncharacteristic increases in Tritium activity were noted in several monitoring installations located on the south side of Unit 1; whereas the Unit 2 Tritium plume is confined to Unit 2 and areas north of the Unit 1 Containment Building. Given that groundwater cannot flow from Unit 2 to this southern area of Unit 1, it was judged likely that a spill had recently occurred and investigations were therefore initiated.

More specifically, the Tritium activity in the deeper sampling intervals directly to the south and southwest of the Unit 1 Containment Building (MW-47-80 and MW-56-83, respectively) increased markedly relative to typical historical levels for these monitoring locations. Also beginning in Q2 2011, a distinct increase in Tritium activity was observed in monitoring installation MW-39, located upgradient/cross-gradient of Unit 1 in the northern portion of Unit 3. Subsequently, monitoring installations located further downgradient (e.g. MW-54, MW-50 and MW-49) exhibited Tritium activity increases in Q3 2011 and Q4 2011, as the perturbation moved through these locations.

The above cited increases in Tritium activity are likely related to a transient CSB Sample Sink Overflow6 observed in the Unit 1 Chemical Systems Building (CSB) in April 2011.

See Figure 6-Q2 and Section 3.4.4 below for further discussion on this identified source and the associated likely migration pathways.

Coincident with the above discussed Unit 1 Tritium increases, a number of wells located further south in Unit 3 (e.g., MW-41, 44, 45, 46) also peaked to uncharacteristically high Tritium levels at the same time. Notwithstanding the temporal connection, and in part because these wells are located on the other side of a groundwater mound from Unit 1 (and MW-39), it is believed that these Unit 3 Tritium increases are not due to the above Sample Sink Overflow, but rather are associated with the washout7 entering Manhole A2 (MH-A2) from the Fuel Storage Building (FSB) roof drain when the vent fan was 5The plume shading on Figure 6 demarks the estimated boundary that separates Tritium levels greater than 5,000 pCi/L from those below this value, and provides a reasonable demarcation level for illustrating plume geometry and temporal variation. Although, this value equates to one-quarter of the drinking water standard for Tritium, GZA emphasizes that drinking water standards (USEPA MCLs) do not apply to the IPEC property given that there are no drinking water sources on or proximate to the site. Where yearly rolling average radionuclide activity data were available for multiple depths at a given location, GZA used the highest value to develop plume delineations. This is a typical approach to conservatively represent three-dimensional contaminant data sets on two-dimensional maps.

6Note that, as further discussed in Section 3.4.4, this release includes the sink overflow, as well as a previously contained pipe leak, all of which flowed into a compromised floor drain. These multiple facets of this release are all associated with the distillate tank waste processing system located in the Unit 1 CSB, and are termed the CSB Sample Sink Overflow.

7The term washout, as used herein, is the process by which Tritiated water vapor is transformed into Tritiated water as a liquid. In general, this transformation is driven by condensation (as is the primary underlying driver associated with MH-A2, above) and/or Tritium diffusion from the Tritiated water vapor into precipitation (rain and/or snow), either while it is still falling or after deposition.

Section 1.0 Executive Summary September 26, 2012 Page 1-3 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 generally not operating8 (see Section 3.4.4 below, and the Q4 2010 quarterly report for further discussion of the washout releases from the FSB roof drain to MH-A2).

Transient Tritium peaks above historical baseline in MH-A2 were initially observed in Q2 of 2009, with more elevated Tritium activity becoming evident between September 2010 and July 2011. These more recent data clearly demonstrated that the Tritium activity within MH-A2 is directly proportional to the discharge from the FSB roof drain when the vent fan was out of service. The vent fan was placed back in service on July 21, 2011, after which the Tritium activity rapidly9 returned to baseline conditions (<2,000 pCi/L) within the FSB roof drain and MH-A2.

The greater response of the proximate groundwater monitoring wells, as compared to that observed during previous MH-A2 Tritium increases, is believed due to the coincident Unit 3 outage. During an outage, the reactor cavity is open and pool temperature becomes significantly elevated, both resulting in greater evaporative losses, and thus greater likely washout impacts. Based on these investigations and associated data collected, it has been concluded that the elevated Tritium levels detected in MH-A2, as well as the proximate and downgradient monitoring wells (MW-41-40, MW-44-66, MW-45-42 and MW-46) and manhole B-1, are due to the FSB roof condensate generated while the vent fan was not operating and, as such, do not indicate a new leak from a System, Structure or Component (SSC). Moreover, the vent fan has been replaced and the subsequent data show this issue to have been rectified (see Section 3.4.4 below for further discussion).

Subsequent to the relatively small, singular peak noted in MH-5 VCFD for the first time in Q3 2010, more elevated peaks in Tritium activity have been observed throughout 2011, where the maximum activity was multiple times higher than the Q3 2010 peak10. Due to these peaks in Tritium activity, the sampling frequency for MH-5 VCFD was increased from quarterly to weekly, including flow rate measurements. This more intensive sampling regimen was initiated in June 2011 to further support an investigation to identify the ultimate cause of these elevated Tritium levels, which is now more focused on potential process inputs such as Tritium contribution from plant/FSB vent condensate (see Figure 6B and Section 3.4.4, MH-5 VCFD below for further discussion). Based on these additional 2011 data, the Tritium peaks in MH-5 VCFD do not appear to be correlated with the recent increase in flow rate in the LCD, nor do they appear to foreshadow increases in the monitoring wells proximate to the Unit 2 SFP11.

During 2011, the flow rate into the Leak Collection Device (LCD) fluctuated between approximately 0.7 and 2.5 liters/day from March 2011 to September 2011, compared to a historical baseline flow rate of <0.02 L/day12. The LCD flow rate then gradually 8It is noted that the Tritiated water vapor evaporating from the SFP is a permitted release through the Plant Vent located atop the VC building.. Analyses were conducted to account for this release to the FSB roof in the dose computations. This same Tritium has therefore been double counted because it is again included in the storm drain and groundwater portions of the dose computations.

9A MH-A2 sample was collected only 7 days after the vent fan was placed back in service (7/28/2011) and the Tritium activity in the sample was 3,140 pCi/L, approximately 30 times lower than the average Tritium activity from September 2010 to July 21, 2011.

Subsequent samples showed further decreases.

10It is noted that the water collected by the MH-5 VCFD is routed to the discharge canal where it is released as a monitored discharge. As a monitored discharge, this Tritium activity is directly accounted for in the dose computations.

11Review of Figure 6B, which includes four additional quarters of data (relative to that presented in the previous Q4 2010 report),

demonstrates that the Tritium peaks observed in MH-5 VCFD (as well as those observed in the proximate the monitoring wells) are not convincingly correlated with the increased flow rates in the LCD. Therefore, the conjecture that these data were potentially correlated, as hypothesized in both the Q3 and Q4 2010 reports, appears to be less likely the case given the additional data. As such, the Tritium peaks observed in the monitoring point data, particularly that from MW-31 and MW-32, appear to be more likely the result of the subsequently discussed transient surfaces spills as well as the Retention Mechanisms.

12All of the water collected by the LCD is fully contained and does not enter the groundwater regime (see below).

Section 1.0 Executive Summary September 26, 2012 Page 1-4 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 decreased to approximately 0.5 L/day between September 2011 and December 201113, but still remained well above the historical baseline collection rate.

A previous, clear increase in the daily volume of water collected by the LCD was also observed in Q3 2010, with an average flow rate of approximately 1.5 L/day. However, this increase was followed by a rapid return to baseline conditions in October 2010, and the LCD flow rate remained at those baseline conditions during Q4 2010. Previous investigations indicated that the increased flow observed in Q3 2010 was potentially correlated14 with the timing of atypically elevated water in the fuel pool associated with dry cask work. Following the limiting of these increases in pool water elevation, a marked decrease was observed in the LCD flow rate throughout Q4 2010.

With the resumed increased LCD flow, further investigations by GZA and Entergy in Q1 2011 and Q2 2011 identified a number of existing light outlet boxes, welded to the inside liner of the fuel pool, as potential locations where pool water could get through the liner during high water levels (i.e., above the designed high water level of the pool). Earlier investigation into the light outlet boxes, through examination of design drawings, indicated that the light boxes were unlikely to be a leak point because the electrical conduits which sourced the boxes were routed up the pool wall, connected to conduits above the top of the pool, and did not penetrate the liner. However, subsequent visual investigations, as confirmed by further plant drawings, identified locations where an alternative design was employed so the conduits sourcing the boxes would not interfere with the crane rail at the top of the pool. In these specific cases, the conduits did penetrate the liner. Following subsequent invasive inspections of the light boxes, it was concluded that there is definitive indication that these specific boxes did contribute, at least in part, to the LCD flow rate under transient overfill conditions. This conclusion is based on the finding of boron precipitate within the boxes and conduit penetrations.

See Section 3.4.4 below for further discussion of the construction and planned permanent sealing of these light boxes.

Given the increased 2010 and 2011 LCD flow rate observations, Figure 6B has been included in this report to visually present both the historical LCD flow rate data and the Tritium data for the monitoring installations located within the Unit 2 Tritium plume. In this regard, it is first emphasized that all water collected in the LCD is captured, measured and disposed of as a monitored release, and does not enter the groundwater system. Further, review of Figure 6B, which includes four additional quarters of data (relative to that presented in the previous Q4 2010 report) demonstrates that the increased flow rates in the LCD are not convincingly correlated with the peaks in the monitoring wells or MH-5 VCFD. Therefore, the conjecture that these data were potentially correlated, as hypothesized in both the Q3 and Q4 2010 reports, now appears to be less likely the case given the additional data. As such, the Tritium peaks observed in the monitoring point data, particularly that from MW-31 and MW-32, appear to be more likely the result of the subsequently discussed transient surfaces spills (see below), as well as the Retention Mechanisms15 associated with the historical releases and these more recent spills. Therefore, we found no conclusive evidence for new, 13It is noted that the LCD flow rate actually increased from approximately 0.5 to 0.9 L/day between December 21, 2011 and the end of the year.

14While the data trends appear to correlate, it is noted that simple correlation does not demonstrate causation.

15Peaks in Tritium activity have been observed in multiple sampling ports of MW-31 and MW-32 since Q1 2009 and to a lesser extent since monitoring began. This long-term variability appears to be consistent with episodic releases of Tritium historically stored in the subsurface via natural and anthropogenic Retention Mechanism(s). This conclusion is further supported by the tracer data and other analyses discussed in Section 3.6 of the Q1 2009 Long Term Monitoring Report. The original discussion of these Retentions Mechanisms can be found, along with the CSM, in the previously cited Hydrogeologic Site Investigation Report.

Section 1.0 Executive Summary September 26, 2012 Page 1-5 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 unidentified leaks in the Unit 2 SFP or other monitored Unit 2 SSCs that have released radionuclides to the groundwater system during 2011.

The recent LCD data are discussed in more detail in Section 3.4.4 below.

While Retention Mechanisms clearly appear to impact Tritium activity as referenced above, more noticeable increases in Tritium levels in several MW-31 and MW-32 sampling intervals were observed during the Q1 2010 through Q3 2010 sampling events, where Tritium activities peaked within multiple intervals at the highest recorded historical levels. These elevated Tritium activities were likely related to a Q4 2009 surface spill, located proximate to these wells, from a temporary rental RWST/R.O. processing skid16, which was first detected during routine 80-1017 sampling of MH-9 in mid-January 2010.

Due to the short duration of the elevated Tritium activity measured at the release point in MH-9 and the transient nature of this surface spill, it was anticipated that the elevated Tritium levels would dissipate in these monitoring locations once this pulse input migrated downgradient. As expected, the Tritium activity at these upgradient monitoring locations generally decreased to the typical historical Tritium levels by Post-Q1 201118.

Furthermore, sampling intervals further downgradient (e.g. MW-36-41, MW-37-40) also returned to typical historical Tritium activities by Q4 2011, in response to the dissipation of the RWST/R.O. spill. As such, the transient release from the RWST/R.O. appears to have generally dissipated through the system19, as seen in Figure G-17 which shows clear reductions in Unit 2 total plume Tritium activity during Q3 2011 and Q4 2011.

Moreover, as a proactive response to this spill, Entergy has made modifications to plant systems and operational procedures to allow the RWST/R.O. processing skid to be positioned inside the Unit 2 MOB for all future outages. These operational modifications were implemented based, in part, on the findings of the Long Term Monitoring Program as a measure to reduce the potential for future spills.

The overall Sr-90 activity within the Unit 1 plume had generally been stable to decreasing in response to the West Pool demineralization operations conducted by Entergy beginning in 2006. However, the final defueling of the Unit 1 SFPs, completed in Q4 of 2008, resulted in a noticeable increase in Strontium activity proximate to the SFPs, followed by downgradient increases (see Figures 7-Q1 through 7-Q4 and 7A). This was expected given the requirement to temporarily raise the pool levels for fuel rod removal, thus increasing leakage rate from the SFPs20. As expected, Strontium levels have decreased since the completion of defueling. The Unit 1 total plume Strontium activity has, on average, decreased by nearly 70% relative to peak defueling levels, and approximately 20% relative to pre-defueling levels (see Figure J-1, Appendix J). More proximate to the pool, the Strontium activity has decreased to an even greater degree. In fact, the Q4 2011 Strontium activities at the majority of these near-pool monitoring locations (e.g. U1-NCD, MW-42-49, U1-SFDS, U1-CSS) were approximately 80-98%

lower than the average pre-defueling levels. The Strontium activity further downgradient of the pool generally exhibited decreasing trends approaching pre-defueling levels (MW-37, MW-55) 16This transient and localized surface spill involved a rented RWST/R.O. processing skid brought on-site by an outside contractor during the Unit 2 outage. As such, this equipment is not an in-place Unit 2 SSCs and is no longer on site.

17NRC Inspection Enforcement Bulletin (IEB) 80-10, Contamination of Nonradioactive System and Resulting Potential for Unmonitored, Uncontrolled Release of Radioactivity to Environment, May 6, 1980.

18Only one sampling interval, MW-32-85, at these monitoring locations did not yet return to the historical baseline by Post-Q1 2011.

A slightly elevated Tritium activity was noted in this sampling interval until Q3 0211. It is also noted that the 2010 Tritium Investigation Level was not exceeded at MW-32-85 from Q1 2010 through Q4 2011.

19Also note that the transient RWST/R.O. skid spill potentially replenished the Retention Mechanism storage. Therefore, future releases from Retention Mechanisms could still be seen in future quarters.

20As of late 2008, all the fuel rods have been removed from the Unit 1 SFPs and the pool water has been drained. As such, the Unit 1 SFPs is no longer an active source of radionuclides to the subsurface.

Section 1.0 Executive Summary September 26, 2012 Page 1-6 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 or decreased to pre-defueling levels (MW-36, MW-49, MW-50, MW-54, MW-57) in recent quarters; however, Strontium increases were noted in a few downgradient sampling intervals (e.g. MW-50-42, MW-53-120 and MW-55-24) during Q3 and Q4 2011. Strontium peaks were observed in both downgradient riverfront wells (MW-66-36 and MW-67-39) during 2011 as this input moved towards the river. It is expected that the downgradient, riverfront wells will also fully return to pre-defueling levels once this transient perturbation has passed through the groundwater flow system. It is anticipated that this flushing mechanism will be protracted given the impact of partitioning on Strontium levels in the groundwater.

Based on the data and analyses provided herein, our conclusion is that the Unit 2 Tritium and Unit 1 Strontium plumes have both been undergoing overall long-term reductions in activity after the respective source interdictions. Given this conclusion, and the recognition that Entergy terminated all previously identified leaks in the Unit 2 SFP21, will permanently seal the light boxes, and has decommissioned the Unit 1 SFPs, these plumes satisfy the requirements for Monitored Natural Attenuation (MNA), the remedial technology selected for the IPEC Site.

However, it is also concluded that, while a portion of the leakage from the above cited localized, transient spills traveled directly to the saturated groundwater regime and resulted in the observed transient peaks in radionuclide levels, additional portions of these releases likely remain above the water table as recharge to the various Retention Mechanism(s). This additional unsaturated zone source recharge will likely be manifested in the future as additional non-specific peaks in radionuclide levels due to episodic releases to the groundwater flow regime from these mechanisms (e.g., from intense/prolonged precipitation events). These localized release events also interfere with the goal of resetting Site Investigation Levels (I.L.s);

updating of Strontium I.L.s must therefore await full return to the original Strontium baseline levels existing prior to Unit 1 defueling in the downgradient wells (i.e. MW-37-40, MW-50-42, MW-55-24), and additional seasonal data is required to better assess Tritium response to precipitation-driven Retention Mechanism release variability. Therefore, the ultimate confirmation of the above conclusions will require monitoring over a number of years so as to allow ranges in seasonal variation to be adequately reflected in the monitoring data and thus demonstrate the rate of continued depletion of Tritium and Strontium from the Retention Mechanism(s). It is important to recognize that, even with these localized, transient spills, the amount of radionuclides being released through the groundwater pathway is still small compared to permitted levels of Tritium discharge to the river through the Discharge Canal.

In summary, based on the data collected to date and the apparent strength of the CSM to evaluate that data, we believe all Program Objectives (see Section 3.0) are being met. These objectives are consistent with and fully encompass the guidance provided in the NEI Groundwater Protection Initiative (GPI). In addition, given the robustness of the monitoring network and the overarching Long Term Monitoring Program, particularly as further data sets are collected, it has become a valuable tool for identifying existing equipment and/or operational procedures that can be upgraded to prevent future radionuclide releases/spills.

21Further justification for this conclusion can be found in Section 3.6 of the Q1 2009 Quarterly Monitoring Report as well as the Hydrogeologic Site Investigation Report. The Q1 2009 Report summarizes additional, more quantitative analyses which were completed to further investigate the integrity of the Unit 2 SFP. However, given the current behavior observed in the Unit 2 LCD data (see Section 3.6 of the Q1 2009 Long Term Monitoring Report and Section 3.4 of this report) even following the temporary sealing of the light boxes, additional investigations/data evaluations are underway to further rule out potential Unit 2 SFP leak mechanisms. In this regard, it is noted that these analyses cannot definitively and completely rule out the possibility of a remaining small leak which could then also be supplying Tritium to the groundwater flow regime in addition to the Retention Mechanism(s) and surface spill from the process skid discussed above. While it is not possible to quantify the size of the minimum detectable leak with any degree of certainty, we believe that the maximum leak rate from the Unit 2 SFP that could potentially remain undetected by the groundwater monitoring system is less than 10 to 30 gpd (0.007 to 0.021 gallons per minute). It is also likely that if a small leak exists in the Unit 2 SFP liner, it should not get worse with time. This opinion is based on liner evaluations previously conducted by Entergy. It is further emphasized that while a leak of more than 0.02 gallons per minute should be large enough to be readily detectable with the existing Long Term Monitoring Program; this amount of Tritium release to the river is still small (<0.01%)

compared to permitted levels of Tritium discharge to the river through the Discharge Canal.

FINAL QUARTERLY LONG-TERM GROUNDWATER MONITORING REPORT Q1 THROUGH Q4 2011 (REPORT NO. 13)

September 26, 2012 Page 2-1 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 2.0 SCOPE OF WORK During each quarter in 2011, GZA performed groundwater monitoring at IPEC in Buchanan, New York (Site) as part of IPECs overall Long Term Groundwater Monitoring Program (LTMP) at the Site22. The overall foundation for the development and execution of this LTMP is based on the CSM, a description of which is contained within GZAs Hydrogeologic Site Investigation Report23. The scope of work completed for this years monitoring is described in the Sections below. Refer to Figures 1 and 2 for a Site Location Plan and Site Plan. Figure 3 provides a Lower Hudson Valley Geologic Map and Figure 4 summarizes Current and Potential Future SSC Source Locations through Q4 2011.

2.1 Groundwater Elevation Measurement GZA maintains a network of long-term monitoring transducers and dataloggers as part of the instrumentation located across the Site. These instruments record groundwater elevation and temperature measurements at regular time intervals24, which are then downloaded on a quarterly basis25. Transducer installation logs are presented in Appendix B.

During the quarterly sampling, GZA downloaded groundwater elevation data from the long-term monitoring transducers, which collected data over the entire duration of the quarter. The low-tide groundwater elevation data during each quarter of 2011 from these 22 transducers are presented in Table 2 and compared to historical minimum and maximum values on the four Figure 5As (5A-Q1 through 5A-Q4)26 included in this report.

The Q1 2011 low-tide groundwater elevation was recorded on January 22, 2011 and the data at four locations (five transducer intervals) were outside 30% of the Q2 2007 through Q2 2009 range. One of these locations (two transducer intervals) is a Unit 2 riverfront well where the maximum deviation was less than one foot in elevation. Both of these intervals (MW-67-39 and MW-67-340) also: (1) recorded a deviation of similar magnitude during the previous, Q4 2010, quarter; and (2) malfunctioned in the following, Q2 2011, quarter. Even with these potential equipment malfunctions, the overall horizontal and vertical gradients are still consistent with 22Refer to the Quarterly Long-Term Groundwater Monitoring Report Q2-Q4 2007 (Report No. 1), dated May 2008 for Site background information and a description of the environmental setting.

23Hydrogeologic Site Investigation Report, January 7, 2008, prepared by GZA GeoEnvironmental, Inc, on behalf of Enercon Services, Inc., for Entergy Nuclear Northeast, Indian Point Energy Center, 450 Broadway, Buchanan, NY 10511.

24Currently, transducers record groundwater elevation and temperature readings on a 20 minute time interval so as to allow capture of tidal variability. An original, more extensive network of pressure transducers provided critical data inputs for the development of the CSM and the computation of yearly radiological dose to the Hudson River. Over the first nine quarters of the LTM program (Q2 2007 through Q2 2009) sufficient data was collected from this more extensive network of transducers to capture groundwater elevation response to seasonal and yearly precipitation variability. Therefore, starting with the Q3 2009 quarterly report, the transducer monitoring program was refocused on a select subset of locations to routinely monitor the on-Site groundwater conditions going forward. These locations were selected to provide the data required to document that groundwater flow conditions remain consistent with the CSM, thus demonstrating the veracity of the subsequent dose computations. The rationale for the specific locations and depths included in the LTMP transducer redeployment are provided in Appendix K of the Q1 2009 Quarterly Monitoring Report (Report No.5), dated July 2, 2010 and Appendix J of the Q2 2009 Quarterly Monitoring Report (Report No.6).

25With regard to these ongoing long term monitoring locations, it is noted that the transducers have a limited life. While some of the transducers can be replaced, and have been replaced in the past, others are permanently installed in the subsurface and are no longer accessible for replacement. However, with time, the base of data upon which model validity is assessed becomes increasingly more robust. Therefore, if some of these transducers fail over time, it is not likely that replacement will be imperative.

This is because the likelihood of encountering a precipitation event substantially outside the already captured range becomes increasingly more remote with time as more data are collected. In addition, it is again emphasized that considerable conservatism has been incorporated within the model development and the dose rates computed are still far below those permitted by regulation.

26Figure 5, which previously presented shallow and deep groundwater contours, can be found in quarterly reports prior to, and including Q2 2009. This figure is no longer required given that sufficient quarterly contour data has already been obtained (See the Q2 2009 Quarterly Monitoring Report for further analysis).

Section 2.0 Scope of Work September 26, 2012 Page 2-2 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 groundwater elevation data from previous quarters. Another location (MW-30-69) deviated by less than 0.1 feet from the 30% criteria; as such, the vertical and horizontal groundwater gradients showed no substantial variations in the Unit 2 power block area of the plant. The final two locations (MW-43-28 and MW-51-40) are both located to the south of Unit 3, and MW-51 represents an on-site boundary well. The groundwater elevation in MW-51 was lower than the 30% criteria by approximately 2 feet, while the groundwater elevation in MW-43 was approximately 3 feet greater than the 30% criteria. Even though these deviations were observed, the groundwater elevation in MW-43 was still lower than MW-51, indicating no alteration in the overall groundwater flow direction towards the power block area of the plant.

Additionally, the overall vertical gradients at both locations were still consistent with the historical data.

The Q2 2011 low-tide groundwater elevation data were recorded on May 25, 2011 and the data at two locations (three transducer intervals) were outside 30% of the Q2 2007 through Q2 2009 range. One of these locations (two transducer intervals) is a Unit 2 riverfront well where the deviation was greater than the 2007 through 2009 criteria by approximately one foot in elevation. However, these data points still represented the lowest groundwater elevations (other than the river location, HR-1) of all the long-term monitoring transducer locations, and thus still demonstrate that groundwater flows towards the Hudson River. The final interval showed a deviation of less than 0.1 feet from the Q2 2007 through Q2 2009 criteria.

The Q3 2011 low-tide groundwater elevation data were recorded on August 22, 2011 and the data at three locations were outside 30% of the Q2 2007 through Q2 2009 range. All three of these intervals were within 1.5 feet of the 30% criteria; as such, the overall groundwater gradients (both horizontal and vertical) were not substantially altered across the site based on the Q3 2011 transducer data.

The Q4 2011 low-tide groundwater elevation data were recorded on November 21, 2011 and the data at three locations (four transducer intervals) were outside 30% of the Q2 2007 through Q2 2009 range. One of these monitoring locations (two transducer intervals) is the same Unit 2 riverfront well (MW-67) that recorded deviations from the 30% criteria in Q4 2010 and Q1 2011.

The Q4 2011 groundwater elevations are consistent with these recent results and the overall horizontal and vertical gradients are still similar to historical data. The remaining two transducer intervals showed a deviation of less than 0.5 feet from the Q2 2007 through Q2 2009 criteria, resulting in no overall alterations to groundwater flow direction.

Therefore, these 2011 groundwater elevation data show no alterations in overall groundwater flow direction and no substantial variations in the overall horizontal and vertical groundwater gradients. As such, these data demonstrate that substantial variations to the observed flow field have not occurred. These data thus further validate the applicability of the Precipitation Mass Balance Model (PMBM) for use in subsequent radiological dose computations - see Section 3.1.

2.2 Monitoring Installation Sampling During each quarter in 2011, GZA collected groundwater samples for radionuclide analysis from scheduled sampling intervals within select monitoring installations (wells) as shown in Tables 3-Q1 through 3-Q4. Chains of Custody for these samples are presented in Appendix C. GZA also collected additional groundwater sample volumes to provide aliquots to the NYDEC in Q2 2011.

Section 2.0 Scope of Work September 26, 2012 Page 2-3 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 GZA used a number of different types of pumping equipment depending upon the sampling method and the characteristics of the individual monitoring installation27. Table 1 lists the monitoring installations sampled, the sampling depths and elevations within sampling installations, and the sampling method and equipment used.

In general, GZA implemented two basic methods of sampling to collect representative groundwater samples: the Low Flow method and a modified well volume purge method. The Low Flow method allows collection of representative groundwater samples from discrete sampling zones within a monitoring installation, while limiting the accumulation of wastewater28.

As agreed by Entergy Nuclear Northeast, the NRC, NYSDEC, and GZA, the modified traditional purge method29 allows for the collection of a representative groundwater sample from a monitoring installation after purging 1.5 volumes of water30. We implemented this method in wells where low flow sampling was not practical. Sampling Data Sheets summarizing water quality data and sampling information are presented in Appendix D.

With all of the above sampling methods, GZA used dedicated sampling equipment, including polyethylene and/or nylon tubing and submersible electric pumps to the extent practical. The use of dedicated sampling equipment limits the possibility of cross-contamination between monitoring installations and/or individual multi-level samples within a single installation. Refer to Table 1 for a summary of the sampling methods, equipment, frequency, and depths employed during this quarters groundwater monitoring round.

2.3 Additional Monitoring Location Installation In October 2011, GZA began the installation of an additional multi-level monitoring installation, designated MW-68, near the southwest corner of the Unit 3 Transformer Yard. Entergy authorized the construction of this monitoring location in order to increase the robustness of the Unit 3 well network and thus reduce risk of potential future Unit 3 releases going undetected.

After grouting 8 inch steel casing four feet into bedrock (top of bedrock was approximately 10 feet below ground surface (bgs)), PQ bedrock core samples were collected to 150 feet bgs, using 5 foot core runs. During borehole advancement, a GZA field engineer evaluated the rock cores and logged rock type/conditions.

Following advancement to 150 feet bgs, the borehole was developed through surging and pumping techniques in preparation for downhole geophysical testing. Due to an open fracture zone in the shallow bedrock, approximately 8,000 gallons of water were purged prior to adequate removal of fines/rock dust, which settled at the bottom of the borehole during the surging process31. After the borehole was developed, multiple downhole geophysical logs were completed, including: fluid resistivity, temperature, caliper, acoustic-televiewer (ATV), television, and heat pulse flow meter (both ambient and stressed) logs. The geophysical data were reviewed by GZA personnel and five sampling intervals were identified within the borehole. See Appendix I for the MW-68 geophysical logs.

27Refer to Section 4.3 of the Final 2007 Quarterly Long-Term Groundwater Monitoring Report No. 1, dated May 2008, for sampling method and equipment selection rationale.

28As described in: Low-Flow Sample Collection, GZA, 7/18/2007 29As described in: Modified Traditional Groundwater Sample Collection, GZA, 7/18/2007 30When external factors (such as well-surface-flooding from storm water runoff or overland flow of plant component leaks) might have infiltrated the top of the well and impacted ambient groundwater conditions at a specific sampling location, GZA typically purged three to five volumes of water (using the modified traditional purge method) prior to collection of a sample to attempt to obtain a representative groundwater sample.

31Approximately 4,700 gallons were introduced during coring activities. Following the initial surging, approximately 12 feet of fines/rock dust had settled into the bottom of the borehole. The apparent source of these fines was a 1.5-foot open fracture located approximately 25 feet below ground surface.

Section 2.0 Scope of Work September 26, 2012 Page 2-4 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 The borehole was subsequently over-reamed to 8 inches using rotary (spun casing) drilling techniques. Approximately 10,000 gallons of water were introduced during the reaming process due to the open, shallow bedrock fracture. The widened borehole was then developed a second time using surging and pumping techniques, and the volume of water introduced during over-reaming was purged from the hole. Following borehole development, four individual PVC monitoring wells (one containing two screens and an inflatable packer) were installed at varying depths based on the geophysical data. For additional information, the borehole and well completion logs are located in Appendix I. The monitoring well installation for MW-68 was completed on December 22, 2011. The initial MW-68 groundwater samples will be collected in Q1 2012 (following the appropriate stabilization time), and this monitoring installation will be sampled quarterly thereafter as part of the Long Term Monitoring Program in the future.

2.4 Vapor Containment Building Foundation Drain Sampling During 2011, GZA collected water samples from on-Site manholes MH-5 VCFD32, B-1 and B-6 to characterize discharge from foundation drains around and below the Unit 2 and 3 Vapor Containment Structures. These drains include both foundation drains around the building peripheries (curtain drains) as well as those around the sumps near the middle of the structures (reactor sump footing drains33).34 2.5 Proactive Mid-Quarter and Confirmatory Sample Collection In response to the 2010 Tritium peaks observed in multiple MW-31 and MW-32 sampling intervals (RWST/ R.O. skid spill), additional Post-Q1 2011 groundwater samples were collected at all active sampling intervals within these two monitoring locations (as well as MW-30).

Additional Post-Q2 2011 and Post-Q3 2011 groundwater samples were also collected at multiple locations in response to the recent Tritium peaks observed in several Unit 1 and Unit 3 monitoring locations (Unit 1 transient sink overflow).

The results of the confirmatory and mid-quarter samples are presented in Section 3.4 along with the quarterly data. Sampling Data Sheets summarizing water quality data and sampling information are presented in Appendix E.

2.6 Preventative Maintenance GZA performed general wellhead maintenance tasks, such as housekeeping of well vaults and roadboxes, and replacement of dedicated sampling equipment, tubing and transducers, as required.

32GZA collects the water sample from the vapor containment foundation drain (VCFD) input into this manhole and not the manholes sump. Thus, the MH-5 VCFD sample name.

33We could not verify that a foundation drain exists around the reactor sump in Unit 2. The assumption that it does exist is based on the plans for Unit 3 and the similarities in construction of both units.

34These two Unit 2 drains which discharge into MH-5 VCFD, along with similar drains for Unit 3 which discharge into Manholes B-1 and B-6, form an integral part of the early leak detection monitoring network. However, sampling from these three manholes has generally been problematic for a number of reasons, but particularly due to conflicts with plant security measures which mandate that the manhole covers be permanently welded shut. Some limited access has been reestablished by modifying the manhole covers to allow for a small access opening. However, for Manholes B-1 and B-6, this modification still limits the ability to routinely collect samples clearly representative of only the foundation drain discharges rather than the total flow through the storm drains.

The piping configuration in MH-5 does allow sampling specific to the foundations drains, hence the designation of this sample as MH-5 VCFD (i.e., Vapor Containment Foundation Drain). Further work is being undertaken on the manhole sampling systems in B-1 and B-6 to facilitate more representative sampling of these foundations drains.

FINAL QUARTERLY LONG-TERM GROUNDWATER MONITORING REPORT Q1 THROUGH Q4 2011 (REPORT NO. 13)

September 26, 2012 Page 3-1 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 3.0 DATA EVALUATION The Long Term Monitoring Program was designed to provide data to address four main objectives:

Monitor radionuclide activities and evaluate groundwater flow rate to both detect and characterize current and potential future off-Site groundwater contaminant migration to the Hudson River, both via direct groundwater discharge to the river and through infiltration into the Discharge Canal, from unplanned radionuclide releases of liquid effluents, so as to allow computation of potential radiation dose to the public from these releases; Monitor groundwater proximate to Systems, Structures and Components (SSCs) that exhibit a credible probability of resulting in a visually undetected release of radionuclides to the subsurface carrying an activity level of significance; Monitor groundwater along the property boundary to confirm that contaminated groundwater is not migrating off the property to locations other than the river; and Monitor the existing groundwater plumes identified on-Site to demonstrate overall reductions in total activity over time as is consistent with the requirements of Monitored Natural Attenuation (MNA)35, the selected remediation for the IPEC Site.

These objectives are consistent with and fully encompass the guidance provided in the NEI Groundwater Protection Initiative (GPI). In addition, given the robustness of the monitoring network and the overarching Long Term Monitoring Program, particularly as further data sets are collected, it has become a valuable tool for identifying existing equipment and/or operational procedures that can be upgraded to prevent future radionuclide releases/spills.

The following sections provide data analyses to address these four objectives.

3.1 Groundwater Mass Flux Computation As presented in the Hydrogeologic Site Investigation Report, the groundwater flow in both the upper and lower flow zones is toward the power block area from the North, East and South, with subsequent discharge to the Hudson River to the West. We estimate that groundwater flow associated with infiltration from the watershed may be as deep as 350 feet, but still ultimately discharges to the river. A corollary to this conclusion is that there is no groundwater flow, and thus no off-Site radionuclide migration, from the power block area to the North, East or South.

To estimate groundwater flow (i.e., groundwater mass flux) beneath the Site, a groundwater flow model was constructed based on a precipitation mass balance analysis. This analysis is based on the precept that, on a long term average, the groundwater flowing through and discharging from the aquifer is equal to the watershed infiltration recharge; this conclusion was reached because the only substantial source of recharge to the aquifer is areal recharge derived from precipitation. The previous sixteen year average for precipitation measured at the Site is approximately 37 inches per year. Based on a USGS infiltration study36, as well as the Precipitation Mass Balance Model (PMBM) calibration37, approximately 25 percent of the 35The selection of MNA as the remedial strategy for the Site is discussed further in the Hydrogeologic Site Investigation Report.

36USGS. Water Use, Ground-Water Recharge and Availability, and Quality of Water in the Greenwich Area, Fairfield County, Connecticut and Westchester County, New York, 2000-2002.

37The Precipitation Mass Balance Model (PMBM) was initially calibrated to groundwater fluxes based on a Darcys Law Model with groundwater gradients derived from Q2 2007 (June 1, 2007) low-tide groundwater elevation contours (initial reference data set).

Section 3.0 Data Evaluation September 26, 2012 Page 3-2 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 precipitation falling on pervious surfaces over the Site watershed area recharges the groundwater system via infiltration.

Since precipitation represents the driving variable for groundwater flux in the PMBM38, the yearly precipitation just prior to Q4 2011 (approximately 61 inches) was calculated and input into the recalibrated model to compute the flows used in the estimation of Q4 2011 dose values.

Based on the USGS study cited above, the aquifer recharge rate is therefore approximately 16 inches for the year prior to the Q4 2011 monitoring event. Applying this value to the pervious surfaces within the six individual groundwater flow zones shown on Figure 4, it is estimated that approximately 11 gpm of groundwater flowed into the Discharge Canal from the upper and lower zones during the previous year. In addition, approximately 17 gpm and 25 gpm of groundwater flowed into the Hudson River from the upper and lower zones, respectively. Storm water discharging into the Discharge Canal and directly into the Hudson River was estimated to be approximately 64 and 7 gpm, respectively. These flows are further subdivided into flow zones with the further detail shown in the table in Appendix F.

3.2 Groundwater Sampling The following sections describe the groundwater sampling results and associated QA/QC protocols.

3.2.1 Groundwater Sampling Results Groundwater samples collected on behalf of Entergy during each quarter in 2011 were analyzed at GEL Laboratories for Tritium, Sr-90, Cs-137, Co-60, and Ni-6339. Table 3-Q4 presents the analytical results for these radionuclides through the last quarter of 2011. The rolling yearly averages, which were calculated using all the valid data from Q1 2011 through Q4 2011, including Mid-Quarter and confirmatory samples, are also presented in Table 3-Q4. Table 4-Q4 presents minimum detection concentrations (MDC), standard deviation, and I.L.s assigned to each well for the Q4 2011 analytical results. Table 5 presents historical Site groundwater analytical data. Isopleth maps of Q4 2011 rolling averages for Tritium and Sr-90 are presented in Figures 6-Q4 and 7-Q4, respectively. Figure 8-Q4 presents a data map of Q4 2011 rolling The two models use different sets of input parameters which are not dependent on or related to each other. This calibration not only verified the reasonableness of the overall groundwater flow rates predicted by the PMBM, but also allowed further discretization of the groundwater flow into upper and lower flow zones as well as flow volumes upgradient and downgradient of the Discharge Canal.

After reviewing the groundwater elevation and precipitation data from the Indian Point meteorological station over the time period from Q2 2007 to Q2 2009, it was concluded that sufficient seasonal data had been collected to encompass the majority of the precipitation variability observed over the last fifteen years. Therefore, the PMBM was also recalibrated after collecting the final full set of transducer data in Q2 2009. Data analyses demonstrated that recalibration to the Q4 2008 data set yielded the most conservative (highest dose to the river) calibration of the nine quarterly data sets obtained during the LTMP, thus this quarters (Q4 2008) data set was adopted for further dose computations. The recalibration of the model to the Q4 2008 data yielded Unit 1/2 Zone and total groundwater fluxes approximately 40% and 25% greater, respectively, than the original reference (Q2 2007) data set.

Further information and the data analyses are provided in the Q2 2009 LTM report.

38To continue to validate the appropriateness and applicability of the PMBM, a subset of the existing transducers are being maintained and monitored quarterly as part of the Long Term Monitoring Program, starting with the Q3 2009 Quarterly Report. The primary objective of maintaining these transducers is to provide ongoing confirmatory data that demonstrate substantial changes to the on-Site groundwater flow field have not taken place and thus verify that the basic assumptions inherent in the PMBM continue to remain valid. The transducer locations are provided on Figure 5A (5A-Q1 through 5A-Q4) of this report, and the rationale for the selection of these specific individual transducer locations is discussed in the Q1 and Q2 2009 quarterly reports. With regard to these ongoing long-term monitoring locations, it is noted that the transducers have a limited life. While some of the transducers can be replaced, and have been replaced in the past, others are permanently installed in the subsurface and are no longer accessible for replacement. However, with time, the base of data upon which model validity is assessed becomes increasingly more robust.

Therefore, if some of these transducers fail over time, it is not likely that replacement will be imperative. This is because the likelihood of encountering a precipitation event substantially outside the already captured range becomes increasingly more remote with time as more data is collected. In addition, it is again emphasized that considerable conservatism has been incorporated within the model development and the dose rates computed are still far below those permitted by regulation.

39It should be noted that samples were also analyzed for gamma emitters via gamma spectroscopy. Although only Co-60 and Cs-137 are reported, gamma spectroscopy should detect and identify other gamma emitters if they became present in groundwater.

Section 3.0 Data Evaluation September 26, 2012 Page 3-3 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 averages for Cs-137, Co-60, and Ni-6340. Similar tables and Figures are also presented in this report for the three previous 2011 quarters (Q1 2011, Q2 2011 and Q3 2011).

An overall evaluation of the sample handling, shipment and analytical procedures indicates that the quality assurance quality control protocols were met in all four 2011 quarters for all of the analyses except for five41, and the analytical results should be useable as presented in Table 5.

This conclusion is further supported by a review of the 2011 analytical data, as compared to previous historical trends. Refer to Section 5.2.2 of the Final 2007 Quarterly Long-Term Groundwater Monitoring Report No. 1 for further details regarding quality assurance quality control protocols.

3.3 Radionuclide Release Rates The recalibrated PMBM-derived groundwater flows within each of the six flow zones are multiplied by yearly rolling average radionuclide levels within each zone to compute groundwater radionuclide release rates to the Discharge Canal and Hudson River. These groundwater radionuclide release rates are computed separately for upper and lower flow zones as well as upgradient and downgradient of the Discharge Canal. The selection of specific monitoring locations for each of the six zones is described in the January 25, 2008 Memorandum - Synopsis of Long Term Monitoring Plan Bases.

Storm drain flows42 computed based on yearly precipitation rates are multiplied by radionuclide activities measured in the storm drains to compute the associated storm drain radionuclide release rates43 to the Discharge Canal and Hudson River.

The radionuclide release rates from the groundwater and storm drains to the Discharge Canal and Hudson River for the most-current quarter, Q4 2011, are shown in the table below.

GROUNDWATER AND SURFACE WATER TO RIVER (Ci/yr)

GROUNDWATER AND SURFACE WATER TO CANAL (Ci/yr)

Northern Clean Zone*

5.94E-04 0.00E+00**

Unit 2 North Zone 4.53E-03 1.24E-01 Unit 1/2 Zone 1.87E-02 4.74E-02 Unit 3 North Zone 1.50E-02 1.06E-02 Unit 3 South Zone 4.83E-03 6.04E-02 Southern Clean Zone*

0.00E+00 7.10E-02

  • Activity in the Northern Clean Zone is attributable to an assumed Tritium background activity of 150 pCi/L in the groundwater. The remaining radionuclides were assumed to not be present in this streamtube. Radionuclide release rate in the Southern Clean Zone is calculated from activity measured in monitoring wells MW-40 and MW-51.
    • The radionuclide release rate to the Discharge Canal from the Northern Clean Zone is zero because the Discharge canal does not extend far enough to the north to be downgradient of the Northern Clean Zone.

40Isopleths were not drawn for Cs-137, Co-60, and Ni-63 because the few positive detections observed did not indicate the existence of a groundwater plume containing these radionuclides. This is likely a result of the high surface affinity (highly adsorptive nature) of these radionuclides for solid geological materials. They therefore tend to rapidly partition out of the groundwater.

41The Q1 2011 Cs-137 positive detections in MW-40-100, MW-127 and MW-51-189 were re-analyzed and verified. However, based on the site hydrogeologic and historical chemistry data, these values do not appear to represent groundwater conditions at these locations. Additionally, Sr-90 was positively detected in the preliminary results for MW-40-46 (Q2 2011) and MW-58-65 (Post-Q3 2011). These samples were re-analyzed and Sr-90 was then found to be below the detection limit. Therefore, these preliminary results were likely false laboratory positives. Documentation of the analyses performed to reach these conclusions was subsequently provided in: Corrections to 2011 RGWMP Analyses from GEL memorandum dated March 1, 2012.

42The storm drain flows also include groundwater discharges from the foundation drains for Unit 2 and Unit 3 VC Buildings, but not from the Unit 1 NCD and SFDS, which are otherwise accounted for.

43It is noted that storm drain samples are not typically taken at times coincident with peak, or even average storm drain flow rates.

By its very nature, the vast majority of the flow through the storm drain system tends to be episodic and of short duration due to storm events; sampling rounds are generally scheduled to avoid such events. Radionuclide concentrations are primarily due to groundwater infiltration into the drains and thus tend to be highest during periods of little rain when this infiltration is not diluted by the storm water flow. This incongruence therefore yields a high bias to the dose computation because the elevated concentrations associated with low flow rates are multiplied by the much higher flow rates based on total yearly rainfall.

Section 3.0 Data Evaluation September 26, 2012 Page 3-4 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 These release rates are then used by Entergy to calculate the radiological dose to a hypothetical maximally exposed individual and the environment via the Discharge Canal and the Hudson River using the procedure outlined in the Off Site Dose Calculation Manual (ODCM)

Revision 3.

3.4 SSCs and Property Boundary Monitoring In addition to providing the data for the dose computation discussed above, the Long Term Monitoring Program has been designed to also provide rapid detection of potential leaks from SSCs. Furthermore, the LTMP also aids in the detection, and thus prevention, of potential future leaks/spills due to the generally wide-ranging investigations that are conducted in response to radionuclide peaks observed in the monitoring network. During these investigations, a number of potential SSCs are inspected and work practices are reviewed.

These inspections and reviews have identified conditions which could have potentially resulted in a future spills/leak before any release had taken place. Such early identification, allows implementation of proactive measures to upgrade these SSCs and/or work practices, thus preventing them from resulting in a future leak/spill44.

Rapid release detection monitoring is specifically focused on those SSCs which exhibit a credible probability of resulting in a visually undetected release of radionuclides to the subsurface45. The monitored SSCs are shown on Figure 4 and a description of the specific monitoring installations associated with each SSC are provided in the January 25, 2008 Memorandum - Synopsis of Long Term Monitoring Plan Bases. In addition to monitoring the SSCs, on-Site and off-Site wells are used to monitor the property boundaries for unanticipated radionuclide migration across these boundaries. Again, the rationale underpinning the selection of wells designated for this purpose is provided in the above cited Memorandum. These monitoring protocols are consistent with the NEI 07-07 Groundwater Protection Initiative (GPI).

As discussed in Section 2.3 above, GZA also completed the installation of an additional multi-level monitoring installation in December 2011. This new installation is designated MW-68, and is located near the southwest corner of the Unit 3 Transformer Yard, downgradient of MW-4646 (see Figure 6-Q4 for location47). Entergy authorized the construction of MW-68 at Unit 3 in order to increase the robustness of the Unit 3 well network and thus reduce risk of potential future releases going undetected. The initial MW-68 groundwater samples will be collected in Q1 2012 (following the appropriate stabilization time), and this monitoring installation will be sampled quarterly thereafter as part of the Long Term Monitoring Program. The sampling of U1-NCD and U1-SFDS will also be continued as part of the Long Term Monitoring Program.

I.L.s were established for the associated monitoring wells to set quantitative radionuclide activities above which further action would be undertaken. As part of the ongoing groundwater 44Previous examples include: (1) work practices updated following the Q4 2009 RWST/R.O. skid spill; (2) maintenance to piping in the utility tunnel (eventually exonerated as a source) following the 2011 Tritium peaks observed at multiple Unit 1/Unit 3 monitoring locations; (3) work practice upgrades made to the RWST and the WHT pit following the U3 FSB washout peaks in MH-A2; and (4) improvements made to sumps following multiple investigations.

45As discussed further in the following sections, reporting of visually identified spills/leaks within structures is included within Condition Reports under Entergys Corrective Action Program. Additional formal procedural emphasis has been placed on routine review of these reports as they potentially relate to GPI objectives.

46While MW-46 was previously evaluated relative to Unit 3 monitoring effectiveness, and was found to be very useful for detecting potential future releases, we also concluded that without an additional monitoring well installation, there was a moderate risk that some small releases could go undetected. In particular, it appeared that a release in the vicinity of the Waste Holdup Tank pit could potentially proceed toward the river to the south of MW-46, given the likely hydrology associated with the pre-construction bedrock valley in this area.

47A cross section has also previously been developed through the Unit 3 area to supplement Figure 4 and further demonstrate the relationship of site groundwater flow patterns and monitoring well placement relative to the individual Unit 3 SSCs (similar cross sections were previously developed for Units 1 and 2, as presented in the Hydrogeologic Site Investigation Report). This Unit 3 cross section C-C is included in the Q1 2009 Quarterly Report as Figure 4A.

Section 3.0 Data Evaluation September 26, 2012 Page 3-5 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 monitoring program, the reported analytical values are compared against I.L.s established based on the criteria shown in the table below. I.L.s are currently computed each year based on yearly averages of all the valid groundwater analytical results from the previous year, including Aliquot, Confirmatory, and Mid-Quarter sample results48. As an exception to the established procedure discussed above, the 2010 Tritium I.L.s (based on 2009 yearly averages) were conservatively used as the I.L.s for the 2011 monitoring period. This exception was deemed appropriate, and conservative, because the uncharacteristic Tritium peaks in multiple Unit 2 and Unit 3 monitoring locations during 2010 would otherwise result in high Tritium I.L.s, which would then desensitize the screening process. For the remaining radionuclides, the standard procedure was followed; i.e., 2010 yearly averages were used to calculate the 2011 Investigation Levels. The monitoring well-specific I.L.s are presented in Tables 4-Q1 through 4-Q4 (identical I.L.s for all four quarters) and are established for a comparison with the 2011 analytical results.

WELL DESIGNATION INVESTIGATION LEVELS (I.L.S)

TRITIUM (pCi/L)

Sr-90 (pCi/L)

OTHER PLANT-RELATED RADIONUCLIDES On-Site Boundary Wells (MW-40, MW-51, MW-52, and MW-107) 1,000**

2**

any detection*

Riverfront Boundary Wells (MW-60, MW-62, MW-63) 2,000**

2**

any detection*

All Other Wells

>2x average***

>2x average***

>2x average***

  • A radionuclide is positively detected when the result is greater than or equal to the MDC and 3 times the 1 sigma uncertainty.
    • The values of 1000 and 2000 pCi/L for H-3 and 2 pCi/L for Sr-90 have been chosen to be low enough to result in timely detection of a new release or change to an existing release and still be outside the normal expected range of sample results at these locations, to the extent possible with the currently available data over time.
      • Any positively detected radionuclide that has a result greater than 2 times the average from a previous year. However, the IL is not reached until an H-3 result is also greater than 1000 pCi/L or a Sr-90 result is also greater than 2 pCi/L.

In the event that the analytical results of a groundwater sample exceed the designated I.L., the following series of actions will be considered:

Contact the laboratory to verify that all quality control checks were satisfactory, sufficient sample volume was used; required MDCs were met; Re-analyze Aliquots of the original sample; Re-sample the location (Confirmatory sample) to verify the result; Increase the frequency of sampling (Mid-Quarter samples) for this location49; 48The calculation of ILs and yearly rolling averages prior to the Q1 2009 Report were based on the analytical results from the quarterly sampling rounds only, and therefore excluded aliquot, confirmatory and mid-quarter sample results. For the Q1 2009 Report and thereafter, if an aliquot analytical result confirms that the original quarterly analytical result was false, then only the aliquot result is utilized in the yearly IL calculation. If the aliquot result confirms the original quarterly result is valid, then both the original and the aliquot results are averaged together and then averaged into the yearly IL calculation as a single value.

Confirmatory analytical results have the potential to impact the use of the original quarterly sample in the same manner as aliquots; however, unlike aliquots, these independent samples are averaged directly into the yearly rolling average without pre-averaging with the associated quarterly sample. Similar to confirmatory samples, mid-quarter samples are also averaged directly into the yearly rolling average calculation. However, mid-quarter sample results do not have any impact on the use of the initial quarterly samples as can either aliquot or confirmatory samples, as described above. In the case of both confirmatory and mid-quarter sample results, direct averaging into the yearly average of these additional results can somewhat bias the yearly average toward a particular quarter/season. However, given that confirmatory and mid-quarter samples are typically taken to confirm and/or prepare for uncharacteristically high radionuclide activities, this direct averaging provides a high bias to the subsequent yearly dose computations, and is thus conservative. In cases such as this, where some bias inevitably will be created, establishing a conservative bias in the dose computations is considered more important than maintaining a seasonal non-bias.

49It is noted that Mid-Quarter samples are also proactively obtained when plant operations could potentially result in an increased probability of a release to the subsurface.

Section 3.0 Data Evaluation September 26, 2012 Page 3-6 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 Initiate an investigation utilizing Entergys corrective action program and related resources as appropriate (e.g. site engineering / radiation protection); and Initiate source/ground water remediation techniques commensurate with the potential dose impact analyses and good environmental stewardship.

3.4.1 Proactive Mid Quarter Samples In response to the 2010 Tritium peaks observed in multiple MW-31 and MW-32 sampling intervals, additional Post-Q1 2011 groundwater samples were collected at all active sampling intervals within these two monitoring installations (as well as MW-30). Additional Post-Q2 2011 and Post-Q3 2011 groundwater samples were also collected at multiple locations in response to the recent Tritium peaks observed in several Unit 1 and Unit 3 monitoring locations.

The results of the confirmatory and mid-quarter samples are presented in Section 3.4 along with the quarterly data. Sampling Data Sheets summarizing water quality data and sampling information are presented in Appendix E.

3.4.2 Previous Q4-2010 Investigation Level Exceedances As indicated in the previous Q4 2010 Quarterly LTM Report, a comparison of the Q4 2010 analytical results to their respective I.L. values shows that the I.L.s were only exceeded at four sampling intervals. All four of these exceedances were likely related to the transient spills discussed in Section 1.0 above (e.g. the RWST/R.O. skid spill and the MH-A2 Tritium peaks from the U3 FSB roof drain condensate); all four of these exceedances were still ongoing during at least portions of 2011. Therefore, these I.L. exceedances are discussed in Section 3.4.4 below.

3.4.3 Q1 through Q4 2011 Boundary Investigation Levels A comparison of the Q1 through Q4 2011 analytical results for the On-Site Boundary Wells to their respective I.L. values shows that the I.L.s were not met for any of the monitoring locations50. Therefore, there was no requirement to further investigate radionuclide activity in these wells. However, monitoring installations MW-40 and MW-51 are being further evaluated on a routine basis, as discussed below.

MW-40 and MW-51. While there have been no historical I.L. exceedances at these two southern boundary locations and the majority of the data from Q1 through Q4 2011 fall within previous ranges, the Tritium activity was at the historical maximum during 2011 in multiple MW-40 and MW-51 sampling intervals. Even though the historical maximum was recorded at the following six intervals: (1) MW-40-46 in Q1 2011; (2) MW-40-81 in Q2 2011; (3) MW-40-100 in Q2 2011; (4) MW-51-40 in Q2 2011; (5) MW-51-163 in Q4 2011; and (6) MW-51-189 in Q2 2011, all of these results were still below 375 pCi/L and, more importantly, below the detection limit. Because historical, internally correlated fluctuations in Tritium activity have been observed in the laboratory results, these monitoring locations continue to be evaluated on a routine basis given the sensitivity associated with the southern power block boundary. Even though it is recognized that the peak Tritium levels detected are low (less that 375 pCi/L) and typically below the limit of detection, there appears to be a general correlation in Tritium peaks (seasonal cyclical pattern) at multiple depth intervals in both of these monitoring installations (see Figure H1 in Appendix H). This general correlation is evident in MW-40 during 2011 as the sampling intervals exhibited a general increase in Tritium activity during Q2 2011, followed by a general 50As discussed in Section 3.4.4 below, while the laboratory reported positive Cesium detections for Q2 2011 samples at MW 122 and MW-52-181, these detections were likely false positives.

Section 3.0 Data Evaluation September 26, 2012 Page 3-7 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 decrease through Q4 2011. MW-51 also remained consistent with this overall pattern, but it recorded a second general increase in Tritium activity from Q3 2011 to Q4 2011.

An appropriate metric to evaluate whether or not these cyclical trends are due to Tritiated groundwater migration from the power block area is the relative groundwater elevations between these locations and the power block areas where Tritium contamination exists. As discussed at length in the CSM sections of the Site Investigation Report, the southern boundary groundwater elevations are well above those in the power block area51. As such, groundwater, and thus Tritium in the groundwater, cannot migrate from the power block to the south; in fact, groundwater is migrating in the opposite direction. This conclusion was previously validated for nine quarters (between Q2 2007 and Q2 2009) through analyses of groundwater elevation contours (see Figure 5 in the quarterly reports prior to Q3 2009). In addition, starting with the Q1 2009 Quarterly Report, Figure 5A is being generated to specifically compare high importance transducer readings to historical maximum and minimum readings. The objective of this analysis is to demonstrate that substantial changes to the on-site groundwater flow field have not taken place and that the CSM remains valid. Multiple sampling zones from both the MW-40 and MW-51 monitoring installations are included in this analysis.

Based on these analyses, as well as the substantial body of data developed over the last 5 years of investigation which underpin our CSM, we conclude, with a high degree of confidence, that the low level peaks in Tritium activity observed in these two monitoring installations are not due to groundwater migration from the power block area. This conclusion has continued to be validated each quarter. However, we do not have a definitive explanation for the observed peaks. Further investigation into other potential mechanisms, such as seasonal atmospheric Tritium washout and seasonal laboratory biases, is ongoing.

3.4.4 Q1 through Q4 2011 SSC Investigation Levels For the SSC monitoring wells, a comparison of the 2011 quarterly analytical results to their respective I.L. values shows that the I.L.s were met at twenty monitoring locations (thirty-five sampling intervals) during the four quarters of 2011. Because multiple I.L. exceedances have been related to the same transient spills, the following discussion is split into four subsections, with general discussion explaining the likely source followed by the corresponding exceedances:

1. Unit 2 RWST/R.O. skid spill;
2. Unit 3 FSB roof condensate;
3. Unit 1 CSB sample sink overflow; and
4. Other (explained individually).

The following table is separated into quarters/radionuclides and summarizes the cases where the I.L.s were met, with these exceedances discussed below. See the footnote to the table for the key to the color designations.

51The current, Q1 through Q4 2011, transducer data confirm the overall groundwater flow direction remains from the southern boundary toward the power block area, as discussed in Section 2.1 above.

Section 3.0 Data Evaluation September 26, 2012 Page 3-8 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 WELL ID Q1 2011 RESULT*

(pCi/L)

Q2 2011 RESULT*

(pCi/L)

Q3 2011 RESULT*

(pCi/L)

Q4 2011 RESULT*

(pCi/L)

INVESTIGATION LEVEL (pCi/L)

MW-32-149 1,060**

1,000 MW-36-24 3,070 2,563 MW-39-67 10,900/2,240 (Post) 14,900 (Post) 1,030 1,000 MW-39-84 3.1 2.1 MW-39-102 14,300/12,400 (Post) 44.8 19,000 (Post) 1,120 1,000 Any Detection*

MW-39-124 9.1 Any Detection*

MW-39-195 7,040/4,190 (Post) 17,200 5,130 1,000 MW-41-40 2,030 11.5 4,510 1,000 7.3 MW-41-63 1,230 1,000 MW-44-66 1,620 (Post) 1,000 MW-44-102 1,050 1,000 MW-45-42 8,120 8,560/39,400 (Post) 27,200 (Post) 5,900 MW-45-61 5,630 5,910 (Post) 2,650 MW-46 2,470 5,250/3,080 (Post) 3,300 2,280 1,844 MW-49-65 4,240 3,030 MW-50-42 3,770 30.2 1,038 11.0 MW-50-66 6,500 7,150 7,830 5,896 MW-52-122 34.8 Any Detection*

MW-52-181 64.6 Any Detection*

MW-53-120 14.5 Any Detection*

MW-54-37 5,160/27,900 (Post) 31,300 14,000 2,710 MW-54-58 2,480 (Post) 4,230 4,830 1,480 MW-54-123 3,920 1,302 MW-54-144 4,340 5,270 6,850 2,635 MW-54-190 8,770 3,490 MW-56-83 76,400/84,200 (Post) 105,000 (Post) 72,500 6,390 MW-57-20 20,300/38,100 (Post) 24,700 (Post) 3,040 MW-57-45 13,500/25,300 (Post) 24,600 (Post) 2,380 MW-58-26 1,860 2,470 (Post) 4,770 1,000 MW-58-65 1,100 (Post) 1,750 1,000 MW-62-138 3,010 2,000 MW-63-121 3,630 2,000 MW-66-36 15.5 14.0 U3-T2 2,270 3,830/2,670 (Post) 2,650 2,980 2,077 U1-CSS 6,380/10,800 (Post) 5,173

  • A radionuclide is positively detected when the result is greater than or equal to the MDC and 3 times the 1 sigma uncertainty.

Section 3.0 Data Evaluation September 26, 2012 Page 3-9 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 RWST/R.O. Skid Spill at Unit 2 In January 2010, a peak in Tritium activity was measured in MH-9 during routine 80-10 Effluents Program sampling52. Additionally, several sampling intervals in MW-31 and MW-32 exhibited clear Tritium increases and I.L. exceedances in 2010, generally reaching maximum historical levels at these locations. Following a series of investigations by IPEC, a Q4 200953 surface spill related to a RWST/R.O. processing skid was identified as the likely source of the Tritium increases. This transient and localized spill involved rented equipment that was brought on-site by an outside contractor for use during the Unit 2 outage, and is no longer on site. In addition to likely entering the subsurface through the storm drain system, this spill also entered the MW-32 well vault, and may have penetrated the well casings54. Additional I.L. exceedances were also noted at downgradient monitoring locations later in 2010 as this perturbation moved through the system.

This spill resulted in numerous I.L exceedances in 2010. However, by Q4 of that year, only one near-source monitoring location (MW-32-149) still exceeded its Tritium I.L.. This sampling interval again exceeded its I.L. during Q1 2011; however, an overall, clear decrease in Tritium activity was noted from June 2010 through Q1 2011, and the Tritium activity decreased below the I.L. for the final three quarters in 2011. It is expected that the Tritium activity in MW-32-149 will continue to exhibit an overall decrease, similar to the other MW-31 and MW-32 sampling intervals, because the probable source has been terminated.

The only additional 2011 I.L. exceedance which may be attributable to the RWST/R.O. skid spill was in MW-36-24 during Q2. This conclusion is based in part on the preceding RWST/R.O.

skid peak seen in the lower sampling interval at this location (MW-36-41), and an I.L.

exceedance in Q4 2010. However, variable Tritium levels have been observed in MW-36-24 since August 2009, which predates the RWST/R.O. skid spill. As such, the 2011 I.L.

exceedance in this monitoring interval is more likely a response to Retention Mechanism releases, some of which are likely associated with RWST/R.O. skid spill. The samples collected at MW-36-24 in Q3 2011 and Q4 2011 showed a decreasing trend (similar to the overall trend seen in the upgradient monitoring locations) to an activity below the detection limit in Q4 2011.

The two 2011 I.L. exceedances discussed above, as related to the transient RWST/R.O. skid spill, were resolved in subsequent 2011 quarterly monitoring rounds. As such, and because the Q4 2009 RWST/R.O. skid spill was transient in nature and Tritium is non-sorbing, it appears that this perturbation had generally dissipated through the system by Q4 2011. However, it is noted that the transient RWST/R.O. skid spill has likely replenished the Retention Mechanism(s) and further contributions to the groundwater flow regime are still possible.

Unit 3 FSB Roof Condensate A transient Tritium peak was observed in manhole A2 (MH-A2) in Q2 2009, with a concurrent Tritium I.L. exceedance in MW-45-42; this well is located immediately adjacent to MH-A2. Both locations exhibited rapid decreases of Tritium activity by the following, Q3 2009, quarter; and the Tritium activity in MH-A2 was consistently below 1,500 pCi/L for the next year. However, in 52The Tritium levels were measured at ~85,000 pCi/L in MH-9 on January 14th and 15th, 2010, and then decreased to 4,650 pCi/L on January 19th, 2010. Typical Tritium levels prior and post-spill were ~1,500-4,000 pCi/L in MH-9.

53Based on forensic research conducted by Entergy, it appears that the date of the spill was November 21, 2009.

54An initial sample was taken of the water remaining in the MW-32 vault on 2/1/2010. This water exhibited a Tritium activity of 390,000 pCi/L. Subsequent sampling of this water in May 2010 measured residual Tritium levels of ~65,000 pCi/L prior to the water being fully removed from the vault. It is further noted that the water in the vault contained other radionuclides in addition to Tritium.

These included Co-60, Sb-125, Cs-134, Cs-137, etc. Therefore, the Q1 2010 groundwater data from wells proximate to, and downgradient of, the MH-9 and MW-32 vault release points were evaluated for detections of these radionuclides; none were found.

However, Cs-137 was detected at MW-111 in Q2 2010. While this well is located downgradient of MW-32, no other wells showed detections of Cs-137, or the other radionuclides discussed above, in Q2 2010.

Section 3.0 Data Evaluation September 26, 2012 Page 3-10 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 early June 2010, a transient Tritium peak was again observed in MH-A2, followed by a rapid decrease in activity (<1 week) to baseline levels for this storm drain system (< 2000 pCi/L). A prolonged peak of elevated Tritium activity was subsequently observed in Q4 2010 through Q3 2011 (10/5/2010 - 07/28/2011)55. Tritium peaks and I.L. exceedances have also been noted in MW-41-40, located adjacent to this storm drain system, and MW-46, hydraulically downgradient of MH-A2, since Q3 201056. Additional I.L. exceedances and Tritium peaks have also been noted in MW-45, MW-44, MH-A4 and MH-B1 during 2011.

Because of these Tritium peaks in the monitoring network, a series of investigations into the correlation and underlying cause of the I.L. exceedances, as well as the increased Tritium in the manholes, have been conducted by Entergy and GZA. Early investigations identified that the likely cause of both the monitoring well and manhole peaks was higher levels of Tritium washout57 entering MH-A2 from the FSB building roof drain during periods when the vent fan was not operational. Under specific climatic conditions, SFP evaporation was likely condensing on the roof and being transported into the storm drain system via rain water.

As one step in the investigative process (to rule out a leak in a SSC), a standpipe was constructed which solely receives inflow from the FSB roof drains and isolates this water from other water sources to MH-A2. The Q3 2010 through Q4 2011 sample data from this standpipe clearly demonstrate, as shown in the graph below, that the recent Tritium activity within MH-A2 is directly proportional to the discharge from the FSB roof.

55Additionally, a clear increase in Tritium activity was also observed downstream in this storm drain system at MH-A4 in Q4 2010.

56A manhole in the vicinity of MW-46, designated MH-B1, has also exhibited an elevated Tritium activity during this time frame.

57The term washout, as used herein, is the process by which Tritiated water vapor is transformed into Tritiated water as a liquid.

In general, this transformation is driven by condensation (as is the primary underlying driver associated with MH-A2, above) and/or Tritium diffusion from the Tritiated water vapor into precipitation (rain and/or snow), either while it is still falling or after deposition.

0 75,000 150,000 225,000 300,000 375,000 450,000 525,000 600,000 675,000 Jan-10 Apr-10 Jul-10 Oct-10 Jan-11 Apr-11 Jul-11 Oct-11 Jan-12 Manhole A2/FSB Roof H3 Activity (pCi/L)

A-2 FSB roof drain Unit 3 Vent Fan Back in Service

Section 3.0 Data Evaluation September 26, 2012 Page 3-11 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 These investigations also identified that the Unit 3 FSB fan was generally out of service from May 2010 through July 201158. Consequently, IPEC repaired the vent fan in Q3 2011 and it was placed back in service on July 21, 2011. The Tritium activity in MH-A2 rapidly59 returned to baseline conditions thereafter (~1 week later) and remained at those levels throughout Q4 2011.

Based on the investigations and associated data collected, it has been concluded that the elevated Tritium levels detected in MH-A2 and A4 were due to the FSB roof condensate entering the storm drain system when the vent fan was not operating.

Some of this highly Tritium-laden water was, in all probability, released into the groundwater from the storm drain system60 and thus likely resulted in the recent Tritium I.L. exceedances observed in monitoring wells adjacent to and downgradient of this system. The greater response of the proximate groundwater monitoring wells, as compared to that observed during previous MH-A2 Tritium increases, is believed due to the coincident Unit 3 outage. During an outage, the reactor cavity is open and the pool temperature becomes significantly elevated, both resulting in greater evaporative losses, and thus greater likely washout impacts. The following 2011 Tritium I.L. exceedances are likely related to (and have been attributed to) the Unit 3 FSB roof condensate, and as such, do not indicate any new SSC leak at Unit 3.

MW-41-40: Q1 2011 and Q2 2011; MW-41-63: Q1 2011; MW-44-66: Post Q2 2011; MW-44-102: Q4 2011; MW-45-42: Q1 2011, Q2 2011, Post Q2 2011 and Post Q3 2011; MW-45-61: Q2 2011 and Post Q3 2011; MW-46: Q1 2011, Q2 2011, Post Q2 2011, Q3 2011 and Q4 2011; and U3-T2: Q1 2011, Q2 2011, Post Q2 2011, Q3 2011 and Q4 2011.

Similar to the response observed within MH-A2, the Tritium activity at the majority of these monitoring installations (e.g. MW-41-40, MW-41-63, MW-44-66, MW-45-42, MW-45-61 and MW-46) has shown an overall decrease following the repair of the vent fan. Because the apparent source of these peaks was transient and terminated, and due to the non-sorbing behavior of Tritium, these decreasing trends are likely to continue at these locations. The Tritium I.L. exceedances at MW-46, U3-T2 and MW-44-102 were not yet resolved through Q4 2011; therefore, these monitoring locations will be specifically evaluated based on the additional data obtained during the upcoming quarterly monitoring round. All other I.L. exceedances related to the U3 FSB condensate were resolved during 2011.

Unit 1 CSB Sample Sink Overflow Beginning with the Q2 and Post-Q2 2011 samples, uncharacteristic increases in Tritium activity were noted in a number of Unit 1 monitoring locations. These increases included historical maximum levels (since the beginning of the LTMP) observed in MW-47-8061 and MW-56-83, and were well above the historical average activities. The highest Tritium peaks were concentrated in the deeper monitoring intervals, with a lack of similarly elevated levels in the 58It is noted that the SFP was ventilated during all fuel transfers.

59A MH-A2 sample was collected only 7 days after the vent fan was placed back in service (7/28/2011) and the Tritium activity in the sample was 3,140 pCi/L, approximately 30 times lower than the average Tritium activity from September 2010 to July 21, 2011.

Subsequent samples showed further decreases.

60It is noted that the Tritiated water vapor evaporating from the SFP is a permitted release through the Plant Vent located atop the vapor containment building. Analyses were conducted to account for this release to the FSB roof in the dose computations. This same Tritium is therefore double counted because it has again been included in the storm drain and groundwater portions of the dose computations.

61It is noted that MW-47 is a standby monitoring well and is thus not typically scheduled for quarterly monitoring. As such, it does not have an I.L for 2011, and therefore does not appear on the above table of I.L. exceedances. With initial detection of the spill in MW-56, MW-47 was reactivated to provide additional definition of the developing IP-1 Tritium plume.

Section 3.0 Data Evaluation September 26, 2012 Page 3-12 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 corresponding shallowest sampling intervals (MW-47-5662 and MW-56-53). These two monitoring locations are located directly to the south and southwest of the Unit 1 Containment Building. Also beginning in Q2 2011, a distinct and coincident increase in Tritium activity was also observed in multiple sampling intervals of MW-39, located upgradient/cross-gradient of Unit 1 in the northern portion of Unit 3. Subsequently, monitoring installations located further downgradient exhibited Tritium activities which continued to increase through Q3 2011 (MW-57) and Q4 2011 (MW-54, MW-50 and MW-49) as the perturbation moved through these locations.

Given the observed Tritium increases, particularly recognizing that groundwater cannot flow from Unit 2 (Tritium plume location) to this southern area of Unit 1, it was judged likely that a spill had recently occurred. As such, an investigation into the underlying cause of these peaks was immediately initiated by Entergy. Through this investigation, an April 1, 2011 sample sink overflow in the Unit 1 Chemical Systems Building (CSB) was initially identified as a likely source of the above identified Tritium peaks. This sample sink, located next to the Waste Distillate Transfer Pumps on the 70 Fuel Handling floor, was found overflowing because the sinks sock filter had become obstructed. This caused subsequent flooding on the floor which flowed into the floor drain. Upon discovering the sink overflow, Entergy removed the materials obstructing the sink, and removed the residual water. However, additional investigations revealed that the 70 floor drain piping was compromised, which resulted in flooding of the Sample Room below63 on the 53 floor. Concurrently, it was noted that leakage previously being captured from Waste Distillate Transfer Pump piping was also being discharged to the 70 floor drain; this captured piping leakage was then rerouted. These multiple facets of this overall release, collectively called the CSB Sample Sink Overflow, are all associated with the distillate tank waste processing system located in the Unit 1 CSB. While the Sample Sink Overflow and associated flooding was previously identified and resolved by IPEC, the release to the environment only became apparent via the Q2 2011 sampling results.

Based on the proximity of the Unit 1 CSB 53 Sample Room to the South Curtain Drain (SCD), it appears that a portion of the above described spill exited the structure through wall/floor joints and entered the curtain drain. The spill then appears to have entered the groundwater flow regime along this drain line. A portion of the highly-Tritium laden water likely stayed within the SCD above the working mat64 and is a likely source of the 2011 Tritium peaks observed in MW-47, MW-56 and additional further downgradient Unit 1 monitoring locations. Additionally, part of the release may have also followed the Southwestern IP1-CB Flow Path, as discussed in Section 8.2 of the Hydrogeologic Site Investigation Report prepared by GZA, dated January 7, 2008 and also impacted these two well locations. Finally, water appears to have also exfiltrated from the SCD near the southern portion of the CSB into the vadose zone. Given the slope of the bedrock surface in this area, as well as the strike and dip of the bedrock fractures65, this migration pathway is likely responsible for the 2011 Tritium increases observed in MW-39.

Given the above discussion, the following 2011 Tritium I.L. exceedances appear related to (and have been attributed to) the Unit 1 CSB Sample Sink Overflow:

62The Tritium activity within MW-47-56 increased by nearly tenfold during 2011; however, this activity was still nearly two orders of magnitude less than that observed in the deeper sampling interval at this monitoring location, MW-47-80.

63The floor drain in this room was obstructed, which resulted in the water backing up until there was 1/2 -3/4 of standing water throughout this room. The water in the 53 Sample Room then leaked down to the 43 CSB landing at the bottom of a nearby stairway (Stairway #11).

64It is noted that this drain is typically dry, and thus, in conjunction with the building foundation and associated working mat, can form a preferential flow path, which can then transport water around the building without it being intercepted by the deeper CSB drain.

65See the Hydrogeologic Site Investigation Report discussion of vadose zone transport along bedrock fracture strike and dip as related to up/cross gradient Tritium migration from Unit 2 to the Unit 1 NCD. A similar migration mechanism is hypothesized to have occurred in the case of MW-39, as graphically presented on Figure 6-Q2 2011.

Section 3.0 Data Evaluation September 26, 2012 Page 3-13 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 MW-39-67: Q2 2011, Post-Q2 2011, Post-Q3 2011 and Q4 2011; MW-39-102: Q2 2011, Post-Q2 2011, Post-Q3 2011 and Q4 2011; MW-39-195: Q2 2011, Post Q2 2011, Post-Q3 2011 and Q4 2011; MW-50-42: Q2 2011; MW-50-66: Q2 2011, Q3 2011 and Q4 2011; MW-54-37: Q2 2011, Post-Q2 2011, Q3 2011 and Q4 2011; MW-54-58: Post-Q2 2011, Q3 2011 and Q4 2011; MW-54-123: Q4 2011; MW-54-144: Q2 2011, Q3 2011 and Q4 2011; MW-54-190: Q4 2011; MW-56-83: Q2 2011, Post-Q2 2011, Post-Q3 2011 and Q4 2011; MW-57-20: Q2 2011, Post-Q2 2011 and Post-Q3 2011; MW-57-45: Q2 2011, Post-Q2 2011 and Post-Q3 2011; MW-58-26: Q2 2011, Post-Q3 2011 and Q4 2011; MW-58-65: Post-Q3 2011 and Q4 2011; MW-62-138: Q4 2011; MW-63-121: Q4 2011; and U1-CSS: Q2 2011 and Post-Q2 2011.

The Tritium activity in the majority of the more upgradient monitoring locations (e.g. MW-39, MW-47, MW-56, U1-CSS and potentially MW-57) appears to have peaked in Q3 2011, and these locations appear to be entering the decreasing portion of the breakthrough curve in Q4 2011. The downgradient wells (e.g. MW-49 and MW-50) are generally still exhibiting increasing trends as the center of mass migrates towards these locations. The first Tritium I.L.

exceedances at the river boundary (monitoring locations MW-62-138 and MW-63-121) occurred in Q4 2011, indicating the leading edge of this pulse input had reached the river boundary wells by Q4 2011.

Due to the transient nature of this spill and the non-sorbing behavior of Tritium, it is expected that the upgradient wells will continue their overall decreasing trend back to historical baseline conditions. However, all indications are that this spill was released into the vadose zone; therefore further releases from associated Retention Mechanisms could potentially cause temporary increases in Tritium activity at these locations in the future. Once this input migrates through the system, it is anticipated that the Tritium activity in the farther downgradient monitoring locations will also return to historical baseline levels. Of all the 2011 I.L.

exceedances that have been attributed to the U1 CSB Sample Sink Overflow, only those at sampling intervals MW-50-42 and U1-CSS were resolved during 2011. As such, the unresolved I.L.s at the other monitoring locations will be further evaluated based on the additional data obtained during the upcoming quarterly monitoring rounds.

Other (Explained Individually)

MW-39-84 (Q4 2011; Strontium). The Q4 2011 Strontium result exceeded the I.L. at MW 84 by approximately 1 pCi/L, which is the highest Strontium activity measured at this interval since the initiation of the LTMP. A corresponding positive Strontium detection was also noted in the sampling interval directly below (MW-39-102). Prior to this point, Strontium was typically detected between 1 and 2 pCi/L at this interval. The source of this Strontium has been associated with the Legacy IP1 Storm Drain piping, which historically carried water collected by the Unit 1 SFDS66. This discharge was rerouted after testing revealed that numerous sections 66Refer to the Hydrogeologic Site Investigation Report prepared by GZA, dated January 7, 2008 for additional information.

Section 3.0 Data Evaluation September 26, 2012 Page 3-14 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 of the storm drains leaked. As such, no active Strontium source has been present in the Legacy piping since 199467.

However, even after source termination, Strontium peaks have still been noted at MW-39 since the initiation of the LTMP. These peaks have been attributed to residual sediment in storm drains as well as fluctuation in precipitation and thus Retention Mechanism influences. The somewhat higher Strontium measured in Q4 2011 is therefore likely related to the high amount of precipitation in 2011 (e.g. Hurricane Irene), and/or storm drain work, which could have potentially remobilized trapped/sorbed Strontium. Given that Strontium discharges to the nearby Legacy Storm Drain have been terminated, the elevated activity is expected to return to historical levels below the I.L. with the resumption of more normal precipitation rates. This monitoring location will be specifically evaluated based on the additional data obtained during the upcoming quarterly monitoring round.

MW-39-102 and MW-39-124 (Q2 2011; Cesium). Cesium was detected in both MW-39-102 and MW-39-124 in Q2 2011. Prior to Q2 2011, Cesium was never detected in either of these sampling intervals, it immediately returned to below the detection limit in both intervals by the Post-Q2 2011 sampling round, and remained below detection through Q3 and Q4 2011. In addition, Cesium was not detected in any of the other sampling intervals (either above or below) these two intervals during Q2 2011, and has never been detected in these intervals since the beginning of the LTMP. Therefore, these Q2 2011 Cesium detections in MW-39-102 and MW-39-124 are likely false positives due to laboratory errors or glassware contamination.

However, it is noted that MW-39-102 concurrently exhibited elevated Tritium in Q2 2011, as attributed to the U1 CSB Sample Sink Overflow. Although unlikely due to the high partitioning affinity of Cesium, these detections could potentially be related to this transient spill. Both of these Cesium detections and I.L. exceedances were resolved in 2011.

MW-41-40 (Q1 2011; Strontium). The Q1 2011 Strontium activity slightly exceeded the I.L. for this sampling interval; this activity is the highest measured at this interval since the initiation of the LTMP. Additionally, a clear increase in Strontium activity was also noted in the lower sampling interval at this location (MW-41-63) in Q1 2011. Strontium has consistently been measured above 2 pCi/L at this monitoring location. As discussed above relative to MW-39-84, the source of this Strontium has been associated with the Legacy IP1 Storm Drain piping, which historically carried water collected by the Unit 1 SFDS (see Figures 7-Q1 through 7-Q4). As such, this Q1 2011 Strontium peak is likely associated with liberation of Strontium stored (Retention Mechanism) near this Unit 1 Legacy piping due to high precipitation events or potentially storm drain work. The Strontium activity at MW-41-40 immediately decreased below the I.L. in Q2 2011 (similar decrease also observed in MW-41-63) and remained at historical levels through Q4 2011. As such, this I.L. exceedance was resolved in 2011.

MW-50-42 (Q4 2011; Strontium). The Q4 2011 sample exceeded the Strontium I.L. by approximately a factor of three, which represented the highest activity measured at this interval since the initiation of the LTMP. Inspection of Figure 7A reveals that this Q4 2011 peak was likely a delayed response to the increase in water levels during defueling operations in the Unit 1 SFPs, possibly resulting from a delayed contribution from Retention Mechanisms. An extended response to the defueling operations has been noted at MW-50-42 since Q3 2009, so the return to pre-defueling levels could potentially be prolonged at this downgradient location.

However, because the ultimate source has been terminated, an eventual decrease below the historical Strontium activity at this location is expected. This monitoring location will be further 67It is also noted that the ultimate Strontium source, the Unit 1 SFPs, has also been terminated during the defueling operations in 2008.

Section 3.0 Data Evaluation September 26, 2012 Page 3-15 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 evaluated based on the additional data obtained during the upcoming quarterly monitoring round.

MW-52-122 and MW-52-181 (Q2 2011; Cesium). Positive Cesium detections were measured in both of these sampling intervals in Q2 2011. However, these detections are likely false positives because: (1) Cesium was not detected in Q2 2011 in the other sampling intervals (both above and below) at this location (e.g. MW-52-11, MW-52-18, MW-52-42, MW-52-64 and MW-52-162); (2) prior to Q2 2011, a positive Cesium detection has never been observed for all sampling intervals (including MW-52-122 and MW-52-181) at this location; (3) Cesium was below the detection limit in MW-52-122 and MW-52-181 immediately following this detection (Q3 2011); (4) additional Cesium detections were not measured in any surrounding monitoring location during Q2 2011; and (5) no plausible upgradient Cesium source is present. As concluded for MW-39-102 and MW-39-124 discussed above, these Cesium detections appear to be false positives.

MW-53-120 (Q3 2011; Nickel). A positive Nickel detection was measured at MW-53-120 in Q3 2011, the first detection observed at this sampling interval since Q4 2008. The MDC, which has been typically around 20 pCi/L historically, was only 11 pCi/L in Q3 2011. If a historically typical MDC had been applied to the Q3 2011 sample results, the Nickel results (14.5 pCi/L) would have been below the detection limit. Therefore, this positive detection is likely only a result of laboratory adjustments during Q3 201168. The MDC returned to a historically typical value (21.7 pCi/L) in the following, Q4 2011, quarter and Nickel was then below the detection limit at this sampling interval. As such, the Q3 2011 I.L. exceedance was resolved in 2011.

MW-66-36 (Q1 2011; Strontium). The Q1 2011 Strontium activity slightly exceeded the I.L.

and slightly exceeded the historical maximum activity measured at this sampling interval.

Inspection of Figure 7A demonstrates that this Q1 2011 increase was the first clear Strontium increase at this location since the defueling operations were completed on the Unit 1 SFPs.

Because this monitoring location is located downgradient of the Unit 1 SFPs, the Q1 2011 increase is likely in response to the defueling operations in the Unit 1 SFPs, as this perturbation migrated downgradient to this location. This Q1 2011 peak was immediately followed by a decrease in Q2 2011 to an activity below the Strontium I.L. The Strontium activity remained below the I.L. in Q3 2011 and Q4 2011, although the activity was slightly elevated and fluctuations were observed. As such, this I.L. was resolved in 2011. However, because this sampling interval is located along the downgradient boundary, and recognizing the partitioning behavior of Strontium, the eventual return to pre-Q1 2011 levels may be prolonged.

Foundation Drains and Manholes The Unit 2 foundation drains which discharge into MH-5 VCFD, along with similar drains for Unit 3 which discharge into Manholes B-1 and B-6, form an integral part of the early leak detection monitoring network.

MH-5 VCFD - Throughout 2011, peaks in Tritium activity have been observed within MH-5 VCFD69, where the maximum activity (12/22/2011 sample) was multiple times higher than the relatively small, singular peak previously noted in Q3 2010.70 This original 2010 peak was immediately followed by a rapid reduction71 to the previous 68It is noted that this monitoring location, MW-53, is located near the U1-NCD. The Nickel activity in this curtain drain is consistently

>100 pCi/L. Additionally, positive Nickel detections have been measured in every sample collected at MW-42-49, an upgradient sampling interval that is also located adjacent to the drain, since the beginning of the LTMP.

69It is noted that the water collected by the MH-5 VCFD is routed to the discharge canal where it is released as a monitored discharge. As a monitored discharge, this Tritium activity is directly accounted for in the dose computations.

70The Q3 Tritium peak in MH-5 VCFD was approximately ten times higher than the previous baseline of approximately 1000 pCi/L.

71After the initial Q3 10 increase, the Post-Q3 2010 sample, obtained only 10 days later, showed the Tritium activity in MH-5 VCFD had already returned to the previous baseline levels.

Section 3.0 Data Evaluation September 26, 2012 Page 3-16 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 baseline levels in Post-Q3 2010, and remained at baseline through Q4 2010. At the time, the Q3 and Q4 Q3 2010 Quarterly Monitoring Reports conjectured that this MH-5 VCFD peak in Tritium activity could be potentially correlated with the increased LCD flow rate, and also associated with the increased activity in proximate monitoring wells MW-31and MW-32 (as discussed in Section 3.4 of these reports).

However, this correlation no longer appears plausible based on weekly samples and flow rate measurements72 more recently collected from MH-5 VCFD. This more intense sampling regimen, relative to the previous quarterly sampling frequency, was initiated in June 2011 as part of the ongoing investigation to identify the ultimate cause of these elevated Tritium levels. As shown on Figure 6B, which includes four additional quarters of data (relative to that presented in the previous Q4 2010 report), the 2011 Tritium peaks observed in MH-5 VCFD (as well as those observed in the proximate the monitoring wells) are not convincingly correlated with the increased flow rates in the LCD. Therefore, the previous conjecture that these data were potentially correlated appears to be less likely the case given the additional data. As such, the Tritium peaks observed in the monitoring points from MW-31 and MW-32 appear to be more likely the result of the previously discussed transient surfaces spills (see above), as well as Retention Mechanisms.

The peaks in MH-5 VCFD currently remain unexplained. The ongoing investigation is now more focused on potential process inputs such as floor and roof drains, with potential contribution from plant/FSB vent condensate. Construction drawings are currently being reviewed in order to potentially identify additional process inputs to the drain lines upstream of this sampling point. Finally, it is noted that the other radionuclides analyzed (e.g. Strontium, Cesium, Cobalt) were all non-detect for all samples collected in 2011, similar to historical results at MH-5 VCFD.

B-I - During Q1 and Q2 2011, elevated Tritium was observed in Unit 3 manhole B-1.

However, the activity then decreased by over an order of magnitude73 by Q3 2011, after the U3 FSB vent fan was placed back in service. The operational vent fan eliminated the roof drain input of Tritium into MH-A2; B-I, and its associated foundation drain, is located downgradient of MH-A2 and likely collects exfiltration from A2 via this groundwater pathway. The 2010 and 2011 trends at B-1 were generally consistent with the transient increases in Tritium activity observed in MH-A2 during that period (See discussion above under Unit 3 FSB roof condensate). However, unlike the earlier Q4 2010 decrease observed in B-1, there was a Tritium peak observed in MH-A2 during that quarter, and the Tritium activity seen at monitoring locations MW-41-40 and MW-46 also remained elevated during that time. Therefore, while it appears that the Tritium activity in B-1 is generally related to the recent MH-A2 / roof drain induced Tritium peaks, a clear correlation is not apparent. As such, the previously inoperable U3 FSB vent fan may not be the only cause for the recent peaks observed in B-1. This manhole will therefore be further evaluated in the upcoming quarterly monitoring rounds.

Similar to the historical sampling events at B-174, Cesium was also detected in all three 2011 samples from this manhole at an activity comparable to the Q3 and Q4 2010 results75. These Cesium levels are well below the 80-10 Effluents Program reporting 72The flow rate at MH-5 VCFD was consistently between 4 and 8 gpm in 2011.

73The Q3 2011 Tritium activity decreased to 736 pCi/L, which is even below baseline activity (~1,000 pCi/L) in this manhole.

74A total of 13 samples have been collected from Manhole B-1 and low levels of Cesium have been positively detected in 9 of these samples.

75At manhole B-1, the Cs-137 activity slightly decreased from the first 2011 sample (Q1 2011) to the final, Q3 2011, sample.

However, a slight increase was noted between Q4 2010 and Q1 2011.

Section 3.0 Data Evaluation September 26, 2012 Page 3-17 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 limits, and are believed to be associated with Unit 1 contaminated construction backfill remaining in the vicinity of the Unit 3 VC Building. The remaining radionuclides were all non-detect during the three 2011 sampling events at B-1.

B-6 Similar to the recent trends seen in the upgradient Unit 3 monitoring locations (and U3-T2), a Tritium peak was observed at Manhole B-6 in Q2 2011. Following this peak, the Tritium activity exhibited an overall decrease through Q4 2011 and the Tritium results were below the detection limit in Q4 2011. All other radionuclides were non-detect at B-6 during the five 2011 sampling events. It is believed that B-6, and its associated foundation drain, is also capturing groundwater with increased Tritium activity due to previous Exfiltration of Unit 3 FSB roof condensate from MH-A2.

Leak Collection Device (LCD). During 2011, the flow rate into the Unit 2 Leak Collection Device (LCD) fluctuated between approximately 0.7 and 2.5 liters/day from March 2011 to September 2011, compared to a historical baseline flow rate of <0.02 L/day. The LCD flow rate then gradually decreased to approximately 0.5 L/day between September 2011 and December 201176, but still remained well above (over an order of magnitude) the historical baseline collection rate.

A previous, clear increase in the daily volume of water collected by the LCD was also observed in Q3 2010, with an average flow rate of approximately 1.5 L/day77. However, this increase was followed by a rapid return to baseline conditions in October 2010, and the LCD flow rate remained at those baseline conditions through Q1 2011.

Previous investigations indicated that the increased flow observed in Q3 2010 was potentially correlated78 with the timing of atypically elevated water levels in the fuel pool, as associated with dry cask work. Following the limiting of these increases in pool water elevation, a marked decrease was observed in the LCD flow rate throughout Q4 2010.

With the resumed increased LCD flow, further investigations by GZA and Entergy identified a number of existing light outlet boxes, welded to the inside liner of the fuel pool, as potential locations where pool water could get through the liner during high water levels (i.e., above the designed high water level of the pool). The majority of the boxes are sourced by electrical conduits which were constructed without penetrating the liner by running the conduit along the side of the wall to the top of the fuel pool. However, for a portion of the light outlet boxes (i.e.

the boxes on sides of the pool where the crane rails are located), these electrical conduits penetrate the liner and do not prohibit water from entering the annulus79. Following subsequent inspections of the light boxes, it has been concluded that there is definitive indication that these boxes did contribute, at least in part, to the LCD flow rate under transient overfill conditions.

This conclusion has been reached based, in part, on the observation of boron precipitate within the boxes and conduit penetrations.

Due to these investigations, the six light boxes that contain electrical conduits which penetrate the liner have been temporarily sealed and IPEC has implemented restrictions on the pool elevation during atypical operations. Entergy is also scheduling the removal of these light boxes 76It is noted that the LCD flow rate increased from approximately 0.5 to 0.9 L/day between December 21, 2011 and the end of the year.

77The LCD collected approximately 50 liters of water during the July to October 2010 time frame, which is greater than the total volume of water collected during the previous 3 year period (April 2007 through June 2010). In this regard, however, it is noted that all of the water collected by the LCD is fully contained and does not enter the groundwater regime.

78While the data trends appear to correlate, it is noted that simple correlation does not demonstrate causation.

79At the time, it was believed that raising pool levels above the light boxes for the dry cask work was acceptable because the construction drawings showed the boxes were sourced via conduits that do not penetrate the liner. Therefore, it was not clear that a transient overfill would pose a problem.

Section 3.0 Data Evaluation September 26, 2012 Page 3-18 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 with permanent plating/sealing of the liner so as to permanently eliminate any possible future contribution to the LCD flow rate.

Given the elevated 2010 and 2011 LCD flow rates, Figure 6B is included in this report to visually present both the historical LCD flow rate data and the Tritium data for the monitoring locations located within the Unit 2 Tritium plume. Review of Figure 6B suggests that the increased flow rates in the LCD do not correlate with trends observed in the Unit 2 monitoring locations, which further supports the conclusion that the flow into the LCD is not indicative of release of similar water into the groundwater system.

However, it is noted that the LCD flow rate remained elevated after the temporary sealing of the light boxes. This could either indicate that: (1) the temporary seals are not sufficiently robust; (2) there is an additional contributing leak in the liner; or (3) the continued 0.5 L/day flow is a residual effect, given the unknown travel time for water trapped behind the liner (prior to the repair) to migrate from the light boxes through the four-foot thick concrete wall and then into the LCD. Given the remaining uncertainty, additional liner investigations are currently being planned, and this monitoring location will be further evaluated based on additional data gathered during the upcoming quarterly monitoring rounds.

U1 NCD AND U1-SFDS. Sampling of the Unit 1 North Curtain Drain (U1-NCD) and the Unit 1 Sphere Foundation Drain Sump (U1-SFDS) are currently included as part of the Long Term Monitoring Program. These drains have been documented to capture a large proportion of the Strontium leakage from the Unit 1 SFPs, and continue to collect groundwater containing Strontium and Cesium and direct it through monitored discharge points with the NCD flow undergoing treatment prior to discharge80. These drains have also historically been assumed to collect some groundwater contaminated with Tritium from the Unit 2 SFP. This conclusion was validated by the tracer test conducted as part of the hydrogeologic site investigation (see the Hydrogeologic Site Investigation Report prepared by GZA, dated January 7, 2008).

Visual inspection of the U1-SFDS Tritium data demonstrates that this drain also likely collected groundwater impacted by the recent U1 CSB Sample Sink Overflow. A clear increase in Tritium activity, by nearly one order of magnitude, was measured in Q2 2011. This was followed by steady decreases through Q4 2011, with the Q4 2011 Tritium activity dropping below the detection limit. The U1-NCD Tritium activity also temporarily increased in Q3 2011 by a factor of three relative to baseline conditions reestablished through Q4 2010. This peak was immediately followed by a decrease of greater magnitude in Q4 2011, which dropped the Tritium activity back to the baseline levels seen in 2009. This increase in the NCD has also been attributed to the U1 CSB Sample Sink Overflow.

Strontium data from these drains continues to show overall decreasing trends since the completion of U1 SFP defueling; in fact, the Q4 2011 Strontium activity in the U1-SFDS and U1-NCD was 85% and 82%, respectively, lower than the average pre-defueling levels seen at these locations (as summarized on Figure 7A).

3.5 Plume Natural Attenuation Monitoring The fourth and final objective of the Long Term Monitoring Program is to evaluate if the groundwater plumes identified on-Site demonstrate overall reductions in total activity over time, 80Prior to the Unit 1 SFP defueling, the U1-NCD and U1-SFDS drains were collecting approximately 20-40 times more Strontium than was discharging through groundwater into the Hudson River. Additionally, these drains were particularly effective during defueling and captured approximately 300-350 times more Strontium during this time frame. Following the completion of the defueling operations, these drains have been removing approximately 10 times more Strontium than is discharging into the Hudson River from groundwater.

Section 3.0 Data Evaluation September 26, 2012 Page 3-19 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 as is consistent with the requirements of Monitored Natural Attenuation (MNA), the selected remediation for the IPEC Site81.

Given the likely ages of the SFP leaks identified and characterized during the hydrogeologic investigation, it is probable that the Unit 2 (Tritium) and Unit 1 (Strontium) plumes had reached steady state conditions prior to the beginning of the LTMP. Given that: (1) the identified leaks in the Unit 2 SFP which impact the geohydrologic flow regime82 have all been previously repaired (the last leak repaired in 2007) and; (2) the water in the Unit 1 West Pool underwent intensified demineralization (beginning in April 2006 with a reduction in Strontium levels of over 95 percent) and the pools were then subsequently fully defueled and drained in Q4 2008, one might expect that the plumes should have started to markedly attenuate toward zero with time. Both plumes have in fact generally shown significant levels of attenuation, when they are viewed in their entirety and past release events (including more-recent localized, transient spills) and expected seasonal variability in the sampling data are accounted for. However, the attenuation has not been as rapid as we originally anticipated during time frames subsequent to the source interdictions implemented by Entergy.

In the case of the Unit 2 Tritium plume, levels have dropped markedly from the highest levels measured during the two-year hydrogeologic investigation; however, the rate of Tritium decrease with time has decreased. In fact, the total Unit 2 Tritium plume activity stopped decreasing and even increased for one quarter due to the impact of the transient RWST/R.O.

skid spill. While the overall decreasing trend since source interdiction is clear, the more current rate of reduction has been difficult to predict due to the impact of: (1) these transient, localized spills; and (2) natural geologic and anthropogenic Retention Mechanism(s)83. However, as seen in the data for Q3 2011 and Q4 2011, the Tritium levels in the plume are once again declining at rates comparable to those seen during the beginning of the LTMP (see Figure G-17). Further discussion of this years data pursuant to evaluation of the Unit 2 Tritium plume MNA is provided in Section 3.5.1 below.

Relative to the Unit 1 Strontium plume, Strontium levels should drop more slowly than Tritium levels. This is because, in addition to the Retention Mechanism(s) discussed above for Tritium (which also apply to Strontium), Strontium also undergoes partitioning whereby this radionuclide is adsorbed from the groundwater onto solid surfaces (both geologic and anthropogenic). When the input of Strontium to the groundwater is reduced (such as via the initial fuel pool demineralization and subsequent decommissioning) the solid surfaces desorb the stored Strontium back into the groundwater, thus maintaining Strontium levels. Strontium partitioning is therefore expected to substantially slow plume attenuation. Despite partitioning effects, some plume attenuation was observed in response to pool demineralization prior to defueling, particularly proximate to the pool. However, defueling of Unit 1 resulted in a temporarily increase in the leakage rate of West Pool water into the formation. This was expected based on previous work on the Unit 1 SFPs, but was unavoidable given the requirement to raise the pool 81The selection of MNA as the remediation for the Site is more fully discussed in the Hydrogeologic Site Investigation Report, dated January 7, 2008.

82While a release of pool water through the Unit 2 SFP liner (and into the LCD) via light outlet boxes has been documented, there is no compelling evidence that any of this water has migrated through the concrete wall elsewhere and entered the groundwater flow regime. This conclusion is based primarily on the lack of convincing correlation of LCD flow rate with the response of groundwater monitoring points proximate to the pool.

83These subsurface features have trapped and stored Tritium that was released during historical Unit 2 SFP leaks and were likely replenished during the transient, localized spills. Therefore, they are still likely releasing this Tritium to the groundwater flow regime in an episodic manner after the physical leaks have been terminated. This conclusion is consistent with the original CSM presented in the Hydrogeologic Site Investigation Report, as further supported by the tracer test data in that report as well as subsequent tracer data, as described in Section 3.6 of the Q1 2009 Quarterly Monitoring Report, dated July 2, 2010.

Section 3.0 Data Evaluation September 26, 2012 Page 3-20 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 level for fuel rod removal84. The increased leakage rate had resulted in a noticeable increase in Strontium levels in the immediate vicinity, and downgradient of, the fuel pool. However, as more currently observed, the Q4 2011 Strontium activity in the near-pool monitoring locations has generally decreased substantially below the average pre-defueling levels (by 80-98%).

More downgradient monitoring locations have also generally returned to pre-defueling Strontium levels, with outliers expected to continue to show further decreases towards pre-defueling levels in the upcoming quarters. As discussed further in Section 3.5.2 below, the total Unit 1 Strontium plume activity has dropped by approximately 68% since the completion of the Unit 1 SFPs defueling operations, and has dropped by approximately 20% when compared to pre-defueling conditions.

3.5.1 Unit 2 Tritium Plume Attenuation Qualitative Evaluation From a qualitative perspective, a reduction in overall Tritium activity in the Unit 2 plume can be seen through a comparison of the most-current, Q4 2011, delineated plume boundary (Figure 6A) to those in early LTMP quarterly reports (2007 and 2008). Not only have Tritium levels within the plume generally shown an overall, long-term decreasing trend, but the reductions over the more recent quarters, downgradient of the discharge canal, have become particularly evident in the delineated, shaded bounds of the plume. This quarter continues the trend where the shaded plume85 no longer extends to the river as it did in previous quarters through Q1 2009. Additionally, the rolling average Tritium activity in MW-111, indicative of the core of the plume, has shown an overall decrease by a factor of greater than six over the last two years, from 70,150 pCi/L in Q1 2009 to 11,100 pCi/L in Q4 2011, and by over an order of magnitude since tracking of the plume began. This trend over time has been summarized on Figure 6A, which is a compilation of the quarterly Tritium plume maps as well as that from the Hydrogeologic Site Investigation Report.

Mann-Kendall Quantitative Analysis To more quantitatively evaluate MNA progress, a Mann-Kendall analysis, as referenced in USEPA Guidance for Data Quality Assessment - Practical Methods for Data Analysis,86 was performed on the Tritium levels measured through the most-current quarterly data, Q4 2011, at monitoring locations associated with the IP2-SFP and downgradient Unit 2 Tritium plume87.

Because this monitoring report covers the entire year, all quarterly data from Q1 through Q4 2011 have been added to the Mann-Kendall analysis. Each of the vertical monitoring intervals 84As of late 2008, all the fuel rods have been removed from the Unit 1 SFPs and the pool water has been drained. As such, the Unit 1 SFPs is no longer an active source of radionuclides to the subsurface.

85The plume shading on Figure 6 demarks the estimated boundary that separates Tritium levels greater than 5,000 pCi/L from those below this value, and provides a reasonable demarcation level for illustrating plume geometry and temporal variation.

Although this value equates to one-quarter of the drinking water standard for Tritium, GZA emphasizes that drinking water standards (USEPA MCLs) do not apply to the IPEC property given that there are no drinking water sources on or proximate to the site. Where yearly rolling average radionuclide activity data were available for multiple depths at a given location, GZA used the highest value to develop plume delineations. This is a typical approach to represent three-dimensional contaminant data sets on two-dimensional maps.

86USEPA Guidance for Data Quality Assessment - Practical Methods for Data Analysis, EPA QA/G9, QA00 UDATE; EPA/600/R-96/084, July, 2000.

87The Mann-Kendall statistical technique was initially chosen because it is particularly well suited for data sets with a limited number of points. The method was subsequently retained because it is also a non-parametric analysis and therefore does not introduce bias by presupposing any particular shape for the trend curve. In addition, the method is robust with respect to outliers, which allows it to handle the variability inherent in the data set. Finally, the method tolerates non-uniform sampling frequencies. This is important because while the sampling frequency is typically quarterly, more frequent samples are proactively taken when a scheduled operation carries an increased risk of potential release, and also when something unexpected is observed that could indicate a new leak or spill.

Section 3.0 Data Evaluation September 26, 2012 Page 3-21 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 at each monitoring installation was analyzed separately. In general, only data collected after final completion of the multi-level installation was used88.

Graphs showing the variation in Tritium activity over time in the immediate vicinity of the Unit 2 SFP are presented as Figures G-1, G-2 and G-3 in Appendix G, for MW-30, 31 and 32, respectively. Additional graphs are also presented in the appendix for the other monitoring locations downgradient of the Unit 2 SFP (see Figures G-4 through G-14 for MW-33 through 37, 4289, 49, 50, 5389, 55 and 111) and downgradient, river boundary wells (see Figures G-15 and G-16 for MW-66 and 67, respectively). The Mann-Kendall analyses for the individual monitoring points are summarized on Table G-1 in Appendix G. The table includes the results of the analysis for each depth interval (well) at each of the multi-level monitoring locations enumerated above. The table is color coded, with green shading designating wells showing a decreasing trend, yellow for no trend, and red for an increasing trend.

Comparison of Table G-1 for Q4 2011 to that from Q4 2010 indicates that the number of increasing trend designations has now begun decreasing, from 5 total intervals (1 river boundary interval) in Q4 2010 to 3 total intervals (0 river boundary intervals) in Q4 2011, and the upgradient monitoring locations (MW-31 and MW-32) also showed an overall shift toward decreasing trends now that the RWST/R.O. skid perturbation has generally migrated through the local groundwater flow regime. Of the 32 non-river-boundary intervals included in the table for Q4 2011, approximately one-half (18) show a decreasing trend, no change from the last quarterly report (Q4 2010). It is important to note that this group of decreasing wells includes all those located within the core of the plume with the highest Tritium activities (MW-30-69, MW-33 and MW-111). These high-activity wells better represent overall plume behavior because they encompass a great percentage of the Tritium activity in the plume. For the river boundary monitoring intervals, slightly less than one-half (4 of 9) show a decreasing trend, the same as last quarterly report (Q4 2010)90.

Notwithstanding the above, it is noted that the Mann Kendal analysis is still currently of limited use for evaluating the behavior of the plume in response to the termination of the identified leaks in the Unit 2 SFP, the reason these analyses were implemented. This is primarily due to the impact of two localized, transient Tritium surface spills91, the most critical of which is the 88The majority of the boreholes were completed as a multi-level installation. These multi-level completions were designed to segregate the borehole length into individual sampling zones with depth. The sampling zones were generally established to coincide with the more productive zones of the fractured bedrock and overburden (both natural soils and backfill). These sampling zones were then isolated from each other with various types of seals placed in the open borehole. The objective of the seals is to prevent vertical flow through the borehole and thus establish the same conditions in the formation which existed prior to the drilling of the borehole. As such, the Tritium data is considered depth-discrete. It is noted that the multi-level installations at some monitoring locations were removed and replaced with upgraded systems, for example MW-32.

While the overall intent was to use only depth-discrete data, there were a number of exceptions where open borehole and/or borehole packer testing data were also used. These data were incorporated where possible given the importance of early time data (proximate to when documented leaks were still active). Additional, more detailed discussion relative to the basis for including these data is provided in Section 3.6 of the Q1 2009 Quarterly LTM Report.

89MW-42 and MW-53 are located downgradient of the Unit 1 SFPs, rather than the Unit 2 SFP. However, these two wells were included in the analyses due to the long-standing hypothesis that the Unit 2 SFP contributes Tritium to the Unit 1 groundwater flow regime via vadose zone transport (see the graphic representation in Figure 6 herein and the discussion in the Hydrogeologic Site Investigation Report). It is noted that any decreasing Tritium trend in this area due to the termination of leaks from the Unit 2 SFP could be masked by increased leakage of Tritiated water from the Unit 1 SFPs up through the completion of defueling in November 2008, and then thereafter via the Retention Mechanism(s) and localized transient releases, as described above.

90Closer inspection of the current no trend river boundary wells reveals that the normalized test statistic decreased from Q4 2010 to Q4 2011 at four of the five intervals (MW-67-219, MW-67-276, MW-67-323 and MW-67-340). In fact, MW-67-340 switched from an increasing trend designation to a no trend designation from Q4 2010 to Q4 2011. As such, these intervals are all statistically shifting towards the decreasing trend designation, which is currently defined at a 95% confidence interval, with the addition of the current, Q4 2011, monitoring data.

91In addition, effectiveness is further impacted by a limitation of the Mann-Kendall analysis method, itself. This method only evaluates the number of increases relative to decreases, and does not weight the analysis relative to the magnitude of each change.

Therefore, once a clearly decreasing trend, even of substantial magnitude, has reached a nearly horizontal asymptotic behavior, numerous insignificantly small positive and negative changes over time (such as due to sampling and hydrogeologic/climatic

Section 3.0 Data Evaluation September 26, 2012 Page 3-22 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 RWST/R.O. skid spill. These spills have been shown to result in increases in activity, which, while valid measures of plume behavior, impair the ability of the trend analysis to serve as a measure of the effectiveness of Unit 2 SFP leak identification and termination, the intended purpose of this analysis. Due to these spills, a number of wells had previously transitioned from decreasing trend status to no trend, and no trend status to increasing trend. While this trend has been somewhat reversed as the RWST/R.O. skid spill has dissipated, as seen in the 2011 sampling data discussed above, associated Retention Mechanism impacts and the recent U1 CSB Sample Sink Overflow will likely further adversely affect the Mann-Kendall analyses. As such, the original practice of providing a discussion of each monitoring interval exhibiting a no trend or increasing trend is no longer in effect (as begun in Q4 2010) until the transient, localized spills have flushed through the groundwater system. The summary table and the individual Tritium plots for each sampling interval are still provided in Appendix G.

Unit 2 Tritium Plume Total Activity Analysis Another method to analyze plume behavior is to compute the total Tritium activity in the plume at multiple snapshots over time. This procedure92 was implemented for each quarterly sampling round from the beginning of the LTMP in Q2 2007 through the current, Q4 2011 quarter. In addition, the bounding Tritium activities from Figure 8.1 of the Hydrogeologic Site Investigation Report93 have also been included as a starting point for the graph. These data are summarized as a histogram on Figure G-17 in Appendix G.

As can be seen from the figure, the total Tritium activity in the plume downgradient of the Unit 2 SFP has shown a distinctly decreasing trend over time. However, the Q4 2009 transient surface RWST/R.O. skid spill did cause a noticeable increase in total Tritium mass in Q1 and Q2 201094. This was followed by a decrease in Q3 2010, and then relatively stable total Tritium mass thereafter through Q2 2011. Once this perturbation moved through the local groundwater flow system, the total Tritium activity reverted back to its overall decreasing trend through Q3 and Q4 2011. Based on the data through Q4 2011, the total Tritium activity in the plume has decreased approximately 55 percent since Q2 2007, and has decreased by approximately 91 percent when compared to the bounding Tritium activity. It is noted that the general first order time/activity plume decay graph is now once again decreasing and no longer appears to be approaching a non-zero horizontal asymptote95.

Conclusion-Unit 2 Tritium Plume MNA Based on the data and analyses provided above, our conclusion is that the Tritium plume associated with the historical Unit 2 SFP leaks is undergoing overall, long-term reductions in variability) can overwhelm the relatively short, early-time string of decreasing changes, thus resulting in a switch from a decreasing trend to a no-trend status. This is particularly true when a 95% confidence interval is applied.

92 The individual sampling point Tritium concentrations were multiplied by the groundwater volumes in representative zones (discretized over area and depth), as computed using soil and bedrock effective porosities developed from the pumping and tracer tests (see the Hydrogeologic Site Investigation Report for further information).

93 Hydrogeologic Site Investigation Report, January 7, 2008, prepared by GZA GeoEnvironmental, Inc, on behalf of Enercon Services, Inc., for Entergy Nuclear Northeast, Indian Point Energy Center, 450 Broadway, Buchanan, NY 10511.

94Approximately 70% of the sampling intervals used in the total Unit 2 Tritium activity calculations recorded an increase in Tritium activity from Q1 2010 to Q2 2010. As such, the total Tritium activity increased from 0.017 Ci to 0.021 Ci during this quarter.

Similarly, an increase in Unit 2 Tritium I.L. exceedances was observed in Q2 2010. It should be noted that an increase in Tritium activity for sampling locations completed in soil (backfill) have greater impacts on the total Tritium mass calculations due to difference in overburden porosity vs. bedrock porosity.

95An apparent non-zero asymptote was previously conjectured, which suggested a continued input of Tritium into the groundwater flow regime. The current data show the graph is once again decreasing, but a lower, non-zero asymptote is still possible given the Retention Mechanism(s), and/or potentially a small unidentified Unit 2 SFP leak. If an unidentified leak does still remain in the Unit 2 SFP, it must be small. With Tritium at approximately 30,000,000 pCi/L in the SFP, a leak directly from the pool of only approximately 10 L/day would be more than sufficient to provide the required Tritium input to the groundwater. To date, the available data do not appear to support the existence of such a leak.

Section 3.0 Data Evaluation September 26, 2012 Page 3-23 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 activity which are consistent with Monitored Natural Attenuation (MNA), the remedial technology selected for the IPEC Site. Given this conclusion and the recognition that Entergy has terminated all identified leaks in the Unit 2 SFP96, this Unit 2 Tritium plume satisfies the requirements for Monitored Natural Attenuation. Finally, it is important to recognize that, even with additional inputs from localized transient spills, the amount of Tritium being released through the groundwater pathway is still small compared to permitted levels of Tritium discharge to the river through the Discharge Canal.

3.5.2 Unit 1 Strontium Plume Attenuation Well - Specific Evaluation Despite the effects of partitioning, as discussed below, the overall Strontium activity within the Unit 1 plume had generally shown some attenuation in response to the West Pool demineralization conducted by Entergy in preparation for defueling. This work began in 2006 and resulted in an approximately 98% reduction in Strontium in the West Pool. See Figure 7A:

monitoring points U1-NCD, U1-SFDS, MW-42 and U1-CSS. The final defueling of the Unit 1 SFPs, however, resulted in a noticeable increase in Strontium groundwater activities proximate to the SFPs, as exhibited by these same monitoring points; an overall increase in Strontium activity was expected given the requirement to temporarily raise the pool levels for fuel rod removal, thus increasing the leakage rate from the SFPs prior to fully draining the pool97. All of these monitoring points have subsequently shown large sustained decreases since mid-2009, to levels that are now even lower than pre-defueling activities. Farther downgradient (MW-53, MW-55, MW-54, MW-57, MW-50, and MW-37), increases in Strontium activities were also measured after defueling, but generally following a time lag as compared to wells more proximate to the SFPs. The majority of these more downgradient monitoring locations have most recently shown decreases to pre-defueling levels, with a few exceptions (MW-53-120, MW-55-24, MW-50-42 and MW-37-40) still exhibiting responses to the increased leakage during defueling. The wells farthest downgradient, river boundary wells MW-66 and MW-67, have shown Strontium activity increases in the past few quarterly sampling events as the perturbation continues to migrate farther downgradient.

Viewed on a more detailed basis with the most current LTMP results, the monitoring well data for Q4 2011 indicate that the overall Strontium levels continued to exhibit a general decrease and are now 80 to 98 % lower than the average pre-defueling levels in the immediate vicinity of the pool (U1-NCD, MW-42-49, U1-SFDS and U1-CSS). These monitoring locations, as expected, were the first to reflect the complete decommissioning of the SFPs given their location/function. For a portion of the somewhat further downgradient wells (most evident in MW-37-22 and MW-50-66), the Q4 2011 data are generally consistent with the decreasing portion of the perturbation peak as the previous increased U1-SFPs leakage moves past these points98. However, other downgradient sampling intervals have most recently shown increases in Strontium activity (MW-53-120, MW-55-24, MW-55-35 and MW-50-42), possibly resulting from delayed input from Retention Mechanism(s), while similarly located monitoring points have already exhibited their peak Strontium activities and have now (Q4 2011) decreased back to pre-defueling levels (MW-53-82, MW-54, MW-57, MW-55-54, MW-36 and MW-49). This 96While a release of pool water through the Unit 2 SFP liner (and into the LCD) has been documented, there is no compelling evidence that this water has gotten through the concrete wall and entered the groundwater flow regime. This conclusion is based primarily on the lack of convincing correlation of LCD flow rate with the response of groundwater monitoring points proximate to the pool.

97As of late 2008, all the fuel rods have been removed from the Unit 1 SFPs and the pool water has been drained. As such, the Unit 1 SFPs is no longer an active source of radionuclides to the subsurface.

98The maximum Strontium levels at these locations were typically recorded in 2009 and have generally shown overall decreases over the past few quarters.

Section 3.0 Data Evaluation September 26, 2012 Page 3-24 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 variable behavior at downgradient monitoring locations serves to again emphasize that the IPEC Site is located in a bedrock fracture controlled hydrologic regime99. As such, this type of localized distance-based inconsistency is to be expected and likely indicates that the downgradient wells which exhibited rapid responses to the defueling operations (e.g. MW-54) are closer to (or within) the more pervious preferential flow pathway. This pathway is hypothesized to be responsible for the convergence and narrowing of the Tritium and Strontium plumes as they move toward the river from sources centered at widely spaced locations upgradient100.

For the farthest downgradient wells, those proximate to the river, it is not clear whether the increased defueling leakage is just beginning to impact these wells, or has generally already past them and the observed increases are due to partitioning/Retention Mechanism impacts.

As discussed above, both scenarios are likely the case, depending on the individual area/depth specific zone monitored. For example, Strontium activity in the MW-62-138 depth interval (along with, but to a lesser extent the shallower intervals in overburden) appears to show several Strontium peaks from Q1 2009 to Q1 2011, and then remained below the detection limit through the most-current, Q4 2011, quarter. It is noted that the Strontium levels in this monitoring installation are all relatively low (below 3 pCi/l), and this location does not appear to be proximate to (or within) the Strontium plume preferential flow path. Therefore, the peaks in Strontium observed may not be associated with the Unit 1 defueling, and may be due to nothing more than hydrogeological variability. The two additional riverfront monitoring installations downgradient of the Unit 1 Strontium plume, MW-66 and MW-67, have also exhibited peaks during the 2011 quarterly monitoring rounds. The Strontium data in the shallowest depth interval of MW-67, MW-67-39, also demonstrated a moderate increase in Strontium activity in Q4 2009, dissimilar to the previous overall decreasing trend that was seen at this sampling interval from Q4 2007 (pre-defueling) through Q3 2009. After slight, but distinct, Strontium decreases from Q1 2010 through Q4 2010, the activity again increased during Q1 2011 at this interval. A similar decrease followed this second perturbation for the next two quarter monitoring rounds; however, the Strontium activity again increased in the most-current, Q4 2011, quarter. The monitoring interval directly below MW-67-39 (MW-67-105) had also shown increases in Strontium activity during the Q2 2010 and Q3 2010 quarterly monitoring events, after previously exhibiting generally stable Strontium levels since the initiation of the LTMP.

Following this 2010 perturbation in MW-67-105, the Strontium activity has been below the detection limit within this sampling interval through the most-current (Q4 2011) quarter. The Strontium data in the shallowest depth interval of MW-66, MW-66-21, has remained generally stable since the initiation of the LTMP and has not shown a clear response to the 2008 defueling activities. However, the deeper sampling interval, MW-66-36, has recently exhibited slightly elevated Strontium levels, beginning in Q1 2011.

Because the ultimate Strontium source was terminated, the Strontium activity at the river boundary locations are expected to decrease to pre-defueling levels once the perturbation passes through the system. However, as discussed above, Strontium partitioning and potential 99While groundwater flow through the fractured bedrock at the IPEC Site is highly preferential at small areal scales, it is characterized by sufficiently interconnected small bedrock fractures to allow the hydrogeologic system to function and be modeled as a non-homogeneous, anisotropic, porous media at Site-wide scales.

100By way of contrast, in a homogeneous porous media uniform flow field, the centerlines of plumes that start at widely spaced locations (spaced perpendicular to the groundwater flow path) will typically remain widely spaced (although the edges of the plumes will likely move closer as the plumes get wider through dispersion). In the case of fracture flow at IPEC however, not only do the Strontium and Tritium plume centerlines converge, but the plumes also get narrower as they move downgradient. In addition, MW-50 displays high relative Strontium concentrations and fault gouge was encountered during the drilling of this well. These behaviors/data are typical of a more fractured zone preferentially controlling groundwater flow and thus the migration of the contaminants therein (see the Site Hydrologic Investigation Report for further CSM-focused discussion of this issue).

Section 3.0 Data Evaluation September 26, 2012 Page 3-25 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 future inputs from Retention Mechanisms could delay the overall decrease in activity at these Unit 1 monitoring locations.

Unit 1 Strontium Plume Total Activity Analysis Similar to the Tritium analysis discussed in Section 3.5.1 above, the behavior of the Unit 1 Strontium plume was analyzed by computing the total Strontium activity in the plume at multiple snapshots over time. This procedure101 was implemented for each quarterly sampling round from the beginning of the LTMP in Q2 2007 through the current, Q4 2011 quarter. These data are summarized as a histogram on Figure J-1 in Appendix J.

As seen on the figure, the total Strontium activity in the plume downgradient of the Unit 1 SFPs has shown an overall decreasing trend since defueling was completed in November 2008. As expected after source termination, a general first order plume decay is observed in Figure J-1.

While it appears that the Strontium data is approaching a non-zero horizontal asymptote, an indication of additional Strontium entering the groundwater flow regime, the ultimate Unit 1 Strontium source has been definitively terminated through the defueling operations in 2008.

This slower attenuation was expected for the Strontium plume due to the strong partitioning behavior of this radionuclide. As such, Strontium was initially adsorbed onto solid surfaces (both geologic and anthropogenic) from the groundwater when the Unit 1 SFPs source was still active. This behavior is an equilibrium process, which means the stored Strontium will then desorb back into groundwater when the groundwater Strontium activity decreases, thus maintaining equilibrium between the sorbed and aqueous phases. Therefore, partitioning is expected to substantially slow plume attenuation as the Strontium desorbs back into groundwater.

Even though Strontium partitioning retards overall plume attenuation, the total Strontium activity in the Unit 1 Plume did initially decrease below the average pre-defueling total activity in Q1 2010, only five quarters after the defueling operations were completed. Further overall decreases in total Strontium activity have also observed between Q1 2010 and the most-current quarter, Q4 2011. Because the ultimate source was terminated, the total Strontium activity is expected to continue this overall decreasing trend over time. Based on the Q4 2011 data, the total Strontium activity in the Unit 1 plume has decreased by approximately 68% since the completion of the Unit 1 SFPs defueling operations, and has decreased by approximately 20%

when compared to pre-defueling conditions. Future transient increases in total Strontium activity, similar to Q1 2011, may occur when Strontium is potentially released via the Retention Mechanism(s). However, an overall downward trend of total Strontium activity in the Unit 1 plume is expected to continue because the source of contamination was terminated when the Unit 1 SFPs defueling operations were completed.

Conclusion - Unit 1 Strontium Plume MNA From an overall, long-term perspective, Strontium levels downgradient of the Unit 1 SFPs are generally behaving as expected. The monitoring installations closest to the SFPs exhibited strong peaks in Strontium activity in response to defueling, and then have decreased even below pre-defueling activities. Monitoring installations farther downgradient have generally shown decreases in Strontium activity over the past four quarterly sampling rounds and are generally approaching pre-defueling levels. As expected, the Strontium activities in a portion of these sampling intervals have already decreased to pre-defueling levels. Monitoring installations closer to the river may still show Strontium increases (similar to the recent 101The individual sampling port Strontium activities were multiplied by the groundwater volumes in representative zones (discretized over area and depth), as computed using soil and bedrock porosities developed from the tracer and pumping tests (see Hydrogeologic Site Investigation Report for additional information).

Section 3.0 Data Evaluation September 26, 2012 Page 3-26 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 increases at MW-67-39 and MW-66-36) as the additional leakage experienced during defueling flushes through the groundwater flow system. It is expected that completion of this flushing mechanism will be protracted given the aforementioned impact of partitioning and Retention Mechanisms on Strontium levels in the groundwater. However, over time it is expected that downgradient Strontium plume levels will also continue their overall downward trend given that Entergy has fully terminated the Unit 1 SFPs as a source through decommissioning.

Based on the Strontium data and plume analysis provided above, our conclusion is that the Strontium plume associated with the historical Unit 1 SFPs leak is undergoing overall, long-term reductions in activity which are consistent with Monitored Natural Attenuation (MNA), the remedial technology selected for the IPEC Site. Additionally, the Strontium plume total activity analysis provides further evidence that the Unit 1 Strontium plume has not only demonstrated a noticeable reduction since U1 SFPs defueling was completed, but also has decreased below the average pre-defueling total plume activity levels. Given this conclusion and the recognition that Entergy has terminated all identified leaks in the Unit 1 SFPs through decommissioning, the Unit 1 Strontium plume satisfies the requirements for Monitored Natural Attenuation.

FINAL QUARTERLY LONG-TERM GROUNDWATER MONITORING REPORT Q1 THROUGH Q4 2011 (REPORT NO. 13)

September 26, 2012 Page 4-1 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92

4.0 CONCLUSION

S AND PLANNED FUTURE WORK Given the data collected to date, the apparent strength of the CSM to evaluate those data, and the completion of source interdictions by Entergy, we believe all Program Objectives (see Section 3.0) are being met. These objectives are consistent with and fully encompass the guidance provided in the NEI Groundwater Protection Initiative (GPI).

Based on the specific results and evaluation of the groundwater monitoring data through Q4 2011, within the context of the Long Term Monitoring Program, IPEC plans to continue routine groundwater and LCD monitoring, related monitoring network maintenance, and reporting of the data and engineering analyses. This work will be conducted in accordance with the IPEC Radiological Groundwater Monitoring Program IP-SMM-CY-110, and will incorporate the enhancements described herein.

It is noted that the analyses and conclusions presented in this report are based on the data and information available up to and including the subject quarter. Data that becomes available after the subject quarter, but before the finalization date of the report, is sequentially reflected in the associated subsequent reports.

In summary, evaluation of data collected during the four 2011 quarters (through Q4 2011) has shown the following:

Tritium I.L.s were met at a number of monitoring locations to the south of the Unit 1 Containment Building from Q2 2011 through Q4 2011. Investigations identified a transient overflow in a Unit 1 CSB Sample Sink102 in April 2011 as the likely cause for these I.L. exceedances. The groundwater data from near-source monitoring locations (MW-47, MW-56 and MW-39) generally exhibit overall decreasing activity from Q3 2011 through Q4 2011, suggesting that the peak of this transient perturbation has migrated past these wells, Further downgradient monitoring locations (MW-55, MW-54, MW-50 and MW-49) are still generally exhibiting increases in Tritium activity through Q4 2011 as the center of mass moves towards these locations. The recent Q4 2011 I.L.

exceedances in two river boundary sampling intervals (MW-62-138 and MW-63-121) also suggest that the leading edge of this perturbation has reached the River. Given that this transient U1 CSB Sample Sink Overflow was terminated, it is expected that the Tritium activity at these Unit 1 monitoring locations will fairly quickly return to the pre-spill levels.

Coincident with the above discussed Unit 1 Tritium increases, a number of wells located further south in Unit 3 (e.g., MW-41, 44, 45, 46) also peaked to uncharacteristically high Tritium levels at the same time. Notwithstanding the temporal connection, and in part because these wells are located on the other side of a groundwater mound from Unit 1 (and MW-39), it is believed that these Unit 3 Tritium increases are not due to the above Sample Sink Overflow, but rather are associated with the washout103 entering Manhole A2 (MH-A2) from the Fuel Storage Building (FSB) roof drain when the vent fan was 102Note that, as further discussed in Section 3.4.4, this release includes the sink overflow, as well as a previously contained pipe leak, all of which flowed into a compromised floor drain. These multiple facets of this release are all associated with the distillate tank waste processing system located in the Unit 1 CSB, and are termed the CSB Sample Sink Overflow.

103The term washout, as used herein, is the process by which Tritiated water vapor is transformed into Tritiated water as a liquid.

In general, this transformation is driven by condensation (as is the primary underlying driver associated with MH-A2, above) and/or Tritium diffusion from the Tritiated water vapor into precipitation (rain and/or snow), either while it is still falling or after deposition.

Section 4.0 Conclusions and Planned Future Work September 26, 2012 Page 4-2 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 generally not operating104 (see Section 3.4.4, and the Q4 2010 quarterly report for further discussion of the washout releases from the FSB roof drain to MH-A2).

Transient Tritium peaks above historical baseline in MH-A2 were initially observed in Q2 of 2009, with more elevated Tritium activity becoming evident between September 2010 and July 2011. These more recent data clearly demonstrated that the Tritium activity within MH-A2 is directly proportional to the discharge from the FSB roof drain when the vent fan was out of service. The vent fan was placed back in service on July 21, 2011, after which the Tritium activity rapidly105 returned to baseline conditions (<2,000 pCi/L) within the FSB roof drain and MH-A2.

The greater response of the proximate groundwater monitoring wells, as compared to that observed during previous MH-A2 Tritium increases, is believed due to the coincident Unit 3 outage. During an outage, the reactor cavity is open and pool temperature becomes significantly elevated, both resulting in greater evaporative losses, and thus greater likely washout impacts. Based on these investigations and associated data collected, it has been concluded that the elevated Tritium levels detected in MH-A2, as well as the proximate and downgradient monitoring wells (MW-41-40, MW-44-66, MW-45-42 and MW-46) and manhole B-1, are due to the FSB roof condensate generated while the vent fan was not operating and, as such, do not indicate a new leak from a System, Structure or Component (SSC). Moreover, the vent fan has been replaced and the subsequent data show this issue to have been rectified (see Section 3.4.4 for further discussion).

During 2011, the flow rate into the Unit 2 Leak Collection Device (LCD) fluctuated between approximately 0.7 and 2.5 liters/day from March 2011 to September 2011, compared to a historical baseline flow rate of <0.02 L/day. The LCD flow rate then gradually decreased to approximately 0.5 L/day by the end of Q4 2011106. A previous increase in the flow rate into the LCD was also measured in Q3 2010, with an average flow rate of approximately 1.5 L/day. However this increase was followed by a rapid return to baseline conditions in October 2010, and the LCD flow rate generally remained at those baseline conditions through Q1 2011.

With the resumed increased LCD flow during the latter part of 2011, further investigations by GZA and Entergy identified a number of existing light outlet boxes, welded to the inside liner of the fuel pool, as potential locations where pool water could get through the liner during high water levels (i.e., above the designed high water level of the pool). The majority of the boxes are sourced by electrical conduits which were constructed without penetrating the liner by running the conduit along the side of the wall to the top of the fuel pool. However, for a portion of the light outlet boxes (i.e. the boxes on sides of the pool where the crane rails are located), these electrical conduits penetrate the liner and do not prohibit water from entering the annulus107. Following 104It is noted that the Tritiated water vapor evaporating from the SFP is a permitted release through the Plant Vent located atop the VC building.. Analyses were conducted to account for this release to the FSB roof in the dose computations. This same Tritium has therefore been double counted because it is again included in the storm drain and groundwater portions of the dose computations.

105A MH-A2 sample was collected only 7 days after the vent fan was placed back in service (7/28/2011) and the Tritium activity in the sample was 3,140 pCi/L, approximately 30 times lower than the average Tritium activity from September 2010 to July 21, 2011.

Subsequent samples showed further decreases.

106It is noted that the LCD flow rate increased from approximately 0.5 to 0.9 L/day between December 21, 2011 and the end of the year.

107At the time, it was believed that raising pool levels above the light boxes for the dry cask work was acceptable because the construction drawings showed the boxes sourced via conduits that do not penetrate the liner. Therefore, it was not clear that a transient, planned operational design overfill would pose a problem. In this regard, it is also important to note that: (1) this light outlet box-mediated release through the liner does not exist under design conditions; and (2) it does not constitute a design flaw nor indication of liner aging issues.

Section 4.0 Conclusions and Planned Future Work September 26, 2012 Page 4-3 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 subsequent invasive inspections of the light boxes, it has been concluded that there is definitive indication that these boxes did contribute, at least in part, to the LCD flow rate under transient overfill conditions. This conclusion has been reached based, in part, on the observation of boron precipitate within the boxes and conduit penetrations.

Due to these investigations, the six light boxes that contain electrical conduits which penetrate the liner have been temporarily sealed and IPEC has implemented restrictions on the pool elevation during atypical operations. Entergy is also scheduling the removal of these light boxes with permanent plating/sealing of the liner so as to permanently eliminate any possible future contribution to the LCD flow rate.

Given the elevated 2010 and 2011 LCD flow rates, Figure 6B is included in this report to visually present both the historical LCD flow rate data and the Tritium data for the monitoring locations located within the Unit 2 Tritium plume boundaries. Review of Figure 6B suggests that the increased flow rates in the LCD do not correlate with trends observed in the Unit 2 monitoring locations, which further supports the conclusion that the flow into the LCD is not indicative of release of similar water into the groundwater system.

However, it is noted that the LCD flow rate remained elevated after the temporary sealing of the light boxes. This could either indicate that: (1) the temporary seals are not sufficiently robust; (2) there is an additional contributing leak in the liner; or (3) the continued 0.5 L/day flow is a residual effect, given the unknown travel time for water trapped behind the liner (prior to the repair) to migrate from the light boxes through the four-foot thick concrete wall and then into the LCD. Given the remaining uncertainty, additional liner investigations are currently being planned, and this monitoring location will be further evaluated based on additional data gathered during the upcoming quarterly monitoring rounds.

Throughout 2011, multiple peaks in Tritium activity have been observed in the MH-5 VCFD data, where the maximum activity (12/22/2011 sample) was multiple times higher than the initial, singular Q3 2010 peak108. While the water collected by the MH-5 VCFD is routed to the discharge canal as a monitored release, which is directly accounted for in the dose computations, the 2011 Tritium peaks initiated an increased MH-5 VCFD sampling frequency, from quarterly to weekly. This regimen was begun in June 2011 as part of an investigation to identify the ultimate cause of these elevated Tritium levels.

Based on these additional 2011 data, the Tritium peaks in MH-5 VCFD do not appear to be correlated with the recent increase in flow rate in the LCD, nor do they appear to foreshadow increases in the monitoring wells proximate to the Unit 2 SFP (see Figure 6B)109. This increased sample collection and additional investigations will continue during the subsequent quarterly monitoring rounds, with the investigation now more focused on potential process inputs such as potential Tritium contribution from plant/FSB vent condensate.

Previously identified, more historical transient leaks more fully discussed in earlier Quarterly Reports included: (1) the additional leakage from the Unit 1 SFPs during the 108The Q3 2010 peak was approximately ten times the baseline Tritium activity of approximately 1000 pCi/L, but had already decreased to baseline prior to the Post-Q3 2010 sample, taken only 10 days later.

109Review of Figure 6B, which includes four additional quarters of data (relative to that presented in the previous Q4 2010 report),

demonstrates that the Tritium peaks observed in MH-5 VCFD (as well as those observed in the proximate the monitoring wells) are not convincingly correlated with the increased flow rates in the LCD. Therefore, the conjecture that these data were potentially correlated, as hypothesized in both the Q3 and Q4 2010 reports, appears to be less likely the case given the additional data. As such, the Tritium peaks observed in the monitoring point data, particularly that from MW-31 and MW-32, appear to be more likely the result of the subsequently discussed transient surfaces spills, as well as the Retention Mechanisms(see above).

Section 4.0 Conclusions and Planned Future Work September 26, 2012 Page 4-4 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 2008 defueling operations; (2) the transient leakage from the distillation tank valves in Q1 2009; and (3) the Q4 2009 RWST/R.O. processing skid surface spill. These transient releases have generally migrated through the groundwater flow system and have nearly fully dissipated:

o Based on past work, additional leakage was expected during the raising of water levels in the Unit 1 SFPs for final fuel removal to ISFSI storage. Unit 1 SFPs leakage was terminated with the drainage and sealing of the pools. This previous, transient leakage was initially verified as pronounced increases in Strontium and Cesium in the monitoring locations closest to Unit 1. These near-pool locations have since decreased below the pre-defueling levels, and downgradient locations have generally decreased to, or are currently approaching, pre-defueling levels. However, additional Strontium increases have recently been observed in a few monitoring installations farther downgradient, possibly related to delayed inputs from Retention Mechanism(s). Sampling intervals within the river boundary wells are also exhibiting general increases in Strontium activity during 2011 as this transient input migrates through the system. The transient Strontium behavior at individual U1 monitoring locations is provided in Figure 7A, and discussed more fully in Section 3.5.2.

o The Q1 2009 leakage from the distillation tank valves was independently110 identified based on an increase in Tritium levels in monitoring installation MW-42 proximate to the tanks, and subsequent increases in downgradient wells (MW-53-82, U1-CSS, and MW-50-42). These valves were immediately repaired and the leakage was terminated. Based on the observed data trends, it appears that the Tritium input into the groundwater flow regime from the waste distillation tank valving leak has generally dissipated through the system111. However, additional potential impacts of this release via the Retention Mechanism(s) will be specifically evaluated during subsequent monitoring rounds.

o Due to a transient surface spill from a rental RWST/R.O. skid, Tritium I.L.s were exceeded in a number of upgradient Unit 2 monitoring locations from Q1 2010 to Q3 2010, and additional exceedances were noted in further downgradient installations as the Tritium-laden groundwater migrated downgradient. IPEC conducted investigations into the cause of these Tritium increases, which identified the Q4 2009 RWST/R.O. skid spill as the likely source (see Section 3.4.4). This Tritium release was transient and quickly eliminated. As expected, the Tritium activity in many of the upgradient locations decreased to below the I.L. relatively quickly (prior to the Q4 2010 quarterly monitoring round). Furthermore, monitoring wells located further downgradient also decreased below I.L s during 2011. Based on the observed data trends in Q3 2011 and Q4 2011, it appears that the Tritium input into the local groundwater flow regime from the transient RWST/R.O. processing skid has generally dissipated through the system. However, future releases from the storage/Retention Mechanism(s), replenished by this spill and historical SFP leaks, could create additional perturbations in Unit 2 Tritium levels.

110The valve leakage was initially identified during routine visual inspection rounds and immediately terminated. Given that the leak was within the Unit 1 FSB structure, it was documented in a Condition Report under Entergys Corrective Action Program. This valve leak and repair subsequently came to light within the GPI program during investigations into the cause of the abrupt increase in Tritium levels in MW-42. Additional emphasis has therefore been placed on routine review of these reports as they potentially relate to GPI objectives.

111Additional portions of these releases likely remain above the water table in the release area as recharge to the various Retention Mechanisms. This additional unsaturated zone source recharge will likely be manifested in the future as additional non-specific peaks in radionuclide levels due to episodic releases to the groundwater flow regime from these mechanisms (e.g., from intense/prolonged precipitation events).

Section 4.0 Conclusions and Planned Future Work September 26, 2012 Page 4-5 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 These data support the validity of the current CSM for use as a basis for Long Term Monitoring Program design. It is further noted that, while a portion of the above five documented localized release events112 traveled directly to the saturated groundwater regime and resulted in the observed transient peaks in radionuclide levels, additional portions of these releases likely remain above the water table as recharge to the various Retention Mechanisms. This additional unsaturated zone source recharge will likely be manifested in the future as additional non-specific peaks in radionuclide levels due to episodic releases to the groundwater flow regime from these mechanisms (e.g., from intense/prolonged precipitation events).

From both qualitative and quantitative perspectives, the overall quarterly monitoring data sets from 2011 support the conclusion that the overall Tritium activity in the Unit 2 plume has decreased substantially since termination of the identified Unit 2 SFP leaks. These overall reductions have become particularly evident on Figures 6 and 6A of the more recent quarterly reports where the shaded plume113 no longer extends to the river, as it did prior to Q2 2009. It is further visually evident from Figure 6A that the core of the plume (with quarterly rolling average activities greater than 100,000 pCi/L and 2007 bounding core activities greater than 250,000 pCi/L) has also shown a marked decrease in activity and extent. The total Tritium plume activity has also reestablished an overall decreasing trend in the past two quarters (Q3 2011 and Q4 2011) as the transient RWST/R.O. surface spill has generally dissipated through the system (see Figure G-17). Based on the data and analyses provided above, our conclusion is that the Tritium plume associated with the historical leaks in the Unit 2 SFP has undergone long-term, overall reductions in activity which are consistent with Monitored Natural Attenuation (MNA), the remedial technology selected for the IPEC Site. Given this conclusion, and the recognition that Entergy has terminated all identified leaks in the Unit 2 SFP that are impacting the groundwater system114, this Unit 2 Tritium plume satisfies the requirements for Monitored Natural Attenuation.

The overall Strontium activity within the Unit 1 plume had generally been stable or decreasing in response to West Pool demineralization conducted by Entergy beginning in 2006. However, the final defueling of the Unit 1 SFPs resulted in an initial, noticeable increase, followed by a subsequent and commensurate decrease, in Strontium levels proximate to the SFPs, with later increases in the downgradient Strontium levels (see 112These transient events included: the increased Unit 1 SFPs leakage during defueling, the Unit 1 Distillate Tank Valve leak, the Unit 2 RWST R.O. skid spill, the Unit 3 FSB roof condensate input into manhole A2 and the Unit 1 CSB Sample Sink Overflow.

113The plume shading on Figure 6 demarks the estimated boundary that separates Tritium levels greater than 5,000 pCi/L from those below this value, and provides a reasonable demarcation level for illustrating plume geometry and temporal variation.

Although this value equates to one-quarter of the drinking water standard for Tritium, GZA emphasizes that drinking water standards (USEPA MCLs) do not apply to the IPEC property given that there are no drinking water sources on or proximate to the site. Where yearly rolling average radionuclide activity data were available for multiple depths at a given location, GZA used the highest value to develop plume delineations. This is a typical approach to represent three-dimensional contaminant data sets on two-dimensional maps.

114In addition to the more current data, further justification for this conclusion can be found in Section 3.6 of the Q1 2009 Quarterly Monitoring Report as well as the Hydrogeologic Site Investigation Report. The Q1 2009 Report summarizes additional, more quantitative analyses which were completed to further investigate the integrity of the Unit 2 SFP. These analyses provide further support for the conclusion that the Unit 2 SFP is no longer releasing Tritium to the groundwater system. However, given the more recent behavior observed in the Unit 2 LCD and MH-5 VCFD data, additional investigations/data evaluations are underway. In this regard, it is noted that these analyses cannot definitively and completely rule out the possibility of a remaining small Unit 2 SFP leak which could then also be supplying Tritium to the groundwater flow regime in addition to the Retention Mechanism(s) and surface spill from the process skid discussed above. While it is not possible to quantify the size of the minimum detectable leak with any degree of certainty, we believe that the maximum leak rate from the Unit 2 SFP that could potentially remain undetected by the groundwater monitoring system is less than 10 to 30 gpd (0.007 to 0.021 gallons per minute). It is also likely that if a small leak exists in the Unit 2 SFP liner, it should not get worse with time, as based on liner evaluations previously conducted by Entergy. It is further emphasized that while a leak of greater than 0.02 gallons per minute should be large enough to be readily detectable with the existing Long Term Monitoring Program; this amount of Tritium release to the river is still small compared to permitted levels of Tritium discharge to the river through the Discharge Canal.

Section 4.0 Conclusions and Planned Future Work September 26, 2012 Page 4-6 12-9-26 FINAL LTM 2011 Quarter One-Four Report.docx File No. 01.0017869.92 Figure 7 and 7A). This is as was predicted given the requirement to temporarily raise the pool levels for fuel rod removal, thus increasing leakage rate from the SFPs115. As anticipated, the levels proximate to the pool have decreased, recently falling to activities approximately 85-98% lower than the average pre-defueling Strontium levels. Levels further downgradient of the pools are generally showing continued decreases as this additional Strontium-contaminated water flushes through the groundwater flow system.

It is expected that this flushing mechanism will be protracted given the aforementioned impact of partitioning on Strontium levels in the groundwater and potential future inputs from Retention Mechanism(s). However, over time it is expected that Strontium levels in more downgradient wells will also exhibit overall downward trends to values below pre-defueling levels. From an overall perspective, as based on the data through Q4 2011, the total Strontium activity in the Unit 1 plume has decreased by approximately 68%

since the completion of the Unit 1 SFPs defueling operations, and has decreased by approximately 20% when compared to pre-defueling conditions. All indications are that the Unit 1 Strontium plume will continue to dissipate given that the SFPs Strontium source has been terminated. Given this conclusion and the recognition that Entergy has terminated all identified leaks in the Unit 1 SFPs through decommissioning, the Unit 1 Strontium plume satisfies the requirements for Monitored Natural Attenuation.

The above conclusions are continually reassessed on a quarterly basis as new data becomes available. In particular, the current LCD flow rates and the elevated MH-5 VCFD Tritium activity have both initiated additional investigations. Even though increased flow rates have recently been observed in the LCD116, no unexplained, recent 2011 Tritium peaks have been observed in the proximate Unit 2 monitoring installations.

Therefore, the current data continues to suggest that no new, unidentified SFP leaks are releasing Tritium to the groundwater system.

The amount of radionuclides being released through the groundwater pathway, even with the somewhat increased Tritium levels currently observed due to the residual RWST/R.O. skid transient surface spill impacts, the more recent Unit 1 CSB Sample Sink Overflow and the manhole A2 release, is still small compared to permitted levels of radionuclides discharged to the river through the Discharge Canal.

115As of late 2008, all the fuel rods have been removed from the Unit 1 SFPs and the pool water has been drained. As such, the Unit 1 SFPs is no longer an active source of radionuclides to the subsurface.

116All of the water collected by the LCD is fully contained and does not enter the groundwater regime.

FINAL QUARTERLY LONG-TERM GROUNDWATER MONITORING REPORT Q1 THROUGH Q4 2011 (REPORT NO. 13)

TABLES Table 1 Groundwater Sampling Methods, Equipment, Frequency, and Depths Table 2 Historic Quarterly Low Tide Groundwater Elevations Table 3-Q1 First Quarter 2011 Groundwater Analytical Results and Averages Table 3-Q2 Second Quarter 2011 Groundwater Analytical Results and Averages Table 3-Q3 Third Quarter 2011 Groundwater Analytical Results and Averages Table 3-Q4 Fourth Quarter 2011 Groundwater Analytical Results and Averages Table 4-Q1 2011 1st Quarter Groundwater Analytical Results and I.L.s Table 4-Q2 2011 2nd Quarter Groundwater Analytical Results and I.L.s Table 4-Q3 2011 3rd Quarter Groundwater Analytical Results and I.L.s Table 4-Q4 2011 4th Quarter Groundwater Analytical Results and I.L.s Table 5 Historic Groundwater Analytical Results

TABLE 1 GROUNDWATER SAMPLING METHODS, EQUIPMENT, FREQUENCY AND DEPTHS INDIAN POINT ENGERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 1 - Groundwater Sampling Methods, Equipment, Frequency and Depths.xlsx; Methods, Frequency, Depths Page 1 of 3 See Page 3 for Notes Top Bottom Top Bottom Feet Below TOC Elevation in Feet msl MW-30-69 Waterloo Low Flow Waterloo Multilevel System Quarterly 67.3 71.3 8.4 4.4 69.3 6.4 MW-30-84 Waterloo Low Flow Waterloo Multilevel System Quarterly 77.3 85.4

-1.6

-9.7 83.8

-8.1 MW-31-49 Waterloo Low Flow Waterloo Multilevel System Quarterly 34.8 49.3 40.8 26.3 48.8 26.8 MW-31-63 Waterloo Low Flow Waterloo Multilevel System Quarterly 55.3 63.8 20.3 11.8 63.3 12.3 MW-31-85 Waterloo Low Flow Waterloo Multilevel System Quarterly 69.8 85.4 5.8

-9.8 84.8

-9.2 MW-32-59 Waterloo Low Flow Waterloo Multilevel System Quarterly 28.3 61.3 48.8 15.8 58.8 18.3 MW-32-85 Waterloo Low Flow Waterloo Multilevel System Quarterly 79.3 92.8

-2.2

-15.7 85.3

-8.2 MW-32-131 Waterloo Low Flow Waterloo Multilevel System Inactive 125.8 138.3

-48.7

-61.2 130.8

-53.7 MW-32-149 Waterloo Low Flow Waterloo Multilevel System Quarterly 125.8 156.8

-48.7

-79.7 149.3

-72.2 MW-32-173 Waterloo Low Flow Waterloo Multilevel System Quarterly 165.8 174.3

-88.7

-97.2 172.8

-95.7 MW-32-190 Waterloo Low Flow Waterloo Multilevel System Quarterly 180.3 193.9

-103.2

-116.8 190.3

-113.2 MW-33 Low Flow Peristaltic Pump Annually 8.0 30.0 10.6

-11.4 16 2.6 MW-34 Low Flow Peristaltic Pump Inactive 5.0 30.0 13.1

-11.9 16.5 1.6 MW-35 Low Flow Peristaltic Pump Annually 6.5 30.0 11.9

-11.6 15 3.4 MW-36-245 Low Flow Peristaltic Pump Quarterly 11.0 24.0 0.6

-12.4 17

-5.4 MW-36-41 Low Flow Peristaltic Pump Inactive 36.0 41.0

-24.3

-29.3 37.0

-25.3 MW-36-52 Low Flow Peristaltic Pump Quarterly 48.0 53.0

-36.3

-41.3 50

-38.3 MW-37-22 Low Flow Peristaltic Pump Quarterly 12.0 22.0 2.9

-7.2 17

-2.2 MW-37-32 Low Flow Peristaltic Pump Quarterly 28.0 32.5

-13.2

-17.7 29.0

-14.2 MW-37-40 Low Flow Peristaltic Pump Quarterly 38.5 40.5

-23.7

-25.7 39.0

-24.2 MW-37-57 Low Flow Peristaltic Pump Quarterly 52.0 57.0

-37.2

-42.2 55.0

-40.2 MW-38 Low Flow Peristaltic Pump Inactive 5.0 40.0 9.0

-26.0 25.4

-11.4 MW-39-67 Waterloo Low Flow Waterloo Multilevel System Semi-Annually 65.0 70.5 15.0 9.5 67.0 13.0 MW-39-84 Waterloo Low Flow Waterloo Multilevel System Semi-Annually 76.5 85.0 3.5

-5.0 83.5

-3.5 MW-39-102 Waterloo Low Flow Waterloo Multilevel System Semi-Annually 93.0 103.0

-13.0

-23.0 101.5

-21.5 MW-39-124 Waterloo Low Flow Waterloo Multilevel System Semi-Annually 115.0 126.5

-35.0

-46.5 124.0

-44.0 MW-39-183 Waterloo Low Flow Waterloo Multilevel System Semi-Annually 169.5 186.0

-89.5

-106.0 182.5

-102.5 MW-39-195 Waterloo Low Flow Waterloo Multilevel System Semi-Annually 193.0 198.6

-113.0

-118.6 195.0

-115.0 MW-40-27 Waterloo Low Flow Waterloo Multilevel System Quarterly 18.2 35.2 55.0 38.0 26.7 46.5 MW-40-46 Waterloo Low Flow Waterloo Multilevel System Quarterly 44.2 53.7 29.0 19.5 46.2 27.0 MW-40-81 Waterloo Low Flow Waterloo Multilevel System Quarterly 64.7 84.2 8.5

-11.0 80.7

-7.5 MW-40-100 Waterloo Low Flow Waterloo Multilevel System Quarterly 93.2 106.7

-20.0

-33.5 100.2

-27.0 MW-40-127 Waterloo Low Flow Waterloo Multilevel System Quarterly 125.2 136.7

-52.0

-63.5 127.2

-54.0 MW-40-162 Waterloo Low Flow Waterloo Multilevel System Quarterly 158.7 190.3

-85.5

-117.1 161.7

-88.5 MW-41-40 Low Flow Peristaltic Pump Quarterly 22.0 42.0 32.1 12.1 36.0 18.1 MW-41-63 Modified Well Vol. Purge Waterra Pump Quarterly 59.0 64.0

-4.9

-9.9 61.0

-6.9 MW-42-49 Modified Well Vol. Purge Submersible Pump Quarterly 31.0 51.0 38.4 18.4 41.0 28.4 MW-42-78 Modified Well Vol. Purge Waterra Pump Quarterly 69.0 79.0 0.5

-9.5 74.0

-4.5 MW-43-28 Low Flow Submersible Pump Quarterly 8.0 28.0 40.0 20.0 23.0 25.0 MW-43-62 Low Flow Submersible Pump Quarterly 42.0 62.0 5.8

-14.2 54.0

-6.2 MW-44-66 Modified Well Vol. Purge Submersible Pump Quarterly 52.0 67.0 41.0 26.0 63.0 30.0 MW-44-102 Modified Well Vol. Purge Waterra Pump Quarterly 79.0 104.0 14.1

-10.9 80.0 13.1 MW-45-42 Modified Well Vol. Purge Peristaltic Pump Quarterly 27.5 42.5 25.7 10.7 37.0 16.2 MW-45-61 Modified Well Vol. Purge Peristaltic Pump Quarterly 51.5 61.5 1.7

-8.3 58.0

-4.8 MW-46 Modified Well Vol. Purge Submersible Pump Quarterly 6.0 30.0 11.0

-13.0 10.5 6.5 MW-47-56 Low Flow Submersible Pump Inactive 36.0 56.0 33.8 13.8 52.0 17.8 MW-47-80 Modified Well Vol. Purge Waterra Pump Inactive 70.0 80.0

-0.3

-10.3 72.0

-2.3 SAMPLING DEPTH4 Sampling Method Well ID1 Sampling Equipment Used SAMPLING INTERVAL3 Ft Below Top of Casing Elevation in Feet msl Projected 2012 Sampling Frequency2

TABLE 1 GROUNDWATER SAMPLING METHODS, EQUIPMENT, FREQUENCY AND DEPTHS INDIAN POINT ENGERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 1 - Groundwater Sampling Methods, Equipment, Frequency and Depths.xlsx; Methods, Frequency, Depths Page 2 of 3 See Page 3 for Notes Top Bottom Top Bottom Feet Below TOC Elevation in Feet msl SAMPLING DEPTH4 Sampling Method Well ID1 Sampling Equipment Used SAMPLING INTERVAL3 Ft Below Top of Casing Elevation in Feet msl Projected 2012 Sampling Frequency2 MW-48-23 Low Flow Peristaltic Pump Inactive 8.0 23.0 6.8

-8.2 15.8

-1.0 MW-48-37 Low Flow Peristaltic Pump Inactive 33.0 38.0

-17.8

-22.8 35.8

-20.6 MW-49-26 Low Flow Peristaltic Pump Quarterly 15.0 25.0

-0.8

-10.8 20.0

-5.8 MW-49-42 Low Flow Peristaltic Pump Quarterly 32.0 42.0

-17.8

-27.8 37.0

-22.8 MW-49-65 Low Flow Peristaltic Pump Quarterly 60.0 65.0

-45.5

-50.5 61.0

-46.5 MW-50-42 Low Flow Peristaltic Pump Quarterly 22.0 42.0

-7.6

-27.6 27.0

-12.6 MW-50-66 Low Flow Peristaltic Pump Quarterly 62.0 67.0

-47.4

-52.4 60.0

-45.4 MW-51-40 Waterloo Low Flow Waterloo Multilevel System Quarterly 29.7 44.2 38.0 23.5 39.7 28.0 MW-51-79 Waterloo Low Flow Waterloo Multilevel System Quarterly 63.2 81.2 4.5

-13.5 78.7

-11.0 MW-51-104 Waterloo Low Flow Waterloo Multilevel System Quarterly 101.2 111.2

-33.5

-43.5 103.7

-36.0 MW-51-135 Waterloo Low Flow Waterloo Multilevel System Quarterly 130.2 143.7

-62.5

-76.0 135.2

-67.5 MW-51-163 Waterloo Low Flow Waterloo Multilevel System Quarterly 154.7 166.2

-87.0

-98.5 162.7

-95.0 MW-51-189 Waterloo Low Flow Waterloo Multilevel System Quarterly 184.2 197.8

-116.5

-130.1 189.2

-121.5 MW-52-11 Modified Well Vol. Purge Peristaltic Pump Annually 2.0 12.0 12.9 2.9 10.0 4.9 MW-52-18 Waterloo Low Flow Waterloo Multilevel System Annually 10.0 30.0 4.9

-15.1 17.5

-2.6 MW-52-48 Waterloo Low Flow Waterloo Multilevel System Annually 48.0 56.0

-33.1

-41.1 48.0

-33.1 MW-52-64 Waterloo Low Flow Waterloo Multilevel System Annually 59.0 71.5

-44.1

-56.6 64.0

-49.1 MW-52-122 Waterloo Low Flow Waterloo Multilevel System Annually 110.5 123.5

-95.6

-108.6 122.0

-107.1 MW-52-162 Waterloo Low Flow Waterloo Multilevel System Annually 154.5 164.0

-139.6

-149.1 161.5

-146.6 MW-52-181 Waterloo Low Flow Waterloo Multilevel System Annually 171.0 198.1

-156.1

-183.2 181.0

-166.1 MW-53-82 Low Flow Submersible Pump Quarterly 62.0 82.0 7.9

-12.1 75.0

-5.1 MW-53-120 Modified Well Vol. Purge Waterra Pump Quarterly 100.0 120.0

-29.8

-49.8 105.0

-34.8 MW-54-37 Waterloo Low Flow Waterloo Multilevel System Quarterly 29.0 42.0

-15.9

-28.9 36.5

-23.4 MW-54-58 Waterloo Low Flow Waterloo Multilevel System Quarterly 51.5 64.0

-38.4

-50.9 57.5

-44.4 MW-54-123 Waterloo Low Flow Waterloo Multilevel System Quarterly 116.0 126.0

-102.9

-112.9 123.0

-109.9 MW-54-144 Waterloo Low Flow Waterloo Multilevel System Quarterly 135.0 155.5

-121.9

-142.4 144.0

-130.9 MW-54-173 Waterloo Low Flow Waterloo Multilevel System Quarterly 170.5 182.0

-157.4

-168.9 172.5

-159.4 MW-54-190 Waterloo Low Flow Waterloo Multilevel System Quarterly 185.0 203.6

-171.9

-190.5 190.0

-176.9 MW-55-24 Low Flow Peristaltic Pump Quarterly 14.0 24.0 3.8

-6.2 16.0 1.8 MW-55-35 Low Flow Peristaltic Pump Quarterly 30.0 35.0

-12.2

-17.2 32.0

-14.2 MW-55-54 Low Flow Peristaltic Pump Quarterly 44.0 54.0

-26.2

-36.2 47.0

-29.2 MW-56-53 Modified Well Vol. Purge Submersible Pump Semi-Annually 49.2 54.2 20.1 15.1 52.0 17.3 MW-56-83 Modified Well Vol. Purge Waterra Pump Semi-Annually 69.9 84.9

-0.7

-15.7 74.0

-4.8 MW-57-11 Modified Well Vol. Purge Peristaltic Pump Annually 6.0 11.0 8.7 3.7 10.0 4.7 MW-57-20 Modified Well Vol. Purge Peristaltic Pump Annually 15.5 20.5

-0.8

-5.8 19.0

-4.3 MW-57-45 Modified Well Vol. Purge Peristaltic Pump Annually 30.5 45.5

-15.7

-30.7 40.0

-25.2 MW-58-26 Low Flow Peristaltic Pump Semi-Annually 16.0 26.0

-1.8

-11.8 20.0

-5.8 MW-58-65 Low Flow Peristaltic Pump Semi-Annually 50.0 65.0

-35.8

-50.8 54.0

-39.8 MW-59-32 Low Flow Peristaltic Pump Inactive 21.0 31.0

-6.6

-16.6 27.0

-12.6 MW-59-45 Low Flow Peristaltic Pump Inactive 35.0 45.0

-21.1

-31.1 42.0

-28.1 MW-59-68 Low Flow Peristaltic Pump Inactive 53.0 68.0

-38.8

-53.8 58.0

-43.8 MW-60-35 Waterloo Low Flow Waterloo Multilevel System Quarterly 24.9 39.4

-12.4

-26.9 34.9

-22.4 MW-60-53 Waterloo Low Flow Waterloo Multilevel System Quarterly 45.4 59.4

-32.9

-46.9 53.4

-40.9 MW-60-72 Waterloo Low Flow Waterloo Multilevel System Quarterly 66.4 78.9

-53.9

-66.4 72.4

-59.9 MW-60-135 Waterloo Low Flow Waterloo Multilevel System Quarterly 124.9 141.4

-112.4

-128.9 134.9

-122.4 MW-60-154 Waterloo Low Flow Waterloo Multilevel System Quarterly 147.4 164.9

-134.9

-152.4 154.4

-141.9 MW-60-176 Waterloo Low Flow Waterloo Multilevel System Quarterly 170.9 200.4

-158.4

-187.9 175.9

-163.4

TABLE 1 GROUNDWATER SAMPLING METHODS, EQUIPMENT, FREQUENCY AND DEPTHS INDIAN POINT ENGERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 1 - Groundwater Sampling Methods, Equipment, Frequency and Depths.xlsx; Methods, Frequency, Depths Page 3 of 3 See Page 3 for Notes Top Bottom Top Bottom Feet Below TOC Elevation in Feet msl SAMPLING DEPTH4 Sampling Method Well ID1 Sampling Equipment Used SAMPLING INTERVAL3 Ft Below Top of Casing Elevation in Feet msl Projected 2012 Sampling Frequency2 MW-62-18 Low Flow Peristaltic Pump Quarterly 4.7 14.7 8.1

-1.9 13.5

-0.7 MW-62-37 Low Flow Peristaltic Pump Quarterly 33.3 38.3

-20.5

-25.5 34.5

-21.7 MW-62-53 Waterloo Low Flow Waterloo Multilevel System Quarterly 49.6 54.1

-36.8

-41.3 53.1

-40.3 MW-62-71 Waterloo Low Flow Waterloo Multilevel System Quarterly 61.1 82.6

-48.3

-69.8 71.1

-58.3 MW-62-92 Waterloo Low Flow Waterloo Multilevel System Quarterly 88.6 99.1

-75.8

-86.3 91.6

-78.8 MW-62-138 Waterloo Low Flow Waterloo Multilevel System Quarterly 126.1 143.6

-113.3

-130.8 138.1

-125.3 MW-62-182 Waterloo Low Flow Waterloo Multilevel System Quarterly 177.6 198.7

-164.8

-185.9 182.1

-169.3 MW-63-18 Low Flow Peristaltic Pump Quarterly 8.0 18.0 5.1

-4.9 14.9

-1.8 MW-63-34 Low Flow Peristaltic Pump Quarterly 30.0 35.0

-16.9

-21.9 31.5

-18.4 MW-63-50 Waterloo Low Flow Waterloo Multilevel System Quarterly 41.5 58.0

-29.2

-45.7 49.5

-37.2 MW-63-93 Waterloo Low Flow Waterloo Multilevel System Quarterly 81.5 100.5

-69.2

-88.2 93.0

-80.7 MW-63-112 Waterloo Low Flow Waterloo Multilevel System Quarterly 106.5 112.0

-94.2

-99.7 111.5

-99.2 MW-63-121 Waterloo Low Flow Waterloo Multilevel System Quarterly 118.0 127.5

-105.7

-115.2 121.0

-108.7 MW-63-163 Waterloo Low Flow Waterloo Multilevel System Quarterly 150.5 165.0

-138.2

-152.7 162.5

-150.2 MW-63-174 Waterloo Low Flow Waterloo Multilevel System Quarterly 168.0 191.1

-155.7

-178.8 174.0

-161.7 MW-66-21 Modified Well Vol. Purge Peristaltic Pump Quarterly 7.0 27.0 6.4

-13.6 14.1

-0.7 MW-66-36 Modified Well Vol. Purge Peristaltic Pump Quarterly 31.0 36.0

-17.6

-22.6 33.6

-20.2 MW-67-39 Waterloo Low Flow Waterloo Multilevel System Quarterly 28.8 54.3

-15.9

-41.4 38.3

-25.4 MW-67-105 Waterloo Low Flow Waterloo Multilevel System Quarterly 90.3 110.8

-77.4

-97.9 104.8

-91.9 MW-67-173 Waterloo Low Flow Waterloo Multilevel System Quarterly 164.8 188.3

-151.9

-175.4 172.3

-159.4 MW-67-219 Waterloo Low Flow Waterloo Multilevel System Quarterly 209.3 229.8

-196.4

-216.9 218.8

-205.9 MW-67-276 Waterloo Low Flow Waterloo Multilevel System Quarterly 250.8 281.3

-237.9

-268.4 275.3

-262.4 MW-67-323 Waterloo Low Flow Waterloo Multilevel System Quarterly 317.8 328.3

-304.9

-315.4 322.3

-309.4 MW-67-340 Waterloo Low Flow Waterloo Multilevel System Quarterly 335.3 347.9

-322.4

-335.0 339.8

-326.9 MW-107 Low Flow Submersible Pump Annually 105.1 126.1 37.7 16.7 32.7 110.1 MW-111 Low Flow Peristaltic Pump Semi-Annually 11.6 17.4 6.8 1.0 16.5 1.9 U3-4S Low Flow Peristaltic Pump Quarterly 7.4 17.4 6.5

-3.5 15.5

-1.6 U3-4D Modified Well Vol. Purge Peristaltic Pump Quarterly 25.0 27.6

-10.5

-13.1 25.6

-11.1 U3-T1 Low Flow Peristaltic Pump Quarterly 0.2 1.2 8.3 7.3 5.7 2.8 U3-T2 Low Flow Peristaltic Pump Quarterly 0.6 1.6 7.9 6.9 5.7 2.8 U1-CSS Low Flow Peristaltic Pump Semi-Annually NA 10.2 NA 9.9 14.0 6.1 LAF-002 Low Flow NA Semi-Annually NA NA NA NA NA

-22.3 I-2 Modified Well Vol. Purge Submersible Pump Annually 30.1 40.1 52.1 42.1 40.0 42.2 U1-NCD Grab NA Quarterly NA NA NA NA NA NA U1-SFDS Grab NA Quarterly NA NA NA NA NA NA MH-5 VCFD6 Grab NA Quarterly NA NA NA NA NA NA B-16 Grab NA Quarterly NA NA NA NA NA NA B-66 Grab NA Quarterly NA NA NA NA NA NA Notes:

1. For nested multi-level monitoring wells, suffix of well ID indicates depth (rounded to nearest foot) from reference point on casing to bottom of well screen.

For Waterloo multi-level systems, suffix indicates depth (rounded to nearest foot) from reference point on casing to top of sampling port. Well IDs without a suffix are open bedrock wellbores.

2. Projected sampling frequencies presented for 2012 are subject to change.
3. For nested multi-level montoring wells, interval includes well screen and sand pack. For Waterloo multi-level systems, interval includes open wellbore between bottom of 1st packer above and top of 1st packer below sampling port. For open bedrock wellbores, interval extends from bottom of casing to bottom of hole.
4. Sampling depths within sampling intervals (i.e. location of pump intake) have been located adjacent to a transmissive zone where possible.
5. Dot pattern denotes sampling interval is positioned within overburden. Open box indicates sampling interval is in bedrock.
6. These locations are storm drains or foundation drains.

TABLE 2 HISTORIC QUARTERLY LOW TIDE GROUNDWATER ELEVATIONS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 2 - Historic Quarterly Low Tide Groundwater Elevations.xlsx; gw elevations Page 1 of 3 See Page 3 for Notes Quarter 21, 2007 Quarter 32, 2007 Quarter 43, 2007 Quarter 14, 2008 Quarter 25, 2008 Quarter 36, 2008 Quarter 47, 2008 Quarter 18, 2009 Quarter 29, 2009 Quarter 310,11, 2009 Quarter 412, 2009 Quarter 113, 2010 Quarter 214, 2010 Quarter 315, 2010 Quarter 416, 2010 Quarter 117, 2011 Quarter 218, 2011 Quarter 319, 2011 Quarter 420, 2011 HR-1 NA

-0.86

-1.57

-2.15

-1.13

-1.05

-1.69

-3.28

-1.52

-0.27

-3.59

-0.36

-0.56

-0.71 NA NA

-1.14

-0.89

-1.51 I-2 50.23 48.62 51.87 53.73 52.11 52.90 50.75 NA NA NA 51.69 52.46 53.33 50.49 NA 50.74 53.62 54.07 51.05 MW-30-69 11.83 11.53 12.00 NA 12.28 11.77 11.71 12.33 11.84 13.76 NA NA NA NA 11.56 11.23 12.18 13.16 11.71 MW-30-84 12.77 12.47 12.83 NA 13.06 12.68 12.36 13.13 12.82 12.48 12.27 13.26 12.76 11.31 12.32 12.29 NA NA NA MW-31-49 44.09 NA 45.40 47.50 46.14 45.39 44.13 46.44 45.40 MW-31-63 41.56 NA 42.71 45.52 43.96 42.17 41.21 44.12 43.20 MW-31-85 39.59 NA 40.81 43.19 41.89 40.58 39.64 42.10 40.64 MW-32-48 NA 42.12 46.73 48.81 47.77 46.98 45.79 48.08 47.31 MW-32-59 NA 41.44 45.99 47.99 46.75 45.72 44.48 46.83 45.62 MW-32-85 (MW-32-92)21 10.27 12.35 12.78 13.30 13.17 12.30 12.16 12.60 11.61 MW-32-131 (MW-32-140)21 13.11 11.96 13.21 25.01 15.67 11.34 11.53 11.86 11.06 MW-32-149 (MW-32-165)21 8.18 9.87 10.06 10.20 10.04 9.71 9.77 10.00 9.18 MW-32-173 NA 9.73 9.86 9.92 9.70 9.45 9.45 9.68 8.81 MW-32-190 (MW-32-196)21 6.74 8.05 7.88 7.88 7.52 7.16 7.05 7.24 6.26 MW-33 10.08 9.80 10.38 11.49 11.66 10.55 10.60 11.23 10.52 MW-34 9.87 9.82 10.44 11.63 12.03 10.54 10.54 11.25 6.71 MW-35 10.03 9.67 10.37 11.65 12.06 10.68 10.68 11.36 NA MW-36-24 8.89 7.31 7.67 6.85 6.86 7.58 9.05 NA 7.25 MW-36-41 8.22 NA NA NA NA NA NA NA NA MW-36-52 7.43 6.43 6.45 6.42 6.29 6.99 7.45 8.12 6.62 MW-37-22 5.51 5.15 4.83 4.66 4.18 5.36 5.55 4.45 5.24 MW-37-32 5.51 5.07 4.82 4.63 4.05 5.36 5.64 4.55 5.32 MW-37-40 5.40 6.83 6.19 6.17 5.95 6.18 6.04 5.46 6.19 MW-37-57 7.07 6.23 6.39 6.28 6.07 6.64 7.20 6.50 6.56 MW-38 3.01 2.19 1.46 2.22 1.53 2.12 1.22 NA 2.24 MW-39-67 NA NA 26.84 32.20 31.69 25.96 25.21 28.74 NA MW-39-84 NA NA 26.64 31.94 31.48 25.78 25.12 28.62 NA MW-39-100 NA NA 26.38 30.99 31.34 25.52 24.79 28.32 NA MW-39-102 NA NA 26.31 31.56 NA NA NA NA NA MW-39-124 NA NA 26.05 28.37 30.67 25.07 24.43 27.74 NA MW-39-183 NA NA 25.28 29.74 29.83 22.33 23.79 26.78 NA MW-39-195 NA NA 24.36 28.80 28.89 23.35 22.70 25.63 NA MW-40-27 NA NA 55.46 60.39 59.99 54.70 54.22 59.53 57.25 58.75 55.71 59.08 59.86 52.85 NA 56.35 58.88 51.14 53.88 MW-40-46 NA 47.27 53.19 59.35 59.09 52.57 52.35 59.13 56.56 MW-40-81 NA 41.65 47.45 56.06 55.78 47.28 46.83 55.67 53.13 MW-40-100 NA 39.47 45.18 54.10 53.75 44.83 44.32 53.59 51.24 MW-40-127 NA 38.89 44.60 53.61 53.39 44.33 43.87 53.29 50.59 MW-40-162 NA 36.67 41.09 50.49 50.26 41.32 40.66 49.76 46.80 48.42 42.85 49.55 50.03 38.96 44.88 45.00 50.64 50.68 NA MW-41-40 29.87 NA 32.48 36.57 33.81 31.28 30.71 33.62 32.05 MW-41-63 25.94 NA 27.77 33.31 32.76 27.53 26.96 30.38 28.39 MW-42-49 NA NA 34.55 34.96 34.81 34.52 34.43 34.78 34.47 MW-42-78 NA NA 35.71 36.63 36.28 35.38 35.07 36.03 35.75 MW-43-28 32.75 31.08 31.98 33.47 33.95 32.51 32.15 33.43 32.54 32.66 NA NA 34.23 37.14 31.95 37.47 NA NA NA MW-43-62 30.83 NA NA NA 32.16 30.48 31.76 34.13 30.88 NA 30.28 32.00 32.00 30.20 31.50 31.43 31.61 32.84 31.33 MW-44-67 33.36 NA 34.36 37.99 35.47 35.29 34.00 34.96 34.50 MW-44-102 23.10 NA 24.84 NA 30.88 25.86 25.16 28.09 27.41 MW-45-42 NA 24.82 28.47 34.19 37.16 28.63 25.45 32.02 29.03 MW-45-61 NA 24.33 27.57 32.91 32.46 27.16 26.68 29.99 23.25 MW-46 12.80 11.95 12.57 15.05 14.97 12.62 12.81 14.29 12.47 12.83 NA NA 16.49 12.45 13.22 13.01 13.21 14.56 11.21 MW-47-56 21.83 20.77 23.05 27.76 31.53 22.84 22.37 26.51 23.43 MW-47-80 22.29 21.41 21.82 26.53 28.35 21.52 21.08 26.37 24.18 MW-48-23

-0.08

-0.27

-0.39

-1.14

-0.23

-0.18

-0.48

-0.91

-0.19 MW-48-37 0.64 0.26

-0.06

-0.18 0.32 0.06

-0.15

-0.50 0.04 MW-49-26 1.04 NA

-0.37

-0.62 0.51 0.37 0.49

-0.25 0.54 MW-49-42 0.31 0.90 0.40

-0.44 0.92 1.02 0.68

-0.06 0.51 MW-49-65 0.89 1.01 0.34 0.07 0.70 0.68 0.47

-0.08 0.57 MW-50-42 7.24 NA NA NA 5.24 6.40 7.06 5.66 6.09 MW-50-66 3.71 NA NA 1.97 2.24 2.83 2.34 1.95 2.82 MW-51-40 NA 48.69 50.07 51.95 52.35 49.44 49.24 49.32 45.15 46.45 42.45 43.37 41.72 41.89 41.24 41.25 NA NA 42.57 MW-51-79 NA 39.92 41.07 42.91 44.17 40.71 40.36 42.75 42.15 MW-51-102 NA 35.98 38.07 38.46 39.04 36.56 36.17 38.18 37.78 MW-51-104 NA NA 37.93 38.41 39.02 36.49 36.03 37.99 37.49 MW-51-135 NA 37.42 39.47 39.99 40.71 38.10 37.68 39.75 39.34 MW-51-163 NA 33.79 34.83 36.15 36.77 34.30 33.90 35.74 35.44 MW-51-189 NA 29.33 30.16 31.34 31.79 29.65 29.36 30.81 30.48 32.18 29.93 31.85 31.42 29.07 29.60 29.48 31.16 31.45 NA MW-52-11 6.04 5.61 8.12 8.47 8.85 8.65 8.44 8.19 9.20 Well ID LOW RIVER TIDE GROUNDWATER ELEVATIONS (Feet msl)

TABLE 2 HISTORIC QUARTERLY LOW TIDE GROUNDWATER ELEVATIONS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 2 - Historic Quarterly Low Tide Groundwater Elevations.xlsx; gw elevations Page 2 of 3 See Page 3 for Notes Quarter 21, 2007 Quarter 32, 2007 Quarter 43, 2007 Quarter 14, 2008 Quarter 25, 2008 Quarter 36, 2008 Quarter 47, 2008 Quarter 18, 2009 Quarter 29, 2009 Quarter 310,11, 2009 Quarter 412, 2009 Quarter 113, 2010 Quarter 214, 2010 Quarter 315, 2010 Quarter 416, 2010 Quarter 117, 2011 Quarter 218, 2011 Quarter 319, 2011 Quarter 420, 2011 Well ID LOW RIVER TIDE GROUNDWATER ELEVATIONS (Feet msl)

MW-52-18 6.64 NA 8.63 6.04 6.07 5.89 6.02 5.78 5.87 MW-52-48 7.08 NA 6.55 6.53 5.95 6.20 6.14 6.05 5.75 MW-52-64 5.96 NA 5.90 5.25 5.03 5.21 5.16 5.20 4.89 MW-52-118 5.34 NA 4.41 4.44 4.32 4.36 4.68 4.23 4.23 MW-52-122 5.25 NA 4.26 4.32 4.18 4.21 4.55 4.11 4.20 MW-52-162 0.67 NA

-0.80

-1.31

-0.80

-0.98

-1.30

-2.07

-1.18 MW-52-181 0.41 NA

-1.08

-1.56

-1.00

-1.30

-1.64

-2.38

-1.54 MW-53-82 NA 9.59 10.03 11.99 12.60 10.35 NA 11.11 NA 11.11 9.87 11.15 11.67 9.98 11.27 10.59 12.07 13.49 11.90 MW-53-120 9.91 9.18 9.59 10.87 11.49 9.76 NA 10.55 9.78 10.43 9.43 10.53 11.02 9.60 10.33 10.35 11.55 12.07 11.13 MW-54-35 NA NA 6.40 6.27 6.36 6.16 6.41 5.75 5.87 MW-54-37 7.52 NA 6.58 6.45 6.53 6.30 6.58 5.90 6.04 MW-54-58 6.86 NA 5.82 5.60 5.55 5.53 5.76 5.49 5.17 MW-54-123 5.69 NA 4.16 3.65 3.52 4.01 4.06 2.99 3.56 MW-54-144 8.85 NA 7.13 6.60 6.48 6.92 6.97 5.89 6.53 MW-54-173 5.17 NA 3.52 2.99 2.85 3.27 3.29 2.19 2.72 MW-54-190 5.08 NA 3.46 2.91 2.76 3.16 3.13 2.00 2.49 MW-55-24 8.56 7.82 7.97 8.17 8.16 8.18 9.02 8.35 8.06 8.39 7.80 8.58 8.56 8.02 8.27 8.88 9.15 9.36 9.70 MW-55-35 8.10 7.29 7.52 7.60 7.59 7.69 8.30 7.63 9.49 MW-55-54 8.47 7.65 7.75 8.08 8.32 8.22 8.82 NA 7.89 8.14 7.66 8.39 8.34 7.97 8.19 7.90 9.26 9.15 8.98 MW-56-53 21.04 20.16 NA NA 29.93 NA 21.90 27.33 22.06 MW-56-83 21.10 20.10 22.18 26.41 29.16 NA 21.51 25.13 22.60 MW-57-11 9.57 8.83 9.36 10.99 NA 10.03 10.27 11.11 10.09 MW-57-20 9.38 NA NA NA 12.07 10.02 9.92 10.63 9.84 MW-57-45 9.08 NA NA NA 10.59 NA NA 10.71 NA MW-58-26 8.03 6.49 6.58 8.32 NA 7.29 7.19 7.56 7.40 MW-58-65 6.03 6.83 6.22 NA 7.36 7.13 6.46 6.68 6.70 MW-59-32 1.06 NA 0.67 0.42 0.77 0.81 0.47 0.31 1.37 MW-59-45 1.06 1.27 0.42 NA 9.23 NA 2.52 0.44 NA MW-59-68 2.91 2.51 1.97 0.90

-0.11 NA

-1.79

-5.66 7.93 MW-60-35 2.19 1.28 1.32 1.58 1.63 0.82 2.04 1.99 3.07 MW-60-53

-0.63

-1.24

-1.67

-2.04

-1.37

-1.76

-2.03

-2.70 NA MW-60-55 NA

-0.28

-0.73

-1.10

-0.47

-0.90

-1.21

-1.91 NA MW-60-72 0.74

-0.09

-0.45

-0.68

-0.14

-0.64 NA

-1.43 0.28 MW-60-135 0.94 0.11

-0.44

-0.90

-0.27

-0.71

-1.02

-1.72 0.11 MW-60-154 0.08

-0.96

-1.61

-2.07

-1.49

-1.91

-2.25

-2.99 NA MW-60-176

-0.48

-1.38

-2.03

-2.47

-1.82

-2.16

-2.59

-3.41 NA MW-62-18 0.25 0.25

-0.37

-0.79 0.13 0.06

-0.12

-0.82 NA MW-62-37 0.59 0.61

-0.03

-0.46 0.49 0.59

-0.15

-1.13 0.11 MW-62-52 NA 0.48

-0.30

-1.13

-0.19

-0.29

-0.93

-1.64

-0.42 MW-62-53 0.95 0.54

-0.25

-1.01

-0.10

-0.16

-0.84

-2.03

-0.44 MW-62-71 0.89 0.22

-0.56

-1.26

-0.55

-0.56

-1.24

-2.15

-1.03 MW-62-92 1.07 0.58

-0.09

-0.76

-0.11

-0.10

-0.85

-1.68

-0.70 MW-62-138 1.40 0.77 0.09

-0.49 0.13 0.26

-0.37

-1.33

-0.40 MW-62-181 1.33 0.38

-0.33

-0.99

-0.32

-0.36

-0.92 NA

-0.88 MW-62-182 NA

-0.33

-1.83

-0.78

-1.29

-1.25

-1.85

-2.66

-1.82 MW-63-18 0.14 0.09

-0.10

-0.37 0.09 0.32

-0.08

-0.64 0.02 MW-63-34 0.51 0.19

-0.09

-0.40 0.13 0.05

-0.13

-0.74 0.18 MW-63-50 0.86 0.29

-0.38

-1.03

-0.47

-0.55

-1.24

-2.08

-0.45 MW-63-91 1.16 0.48

-0.19

-0.87

-0.25

-0.16

-0.89 NA

-0.01 MW-63-93 NA 0.55

-0.20

-0.87

-0.30

-0.24

-0.98

-1.68

-0.13 MW-63-112 0.03

-0.82

-1.46

-2.05

-1.69

-1.60

-2.26

-3.14

-1.45 MW-63-121 1.41 0.60

-0.18

-0.78

-0.24

-0.05

-0.86

-1.49 0.11 MW-63-163 0.70

-0.09

-0.83

-1.48

-0.86

-0.90

-1.54

-2.46

-0.98 MW-63-174 0.88 0.05

-0.65

-1.29

-0.62

-0.61

-1.19

-1.97

-0.59 MW-65-48 NA NA NA NA 38.60 43.22 NA 48.19 36.98 40.08 38.06 39.94 42.26 59.97 NA NA NA NA NA MW-65-80 NA NA NA NA 34.97 32.95 32.72 33.71 33.30 33.79 32.81 33.69 33.98 49.35 NA NA NA NA NA MW-66-21 0.26 0.17

-0.22

-0.74 0.05 0.17 0.29

-0.33 0.50 0.52 0.10

-0.01 1.82 1.05 1.02 0.74 1.65 0.45 0.50 MW-66-36 0.81 0.48

-0.04

-0.51 0.35 0.15 0.10

-0.86 0.51

-0.25

-0.43 1.75 1.49 0.36 0.59 2.28 1.18 0.41 MW-67-39 NA 1.02 0.34

-0.33 0.36 0.41

-0.02

-0.07

-0.56 0.81

-1.25

-0.76

-0.13

-0.09

-1.70

-1.42 NA

-1.58

-1.73 MW-67-105 NA 1.39 0.61

-0.04 0.57 0.65 0.16

-0.67

-0.43 MW-67-173 NA 0.75

-0.14

-0.83

-0.28

-0.26

-0.82

-1.62

-1.55 MW-67-219 NA 0.74

-0.19

-0.91

-0.32

-0.32

-0.86

-1.87

-1.59 MW-67-276 NA 1.61 0.60

-0.13 0.44 0.41

-0.14

-1.03

-0.91 MW-67-323 NA 0.18

-0.96

-1.75

-1.13

-1.35

-1.93

-2.86

-2.73 MW-67-340 NA 0.63

-0.52

-1.31

-0.87

-0.96

-1.56

-2.42

-2.40

-0.76

-3.27

-2.63

-2.26

-1.97

-3.72

-3.47 NA

-2.99

-3.80 MW-107 116.85 113.87 117.48 121.79 118.94 115.00 115.76 120.28 117.52

TABLE 2 HISTORIC QUARTERLY LOW TIDE GROUNDWATER ELEVATIONS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 2 - Historic Quarterly Low Tide Groundwater Elevations.xlsx; gw elevations Page 3 of 3 See Page 3 for Notes Quarter 21, 2007 Quarter 32, 2007 Quarter 43, 2007 Quarter 14, 2008 Quarter 25, 2008 Quarter 36, 2008 Quarter 47, 2008 Quarter 18, 2009 Quarter 29, 2009 Quarter 310,11, 2009 Quarter 412, 2009 Quarter 113, 2010 Quarter 214, 2010 Quarter 315, 2010 Quarter 416, 2010 Quarter 117, 2011 Quarter 218, 2011 Quarter 319, 2011 Quarter 420, 2011 Well ID LOW RIVER TIDE GROUNDWATER ELEVATIONS (Feet msl)

MW-108 9.58 8.61 8.77 9.98 10.07 NA 9.02 9.65 9.26 MW-109 9.52 6.80 7.22 9.50 10.12 7.82 7.88 NA 4.95 MW-111 9.56 9.66 9.74 10.74 11.24 9.74 10.48 10.87 9.47 OUT-1 NA 1.31 1.16 0.76 0.81 NA NA NA 1.08

-0.77 1.02 5.06 NA NA NA NA NA NA RW-1 NA NA 30.15 NA 30.04 29.52 29.05 29.10 NA U1-CSS NA 8.98 NA NA 19.11 15.39 NA 20.46 13.89 U3-1 4.20 NA NA NA NA NA NA NA NA U3-2 5.34 NA NA NA NA NA NA NA NA U3-3 7.53 6.52 6.63 8.67 9.25 8.25 8.94 9.13 7.29 U3-4D 4.25 NA 3.35 3.22 2.74 3.49 2.69 3.41 3.75 U3-4S 3.91 4.13 3.80 3.74 3.97 4.31 3.81 4.01 4.23 U3-C1 NA 1.64 3.58 3.36 0.99 2.36 0.81 0.64 1.92 2.43 0.12 0.20 2.98 NA 0.26 3.28 3.20 NA NA U3-T1 4.51 4.12 3.67 3.99 3.86 4.33 3.69 3.83 4.12 U3-T2 4.33 4.02 3.79 4.20 3.94 4.28 3.76 4.05 4.20 Notes:

NA = Data Not Available

1. Quarter 2, 2007 groundwater elevations were measured on 6/1/07 at 6:20 am.
2. Quarter 3, 2007 groundwater elevations were measured on 9/25/07 at 4:32 am.
3. Quarter 4, 2007 groundwater elevations were measured on 12/9/07 at 4:15 am.
4. Quarter 1, 2008 groundwater elevations were measured on 1/3/08 at 1:14 a.m.
5. Quarter 2, 2008 groundwater elevations were measured on 4/4/08 at 5:14 pm.
6. Quarter 3, 2008 groundwater elevations were measured on 7/10/08 at 11:35 am.
7. Quarter 4, 2008 groundwater elevations were measured on 11/11/08 at 2:54 am.
8. Quarter 1, 2009 groundwater elevations were measured on 1/9/09 at 2:42 am.
9. Quarter 2, 2009 groundwater elevations were measured on 5/22/09 at 2:41 pm.
10. Subsequent to Quarter 2, 2009, as described in our June 14, 2010 memorandum which was included as Appendix J in the Quarter 1, 2009 Report, a reduced number of transducers will be maintained in long term operation.

The rationale for this reduced transducer redeployment is included in the June 14, 2010 memorandum.

11. Quarter 3, 2009 groundwater elevations were measured on 8/9/09 at 8:18 am.
12. Quarter 4, 2009 groundwater elevations were measured on 11/28/09 at 3:45 pm.
13. Quarter 1, 2010 groundwater elevations were measured on 1/30/10 at 6:00 am.
14. Quarter 2, 2010 groundwater elevations were measured on 4/09/10 at 12:06 pm.
15. Quarter 3, 2010 groundwater elevations were measured on 7/31/10 at 12:30 am.
16. Quarter 4, 2010 groundwater elevations were measured on 10/16/10 at 1:36 am.
17. Quarter 1, 2011 groundwater elevations were measured on 1/22/11 at 8:20 pm.
18. Quarter 2, 2011 groundwater elevations were measured on 5/25/11 at 5:13 pm.
19. Quarter 3, 2011groundwater elevations were measured on 8/22/11 at 10:48 am.
20. Quarter 4, 2011 groundwater elevations were measured on 11/21/11 at 1:37 am.
21. MW-32 groundwater elevations from 2nd quarter, 2007 were based on an initial Waterloo Multi-Level configuration, which was subsequently reconfigured; initial depth intervals approximately corresponding to current configuration are listed in parentheses. The current configuration intervals MW-32-48 and MW-32-173 have no representative equivalent within the old configuration.

TABLE 3 FIRST QUARTER 2011 GROUNDWATER ANALYTICAL RESULTS AND AVERAGES INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q12011 FINAL Table 3 - First Quarter 2011 Groundwater Analytical Results and Averages.xlsx; Q12011 Table 3 Page 1 of 5 See Page 5 for Notes TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Date Time Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Average Average Average Average Average MW-30-69 Q2-2010 031 69.3 6.4 4/29/2010 12:55 1.61E+05 4.67E+03 2.78E+02

-1.31E-01 7.56E-01 9.40E-01

-2.29E+00 5.33E+00 5.59E+00 2.06E+00 5.37E+00 6.58E+00 NA NA NA 1.26E+05 ND ND ND NA MW-30-69 MW-30-69 Q2-2010 Mid 032 69.3 6.4 6/8/2010 12:32 1.52E+05 4.49E+03 4.80E+02 2.56E-01 4.79E-01 5.40E-01

-1.20E+00 6.55E+00 7.22E+00

-1.72E-01 5.45E+00 5.99E+00 NA NA NA 1.26E+05 MW-30-69 MW-30-69 Q3-2010 033 69.3 6.4 7/28/2010 12:33 1.28E+05 3.72E+03 1.80E+02 9.14E-02 5.26E-01 6.35E-01

-5.08E-01 9.69E+00 1.09E+01 1.67E+00 7.46E+00 9.20E+00 NA NA NA 1.26E+05 ND ND ND NA MW-30-69 MW-30-69 Q3-2010 034 69.3 6.4 8/20/2010 15:08 1.11E+05 3.24E+03 2.02E+02 3.53E-01 7.80E-01 9.08E-01

-3.14E+00 5.22E+00 5.12E+00

-2.41E+00 5.25E+00 5.03E+00 NA NA NA 1.26E+05 MW-30-69 MW-30-69 Q3-2010 Mid 035 69.3 6.4 9/8/2010 12:35 1.23E+05 3.65E+03 4.47E+02 1.93E-01 4.41E-01 5.14E-01

-1.10E+00 4.42E+00 4.87E+00 1.40E+00 4.72E+00 5.73E+00 NA NA NA 1.26E+05 MW-30-69 MW-30-69 Q4-2010 036 69.3 6.4 11/5/2010 11:56 1.25E+05 1.88E+03 4.34E+02 9.69E-01 8.79E-01 1.94E+00

-3.68E+00 3.94E+00 7.79E+00

-5.01E+00 5.09E+00 9.47E+00 NA NA NA 1.26E+05 MW-30-69 MW-30-69 Q1-2011 037 69.3 6.4 2/9/2011 12:17 1.01E+05 2.18E+03 2.98E+02 1.62E+00 1.93E+00 2.00E+00 1.87E+00 5.80E+00 6.74E+00

-1.13E-01 5.88E+00 6.44E+00 NA NA NA 1.26E+05 MW-30-69 MW-30-69 Q1-2011 Mid 038 69.3 6.4 3/31/2011 11:38 1.08E+05 3.40E+03 4.72E+02

-6.11E-01 1.63E+00 2.15E+00 2.48E+00 7.96E+00 9.14E+00

-1.41E+00 6.70E+00 6.46E+00 NA NA NA 1.26E+05 MW-30-69 MW-30-84 Q2-2010 022 83.8

-8.1 4/29/2010 13:46 9.56E+03 5.40E+02 1.48E+02 4.08E-01 8.33E-01 9.56E-01

-3.84E-01 5.71E+00 6.36E+00 2.19E+00 5.36E+00 6.57E+00 NA NA NA 9.60E+03 ND ND ND NA MW-30-84 MW-30-84 Q2-2010 Mid 023 83.8

-8.1 6/8/2010 12:19 9.40E+03 4.37E+02 2.14E+02 2.01E-01 4.85E-01 5.52E-01 7.20E-01 5.49E+00 6.21E+00

-4.01E+00 6.36E+00 6.10E+00 NA NA NA 9.60E+03 MW-30-84 MW-30-84 Q3-2010 024 83.8

-8.1 7/28/2010 13:07 9.26E+03 5.09E+02 1.01E+02 4.48E-01 7.63E-01 8.52E-01

-1.46E+00 9.30E+00 1.02E+01

-3.03E-01 9.79E+00 1.08E+01 NA NA NA 9.60E+03 MW-30-84 MW-30-84 Q3-2010 025 83.8

-8.1 8/20/2010 16:51 1.00E+04 5.57E+02 1.29E+02 5.65E-01 8.70E-01 9.53E-01 3.22E+00 6.27E+00 7.54E+00

-3.97E+00 6.69E+00 6.20E+00 NA NA NA 9.60E+03 MW-30-84 MW-30-84 Q3-2010 Mid 026 83.8

-8.1 9/8/2010 13:14 1.01E+04 4.32E+02 2.10E+02 3.18E-01 6.20E-01 7.05E-01

-1.48E+00 6.18E+00 6.74E+00

-4.19E-01 7.65E+00 8.58E+00 NA NA NA 9.60E+03 MW-30-84 MW-30-84 Q4-2010 027 83.8

-8.1 11/5/2010 12:35 1.02E+04 4.80E+02 3.87E+02 5.25E-01 7.56E-01 1.70E+00

-3.07E+00 4.23E+00 8.38E+00

-5.22E+00 4.86E+00 8.20E+00 NA NA NA 9.60E+03 MW-30-84 MW-30-84 Q1-2011 028 83.8

-8.1 2/9/2011 12:57 9.20E+03 8.86E+02 3.79E+02 1.12E+00 1.82E+00 1.98E+00 5.89E-01 4.74E+00 5.22E+00 1.09E+00 5.76E+00 6.49E+00 NA NA NA 9.60E+03 MW-30-84 MW-30-84 Q1-2011 Mid 029 83.8

-8.1 3/31/2011 12:03 9.04E+03 1.06E+03 4.74E+02

-4.78E-01 1.66E+00 2.13E+00 5.00E-01 1.12E+01 1.21E+01

-3.04E+00 9.48E+00 9.12E+00 NA NA NA 9.60E+03 MW-30-84 MW-31-49 Q2-2010 023 48.8 26.8 4/14/2010 10:42 1.16E+04 3.90E+02 1.00E+02 1.18E-01 4.62E-01 5.72E-01

-2.95E+00 8.54E+00 9.00E+00 9.25E-03 8.91E+00 9.95E+00 NA NA NA 2.88E+04 ND ND ND NA MW-31-49 MW-31-49 Q2-2010 Mid 024 48.8 26.8 6/7/2010 11:30 1.73E+04 5.79E+02 2.22E+02 3.41E-01 7.95E-01 9.18E-01

-3.80E+00 7.42E+00 7.51E+00 1.82E+00 6.72E+00 8.03E+00 NA NA NA 2.88E+04 MW-31-49 MW-31-49 Q3-2010 025 48.8 26.8 7/27/2010 14:43 5.46E+04 1.59E+03 1.21E+02 3.05E-01 4.71E-01 5.22E-01 2.74E+00 1.17E+01 1.40E+01 2.23E+00 8.03E+00 9.96E+00 NA NA NA 2.88E+04 MW-31-49 MW-31-49 Q3-2010 026 48.8 26.8 8/23/2010 12:11 4.11E+03 3.56E+02 1.23E+02 1.62E-01 7.89E-01 9.57E-01

-1.21E+00 5.42E+00 5.91E+00

-3.35E-02 5.19E+00 5.80E+00 NA NA NA 2.88E+04 MW-31-49 MW-31-49 Q3-2010 Mid 027 48.8 26.8 9/7/2010 13:49 1.04E+05 3.02E+03 1.68E+02

-1.15E-01 2.82E-01 4.23E-01 3.35E+00 5.52E+00 6.68E+00 2.16E+00 5.97E+00 7.20E+00 NA NA NA 2.88E+04 MW-31-49 MW-31-49 Q4-2010 028 48.8 26.8 11/3/2010 11:55 3.35E+04 9.81E+02 1.15E+02

-3.04E-02 4.26E-01 5.51E-01

-2.82E+00 8.51E+00 8.97E+00 2.22E+00 8.87E+00 1.06E+01 NA NA NA 2.88E+04 MW-31-49 MW-31-49 Q1-2011 029 48.8 26.8 2/9/2011 13:12 1.06E+03 3.40E+02 2.98E+02

-5.51E-01 1.76E+00 2.14E+00 1.39E+00 5.22E+00 6.02E+00 4.84E-01 5.26E+00 5.91E+00 NA NA NA 2.88E+04 MW-31-49 MW-31-49 Q1-2011 Mid 030 48.8 26.8 3/30/2011 12:33 4.31E+03 7.84E+02 4.65E+02 1.77E+00 2.04E+00 2.16E+00

-2.34E+00 7.80E+00 8.17E+00

-5.38E-01 9.18E+00 1.00E+01 NA NA NA 2.88E+04 MW-31-49 MW-31-63 Q2-2010 023 63.3 12.3 4/14/2010 13:05 1.84E+04 5.46E+02 1.08E+02

-1.50E-01 4.43E-01 6.61E-01

-4.58E+00 9.18E+00 9.12E+00 2.75E-01 9.97E+00 1.12E+01 NA NA NA 3.90E+04 ND ND ND NA MW-31-63 MW-31-63 Q2-2010 Mid 024 63.3 12.3 6/7/2010 12:19 5.11E+04 1.53E+03 2.93E+02 3.68E-01 8.04E-01 9.11E-01 2.95E+00 5.94E+00 7.20E+00 9.47E-01 6.12E+00 7.09E+00 NA NA NA 3.90E+04 MW-31-63 MW-31-63 Q3-2010 025 63.3 12.3 7/27/2010 15:54 6.17E+04 1.80E+03 1.27E+02 5.31E-01 6.45E-01 6.89E-01

-1.81E+00 8.27E+00 8.91E+00 1.22E+00 7.33E+00 8.70E+00 NA NA NA 3.90E+04 MW-31-63 MW-31-63 Q3-2010 026 63.3 12.3 8/23/2010 13:11 6.69E+04 1.95E+03 1.60E+02 4.60E-01 7.62E-01 8.48E-01 1.77E+00 6.11E+00 7.13E+00

-1.67E+00 6.17E+00 6.44E+00 NA NA NA 3.90E+04 MW-31-63 MW-31-63 Q3-2010 Mid 027 63.3 12.3 9/7/2010 15:28 4.65E+04 1.41E+03 1.46E+02 3.99E-01 7.26E-01 8.18E-01 4.05E-01 4.75E+00 5.31E+00

-1.47E+00 5.45E+00 5.56E+00 NA NA NA 3.90E+04 MW-31-63 MW-31-63 Q4-2010 028 63.3 12.3 11/3/2010 12:32 2.95E+04 9.02E+02 1.14E+02 3.31E-01 6.30E-01 7.13E-01

-2.24E+00 9.63E+00 1.02E+01 3.44E+00 8.40E+00 1.07E+01 NA NA NA 3.90E+04 MW-31-63 MW-31-63 Q1-2011 029 63.3 12.3 2/9/2011 13:14 2.46E+04 1.10E+03 2.98E+02 4.29E-01 1.78E+00 2.08E+00

-1.42E+00 6.46E+00 6.81E+00

-2.31E+00 6.42E+00 6.26E+00 NA NA NA 3.90E+04 MW-31-63 MW-31-63 Q1-2011 Mid 030 63.3 12.3 3/30/2011 13:13 1.33E+04 1.14E+03 4.53E+02 1.49E+00 1.87E+00 2.02E+00 8.76E-01 9.00E+00 9.97E+00

-1.92E-01 7.26E+00 7.92E+00 NA NA NA 3.90E+04 MW-31-63 MW-31-85 Q2-2010 023 84.8

-9.2 4/14/2010 12:09 4.85E+03 2.60E+02 9.99E+01

-1.42E-01 4.23E-01 6.36E-01 3.84E+00 6.90E+00 8.60E+00 1.40E-01 6.13E+00 6.84E+00 NA NA NA 5.48E+03 ND ND ND NA MW-31-85 MW-31-85 Q2-2010 Mid 024 84.8

-9.2 6/7/2010 12:00 9.34E+03 4.35E+02 2.13E+02 3.29E-01 5.73E-01 6.43E-01 2.30E+00 4.86E+00 5.78E+00

-1.07E+00 4.70E+00 4.81E+00 NA NA NA 5.48E+03 MW-31-85 MW-31-85 Q3-2010 025 84.8

-9.2 7/27/2010 15:22 6.70E+03 4.34E+02 1.00E+02 3.55E-01 4.72E-01 5.04E-01

-3.98E+00 8.82E+00 9.22E+00 2.50E+00 8.43E+00 9.93E+00 NA NA NA 5.48E+03 MW-31-85 MW-31-85 Q3-2010 026 84.8

-9.2 8/23/2010 12:10 5.07E+03 3.96E+02 1.25E+02 6.61E-03 7.89E-01 9.16E-01 3.42E+00 4.95E+00 6.08E+00 1.52E+00 4.77E+00 5.71E+00 NA NA NA 5.48E+03 MW-31-85 MW-31-85 Q3-2010 Mid 027 84.8

-9.2 9/7/2010 14:14 6.21E+03 5.24E+02 1.44E+02

-3.25E-01 4.45E-01 6.85E-01

-1.54E+00 5.68E+00 6.11E+00 2.71E+00 6.42E+00 7.79E+00 NA NA NA 5.48E+03 MW-31-85 MW-31-85 Q4-2010 028 84.8

-9.2 11/3/2010 12:00 6.06E+03 4.16E+02 1.14E+02 2.41E-01 4.83E-01 5.47E-01

-1.36E+00 8.88E+00 9.62E+00

-2.66E-01 1.08E+01 1.19E+01 NA NA NA 5.48E+03 MW-31-85 MW-31-85 Q1-2011 029 84.8

-9.2 2/9/2011 13:03 4.83E+03 6.84E+02 3.82E+02 3.26E-01 1.79E+00 2.18E+00 3.19E+00 5.96E+00 7.08E+00 3.14E+00 6.06E+00 7.39E+00 NA NA NA 5.48E+03 MW-31-85 MW-31-85 Q1-2011 Mid 030 84.8

-9.2 3/30/2011 12:55 7.75E+02 4.66E+02 4.52E+02 9.37E-01 1.81E+00 2.00E+00 5.90E+00 1.31E+01 8.10E+00 6.43E+00 8.88E+00 1.17E+01 NA NA NA 5.48E+03 MW-31-85 MW-32-48 Q2-2010 006 4/28/2010 11:28 6.18E+04 1.80E+03 1.79E+02 7.51E-01 8.02E-01 8.21E-01 3.11E+00 7.80E+00 7.62E+00 1.38E+00 6.18E+00 7.26E+00 NA NA NA 2.38E+04 ND ND ND NA MW-32-48 MW-32-48 Q3-2010 007 7/27/2010 12:52 3.69E+03 3.26E+02 9.94E+01 3.59E-01 8.37E-01 9.60E-01 1.54E-01 7.00E+00 8.04E+00

-3.86E+00 7.74E+00 7.51E+00 NA NA NA 2.38E+04 MW-32-48 MW-32-48 Q3-2010 008 8/24/2010 14:03 5.90E+03 3.51E+02 2.10E+02 3.55E-01 6.33E-01 7.09E-01

-4.34E-01 4.49E+00 5.04E+00 1.96E+00 4.95E+00 5.95E+00 NA NA NA 2.38E+04 MW-32-48 MW-32-59 Q2-2010 017 58.8 18.3 4/28/2010 11:30 6.83E+04 2.00E+03 1.88E+02

-3.10E-01 3.61E-01 6.30E-01 4.95E+00 4.86E+00 6.21E+00 1.55E+00 4.86E+00 5.81E+00 NA NA NA 5.28E+04 ND ND ND NA MW-32-59 MW-32-59 Q2-2010 Mid 018 58.8 18.3 6/9/2010 14:53 1.55E+05 4.58E+03 4.89E+02 4.10E-01 7.75E-01 8.75E-01

-9.71E-01 6.12E+00 6.76E+00 1.48E+00 6.66E+00 7.93E+00 NA NA NA 5.28E+04 MW-32-59 MW-32-59 Q3-2010 019 58.8 18.3 7/27/2010 13:00 6.54E+04 1.91E+03 1.33E+02 1.50E-01 4.37E-01 5.21E-01 1.07E+00 1.02E+01 1.14E+01 3.80E+00 9.26E+00 1.21E+01 NA NA NA 5.28E+04 MW-32-59 MW-32-59 Q3-2010 020 58.8 18.3 8/24/2010 14:22 5.78E+03 3.48E+02 2.10E+02

-9.82E-02 6.14E-01 8.32E-01 3.21E+00 5.84E+00 7.14E+00

-2.01E+00 6.60E+00 6.75E+00 NA NA NA 5.28E+04 MW-32-59 MW-32-59 Q3-2010 Mid 021 58.8 18.3 9/9/2010 13:57 7.44E+04 2.18E+03 1.67E+02 4.21E-01 7.20E-01 8.03E-01 1.68E+00 5.43E+00 6.39E+00

-1.58E+00 5.38E+00 5.54E+00 NA NA NA 5.28E+04 MW-32-59 MW-32-59 Q4-2010 022 58.8 18.3 11/3/2010 12:08 1.58E+04 6.66E+02 1.16E+02 2.02E-01 6.15E-01 7.14E-01 6.67E+00 7.98E+00 1.03E+01 1.19E+00 9.11E+00 1.06E+01 NA NA NA 5.28E+04 MW-32-59 MW-32-59 Q1-2011 023 58.8 18.3 3/1/2011 11:28 4.39E+03 6.42E+02 3.59E+02 1.25E+00 1.49E+00 1.55E+00 6.56E-01 5.82E+00 6.63E+00

-4.41E-01 7.00E+00 7.58E+00 NA NA NA 5.28E+04 MW-32-59 MW-32-59 Q1-2011 Mid 024 58.8 18.3 3/31/2011 12:46 3.37E+04 1.96E+03 5.07E+02

-2.13E-01 1.15E+00 1.51E+00 8.24E-01 8.92E+00 9.96E+00 1.99E-02 1.02E+01 1.11E+01 NA NA NA 5.28E+04 MW-32-59 MW-32-85 Q2-2010 020 85.3 85.3 4/28/2010 13:08 1.15E+04 5.85E+02 1.45E+02 3.95E-02 6.03E-01 7.62E-01 7.18E-01 9.07E+00 9.43E+00 1.03E+00 6.79E+00 8.05E+00 NA NA NA 1.32E+04 ND ND ND NA MW-32-85 MW-32-85 Q2-2010 Mid 021 85.3 85.3 6/9/2010 12:03 1.20E+04 4.85E+02 2.14E+02 3.30E-01 7.56E-01 8.66E-01

-1.92E+00 5.57E+00 6.05E+00

-7.73E-01 5.68E+00 6.30E+00 NA NA NA 1.32E+04 MW-32-85 MW-32-85 Q3-2010 022 85.3 85.3 7/27/2010 14:51 1.21E+04 5.81E+02 1.01E+02 3.80E-01 6.37E-01 7.07E-01 1.38E+00 7.47E+00 8.69E+00 2.30E+00 7.74E+00 9.52E+00 NA NA NA 1.32E+04 MW-32-85 MW-32-85 Q3-2010 023 85.3 85.3 8/24/2010 11:03 1.38E+04 4.94E+02 2.10E+02

-3.76E-01 4.75E-01 7.02E-01

-6.66E-01 5.96E+00 6.62E+00

-1.19E+00 5.22E+00 5.48E+00 NA NA NA 1.32E+04 MW-32-85 MW-32-85 Q3-2010 Mid 024 85.3 85.3 9/9/2010 15:29 1.44E+04 6.57E+02 1.27E+02 1.34E-01 6.77E-01 8.36E-01 1.43E+00 6.27E+00 6.90E+00

-1.25E-01 5.49E+00 6.10E+00 NA NA NA 1.32E+04 MW-32-85 MW-32-85 Q4-2010 025 85.3 85.3 11/3/2010 12:45 1.49E+04 6.48E+02 1.16E+02 3.80E-01 4.90E-01 5.36E-01 5.89E+00 9.60E+00 1.18E+01

-5.55E+00 8.71E+00 7.61E+00 NA NA NA 1.32E+04 MW-32-85 MW-32-85 Q1-2011 026 85.3 85.3 3/1/2011 12:05 1.34E+04 1.41E+03 2.62E+02 3.81E-01 1.41E+00 1.63E+00 7.79E-01 8.26E+00 9.36E+00 4.73E+00 9.72E+00 1.24E+01 NA NA NA 1.32E+04 MW-32-85 MW-32-85 Q1-2011 Mid 027 85.3 85.3 3/31/2011 13:18 1.32E+04 1.27E+03 5.07E+02

-1.62E-01 1.20E+00 1.56E+00

-6.56E-01 7.26E+00 7.61E+00 3.80E+00 8.28E+00 1.02E+01 NA NA NA 1.32E+04 MW-32-85 MW-32-149 Q2-2010 017 149.3

-72.2 4/28/2010 13:50 6.60E+03 4.52E+02 1.47E+02 3.03E-01 7.08E-01 8.24E-01 1.98E+00 6.88E+00 7.55E+00 9.80E-01 4.44E+00 5.36E+00 NA NA NA 3.55E+03 ND ND ND NA MW-32-149 MW-32-149 Q2-2010 Mid 018 149.3

-72.2 6/9/2010 12:52 9.76E+03 4.44E+02 2.14E+02

-1.16E-01 6.45E-01 8.05E-01

-8.57E-01 8.36E+00 9.08E+00

-4.49E+00 6.20E+00 5.62E+00 NA NA NA 3.55E+03 MW-32-149 MW-32-149 Q3-2010 019 149.3

-72.2 7/27/2010 15:34 3.81E+03 3.33E+02 1.01E+02 1.14E-01 3.57E-01 4.33E-01 7.24E-01 1.28E+01 1.64E+01 1.53E+00 8.88E+00 1.06E+01 NA NA NA 3.55E+03 MW-32-149 MW-32-149 Q3-2010 020 149.3

-72.2 8/24/2010 11:27 2.60E+03 2.70E+02 2.10E+02 1.04E-01 6.64E-01 8.13E-01 1.04E-01 6.51E+00 7.44E+00 2.67E-02 5.89E+00 6.71E+00 NA NA NA 3.55E+03 MW-32-149 MW-32-149 Q3-2010 Mid 021 149.3

-72.2 9/9/2010 11:36 2.12E+03 2.70E+02 1.27E+02 2.27E-01 7.72E-01 9.22E-01 3.68E+00 7.83E+00 9.16E+00 1.24E+00 8.52E+00 1.00E+01 NA NA NA 3.55E+03 MW-32-149 MW-32-149 Q4-2010 022 149.3

-72.2 11/3/2010 16:09 1.55E+03 2.24E+02 1.12E+02 4.08E-01 5.02E-01 5.49E-01

-1.00E+01 1.08E+01 1.15E+01 3.36E+00 7.71E+00 9.94E+00 NA NA NA 3.55E+03 MW-32-149 MW-32-149 Q1-2011 023 149.3

-72.2 3/1/2011 13:37 1.06E+03 4.48E+02 2.68E+02

-7.01E-01 1.66E+00 2.15E+00 9.25E-01 5.42E+00 6.30E+00 2.06E+00 6.60E+00 7.93E+00 NA NA NA 3.55E+03 MW-32-149 MW-32-149 Q1-2011 Mid 024 149.3

-72.2 3/31/2011 11:33 8.99E+02 5.34E+02 5.09E+02

-2.01E-01 1.10E+00 1.49E+00 2.52E+00 9.30E+00 1.09E+01 2.31E+00 9.92E+00 1.18E+01 NA NA NA 3.55E+03 MW-32-149 MW-32-173 Q2-2010 015 172.8

-95.7 4/28/2010 15:45 1.54E+03 2.45E+02 1.48E+02 4.63E-01 5.34E-01 5.49E-01 4.96E+00 5.45E+00 6.79E+00

-8.08E-01 4.93E+00 5.21E+00 NA NA NA 1.71E+03 ND ND ND NA MW-32-173 MW-32-173 Q2-2010 Mid 016 172.8

-95.7 6/9/2010 12:23 2.34E+03 2.66E+02 2.08E+02 3.04E-01 5.97E-01 6.81E-01

-9.18E-01 6.63E+00 7.29E+00 8.09E-01 6.48E+00 7.43E+00 NA NA NA 1.71E+03 MW-32-173 MW-32-173 Q3-2010 017 172.8

-95.7 7/27/2010 15:17 2.47E+03 2.69E+02 9.88E+01 9.64E-02 3.38E-01 4.14E-01

-1.51E+00 8.71E+00 9.65E+00

-2.29E+00 7.04E+00 7.12E+00 NA NA NA 1.71E+03 MW-32-173 MW-32-173 Q3-2010 018 172.8

-95.7 8/24/2010 11:23 2.19E+03 2.60E+02 2.10E+02

-1.37E-01 3.98E-01 5.77E-01 2.92E+00 6.57E+00 7.82E+00 4.56E-01 6.55E+00 7.41E+00 NA NA NA 1.71E+03 MW-32-173 MW-32-173 Q3-2010 Mid 019 172.8

-95.7 9/9/2010 11:29 1.98E+03 2.63E+02 1.28E+02 5.82E-01 8.34E-01 8.96E-01 1.67E+00 4.86E+00 5.81E+00 9.94E-01 4.84E+00 5.77E+00 NA NA NA 1.71E+03 MW-32-173 MW-32-173 Q4-2010 020 172.8

-95.7 11/3/2010 15:53 1.40E+03 2.16E+02 1.14E+02 1.65E-02 4.38E-01 5.24E-01 3.87E+00 1.76E+01 9.62E+00

-2.94E+00 9.88E+00 1.01E+01 NA NA NA 1.71E+03 MW-32-173 MW-32-173 Q1-2011 021 172.8

-95.7 3/1/2011 13:13 9.02E+02 4.12E+02 2.61E+02

-4.04E-01 1.12E+00 1.45E+00 5.99E+00 6.06E+00 7.73E+00

-2.04E+00 7.36E+00 7.55E+00 NA NA NA 1.71E+03 MW-32-173 MW-32-173 Q1-2011 Mid 022 172.8

-95.7 3/31/2011 11:35 8.41E+02 5.22E+02 5.04E+02 2.46E-01 1.27E+00 1.54E+00 6.51E+00 1.58E+01 8.26E+00 2.19E+00 8.22E+00 9.98E+00 NA NA NA 1.71E+03 MW-32-173 MW-32-190 Q2-2010 019 190.3

-113.7 4/28/2010 15:51 1.59E+03 2.48E+02 1.49E+02

-2.92E-01 7.01E-01 9.85E-01 1.82E+00 5.66E+00 6.65E+00

-2.37E+00 5.38E+00 5.33E+00 NA NA NA 1.61E+03 ND ND ND NA MW-32-190 MW-32-190 Q2-2010 Mid 020 190.3

-113.7 6/9/2010 12:43 1.76E+03 2.45E+02 2.05E+02 4.69E-01 8.43E-01 9.49E-01

-3.64E+00 5.89E+00 6.02E+00 1.50E+00 5.84E+00 6.92E+00 NA NA NA 1.61E+03 MW-32-190 MW-32-190 Q3-2010 021 190.3

-113.7 7/27/2010 15:41 1.58E+03 2.21E+02 9.83E+01

-8.57E-02 3.52E-01 5.06E-01 6.23E-01 7.98E+00 9.16E+00

-2.62E+00 7.77E+00 7.60E+00 NA NA NA 1.61E+03 MW-32-190 MW-32-190 Q3-2010 022 190.3

-113.7 8/24/2010 11:37 1.69E+03 2.43E+02 2.09E+02 2.54E-01 7.84E-01 9.25E-01

-5.47E-01 4.84E+00 5.45E+00 9.00E-01 4.96E+00 5.87E+00 NA NA NA 1.61E+03 MW-32-190 MW-32-190 Q3-2010 Mid 023 190.3

-113.7 9/9/2010 11:34 1.65E+03 2.48E+02 1.30E+02

-1.31E-01 5.85E-01 8.27E-01

-2.39E-01 9.87E+00 1.08E+01 2.00E+00 6.66E+00 7.98E+00 NA NA NA 1.61E+03 MW-32-190 MW-32-190 Q4-2010 024 190.3

-113.7 11/3/2010 16:07 1.53E+03 2.28E+02 1.17E+02

-9.74E-02 4.35E-01 5.82E-01 2.12E+00 9.02E+00 1.07E+01

-2.40E+00 9.21E+00 9.36E+00 NA NA NA 1.61E+03 MW-32-190 MW-32-190 Q1-2011 025 190.3

-113.7 3/1/2011 13:24 1.64E+03 5.32E+02 2.64E+02 7.65E-01 1.20E+00 1.29E+00 2.74E+00 5.52E+00 6.57E+00 4.88E+00 7.64E+00 8.75E+00 NA NA NA 1.61E+03 MW-32-190 MW-32-190 Q1-2011 Mid 026 190.3

-113.7 3/31/2011 11:47 1.41E+03 5.76E+02 5.02E+02

-7.79E-01 1.15E+00 1.67E+00 8.78E-01 7.96E+00 9.01E+00 5.11E+00 1.04E+01 1.30E+01 NA NA NA 1.61E+03 MW-32-190 MW-33 Q2-2010 026 19.2

-0.4 4/15/2010 13:54 6.31E+04 1.06E+03 1.76E+02

-1.77E-01 6.60E-01 8.85E-01

-3.35E+00 7.39E+00 7.21E+00

-5.17E+00 7.74E+00 6.17E+00 NA NA NA 2.36E+04 ND ND ND NA MW-33 MW-33 Q3-2010 027 19.2

-0.4 8/30/2010 14:29 3.69E+03 3.42E+02 1.26E+02 1.64E-01 3.24E-01 3.69E-01 7.72E-01 5.64E+00 6.38E+00

-3.08E-01 5.07E+00 5.60E+00 NA NA NA 2.36E+04 MW-33 MW-33 Q3-2010 Mid 028 19.2

-0.4 9/11/2010 13:28 3.86E+03 3.53E+02 1.27E+02 9.96E-03 7.38E-01 9.28E-01

-1.30E+00 4.86E+00 5.14E+00 1.12E+00 5.10E+00 5.95E+00 NA NA NA 2.36E+04 MW-33 MW-35 Q2-2010 Mid 020 19

-0.4 5/20/2010 13:25 2.82E+03 2.87E+02 2.14E+02

-1.97E-01 4.52E-01 6.73E-01 1.51E+00 5.67E+00 6.71E+00

-1.24E+00 6.33E+00 6.84E+00 NA NA NA 2.82E+03 ND ND ND NA MW-35 MW-36-24 Q2-2010 018 16.1

-4.3 4/28/2010 14:14 3.53E+03 3.39E+02 1.45E+02 1.91E-01 5.60E-01 6.67E-01 1.74E+00 5.87E+00 6.86E+00 2.13E+00 5.66E+00 6.86E+00 NA NA NA 2.14E+03 ND ND ND NA MW-36-24 MW-36-24 Q3-2010 019 16.1

-4.3 7/29/2010 12:04 2.64E+02 1.17E+02 1.00E+02 2.45E-01 3.84E-01 4.23E-01 8.89E-01 9.88E+00 1.10E+01

-2.61E+00 1.19E+01 1.26E+01 NA NA NA 2.14E+03 MW-36-24 MW-36-24 Q4-2010 020 16.1

-4.3 11/4/2010 16:15 2.62E+03 2.82E+02 1.13E+02 3.79E-01 5.81E-01 6.42E-01 3.42E+00 9.88E+00 1.17E+01

-1.80E+00 1.16E+01 1.26E+01 NA NA NA 2.14E+03 MW-36-24 MW-36-24 Q1-2011 021 16.1

-4.3 2/28/2011 12:37 2.56E+02 3.54E+02 3.81E+02

-8.87E-02 1.67E+00 2.08E+00 4.53E-01 5.26E+00 5.75E+00

-3.09E-01 4.74E+00 5.03E+00 NA NA NA 2.14E+03 MW-36-24 MW-36-41 Q2-2010 012 37

-25.2 4/28/2010 15:38 1.56E+04 6.89E+02 1.50E+02 5.95E+00 1.30E+00 5.74E-01 1.38E+00 6.43E+00 6.92E+00 8.55E-01 5.70E+00 6.68E+00 NA NA NA 1.24E+04 3.87E+00 ND ND NA MW-36-41 MW-36-41 Q3-2010 013 37

-25.2 7/29/2010 12:23 1.30E+04 7.52E+02 1.46E+02 1.88E+00 7.41E-01 5.17E-01

-1.84E+00 6.35E+00 6.48E+00 4.07E+00 6.12E+00 7.75E+00 NA NA NA 1.24E+04 3.87E+00 MW-36-41 MW-36-41 Q4-2010 014 37

-25.2 11/4/2010 16:55 1.22E+04 5.75E+02 1.10E+02 3.54E+00 9.13E-01 6.12E-01 7.62E-01 8.76E+00 1.01E+01 3.09E+00 8.58E+00 1.06E+01 NA NA NA 1.24E+04 3.87E+00 MW-36-41 MW-36-41 Q1-2011 015 37

-25.2 2/28/2011 13:53 8.74E+03 6.88E+02 2.97E+02 4.11E+00 1.87E+00 1.57E+00 1.31E+00 5.26E+00 6.09E+00 1.58E+00 5.68E+00 6.65E+00 NA NA NA 1.24E+04 3.87E+00 MW-36-41 MW-36-52 Q2-2010 017 49.7

-37.9 4/28/2010 15:46 8.49E+03 5.09E+02 1.47E+02 5.36E+00 1.35E+00 6.85E-01 2.29E+00 5.31E+00 6.27E+00 2.98E+00 4.80E+00 6.12E+00 NA NA NA 6.45E+03 5.05E+00 ND ND NA MW-36-52 MW-36-52 Q3-2010 018 49.7

-37.9 7/29/2010 12:24 7.07E+03 4.46E+02 1.00E+02

-1.52E-01 6.33E-01 8.23E-01

-1.63E+00 7.79E+00 8.33E+00

-1.74E+00 9.63E+00 1.03E+01 NA NA NA 6.45E+03 5.05E+00 MW-36-52 MW-36-52 Q4-2010 019 49.7

-37.9 11/4/2010 15:55 7.08E+03 4.40E+02 1.10E+02 4.73E+00 1.11E+00 6.76E-01 1.15E-01 5.89E+00 6.52E+00

-2.28E+00 7.92E+00 7.79E+00 NA NA NA 6.45E+03 5.05E+00 MW-36-52 MW-36-52 Q1-2011 020 49.7

-37.9 2/28/2011 12:43 3.14E+03 4.92E+02 3.37E+02 1.33E+00 2.00E+00 2.14E+00

-6.00E+00 5.58E+00 4.80E+00

-2.66E+00 5.94E+00 5.65E+00 NA NA NA 6.45E+03 5.05E+00 MW-36-52 MW-37-22 Q2-2010 018 17

-2 4/27/2010 13:23 9.06E+03 4.26E+02 2.09E+02 1.29E+01 1.68E+00 6.44E-01

-1.08E+00 5.73E+00 5.64E+00 1.34E+00 4.41E+00 5.29E+00 NA NA NA 5.99E+03 1.06E+01 ND ND NA MW-37-22 MW-37-22 Q3-2010 019 17

-2 8/5/2010 14:06 3.70E+03 3.26E+02 9.90E+01 5.19E+00 1.39E+00 9.19E-01

-1.60E+00 7.62E+00 8.20E+00 4.53E+00 7.13E+00 9.76E+00 NA NA NA 5.99E+03 1.06E+01 MW-37-22 MW-37-22 Q4-2010 020 17

-2 11/4/2010 14:28 4.46E+03 3.57E+02 1.12E+02 1.38E+01 1.33E+00 5.33E-01

-2.26E+00 7.33E+00 7.68E+00

-1.24E+00 9.31E+00 1.00E+01 NA NA NA 5.99E+03 1.06E+01 MW-37-22 MW-37-22 Q1-2011 021 17

-2 1/27/2011 15:19 6.74E+03 6.18E+02 2.98E+02 1.04E+01 2.52E+00 1.68E+00

-2.18E+00 4.74E+00 4.94E+00 2.59E+00 5.38E+00 6.55E+00 NA NA NA 5.99E+03 1.06E+01 MW-37-22 ANALYSIS RESULTS5 YEARLY ROLLING AVERAGES4,6 Well ID1 TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

SAMPLE COLLECTION Well ID1 SAMPLING QUARTER2,8 SAMPLE ID SAMPLE ZONE CENTER, Depth Ft Below Top of Casing3 SAMPLE ZONE CENTER Elevation Ft msl3

TABLE 3 FIRST QUARTER 2011 GROUNDWATER ANALYTICAL RESULTS AND AVERAGES INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q12011 FINAL Table 3 - First Quarter 2011 Groundwater Analytical Results and Averages.xlsx; Q12011 Table 3 Page 2 of 5 See Page 5 for Notes TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Date Time Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Average Average Average Average Average ANALYSIS RESULTS5 YEARLY ROLLING AVERAGES4,6 Well ID1 TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

SAMPLE COLLECTION Well ID1 SAMPLING QUARTER2,8 SAMPLE ID SAMPLE ZONE CENTER, Depth Ft Below Top of Casing3 SAMPLE ZONE CENTER Elevation Ft msl3 MW-37-32 Q2-2010 018 29

-14 4/27/2010 17:25 7.24E+03 3.90E+02 2.10E+02 1.87E+01 2.28E+00 6.59E-01 6.85E-01 5.87E+00 6.72E+00

-2.27E+00 4.88E+00 4.69E+00 NA NA NA 5.65E+03 1.59E+01 ND ND NA MW-37-32 MW-37-32 Q3-2010 019 29

-14 8/5/2010 14:00 4.80E+03 3.69E+02 9.97E+01 1.41E+01 1.85E+00 5.42E-01

-5.90E+00 8.89E+00 8.07E+00

-3.93E-01 8.67E+00 9.54E+00 NA NA NA 5.65E+03 1.59E+01 MW-37-32 MW-37-32 Q4-2010 020 29

-14 11/4/2010 13:14 5.99E+03 4.22E+02 1.17E+02

-2.91E-01 6.15E-01 7.91E-01

-4.11E+00 7.41E+00 7.07E+00 1.54E+00 7.68E+00 9.04E+00 NA NA NA 5.65E+03 1.59E+01 MW-37-32 MW-37-32 Q1-2011 021 29

-14 1/27/2011 15:09 4.57E+03 5.28E+02 2.98E+02 1.49E+01 3.02E+00 1.74E+00 4.20E-01 6.12E+00 6.85E+00 1.72E+00 6.60E+00 7.76E+00 NA NA NA 5.65E+03 1.59E+01 MW-37-32 MW-37-40 Q2-2010 018 39.2

-24.2 4/27/2010 12:43 5.37E+03 3.45E+02 2.07E+02 1.71E+01 1.81E+00 6.52E-01

-2.56E+00 4.54E+00 4.41E+00

-7.35E-02 5.03E+00 5.51E+00 NA NA NA 6.19E+03 1.59E+01 ND ND NA MW-37-40 MW-37-40 Q3-2010 019 39.2

-24.2 8/5/2010 14:25 7.00E+03 4.43E+02 9.99E+01 1.43E+01 1.74E+00 4.81E-01 3.15E-01 7.86E+00 9.00E+00 3.82E+00 7.44E+00 9.31E+00 NA NA NA 6.19E+03 1.59E+01 MW-37-40 MW-37-40 Q4-2010 020 39.2

-24.2 11/4/2010 12:06 6.41E+03 4.29E+02 1.15E+02 1.28E+01 1.92E+00 6.32E-01 2.77E+00 8.58E+00 1.03E+01

-2.01E+00 8.29E+00 8.39E+00 NA NA NA 6.19E+03 1.59E+01 MW-37-40 MW-37-40 Q1-2011 021 39.2

-24.2 1/27/2011 13:35 5.97E+03 7.42E+02 3.82E+02 1.93E+01 3.34E+00 1.85E+00 1.95E+00 5.84E+00 6.78E+00 2.03E+00 6.84E+00 7.92E+00 NA NA NA 6.19E+03 1.59E+01 MW-37-40 MW-37-57 Q2-2010 018 53.2

-38.2 4/27/2010 17:28 5.20E+03 3.50E+02 2.16E+02 1.90E+01 2.15E+00 6.60E-01

-5.08E+00 7.63E+00 7.24E+00 1.71E+00 6.43E+00 7.85E+00 NA NA NA 6.21E+03 1.91E+01 ND ND NA MW-37-57 MW-37-57 Q3-2010 019 53.2

-38.2 8/5/2010 13:59 7.30E+03 4.52E+02 9.94E+01 1.73E+01 1.69E+00 5.57E-01

-2.16E+00 7.37E+00 7.75E+00

-6.93E-01 8.96E+00 9.77E+00 NA NA NA 6.21E+03 1.91E+01 MW-37-57 MW-37-57 Q4-2010 020 53.2

-38.2 11/4/2010 13:49 6.72E+03 4.41E+02 1.15E+02 1.97E+01 2.15E+00 5.70E-01 6.72E+00 1.52E+01 9.04E+00

-3.60E+00 7.95E+00 7.35E+00 NA NA NA 6.21E+03 1.91E+01 MW-37-57 MW-37-57 Q1-2011 021 53.2

-38.2 1/27/2011 15:26 5.63E+03 5.76E+02 2.99E+02 2.02E+01 3.60E+00 1.96E+00

-3.70E-01 6.34E+00 6.92E+00

-1.36E+00 5.64E+00 5.68E+00 NA NA NA 6.21E+03 1.91E+01 MW-37-57 MW-39-67 Q2-2010 008 67 13 5/4/2010 15:23 3.79E+02 2.01E+02 2.13E+02 1.26E+00 6.60E-01 6.33E-01 4.66E-01 5.42E+00 6.14E+00 1.30E+00 6.75E+00 7.87E+00 NA NA NA 3.33E+02 1.65E+00 ND ND NA MW-39-67 MW-39-67 Q3-2010 009 67 13 7/22/2010 14:26 2.86E+02 1.19E+02 9.90E+01 1.73E+00 6.00E-01 3.90E-01 2.94E+00 6.33E+00 7.80E+00

-5.65E+00 7.25E+00 5.04E+00 NA NA NA 3.33E+02 1.65E+00 MW-39-67 MW-39-67 Q4-2010 010 67 13 11/15/2010 16:28 3.74E+02 1.86E+02 3.88E+02 1.96E+00 9.36E-01 1.94E+00

-1.74E+00 3.99E+00 8.40E+00

-3.17E+00 4.38E+00 8.38E+00 NA NA NA 3.33E+02 1.65E+00 MW-39-67 MW-39-84 Q2-2010 008 83.5

-3.5 5/4/2010 15:32 2.25E+02 1.95E+02 2.12E+02 1.26E+00 6.00E-01 5.62E-01 1.07E+00 5.85E+00 6.81E+00

-2.75E+00 5.78E+00 5.93E+00 NA NA NA 2.98E+02 1.05E+00 ND ND NA MW-39-84 MW-39-84 Q3-2010 009 83.5

-3.5 7/22/2010 14:42 3.70E+02 1.30E+02 1.01E+02 8.43E-01 6.21E-01 5.85E-01

-3.32E+00 6.79E+00 6.90E+00 2.43E+00 6.95E+00 8.54E+00 NA NA NA 2.98E+02 1.05E+00 MW-39-84 MW-39-84 Q4-2010 010 83.5

-3.5 11/15/2010 16:38 2.51E+02 2.10E+02 4.59E+02 1.80E+00 8.83E-01 1.86E+00 3.58E+00 4.41E+00 1.05E+01 7.47E+00 4.82E+00 1.24E+01 NA NA NA 2.98E+02 1.05E+00 MW-39-84 MW-39-102 Q2-2010 008 101.5

-21.5 5/4/2010 15:27 3.93E+02 2.01E+02 2.13E+02 4.15E-01 6.36E-01 6.97E-01

-2.40E+00 5.49E+00 5.72E+00

-5.18E-01 6.30E+00 6.91E+00 NA NA NA 3.16E+02 4.05E+00 ND ND NA MW-39-102 MW-39-102 Q3-2010 009 101.5

-21.5 7/22/2010 14:52 2.39E+02 1.49E+02 1.49E+02 4.05E+00 9.93E-01 4.71E-01

-1.08E+00 6.35E+00 6.98E+00

-3.68E+00 5.55E+00 4.42E+00 NA NA NA 3.16E+02 4.05E+00 MW-39-102 MW-39-102 Q4-2010 010 101.5

-21.5 11/15/2010 16:12 3.61E+02 1.83E+02 3.84E+02 1.40E+00 9.00E-01 1.93E+00 2.98E+00 3.38E+00 8.21E+00

-4.12E+00 3.52E+00 6.23E+00 NA NA NA 3.16E+02 4.05E+00 MW-39-102 MW-39-124 Q2-2010 008 124

-44 5/4/2010 12:32 3.08E+02 1.92E+02 2.06E+02 5.90E-01 8.18E-01 8.96E-01

-2.76E-02 5.43E+00 5.45E+00 1.35E-02 5.05E+00 5.58E+00 NA NA NA 3.08E+02 2.25E+00 ND ND NA MW-39-124 MW-39-124 Q3-2010 009 124

-44 7/22/2010 11:39 1.12E+02 1.34E+02 1.46E+02 2.25E+00 7.71E-01 5.01E-01

-1.11E+00 8.32E+00 9.28E+00

-4.37E-01 9.75E+00 1.10E+01 NA NA NA 3.08E+02 2.25E+00 MW-39-124 MW-39-124 Q4-2010 010 124

-44 11/15/2010 12:46 3.73E+02 1.83E+02 3.86E+02 1.17E+00 8.85E-01 1.93E+00

-6.40E+00 6.71E+00 1.61E+01

-1.31E-01 4.98E+00 1.10E+01 NA NA NA 3.08E+02 2.25E+00 MW-39-124 MW-39-183 Q2-2010 008 182.5

-102.5 5/4/2010 12:51 1.34E+02 1.89E+02 2.10E+02 8.20E-02 5.44E-01 6.90E-01 2.11E+00 6.52E+00 7.73E+00

-2.38E+00 7.59E+00 6.99E+00 NA NA NA ND ND ND ND NA MW-39-183 MW-39-183 Q3-2010 009 182.5

-102.5 7/22/2010 11:38 1.07E+02 1.12E+02 1.19E+02 2.08E-01 4.19E-01 4.79E-01

-4.62E+00 8.88E+00 9.01E+00

-5.09E+00 9.62E+00 8.98E+00 NA NA NA MW-39-183 MW-39-183 Q4-2010 010 182.5

-102.5 11/15/2010 12:53

-8.02E+01 1.61E+02 3.88E+02 4.19E-01 7.56E-01 1.77E+00 1.45E+00 4.83E+00 1.10E+01 3.58E+00 4.93E+00 1.19E+01 NA NA NA MW-39-183 MW-39-195 Q2-2010 008 195

-115 5/4/2010 13:14 6.99E+01 1.64E+02 1.84E+02 6.21E-01 6.54E-01 6.82E-01

-1.56E+00 6.42E+00 6.86E+00

-1.59E-01 6.84E+00 7.63E+00 NA NA NA ND ND ND ND NA MW-39-195 MW-39-195 Q3-2010 009 195

-115 7/22/2010 12:10 9.26E+01 1.11E+02 1.20E+02 5.61E-01 5.70E-01 5.97E-01 7.86E-01 8.64E+00 9.43E+00

-9.78E-01 8.93E+00 9.62E+00 NA NA NA MW-39-195 MW-39-195 Q4-2010 010 195

-115 11/15/2010 13:25 2.16E+02 1.86E+02 4.09E+02 1.52E-01 7.35E-01 1.73E+00

-3.21E+00 4.09E+00 6.54E+00 8.70E+00 4.38E+00 1.20E+01 NA NA NA MW-39-195 MW-40-27 Q2-2010 011 26.7 46.5 4/15/2010 16:00 1.48E+02 1.74E+02 1.93E+02 1.05E-01 6.29E-01 7.95E-01

-1.30E+00 4.02E+00 4.36E+00

-2.98E+00 5.64E+00 4.86E+00 NA NA NA 2.00E+02 ND ND ND NA MW-40-27 MW-40-27 Q3-2010 012 26.7 46.5 8/26/2010 14:42 1.93E+02 1.26E+02 1.24E+02 2.23E-01 6.54E-01 7.73E-01 1.95E+00 4.50E+00 5.46E+00

-1.03E+00 4.72E+00 5.12E+00 NA NA NA 2.00E+02 MW-40-27 MW-40-27 Q4-2010 013 26.7 46.5 11/29/2010 15:23 2.06E+02 1.49E+02 1.44E+02 1.10E-01 7.98E-01 9.63E-01 3.16E-01 3.38E+00 3.76E+00 1.01E+00 3.63E+00 4.18E+00 NA NA NA 2.00E+02 MW-40-27 MW-40-27 Q1-2011 014 26.7 46.5 3/8/2011 12:55 1.85E+02 2.56E+02 2.65E+02 1.58E-01 1.37E+00 1.61E+00 3.72E-01 6.78E+00 7.39E+00 2.83E+00 8.56E+00 9.99E+00 NA NA NA 2.00E+02 MW-40-27 MW-40-46 Q2-2010 012 46.2 27 4/15/2010 16:18 2.35E+02 1.38E+02 1.45E+02 3.98E-01 7.23E-01 8.15E-01 2.73E+00 3.30E+00 4.08E+00 1.19E+00 3.40E+00 3.95E+00 NA NA NA 1.99E+02 ND ND ND NA MW-40-46 MW-40-46 Q3-2010 013 46.2 27 8/26/2010 14:56 1.24E+02 1.22E+02 1.29E+02

-1.83E-01 5.11E-01 7.19E-01 7.02E-01 6.01E+00 6.90E+00 5.48E+00 6.17E+00 8.30E+00 NA NA NA 1.99E+02 MW-40-46 MW-40-46 Q4-2010 014 46.2 27 11/29/2010 16:36 1.63E+02 1.47E+02 1.48E+02 6.60E-02 7.89E-01 9.38E-01 5.82E-01 3.82E+00 4.28E+00 2.06E+00 3.99E+00 4.74E+00 NA NA NA 1.99E+02 MW-40-46 MW-40-46 Q1-2011 015 46.2 27 3/8/2011 12:58 2.48E+02 2.74E+02 2.63E+02 1.03E-01 8.58E-01 1.07E+00 2.82E+00 8.00E+00 9.18E+00 7.99E+00 8.74E+00 1.19E+01 NA NA NA 1.99E+02 MW-40-46 MW-40-81 Q2-2010 012 80.7

-7.5 4/15/2010 12:15 1.92E+02 1.37E+02 1.47E+02 4.25E-01 7.02E-01 7.79E-01 1.72E+00 4.20E+00 4.93E+00 1.08E-01 3.82E+00 4.36E+00 NA NA NA 2.20E+02 ND ND ND NA MW-40-81 MW-40-81 Q3-2010 013 80.7

-7.5 8/26/2010 11:05 9.08E+01 1.14E+02 1.24E+02 2.45E-01 5.25E-01 6.06E-01

-3.95E+00 5.24E+00 4.96E+00

-2.64E+00 4.68E+00 4.20E+00 NA NA NA 2.20E+02 MW-40-81 MW-40-81 Q4-2010 014 80.7

-7.5 11/29/2010 12:03 2.48E+02 1.58E+02 1.47E+02 1.13E-03 6.45E-01 7.85E-01

-9.67E-01 4.38E+00 4.79E+00

-4.37E-01 4.83E+00 5.28E+00 NA NA NA 2.20E+02 MW-40-81 MW-40-81 Q1-2011 015 80.7

-7.5 3/8/2011 10:17 2.33E+02 2.68E+02 2.63E+02 8.50E-01 1.51E+00 1.67E+00 1.26E+00 1.06E+01 7.71E+00

-1.45E+00 6.08E+00 6.16E+00 NA NA NA 2.20E+02 MW-40-81 MW-40-100 Q2-2010 014 100.2

-27 4/15/2010 12:16 1.39E+02 1.33E+02 1.46E+02

-1.08E-01 5.37E-01 7.48E-01

-2.83E-01 3.54E+00 3.96E+00

-2.16E+00 5.12E+00 4.80E+00 NA NA NA ND ND ND*

ND NA MW-40-100 MW-40-100 Q3-2010 015 100.2

-27 8/26/2010 11:09 1.24E+02 1.37E+02 1.45E+02

-2.33E-01 3.95E-01 6.21E-01 8.87E-01 6.15E+00 7.12E+00 6.51E-01 5.61E+00 6.53E+00 NA NA NA 2.46E+01 MW-40-100 MW-40-100 Q4-2010 016 100.2

-27 11/29/2010 12:12 1.34E+02 1.40E+02 1.46E+02

-2.12E-01 6.70E-01 8.39E-01

-1.46E-01 4.05E+00 4.53E+00 3.11E-01 4.26E+00 4.81E+00 NA NA NA 2.46E+01 MW-40-100 MW-40-100*

Q1-2011 017 100.2

-27 3/8/2011 10:27 5.17E+01 2.14E+02 2.64E+02 2.52E-02 1.30E+00 1.58E+00 2.46E+01*

1.35E+01 7.66E+00

-1.40E+00 7.88E+00 8.30E+00 NA NA NA 2.46E+01 MW-40-100*

MW-40-127 Q2-2010 014 127.2

-54 4/15/2010 13:13 1.26E+02 1.34E+02 1.47E+02

-5.12E-03 3.50E-01 4.61E-01

-2.40E+00 9.29E+00 9.96E+00 2.32E+00 9.72E+00 1.18E+01 NA NA NA ND ND ND*

ND NA MW-40-127 MW-40-127 Q3-2010 015 127.2

-54 8/26/2010 11:16 1.36E+02 1.40E+02 1.47E+02 2.23E-02 2.78E-01 3.67E-01

-5.02E+00 7.95E+00 8.28E+00 6.43E-01 6.48E+00 7.48E+00 NA NA NA 5.07E+01 MW-40-127 MW-40-127 Q4-2010 016 127.2

-54 11/29/2010 12:26 1.22E+02 1.38E+02 1.45E+02 7.34E-01 9.02E-01 9.73E-01

-1.53E-01 4.82E+00 5.43E+00 1.12E+00 4.38E+00 5.06E+00 NA NA NA 5.07E+01 MW-40-127 MW-40-127*

Q1-2011 017 127.2

-54 3/8/2011 10:41 1.33E+02 2.40E+02 2.64E+02 1.03E+00 1.40E+00 1.51E+00 5.07E+01*

1.64E+01 7.63E+00 3.45E-01 7.18E+00 7.96E+00 NA NA NA 5.07E+01 MW-40-127*

MW-40-162 Q2-2010 012 161.7

-88.5 4/15/2010 14:50 1.03E+02 1.32E+02 1.46E+02 9.77E-02 6.63E-01 8.18E-01

-2.73E+00 8.36E+00 8.61E+00 2.35E+00 8.63E+00 1.05E+01 NA NA NA ND ND ND ND NA MW-40-162 MW-40-162 Q3-2010 013 161.7

-88.5 8/26/2010 12:29 1.02E+02 1.36E+02 1.48E+02 5.09E-01 7.23E-01 7.75E-01 7.14E-01 6.23E+00 7.08E+00 3.52E+00 6.78E+00 8.38E+00 NA NA NA MW-40-162 MW-40-162 Q4-2010 014 161.7

-88.5 11/29/2010 12:45 6.40E+01 1.27E+02 1.45E+02

-5.51E-03 6.55E-01 7.94E-01 3.60E-01 4.34E+00 4.91E+00 3.43E-01 4.47E+00 5.03E+00 NA NA NA MW-40-162 MW-40-162 Q1-2011 015 161.7

-88.5 3/8/2011 11:02 8.33E+01 2.24E+02 2.63E+02

-1.03E+00 1.07E+00 1.57E+00

-3.72E+00 6.12E+00 5.93E+00

-2.11E+00 6.42E+00 6.37E+00 NA NA NA MW-40-162 MW-41-40 Q2-2010 016 34.4 20.5 4/19/2010 14:09 4.32E+02 1.79E+02 1.50E+02 2.09E+00 1.05E+00 8.40E-01

-2.56E+00 8.09E+00 8.29E+00

-6.83E-01 8.55E+00 9.32E+00 NA NA NA 1.92E+03 5.51E+00 ND ND NA MW-41-40 MW-41-40 Q3-2010 017 34.4 20.5 7/21/2010 13:41 2.79E+03 3.02E+02 1.47E+02 4.37E+00 1.02E+00 6.33E-01 1.59E+00 5.82E+00 7.07E+00

-6.50E-01 7.18E+00 7.61E+00 NA NA NA 1.92E+03 5.51E+00 MW-41-40 MW-41-40 Q4-2010 018 34.4 20.5 10/25/2010 16:06 2.43E+03 2.78E+02 1.17E+02 4.08E+00 1.16E+00 6.72E-01 3.32E+00 5.63E+00 6.87E+00

-1.99E+00 6.74E+00 6.96E+00 NA NA NA 1.92E+03 5.51E+00 MW-41-40 MW-41-40 Q1-2011 019 34.4 20.5 2/14/2011 14:05 2.03E+03 4.02E+02 2.98E+02 1.15E+01 2.68E+00 1.83E+00 4.60E+00 7.30E+00 8.61E+00 4.22E+00 7.36E+00 9.28E+00 NA NA NA 1.92E+03 5.51E+00 MW-41-40 MW-41-63 Q2-2010 015 59.5

-4.6 4/19/2010 14:03 4.36E+02 1.77E+02 1.49E+02 3.66E+00 1.22E+00 7.70E-01

-4.51E+00 1.22E+01 1.52E+01

-7.27E-02 6.99E+00 7.76E+00 NA NA NA 6.73E+02 4.91E+00 ND ND NA MW-41-63 MW-41-63 Q3-2010 016 59.5

-4.6 7/21/2010 13:41 5.18E+02 1.68E+02 1.43E+02 4.79E+00 1.09E+00 6.23E-01

-2.71E+00 8.29E+00 8.77E+00 1.61E+00 7.93E+00 9.59E+00 NA NA NA 6.73E+02 4.91E+00 MW-41-63 MW-41-63 Q4-2010 017 59.5

-4.6 10/25/2010 12:59 5.06E+02 1.50E+02 1.14E+02 4.25E+00 1.19E+00 7.17E-01 1.06E+00 6.08E+00 7.07E+00 2.87E+00 5.85E+00 7.23E+00 NA NA NA 6.73E+02 4.91E+00 MW-41-63 MW-41-63 Q1-2011 018 59.5

-4.6 2/14/2011 13:37 1.23E+03 4.44E+02 3.80E+02 6.92E+00 2.46E+00 1.96E+00 1.24E+00 5.30E+00 6.03E+00 2.69E+00 6.06E+00 7.29E+00 NA NA NA 6.73E+02 4.91E+00 MW-41-63 MW-42-49 Q2-2010 021 42.6 27.1 4/16/2010 12:59 1.30E+03 4.25E+02 3.71E+02 2.40E+01 2.31E+00 8.23E-01 2.37E+04 2.85E+03 2.92E+01 8.37E-01 1.06E+01 1.23E+01 2.36E+02 2.88E+01 2.07E+01 1.44E+03 1.98E+01 2.48E+04 ND 2.35E+02 MW-42-49 MW-42-49 Q3-2010 022 42.6 27.1 7/30/2010 11:38 1.69E+03 2.34E+02 1.24E+02 1.39E+01 1.53E+00 3.90E-01 1.87E+04 2.46E+03 2.50E+01 7.33E-01 6.64E+00 7.77E+00 1.77E+02 2.97E+01 2.18E+01 1.44E+03 1.98E+01 2.48E+04 2.35E+02 MW-42-49 MW-42-49 Q4-2010 023 42.6 27.1 10/27/2010 12:23 1.28E+03 2.03E+02 1.64E+02 1.81E+01 2.31E+00 8.72E-01 2.39E+04 2.94E+03 2.93E+01

-1.67E+00 9.77E+00 1.03E+01 2.24E+02 2.66E+01 2.10E+01 1.44E+03 1.98E+01 2.48E+04 2.35E+02 MW-42-49 MW-42-49 Q1-2011 024 42.6 27.1 3/4/2011 11:37 1.49E+03 5.14E+02 3.88E+02 2.32E+01 3.34E+00 1.11E+00 3.30E+04 4.42E+03 2.75E+01 1.42E+00 6.78E+00 7.87E+00 3.02E+02 3.04E+01 2.00E+01 1.44E+03 1.98E+01 2.48E+04 2.35E+02 MW-42-49 MW-42-78 Q2-2010 016 74

-4.3 4/16/2010 13:29 3.93E+02 2.91E+02 3.10E+02 1.81E-01 7.86E-01 9.23E-01 2.22E+00 8.67E+00 1.03E+01

-6.97E+00 9.24E+00 7.54E+00

-6.55E+00 1.76E+01 2.08E+01 5.59E+02 ND ND ND ND MW-42-78 MW-42-78 Q3-2010 017 74

-4.3 7/30/2010 12:23 6.31E+02 1.71E+02 1.31E+02 2.78E-02 3.03E-01 3.85E-01

-1.17E-01 7.56E+00 8.30E+00

-7.43E-01 7.04E+00 7.42E+00 1.96E+00 1.31E+01 1.52E+01 5.59E+02 MW-42-78 MW-42-78 Q4-2010 018 74

-4.3 10/27/2010 13:56 6.13E+02 1.74E+02 1.64E+02

-1.14E-01 4.79E-01 5.87E-01

-1.09E+00 8.69E+00 9.51E+00

-5.11E+00 8.41E+00 7.24E+00

-4.24E+00 1.80E+01 2.09E+01 5.59E+02 MW-42-78 MW-42-78 Q1-2011 019 74

-4.3 3/4/2011 10:58 5.98E+02 4.06E+02 3.84E+02 8.92E-01 1.47E+00 1.60E+00

-2.03E+00 6.72E+00 6.99E+00 8.03E-02 6.70E+00 7.41E+00 0.00E+00 1.73E+01 1.96E+01 5.59E+02 MW-42-78 MW-43-28 Q2-2010 015 23.5 25.3 4/19/2010 13:38 2.25E+02 1.39E+02 1.47E+02

-7.48E-02 5.52E-01 7.63E-01

-2.66E-01 5.61E+00 6.36E+00

-1.90E-01 5.61E+00 6.33E+00 NA NA NA 2.10E+02 ND ND ND NA MW-43-28 MW-43-28 Q3-2010 016 23.5 25.3 7/20/2010 13:48 9.11E+01 1.33E+02 1.47E+02

-6.43E-02 3.80E-01 5.33E-01 5.80E+00 7.53E+00 9.76E+00

-1.44E+00 9.49E+00 1.01E+01 NA NA NA 2.10E+02 MW-43-28 MW-43-28 Q4-2010 017 23.5 25.3 10/25/2010 11:29 1.95E+02 1.17E+02 1.13E+02

-1.98E-01 5.01E-01 6.94E-01 3.36E+00 5.00E+00 6.09E+00

-5.01E-01 5.43E+00 5.84E+00 NA NA NA 2.10E+02 MW-43-28 MW-43-28 Q1-2011 018 23.5 25.3 2/15/2011 13:08 2.54E+02 2.80E+02 2.99E+02

-1.06E+00 1.40E+00 2.00E+00 5.75E-02 1.26E+01 7.06E+00

-3.84E+00 6.84E+00 6.54E+00 NA NA NA 2.10E+02 MW-43-28 MW-43-62 Q2-2010 015 51

-2.2 4/19/2010 13:17 2.16E+02 1.39E+02 1.47E+02 6.35E-01 7.10E-01 7.15E-01

-1.08E+00 4.44E+00 4.90E+00 1.30E+00 4.68E+00 5.52E+00 NA NA NA 2.16E+02 ND ND ND NA MW-43-62 MW-43-62 Q3-2010 016 51

-2.2 7/20/2010 15:07 5.97E+01 1.33E+02 1.51E+02 4.41E-01 4.75E-01 4.94E-01

-1.11E+00 7.96E+00 8.85E+00

-2.40E+00 8.22E+00 8.59E+00 NA NA NA 2.16E+02 MW-43-62 MW-43-62 Q4-2010 017 51

-2.2 10/25/2010 11:06 9.76E+01 1.05E+02 1.12E+02 3.69E-01 7.10E-01 8.03E-01 5.94E-01 6.27E+00 6.81E+00

-6.69E-01 5.37E+00 5.81E+00 NA NA NA 2.16E+02 MW-43-62 MW-43-62 Q1-2011 018 51

-2.2 2/15/2011 13:15 1.82E+02 2.76E+02 3.00E+02 7.75E-01 1.74E+00 1.95E+00 6.59E-01 5.08E+00 5.56E+00

-2.37E-01 5.16E+00 5.52E+00 NA NA NA 2.16E+02 MW-43-62 MW-44-66 Q2-2010 Mid 016 62.4 31.1 6/10/2010 15:30 4.75E+02 1.89E+02 1.92E+02 2.16E-01 6.77E-01 7.93E-01

-1.54E+00 5.91E+00 6.37E+00

-1.91E+00 6.06E+00 6.25E+00 NA NA NA 3.54E+02 ND ND ND NA MW-44-66 MW-44-66 Q3-2010 017 62.4 31.1 7/22/2010 15:47 1.75E+02 1.41E+02 1.47E+02 2.76E-01 5.63E-01 6.43E-01

-3.76E+00 6.86E+00 6.84E+00 1.20E+00 8.52E+00 9.73E+00 NA NA NA 3.54E+02 MW-44-66 MW-44-66 Q4-2010 018 62.4 31.1 10/26/2010 14:46 3.10E+02 1.29E+02 1.11E+02

-1.07E-01 4.30E-01 5.95E-01 4.23E-01 6.24E+00 7.11E+00

-3.70E+00 7.37E+00 7.27E+00 NA NA NA 3.54E+02 MW-44-66 MW-44-66 Q1-2011 019 62.4 31.1 2/18/2011 10:41 4.57E+02 3.90E+02 3.99E+02

-2.94E-01 1.59E+00 1.95E+00 1.74E+00 7.72E+00 8.56E+00

-1.40E+00 7.92E+00 8.46E+00 NA NA NA 3.54E+02 MW-44-66 MW-44-102 Q2-2010 Mid 017 80 13.5 6/10/2010 13:13 4.94E+02 1.79E+02 1.83E+02

-1.79E-01 5.13E-01 6.74E-01

-2.41E+00 7.89E+00 8.11E+00

-5.22E+00 7.37E+00 6.86E+00 NA NA NA 4.03E+02 ND ND ND NA MW-44-102 MW-44-102 Q3-2010 018 80 13.5 7/21/2010 13:20 2.76E+02 1.49E+02 1.45E+02 4.11E-01 4.70E-01 4.80E-01 2.38E+00 1.02E+01 1.18E+01

-1.83E+00 8.85E+00 9.25E+00 NA NA NA 4.03E+02 MW-44-102 MW-44-102 Q4-2010 019 80 13.5 10/26/2010 13:32 4.47E+02 1.42E+02 1.12E+02 2.42E-01 5.47E-01 6.33E-01

-2.73E+00 5.49E+00 5.54E+00 6.85E-01 5.38E+00 6.11E+00 NA NA NA 4.03E+02 MW-44-102 MW-44-102 Q1-2011 020 80 13.5 2/18/2011 10:44 3.93E+02 2.90E+02 2.97E+02 2.63E-01 1.86E+00 2.15E+00 2.22E-01 4.96E+00 5.47E+00

-2.93E-01 6.02E+00 6.58E+00 NA NA NA 4.03E+02 MW-44-102 MW-45-42 Q2-2010 020 37 16.6 4/20/2010 16:13 2.02E+03 3.05E+02 1.51E+02 2.96E-01 6.27E-01 7.22E-01 2.94E+00 6.79E+00 7.62E+00

-7.47E+00 8.46E+00 5.97E+00 NA NA NA 4.14E+03 ND ND ND NA MW-45-42 MW-45-42 Q3-2010 021 37 16.6 7/19/2010 15:38 3.69E+03 3.35E+02 1.43E+02 5.08E-01 6.10E-01 6.47E-01 1.04E+00 7.75E+00 8.85E+00

-1.87E+00 7.10E+00 7.11E+00 NA NA NA 4.14E+03 MW-45-42 MW-45-42 Q4-2010 022 37 16.6 10/22/2010 15:59 2.74E+03 2.90E+02 1.13E+02 9.55E-02 5.19E-01 6.32E-01 1.35E+00 6.04E+00 6.99E+00

-1.65E+00 5.70E+00 5.89E+00 NA NA NA 4.14E+03 MW-45-42 MW-45-42 Q1-2011 023 37 16.6 2/16/2011 16:58 8.12E+03 7.86E+02 3.63E+02 1.03E+00 1.39E+00 1.48E+00

-8.53E-01 5.64E+00 5.99E+00 1.42E+00 6.30E+00 7.17E+00 NA NA NA 4.14E+03 MW-45-42 MW-45-61 Q2-2010 020 58

-4.4 4/20/2010 11:13 9.89E+02 2.25E+02 1.45E+02 2.71E-01 7.70E-01 8.89E-01

-8.78E-02 7.91E+00 8.84E+00

-3.82E+00 8.70E+00 8.72E+00 NA NA NA 1.33E+03 ND ND ND NA MW-45-61 MW-45-61 Q3-2010 021 58

-4.4 7/19/2010 13:28 1.00E+03 2.07E+02 1.48E+02 4.07E-01 5.04E-01 5.30E-01

-2.93E+00 8.29E+00 8.61E+00

-2.24E+00 8.88E+00 9.24E+00 NA NA NA 1.33E+03 MW-45-61 MW-45-61 Q4-2010 022 58

-4.4 10/22/2010 11:54 1.51E+03 2.22E+02 1.12E+02 3.58E-01 5.53E-01 6.05E-01

-2.92E+00 5.78E+00 5.94E+00 1.19E-01 6.92E+00 7.73E+00 NA NA NA 1.33E+03 MW-45-61 MW-45-61 Q1-2011 023 58

-4.4 2/16/2011 16:15 1.84E+03 5.20E+02 3.98E+02

-2.25E-01 1.64E+00 1.96E+00 1.38E+00 4.80E+00 5.41E+00 9.89E-01 5.46E+00 6.15E+00 NA NA NA 1.33E+03 MW-45-61 MW-46 Q2-2010 020 10.5 7.6 4/12/2010 11:32 7.62E+02 1.92E+02 1.77E+02 8.57E-01 7.68E-01 7.39E-01

-2.73E+00 1.08E+01 1.14E+01

-2.57E+00 1.05E+01 1.13E+01 NA NA NA 2.07E+03 8.57E-01 ND ND NA MW-46 MW-46 Q3-2010 021 10.5 7.6 7/23/2010 13:10 1.92E+03 2.58E+02 1.46E+02 1.80E-01 5.63E-01 6.59E-01 1.28E-01 7.65E+00 8.12E+00

-1.36E+00 7.96E+00 8.34E+00 NA NA NA 2.07E+03 8.57E-01 MW-46 MW-46 Q4-2010 022 10.5 7.6 10/28/2010 13:25 3.13E+03 3.08E+02 1.13E+02 3.76E-01 5.09E-01 5.49E-01

-2.05E+00 5.85E+00 5.88E+00 2.98E+00 6.81E+00 8.22E+00 NA NA NA 2.07E+03 8.57E-01 MW-46 MW-46 Q1-2011 023 10.5 7.6 2/23/2011 12:46 2.47E+03 5.70E+02 3.98E+02 1.12E+00 1.89E+00 2.06E+00

-2.22E+00 5.28E+00 5.28E+00 5.21E-01 5.10E+00 5.66E+00 NA NA NA 2.07E+03 8.57E-01 MW-46 MW-49-26 Q2-2010 020 19.1

-4.4 4/23/2010 14:42 3.00E+03 3.30E+02 1.38E+02 1.55E+01 2.44E+00 8.19E-01 2.82E+00 7.32E+00 8.92E+00

-2.28E-01 9.12E+00 1.01E+01

-7.28E+00 1.95E+01 2.26E+01 2.95E+03 1.38E+01 ND ND ND MW-49-26 MW-49-26 Q3-2010 021 19.1

-4.4 8/11/2010 11:27 3.03E+03 3.03E+02 1.27E+02 1.28E+01 1.44E+00 3.66E-01

-7.91E-01 1.14E+01 1.15E+01

-1.86E+00 1.10E+01 1.19E+01 3.27E-01 1.64E+01 1.92E+01 2.95E+03 1.38E+01 MW-49-26 MW-49-26 Q4-2010 022 19.1

-4.4 11/11/2010 14:23 2.59E+03 3.00E+02 4.76E+02

-3.42E-01 9.56E-01 2.34E+00 4.62E+00 4.84E+00 1.15E+01 1.18E+00 3.96E+00 9.11E+00

-1.79E+00 1.02E+01 2.29E+01 2.95E+03 1.38E+01 MW-49-26 MW-49-26 Q1-2011 023 19.1

-4.4 1/28/2011 13:37 3.17E+03 6.00E+02 4.29E+02 1.30E+01 2.86E+00 2.01E+00 3.39E-01 1.04E+01 7.00E+00

-2.43E+00 6.42E+00 6.44E+00

-4.38E+00 1.87E+01 2.20E+01 2.95E+03 1.38E+01 MW-49-26

TABLE 3 FIRST QUARTER 2011 GROUNDWATER ANALYTICAL RESULTS AND AVERAGES INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q12011 FINAL Table 3 - First Quarter 2011 Groundwater Analytical Results and Averages.xlsx; Q12011 Table 3 Page 3 of 5 See Page 5 for Notes TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Date Time Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Average Average Average Average Average ANALYSIS RESULTS5 YEARLY ROLLING AVERAGES4,6 Well ID1 TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

SAMPLE COLLECTION Well ID1 SAMPLING QUARTER2,8 SAMPLE ID SAMPLE ZONE CENTER, Depth Ft Below Top of Casing3 SAMPLE ZONE CENTER Elevation Ft msl3 MW-49-42 Q2-2010 020 38.1

-23.4 4/23/2010 14:39 2.76E+03 3.26E+02 1.43E+02 1.75E+01 2.28E+00 7.01E-01

-5.63E+00 6.62E+00 6.01E+00

-1.68E+00 7.58E+00 7.64E+00

-3.23E+00 2.18E+01 2.51E+01 2.47E+03 1.97E+01 ND ND ND MW-49-42 MW-49-42 Q3-2010 021 38.1

-23.4 8/11/2010 11:00 2.27E+03 2.72E+02 1.30E+02 1.85E+01 1.67E+00 3.91E-01 4.80E+00 7.88E+00 9.85E+00

-2.34E+00 8.76E+00 9.06E+00

-1.91E+00 1.65E+01 1.96E+01 2.47E+03 1.97E+01 MW-49-42 MW-49-42 Q4-2010 022 38.1

-23.4 11/11/2010 14:13 2.39E+03 2.73E+02 4.02E+02 1.99E+01 1.65E+00 1.12E+00 8.48E-01 6.79E+00 9.79E+00 3.75E+00 5.42E+00 1.30E+01 4.00E+00 8.14E+00 1.80E+01 2.47E+03 1.97E+01 MW-49-42 MW-49-42 Q1-2011 023 38.1

-23.4 1/28/2011 13:00 2.45E+03 5.38E+02 3.86E+02 2.30E+01 4.02E+00 2.02E+00

-1.07E+00 5.74E+00 6.21E+00

-2.45E+00 5.50E+00 5.32E+00

-3.26E+00 1.86E+01 2.18E+01 2.47E+03 1.97E+01 MW-49-42 MW-49-65 Q2-2010 020 60

-45.4 4/23/2010 15:17 1.55E+03 2.63E+02 1.50E+02 1.04E+01 1.85E+00 6.37E-01 6.11E+00 1.36E+01 9.18E+00

-2.53E-01 1.17E+01 1.35E+01

-1.29E+01 1.96E+01 2.32E+01 1.55E+03 1.21E+01 ND ND ND MW-49-65 MW-49-65 Q3-2010 021 60

-45.4 8/11/2010 11:19 1.32E+03 2.16E+02 1.28E+02 1.24E+01 1.44E+00 4.49E-01

-1.12E+01 1.22E+01 1.43E+01

-2.58E-01 9.88E+00 1.11E+01

-6.74E-01 1.80E+01 2.13E+01 1.55E+03 1.21E+01 MW-49-65 MW-49-65 Q4-2010 022 60

-45.4 11/11/2010 14:18 1.37E+03 2.34E+02 3.97E+02 1.41E+01 1.45E+00 1.34E+00 6.99E+00 6.88E+00 1.07E+01 3.39E-01 5.37E+00 1.18E+01

-3.41E+00 9.31E+00 2.09E+01 1.55E+03 1.21E+01 MW-49-65 MW-49-65 Q1-2011 023 60

-45.4 1/28/2011 13:15 1.94E+03 5.02E+02 3.85E+02 1.15E+01 3.28E+00 2.06E+00

-6.30E-01 4.96E+00 5.21E+00 7.15E-01 5.20E+00 5.81E+00

-9.08E+00 1.83E+01 2.20E+01 1.55E+03 1.21E+01 MW-49-65 MW-50-42 Q2-2010 021 42

-27.1 4/30/2010 12:34 1.36E+03 2.46E+02 1.68E+02 4.36E+00 1.33E+00 8.88E-01 8.49E-01 7.56E+00 8.38E+00

-1.97E+00 5.09E+00 5.04E+00

-1.48E+01 2.25E+01 2.61E+01 7.37E+02 5.49E+00 ND ND ND MW-50-42 MW-50-42 Q3-2010 022 42

-27.1 8/4/2010 13:11 1.61E+02 1.25E+02 1.28E+02 8.43E+00 1.42E+00 5.63E-01

-1.94E+00 8.65E+00 9.25E+00 1.30E-01 8.05E+00 9.05E+00 0.00E+00 1.59E+01 1.88E+01 7.37E+02 5.49E+00 MW-50-42 MW-50-42 Q4-2010 023 42

-27.1 11/12/2010 12:10 8.67E+02 1.83E+02 1.22E+02 3.73E+00 1.31E+00 9.89E-01 2.40E+00 5.71E+00 6.76E+00 2.73E+00 5.58E+00 6.94E+00

-7.36E+00 1.79E+01 2.15E+01 7.37E+02 5.49E+00 MW-50-42 MW-50-42 Q1-2011 024 42

-27.1 2/25/2011 12:36 5.61E+02 3.88E+02 3.85E+02 5.42E+00 2.34E+00 1.91E+00

-1.29E-01 5.46E+00 5.88E+00

-9.07E-01 4.42E+00 4.42E+00

-7.19E+00 1.82E+01 2.18E+01 7.37E+02 5.49E+00 MW-50-42 MW-50-66 Q2-2010 026 60

-45.1 4/30/2010 14:25 2.76E+03 3.21E+02 1.68E+02 2.99E+01 3.01E+00 8.81E-01

-1.86E+00 5.84E+00 6.18E+00 3.85E-01 5.38E+00 6.13E+00

-1.14E+01 2.19E+01 2.52E+01 3.44E+03 2.65E+01 ND ND ND MW-50-66 MW-50-66 Q3-2010 027 60

-45.1 8/4/2010 16:38 3.51E+03 3.33E+02 1.34E+02 2.65E+01 2.28E+00 4.80E-01 3.52E+00 8.29E+00 9.99E+00 9.22E-01 9.18E+00 1.06E+01 2.07E+00 1.56E+01 1.81E+01 3.44E+03 2.65E+01 MW-50-66 MW-50-66 Q4-2010 028 60

-45.1 11/12/2010 12:30 3.72E+03 3.30E+02 1.20E+02 2.33E+01 2.71E+00 9.50E-01

-1.39E+00 6.21E+00 6.79E+00

-1.67E+00 6.95E+00 7.30E+00 3.25E-01 1.88E+01 2.18E+01 3.44E+03 2.65E+01 MW-50-66 MW-50-66 Q1-2011 029 60

-45.1 2/25/2011 12:36 3.76E+03 6.18E+02 3.83E+02 2.61E+01 4.02E+00 2.13E+00 2.94E+00 7.20E+00 8.24E+00 6.79E-01 8.00E+00 9.10E+00

-2.80E+00 1.81E+01 2.12E+01 3.44E+03 2.65E+01 MW-50-66 MW-51-40 Q2-2010 015 39.7 28 4/8/2010 13:58 9.55E+01 1.32E+02 1.44E+02

-1.04E-01 7.30E-01 8.98E-01 8.94E-01 8.25E+00 9.56E+00

-1.94E+00 9.18E+00 9.55E+00 NA NA NA 1.59E+02 ND ND ND NA MW-51-40 MW-51-40 Q3-2010 016 39.7 28 8/25/2010 16:29 1.70E+02 1.07E+02 1.03E+02

-4.31E-02 3.11E-01 4.19E-01

-2.48E+00 6.17E+00 6.53E+00 1.46E+00 5.21E+00 6.37E+00 NA NA NA 1.59E+02 MW-51-40 MW-51-40 Q4-2010 017 39.7 28 11/30/2010 12:54 1.48E+02 1.41E+02 1.44E+02 1.46E-01 6.05E-01 7.12E-01 1.54E+00 4.28E+00 4.95E+00 1.72E+00 4.17E+00 4.95E+00 NA NA NA 1.59E+02 MW-51-40 MW-51-40 Q1-2011 018 39.7 28 3/8/2011 10:18 1.02E+02 2.34E+02 2.67E+02 1.07E+00 1.51E+00 1.61E+00

-7.97E+00 1.21E+01 1.36E+01 2.42E+00 7.30E+00 8.76E+00 NA NA NA 1.59E+02 MW-51-40 MW-51-79 Q2-2010 015 78.7

-11 4/8/2010 14:21 6.44E+01 1.33E+02 1.51E+02 4.88E-01 8.07E-01 9.02E-01 4.35E+00 8.89E+00 1.11E+01 4.52E+00 1.00E+01 1.28E+01 NA NA NA 1.10E+02 ND ND ND NA MW-51-79 MW-51-79 Q3-2010 016 78.7

-11 8/25/2010 16:47 1.10E+02 9.84E+01 1.01E+02 5.81E-01 8.23E-01 8.92E-01 5.29E+00 6.13E+00 7.76E+00 1.58E+00 6.71E+00 7.88E+00 NA NA NA 1.10E+02 MW-51-79 MW-51-79 Q4-2010 017 78.7

-11 11/30/2010 13:08 3.11E+01 1.21E+02 1.44E+02

-1.22E-01 4.32E-01 5.24E-01

-8.30E-01 4.13E+00 4.54E+00 9.98E-01 4.02E+00 4.66E+00 NA NA NA 1.10E+02 MW-51-79 MW-51-79 Q1-2011 018 78.7

-11 3/8/2011 10:34 1.36E+02 2.46E+02 2.70E+02

-2.03E-01 1.22E+00 1.53E+00 2.42E+00 5.42E+00 6.52E+00

-2.74E+00 7.36E+00 6.45E+00 NA NA NA 1.10E+02 MW-51-79 MW-51-104 Q2-2010 013 103.7

-36 4/8/2010 10:42 1.10E+02 1.34E+02 1.45E+02 1.26E-01 7.62E-01 8.99E-01

-5.36E-01 8.43E+00 9.34E+00 2.15E+00 7.96E+00 9.79E+00 NA NA NA ND ND ND ND NA MW-51-104 MW-51-104 Q3-2010 014 103.7

-36 8/25/2010 13:18 1.33E+02 1.37E+02 1.44E+02 7.62E-01 8.15E-01 8.20E-01 8.90E-01 5.75E+00 6.63E+00

-2.70E-01 4.96E+00 5.47E+00 NA NA NA MW-51-104 MW-51-104 Q4-2010 015 103.7

-36 11/30/2010 9:55 8.54E+01 1.33E+02 1.47E+02 3.74E-01 7.18E-01 8.12E-01

-1.43E-01 3.99E+00 4.55E+00 2.19E-01 4.56E+00 5.05E+00 NA NA NA MW-51-104 MW-51-104 Q1-2011 016 103.7

-36 3/8/2011 12:10 5.76E+01 3.10E+02 3.55E+02 8.91E-01 1.47E+00 1.60E+00 2.54E+00 7.20E+00 8.14E+00 9.02E-01 5.50E+00 6.24E+00 NA NA NA MW-51-104 MW-51-135 Q2-2010 013 135.2

-67.5 4/8/2010 11:06 5.86E+01 1.31E+02 1.50E+02

-2.09E-02 5.99E-01 7.85E-01

-7.04E-03 8.73E+00 9.88E+00

-4.95E-01 1.04E+01 1.19E+01 NA NA NA ND ND ND ND NA MW-51-135 MW-51-135 Q3-2010 014 135.2

-67.5 8/25/2010 13:21 1.36E+02 1.41E+02 1.47E+02

-2.33E-01 4.44E-01 6.70E-01

-6.64E-01 6.15E+00 6.80E+00 1.74E+00 6.62E+00 7.77E+00 NA NA NA MW-51-135 MW-51-135 Q4-2010 015 135.2

-67.5 11/30/2010 9:57 9.53E+01 1.33E+02 1.45E+02 4.21E-01 7.13E-01 7.98E-01

-5.11E-01 4.18E+00 4.61E+00

-2.98E-01 4.20E+00 4.58E+00 NA NA NA MW-51-135 MW-51-135 Q1-2011 016 135.2

-67.5 3/8/2011 12:44 8.29E+01 2.24E+02 2.62E+02 8.62E-01 1.31E+00 1.42E+00 8.60E-02 6.02E+00 6.77E+00 2.37E+00 5.96E+00 7.38E+00 NA NA NA MW-51-135 MW-51-163 Q2-2010 013 162.7

-95 4/8/2010 11:31 5.35E+01 1.27E+02 1.46E+02

-7.65E-02 6.06E-01 8.13E-01

-2.95E+00 8.55E+00 8.74E+00

-1.50E+00 1.04E+01 1.10E+01 NA NA NA ND ND ND ND NA MW-51-163 MW-51-163 Q3-2010 014 162.7

-95 8/25/2010 13:51 8.26E+01 9.75E+01 1.05E+02

-1.08E-01 3.98E-01 5.31E-01 3.91E+00 6.72E+00 8.11E+00 8.67E-01 6.32E+00 7.26E+00 NA NA NA MW-51-163 MW-51-163 Q4-2010 015 162.7

-95 11/30/2010 10:02 9.01E+01 1.31E+02 1.44E+02

-3.11E-01 6.98E-01 9.94E-01 1.23E+00 8.07E+00 4.14E+00 3.30E-01 3.94E+00 4.43E+00 NA NA NA MW-51-163 MW-51-163 Q1-2011 016 162.7

-95 3/8/2011 13:01 0.00E+00 1.96E+02 2.63E+02

-5.97E-01 1.39E+00 1.98E+00 2.81E+00 6.54E+00 7.66E+00 5.35E-01 7.76E+00 8.69E+00 NA NA NA MW-51-163 MW-51-189 Q2-2010 013 189.2

-121.5 4/8/2010 11:16 5.35E+01 1.27E+02 1.46E+02 3.25E-01 7.35E-01 8.47E-01

-2.07E+00 8.19E+00 8.51E+00 3.45E-01 7.39E+00 8.29E+00 NA NA NA ND ND ND*

ND NA MW-51-189 MW-51-189 Q3-2010 014 189.2

-121.5 8/25/2010 13:13 5.86E+01 9.38E+01 1.04E+02 4.40E-02 5.97E-01 7.65E-01 2.87E+00 5.64E+00 6.69E+00

-8.01E-01 5.85E+00 6.25E+00 NA NA NA 3.77E+01 MW-51-189 MW-51-189 Q4-2010 015 189.2

-121.5 11/30/2010 9:56 6.91E+01 1.29E+02 1.46E+02 1.93E-01 7.99E-01 9.81E-01

-7.45E-01 4.51E+00 4.98E+00

-3.16E-01 4.61E+00 5.06E+00 NA NA NA 3.77E+01 MW-51-189 MW-51-189*

Q1-2011 016 189.2

-121.5 3/8/2011 12:30

-1.50E+01 1.93E+02 2.68E+02

-3.06E-01 1.46E+00 1.97E+00 3.77E+01*

1.47E+01 6.28E+00 2.28E-01 5.28E+00 5.79E+00 NA NA NA 3.77E+01 MW-51-189*

MW-52-11 Q2-2010 005 10 6.8 5/5/2010 12:26 3.73E+02 1.74E+02 1.83E+02 1.89E-01 4.77E-01 5.62E-01 2.14E+00 5.99E+00 6.97E+00

-2.04E+00 5.91E+00 6.08E+00 NA NA NA 3.73E+02 ND ND ND NA MW-52-11 MW-52-18 Q2-2010 005 17.5

-2.6 5/5/2010 16:19 3.01E+02 1.71E+02 1.83E+02 8.08E-02 4.19E-01 5.26E-01 1.60E+00 5.61E+00 6.44E+00 9.40E-01 5.42E+00 6.22E+00 NA NA NA 3.01E+02 ND ND ND NA MW-52-18 MW-52-48 Q2-2010 005 48

-33.1 5/5/2010 16:43 1.60E+02 1.65E+02 1.82E+02 6.40E-01 6.58E-01 6.90E-01

-6.17E-01 6.04E+00 6.70E+00

-1.90E-01 5.13E+00 5.67E+00 NA NA NA ND ND ND ND NA MW-52-48 MW-52-64 Q2-2010 005 64

-49.1 5/5/2010 12:52 7.62E+01 1.61E+02 1.81E+02

-2.23E-01 7.02E-01 9.13E-01

-1.12E+00 5.21E+00 4.96E+00 1.49E+00 4.05E+00 4.98E+00 NA NA NA ND ND ND ND NA MW-52-64 MW-52-122 Q2-2010 005 122

-107.1 5/5/2010 14:57 6.46E+01 1.64E+02 1.84E+02 1.59E-01 4.66E-01 5.60E-01 3.04E-02 5.33E+00 6.01E+00

-3.25E+00 6.25E+00 6.14E+00 NA NA NA ND ND ND ND NA MW-52-122 MW-52-162 Q2-2010 005 161.5

-146.6 5/5/2010 12:39 2.60E+02 1.70E+02 1.83E+02

-7.86E-02 4.15E-01 5.66E-01

-1.54E+00 5.52E+00 5.96E+00 3.03E+00 5.68E+00 7.13E+00 NA NA NA 2.60E+02 ND ND ND NA MW-52-162 MW-52-181 Q2-2010 005 181

-166.1 5/5/2010 12:47 2.18E+02 1.70E+02 1.84E+02 2.80E-01 4.29E-01 4.67E-01

-2.64E-01 5.64E+00 6.37E+00

-2.38E+00 6.40E+00 6.61E+00 NA NA NA 2.18E+02 ND ND ND NA MW-52-181 MW-53-82 Q2-2010 015 75

-4.7 4/15/2010 15:14 4.71E+03 6.56E+02 3.96E+02 4.06E-01 7.37E-01 8.29E-01 4.40E+00 1.27E+01 1.51E+01

-4.95E+00 1.13E+01 1.13E+01 1.39E+00 1.89E+01 2.19E+01 2.54E+03 ND ND ND ND MW-53-82 MW-53-82 Q3-2010 016 75

-4.7 7/30/2010 12:32 2.25E+03 2.66E+02 1.27E+02 3.34E-01 3.83E-01 4.00E-01

-3.03E+00 8.36E+00 8.46E+00

-1.90E+00 8.00E+00 8.03E+00

-1.45E+01 1.77E+01 2.23E+01 2.54E+03 MW-53-82 MW-53-82 Q4-2010 017 75

-4.7 10/27/2010 12:07 2.59E+03 2.79E+02 1.10E+02 8.07E-01 7.90E-01 8.26E-01

-3.74E-02 5.82E+00 6.57E+00 1.14E-01 6.23E+00 7.00E+00 NA NA NA 2.54E+03 MW-53-82 MW-53-82 Q1-2011 018 75

-4.7 3/3/2011 11:53 5.95E+02 3.76E+02 3.73E+02 1.61E+00 1.82E+00 1.91E+00 3.61E+00 6.18E+00 7.60E+00

-1.88E+00 7.02E+00 7.25E+00

-7.63E+00 1.59E+01 1.85E+01 2.54E+03 MW-53-82 MW-53-120 Q2-2010 019 109.8

-39.5 4/15/2010 14:36 4.10E+03 6.14E+02 3.86E+02 3.32E+01 2.69E+00 9.06E-01

-6.92E+00 8.73E+00 8.19E+00 2.24E-01 8.74E+00 9.97E+00 7.53E+00 1.96E+01 2.22E+01 3.92E+03 3.05E+01 ND ND ND MW-53-120 MW-53-120 Q3-2010 020 109.8

-39.5 7/30/2010 14:36 3.81E+03 3.38E+02 1.28E+02 2.97E+01 2.22E+00 4.77E-01 2.09E+00 1.27E+01 1.37E+01

-4.76E-01 8.04E+00 8.95E+00 3.59E+00 1.91E+01 2.21E+01 3.92E+03 3.05E+01 MW-53-120 MW-53-120 Q4-2010 021 109.8

-39.5 10/27/2010 12:48 3.91E+03 3.38E+02 1.11E+02 2.96E+01 2.91E+00 7.02E-01 2.32E+00 5.07E+00 6.00E+00

-9.52E-01 5.46E+00 5.76E+00 NA NA NA 3.92E+03 3.05E+01 MW-53-120 MW-53-120 Q1-2011 022 109.8

-39.5 3/3/2011 12:00 3.84E+03 7.18E+02 3.89E+02 2.95E+01 3.76E+00 1.13E+00 2.30E+00 7.32E+00 8.49E+00

-2.43E+00 8.14E+00 8.13E+00 1.00E+01 1.70E+01 1.87E+01 3.92E+03 3.05E+01 MW-53-120 MW-54-37 Q2-2010 013 36.5

-23.4 5/3/2010 14:09 1.18E+03 2.25E+02 1.38E+02 4.71E+00 1.26E+00 6.67E-01

-3.67E+00 8.43E+00 8.56E+00 1.69E+00 9.49E+00 1.14E+01 3.61E+00 2.07E+01 2.36E+01 1.29E+03 4.53E+00 ND ND ND MW-54-37 MW-54-37 Q3-2010 014 36.5

-23.4 8/4/2010 14:32 1.21E+03 2.10E+02 1.30E+02 4.00E+00 8.07E-01 3.32E-01

-4.96E-01 7.38E+00 8.14E+00

-3.97E+00 9.63E+00 9.58E+00

-3.50E+00 1.50E+01 1.80E+01 1.29E+03 4.53E+00 MW-54-37 MW-54-37 Q4-2010 015 36.5

-23.4 11/23/2010 14:47 1.45E+03 2.27E+02 1.26E+02 4.51E+00 1.42E+00 9.84E-01

-2.09E+00 5.46E+00 5.80E+00

-6.89E-01 6.35E+00 6.93E+00

-2.56E+00 1.81E+01 2.15E+01 1.29E+03 4.53E+00 MW-54-37 MW-54-37 Q1-2011 016 36.5

-23.4 2/1/2011 14:10 1.33E+03 4.86E+02 3.78E+02 4.88E+00 1.77E+00 1.26E+00

-1.42E+00 5.54E+00 5.67E+00 3.12E-01 6.42E+00 7.04E+00

-2.81E+00 1.59E+01 1.82E+01 1.29E+03 4.53E+00 MW-54-37 MW-54-58 Q2-2010 013 57.5

-44.4 5/3/2010 14:23 1.11E+03 2.25E+02 1.42E+02 1.44E+00 8.33E-01 6.81E-01 6.00E-01 1.10E+01 1.30E+01

-4.85E-01 8.46E+00 9.38E+00 6.55E+00 1.99E+01 2.26E+01 9.14E+02 1.79E+00 ND ND ND MW-54-58 MW-54-58 Q3-2010 014 57.5

-44.4 8/4/2010 14:35 7.67E+02 1.79E+02 1.28E+02 1.36E+00 6.88E-01 6.20E-01

-3.95E+00 9.51E+00 9.85E+00 8.15E-01 1.14E+01 1.32E+01

-5.38E-01 1.44E+01 1.70E+01 9.14E+02 1.79E+00 MW-54-58 MW-54-58 Q4-2010 015 57.5

-44.4 11/23/2010 14:55 8.21E+02 1.80E+02 1.23E+02 2.67E+00 1.13E+00 9.76E-01 3.83E+00 6.50E+00 7.88E+00 2.75E+00 6.57E+00 8.00E+00

-3.94E+00 1.86E+01 2.21E+01 9.14E+02 1.79E+00 MW-54-58 MW-54-58 Q1-2011 016 57.5

-44.4 2/1/2011 14:22 9.58E+02 4.56E+02 3.92E+02 1.68E+00 1.34E+00 1.28E+00

-4.20E-02 7.14E+00 7.94E+00

-2.21E+00 6.84E+00 6.82E+00

-4.89E+00 1.66E+01 1.92E+01 9.14E+02 1.79E+00 MW-54-58 MW-54-123 Q2-2010 013 123

-109.9 5/3/2010 15:08 9.16E+02 2.04E+02 1.37E+02 2.25E+00 1.12E+00 8.35E-01

-3.24E+00 8.00E+00 8.03E+00 5.74E-01 9.62E+00 1.09E+01

-6.51E+00 1.94E+01 2.25E+01 8.98E+02 3.86E+00 ND ND ND MW-54-123 MW-54-123 Q3-2010 014 123

-109.9 8/4/2010 14:49 7.83E+02 1.80E+02 1.28E+02 2.98E+00 7.55E-01 4.15E-01 1.53E+00 9.99E+00 1.16E+01

-9.37E-01 8.21E+00 8.72E+00

-5.12E+00 1.64E+01 1.97E+01 8.98E+02 3.86E+00 MW-54-123 MW-54-123 Q4-2010 015 123

-109.9 11/23/2010 15:12 8.12E+02 1.80E+02 1.22E+02 7.65E+00 1.46E+00 9.15E-01 2.19E+00 6.74E+00 7.78E+00

-1.25E+00 6.18E+00 6.62E+00 9.26E+00 1.91E+01 2.15E+01 8.98E+02 3.86E+00 MW-54-123 MW-54-123 Q1-2011 016 123

-109.9 2/1/2011 14:11 1.08E+03 4.68E+02 3.90E+02 2.56E+00 1.39E+00 1.08E+00

-3.56E-01 6.02E+00 6.69E+00

-3.66E-03 5.16E+00 5.75E+00 2.50E+00 1.66E+01 1.87E+01 8.98E+02 3.86E+00 MW-54-123 MW-54-144 Q2-2010 013 144

-130.9 5/3/2010 11:41 1.28E+03 2.40E+02 1.45E+02 1.37E+01 2.04E+00 6.93E-01

-3.08E+00 7.11E+00 7.03E+00

-4.60E+00 8.03E+00 6.97E+00

-6.93E+00 2.11E+01 2.46E+01 1.35E+03 1.14E+01 ND ND ND MW-54-144 MW-54-144 Q3-2010 014 144

-130.9 8/4/2010 11:44 1.44E+03 2.28E+02 1.33E+02 1.17E+01 1.42E+00 4.70E-01 8.96E+00 1.13E+01 1.44E+01 1.72E+00 8.79E+00 1.06E+01 1.78E+00 1.89E+01 2.21E+01 1.35E+03 1.14E+01 MW-54-144 MW-54-144 Q4-2010 015 144

-130.9 11/23/2010 12:30 1.34E+03 2.15E+02 1.21E+02 1.08E+01 1.36E+00 5.83E-01 1.02E+00 7.82E+00 8.59E+00

-3.87E+00 6.48E+00 5.93E+00 2.30E+00 1.91E+01 2.21E+01 1.35E+03 1.14E+01 MW-54-144 MW-54-144 Q1-2011 016 144

-130.9 2/1/2011 12:34 1.35E+03 4.96E+02 3.87E+02 9.31E+00 2.24E+00 1.06E+00

-9.04E-01 6.14E+00 6.70E+00

-6.36E-01 6.20E+00 6.74E+00

-4.27E+00 1.58E+01 1.82E+01 1.35E+03 1.14E+01 MW-54-144 MW-54-173 Q2-2010 013 172.5

-159.4 5/3/2010 11:47 2.03E+03 2.84E+02 1.42E+02 6.28E+00 1.42E+00 5.94E-01

-3.87E-01 8.87E+00 9.74E+00 2.77E+00 7.82E+00 9.75E+00

-1.68E+00 2.03E+01 2.33E+01 1.68E+03 5.68E+00 ND ND ND MW-54-173 MW-54-173 Q3-2010 014 172.5

-159.4 8/4/2010 12:09 1.53E+03 2.31E+02 1.30E+02 5.97E+00 1.02E+00 3.24E-01

-7.48E+00 8.07E+00 7.10E+00 4.86E-01 9.46E+00 1.08E+01

-1.31E+00 1.68E+01 1.99E+01 1.68E+03 5.68E+00 MW-54-173 MW-54-173 Q4-2010 015 172.5

-159.4 11/23/2010 12:25 1.51E+03 2.28E+02 1.24E+02 4.65E+00 1.28E+00 8.17E-01

-1.84E+00 7.05E+00 7.31E+00

-1.82E+00 6.23E+00 6.51E+00 2.22E+00 1.84E+01 2.14E+01 1.68E+03 5.68E+00 MW-54-173 MW-54-173 Q1-2011 016 172.5

-159.4 2/1/2011 12:29 1.66E+03 5.26E+02 3.81E+02 5.81E+00 1.88E+00 1.10E+00

-2.87E-01 8.00E+00 8.79E+00 1.01E+00 1.06E+01 1.20E+01

-5.49E+00 1.77E+01 2.05E+01 1.68E+03 5.68E+00 MW-54-173 MW-54-190 Q2-2010 013 190

-176.9 5/3/2010 12:01 1.71E+03 2.67E+02 1.44E+02 2.22E+01 2.61E+00 6.32E-01 3.80E+00 1.05E+01 1.25E+01

-3.30E+00 1.11E+01 1.14E+01

-6.89E+00 2.24E+01 2.60E+01 1.78E+03 1.85E+01 ND ND ND MW-54-190 MW-54-190 Q3-2010 014 190

-176.9 8/4/2010 12:34 1.60E+03 2.33E+02 1.28E+02 1.57E+01 1.51E+00 2.87E-01

-1.62E+00 8.25E+00 8.88E+00

-1.20E+00 8.80E+00 9.41E+00

-3.22E+00 1.84E+01 2.21E+01 1.78E+03 1.85E+01 MW-54-190 MW-54-190 Q4-2010 015 190

-176.9 11/23/2010 12:22 1.93E+03 2.55E+02 1.27E+02 1.92E+01 1.89E+00 7.12E-01

-9.64E-01 6.04E+00 6.61E+00

-2.29E+00 6.71E+00 6.79E+00

-3.18E-01 1.81E+01 2.14E+01 1.78E+03 1.85E+01 MW-54-190 MW-54-190 Q1-2011 016 190

-176.9 2/1/2011 12:25 1.89E+03 5.56E+02 3.90E+02 1.68E+01 3.36E+00 1.28E+00 4.59E-01 6.34E+00 7.14E+00

-3.55E+00 5.96E+00 5.21E+00 1.71E+00 1.67E+01 1.89E+01 1.78E+03 1.85E+01 MW-54-190 MW-55-24 Q2-2010 014 16 2.3 4/21/2010 14:08 1.62E+03 4.65E+02 3.90E+02 1.94E+01 2.09E+00 8.38E-01

-1.91E+00 7.13E+00 7.46E+00 6.66E-01 9.22E+00 1.03E+01

-7.52E-01 1.79E+01 2.07E+01 1.31E+03 1.24E+01 ND ND ND MW-55-24 MW-55-24 Q3-2010 015 16 2.3 8/6/2010 13:11 1.21E+03 2.12E+02 1.30E+02 8.64E+00 1.22E+00 4.51E-01 1.13E+00 8.94E+00 1.04E+01 8.02E-01 8.22E+00 9.59E+00 1.17E+01 1.64E+01 1.81E+01 1.31E+03 1.24E+01 MW-55-24 MW-55-24 Q4-2010 016 16 2.3 11/1/2010 14:10 1.39E+03 2.09E+02 1.65E+02 1.08E+01 1.98E+00 9.92E-01

-2.29E-01 8.10E+00 9.04E+00

-4.71E+00 7.93E+00 6.54E+00 7.56E+00 1.88E+01 2.12E+01 1.31E+03 1.24E+01 MW-55-24 MW-55-24 Q1-2011 017 16 2.3 2/3/2011 14:13 1.02E+03 4.48E+02 4.20E+02 1.09E+01 2.82E+00 1.96E+00

-3.57E-01 4.92E+00 5.43E+00 4.75E+00 8.74E+00 7.44E+00

-5.31E+00 1.81E+01 2.14E+01 1.31E+03 1.24E+01 MW-55-24 MW-55-35 Q2-2010 013 32

-13.8 4/21/2010 14:31 2.01E+03 4.92E+02 3.90E+02 2.63E+01 2.44E+00 7.84E-01

-4.26E+00 8.04E+00 7.79E+00 2.77E+00 7.27E+00 9.17E+00

-4.98E-01 1.77E+01 2.06E+01 1.79E+03 1.84E+01 ND ND ND MW-55-35 MW-55-35 Q3-2010 014 32

-13.8 8/6/2010 13:15 1.89E+03 2.46E+02 1.25E+02 1.66E+01 1.65E+00 3.57E-01

-4.27E-01 8.60E+00 9.69E+00 4.31E+00 9.66E+00 1.22E+01 9.65E+00 1.62E+01 1.81E+01 1.79E+03 1.84E+01 MW-55-35 MW-55-35 Q4-2010 015 32

-13.8 11/1/2010 14:26 1.57E+03 2.12E+02 1.62E+02 1.13E+01 1.97E+00 9.17E-01

-2.41E+00 8.88E+00 9.46E+00 5.36E-01 8.18E+00 9.32E+00 6.22E+00 1.79E+01 2.03E+01 1.79E+03 1.84E+01 MW-55-35 MW-55-35 Q1-2011 016 32

-13.8 2/3/2011 14:16 1.70E+03 4.84E+02 3.86E+02 1.93E+01 3.42E+00 2.05E+00 8.32E-01 5.82E+00 6.45E+00 1.03E+00 6.24E+00 7.03E+00

-2.16E+00 1.86E+01 2.17E+01 1.79E+03 1.84E+01 MW-55-35 MW-55-54 Q2-2010 014 47

-28.8 4/21/2010 13:56 1.13E+04 9.27E+02 3.88E+02 2.32E+01 2.31E+00 8.38E-01

-5.23E+00 1.21E+01 1.49E+01

-4.30E+00 1.11E+01 1.10E+01

-3.67E+00 1.79E+01 2.09E+01 9.55E+03 2.02E+01 ND ND ND MW-55-54 MW-55-54 Q3-2010 015 47

-28.8 8/6/2010 12:50 9.74E+03 5.22E+02 1.28E+02 1.93E+01 1.88E+00 3.96E-01

-1.51E+00 7.77E+00 8.26E+00 1.82E+00 7.26E+00 8.71E+00

-1.77E-01 1.41E+01 1.65E+01 9.55E+03 2.02E+01 MW-55-54 MW-55-54 Q4-2010 016 47

-28.8 11/1/2010 13:36 8.68E+03 3.95E+02 1.57E+02 1.93E+01 1.72E+00 6.48E-01

-3.03E+00 7.29E+00 7.24E+00 9.59E-01 7.50E+00 8.63E+00 1.12E-01 1.77E+01 2.04E+01 9.55E+03 2.02E+01 MW-55-54 MW-55-54 Q1-2011 017 47

-28.8 2/3/2011 14:17 8.46E+03 8.58E+02 3.89E+02 1.91E+01 3.78E+00 1.95E+00 3.62E+00 5.80E+00 7.00E+00

-6.59E-01 7.44E+00 7.93E+00

-8.13E+00 1.78E+01 2.14E+01 9.55E+03 2.02E+01 MW-55-54 MW-56-53 Q2-2010 008 52 18.3 4/20/2010 15:23 2.58E+02 1.65E+02 1.75E+02

-1.49E-01 5.35E-01 7.58E-01 3.61E+00 7.63E+00 9.44E+00

-1.55E+00 8.91E+00 9.68E+00 NA NA NA 3.61E+02 ND ND ND NA MW-56-53 MW-56-53 Q4-2010 009 52 18.3 11/15/2010 12:48 4.64E+02 1.88E+02 3.82E+02 1.27E+00 8.67E-01 1.86E+00 3.71E+00 4.39E+00 1.06E+01

-1.74E+00 4.89E+00 9.96E+00 NA NA NA 3.61E+02 MW-56-53 MW-56-83 Q2-2010 010 74

-3.7 4/20/2010 14:51 1.93E+03 2.96E+02 1.48E+02 1.99E+00 1.05E+00 8.74E-01 2.04E+00 8.03E+00 9.48E+00

-1.05E+00 8.71E+00 9.04E+00 NA NA NA 2.34E+03 1.99E+00 ND ND NA MW-56-83 MW-56-83 Q4-2010 011 74

-3.7 11/15/2010 14:37 2.74E+03 2.63E+02 3.84E+02 1.02E+00 7.08E-01 1.50E+00

-2.51E+00 3.87E+00 7.83E+00

-2.67E+00 3.90E+00 7.34E+00 NA NA NA 2.34E+03 1.99E+00 MW-56-83 MW-57-11 Q2-2010 006 10 5

5/4/2010 12:36 3.27E+03 3.48E+02 1.72E+02 2.46E+01 3.00E+00 8.46E-01 8.07E-01 6.20E+00 6.51E+00 1.85E-01 5.09E+00 5.67E+00

-1.79E+01 2.21E+01 2.56E+01 3.27E+03 2.46E+01 ND ND ND MW-57-11 MW-57-20 Q2-2010 006 19

-4 5/4/2010 12:45 8.07E+02 2.04E+02 1.61E+02 1.12E+00 9.05E-01 8.77E-01

-2.11E+00 7.95E+00 8.24E+00

-2.23E-01 7.54E+00 8.56E+00

-6.07E+00 2.19E+01 2.51E+01 8.07E+02 1.12E+00 ND ND ND MW-57-20 MW-57-45 Q2-2010 007 40

-25 5/4/2010 13:24 8.79E+02 2.19E+02 1.72E+02 1.30E+00 9.43E-01 8.65E-01 6.16E-02 5.31E+00 5.86E+00

-2.99E-01 4.77E+00 5.16E+00 7.57E-01 2.26E+01 2.58E+01 8.79E+02 1.30E+00 ND ND ND MW-57-45 MW-58-26 Q2-2010 010 20

-5.4 4/30/2010 14:12 5.75E+02 1.80E+02 1.82E+02 2.92E-01 5.47E-01 6.20E-01 4.25E-01 5.59E+00 6.27E+00 9.40E-01 5.75E+00 6.68E+00 NA NA NA 4.71E+02 ND ND ND NA MW-58-26 MW-58-26 Q4-2010 011 20

-5.4 11/11/2010 15:12 3.66E+02 1.73E+02 1.44E+02 4.13E-01 7.89E-01 8.92E-01 1.98E+00 3.81E+00 4.51E+00 2.98E+00 3.75E+00 4.70E+00 NA NA NA 4.71E+02 MW-58-26

TABLE 3 FIRST QUARTER 2011 GROUNDWATER ANALYTICAL RESULTS AND AVERAGES INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q12011 FINAL Table 3 - First Quarter 2011 Groundwater Analytical Results and Averages.xlsx; Q12011 Table 3 Page 4 of 5 See Page 5 for Notes TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Date Time Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Average Average Average Average Average ANALYSIS RESULTS5 YEARLY ROLLING AVERAGES4,6 Well ID1 TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

SAMPLE COLLECTION Well ID1 SAMPLING QUARTER2,8 SAMPLE ID SAMPLE ZONE CENTER, Depth Ft Below Top of Casing3 SAMPLE ZONE CENTER Elevation Ft msl3 MW-58-65 Q2-2010 010 54

-39.4 4/30/2010 13:51 3.59E+02 1.64E+02 1.72E+02 7.38E-02 5.17E-01 6.40E-01 1.50E+00 8.09E+00 9.07E+00 3.34E-01 5.75E+00 6.60E+00 NA NA NA 4.20E+02 ND ND ND NA MW-58-65 MW-58-65 Q4-2010 011 54

-39.4 11/11/2010 13:53 4.81E+02 1.88E+02 1.45E+02 7.15E-01 7.72E-01 8.31E-01 2.61E-01 3.71E+00 4.18E+00 3.74E+00 4.41E+00 5.49E+00 NA NA NA 4.20E+02 MW-58-65 MW-60-35 Q2-2010 Mid 013 34.9

-22.4 5/10/2010 15:58 2.85E+02 1.46E+02 1.35E+02 2.89E-02 5.05E-01 6.56E-01

-1.78E+00 7.56E+00 8.03E+00

-1.43E+00 9.12E+00 9.76E+00 4.12E-01 2.24E+01 2.56E+01 2.60E+02 ND ND ND ND MW-60-35 MW-60-35 Q3-2010 014 34.9

-22.4 8/16/2010 14:43 2.35E+02 1.42E+02 1.41E+02 3.19E-01 6.48E-01 7.39E-01 3.02E-01 5.73E+00 6.47E+00

-1.36E+00 6.23E+00 6.68E+00

-4.52E+00 2.14E+01 2.52E+01 2.60E+02 MW-60-35 MW-60-35 Q4-2010 015 34.9

-22.4 11/18/2010 13:25 2.44E+02 1.85E+02 4.00E+02

-5.33E-01 6.54E-01 1.73E+00 9.47E-01 4.80E+00 1.08E+01

-4.28E-01 4.56E+00 9.75E+00

-1.11E+01 8.47E+00 1.92E+01 2.60E+02 MW-60-35 MW-60-35 Q1-2011 016 34.9

-22.4 2/11/2011 12:17 3.20E+02 3.72E+02 3.88E+02 9.73E-01 1.63E+00 1.78E+00 2.69E+00 6.24E+00 7.46E+00 1.22E-01 3.76E+00 4.24E+00

-1.61E+00 1.62E+01 1.84E+01 2.60E+02 MW-60-35 MW-60-53 Q2-2010 Mid 013 53.4

-40.9 5/10/2010 16:31 3.45E+02 1.58E+02 1.41E+02

-9.87E-02 4.95E-01 6.82E-01 8.10E-01 7.58E+00 8.81E+00

-2.08E+00 8.49E+00 9.02E+00

-5.02E+00 2.07E+01 2.40E+01 3.02E+02 ND ND ND ND MW-60-53 MW-60-53 Q3-2010 014 53.4

-40.9 8/16/2010 15:34 2.58E+02 1.50E+02 1.60E+02

-2.84E-02 4.87E-01 6.04E-01

-8.42E+00 7.92E+00 7.70E+00

-2.64E+00 6.03E+00 6.02E+00

-8.48E+00 1.98E+01 2.37E+01 3.02E+02 MW-60-53 MW-60-53 Q4-2010 015 53.4

-40.9 11/18/2010 12:22 2.49E+02 1.83E+02 3.96E+02

-4.58E-01 4.20E-01 1.32E+00 4.54E-01 4.11E+00 9.15E+00 2.23E+00 3.57E+00 8.75E+00 1.10E+01 8.93E+00 1.96E+01 3.02E+02 MW-60-53 MW-60-53 Q1-2011 016 53.4

-40.9 2/11/2011 10:57 3.19E+02 3.70E+02 3.87E+02 7.44E-01 1.52E+00 1.70E+00

-2.03E+00 5.88E+00 6.16E+00 1.39E+00 7.96E+00 8.33E+00

-1.39E+00 1.50E+01 1.72E+01 3.02E+02 MW-60-53 MW-60-72 Q2-2010 Mid 013 72.4

-59.9 5/10/2010 12:11 3.01E+02 1.52E+02 1.40E+02 1.57E-02 5.49E-01 7.10E-01

-3.66E+00 1.29E+01 1.58E+01

-7.77E+00 1.16E+01 1.10E+01

-6.97E+00 2.07E+01 2.41E+01 3.01E+02 ND ND ND ND MW-60-72 MW-60-72 Q3-2010 014 72.4

-59.9 8/17/2010 11:59 2.33E+01 1.23E+02 1.44E+02 1.97E-01 5.90E-01 6.91E-01

-5.91E-01 5.40E+00 6.06E+00

-1.59E+00 6.08E+00 6.57E+00 1.19E+00 2.04E+01 2.37E+01 3.01E+02 MW-60-72 MW-60-72 Q4-2010 015 72.4

-59.9 11/16/2010 13:17

-2.51E+01 1.68E+02 3.98E+02 5.83E-02 5.15E-01 1.33E+00 2.12E+00 5.34E+00 1.26E+01

-3.92E+00 5.67E+00 1.09E+01

-1.14E+01 8.32E+00 1.89E+01 3.01E+02 MW-60-72 MW-60-72 Q1-2011 016 72.4

-59.9 2/10/2011 12:54 3.64E+02 3.76E+02 3.84E+02 2.41E-01 1.45E+00 1.70E+00

-5.10E-02 9.12E+00 1.01E+01 2.27E+00 8.84E+00 1.07E+01 2.12E+00 1.54E+01 1.75E+01 3.01E+02 MW-60-72 MW-60-135 Q2-2010 Mid 013 134.9

-122.4 5/10/2010 12:21 4.18E+02 1.80E+02 1.65E+02

-9.46E-02 6.05E-01 8.55E-01 1.55E+00 7.70E+00 9.03E+00 6.68E-03 8.37E+00 9.36E+00

-8.62E+00 2.04E+01 2.38E+01 3.34E+02 ND ND ND ND MW-60-135 MW-60-135 Q3-2010 014 134.9

-122.4 8/17/2010 12:09 1.87E+02 1.39E+02 1.43E+02

-2.74E-01 5.38E-01 7.27E-01

-3.46E+00 8.41E+00 9.07E+00

-1.52E+00 6.30E+00 6.70E+00 8.77E-01 2.11E+01 2.45E+01 3.34E+02 MW-60-135 MW-60-135 Q4-2010 015 134.9

-122.4 11/16/2010 13:22 2.41E+02 1.82E+02 3.96E+02

-4.96E-02 7.62E-01 1.88E+00 9.16E-01 5.37E+00 1.20E+01 1.02E+00 4.53E+00 1.03E+01 8.67E-01 8.52E+00 1.90E+01 3.34E+02 MW-60-135 MW-60-135 Q1-2011 016 134.9

-122.4 2/10/2011 13:04 3.98E+02 3.78E+02 3.83E+02 1.14E+00 1.82E+00 1.98E+00 1.72E+00 6.72E+00 7.79E+00 2.24E-01 7.44E+00 8.25E+00

-3.56E+00 1.52E+01 1.76E+01 3.34E+02 MW-60-135 MW-60-154 Q2-2010 Mid 013 154.4

-141.9 5/10/2010 12:32 4.38E+02 1.85E+02 1.69E+02 3.52E-01 6.25E-01 7.01E-01

-1.33E+00 8.40E+00 9.22E+00 1.61E-01 7.65E+00 8.61E+00

-5.15E+00 2.13E+01 2.46E+01 4.36E+02 ND ND ND ND MW-60-154 MW-60-154 Q3-2010 014 154.4

-141.9 8/17/2010 12:18 2.93E+02 1.50E+02 1.45E+02

-2.33E-01 5.00E-01 6.61E-01

-4.41E-01 6.04E+00 6.67E+00 1.95E+00 6.78E+00 8.02E+00

-1.16E+00 2.13E+01 2.48E+01 4.36E+02 MW-60-154 MW-60-154 Q4-2010 015 154.4

-141.9 11/16/2010 13:40 4.68E+02 1.94E+02 3.98E+02 3.29E-01 8.30E-01 1.94E+00

-5.28E+00 4.02E+00 7.52E+00

-2.29E-01 5.09E+00 1.11E+01

-4.54E+00 7.93E+00 1.78E+01 4.36E+02 MW-60-154 MW-60-154 Q1-2011 016 154.4

-141.9 2/10/2011 12:53 5.44E+02 4.02E+02 3.87E+02 2.32E-02 8.50E-01 1.07E+00

-4.12E+00 9.26E+00 8.97E+00 9.91E-01 7.86E+00 9.12E+00 4.61E+00 1.52E+01 1.71E+01 4.36E+02 MW-60-154 MW-60-176 Q2-2010 Mid 013 175.9

-163.4 5/10/2010 13:29 9.93E+02 2.24E+02 1.63E+02

-3.09E-01 4.52E-01 6.99E-01

-5.66E-01 8.13E+00 9.07E+00 9.92E-01 8.25E+00 9.76E+00 0.00E+00 2.04E+01 2.34E+01 9.40E+02 ND ND ND ND MW-60-176 MW-60-176 Q3-2010 014 175.9

-163.4 8/17/2010 12:51 8.13E+02 1.91E+02 1.44E+02

-6.59E-01 6.48E-01 9.01E-01 1.23E-01 6.43E+00 7.32E+00 1.35E+00 5.80E+00 6.97E+00 0.00E+00 2.13E+01 2.48E+01 9.40E+02 MW-60-176 MW-60-176 Q4-2010 015 175.9

-163.4 11/16/2010 14:06 8.33E+02 2.10E+02 3.97E+02 9.07E-01 9.42E-01 2.10E+00

-1.97E+00 4.38E+00 9.04E+00 2.85E+00 4.70E+00 1.12E+01

-6.40E+00 7.91E+00 1.78E+01 9.40E+02 MW-60-176 MW-60-176 Q1-2011 016 175.9

-163.4 2/10/2011 10:31 1.12E+03 4.68E+02 3.85E+02 2.58E-01 1.49E+00 1.74E+00 4.88E+00 1.13E+01 6.69E+00

-1.75E+00 6.70E+00 6.74E+00 7.24E+00 1.62E+01 1.79E+01 9.40E+02 MW-60-176 MW-62-18 Q2-2010 013 13.5 1.2 4/13/2010 15:17 2.04E+02 1.34E+02 1.42E+02 2.74E-02 6.16E-01 7.97E-01

-1.48E+00 4.05E+00 4.37E+00 6.69E-01 5.38E+00 4.96E+00 NA NA NA 2.04E+02 ND ND ND NA MW-62-18 MW-62-18 Q3-2010 014 13.5 1.2 8/3/2010 13:00 1.14E+02 1.32E+02 1.44E+02 6.60E-01 6.55E-01 6.80E-01 3.08E+00 8.40E+00 1.03E+01 5.07E+00 1.02E+01 1.32E+01 NA NA NA 2.04E+02 MW-62-18 MW-62-18 Q4-2010 015 13.5 1.2 11/9/2010 11:57 7.48E+01 1.71E+02 3.86E+02

-1.05E-02 6.10E-01 1.54E+00 2.87E+00 4.59E+00 1.07E+01

-6.86E-01 4.79E+00 1.01E+01 NA NA NA 2.04E+02 MW-62-18 MW-62-18 Q1-2011 016 13.5 1.2 2/24/2011 12:49 1.81E+02 3.60E+02 4.00E+02

-3.86E-01 1.71E+00 2.13E+00 2.12E-01 4.74E+00 5.18E+00 3.58E+00 5.46E+00 6.78E+00 NA NA NA 2.04E+02 MW-62-18 MW-62-37 Q2-2010 013 34.5

-19.8 4/13/2010 15:22 2.59E+02 2.07E+02 2.26E+02 5.46E-01 7.33E-01 7.81E-01

-2.42E+00 3.86E+00 4.07E+00 1.34E+00 4.04E+00 4.80E+00 NA NA NA 2.25E+02 ND ND ND NA MW-62-37 MW-62-37 Q3-2010 014 34.5

-19.8 8/3/2010 12:52 1.91E+02 1.43E+02 1.47E+02

-1.52E-02 5.47E-01 6.85E-01

-9.69E-01 8.78E+00 9.70E+00

-5.33E+00 9.12E+00 7.92E+00 NA NA NA 2.25E+02 MW-62-37 MW-62-37 Q4-2010 015 34.5

-19.8 11/9/2010 11:56 6.09E+01 1.70E+02 3.85E+02 7.62E-01 6.69E-01 1.47E+00

-8.46E-02 4.49E+00 9.91E+00 3.83E+00 4.28E+00 1.07E+01 NA NA NA 2.25E+02 MW-62-37 MW-62-37 Q1-2011 016 34.5

-19.8 2/24/2011 12:52 3.05E+02 3.76E+02 4.00E+02 5.14E-01 1.84E+00 2.13E+00 1.07E+00 6.06E+00 6.86E+00

-2.84E+00 6.38E+00 6.28E+00 NA NA NA 2.25E+02 MW-62-37 MW-62-53 Q2-2010 012 53.1

-40.3 4/13/2010 15:27 3.25E+02 1.44E+02 1.47E+02

-1.84E-02 5.67E-01 7.67E-01 1.33E+00 3.35E+00 3.87E+00

-1.52E+00 5.03E+00 4.08E+00 NA NA NA 2.42E+02 ND ND ND NA MW-62-53 MW-62-53 Q3-2010 013 53.1

-40.3 8/3/2010 12:20 1.59E+02 1.40E+02 1.47E+02 3.13E-01 5.61E-01 6.32E-01 2.99E+00 1.11E+01 1.33E+01 2.39E-01 7.18E+00 8.24E+00 NA NA NA 2.42E+02 MW-62-53 MW-62-53 Q4-2010 014 53.1

-40.3 11/9/2010 12:49 2.05E+02 1.77E+02 3.88E+02 8.32E-02 6.79E-01 1.59E+00

-4.23E+00 4.83E+00 9.52E+00

-2.68E+00 5.26E+00 1.04E+01 NA NA NA 2.42E+02 MW-62-53 MW-62-53 Q1-2011 015 53.1

-40.3 2/24/2011 12:57 3.08E+02 3.78E+02 4.03E+02 8.98E-01 1.94E+00 2.18E+00

-2.62E-01 4.72E+00 5.23E+00

-1.84E+00 5.58E+00 5.81E+00 NA NA NA 2.42E+02 MW-62-53 MW-62-71 Q2-2010 013 71.1

-58.3 4/13/2010 13:45 3.77E+02 2.16E+02 2.30E+02

-2.24E-01 5.64E-01 8.12E-01

-6.51E-01 4.44E+00 4.86E+00

-3.24E+00 5.89E+00 4.62E+00 NA NA NA 4.14E+02 ND ND ND NA MW-62-71 MW-62-71 Q3-2010 014 71.1

-58.3 8/3/2010 11:30 3.25E+02 1.70E+02 1.77E+02 2.44E-01 3.75E-01 4.12E-01

-2.03E+00 8.37E+00 8.99E+00 1.86E+00 9.87E+00 1.16E+01 NA NA NA 4.14E+02 MW-62-71 MW-62-71 Q4-2010 015 71.1

-58.3 11/9/2010 11:02 4.17E+02 1.83E+02 3.82E+02

-6.74E-02 6.02E-01 1.52E+00

-6.58E-01 3.90E+00 8.41E+00

-4.59E+00 5.63E+00 1.09E+01 NA NA NA 4.14E+02 MW-62-71 MW-62-71 Q1-2011 016 71.1

-58.3 2/24/2011 12:40 5.38E+02 4.06E+02 4.03E+02 1.28E-01 1.22E+00 1.48E+00 4.10E+00 1.18E+01 6.67E+00

-2.36E-01 5.00E+00 5.47E+00 NA NA NA 4.14E+02 MW-62-71 MW-62-92 Q2-2010 013 91.6

-78.8 4/13/2010 13:38 5.96E+02 1.55E+02 1.44E+02 1.77E-01 6.88E-01 8.34E-01 1.16E+00 3.72E+00 4.24E+00 7.23E-03 3.75E+00 4.13E+00 NA NA NA 4.76E+02 ND ND ND NA MW-62-92 MW-62-92 Q3-2010 014 91.6

-78.8 8/3/2010 11:32 3.18E+02 1.68E+02 1.76E+02 4.11E-01 5.37E-01 5.80E-01

-3.42E+00 8.13E+00 8.38E+00

-4.99E-01 7.59E+00 8.36E+00 NA NA NA 4.76E+02 MW-62-92 MW-62-92 Q4-2010 015 91.6

-78.8 11/9/2010 11:15 4.82E+02 1.88E+02 3.86E+02

-9.75E-01 7.72E-01 1.95E+00

-2.96E+00 5.42E+00 1.17E+01 1.77E+00 4.84E+00 1.12E+01 NA NA NA 4.76E+02 MW-62-92 MW-62-92 Q1-2011 016 91.6

-78.8 2/24/2011 12:39 5.09E+02 4.00E+02 4.02E+02 9.56E-01 1.85E+00 2.06E+00 1.68E+00 5.38E+00 6.27E+00

-1.45E+00 5.68E+00 5.86E+00 NA NA NA 4.76E+02 MW-62-92 MW-62-138 Q2-2010 013 138.1

-125.3 4/13/2010 18:02 6.54E+02 1.59E+02 1.46E+02 1.28E+00 7.41E-01 6.91E-01

-7.33E-01 6.39E+00 5.98E+00

-2.36E+00 6.71E+00 5.83E+00 NA NA NA 5.87E+02 1.63E+00 ND ND NA MW-62-138 MW-62-138 Q3-2010 014 138.1

-125.3 8/3/2010 14:09 5.91E+02 1.82E+02 1.76E+02 1.47E+00 7.40E-01 6.56E-01 3.83E+00 7.26E+00 8.95E+00

-1.73E+00 7.35E+00 7.39E+00 NA NA NA 5.87E+02 1.63E+00 MW-62-138 MW-62-138 Q4-2010 015 138.1

-125.3 11/9/2010 14:31 3.31E+02 2.07E+02 4.46E+02

-1.05E-01 6.18E-01 1.57E+00

-1.42E+00 4.04E+00 8.57E+00 2.51E+00 4.68E+00 1.11E+01 NA NA NA 5.87E+02 1.63E+00 MW-62-138 MW-62-138 Q1-2011 016 138.1

-125.3 2/24/2011 14:54 5.17E+02 4.00E+02 4.01E+02 2.15E+00 1.77E+00 1.75E+00

-1.67E+00 4.72E+00 4.94E+00 1.88E+00 7.04E+00 8.19E+00 NA NA NA 5.87E+02 1.63E+00 MW-62-138 MW-62-182 Q2-2010 013 182.1

-169.3 4/13/2010 18:18 4.77E+02 1.52E+02 1.46E+02 2.86E-01 6.55E-01 7.61E-01 9.81E-01 3.93E+00 4.57E+00 3.69E-01 4.09E+00 4.65E+00 NA NA NA 4.10E+02 ND ND ND NA MW-62-182 MW-62-182 Q3-2010 014 182.1

-169.3 8/3/2010 14:02 2.78E+02 1.65E+02 1.75E+02 2.87E-01 7.05E-01 8.30E-01

-5.53E+00 1.24E+01 1.51E+01

-9.25E-01 8.00E+00 8.64E+00 NA NA NA 4.10E+02 MW-62-182 MW-62-182 Q4-2010 015 182.1

-169.3 11/9/2010 14:43 4.76E+02 1.88E+02 3.87E+02 1.02E+00 6.77E-01 1.46E+00

-2.35E+00 4.16E+00 8.56E+00 1.99E+00 5.26E+00 1.21E+01 NA NA NA 4.10E+02 MW-62-182 MW-62-182 Q1-2011 016 182.1

-169.3 2/24/2011 15:07 3.55E+02 3.84E+02 4.03E+02

-1.46E-01 1.45E+00 1.94E+00

-1.95E+00 6.24E+00 6.60E+00 5.86E-01 6.60E+00 7.33E+00 NA NA NA 4.10E+02 MW-62-182 MW-63-18 Q2-2010 013 14.9 0.7 4/26/2010 13:22 3.16E+02 1.55E+02 1.47E+02

-7.37E-02 6.62E-01 8.66E-01 3.73E-01 5.22E+00 5.91E+00 3.24E+00 6.03E+00 7.50E+00 NA NA NA 3.34E+02 ND ND ND NA MW-63-18 MW-63-18 Q3-2010 014 14.9 0.7 8/10/2010 12:08 1.62E+02 1.58E+02 1.73E+02

-1.55E-02 3.48E-01 4.72E-01

-6.04E-01 7.20E+00 8.11E+00

-2.17E+00 6.42E+00 6.45E+00 NA NA NA 3.34E+02 MW-63-18 MW-63-18 Q4-2010 015 14.9 0.7 11/2/2010 12:22 1.97E+02 1.18E+02 1.13E+02 1.31E-01 6.87E-01 8.18E-01 1.81E+00 5.46E+00 6.40E+00 3.45E+00 6.55E+00 8.07E+00 NA NA NA 3.34E+02 MW-63-18 MW-63-18 Q1-2011 016 14.9 0.7 3/2/2011 11:10 4.90E+02 3.58E+02 3.55E+02

-4.34E-01 1.50E+00 2.03E+00 1.82E+00 6.78E+00 7.90E+00 2.40E+00 7.38E+00 8.82E+00 NA NA NA 3.34E+02 MW-63-18 MW-63-34 Q2-2010 013 31.5

-17.3 4/26/2010 13:21 2.89E+02 1.53E+02 1.47E+02

-3.04E-01 7.18E-01 9.93E-01

-5.64E-01 5.55E+00 5.88E+00

-1.09E+00 5.19E+00 5.37E+00 NA NA NA 2.79E+02 ND ND ND NA MW-63-34 MW-63-34 Q3-2010 014 31.5

-17.3 8/10/2010 11:44 1.89E+02 1.64E+02 1.78E+02 2.21E-01 3.59E-01 3.95E-01 2.60E+00 9.29E+00 1.06E+01 3.10E+00 7.21E+00 9.27E+00 NA NA NA 2.79E+02 MW-63-34 MW-63-34 Q4-2010 015 31.5

-17.3 11/2/2010 13:04 3.41E+02 1.35E+02 1.14E+02 3.11E-01 5.72E-01 6.45E-01 1.16E-01 5.66E+00 6.29E+00

-2.31E+00 6.33E+00 6.51E+00 NA NA NA 2.79E+02 MW-63-34 MW-63-34 Q1-2011 016 31.5

-17.3 3/2/2011 10:50 2.98E+02 2.86E+02 2.62E+02

-4.29E-01 1.57E+00 2.11E+00 7.43E-02 7.96E+00 8.82E+00

-2.10E+00 8.42E+00 8.59E+00 NA NA NA 2.79E+02 MW-63-34 MW-63-50 Q2-2010 013 49.5

-37.2 4/26/2010 12:06 4.13E+02 1.62E+02 1.45E+02 2.38E-01 5.82E-01 6.82E-01

-5.57E+00 1.01E+01 1.12E+01

-4.30E+00 6.74E+00 6.45E+00 NA NA NA 3.62E+02 ND ND ND NA MW-63-50 MW-63-50 Q3-2010 014 49.5

-37.2 8/10/2010 14:32 2.72E+02 1.65E+02 1.75E+02

-2.47E-02 5.47E-01 6.90E-01

-1.32E+00 7.10E+00 7.82E+00 7.73E-01 7.74E+00 8.96E+00 NA NA NA 3.62E+02 MW-63-50 MW-63-50 Q4-2010 015 49.5

-37.2 11/2/2010 15:07 3.29E+02 1.31E+02 1.12E+02 2.27E-01 6.23E-01 7.23E-01

-2.98E-02 7.72E+00 8.42E+00 2.76E+00 8.00E+00 9.78E+00 NA NA NA 3.62E+02 MW-63-50 MW-63-50 Q1-2011 016 49.5

-37.2 3/2/2011 14:21 4.35E+02 3.40E+02 3.44E+02 1.73E-01 1.62E+00 2.03E+00 1.13E+00 6.50E+00 7.48E+00 3.64E+00 7.02E+00 8.70E+00 NA NA NA 3.62E+02 MW-63-50 MW-63-93 Q2-2010 014 93

-80.7 4/26/2010 12:42 3.03E+02 1.55E+02 1.47E+02

-2.90E-02 5.61E-01 7.42E-01

-6.91E-01 5.55E+00 6.23E+00

-3.69E+00 5.52E+00 5.35E+00 NA NA NA 2.46E+02 ND ND ND NA MW-63-93 MW-63-93 Q3-2010 015 93

-80.7 8/10/2010 15:10 1.95E+02 1.61E+02 1.74E+02

-1.91E-01 4.38E-01 6.16E-01 1.24E+00 6.64E+00 7.70E+00 2.61E-01 7.58E+00 8.46E+00 NA NA NA 2.46E+02 MW-63-93 MW-63-93 Q4-2010 016 93

-80.7 11/2/2010 15:08 2.39E+02 1.21E+02 1.11E+02 3.29E-01 5.72E-01 6.42E-01

-4.18E-02 4.95E+00 5.64E+00 3.38E+00 5.80E+00 7.11E+00 NA NA NA 2.46E+02 MW-63-93 MW-63-93 Q1-2011 017 93

-80.7 3/2/2011 14:14 2.69E+02 3.00E+02 2.94E+02 3.30E-01 1.79E+00 2.17E+00

-1.51E+00 8.78E+00 9.05E+00 3.38E+00 7.56E+00 9.56E+00 NA NA NA 2.46E+02 MW-63-93 MW-63-112 Q2-2010 013 111.5

-99.2 4/26/2010 12:39 4.47E+02 1.64E+02 1.42E+02 4.81E-01 5.84E-01 6.06E-01 4.15E+00 6.75E+00 8.37E+00 4.44E+00 7.86E+00 9.87E+00 NA NA NA 3.64E+02 ND ND ND NA MW-63-112 MW-63-112 Q3-2010 014 111.5

-99.2 8/10/2010 14:52 3.71E+02 1.73E+02 1.78E+02 2.83E-01 4.37E-01 4.78E-01

-3.00E+00 7.68E+00 7.90E+00

-5.28E+00 9.73E+00 9.11E+00 NA NA NA 3.64E+02 MW-63-112 MW-63-112 Q4-2010 015 111.5

-99.2 11/2/2010 15:05 3.01E+02 1.29E+02 1.13E+02 6.02E-02 5.25E-01 6.51E-01

-2.54E+00 6.29E+00 6.56E+00 1.96E+00 6.72E+00 7.95E+00 NA NA NA 3.64E+02 MW-63-112 MW-63-112 Q1-2011 016 111.5

-99.2 3/2/2011 14:15 3.38E+02 3.18E+02 2.96E+02 1.48E-01 1.60E+00 2.00E+00

-3.72E-01 6.70E+00 7.21E+00 1.19E+00 6.36E+00 7.21E+00 NA NA NA 3.64E+02 MW-63-112 MW-63-121 Q2-2010 013 121

-108.7 4/26/2010 12:59 6.06E+02 1.80E+02 1.46E+02 4.17E-01 6.09E-01 6.57E-01 3.57E+00 6.06E+00 7.40E+00 1.16E+00 6.13E+00 7.15E+00 NA NA NA 5.42E+02 ND ND ND NA MW-63-121 MW-63-121 Q3-2010 014 121

-108.7 8/10/2010 11:28 5.39E+02 1.80E+02 1.77E+02 3.67E-01 5.93E-01 6.58E-01

-9.48E-01 8.12E+00 8.95E+00

-6.58E-01 8.76E+00 9.58E+00 NA NA NA 5.42E+02 MW-63-121 MW-63-121 Q4-2010 015 121

-108.7 11/2/2010 11:46 5.20E+02 1.49E+02 1.10E+02 6.38E-01 7.57E-01 8.11E-01 1.17E+00 6.66E+00 7.68E+00

-4.06E+00 7.17E+00 6.83E+00 NA NA NA 5.42E+02 MW-63-121 MW-63-121 Q1-2011 016 121

-108.7 3/2/2011 11:10 5.03E+02 3.54E+02 2.94E+02

-6.82E-02 1.55E+00 2.03E+00

-6.26E-01 6.72E+00 7.20E+00 3.49E-01 6.00E+00 6.67E+00 NA NA NA 5.42E+02 MW-63-121 MW-63-163 Q2-2010 013 162.5

-150.2 4/26/2010 14:30 5.29E+02 1.70E+02 1.43E+02 1.98E-01 5.64E-01 6.75E-01

-1.45E+00 7.71E+00 8.86E+00

-2.98E+00 6.17E+00 5.91E+00 NA NA NA 4.98E+02 ND ND ND NA MW-63-163 MW-63-163 Q3-2010 014 162.5

-150.2 8/10/2010 11:21 4.13E+02 1.74E+02 1.78E+02 2.45E-01 4.43E-01 4.98E-01

-6.87E-01 8.55E+00 9.17E+00

-5.25E-01 8.23E+00 9.24E+00 NA NA NA 4.98E+02 MW-63-163 MW-63-163 Q4-2010 015 162.5

-150.2 11/2/2010 11:49 4.44E+02 1.41E+02 1.10E+02 7.71E-01 8.38E-01 8.77E-01

-3.99E+00 9.88E+00 1.10E+01 2.94E+00 6.12E+00 7.63E+00 NA NA NA 4.98E+02 MW-63-163 MW-63-163 Q1-2011 016 162.5

-150.2 3/2/2011 10:27 6.05E+02 3.76E+02 2.95E+02 1.37E+00 1.99E+00 2.12E+00 3.09E+00 5.40E+00 6.62E+00

-2.05E+00 7.72E+00 7.12E+00 NA NA NA 4.98E+02 MW-63-163 MW-63-174 Q2-2010 013 174

-161.7 4/26/2010 14:28 4.98E+02 1.71E+02 1.46E+02

-1.69E-02 5.53E-01 7.24E-01 2.68E+00 4.74E+00 5.86E+00

-4.68E+00 5.26E+00 4.32E+00 NA NA NA 3.77E+02 ND ND ND NA MW-63-174 MW-63-174 Q3-2010 014 174

-161.7 8/10/2010 11:40 3.33E+02 1.65E+02 1.71E+02 3.54E-01 5.43E-01 6.01E-01

-3.32E+00 7.07E+00 6.89E+00

-1.41E+00 7.84E+00 8.11E+00 NA NA NA 3.77E+02 MW-63-174 MW-63-174 Q4-2010 015 174

-161.7 11/2/2010 11:50 2.63E+02 1.26E+02 1.13E+02

-1.42E-01 4.59E-01 6.06E-01

-6.01E-01 6.03E+00 6.82E+00 2.17E-01 6.42E+00 7.11E+00 NA NA NA 3.77E+02 MW-63-174 MW-63-174 Q1-2011 016 174

-161.7 3/2/2011 10:26 4.13E+02 3.30E+02 2.91E+02 8.20E-01 1.80E+00 2.03E+00 3.65E+00 6.96E+00 8.18E+00 2.34E+00 7.86E+00 9.20E+00 NA NA NA 3.77E+02 MW-63-174 MW-66-21 Q2-2010 013 14.1 0

4/9/2010 15:27 9.50E+02 4.07E+02 3.82E+02 1.12E-02 4.34E-01 5.44E-01 3.09E+00 6.75E+00 8.43E+00 3.15E+00 5.19E+00 7.18E+00

-2.25E+00 1.92E+01 2.25E+01 8.32E+02 1.17E+00 ND ND ND MW-66-21 MW-66-21 Q3-2010 014 14.1 0

8/9/2010 12:30 1.07E+03 2.01E+02 1.29E+02 1.17E+00 5.52E-01 4.41E-01

-5.85E+00 9.45E+00 9.34E+00

-9.97E-01 8.07E+00 8.65E+00 3.11E+00 1.19E+01 1.37E+01 8.32E+02 1.17E+00 MW-66-21 MW-66-21 Q4-2010 015 14.1 0

11/10/2010 15:13 3.22E+02 1.64E+02 3.46E+02 2.57E-01 7.74E-01 1.84E+00 6.04E+00 5.26E+00 1.28E+01

-1.91E-01 5.67E+00 1.26E+01 9.56E+00 8.45E+00 1.85E+01 8.32E+02 1.17E+00 MW-66-21 MW-66-21 Q1-2011 016 14.1 0

1/31/2011 16:26 4.77E+02 4.08E+02 4.24E+02 3.48E-01 1.73E+00 2.02E+00

-2.19E-01 5.00E+00 5.33E+00 9.80E-01 6.50E+00 7.23E+00

-1.06E+00 1.84E+01 2.14E+01 8.32E+02 1.17E+00 MW-66-21 MW-66-36 Q2-2010 012 33.6

-19.5 4/9/2010 15:17 3.64E+03 5.90E+02 3.87E+02 7.05E+00 1.36E+00 7.54E-01 1.79E+00 7.65E+00 9.10E+00 6.63E+00 8.54E+00 1.20E+01

-7.64E+00 1.69E+01 2.02E+01 3.22E+03 9.10E+00 ND ND ND MW-66-36 MW-66-36 Q3-2010 013 33.6

-19.5 8/9/2010 11:47 3.08E+03 3.06E+02 1.24E+02 6.40E+00 1.07E+00 3.74E-01

-1.53E+00 8.82E+00 9.41E+00 4.62E+00 7.61E+00 1.02E+01 4.59E+00 1.58E+01 1.80E+01 3.22E+03 9.10E+00 MW-66-36 MW-66-36 Q4-2010 014 33.6

-19.5 11/10/2010 12:33 3.13E+03 2.96E+02 3.96E+02 7.43E+00 1.03E+00 1.13E+00 5.42E+00 3.87E+00 9.67E+00 7.18E-01 4.34E+00 9.81E+00

-4.23E+00 9.63E+00 2.16E+01 3.22E+03 9.10E+00 MW-66-36 MW-66-36 Q1-2011 015 33.6

-19.5 1/31/2011 15:51 3.01E+03 6.78E+02 4.61E+02 1.55E+01 3.18E+00 2.11E+00

-1.13E+00 6.12E+00 6.49E+00

-8.31E-01 6.80E+00 7.15E+00

-4.89E+00 1.79E+01 2.12E+01 3.22E+03 9.10E+00 MW-66-36 MW-67-39 Q2-2010 013 38.3

-25.8 5/6/2010 15:38 3.30E+03 3.60E+02 1.70E+02 9.77E+00 1.69E+00 5.74E-01

-1.53E+00 9.44E+00 1.08E+01

-1.11E+00 7.71E+00 8.22E+00

-1.04E+01 2.13E+01 2.48E+01 3.52E+03 9.86E+00 ND ND ND MW-67-39 MW-67-39 Q3-2010 014 38.3

-25.8 8/9/2010 10:43 3.37E+03 3.15E+02 1.22E+02 8.52E+00 1.21E+00 5.69E-01

-9.27E+00 1.08E+01 1.30E+01

-1.39E+00 8.28E+00 8.77E+00

-2.31E+00 1.43E+01 1.69E+01 3.52E+03 9.86E+00 MW-67-39 MW-67-39 Q4-2010 015 38.3

-25.8 11/10/2010 11:49 3.56E+03 3.09E+02 3.95E+02 5.43E+00 8.85E-01 1.10E+00 1.04E+00 3.96E+00 8.88E+00 2.82E+00 4.30E+00 1.04E+01

-1.86E+00 9.87E+00 2.21E+01 3.52E+03 9.86E+00 MW-67-39 MW-67-39 Q1-2011 016 38.3

-25.8 2/7/2011 13:48 3.85E+03 7.60E+02 4.81E+02 1.57E+01 3.34E+00 1.83E+00 8.03E-02 6.18E+00 6.83E+00 6.64E-01 6.78E+00 7.57E+00 4.43E+00 1.97E+01 2.23E+01 3.52E+03 9.86E+00 MW-67-39 MW-67-105 Q2-2010 012 104.8

-92.3 5/6/2010 15:46 1.54E+03 2.60E+02 1.64E+02 1.77E+00 1.01E+00 7.88E-01 4.33E-01 8.65E+00 9.84E+00 3.51E+00 1.01E+01 1.24E+01

-6.18E+00 2.07E+01 2.40E+01 1.23E+03 2.19E+00 ND ND ND MW-67-105 MW-67-105 Q3-2010 013 104.8

-92.3 8/9/2010 10:37 1.26E+03 2.10E+02 1.24E+02 2.61E+00 8.16E-01 6.26E-01 1.46E+00 6.24E+00 7.48E+00 1.75E+00 5.78E+00 7.28E+00 9.56E+00 1.69E+01 1.90E+01 1.23E+03 2.19E+00 MW-67-105 MW-67-105 Q4-2010 014 104.8

-92.3 11/10/2010 11:42 1.14E+03 2.24E+02 3.95E+02 1.41E+00 8.12E-01 1.69E+00

-1.68E+00 3.59E+00 7.64E+00

-3.12E+00 4.14E+00 8.26E+00 1.24E+00 8.56E+00 1.90E+01 1.23E+03 2.19E+00 MW-67-105 MW-67-105 Q1-2011 015 104.8

-92.3 2/7/2011 13:57 9.94E+02 4.26E+02 3.86E+02 3.37E-01 1.64E+00 1.94E+00 2.40E+00 4.84E+00 5.67E+00

-1.22E+00 4.86E+00 4.81E+00

-4.59E+00 1.96E+01 2.31E+01 1.23E+03 2.19E+00 MW-67-105

TABLE 3 FIRST QUARTER 2011 GROUNDWATER ANALYTICAL RESULTS AND AVERAGES INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q12011 FINAL Table 3 - First Quarter 2011 Groundwater Analytical Results and Averages.xlsx; Q12011 Table 3 Page 5 of 5 See Page 5 for Notes TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Date Time Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Average Average Average Average Average ANALYSIS RESULTS5 YEARLY ROLLING AVERAGES4,6 Well ID1 TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

SAMPLE COLLECTION Well ID1 SAMPLING QUARTER2,8 SAMPLE ID SAMPLE ZONE CENTER, Depth Ft Below Top of Casing3 SAMPLE ZONE CENTER Elevation Ft msl3 MW-67-173 Q2-2010 013 172.3

-159.8 5/6/2010 16:03 6.78E+02 2.03E+02 1.66E+02

-1.35E-01 4.87E-01 7.07E-01

-3.30E+00 9.64E+00 1.02E+01

-8.48E-01 1.00E+01 1.11E+01

-7.30E+00 2.01E+01 2.37E+01 6.58E+02 ND ND ND ND MW-67-173 MW-67-173 Q3-2010 014 172.3

-159.8 8/9/2010 11:07 6.72E+02 1.71E+02 1.27E+02 7.70E-02 4.44E-01 5.35E-01

-7.06E-01 1.34E+01 1.68E+01 6.44E-01 8.97E+00 1.04E+01

-1.44E+00 1.14E+01 1.34E+01 6.58E+02 MW-67-173 MW-67-173 Q4-2010 015 172.3

-159.8 11/10/2010 12:04 6.25E+02 2.01E+02 3.97E+02

-9.99E-01 6.33E-01 1.86E+00 4.02E-01 7.80E+00 1.12E+01

-1.17E+00 4.83E+00 1.03E+01

-1.65E+00 8.09E+00 1.81E+01 6.58E+02 MW-67-173 MW-67-173 Q1-2011 016 172.3

-159.8 2/7/2011 14:13 4.47E+02 4.48E+02 4.65E+02

-2.38E-01 1.68E+00 2.12E+00

-4.75E-01 5.28E+00 5.83E+00 7.55E-01 6.38E+00 5.76E+00

-7.05E-01 1.88E+01 2.18E+01 6.58E+02 MW-67-173 MW-67-219 Q2-2010 012 218.8

-206.3 5/6/2010 11:51 1.20E+03 2.40E+02 1.66E+02 1.78E-01 6.31E-01 7.71E-01 2.27E+00 8.87E+00 1.05E+01 2.35E+00 7.38E+00 9.29E+00

-7.98E+00 1.95E+01 2.31E+01 1.03E+03 ND ND ND ND MW-67-219 MW-67-219 Q3-2010 013 218.8

-206.3 8/9/2010 13:33 1.11E+03 2.01E+02 1.25E+02 9.94E-02 5.32E-01 6.41E-01

-7.99E-01 8.14E+00 9.12E+00

-6.19E+00 9.03E+00 8.33E+00 2.34E+00 1.21E+01 1.39E+01 1.03E+03 MW-67-219 MW-67-219 Q4-2010 014 218.8

-206.3 11/10/2010 13:40 1.15E+03 2.24E+02 3.96E+02 3.53E-01 7.28E-01 1.78E+00

-2.80E-01 3.60E+00 7.62E+00 2.49E-01 3.62E+00 7.89E+00

-4.41E+00 8.84E+00 1.98E+01 1.03E+03 MW-67-219 MW-67-219 Q1-2011 015 218.8

-206.3 1/31/2011 14:48 6.41E+02 4.18E+02 4.20E+02

-1.08E+00 1.42E+00 1.97E+00 9.72E-01 5.80E+00 6.44E+00 2.44E+00 5.46E+00 6.55E+00

-4.58E+00 1.81E+01 2.14E+01 1.03E+03 MW-67-219 MW-67-276 Q2-2010 012 275.3

-262.8 5/6/2010 12:20 1.09E+03 2.33E+02 1.65E+02

-1.16E-01 5.38E-01 7.47E-01

-1.34E+00 7.98E+00 8.70E+00 2.02E+00 9.16E+00 1.09E+01 9.78E+00 2.03E+01 2.27E+01 9.77E+02 ND ND ND ND MW-67-276 MW-67-276 Q3-2010 013 275.3

-262.8 8/9/2010 13:36 9.33E+02 1.86E+02 1.22E+02 4.00E-01 4.66E-01 4.98E-01 2.56E+00 7.23E+00 8.80E+00

-2.39E+00 8.22E+00 8.27E+00 9.94E+00 1.28E+01 1.42E+01 9.77E+02 MW-67-276 MW-67-276 Q4-2010 014 275.3

-262.8 11/10/2010 14:16 1.01E+03 2.18E+02 3.96E+02

-7.85E-01 5.64E-01 1.77E+00 1.94E+00 4.26E+00 9.92E+00

-5.48E+00 4.42E+00 7.40E+00 5.46E+00 8.55E+00 1.89E+01 9.77E+02 MW-67-276 MW-67-276 Q1-2011 015 275.3

-262.8 1/31/2011 14:31 8.75E+02 4.18E+02 3.87E+02

-2.57E-02 1.66E+00 2.03E+00

-2.56E+00 8.76E+00 8.16E+00 6.49E-01 6.48E+00 7.20E+00

-7.18E-01 1.92E+01 2.22E+01 9.77E+02 MW-67-276 MW-67-323 Q2-2010 012 322.3

-309.8 5/6/2010 12:30 4.44E+02 1.83E+02 1.67E+02

-1.63E-01 4.58E-01 6.67E-01

-2.50E+00 7.72E+00 7.87E+00 2.97E-01 8.21E+00 9.30E+00

-1.13E+01 1.96E+01 2.33E+01 4.38E+02 ND ND ND ND MW-67-323 MW-67-323 Q3-2010 013 322.3

-309.8 8/9/2010 13:23 4.32E+02 1.48E+02 1.23E+02 6.38E-01 6.31E-01 6.53E-01 1.47E+00 6.88E+00 8.02E+00 3.28E-01 6.72E+00 7.56E+00

-4.51E+00 1.37E+01 1.63E+01 4.38E+02 MW-67-323 MW-67-323 Q4-2010 014 322.3

-309.8 11/10/2010 14:03 3.88E+02 1.89E+02 3.94E+02 1.89E-01 8.21E-01 2.01E+00 2.70E+00 4.61E+00 1.06E+01 3.11E-01 5.07E+00 1.12E+01

-3.22E+00 7.93E+00 1.78E+01 4.38E+02 MW-67-323 MW-67-323 Q1-2011 015 322.3

-309.8 1/31/2011 15:04 3.38E+02 3.70E+02 3.90E+02 2.58E-01 1.71E+00 2.03E+00 2.47E-01 5.70E+00 6.35E+00 8.12E-03 5.80E+00 6.35E+00

-5.93E+00 1.90E+01 2.25E+01 4.38E+02 MW-67-323 MW-67-340 Q2-2010 012 339.8

-327.3 5/6/2010 12:24 6.57E+02 2.00E+02 1.65E+02

-2.13E-01 4.66E-01 7.01E-01

-2.61E+00 7.77E+00 8.17E+00 3.62E-01 8.78E+00 1.00E+01

-5.47E+00 1.94E+01 2.28E+01 5.58E+02 ND ND ND ND MW-67-340 MW-67-340 Q3-2010 013 339.8

-327.3 8/9/2010 13:20 4.86E+02 1.55E+02 1.25E+02

-3.81E-02 5.00E-01 6.29E-01 1.20E+00 7.44E+00 8.75E+00

-2.42E+00 6.98E+00 7.06E+00 2.60E+00 1.45E+01 1.67E+01 5.58E+02 MW-67-340 MW-67-340 Q4-2010 014 339.8

-327.3 11/10/2010 13:53 5.31E+02 1.97E+02 3.95E+02

-8.93E-01 5.00E-01 1.64E+00 1.72E+00 4.50E+00 1.03E+01

-2.97E+00 3.90E+00 7.25E+00 2.25E+00 8.84E+00 1.97E+01 5.58E+02 MW-67-340 MW-67-340 Q1-2011 015 339.8

-327.3 1/31/2011 14:53 2.75E+02 3.58E+02 3.83E+02

-7.06E-01 1.51E+00 1.99E+00 4.30E-01 6.34E+00 7.02E+00

-1.15E+00 6.54E+00 6.88E+00

-5.79E+00 1.85E+01 2.20E+01 5.58E+02 MW-67-340 MW-107 Q2-2010 009 32.7 110.1 4/22/2010 10:11 9.67E+01 1.64E+02 1.83E+02

-7.61E-02 5.23E-01 6.74E-01 9.25E-01 6.08E+00 6.99E+00

-1.88E+00 7.25E+00 7.56E+00 NA NA NA ND ND ND ND NA MW-107 MW-111 Q2-2010 032 16.5 2.4 4/21/2010 14:48 3.35E+04 1.07E+03 1.91E+02 1.48E+00 7.26E-01 6.28E-01 6.79E+00 6.54E+00 4.32E+00 1.70E+00 4.37E+00 5.18E+00 NA NA NA 4.12E+04 1.64E+00 6.79E+00 ND NA MW-111 MW-111 Q3-2010 033 16.5 2.4 8/27/2010 15:21 3.86E+04 1.13E+03 1.28E+02 6.44E-01 8.07E-01 8.55E-01

-8.83E-01 6.30E+00 6.59E+00 1.88E+00 5.70E+00 6.84E+00 NA NA NA 4.12E+04 1.64E+00 6.79E+00 MW-111 MW-111 Q3-2010 Mid 034 16.5 2.4 9/10/2010 14:09 4.69E+04 1.37E+03 1.40E+02 1.80E+00 1.00E+00 8.02E-01

-5.04E+00 6.84E+00 6.88E+00

-5.62E-01 6.84E+00 7.62E+00 NA NA NA 4.12E+04 1.64E+00 6.79E+00 MW-111 MW-111 Q4-2010 035 16.5 2.4 11/1/2010 14:55 4.59E+04 1.34E+03 1.27E+02 3.47E-01 5.90E-01 6.60E-01

-1.99E-01 5.63E+00 6.38E+00 5.49E+00 5.91E+00 7.75E+00 NA NA NA 4.12E+04 1.64E+00 6.79E+00 MW-111 U3-4D Q2-2010 024 25.6

-10.8 4/12/2010 12:49 1.07E+03 2.06E+02 1.77E+02

-4.68E-02 5.46E-01 7.39E-01

-5.85E+00 9.33E+00 8.95E+00

-2.13E+00 8.04E+00 7.89E+00 NA NA NA 7.74E+02 ND ND ND NA U3-4D U3-4D Q3-2010 025 25.6

-10.8 7/23/2010 13:21 6.84E+02 1.86E+02 1.77E+02

-1.56E-01 4.60E-01 6.46E-01 2.21E+00 7.56E+00 8.91E+00

-1.01E+00 7.61E+00 8.14E+00 NA NA NA 7.74E+02 U3-4D U3-4D Q4-2010 026 25.6

-10.8 10/28/2010 14:04 7.12E+02 1.68E+02 1.13E+02 2.26E-01 4.89E-01 5.61E-01 2.75E+00 5.75E+00 6.97E+00 1.33E+00 7.82E+00 9.00E+00 NA NA NA 7.74E+02 U3-4D U3-4D Q1-2011 027 25.6

-10.8 2/17/2011 14:41 6.28E+02 4.14E+02 4.05E+02

-8.34E-02 1.55E+00 1.95E+00 1.24E+00 4.72E+00 5.29E+00 8.61E-01 4.84E+00 5.47E+00 NA NA NA 7.74E+02 U3-4D U3-4S Q3-2010 001 7/23/2010 14:12 3.74E+02 1.74E+02 1.79E+02 3.76E-01 4.15E-01 4.21E-01 9.00E-01 8.51E+00 9.30E+00 1.89E+00 7.75E+00 9.37E+00 NA NA NA 3.63E+02 ND ND ND NA U3-4S U3-4S Q4-2010 002 10/29/2010 11:40 3.51E+02 1.32E+02 1.10E+02 3.86E-01 5.82E-01 6.43E-01 1.64E+00 5.59E+00 6.52E+00

-2.02E+00 5.91E+00 6.14E+00 NA NA NA 3.63E+02 U3-4S U3-T1 Q2-2010 028 5.7 2.8 5/5/2010 16:54 5.00E+02 1.79E+02 1.84E+02 6.48E-02 4.95E-01 5.97E-01

-3.25E+00 8.98E+00 1.04E+01

-8.61E-01 6.62E+00 7.16E+00 NA NA NA 4.61E+02 ND ND ND NA U3-T1 U3-T1 Q3-2010 029 5.7 2.8 7/26/2010 12:15 3.84E+02 1.74E+02 1.78E+02 1.20E-02 3.91E-01 4.99E-01 5.07E+00 7.68E+00 9.77E+00

-6.61E-01 6.96E+00 7.49E+00 NA NA NA 4.61E+02 U3-T1 U3-T1 Q4-2010 030 5.7 2.8 10/29/2010 16:04 3.04E+02 1.28E+02 1.10E+02 4.84E-02 6.36E-01 7.68E-01

-8.56E-01 6.04E+00 6.70E+00 1.59E+00 5.73E+00 6.79E+00 NA NA NA 4.61E+02 U3-T1 U3-T1 Q1-2011 031 5.7 2.8 2/22/2011 11:11 6.55E+02 4.08E+02 3.92E+02 1.62E+00 1.96E+00 2.02E+00 1.80E+00 1.05E+01 6.14E+00 2.12E+00 6.42E+00 7.54E+00 NA NA NA 4.61E+02 U3-T1 U3-T2 Q2-2010 033 5.7 2.6 5/7/2010 13:05 9.75E+02 1.95E+02 1.83E+02 6.31E-01 6.31E-01 6.58E-01

-2.27E+00 5.70E+00 5.99E+00

-1.66E+00 6.62E+00 6.97E+00 NA NA NA 1.40E+03 ND ND ND NA U3-T2 U3-T2 Q3-2010 034 5.7 2.6 7/26/2010 14:26 8.76E+02 1.92E+02 1.74E+02 5.34E-01 6.12E-01 6.47E-01

-2.12E+00 7.50E+00 7.69E+00 2.29E+00 7.21E+00 8.84E+00 NA NA NA 1.40E+03 U3-T2 U3-T2 Q4-2010 035 5.7 2.6 10/29/2010 11:22 1.47E+03 2.19E+02 1.11E+02 4.22E-01 6.79E-01 7.56E-01

-6.11E-02 5.42E+00 6.11E+00 3.00E+00 5.47E+00 6.89E+00 NA NA NA 1.40E+03 U3-T2 U3-T2 Q1-2011 036 5.7 2.6 2/22/2011 14:30 2.27E+03 4.92E+02 3.62E+02 1.82E+00 2.04E+00 2.05E+00 3.65E+00 6.08E+00 7.29E+00 5.97E-01 7.12E+00 7.85E+00 NA NA NA 1.40E+03 U3-T2 U1-CSS Q2-2010 014 14 6.1 5/3/2010 15:58 1.88E+03 2.79E+02 1.70E+02 8.95E+00 1.81E+00 8.92E-01 4.61E-01 5.87E+00 6.66E+00 3.94E+00 5.22E+00 6.88E+00

-1.79E+01 2.18E+01 2.53E+01 2.07E+03 1.04E+01 ND ND ND U1-CSS U1-CSS Q4-2010 015 14 6.1 11/8/2010 14:56 2.26E+03 2.72E+02 1.26E+02 1.18E+01 1.45E+00 6.84E-01 2.29E+00 5.01E+00 5.93E+00 2.07E+00 5.61E+00 6.70E+00 3.16E-01 1.81E+01 2.13E+01 2.07E+03 1.04E+01 U1-CSS U1-NCD Q3-2010 008 7/15/2010 9:10 1.35E+04 4.41E+02 1.58E+02 5.06E+01 3.21E+00 7.59E-01 1.14E+04 1.42E+03 1.40E+01 7.51E-01 5.21E+00 6.03E+00 2.90E+02 3.39E+01 2.40E+01 8.42E+03 4.47E+01 1.17E+04 ND 2.61E+02 U1-NCD U1-NCD Q4-2010 009 10/20/2010 13:40 3.34E+03 3.23E+02 1.27E+02 3.88E+01 2.31E+00 6.39E-01 1.20E+04 1.47E+03 9.98E+00

-1.14E+00 4.96E+00 5.42E+00 2.31E+02 3.19E+01 2.23E+01 8.42E+03 4.47E+01 1.17E+04 2.61E+02 U1-NCD U1-SFDS Q3-2010 009 7/7/2010 8:45 6.44E+02 1.80E+02 1.45E+02 1.88E+01 2.10E+00 6.82E-01 2.09E+01 1.26E+01 7.48E+00 1.64E+00 7.91E+00 9.44E+00 3.42E+00 2.24E+01 2.58E+01 5.63E+02 1.53E+01 1.44E+01 ND ND U1-SFDS U1-SFDS Q4-2010 010 10/20/2010 8:45 4.82E+02 1.56E+02 1.26E+02 1.17E+01 1.83E+00 8.74E-01 7.99E+00 7.54E+00 5.78E+00

-8.31E-01 5.24E+00 5.67E+00 9.71E-01 1.86E+01 2.18E+01 5.63E+02 1.53E+01 1.44E+01 U1-SFDS I-2 Q3-2010 001 8/2/2010 14:39 6.21E+01 1.53E+02 1.73E+02

-2.56E-01 3.72E-01 5.25E-01 7.04E+00 7.80E+00 1.02E+01 9.34E-02 6.54E+00 7.19E+00 NA NA NA ND ND ND ND NA I-2 I-2 Q4-2010 002 11/17/2010 14:25 1.74E+02 1.71E+02 3.78E+02 2.25E-01 6.25E-01 1.50E+00

-4.50E-01 5.04E+00 1.10E+01 3.35E+00 5.94E+00 1.40E+01 NA NA NA I-2 MH-5 VCFD7 Q2-2010 Mid 009 5/17/2010 10:15 4.33E+02 1.73E+02 1.79E+02 3.66E-01 5.84E-01 6.48E-01 2.13E+00 6.00E+00 7.18E+00 4.52E-01 6.63E+00 7.65E+00 NA NA NA 2.94E+03 ND ND ND NA MH-5 VCFD7 MH-5 VCFD Q3-2010 010 8/5/2010 14:45 7.32E+02 1.89E+02 1.77E+02 5.37E-01 5.67E-01 5.84E-01 7.26E-01 7.72E+00 8.69E+00

-2.26E+00 6.93E+00 7.07E+00 NA NA NA 2.94E+03 MH-5 VCFD MH-5 VCFD Q3-2010 011 8/30/2010 13:30 9.96E+03 5.48E+02 1.26E+02 1.25E-01 3.21E-01 3.81E-01 1.50E+00 5.58E+00 6.48E+00 8.08E-01 6.51E+00 7.50E+00 NA NA NA 2.94E+03 MH-5 VCFD MH-5 VCFD Q3-2010 Mid 012 9/10/2010 15:30 8.80E+02 1.89E+02 1.25E+02 3.60E-01 6.35E-01 7.11E-01 7.21E-01 6.45E+00 7.44E+00 1.23E+00 5.71E+00 6.85E+00 NA NA NA 2.94E+03 MH-5 VCFD MH-5 VCFD Q4-2010 013 11/24/2010 11:10 4.60E+02 1.86E+02 1.47E+02 1.36E-01 7.57E-01 8.85E-01 1.75E+00 3.45E+00 4.02E+00 5.48E-01 3.79E+00 4.28E+00 NA NA NA 2.94E+03 MH-5 VCFD MH-5 VCFD Q1-2011 014 2/28/2011 9:47 5.17E+03 6.58E+02 3.66E+02 1.90E+00 1.99E+00 1.94E+00 3.45E-01 5.64E+00 6.19E+00

-1.28E+00 6.18E+00 6.45E+00 NA NA NA 2.94E+03 MH-5 VCFD LAF-002 Q2-2010 Mid 013

-22.3 5/11/2010 13:44

-4.21E+01 1.32E+02 1.63E+02 6.55E-01 7.37E-01 7.78E-01

-1.49E+00 6.90E+00 7.60E+00 1.64E+00 6.08E+00 7.34E+00

-6.88E+00 2.21E+01 2.54E+01 ND ND ND ND ND LAF-002 LAF-002 Q4-2010 014

-22.3 11/22/2010 14:41 1.02E+02 1.13E+02 1.21E+02 1.96E-01 4.62E-01 5.40E-01

-6.13E-01 6.13E+00 6.83E+00

-1.60E+00 5.88E+00 6.15E+00 3.65E+00 1.77E+01 2.05E+01 LAF-002 B-17 Q2-2010 008 4/23/2010 16:44 8.15E+02 1.91E+02 1.85E+02 2.22E-01 5.20E-01 6.03E-01 9.79E+00 7.91E+00 6.38E+00 5.59E-01 6.24E+00 7.21E+00 NA NA NA 5.25E+03 ND 1.82E+01 ND NA B-17 B-1 Q3-2010 009 8/17/2010 15:40 1.40E+04 6.48E+02 1.27E+02 1.25E-01 6.43E-01 7.91E-01 2.27E+01 1.06E+01 5.87E+00 2.96E+00 6.00E+00 7.45E+00 NA NA NA 5.25E+03 1.82E+01 B-1 B-1 Q4-2010 010 11/17/2010 11:10 2.37E+03 2.72E+02 3.86E+02 6.87E-01 7.68E-01 1.72E+00 1.89E+01 6.46E+00 7.93E+00 8.39E-01 4.32E+00 9.74E+00 NA NA NA 5.25E+03 1.82E+01 B-1 B-1 Q1-2011 011 2/14/2011 15:44 3.82E+03 5.88E+02 3.65E+02 5.41E-02 1.70E+00 2.14E+00 2.15E+01 1.22E+01 6.75E+00

-1.81E+00 7.00E+00 7.25E+00 NA NA NA 5.25E+03 1.82E+01 B-1 B-67 Q2-2010 Mid 008 5/18/2010 9:40 4.48E+01 1.62E+02 1.84E+02

-1.02E-01 4.47E-01 5.71E-01 5.39E-01 5.58E+00 6.34E+00 2.39E-01 5.50E+00 6.27E+00 NA NA NA 8.39E+02 ND ND ND NA B-67 B-6 Q3-2010 009 8/5/2010 13:43 1.49E+02 1.62E+02 1.79E+02 1.12E-01 8.02E-01 9.78E-01 2.32E+00 6.57E+00 8.03E+00

-9.21E-02 8.23E+00 9.37E+00 NA NA NA 8.39E+02 B-6 B-6 Q4-2010 010 11/8/2010 11:45 1.05E+02 1.33E+02 1.43E+02 1.43E-01 6.60E-01 7.68E-01 0.00E+00 5.04E+00 6.20E+00

-3.20E-01 4.70E+00 5.29E+00 NA NA NA 8.39E+02 B-6 B-6 Q1-2011 011 2/28/2011 11:27 8.39E+02 3.90E+02 3.65E+02 6.28E-01 1.78E+00 2.05E+00 4.45E+00 5.82E+00 7.02E+00

-1.35E+00 6.50E+00 6.88E+00 NA NA NA 8.39E+02 B-6 Notes:

1. For nested multi-level monitoring wells, suffix of well ID indicates depth (rounded to nearest foot) from reference point on casing to bottom of well screen. For Waterloo multi-level systems, suffix indicates depth (rounded to nearest foot) from reference point on casing to top of sampling port. Well IDs without a suffix are open bedrock wellbores.
2. All analytical results from the last 12 months from each location are provided. Monitoring locations are sampled quarterly, bi-annually, or annually, and as necessary during the year.
3. Sampling depths within sampling intervals (i.e. location of pump intake) have been located adjacent to a transmissive zone where possible.
4. Averages provided are analytical result averages of all valid samples (including mid-quarter and confirmatory samples) collected from each monitoring location from the second quarter of 2010 (Q2-2010) to the first quarter of 2011 (Q1-2011) including the post Q1-2011 samples.

Monitoring locations are sampled quarterly, bi-annually, or annually and additional samples are collected when necessary. Therefore, some results provided are the average of more than 4 samples.

For quarters in which samples were reanalyzed due to potential false positives, both results were used to calculate averages if subsequent results confirmed the validity of the original sample/analysis. For cases in which reanalysis discredited the validity of the original sample result, the replacement results were used to calculate the average. If analytical results resulted in resampling, and the resample result discredited the validity of the original sample result of a particular radionuclide, the original sample results were not used for any radionuclides and only the resample result was used. For cases in which an aliquot of the original sample was reanalyzed, if the result of the aliquot confirmed the original result, then the aliquot result and the original result were averaged and the average of the two was used to calculate the rolling average. If the aliquot result indicated the original result was false, then only the aliquot result was used to calculate the rolling average.

5. NA indicates that the constituent was not analyzed.
6. ND indicates that all of the analytical results used to calculate the average were less than MDC and/or 3 times the 1 sigma uncertainty.
7. These locations are storm drains or foundation drains.
8. Mid-quarter samples were collected and analyzed to evaluate the potential effect of certain operations on groundwater quality.
9. Column designated as Std. Dev. provides the three times 1 sigma uncertainty values.
  • The Q1 2011 MW-40-100, MW-40-127 and MW-51-189 Cs-137 results were verified by re-analysis. However, based on the available chemistry and Site hydrogeologic data, these values do not appear to be representative of the groundwater conditions at these sampling intervals.

TABLE 3 SECOND QUARTER 2011 GROUNDWATER ANALYTICAL RESULTS AND AVERAGES INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q22011 FINAL Table 3 - Second Quarter 2011 Groundwater Analytical Results and Averages.xlsx; Q22011 Table 3 Page 1 of 6 See Page 6 for Notes TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Date Time Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Average Average Average Average Average MW-30-69 Q3-2010 033 69.3 6.4 7/28/2010 12:33 1.28E+05 3.72E+03 1.80E+02 9.14E-02 5.26E-01 6.35E-01

-5.08E-01 9.69E+00 1.09E+01 1.67E+00 7.46E+00 9.20E+00 NA NA NA 1.16E+05 2.40E+00 ND ND NA MW-30-69 MW-30-69 Q3-2010 034 69.3 6.4 8/20/2010 15:08 1.11E+05 3.24E+03 2.02E+02 3.53E-01 7.80E-01 9.08E-01

-3.14E+00 5.22E+00 5.12E+00

-2.41E+00 5.25E+00 5.03E+00 NA NA NA 1.16E+05 2.40E+00 ND ND NA MW-30-69 MW-30-69 Q3-2010 Mid 035 69.3 6.4 9/8/2010 12:35 1.23E+05 3.65E+03 4.47E+02 1.93E-01 4.41E-01 5.14E-01

-1.10E+00 4.42E+00 4.87E+00 1.40E+00 4.72E+00 5.73E+00 NA NA NA 1.16E+05 2.40E+00 ND ND NA MW-30-69 MW-30-69 Q4-2010 036 69.3 6.4 11/5/2010 11:56 1.25E+05 1.88E+03 4.34E+02 9.69E-01 8.79E-01 1.94E+00

-3.68E+00 3.94E+00 7.79E+00

-5.01E+00 5.09E+00 9.47E+00 NA NA NA 1.16E+05 2.40E+00 MW-30-69 MW-30-69 Q1-2011 037 69.3 6.4 2/9/2011 12:17 1.01E+05 2.18E+03 2.98E+02 1.62E+00 1.93E+00 2.00E+00 1.87E+00 5.80E+00 6.74E+00

-1.13E-01 5.88E+00 6.44E+00 NA NA NA 1.16E+05 2.40E+00 MW-30-69 MW-30-69 Q1-2011 Mid 038 69.3 6.4 3/31/2011 11:38 1.08E+05 3.40E+03 4.72E+02

-6.11E-01 1.63E+00 2.15E+00 2.48E+00 7.96E+00 9.14E+00

-1.41E+00 6.70E+00 6.46E+00 NA NA NA 1.16E+05 2.40E+00 MW-30-69 MW-30-69 Q2-2011 039 69.3 6.4 5/5/2011 12:08 1.13E+05 3.48E+03 3.99E+02 2.40E+00 1.37E+00 1.23E+00 2.46E+00 8.92E+00 1.03E+01 2.21E+00 9.58E+00 1.16E+01 NA NA NA 1.16E+05 2.40E+00 MW-30-69 MW-30-69 Q2-2011 Mid 040 69.3 6.4 7/11/2011 12:05 1.19E+05 4.23E+03 2.83E+02

-6.14E-02 7.62E-01 1.00E+00 3.56E+00 1.07E+01 1.24E+01 2.40E+00 1.19E+01 1.40E+01 NA NA NA 1.16E+05 2.40E+00 MW-30-69 MW-30-84 Q3-2010 024 83.8

-8.1 7/28/2010 13:07 9.26E+03 5.09E+02 1.01E+02 4.48E-01 7.63E-01 8.52E-01

-1.46E+00 9.30E+00 1.02E+01

-3.03E-01 9.79E+00 1.08E+01 NA NA NA 9.12E+03 ND ND ND NA MW-30-84 MW-30-84 Q3-2010 025 83.8

-8.1 8/20/2010 16:51 1.00E+04 5.57E+02 1.29E+02 5.65E-01 8.70E-01 9.53E-01 3.22E+00 6.27E+00 7.54E+00

-3.97E+00 6.69E+00 6.20E+00 NA NA NA 9.12E+03 MW-30-84 MW-30-84 Q3-2010 Mid 026 83.8

-8.1 9/8/2010 13:14 1.01E+04 4.32E+02 2.10E+02 3.18E-01 6.20E-01 7.05E-01

-1.48E+00 6.18E+00 6.74E+00

-4.19E-01 7.65E+00 8.58E+00 NA NA NA 9.12E+03 MW-30-84 MW-30-84 Q4-2010 027 83.8

-8.1 11/5/2010 12:35 1.02E+04 4.80E+02 3.87E+02 5.25E-01 7.56E-01 1.70E+00

-3.07E+00 4.23E+00 8.38E+00

-5.22E+00 4.86E+00 8.20E+00 NA NA NA 9.12E+03 MW-30-84 MW-30-84 Q1-2011 028 83.8

-8.1 2/9/2011 12:57 9.20E+03 8.86E+02 3.79E+02 1.12E+00 1.82E+00 1.98E+00 5.89E-01 4.74E+00 5.22E+00 1.09E+00 5.76E+00 6.49E+00 NA NA NA 9.12E+03 MW-30-84 MW-30-84 Q1-2011 Mid 029 83.8

-8.1 3/31/2011 12:03 9.04E+03 1.06E+03 4.74E+02

-4.78E-01 1.66E+00 2.13E+00 5.00E-01 1.12E+01 1.21E+01

-3.04E+00 9.48E+00 9.12E+00 NA NA NA 9.12E+03 MW-30-84 MW-30-84 Q2-2011 030 83.8

-8.1 5/5/2011 12:58 7.57E+03 9.46E+02 3.92E+02 1.64E-01 1.15E+00 1.40E+00 3.00E+00 8.04E+00 9.35E+00 4.65E-02 7.14E+00 7.76E+00 NA NA NA 9.12E+03 MW-30-84 MW-30-84 Q2-2011 Mid 031 83.8

-8.1 7/11/2011 12:45 7.55E+03 1.08E+03 2.82E+02

-3.75E-01 9.75E-01 1.29E+00 2.17E-01 7.89E+00 8.89E+00 1.39E+01 1.16E+01 1.59E+01 NA NA NA 9.12E+03 MW-30-84 MW-31-49 Q3-2010 025 48.8 26.8 7/27/2010 14:43 5.46E+04 1.59E+03 1.21E+02 3.05E-01 4.71E-01 5.22E-01 2.74E+00 1.17E+01 1.40E+01 2.23E+00 8.03E+00 9.96E+00 NA NA NA 2.90E+04 ND ND ND NA MW-31-49 MW-31-49 Q3-2010 026 48.8 26.8 8/23/2010 12:11 4.11E+03 3.56E+02 1.23E+02 1.62E-01 7.89E-01 9.57E-01

-1.21E+00 5.42E+00 5.91E+00

-3.35E-02 5.19E+00 5.80E+00 NA NA NA 2.90E+04 MW-31-49 MW-31-49 Q3-2010 Mid 027 48.8 26.8 9/7/2010 13:49 1.04E+05 3.02E+03 1.68E+02

-1.15E-01 2.82E-01 4.23E-01 3.35E+00 5.52E+00 6.68E+00 2.16E+00 5.97E+00 7.20E+00 NA NA NA 2.90E+04 MW-31-49 MW-31-49 Q4-2010 028 48.8 26.8 11/3/2010 11:55 3.35E+04 9.81E+02 1.15E+02

-3.04E-02 4.26E-01 5.51E-01

-2.82E+00 8.51E+00 8.97E+00 2.22E+00 8.87E+00 1.06E+01 NA NA NA 2.90E+04 MW-31-49 MW-31-49 Q1-2011 029 48.8 26.8 2/9/2011 13:12 1.06E+03 3.40E+02 2.98E+02

-5.51E-01 1.76E+00 2.14E+00 1.39E+00 5.22E+00 6.02E+00 4.84E-01 5.26E+00 5.91E+00 NA NA NA 2.90E+04 MW-31-49 MW-31-49 Q1-2011 Mid 030 48.8 26.8 3/30/2011 12:33 4.31E+03 7.84E+02 4.65E+02 1.77E+00 2.04E+00 2.16E+00

-2.34E+00 7.80E+00 8.17E+00

-5.38E-01 9.18E+00 1.00E+01 NA NA NA 2.90E+04 MW-31-49 MW-31-49 Q2-2011 031 48.8 26.8 4/18/2011 12:53 1.08E+03 5.20E+02 4.66E+02 4.98E-01 1.81E+00 2.09E+00

-1.82E+00 8.82E+00 9.22E+00 6.17E+00 8.70E+00 1.13E+01 NA NA NA 2.90E+04 MW-31-49 MW-31-63 Q3-2010 025 63.3 12.3 7/27/2010 15:54 6.17E+04 1.80E+03 1.27E+02 5.31E-01 6.45E-01 6.89E-01

-1.81E+00 8.27E+00 8.91E+00 1.22E+00 7.33E+00 8.70E+00 NA NA NA 3.72E+04 ND ND ND NA MW-31-63 MW-31-63 Q3-2010 026 63.3 12.3 8/23/2010 13:11 6.69E+04 1.95E+03 1.60E+02 4.60E-01 7.62E-01 8.48E-01 1.77E+00 6.11E+00 7.13E+00

-1.67E+00 6.17E+00 6.44E+00 NA NA NA 3.72E+04 MW-31-63 MW-31-63 Q3-2010 Mid 027 63.3 12.3 9/7/2010 15:28 4.65E+04 1.41E+03 1.46E+02 3.99E-01 7.26E-01 8.18E-01 4.05E-01 4.75E+00 5.31E+00

-1.47E+00 5.45E+00 5.56E+00 NA NA NA 3.72E+04 MW-31-63 MW-31-63 Q4-2010 028 63.3 12.3 11/3/2010 12:32 2.95E+04 9.02E+02 1.14E+02 3.31E-01 6.30E-01 7.13E-01

-2.24E+00 9.63E+00 1.02E+01 3.44E+00 8.40E+00 1.07E+01 NA NA NA 3.72E+04 MW-31-63 MW-31-63 Q1-2011 029 63.3 12.3 2/9/2011 13:14 2.46E+04 1.10E+03 2.98E+02 4.29E-01 1.78E+00 2.08E+00

-1.42E+00 6.46E+00 6.81E+00

-2.31E+00 6.42E+00 6.26E+00 NA NA NA 3.72E+04 MW-31-63 MW-31-63 Q1-2011 Mid 030 63.3 12.3 3/30/2011 13:13 1.33E+04 1.14E+03 4.53E+02 1.49E+00 1.87E+00 2.02E+00 8.76E-01 9.00E+00 9.97E+00

-1.92E-01 7.26E+00 7.92E+00 NA NA NA 3.72E+04 MW-31-63 MW-31-63 Q2-2011 031 63.3 12.3 4/18/2011 13:21 1.81E+04 1.45E+03 4.67E+02 7.26E-01 1.84E+00 2.08E+00

-3.10E-01 7.62E+00 8.46E+00 1.76E+00 8.74E+00 1.03E+01 NA NA NA 3.72E+04 MW-31-63 MW-31-85 Q3-2010 025 84.8

-9.2 7/27/2010 15:22 6.70E+03 4.34E+02 1.00E+02 3.55E-01 4.72E-01 5.04E-01

-3.98E+00 8.82E+00 9.22E+00 2.50E+00 8.43E+00 9.93E+00 NA NA NA 4.68E+03 ND ND ND NA MW-31-85 MW-31-85 Q3-2010 026 84.8

-9.2 8/23/2010 12:10 5.07E+03 3.96E+02 1.25E+02 6.61E-03 7.89E-01 9.16E-01 3.42E+00 4.95E+00 6.08E+00 1.52E+00 4.77E+00 5.71E+00 NA NA NA 4.68E+03 MW-31-85 MW-31-85 Q3-2010 Mid 027 84.8

-9.2 9/7/2010 14:14 6.21E+03 5.24E+02 1.44E+02

-3.25E-01 4.45E-01 6.85E-01

-1.54E+00 5.68E+00 6.11E+00 2.71E+00 6.42E+00 7.79E+00 NA NA NA 4.68E+03 MW-31-85 MW-31-85 Q4-2010 028 84.8

-9.2 11/3/2010 12:00 6.06E+03 4.16E+02 1.14E+02 2.41E-01 4.83E-01 5.47E-01

-1.36E+00 8.88E+00 9.62E+00

-2.66E-01 1.08E+01 1.19E+01 NA NA NA 4.68E+03 MW-31-85 MW-31-85 Q1-2011 029 84.8

-9.2 2/9/2011 13:03 4.83E+03 6.84E+02 3.82E+02 3.26E-01 1.79E+00 2.18E+00 3.19E+00 5.96E+00 7.08E+00 3.14E+00 6.06E+00 7.39E+00 NA NA NA 4.68E+03 MW-31-85 MW-31-85 Q1-2011 Mid 030 84.8

-9.2 3/30/2011 12:55 7.75E+02 4.66E+02 4.52E+02 9.37E-01 1.81E+00 2.00E+00 5.90E+00 1.31E+01 8.10E+00 6.43E+00 8.88E+00 1.17E+01 NA NA NA 4.68E+03 MW-31-85 MW-31-85 Q2-2011 031 84.8

-9.2 4/18/2011 13:18 3.08E+03 6.96E+02 4.66E+02

-1.09E+00 1.46E+00 2.09E+00

-4.50E+00 9.34E+00 9.19E+00 3.84E+00 1.01E+01 1.22E+01 NA NA NA 4.68E+03 MW-31-85 MW-32-48 Q3-2010 007 7/27/2010 12:52 3.69E+03 3.26E+02 9.94E+01 3.59E-01 8.37E-01 9.60E-01 1.54E-01 7.00E+00 8.04E+00

-3.86E+00 7.74E+00 7.51E+00 NA NA NA 4.80E+03 ND ND ND NA MW-32-48 MW-32-48 Q3-2010 008 8/24/2010 14:03 5.90E+03 3.51E+02 2.10E+02 3.55E-01 6.33E-01 7.09E-01

-4.34E-01 4.49E+00 5.04E+00 1.96E+00 4.95E+00 5.95E+00 NA NA NA 4.80E+03 MW-32-48 MW-32-59 Q3-2010 019 58.8 18.3 7/27/2010 13:00 6.54E+04 1.91E+03 1.33E+02 1.50E-01 4.37E-01 5.21E-01 1.07E+00 1.02E+01 1.14E+01 3.80E+00 9.26E+00 1.21E+01 NA NA NA 2.90E+04 ND ND ND NA MW-32-59 MW-32-59 Q3-2010 020 58.8 18.3 8/24/2010 14:22 5.78E+03 3.48E+02 2.10E+02

-9.82E-02 6.14E-01 8.32E-01 3.21E+00 5.84E+00 7.14E+00

-2.01E+00 6.60E+00 6.75E+00 NA NA NA 2.90E+04 MW-32-59 MW-32-59 Q3-2010 Mid 021 58.8 18.3 9/9/2010 13:57 7.44E+04 2.18E+03 1.67E+02 4.21E-01 7.20E-01 8.03E-01 1.68E+00 5.43E+00 6.39E+00

-1.58E+00 5.38E+00 5.54E+00 NA NA NA 2.90E+04 MW-32-59 MW-32-59 Q4-2010 022 58.8 18.3 11/3/2010 12:08 1.58E+04 6.66E+02 1.16E+02 2.02E-01 6.15E-01 7.14E-01 6.67E+00 7.98E+00 1.03E+01 1.19E+00 9.11E+00 1.06E+01 NA NA NA 2.90E+04 MW-32-59 MW-32-59 Q1-2011 023 58.8 18.3 3/1/2011 11:28 4.39E+03 6.42E+02 3.59E+02 1.25E+00 1.49E+00 1.55E+00 6.56E-01 5.82E+00 6.63E+00

-4.41E-01 7.00E+00 7.58E+00 NA NA NA 2.90E+04 MW-32-59 MW-32-59 Q1-2011 Mid 024 58.8 18.3 3/31/2011 12:46 3.37E+04 1.96E+03 5.07E+02

-2.13E-01 1.15E+00 1.51E+00 8.24E-01 8.92E+00 9.96E+00 1.99E-02 1.02E+01 1.11E+01 NA NA NA 2.90E+04 MW-32-59 MW-32-59 Q2-2011 025 58.8 18.3 4/27/2011 12:26 3.31E+03 6.36E+02 4.08E+02 4.03E-01 1.50E+00 1.74E+00 4.77E+00 8.64E+00 1.04E+01

-3.37E+00 9.58E+00 9.50E+00 NA NA NA 2.90E+04 MW-32-59 MW-32-85 Q3-2010 022 85.3 85.3 7/27/2010 14:51 1.21E+04 5.81E+02 1.01E+02 3.80E-01 6.37E-01 7.07E-01 1.38E+00 7.47E+00 8.69E+00 2.30E+00 7.74E+00 9.52E+00 NA NA NA 1.33E+04 ND ND ND NA MW-32-85 MW-32-85 Q3-2010 023 85.3 85.3 8/24/2010 11:03 1.38E+04 4.94E+02 2.10E+02

-3.76E-01 4.75E-01 7.02E-01

-6.66E-01 5.96E+00 6.62E+00

-1.19E+00 5.22E+00 5.48E+00 NA NA NA 1.33E+04 MW-32-85 MW-32-85 Q3-2010 Mid 024 85.3 85.3 9/9/2010 15:29 1.44E+04 6.57E+02 1.27E+02 1.34E-01 6.77E-01 8.36E-01 1.43E+00 6.27E+00 6.90E+00

-1.25E-01 5.49E+00 6.10E+00 NA NA NA 1.33E+04 MW-32-85 MW-32-85 Q4-2010 025 85.3 85.3 11/3/2010 12:45 1.49E+04 6.48E+02 1.16E+02 3.80E-01 4.90E-01 5.36E-01 5.89E+00 9.60E+00 1.18E+01

-5.55E+00 8.71E+00 7.61E+00 NA NA NA 1.33E+04 MW-32-85 MW-32-85 Q1-2011 026 85.3 85.3 3/1/2011 12:05 1.34E+04 1.41E+03 2.62E+02 3.81E-01 1.41E+00 1.63E+00 7.79E-01 8.26E+00 9.36E+00 4.73E+00 9.72E+00 1.24E+01 NA NA NA 1.33E+04 MW-32-85 MW-32-85 Q1-2011 Mid 027 85.3 85.3 3/31/2011 13:18 1.32E+04 1.27E+03 5.07E+02

-1.62E-01 1.20E+00 1.56E+00

-6.56E-01 7.26E+00 7.61E+00 3.80E+00 8.28E+00 1.02E+01 NA NA NA 1.33E+04 MW-32-85 MW-32-85 Q2-2011 028 85.3 85.3 4/27/2011 13:04 1.14E+04 1.19E+03 5.10E+02 1.58E+00 1.69E+00 1.75E+00

-1.23E+00 6.80E+00 7.31E+00 5.30E-01 1.02E+01 1.15E+01 NA NA NA 1.33E+04 MW-32-85 MW-32-149 Q3-2010 019 149.3

-72.2 7/27/2010 15:34 3.81E+03 3.33E+02 1.01E+02 1.14E-01 3.57E-01 4.33E-01 7.24E-01 1.28E+01 1.64E+01 1.53E+00 8.88E+00 1.06E+01 NA NA NA 1.84E+03 ND ND ND NA MW-32-149 MW-32-149 Q3-2010 020 149.3

-72.2 8/24/2010 11:27 2.60E+03 2.70E+02 2.10E+02 1.04E-01 6.64E-01 8.13E-01 1.04E-01 6.51E+00 7.44E+00 2.67E-02 5.89E+00 6.71E+00 NA NA NA 1.84E+03 MW-32-149 MW-32-149 Q3-2010 Mid 021 149.3

-72.2 9/9/2010 11:36 2.12E+03 2.70E+02 1.27E+02 2.27E-01 7.72E-01 9.22E-01 3.68E+00 7.83E+00 9.16E+00 1.24E+00 8.52E+00 1.00E+01 NA NA NA 1.84E+03 MW-32-149 MW-32-149 Q4-2010 022 149.3

-72.2 11/3/2010 16:09 1.55E+03 2.24E+02 1.12E+02 4.08E-01 5.02E-01 5.49E-01

-1.00E+01 1.08E+01 1.15E+01 3.36E+00 7.71E+00 9.94E+00 NA NA NA 1.84E+03 MW-32-149 MW-32-149 Q1-2011 023 149.3

-72.2 3/1/2011 13:37 1.06E+03 4.48E+02 2.68E+02

-7.01E-01 1.66E+00 2.15E+00 9.25E-01 5.42E+00 6.30E+00 2.06E+00 6.60E+00 7.93E+00 NA NA NA 1.84E+03 MW-32-149 MW-32-149 Q1-2011 Mid 024 149.3

-72.2 3/31/2011 11:33 8.99E+02 5.34E+02 5.09E+02

-2.01E-01 1.10E+00 1.49E+00 2.52E+00 9.30E+00 1.09E+01 2.31E+00 9.92E+00 1.18E+01 NA NA NA 1.84E+03 MW-32-149 MW-32-149 Q2-2011 025 149.3

-72.2 4/27/2011 11:12 8.69E+02 4.44E+02 4.11E+02 3.00E-01 1.43E+00 1.67E+00 2.12E+00 7.44E+00 8.59E+00 9.88E-01 7.76E+00 8.83E+00 NA NA NA 1.84E+03 MW-32-149 MW-32-173 Q3-2010 017 172.8

-95.7 7/27/2010 15:17 2.47E+03 2.69E+02 9.88E+01 9.64E-02 3.38E-01 4.14E-01

-1.51E+00 8.71E+00 9.65E+00

-2.29E+00 7.04E+00 7.12E+00 NA NA NA 1.48E+03 ND ND ND NA MW-32-173 MW-32-173 Q3-2010 018 172.8

-95.7 8/24/2010 11:23 2.19E+03 2.60E+02 2.10E+02

-1.37E-01 3.98E-01 5.77E-01 2.92E+00 6.57E+00 7.82E+00 4.56E-01 6.55E+00 7.41E+00 NA NA NA 1.48E+03 MW-32-173 MW-32-173 Q3-2010 Mid 019 172.8

-95.7 9/9/2010 11:29 1.98E+03 2.63E+02 1.28E+02 5.82E-01 8.34E-01 8.96E-01 1.67E+00 4.86E+00 5.81E+00 9.94E-01 4.84E+00 5.77E+00 NA NA NA 1.48E+03 MW-32-173 MW-32-173 Q4-2010 020 172.8

-95.7 11/3/2010 15:53 1.40E+03 2.16E+02 1.14E+02 1.65E-02 4.38E-01 5.24E-01 3.87E+00 1.76E+01 9.62E+00

-2.94E+00 9.88E+00 1.01E+01 NA NA NA 1.48E+03 MW-32-173 MW-32-173 Q1-2011 021 172.8

-95.7 3/1/2011 13:13 9.02E+02 4.12E+02 2.61E+02

-4.04E-01 1.12E+00 1.45E+00 5.99E+00 6.06E+00 7.73E+00

-2.04E+00 7.36E+00 7.55E+00 NA NA NA 1.48E+03 MW-32-173 MW-32-173 Q1-2011 Mid 022 172.8

-95.7 3/31/2011 11:35 8.41E+02 5.22E+02 5.04E+02 2.46E-01 1.27E+00 1.54E+00 6.51E+00 1.58E+01 8.26E+00 2.19E+00 8.22E+00 9.98E+00 NA NA NA 1.48E+03 MW-32-173 MW-32-173 Q2-2011 023 172.8

-95.7 4/27/2011 11:27 5.82E+02 4.98E+02 5.08E+02 6.37E-01 1.54E+00 1.74E+00 0.00E+00 2.00E+01 9.23E+00 2.47E-01 9.58E+00 1.07E+01 NA NA NA 1.48E+03 MW-32-173 MW-32-190 Q3-2010 021 190.3

-113.7 7/27/2010 15:41 1.58E+03 2.21E+02 9.83E+01

-8.57E-02 3.52E-01 5.06E-01 6.23E-01 7.98E+00 9.16E+00

-2.62E+00 7.77E+00 7.60E+00 NA NA NA 1.53E+03 ND ND ND NA MW-32-190 MW-32-190 Q3-2010 022 190.3

-113.7 8/24/2010 11:37 1.69E+03 2.43E+02 2.09E+02 2.54E-01 7.84E-01 9.25E-01

-5.47E-01 4.84E+00 5.45E+00 9.00E-01 4.96E+00 5.87E+00 NA NA NA 1.53E+03 MW-32-190 MW-32-190 Q3-2010 Mid 023 190.3

-113.7 9/9/2010 11:34 1.65E+03 2.48E+02 1.30E+02

-1.31E-01 5.85E-01 8.27E-01

-2.39E-01 9.87E+00 1.08E+01 2.00E+00 6.66E+00 7.98E+00 NA NA NA 1.53E+03 MW-32-190 MW-32-190 Q4-2010 024 190.3

-113.7 11/3/2010 16:07 1.53E+03 2.28E+02 1.17E+02

-9.74E-02 4.35E-01 5.82E-01 2.12E+00 9.02E+00 1.07E+01

-2.40E+00 9.21E+00 9.36E+00 NA NA NA 1.53E+03 MW-32-190 MW-32-190 Q1-2011 025 190.3

-113.7 3/1/2011 13:24 1.64E+03 5.32E+02 2.64E+02 7.65E-01 1.20E+00 1.29E+00 2.74E+00 5.52E+00 6.57E+00 4.88E+00 7.64E+00 8.75E+00 NA NA NA 1.53E+03 MW-32-190 MW-32-190 Q1-2011 Mid 026 190.3

-113.7 3/31/2011 11:47 1.41E+03 5.76E+02 5.02E+02

-7.79E-01 1.15E+00 1.67E+00 8.78E-01 7.96E+00 9.01E+00 5.11E+00 1.04E+01 1.30E+01 NA NA NA 1.53E+03 MW-32-190 MW-32-190 Q2-2011 027 190.3

-113.7 4/27/2011 11:17 1.21E+03 5.64E+02 5.10E+02 7.54E-01 1.13E+00 1.20E+00 8.61E-01 8.68E+00 9.74E+00

-6.60E+00 8.98E+00 6.37E+00 NA NA NA 1.53E+03 MW-32-190 MW-33 Q3-2010 027 19.2

-0.4 8/30/2010 14:29 3.69E+03 3.42E+02 1.26E+02 1.64E-01 3.24E-01 3.69E-01 7.72E-01 5.64E+00 6.38E+00

-3.08E-01 5.07E+00 5.60E+00 NA NA NA 3.78E+03 ND ND ND NA MW-33 MW-33 Q3-2010 Mid 028 19.2

-0.4 9/11/2010 13:28 3.86E+03 3.53E+02 1.27E+02 9.96E-03 7.38E-01 9.28E-01

-1.30E+00 4.86E+00 5.14E+00 1.12E+00 5.10E+00 5.95E+00 NA NA NA 3.78E+03 MW-33 MW-36-24 Q3-2010 019 16.1

-4.3 7/29/2010 12:04 2.64E+02 1.17E+02 1.00E+02 2.45E-01 3.84E-01 4.23E-01 8.89E-01 9.88E+00 1.10E+01

-2.61E+00 1.19E+01 1.26E+01 NA NA NA 1.98E+03 ND ND ND NA MW-36-24 MW-36-24 Q4-2010 020 16.1

-4.3 11/4/2010 16:15 2.62E+03 2.82E+02 1.13E+02 3.79E-01 5.81E-01 6.42E-01 3.42E+00 9.88E+00 1.17E+01

-1.80E+00 1.16E+01 1.26E+01 NA NA NA 1.98E+03 MW-36-24 MW-36-24 Q1-2011 021 16.1

-4.3 2/28/2011 12:37 2.56E+02 3.54E+02 3.81E+02

-8.87E-02 1.67E+00 2.08E+00 4.53E-01 5.26E+00 5.75E+00

-3.09E-01 4.74E+00 5.03E+00 NA NA NA 1.98E+03 MW-36-24 MW-36-24 Q2-2011 022 16.1

-4.3 4/28/2011 14:34 3.07E+03 7.26E+02 5.19E+02 1.38E+00 1.53E+00 1.59E+00

-6.43E-01 7.68E+00 8.47E+00 2.82E+00 7.48E+00 9.35E+00 NA NA NA 1.98E+03 MW-36-24 MW-36-41 Q3-2010 013 37

-25.2 7/29/2010 12:23 1.30E+04 7.52E+02 1.46E+02 1.88E+00 7.41E-01 5.17E-01

-1.84E+00 6.35E+00 6.48E+00 4.07E+00 6.12E+00 7.75E+00 NA NA NA 1.05E+04 3.21E+00 ND ND NA MW-36-41 MW-36-41 Q4-2010 014 37

-25.2 11/4/2010 16:55 1.22E+04 5.75E+02 1.10E+02 3.54E+00 9.13E-01 6.12E-01 7.62E-01 8.76E+00 1.01E+01 3.09E+00 8.58E+00 1.06E+01 NA NA NA 1.05E+04 3.21E+00 MW-36-41 MW-36-41 Q1-2011 015 37

-25.2 2/28/2011 13:53 8.74E+03 6.88E+02 2.97E+02 4.11E+00 1.87E+00 1.57E+00 1.31E+00 5.26E+00 6.09E+00 1.58E+00 5.68E+00 6.65E+00 NA NA NA 1.05E+04 3.21E+00 MW-36-41 MW-36-41 Q2-2011 016 37

-25.2 4/28/2011 15:39 8.17E+03 1.04E+03 5.14E+02 3.31E+00 1.75E+00 1.36E+00 2.18E+00 9.26E+00 1.07E+01

-2.96E-01 1.04E+01 1.12E+01 NA NA NA 1.05E+04 3.21E+00 MW-36-41 MW-36-52 Q3-2010 018 49.7

-37.9 7/29/2010 12:24 7.07E+03 4.46E+02 1.00E+02

-1.52E-01 6.33E-01 8.23E-01

-1.63E+00 7.79E+00 8.33E+00

-1.74E+00 9.63E+00 1.03E+01 NA NA NA 5.78E+03 4.07E+00 ND ND NA MW-36-52 MW-36-52 Q4-2010 019 49.7

-37.9 11/4/2010 15:55 7.08E+03 4.40E+02 1.10E+02 4.73E+00 1.11E+00 6.76E-01 1.15E-01 5.89E+00 6.52E+00

-2.28E+00 7.92E+00 7.79E+00 NA NA NA 5.78E+03 4.07E+00 MW-36-52 MW-36-52 Q1-2011 020 49.7

-37.9 2/28/2011 12:43 3.14E+03 4.92E+02 3.37E+02 1.33E+00 2.00E+00 2.14E+00

-6.00E+00 5.58E+00 4.80E+00

-2.66E+00 5.94E+00 5.65E+00 NA NA NA 5.78E+03 4.07E+00 MW-36-52 MW-36-52 Q2-2011 021 49.7

-37.9 4/28/2011 14:38 5.84E+03 9.06E+02 5.15E+02 3.41E+00 1.56E+00 1.11E+00 4.29E+00 8.42E+00 1.03E+01

-2.61E+00 8.50E+00 8.36E+00 NA NA NA 5.78E+03 4.07E+00 MW-36-52 MW-37-22 Q3-2010 019 17

-2 8/5/2010 14:06 3.70E+03 3.26E+02 9.90E+01 5.19E+00 1.39E+00 9.19E-01

-1.60E+00 7.62E+00 8.20E+00 4.53E+00 7.13E+00 9.76E+00 NA NA NA 5.44E+03 9.53E+00 ND ND NA MW-37-22 MW-37-22 Q4-2010 020 17

-2 11/4/2010 14:28 4.46E+03 3.57E+02 1.12E+02 1.38E+01 1.33E+00 5.33E-01

-2.26E+00 7.33E+00 7.68E+00

-1.24E+00 9.31E+00 1.00E+01 NA NA NA 5.44E+03 9.53E+00 MW-37-22 MW-37-22 Q1-2011 021 17

-2 1/27/2011 15:19 6.74E+03 6.18E+02 2.98E+02 1.04E+01 2.52E+00 1.68E+00

-2.18E+00 4.74E+00 4.94E+00 2.59E+00 5.38E+00 6.55E+00 NA NA NA 5.44E+03 9.53E+00 MW-37-22 MW-37-22 Q2-2011 022 17

-2 4/28/2011 12:05 6.87E+03 9.66E+02 5.14E+02 8.72E+00 2.90E+00 2.05E+00 7.12E-01 6.96E+00 7.67E+00 5.14E-01 7.86E+00 8.62E+00 NA NA NA 5.44E+03 9.53E+00 MW-37-22 MW-37-32 Q3-2010 019 29

-14 8/5/2010 14:00 4.80E+03 3.69E+02 9.97E+01 1.41E+01 1.85E+00 5.42E-01

-5.90E+00 8.89E+00 8.07E+00

-3.93E-01 8.67E+00 9.54E+00 NA NA NA 4.87E+03 1.84E+01 ND ND NA MW-37-32 MW-37-32 Q4-2010 020 29

-14 11/4/2010 13:14 5.99E+03 4.22E+02 1.17E+02

-2.91E-01 6.15E-01 7.91E-01

-4.11E+00 7.41E+00 7.07E+00 1.54E+00 7.68E+00 9.04E+00 NA NA NA 4.87E+03 1.84E+01 MW-37-32 MW-37-32 Q1-2011 021 29

-14 1/27/2011 15:09 4.57E+03 5.28E+02 2.98E+02 1.49E+01 3.02E+00 1.74E+00 4.20E-01 6.12E+00 6.85E+00 1.72E+00 6.60E+00 7.76E+00 NA NA NA 4.87E+03 1.84E+01 MW-37-32 MW-37-32 Q2-2011 022 29

-14 4/28/2011 12:21 4.11E+03 7.98E+02 5.15E+02 2.62E+01 3.76E+00 1.68E+00 3.56E+00 1.20E+01 1.42E+01

-1.92E+00 1.09E+01 1.09E+01 NA NA NA 4.87E+03 1.84E+01 MW-37-32 MW-37-40 Q3-2010 019 39.2

-24.2 8/5/2010 14:25 7.00E+03 4.43E+02 9.99E+01 1.43E+01 1.74E+00 4.81E-01 3.15E-01 7.86E+00 9.00E+00 3.82E+00 7.44E+00 9.31E+00 NA NA NA 5.83E+03 1.74E+01 ND ND NA MW-37-40 MW-37-40 Q4-2010 020 39.2

-24.2 11/4/2010 12:06 6.41E+03 4.29E+02 1.15E+02 1.28E+01 1.92E+00 6.32E-01 2.77E+00 8.58E+00 1.03E+01

-2.01E+00 8.29E+00 8.39E+00 NA NA NA 5.83E+03 1.74E+01 MW-37-40 MW-37-40 Q1-2011 021 39.2

-24.2 1/27/2011 13:35 5.97E+03 7.42E+02 3.82E+02 1.93E+01 3.34E+00 1.85E+00 1.95E+00 5.84E+00 6.78E+00 2.03E+00 6.84E+00 7.92E+00 NA NA NA 5.83E+03 1.74E+01 MW-37-40 MW-37-40 Q2-2011 022 39.2

-24.2 4/28/2011 11:31 3.92E+03 8.02E+02 5.33E+02 2.30E+01 3.66E+00 1.68E+00 4.10E+00 9.02E+00 1.09E+01 6.47E-01 8.94E+00 1.02E+01 NA NA NA 5.83E+03 1.74E+01 MW-37-40 MW-37-57 Q3-2010 019 53.2

-38.2 8/5/2010 13:59 7.30E+03 4.52E+02 9.94E+01 1.73E+01 1.69E+00 5.57E-01

-2.16E+00 7.37E+00 7.75E+00

-6.93E-01 8.96E+00 9.77E+00 NA NA NA 6.37E+03 1.83E+01 ND ND NA MW-37-57 MW-37-57 Q4-2010 020 53.2

-38.2 11/4/2010 13:49 6.72E+03 4.41E+02 1.15E+02 1.97E+01 2.15E+00 5.70E-01 6.72E+00 1.52E+01 9.04E+00

-3.60E+00 7.95E+00 7.35E+00 NA NA NA 6.37E+03 1.83E+01 MW-37-57 MW-37-57 Q1-2011 021 53.2

-38.2 1/27/2011 15:26 5.63E+03 5.76E+02 2.99E+02 2.02E+01 3.60E+00 1.96E+00

-3.70E-01 6.34E+00 6.92E+00

-1.36E+00 5.64E+00 5.68E+00 NA NA NA 6.37E+03 1.83E+01 MW-37-57 MW-37-57 Q2-2011 022 53.2

-38.2 4/28/2011 12:17 5.81E+03 8.98E+02 5.07E+02 1.58E+01 3.54E+00 2.00E+00 5.18E+00 1.72E+01 8.67E+00

-1.42E+00 8.36E+00 8.80E+00 NA NA NA 6.37E+03 1.83E+01 MW-37-57 ANALYSIS RESULTS5 YEARLY ROLLING AVERAGES4,6 Well ID1 TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

SAMPLE COLLECTION Well ID1 SAMPLING QUARTER2,8 SAMPLE ID SAMPLE ZONE CENTER Depth Ft Below Top of Casing3 SAMPLE ZONE CENTER Elevation Ft msl3

TABLE 3 SECOND QUARTER 2011 GROUNDWATER ANALYTICAL RESULTS AND AVERAGES INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q22011 FINAL Table 3 - Second Quarter 2011 Groundwater Analytical Results and Averages.xlsx; Q22011 Table 3 Page 2 of 6 See Page 6 for Notes TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Date Time Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Average Average Average Average Average ANALYSIS RESULTS5 YEARLY ROLLING AVERAGES4,6 Well ID1 TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

SAMPLE COLLECTION Well ID1 SAMPLING QUARTER2,8 SAMPLE ID SAMPLE ZONE CENTER Depth Ft Below Top of Casing3 SAMPLE ZONE CENTER Elevation Ft msl3 MW-39-67 Q3-2010 009 67 13 7/22/2010 14:26 2.86E+02 1.19E+02 9.90E+01 1.73E+00 6.00E-01 3.90E-01 2.94E+00 6.33E+00 7.80E+00

-5.65E+00 7.25E+00 5.04E+00 NA NA NA 4.48E+03 1.81E+00 ND ND NA MW-39-67 MW-39-67 Q4-2010 010 67 13 11/15/2010 16:28 3.74E+02 1.86E+02 3.88E+02 1.96E+00 9.36E-01 1.94E+00

-1.74E+00 3.99E+00 8.40E+00

-3.17E+00 4.38E+00 8.38E+00 NA NA NA 4.48E+03 1.81E+00 MW-39-67 MW-39-67 Q2-2011 011 67 13 4/26/2011 14:52 1.09E+04 9.64E+02 4.18E+02 1.74E+00 1.49E+00 1.50E+00

-8.12E-01 8.22E+00 8.78E+00

-4.05E+00 9.42E+00 9.00E+00 NA NA NA 4.48E+03 1.81E+00 MW-39-67 MW-39-67 Q2-2011 Mid 012 67 13 7/15/2011 13:42 2.24E+03 6.12E+02 4.40E+02 2.55E-01 1.16E+00 1.34E+00

-1.15E-01 8.28E+00 9.19E+00

-2.42E-02 9.72E+00 1.12E+01 NA NA NA 4.48E+03 1.81E+00 MW-39-67 MW-39-84 Q3-2010 009 83.5

-3.5 7/22/2010 14:42 3.70E+02 1.30E+02 1.01E+02 8.43E-01 6.21E-01 5.85E-01

-3.32E+00 6.79E+00 6.90E+00 2.43E+00 6.95E+00 8.54E+00 NA NA NA 4.05E+02 8.43E-01 ND ND NA MW-39-84 MW-39-84 Q4-2010 010 83.5

-3.5 11/15/2010 16:38 2.51E+02 2.10E+02 4.59E+02 1.80E+00 8.83E-01 1.86E+00 3.58E+00 4.41E+00 1.05E+01 7.47E+00 4.82E+00 1.24E+01 NA NA NA 4.05E+02 8.43E-01 MW-39-84 MW-39-84 Q2-2011 011 83.5

-3.5 4/26/2011 14:25 4.40E+02 4.02E+02 4.13E+02

-2.03E-01 1.15E+00 1.50E+00

-9.39E-01 7.42E+00 7.84E+00

-4.02E-01 6.92E+00 7.41E+00 NA NA NA 4.05E+02 8.43E-01 MW-39-84 MW-39-84 Q2-2011 Mid 012 83.5

-3.5 7/15/2011 14:33 3.55E+02 4.17E+02 4.40E+02 6.54E-01 1.15E+00 1.27E+00

-1.78E+00 1.43E+01 1.71E+01

-4.89E+00 9.45E+00 8.20E+00 NA NA NA 4.05E+02 8.43E-01 MW-39-84 MW-39-102 Q3-2010 009 101.5

-21.5 7/22/2010 14:52 2.39E+02 1.49E+02 1.49E+02 4.05E+00 9.93E-01 4.71E-01

-1.08E+00 6.35E+00 6.98E+00

-3.68E+00 5.55E+00 4.42E+00 NA NA NA 8.98E+03 4.05E+00 4.48E+01 ND NA MW-39-102 MW-39-102 Q4-2010 010 101.5

-21.5 11/15/2010 16:12 3.61E+02 1.83E+02 3.84E+02 1.40E+00 9.00E-01 1.93E+00 2.98E+00 3.38E+00 8.21E+00

-4.12E+00 3.52E+00 6.23E+00 NA NA NA 8.98E+03 4.05E+00 4.48E+01 MW-39-102 MW-39-102 Q2-2011 011 101.5

-21.5 4/26/2011 14:33 1.43E+04 1.09E+03 4.19E+02 1.08E+00 1.85E+00 2.03E+00 4.48E+01 2.08E+01 9.86E+00 6.03E+00 7.96E+00 1.07E+01 NA NA NA 8.98E+03 4.05E+00 4.48E+01 MW-39-102 MW-39-102 Q2-2011 Mid 012 101.5

-21.5 7/15/2011 14:02 1.24E+04 1.20E+03 4.36E+02 5.88E-01 1.09E+00 1.20E+00 3.70E+00 8.76E+00 1.02E+01

-6.84E-01 9.42E+00 9.35E+00 NA NA NA 8.98E+03 4.05E+00 4.48E+01 MW-39-102 MW-39-124 Q3-2010 009 124

-44 7/22/2010 11:39 1.12E+02 1.34E+02 1.46E+02 2.25E+00 7.71E-01 5.01E-01

-1.11E+00 8.32E+00 9.28E+00

-4.37E-01 9.75E+00 1.10E+01 NA NA NA ND 2.25E+00 9.13E+00 ND NA MW-39-124 MW-39-124 Q4-2010 010 124

-44 11/15/2010 12:46 3.73E+02 1.83E+02 3.86E+02 1.17E+00 8.85E-01 1.93E+00

-6.40E+00 6.71E+00 1.61E+01

-1.31E-01 4.98E+00 1.10E+01 NA NA NA 2.25E+00 9.13E+00 MW-39-124 MW-39-124 Q2-2011 011 124

-44 4/26/2011 13:01 1.51E+02 3.70E+02 4.15E+02 5.20E-01 1.37E+00 1.55E+00 9.13E+00 8.56E+00 8.57E+00 3.07E+00 7.52E+00 9.27E+00 NA NA NA 2.25E+00 9.13E+00 MW-39-124 MW-39-124 Q2-2011 Mid 012 124

-44 7/15/2011 11:44 2.30E+01 3.72E+02 4.39E+02 8.78E-01 1.19E+00 1.27E+00

-4.10E+00 1.13E+01 1.15E+01

-1.82E+00 9.51E+00 9.57E+00 NA NA NA 2.25E+00 9.13E+00 MW-39-124 MW-39-183 Q3-2010 009 182.5

-102.5 7/22/2010 11:38 1.07E+02 1.12E+02 1.19E+02 2.08E-01 4.19E-01 4.79E-01

-4.62E+00 8.88E+00 9.01E+00

-5.09E+00 9.62E+00 8.98E+00 NA NA NA ND ND ND ND NA MW-39-183 MW-39-183 Q4-2010 010 182.5

-102.5 11/15/2010 12:53

-8.02E+01 1.61E+02 3.88E+02 4.19E-01 7.56E-01 1.77E+00 1.45E+00 4.83E+00 1.10E+01 3.58E+00 4.93E+00 1.19E+01 NA NA NA MW-39-183 MW-39-183 Q2-2011 011 182.5

-102.5 4/26/2011 11:35 1.15E+02 3.54E+02 4.02E+02 1.12E+00 1.56E+00 1.67E+00 6.46E+00 8.88E+00 1.09E+01

-1.52E+00 8.68E+00 8.94E+00 NA NA NA MW-39-183 MW-39-183 Q2-2011 Mid 012 182.5

-102.5 7/15/2011 11:49 7.02E+01 3.75E+02 4.35E+02 3.45E-01 1.03E+00 1.19E+00 2.51E+00 1.08E+01 1.22E+01

-2.37E+00 1.30E+01 1.37E+01 NA NA NA MW-39-183 MW-39-195 Q3-2010 009 195

-115 7/22/2010 12:10 9.26E+01 1.11E+02 1.20E+02 5.61E-01 5.70E-01 5.97E-01 7.86E-01 8.64E+00 9.43E+00

-9.78E-01 8.93E+00 9.62E+00 NA NA NA 5.62E+03 1.88E+00 ND ND NA MW-39-195 MW-39-195 Q4-2010 010 195

-115 11/15/2010 13:25 2.16E+02 1.86E+02 4.09E+02 1.52E-01 7.35E-01 1.73E+00

-3.21E+00 4.09E+00 6.54E+00 8.70E+00 4.38E+00 1.20E+01 NA NA NA 5.62E+03 1.88E+00 MW-39-195 MW-39-195 Q2-2011 011 195

-115 4/26/2011 12:38 7.04E+03 8.04E+02 4.20E+02 1.88E+00 1.75E+00 1.79E+00

-2.03E+00 1.11E+01 1.28E+01 4.62E+00 8.70E+00 1.13E+01 NA NA NA 5.62E+03 1.88E+00 MW-39-195 MW-39-195 Q2-2011 Mid 012 195

-115 7/15/2011 11:13 4.19E+03 7.56E+02 4.35E+02 1.10E+00 1.78E+00 1.93E+00 2.79E+00 8.46E+00 9.76E+00 6.38E-01 1.01E+01 1.08E+01 NA NA NA 5.62E+03 1.88E+00 MW-39-195 MW-40-27 Q3-2010 012 26.7 46.5 8/26/2010 14:42 1.93E+02 1.26E+02 1.24E+02 2.23E-01 6.54E-01 7.73E-01 1.95E+00 4.50E+00 5.46E+00

-1.03E+00 4.72E+00 5.12E+00 NA NA NA 2.00E+02 ND ND ND NA MW-40-27 MW-40-27 Q4-2010 013 26.7 46.5 11/29/2010 15:23 2.06E+02 1.49E+02 1.44E+02 1.10E-01 7.98E-01 9.63E-01 3.16E-01 3.38E+00 3.76E+00 1.01E+00 3.63E+00 4.18E+00 NA NA NA 2.00E+02 MW-40-27 MW-40-27 Q1-2011 014 26.7 46.5 3/8/2011 12:55 1.85E+02 2.56E+02 2.65E+02 1.58E-01 1.37E+00 1.61E+00 3.72E-01 6.78E+00 7.39E+00 2.83E+00 8.56E+00 9.99E+00 NA NA NA 2.00E+02 MW-40-27 MW-40-27 Q2-2011 015 26.7 46.5 4/29/2011 13:29 1.77E+02 3.66E+02 4.07E+02 1.18E+00 1.74E+00 1.87E+00 1.91E+00 8.40E+00 9.77E+00

-9.20E-01 9.86E+00 1.15E+01 NA NA NA 2.00E+02 MW-40-27 MW-40-27 Q2-2011 Mid 016 26.7 46.5 7/27/2011 15:12 3.69E+01 3.00E+02 3.43E+02

-4.37E-01 1.40E+00 1.93E+00

-2.18E+00 7.35E+00 7.64E+00 1.36E+00 9.03E+00 1.03E+01 NA NA NA 2.00E+02 MW-40-27 MW-40-46**

Q3-2010 013 46.2 27 8/26/2010 14:56 1.24E+02 1.22E+02 1.29E+02

-1.83E-01 5.11E-01 7.19E-01 7.02E-01 6.01E+00 6.90E+00 5.48E+00 6.17E+00 8.30E+00 NA NA NA 1.63E+02 ND**

ND ND NA MW-40-46**

MW-40-46**

Q4-2010 014 46.2 27 11/29/2010 16:36 1.63E+02 1.47E+02 1.48E+02 6.60E-02 7.89E-01 9.38E-01 5.82E-01 3.82E+00 4.28E+00 2.06E+00 3.99E+00 4.74E+00 NA NA NA 1.63E+02 2.83E+00 MW-40-46**

MW-40-46**

Q1-2011 015 46.2 27 3/8/2011 12:58 2.48E+02 2.74E+02 2.63E+02 1.03E-01 8.58E-01 1.07E+00 2.82E+00 8.00E+00 9.18E+00 7.99E+00 8.74E+00 1.19E+01 NA NA NA 1.63E+02 2.83E+00 MW-40-46**

MW-40-46**

Q2-2011 016 46.2 27 4/29/2011 13:31 7.82E+01 3.54E+02 4.05E+02

-1.35E-01**

1.88E+00 1.77E+00

-9.96E-01 8.46E+00 9.00E+00

-3.98E+00 9.84E+00 9.04E+00 NA NA NA 1.63E+02 2.83E+00 MW-40-46**

MW-40-46**

Q2-2011 Mid 017 46.2 27 7/27/2011 15:55 1.35E+02 3.09E+02 3.44E+02

-9.06E-01 1.26E+00 1.86E+00 2.28E+00 8.85E+00 1.01E+01 5.01E-01 9.30E+00 1.03E+01 NA NA NA 1.63E+02 2.83E+00 MW-40-46**

MW-40-81 Q3-2010 013 80.7

-7.5 8/26/2010 11:05 9.08E+01 1.14E+02 1.24E+02 2.45E-01 5.25E-01 6.06E-01

-3.95E+00 5.24E+00 4.96E+00

-2.64E+00 4.68E+00 4.20E+00 NA NA NA 2.48E+02 ND ND ND NA MW-40-81 MW-40-81 Q4-2010 014 80.7

-7.5 11/29/2010 12:03 2.48E+02 1.58E+02 1.47E+02 1.13E-03 6.45E-01 7.85E-01

-9.67E-01 4.38E+00 4.79E+00

-4.37E-01 4.83E+00 5.28E+00 NA NA NA 2.48E+02 MW-40-81 MW-40-81 Q1-2011 015 80.7

-7.5 3/8/2011 10:17 2.33E+02 2.68E+02 2.63E+02 8.50E-01 1.51E+00 1.67E+00 1.26E+00 1.06E+01 7.71E+00

-1.45E+00 6.08E+00 6.16E+00 NA NA NA 2.48E+02 MW-40-81 MW-40-81 Q2-2011 016 80.7

-7.5 4/29/2011 11:08 3.39E+02 4.12E+02 4.36E+02 1.07E+00 1.58E+00 1.70E+00 3.05E+00 6.90E+00 8.51E+00

-2.66E-01 8.04E+00 8.83E+00 NA NA NA 2.48E+02 MW-40-81 MW-40-81 Q2-2011 Mid 017 80.7

-7.5 7/27/2011 13:24

-1.18E+02 2.89E+02 3.48E+02 8.36E-01 1.70E+00 1.90E+00

-3.22E-01 6.48E+00 6.87E+00

-1.05E+00 8.67E+00 8.91E+00 NA NA NA 2.48E+02 MW-40-81 MW-40-100*

Q3-2010 015 100.2

-27 8/26/2010 11:09 1.24E+02 1.37E+02 1.45E+02

-2.33E-01 3.95E-01 6.21E-01 8.87E-01 6.15E+00 7.12E+00 6.51E-01 5.61E+00 6.53E+00 NA NA NA ND ND ND*

ND NA MW-40-100*

MW-40-100*

Q4-2010 016 100.2

-27 11/29/2010 12:12 1.34E+02 1.40E+02 1.46E+02

-2.12E-01 6.70E-01 8.39E-01

-1.46E-01 4.05E+00 4.53E+00 3.11E-01 4.26E+00 4.81E+00 NA NA NA 2.46E+01 MW-40-100*

MW-40-100*

Q1-2011 017 100.2

-27 3/8/2011 10:27 5.17E+01 2.14E+02 2.64E+02 2.52E-02 1.30E+00 1.58E+00 2.46E+01*

1.35E+01 7.66E+00

-1.40E+00 7.88E+00 8.30E+00 NA NA NA 2.46E+01 MW-40-100*

MW-40-100*

Q2-2011 018 100.2

-27 4/29/2011 11:27 2.70E+02 4.06E+02 4.38E+02 2.46E-01 1.42E+00 1.67E+00 5.53E+00 7.14E+00 9.23E+00 2.99E+00 7.96E+00 9.80E+00 NA NA NA 2.46E+01 MW-40-100*

MW-40-100*

Q2-2011 Mid 019 100.2

-27 7/27/2011 13:29 1.07E+02 3.12E+02 3.50E+02

-9.50E-01 1.41E+00 1.98E+00 2.29E+00 9.03E+00 1.04E+01 7.10E-01 1.08E+01 1.20E+01 NA NA NA 2.46E+01 MW-40-100*

MW-40-127*

Q3-2010 015 127.2

-54 8/26/2010 11:16 1.36E+02 1.40E+02 1.47E+02 2.23E-02 2.78E-01 3.67E-01

-5.02E+00 7.95E+00 8.28E+00 6.43E-01 6.48E+00 7.48E+00 NA NA NA ND ND ND*

ND NA MW-40-127*

MW-40-127*

Q4-2010 016 127.2

-54 11/29/2010 12:26 1.22E+02 1.38E+02 1.45E+02 7.34E-01 9.02E-01 9.73E-01

-1.53E-01 4.82E+00 5.43E+00 1.12E+00 4.38E+00 5.06E+00 NA NA NA 5.07E+01 MW-40-127*

MW-40-127*

Q1-2011 017 127.2

-54 3/8/2011 10:41 1.33E+02 2.40E+02 2.64E+02 1.03E+00 1.40E+00 1.51E+00 5.07E+01*

1.64E+01 7.63E+00 3.45E-01 7.18E+00 7.96E+00 NA NA NA 5.07E+01 MW-40-127*

MW-40-127*

Q2-2011 018 127.2

-54 4/29/2011 11:26

-2.27E+01 3.60E+02 4.32E+02 5.72E-01 1.78E+00 2.05E+00

-2.13E-01 8.26E+00 8.83E+00

-1.62E+00 9.68E+00 9.87E+00 NA NA NA 5.07E+01 MW-40-127*

MW-40-127*

Q2-2011 Mid 019 127.2

-54 7/27/2011 13:56 1.56E+02 3.15E+02 3.50E+02 4.81E-01 1.64E+00 1.92E+00 1.48E+00 9.06E+00 1.03E+01

-8.00E+00 1.02E+01 7.94E+00 NA NA NA 5.07E+01 MW-40-127*

MW-40-162 Q3-2010 013 161.7

-88.5 8/26/2010 12:29 1.02E+02 1.36E+02 1.48E+02 5.09E-01 7.23E-01 7.75E-01 7.14E-01 6.23E+00 7.08E+00 3.52E+00 6.78E+00 8.38E+00 NA NA NA ND ND ND ND NA MW-40-162 MW-40-162 Q4-2010 014 161.7

-88.5 11/29/2010 12:45 6.40E+01 1.27E+02 1.45E+02

-5.51E-03 6.55E-01 7.94E-01 3.60E-01 4.34E+00 4.91E+00 3.43E-01 4.47E+00 5.03E+00 NA NA NA MW-40-162 MW-40-162 Q1-2011 015 161.7

-88.5 3/8/2011 11:02 8.33E+01 2.24E+02 2.63E+02

-1.03E+00 1.07E+00 1.57E+00

-3.72E+00 6.12E+00 5.93E+00

-2.11E+00 6.42E+00 6.37E+00 NA NA NA MW-40-162 MW-40-162 Q2-2011 016 161.7

-88.5 4/29/2011 12:26 1.05E+02 3.78E+02 4.33E+02 8.71E-01 1.34E+00 1.46E+00 4.54E+00 1.23E+01 1.42E+01 4.43E-01 9.50E+00 1.08E+01 NA NA NA MW-40-162 MW-40-162 Q2-2011 Mid 017 161.7

-88.5 7/27/2011 14:40 5.54E+00 2.97E+02 3.44E+02

-8.61E-01 1.58E+00 1.98E+00

-2.44E+00 9.21E+00 8.54E+00

-6.93E-01 8.70E+00 9.41E+00 NA NA NA MW-40-162 MW-41-40 Q3-2010 017 34.4 20.5 7/21/2010 13:41 2.79E+03 3.02E+02 1.47E+02 4.37E+00 1.02E+00 6.33E-01 1.59E+00 5.82E+00 7.07E+00

-6.50E-01 7.18E+00 7.61E+00 NA NA NA 2.49E+03 4.95E+00 ND ND NA MW-41-40 MW-41-40 Q4-2010 018 34.4 20.5 10/25/2010 16:06 2.43E+03 2.78E+02 1.17E+02 4.08E+00 1.16E+00 6.72E-01 3.32E+00 5.63E+00 6.87E+00

-1.99E+00 6.74E+00 6.96E+00 NA NA NA 2.49E+03 4.95E+00 MW-41-40 MW-41-40 Q1-2011 019 34.4 20.5 2/14/2011 14:05 2.03E+03 4.02E+02 2.98E+02 1.15E+01 2.68E+00 1.83E+00 4.60E+00 7.30E+00 8.61E+00 4.22E+00 7.36E+00 9.28E+00 NA NA NA 2.49E+03 4.95E+00 MW-41-40 MW-41-40 Q2-2011 020 34.4 20.5 4/20/2011 13:51 4.51E+03 7.36E+02 4.55E+02 2.32E+00 1.57E+00 1.44E+00 2.20E+00 9.22E+00 1.06E+01 3.02E+00 1.06E+01 1.25E+01 NA NA NA 2.49E+03 4.95E+00 MW-41-40 MW-41-40 Q2-2011 Mid 021 34.4 20.5 7/15/2011 12:30 6.99E+02 4.59E+02 4.41E+02 2.48E+00 1.35E+00 1.19E+00

-1.93E+00 1.09E+01 1.14E+01

-1.11E+00 8.94E+00 9.13E+00 NA NA NA 2.49E+03 4.95E+00 MW-41-40 MW-41-63 Q3-2010 016 59.5

-4.6 7/21/2010 13:41 5.18E+02 1.68E+02 1.43E+02 4.79E+00 1.09E+00 6.23E-01

-2.71E+00 8.29E+00 8.77E+00 1.61E+00 7.93E+00 9.59E+00 NA NA NA 7.45E+02 4.75E+00 ND ND NA MW-41-63 MW-41-63 Q4-2010 017 59.5

-4.6 10/25/2010 12:59 5.06E+02 1.50E+02 1.14E+02 4.25E+00 1.19E+00 7.17E-01 1.06E+00 6.08E+00 7.07E+00 2.87E+00 5.85E+00 7.23E+00 NA NA NA 7.45E+02 4.75E+00 MW-41-63 MW-41-63 Q1-2011 018 59.5

-4.6 2/14/2011 13:37 1.23E+03 4.44E+02 3.80E+02 6.92E+00 2.46E+00 1.96E+00 1.24E+00 5.30E+00 6.03E+00 2.69E+00 6.06E+00 7.29E+00 NA NA NA 7.45E+02 4.75E+00 MW-41-63 MW-41-63 Q2-2011 019 59.5

-4.6 4/20/2011 13:13 7.58E+02 4.90E+02 4.72E+02

-7.72E-01 1.51E+00 2.03E+00 3.53E+00 8.52E+00 1.01E+01 4.02E+00 8.74E+00 1.09E+01 NA NA NA 7.45E+02 4.75E+00 MW-41-63 MW-41-63 Q2-2011 Mid 020 59.5

-4.6 7/15/2011 12:51 7.14E+02 4.56E+02 4.35E+02 3.03E+00 1.50E+00 1.30E+00 2.36E+00 7.71E+00 8.88E+00 4.47E-01 6.81E+00 7.51E+00 NA NA NA 7.45E+02 4.75E+00 MW-41-63 MW-42-49 Q3-2010 022 42.6 27.1 7/30/2010 11:38 1.69E+03 2.34E+02 1.24E+02 1.39E+01 1.53E+00 3.90E-01 1.87E+04 2.46E+03 2.50E+01 7.33E-01 6.64E+00 7.77E+00 1.77E+02 2.97E+01 2.18E+01 1.54E+03 1.52E+01 2.43E+04 ND 2.23E+02 MW-42-49 MW-42-49 Q4-2010 023 42.6 27.1 10/27/2010 12:23 1.28E+03 2.03E+02 1.64E+02 1.81E+01 2.31E+00 8.72E-01 2.39E+04 2.94E+03 2.93E+01

-1.67E+00 9.77E+00 1.03E+01 2.24E+02 2.66E+01 2.10E+01 1.54E+03 1.52E+01 2.43E+04 2.23E+02 MW-42-49 MW-42-49 Q1-2011 024 42.6 27.1 3/4/2011 11:37 1.49E+03 5.14E+02 3.88E+02 2.32E+01 3.34E+00 1.11E+00 3.30E+04 4.42E+03 2.75E+01 1.42E+00 6.78E+00 7.87E+00 3.02E+02 3.04E+01 2.00E+01 1.54E+03 1.52E+01 2.43E+04 2.23E+02 MW-42-49 MW-42-49 Q2-2011 025 42.6 27.1 4/21/2011 14:04 1.71E+03 5.88E+02 4.80E+02 5.45E+00 2.18E+00 1.45E+00 2.15E+04 2.88E+03 2.08E+01 3.41E+00 9.16E+00 1.09E+01 1.90E+02 2.72E+01 1.73E+01 1.54E+03 1.52E+01 2.43E+04 2.23E+02 MW-42-49 MW-42-78 Q3-2010 017 74

-4.3 7/30/2010 12:23 6.31E+02 1.71E+02 1.31E+02 2.78E-02 3.03E-01 3.85E-01

-1.17E-01 7.56E+00 8.30E+00

-7.43E-01 7.04E+00 7.42E+00 1.96E+00 1.31E+01 1.52E+01 6.17E+02 ND ND ND ND MW-42-78 MW-42-78 Q4-2010 018 74

-4.3 10/27/2010 13:56 6.13E+02 1.74E+02 1.64E+02

-1.14E-01 4.79E-01 5.87E-01

-1.09E+00 8.69E+00 9.51E+00

-5.11E+00 8.41E+00 7.24E+00

-4.24E+00 1.80E+01 2.09E+01 6.17E+02 MW-42-78 MW-42-78 Q1-2011 019 74

-4.3 3/4/2011 10:58 5.98E+02 4.06E+02 3.84E+02 8.92E-01 1.47E+00 1.60E+00

-2.03E+00 6.72E+00 6.99E+00 8.03E-02 6.70E+00 7.41E+00 0.00E+00 1.73E+01 1.96E+01 6.17E+02 MW-42-78 MW-42-78 Q2-2011 020 74

-4.3 4/21/2011 13:45 6.26E+02 4.78E+02 4.77E+02 4.25E-01 1.13E+00 1.32E+00

-9.71E-01 9.16E+00 9.83E+00 3.58E+00 8.56E+00 1.11E+01 5.89E-01 1.49E+01 1.72E+01 6.17E+02 MW-42-78 MW-43-28 Q3-2010 016 23.5 25.3 7/20/2010 13:48 9.11E+01 1.33E+02 1.47E+02

-6.43E-02 3.80E-01 5.33E-01 5.80E+00 7.53E+00 9.76E+00

-1.44E+00 9.49E+00 1.01E+01 NA NA NA 1.95E+02 ND ND ND NA MW-43-28 MW-43-28 Q4-2010 017 23.5 25.3 10/25/2010 11:29 1.95E+02 1.17E+02 1.13E+02

-1.98E-01 5.01E-01 6.94E-01 3.36E+00 5.00E+00 6.09E+00

-5.01E-01 5.43E+00 5.84E+00 NA NA NA 1.95E+02 MW-43-28 MW-43-28 Q1-2011 018 23.5 25.3 2/15/2011 13:08 2.54E+02 2.80E+02 2.99E+02

-1.06E+00 1.40E+00 2.00E+00 5.75E-02 1.26E+01 7.06E+00

-3.84E+00 6.84E+00 6.54E+00 NA NA NA 1.95E+02 MW-43-28 MW-43-28 Q2-2011 019 23.5 25.3 4/21/2011 11:15 2.34E+02 4.30E+02 4.72E+02 1.46E+00 1.96E+00 2.04E+00

-9.31E-01 8.74E+00 9.22E+00 4.50E+00 8.60E+00 1.09E+01 NA NA NA 1.95E+02 MW-43-28 MW-43-62 Q3-2010 016 51

-2.2 7/20/2010 15:07 5.97E+01 1.33E+02 1.51E+02 4.41E-01 4.75E-01 4.94E-01

-1.11E+00 7.96E+00 8.85E+00

-2.40E+00 8.22E+00 8.59E+00 NA NA NA ND ND ND ND NA MW-43-62 MW-43-62 Q4-2010 017 51

-2.2 10/25/2010 11:06 9.76E+01 1.05E+02 1.12E+02 3.69E-01 7.10E-01 8.03E-01 5.94E-01 6.27E+00 6.81E+00

-6.69E-01 5.37E+00 5.81E+00 NA NA NA MW-43-62 MW-43-62 Q1-2011 018 51

-2.2 2/15/2011 13:15 1.82E+02 2.76E+02 3.00E+02 7.75E-01 1.74E+00 1.95E+00 6.59E-01 5.08E+00 5.56E+00

-2.37E-01 5.16E+00 5.52E+00 NA NA NA MW-43-62 MW-43-62 Q2-2011 019 51

-2.2 4/21/2011 11:00 1.05E+02 4.12E+02 4.72E+02

-4.65E-01 1.67E+00 2.18E+00

-1.90E+00 9.08E+00 9.35E+00

-2.34E+00 8.70E+00 8.43E+00 NA NA NA MW-43-62 MW-44-66 Q3-2010 017 62.4 31.1 7/22/2010 15:47 1.75E+02 1.41E+02 1.47E+02 2.76E-01 5.63E-01 6.43E-01

-3.76E+00 6.86E+00 6.84E+00 1.20E+00 8.52E+00 9.73E+00 NA NA NA 6.50E+02 ND ND ND NA MW-44-66 MW-44-66 Q4-2010 018 62.4 31.1 10/26/2010 14:46 3.10E+02 1.29E+02 1.11E+02

-1.07E-01 4.30E-01 5.95E-01 4.23E-01 6.24E+00 7.11E+00

-3.70E+00 7.37E+00 7.27E+00 NA NA NA 6.50E+02 MW-44-66 MW-44-66 Q1-2011 019 62.4 31.1 2/18/2011 10:41 4.57E+02 3.90E+02 3.99E+02

-2.94E-01 1.59E+00 1.95E+00 1.74E+00 7.72E+00 8.56E+00

-1.40E+00 7.92E+00 8.46E+00 NA NA NA 6.50E+02 MW-44-66 MW-44-66 Q2-2011 020 62.4 31.1 4/26/2011 13:17 6.87E+02 4.20E+02 4.03E+02 7.05E-01 1.52E+00 1.70E+00

-1.14E-01 9.36E+00 1.03E+01 3.29E+00 1.07E+01 1.31E+01 NA NA NA 6.50E+02 MW-44-66 MW-44-66 Q2-2011 Mid 021 62.4 31.1 7/19/2011 15:39 1.62E+03 5.49E+02 4.32E+02

-7.04E-01 6.48E-01 1.06E+00 4.61E+00 9.66E+00 1.16E+01

-5.76E+00 1.11E+01 9.79E+00 NA NA NA 6.50E+02 MW-44-66 MW-44-102 Q3-2010 018 80 13.5 7/21/2010 13:20 2.76E+02 1.49E+02 1.45E+02 4.11E-01 4.70E-01 4.80E-01 2.38E+00 1.02E+01 1.18E+01

-1.83E+00 8.85E+00 9.25E+00 NA NA NA 4.85E+02 ND ND ND NA MW-44-102 MW-44-102 Q4-2010 019 80 13.5 10/26/2010 13:32 4.47E+02 1.42E+02 1.12E+02 2.42E-01 5.47E-01 6.33E-01

-2.73E+00 5.49E+00 5.54E+00 6.85E-01 5.38E+00 6.11E+00 NA NA NA 4.85E+02 MW-44-102 MW-44-102 Q1-2011 020 80 13.5 2/18/2011 10:44 3.93E+02 2.90E+02 2.97E+02 2.63E-01 1.86E+00 2.15E+00 2.22E-01 4.96E+00 5.47E+00

-2.93E-01 6.02E+00 6.58E+00 NA NA NA 4.85E+02 MW-44-102 MW-44-102 Q2-2011 021 80 13.5 4/26/2011 12:18 6.70E+02 4.14E+02 3.99E+02 1.09E+00 1.41E+00 1.49E+00 3.59E-01 7.42E+00 8.15E+00

-2.06E+00 7.86E+00 7.82E+00 NA NA NA 4.85E+02 MW-44-102 MW-44-102 Q2-2011 Mid 022 80 13.5 7/19/2011 10:53 6.38E+02 4.50E+02 4.39E+02 2.55E-01 1.02E+00 1.19E+00 1.01E+00 6.63E+00 7.60E+00 1.28E+00 6.27E+00 7.47E+00 NA NA NA 4.85E+02 MW-44-102 MW-45-42 Q3-2010 021 37 16.6 7/19/2010 15:38 3.69E+03 3.35E+02 1.43E+02 5.08E-01 6.10E-01 6.47E-01 1.04E+00 7.75E+00 8.85E+00

-1.87E+00 7.10E+00 7.11E+00 NA NA NA 1.25E+04 ND ND ND NA MW-45-42 MW-45-42 Q4-2010 022 37 16.6 10/22/2010 15:59 2.74E+03 2.90E+02 1.13E+02 9.55E-02 5.19E-01 6.32E-01 1.35E+00 6.04E+00 6.99E+00

-1.65E+00 5.70E+00 5.89E+00 NA NA NA 1.25E+04 MW-45-42 MW-45-42 Q1-2011 023 37 16.6 2/16/2011 16:58 8.12E+03 7.86E+02 3.63E+02 1.03E+00 1.39E+00 1.48E+00

-8.53E-01 5.64E+00 5.99E+00 1.42E+00 6.30E+00 7.17E+00 NA NA NA 1.25E+04 MW-45-42 MW-45-42 Q2-2011 024 37 16.6 4/20/2011 14:09 8.56E+03 1.03E+03 4.65E+02 1.45E+00 1.56E+00 1.61E+00 7.04E-01 6.50E+00 7.46E+00 7.13E+00 1.07E+01 1.29E+01 NA NA NA 1.25E+04 MW-45-42 MW-45-42 Q2-2011 Mid 025 37 16.6 7/25/2011 13:23 3.94E+04 2.07E+03 4.36E+02 1.14E+00 1.30E+00 1.37E+00 3.09E+00 7.41E+00 8.65E+00

-2.66E+00 1.01E+01 1.05E+01 NA NA NA 1.25E+04 MW-45-42 MW-45-61 Q3-2010 021 58

-4.4 7/19/2010 13:28 1.00E+03 2.07E+02 1.48E+02 4.07E-01 5.04E-01 5.30E-01

-2.93E+00 8.29E+00 8.61E+00

-2.24E+00 8.88E+00 9.24E+00 NA NA NA 2.40E+03 ND ND ND NA MW-45-61 MW-45-61 Q4-2010 022 58

-4.4 10/22/2010 11:54 1.51E+03 2.22E+02 1.12E+02 3.58E-01 5.53E-01 6.05E-01

-2.92E+00 5.78E+00 5.94E+00 1.19E-01 6.92E+00 7.73E+00 NA NA NA 2.40E+03 MW-45-61 MW-45-61 Q1-2011 023 58

-4.4 2/16/2011 16:15 1.84E+03 5.20E+02 3.98E+02

-2.25E-01 1.64E+00 1.96E+00 1.38E+00 4.80E+00 5.41E+00 9.89E-01 5.46E+00 6.15E+00 NA NA NA 2.40E+03 MW-45-61 MW-45-61 Q2-2011 024 58

-4.4 4/20/2011 10:07 2.03E+03 6.12E+02 4.74E+02 7.22E-01 1.36E+00 1.51E+00

-4.02E+00 7.76E+00 7.55E+00

-8.47E-01 7.56E+00 7.91E+00 NA NA NA 2.40E+03 MW-45-61 MW-45-61 Q2-2011 Mid 025 58

-4.4 7/25/2011 10:00 5.63E+03 8.49E+02 4.33E+02 9.47E-01 1.19E+00 1.25E+00 1.42E+00 5.79E+00 6.69E+00 2.07E+00 8.34E+00 9.68E+00 NA NA NA 2.40E+03 MW-45-61

TABLE 3 SECOND QUARTER 2011 GROUNDWATER ANALYTICAL RESULTS AND AVERAGES INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q22011 FINAL Table 3 - Second Quarter 2011 Groundwater Analytical Results and Averages.xlsx; Q22011 Table 3 Page 3 of 6 See Page 6 for Notes TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Date Time Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Average Average Average Average Average ANALYSIS RESULTS5 YEARLY ROLLING AVERAGES4,6 Well ID1 TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

SAMPLE COLLECTION Well ID1 SAMPLING QUARTER2,8 SAMPLE ID SAMPLE ZONE CENTER Depth Ft Below Top of Casing3 SAMPLE ZONE CENTER Elevation Ft msl3 MW-46 Q3-2010 021 10.5 7.6 7/23/2010 13:10 1.92E+03 2.58E+02 1.46E+02 1.80E-01 5.63E-01 6.59E-01 1.28E-01 7.65E+00 8.12E+00

-1.36E+00 7.96E+00 8.34E+00 NA NA NA 3.17E+03 ND ND ND NA MW-46 MW-46 Q4-2010 022 10.5 7.6 10/28/2010 13:25 3.13E+03 3.08E+02 1.13E+02 3.76E-01 5.09E-01 5.49E-01

-2.05E+00 5.85E+00 5.88E+00 2.98E+00 6.81E+00 8.22E+00 NA NA NA 3.17E+03 MW-46 MW-46 Q1-2011 023 10.5 7.6 2/23/2011 12:46 2.47E+03 5.70E+02 3.98E+02 1.12E+00 1.89E+00 2.06E+00

-2.22E+00 5.28E+00 5.28E+00 5.21E-01 5.10E+00 5.66E+00 NA NA NA 3.17E+03 MW-46 MW-46 Q2-2011 024 10.5 7.6 4/25/2011 11:19 5.25E+03 7.54E+02 3.95E+02 1.48E+00 1.72E+00 1.80E+00

-2.48E+00 7.24E+00 7.06E+00

-4.44E+00 7.44E+00 6.77E+00 NA NA NA 3.17E+03 MW-46 MW-46 Q2-2011 Mid 025 10.5 7.6 7/13/2011 13:29 3.08E+03 7.17E+02 2.86E+02 8.44E-01 1.19E+00 1.26E+00 3.71E+00 8.64E+00 1.04E+01

-9.54E-01 1.02E+01 1.08E+01 NA NA NA 3.17E+03 MW-46 MW-47-56 Q2-2011 Mid 006 53.2 17.1 7/6/2011 15:32 3.52E+03 6.57E+02 4.48E+02 4.63E-01 1.08E+00 1.22E+00

-1.56E+00 1.11E+01 1.20E+01 1.45E-01 7.41E+00 8.25E+00

-1.99E+01 2.17E+01 2.50E+01 3.52E+03 ND ND ND ND MW-47-56 MW-47-80 Q2-2011 Mid 005 74

-3.7 7/6/2011 14:37 1.36E+05 3.36E+03 4.50E+02 1.95E+00 1.33E+00 1.22E+00

-1.57E+00 8.37E+00 8.73E+00

-3.43E+00 7.80E+00 7.13E+00 3.07E+00 2.59E+01 2.89E+01 1.36E+05 1.95E+00 ND ND ND MW-47-80 MW-49-26 Q3-2010 021 19.1

-4.4 8/11/2010 11:27 3.03E+03 3.03E+02 1.27E+02 1.28E+01 1.44E+00 3.66E-01

-7.91E-01 1.14E+01 1.15E+01

-1.86E+00 1.10E+01 1.19E+01 3.27E-01 1.64E+01 1.92E+01 3.02E+03 1.28E+01 ND ND ND MW-49-26 MW-49-26 Q4-2010 022 19.1

-4.4 11/11/2010 14:23 2.59E+03 3.00E+02 4.76E+02

-3.42E-01 9.56E-01 2.34E+00 4.62E+00 4.84E+00 1.15E+01 1.18E+00 3.96E+00 9.11E+00

-1.79E+00 1.02E+01 2.29E+01 3.02E+03 1.28E+01 MW-49-26 MW-49-26 Q1-2011 023 19.1

-4.4 1/28/2011 13:37 3.17E+03 6.00E+02 4.29E+02 1.30E+01 2.86E+00 2.01E+00 3.39E-01 1.04E+01 7.00E+00

-2.43E+00 6.42E+00 6.44E+00

-4.38E+00 1.87E+01 2.20E+01 3.02E+03 1.28E+01 MW-49-26 MW-49-26 Q2-2011 024 19.1

-4.4 4/15/2011 11:58 3.29E+03 7.18E+02 4.80E+02 1.26E+01 3.06E+00 1.91E+00 4.75E+00 1.07E+01 1.27E+01 4.03E+00 1.20E+01 1.47E+01 1.81E+00 1.50E+01 1.72E+01 3.02E+03 1.28E+01 MW-49-26 MW-49-42 Q3-2010 021 38.1

-23.4 8/11/2010 11:00 2.27E+03 2.72E+02 1.30E+02 1.85E+01 1.67E+00 3.91E-01 4.80E+00 7.88E+00 9.85E+00

-2.34E+00 8.76E+00 9.06E+00

-1.91E+00 1.65E+01 1.96E+01 2.25E+03 1.93E+01 ND ND ND MW-49-42 MW-49-42 Q4-2010 022 38.1

-23.4 11/11/2010 14:13 2.39E+03 2.73E+02 4.02E+02 1.99E+01 1.65E+00 1.12E+00 8.48E-01 6.79E+00 9.79E+00 3.75E+00 5.42E+00 1.30E+01 4.00E+00 8.14E+00 1.80E+01 2.25E+03 1.93E+01 MW-49-42 MW-49-42 Q1-2011 023 38.1

-23.4 1/28/2011 13:00 2.45E+03 5.38E+02 3.86E+02 2.30E+01 4.02E+00 2.02E+00

-1.07E+00 5.74E+00 6.21E+00

-2.45E+00 5.50E+00 5.32E+00

-3.26E+00 1.86E+01 2.18E+01 2.25E+03 1.93E+01 MW-49-42 MW-49-42 Q2-2011 024 38.1

-23.4 4/15/2011 11:55 1.90E+03 6.04E+02 4.78E+02 1.57E+01 3.34E+00 2.07E+00

-6.72E+00 7.62E+00 6.17E+00 1.15E-01 7.72E+00 8.33E+00 6.68E+00 1.55E+01 1.73E+01 2.25E+03 1.93E+01 MW-49-42 MW-49-65 Q3-2010 021 60

-45.4 8/11/2010 11:19 1.32E+03 2.16E+02 1.28E+02 1.24E+01 1.44E+00 4.49E-01

-1.12E+01 1.22E+01 1.43E+01

-2.58E-01 9.88E+00 1.11E+01

-6.74E-01 1.80E+01 2.13E+01 1.75E+03 1.36E+01 ND ND ND MW-49-65 MW-49-65 Q4-2010 022 60

-45.4 11/11/2010 14:18 1.37E+03 2.34E+02 3.97E+02 1.41E+01 1.45E+00 1.34E+00 6.99E+00 6.88E+00 1.07E+01 3.39E-01 5.37E+00 1.18E+01

-3.41E+00 9.31E+00 2.09E+01 1.75E+03 1.36E+01 MW-49-65 MW-49-65 Q1-2011 023 60

-45.4 1/28/2011 13:15 1.94E+03 5.02E+02 3.85E+02 1.15E+01 3.28E+00 2.06E+00

-6.30E-01 4.96E+00 5.21E+00 7.15E-01 5.20E+00 5.81E+00

-9.08E+00 1.83E+01 2.20E+01 1.75E+03 1.36E+01 MW-49-65 MW-49-65 Q2-2011 024 60

-45.4 4/15/2011 11:50 2.38E+03 6.48E+02 4.81E+02 1.62E+01 3.12E+00 1.60E+00 2.59E+00 9.66E+00 1.12E+01 4.62E-02 1.01E+01 1.10E+01 4.11E+00 1.49E+01 1.68E+01 1.75E+03 1.36E+01 MW-49-65 MW-50-42 Q3-2010 022 42

-27.1 8/4/2010 13:11 1.61E+02 1.25E+02 1.28E+02 8.43E+00 1.42E+00 5.63E-01

-1.94E+00 8.65E+00 9.25E+00 1.30E-01 8.05E+00 9.05E+00 0.00E+00 1.59E+01 1.88E+01 1.28E+03 6.02E+00 ND ND ND MW-50-42 MW-50-42 Q4-2010 023 42

-27.1 11/12/2010 12:10 8.67E+02 1.83E+02 1.22E+02 3.73E+00 1.31E+00 9.89E-01 2.40E+00 5.71E+00 6.76E+00 2.73E+00 5.58E+00 6.94E+00

-7.36E+00 1.79E+01 2.15E+01 1.28E+03 6.02E+00 MW-50-42 MW-50-42 Q1-2011 024 42

-27.1 2/25/2011 12:36 5.61E+02 3.88E+02 3.85E+02 5.42E+00 2.34E+00 1.91E+00

-1.29E-01 5.46E+00 5.88E+00

-9.07E-01 4.42E+00 4.42E+00

-7.19E+00 1.82E+01 2.18E+01 1.28E+03 6.02E+00 MW-50-42 MW-50-42 Q2-2011 025 42

-27.1 5/3/2011 12:05 3.77E+03 5.58E+02 3.41E+02 9.53E+00 2.20E+00 1.04E+00 1.92E+00 9.44E+00 1.07E+01 5.79E-01 1.02E+01 1.16E+01 5.86E-01 1.69E+01 1.92E+01 1.28E+03 6.02E+00 MW-50-42 MW-50-42 Q2-2011 Mid 026 42

-27.1 7/25/2011 12:18 1.03E+03 4.89E+02 4.43E+02 3.01E+00 2.09E+00 2.02E+00

-1.11E+00 7.86E+00 8.36E+00 6.63E-02 8.16E+00 9.04E+00 3.81E+00 1.71E+01 1.91E+01 1.28E+03 6.02E+00 MW-50-42 MW-50-66 Q3-2010 027 60

-45.1 8/4/2010 16:38 3.51E+03 3.33E+02 1.34E+02 2.65E+01 2.28E+00 4.80E-01 3.52E+00 8.29E+00 9.99E+00 9.22E-01 9.18E+00 1.06E+01 2.07E+00 1.56E+01 1.81E+01 4.44E+03 2.57E+01 ND ND ND MW-50-66 MW-50-66 Q4-2010 028 60

-45.1 11/12/2010 12:30 3.72E+03 3.30E+02 1.20E+02 2.33E+01 2.71E+00 9.50E-01

-1.39E+00 6.21E+00 6.79E+00

-1.67E+00 6.95E+00 7.30E+00 3.25E-01 1.88E+01 2.18E+01 4.44E+03 2.57E+01 MW-50-66 MW-50-66 Q1-2011 029 60

-45.1 2/25/2011 12:36 3.76E+03 6.18E+02 3.83E+02 2.61E+01 4.02E+00 2.13E+00 2.94E+00 7.20E+00 8.24E+00 6.79E-01 8.00E+00 9.10E+00

-2.80E+00 1.81E+01 2.12E+01 4.44E+03 2.57E+01 MW-50-66 MW-50-66 Q2-2011 030 60

-45.1 5/3/2011 12:07 4.73E+03 6.12E+02 3.45E+02 2.63E+01 3.30E+00 1.08E+00 0.00E+00 1.77E+01 9.05E+00

-2.32E+00 9.06E+00 9.12E+00 8.43E+00 1.70E+01 1.88E+01 4.44E+03 2.57E+01 MW-50-66 MW-50-66 Q2-2011 Mid 031 60

-45.1 7/25/2011 12:26 6.50E+03 8.73E+02 4.48E+02 2.61E+01 4.08E+00 1.35E+00

-4.59E-01 7.02E+00 7.74E+00 3.81E+00 8.55E+00 1.07E+01 1.02E+01 1.66E+01 1.81E+01 4.44E+03 2.57E+01 MW-50-66 MW-51-40 Q3-2010 016 39.7 28 8/25/2010 16:29 1.70E+02 1.07E+02 1.03E+02

-4.31E-02 3.11E-01 4.19E-01

-2.48E+00 6.17E+00 6.53E+00 1.46E+00 5.21E+00 6.37E+00 NA NA NA 1.59E+02 ND ND ND NA MW-51-40 MW-51-40 Q4-2010 017 39.7 28 11/30/2010 12:54 1.48E+02 1.41E+02 1.44E+02 1.46E-01 6.05E-01 7.12E-01 1.54E+00 4.28E+00 4.95E+00 1.72E+00 4.17E+00 4.95E+00 NA NA NA 1.59E+02 MW-51-40 MW-51-40 Q1-2011 018 39.7 28 3/8/2011 10:18 1.02E+02 2.34E+02 2.67E+02 1.07E+00 1.51E+00 1.61E+00

-7.97E+00 1.21E+01 1.36E+01 2.42E+00 7.30E+00 8.76E+00 NA NA NA 1.59E+02 MW-51-40 MW-51-40 Q2-2011 019 39.7 28 4/29/2011 10:41 3.63E+02 4.14E+02 4.35E+02 2.26E-01 1.37E+00 1.59E+00

-3.40E+00 9.48E+00 9.62E+00 6.20E+00 1.11E+01 1.40E+01 NA NA NA 1.59E+02 MW-51-40 MW-51-79 Q3-2010 016 78.7

-11 8/25/2010 16:47 1.10E+02 9.84E+01 1.01E+02 5.81E-01 8.23E-01 8.92E-01 5.29E+00 6.13E+00 7.76E+00 1.58E+00 6.71E+00 7.88E+00 NA NA NA 1.10E+02 ND ND ND NA MW-51-79 MW-51-79 Q4-2010 017 78.7

-11 11/30/2010 13:08 3.11E+01 1.21E+02 1.44E+02

-1.22E-01 4.32E-01 5.24E-01

-8.30E-01 4.13E+00 4.54E+00 9.98E-01 4.02E+00 4.66E+00 NA NA NA 1.10E+02 MW-51-79 MW-51-79 Q1-2011 018 78.7

-11 3/8/2011 10:34 1.36E+02 2.46E+02 2.70E+02

-2.03E-01 1.22E+00 1.53E+00 2.42E+00 5.42E+00 6.52E+00

-2.74E+00 7.36E+00 6.45E+00 NA NA NA 1.10E+02 MW-51-79 MW-51-79 Q2-2011 019 78.7

-11 4/29/2011 10:57 1.17E+02 3.82E+02 4.33E+02 1.03E+00 1.67E+00 1.82E+00

-4.93E-01 7.56E+00 8.23E+00

-8.38E-01 8.08E+00 8.53E+00 NA NA NA 1.10E+02 MW-51-79 MW-51-104 Q3-2010 014 103.7

-36 8/25/2010 13:18 1.33E+02 1.37E+02 1.44E+02 7.62E-01 8.15E-01 8.20E-01 8.90E-01 5.75E+00 6.63E+00

-2.70E-01 4.96E+00 5.47E+00 NA NA NA ND ND ND ND NA MW-51-104 MW-51-104 Q4-2010 015 103.7

-36 11/30/2010 9:55 8.54E+01 1.33E+02 1.47E+02 3.74E-01 7.18E-01 8.12E-01

-1.43E-01 3.99E+00 4.55E+00 2.19E-01 4.56E+00 5.05E+00 NA NA NA MW-51-104 MW-51-104 Q1-2011 016 103.7

-36 3/8/2011 12:10 5.76E+01 3.10E+02 3.55E+02 8.91E-01 1.47E+00 1.60E+00 2.54E+00 7.20E+00 8.14E+00 9.02E-01 5.50E+00 6.24E+00 NA NA NA MW-51-104 MW-51-104 Q2-2011 017 103.7

-36 4/29/2011 12:35 1.97E+02 3.90E+02 4.32E+02 1.41E+00 1.45E+00 1.48E+00

-1.90E+00 1.08E+01 1.25E+01

-6.79E-01 1.10E+01 1.20E+01 NA NA NA MW-51-104 MW-51-135 Q3-2010 014 135.2

-67.5 8/25/2010 13:21 1.36E+02 1.41E+02 1.47E+02

-2.33E-01 4.44E-01 6.70E-01

-6.64E-01 6.15E+00 6.80E+00 1.74E+00 6.62E+00 7.77E+00 NA NA NA ND ND ND ND NA MW-51-135 MW-51-135 Q4-2010 015 135.2

-67.5 11/30/2010 9:57 9.53E+01 1.33E+02 1.45E+02 4.21E-01 7.13E-01 7.98E-01

-5.11E-01 4.18E+00 4.61E+00

-2.98E-01 4.20E+00 4.58E+00 NA NA NA MW-51-135 MW-51-135 Q1-2011 016 135.2

-67.5 3/8/2011 12:44 8.29E+01 2.24E+02 2.62E+02 8.62E-01 1.31E+00 1.42E+00 8.60E-02 6.02E+00 6.77E+00 2.37E+00 5.96E+00 7.38E+00 NA NA NA MW-51-135 MW-51-135 Q2-2011 017 135.2

-67.5 4/29/2011 13:16 0.00E+00 3.66E+02 4.35E+02 1.14E+00 1.52E+00 1.63E+00 2.52E+00 1.01E+01 1.17E+01

-5.69E-01 9.00E+00 9.56E+00 NA NA NA MW-51-135 MW-51-163 Q3-2010 014 162.7

-95 8/25/2010 13:51 8.26E+01 9.75E+01 1.05E+02

-1.08E-01 3.98E-01 5.31E-01 3.91E+00 6.72E+00 8.11E+00 8.67E-01 6.32E+00 7.26E+00 NA NA NA ND ND ND ND NA MW-51-163 MW-51-163 Q4-2010 015 162.7

-95 11/30/2010 10:02 9.01E+01 1.31E+02 1.44E+02

-3.11E-01 6.98E-01 9.94E-01 1.23E+00 8.07E+00 4.14E+00 3.30E-01 3.94E+00 4.43E+00 NA NA NA MW-51-163 MW-51-163 Q1-2011 016 162.7

-95 3/8/2011 13:01 0.00E+00 1.96E+02 2.63E+02

-5.97E-01 1.39E+00 1.98E+00 2.81E+00 6.54E+00 7.66E+00 5.35E-01 7.76E+00 8.69E+00 NA NA NA MW-51-163 MW-51-163 Q2-2011 017 162.7

-95 4/29/2011 13:19 4.68E+01 3.66E+02 4.30E+02 5.27E-01 1.45E+00 1.65E+00 2.26E+00 8.40E+00 9.72E+00 9.25E-01 7.72E+00 8.87E+00 NA NA NA MW-51-163 MW-51-189*

Q3-2010 014 189.2

-121.5 8/25/2010 13:13 5.86E+01 9.38E+01 1.04E+02 4.40E-02 5.97E-01 7.65E-01 2.87E+00 5.64E+00 6.69E+00

-8.01E-01 5.85E+00 6.25E+00 NA NA NA ND ND ND*

ND NA MW-51-189*

MW-51-189*

Q4-2010 015 189.2

-121.5 11/30/2010 9:56 6.91E+01 1.29E+02 1.46E+02 1.93E-01 7.99E-01 9.81E-01

-7.45E-01 4.51E+00 4.98E+00

-3.16E-01 4.61E+00 5.06E+00 NA NA NA 3.77E+01 MW-51-189*

MW-51-189*

Q1-2011 016 189.2

-121.5 3/8/2011 12:30

-1.50E+01 1.93E+02 2.68E+02

-3.06E-01 1.46E+00 1.97E+00 3.77E+01*

1.47E+01 6.28E+00 2.28E-01 5.28E+00 5.79E+00 NA NA NA 3.77E+01 MW-51-189*

MW-51-189*

Q2-2011 017 189.2

-121.5 4/29/2011 12:52 2.32E+02 3.96E+02 4.33E+02 1.28E+00 1.50E+00 1.57E+00

-8.07E-01 5.82E+00 6.25E+00

-5.07E+00 9.48E+00 8.89E+00 NA NA NA 3.77E+01 MW-51-189*

MW-52-11 Q2-2011 006 10 6.8 4/22/2011 12:10 3.04E+02 4.08E+02 4.35E+02 1.29E-01 1.35E+00 1.60E+00 2.27E+00 1.02E+01 1.17E+01 5.08E+00 9.92E+00 1.24E+01 NA NA NA ND ND ND ND NA MW-52-11 MW-52-11 Q2-2011 Mid 007 10 6.8 7/26/2011 12:32 3.39E+02 3.99E+02 4.21E+02 1.86E-01 1.49E+00 1.74E+00 1.71E+00 8.76E+00 9.71E+00

-2.27E+00 8.43E+00 8.63E+00 NA NA NA MW-52-11 MW-52-18 Q2-2011 006 17.5

-2.6 4/22/2011 12:16 7.01E+01 3.76E+02 4.35E+02 1.37E+00 1.39E+00 1.42E+00 8.81E+00 1.29E+01 9.01E+00

-1.49E+00 9.44E+00 9.90E+00 NA NA NA ND ND ND ND NA MW-52-18 MW-52-18 Q2-2011 Mid 007 17.5

-2.6 7/26/2011 14:39 2.52E+02 3.87E+02 4.22E+02 1.06E+00 1.62E+00 1.76E+00 3.80E+00 6.45E+00 8.08E+00

-3.24E+00 8.10E+00 7.84E+00 NA NA NA MW-52-18 MW-52-48 Q2-2011 006 48

-33.1 4/22/2011 12:18 1.06E+02 3.82E+02 4.36E+02 1.69E-01 1.37E+00 1.62E+00

-4.59E+00 7.58E+00 7.31E+00 1.35E+00 7.80E+00 9.17E+00 NA NA NA ND ND ND ND NA MW-52-48 MW-52-48 Q2-2011 Mid 007 48

-33.1 7/26/2011 15:08 7.68E+01 3.66E+02 4.21E+02 2.58E-01 1.20E+00 1.46E+00 2.34E+00 9.60E+00 1.07E+01

-7.68E-01 8.73E+00 1.01E+01 NA NA NA MW-52-48 MW-52-64 Q2-2011 006 64

-49.1 4/22/2011 15:23

-2.26E+01 3.58E+02 4.32E+02 5.12E-01 1.13E+00 1.27E+00 1.87E+00 6.72E+00 7.70E+00

-8.05E+00 8.28E+00 6.18E+00 NA NA NA ND ND ND ND NA MW-52-64 MW-52-64 Q2-2011 Mid 007 64

-49.1 7/27/2011 10:45 1.35E+02 3.81E+02 4.31E+02

-4.58E-01 8.67E-01 1.27E+00 2.48E+00 7.17E+00 8.34E+00 6.66E-01 8.13E+00 9.05E+00 NA NA NA MW-52-64 MW-52-122 Q2-2011 006 122

-107.1 4/22/2011 10:45

-2.27E+01 3.60E+02 4.33E+02 1.14E+00 1.17E+00 1.17E+00 3.48E+01 2.08E+01 9.71E+00

-1.96E+00 7.96E+00 7.90E+00 NA NA NA ND ND 3.48E+01 ND NA MW-52-122 MW-52-122 Q2-2011 Mid 007 122

-107.1 7/26/2011 13:36

-2.18E+01 3.48E+02 4.19E+02 1.05E-01 1.19E+00 1.47E+00

-5.49E+00 7.92E+00 7.50E+00 8.02E-01 6.84E+00 7.89E+00 NA NA NA 3.48E+01 MW-52-122 MW-52-162 Q2-2011 006 161.5

-146.6 4/22/2011 10:18 1.85E+02 3.84E+02 4.29E+02

-7.50E-01 9.50E-01 1.42E+00 1.47E+00 8.40E+00 9.68E+00 1.95E-02 1.00E+01 1.10E+01 NA NA NA 5.16E+02 ND ND ND NA MW-52-162 MW-52-162 Q2-2011 Mid 007 161.5

-146.6 7/26/2011 11:33 5.16E+02 4.20E+02 4.22E+02 3.77E-03 1.21E+00 1.57E+00 4.29E-02 8.34E+00 9.09E+00

-2.32E+00 9.87E+00 1.00E+01 NA NA NA 5.16E+02 MW-52-162 MW-52-181 Q2-2011 006 181

-166.1 4/22/2011 10:22 2.45E+02 3.96E+02 4.33E+02 1.18E+00 1.42E+00 1.48E+00 6.46E+01 2.68E+01 1.22E+01

-1.09E+00 1.22E+01 1.30E+01 NA NA NA ND ND 6.46E+01 ND NA MW-52-181 MW-52-181 Q2-2011 Mid 007 181

-166.1 7/26/2011 11:43 2.41E+02 3.87E+02 4.22E+02 3.57E-01 1.28E+00 1.54E+00

-1.99E+00 7.50E+00 7.52E+00

-1.27E+00 9.39E+00 9.97E+00 NA NA NA 6.46E+01 MW-52-181 MW-53-82 Q3-2010 016 75

-4.7 7/30/2010 12:32 2.25E+03 2.66E+02 1.27E+02 3.34E-01 3.83E-01 4.00E-01

-3.03E+00 8.36E+00 8.46E+00

-1.90E+00 8.00E+00 8.03E+00

-1.45E+01 1.77E+01 2.23E+01 1.51E+03 ND ND ND ND MW-53-82 MW-53-82 Q4-2010 017 75

-4.7 10/27/2010 12:07 2.59E+03 2.79E+02 1.10E+02 8.07E-01 7.90E-01 8.26E-01

-3.74E-02 5.82E+00 6.57E+00 1.14E-01 6.23E+00 7.00E+00 NA NA NA 1.51E+03 MW-53-82 MW-53-82 Q1-2011 018 75

-4.7 3/3/2011 11:53 5.95E+02 3.76E+02 3.73E+02 1.61E+00 1.82E+00 1.91E+00 3.61E+00 6.18E+00 7.60E+00

-1.88E+00 7.02E+00 7.25E+00

-7.63E+00 1.59E+01 1.85E+01 1.51E+03 MW-53-82 MW-53-82 Q2-2011 019 75

-4.7 4/18/2011 12:45 6.24E+02 4.56E+02 4.50E+02 4.40E-01 1.45E+00 1.67E+00

-4.57E+00 9.82E+00 9.80E+00 3.12E+00 8.78E+00 1.07E+01

-5.86E-01 1.48E+01 1.72E+01 1.51E+03 MW-53-82 MW-53-120 Q3-2010 020 109.8

-39.5 7/30/2010 14:36 3.81E+03 3.38E+02 1.28E+02 2.97E+01 2.22E+00 4.77E-01 2.09E+00 1.27E+01 1.37E+01

-4.76E-01 8.04E+00 8.95E+00 3.59E+00 1.91E+01 2.21E+01 3.92E+03 3.11E+01 ND ND ND MW-53-120 MW-53-120 Q4-2010 021 109.8

-39.5 10/27/2010 12:48 3.91E+03 3.38E+02 1.11E+02 2.96E+01 2.91E+00 7.02E-01 2.32E+00 5.07E+00 6.00E+00

-9.52E-01 5.46E+00 5.76E+00 NA NA NA 3.92E+03 3.11E+01 MW-53-120 MW-53-120 Q1-2011 022 109.8

-39.5 3/3/2011 12:00 3.84E+03 7.18E+02 3.89E+02 2.95E+01 3.76E+00 1.13E+00 2.30E+00 7.32E+00 8.49E+00

-2.43E+00 8.14E+00 8.13E+00 1.00E+01 1.70E+01 1.87E+01 3.92E+03 3.11E+01 MW-53-120 MW-53-120 Q2-2011 023 109.8

-39.5 4/18/2011 11:52 4.11E+03 7.72E+02 4.75E+02 3.55E+01 4.56E+00 1.67E+00 1.38E+00 8.82E+00 9.99E+00 4.87E-01 9.24E+00 1.02E+01 1.76E+01 1.77E+01 1.87E+01 3.92E+03 3.11E+01 MW-53-120 MW-54-37 Q3-2010 014 36.5

-23.4 8/4/2010 14:32 1.21E+03 2.10E+02 1.30E+02 4.00E+00 8.07E-01 3.32E-01

-4.96E-01 7.38E+00 8.14E+00

-3.97E+00 9.63E+00 9.58E+00

-3.50E+00 1.50E+01 1.80E+01 7.41E+03 4.53E+00 ND ND ND MW-54-37 MW-54-37 Q4-2010 015 36.5

-23.4 11/23/2010 14:47 1.45E+03 2.27E+02 1.26E+02 4.51E+00 1.42E+00 9.84E-01

-2.09E+00 5.46E+00 5.80E+00

-6.89E-01 6.35E+00 6.93E+00

-2.56E+00 1.81E+01 2.15E+01 7.41E+03 4.53E+00 MW-54-37 MW-54-37 Q1-2011 016 36.5

-23.4 2/1/2011 14:10 1.33E+03 4.86E+02 3.78E+02 4.88E+00 1.77E+00 1.26E+00

-1.42E+00 5.54E+00 5.67E+00 3.12E-01 6.42E+00 7.04E+00

-2.81E+00 1.59E+01 1.82E+01 7.41E+03 4.53E+00 MW-54-37 MW-54-37 Q2-2011 017 36.5

-23.4 4/12/2011 12:02 5.16E+03 8.40E+02 4.76E+02 4.91E+00 2.08E+00 1.69E+00 2.95E+00 8.26E+00 9.69E+00 2.50E+00 8.26E+00 9.96E+00 3.16E+00 1.45E+01 1.65E+01 7.41E+03 4.53E+00 MW-54-37 MW-54-37 Q2-2011 Mid 018 36.5

-23.4 7/18/2011 13:45 2.79E+04 1.67E+03 4.43E+02 4.34E+00 2.19E+00 1.85E+00

-1.17E+00 6.36E+00 6.58E+00 4.07E+00 9.21E+00 1.09E+01 1.56E+01 1.91E+01 2.07E+01 7.41E+03 4.53E+00 MW-54-37 MW-54-58 Q3-2010 014 57.5

-44.4 8/4/2010 14:35 7.67E+02 1.79E+02 1.28E+02 1.36E+00 6.88E-01 6.20E-01

-3.95E+00 9.51E+00 9.85E+00 8.15E-01 1.14E+01 1.32E+01

-5.38E-01 1.44E+01 1.70E+01 1.20E+03 1.80E+00 ND ND ND MW-54-58 MW-54-58 Q4-2010 015 57.5

-44.4 11/23/2010 14:55 8.21E+02 1.80E+02 1.23E+02 2.67E+00 1.13E+00 9.76E-01 3.83E+00 6.50E+00 7.88E+00 2.75E+00 6.57E+00 8.00E+00

-3.94E+00 1.86E+01 2.21E+01 1.20E+03 1.80E+00 MW-54-58 MW-54-58 Q1-2011 016 57.5

-44.4 2/1/2011 14:22 9.58E+02 4.56E+02 3.92E+02 1.68E+00 1.34E+00 1.28E+00

-4.20E-02 7.14E+00 7.94E+00

-2.21E+00 6.84E+00 6.82E+00

-4.89E+00 1.66E+01 1.92E+01 1.20E+03 1.80E+00 MW-54-58 MW-54-58 Q2-2011 017 57.5

-44.4 4/12/2011 12:04 9.94E+02 5.20E+02 4.79E+02 1.15E+00 1.84E+00 2.01E+00 1.70E+00 8.58E+00 9.66E+00 1.14E+00 8.74E+00 9.95E+00 5.01E+00 1.58E+01 1.78E+01 1.20E+03 1.80E+00 MW-54-58 MW-54-58 Q2-2011 Mid 018 57.5

-44.4 7/18/2011 13:33 2.48E+03 6.12E+02 4.44E+02 1.49E+00 1.21E+00 1.14E+00

-1.98E+00 8.85E+00 9.27E+00 2.35E-01 9.09E+00 1.01E+01 1.83E+01 1.97E+01 2.13E+01 1.20E+03 1.80E+00 MW-54-58 MW-54-123 Q3-2010 014 123

-109.9 8/4/2010 14:49 7.83E+02 1.80E+02 1.28E+02 2.98E+00 7.55E-01 4.15E-01 1.53E+00 9.99E+00 1.16E+01

-9.37E-01 8.21E+00 8.72E+00

-5.12E+00 1.64E+01 1.97E+01 8.14E+02 4.16E+00 ND ND ND MW-54-123 MW-54-123 Q4-2010 015 123

-109.9 11/23/2010 15:12 8.12E+02 1.80E+02 1.22E+02 7.65E+00 1.46E+00 9.15E-01 2.19E+00 6.74E+00 7.78E+00

-1.25E+00 6.18E+00 6.62E+00 9.26E+00 1.91E+01 2.15E+01 8.14E+02 4.16E+00 MW-54-123 MW-54-123 Q1-2011 016 123

-109.9 2/1/2011 14:11 1.08E+03 4.68E+02 3.90E+02 2.56E+00 1.39E+00 1.08E+00

-3.56E-01 6.02E+00 6.69E+00

-3.66E-03 5.16E+00 5.75E+00 2.50E+00 1.66E+01 1.87E+01 8.14E+02 4.16E+00 MW-54-123 MW-54-123 Q2-2011 017 123

-109.9 4/12/2011 12:22 8.24E+02 4.98E+02 4.77E+02 3.44E+00 1.96E+00 1.72E+00

-5.24E+00 8.14E+00 7.60E+00 1.86E+00 8.04E+00 9.55E+00

-3.35E+00 1.48E+01 1.75E+01 8.14E+02 4.16E+00 MW-54-123 MW-54-123 Q2-2011 Mid 018 123

-109.9 7/18/2011 14:06 5.70E+02 4.44E+02 4.46E+02 7.16E-01 1.02E+00 1.07E+00 1.92E+00 9.66E+00 1.05E+01 3.87E-02 6.30E+00 6.97E+00 6.27E+00 1.84E+01 2.04E+01 8.14E+02 4.16E+00 MW-54-123 MW-54-144 Q3-2010 014 144

-130.9 8/4/2010 11:44 1.44E+03 2.28E+02 1.33E+02 1.17E+01 1.42E+00 4.70E-01 8.96E+00 1.13E+01 1.44E+01 1.72E+00 8.79E+00 1.06E+01 1.78E+00 1.89E+01 2.21E+01 1.99E+03 1.10E+01 ND ND ND MW-54-144 MW-54-144 Q4-2010 015 144

-130.9 11/23/2010 12:30 1.34E+03 2.15E+02 1.21E+02 1.08E+01 1.36E+00 5.83E-01 1.02E+00 7.82E+00 8.59E+00

-3.87E+00 6.48E+00 5.93E+00 2.30E+00 1.91E+01 2.21E+01 1.99E+03 1.10E+01 MW-54-144 MW-54-144 Q1-2011 016 144

-130.9 2/1/2011 12:34 1.35E+03 4.96E+02 3.87E+02 9.31E+00 2.24E+00 1.06E+00

-9.04E-01 6.14E+00 6.70E+00

-6.36E-01 6.20E+00 6.74E+00

-4.27E+00 1.58E+01 1.82E+01 1.99E+03 1.10E+01 MW-54-144 MW-54-144 Q2-2011 017 144

-130.9 4/12/2011 9:50 1.48E+03 5.68E+02 4.79E+02 1.20E+01 2.92E+00 1.81E+00 6.43E+00 7.44E+00 9.59E+00

-4.68E+00 9.58E+00 8.86E+00

-2.75E+00 1.48E+01 1.74E+01 1.99E+03 1.10E+01 MW-54-144 MW-54-144 Q2-2011 Mid 018 144

-130.9 7/18/2011 12:38 4.34E+03 7.41E+02 4.43E+02 1.13E+01 2.44E+00 1.26E+00 3.37E+00 7.47E+00 8.78E+00

-3.49E+00 8.91E+00 8.88E+00 1.53E+01 1.87E+01 2.03E+01 1.99E+03 1.10E+01 MW-54-144 MW-54-173 Q3-2010 014 172.5

-159.4 8/4/2010 12:09 1.53E+03 2.31E+02 1.30E+02 5.97E+00 1.02E+00 3.24E-01

-7.48E+00 8.07E+00 7.10E+00 4.86E-01 9.46E+00 1.08E+01

-1.31E+00 1.68E+01 1.99E+01 1.49E+03 4.98E+00 ND ND ND MW-54-173 MW-54-173 Q4-2010 015 172.5

-159.4 11/23/2010 12:25 1.51E+03 2.28E+02 1.24E+02 4.65E+00 1.28E+00 8.17E-01

-1.84E+00 7.05E+00 7.31E+00

-1.82E+00 6.23E+00 6.51E+00 2.22E+00 1.84E+01 2.14E+01 1.49E+03 4.98E+00 MW-54-173 MW-54-173 Q1-2011 016 172.5

-159.4 2/1/2011 12:29 1.66E+03 5.26E+02 3.81E+02 5.81E+00 1.88E+00 1.10E+00

-2.87E-01 8.00E+00 8.79E+00 1.01E+00 1.06E+01 1.20E+01

-5.49E+00 1.77E+01 2.05E+01 1.49E+03 4.98E+00 MW-54-173 MW-54-173 Q2-2011 017 172.5

-159.4 4/12/2011 9:56 1.26E+03 5.46E+02 4.78E+02 3.91E+00 1.92E+00 1.58E+00

-1.29E+01 1.38E+01 1.53E+01 5.93E+00 9.66E+00 1.25E+01

-2.17E+00 1.50E+01 1.76E+01 1.49E+03 4.98E+00 MW-54-173 MW-54-173 Q2-2011 Mid 018 172.5

-159.4 7/18/2011 12:20 1.48E+03 5.28E+02 4.40E+02 4.54E+00 1.64E+00 1.11E+00 2.97E-01 6.84E+00 7.45E+00 1.10E+00 6.51E+00 7.50E+00

-5.43E+00 1.56E+01 1.75E+01 1.49E+03 4.98E+00 MW-54-173

TABLE 3 SECOND QUARTER 2011 GROUNDWATER ANALYTICAL RESULTS AND AVERAGES INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q22011 FINAL Table 3 - Second Quarter 2011 Groundwater Analytical Results and Averages.xlsx; Q22011 Table 3 Page 4 of 6 See Page 6 for Notes TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Date Time Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Average Average Average Average Average ANALYSIS RESULTS5 YEARLY ROLLING AVERAGES4,6 Well ID1 TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

SAMPLE COLLECTION Well ID1 SAMPLING QUARTER2,8 SAMPLE ID SAMPLE ZONE CENTER Depth Ft Below Top of Casing3 SAMPLE ZONE CENTER Elevation Ft msl3 MW-54-190 Q3-2010 014 190

-176.9 8/4/2010 12:34 1.60E+03 2.33E+02 1.28E+02 1.57E+01 1.51E+00 2.87E-01

-1.62E+00 8.25E+00 8.88E+00

-1.20E+00 8.80E+00 9.41E+00

-3.22E+00 1.84E+01 2.21E+01 1.97E+03 1.76E+01 ND ND ND MW-54-190 MW-54-190 Q4-2010 015 190

-176.9 11/23/2010 12:22 1.93E+03 2.55E+02 1.27E+02 1.92E+01 1.89E+00 7.12E-01

-9.64E-01 6.04E+00 6.61E+00

-2.29E+00 6.71E+00 6.79E+00

-3.18E-01 1.81E+01 2.14E+01 1.97E+03 1.76E+01 MW-54-190 MW-54-190 Q1-2011 016 190

-176.9 2/1/2011 12:25 1.89E+03 5.56E+02 3.90E+02 1.68E+01 3.36E+00 1.28E+00 4.59E-01 6.34E+00 7.14E+00

-3.55E+00 5.96E+00 5.21E+00 1.71E+00 1.67E+01 1.89E+01 1.97E+03 1.76E+01 MW-54-190 MW-54-190 Q2-2011 017 190

-176.9 4/12/2011 10:01 2.07E+03 6.18E+02 4.78E+02 1.90E+01 3.38E+00 1.77E+00 3.33E+00 7.86E+00 9.23E+00 8.70E-01 9.00E+00 1.00E+01 3.35E-01 1.58E+01 1.82E+01 1.97E+03 1.76E+01 MW-54-190 MW-54-190 Q2-2011 Mid 018 190

-176.9 7/18/2011 12:14 2.37E+03 6.06E+02 4.45E+02 1.75E+01 2.85E+00 1.12E+00 2.24E+00 1.16E+01 1.29E+01

-2.72E+00 1.18E+01 1.22E+01

-3.86E+00 1.55E+01 1.74E+01 1.97E+03 1.76E+01 MW-54-190 MW-55-24 Q3-2010 015 16 2.3 8/6/2010 13:11 1.21E+03 2.12E+02 1.30E+02 8.64E+00 1.22E+00 4.51E-01 1.13E+00 8.94E+00 1.04E+01 8.02E-01 8.22E+00 9.59E+00 1.17E+01 1.64E+01 1.81E+01 1.21E+03 1.01E+01 ND ND ND MW-55-24 MW-55-24 Q4-2010 016 16 2.3 11/1/2010 14:10 1.39E+03 2.09E+02 1.65E+02 1.08E+01 1.98E+00 9.92E-01

-2.29E-01 8.10E+00 9.04E+00

-4.71E+00 7.93E+00 6.54E+00 7.56E+00 1.88E+01 2.12E+01 1.21E+03 1.01E+01 MW-55-24 MW-55-24 Q1-2011 017 16 2.3 2/3/2011 14:13 1.02E+03 4.48E+02 4.20E+02 1.09E+01 2.82E+00 1.96E+00

-3.57E-01 4.92E+00 5.43E+00 4.75E+00 8.74E+00 7.44E+00

-5.31E+00 1.81E+01 2.14E+01 1.21E+03 1.01E+01 MW-55-24 MW-55-35 Q3-2010 014 32

-13.8 8/6/2010 13:15 1.89E+03 2.46E+02 1.25E+02 1.66E+01 1.65E+00 3.57E-01

-4.27E-01 8.60E+00 9.69E+00 4.31E+00 9.66E+00 1.22E+01 9.65E+00 1.62E+01 1.81E+01 1.72E+03 1.57E+01 ND ND ND MW-55-35 MW-55-35 Q4-2010 015 32

-13.8 11/1/2010 14:26 1.57E+03 2.12E+02 1.62E+02 1.13E+01 1.97E+00 9.17E-01

-2.41E+00 8.88E+00 9.46E+00 5.36E-01 8.18E+00 9.32E+00 6.22E+00 1.79E+01 2.03E+01 1.72E+03 1.57E+01 MW-55-35 MW-55-35 Q1-2011 016 32

-13.8 2/3/2011 14:16 1.70E+03 4.84E+02 3.86E+02 1.93E+01 3.42E+00 2.05E+00 8.32E-01 5.82E+00 6.45E+00 1.03E+00 6.24E+00 7.03E+00

-2.16E+00 1.86E+01 2.17E+01 1.72E+03 1.57E+01 MW-55-35 MW-55-54 Q3-2010 015 47

-28.8 8/6/2010 12:50 9.74E+03 5.22E+02 1.28E+02 1.93E+01 1.88E+00 3.96E-01

-1.51E+00 7.77E+00 8.26E+00 1.82E+00 7.26E+00 8.71E+00

-1.77E-01 1.41E+01 1.65E+01 8.96E+03 1.92E+01 ND ND ND MW-55-54 MW-55-54 Q4-2010 016 47

-28.8 11/1/2010 13:36 8.68E+03 3.95E+02 1.57E+02 1.93E+01 1.72E+00 6.48E-01

-3.03E+00 7.29E+00 7.24E+00 9.59E-01 7.50E+00 8.63E+00 1.12E-01 1.77E+01 2.04E+01 8.96E+03 1.92E+01 MW-55-54 MW-55-54 Q1-2011 017 47

-28.8 2/3/2011 14:17 8.46E+03 8.58E+02 3.89E+02 1.91E+01 3.78E+00 1.95E+00 3.62E+00 5.80E+00 7.00E+00

-6.59E-01 7.44E+00 7.93E+00

-8.13E+00 1.78E+01 2.14E+01 8.96E+03 1.92E+01 MW-55-54 MW-56-53 Q4-2010 009 52 18.3 11/15/2010 12:48 4.64E+02 1.88E+02 3.82E+02 1.27E+00 8.67E-01 1.86E+00 3.71E+00 4.39E+00 1.06E+01

-1.74E+00 4.89E+00 9.96E+00 NA NA NA 4.64E+02 ND ND ND NA MW-56-53 MW-56-53 Q2-2011 010 52 18.3 4/27/2011 12:08 1.18E+02 3.48E+02 3.97E+02

-3.07E-02 1.23E+00 1.60E+00 3.04E+00 8.50E+00 1.01E+01

-1.64E+00 8.42E+00 8.44E+00 NA NA NA 4.64E+02 MW-56-53 MW-56-53 Q2-2011 Mid 011 52 18.3 7/6/2011 12:58 2.03E+02 2.75E+02 2.83E+02

-3.68E-01 7.89E-01 1.12E+00 3.72E+00 7.77E+00 9.45E+00

-4.34E+00 8.82E+00 9.56E+00

-4.67E+00 2.28E+01 2.56E+01 4.64E+02 MW-56-53 MW-56-83 Q4-2010 011 74

-3.7 11/15/2010 14:37 2.74E+03 2.63E+02 3.84E+02 1.02E+00 7.08E-01 1.50E+00

-2.51E+00 3.87E+00 7.83E+00

-2.67E+00 3.90E+00 7.34E+00 NA NA NA 5.44E+04 2.66E+00 ND ND NA MW-56-83 MW-56-83 Q2-2011 012 74

-3.7 4/27/2011 13:46 7.64E+04 2.40E+03 4.19E+02 3.87E+00 1.60E+00 1.28E+00

-1.05E+00 1.14E+01 1.33E+01

-1.27E+00 9.50E+00 1.01E+01 NA NA NA 5.44E+04 2.66E+00 MW-56-83 MW-56-83 Q2-2011 Mid 013 74

-3.7 7/6/2011 11:58 8.42E+04 3.54E+03 2.81E+02 1.45E+00 1.27E+00 1.19E+00 2.77E+00 2.01E+01 9.44E+00 4.20E-01 8.16E+00 9.20E+00

-1.36E+01 2.15E+01 2.46E+01 5.44E+04 2.66E+00 MW-56-83 MW-57-11 Q2-2011 007 10 5

5/4/2011 10:28 6.40E+03 6.84E+02 3.41E+02 3.11E+01 3.62E+00 1.04E+00 3.74E+00 8.32E+00 9.74E+00 2.05E+00 8.40E+00 9.72E+00 6.20E+00 1.66E+01 1.85E+01 6.88E+03 3.49E+01 ND ND ND MW-57-11 MW-57-11 Q2-2011 Mid 008 10 5

7/18/2011 11:57 7.36E+03 9.18E+02 4.45E+02 3.87E+01 5.28E+00 2.11E+00 3.27E-01 8.88E+00 9.84E+00

-2.34E+00 9.18E+00 9.39E+00

-6.76E+00 1.48E+01 1.67E+01 6.88E+03 3.49E+01 MW-57-11 MW-57-20 Q2-2011 007 19

-4 5/4/2011 10:37 2.03E+04 1.15E+03 3.44E+02 1.74E+00 1.11E+00 9.49E-01 1.48E+00 7.52E+00 8.43E+00

-7.32E-01 9.22E+00 1.02E+01

-5.44E+00 1.64E+01 1.91E+01 2.92E+04 1.51E+00 ND ND ND MW-57-20 MW-57-20 Q2-2011 Mid 008 19

-4 7/18/2011 12:09 3.81E+04 1.94E+03 4.43E+02 1.27E+00 1.08E+00 1.01E+00

-5.13E+00 7.71E+00 7.35E+00 9.16E-01 8.67E+00 9.92E+00

-5.69E+00 1.93E+01 2.20E+01 2.92E+04 1.51E+00 MW-57-20 MW-57-45 Q2-2011 008 40

-25 5/4/2011 11:03 1.35E+04 9.48E+02 3.43E+02 9.06E-01 9.74E-01 9.60E-01 7.40E+00 9.54E+00 1.21E+01

-1.84E+00 9.48E+00 9.59E+00 6.39E+00 1.78E+01 1.98E+01 1.94E+04 ND ND ND ND MW-57-45 MW-57-45 Q2-2011 Mid 009 40

-25 7/18/2011 12:36 2.53E+04 1.60E+03 4.47E+02 1.28E+00 1.32E+00 1.34E+00

-2.08E-01 8.16E+00 8.83E+00

-7.58E-01 9.39E+00 9.67E+00

-1.04E+01 1.53E+01 1.74E+01 1.94E+04 MW-57-45 MW-58-26 Q4-2010 011 20

-5.4 11/11/2010 15:12 3.66E+02 1.73E+02 1.44E+02 4.13E-01 7.89E-01 8.92E-01 1.98E+00 3.81E+00 4.51E+00 2.98E+00 3.75E+00 4.70E+00 NA NA NA 9.83E+02 ND ND ND NA MW-58-26 MW-58-26 Q2-2011 012 20

-5.4 5/3/2011 9:58 7.22E+02 4.30E+02 4.21E+02 3.15E-01 1.13E+00 1.32E+00 2.29E+00 5.80E+00 6.89E+00

-6.42E+00 9.02E+00 8.00E+00 NA NA NA 9.83E+02 MW-58-26 MW-58-26 Q2-2011 Mid 013 20

-5.4 7/5/2011 13:29 1.86E+03 5.46E+02 4.47E+02

-3.25E-01 1.10E+00 1.41E+00 7.41E-01 6.84E+00 7.61E+00 1.22E+00 7.32E+00 8.39E+00

-1.01E+01 1.99E+01 2.25E+01 9.83E+02 MW-58-26 MW-58-65 Q4-2010 011 54

-39.4 11/11/2010 13:53 4.81E+02 1.88E+02 1.45E+02 7.15E-01 7.72E-01 8.31E-01 2.61E-01 3.71E+00 4.18E+00 3.74E+00 4.41E+00 5.49E+00 NA NA NA 6.04E+02 ND ND ND NA MW-58-65 MW-58-65 Q2-2011 012 54

-39.4 5/3/2011 10:11 3.29E+02 3.78E+02 3.97E+02

-4.47E-01 1.03E+00 1.44E+00 1.93E+00 5.92E+00 7.00E+00

-7.81E-01 7.04E+00 7.26E+00 NA NA NA 6.04E+02 MW-58-65 MW-58-65 Q2-2011 Mid 013 54

-39.4 7/5/2011 13:30 7.26E+02 3.93E+02 2.83E+02 4.19E-01 9.12E-01 1.03E+00 5.29E+00 1.05E+01 1.25E+01 1.47E+00 7.53E+00 8.78E+00 3.44E-01 2.03E+01 2.27E+01 6.04E+02 MW-58-65 MW-59-32 Q2-2011 Mid 005 27

-12.5 7/20/2011 9:59 1.56E+02 3.90E+02 4.38E+02 5.88E-01 1.14E+00 1.27E+00

-1.79E+00 7.92E+00 8.02E+00

-2.58E+00 9.78E+00 1.02E+01

-1.40E+01 1.82E+01 2.07E+01 ND ND ND ND ND MW-59-32 MW-59-45 Q2-2011 Mid 005 42

-27.5 7/20/2011 9:59 5.24E+02 4.35E+02 4.43E+02

-1.01E+00 1.05E+00 1.49E+00 1.81E+00 8.52E+00 9.88E+00 2.79E+00 9.48E+00 1.15E+01

-1.12E+01 1.83E+01 2.08E+01 5.24E+02 ND ND ND ND MW-59-45 MW-59-68 Q2-2011 Mid 005 58

-43.5 7/20/2011 10:14 1.15E+02 3.90E+02 4.42E+02 1.10E-01 7.26E-01 9.01E-01 2.83E+00 9.33E+00 1.09E+01 8.22E-01 9.87E+00 1.06E+01

-1.57E+01 2.17E+01 2.47E+01 ND ND ND ND ND MW-59-68 MW-60-35 Q3-2010 014 34.9

-22.4 8/16/2010 14:43 2.35E+02 1.42E+02 1.41E+02 3.19E-01 6.48E-01 7.39E-01 3.02E-01 5.73E+00 6.47E+00

-1.36E+00 6.23E+00 6.68E+00

-4.52E+00 2.14E+01 2.52E+01 2.35E+02 ND ND ND ND MW-60-35 MW-60-35 Q4-2010 015 34.9

-22.4 11/18/2010 13:25 2.44E+02 1.85E+02 4.00E+02

-5.33E-01 6.54E-01 1.73E+00 9.47E-01 4.80E+00 1.08E+01

-4.28E-01 4.56E+00 9.75E+00

-1.11E+01 8.47E+00 1.92E+01 2.35E+02 MW-60-35 MW-60-35 Q1-2011 016 34.9

-22.4 2/11/2011 12:17 3.20E+02 3.72E+02 3.88E+02 9.73E-01 1.63E+00 1.78E+00 2.69E+00 6.24E+00 7.46E+00 1.22E-01 3.76E+00 4.24E+00

-1.61E+00 1.62E+01 1.84E+01 2.35E+02 MW-60-35 MW-60-35 Q2-2011 017 34.9

-22.4 4/15/2011 11:36 2.03E+02 4.32E+02 4.80E+02 3.77E-01 1.66E+00 2.00E+00 2.46E+00 1.14E+01 8.95E+00

-8.48E-01 9.58E+00 1.03E+01 2.65E+00 1.42E+01 1.61E+01 2.35E+02 MW-60-35 MW-60-53 Q3-2010 014 53.4

-40.9 8/16/2010 15:34 2.58E+02 1.50E+02 1.60E+02

-2.84E-02 4.87E-01 6.04E-01

-8.42E+00 7.92E+00 7.70E+00

-2.64E+00 6.03E+00 6.02E+00

-8.48E+00 1.98E+01 2.37E+01 2.58E+02 ND ND ND ND MW-60-53 MW-60-53 Q4-2010 015 53.4

-40.9 11/18/2010 12:22 2.49E+02 1.83E+02 3.96E+02

-4.58E-01 4.20E-01 1.32E+00 4.54E-01 4.11E+00 9.15E+00 2.23E+00 3.57E+00 8.75E+00 1.10E+01 8.93E+00 1.96E+01 2.58E+02 MW-60-53 MW-60-53 Q1-2011 016 53.4

-40.9 2/11/2011 10:57 3.19E+02 3.70E+02 3.87E+02 7.44E-01 1.52E+00 1.70E+00

-2.03E+00 5.88E+00 6.16E+00 1.39E+00 7.96E+00 8.33E+00

-1.39E+00 1.50E+01 1.72E+01 2.58E+02 MW-60-53 MW-60-53 Q2-2011 017 53.4

-40.9 4/15/2011 11:37

-5.87E+01 3.96E+02 4.80E+02

-1.18E-02 1.60E+00 2.04E+00 2.17E+00 9.90E+00 1.14E+01

-1.11E+00 8.68E+00 8.95E+00

-1.06E+00 1.43E+01 1.66E+01 2.58E+02 MW-60-53 MW-60-72 Q3-2010 014 72.4

-59.9 8/17/2010 11:59 2.33E+01 1.23E+02 1.44E+02 1.97E-01 5.90E-01 6.91E-01

-5.91E-01 5.40E+00 6.06E+00

-1.59E+00 6.08E+00 6.57E+00 1.19E+00 2.04E+01 2.37E+01 ND ND ND ND ND MW-60-72 MW-60-72 Q4-2010 015 72.4

-59.9 11/16/2010 13:17

-2.51E+01 1.68E+02 3.98E+02 5.83E-02 5.15E-01 1.33E+00 2.12E+00 5.34E+00 1.26E+01

-3.92E+00 5.67E+00 1.09E+01

-1.14E+01 8.32E+00 1.89E+01 MW-60-72 MW-60-72 Q1-2011 016 72.4

-59.9 2/10/2011 12:54 3.64E+02 3.76E+02 3.84E+02 2.41E-01 1.45E+00 1.70E+00

-5.10E-02 9.12E+00 1.01E+01 2.27E+00 8.84E+00 1.07E+01 2.12E+00 1.54E+01 1.75E+01 MW-60-72 MW-60-72 Q2-2011 017 72.4

-59.9 4/15/2011 13:12 2.19E+02 3.78E+02 4.13E+02 7.12E-01 1.72E+00 1.97E+00

-5.14E+00 6.54E+00 5.80E+00

-3.30E+00 1.14E+01 1.14E+01

-2.93E+00 1.39E+01 1.63E+01 MW-60-72 MW-60-135 Q3-2010 014 134.9

-122.4 8/17/2010 12:09 1.87E+02 1.39E+02 1.43E+02

-2.74E-01 5.38E-01 7.27E-01

-3.46E+00 8.41E+00 9.07E+00

-1.52E+00 6.30E+00 6.70E+00 8.77E-01 2.11E+01 2.45E+01 3.33E+02 ND ND ND ND MW-60-135 MW-60-135 Q4-2010 015 134.9

-122.4 11/16/2010 13:22 2.41E+02 1.82E+02 3.96E+02

-4.96E-02 7.62E-01 1.88E+00 9.16E-01 5.37E+00 1.20E+01 1.02E+00 4.53E+00 1.03E+01 8.67E-01 8.52E+00 1.90E+01 3.33E+02 MW-60-135 MW-60-135 Q1-2011 016 134.9

-122.4 2/10/2011 13:04 3.98E+02 3.78E+02 3.83E+02 1.14E+00 1.82E+00 1.98E+00 1.72E+00 6.72E+00 7.79E+00 2.24E-01 7.44E+00 8.25E+00

-3.56E+00 1.52E+01 1.76E+01 3.33E+02 MW-60-135 MW-60-135 Q2-2011 017 134.9

-122.4 4/15/2011 13:25 4.14E+02 4.02E+02 4.12E+02 6.52E-01 1.90E+00 2.16E+00

-6.83E+00 1.39E+01 1.63E+01

-2.48E+00 9.86E+00 1.01E+01 4.64E+00 1.47E+01 1.65E+01 3.33E+02 MW-60-135 MW-60-154 Q3-2010 014 154.4

-141.9 8/17/2010 12:18 2.93E+02 1.50E+02 1.45E+02

-2.33E-01 5.00E-01 6.61E-01

-4.41E-01 6.04E+00 6.67E+00 1.95E+00 6.78E+00 8.02E+00

-1.16E+00 2.13E+01 2.48E+01 4.35E+02 ND ND ND ND MW-60-154 MW-60-154 Q4-2010 015 154.4

-141.9 11/16/2010 13:40 4.68E+02 1.94E+02 3.98E+02 3.29E-01 8.30E-01 1.94E+00

-5.28E+00 4.02E+00 7.52E+00

-2.29E-01 5.09E+00 1.11E+01

-4.54E+00 7.93E+00 1.78E+01 4.35E+02 MW-60-154 MW-60-154 Q1-2011 016 154.4

-141.9 2/10/2011 12:53 5.44E+02 4.02E+02 3.87E+02 2.32E-02 8.50E-01 1.07E+00

-4.12E+00 9.26E+00 8.97E+00 9.91E-01 7.86E+00 9.12E+00 4.61E+00 1.52E+01 1.71E+01 4.35E+02 MW-60-154 MW-60-154 Q2-2011 017 154.4

-141.9 4/15/2011 13:19 3.06E+02 3.96E+02 4.21E+02

-4.20E-01 1.53E+00 2.02E+00

-2.09E+00 7.62E+00 7.82E+00

-7.25E-01 6.50E+00 6.79E+00 1.62E+00 1.44E+01 1.64E+01 4.35E+02 MW-60-154 MW-60-176 Q3-2010 014 175.9

-163.4 8/17/2010 12:51 8.13E+02 1.91E+02 1.44E+02

-6.59E-01 6.48E-01 9.01E-01 1.23E-01 6.43E+00 7.32E+00 1.35E+00 5.80E+00 6.97E+00 0.00E+00 2.13E+01 2.48E+01 9.16E+02 ND ND ND ND MW-60-176 MW-60-176 Q4-2010 015 175.9

-163.4 11/16/2010 14:06 8.33E+02 2.10E+02 3.97E+02 9.07E-01 9.42E-01 2.10E+00

-1.97E+00 4.38E+00 9.04E+00 2.85E+00 4.70E+00 1.12E+01

-6.40E+00 7.91E+00 1.78E+01 9.16E+02 MW-60-176 MW-60-176 Q1-2011 016 175.9

-163.4 2/10/2011 10:31 1.12E+03 4.68E+02 3.85E+02 2.58E-01 1.49E+00 1.74E+00 4.88E+00 1.13E+01 6.69E+00

-1.75E+00 6.70E+00 6.74E+00 7.24E+00 1.62E+01 1.79E+01 9.16E+02 MW-60-176 MW-60-176 Q2-2011 017 175.9

-163.4 4/15/2011 13:49 8.99E+02 4.66E+02 4.18E+02

-8.29E-01 1.41E+00 2.10E+00

-7.83E-02 9.90E+00 1.10E+01

-2.35E+00 1.02E+01 1.03E+01

-2.40E-01 1.40E+01 1.62E+01 9.16E+02 MW-60-176 MW-62-18 Q3-2010 014 13.5 1.2 8/3/2010 13:00 1.14E+02 1.32E+02 1.44E+02 6.60E-01 6.55E-01 6.80E-01 3.08E+00 8.40E+00 1.03E+01 5.07E+00 1.02E+01 1.32E+01 NA NA NA ND 1.26E+00 ND ND NA MW-62-18 MW-62-18 Q4-2010 015 13.5 1.2 11/9/2010 11:57 7.48E+01 1.71E+02 3.86E+02

-1.05E-02 6.10E-01 1.54E+00 2.87E+00 4.59E+00 1.07E+01

-6.86E-01 4.79E+00 1.01E+01 NA NA NA 1.26E+00 MW-62-18 MW-62-18 Q1-2011 016 13.5 1.2 2/24/2011 12:49 1.81E+02 3.60E+02 4.00E+02

-3.86E-01 1.71E+00 2.13E+00 2.12E-01 4.74E+00 5.18E+00 3.58E+00 5.46E+00 6.78E+00 NA NA NA 1.26E+00 MW-62-18 MW-62-18 Q2-2011 017 13.5 1.2 4/13/2011 11:58 3.25E+02 4.56E+02 4.92E+02 7.82E-01 1.54E+00 1.71E+00

-4.38E+00 1.00E+01 1.09E+01

-4.07E-01 1.06E+01 1.16E+01 NA NA NA 1.26E+00 MW-62-18 MW-62-18 Q2-2011 Mid 018 13.5 1.2 7/22/2011 11:35 2.00E+02 4.02E+02 4.45E+02 1.26E+00 1.24E+00 1.25E+00 4.94E+00 9.42E+00 1.14E+01

-1.79E+00 1.05E+01 1.08E+01

-3.83E+00 1.96E+01 2.20E+01 1.26E+00 MW-62-18 MW-62-37 Q3-2010 014 34.5

-19.8 8/3/2010 12:52 1.91E+02 1.43E+02 1.47E+02

-1.52E-02 5.47E-01 6.85E-01

-9.69E-01 8.78E+00 9.70E+00

-5.33E+00 9.12E+00 7.92E+00 NA NA NA 1.91E+02 ND ND ND NA MW-62-37 MW-62-37 Q4-2010 015 34.5

-19.8 11/9/2010 11:56 6.09E+01 1.70E+02 3.85E+02 7.62E-01 6.69E-01 1.47E+00

-8.46E-02 4.49E+00 9.91E+00 3.83E+00 4.28E+00 1.07E+01 NA NA NA 1.91E+02 MW-62-37 MW-62-37 Q1-2011 016 34.5

-19.8 2/24/2011 12:52 3.05E+02 3.76E+02 4.00E+02 5.14E-01 1.84E+00 2.13E+00 1.07E+00 6.06E+00 6.86E+00

-2.84E+00 6.38E+00 6.28E+00 NA NA NA 1.91E+02 MW-62-37 MW-62-37 Q2-2011 017 34.5

-19.8 4/13/2011 12:10 1.56E+02 4.36E+02 4.91E+02

-1.97E-01 1.08E+00 1.37E+00

-4.48E+00 8.32E+00 7.76E+00

-1.68E+00 9.02E+00 9.05E+00 NA NA NA 1.91E+02 MW-62-37 MW-62-37 Q2-2011 Mid 018 34.5

-19.8 7/22/2011 12:28 1.15E+02 3.90E+02 4.42E+02 1.03E+00 1.60E+00 1.73E+00

-3.64E+00 7.95E+00 8.03E+00 2.96E+00 1.10E+01 1.30E+01

-8.92E+00 1.85E+01 2.09E+01 1.91E+02 MW-62-37 MW-62-53 Q3-2010 013 53.1

-40.3 8/3/2010 12:20 1.59E+02 1.40E+02 1.47E+02 3.13E-01 5.61E-01 6.32E-01 2.99E+00 1.11E+01 1.33E+01 2.39E-01 7.18E+00 8.24E+00 NA NA NA 1.59E+02 ND ND ND NA MW-62-53 MW-62-53 Q4-2010 014 53.1

-40.3 11/9/2010 12:49 2.05E+02 1.77E+02 3.88E+02 8.32E-02 6.79E-01 1.59E+00

-4.23E+00 4.83E+00 9.52E+00

-2.68E+00 5.26E+00 1.04E+01 NA NA NA 1.59E+02 MW-62-53 MW-62-53 Q1-2011 015 53.1

-40.3 2/24/2011 12:57 3.08E+02 3.78E+02 4.03E+02 8.98E-01 1.94E+00 2.18E+00

-2.62E-01 4.72E+00 5.23E+00

-1.84E+00 5.58E+00 5.81E+00 NA NA NA 1.59E+02 MW-62-53 MW-62-53 Q2-2011 016 53.1

-40.3 4/13/2011 11:32 1.57E+02 4.36E+02 4.92E+02 1.72E+00 1.79E+00 1.84E+00 5.42E-01 6.78E+00 7.51E+00

-3.00E-01 6.24E+00 6.58E+00 NA NA NA 1.59E+02 MW-62-53 MW-62-53 Q2-2011 Mid 017 53.1

-40.3 7/22/2011 10:47 1.60E+02 3.96E+02 4.45E+02

-4.83E-01 1.07E+00 1.58E+00 4.34E+00 7.86E+00 9.52E+00 1.66E+00 8.85E+00 1.02E+01

-1.60E+01 1.79E+01 2.05E+01 1.59E+02 MW-62-53 MW-62-71 Q3-2010 014 71.1

-58.3 8/3/2010 11:30 3.25E+02 1.70E+02 1.77E+02 2.44E-01 3.75E-01 4.12E-01

-2.03E+00 8.37E+00 8.99E+00 1.86E+00 9.87E+00 1.16E+01 NA NA NA 4.27E+02 ND ND ND NA MW-62-71 MW-62-71 Q4-2010 015 71.1

-58.3 11/9/2010 11:02 4.17E+02 1.83E+02 3.82E+02

-6.74E-02 6.02E-01 1.52E+00

-6.58E-01 3.90E+00 8.41E+00

-4.59E+00 5.63E+00 1.09E+01 NA NA NA 4.27E+02 MW-62-71 MW-62-71 Q1-2011 016 71.1

-58.3 2/24/2011 12:40 5.38E+02 4.06E+02 4.03E+02 1.28E-01 1.22E+00 1.48E+00 4.10E+00 1.18E+01 6.67E+00

-2.36E-01 5.00E+00 5.47E+00 NA NA NA 4.27E+02 MW-62-71 MW-62-71 Q2-2011 017 71.1

-58.3 4/13/2011 11:15 3.39E+02 4.72E+02 5.08E+02 9.04E-01 1.45E+00 1.58E+00 2.33E+00 7.96E+00 9.27E+00

-2.38E+00 8.50E+00 8.56E+00 NA NA NA 4.27E+02 MW-62-71 MW-62-71 Q2-2011 Mid 018 71.1

-58.3 7/22/2011 10:12 4.21E+02 4.26E+02 4.44E+02

-3.90E-01 1.36E+00 1.90E+00

-7.29E-02 7.74E+00 8.31E+00

-7.90E-01 8.28E+00 8.59E+00

-6.70E+00 1.89E+01 2.13E+01 4.27E+02 MW-62-71 MW-62-92 Q3-2010 014 91.6

-78.8 8/3/2010 11:32 3.18E+02 1.68E+02 1.76E+02 4.11E-01 5.37E-01 5.80E-01

-3.42E+00 8.13E+00 8.38E+00

-4.99E-01 7.59E+00 8.36E+00 NA NA NA 4.75E+02 ND ND ND NA MW-62-92 MW-62-92 Q4-2010 015 91.6

-78.8 11/9/2010 11:15 4.82E+02 1.88E+02 3.86E+02

-9.75E-01 7.72E-01 1.95E+00

-2.96E+00 5.42E+00 1.17E+01 1.77E+00 4.84E+00 1.12E+01 NA NA NA 4.75E+02 MW-62-92 MW-62-92 Q1-2011 016 91.6

-78.8 2/24/2011 12:39 5.09E+02 4.00E+02 4.02E+02 9.56E-01 1.85E+00 2.06E+00 1.68E+00 5.38E+00 6.27E+00

-1.45E+00 5.68E+00 5.86E+00 NA NA NA 4.75E+02 MW-62-92 MW-62-92 Q2-2011 017 91.6

-78.8 4/13/2011 11:03 5.06E+02 4.78E+02 4.92E+02 2.87E-01 1.11E+00 1.30E+00

-2.87E+00 7.18E+00 7.31E+00

-2.10E+00 8.94E+00 8.88E+00 NA NA NA 4.75E+02 MW-62-92 MW-62-92 Q2-2011 Mid 018 91.6

-78.8 7/22/2011 10:18 5.61E+02 4.35E+02 4.39E+02

-1.12E+00 1.52E+00 2.06E+00 5.26E+00 9.42E+00 1.13E+01

-7.24E-02 9.48E+00 1.05E+01

-6.69E+00 1.76E+01 1.99E+01 4.75E+02 MW-62-92 MW-62-138 Q3-2010 014 138.1

-125.3 8/3/2010 14:09 5.91E+02 1.82E+02 1.76E+02 1.47E+00 7.40E-01 6.56E-01 3.83E+00 7.26E+00 8.95E+00

-1.73E+00 7.35E+00 7.39E+00 NA NA NA 5.51E+02 1.81E+00 ND ND NA MW-62-138 MW-62-138 Q4-2010 015 138.1

-125.3 11/9/2010 14:31 3.31E+02 2.07E+02 4.46E+02

-1.05E-01 6.18E-01 1.57E+00

-1.42E+00 4.04E+00 8.57E+00 2.51E+00 4.68E+00 1.11E+01 NA NA NA 5.51E+02 1.81E+00 MW-62-138 MW-62-138 Q1-2011 016 138.1

-125.3 2/24/2011 14:54 5.17E+02 4.00E+02 4.01E+02 2.15E+00 1.77E+00 1.75E+00

-1.67E+00 4.72E+00 4.94E+00 1.88E+00 7.04E+00 8.19E+00 NA NA NA 5.51E+02 1.81E+00 MW-62-138 MW-62-138 Q2-2011 017 138.1

-125.3 4/13/2011 14:39 6.31E+02 5.04E+02 5.09E+02 1.22E+00 1.29E+00 1.32E+00 1.29E+00 9.08E+00 1.04E+01 1.71E+00 8.82E+00 1.02E+01 NA NA NA 5.51E+02 1.81E+00 MW-62-138 MW-62-138 Q2-2011 Mid 018 138.1

-125.3 7/22/2011 11:50 4.66E+02 4.23E+02 4.36E+02 6.72E-01 1.20E+00 1.32E+00

-5.97E-01 7.41E+00 8.13E+00 6.36E+00 9.57E+00 1.23E+01

-1.13E+01 1.79E+01 2.03E+01 5.51E+02 1.81E+00 MW-62-138 MW-62-182 Q3-2010 014 182.1

-169.3 8/3/2010 14:02 2.78E+02 1.65E+02 1.75E+02 2.87E-01 7.05E-01 8.30E-01

-5.53E+00 1.24E+01 1.51E+01

-9.25E-01 8.00E+00 8.64E+00 NA NA NA 3.77E+02 ND ND ND NA MW-62-182 MW-62-182 Q4-2010 015 182.1

-169.3 11/9/2010 14:43 4.76E+02 1.88E+02 3.87E+02 1.02E+00 6.77E-01 1.46E+00

-2.35E+00 4.16E+00 8.56E+00 1.99E+00 5.26E+00 1.21E+01 NA NA NA 3.77E+02 MW-62-182 MW-62-182 Q1-2011 016 182.1

-169.3 2/24/2011 15:07 3.55E+02 3.84E+02 4.03E+02

-1.46E-01 1.45E+00 1.94E+00

-1.95E+00 6.24E+00 6.60E+00 5.86E-01 6.60E+00 7.33E+00 NA NA NA 3.77E+02 MW-62-182 MW-62-182 Q2-2011 017 182.1

-169.3 4/13/2011 14:44 1.92E+02 4.50E+02 5.03E+02

-5.04E-01 1.05E+00 1.45E+00 5.54E+00 8.70E+00 1.09E+01

-9.44E-01 1.08E+01 1.15E+01 NA NA NA 3.77E+02 MW-62-182 MW-62-182 Q2-2011 Mid 018 182.1

-169.3 7/22/2011 12:02 2.90E+02 4.20E+02 4.54E+02 2.09E-01 1.22E+00 1.47E+00 6.48E-01 7.41E+00 8.36E+00

-5.94E-01 7.65E+00 8.31E+00

-2.27E+00 1.56E+01 1.75E+01 3.77E+02 MW-62-182 MW-63-18 Q3-2010 014 14.9 0.7 8/10/2010 12:08 1.62E+02 1.58E+02 1.73E+02

-1.55E-02 3.48E-01 4.72E-01

-6.04E-01 7.20E+00 8.11E+00

-2.17E+00 6.42E+00 6.45E+00 NA NA NA 3.44E+02 ND ND ND NA MW-63-18 MW-63-18 Q4-2010 015 14.9 0.7 11/2/2010 12:22 1.97E+02 1.18E+02 1.13E+02 1.31E-01 6.87E-01 8.18E-01 1.81E+00 5.46E+00 6.40E+00 3.45E+00 6.55E+00 8.07E+00 NA NA NA 3.44E+02 MW-63-18 MW-63-18 Q1-2011 016 14.9 0.7 3/2/2011 11:10 4.90E+02 3.58E+02 3.55E+02

-4.34E-01 1.50E+00 2.03E+00 1.82E+00 6.78E+00 7.90E+00 2.40E+00 7.38E+00 8.82E+00 NA NA NA 3.44E+02 MW-63-18 MW-63-18 Q2-2011 017 14.9 0.7 4/19/2011 10:35 7.23E+01 4.38E+02 5.05E+02

-3.13E-01 1.13E+00 1.49E+00 8.69E-01 8.04E+00 8.92E+00

-3.22E+00 8.16E+00 7.75E+00 NA NA NA 3.44E+02 MW-63-18 MW-63-18 Q2-2011 Mid 018 14.9 0.7 7/21/2011 10:26 2.96E+02 3.99E+02 4.29E+02 6.58E-02 1.19E+00 1.50E+00 2.40E+00 7.62E+00 9.09E+00 2.37E+00 7.53E+00 9.30E+00

-8.91E+00 1.69E+01 1.92E+01 3.44E+02 MW-63-18

TABLE 3 SECOND QUARTER 2011 GROUNDWATER ANALYTICAL RESULTS AND AVERAGES INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q22011 FINAL Table 3 - Second Quarter 2011 Groundwater Analytical Results and Averages.xlsx; Q22011 Table 3 Page 5 of 6 See Page 6 for Notes TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Date Time Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Average Average Average Average Average ANALYSIS RESULTS5 YEARLY ROLLING AVERAGES4,6 Well ID1 TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

SAMPLE COLLECTION Well ID1 SAMPLING QUARTER2,8 SAMPLE ID SAMPLE ZONE CENTER Depth Ft Below Top of Casing3 SAMPLE ZONE CENTER Elevation Ft msl3 MW-63-34 Q3-2010 014 31.5

-17.3 8/10/2010 11:44 1.89E+02 1.64E+02 1.78E+02 2.21E-01 3.59E-01 3.95E-01 2.60E+00 9.29E+00 1.06E+01 3.10E+00 7.21E+00 9.27E+00 NA NA NA 2.76E+02 ND ND ND NA MW-63-34 MW-63-34 Q4-2010 015 31.5

-17.3 11/2/2010 13:04 3.41E+02 1.35E+02 1.14E+02 3.11E-01 5.72E-01 6.45E-01 1.16E-01 5.66E+00 6.29E+00

-2.31E+00 6.33E+00 6.51E+00 NA NA NA 2.76E+02 MW-63-34 MW-63-34 Q1-2011 016 31.5

-17.3 3/2/2011 10:50 2.98E+02 2.86E+02 2.62E+02

-4.29E-01 1.57E+00 2.11E+00 7.43E-02 7.96E+00 8.82E+00

-2.10E+00 8.42E+00 8.59E+00 NA NA NA 2.76E+02 MW-63-34 MW-63-34 Q2-2011 017 31.5

-17.3 4/19/2011 10:25 3.94E+02 4.60E+02 4.87E+02

-1.13E+00 1.22E+00 1.83E+00 4.36E+00 8.34E+00 9.94E+00 3.72E+00 8.28E+00 1.02E+01 NA NA NA 2.76E+02 MW-63-34 MW-63-34 Q2-2011 Mid 018 31.5

-17.3 7/21/2011 10:08 3.04E+02 4.08E+02 4.39E+02 2.38E-01 1.17E+00 1.42E+00

-1.34E+00 9.03E+00 9.54E+00 1.66E-01 7.89E+00 8.63E+00

-1.26E+01 1.28E+01 1.47E+01 2.76E+02 MW-63-34 MW-63-50 Q3-2010 014 49.5

-37.2 8/10/2010 14:32 2.72E+02 1.65E+02 1.75E+02

-2.47E-02 5.47E-01 6.90E-01

-1.32E+00 7.10E+00 7.82E+00 7.73E-01 7.74E+00 8.96E+00 NA NA NA 3.45E+02 ND ND ND NA MW-63-50 MW-63-50 Q4-2010 015 49.5

-37.2 11/2/2010 15:07 3.29E+02 1.31E+02 1.12E+02 2.27E-01 6.23E-01 7.23E-01

-2.98E-02 7.72E+00 8.42E+00 2.76E+00 8.00E+00 9.78E+00 NA NA NA 3.45E+02 MW-63-50 MW-63-50 Q1-2011 016 49.5

-37.2 3/2/2011 14:21 4.35E+02 3.40E+02 3.44E+02 1.73E-01 1.62E+00 2.03E+00 1.13E+00 6.50E+00 7.48E+00 3.64E+00 7.02E+00 8.70E+00 NA NA NA 3.45E+02 MW-63-50 MW-63-50 Q2-2011 017 49.5

-37.2 4/19/2011 11:25 1.68E+02 4.36E+02 4.89E+02 7.72E-01 1.39E+00 1.53E+00

-6.46E+00 9.76E+00 9.29E+00 3.72E+00 8.18E+00 1.03E+01 NA NA NA 3.45E+02 MW-63-50 MW-63-50 Q2-2011 Mid 018 49.5

-37.2 7/21/2011 11:25 2.09E+02 3.99E+02 4.41E+02

-6.50E-01 8.58E-01 1.39E+00 2.46E-01 7.56E+00 8.55E+00 2.77E+00 8.64E+00 1.05E+01

-2.89E+00 1.51E+01 1.69E+01 3.45E+02 MW-63-50 MW-63-93 Q3-2010 015 93

-80.7 8/10/2010 15:10 1.95E+02 1.61E+02 1.74E+02

-1.91E-01 4.38E-01 6.16E-01 1.24E+00 6.64E+00 7.70E+00 2.61E-01 7.58E+00 8.46E+00 NA NA NA 2.17E+02 ND ND ND NA MW-63-93 MW-63-93 Q4-2010 016 93

-80.7 11/2/2010 15:08 2.39E+02 1.21E+02 1.11E+02 3.29E-01 5.72E-01 6.42E-01

-4.18E-02 4.95E+00 5.64E+00 3.38E+00 5.80E+00 7.11E+00 NA NA NA 2.17E+02 MW-63-93 MW-63-93 Q1-2011 017 93

-80.7 3/2/2011 14:14 2.69E+02 3.00E+02 2.94E+02 3.30E-01 1.79E+00 2.17E+00

-1.51E+00 8.78E+00 9.05E+00 3.38E+00 7.56E+00 9.56E+00 NA NA NA 2.17E+02 MW-63-93 MW-63-93 Q2-2011 018 93

-80.7 4/19/2011 11:27 9.64E+01 4.42E+02 5.05E+02

-4.30E-02 1.14E+00 1.44E+00 3.31E+00 8.92E+00 1.03E+01

-4.35E-01 6.80E+00 7.25E+00 NA NA NA 2.17E+02 MW-63-93 MW-63-93 Q2-2011 Mid 019 93

-80.7 7/21/2011 11:32 4.17E+02 4.20E+02 4.40E+02

-4.28E-01 1.06E+00 1.48E+00

-3.58E+00 8.10E+00 7.77E+00

-6.11E+00 7.92E+00 5.51E+00 6.50E-01 1.71E+01 1.90E+01 2.17E+02 MW-63-93 MW-63-112 Q3-2010 014 111.5

-99.2 8/10/2010 14:52 3.71E+02 1.73E+02 1.78E+02 2.83E-01 4.37E-01 4.78E-01

-3.00E+00 7.68E+00 7.90E+00

-5.28E+00 9.73E+00 9.11E+00 NA NA NA 4.03E+02 ND ND ND NA MW-63-112 MW-63-112 Q4-2010 015 111.5

-99.2 11/2/2010 15:05 3.01E+02 1.29E+02 1.13E+02 6.02E-02 5.25E-01 6.51E-01

-2.54E+00 6.29E+00 6.56E+00 1.96E+00 6.72E+00 7.95E+00 NA NA NA 4.03E+02 MW-63-112 MW-63-112 Q1-2011 016 111.5

-99.2 3/2/2011 14:15 3.38E+02 3.18E+02 2.96E+02 1.48E-01 1.60E+00 2.00E+00

-3.72E-01 6.70E+00 7.21E+00 1.19E+00 6.36E+00 7.21E+00 NA NA NA 4.03E+02 MW-63-112 MW-63-112 Q2-2011 017 111.5

-99.2 4/19/2011 11:25 4.22E+02 4.68E+02 4.92E+02

-7.96E-01 1.00E+00 1.47E+00 4.96E+00 1.05E+01 1.25E+01 1.64E+00 1.17E+01 1.36E+01 NA NA NA 4.03E+02 MW-63-112 MW-63-112 Q2-2011 Mid 018 111.5

-99.2 7/21/2011 11:46 6.01E+02 4.44E+02 4.44E+02 2.29E-01 1.13E+00 1.37E+00

-8.46E-01 1.06E+01 1.11E+01 6.03E+00 1.21E+01 1.54E+01

-1.22E+00 1.77E+01 1.98E+01 4.03E+02 MW-63-112 MW-63-121 Q3-2010 014 121

-108.7 8/10/2010 11:28 5.39E+02 1.80E+02 1.77E+02 3.67E-01 5.93E-01 6.58E-01

-9.48E-01 8.12E+00 8.95E+00

-6.58E-01 8.76E+00 9.58E+00 NA NA NA 6.94E+02 ND ND ND NA MW-63-121 MW-63-121 Q4-2010 015 121

-108.7 11/2/2010 11:46 5.20E+02 1.49E+02 1.10E+02 6.38E-01 7.57E-01 8.11E-01 1.17E+00 6.66E+00 7.68E+00

-4.06E+00 7.17E+00 6.83E+00 NA NA NA 6.94E+02 MW-63-121 MW-63-121 Q1-2011 016 121

-108.7 3/2/2011 11:10 5.03E+02 3.54E+02 2.94E+02

-6.82E-02 1.55E+00 2.03E+00

-6.26E-01 6.72E+00 7.20E+00 3.49E-01 6.00E+00 6.67E+00 NA NA NA 6.94E+02 MW-63-121 MW-63-121 Q2-2011 017 121

-108.7 4/19/2011 9:54 5.77E+02 4.84E+02 4.91E+02 4.12E-01 1.18E+00 1.37E+00

-1.03E+00 6.92E+00 7.17E+00

-1.09E+01 9.86E+00 5.99E+00 NA NA NA 6.94E+02 MW-63-121 MW-63-121 Q2-2011 Mid 018 121

-108.7 7/21/2011 9:58 1.33E+03 5.28E+02 4.45E+02

-3.05E-01 1.36E+00 1.74E+00 1.63E-03 7.44E+00 8.17E+00

-3.19E+00 1.05E+01 1.07E+01 1.12E+00 1.84E+01 2.05E+01 6.94E+02 MW-63-121 MW-63-163 Q3-2010 014 162.5

-150.2 8/10/2010 11:21 4.13E+02 1.74E+02 1.78E+02 2.45E-01 4.43E-01 4.98E-01

-6.87E-01 8.55E+00 9.17E+00

-5.25E-01 8.23E+00 9.24E+00 NA NA NA 4.93E+02 ND ND ND NA MW-63-163 MW-63-163 Q4-2010 015 162.5

-150.2 11/2/2010 11:49 4.44E+02 1.41E+02 1.10E+02 7.71E-01 8.38E-01 8.77E-01

-3.99E+00 9.88E+00 1.10E+01 2.94E+00 6.12E+00 7.63E+00 NA NA NA 4.93E+02 MW-63-163 MW-63-163 Q1-2011 016 162.5

-150.2 3/2/2011 10:27 6.05E+02 3.76E+02 2.95E+02 1.37E+00 1.99E+00 2.12E+00 3.09E+00 5.40E+00 6.62E+00

-2.05E+00 7.72E+00 7.12E+00 NA NA NA 4.93E+02 MW-63-163 MW-63-163 Q2-2011 017 162.5

-150.2 4/19/2011 9:49 4.92E+02 4.84E+02 5.03E+02 1.11E+00 1.82E+00 2.00E+00 4.43E-01 8.94E+00 9.98E+00 4.78E+00 1.02E+01 1.26E+01 NA NA NA 4.93E+02 MW-63-163 MW-63-163 Q2-2011 Mid 018 162.5

-150.2 7/21/2011 10:09 5.08E+02 4.26E+02 4.36E+02

-6.14E-01 1.01E+00 1.48E+00

-8.47E-01 7.47E+00 8.17E+00 4.07E-01 7.53E+00 8.66E+00

-8.69E+00 1.47E+01 1.67E+01 4.93E+02 MW-63-163 MW-63-174 Q3-2010 014 174

-161.7 8/10/2010 11:40 3.33E+02 1.65E+02 1.71E+02 3.54E-01 5.43E-01 6.01E-01

-3.32E+00 7.07E+00 6.89E+00

-1.41E+00 7.84E+00 8.11E+00 NA NA NA 3.36E+02 ND ND ND NA MW-63-174 MW-63-174 Q4-2010 015 174

-161.7 11/2/2010 11:50 2.63E+02 1.26E+02 1.13E+02

-1.42E-01 4.59E-01 6.06E-01

-6.01E-01 6.03E+00 6.82E+00 2.17E-01 6.42E+00 7.11E+00 NA NA NA 3.36E+02 MW-63-174 MW-63-174 Q1-2011 016 174

-161.7 3/2/2011 10:26 4.13E+02 3.30E+02 2.91E+02 8.20E-01 1.80E+00 2.03E+00 3.65E+00 6.96E+00 8.18E+00 2.34E+00 7.86E+00 9.20E+00 NA NA NA 3.36E+02 MW-63-174 MW-63-174 Q2-2011 017 174

-161.7 4/19/2011 9:52 1.56E+02 4.48E+02 5.04E+02

-7.87E-01 9.72E-01 1.48E+00

-6.41E+00 8.32E+00 7.72E+00

-9.85E-01 8.58E+00 9.20E+00 NA NA NA 3.36E+02 MW-63-174 MW-63-174 Q2-2011 Mid 018 174

-161.7 7/21/2011 9:57 4.14E+02 4.17E+02 4.36E+02 6.96E-01 1.85E+00 2.10E+00

-3.57E+00 8.10E+00 8.27E+00 4.67E-01 9.36E+00 1.09E+01

-2.55E+00 1.33E+01 1.49E+01 3.36E+02 MW-63-174 MW-65-48 Q2-2011 Mid 002 43.3 26.356 7/7/2011 12:19 8.59E+01 2.43E+02 2.85E+02 5.73E-01 1.04E+00 1.15E+00 4.10E+00 9.03E+00 1.09E+01

-1.15E+00 1.12E+01 1.18E+01

-5.93E+00 2.39E+01 2.69E+01 ND ND ND ND ND MW-65-48 MW-65-80 Q2-2011 Mid 003 71.4

-1.659 7/13/2011 10:12 8.54E+01 2.41E+02 2.84E+02 1.26E-01 9.24E-01 1.12E+00

-2.33E+00 9.12E+00 9.46E+00 2.88E+00 1.15E+01 1.34E+01

-1.27E+01 2.00E+01 2.29E+01 ND ND ND ND ND MW-65-80 MW-66-21 Q3-2010 014 14.1 0

8/9/2010 12:30 1.07E+03 2.01E+02 1.29E+02 1.17E+00 5.52E-01 4.41E-01

-5.85E+00 9.45E+00 9.34E+00

-9.97E-01 8.07E+00 8.65E+00 3.11E+00 1.19E+01 1.37E+01 7.74E+02 1.17E+00 ND ND ND MW-66-21 MW-66-21 Q4-2010 015 14.1 0

11/10/2010 15:13 3.22E+02 1.64E+02 3.46E+02 2.57E-01 7.74E-01 1.84E+00 6.04E+00 5.26E+00 1.28E+01

-1.91E-01 5.67E+00 1.26E+01 9.56E+00 8.45E+00 1.85E+01 7.74E+02 1.17E+00 MW-66-21 MW-66-21 Q1-2011 016 14.1 0

1/31/2011 16:26 4.77E+02 4.08E+02 4.24E+02 3.48E-01 1.73E+00 2.02E+00

-2.19E-01 5.00E+00 5.33E+00 9.80E-01 6.50E+00 7.23E+00

-1.06E+00 1.84E+01 2.14E+01 7.74E+02 1.17E+00 MW-66-21 MW-66-21 Q2-2011 017 14.1 0

4/14/2011 13:43 9.30E+01 3.88E+02 4.46E+02 6.73E-01 1.64E+00 1.85E+00

-4.70E+00 8.74E+00 8.45E+00 6.94E+00 9.82E+00 1.25E+01 1.81E+00 1.51E+01 1.72E+01 7.74E+02 1.17E+00 MW-66-21 MW-66-36 Q3-2010 013 33.6

-19.5 8/9/2010 11:47 3.08E+03 3.06E+02 1.24E+02 6.40E+00 1.07E+00 3.74E-01

-1.53E+00 8.82E+00 9.41E+00 4.62E+00 7.61E+00 1.02E+01 4.59E+00 1.58E+01 1.80E+01 3.19E+03 9.98E+00 ND ND ND MW-66-36 MW-66-36 Q4-2010 014 33.6

-19.5 11/10/2010 12:33 3.13E+03 2.96E+02 3.96E+02 7.43E+00 1.03E+00 1.13E+00 5.42E+00 3.87E+00 9.67E+00 7.18E-01 4.34E+00 9.81E+00

-4.23E+00 9.63E+00 2.16E+01 3.19E+03 9.98E+00 MW-66-36 MW-66-36 Q1-2011 015 33.6

-19.5 1/31/2011 15:51 3.01E+03 6.78E+02 4.61E+02 1.55E+01 3.18E+00 2.11E+00

-1.13E+00 6.12E+00 6.49E+00

-8.31E-01 6.80E+00 7.15E+00

-4.89E+00 1.79E+01 2.12E+01 3.19E+03 9.98E+00 MW-66-36 MW-66-36 Q2-2011 016 33.6

-19.5 4/14/2011 12:53 3.52E+03 7.36E+02 4.79E+02 1.06E+01 2.88E+00 1.95E+00 1.50E-01 7.24E+00 8.14E+00 5.40E-01 7.92E+00 9.01E+00 6.10E-01 1.55E+01 1.79E+01 3.19E+03 9.98E+00 MW-66-36 MW-67-39 Q3-2010 014 38.3

-25.8 8/9/2010 10:43 3.37E+03 3.15E+02 1.22E+02 8.52E+00 1.21E+00 5.69E-01

-9.27E+00 1.08E+01 1.30E+01

-1.39E+00 8.28E+00 8.77E+00

-2.31E+00 1.43E+01 1.69E+01 3.63E+03 1.05E+01 ND ND ND MW-67-39 MW-67-39 Q4-2010 015 38.3

-25.8 11/10/2010 11:49 3.56E+03 3.09E+02 3.95E+02 5.43E+00 8.85E-01 1.10E+00 1.04E+00 3.96E+00 8.88E+00 2.82E+00 4.30E+00 1.04E+01

-1.86E+00 9.87E+00 2.21E+01 3.63E+03 1.05E+01 MW-67-39 MW-67-39 Q1-2011 016 38.3

-25.8 2/7/2011 13:48 3.85E+03 7.60E+02 4.81E+02 1.57E+01 3.34E+00 1.83E+00 8.03E-02 6.18E+00 6.83E+00 6.64E-01 6.78E+00 7.57E+00 4.43E+00 1.97E+01 2.23E+01 3.63E+03 1.05E+01 MW-67-39 MW-67-39 Q2-2011 017 38.3

-25.8 4/14/2011 13:25 3.73E+03 7.14E+02 4.17E+02 1.25E+01 3.76E+00 2.10E+00 4.53E+00 8.78E+00 1.04E+01 3.71E+00 9.54E+00 1.14E+01 6.99E+00 1.47E+01 1.63E+01 3.63E+03 1.05E+01 MW-67-39 MW-67-105 Q3-2010 013 104.8

-92.3 8/9/2010 10:37 1.26E+03 2.10E+02 1.24E+02 2.61E+00 8.16E-01 6.26E-01 1.46E+00 6.24E+00 7.48E+00 1.75E+00 5.78E+00 7.28E+00 9.56E+00 1.69E+01 1.90E+01 1.12E+03 2.61E+00 ND ND ND MW-67-105 MW-67-105 Q4-2010 014 104.8

-92.3 11/10/2010 11:42 1.14E+03 2.24E+02 3.95E+02 1.41E+00 8.12E-01 1.69E+00

-1.68E+00 3.59E+00 7.64E+00

-3.12E+00 4.14E+00 8.26E+00 1.24E+00 8.56E+00 1.90E+01 1.12E+03 2.61E+00 MW-67-105 MW-67-105 Q1-2011 015 104.8

-92.3 2/7/2011 13:57 9.94E+02 4.26E+02 3.86E+02 3.37E-01 1.64E+00 1.94E+00 2.40E+00 4.84E+00 5.67E+00

-1.22E+00 4.86E+00 4.81E+00

-4.59E+00 1.96E+01 2.31E+01 1.12E+03 2.61E+00 MW-67-105 MW-67-105 Q2-2011 016 104.8

-92.3 4/14/2011 13:43 1.10E+03 4.84E+02 4.12E+02 2.70E-01 1.72E+00 2.11E+00

-3.96E-01 9.66E+00 1.05E+01

-1.91E-01 7.24E+00 7.88E+00 5.71E+00 1.55E+01 1.73E+01 1.12E+03 2.61E+00 MW-67-105 MW-67-173 Q3-2010 014 172.3

-159.8 8/9/2010 11:07 6.72E+02 1.71E+02 1.27E+02 7.70E-02 4.44E-01 5.35E-01

-7.06E-01 1.34E+01 1.68E+01 6.44E-01 8.97E+00 1.04E+01

-1.44E+00 1.14E+01 1.34E+01 6.23E+02 ND ND ND ND MW-67-173 MW-67-173 Q4-2010 015 172.3

-159.8 11/10/2010 12:04 6.25E+02 2.01E+02 3.97E+02

-9.99E-01 6.33E-01 1.86E+00 4.02E-01 7.80E+00 1.12E+01

-1.17E+00 4.83E+00 1.03E+01

-1.65E+00 8.09E+00 1.81E+01 6.23E+02 MW-67-173 MW-67-173 Q1-2011 016 172.3

-159.8 2/7/2011 14:13 4.47E+02 4.48E+02 4.65E+02

-2.38E-01 1.68E+00 2.12E+00

-4.75E-01 5.28E+00 5.83E+00 7.55E-01 6.38E+00 5.76E+00

-7.05E-01 1.88E+01 2.18E+01 6.23E+02 MW-67-173 MW-67-173 Q2-2011 017 172.3

-159.8 4/14/2011 14:09 5.72E+02 4.20E+02 4.10E+02

-2.56E-01 1.69E+00 1.99E+00 5.04E+00 9.64E+00 1.17E+01

-9.27E+00 1.03E+01 6.85E+00 7.50E+00 1.23E+01 1.34E+01 6.23E+02 MW-67-173 MW-67-219 Q3-2010 013 218.8

-206.3 8/9/2010 13:33 1.11E+03 2.01E+02 1.25E+02 9.94E-02 5.32E-01 6.41E-01

-7.99E-01 8.14E+00 9.12E+00

-6.19E+00 9.03E+00 8.33E+00 2.34E+00 1.21E+01 1.39E+01 9.93E+02 ND ND ND ND MW-67-219 MW-67-219 Q4-2010 014 218.8

-206.3 11/10/2010 13:40 1.15E+03 2.24E+02 3.96E+02 3.53E-01 7.28E-01 1.78E+00

-2.80E-01 3.60E+00 7.62E+00 2.49E-01 3.62E+00 7.89E+00

-4.41E+00 8.84E+00 1.98E+01 9.93E+02 MW-67-219 MW-67-219 Q1-2011 015 218.8

-206.3 1/31/2011 14:48 6.41E+02 4.18E+02 4.20E+02

-1.08E+00 1.42E+00 1.97E+00 9.72E-01 5.80E+00 6.44E+00 2.44E+00 5.46E+00 6.55E+00

-4.58E+00 1.81E+01 2.14E+01 9.93E+02 MW-67-219 MW-67-219 Q2-2011 016 218.8

-206.3 4/14/2011 10:49 1.07E+03 4.78E+02 4.12E+02

-7.57E-01 9.50E-01 1.53E+00

-2.70E+00 6.62E+00 6.47E+00 4.16E+00 9.78E+00 1.20E+01 2.95E+00 1.43E+01 1.62E+01 9.93E+02 MW-67-219 MW-67-276 Q3-2010 013 275.3

-262.8 8/9/2010 13:36 9.33E+02 1.86E+02 1.22E+02 4.00E-01 4.66E-01 4.98E-01 2.56E+00 7.23E+00 8.80E+00

-2.39E+00 8.22E+00 8.27E+00 9.94E+00 1.28E+01 1.42E+01 9.70E+02 ND ND ND ND MW-67-276 MW-67-276 Q4-2010 014 275.3

-262.8 11/10/2010 14:16 1.01E+03 2.18E+02 3.96E+02

-7.85E-01 5.64E-01 1.77E+00 1.94E+00 4.26E+00 9.92E+00

-5.48E+00 4.42E+00 7.40E+00 5.46E+00 8.55E+00 1.89E+01 9.70E+02 MW-67-276 MW-67-276 Q1-2011 015 275.3

-262.8 1/31/2011 14:31 8.75E+02 4.18E+02 3.87E+02

-2.57E-02 1.66E+00 2.03E+00

-2.56E+00 8.76E+00 8.16E+00 6.49E-01 6.48E+00 7.20E+00

-7.18E-01 1.92E+01 2.22E+01 9.70E+02 MW-67-276 MW-67-276 Q2-2011 016 275.3

-262.8 4/14/2011 10:53 1.06E+03 4.84E+02 4.19E+02 3.46E-01 1.22E+00 1.45E+00

-5.30E+00 6.78E+00 6.12E+00 1.62E+00 1.02E+01 1.15E+01 5.62E-01 1.42E+01 1.63E+01 9.70E+02 MW-67-276 MW-67-323 Q3-2010 013 322.3

-309.8 8/9/2010 13:23 4.32E+02 1.48E+02 1.23E+02 6.38E-01 6.31E-01 6.53E-01 1.47E+00 6.88E+00 8.02E+00 3.28E-01 6.72E+00 7.56E+00

-4.51E+00 1.37E+01 1.63E+01 4.29E+02 ND ND ND ND MW-67-323 MW-67-323 Q4-2010 014 322.3

-309.8 11/10/2010 14:03 3.88E+02 1.89E+02 3.94E+02 1.89E-01 8.21E-01 2.01E+00 2.70E+00 4.61E+00 1.06E+01 3.11E-01 5.07E+00 1.12E+01

-3.22E+00 7.93E+00 1.78E+01 4.29E+02 MW-67-323 MW-67-323 Q1-2011 015 322.3

-309.8 1/31/2011 15:04 3.38E+02 3.70E+02 3.90E+02 2.58E-01 1.71E+00 2.03E+00 2.47E-01 5.70E+00 6.35E+00 8.12E-03 5.80E+00 6.35E+00

-5.93E+00 1.90E+01 2.25E+01 4.29E+02 MW-67-323 MW-67-323 Q2-2011 016 322.3

-309.8 4/14/2011 11:33 4.26E+02 4.06E+02 4.13E+02 1.05E+00 1.52E+00 1.62E+00 2.02E+00 8.36E+00 9.62E+00

-1.12E+00 7.80E+00 8.21E+00

-2.21E-01 1.30E+01 1.50E+01 4.29E+02 MW-67-323 MW-67-340 Q3-2010 013 339.8

-327.3 8/9/2010 13:20 4.86E+02 1.55E+02 1.25E+02

-3.81E-02 5.00E-01 6.29E-01 1.20E+00 7.44E+00 8.75E+00

-2.42E+00 6.98E+00 7.06E+00 2.60E+00 1.45E+01 1.67E+01 5.58E+02 ND ND ND ND MW-67-340 MW-67-340 Q4-2010 014 339.8

-327.3 11/10/2010 13:53 5.31E+02 1.97E+02 3.95E+02

-8.93E-01 5.00E-01 1.64E+00 1.72E+00 4.50E+00 1.03E+01

-2.97E+00 3.90E+00 7.25E+00 2.25E+00 8.84E+00 1.97E+01 5.58E+02 MW-67-340 MW-67-340 Q1-2011 015 339.8

-327.3 1/31/2011 14:53 2.75E+02 3.58E+02 3.83E+02

-7.06E-01 1.51E+00 1.99E+00 4.30E-01 6.34E+00 7.02E+00

-1.15E+00 6.54E+00 6.88E+00

-5.79E+00 1.85E+01 2.20E+01 5.58E+02 MW-67-340 MW-67-340 Q2-2011 016 339.8

-327.3 4/14/2011 11:17 6.56E+02 4.32E+02 4.13E+02 2.62E-01 1.16E+00 1.40E+00 5.89E+00 9.02E+00 1.12E+01 4.57E+00 9.02E+00 1.15E+01 7.58E+00 1.54E+01 1.71E+01 5.58E+02 MW-67-340 MW-107 Q2-2011 010 32.7 110.1 5/2/2011 9:25 3.15E+02 3.76E+02 3.95E+02 8.29E-01 1.29E+00 1.40E+00

-3.56E+00 1.30E+01 1.65E+01 2.39E+00 6.84E+00 8.63E+00 NA NA NA ND ND ND ND NA MW-107 MW-108 Q2-2011 Mid 005 8.3 6.2 7/5/2011 15:08 1.24E+03 4.89E+02 2.90E+02

-9.21E-02 1.29E+00 1.55E+00 4.93E+00 9.84E+00 1.17E+01

-7.54E+00 8.49E+00 7.19E+00

-8.75E+00 2.32E+01 2.62E+01 1.24E+03 ND ND ND ND MW-108 MW-109 Q2-2011 Mid 005 8.5 6.1 7/5/2011 12:45 2.43E+03 6.36E+02 2.79E+02 2.60E-01 1.25E+00 1.45E+00 2.23E-01 8.67E+00 9.62E+00

-3.32E+00 7.74E+00 6.65E+00 3.57E+00 3.51E+01 3.92E+01 2.43E+03 ND ND ND ND MW-109 MW-111 Q3-2010 033 16.5 2.4 8/27/2010 15:21 3.86E+04 1.13E+03 1.28E+02 6.44E-01 8.07E-01 8.55E-01

-8.83E-01 6.30E+00 6.59E+00 1.88E+00 5.70E+00 6.84E+00 NA NA NA 4.38E+04 1.80E+00 ND ND NA MW-111 MW-111 Q3-2010 Mid 034 16.5 2.4 9/10/2010 14:09 4.69E+04 1.37E+03 1.40E+02 1.80E+00 1.00E+00 8.02E-01

-5.04E+00 6.84E+00 6.88E+00

-5.62E-01 6.84E+00 7.62E+00 NA NA NA 4.38E+04 1.80E+00 MW-111 MW-111 Q4-2010 035 16.5 2.4 11/1/2010 14:55 4.59E+04 1.34E+03 1.27E+02 3.47E-01 5.90E-01 6.60E-01

-1.99E-01 5.63E+00 6.38E+00 5.49E+00 5.91E+00 7.75E+00 NA NA NA 4.38E+04 1.80E+00 MW-111 U3-3 Q2-2011 Mid 014 7/13/2011 12:28 6.73E+02 3.81E+02 2.81E+02

-3.49E-01 8.13E-01 1.19E+00

-4.64E-01 8.01E+00 8.64E+00

-3.52E+00 8.61E+00 8.20E+00 NA NA NA 6.73E+02 ND ND ND NA U3-3 U3-4D Q3-2010 025 25.6

-10.8 7/23/2010 13:21 6.84E+02 1.86E+02 1.77E+02

-1.56E-01 4.60E-01 6.46E-01 2.21E+00 7.56E+00 8.91E+00

-1.01E+00 7.61E+00 8.14E+00 NA NA NA 6.91E+02 ND ND ND NA U3-4D U3-4D Q4-2010 026 25.6

-10.8 10/28/2010 14:04 7.12E+02 1.68E+02 1.13E+02 2.26E-01 4.89E-01 5.61E-01 2.75E+00 5.75E+00 6.97E+00 1.33E+00 7.82E+00 9.00E+00 NA NA NA 6.91E+02 U3-4D U3-4D Q1-2011 027 25.6

-10.8 2/17/2011 14:41 6.28E+02 4.14E+02 4.05E+02

-8.34E-02 1.55E+00 1.95E+00 1.24E+00 4.72E+00 5.29E+00 8.61E-01 4.84E+00 5.47E+00 NA NA NA 6.91E+02 U3-4D U3-4D Q2-2011 028 25.6

-10.8 4/25/2011 14:50 7.41E+02 4.36E+02 3.98E+02 1.18E+00 1.38E+00 1.46E+00

-3.17E+00 7.58E+00 7.50E+00 4.81E-01 7.14E+00 8.11E+00 NA NA NA 6.91E+02 U3-4D U3-4D Q2-2011 Mid 029 25.6

-10.8 7/14/2011 11:55 3.88E+02 4.20E+02 4.38E+02 1.24E-01 1.06E+00 1.26E+00 4.78E+00 1.13E+01 1.32E+01 3.12E+00 1.22E+01 1.46E+01 NA NA NA 6.91E+02 U3-4D U3-4S Q3-2010 001 7/23/2010 14:12 3.74E+02 1.74E+02 1.79E+02 3.76E-01 4.15E-01 4.21E-01 9.00E-01 8.51E+00 9.30E+00 1.89E+00 7.75E+00 9.37E+00 NA NA NA 3.63E+02 ND ND ND NA U3-4S U3-4S Q4-2010 002 10/29/2010 11:40 3.51E+02 1.32E+02 1.10E+02 3.86E-01 5.82E-01 6.43E-01 1.64E+00 5.59E+00 6.52E+00

-2.02E+00 5.91E+00 6.14E+00 NA NA NA 3.63E+02 U3-4S U3-4S Q2-2011 003 4/25/2011 14:13 1.48E+02 3.78E+02 4.22E+02 6.69E-01 1.27E+00 1.41E+00 5.35E+00 8.82E+00 1.07E+01 1.75E+00 8.92E+00 1.03E+01 NA NA NA 3.63E+02 U3-4S U3-4S Q2-2011 Mid 004 7/14/2011 11:27 3.29E+02 4.11E+02 4.36E+02 1.06E+00 1.33E+00 1.40E+00

-2.41E+00 7.59E+00 7.88E+00 3.25E+00 7.65E+00 9.52E+00 NA NA NA 3.63E+02 U3-4S U3-T1 Q3-2010 029 5.7 2.8 7/26/2010 12:15 3.84E+02 1.74E+02 1.78E+02 1.20E-02 3.91E-01 4.99E-01 5.07E+00 7.68E+00 9.77E+00

-6.61E-01 6.96E+00 7.49E+00 NA NA NA 5.31E+02 ND ND ND NA U3-T1 U3-T1 Q4-2010 030 5.7 2.8 10/29/2010 16:04 3.04E+02 1.28E+02 1.10E+02 4.84E-02 6.36E-01 7.68E-01

-8.56E-01 6.04E+00 6.70E+00 1.59E+00 5.73E+00 6.79E+00 NA NA NA 5.31E+02 U3-T1 U3-T1 Q1-2011 031 5.7 2.8 2/22/2011 11:11 6.55E+02 4.08E+02 3.92E+02 1.62E+00 1.96E+00 2.02E+00 1.80E+00 1.05E+01 6.14E+00 2.12E+00 6.42E+00 7.54E+00 NA NA NA 5.31E+02 U3-T1 U3-T1 Q2-2011 032 5.7 2.8 5/6/2011 10:23 7.82E+02 5.16E+02 5.03E+02

-6.43E-02 9.94E-01 1.30E+00

-3.24E+00 9.12E+00 9.22E+00 8.49E-01 1.09E+01 1.21E+01 NA NA NA 5.31E+02 U3-T1 U3-T2 Q3-2010 034 5.7 2.6 7/26/2010 14:26 8.76E+02 1.92E+02 1.74E+02 5.34E-01 6.12E-01 6.47E-01

-2.12E+00 7.50E+00 7.69E+00 2.29E+00 7.21E+00 8.84E+00 NA NA NA 2.22E+03 ND ND ND NA U3-T2 U3-T2 Q4-2010 035 5.7 2.6 10/29/2010 11:22 1.47E+03 2.19E+02 1.11E+02 4.22E-01 6.79E-01 7.56E-01

-6.11E-02 5.42E+00 6.11E+00 3.00E+00 5.47E+00 6.89E+00 NA NA NA 2.22E+03 U3-T2 U3-T2 Q1-2011 036 5.7 2.6 2/22/2011 14:30 2.27E+03 4.92E+02 3.62E+02 1.82E+00 2.04E+00 2.05E+00 3.65E+00 6.08E+00 7.29E+00 5.97E-01 7.12E+00 7.85E+00 NA NA NA 2.22E+03 U3-T2 U3-T2 Q2-2011 037 5.7 2.6 5/6/2011 11:41 3.83E+03 6.42E+02 4.19E+02 3.27E-01 1.32E+00 1.58E+00 2.82E+00 7.26E+00 8.74E+00 5.77E-01 9.68E+00 1.08E+01 NA NA NA 2.22E+03 U3-T2 U3-T2 Q2-2011 Mid 038 5.7 2.6 7/8/2011 10:55 2.67E+03 6.63E+02 2.80E+02 4.75E-01 1.31E+00 1.50E+00 3.77E+00 1.08E+01 1.19E+01

-1.06E+00 1.02E+01 1.07E+01 NA NA NA 2.22E+03 U3-T2 U1-CSS Q4-2010 015 14 6.1 11/8/2010 14:56 2.26E+03 2.72E+02 1.26E+02 1.18E+01 1.45E+00 6.84E-01 2.29E+00 5.01E+00 5.93E+00 2.07E+00 5.61E+00 6.70E+00 3.16E-01 1.81E+01 2.13E+01 6.48E+03 1.06E+01 ND ND ND U1-CSS U1-CSS Q2-2011 016 14 6.1 5/4/2011 13:24 6.38E+03 6.84E+02 3.40E+02 1.61E+01 2.70E+00 1.01E+00 3.29E+00 8.36E+00 9.79E+00 7.12E+00 9.42E+00 1.24E+01

-1.05E+01 1.55E+01 1.84E+01 6.48E+03 1.06E+01 U1-CSS U1-CSS Q2-2011 Mid 017 14 6.1 7/8/2011 13:33 1.08E+04 1.28E+03 2.79E+02 3.90E+00 1.82E+00 1.30E+00 3.84E-02 9.18E+00 1.01E+01

-3.60E+00 9.96E+00 1.06E+01

-3.20E+00 2.09E+01 2.34E+01 6.48E+03 1.06E+01 U1-CSS

TABLE 3 SECOND QUARTER 2011 GROUNDWATER ANALYTICAL RESULTS AND AVERAGES INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q22011 FINAL Table 3 - Second Quarter 2011 Groundwater Analytical Results and Averages.xlsx; Q22011 Table 3 Page 6 of 6 See Page 6 for Notes TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Date Time Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Average Average Average Average Average ANALYSIS RESULTS5 YEARLY ROLLING AVERAGES4,6 Well ID1 TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

SAMPLE COLLECTION Well ID1 SAMPLING QUARTER2,8 SAMPLE ID SAMPLE ZONE CENTER Depth Ft Below Top of Casing3 SAMPLE ZONE CENTER Elevation Ft msl3 U1-NCD Q3-2010 008 7/15/2010 9:10 1.35E+04 4.41E+02 1.58E+02 5.06E+01 3.21E+00 7.59E-01 1.14E+04 1.42E+03 1.40E+01 7.51E-01 5.21E+00 6.03E+00 2.90E+02 3.39E+01 2.40E+01 8.42E+03 4.47E+01 1.17E+04 ND 2.61E+02 U1-NCD U1-NCD Q4-2010 009 10/20/2010 13:40 3.34E+03 3.23E+02 1.27E+02 3.88E+01 2.31E+00 6.39E-01 1.20E+04 1.47E+03 9.98E+00

-1.14E+00 4.96E+00 5.42E+00 2.31E+02 3.19E+01 2.23E+01 8.42E+03 4.47E+01 1.17E+04 2.61E+02 U1-NCD U1-SFDS Q3-2010 009 7/7/2010 8:45 6.44E+02 1.80E+02 1.45E+02 1.88E+01 2.10E+00 6.82E-01 2.09E+01 1.26E+01 7.48E+00 1.64E+00 7.91E+00 9.44E+00 3.42E+00 2.24E+01 2.58E+01 5.63E+02 1.53E+01 1.44E+01 ND ND U1-SFDS U1-SFDS Q4-2010 010 10/20/2010 8:45 4.82E+02 1.56E+02 1.26E+02 1.17E+01 1.83E+00 8.74E-01 7.99E+00 7.54E+00 5.78E+00

-8.31E-01 5.24E+00 5.67E+00 9.71E-01 1.86E+01 2.18E+01 5.63E+02 1.53E+01 1.44E+01 U1-SFDS I-2 Q3-2010 001 8/2/2010 14:39 6.21E+01 1.53E+02 1.73E+02

-2.56E-01 3.72E-01 5.25E-01 7.04E+00 7.80E+00 1.02E+01 9.34E-02 6.54E+00 7.19E+00 NA NA NA ND ND ND ND NA I-2 I-2 Q4-2010 002 11/17/2010 14:25 1.74E+02 1.71E+02 3.78E+02 2.25E-01 6.25E-01 1.50E+00

-4.50E-01 5.04E+00 1.10E+01 3.35E+00 5.94E+00 1.40E+01 NA NA NA I-2 MH-5 VCFD7 Q3-2010 010 8/5/2010 14:45 7.32E+02 1.89E+02 1.77E+02 5.37E-01 5.67E-01 5.84E-01 7.26E-01 7.72E+00 8.69E+00

-2.26E+00 6.93E+00 7.07E+00 NA NA NA 4.73E+03 ND ND ND NA MH-5 VCFD7 MH-5 VCFD Q3-2010 011 8/30/2010 13:30 9.96E+03 5.48E+02 1.26E+02 1.25E-01 3.21E-01 3.81E-01 1.50E+00 5.58E+00 6.48E+00 8.08E-01 6.51E+00 7.50E+00 NA NA NA 4.73E+03 MH-5 VCFD MH-5 VCFD Q3-2010 Mid 012 9/10/2010 15:30 8.80E+02 1.89E+02 1.25E+02 3.60E-01 6.35E-01 7.11E-01 7.21E-01 6.45E+00 7.44E+00 1.23E+00 5.71E+00 6.85E+00 NA NA NA 4.73E+03 MH-5 VCFD MH-5 VCFD Q4-2010 013 11/24/2010 11:10 4.60E+02 1.86E+02 1.47E+02 1.36E-01 7.57E-01 8.85E-01 1.75E+00 3.45E+00 4.02E+00 5.48E-01 3.79E+00 4.28E+00 NA NA NA 4.73E+03 MH-5 VCFD MH-5 VCFD Q1-2011 014 2/28/2011 9:47 5.17E+03 6.58E+02 3.66E+02 1.90E+00 1.99E+00 1.94E+00 3.45E-01 5.64E+00 6.19E+00

-1.28E+00 6.18E+00 6.45E+00 NA NA NA 4.73E+03 MH-5 VCFD MH-5 VCFD Q2-2011 015 4/22/2011 13:37 1.25E+04 1.10E+03 4.46E+02 8.17E-01 1.85E+00 2.08E+00

-3.21E+00 8.36E+00 8.43E+00

-1.60E+00 9.06E+00 9.51E+00 NA NA NA 4.73E+03 MH-5 VCFD MH-5 VCFD Q2-2011 Mid 018 7/7/2011 14:29 2.97E+03 7.02E+02 2.83E+02

-3.05E-01 8.04E-01 1.11E+00 9.24E-01 7.95E+00 8.84E+00 5.11E-01 8.49E+00 9.13E+00 NA NA NA 4.73E+03 MH-5 VCFD MH-5 VCFD Q2-2011 Mid 019 7/12/2011 12:46 9.86E+03 1.23E+03 2.81E+02 9.15E-01 1.05E+00 1.06E+00

-1.17E+01 1.33E+01 1.52E+01

-1.19E+00 9.99E+00 1.06E+01 NA NA NA 4.73E+03 MH-5 VCFD MH-5 VCFD Q2-2011 Mid 020 7/20/2011 10:48 2.89E+03 7.32E+02 3.35E+02

-4.57E-01 1.01E+00 1.47E+00 1.79E+00 6.30E+00 7.26E+00

-2.61E+00 8.34E+00 8.34E+00 NA NA NA 4.73E+03 MH-5 VCFD MH-5 VCFD Q2-2011 Mid 021 7/26/2011 12:50 1.86E+03 6.03E+02 3.33E+02

-7.10E-01 9.45E-01 1.45E+00 2.81E+00 7.47E+00 8.99E+00

-8.33E-01 9.66E+00 1.03E+01 NA NA NA 4.73E+03 MH-5 VCFD LAF-002 Q4-2010 014

-22.3 11/22/2010 14:41 1.02E+02 1.13E+02 1.21E+02 1.96E-01 4.62E-01 5.40E-01

-6.13E-01 6.13E+00 6.83E+00

-1.60E+00 5.88E+00 6.15E+00 3.65E+00 1.77E+01 2.05E+01 ND ND ND ND ND LAF-002 LAF-002 Q2-2011 015

-22.3 5/2/2011 12:50 6.69E+01 3.04E+02 3.43E+02 1.16E+00 1.55E+00 1.66E+00

-5.80E-01 7.86E+00 8.57E+00

-6.46E-01 7.24E+00 7.65E+00

-3.48E-01 1.60E+01 1.83E+01 LAF-002 B-17 Q3-2010 009 8/17/2010 15:40 1.40E+04 6.48E+02 1.27E+02 1.25E-01 6.43E-01 7.91E-01 2.27E+01 1.06E+01 5.87E+00 2.96E+00 6.00E+00 7.45E+00 NA NA NA 7.07E+03 ND 2.09E+01 ND NA B-17 B-1 Q4-2010 010 11/17/2010 11:10 2.37E+03 2.72E+02 3.86E+02 6.87E-01 7.68E-01 1.72E+00 1.89E+01 6.46E+00 7.93E+00 8.39E-01 4.32E+00 9.74E+00 NA NA NA 7.07E+03 2.09E+01 B-1 B-1 Q1-2011 011 2/14/2011 15:44 3.82E+03 5.88E+02 3.65E+02 5.41E-02 1.70E+00 2.14E+00 2.15E+01 1.22E+01 6.75E+00

-1.81E+00 7.00E+00 7.25E+00 NA NA NA 7.07E+03 2.09E+01 B-1 B-1 Q2-2011 012 4/25/2011 10:50 8.10E+03 9.22E+02 4.53E+02

-6.21E-03 1.74E+00 2.09E+00 2.05E+01 1.33E+01 1.03E+01 3.18E+00 9.06E+00 1.11E+01 NA NA NA 7.07E+03 2.09E+01 B-1 B-67 Q3-2010 009 8/5/2010 13:43 1.49E+02 1.62E+02 1.79E+02 1.12E-01 8.02E-01 9.78E-01 2.32E+00 6.57E+00 8.03E+00

-9.21E-02 8.23E+00 9.37E+00 NA NA NA 1.35E+03 ND ND ND NA B-67 B-6 Q4-2010 010 11/8/2010 11:45 1.05E+02 1.33E+02 1.43E+02 1.43E-01 6.60E-01 7.68E-01 0.00E+00 5.04E+00 6.20E+00

-3.20E-01 4.70E+00 5.29E+00 NA NA NA 1.35E+03 B-6 B-6 Q1-2011 011 2/28/2011 11:27 8.39E+02 3.90E+02 3.65E+02 6.28E-01 1.78E+00 2.05E+00 4.45E+00 5.82E+00 7.02E+00

-1.35E+00 6.50E+00 6.88E+00 NA NA NA 1.35E+03 B-6 B-6 Q2-2011 012 4/25/2011 9:48 2.68E+03 6.18E+02 4.53E+02

-6.69E-01 1.58E+00 2.09E+00

-1.31E-01 8.56E+00 9.08E+00 4.73E+00 1.06E+01 1.35E+01 NA NA NA 1.35E+03 B-6 B-6 Q2-2011 Mid 013 7/8/2011 11:05 5.39E+02 3.54E+02 2.82E+02 1.32E+00 1.56E+00 1.63E+00 6.09E+00 1.58E+01 8.04E+00

-2.64E+00 8.97E+00 8.84E+00 NA NA NA 1.35E+03 B-6 Notes:

1. For nested multi-level monitoring wells, suffix of well ID indicates depth (rounded to nearest foot) from reference point on casing to bottom of well screen. For Waterloo multi-level systems, suffix indicates depth (rounded to nearest foot) from reference point on casing to top of sampling port. Well IDs without a suffix are open bedrock wellbores.
2. All analytical results from the last 12 months from each location are provided. Monitoring locations are sampled quarterly, bi-annually, or annually, and as necessary during the year.
3. Sampling depths within sampling intervals (i.e. location of pump intake) have been located adjacent to a transmissive zone where possible.
4. Averages provided are analytical result averages of all valid samples (including mid-quarter and confirmatory samples) collected from each monitoring location from the third quarter of 2010 (Q3-2010) to the second quarter of 2011 (Q2-2011) including the post Q2-2011 samples.

Monitoring locations are sampled quarterly, bi-annually, or annually and additional samples are collected when necessary. Therefore, some results provided are the average of more than 4 samples.

For quarters in which samples were reanalyzed due to potential false positives, both results were used to calculate averages if subsequent results confirmed the validity of the original sample/analysis. For cases in which reanalysis discredited the validity of the original sample result, the replacement results were used to calculate the average. If analytical results resulted in resampling, and the resample result discredited the validity of the original sample result of a particular radionuclide, the original sample results were not used for any radionuclides and only the resample result was used. For cases in which an aliquot of the original sample was reanalyzed, if the result of the aliquot confirmed the original result, then the aliquot result and the original result were averaged and the average of the two was used to calculate the rolling average. If the aliquot result indicated the original result was false, then only the aliquot result was used to calculate the rolling average.

5. NA indicates that the constituent was not analyzed.
6. ND indicates that all of the analytical results used to calculate the average were less than MDC and/or 3 times the 1 sigma uncertainty.
7. These locations are storm drains or foundation drains.
8. Mid-quarter samples were collected and analyzed to evaluate the potential effect of certain operations on groundwater quality.
9. Column designated as Std. Dev. provides the three times 1 sigma uncertainty values.
  • The Q1 2011 MW-40-100, MW-40-127 and MW-51-189 Cs-137 results were verified by re-analysis. However, based on the available chemistry and Site hydrogeologic data, these values do not appear to be representative of the groundwater conditions at these sampling intervals.
    • The Q2 2011 MW-40-46 preliminary Sr-90 result was 2.83 pCi/L and exceeded the IL. However, after re-analysis, the sample was below the detection limit which suggests the preliminary result was likely a false positive. A shift in the MDC for the preliminary result could have possibly resulted from contaminated laboratory equipment, modified count time, or changes in sample preparation.

TABLE 3 THIRD QUARTER 2011 GROUNDWATER ANALYTICAL RESULTS AND AVERAGES INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q32011 FINAL Table 3 - Third Quarter 2011 Groundwater Analytical Results and Averages.xlsx; Q32011 Table 3 Page 1 of 6 See Page 6 for Notes TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Date Time Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Average Average Average Average Average MW-30-69 Q4-2010 036 69.3 6.4 11/5/2010 11:56 1.25E+05 1.88E+03 4.34E+02 9.69E-01 8.79E-01 1.94E+00

-3.68E+00 3.94E+00 7.79E+00

-5.01E+00 5.09E+00 9.47E+00 NA NA NA 1.13E+05 2.40E+00 ND ND NA MW-30-69 MW-30-69 Q1-2011 037 69.3 6.4 2/9/2011 12:17 1.01E+05 2.18E+03 2.98E+02 1.62E+00 1.93E+00 2.00E+00 1.87E+00 5.80E+00 6.74E+00

-1.13E-01 5.88E+00 6.44E+00 NA NA NA 1.13E+05 2.40E+00 MW-30-69 Q1-2011 Mid 038 69.3 6.4 3/31/2011 11:38 1.08E+05 3.40E+03 4.72E+02

-6.11E-01 1.63E+00 2.15E+00 2.48E+00 7.96E+00 9.14E+00

-1.41E+00 6.70E+00 6.46E+00 NA NA NA 1.13E+05 2.40E+00 ND ND NA MW-30-69 MW-30-69 Q2-2011 039 69.3 6.4 5/5/2011 12:08 1.13E+05 3.48E+03 3.99E+02 2.40E+00 1.37E+00 1.23E+00 2.46E+00 8.92E+00 1.03E+01 2.21E+00 9.58E+00 1.16E+01 NA NA NA 1.13E+05 2.40E+00 MW-30-69 MW-30-69 Q2-2011 Mid 040 69.3 6.4 7/11/2011 12:05 1.19E+05 4.23E+03 2.83E+02

-6.14E-02 7.62E-01 1.00E+00 3.56E+00 1.07E+01 1.24E+01 2.40E+00 1.19E+01 1.40E+01 NA NA NA 1.13E+05 2.40E+00 MW-30-69 MW-30-69 Q3-2011 041 69.3 6.4 8/9/2011 10:49 1.14E+05 3.45E+03 4.22E+02 1.02E+00 1.76E+00 1.92E+00

-7.63E-01 1.03E+01 1.15E+01

-2.42E+00 8.58E+00 8.50E+00 NA NA NA 1.13E+05 2.40E+00 MW-30-69 MW-30-84 Q4-2010 027 83.8

-8.1 11/5/2010 12:35 1.02E+04 4.80E+02 3.87E+02 5.25E-01 7.56E-01 1.70E+00

-3.07E+00 4.23E+00 8.38E+00

-5.22E+00 4.86E+00 8.20E+00 NA NA NA 8.44E+03 ND ND ND NA MW-30-84 MW-30-84 Q1-2011 028 83.8

-8.1 2/9/2011 12:57 9.20E+03 8.86E+02 3.79E+02 1.12E+00 1.82E+00 1.98E+00 5.89E-01 4.74E+00 5.22E+00 1.09E+00 5.76E+00 6.49E+00 NA NA NA 8.44E+03 MW-30-84 MW-30-84 Q1-2011 Mid 029 83.8

-8.1 3/31/2011 12:03 9.04E+03 1.06E+03 4.74E+02

-4.78E-01 1.66E+00 2.13E+00 5.00E-01 1.12E+01 1.21E+01

-3.04E+00 9.48E+00 9.12E+00 NA NA NA 8.44E+03 MW-30-84 MW-30-84 Q2-2011 030 83.8

-8.1 5/5/2011 12:58 7.57E+03 9.46E+02 3.92E+02 1.64E-01 1.15E+00 1.40E+00 3.00E+00 8.04E+00 9.35E+00 4.65E-02 7.14E+00 7.76E+00 NA NA NA 8.44E+03 MW-30-84 MW-30-84 Q2-2011 Mid 031 83.8

-8.1 7/11/2011 12:45 7.55E+03 1.08E+03 2.82E+02

-3.75E-01 9.75E-01 1.29E+00 2.17E-01 7.89E+00 8.89E+00 1.39E+01 1.16E+01 1.59E+01 NA NA NA 8.44E+03 MW-30-84 MW-30-84 Q3-2011 032 83.8

-8.1 8/9/2011 11:16 7.06E+03 7.05E+02 3.54E+02

-1.22E+00 1.28E+00 1.92E+00

-1.67E+00 7.08E+00 7.43E+00

-3.28E+00 9.63E+00 9.46E+00 NA NA NA 8.44E+03 MW-30-84 MW-31-49 Q4-2010 028 48.8 26.8 11/3/2010 11:55 3.35E+04 9.81E+02 1.15E+02

-3.04E-02 4.26E-01 5.51E-01

-2.82E+00 8.51E+00 8.97E+00 2.22E+00 8.87E+00 1.06E+01 NA NA NA 8.99E+03 ND ND ND NA MW-31-49 MW-31-49 Q1-2011 029 48.8 26.8 2/9/2011 13:12 1.06E+03 3.40E+02 2.98E+02

-5.51E-01 1.76E+00 2.14E+00 1.39E+00 5.22E+00 6.02E+00 4.84E-01 5.26E+00 5.91E+00 NA NA NA 8.99E+03 MW-31-49 MW-31-49 Q1-2011 Mid 030 48.8 26.8 3/30/2011 12:33 4.31E+03 7.84E+02 4.65E+02 1.77E+00 2.04E+00 2.16E+00

-2.34E+00 7.80E+00 8.17E+00

-5.38E-01 9.18E+00 1.00E+01 NA NA NA 8.99E+03 MW-31-49 MW-31-49 Q2-2011 031 48.8 26.8 4/18/2011 12:53 1.08E+03 5.20E+02 4.66E+02 4.98E-01 1.81E+00 2.09E+00

-1.82E+00 8.82E+00 9.22E+00 6.17E+00 8.70E+00 1.13E+01 NA NA NA 8.99E+03 MW-31-49 MW-31-49 Q3-2011 033 48.8 26.8 8/5/2011 10:47 4.98E+03 7.80E+02 4.16E+02

-2.63E-02 1.34E+00 1.58E+00 6.39E+00 8.76E+00 1.10E+01 5.20E-01 1.06E+01 1.16E+01 NA NA NA 8.99E+03 MW-31-49 MW-31-63 Q4-2010 028 63.3 12.3 11/3/2010 12:32 2.95E+04 9.02E+02 1.14E+02 3.31E-01 6.30E-01 7.13E-01

-2.24E+00 9.63E+00 1.02E+01 3.44E+00 8.40E+00 1.07E+01 NA NA NA 2.04E+04 ND ND ND NA MW-31-63 MW-31-63 Q1-2011 029 63.3 12.3 2/9/2011 13:14 2.46E+04 1.10E+03 2.98E+02 4.29E-01 1.78E+00 2.08E+00

-1.42E+00 6.46E+00 6.81E+00

-2.31E+00 6.42E+00 6.26E+00 NA NA NA 2.04E+04 MW-31-63 MW-31-63 Q1-2011 Mid 030 63.3 12.3 3/30/2011 13:13 1.33E+04 1.14E+03 4.53E+02 1.49E+00 1.87E+00 2.02E+00 8.76E-01 9.00E+00 9.97E+00

-1.92E-01 7.26E+00 7.92E+00 NA NA NA 2.04E+04 MW-31-63 MW-31-63 Q2-2011 031 63.3 12.3 4/18/2011 13:21 1.81E+04 1.45E+03 4.67E+02 7.26E-01 1.84E+00 2.08E+00

-3.10E-01 7.62E+00 8.46E+00 1.76E+00 8.74E+00 1.03E+01 NA NA NA 2.04E+04 MW-31-63 MW-31-63 Q3-2011 033 63.3 12.3 8/5/2011 11:29 1.63E+04 1.31E+03 4.18E+02

-1.30E-01 1.71E+00 2.02E+00

-2.83E-01 9.87E+00 1.12E+01 2.13E+00 9.24E+00 1.08E+01 NA NA NA 2.04E+04 MW-31-63 MW-31-85 Q4-2010 028 84.8

-9.2 11/3/2010 12:00 6.06E+03 4.16E+02 1.14E+02 2.41E-01 4.83E-01 5.47E-01

-1.36E+00 8.88E+00 9.62E+00

-2.66E-01 1.08E+01 1.19E+01 NA NA NA 3.91E+03 ND ND ND NA MW-31-85 MW-31-85 Q1-2011 029 84.8

-9.2 2/9/2011 13:03 4.83E+03 6.84E+02 3.82E+02 3.26E-01 1.79E+00 2.18E+00 3.19E+00 5.96E+00 7.08E+00 3.14E+00 6.06E+00 7.39E+00 NA NA NA 3.91E+03 MW-31-85 MW-31-85 Q1-2011 Mid 030 84.8

-9.2 3/30/2011 12:55 7.75E+02 4.66E+02 4.52E+02 9.37E-01 1.81E+00 2.00E+00 5.90E+00 1.31E+01 8.10E+00 6.43E+00 8.88E+00 1.17E+01 NA NA NA 3.91E+03 MW-31-85 MW-31-85 Q2-2011 031 84.8

-9.2 4/18/2011 13:18 3.08E+03 6.96E+02 4.66E+02

-1.09E+00 1.46E+00 2.09E+00

-4.50E+00 9.34E+00 9.19E+00 3.84E+00 1.01E+01 1.22E+01 NA NA NA 3.91E+03 MW-31-85 MW-31-85 Q3-2011 033 84.8

-9.2 8/5/2011 11:27 4.82E+03 7.74E+02 4.22E+02 1.39E-01 1.40E+00 1.63E+00

-8.79E-01 8.25E+00 8.80E+00

-4.79E+00 9.57E+00 8.27E+00 NA NA NA 3.91E+03 MW-31-85 MW-32-59 Q4-2010 022 58.8 18.3 11/3/2010 12:08 1.58E+04 6.66E+02 1.16E+02 2.02E-01 6.15E-01 7.14E-01 6.67E+00 7.98E+00 1.03E+01 1.19E+00 9.11E+00 1.06E+01 NA NA NA 1.56E+04 ND ND ND NA MW-32-59 MW-32-59 Q1-2011 023 58.8 18.3 3/1/2011 11:28 4.39E+03 6.42E+02 3.59E+02 1.25E+00 1.49E+00 1.55E+00 6.56E-01 5.82E+00 6.63E+00

-4.41E-01 7.00E+00 7.58E+00 NA NA NA 1.56E+04 MW-32-59 MW-32-59 Q1-2011 Mid 024 58.8 18.3 3/31/2011 12:46 3.37E+04 1.96E+03 5.07E+02

-2.13E-01 1.15E+00 1.51E+00 8.24E-01 8.92E+00 9.96E+00 1.99E-02 1.02E+01 1.11E+01 NA NA NA 1.56E+04 MW-32-59 MW-32-59 Q2-2011 025 58.8 18.3 4/27/2011 12:26 3.31E+03 6.36E+02 4.08E+02 4.03E-01 1.50E+00 1.74E+00 4.77E+00 8.64E+00 1.04E+01

-3.37E+00 9.58E+00 9.50E+00 NA NA NA 1.56E+04 MW-32-59 MW-32-59 Q3-2011 027 58.8 18.3 8/5/2011 12:30 2.06E+04 1.47E+03 4.19E+02 1.64E+00 1.66E+00 1.71E+00

-3.73E+00 8.34E+00 8.04E+00

-1.05E+00 8.79E+00 9.24E+00 NA NA NA 1.56E+04 MW-32-59 MW-32-85 Q4-2010 025 85.3 85.3 11/3/2010 12:45 1.49E+04 6.48E+02 1.16E+02 3.80E-01 4.90E-01 5.36E-01 5.89E+00 9.60E+00 1.18E+01

-5.55E+00 8.71E+00 7.61E+00 NA NA NA 1.29E+04 ND ND ND NA MW-32-85 MW-32-85 Q1-2011 026 85.3 85.3 3/1/2011 12:05 1.34E+04 1.41E+03 2.62E+02 3.81E-01 1.41E+00 1.63E+00 7.79E-01 8.26E+00 9.36E+00 4.73E+00 9.72E+00 1.24E+01 NA NA NA 1.29E+04 MW-32-85 MW-32-85 Q1-2011 Mid 027 85.3 85.3 3/31/2011 13:18 1.32E+04 1.27E+03 5.07E+02

-1.62E-01 1.20E+00 1.56E+00

-6.56E-01 7.26E+00 7.61E+00 3.80E+00 8.28E+00 1.02E+01 NA NA NA 1.29E+04 MW-32-85 MW-32-85 Q2-2011 028 85.3 85.3 4/27/2011 13:04 1.14E+04 1.19E+03 5.10E+02 1.58E+00 1.69E+00 1.75E+00

-1.23E+00 6.80E+00 7.31E+00 5.30E-01 1.02E+01 1.15E+01 NA NA NA 1.29E+04 MW-32-85 MW-32-85 Q3-2011 030 85.3 85.3 8/5/2011 13:36 1.14E+04 1.12E+03 4.20E+02 1.14E-01 1.64E+00 1.92E+00 5.40E+00 6.87E+00 8.79E+00

-1.21E+00 6.69E+00 6.57E+00 NA NA NA 1.29E+04 MW-32-85 MW-32-149 Q4-2010 022 149.3

-72.2 11/3/2010 16:09 1.55E+03 2.24E+02 1.12E+02 4.08E-01 5.02E-01 5.49E-01

-1.00E+01 1.08E+01 1.15E+01 3.36E+00 7.71E+00 9.94E+00 NA NA NA 1.07E+03 ND ND ND NA MW-32-149 MW-32-149 Q1-2011 023 149.3

-72.2 3/1/2011 13:37 1.06E+03 4.48E+02 2.68E+02

-7.01E-01 1.66E+00 2.15E+00 9.25E-01 5.42E+00 6.30E+00 2.06E+00 6.60E+00 7.93E+00 NA NA NA 1.07E+03 MW-32-149 MW-32-149 Q1-2011 Mid 024 149.3

-72.2 3/31/2011 11:33 8.99E+02 5.34E+02 5.09E+02

-2.01E-01 1.10E+00 1.49E+00 2.52E+00 9.30E+00 1.09E+01 2.31E+00 9.92E+00 1.18E+01 NA NA NA 1.07E+03 MW-32-149 MW-32-149 Q2-2011 025 149.3

-72.2 4/27/2011 11:12 8.69E+02 4.44E+02 4.11E+02 3.00E-01 1.43E+00 1.67E+00 2.12E+00 7.44E+00 8.59E+00 9.88E-01 7.76E+00 8.83E+00 NA NA NA 1.07E+03 MW-32-149 MW-32-149 Q3-2011 027 149.3

-72.2 8/5/2011 11:10 9.86E+02 4.71E+02 4.21E+02 4.80E-01 1.81E+00 2.06E+00

-9.94E-01 9.60E+00 9.39E+00 2.75E+00 7.41E+00 9.28E+00 NA NA NA 1.07E+03 MW-32-149 MW-32-173 Q4-2010 020 172.8

-95.7 11/3/2010 15:53 1.40E+03 2.16E+02 1.14E+02 1.65E-02 4.38E-01 5.24E-01 3.87E+00 1.76E+01 9.62E+00

-2.94E+00 9.88E+00 1.01E+01 NA NA NA 8.59E+02 ND ND ND NA MW-32-173 MW-32-173 Q1-2011 021 172.8

-95.7 3/1/2011 13:13 9.02E+02 4.12E+02 2.61E+02

-4.04E-01 1.12E+00 1.45E+00 5.99E+00 6.06E+00 7.73E+00

-2.04E+00 7.36E+00 7.55E+00 NA NA NA 8.59E+02 MW-32-173 MW-32-173 Q1-2011 Mid 022 172.8

-95.7 3/31/2011 11:35 8.41E+02 5.22E+02 5.04E+02 2.46E-01 1.27E+00 1.54E+00 6.51E+00 1.58E+01 8.26E+00 2.19E+00 8.22E+00 9.98E+00 NA NA NA 8.59E+02 MW-32-173 MW-32-173 Q2-2011 023 172.8

-95.7 4/27/2011 11:27 5.82E+02 4.98E+02 5.08E+02 6.37E-01 1.54E+00 1.74E+00 0.00E+00 2.00E+01 9.23E+00 2.47E-01 9.58E+00 1.07E+01 NA NA NA 8.59E+02 MW-32-173 MW-32-173 Q3-2011 025 172.8

-95.7 8/5/2011 11:11 5.69E+02 4.17E+02 4.12E+02 6.34E-01 1.48E+00 1.66E+00

-9.50E-01 6.36E+00 6.56E+00

-1.55E+00 1.10E+01 1.14E+01 NA NA NA 8.59E+02 MW-32-173 MW-32-190 Q4-2010 024 190.3

-113.7 11/3/2010 16:07 1.53E+03 2.28E+02 1.17E+02

-9.74E-02 4.35E-01 5.82E-01 2.12E+00 9.02E+00 1.07E+01

-2.40E+00 9.21E+00 9.36E+00 NA NA NA 1.45E+03 ND ND ND NA MW-32-190 MW-32-190 Q1-2011 025 190.3

-113.7 3/1/2011 13:24 1.64E+03 5.32E+02 2.64E+02 7.65E-01 1.20E+00 1.29E+00 2.74E+00 5.52E+00 6.57E+00 4.88E+00 7.64E+00 8.75E+00 NA NA NA 1.45E+03 MW-32-190 MW-32-190 Q1-2011 Mid 026 190.3

-113.7 3/31/2011 11:47 1.41E+03 5.76E+02 5.02E+02

-7.79E-01 1.15E+00 1.67E+00 8.78E-01 7.96E+00 9.01E+00 5.11E+00 1.04E+01 1.30E+01 NA NA NA 1.45E+03 MW-32-190 MW-32-190 Q2-2011 027 190.3

-113.7 4/27/2011 11:17 1.21E+03 5.64E+02 5.10E+02 7.54E-01 1.13E+00 1.20E+00 8.61E-01 8.68E+00 9.74E+00

-6.60E+00 8.98E+00 6.37E+00 NA NA NA 1.45E+03 MW-32-190 MW-32-190 Q3-2011 029 190.3

-113.7 8/5/2011 11:15 1.44E+03 5.16E+02 4.20E+02 7.59E-01 1.64E+00 1.82E+00 2.02E+00 7.23E+00 8.43E+00 1.28E+00 9.24E+00 1.06E+01 NA NA NA 1.45E+03 MW-32-190 MW-36-24 Q4-2010 020 16.1

-4.3 11/4/2010 16:15 2.62E+03 2.82E+02 1.13E+02 3.79E-01 5.81E-01 6.42E-01 3.42E+00 9.88E+00 1.17E+01

-1.80E+00 1.16E+01 1.26E+01 NA NA NA 2.27E+03 ND ND ND NA MW-36-24 MW-36-24 Q1-2011 021 16.1

-4.3 2/28/2011 12:37 2.56E+02 3.54E+02 3.81E+02

-8.87E-02 1.67E+00 2.08E+00 4.53E-01 5.26E+00 5.75E+00

-3.09E-01 4.74E+00 5.03E+00 NA NA NA 2.27E+03 MW-36-24 MW-36-24 Q2-2011 022 16.1

-4.3 4/28/2011 14:34 3.07E+03 7.26E+02 5.19E+02 1.38E+00 1.53E+00 1.59E+00

-6.43E-01 7.68E+00 8.47E+00 2.82E+00 7.48E+00 9.35E+00 NA NA NA 2.27E+03 MW-36-24 MW-36-24 Q3-2011 023 16.1

-4.3 8/16/2011 13:34 1.12E+03 5.01E+02 4.51E+02 2.34E-01 9.96E-01 1.18E+00

-2.80E+00 7.71E+00 7.54E+00 7.10E-01 7.89E+00 8.75E+00 NA NA NA 2.27E+03 MW-36-24 MW-36-41 Q4-2010 014 37

-25.2 11/4/2010 16:55 1.22E+04 5.75E+02 1.10E+02 3.54E+00 9.13E-01 6.12E-01 7.62E-01 8.76E+00 1.01E+01 3.09E+00 8.58E+00 1.06E+01 NA NA NA 8.75E+03 3.18E+00 ND ND NA MW-36-41 MW-36-41 Q1-2011 015 37

-25.2 2/28/2011 13:53 8.74E+03 6.88E+02 2.97E+02 4.11E+00 1.87E+00 1.57E+00 1.31E+00 5.26E+00 6.09E+00 1.58E+00 5.68E+00 6.65E+00 NA NA NA 8.75E+03 3.18E+00 MW-36-41 MW-36-41 Q2-2011 016 37

-25.2 4/28/2011 15:39 8.17E+03 1.04E+03 5.14E+02 3.31E+00 1.75E+00 1.36E+00 2.18E+00 9.26E+00 1.07E+01

-2.96E-01 1.04E+01 1.12E+01 NA NA NA 8.75E+03 3.18E+00 MW-36-41 MW-36-41 Q3-2011 017 37

-25.2 8/16/2011 14:18 5.90E+03 8.37E+02 4.55E+02 1.74E+00 1.26E+00 1.13E+00 1.75E+00 8.91E+00 9.88E+00 4.43E+00 9.15E+00 1.15E+01 NA NA NA 8.75E+03 3.18E+00 MW-36-41 MW-36-52 Q4-2010 019 49.7

-37.9 11/4/2010 15:55 7.08E+03 4.40E+02 1.10E+02 4.73E+00 1.11E+00 6.76E-01 1.15E-01 5.89E+00 6.52E+00

-2.28E+00 7.92E+00 7.79E+00 NA NA NA 5.19E+03 3.69E+00 ND ND NA MW-36-52 MW-36-52 Q1-2011 020 49.7

-37.9 2/28/2011 12:43 3.14E+03 4.92E+02 3.37E+02 1.33E+00 2.00E+00 2.14E+00

-6.00E+00 5.58E+00 4.80E+00

-2.66E+00 5.94E+00 5.65E+00 NA NA NA 5.19E+03 3.69E+00 MW-36-52 MW-36-52 Q2-2011 021 49.7

-37.9 4/28/2011 14:38 5.84E+03 9.06E+02 5.15E+02 3.41E+00 1.56E+00 1.11E+00 4.29E+00 8.42E+00 1.03E+01

-2.61E+00 8.50E+00 8.36E+00 NA NA NA 5.19E+03 3.69E+00 MW-36-52 MW-36-52 Q3-2011 022 49.7

-37.9 8/16/2011 14:52 4.69E+03 7.59E+02 4.48E+02 2.93E+00 1.57E+00 1.36E+00 3.59E+00 8.22E+00 9.80E+00

-1.83E+00 9.33E+00 9.74E+00 NA NA NA 5.19E+03 3.69E+00 MW-36-52 MW-37-22 Q4-2010 020 17

-2 11/4/2010 14:28 4.46E+03 3.57E+02 1.12E+02 1.38E+01 1.33E+00 5.33E-01

-2.26E+00 7.33E+00 7.68E+00

-1.24E+00 9.31E+00 1.00E+01 NA NA NA 5.65E+03 1.01E+01 ND ND NA MW-37-22 MW-37-22 Q1-2011 021 17

-2 1/27/2011 15:19 6.74E+03 6.18E+02 2.98E+02 1.04E+01 2.52E+00 1.68E+00

-2.18E+00 4.74E+00 4.94E+00 2.59E+00 5.38E+00 6.55E+00 NA NA NA 5.65E+03 1.01E+01 MW-37-22 MW-37-22 Q2-2011 022 17

-2 4/28/2011 12:05 6.87E+03 9.66E+02 5.14E+02 8.72E+00 2.90E+00 2.05E+00 7.12E-01 6.96E+00 7.67E+00 5.14E-01 7.86E+00 8.62E+00 NA NA NA 5.65E+03 1.01E+01 MW-37-22 MW-37-22 Q3-2011 023 17

-2 8/16/2011 10:35 4.52E+03 7.56E+02 4.53E+02 7.59E+00 2.07E+00 1.32E+00 3.10E+00 7.26E+00 8.77E+00

-9.99E-01 7.35E+00 7.48E+00 NA NA NA 5.65E+03 1.01E+01 MW-37-22 MW-37-32 Q4-2010 020 29

-14 11/4/2010 13:14 5.99E+03 4.22E+02 1.17E+02

-2.91E-01 6.15E-01 7.91E-01

-4.11E+00 7.41E+00 7.07E+00 1.54E+00 7.68E+00 9.04E+00 NA NA NA 4.98E+03 1.93E+01 ND ND NA MW-37-32 MW-37-32 Q1-2011 021 29

-14 1/27/2011 15:09 4.57E+03 5.28E+02 2.98E+02 1.49E+01 3.02E+00 1.74E+00 4.20E-01 6.12E+00 6.85E+00 1.72E+00 6.60E+00 7.76E+00 NA NA NA 4.98E+03 1.93E+01 MW-37-32 MW-37-32 Q2-2011 022 29

-14 4/28/2011 12:21 4.11E+03 7.98E+02 5.15E+02 2.62E+01 3.76E+00 1.68E+00 3.56E+00 1.20E+01 1.42E+01

-1.92E+00 1.09E+01 1.09E+01 NA NA NA 4.98E+03 1.93E+01 MW-37-32 MW-37-32 Q3-2011 023 29

-14 8/16/2011 11:00 5.23E+03 7.95E+02 4.52E+02 1.68E+01 2.87E+00 1.13E+00

-2.53E+00 8.34E+00 7.53E+00

-6.09E+00 9.06E+00 8.10E+00 NA NA NA 4.98E+03 1.93E+01 MW-37-32 MW-37-40 Q4-2010 020 39.2

-24.2 11/4/2010 12:06 6.41E+03 4.29E+02 1.15E+02 1.28E+01 1.92E+00 6.32E-01 2.77E+00 8.58E+00 1.03E+01

-2.01E+00 8.29E+00 8.39E+00 NA NA NA 5.33E+03 1.87E+01 ND ND NA MW-37-40 MW-37-40 Q1-2011 021 39.2

-24.2 1/27/2011 13:35 5.97E+03 7.42E+02 3.82E+02 1.93E+01 3.34E+00 1.85E+00 1.95E+00 5.84E+00 6.78E+00 2.03E+00 6.84E+00 7.92E+00 NA NA NA 5.33E+03 1.87E+01 MW-37-40 MW-37-40 Q2-2011 022 39.2

-24.2 4/28/2011 11:31 3.92E+03 8.02E+02 5.33E+02 2.30E+01 3.66E+00 1.68E+00 4.10E+00 9.02E+00 1.09E+01 6.47E-01 8.94E+00 1.02E+01 NA NA NA 5.33E+03 1.87E+01 MW-37-40 MW-37-40 Q3-2011 023 39.2

-24.2 8/16/2011 11:24 5.03E+03 7.86E+02 4.53E+02 1.95E+01 3.18E+00 1.17E+00

-2.08E+00 8.25E+00 8.54E+00 1.79E+00 7.35E+00 8.59E+00 NA NA NA 5.33E+03 1.87E+01 MW-37-40 MW-37-57 Q4-2010 020 53.2

-38.2 11/4/2010 13:49 6.72E+03 4.41E+02 1.15E+02 1.97E+01 2.15E+00 5.70E-01 6.72E+00 1.52E+01 9.04E+00

-3.60E+00 7.95E+00 7.35E+00 NA NA NA 5.82E+03 1.93E+01 ND ND NA MW-37-57 MW-37-57 Q1-2011 021 53.2

-38.2 1/27/2011 15:26 5.63E+03 5.76E+02 2.99E+02 2.02E+01 3.60E+00 1.96E+00

-3.70E-01 6.34E+00 6.92E+00

-1.36E+00 5.64E+00 5.68E+00 NA NA NA 5.82E+03 1.93E+01 MW-37-57 MW-37-57 Q2-2011 022 53.2

-38.2 4/28/2011 12:17 5.81E+03 8.98E+02 5.07E+02 1.58E+01 3.54E+00 2.00E+00 5.18E+00 1.72E+01 8.67E+00

-1.42E+00 8.36E+00 8.80E+00 NA NA NA 5.82E+03 1.93E+01 MW-37-57 MW-37-57 Q3-2011 023 53.2

-38.2 8/16/2011 10:55 5.11E+03 7.98E+02 4.59E+02 2.15E+01 3.27E+00 1.30E+00 1.82E+00 7.92E+00 9.16E+00

-1.34E+00 6.39E+00 6.57E+00 NA NA NA 5.82E+03 1.93E+01 MW-37-57 MW-39-67 Q4-2010 010 67 13 11/15/2010 16:28 3.74E+02 1.86E+02 3.88E+02 1.96E+00 9.36E-01 1.94E+00

-1.74E+00 3.99E+00 8.40E+00

-3.17E+00 4.38E+00 8.38E+00 NA NA NA 9.35E+03 1.85E+00 ND ND NA MW-39-67 MW-39-67 Q2-2011 011 67 13 4/26/2011 14:52 1.09E+04 9.64E+02 4.18E+02 1.74E+00 1.49E+00 1.50E+00

-8.12E-01 8.22E+00 8.78E+00

-4.05E+00 9.42E+00 9.00E+00 NA NA NA 9.35E+03 1.85E+00 MW-39-67 MW-39-67 Q2-2011 Mid 012 67 13 7/15/2011 13:42 2.24E+03 6.12E+02 4.40E+02 2.55E-01 1.16E+00 1.34E+00

-1.15E-01 8.28E+00 9.19E+00

-2.42E-02 9.72E+00 1.12E+01 NA NA NA 9.35E+03 1.85E+00 MW-39-67 MW-39-67 Q3-2011 Mid 013 67 13 8/29/2011 13:47 1.49E+04 1.24E+03 4.51E+02 1.08E+00 1.18E+00 1.20E+00 2.23E+00 7.77E+00 8.94E+00 4.82E+00 8.25E+00 1.05E+01 NA NA NA 9.35E+03 1.85E+00 MW-39-67 MW-39-84 Q4-2010 010 83.5

-3.5 11/15/2010 16:38 2.51E+02 2.10E+02 4.59E+02 1.80E+00 8.83E-01 1.86E+00 3.58E+00 4.41E+00 1.05E+01 7.47E+00 4.82E+00 1.24E+01 NA NA NA 4.40E+02 ND ND ND ND MW-39-84 MW-39-84 Q2-2011 011 83.5

-3.5 4/26/2011 14:25 4.40E+02 4.02E+02 4.13E+02

-2.03E-01 1.15E+00 1.50E+00

-9.39E-01 7.42E+00 7.84E+00

-4.02E-01 6.92E+00 7.41E+00 NA NA NA 4.40E+02 MW-39-84 MW-39-84 Q2-2011 Mid 012 83.5

-3.5 7/15/2011 14:33 3.55E+02 4.17E+02 4.40E+02 6.54E-01 1.15E+00 1.27E+00

-1.78E+00 1.43E+01 1.71E+01

-4.89E+00 9.45E+00 8.20E+00 NA NA NA 4.40E+02 MW-39-84 MW-39-84 Q3-2011 Mid 013 83.5

-3.5 8/29/2011 13:56 2.38E+02 4.14E+02 4.54E+02 8.64E-01 1.00E+00 1.00E+00 5.19E+00 1.54E+01 9.85E+00

-1.20E+00 9.99E+00 1.04E+01 NA NA NA 4.40E+02 MW-39-84 MW-39-102 Q4-2010 010 101.5

-21.5 11/15/2010 16:12 3.61E+02 1.83E+02 3.84E+02 1.40E+00 9.00E-01 1.93E+00 2.98E+00 3.38E+00 8.21E+00

-4.12E+00 3.52E+00 6.23E+00 NA NA NA 1.52E+04 ND 4.48E+01 ND ND MW-39-102 MW-39-102 Q2-2011 011 101.5

-21.5 4/26/2011 14:33 1.43E+04 1.09E+03 4.19E+02 1.08E+00 1.85E+00 2.03E+00 4.48E+01 2.08E+01 9.86E+00 6.03E+00 7.96E+00 1.07E+01 NA NA NA 1.52E+04 4.48E+01 MW-39-102 MW-39-102 Q2-2011 Mid 012 101.5

-21.5 7/15/2011 14:02 1.24E+04 1.20E+03 4.36E+02 5.88E-01 1.09E+00 1.20E+00 3.70E+00 8.76E+00 1.02E+01

-6.84E-01 9.42E+00 9.35E+00 NA NA NA 1.52E+04 4.48E+01 MW-39-102 MW-39-102 Q3-2011 Mid 013 101.5

-21.5 8/29/2011 14:11 1.90E+04 1.37E+03 4.41E+02

-7.38E-01 1.20E+00 1.60E+00

-3.14E+00 7.92E+00 7.72E+00 4.66E+00 7.83E+00 1.04E+01 NA NA NA 1.52E+04 4.48E+01 MW-39-102 MW-39-124 Q4-2010 010 124

-44 11/15/2010 12:46 3.73E+02 1.83E+02 3.86E+02 1.17E+00 8.85E-01 1.93E+00

-6.40E+00 6.71E+00 1.61E+01

-1.31E-01 4.98E+00 1.10E+01 NA NA NA ND ND 9.13E+00 ND ND MW-39-124 MW-39-124 Q2-2011 011 124

-44 4/26/2011 13:01 1.51E+02 3.70E+02 4.15E+02 5.20E-01 1.37E+00 1.55E+00 9.13E+00 8.56E+00 8.57E+00 3.07E+00 7.52E+00 9.27E+00 NA NA NA 9.13E+00 MW-39-124 MW-39-124 Q2-2011 Mid 012 124

-44 7/15/2011 11:44 2.30E+01 3.72E+02 4.39E+02 8.78E-01 1.19E+00 1.27E+00

-4.10E+00 1.13E+01 1.15E+01

-1.82E+00 9.51E+00 9.57E+00 NA NA NA 9.13E+00 MW-39-124 MW-39-124 Q3-2011 Mid 013 124

-44 8/29/2011 10:54

-1.02E+01 3.75E+02 4.45E+02 3.16E-01 1.12E+00 1.30E+00

-7.05E+00 1.06E+01 1.01E+01 7.76E+00 1.13E+01 1.46E+01 NA NA NA 9.13E+00 MW-39-124 MW-39-183 Q4-2010 010 182.5

-102.5 11/15/2010 12:53

-8.02E+01 1.61E+02 3.88E+02 4.19E-01 7.56E-01 1.77E+00 1.45E+00 4.83E+00 1.10E+01 3.58E+00 4.93E+00 1.19E+01 NA NA NA ND ND ND ND NA MW-39-183 MW-39-183 Q2-2011 011 182.5

-102.5 4/26/2011 11:35 1.15E+02 3.54E+02 4.02E+02 1.12E+00 1.56E+00 1.67E+00 6.46E+00 8.88E+00 1.09E+01

-1.52E+00 8.68E+00 8.94E+00 NA NA NA MW-39-183 MW-39-183 Q2-2011 Mid 012 182.5

-102.5 7/15/2011 11:49 7.02E+01 3.75E+02 4.35E+02 3.45E-01 1.03E+00 1.19E+00 2.51E+00 1.08E+01 1.22E+01

-2.37E+00 1.30E+01 1.37E+01 NA NA NA MW-39-183 MW-39-183 Q3-2011 Mid 013 182.5

-102.5 8/29/2011 10:45 1.14E+02 3.81E+02 4.33E+02 1.10E+00 1.13E+00 1.10E+00

-3.70E+00 1.05E+01 1.05E+01 5.90E+00 9.54E+00 1.22E+01 NA NA NA MW-39-183 MW-39-195 Q4-2010 010 195

-115 11/15/2010 13:25 2.16E+02 1.86E+02 4.09E+02 1.52E-01 7.35E-01 1.73E+00

-3.21E+00 4.09E+00 6.54E+00 8.70E+00 4.38E+00 1.20E+01 NA NA NA 9.48E+03 1.88E+00 ND ND NA MW-39-195 MW-39-195 Q2-2011 011 195

-115 4/26/2011 12:38 7.04E+03 8.04E+02 4.20E+02 1.88E+00 1.75E+00 1.79E+00

-2.03E+00 1.11E+01 1.28E+01 4.62E+00 8.70E+00 1.13E+01 NA NA NA 9.48E+03 1.88E+00 MW-39-195 MW-39-195 Q2-2011 Mid 012 195

-115 7/15/2011 11:13 4.19E+03 7.56E+02 4.35E+02 1.10E+00 1.78E+00 1.93E+00 2.79E+00 8.46E+00 9.76E+00 6.38E-01 1.01E+01 1.08E+01 NA NA NA 9.48E+03 1.88E+00 MW-39-195 MW-39-195 Q3-2011 Mid 013 195

-115 8/29/2011 10:51 1.72E+04 1.31E+03 4.43E+02 4.98E-02 7.50E-01 9.59E-01 7.98E-01 7.62E+00 8.56E+00 2.43E+00 8.19E+00 9.86E+00 NA NA NA 9.48E+03 1.88E+00 MW-39-195 ANALYSIS RESULTS5 YEARLY ROLLING AVERAGES4,6 Well ID1 TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

SAMPLE COLLECTION Well ID1 SAMPLING QUARTER2,8 SAMPLE ID SAMPLE ZONE CENTER Depth Ft Below Top of Casing3 SAMPLE ZONE CENTER Elevation Ft msl3

TABLE 3 THIRD QUARTER 2011 GROUNDWATER ANALYTICAL RESULTS AND AVERAGES INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q32011 FINAL Table 3 - Third Quarter 2011 Groundwater Analytical Results and Averages.xlsx; Q32011 Table 3 Page 2 of 6 See Page 6 for Notes TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Date Time Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Average Average Average Average Average ANALYSIS RESULTS5 YEARLY ROLLING AVERAGES4,6 Well ID1 TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

SAMPLE COLLECTION Well ID1 SAMPLING QUARTER2,8 SAMPLE ID SAMPLE ZONE CENTER Depth Ft Below Top of Casing3 SAMPLE ZONE CENTER Elevation Ft msl3 MW-40-27 Q4-2010 013 26.7 46.5 11/29/2010 15:23 2.06E+02 1.49E+02 1.44E+02 1.10E-01 7.98E-01 9.63E-01 3.16E-01 3.38E+00 3.76E+00 1.01E+00 3.63E+00 4.18E+00 NA NA NA 2.06E+02 ND ND ND NA MW-40-27 MW-40-27 Q1-2011 014 26.7 46.5 3/8/2011 12:55 1.85E+02 2.56E+02 2.65E+02 1.58E-01 1.37E+00 1.61E+00 3.72E-01 6.78E+00 7.39E+00 2.83E+00 8.56E+00 9.99E+00 NA NA NA 2.06E+02 MW-40-27 MW-40-27 Q2-2011 015 26.7 46.5 4/29/2011 13:29 1.77E+02 3.66E+02 4.07E+02 1.18E+00 1.74E+00 1.87E+00 1.91E+00 8.40E+00 9.77E+00

-9.20E-01 9.86E+00 1.15E+01 NA NA NA 2.06E+02 MW-40-27 MW-40-27 Q2-2011 Mid 016 26.7 46.5 7/27/2011 15:12 3.69E+01 3.00E+02 3.43E+02

-4.37E-01 1.40E+00 1.93E+00

-2.18E+00 7.35E+00 7.64E+00 1.36E+00 9.03E+00 1.03E+01 NA NA NA 2.06E+02 MW-40-27 MW-40-46**

Q4-2010 014 46.2 27 11/29/2010 16:36 1.63E+02 1.47E+02 1.48E+02 6.60E-02 7.89E-01 9.38E-01 5.82E-01 3.82E+00 4.28E+00 2.06E+00 3.99E+00 4.74E+00 NA NA NA 1.63E+02 ND**

ND ND NA MW-40-46**

MW-40-46**

Q1-2011 015 46.2 27 3/8/2011 12:58 2.48E+02 2.74E+02 2.63E+02 1.03E-01 8.58E-01 1.07E+00 2.82E+00 8.00E+00 9.18E+00 7.99E+00 8.74E+00 1.19E+01 NA NA NA 1.63E+02 2.83E+00 MW-40-46**

MW-40-46**

Q2-2011 016 46.2 27 4/29/2011 13:31 7.82E+01 3.54E+02 4.05E+02

-1.35E-01**

1.88E+00 1.77E+00

-9.96E-01 8.46E+00 9.00E+00

-3.98E+00 9.84E+00 9.04E+00 NA NA NA 1.63E+02 2.83E+00 MW-40-46**

MW-40-46**

Q2-2011 Mid 017 46.2 27 7/27/2011 15:55 1.35E+02 3.09E+02 3.44E+02

-9.06E-01 1.26E+00 1.86E+00 2.28E+00 8.85E+00 1.01E+01 5.01E-01 9.30E+00 1.03E+01 NA NA NA 1.63E+02 2.83E+00 MW-40-46**

MW-40-81 Q4-2010 014 80.7

-7.5 11/29/2010 12:03 2.48E+02 1.58E+02 1.47E+02 1.13E-03 6.45E-01 7.85E-01

-9.67E-01 4.38E+00 4.79E+00

-4.37E-01 4.83E+00 5.28E+00 NA NA NA 2.48E+02 ND ND ND NA MW-40-81 MW-40-81 Q1-2011 015 80.7

-7.5 3/8/2011 10:17 2.33E+02 2.68E+02 2.63E+02 8.50E-01 1.51E+00 1.67E+00 1.26E+00 1.06E+01 7.71E+00

-1.45E+00 6.08E+00 6.16E+00 NA NA NA 2.48E+02 MW-40-81 MW-40-81 Q2-2011 016 80.7

-7.5 4/29/2011 11:08 3.39E+02 4.12E+02 4.36E+02 1.07E+00 1.58E+00 1.70E+00 3.05E+00 6.90E+00 8.51E+00

-2.66E-01 8.04E+00 8.83E+00 NA NA NA 2.48E+02 MW-40-81 MW-40-81 Q2-2011 Mid 017 80.7

-7.5 7/27/2011 13:24

-1.18E+02 2.89E+02 3.48E+02 8.36E-01 1.70E+00 1.90E+00

-3.22E-01 6.48E+00 6.87E+00

-1.05E+00 8.67E+00 8.91E+00 NA NA NA 2.48E+02 MW-40-81 MW-40-100*

Q4-2010 016 100.2

-27 11/29/2010 12:12 1.34E+02 1.40E+02 1.46E+02

-2.12E-01 6.70E-01 8.39E-01

-1.46E-01 4.05E+00 4.53E+00 3.11E-01 4.26E+00 4.81E+00 NA NA NA ND ND ND*

ND NA MW-40-100*

MW-40-100*

Q1-2011 017 100.2

-27 3/8/2011 10:27 5.17E+01 2.14E+02 2.64E+02 2.52E-02 1.30E+00 1.58E+00 2.46E+01*

1.35E+01 7.66E+00

-1.40E+00 7.88E+00 8.30E+00 NA NA NA 2.46E+01 MW-40-100*

MW-40-100*

Q2-2011 018 100.2

-27 4/29/2011 11:27 2.70E+02 4.06E+02 4.38E+02 2.46E-01 1.42E+00 1.67E+00 5.53E+00 7.14E+00 9.23E+00 2.99E+00 7.96E+00 9.80E+00 NA NA NA 2.46E+01 MW-40-100*

MW-40-100*

Q2-2011 Mid 019 100.2

-27 7/27/2011 13:29 1.07E+02 3.12E+02 3.50E+02

-9.50E-01 1.41E+00 1.98E+00 2.29E+00 9.03E+00 1.04E+01 7.10E-01 1.08E+01 1.20E+01 NA NA NA 2.46E+01 MW-40-100*

MW-40-127*

Q4-2010 016 127.2

-54 11/29/2010 12:26 1.22E+02 1.38E+02 1.45E+02 7.34E-01 9.02E-01 9.73E-01

-1.53E-01 4.82E+00 5.43E+00 1.12E+00 4.38E+00 5.06E+00 NA NA NA ND ND ND*

ND NA MW-40-127*

MW-40-127*

Q1-2011 017 127.2

-54 3/8/2011 10:41 1.33E+02 2.40E+02 2.64E+02 1.03E+00 1.40E+00 1.51E+00 5.07E+01*

1.64E+01 7.63E+00 3.45E-01 7.18E+00 7.96E+00 NA NA NA 5.07E+01 MW-40-127*

MW-40-127*

Q2-2011 018 127.2

-54 4/29/2011 11:26

-2.27E+01 3.60E+02 4.32E+02 5.72E-01 1.78E+00 2.05E+00

-2.13E-01 8.26E+00 8.83E+00

-1.62E+00 9.68E+00 9.87E+00 NA NA NA 5.07E+01 MW-40-127*

MW-40-127*

Q2-2011 Mid 019 127.2

-54 7/27/2011 13:56 1.56E+02 3.15E+02 3.50E+02 4.81E-01 1.64E+00 1.92E+00 1.48E+00 9.06E+00 1.03E+01

-8.00E+00 1.02E+01 7.94E+00 NA NA NA 5.07E+01 MW-40-127*

MW-40-162 Q4-2010 014 161.7

-88.5 11/29/2010 12:45 6.40E+01 1.27E+02 1.45E+02

-5.51E-03 6.55E-01 7.94E-01 3.60E-01 4.34E+00 4.91E+00 3.43E-01 4.47E+00 5.03E+00 NA NA NA ND ND ND ND NA MW-40-162 MW-40-162 Q1-2011 015 161.7

-88.5 3/8/2011 11:02 8.33E+01 2.24E+02 2.63E+02

-1.03E+00 1.07E+00 1.57E+00

-3.72E+00 6.12E+00 5.93E+00

-2.11E+00 6.42E+00 6.37E+00 NA NA NA MW-40-162 MW-40-162 Q2-2011 016 161.7

-88.5 4/29/2011 12:26 1.05E+02 3.78E+02 4.33E+02 8.71E-01 1.34E+00 1.46E+00 4.54E+00 1.23E+01 1.42E+01 4.43E-01 9.50E+00 1.08E+01 NA NA NA MW-40-162 MW-40-162 Q2-2011 Mid 017 161.7

-88.5 7/27/2011 14:40 5.54E+00 2.97E+02 3.44E+02

-8.61E-01 1.58E+00 1.98E+00

-2.44E+00 9.21E+00 8.54E+00

-6.93E-01 8.70E+00 9.41E+00 NA NA NA MW-40-162 MW-41-40 Q4-2010 018 34.4 20.5 10/25/2010 16:06 2.43E+03 2.78E+02 1.17E+02 4.08E+00 1.16E+00 6.72E-01 3.32E+00 5.63E+00 6.87E+00

-1.99E+00 6.74E+00 6.96E+00 NA NA NA 2.05E+03 5.10E+00 ND ND NA MW-41-40 MW-41-40 Q1-2011 019 34.4 20.5 2/14/2011 14:05 2.03E+03 4.02E+02 2.98E+02 1.15E+01 2.68E+00 1.83E+00 4.60E+00 7.30E+00 8.61E+00 4.22E+00 7.36E+00 9.28E+00 NA NA NA 2.05E+03 5.10E+00 MW-41-40 MW-41-40 Q2-2011 020 34.4 20.5 4/20/2011 13:51 4.51E+03 7.36E+02 4.55E+02 2.32E+00 1.57E+00 1.44E+00 2.20E+00 9.22E+00 1.06E+01 3.02E+00 1.06E+01 1.25E+01 NA NA NA 2.05E+03 5.10E+00 MW-41-40 MW-41-40 Q2-2011 Mid 021 34.4 20.5 7/15/2011 12:30 6.99E+02 4.59E+02 4.41E+02 2.48E+00 1.35E+00 1.19E+00

-1.93E+00 1.09E+01 1.14E+01

-1.11E+00 8.94E+00 9.13E+00 NA NA NA 2.05E+03 5.10E+00 MW-41-40 MW-41-40 Q3-2011 022 34.4 20.5 8/4/2011 14:39 5.94E+02 3.57E+02 3.53E+02 1.70E+00 1.87E+00 1.93E+00 4.91E-01 5.97E+00 6.61E+00

-6.02E-02 8.16E+00 8.80E+00 NA NA NA 2.05E+03 5.10E+00 MW-41-40 MW-41-63 Q4-2010 017 59.5

-4.6 10/25/2010 12:59 5.06E+02 1.50E+02 1.14E+02 4.25E+00 1.19E+00 7.17E-01 1.06E+00 6.08E+00 7.07E+00 2.87E+00 5.85E+00 7.23E+00 NA NA NA 7.74E+02 4.73E+00 ND ND NA MW-41-63 MW-41-63 Q1-2011 018 59.5

-4.6 2/14/2011 13:37 1.23E+03 4.44E+02 3.80E+02 6.92E+00 2.46E+00 1.96E+00 1.24E+00 5.30E+00 6.03E+00 2.69E+00 6.06E+00 7.29E+00 NA NA NA 7.74E+02 4.73E+00 MW-41-63 MW-41-63 Q2-2011 019 59.5

-4.6 4/20/2011 13:13 7.58E+02 4.90E+02 4.72E+02

-7.72E-01 1.51E+00 2.03E+00 3.53E+00 8.52E+00 1.01E+01 4.02E+00 8.74E+00 1.09E+01 NA NA NA 7.74E+02 4.73E+00 MW-41-63 MW-41-63 Q2-2011 Mid 020 59.5

-4.6 7/15/2011 12:51 7.14E+02 4.56E+02 4.35E+02 3.03E+00 1.50E+00 1.30E+00 2.36E+00 7.71E+00 8.88E+00 4.47E-01 6.81E+00 7.51E+00 NA NA NA 7.74E+02 4.73E+00 MW-41-63 MW-41-63 Q3-2011 021 59.5

-4.6 8/4/2011 14:20 6.60E+02 3.60E+02 3.51E+02 1.91E+00 1.95E+00 1.96E+00 1.64E+00 7.89E+00 8.72E+00

-1.43E+00 7.29E+00 7.72E+00 NA NA NA 7.74E+02 4.73E+00 MW-41-63 MW-42-49 Q4-2010 023 42.6 27.1 10/27/2010 12:23 1.28E+03 2.03E+02 1.64E+02 1.81E+01 2.31E+00 8.72E-01 2.39E+04 2.94E+03 2.93E+01

-1.67E+00 9.77E+00 1.03E+01 2.24E+02 2.66E+01 2.10E+01 1.31E+03 1.23E+01 2.35E+04 ND 2.49E+02 MW-42-49 MW-42-49 Q1-2011 024 42.6 27.1 3/4/2011 11:37 1.49E+03 5.14E+02 3.88E+02 2.32E+01 3.34E+00 1.11E+00 3.30E+04 4.42E+03 2.75E+01 1.42E+00 6.78E+00 7.87E+00 3.02E+02 3.04E+01 2.00E+01 1.31E+03 1.23E+01 2.35E+04 2.49E+02 MW-42-49 MW-42-49 Q2-2011 025 42.6 27.1 4/21/2011 14:04 1.71E+03 5.88E+02 4.80E+02 5.45E+00 2.18E+00 1.45E+00 2.15E+04 2.88E+03 2.08E+01 3.41E+00 9.16E+00 1.09E+01 1.90E+02 2.72E+01 1.73E+01 1.31E+03 1.23E+01 2.35E+04 2.49E+02 MW-42-49 MW-42-49 Q3-2011 027 42.6 27.1 8/1/2011 12:50 7.78E+02 3.90E+02 3.74E+02 2.60E+00 1.92E+00 1.82E+00 1.57E+04 1.92E+03 2.16E+01 3.58E+00 8.40E+00 1.01E+01 2.80E+02 3.48E+01 2.02E+01 1.31E+03 1.23E+01 2.35E+04 2.49E+02 MW-42-49 MW-42-78 Q4-2010 018 74

-4.3 10/27/2010 13:56 6.13E+02 1.74E+02 1.64E+02

-1.14E-01 4.79E-01 5.87E-01

-1.09E+00 8.69E+00 9.51E+00

-5.11E+00 8.41E+00 7.24E+00

-4.24E+00 1.80E+01 2.09E+01 5.59E+02 ND ND ND ND MW-42-78 MW-42-78 Q1-2011 019 74

-4.3 3/4/2011 10:58 5.98E+02 4.06E+02 3.84E+02 8.92E-01 1.47E+00 1.60E+00

-2.03E+00 6.72E+00 6.99E+00 8.03E-02 6.70E+00 7.41E+00 0.00E+00 1.73E+01 1.96E+01 5.59E+02 MW-42-78 MW-42-78 Q2-2011 020 74

-4.3 4/21/2011 13:45 6.26E+02 4.78E+02 4.77E+02 4.25E-01 1.13E+00 1.32E+00

-9.71E-01 9.16E+00 9.83E+00 3.58E+00 8.56E+00 1.11E+01 5.89E-01 1.49E+01 1.72E+01 5.59E+02 MW-42-78 MW-42-78 Q3-2011 022 74

-4.3 8/1/2011 12:50 3.97E+02 3.57E+02 3.72E+02

-1.16E-01 1.13E+00 1.49E+00 5.85E-01 7.98E+00 7.65E+00

-5.68E-01 9.45E+00 1.03E+01 1.02E+00 1.17E+01 1.31E+01 5.59E+02 MW-42-78 MW-43-28 Q4-2010 017 23.5 25.3 10/25/2010 11:29 1.95E+02 1.17E+02 1.13E+02

-1.98E-01 5.01E-01 6.94E-01 3.36E+00 5.00E+00 6.09E+00

-5.01E-01 5.43E+00 5.84E+00 NA NA NA 1.95E+02 ND ND ND NA MW-43-28 MW-43-28 Q1-2011 018 23.5 25.3 2/15/2011 13:08 2.54E+02 2.80E+02 2.99E+02

-1.06E+00 1.40E+00 2.00E+00 5.75E-02 1.26E+01 7.06E+00

-3.84E+00 6.84E+00 6.54E+00 NA NA NA 1.95E+02 MW-43-28 MW-43-28 Q2-2011 019 23.5 25.3 4/21/2011 11:15 2.34E+02 4.30E+02 4.72E+02 1.46E+00 1.96E+00 2.04E+00

-9.31E-01 8.74E+00 9.22E+00 4.50E+00 8.60E+00 1.09E+01 NA NA NA 1.95E+02 MW-43-28 MW-43-28 Q3-2011 020 23.5 25.3 8/4/2011 11:15 2.26E+02 3.24E+02 3.50E+02

-1.34E-01 1.42E+00 1.87E+00 4.00E+00 7.35E+00 9.02E+00

-3.51E+00 9.33E+00 9.21E+00 NA NA NA 1.95E+02 MW-43-28 MW-43-62 Q4-2010 017 51

-2.2 10/25/2010 11:06 9.76E+01 1.05E+02 1.12E+02 3.69E-01 7.10E-01 8.03E-01 5.94E-01 6.27E+00 6.81E+00

-6.69E-01 5.37E+00 5.81E+00 NA NA NA ND ND ND ND NA MW-43-62 MW-43-62 Q1-2011 018 51

-2.2 2/15/2011 13:15 1.82E+02 2.76E+02 3.00E+02 7.75E-01 1.74E+00 1.95E+00 6.59E-01 5.08E+00 5.56E+00

-2.37E-01 5.16E+00 5.52E+00 NA NA NA MW-43-62 MW-43-62 Q2-2011 019 51

-2.2 4/21/2011 11:00 1.05E+02 4.12E+02 4.72E+02

-4.65E-01 1.67E+00 2.18E+00

-1.90E+00 9.08E+00 9.35E+00

-2.34E+00 8.70E+00 8.43E+00 NA NA NA MW-43-62 MW-43-62 Q3-2011 021 51

-2.2 8/4/2011 11:35 1.66E+02 3.21E+02 3.55E+02

-2.14E-01 1.61E+00 1.93E+00

-1.62E+00 7.95E+00 8.00E+00

-2.98E+00 8.13E+00 8.75E+00 NA NA NA MW-43-62 MW-44-66 Q4-2010 018 62.4 31.1 10/26/2010 14:46 3.10E+02 1.29E+02 1.11E+02

-1.07E-01 4.30E-01 5.95E-01 4.23E-01 6.24E+00 7.11E+00

-3.70E+00 7.37E+00 7.27E+00 NA NA NA 7.10E+02 ND ND ND NA MW-44-66 MW-44-66 Q1-2011 019 62.4 31.1 2/18/2011 10:41 4.57E+02 3.90E+02 3.99E+02

-2.94E-01 1.59E+00 1.95E+00 1.74E+00 7.72E+00 8.56E+00

-1.40E+00 7.92E+00 8.46E+00 NA NA NA 7.10E+02 MW-44-66 MW-44-66 Q2-2011 020 62.4 31.1 4/26/2011 13:17 6.87E+02 4.20E+02 4.03E+02 7.05E-01 1.52E+00 1.70E+00

-1.14E-01 9.36E+00 1.03E+01 3.29E+00 1.07E+01 1.31E+01 NA NA NA 7.10E+02 MW-44-66 MW-44-66 Q2-2011 Mid 021 62.4 31.1 7/19/2011 15:39 1.62E+03 5.49E+02 4.32E+02

-7.04E-01 6.48E-01 1.06E+00 4.61E+00 9.66E+00 1.16E+01

-5.76E+00 1.11E+01 9.79E+00 NA NA NA 7.10E+02 MW-44-66 MW-44-66 Q3-2011 022 62.4 31.1 8/22/2011 12:08 4.76E+02 4.32E+02 4.45E+02 1.13E-01 9.03E-01 1.11E+00

-7.41E+00 8.73E+00 6.89E+00

-3.14E+00 9.09E+00 9.07E+00 NA NA NA 7.10E+02 MW-44-66 MW-44-102 Q4-2010 019 80 13.5 10/26/2010 13:32 4.47E+02 1.42E+02 1.12E+02 2.42E-01 5.47E-01 6.33E-01

-2.73E+00 5.49E+00 5.54E+00 6.85E-01 5.38E+00 6.11E+00 NA NA NA 5.95E+02 ND ND ND NA MW-44-102 MW-44-102 Q1-2011 020 80 13.5 2/18/2011 10:44 3.93E+02 2.90E+02 2.97E+02 2.63E-01 1.86E+00 2.15E+00 2.22E-01 4.96E+00 5.47E+00

-2.93E-01 6.02E+00 6.58E+00 NA NA NA 5.95E+02 MW-44-102 MW-44-102 Q2-2011 021 80 13.5 4/26/2011 12:18 6.70E+02 4.14E+02 3.99E+02 1.09E+00 1.41E+00 1.49E+00 3.59E-01 7.42E+00 8.15E+00

-2.06E+00 7.86E+00 7.82E+00 NA NA NA 5.95E+02 MW-44-102 MW-44-102 Q2-2011 Mid 022 80 13.5 7/19/2011 10:53 6.38E+02 4.50E+02 4.39E+02 2.55E-01 1.02E+00 1.19E+00 1.01E+00 6.63E+00 7.60E+00 1.28E+00 6.27E+00 7.47E+00 NA NA NA 5.95E+02 MW-44-102 MW-44-102 Q3-2011 023 80 13.5 8/22/2011 10:43 8.25E+02 4.77E+02 4.57E+02

-1.10E-01 9.69E-01 1.28E+00

-3.22E+00 6.69E+00 6.63E+00 8.99E+00 7.50E+00 1.08E+01 NA NA NA 5.95E+02 MW-44-102 MW-45-42 Q4-2010 022 37 16.6 10/22/2010 15:59 2.74E+03 2.90E+02 1.13E+02 9.55E-02 5.19E-01 6.32E-01 1.35E+00 6.04E+00 6.99E+00

-1.65E+00 5.70E+00 5.89E+00 NA NA NA 1.72E+04 ND ND ND NA MW-45-42 MW-45-42 Q1-2011 023 37 16.6 2/16/2011 16:58 8.12E+03 7.86E+02 3.63E+02 1.03E+00 1.39E+00 1.48E+00

-8.53E-01 5.64E+00 5.99E+00 1.42E+00 6.30E+00 7.17E+00 NA NA NA 1.72E+04 MW-45-42 MW-45-42 Q2-2011 024 37 16.6 4/20/2011 14:09 8.56E+03 1.03E+03 4.65E+02 1.45E+00 1.56E+00 1.61E+00 7.04E-01 6.50E+00 7.46E+00 7.13E+00 1.07E+01 1.29E+01 NA NA NA 1.72E+04 MW-45-42 MW-45-42 Q2-2011 Mid 025 37 16.6 7/25/2011 13:23 3.94E+04 2.07E+03 4.36E+02 1.14E+00 1.30E+00 1.37E+00 3.09E+00 7.41E+00 8.65E+00

-2.66E+00 1.01E+01 1.05E+01 NA NA NA 1.72E+04 MW-45-42 MW-45-42 Q3-2011 Mid 026 37 16.6 8/23/2011 13:58 2.72E+04 1.63E+03 4.50E+02 1.77E-01 9.15E-01 1.10E+00 8.73E-01 1.12E+01 1.05E+01

-7.52E+00 1.06E+01 8.89E+00 NA NA NA 1.72E+04 MW-45-42 MW-45-61 Q4-2010 022 58

-4.4 10/22/2010 11:54 1.51E+03 2.22E+02 1.12E+02 3.58E-01 5.53E-01 6.05E-01

-2.92E+00 5.78E+00 5.94E+00 1.19E-01 6.92E+00 7.73E+00 NA NA NA 3.38E+03 ND ND ND NA MW-45-61 MW-45-61 Q1-2011 023 58

-4.4 2/16/2011 16:15 1.84E+03 5.20E+02 3.98E+02

-2.25E-01 1.64E+00 1.96E+00 1.38E+00 4.80E+00 5.41E+00 9.89E-01 5.46E+00 6.15E+00 NA NA NA 3.38E+03 MW-45-61 MW-45-61 Q2-2011 024 58

-4.4 4/20/2011 10:07 2.03E+03 6.12E+02 4.74E+02 7.22E-01 1.36E+00 1.51E+00

-4.02E+00 7.76E+00 7.55E+00

-8.47E-01 7.56E+00 7.91E+00 NA NA NA 3.38E+03 MW-45-61 MW-45-61 Q2-2011 Mid 025 58

-4.4 7/25/2011 10:00 5.63E+03 8.49E+02 4.33E+02 9.47E-01 1.19E+00 1.25E+00 1.42E+00 5.79E+00 6.69E+00 2.07E+00 8.34E+00 9.68E+00 NA NA NA 3.38E+03 MW-45-61 MW-45-61 Q3-2011 Mid 026 58

-4.4 8/23/2011 10:48 5.91E+03 8.13E+02 4.34E+02 7.01E-01 1.16E+00 1.26E+00

-8.68E-01 7.44E+00 7.90E+00 1.84E+00 6.63E+00 7.89E+00 NA NA NA 3.38E+03 MW-45-61 MW-46 Q4-2010 022 10.5 7.6 10/28/2010 13:25 3.13E+03 3.08E+02 1.13E+02 3.76E-01 5.09E-01 5.49E-01

-2.05E+00 5.85E+00 5.88E+00 2.98E+00 6.81E+00 8.22E+00 NA NA NA 3.45E+03 ND ND ND NA MW-46 MW-46 Q1-2011 023 10.5 7.6 2/23/2011 12:46 2.47E+03 5.70E+02 3.98E+02 1.12E+00 1.89E+00 2.06E+00

-2.22E+00 5.28E+00 5.28E+00 5.21E-01 5.10E+00 5.66E+00 NA NA NA 3.45E+03 MW-46 MW-46 Q2-2011 024 10.5 7.6 4/25/2011 11:19 5.25E+03 7.54E+02 3.95E+02 1.48E+00 1.72E+00 1.80E+00

-2.48E+00 7.24E+00 7.06E+00

-4.44E+00 7.44E+00 6.77E+00 NA NA NA 3.45E+03 MW-46 MW-46 Q2-2011 Mid 025 10.5 7.6 7/13/2011 13:29 3.08E+03 7.17E+02 2.86E+02 8.44E-01 1.19E+00 1.26E+00 3.71E+00 8.64E+00 1.04E+01

-9.54E-01 1.02E+01 1.08E+01 NA NA NA 3.45E+03 MW-46 MW-46 Q3-2011 026 10.5 7.6 8/17/2011 11:36 3.30E+03 6.72E+02 4.50E+02 8.77E-01 1.21E+00 1.29E+00 3.43E-01 7.86E+00 8.82E+00

-1.10E+00 7.50E+00 7.97E+00 NA NA NA 3.45E+03 MW-46 MW-47-56 Q2-2011 Mid 006 53.2 17.1 7/6/2011 15:32 3.52E+03 6.57E+02 4.48E+02 4.63E-01 1.08E+00 1.22E+00

-1.56E+00 1.11E+01 1.20E+01 1.45E-01 7.41E+00 8.25E+00

-1.99E+01 2.17E+01 2.50E+01 2.03E+03 ND ND ND ND MW-47-56 MW-47-56 Q3-2011 Mid 007 53.2 17.1 8/18/2011 12:39 5.42E+02 2.76E+02 2.00E+02 1.03E+00 1.28E+00 1.31E+00

-8.54E-01 1.13E+01 1.25E+01 3.86E+00 8.64E+00 1.07E+01

-2.22E+00 1.75E+01 2.00E+01 2.03E+03 MW-47-56 MW-47-80 Q2-2011 Mid 005 74

-3.7 7/6/2011 14:37 1.36E+05 3.36E+03 4.50E+02 1.95E+00 1.33E+00 1.22E+00

-1.57E+00 8.37E+00 8.73E+00

-3.43E+00 7.80E+00 7.13E+00 3.07E+00 2.59E+01 2.89E+01 1.37E+05 1.95E+00 ND ND ND MW-47-80 MW-47-80 Q3-2011 Mid 006 74

-3.7 8/18/2011 11:36 1.37E+05 4.08E+03 2.18E+02 8.23E-01 1.22E+00 1.29E+00

-5.83E+00 9.30E+00 8.60E+00

-6.32E-01 8.79E+00 9.27E+00

-1.15E+00 1.88E+01 2.15E+01 1.37E+05 1.95E+00 MW-47-80 MW-49-26 Q4-2010 022 19.1

-4.4 11/11/2010 14:23 2.59E+03 3.00E+02 4.76E+02

-3.42E-01 9.56E-01 2.34E+00 4.62E+00 4.84E+00 1.15E+01 1.18E+00 3.96E+00 9.11E+00

-1.79E+00 1.02E+01 2.29E+01 3.26E+03 1.27E+01 ND ND ND MW-49-26 MW-49-26 Q1-2011 023 19.1

-4.4 1/28/2011 13:37 3.17E+03 6.00E+02 4.29E+02 1.30E+01 2.86E+00 2.01E+00 3.39E-01 1.04E+01 7.00E+00

-2.43E+00 6.42E+00 6.44E+00

-4.38E+00 1.87E+01 2.20E+01 3.26E+03 1.27E+01 MW-49-26 MW-49-26 Q2-2011 024 19.1

-4.4 4/15/2011 11:58 3.29E+03 7.18E+02 4.80E+02 1.26E+01 3.06E+00 1.91E+00 4.75E+00 1.07E+01 1.27E+01 4.03E+00 1.20E+01 1.47E+01 1.81E+00 1.50E+01 1.72E+01 3.26E+03 1.27E+01 MW-49-26 MW-49-26 Q3-2011 025 19.1

-4.4 8/10/2011 10:46 3.97E+03 6.39E+02 2.00E+02 1.26E+01 2.89E+00 1.34E+00

-1.94E+00 9.06E+00 9.33E+00 2.94E+00 8.31E+00 1.00E+01

-1.77E+01 2.04E+01 2.57E+01 3.26E+03 1.27E+01 MW-49-26 MW-49-42 Q4-2010 022 38.1

-23.4 11/11/2010 14:13 2.39E+03 2.73E+02 4.02E+02 1.99E+01 1.65E+00 1.12E+00 8.48E-01 6.79E+00 9.79E+00 3.75E+00 5.42E+00 1.30E+01 4.00E+00 8.14E+00 1.80E+01 2.64E+03 1.87E+01 ND ND ND MW-49-42 MW-49-42 Q1-2011 023 38.1

-23.4 1/28/2011 13:00 2.45E+03 5.38E+02 3.86E+02 2.30E+01 4.02E+00 2.02E+00

-1.07E+00 5.74E+00 6.21E+00

-2.45E+00 5.50E+00 5.32E+00

-3.26E+00 1.86E+01 2.18E+01 2.64E+03 1.87E+01 MW-49-42 MW-49-42 Q2-2011 024 38.1

-23.4 4/15/2011 11:55 1.90E+03 6.04E+02 4.78E+02 1.57E+01 3.34E+00 2.07E+00

-6.72E+00 7.62E+00 6.17E+00 1.15E-01 7.72E+00 8.33E+00 6.68E+00 1.55E+01 1.73E+01 2.64E+03 1.87E+01 MW-49-42 MW-49-42 Q3-2011 025 38.1

-23.4 8/10/2011 11:16 3.83E+03 6.21E+02 1.96E+02 1.61E+01 3.24E+00 1.64E+00

-1.22E+00 8.94E+00 9.69E+00

-3.72E+00 8.79E+00 8.23E+00

-1.40E+01 1.81E+01 2.15E+01 2.64E+03 1.87E+01 MW-49-42 MW-49-65 Q4-2010 022 60

-45.4 11/11/2010 14:18 1.37E+03 2.34E+02 3.97E+02 1.41E+01 1.45E+00 1.34E+00 6.99E+00 6.88E+00 1.07E+01 3.39E-01 5.37E+00 1.18E+01

-3.41E+00 9.31E+00 2.09E+01 2.03E+03 1.33E+01 ND ND ND MW-49-65 MW-49-65 Q1-2011 023 60

-45.4 1/28/2011 13:15 1.94E+03 5.02E+02 3.85E+02 1.15E+01 3.28E+00 2.06E+00

-6.30E-01 4.96E+00 5.21E+00 7.15E-01 5.20E+00 5.81E+00

-9.08E+00 1.83E+01 2.20E+01 2.03E+03 1.33E+01 MW-49-65 MW-49-65 Q2-2011 024 60

-45.4 4/15/2011 11:50 2.38E+03 6.48E+02 4.81E+02 1.62E+01 3.12E+00 1.60E+00 2.59E+00 9.66E+00 1.12E+01 4.62E-02 1.01E+01 1.10E+01 4.11E+00 1.49E+01 1.68E+01 2.03E+03 1.33E+01 MW-49-65 MW-49-65 Q3-2011 025 60

-45.4 8/10/2011 10:55 2.43E+03 5.10E+02 2.00E+02 1.14E+01 2.75E+00 1.42E+00 1.12E-01 7.77E+00 8.40E+00

-4.19E+00 9.00E+00 8.02E+00

-6.91E-01 1.81E+01 2.05E+01 2.03E+03 1.33E+01 MW-49-65 MW-50-42 Q4-2010 023 42

-27.1 11/12/2010 12:10 8.67E+02 1.83E+02 1.22E+02 3.73E+00 1.31E+00 9.89E-01 2.40E+00 5.71E+00 6.76E+00 2.73E+00 5.58E+00 6.94E+00

-7.36E+00 1.79E+01 2.15E+01 1.44E+03 6.23E+00 ND ND ND MW-50-42 MW-50-42 Q1-2011 024 42

-27.1 2/25/2011 12:36 5.61E+02 3.88E+02 3.85E+02 5.42E+00 2.34E+00 1.91E+00

-1.29E-01 5.46E+00 5.88E+00

-9.07E-01 4.42E+00 4.42E+00

-7.19E+00 1.82E+01 2.18E+01 1.44E+03 6.23E+00 MW-50-42 MW-50-42 Q2-2011 025 42

-27.1 5/3/2011 12:05 3.77E+03 5.58E+02 3.41E+02 9.53E+00 2.20E+00 1.04E+00 1.92E+00 9.44E+00 1.07E+01 5.79E-01 1.02E+01 1.16E+01 5.86E-01 1.69E+01 1.92E+01 1.44E+03 6.23E+00 MW-50-42 MW-50-42 Q2-2011 Mid 026 42

-27.1 7/25/2011 12:18 1.03E+03 4.89E+02 4.43E+02 3.01E+00 2.09E+00 2.02E+00

-1.11E+00 7.86E+00 8.36E+00 6.63E-02 8.16E+00 9.04E+00 3.81E+00 1.71E+01 1.91E+01 1.44E+03 6.23E+00 MW-50-42 MW-50-42 Q3-2011 027 42

-27.1 8/19/2011 12:10 9.52E+02 3.42E+02 2.00E+02 9.47E+00 2.60E+00 1.31E+00 2.17E+00 8.01E+00 9.07E+00 4.72E+00 9.81E+00 1.22E+01

-7.08E+00 1.81E+01 2.10E+01 1.44E+03 6.23E+00 MW-50-42 MW-50-66 Q4-2010 028 60

-45.1 11/12/2010 12:30 3.72E+03 3.30E+02 1.20E+02 2.33E+01 2.71E+00 9.50E-01

-1.39E+00 6.21E+00 6.79E+00

-1.67E+00 6.95E+00 7.30E+00 3.25E-01 1.88E+01 2.18E+01 5.17E+03 2.55E+01 ND ND ND MW-50-66 MW-50-66 Q1-2011 029 60

-45.1 2/25/2011 12:36 3.76E+03 6.18E+02 3.83E+02 2.61E+01 4.02E+00 2.13E+00 2.94E+00 7.20E+00 8.24E+00 6.79E-01 8.00E+00 9.10E+00

-2.80E+00 1.81E+01 2.12E+01 5.17E+03 2.55E+01 MW-50-66 MW-50-66 Q2-2011 030 60

-45.1 5/3/2011 12:07 4.73E+03 6.12E+02 3.45E+02 2.63E+01 3.30E+00 1.08E+00 0.00E+00 1.77E+01 9.05E+00

-2.32E+00 9.06E+00 9.12E+00 8.43E+00 1.70E+01 1.88E+01 5.17E+03 2.55E+01 MW-50-66 MW-50-66 Q2-2011 Mid 031 60

-45.1 7/25/2011 12:26 6.50E+03 8.73E+02 4.48E+02 2.61E+01 4.08E+00 1.35E+00

-4.59E-01 7.02E+00 7.74E+00 3.81E+00 8.55E+00 1.07E+01 1.02E+01 1.66E+01 1.81E+01 5.17E+03 2.55E+01 MW-50-66 MW-50-66 Q3-2011 032 60

-45.1 8/19/2011 12:12 7.15E+03 8.49E+02 2.00E+02 2.57E+01 4.05E+00 1.65E+00 3.97E+00 8.46E+00 1.01E+01 1.73E+00 9.03E+00 1.05E+01

-8.92E+00 1.80E+01 2.11E+01 5.17E+03 2.55E+01 MW-50-66 MW-51-40 Q4-2010 017 39.7 28 11/30/2010 12:54 1.48E+02 1.41E+02 1.44E+02 1.46E-01 6.05E-01 7.12E-01 1.54E+00 4.28E+00 4.95E+00 1.72E+00 4.17E+00 4.95E+00 NA NA NA 1.48E+02 ND ND ND NA MW-51-40

TABLE 3 THIRD QUARTER 2011 GROUNDWATER ANALYTICAL RESULTS AND AVERAGES INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q32011 FINAL Table 3 - Third Quarter 2011 Groundwater Analytical Results and Averages.xlsx; Q32011 Table 3 Page 3 of 6 See Page 6 for Notes TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Date Time Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Average Average Average Average Average ANALYSIS RESULTS5 YEARLY ROLLING AVERAGES4,6 Well ID1 TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

SAMPLE COLLECTION Well ID1 SAMPLING QUARTER2,8 SAMPLE ID SAMPLE ZONE CENTER Depth Ft Below Top of Casing3 SAMPLE ZONE CENTER Elevation Ft msl3 MW-51-40 Q1-2011 018 39.7 28 3/8/2011 10:18 1.02E+02 2.34E+02 2.67E+02 1.07E+00 1.51E+00 1.61E+00

-7.97E+00 1.21E+01 1.36E+01 2.42E+00 7.30E+00 8.76E+00 NA NA NA 1.48E+02 MW-51-40 MW-51-40 Q2-2011 019 39.7 28 4/29/2011 10:41 3.63E+02 4.14E+02 4.35E+02 2.26E-01 1.37E+00 1.59E+00

-3.40E+00 9.48E+00 9.62E+00 6.20E+00 1.11E+01 1.40E+01 NA NA NA 1.48E+02 MW-51-40 MW-51-40 Q3-2011 020 39.7 28 7/28/2011 11:43 3.78E+01 3.06E+02 3.52E+02

-2.51E-01 1.37E+00 1.85E+00

-2.58E+00 1.35E+01 1.68E+01

-3.37E+00 9.33E+00 9.05E+00 NA NA NA 1.48E+02 MW-51-40 MW-51-79 Q4-2010 017 78.7

-11 11/30/2010 13:08 3.11E+01 1.21E+02 1.44E+02

-1.22E-01 4.32E-01 5.24E-01

-8.30E-01 4.13E+00 4.54E+00 9.98E-01 4.02E+00 4.66E+00 NA NA NA ND ND ND ND NA MW-51-79 MW-51-79 Q1-2011 018 78.7

-11 3/8/2011 10:34 1.36E+02 2.46E+02 2.70E+02

-2.03E-01 1.22E+00 1.53E+00 2.42E+00 5.42E+00 6.52E+00

-2.74E+00 7.36E+00 6.45E+00 NA NA NA MW-51-79 MW-51-79 Q2-2011 019 78.7

-11 4/29/2011 10:57 1.17E+02 3.82E+02 4.33E+02 1.03E+00 1.67E+00 1.82E+00

-4.93E-01 7.56E+00 8.23E+00

-8.38E-01 8.08E+00 8.53E+00 NA NA NA MW-51-79 MW-51-79 Q3-2011 020 78.7

-11 7/28/2011 11:55

-1.93E+01 3.09E+02 3.60E+02 1.36E-01 1.63E+00 1.96E+00 2.20E+00 8.28E+00 9.43E+00

-5.24E-01 9.27E+00 9.93E+00 NA NA NA MW-51-79 MW-51-104 Q4-2010 015 103.7

-36 11/30/2010 9:55 8.54E+01 1.33E+02 1.47E+02 3.74E-01 7.18E-01 8.12E-01

-1.43E-01 3.99E+00 4.55E+00 2.19E-01 4.56E+00 5.05E+00 NA NA NA ND ND ND ND NA MW-51-104 MW-51-104 Q1-2011 016 103.7

-36 3/8/2011 12:10 5.76E+01 3.10E+02 3.55E+02 8.91E-01 1.47E+00 1.60E+00 2.54E+00 7.20E+00 8.14E+00 9.02E-01 5.50E+00 6.24E+00 NA NA NA MW-51-104 MW-51-104 Q2-2011 017 103.7

-36 4/29/2011 12:35 1.97E+02 3.90E+02 4.32E+02 1.41E+00 1.45E+00 1.48E+00

-1.90E+00 1.08E+01 1.25E+01

-6.79E-01 1.10E+01 1.20E+01 NA NA NA MW-51-104 MW-51-104 Q3-2011 018 103.7

-36 7/28/2011 9:51 1.64E+02 3.18E+02 3.51E+02

-8.86E-01 1.26E+00 1.94E+00

-1.15E-01 6.18E+00 6.84E+00

-3.12E+00 8.10E+00 7.98E+00 NA NA NA MW-51-104 MW-51-135 Q4-2010 015 135.2

-67.5 11/30/2010 9:57 9.53E+01 1.33E+02 1.45E+02 4.21E-01 7.13E-01 7.98E-01

-5.11E-01 4.18E+00 4.61E+00

-2.98E-01 4.20E+00 4.58E+00 NA NA NA ND ND ND ND NA MW-51-135 MW-51-135 Q1-2011 016 135.2

-67.5 3/8/2011 12:44 8.29E+01 2.24E+02 2.62E+02 8.62E-01 1.31E+00 1.42E+00 8.60E-02 6.02E+00 6.77E+00 2.37E+00 5.96E+00 7.38E+00 NA NA NA MW-51-135 MW-51-135 Q2-2011 017 135.2

-67.5 4/29/2011 13:16 0.00E+00 3.66E+02 4.35E+02 1.14E+00 1.52E+00 1.63E+00 2.52E+00 1.01E+01 1.17E+01

-5.69E-01 9.00E+00 9.56E+00 NA NA NA MW-51-135 MW-51-135 Q3-2011 018 135.2

-67.5 7/28/2011 10:04

-5.63E+01 2.96E+02 3.49E+02 8.06E-01 1.71E+00 1.92E+00 4.41E+00 8.22E+00 9.83E+00 1.32E+00 9.36E+00 1.05E+01 NA NA NA MW-51-135 MW-51-163 Q4-2010 015 162.7

-95 11/30/2010 10:02 9.01E+01 1.31E+02 1.44E+02

-3.11E-01 6.98E-01 9.94E-01 1.23E+00 8.07E+00 4.14E+00 3.30E-01 3.94E+00 4.43E+00 NA NA NA ND ND ND ND NA MW-51-163 MW-51-163 Q1-2011 016 162.7

-95 3/8/2011 13:01 0.00E+00 1.96E+02 2.63E+02

-5.97E-01 1.39E+00 1.98E+00 2.81E+00 6.54E+00 7.66E+00 5.35E-01 7.76E+00 8.69E+00 NA NA NA MW-51-163 MW-51-163 Q2-2011 017 162.7

-95 4/29/2011 13:19 4.68E+01 3.66E+02 4.30E+02 5.27E-01 1.45E+00 1.65E+00 2.26E+00 8.40E+00 9.72E+00 9.25E-01 7.72E+00 8.87E+00 NA NA NA MW-51-163 MW-51-163 Q3-2011 018 162.7

-95 7/28/2011 10:18 1.20E+02 3.18E+02 3.54E+02

-7.15E-01 1.26E+00 1.96E+00 6.34E-01 7.71E+00 8.41E+00 3.60E+00 9.69E+00 1.17E+01 NA NA NA MW-51-163 MW-51-189*

Q4-2010 015 189.2

-121.5 11/30/2010 9:56 6.91E+01 1.29E+02 1.46E+02 1.93E-01 7.99E-01 9.81E-01

-7.45E-01 4.51E+00 4.98E+00

-3.16E-01 4.61E+00 5.06E+00 NA NA NA ND ND ND*

ND NA MW-51-189*

MW-51-189*

Q1-2011 016 189.2

-121.5 3/8/2011 12:30

-1.50E+01 1.93E+02 2.68E+02

-3.06E-01 1.46E+00 1.97E+00 3.77E+01*

1.47E+01 6.28E+00 2.28E-01 5.28E+00 5.79E+00 NA NA NA 3.77E+01 MW-51-189*

MW-51-189*

Q2-2011 017 189.2

-121.5 4/29/2011 12:52 2.32E+02 3.96E+02 4.33E+02 1.28E+00 1.50E+00 1.57E+00

-8.07E-01 5.82E+00 6.25E+00

-5.07E+00 9.48E+00 8.89E+00 NA NA NA 3.77E+01 MW-51-189*

MW-51-189*

Q3-2011 018 189.2

-121.5 7/28/2011 10:42

-5.69E+00 3.03E+02 3.53E+02 3.69E-02 1.66E+00 1.95E+00 2.36E+00 1.07E+01 1.02E+01 2.52E+00 1.01E+01 1.17E+01 NA NA NA 3.77E+01 MW-51-189*

MW-52-11 Q2-2011 006 10 6.8 4/22/2011 12:10 3.04E+02 4.08E+02 4.35E+02 1.29E-01 1.35E+00 1.60E+00 2.27E+00 1.02E+01 1.17E+01 5.08E+00 9.92E+00 1.24E+01 NA NA NA ND ND ND ND NA MW-52-11 MW-52-11 Q2-2011 Mid 007 10 6.8 7/26/2011 12:32 3.39E+02 3.99E+02 4.21E+02 1.86E-01 1.49E+00 1.74E+00 1.71E+00 8.76E+00 9.71E+00

-2.27E+00 8.43E+00 8.63E+00 NA NA NA MW-52-11 MW-52-18 Q2-2011 006 17.5

-2.6 4/22/2011 12:16 7.01E+01 3.76E+02 4.35E+02 1.37E+00 1.39E+00 1.42E+00 8.81E+00 1.29E+01 9.01E+00

-1.49E+00 9.44E+00 9.90E+00 NA NA NA ND ND ND ND NA MW-52-18 MW-52-18 Q2-2011 Mid 007 17.5

-2.6 7/26/2011 14:39 2.52E+02 3.87E+02 4.22E+02 1.06E+00 1.62E+00 1.76E+00 3.80E+00 6.45E+00 8.08E+00

-3.24E+00 8.10E+00 7.84E+00 NA NA NA MW-52-18 MW-52-48 Q2-2011 006 48

-33.1 4/22/2011 12:18 1.06E+02 3.82E+02 4.36E+02 1.69E-01 1.37E+00 1.62E+00

-4.59E+00 7.58E+00 7.31E+00 1.35E+00 7.80E+00 9.17E+00 NA NA NA ND ND ND ND NA MW-52-48 MW-52-48 Q2-2011 Mid 007 48

-33.1 7/26/2011 15:08 7.68E+01 3.66E+02 4.21E+02 2.58E-01 1.20E+00 1.46E+00 2.34E+00 9.60E+00 1.07E+01

-7.68E-01 8.73E+00 1.01E+01 NA NA NA MW-52-48 MW-52-64 Q2-2011 006 64

-49.1 4/22/2011 15:23

-2.26E+01 3.58E+02 4.32E+02 5.12E-01 1.13E+00 1.27E+00 1.87E+00 6.72E+00 7.70E+00

-8.05E+00 8.28E+00 6.18E+00 NA NA NA ND ND ND ND NA MW-52-64 MW-52-64 Q2-2011 Mid 007 64

-49.1 7/27/2011 10:45 1.35E+02 3.81E+02 4.31E+02

-4.58E-01 8.67E-01 1.27E+00 2.48E+00 7.17E+00 8.34E+00 6.66E-01 8.13E+00 9.05E+00 NA NA NA MW-52-64 MW-52-122 Q2-2011 006 122

-107.1 4/22/2011 10:45

-2.27E+01 3.60E+02 4.33E+02 1.14E+00 1.17E+00 1.17E+00 3.48E+01 2.08E+01 9.71E+00

-1.96E+00 7.96E+00 7.90E+00 NA NA NA ND ND 3.48E+01 ND NA MW-52-122 MW-52-122 Q2-2011 Mid 007 122

-107.1 7/26/2011 13:36

-2.18E+01 3.48E+02 4.19E+02 1.05E-01 1.19E+00 1.47E+00

-5.49E+00 7.92E+00 7.50E+00 8.02E-01 6.84E+00 7.89E+00 NA NA NA 3.48E+01 MW-52-122 MW-52-162 Q2-2011 006 161.5

-146.6 4/22/2011 10:18 1.85E+02 3.84E+02 4.29E+02

-7.50E-01 9.50E-01 1.42E+00 1.47E+00 8.40E+00 9.68E+00 1.95E-02 1.00E+01 1.10E+01 NA NA NA 5.16E+02 ND ND ND NA MW-52-162 MW-52-162 Q2-2011 Mid 007 161.5

-146.6 7/26/2011 11:33 5.16E+02 4.20E+02 4.22E+02 3.77E-03 1.21E+00 1.57E+00 4.29E-02 8.34E+00 9.09E+00

-2.32E+00 9.87E+00 1.00E+01 NA NA NA 5.16E+02 MW-52-162 MW-52-181 Q2-2011 006 181

-166.1 4/22/2011 10:22 2.45E+02 3.96E+02 4.33E+02 1.18E+00 1.42E+00 1.48E+00 6.46E+01 2.68E+01 1.22E+01

-1.09E+00 1.22E+01 1.30E+01 NA NA NA ND ND 6.46E+01 ND NA MW-52-181 MW-52-181 Q2-2011 Mid 007 181

-166.1 7/26/2011 11:43 2.41E+02 3.87E+02 4.22E+02 3.57E-01 1.28E+00 1.54E+00

-1.99E+00 7.50E+00 7.52E+00

-1.27E+00 9.39E+00 9.97E+00 NA NA NA 6.46E+01 MW-52-181 MW-53-82 Q4-2010 017 75

-4.7 10/27/2010 12:07 2.59E+03 2.79E+02 1.10E+02 8.07E-01 7.90E-01 8.26E-01

-3.74E-02 5.82E+00 6.57E+00 1.14E-01 6.23E+00 7.00E+00 NA NA NA 1.13E+03 ND ND ND NA MW-53-82 MW-53-82 Q1-2011 018 75

-4.7 3/3/2011 11:53 5.95E+02 3.76E+02 3.73E+02 1.61E+00 1.82E+00 1.91E+00 3.61E+00 6.18E+00 7.60E+00

-1.88E+00 7.02E+00 7.25E+00

-7.63E+00 1.59E+01 1.85E+01 1.13E+03 MW-53-82 MW-53-82 Q2-2011 019 75

-4.7 4/18/2011 12:45 6.24E+02 4.56E+02 4.50E+02 4.40E-01 1.45E+00 1.67E+00

-4.57E+00 9.82E+00 9.80E+00 3.12E+00 8.78E+00 1.07E+01

-5.86E-01 1.48E+01 1.72E+01 1.13E+03 MW-53-82 MW-53-82 Q3-2011 021 75

-4.7 8/1/2011 11:11 7.16E+02 3.84E+02 3.71E+02

-5.52E-01 7.86E-01 1.06E+00

-2.46E+00 7.38E+00 7.34E+00

-3.40E-01 8.49E+00 9.05E+00 8.23E+00 1.80E+01 1.98E+01 1.13E+03 MW-53-82 MW-53-120 Q4-2010 021 109.8

-39.5 10/27/2010 12:48 3.91E+03 3.38E+02 1.11E+02 2.96E+01 2.91E+00 7.02E-01 2.32E+00 5.07E+00 6.00E+00

-9.52E-01 5.46E+00 5.76E+00 NA NA NA 4.08E+03 3.19E+01 ND ND 1.45E+01 MW-53-120 MW-53-120 Q1-2011 022 109.8

-39.5 3/3/2011 12:00 3.84E+03 7.18E+02 3.89E+02 2.95E+01 3.76E+00 1.13E+00 2.30E+00 7.32E+00 8.49E+00

-2.43E+00 8.14E+00 8.13E+00 1.00E+01 1.70E+01 1.87E+01 4.08E+03 3.19E+01 1.45E+01 MW-53-120 MW-53-120 Q2-2011 023 109.8

-39.5 4/18/2011 11:52 4.11E+03 7.72E+02 4.75E+02 3.55E+01 4.56E+00 1.67E+00 1.38E+00 8.82E+00 9.99E+00 4.87E-01 9.24E+00 1.02E+01 1.76E+01 1.77E+01 1.87E+01 4.08E+03 3.19E+01 1.45E+01 MW-53-120 MW-53-120 Q3-2011 025 109.8

-39.5 8/1/2011 10:00 4.44E+03 6.15E+02 3.71E+02 3.30E+01 5.22E+00 1.94E+00

-2.07E+00 8.49E+00 8.67E+00

-5.10E-01 9.36E+00 1.01E+01 1.45E+01 1.02E+01 1.07E+01 4.08E+03 3.19E+01 1.45E+01 MW-53-120 MW-54-37 Q4-2010 015 36.5

-23.4 11/23/2010 14:47 1.45E+03 2.27E+02 1.26E+02 4.51E+00 1.42E+00 9.84E-01

-2.09E+00 5.46E+00 5.80E+00

-6.89E-01 6.35E+00 6.93E+00

-2.56E+00 1.81E+01 2.15E+01 1.34E+04 4.66E+00 ND ND ND MW-54-37 MW-54-37 Q1-2011 016 36.5

-23.4 2/1/2011 14:10 1.33E+03 4.86E+02 3.78E+02 4.88E+00 1.77E+00 1.26E+00

-1.42E+00 5.54E+00 5.67E+00 3.12E-01 6.42E+00 7.04E+00

-2.81E+00 1.59E+01 1.82E+01 1.34E+04 4.66E+00 MW-54-37 MW-54-37 Q2-2011 017 36.5

-23.4 4/12/2011 12:02 5.16E+03 8.40E+02 4.76E+02 4.91E+00 2.08E+00 1.69E+00 2.95E+00 8.26E+00 9.69E+00 2.50E+00 8.26E+00 9.96E+00 3.16E+00 1.45E+01 1.65E+01 1.34E+04 4.66E+00 MW-54-37 MW-54-37 Q2-2011 Mid 018 36.5

-23.4 7/18/2011 13:45 2.79E+04 1.67E+03 4.43E+02 4.34E+00 2.19E+00 1.85E+00

-1.17E+00 6.36E+00 6.58E+00 4.07E+00 9.21E+00 1.09E+01 1.56E+01 1.91E+01 2.07E+01 1.34E+04 4.66E+00 MW-54-37 MW-54-37 Q3-2011 019 36.5

-23.4 8/15/2011 9:25 3.13E+04 1.75E+03 1.98E+02 2.75E-01 1.60E+00 1.88E+00 5.03E-01 6.69E+00 7.58E+00 3.36E+00 7.56E+00 9.28E+00

-1.05E+01 1.66E+01 1.96E+01 1.34E+04 4.66E+00 MW-54-37 MW-54-58 Q4-2010 015 57.5

-44.4 11/23/2010 14:55 8.21E+02 1.80E+02 1.23E+02 2.67E+00 1.13E+00 9.76E-01 3.83E+00 6.50E+00 7.88E+00 2.75E+00 6.57E+00 8.00E+00

-3.94E+00 1.86E+01 2.21E+01 1.90E+03 1.95E+00 ND ND ND MW-54-58 MW-54-58 Q1-2011 016 57.5

-44.4 2/1/2011 14:22 9.58E+02 4.56E+02 3.92E+02 1.68E+00 1.34E+00 1.28E+00

-4.20E-02 7.14E+00 7.94E+00

-2.21E+00 6.84E+00 6.82E+00

-4.89E+00 1.66E+01 1.92E+01 1.90E+03 1.95E+00 MW-54-58 MW-54-58 Q2-2011 017 57.5

-44.4 4/12/2011 12:04 9.94E+02 5.20E+02 4.79E+02 1.15E+00 1.84E+00 2.01E+00 1.70E+00 8.58E+00 9.66E+00 1.14E+00 8.74E+00 9.95E+00 5.01E+00 1.58E+01 1.78E+01 1.90E+03 1.95E+00 MW-54-58 MW-54-58 Q2-2011 Mid 018 57.5

-44.4 7/18/2011 13:33 2.48E+03 6.12E+02 4.44E+02 1.49E+00 1.21E+00 1.14E+00

-1.98E+00 8.85E+00 9.27E+00 2.35E-01 9.09E+00 1.01E+01 1.83E+01 1.97E+01 2.13E+01 1.90E+03 1.95E+00 MW-54-58 MW-54-58 Q3-2011 019 57.5

-44.4 8/15/2011 9:47 4.23E+03 6.63E+02 2.02E+02

-1.92E-01 9.75E-01 1.31E+00

-1.08E+00 8.61E+00 8.19E+00

-8.43E-01 9.45E+00 1.01E+01 2.37E+00 1.84E+01 2.07E+01 1.90E+03 1.95E+00 MW-54-58 MW-54-123 Q4-2010 015 123

-109.9 11/23/2010 15:12 8.12E+02 1.80E+02 1.22E+02 7.65E+00 1.46E+00 9.15E-01 2.19E+00 6.74E+00 7.78E+00

-1.25E+00 6.18E+00 6.62E+00 9.26E+00 1.91E+01 2.15E+01 8.99E+02 4.35E+00 ND ND ND MW-54-123 MW-54-123 Q1-2011 016 123

-109.9 2/1/2011 14:11 1.08E+03 4.68E+02 3.90E+02 2.56E+00 1.39E+00 1.08E+00

-3.56E-01 6.02E+00 6.69E+00

-3.66E-03 5.16E+00 5.75E+00 2.50E+00 1.66E+01 1.87E+01 8.99E+02 4.35E+00 MW-54-123 MW-54-123 Q2-2011 017 123

-109.9 4/12/2011 12:22 8.24E+02 4.98E+02 4.77E+02 3.44E+00 1.96E+00 1.72E+00

-5.24E+00 8.14E+00 7.60E+00 1.86E+00 8.04E+00 9.55E+00

-3.35E+00 1.48E+01 1.75E+01 8.99E+02 4.35E+00 MW-54-123 MW-54-123 Q2-2011 Mid 018 123

-109.9 7/18/2011 14:06 5.70E+02 4.44E+02 4.46E+02 7.16E-01 1.02E+00 1.07E+00 1.92E+00 9.66E+00 1.05E+01 3.87E-02 6.30E+00 6.97E+00 6.27E+00 1.84E+01 2.04E+01 8.99E+02 4.35E+00 MW-54-123 MW-54-123 Q3-2011 019 123

-109.9 8/15/2011 9:55 1.21E+03 3.75E+02 2.00E+02 3.74E+00 2.03E+00 1.78E+00 5.50E-01 8.46E+00 9.31E+00

-5.09E-01 8.88E+00 9.49E+00

-3.43E+00 1.94E+01 2.22E+01 8.99E+02 4.35E+00 MW-54-123 MW-54-144 Q4-2010 015 144

-130.9 11/23/2010 12:30 1.34E+03 2.15E+02 1.21E+02 1.08E+01 1.36E+00 5.83E-01 1.02E+00 7.82E+00 8.59E+00

-3.87E+00 6.48E+00 5.93E+00 2.30E+00 1.91E+01 2.21E+01 2.76E+03 1.09E+01 ND ND ND MW-54-144 MW-54-144 Q1-2011 016 144

-130.9 2/1/2011 12:34 1.35E+03 4.96E+02 3.87E+02 9.31E+00 2.24E+00 1.06E+00

-9.04E-01 6.14E+00 6.70E+00

-6.36E-01 6.20E+00 6.74E+00

-4.27E+00 1.58E+01 1.82E+01 2.76E+03 1.09E+01 MW-54-144 MW-54-144 Q2-2011 017 144

-130.9 4/12/2011 9:50 1.48E+03 5.68E+02 4.79E+02 1.20E+01 2.92E+00 1.81E+00 6.43E+00 7.44E+00 9.59E+00

-4.68E+00 9.58E+00 8.86E+00

-2.75E+00 1.48E+01 1.74E+01 2.76E+03 1.09E+01 MW-54-144 MW-54-144 Q2-2011 Mid 018 144

-130.9 7/18/2011 12:38 4.34E+03 7.41E+02 4.43E+02 1.13E+01 2.44E+00 1.26E+00 3.37E+00 7.47E+00 8.78E+00

-3.49E+00 8.91E+00 8.88E+00 1.53E+01 1.87E+01 2.03E+01 2.76E+03 1.09E+01 MW-54-144 MW-54-144 Q3-2011 019 144

-130.9 8/15/2011 11:44 5.27E+03 7.23E+02 1.96E+02 1.10E+01 2.75E+00 1.62E+00 4.07E+00 9.39E+00 1.10E+01 4.25E-01 9.81E+00 1.08E+01

-5.13E+00 1.89E+01 2.18E+01 2.76E+03 1.09E+01 MW-54-144 MW-54-173 Q4-2010 015 172.5

-159.4 11/23/2010 12:25 1.51E+03 2.28E+02 1.24E+02 4.65E+00 1.28E+00 8.17E-01

-1.84E+00 7.05E+00 7.31E+00

-1.82E+00 6.23E+00 6.51E+00 2.22E+00 1.84E+01 2.14E+01 1.48E+03 4.65E+00 ND ND ND MW-54-173 MW-54-173 Q1-2011 016 172.5

-159.4 2/1/2011 12:29 1.66E+03 5.26E+02 3.81E+02 5.81E+00 1.88E+00 1.10E+00

-2.87E-01 8.00E+00 8.79E+00 1.01E+00 1.06E+01 1.20E+01

-5.49E+00 1.77E+01 2.05E+01 1.48E+03 4.65E+00 MW-54-173 MW-54-173 Q2-2011 017 172.5

-159.4 4/12/2011 9:56 1.26E+03 5.46E+02 4.78E+02 3.91E+00 1.92E+00 1.58E+00

-1.29E+01 1.38E+01 1.53E+01 5.93E+00 9.66E+00 1.25E+01

-2.17E+00 1.50E+01 1.76E+01 1.48E+03 4.65E+00 MW-54-173 MW-54-173 Q2-2011 Mid 018 172.5

-159.4 7/18/2011 12:20 1.48E+03 5.28E+02 4.40E+02 4.54E+00 1.64E+00 1.11E+00 2.97E-01 6.84E+00 7.45E+00 1.10E+00 6.51E+00 7.50E+00

-5.43E+00 1.56E+01 1.75E+01 1.48E+03 4.65E+00 MW-54-173 MW-54-173 Q3-2011 019 172.5

-159.4 8/15/2011 11:50 1.50E+03 4.08E+02 1.97E+02 4.32E+00 1.94E+00 1.48E+00

-1.36E+00 1.01E+01 1.05E+01

-7.70E-01 1.21E+01 1.33E+01

-7.41E+00 2.05E+01 2.42E+01 1.48E+03 4.65E+00 MW-54-173 MW-54-190 Q4-2010 015 190

-176.9 11/23/2010 12:22 1.93E+03 2.55E+02 1.27E+02 1.92E+01 1.89E+00 7.12E-01

-9.64E-01 6.04E+00 6.61E+00

-2.29E+00 6.71E+00 6.79E+00

-3.18E-01 1.81E+01 2.14E+01 2.31E+03 1.83E+01 ND ND ND MW-54-190 MW-54-190 Q1-2011 016 190

-176.9 2/1/2011 12:25 1.89E+03 5.56E+02 3.90E+02 1.68E+01 3.36E+00 1.28E+00 4.59E-01 6.34E+00 7.14E+00

-3.55E+00 5.96E+00 5.21E+00 1.71E+00 1.67E+01 1.89E+01 2.31E+03 1.83E+01 MW-54-190 MW-54-190 Q2-2011 017 190

-176.9 4/12/2011 10:01 2.07E+03 6.18E+02 4.78E+02 1.90E+01 3.38E+00 1.77E+00 3.33E+00 7.86E+00 9.23E+00 8.70E-01 9.00E+00 1.00E+01 3.35E-01 1.58E+01 1.82E+01 2.31E+03 1.83E+01 MW-54-190 MW-54-190 Q2-2011 Mid 018 190

-176.9 7/18/2011 12:14 2.37E+03 6.06E+02 4.45E+02 1.75E+01 2.85E+00 1.12E+00 2.24E+00 1.16E+01 1.29E+01

-2.72E+00 1.18E+01 1.22E+01

-3.86E+00 1.55E+01 1.74E+01 2.31E+03 1.83E+01 MW-54-190 MW-54-190 Q3-2011 019 190

-176.9 8/15/2011 12:00 3.31E+03 5.88E+02 2.00E+02 1.89E+01 3.39E+00 1.22E+00

-3.96E+00 8.61E+00 7.57E+00

-4.68E+00 8.73E+00 8.11E+00

-5.67E+00 1.96E+01 2.30E+01 2.31E+03 1.83E+01 MW-54-190 MW-55-24 Q4-2010 016 16 2.3 11/1/2010 14:10 1.39E+03 2.09E+02 1.65E+02 1.08E+01 1.98E+00 9.92E-01

-2.29E-01 8.10E+00 9.04E+00

-4.71E+00 7.93E+00 6.54E+00 7.56E+00 1.88E+01 2.12E+01 1.37E+03 1.15E+01 ND ND ND MW-55-24 MW-55-24 Q1-2011 017 16 2.3 2/3/2011 14:13 1.02E+03 4.48E+02 4.20E+02 1.09E+01 2.82E+00 1.96E+00

-3.57E-01 4.92E+00 5.43E+00 4.75E+00 8.74E+00 7.44E+00

-5.31E+00 1.81E+01 2.14E+01 1.37E+03 1.15E+01 MW-55-24 MW-55-24 Q3-2011 018 16 2.3 8/12/2011 12:12 1.71E+03 4.35E+02 2.01E+02 1.29E+01 3.21E+00 1.59E+00

-4.41E+00 7.32E+00 6.86E+00 5.14E-01 7.95E+00 8.82E+00 6.75E+00 2.09E+01 2.34E+01 1.37E+03 1.15E+01 MW-55-24 MW-55-35 Q4-2010 015 32

-13.8 11/1/2010 14:26 1.57E+03 2.12E+02 1.62E+02 1.13E+01 1.97E+00 9.17E-01

-2.41E+00 8.88E+00 9.46E+00 5.36E-01 8.18E+00 9.32E+00 6.22E+00 1.79E+01 2.03E+01 2.07E+03 1.56E+01 ND ND ND MW-55-35 MW-55-35 Q1-2011 016 32

-13.8 2/3/2011 14:16 1.70E+03 4.84E+02 3.86E+02 1.93E+01 3.42E+00 2.05E+00 8.32E-01 5.82E+00 6.45E+00 1.03E+00 6.24E+00 7.03E+00

-2.16E+00 1.86E+01 2.17E+01 2.07E+03 1.56E+01 MW-55-35 MW-55-35 Q3-2011 017 32

-13.8 8/12/2011 12:15 2.94E+03 5.58E+02 2.01E+02 1.63E+01 3.18E+00 1.50E+00 4.22E-01 7.50E+00 8.42E+00

-1.40E+00 8.31E+00 8.83E+00

-1.22E+01 2.17E+01 2.60E+01 2.07E+03 1.56E+01 MW-55-35 MW-55-54 Q4-2010 016 47

-28.8 11/1/2010 13:36 8.68E+03 3.95E+02 1.57E+02 1.93E+01 1.72E+00 6.48E-01

-3.03E+00 7.29E+00 7.24E+00 9.59E-01 7.50E+00 8.63E+00 1.12E-01 1.77E+01 2.04E+01 8.56E+03 2.01E+01 ND ND ND MW-55-54 MW-55-54 Q1-2011 017 47

-28.8 2/3/2011 14:17 8.46E+03 8.58E+02 3.89E+02 1.91E+01 3.78E+00 1.95E+00 3.62E+00 5.80E+00 7.00E+00

-6.59E-01 7.44E+00 7.93E+00

-8.13E+00 1.78E+01 2.14E+01 8.56E+03 2.01E+01 MW-55-54 MW-55-54 Q3-2011 018 47

-28.8 8/12/2011 12:09 8.53E+03 9.24E+02 2.00E+02 2.20E+01 3.36E+00 1.17E+00 7.03E+00 8.73E+00 1.08E+01

-2.52E+00 8.07E+00 7.92E+00

-2.57E+00 1.96E+01 2.27E+01 8.56E+03 2.01E+01 MW-55-54 MW-56-53 Q4-2010 009 52 18.3 11/15/2010 12:48 4.64E+02 1.88E+02 3.82E+02 1.27E+00 8.67E-01 1.86E+00 3.71E+00 4.39E+00 1.06E+01

-1.74E+00 4.89E+00 9.96E+00 NA NA NA 4.64E+02 ND ND ND NA MW-56-53 MW-56-53 Q2-2011 010 52 18.3 4/27/2011 12:08 1.18E+02 3.48E+02 3.97E+02

-3.07E-02 1.23E+00 1.60E+00 3.04E+00 8.50E+00 1.01E+01

-1.64E+00 8.42E+00 8.44E+00 NA NA NA 4.64E+02 MW-56-53 MW-56-53 Q2-2011 Mid 011 52 18.3 7/6/2011 12:58 2.03E+02 2.75E+02 2.83E+02

-3.68E-01 7.89E-01 1.12E+00 3.72E+00 7.77E+00 9.45E+00

-4.34E+00 8.82E+00 9.56E+00

-4.67E+00 2.28E+01 2.56E+01 4.64E+02 MW-56-53 MW-56-53 Q3-2011 Mid 012 52 18.3 8/26/2011 11:06 2.47E+02 3.96E+02 4.32E+02

-6.50E-01 7.17E-01 1.13E+00 1.31E+00 8.97E+00 1.00E+01 2.45E+00 7.50E+00 9.03E+00 NA NA NA 4.64E+02 MW-56-53 MW-56-83 Q4-2010 011 74

-3.7 11/15/2010 14:37 2.74E+03 2.63E+02 3.84E+02 1.02E+00 7.08E-01 1.50E+00

-2.51E+00 3.87E+00 7.83E+00

-2.67E+00 3.90E+00 7.34E+00 NA NA NA 6.71E+04 2.81E+00 ND ND NA MW-56-83 MW-56-83 Q2-2011 012 74

-3.7 4/27/2011 13:46 7.64E+04 2.40E+03 4.19E+02 3.87E+00 1.60E+00 1.28E+00

-1.05E+00 1.14E+01 1.33E+01

-1.27E+00 9.50E+00 1.01E+01 NA NA NA 6.71E+04 2.81E+00 MW-56-83 MW-56-83 Q2-2011 Mid 013 74

-3.7 7/6/2011 11:58 8.42E+04 3.54E+03 2.81E+02 1.45E+00 1.27E+00 1.19E+00 2.77E+00 2.01E+01 9.44E+00 4.20E-01 8.16E+00 9.20E+00

-1.36E+01 2.15E+01 2.46E+01 6.71E+04 2.81E+00 MW-56-83 MW-56-83 Q3-2011 Mid 014 74

-3.7 8/26/2011 10:56 1.05E+05 3.12E+03 4.42E+02 3.12E+00 1.61E+00 1.37E+00

-2.12E+00 8.13E+00 8.21E+00

-6.41E-01 8.67E+00 9.15E+00 NA NA NA 6.71E+04 2.81E+00 MW-56-83 MW-57-11 Q2-2011 007 10 5

5/4/2011 10:28 6.40E+03 6.84E+02 3.41E+02 3.11E+01 3.62E+00 1.04E+00 3.74E+00 8.32E+00 9.74E+00 2.05E+00 8.40E+00 9.72E+00 6.20E+00 1.66E+01 1.85E+01 7.01E+03 3.02E+01 ND ND ND MW-57-11 MW-57-11 Q2-2011 Mid 008 10 5

7/18/2011 11:57 7.36E+03 9.18E+02 4.45E+02 3.87E+01 5.28E+00 2.11E+00 3.27E-01 8.88E+00 9.84E+00

-2.34E+00 9.18E+00 9.39E+00

-6.76E+00 1.48E+01 1.67E+01 7.01E+03 3.02E+01 MW-57-11 MW-57-11 Q3-2011 Mid 009 10 5

8/19/2011 9:49 7.27E+03 8.58E+02 2.02E+02 2.08E+01 3.21E+00 1.24E+00 4.49E+00 7.50E+00 9.07E+00 2.31E+00 7.74E+00 9.17E+00 4.92E-01 2.06E+01 2.36E+01 7.01E+03 3.02E+01 MW-57-11 MW-57-20 Q2-2011 007 19

-4 5/4/2011 10:37 2.03E+04 1.15E+03 3.44E+02 1.74E+00 1.11E+00 9.49E-01 1.48E+00 7.52E+00 8.43E+00

-7.32E-01 9.22E+00 1.02E+01

-5.44E+00 1.64E+01 1.91E+01 2.77E+04 1.64E+00 ND ND ND MW-57-20 MW-57-20 Q2-2011 Mid 008 19

-4 7/18/2011 12:09 3.81E+04 1.94E+03 4.43E+02 1.27E+00 1.08E+00 1.01E+00

-5.13E+00 7.71E+00 7.35E+00 9.16E-01 8.67E+00 9.92E+00

-5.69E+00 1.93E+01 2.20E+01 2.77E+04 1.64E+00 MW-57-20 MW-57-20 Q3-2011 Mid 009 19

-4 8/19/2011 9:54 2.47E+04 1.55E+03 1.98E+02 1.90E+00 1.68E+00 1.56E+00

-2.01E+00 7.35E+00 7.66E+00 1.68E+00 8.07E+00 9.48E+00 3.14E+00 1.98E+01 2.25E+01 2.77E+04 1.64E+00 MW-57-20 MW-57-45 Q2-2011 008 40

-25 5/4/2011 11:03 1.35E+04 9.48E+02 3.43E+02 9.06E-01 9.74E-01 9.60E-01 7.40E+00 9.54E+00 1.21E+01

-1.84E+00 9.48E+00 9.59E+00 6.39E+00 1.78E+01 1.98E+01 2.11E+04 ND ND ND ND MW-57-45 MW-57-45 Q2-2011 Mid 009 40

-25 7/18/2011 12:36 2.53E+04 1.60E+03 4.47E+02 1.28E+00 1.32E+00 1.34E+00

-2.08E-01 8.16E+00 8.83E+00

-7.58E-01 9.39E+00 9.67E+00

-1.04E+01 1.53E+01 1.74E+01 2.11E+04 MW-57-45 MW-57-45 Q3-2011 Mid 010 40

-25 8/19/2011 10:19 2.46E+04 1.56E+03 2.02E+02 4.31E-01 1.01E+00 1.15E+00

-5.69E+00 1.03E+01 1.04E+01 2.03E+00 8.04E+00 9.53E+00 2.27E+00 2.09E+01 2.38E+01 2.11E+04 MW-57-45 MW-58-26 Q4-2010 011 20

-5.4 11/11/2010 15:12 3.66E+02 1.73E+02 1.44E+02 4.13E-01 7.89E-01 8.92E-01 1.98E+00 3.81E+00 4.51E+00 2.98E+00 3.75E+00 4.70E+00 NA NA NA 1.35E+03 ND ND ND NA MW-58-26

TABLE 3 THIRD QUARTER 2011 GROUNDWATER ANALYTICAL RESULTS AND AVERAGES INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q32011 FINAL Table 3 - Third Quarter 2011 Groundwater Analytical Results and Averages.xlsx; Q32011 Table 3 Page 4 of 6 See Page 6 for Notes TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Date Time Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Average Average Average Average Average ANALYSIS RESULTS5 YEARLY ROLLING AVERAGES4,6 Well ID1 TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

SAMPLE COLLECTION Well ID1 SAMPLING QUARTER2,8 SAMPLE ID SAMPLE ZONE CENTER Depth Ft Below Top of Casing3 SAMPLE ZONE CENTER Elevation Ft msl3 MW-58-26 Q2-2011 012 20

-5.4 5/3/2011 9:58 7.22E+02 4.30E+02 4.21E+02 3.15E-01 1.13E+00 1.32E+00 2.29E+00 5.80E+00 6.89E+00

-6.42E+00 9.02E+00 8.00E+00 NA NA NA 1.35E+03 MW-58-26 MW-58-26 Q2-2011 Mid 013 20

-5.4 7/5/2011 13:29 1.86E+03 5.46E+02 4.47E+02

-3.25E-01 1.10E+00 1.41E+00 7.41E-01 6.84E+00 7.61E+00 1.22E+00 7.32E+00 8.39E+00

-1.01E+01 1.99E+01 2.25E+01 1.35E+03 MW-58-26 MW-58-26 Q3-2011 Mid 014 20

-5.4 8/26/2011 14:47 2.47E+03 5.10E+02 1.99E+02

-6.17E-02 7.95E-01 1.05E+00 2.39E-01 7.65E+00 8.47E+00 3.25E-01 8.22E+00 9.22E+00 NA NA NA 1.35E+03 MW-58-26 MW-58-65***

Q4-2010 011 54

-39.4 11/11/2010 13:53 4.81E+02 1.88E+02 1.45E+02 7.15E-01 7.72E-01 8.31E-01 2.61E-01 3.71E+00 4.18E+00 3.74E+00 4.41E+00 5.49E+00 NA NA NA 7.69E+02 ND***

ND ND NA MW-58-65***

MW-58-65***

Q2-2011 012 54

-39.4 5/3/2011 10:11 3.29E+02 3.78E+02 3.97E+02

-4.47E-01 1.03E+00 1.44E+00 1.93E+00 5.92E+00 7.00E+00

-7.81E-01 7.04E+00 7.26E+00 NA NA NA 7.69E+02 3.64E+00 MW-58-65***

MW-58-65***

Q2-2011 Mid 013 54

-39.4 7/5/2011 13:30 7.26E+02 3.93E+02 2.83E+02 4.19E-01 9.12E-01 1.03E+00 5.29E+00 1.05E+01 1.25E+01 1.47E+00 7.53E+00 8.78E+00 3.44E-01 2.03E+01 2.27E+01 7.69E+02 3.64E+00 MW-58-65***

MW-58-65***

Q3-2011 Mid 014 54

-39.4 8/26/2011 14:04 1.10E+03 4.62E+02 2.61E+02 6.31E-01***

1.82E+00 1.60E+00

-1.06E+00 9.00E+00 9.65E+00

-1.54E+00 1.01E+01 1.04E+01 NA NA NA 7.69E+02 3.64E+00 MW-58-65***

MW-59-32 Q2-2011 Mid 005 27

-12.5 7/20/2011 9:59 1.56E+02 3.90E+02 4.38E+02 5.88E-01 1.14E+00 1.27E+00

-1.79E+00 7.92E+00 8.02E+00

-2.58E+00 9.78E+00 1.02E+01

-1.40E+01 1.82E+01 2.07E+01 4.74E+02 ND ND ND ND MW-59-32 MW-59-32 Q3-2011 Mid 006 27

-12.5 8/24/2011 14:22 4.74E+02 2.72E+02 2.17E+02 7.95E-01 1.13E+00 1.20E+00

-2.52E+00 1.05E+01 1.13E+01 2.65E+00 8.25E+00 9.93E+00

-6.65E+00 2.16E+01 2.54E+01 4.74E+02 MW-59-32 MW-59-45 Q2-2011 Mid 005 42

-27.5 7/20/2011 9:59 5.24E+02 4.35E+02 4.43E+02

-1.01E+00 1.05E+00 1.49E+00 1.81E+00 8.52E+00 9.88E+00 2.79E+00 9.48E+00 1.15E+01

-1.12E+01 1.83E+01 2.08E+01 8.82E+02 ND ND ND ND MW-59-45 MW-59-45 Q3-2011 Mid 006 42

-27.5 8/24/2011 14:32 1.24E+03 4.92E+02 2.64E+02 1.13E-01 1.11E+00 1.33E+00

-1.32E+00 8.37E+00 8.81E+00 4.22E+00 9.42E+00 1.18E+01 1.31E+00 1.07E+01 1.20E+01 8.82E+02 MW-59-45 MW-59-68 Q2-2011 Mid 005 58

-43.5 7/20/2011 10:14 1.15E+02 3.90E+02 4.42E+02 1.10E-01 7.26E-01 9.01E-01 2.83E+00 9.33E+00 1.09E+01 8.22E-01 9.87E+00 1.06E+01

-1.57E+01 2.17E+01 2.47E+01 ND ND ND ND ND MW-59-68 MW-59-68 Q3-2011 Mid 006 58

-43.5 8/24/2011 14:09 2.61E+02 2.83E+02 2.66E+02

-5.46E-01 7.35E-01 1.14E+00

-5.62E+00 8.52E+00 7.69E+00 1.56E+00 9.03E+00 1.03E+01 4.94E+00 1.28E+01 1.42E+01 MW-59-68 MW-60-35 Q4-2010 015 34.9

-22.4 11/18/2010 13:25 2.44E+02 1.85E+02 4.00E+02

-5.33E-01 6.54E-01 1.73E+00 9.47E-01 4.80E+00 1.08E+01

-4.28E-01 4.56E+00 9.75E+00

-1.11E+01 8.47E+00 1.92E+01 4.99E+02 ND ND ND ND MW-60-35 MW-60-35 Q1-2011 016 34.9

-22.4 2/11/2011 12:17 3.20E+02 3.72E+02 3.88E+02 9.73E-01 1.63E+00 1.78E+00 2.69E+00 6.24E+00 7.46E+00 1.22E-01 3.76E+00 4.24E+00

-1.61E+00 1.62E+01 1.84E+01 4.99E+02 MW-60-35 MW-60-35 Q2-2011 017 34.9

-22.4 4/15/2011 11:36 2.03E+02 4.32E+02 4.80E+02 3.77E-01 1.66E+00 2.00E+00 2.46E+00 1.14E+01 8.95E+00

-8.48E-01 9.58E+00 1.03E+01 2.65E+00 1.42E+01 1.61E+01 4.99E+02 MW-60-35 MW-60-35 Q3-2011 018 34.9

-22.4 8/10/2011 10:54 4.99E+02 2.69E+02 2.00E+02

-5.84E-01 7.74E-01 1.17E+00 2.11E+00 6.96E+00 8.28E+00

-1.04E+00 1.03E+01 1.10E+01 NA NA NA 4.99E+02 MW-60-35 MW-60-53 Q4-2010 015 53.4

-40.9 11/18/2010 12:22 2.49E+02 1.83E+02 3.96E+02

-4.58E-01 4.20E-01 1.32E+00 4.54E-01 4.11E+00 9.15E+00 2.23E+00 3.57E+00 8.75E+00 1.10E+01 8.93E+00 1.96E+01 5.16E+02 ND ND ND ND MW-60-53 MW-60-53 Q1-2011 016 53.4

-40.9 2/11/2011 10:57 3.19E+02 3.70E+02 3.87E+02 7.44E-01 1.52E+00 1.70E+00

-2.03E+00 5.88E+00 6.16E+00 1.39E+00 7.96E+00 8.33E+00

-1.39E+00 1.50E+01 1.72E+01 5.16E+02 MW-60-53 MW-60-53 Q2-2011 017 53.4

-40.9 4/15/2011 11:37

-5.87E+01 3.96E+02 4.80E+02

-1.18E-02 1.60E+00 2.04E+00 2.17E+00 9.90E+00 1.14E+01

-1.11E+00 8.68E+00 8.95E+00

-1.06E+00 1.43E+01 1.66E+01 5.16E+02 MW-60-53 MW-60-53 Q3-2011 018 53.4

-40.9 8/10/2011 11:45 5.16E+02 2.70E+02 1.99E+02 1.18E+00 1.39E+00 1.45E+00 5.77E-01 1.34E+01 8.78E+00

-5.16E-01 1.07E+01 1.15E+01 NA NA NA 5.16E+02 MW-60-53 MW-60-72 Q4-2010 015 72.4

-59.9 11/16/2010 13:17

-2.51E+01 1.68E+02 3.98E+02 5.83E-02 5.15E-01 1.33E+00 2.12E+00 5.34E+00 1.26E+01

-3.92E+00 5.67E+00 1.09E+01

-1.14E+01 8.32E+00 1.89E+01 2.91E+02 ND ND ND ND MW-60-72 MW-60-72 Q1-2011 016 72.4

-59.9 2/10/2011 12:54 3.64E+02 3.76E+02 3.84E+02 2.41E-01 1.45E+00 1.70E+00

-5.10E-02 9.12E+00 1.01E+01 2.27E+00 8.84E+00 1.07E+01 2.12E+00 1.54E+01 1.75E+01 2.91E+02 MW-60-72 MW-60-72 Q2-2011 017 72.4

-59.9 4/15/2011 13:12 2.19E+02 3.78E+02 4.13E+02 7.12E-01 1.72E+00 1.97E+00

-5.14E+00 6.54E+00 5.80E+00

-3.30E+00 1.14E+01 1.14E+01

-2.93E+00 1.39E+01 1.63E+01 2.91E+02 MW-60-72 MW-60-72 Q3-2011 018 72.4

-59.9 8/10/2011 13:25 2.91E+02 2.23E+02 1.95E+02 1.22E-01 9.33E-01 1.14E+00

-4.08E+00 9.63E+00 1.00E+01 4.20E+00 8.40E+00 1.06E+01 NA NA NA 2.91E+02 MW-60-72 MW-60-135 Q4-2010 015 134.9

-122.4 11/16/2010 13:22 2.41E+02 1.82E+02 3.96E+02

-4.96E-02 7.62E-01 1.88E+00 9.16E-01 5.37E+00 1.20E+01 1.02E+00 4.53E+00 1.03E+01 8.67E-01 8.52E+00 1.90E+01 4.04E+02 ND ND ND ND MW-60-135 MW-60-135 Q1-2011 016 134.9

-122.4 2/10/2011 13:04 3.98E+02 3.78E+02 3.83E+02 1.14E+00 1.82E+00 1.98E+00 1.72E+00 6.72E+00 7.79E+00 2.24E-01 7.44E+00 8.25E+00

-3.56E+00 1.52E+01 1.76E+01 4.04E+02 MW-60-135 MW-60-135 Q2-2011 017 134.9

-122.4 4/15/2011 13:25 4.14E+02 4.02E+02 4.12E+02 6.52E-01 1.90E+00 2.16E+00

-6.83E+00 1.39E+01 1.63E+01

-2.48E+00 9.86E+00 1.01E+01 4.64E+00 1.47E+01 1.65E+01 4.04E+02 MW-60-135 MW-60-135 Q3-2011 018 134.9

-122.4 8/10/2011 13:51 4.00E+02 2.46E+02 1.96E+02

-2.08E-01 9.78E-01 1.25E+00

-7.37E+00 9.39E+00 8.24E+00

-6.27E+00 1.07E+01 9.07E+00 NA NA NA 4.04E+02 MW-60-135 MW-60-154 Q4-2010 015 154.4

-141.9 11/16/2010 13:40 4.68E+02 1.94E+02 3.98E+02 3.29E-01 8.30E-01 1.94E+00

-5.28E+00 4.02E+00 7.52E+00

-2.29E-01 5.09E+00 1.11E+01

-4.54E+00 7.93E+00 1.78E+01 5.34E+02 ND ND ND ND MW-60-154 MW-60-154 Q1-2011 016 154.4

-141.9 2/10/2011 12:53 5.44E+02 4.02E+02 3.87E+02 2.32E-02 8.50E-01 1.07E+00

-4.12E+00 9.26E+00 8.97E+00 9.91E-01 7.86E+00 9.12E+00 4.61E+00 1.52E+01 1.71E+01 5.34E+02 MW-60-154 MW-60-154 Q2-2011 017 154.4

-141.9 4/15/2011 13:19 3.06E+02 3.96E+02 4.21E+02

-4.20E-01 1.53E+00 2.02E+00

-2.09E+00 7.62E+00 7.82E+00

-7.25E-01 6.50E+00 6.79E+00 1.62E+00 1.44E+01 1.64E+01 5.34E+02 MW-60-154 MW-60-154 Q3-2011 018 154.4

-141.9 8/10/2011 13:22 5.89E+02 2.81E+02 1.97E+02

-5.08E-02 1.13E+00 1.40E+00

-1.03E+00 8.01E+00 8.47E+00 2.98E+00 9.03E+00 1.07E+01 NA NA NA 5.34E+02 MW-60-154 MW-60-176 Q4-2010 015 175.9

-163.4 11/16/2010 14:06 8.33E+02 2.10E+02 3.97E+02 9.07E-01 9.42E-01 2.10E+00

-1.97E+00 4.38E+00 9.04E+00 2.85E+00 4.70E+00 1.12E+01

-6.40E+00 7.91E+00 1.78E+01 9.56E+02 ND ND ND ND MW-60-176 MW-60-176 Q1-2011 016 175.9

-163.4 2/10/2011 10:31 1.12E+03 4.68E+02 3.85E+02 2.58E-01 1.49E+00 1.74E+00 4.88E+00 1.13E+01 6.69E+00

-1.75E+00 6.70E+00 6.74E+00 7.24E+00 1.62E+01 1.79E+01 9.56E+02 MW-60-176 MW-60-176 Q2-2011 017 175.9

-163.4 4/15/2011 13:49 8.99E+02 4.66E+02 4.18E+02

-8.29E-01 1.41E+00 2.10E+00

-7.83E-02 9.90E+00 1.10E+01

-2.35E+00 1.02E+01 1.03E+01

-2.40E-01 1.40E+01 1.62E+01 9.56E+02 MW-60-176 MW-60-176 Q3-2011 018 175.9

-163.4 8/10/2011 14:12 9.72E+02 3.42E+02 2.00E+02

-1.79E-01 9.21E-01 1.22E+00

-3.87E+00 7.74E+00 7.27E+00

-1.71E-01 8.91E+00 9.60E+00 NA NA NA 9.56E+02 MW-60-176 MW-62-18 Q4-2010 015 13.5 1.2 11/9/2010 11:57 7.48E+01 1.71E+02 3.86E+02

-1.05E-02 6.10E-01 1.54E+00 2.87E+00 4.59E+00 1.07E+01

-6.86E-01 4.79E+00 1.01E+01 NA NA NA 4.04E+02 1.26E+00 ND ND NA MW-62-18 MW-62-18 Q1-2011 016 13.5 1.2 2/24/2011 12:49 1.81E+02 3.60E+02 4.00E+02

-3.86E-01 1.71E+00 2.13E+00 2.12E-01 4.74E+00 5.18E+00 3.58E+00 5.46E+00 6.78E+00 NA NA NA 4.04E+02 1.26E+00 MW-62-18 MW-62-18 Q2-2011 017 13.5 1.2 4/13/2011 11:58 3.25E+02 4.56E+02 4.92E+02 7.82E-01 1.54E+00 1.71E+00

-4.38E+00 1.00E+01 1.09E+01

-4.07E-01 1.06E+01 1.16E+01 NA NA NA 4.04E+02 1.26E+00 MW-62-18 MW-62-18 Q2-2011 Mid 018 13.5 1.2 7/22/2011 11:35 2.00E+02 4.02E+02 4.45E+02 1.26E+00 1.24E+00 1.25E+00 4.94E+00 9.42E+00 1.14E+01

-1.79E+00 1.05E+01 1.08E+01

-3.83E+00 1.96E+01 2.20E+01 4.04E+02 1.26E+00 MW-62-18 MW-62-18 Q3-2011 019 13.5 1.2 8/3/2011 10:18 4.04E+02 3.39E+02 3.53E+02 2.03E-01 1.37E+00 1.74E+00

-1.12E+00 8.70E+00 9.13E+00 4.76E+00 9.81E+00 1.21E+01 NA NA NA 4.04E+02 1.26E+00 MW-62-18 MW-62-37 Q4-2010 015 34.5

-19.8 11/9/2010 11:56 6.09E+01 1.70E+02 3.85E+02 7.62E-01 6.69E-01 1.47E+00

-8.46E-02 4.49E+00 9.91E+00 3.83E+00 4.28E+00 1.07E+01 NA NA NA ND ND ND ND NA MW-62-37 MW-62-37 Q1-2011 016 34.5

-19.8 2/24/2011 12:52 3.05E+02 3.76E+02 4.00E+02 5.14E-01 1.84E+00 2.13E+00 1.07E+00 6.06E+00 6.86E+00

-2.84E+00 6.38E+00 6.28E+00 NA NA NA MW-62-37 MW-62-37 Q2-2011 017 34.5

-19.8 4/13/2011 12:10 1.56E+02 4.36E+02 4.91E+02

-1.97E-01 1.08E+00 1.37E+00

-4.48E+00 8.32E+00 7.76E+00

-1.68E+00 9.02E+00 9.05E+00 NA NA NA MW-62-37 MW-62-37 Q2-2011 Mid 018 34.5

-19.8 7/22/2011 12:28 1.15E+02 3.90E+02 4.42E+02 1.03E+00 1.60E+00 1.73E+00

-3.64E+00 7.95E+00 8.03E+00 2.96E+00 1.10E+01 1.30E+01

-8.92E+00 1.85E+01 2.09E+01 MW-62-37 MW-62-37 Q3-2011 019 34.5

-19.8 8/3/2011 10:35 3.09E+02 3.33E+02 3.52E+02 1.23E+00 1.81E+00 1.96E+00 3.02E+00 6.69E+00 8.03E+00 2.71E+00 8.55E+00 1.01E+01 NA NA NA MW-62-37 MW-62-53 Q4-2010 014 53.1

-40.3 11/9/2010 12:49 2.05E+02 1.77E+02 3.88E+02 8.32E-02 6.79E-01 1.59E+00

-4.23E+00 4.83E+00 9.52E+00

-2.68E+00 5.26E+00 1.04E+01 NA NA NA 4.12E+02 ND ND ND NA MW-62-53 MW-62-53 Q1-2011 015 53.1

-40.3 2/24/2011 12:57 3.08E+02 3.78E+02 4.03E+02 8.98E-01 1.94E+00 2.18E+00

-2.62E-01 4.72E+00 5.23E+00

-1.84E+00 5.58E+00 5.81E+00 NA NA NA 4.12E+02 MW-62-53 MW-62-53 Q2-2011 016 53.1

-40.3 4/13/2011 11:32 1.57E+02 4.36E+02 4.92E+02 1.72E+00 1.79E+00 1.84E+00 5.42E-01 6.78E+00 7.51E+00

-3.00E-01 6.24E+00 6.58E+00 NA NA NA 4.12E+02 MW-62-53 MW-62-53 Q2-2011 Mid 017 53.1

-40.3 7/22/2011 10:47 1.60E+02 3.96E+02 4.45E+02

-4.83E-01 1.07E+00 1.58E+00 4.34E+00 7.86E+00 9.52E+00 1.66E+00 8.85E+00 1.02E+01

-1.60E+01 1.79E+01 2.05E+01 4.12E+02 MW-62-53 MW-62-53 Q3-2011 018 53.1

-40.3 8/3/2011 12:44 4.12E+02 3.42E+02 3.00E+02 1.52E-01 1.46E+00 1.75E+00 2.87E+00 7.59E+00 9.04E+00 3.15E+00 8.76E+00 1.06E+01 NA NA NA 4.12E+02 MW-62-53 MW-62-71 Q4-2010 015 71.1

-58.3 11/9/2010 11:02 4.17E+02 1.83E+02 3.82E+02

-6.74E-02 6.02E-01 1.52E+00

-6.58E-01 3.90E+00 8.41E+00

-4.59E+00 5.63E+00 1.09E+01 NA NA NA 4.90E+02 ND ND ND NA MW-62-71 MW-62-71 Q1-2011 016 71.1

-58.3 2/24/2011 12:40 5.38E+02 4.06E+02 4.03E+02 1.28E-01 1.22E+00 1.48E+00 4.10E+00 1.18E+01 6.67E+00

-2.36E-01 5.00E+00 5.47E+00 NA NA NA 4.90E+02 MW-62-71 MW-62-71 Q2-2011 017 71.1

-58.3 4/13/2011 11:15 3.39E+02 4.72E+02 5.08E+02 9.04E-01 1.45E+00 1.58E+00 2.33E+00 7.96E+00 9.27E+00

-2.38E+00 8.50E+00 8.56E+00 NA NA NA 4.90E+02 MW-62-71 MW-62-71 Q2-2011 Mid 018 71.1

-58.3 7/22/2011 10:12 4.21E+02 4.26E+02 4.44E+02

-3.90E-01 1.36E+00 1.90E+00

-7.29E-02 7.74E+00 8.31E+00

-7.90E-01 8.28E+00 8.59E+00

-6.70E+00 1.89E+01 2.13E+01 4.90E+02 MW-62-71 MW-62-71 Q3-2011 019 71.1

-58.3 8/3/2011 11:58 5.14E+02 3.69E+02 3.07E+02 3.49E-01 1.39E+00 1.65E+00

-7.31E-01 1.01E+01 1.10E+01 2.51E+00 1.04E+01 1.20E+01 NA NA NA 4.90E+02 MW-62-71 MW-62-92 Q4-2010 015 91.6

-78.8 11/9/2010 11:15 4.82E+02 1.88E+02 3.86E+02

-9.75E-01 7.72E-01 1.95E+00

-2.96E+00 5.42E+00 1.17E+01 1.77E+00 4.84E+00 1.12E+01 NA NA NA 5.24E+02 ND ND ND NA MW-62-92 MW-62-92 Q1-2011 016 91.6

-78.8 2/24/2011 12:39 5.09E+02 4.00E+02 4.02E+02 9.56E-01 1.85E+00 2.06E+00 1.68E+00 5.38E+00 6.27E+00

-1.45E+00 5.68E+00 5.86E+00 NA NA NA 5.24E+02 MW-62-92 MW-62-92 Q2-2011 017 91.6

-78.8 4/13/2011 11:03 5.06E+02 4.78E+02 4.92E+02 2.87E-01 1.11E+00 1.30E+00

-2.87E+00 7.18E+00 7.31E+00

-2.10E+00 8.94E+00 8.88E+00 NA NA NA 5.24E+02 MW-62-92 MW-62-92 Q2-2011 Mid 018 91.6

-78.8 7/22/2011 10:18 5.61E+02 4.35E+02 4.39E+02

-1.12E+00 1.52E+00 2.06E+00 5.26E+00 9.42E+00 1.13E+01

-7.24E-02 9.48E+00 1.05E+01

-6.69E+00 1.76E+01 1.99E+01 5.24E+02 MW-62-92 MW-62-92 Q3-2011 019 91.6

-78.8 8/3/2011 12:10 5.61E+02 3.78E+02 3.03E+02

-3.26E-01 1.09E+00 1.52E+00 3.82E+00 1.46E+01 9.22E+00

-5.05E+00 1.17E+01 1.15E+01 NA NA NA 5.24E+02 MW-62-92 MW-62-138 Q4-2010 015 138.1

-125.3 11/9/2010 14:31 3.31E+02 2.07E+02 4.46E+02

-1.05E-01 6.18E-01 1.57E+00

-1.42E+00 4.04E+00 8.57E+00 2.51E+00 4.68E+00 1.11E+01 NA NA NA 7.59E+02 2.15E+00 ND ND NA MW-62-138 MW-62-138 Q1-2011 016 138.1

-125.3 2/24/2011 14:54 5.17E+02 4.00E+02 4.01E+02 2.15E+00 1.77E+00 1.75E+00

-1.67E+00 4.72E+00 4.94E+00 1.88E+00 7.04E+00 8.19E+00 NA NA NA 7.59E+02 2.15E+00 MW-62-138 MW-62-138 Q2-2011 017 138.1

-125.3 4/13/2011 14:39 6.31E+02 5.04E+02 5.09E+02 1.22E+00 1.29E+00 1.32E+00 1.29E+00 9.08E+00 1.04E+01 1.71E+00 8.82E+00 1.02E+01 NA NA NA 7.59E+02 2.15E+00 MW-62-138 MW-62-138 Q2-2011 Mid 018 138.1

-125.3 7/22/2011 11:50 4.66E+02 4.23E+02 4.36E+02 6.72E-01 1.20E+00 1.32E+00

-5.97E-01 7.41E+00 8.13E+00 6.36E+00 9.57E+00 1.23E+01

-1.13E+01 1.79E+01 2.03E+01 7.59E+02 2.15E+00 MW-62-138 MW-62-138 Q3-2011 019 138.1

-125.3 8/3/2011 10:08 1.42E+03 5.46E+02 3.34E+02 1.53E+00 1.69E+00 1.73E+00 2.51E-01 9.48E+00 1.05E+01 1.35E+00 8.40E+00 9.73E+00 NA NA NA 7.59E+02 2.15E+00 MW-62-138 MW-62-182 Q4-2010 015 182.1

-169.3 11/9/2010 14:43 4.76E+02 1.88E+02 3.87E+02 1.02E+00 6.77E-01 1.46E+00

-2.35E+00 4.16E+00 8.56E+00 1.99E+00 5.26E+00 1.21E+01 NA NA NA 5.30E+02 ND ND ND NA MW-62-182 MW-62-182 Q1-2011 016 182.1

-169.3 2/24/2011 15:07 3.55E+02 3.84E+02 4.03E+02

-1.46E-01 1.45E+00 1.94E+00

-1.95E+00 6.24E+00 6.60E+00 5.86E-01 6.60E+00 7.33E+00 NA NA NA 5.30E+02 MW-62-182 MW-62-182 Q2-2011 017 182.1

-169.3 4/13/2011 14:44 1.92E+02 4.50E+02 5.03E+02

-5.04E-01 1.05E+00 1.45E+00 5.54E+00 8.70E+00 1.09E+01

-9.44E-01 1.08E+01 1.15E+01 NA NA NA 5.30E+02 MW-62-182 MW-62-182 Q2-2011 Mid 018 182.1

-169.3 7/22/2011 12:02 2.90E+02 4.20E+02 4.54E+02 2.09E-01 1.22E+00 1.47E+00 6.48E-01 7.41E+00 8.36E+00

-5.94E-01 7.65E+00 8.31E+00

-2.27E+00 1.56E+01 1.75E+01 5.30E+02 MW-62-182 MW-62-182 Q3-2011 019 182.1

-169.3 8/3/2011 10:20 5.84E+02 3.84E+02 3.05E+02 2.04E-01 1.47E+00 1.75E+00

-5.99E+00 1.25E+01 1.14E+01

-2.96E-01 1.13E+01 1.24E+01 NA NA NA 5.30E+02 MW-62-182 MW-63-18 Q4-2010 015 14.9 0.7 11/2/2010 12:22 1.97E+02 1.18E+02 1.13E+02 1.31E-01 6.87E-01 8.18E-01 1.81E+00 5.46E+00 6.40E+00 3.45E+00 6.55E+00 8.07E+00 NA NA NA 3.44E+02 ND ND ND NA MW-63-18 MW-63-18 Q1-2011 016 14.9 0.7 3/2/2011 11:10 4.90E+02 3.58E+02 3.55E+02

-4.34E-01 1.50E+00 2.03E+00 1.82E+00 6.78E+00 7.90E+00 2.40E+00 7.38E+00 8.82E+00 NA NA NA 3.44E+02 MW-63-18 MW-63-18 Q2-2011 017 14.9 0.7 4/19/2011 10:35 7.23E+01 4.38E+02 5.05E+02

-3.13E-01 1.13E+00 1.49E+00 8.69E-01 8.04E+00 8.92E+00

-3.22E+00 8.16E+00 7.75E+00 NA NA NA 3.44E+02 MW-63-18 MW-63-18 Q2-2011 Mid 018 14.9 0.7 7/21/2011 10:26 2.96E+02 3.99E+02 4.29E+02 6.58E-02 1.19E+00 1.50E+00 2.40E+00 7.62E+00 9.09E+00 2.37E+00 7.53E+00 9.30E+00

-8.91E+00 1.69E+01 1.92E+01 3.44E+02 MW-63-18 MW-63-18 Q3-2011 019 14.9 0.7 8/3/2011 10:02 2.90E+02 3.15E+02 3.03E+02

-1.29E-01 1.20E+00 1.57E+00 1.70E+00 6.87E+00 7.90E+00 3.80E+00 8.58E+00 1.05E+01 NA NA NA 3.44E+02 MW-63-18 MW-63-34 Q4-2010 015 31.5

-17.3 11/2/2010 13:04 3.41E+02 1.35E+02 1.14E+02 3.11E-01 5.72E-01 6.45E-01 1.16E-01 5.66E+00 6.29E+00

-2.31E+00 6.33E+00 6.51E+00 NA NA NA 3.33E+02 ND ND ND NA MW-63-34 MW-63-34 Q1-2011 016 31.5

-17.3 3/2/2011 10:50 2.98E+02 2.86E+02 2.62E+02

-4.29E-01 1.57E+00 2.11E+00 7.43E-02 7.96E+00 8.82E+00

-2.10E+00 8.42E+00 8.59E+00 NA NA NA 3.33E+02 MW-63-34 MW-63-34 Q2-2011 017 31.5

-17.3 4/19/2011 10:25 3.94E+02 4.60E+02 4.87E+02

-1.13E+00 1.22E+00 1.83E+00 4.36E+00 8.34E+00 9.94E+00 3.72E+00 8.28E+00 1.02E+01 NA NA NA 3.33E+02 MW-63-34 MW-63-34 Q2-2011 Mid 018 31.5

-17.3 7/21/2011 10:08 3.04E+02 4.08E+02 4.39E+02 2.38E-01 1.17E+00 1.42E+00

-1.34E+00 9.03E+00 9.54E+00 1.66E-01 7.89E+00 8.63E+00

-1.26E+01 1.28E+01 1.47E+01 3.33E+02 MW-63-34 MW-63-34 Q3-2011 019 31.5

-17.3 8/3/2011 10:14 3.61E+02 3.30E+02 3.02E+02 1.90E-01 1.37E+00 1.66E+00 8.99E+00 9.09E+00 1.15E+01

-7.29E-01 8.16E+00 8.53E+00 NA NA NA 3.33E+02 MW-63-34 MW-63-50 Q4-2010 015 49.5

-37.2 11/2/2010 15:07 3.29E+02 1.31E+02 1.12E+02 2.27E-01 6.23E-01 7.23E-01

-2.98E-02 7.72E+00 8.42E+00 2.76E+00 8.00E+00 9.78E+00 NA NA NA 3.71E+02 ND ND ND NA MW-63-50 MW-63-50 Q1-2011 016 49.5

-37.2 3/2/2011 14:21 4.35E+02 3.40E+02 3.44E+02 1.73E-01 1.62E+00 2.03E+00 1.13E+00 6.50E+00 7.48E+00 3.64E+00 7.02E+00 8.70E+00 NA NA NA 3.71E+02 MW-63-50 MW-63-50 Q2-2011 017 49.5

-37.2 4/19/2011 11:25 1.68E+02 4.36E+02 4.89E+02 7.72E-01 1.39E+00 1.53E+00

-6.46E+00 9.76E+00 9.29E+00 3.72E+00 8.18E+00 1.03E+01 NA NA NA 3.71E+02 MW-63-50 MW-63-50 Q2-2011 Mid 018 49.5

-37.2 7/21/2011 11:25 2.09E+02 3.99E+02 4.41E+02

-6.50E-01 8.58E-01 1.39E+00 2.46E-01 7.56E+00 8.55E+00 2.77E+00 8.64E+00 1.05E+01

-2.89E+00 1.51E+01 1.69E+01 3.71E+02 MW-63-50 MW-63-50 Q3-2011 019 49.5

-37.2 8/3/2011 11:38 3.50E+02 3.33E+02 3.09E+02

-8.45E-01 1.10E+00 1.60E+00 8.12E+00 1.18E+01 1.44E+01 4.49E+00 8.52E+00 1.14E+01 NA NA NA 3.71E+02 MW-63-50 MW-63-93 Q4-2010 016 93

-80.7 11/2/2010 15:08 2.39E+02 1.21E+02 1.11E+02 3.29E-01 5.72E-01 6.42E-01

-4.18E-02 4.95E+00 5.64E+00 3.38E+00 5.80E+00 7.11E+00 NA NA NA 2.39E+02 ND ND ND NA MW-63-93 MW-63-93 Q1-2011 017 93

-80.7 3/2/2011 14:14 2.69E+02 3.00E+02 2.94E+02 3.30E-01 1.79E+00 2.17E+00

-1.51E+00 8.78E+00 9.05E+00 3.38E+00 7.56E+00 9.56E+00 NA NA NA 2.39E+02 MW-63-93 MW-63-93 Q2-2011 018 93

-80.7 4/19/2011 11:27 9.64E+01 4.42E+02 5.05E+02

-4.30E-02 1.14E+00 1.44E+00 3.31E+00 8.92E+00 1.03E+01

-4.35E-01 6.80E+00 7.25E+00 NA NA NA 2.39E+02 MW-63-93 MW-63-93 Q2-2011 Mid 019 93

-80.7 7/21/2011 11:32 4.17E+02 4.20E+02 4.40E+02

-4.28E-01 1.06E+00 1.48E+00

-3.58E+00 8.10E+00 7.77E+00

-6.11E+00 7.92E+00 5.51E+00 6.50E-01 1.71E+01 1.90E+01 2.39E+02 MW-63-93 MW-63-93 Q3-2011 020 93

-80.7 8/3/2011 11:50 1.84E+02 3.12E+02 3.38E+02 4.25E-02 1.31E+00 1.63E+00 1.61E+00 7.26E+00 7.83E+00

-2.65E+00 7.71E+00 8.38E+00 NA NA NA 2.39E+02 MW-63-93 MW-63-112 Q4-2010 015 111.5

-99.2 11/2/2010 15:05 3.01E+02 1.29E+02 1.13E+02 6.02E-02 5.25E-01 6.51E-01

-2.54E+00 6.29E+00 6.56E+00 1.96E+00 6.72E+00 7.95E+00 NA NA NA 5.31E+02 ND ND ND NA MW-63-112 MW-63-112 Q1-2011 016 111.5

-99.2 3/2/2011 14:15 3.38E+02 3.18E+02 2.96E+02 1.48E-01 1.60E+00 2.00E+00

-3.72E-01 6.70E+00 7.21E+00 1.19E+00 6.36E+00 7.21E+00 NA NA NA 5.31E+02 MW-63-112 MW-63-112 Q2-2011 017 111.5

-99.2 4/19/2011 11:25 4.22E+02 4.68E+02 4.92E+02

-7.96E-01 1.00E+00 1.47E+00 4.96E+00 1.05E+01 1.25E+01 1.64E+00 1.17E+01 1.36E+01 NA NA NA 5.31E+02 MW-63-112 MW-63-112 Q2-2011 Mid 018 111.5

-99.2 7/21/2011 11:46 6.01E+02 4.44E+02 4.44E+02 2.29E-01 1.13E+00 1.37E+00

-8.46E-01 1.06E+01 1.11E+01 6.03E+00 1.21E+01 1.54E+01

-1.22E+00 1.77E+01 1.98E+01 5.31E+02 MW-63-112 MW-63-112 Q3-2011 019 111.5

-99.2 8/3/2011 12:01 8.82E+02 4.59E+02 3.36E+02

-1.83E-01 1.31E+00 1.67E+00 2.07E+00 7.35E+00 8.45E+00

-2.13E+00 7.26E+00 7.10E+00 NA NA NA 5.31E+02 MW-63-112 MW-63-121 Q4-2010 015 121

-108.7 11/2/2010 11:46 5.20E+02 1.49E+02 1.10E+02 6.38E-01 7.57E-01 8.11E-01 1.17E+00 6.66E+00 7.68E+00

-4.06E+00 7.17E+00 6.83E+00 NA NA NA 9.70E+02 ND ND ND NA MW-63-121 MW-63-121 Q1-2011 016 121

-108.7 3/2/2011 11:10 5.03E+02 3.54E+02 2.94E+02

-6.82E-02 1.55E+00 2.03E+00

-6.26E-01 6.72E+00 7.20E+00 3.49E-01 6.00E+00 6.67E+00 NA NA NA 9.70E+02 MW-63-121 MW-63-121 Q2-2011 017 121

-108.7 4/19/2011 9:54 5.77E+02 4.84E+02 4.91E+02 4.12E-01 1.18E+00 1.37E+00

-1.03E+00 6.92E+00 7.17E+00

-1.09E+01 9.86E+00 5.99E+00 NA NA NA 9.70E+02 MW-63-121 MW-63-121 Q2-2011 Mid 018 121

-108.7 7/21/2011 9:58 1.33E+03 5.28E+02 4.45E+02

-3.05E-01 1.36E+00 1.74E+00 1.63E-03 7.44E+00 8.17E+00

-3.19E+00 1.05E+01 1.07E+01 1.12E+00 1.84E+01 2.05E+01 9.70E+02 MW-63-121 MW-63-121 Q3-2011 019 121

-108.7 8/3/2011 10:03 1.92E+03 6.09E+02 3.29E+02 9.09E-01 1.49E+00 1.62E+00

-6.79E+00 9.27E+00 9.08E+00 6.01E+00 8.16E+00 1.09E+01 NA NA NA 9.70E+02 MW-63-121

TABLE 3 THIRD QUARTER 2011 GROUNDWATER ANALYTICAL RESULTS AND AVERAGES INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q32011 FINAL Table 3 - Third Quarter 2011 Groundwater Analytical Results and Averages.xlsx; Q32011 Table 3 Page 5 of 6 See Page 6 for Notes TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Date Time Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Average Average Average Average Average ANALYSIS RESULTS5 YEARLY ROLLING AVERAGES4,6 Well ID1 TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

SAMPLE COLLECTION Well ID1 SAMPLING QUARTER2,8 SAMPLE ID SAMPLE ZONE CENTER Depth Ft Below Top of Casing3 SAMPLE ZONE CENTER Elevation Ft msl3 MW-63-163 Q4-2010 015 162.5

-150.2 11/2/2010 11:49 4.44E+02 1.41E+02 1.10E+02 7.71E-01 8.38E-01 8.77E-01

-3.99E+00 9.88E+00 1.10E+01 2.94E+00 6.12E+00 7.63E+00 NA NA NA 5.00E+02 ND ND ND NA MW-63-163 MW-63-163 Q1-2011 016 162.5

-150.2 3/2/2011 10:27 6.05E+02 3.76E+02 2.95E+02 1.37E+00 1.99E+00 2.12E+00 3.09E+00 5.40E+00 6.62E+00

-2.05E+00 7.72E+00 7.12E+00 NA NA NA 5.00E+02 MW-63-163 MW-63-163 Q2-2011 017 162.5

-150.2 4/19/2011 9:49 4.92E+02 4.84E+02 5.03E+02 1.11E+00 1.82E+00 2.00E+00 4.43E-01 8.94E+00 9.98E+00 4.78E+00 1.02E+01 1.26E+01 NA NA NA 5.00E+02 MW-63-163 MW-63-163 Q2-2011 Mid 018 162.5

-150.2 7/21/2011 10:09 5.08E+02 4.26E+02 4.36E+02

-6.14E-01 1.01E+00 1.48E+00

-8.47E-01 7.47E+00 8.17E+00 4.07E-01 7.53E+00 8.66E+00

-8.69E+00 1.47E+01 1.67E+01 5.00E+02 MW-63-163 MW-63-163 Q3-2011 019 162.5

-150.2 8/3/2011 10:06 4.41E+02 3.54E+02 3.08E+02 7.99E-02 1.35E+00 1.69E+00 5.51E-01 8.40E+00 9.33E+00 2.23E+00 1.03E+01 1.20E+01 NA NA NA 5.00E+02 MW-63-163 MW-63-174 Q4-2010 015 174

-161.7 11/2/2010 11:50 2.63E+02 1.26E+02 1.13E+02

-1.42E-01 4.59E-01 6.06E-01

-6.01E-01 6.03E+00 6.82E+00 2.17E-01 6.42E+00 7.11E+00 NA NA NA 4.28E+02 ND ND ND NA MW-63-174 MW-63-174 Q1-2011 016 174

-161.7 3/2/2011 10:26 4.13E+02 3.30E+02 2.91E+02 8.20E-01 1.80E+00 2.03E+00 3.65E+00 6.96E+00 8.18E+00 2.34E+00 7.86E+00 9.20E+00 NA NA NA 4.28E+02 MW-63-174 MW-63-174 Q2-2011 017 174

-161.7 4/19/2011 9:52 1.56E+02 4.48E+02 5.04E+02

-7.87E-01 9.72E-01 1.48E+00

-6.41E+00 8.32E+00 7.72E+00

-9.85E-01 8.58E+00 9.20E+00 NA NA NA 4.28E+02 MW-63-174 MW-63-174 Q2-2011 Mid 018 174

-161.7 7/21/2011 9:57 4.14E+02 4.17E+02 4.36E+02 6.96E-01 1.85E+00 2.10E+00

-3.57E+00 8.10E+00 8.27E+00 4.67E-01 9.36E+00 1.09E+01

-2.55E+00 1.33E+01 1.49E+01 4.28E+02 MW-63-174 MW-63-174 Q3-2011 019 174

-161.7 8/3/2011 10:18 6.09E+02 3.93E+02 3.09E+02 6.96E-01 1.49E+00 1.68E+00

-4.15E+00 9.15E+00 8.88E+00 4.51E+00 8.19E+00 1.05E+01 NA NA NA 4.28E+02 MW-63-174 MW-65-48 Q2-2011 Mid 002 43.3 26.356 7/7/2011 12:19 8.59E+01 2.43E+02 2.85E+02 5.73E-01 1.04E+00 1.15E+00 4.10E+00 9.03E+00 1.09E+01

-1.15E+00 1.12E+01 1.18E+01

-5.93E+00 2.39E+01 2.69E+01 ND ND ND ND ND MW-65-48 MW-65-80 Q2-2011 Mid 003 71.4

-1.659 7/13/2011 10:12 8.54E+01 2.41E+02 2.84E+02 1.26E-01 9.24E-01 1.12E+00

-2.33E+00 9.12E+00 9.46E+00 2.88E+00 1.15E+01 1.34E+01

-1.27E+01 2.00E+01 2.29E+01 ND ND ND ND ND MW-65-80 MW-66-21 Q4-2010 015 14.1 0

11/10/2010 15:13 3.22E+02 1.64E+02 3.46E+02 2.57E-01 7.74E-01 1.84E+00 6.04E+00 5.26E+00 1.28E+01

-1.91E-01 5.67E+00 1.26E+01 9.56E+00 8.45E+00 1.85E+01 6.31E+02 ND ND ND ND MW-66-21 MW-66-21 Q1-2011 016 14.1 0

1/31/2011 16:26 4.77E+02 4.08E+02 4.24E+02 3.48E-01 1.73E+00 2.02E+00

-2.19E-01 5.00E+00 5.33E+00 9.80E-01 6.50E+00 7.23E+00

-1.06E+00 1.84E+01 2.14E+01 6.31E+02 MW-66-21 MW-66-21 Q2-2011 017 14.1 0

4/14/2011 13:43 9.30E+01 3.88E+02 4.46E+02 6.73E-01 1.64E+00 1.85E+00

-4.70E+00 8.74E+00 8.45E+00 6.94E+00 9.82E+00 1.25E+01 1.81E+00 1.51E+01 1.72E+01 6.31E+02 MW-66-21 MW-66-21 Q3-2011 018 14.1 0

8/8/2011 10:55 7.84E+02 3.90E+02 3.73E+02 8.00E-01 1.44E+00 1.59E+00

-2.25E+00 8.16E+00 8.11E+00 3.27E-01 7.05E+00 7.73E+00 6.75E+00 9.00E+00 9.81E+00 6.31E+02 MW-66-21 MW-66-36 Q4-2010 014 33.6

-19.5 11/10/2010 12:33 3.13E+03 2.96E+02 3.96E+02 7.43E+00 1.03E+00 1.13E+00 5.42E+00 3.87E+00 9.67E+00 7.18E-01 4.34E+00 9.81E+00

-4.23E+00 9.63E+00 2.16E+01 3.39E+03 1.04E+01 ND ND ND MW-66-36 MW-66-36 Q1-2011 015 33.6

-19.5 1/31/2011 15:51 3.01E+03 6.78E+02 4.61E+02 1.55E+01 3.18E+00 2.11E+00

-1.13E+00 6.12E+00 6.49E+00

-8.31E-01 6.80E+00 7.15E+00

-4.89E+00 1.79E+01 2.12E+01 3.39E+03 1.04E+01 MW-66-36 MW-66-36 Q2-2011 016 33.6

-19.5 4/14/2011 12:53 3.52E+03 7.36E+02 4.79E+02 1.06E+01 2.88E+00 1.95E+00 1.50E-01 7.24E+00 8.14E+00 5.40E-01 7.92E+00 9.01E+00 6.10E-01 1.55E+01 1.79E+01 3.39E+03 1.04E+01 MW-66-36 MW-66-36 Q3-2011 017 33.6

-19.5 8/8/2011 10:49 3.90E+03 5.91E+02 3.74E+02 8.00E+00 2.60E+00 1.61E+00

-3.94E+00 1.11E+01 1.07E+01 1.48E+00 1.26E+01 1.46E+01 2.82E+00 1.53E+01 1.71E+01 3.39E+03 1.04E+01 MW-66-36 MW-67-39 Q4-2010 015 38.3

-25.8 11/10/2010 11:49 3.56E+03 3.09E+02 3.95E+02 5.43E+00 8.85E-01 1.10E+00 1.04E+00 3.96E+00 8.88E+00 2.82E+00 4.30E+00 1.04E+01

-1.86E+00 9.87E+00 2.21E+01 3.69E+03 9.74E+00 ND ND ND MW-67-39 MW-67-39 Q1-2011 016 38.3

-25.8 2/7/2011 13:48 3.85E+03 7.60E+02 4.81E+02 1.57E+01 3.34E+00 1.83E+00 8.03E-02 6.18E+00 6.83E+00 6.64E-01 6.78E+00 7.57E+00 4.43E+00 1.97E+01 2.23E+01 3.69E+03 9.74E+00 MW-67-39 MW-67-39 Q2-2011 017 38.3

-25.8 4/14/2011 13:25 3.73E+03 7.14E+02 4.17E+02 1.25E+01 3.76E+00 2.10E+00 4.53E+00 8.78E+00 1.04E+01 3.71E+00 9.54E+00 1.14E+01 6.99E+00 1.47E+01 1.63E+01 3.69E+03 9.74E+00 MW-67-39 MW-67-39 Q3-2011 018 38.3

-25.8 8/8/2011 12:26 3.62E+03 5.76E+02 3.73E+02 5.31E+00 2.39E+00 1.98E+00

-3.01E+00 8.34E+00 8.17E+00

-7.13E+00 8.22E+00 7.50E+00 5.90E+00 1.71E+01 1.90E+01 3.69E+03 9.74E+00 MW-67-39 MW-67-105 Q4-2010 014 104.8

-92.3 11/10/2010 11:42 1.14E+03 2.24E+02 3.95E+02 1.41E+00 8.12E-01 1.69E+00

-1.68E+00 3.59E+00 7.64E+00

-3.12E+00 4.14E+00 8.26E+00 1.24E+00 8.56E+00 1.90E+01 1.16E+03 ND ND ND ND MW-67-105 MW-67-105 Q1-2011 015 104.8

-92.3 2/7/2011 13:57 9.94E+02 4.26E+02 3.86E+02 3.37E-01 1.64E+00 1.94E+00 2.40E+00 4.84E+00 5.67E+00

-1.22E+00 4.86E+00 4.81E+00

-4.59E+00 1.96E+01 2.31E+01 1.16E+03 MW-67-105 MW-67-105 Q2-2011 016 104.8

-92.3 4/14/2011 13:43 1.10E+03 4.84E+02 4.12E+02 2.70E-01 1.72E+00 2.11E+00

-3.96E-01 9.66E+00 1.05E+01

-1.91E-01 7.24E+00 7.88E+00 5.71E+00 1.55E+01 1.73E+01 1.16E+03 MW-67-105 MW-67-105 Q3-2011 017 104.8

-92.3 8/8/2011 12:48 1.42E+03 4.38E+02 3.74E+02 7.40E-01 1.71E+00 1.92E+00

-4.93E-01 7.77E+00 8.36E+00

-6.18E+00 8.67E+00 7.26E+00 6.67E+00 1.25E+01 1.38E+01 1.16E+03 MW-67-105 MW-67-173 Q4-2010 015 172.3

-159.8 11/10/2010 12:04 6.25E+02 2.01E+02 3.97E+02

-9.99E-01 6.33E-01 1.86E+00 4.02E-01 7.80E+00 1.12E+01

-1.17E+00 4.83E+00 1.03E+01

-1.65E+00 8.09E+00 1.81E+01 6.03E+02 ND ND ND ND MW-67-173 MW-67-173 Q1-2011 016 172.3

-159.8 2/7/2011 14:13 4.47E+02 4.48E+02 4.65E+02

-2.38E-01 1.68E+00 2.12E+00

-4.75E-01 5.28E+00 5.83E+00 7.55E-01 6.38E+00 5.76E+00

-7.05E-01 1.88E+01 2.18E+01 6.03E+02 MW-67-173 MW-67-173 Q2-2011 017 172.3

-159.8 4/14/2011 14:09 5.72E+02 4.20E+02 4.10E+02

-2.56E-01 1.69E+00 1.99E+00 5.04E+00 9.64E+00 1.17E+01

-9.27E+00 1.03E+01 6.85E+00 7.50E+00 1.23E+01 1.34E+01 6.03E+02 MW-67-173 MW-67-173 Q3-2011 018 172.3

-159.8 8/8/2011 12:53 6.13E+02 3.75E+02 3.72E+02

-3.44E-01 1.55E+00 1.94E+00

-1.95E+00 8.79E+00 9.16E+00 1.25E+00 8.70E+00 9.80E+00 4.91E+00 1.20E+01 1.33E+01 6.03E+02 MW-67-173 MW-67-219 Q4-2010 014 218.8

-206.3 11/10/2010 13:40 1.15E+03 2.24E+02 3.96E+02 3.53E-01 7.28E-01 1.78E+00

-2.80E-01 3.60E+00 7.62E+00 2.49E-01 3.62E+00 7.89E+00

-4.41E+00 8.84E+00 1.98E+01 9.93E+02 ND ND ND ND MW-67-219 MW-67-219 Q1-2011 015 218.8

-206.3 1/31/2011 14:48 6.41E+02 4.18E+02 4.20E+02

-1.08E+00 1.42E+00 1.97E+00 9.72E-01 5.80E+00 6.44E+00 2.44E+00 5.46E+00 6.55E+00

-4.58E+00 1.81E+01 2.14E+01 9.93E+02 MW-67-219 MW-67-219 Q2-2011 016 218.8

-206.3 4/14/2011 10:49 1.07E+03 4.78E+02 4.12E+02

-7.57E-01 9.50E-01 1.53E+00

-2.70E+00 6.62E+00 6.47E+00 4.16E+00 9.78E+00 1.20E+01 2.95E+00 1.43E+01 1.62E+01 9.93E+02 MW-67-219 MW-67-219 Q3-2011 017 218.8

-206.3 8/8/2011 10:33 1.11E+03 4.17E+02 3.73E+02 3.18E-02 1.61E+00 1.90E+00 8.34E-01 7.41E+00 8.13E+00

-6.37E+00 9.30E+00 8.11E+00 1.06E+01 1.64E+01 1.79E+01 9.93E+02 MW-67-219 MW-67-276 Q4-2010 014 275.3

-262.8 11/10/2010 14:16 1.01E+03 2.18E+02 3.96E+02

-7.85E-01 5.64E-01 1.77E+00 1.94E+00 4.26E+00 9.92E+00

-5.48E+00 4.42E+00 7.40E+00 5.46E+00 8.55E+00 1.89E+01 9.61E+02 ND ND ND ND MW-67-276 MW-67-276 Q1-2011 015 275.3

-262.8 1/31/2011 14:31 8.75E+02 4.18E+02 3.87E+02

-2.57E-02 1.66E+00 2.03E+00

-2.56E+00 8.76E+00 8.16E+00 6.49E-01 6.48E+00 7.20E+00

-7.18E-01 1.92E+01 2.22E+01 9.61E+02 MW-67-276 MW-67-276 Q2-2011 016 275.3

-262.8 4/14/2011 10:53 1.06E+03 4.84E+02 4.19E+02 3.46E-01 1.22E+00 1.45E+00

-5.30E+00 6.78E+00 6.12E+00 1.62E+00 1.02E+01 1.15E+01 5.62E-01 1.42E+01 1.63E+01 9.61E+02 MW-67-276 MW-67-276 Q3-2011 017 275.3

-262.8 8/8/2011 10:45 8.99E+02 3.90E+02 3.63E+02

-3.98E-01 1.38E+00 1.82E+00

-3.35E-01 8.67E+00 9.58E+00 1.65E+00 9.24E+00 1.07E+01 1.22E+01 1.91E+01 2.10E+01 9.61E+02 MW-67-276 MW-67-323 Q4-2010 014 322.3

-309.8 11/10/2010 14:03 3.88E+02 1.89E+02 3.94E+02 1.89E-01 8.21E-01 2.01E+00 2.70E+00 4.61E+00 1.06E+01 3.11E-01 5.07E+00 1.12E+01

-3.22E+00 7.93E+00 1.78E+01 4.26E+02 ND ND ND ND MW-67-323 MW-67-323 Q1-2011 015 322.3

-309.8 1/31/2011 15:04 3.38E+02 3.70E+02 3.90E+02 2.58E-01 1.71E+00 2.03E+00 2.47E-01 5.70E+00 6.35E+00 8.12E-03 5.80E+00 6.35E+00

-5.93E+00 1.90E+01 2.25E+01 4.26E+02 MW-67-323 MW-67-323 Q2-2011 016 322.3

-309.8 4/14/2011 11:33 4.26E+02 4.06E+02 4.13E+02 1.05E+00 1.52E+00 1.62E+00 2.02E+00 8.36E+00 9.62E+00

-1.12E+00 7.80E+00 8.21E+00

-2.21E-01 1.30E+01 1.50E+01 4.26E+02 MW-67-323 MW-67-323 Q3-2011 017 322.3

-309.8 8/8/2011 10:53 3.09E+02 3.51E+02 3.73E+02 1.75E+00 1.85E+00 1.91E+00

-6.64E-01 6.66E+00 7.23E+00 4.13E+00 8.82E+00 1.09E+01

-9.62E+00 2.15E+01 2.43E+01 4.26E+02 MW-67-323 MW-67-340 Q4-2010 014 339.8

-327.3 11/10/2010 13:53 5.31E+02 1.97E+02 3.95E+02

-8.93E-01 5.00E-01 1.64E+00 1.72E+00 4.50E+00 1.03E+01

-2.97E+00 3.90E+00 7.25E+00 2.25E+00 8.84E+00 1.97E+01 5.35E+02 ND ND ND ND MW-67-340 MW-67-340 Q1-2011 015 339.8

-327.3 1/31/2011 14:53 2.75E+02 3.58E+02 3.83E+02

-7.06E-01 1.51E+00 1.99E+00 4.30E-01 6.34E+00 7.02E+00

-1.15E+00 6.54E+00 6.88E+00

-5.79E+00 1.85E+01 2.20E+01 5.35E+02 MW-67-340 MW-67-340 Q2-2011 016 339.8

-327.3 4/14/2011 11:17 6.56E+02 4.32E+02 4.13E+02 2.62E-01 1.16E+00 1.40E+00 5.89E+00 9.02E+00 1.12E+01 4.57E+00 9.02E+00 1.15E+01 7.58E+00 1.54E+01 1.71E+01 5.35E+02 MW-67-340 MW-67-340 Q3-2011 017 339.8

-327.3 8/8/2011 10:43 4.19E+02 3.60E+02 3.72E+02

-5.52E-01 1.49E+00 1.89E+00

-9.17E-01 7.92E+00 8.61E+00

-4.93E+00 1.06E+01 1.00E+01 6.17E+00 1.84E+01 2.05E+01 5.35E+02 MW-67-340 MW-107 Q2-2011 010 32.7 110.1 5/2/2011 9:25 3.15E+02 3.76E+02 3.95E+02 8.29E-01 1.29E+00 1.40E+00

-3.56E+00 1.30E+01 1.65E+01 2.39E+00 6.84E+00 8.63E+00 NA NA NA ND ND ND ND NA MW-107 MW-108 Q2-2011 Mid 005 8.3 6.2 7/5/2011 15:08 1.24E+03 4.89E+02 2.90E+02

-9.21E-02 1.29E+00 1.55E+00 4.93E+00 9.84E+00 1.17E+01

-7.54E+00 8.49E+00 7.19E+00

-8.75E+00 2.32E+01 2.62E+01 1.51E+03 ND ND ND ND MW-108 MW-108 Q3-2011 Mid 006 8.3 6.2 8/29/2011 11:25 1.78E+03 5.73E+02 2.62E+02

-7.81E-01 7.89E-01 1.24E+00

-1.86E-01 1.19E+01 1.21E+01

-4.10E+00 1.13E+01 1.10E+01 2.65E+00 1.16E+01 1.30E+01 1.51E+03 MW-108 MW-109 Q2-2011 Mid 005 8.5 6.1 7/5/2011 12:45 2.43E+03 6.36E+02 2.79E+02 2.60E-01 1.25E+00 1.45E+00 2.23E-01 8.67E+00 9.62E+00

-3.32E+00 7.74E+00 6.65E+00 3.57E+00 3.51E+01 3.92E+01 2.85E+03 ND ND ND ND MW-109 MW-109 Q3-2011 Mid 006 8.5 6.1 8/26/2011 13:49 3.26E+03 7.50E+02 2.59E+02 5.48E-01 1.01E+00 1.12E+00 2.37E+00 7.65E+00 8.94E+00 3.72E+00 9.60E+00 1.17E+01

-8.72E-01 8.73E+00 1.00E+01 2.85E+03 MW-109 MW-111 Q4-2010 035 16.5 2.4 11/1/2010 14:55 4.59E+04 1.34E+03 1.27E+02 3.47E-01 5.90E-01 6.60E-01

-1.99E-01 5.63E+00 6.38E+00 5.49E+00 5.91E+00 7.75E+00 NA NA NA 4.59E+04 ND ND ND NA MW-111 U3-3 Q2-2011 Mid 014 7/13/2011 12:28 6.73E+02 3.81E+02 2.81E+02

-3.49E-01 8.13E-01 1.19E+00

-4.64E-01 8.01E+00 8.64E+00

-3.52E+00 8.61E+00 8.20E+00 NA NA NA 8.52E+02 ND ND ND NA U3-3 U3-3 Q3-2011 Mid 015 8/29/2011 13:09 1.03E+03 4.56E+02 2.66E+02

-5.04E-01 6.63E-01 1.06E+00

-2.50E+00 8.55E+00 7.82E+00

-3.69E+00 7.74E+00 7.12E+00 NA NA NA 8.52E+02 U3-3 U3-4D Q4-2010 026 25.6

-10.8 10/28/2010 14:04 7.12E+02 1.68E+02 1.13E+02 2.26E-01 4.89E-01 5.61E-01 2.75E+00 5.75E+00 6.97E+00 1.33E+00 7.82E+00 9.00E+00 NA NA NA 6.89E+02 ND ND ND NA U3-4D U3-4D Q1-2011 027 25.6

-10.8 2/17/2011 14:41 6.28E+02 4.14E+02 4.05E+02

-8.34E-02 1.55E+00 1.95E+00 1.24E+00 4.72E+00 5.29E+00 8.61E-01 4.84E+00 5.47E+00 NA NA NA 6.89E+02 U3-4D U3-4D Q2-2011 028 25.6

-10.8 4/25/2011 14:50 7.41E+02 4.36E+02 3.98E+02 1.18E+00 1.38E+00 1.46E+00

-3.17E+00 7.58E+00 7.50E+00 4.81E-01 7.14E+00 8.11E+00 NA NA NA 6.89E+02 U3-4D U3-4D Q2-2011 Mid 029 25.6

-10.8 7/14/2011 11:55 3.88E+02 4.20E+02 4.38E+02 1.24E-01 1.06E+00 1.26E+00 4.78E+00 1.13E+01 1.32E+01 3.12E+00 1.22E+01 1.46E+01 NA NA NA 6.89E+02 U3-4D U3-4D Q3-2011 030 25.6

-10.8 7/29/2011 11:05 6.73E+02 4.02E+02 3.04E+02 1.23E-01 1.58E+00 1.90E+00 5.66E+00 8.43E+00 1.05E+01

-2.58E+00 9.30E+00 9.06E+00 NA NA NA 6.89E+02 U3-4D U3-4S Q4-2010 002 10/29/2010 11:40 3.51E+02 1.32E+02 1.10E+02 3.86E-01 5.82E-01 6.43E-01 1.64E+00 5.59E+00 6.52E+00

-2.02E+00 5.91E+00 6.14E+00 NA NA NA 4.09E+02 ND ND ND NA U3-4S U3-4S Q2-2011 003 4/25/2011 14:13 1.48E+02 3.78E+02 4.22E+02 6.69E-01 1.27E+00 1.41E+00 5.35E+00 8.82E+00 1.07E+01 1.75E+00 8.92E+00 1.03E+01 NA NA NA 4.09E+02 U3-4S U3-4S Q2-2011 Mid 004 7/14/2011 11:27 3.29E+02 4.11E+02 4.36E+02 1.06E+00 1.33E+00 1.40E+00

-2.41E+00 7.59E+00 7.88E+00 3.25E+00 7.65E+00 9.52E+00 NA NA NA 4.09E+02 U3-4S U3-4S Q3-2011 005 7/29/2011 10:06 4.67E+02 3.84E+02 3.43E+02 2.84E-01 1.64E+00 1.90E+00 9.19E+00 1.58E+01 9.23E+00 7.83E-01 1.02E+01 1.17E+01 NA NA NA 4.09E+02 U3-4S U3-T1 Q4-2010 030 5.7 2.8 10/29/2010 16:04 3.04E+02 1.28E+02 1.10E+02 4.84E-02 6.36E-01 7.68E-01

-8.56E-01 6.04E+00 6.70E+00 1.59E+00 5.73E+00 6.79E+00 NA NA NA 6.85E+02 ND ND ND NA U3-T1 U3-T1 Q1-2011 031 5.7 2.8 2/22/2011 11:11 6.55E+02 4.08E+02 3.92E+02 1.62E+00 1.96E+00 2.02E+00 1.80E+00 1.05E+01 6.14E+00 2.12E+00 6.42E+00 7.54E+00 NA NA NA 6.85E+02 U3-T1 U3-T1 Q2-2011 032 5.7 2.8 5/6/2011 10:23 7.82E+02 5.16E+02 5.03E+02

-6.43E-02 9.94E-01 1.30E+00

-3.24E+00 9.12E+00 9.22E+00 8.49E-01 1.09E+01 1.21E+01 NA NA NA 6.85E+02 U3-T1 U3-T1 Q3-2011 033 5.7 2.8 8/22/2011 14:40 1.00E+03 3.42E+02 1.95E+02

-6.26E-02 1.10E+00 1.37E+00

-4.61E-01 8.70E+00 8.45E+00

-2.62E+00 8.31E+00 8.23E+00 NA NA NA 6.85E+02 U3-T1 U3-T2 Q4-2010 035 5.7 2.6 10/29/2010 11:22 1.47E+03 2.19E+02 1.11E+02 4.22E-01 6.79E-01 7.56E-01

-6.11E-02 5.42E+00 6.11E+00 3.00E+00 5.47E+00 6.89E+00 NA NA NA 2.58E+03 ND ND ND NA U3-T2 U3-T2 Q1-2011 036 5.7 2.6 2/22/2011 14:30 2.27E+03 4.92E+02 3.62E+02 1.82E+00 2.04E+00 2.05E+00 3.65E+00 6.08E+00 7.29E+00 5.97E-01 7.12E+00 7.85E+00 NA NA NA 2.58E+03 U3-T2 U3-T2 Q2-2011 037 5.7 2.6 5/6/2011 11:41 3.83E+03 6.42E+02 4.19E+02 3.27E-01 1.32E+00 1.58E+00 2.82E+00 7.26E+00 8.74E+00 5.77E-01 9.68E+00 1.08E+01 NA NA NA 2.58E+03 U3-T2 U3-T2 Q2-2011 Mid 038 5.7 2.6 7/8/2011 10:55 2.67E+03 6.63E+02 2.80E+02 4.75E-01 1.31E+00 1.50E+00 3.77E+00 1.08E+01 1.19E+01

-1.06E+00 1.02E+01 1.07E+01 NA NA NA 2.58E+03 U3-T2 U3-T2 Q3-2011 039 5.7 2.6 7/29/2011 12:32 2.65E+03 7.02E+02 3.34E+02 1.05E+00 1.81E+00 1.99E+00

-5.43E-01 8.49E+00 9.21E+00 2.63E+00 8.91E+00 1.07E+01 NA NA NA 2.58E+03 U3-T2 U1-CSS Q4-2010 015 14 6.1 11/8/2010 14:56 2.26E+03 2.72E+02 1.26E+02 1.18E+01 1.45E+00 6.84E-01 2.29E+00 5.01E+00 5.93E+00 2.07E+00 5.61E+00 6.70E+00 3.16E-01 1.81E+01 2.13E+01 6.48E+03 1.06E+01 ND ND ND U1-CSS U1-CSS Q2-2011 016 14 6.1 5/4/2011 13:24 6.38E+03 6.84E+02 3.40E+02 1.61E+01 2.70E+00 1.01E+00 3.29E+00 8.36E+00 9.79E+00 7.12E+00 9.42E+00 1.24E+01

-1.05E+01 1.55E+01 1.84E+01 6.48E+03 1.06E+01 U1-CSS U1-CSS Q2-2011 Mid 017 14 6.1 7/8/2011 13:33 1.08E+04 1.28E+03 2.79E+02 3.90E+00 1.82E+00 1.30E+00 3.84E-02 9.18E+00 1.01E+01

-3.60E+00 9.96E+00 1.06E+01

-3.20E+00 2.09E+01 2.34E+01 6.48E+03 1.06E+01 U1-CSS U1-NCD Q4-2010 009 10/20/2010 13:40 3.34E+03 3.23E+02 1.27E+02 3.88E+01 2.31E+00 6.39E-01 1.20E+04 1.47E+03 9.98E+00

-1.14E+00 4.96E+00 5.42E+00 2.31E+02 3.19E+01 2.23E+01 3.60E+03 6.48E+01 8.39E+03 ND 1.73E+02 U1-NCD U1-NCD Q3-2011 011 9/15/2011 11:45 3.86E+03 6.39E+02 3.99E+02 9.08E+01 7.80E+00 1.54E+00 4.77E+03 6.42E+02 8.81E+00 3.36E+00 4.68E+00 5.97E+00 1.14E+02 2.09E+01 1.82E+01 3.60E+03 6.48E+01 8.39E+03 1.73E+02 U1-NCD U1-SFDS Q4-2010 010 10/20/2010 8:45 4.82E+02 1.56E+02 1.26E+02 1.17E+01 1.83E+00 8.74E-01 7.99E+00 7.54E+00 5.78E+00

-8.31E-01 5.24E+00 5.67E+00 9.71E-01 1.86E+01 2.18E+01 1.29E+03 9.75E+00 8.61E+00 ND ND U1-SFDS U1-SFDS Q3-2011 013 9/15/2011 11:35 2.09E+03 5.25E+02 4.00E+02 7.79E+00 2.54E+00 1.39E+00 9.23E+00 6.72E+00 6.70E+00 1.14E+00 6.27E+00 7.16E+00

-4.97E+00 1.70E+01 1.95E+01 1.29E+03 9.75E+00 8.61E+00 U1-SFDS I-2 Q4-2010 002 11/17/2010 14:25 1.74E+02 1.71E+02 3.78E+02 2.25E-01 6.25E-01 1.50E+00

-4.50E-01 5.04E+00 1.10E+01 3.35E+00 5.94E+00 1.40E+01 NA NA NA 2.34E+02 ND ND ND NA I-2 I-2 Q3-2011 003 8/12/2011 15:13 2.34E+02 2.15E+02 2.00E+02

-5.95E-01 7.44E-01 1.16E+00 5.11E+00 1.19E+01 1.35E+01

-2.57E-01 9.24E+00 1.02E+01 NA NA NA 2.34E+02 I-2 MH-5 VCFD7 Q4-2010 013 11/24/2010 11:10 4.60E+02 1.86E+02 1.47E+02 1.36E-01 7.57E-01 8.85E-01 1.75E+00 3.45E+00 4.02E+00 5.48E-01 3.79E+00 4.28E+00 NA NA NA 1.13E+04 ND ND ND NA MH-5 VCFD7 MH-5 VCFD7 Q1-2011 014 2/28/2011 9:47 5.17E+03 6.58E+02 3.66E+02 1.90E+00 1.99E+00 1.94E+00 3.45E-01 5.64E+00 6.19E+00

-1.28E+00 6.18E+00 6.45E+00 NA NA NA 1.13E+04 MH-5 VCFD7 MH-5 VCFD7 Q2-2011 015 4/22/2011 13:37 1.25E+04 1.10E+03 4.46E+02 8.17E-01 1.85E+00 2.08E+00

-3.21E+00 8.36E+00 8.43E+00

-1.60E+00 9.06E+00 9.51E+00 NA NA NA 1.13E+04 MH-5 VCFD7 MH-5 VCFD7 Q2-2011 Mid 018 7/7/2011 14:29 2.97E+03 7.02E+02 2.83E+02

-3.05E-01 8.04E-01 1.11E+00 9.24E-01 7.95E+00 8.84E+00 5.11E-01 8.49E+00 9.13E+00 NA NA NA 1.13E+04 MH-5 VCFD7 MH-5 VCFD7 Q2-2011 Mid 019 7/12/2011 12:46 9.86E+03 1.23E+03 2.81E+02 9.15E-01 1.05E+00 1.06E+00

-1.17E+01 1.33E+01 1.52E+01

-1.19E+00 9.99E+00 1.06E+01 NA NA NA 1.13E+04 MH-5 VCFD7 MH-5 VCFD7 Q2-2011 Mid 020 7/20/2011 10:48 2.89E+03 7.32E+02 3.35E+02

-4.57E-01 1.01E+00 1.47E+00 1.79E+00 6.30E+00 7.26E+00

-2.61E+00 8.34E+00 8.34E+00 NA NA NA 1.13E+04 MH-5 VCFD7 MH-5 VCFD7 Q2-2011 Mid 021 7/26/2011 12:50 1.86E+03 6.03E+02 3.33E+02

-7.10E-01 9.45E-01 1.45E+00 2.81E+00 7.47E+00 8.99E+00

-8.33E-01 9.66E+00 1.03E+01 NA NA NA 1.13E+04 MH-5 VCFD7 MH-5 VCFD7 Q3-2011 022 8/3/2011 14:12 3.90E+03 8.31E+02 3.31E+02

-4.45E-01 1.07E+00 1.50E+00

-6.18E-01 1.01E+01 1.10E+01

-6.71E+00 1.43E+01 1.29E+01 NA NA NA 1.13E+04 MH-5 VCFD7 MH-5 VCFD7 Q3-2011 023 8/11/2011 12:39 2.74E+04 1.65E+03 2.02E+02 6.43E-01 1.19E+00 1.32E+00

-2.20E+00 7.47E+00 7.63E+00 1.85E+00 5.85E+00 7.32E+00 NA NA NA 1.13E+04 MH-5 VCFD7 MH-5 VCFD7 Q3-2011 024 8/18/2011 9:50 2.09E+04 1.87E+03 2.64E+02 9.64E-01 1.55E+00 1.70E+00 1.90E+00 7.98E+00 9.05E+00

-3.10E+00 9.60E+00 9.54E+00 NA NA NA 1.13E+04 MH-5 VCFD7 MH-5 VCFD7 Q3-2011 Mid 025 8/24/2011 11:01 1.40E+04 1.51E+03 2.58E+02 5.99E-01 1.30E+00 1.46E+00

-2.36E+00 7.86E+00 8.21E+00 3.46E+00 7.98E+00 9.92E+00 NA NA NA 1.13E+04 MH-5 VCFD7 MH-5 VCFD7 Q3-2011 Mid 026 8/30/2011 13:55 3.37E+04 1.83E+03 2.03E+02 9.19E-01 1.31E+00 1.40E+00 1.76E+00 7.23E+00 8.47E+00

-1.69E+00 7.86E+00 7.79E+00 NA NA NA 1.13E+04 MH-5 VCFD7 LAF-002 Q4-2010 014

-22.3 11/22/2010 14:41 1.02E+02 1.13E+02 1.21E+02 1.96E-01 4.62E-01 5.40E-01

-6.13E-01 6.13E+00 6.83E+00

-1.60E+00 5.88E+00 6.15E+00 3.65E+00 1.77E+01 2.05E+01 ND ND ND ND ND LAF-002 LAF-002 Q2-2011 015

-22.3 5/2/2011 12:50 6.69E+01 3.04E+02 3.43E+02 1.16E+00 1.55E+00 1.66E+00

-5.80E-01 7.86E+00 8.57E+00

-6.46E-01 7.24E+00 7.65E+00

-3.48E-01 1.60E+01 1.83E+01 LAF-002 B-17 Q4-2010 010 11/17/2010 11:10 2.37E+03 2.72E+02 3.86E+02 6.87E-01 7.68E-01 1.72E+00 1.89E+01 6.46E+00 7.93E+00 8.39E-01 4.32E+00 9.74E+00 NA NA NA 3.76E+03 ND 1.90E+01 ND NA B-17 B-17 Q1-2011 011 2/14/2011 15:44 3.82E+03 5.88E+02 3.65E+02 5.41E-02 1.70E+00 2.14E+00 2.15E+01 1.22E+01 6.75E+00

-1.81E+00 7.00E+00 7.25E+00 NA NA NA 3.76E+03 1.90E+01 B-17 B-17 Q2-2011 012 4/25/2011 10:50 8.10E+03 9.22E+02 4.53E+02

-6.21E-03 1.74E+00 2.09E+00 2.05E+01 1.33E+01 1.03E+01 3.18E+00 9.06E+00 1.11E+01 NA NA NA 3.76E+03 1.90E+01 B-17 B-17 Q3-2011 013 8/17/2011 13:17 7.36E+02 3.03E+02 1.96E+02

-6.00E-02 9.87E-01 1.25E+00 1.51E+01 1.49E+01 7.29E+00

-4.01E-01 7.02E+00 7.34E+00 NA NA NA 3.76E+03 1.90E+01 B-17

TABLE 3 THIRD QUARTER 2011 GROUNDWATER ANALYTICAL RESULTS AND AVERAGES INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q32011 FINAL Table 3 - Third Quarter 2011 Groundwater Analytical Results and Averages.xlsx; Q32011 Table 3 Page 6 of 6 See Page 6 for Notes TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Date Time Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Average Average Average Average Average ANALYSIS RESULTS5 YEARLY ROLLING AVERAGES4,6 Well ID1 TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

SAMPLE COLLECTION Well ID1 SAMPLING QUARTER2,8 SAMPLE ID SAMPLE ZONE CENTER Depth Ft Below Top of Casing3 SAMPLE ZONE CENTER Elevation Ft msl3 B-67 Q4-2010 010 11/8/2010 11:45 1.05E+02 1.33E+02 1.43E+02 1.43E-01 6.60E-01 7.68E-01 0.00E+00 5.04E+00 6.20E+00

-3.20E-01 4.70E+00 5.29E+00 NA NA NA 1.18E+03 ND ND ND NA B-67 B-67 Q1-2011 011 2/28/2011 11:27 8.39E+02 3.90E+02 3.65E+02 6.28E-01 1.78E+00 2.05E+00 4.45E+00 5.82E+00 7.02E+00

-1.35E+00 6.50E+00 6.88E+00 NA NA NA 1.18E+03 B-67 B-67 Q2-2011 012 4/25/2011 9:48 2.68E+03 6.18E+02 4.53E+02

-6.69E-01 1.58E+00 2.09E+00

-1.31E-01 8.56E+00 9.08E+00 4.73E+00 1.06E+01 1.35E+01 NA NA NA 1.18E+03 B-67 B-67 Q2-2011 Mid 013 7/8/2011 11:05 5.39E+02 3.54E+02 2.82E+02 1.32E+00 1.56E+00 1.63E+00 6.09E+00 1.58E+01 8.04E+00

-2.64E+00 8.97E+00 8.84E+00 NA NA NA 1.18E+03 B-67 B-67 Q3-2011 014 7/29/2011 10:52 6.45E+02 4.14E+02 3.38E+02

-2.59E-01 1.39E+00 1.79E+00 1.60E+00 7.74E+00 8.72E+00 4.72E+00 5.07E+00 7.82E+00 NA NA NA 1.18E+03 B-67 Notes:

1. For nested multi-level monitoring wells, suffix of well ID indicates depth (rounded to nearest foot) from reference point on casing to bottom of well screen. For Waterloo multi-level systems, suffix indicates depth (rounded to nearest foot) from reference point on casing to top of sampling port. Well IDs without a suffix are open bedrock wellbores.
2. All analytical results from the last 12 months from each location are provided. Monitoring locations are sampled quarterly, bi-annually, or annually, and as necessary during the year.
3. Sampling depths within sampling intervals (i.e. location of pump intake) have been located adjacent to a transmissive zone where possible.
4. Averages provided are analytical result averages of all valid samples (including mid-quarter and confirmatory samples) collected from each monitoring location from the fourth quarter of 2010 (Q4-2010) to the third quarter of 2011 (Q3-2011) including the post Q3-2011 samples.

Monitoring locations are sampled quarterly, bi-annually, or annually and additional samples are collected when necessary. Therefore, some results provided are the average of more than 4 samples.

For quarters in which samples were reanalyzed due to potential false positives, both results were used to calculate averages if subsequent results confirmed the validity of the original sample/analysis. For cases in which reanalysis discredited the validity of the original sample result, the replacement results were used to calculate the average. If analytical results resulted in resampling, and the resample result discredited the validity of the original sample result of a particular radionuclide, the original sample results were not used for any radionuclides and only the resample result was used. For cases in which an aliquot of the original sample was reanalyzed, if the result of the aliquot confirmed the original result, then the aliquot result and the original result were averaged and the average of the two was used to calculate the rolling average. If the aliquot result indicated the original result was false, then only the aliquot result was used to calculate the rolling average.

5. NA indicates that the constituent was not analyzed.
6. ND indicates that all of the analytical results used to calculate the average were less than MDC and/or 3 times the 1 sigma uncertainty.
7. These locations are storm drains or foundation drains.
8. Mid-quarter samples were collected and analyzed to evaluate the potential effect of certain operations on groundwater quality.
9. Column designated as Std. Dev. provides the three times 1 sigma uncertainty values.
  • The Q1 2011 MW-40-100, MW-40-127 and MW-51-189 Cs-137 results were verified by re-analysis. However, based on the available chemistry and Site hydrogeologic data, these values do not appear to be representative of the groundwater conditions at these sampling intervals.
    • The Q2 2011 MW-40-46 preliminary Sr-90 result was 2.83 pCi/L and exceeded the IL. However, after re-analysis, the sample was below the detection limit which suggests the preliminary result was likely a false positive. A shift in the MDC for the preliminary result could have possibly resulted from contaminated laboratory equipment, modified count time, or changes in sample preparation.
      • The Post-Q3 2011 MW-58-65 preliminary Sr-90 result was 3.64 pCi/L and exceeded the IL. However, after re-analysis, the sample was below the detection limit which suggests the preliminary result was likely a false positive. A shift in the MDC for the preliminary result could have possibly resulted from contaminated laboratory equipment, modified count time, or changes in sample preparation.

TABLE 3 FOURTH QUARTER 2011 GROUNDWATER ANALYTICAL RESULTS AND AVERAGES INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q42011 FINAL Table 3 - Forth Quarter 2011 Groundwater Analytical Results and Averages.xlsx; Q42011 Table 3 Page 1 of 7 See Page 7 for Notes TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Date Time Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Average Average Average Average Average MW-30-69 Q1-2011 037 69.3 6.4 2/9/2011 12:17 1.01E+05 2.18E+03 2.98E+02 1.62E+00 1.93E+00 2.00E+00 1.87E+00 5.80E+00 6.74E+00

-1.13E-01 5.88E+00 6.44E+00 NA NA NA 1.08E+05 2.40E+00 ND ND NA MW-30-69 MW-30-69 Q1-2011 Mid 038 69.3 6.4 3/31/2011 11:38 1.08E+05 3.40E+03 4.72E+02

-6.11E-01 1.63E+00 2.15E+00 2.48E+00 7.96E+00 9.14E+00

-1.41E+00 6.70E+00 6.46E+00 NA NA NA 1.08E+05 2.40E+00 MW-30-69 Q2-2011 039 69.3 6.4 5/5/2011 12:08 1.13E+05 3.48E+03 3.99E+02 2.40E+00 1.37E+00 1.23E+00 2.46E+00 8.92E+00 1.03E+01 2.21E+00 9.58E+00 1.16E+01 NA NA NA 1.08E+05 2.40E+00 ND ND NA MW-30-69 MW-30-69 Q2-2011 Mid 040 69.3 6.4 7/11/2011 12:05 1.19E+05 4.23E+03 2.83E+02

-6.14E-02 7.62E-01 1.00E+00 3.56E+00 1.07E+01 1.24E+01 2.40E+00 1.19E+01 1.40E+01 NA NA NA 1.08E+05 2.40E+00 MW-30-69 MW-30-69 Q3-2011 041 69.3 6.4 8/9/2011 10:49 1.14E+05 3.45E+03 4.22E+02 1.02E+00 1.76E+00 1.92E+00

-7.63E-01 1.03E+01 1.15E+01

-2.42E+00 8.58E+00 8.50E+00 NA NA NA 1.08E+05 2.40E+00 MW-30-69 MW-30-69 Q4-2011 042 69.3 6.4 11/30/2011 11:20 9.12E+04 3.06E+03 4.87E+02

-4.56E-01 1.51E+00 1.96E+00 1.95E+00 7.71E+00 9.97E+00 2.82E+00 7.41E+00 1.11E+01 NA NA NA 1.08E+05 2.40E+00 MW-30-69 MW-30-84 Q1-2011 028 83.8

-8.1 2/9/2011 12:57 9.20E+03 8.86E+02 3.79E+02 1.12E+00 1.82E+00 1.98E+00 5.89E-01 4.74E+00 5.22E+00 1.09E+00 5.76E+00 6.49E+00 NA NA NA 7.94E+03 ND ND ND NA MW-30-84 MW-30-84 Q1-2011 Mid 029 83.8

-8.1 3/31/2011 12:03 9.04E+03 1.06E+03 4.74E+02

-4.78E-01 1.66E+00 2.13E+00 5.00E-01 1.12E+01 1.21E+01

-3.04E+00 9.48E+00 9.12E+00 NA NA NA 7.94E+03 MW-30-84 MW-30-84 Q2-2011 030 83.8

-8.1 5/5/2011 12:58 7.57E+03 9.46E+02 3.92E+02 1.64E-01 1.15E+00 1.40E+00 3.00E+00 8.04E+00 9.35E+00 4.65E-02 7.14E+00 7.76E+00 NA NA NA 7.94E+03 MW-30-84 MW-30-84 Q2-2011 Mid 031 83.8

-8.1 7/11/2011 12:45 7.55E+03 1.08E+03 2.82E+02

-3.75E-01 9.75E-01 1.29E+00 2.17E-01 7.89E+00 8.89E+00 1.39E+01 1.16E+01 1.59E+01 NA NA NA 7.94E+03 MW-30-84 MW-30-84 Q3-2011 032 83.8

-8.1 8/9/2011 11:16 7.06E+03 7.05E+02 3.54E+02

-1.22E+00 1.28E+00 1.92E+00

-1.67E+00 7.08E+00 7.43E+00

-3.28E+00 9.63E+00 9.46E+00 NA NA NA 7.94E+03 MW-30-84 MW-30-84 Q4-2011 033 83.8

-8.1 11/30/2011 11:37 7.24E+03 9.39E+02 4.80E+02 5.31E-02 1.45E+00 1.81E+00

-1.63E+00 9.48E+00 1.09E+01

-1.64E+00 1.05E+01 1.26E+01 NA NA NA 7.94E+03 MW-30-84 MW-31-49 Q1-2011 029 48.8 26.8 2/9/2011 13:12 1.06E+03 3.40E+02 2.98E+02

-5.51E-01 1.76E+00 2.14E+00 1.39E+00 5.22E+00 6.02E+00 4.84E-01 5.26E+00 5.91E+00 NA NA NA 5.37E+03 ND ND ND NA MW-31-49 MW-31-49 Q1-2011 Mid 030 48.8 26.8 3/30/2011 12:33 4.31E+03 7.84E+02 4.65E+02 1.77E+00 2.04E+00 2.16E+00

-2.34E+00 7.80E+00 8.17E+00

-5.38E-01 9.18E+00 1.00E+01 NA NA NA 5.37E+03 MW-31-49 MW-31-49 Q2-2011 031 48.8 26.8 4/18/2011 12:53 1.08E+03 5.20E+02 4.66E+02 4.98E-01 1.81E+00 2.09E+00

-1.82E+00 8.82E+00 9.22E+00 6.17E+00 8.70E+00 1.13E+01 NA NA NA 5.37E+03 MW-31-49 MW-31-49 Q3-2011 033 48.8 26.8 8/5/2011 10:47 4.98E+03 7.80E+02 4.16E+02

-2.63E-02 1.34E+00 1.58E+00 6.39E+00 8.76E+00 1.10E+01 5.20E-01 1.06E+01 1.16E+01 NA NA NA 5.37E+03 MW-31-49 MW-31-49 Q4-2011 034 48.8 26.8 11/21/2011 10:32 1.54E+04 9.78E+02 3.42E+02

-3.16E-01 1.08E+00 1.45E+00 0.00E+00 1.14E+01 9.96E+00

-3.55E+00 9.54E+00 1.08E+01 NA NA NA 5.37E+03 MW-31-49 MW-31-63 Q1-2011 029 63.3 12.3 2/9/2011 13:14 2.46E+04 1.10E+03 2.98E+02 4.29E-01 1.78E+00 2.08E+00

-1.42E+00 6.46E+00 6.81E+00

-2.31E+00 6.42E+00 6.26E+00 NA NA NA 1.59E+04 ND ND ND NA MW-31-63 MW-31-63 Q1-2011 Mid 030 63.3 12.3 3/30/2011 13:13 1.33E+04 1.14E+03 4.53E+02 1.49E+00 1.87E+00 2.02E+00 8.76E-01 9.00E+00 9.97E+00

-1.92E-01 7.26E+00 7.92E+00 NA NA NA 1.59E+04 MW-31-63 MW-31-63 Q2-2011 031 63.3 12.3 4/18/2011 13:21 1.81E+04 1.45E+03 4.67E+02 7.26E-01 1.84E+00 2.08E+00

-3.10E-01 7.62E+00 8.46E+00 1.76E+00 8.74E+00 1.03E+01 NA NA NA 1.59E+04 MW-31-63 MW-31-63 Q3-2011 033 63.3 12.3 8/5/2011 11:29 1.63E+04 1.31E+03 4.18E+02

-1.30E-01 1.71E+00 2.02E+00

-2.83E-01 9.87E+00 1.12E+01 2.13E+00 9.24E+00 1.08E+01 NA NA NA 1.59E+04 MW-31-63 MW-31-63 Q4-2011 034 63.3 12.3 11/21/2011 11:14 7.23E+03 9.00E+02 2.36E+02 1.36E+00 1.42E+00 1.40E+00

-2.72E+00 9.45E+00 1.09E+01 2.93E+00 8.19E+00 1.20E+01 NA NA NA 1.59E+04 MW-31-63 MW-31-85 Q1-2011 029 84.8

-9.2 2/9/2011 13:03 4.83E+03 6.84E+02 3.82E+02 3.26E-01 1.79E+00 2.18E+00 3.19E+00 5.96E+00 7.08E+00 3.14E+00 6.06E+00 7.39E+00 NA NA NA 3.80E+03 ND ND ND NA MW-31-85 MW-31-85 Q1-2011 Mid 030 84.8

-9.2 3/30/2011 12:55 7.75E+02 4.66E+02 4.52E+02 9.37E-01 1.81E+00 2.00E+00 5.90E+00 1.31E+01 8.10E+00 6.43E+00 8.88E+00 1.17E+01 NA NA NA 3.80E+03 MW-31-85 MW-31-85 Q2-2011 031 84.8

-9.2 4/18/2011 13:18 3.08E+03 6.96E+02 4.66E+02

-1.09E+00 1.46E+00 2.09E+00

-4.50E+00 9.34E+00 9.19E+00 3.84E+00 1.01E+01 1.22E+01 NA NA NA 3.80E+03 MW-31-85 MW-31-85 Q3-2011 033 84.8

-9.2 8/5/2011 11:27 4.82E+03 7.74E+02 4.22E+02 1.39E-01 1.40E+00 1.63E+00

-8.79E-01 8.25E+00 8.80E+00

-4.79E+00 9.57E+00 8.27E+00 NA NA NA 3.80E+03 MW-31-85 MW-31-85 Q4-2011 034 84.8

-9.2 11/21/2011 11:25 5.49E+03 6.33E+02 3.45E+02 9.56E-01 1.41E+00 1.50E+00

-3.23E+00 9.21E+00 1.04E+01

-6.05E-01 9.57E+00 1.22E+01 NA NA NA 3.80E+03 MW-31-85 MW-32-59 Q1-2011 023 58.8 18.3 3/1/2011 11:28 4.39E+03 6.42E+02 3.59E+02 1.25E+00 1.49E+00 1.55E+00 6.56E-01 5.82E+00 6.63E+00

-4.41E-01 7.00E+00 7.58E+00 NA NA NA 1.82E+04 ND ND ND NA MW-32-59 MW-32-59 Q1-2011 Mid 024 58.8 18.3 3/31/2011 12:46 3.37E+04 1.96E+03 5.07E+02

-2.13E-01 1.15E+00 1.51E+00 8.24E-01 8.92E+00 9.96E+00 1.99E-02 1.02E+01 1.11E+01 NA NA NA 1.82E+04 MW-32-59 MW-32-59 Q2-2011 025 58.8 18.3 4/27/2011 12:26 3.31E+03 6.36E+02 4.08E+02 4.03E-01 1.50E+00 1.74E+00 4.77E+00 8.64E+00 1.04E+01

-3.37E+00 9.58E+00 9.50E+00 NA NA NA 1.82E+04 MW-32-59 MW-32-59 Q3-2011 027 58.8 18.3 8/5/2011 12:30 2.06E+04 1.47E+03 4.19E+02 1.64E+00 1.66E+00 1.71E+00

-3.73E+00 8.34E+00 8.04E+00

-1.05E+00 8.79E+00 9.24E+00 NA NA NA 1.82E+04 MW-32-59 MW-32-59 Q4-2011 028 58.8 18.3 11/17/2011 14:15 2.91E+04 1.74E+03 2.26E+02

-1.28E+00 1.58E+00 2.33E+00

-3.91E+00 1.01E+01 1.18E+01

-1.58E+00 9.84E+00 1.21E+01 NA NA NA 1.82E+04 MW-32-59 MW-32-85 Q1-2011 026 85.3 85.3 3/1/2011 12:05 1.34E+04 1.41E+03 2.62E+02 3.81E-01 1.41E+00 1.63E+00 7.79E-01 8.26E+00 9.36E+00 4.73E+00 9.72E+00 1.24E+01 NA NA NA 1.17E+04 ND ND ND NA MW-32-85 MW-32-85 Q1-2011 Mid 027 85.3 85.3 3/31/2011 13:18 1.32E+04 1.27E+03 5.07E+02

-1.62E-01 1.20E+00 1.56E+00

-6.56E-01 7.26E+00 7.61E+00 3.80E+00 8.28E+00 1.02E+01 NA NA NA 1.17E+04 MW-32-85 MW-32-85 Q2-2011 028 85.3 85.3 4/27/2011 13:04 1.14E+04 1.19E+03 5.10E+02 1.58E+00 1.69E+00 1.75E+00

-1.23E+00 6.80E+00 7.31E+00 5.30E-01 1.02E+01 1.15E+01 NA NA NA 1.17E+04 MW-32-85 MW-32-85 Q3-2011 030 85.3 85.3 8/5/2011 13:36 1.14E+04 1.12E+03 4.20E+02 1.14E-01 1.64E+00 1.92E+00 5.40E+00 6.87E+00 8.79E+00

-1.21E+00 6.69E+00 6.57E+00 NA NA NA 1.17E+04 MW-32-85 MW-32-85 Q4-2011 031 85.3 85.3 11/17/2011 15:08 8.88E+03 7.65E+02 3.42E+02 4.57E-01 1.56E+00 1.82E+00

-1.20E+00 7.38E+00 8.80E+00

-1.88E+00 9.06E+00 1.09E+01 NA NA NA 1.17E+04 MW-32-85 MW-32-149 Q1-2011 023 149.3

-72.2 3/1/2011 13:37 1.06E+03 4.48E+02 2.68E+02

-7.01E-01 1.66E+00 2.15E+00 9.25E-01 5.42E+00 6.30E+00 2.06E+00 6.60E+00 7.93E+00 NA NA NA 8.81E+02 ND ND ND NA MW-32-149 MW-32-149 Q1-2011 Mid 024 149.3

-72.2 3/31/2011 11:33 8.99E+02 5.34E+02 5.09E+02

-2.01E-01 1.10E+00 1.49E+00 2.52E+00 9.30E+00 1.09E+01 2.31E+00 9.92E+00 1.18E+01 NA NA NA 8.81E+02 MW-32-149 MW-32-149 Q2-2011 025 149.3

-72.2 4/27/2011 11:12 8.69E+02 4.44E+02 4.11E+02 3.00E-01 1.43E+00 1.67E+00 2.12E+00 7.44E+00 8.59E+00 9.88E-01 7.76E+00 8.83E+00 NA NA NA 8.81E+02 MW-32-149 MW-32-149 Q3-2011 027 149.3

-72.2 8/5/2011 11:10 9.86E+02 4.71E+02 4.21E+02 4.80E-01 1.81E+00 2.06E+00

-9.94E-01 9.60E+00 9.39E+00 2.75E+00 7.41E+00 9.28E+00 NA NA NA 8.81E+02 MW-32-149 MW-32-149 Q4-2011 028 149.3

-72.2 11/17/2011 12:05 5.91E+02 3.45E+02 3.41E+02 3.84E-01 1.46E+00 1.72E+00

-5.25E+00 7.74E+00 7.86E+00 2.57E+00 8.07E+00 1.12E+01 NA NA NA 8.81E+02 MW-32-149 MW-32-173 Q1-2011 021 172.8

-95.7 3/1/2011 13:13 9.02E+02 4.12E+02 2.61E+02

-4.04E-01 1.12E+00 1.45E+00 5.99E+00 6.06E+00 7.73E+00

-2.04E+00 7.36E+00 7.55E+00 NA NA NA 6.80E+02 ND ND ND NA MW-32-173 MW-32-173 Q1-2011 Mid 022 172.8

-95.7 3/31/2011 11:35 8.41E+02 5.22E+02 5.04E+02 2.46E-01 1.27E+00 1.54E+00 6.51E+00 1.58E+01 8.26E+00 2.19E+00 8.22E+00 9.98E+00 NA NA NA 6.80E+02 MW-32-173 MW-32-173 Q2-2011 023 172.8

-95.7 4/27/2011 11:27 5.82E+02 4.98E+02 5.08E+02 6.37E-01 1.54E+00 1.74E+00 0.00E+00 2.00E+01 9.23E+00 2.47E-01 9.58E+00 1.07E+01 NA NA NA 6.80E+02 MW-32-173 MW-32-173 Q3-2011 025 172.8

-95.7 8/5/2011 11:11 5.69E+02 4.17E+02 4.12E+02 6.34E-01 1.48E+00 1.66E+00

-9.50E-01 6.36E+00 6.56E+00

-1.55E+00 1.10E+01 1.14E+01 NA NA NA 6.80E+02 MW-32-173 MW-32-173 Q4-2011 026 172.8

-95.7 11/17/2011 12:01 5.06E+02 3.33E+02 3.34E+02 7.83E-02 9.63E-01 1.24E+00 2.87E+00 9.12E+00 1.13E+01

-1.50E-01 9.93E+00 1.26E+01 NA NA NA 6.80E+02 MW-32-173 MW-32-190 Q1-2011 025 190.3

-113.7 3/1/2011 13:24 1.64E+03 5.32E+02 2.64E+02 7.65E-01 1.20E+00 1.29E+00 2.74E+00 5.52E+00 6.57E+00 4.88E+00 7.64E+00 8.75E+00 NA NA NA 1.43E+03 ND ND ND NA MW-32-190 MW-32-190 Q1-2011 Mid 026 190.3

-113.7 3/31/2011 11:47 1.41E+03 5.76E+02 5.02E+02

-7.79E-01 1.15E+00 1.67E+00 8.78E-01 7.96E+00 9.01E+00 5.11E+00 1.04E+01 1.30E+01 NA NA NA 1.43E+03 MW-32-190 MW-32-190 Q2-2011 027 190.3

-113.7 4/27/2011 11:17 1.21E+03 5.64E+02 5.10E+02 7.54E-01 1.13E+00 1.20E+00 8.61E-01 8.68E+00 9.74E+00

-6.60E+00 8.98E+00 6.37E+00 NA NA NA 1.43E+03 MW-32-190 MW-32-190 Q3-2011 029 190.3

-113.7 8/5/2011 11:15 1.44E+03 5.16E+02 4.20E+02 7.59E-01 1.64E+00 1.82E+00 2.02E+00 7.23E+00 8.43E+00 1.28E+00 9.24E+00 1.06E+01 NA NA NA 1.43E+03 MW-32-190 MW-32-190 Q4-2011 030 190.3

-113.7 11/17/2011 12:03 1.46E+03 4.05E+02 3.36E+02

-7.57E-01 8.37E-01 1.41E+00 1.30E+00 6.57E+00 8.59E+00

-4.42E-01 6.24E+00 7.93E+00 NA NA NA 1.43E+03 MW-32-190 MW-36-24 Q1-2011 021 16.1

-4.3 2/28/2011 12:37 2.56E+02 3.54E+02 3.81E+02

-8.87E-02 1.67E+00 2.08E+00 4.53E-01 5.26E+00 5.75E+00

-3.09E-01 4.74E+00 5.03E+00 NA NA NA 2.10E+03 ND ND ND NA MW-36-24 MW-36-24 Q2-2011 022 16.1

-4.3 4/28/2011 14:34 3.07E+03 7.26E+02 5.19E+02 1.38E+00 1.53E+00 1.59E+00

-6.43E-01 7.68E+00 8.47E+00 2.82E+00 7.48E+00 9.35E+00 NA NA NA 2.10E+03 MW-36-24 MW-36-24 Q3-2011 023 16.1

-4.3 8/16/2011 13:34 1.12E+03 5.01E+02 4.51E+02 2.34E-01 9.96E-01 1.18E+00

-2.80E+00 7.71E+00 7.54E+00 7.10E-01 7.89E+00 8.75E+00 NA NA NA 2.10E+03 MW-36-24 MW-36-24 Q4-2011 024 16.1

-4.3 12/7/2011 11:04 0.00E+00 4.20E+02 4.96E+02

-3.36E-01 1.29E+00 1.70E+00 1.75E+00 7.26E+00 9.17E+00

-1.38E+00 6.00E+00 7.29E+00 NA NA NA 2.10E+03 MW-36-24 MW-36-41 Q1-2011 015 37

-25.2 2/28/2011 13:53 8.74E+03 6.88E+02 2.97E+02 4.11E+00 1.87E+00 1.57E+00 1.31E+00 5.26E+00 6.09E+00 1.58E+00 5.68E+00 6.65E+00 NA NA NA 6.36E+03 3.05E+00 ND ND NA MW-36-41 MW-36-41 Q2-2011 016 37

-25.2 4/28/2011 15:39 8.17E+03 1.04E+03 5.14E+02 3.31E+00 1.75E+00 1.36E+00 2.18E+00 9.26E+00 1.07E+01

-2.96E-01 1.04E+01 1.12E+01 NA NA NA 6.36E+03 3.05E+00 MW-36-41 MW-36-41 Q3-2011 017 37

-25.2 8/16/2011 14:18 5.90E+03 8.37E+02 4.55E+02 1.74E+00 1.26E+00 1.13E+00 1.75E+00 8.91E+00 9.88E+00 4.43E+00 9.15E+00 1.15E+01 NA NA NA 6.36E+03 3.05E+00 MW-36-41 MW-36-41 Q4-2011 018 37

-25.2 12/7/2011 13:09 2.63E+03 6.51E+02 4.78E+02 9.00E-01 1.71E+00 1.89E+00 1.19E-02 7.17E+00 9.00E+00

-5.23E-01 7.86E+00 1.01E+01 NA NA NA 6.36E+03 3.05E+00 MW-36-41 MW-36-52 Q1-2011 020 49.7

-37.9 2/28/2011 12:43 3.14E+03 4.92E+02 3.37E+02 1.33E+00 2.00E+00 2.14E+00

-6.00E+00 5.58E+00 4.80E+00

-2.66E+00 5.94E+00 5.65E+00 NA NA NA 4.61E+03 3.86E+00 ND ND NA MW-36-52 MW-36-52 Q2-2011 021 49.7

-37.9 4/28/2011 14:38 5.84E+03 9.06E+02 5.15E+02 3.41E+00 1.56E+00 1.11E+00 4.29E+00 8.42E+00 1.03E+01

-2.61E+00 8.50E+00 8.36E+00 NA NA NA 4.61E+03 3.86E+00 MW-36-52 MW-36-52 Q3-2011 022 49.7

-37.9 8/16/2011 14:52 4.69E+03 7.59E+02 4.48E+02 2.93E+00 1.57E+00 1.36E+00 3.59E+00 8.22E+00 9.80E+00

-1.83E+00 9.33E+00 9.74E+00 NA NA NA 4.61E+03 3.86E+00 MW-36-52 MW-36-52 Q4-2011 023 49.7

-37.9 12/7/2011 11:36 4.76E+03 8.10E+02 4.91E+02 5.23E+00 1.96E+00 1.24E+00 2.89E+00 7.74E+00 1.01E+01 5.68E+00 9.03E+00 1.31E+01 NA NA NA 4.61E+03 3.86E+00 MW-36-52 MW-37-22 Q1-2011 021 17

-2 1/27/2011 15:19 6.74E+03 6.18E+02 2.98E+02 1.04E+01 2.52E+00 1.68E+00

-2.18E+00 4.74E+00 4.94E+00 2.59E+00 5.38E+00 6.55E+00 NA NA NA 5.78E+03 8.68E+00 ND ND NA MW-37-22 MW-37-22 Q2-2011 022 17

-2 4/28/2011 12:05 6.87E+03 9.66E+02 5.14E+02 8.72E+00 2.90E+00 2.05E+00 7.12E-01 6.96E+00 7.67E+00 5.14E-01 7.86E+00 8.62E+00 NA NA NA 5.78E+03 8.68E+00 MW-37-22 MW-37-22 Q3-2011 023 17

-2 8/16/2011 10:35 4.52E+03 7.56E+02 4.53E+02 7.59E+00 2.07E+00 1.32E+00 3.10E+00 7.26E+00 8.77E+00

-9.99E-01 7.35E+00 7.48E+00 NA NA NA 5.78E+03 8.68E+00 MW-37-22 MW-37-22 Q4-2011 024 17

-2 11/23/2011 11:33 4.97E+03 8.28E+02 4.96E+02 8.02E+00 2.57E+00 1.38E+00 2.26E+00 9.12E+00 1.19E+01

-1.41E+00 7.35E+00 9.09E+00 NA NA NA 5.78E+03 8.68E+00 MW-37-22 MW-37-32 Q1-2011 021 29

-14 1/27/2011 15:09 4.57E+03 5.28E+02 2.98E+02 1.49E+01 3.02E+00 1.74E+00 4.20E-01 6.12E+00 6.85E+00 1.72E+00 6.60E+00 7.76E+00 NA NA NA 4.56E+03 1.76E+01 ND ND NA MW-37-32 MW-37-32 Q2-2011 022 29

-14 4/28/2011 12:21 4.11E+03 7.98E+02 5.15E+02 2.62E+01 3.76E+00 1.68E+00 3.56E+00 1.20E+01 1.42E+01

-1.92E+00 1.09E+01 1.09E+01 NA NA NA 4.56E+03 1.76E+01 MW-37-32 MW-37-32 Q3-2011 023 29

-14 8/16/2011 11:00 5.23E+03 7.95E+02 4.52E+02 1.68E+01 2.87E+00 1.13E+00

-2.53E+00 8.34E+00 7.53E+00

-6.09E+00 9.06E+00 8.10E+00 NA NA NA 4.56E+03 1.76E+01 MW-37-32 MW-37-32 Q4-2011 024 29

-14 11/23/2011 11:19 4.33E+03 7.80E+02 4.91E+02 1.26E+01 3.21E+00 1.52E+00 7.81E+00 9.00E+00 1.28E+01

-6.59E+00 8.76E+00 8.06E+00 NA NA NA 4.56E+03 1.76E+01 MW-37-32 MW-37-40 Q1-2011 021 39.2

-24.2 1/27/2011 13:35 5.97E+03 7.42E+02 3.82E+02 1.93E+01 3.34E+00 1.85E+00 1.95E+00 5.84E+00 6.78E+00 2.03E+00 6.84E+00 7.92E+00 NA NA NA 5.04E+03 1.92E+01 ND ND NA MW-37-40 MW-37-40 Q2-2011 022 39.2

-24.2 4/28/2011 11:31 3.92E+03 8.02E+02 5.33E+02 2.30E+01 3.66E+00 1.68E+00 4.10E+00 9.02E+00 1.09E+01 6.47E-01 8.94E+00 1.02E+01 NA NA NA 5.04E+03 1.92E+01 MW-37-40 MW-37-40 Q3-2011 023 39.2

-24.2 8/16/2011 11:24 5.03E+03 7.86E+02 4.53E+02 1.95E+01 3.18E+00 1.17E+00

-2.08E+00 8.25E+00 8.54E+00 1.79E+00 7.35E+00 8.59E+00 NA NA NA 5.04E+03 1.92E+01 MW-37-40 MW-37-40 Q4-2011 024 39.2

-24.2 11/23/2011 11:46 5.22E+03 8.28E+02 4.83E+02 1.50E+01 3.45E+00 1.47E+00 1.06E+00 1.43E+01 7.71E+00 9.11E-01 7.29E+00 1.00E+01 NA NA NA 5.04E+03 1.92E+01 MW-37-40 MW-37-57 Q1-2011 021 53.2

-38.2 1/27/2011 15:26 5.63E+03 5.76E+02 2.99E+02 2.02E+01 3.60E+00 1.96E+00

-3.70E-01 6.34E+00 6.92E+00

-1.36E+00 5.64E+00 5.68E+00 NA NA NA 5.36E+03 1.91E+01 ND ND NA MW-37-57 MW-37-57 Q2-2011 022 53.2

-38.2 4/28/2011 12:17 5.81E+03 8.98E+02 5.07E+02 1.58E+01 3.54E+00 2.00E+00 5.18E+00 1.72E+01 8.67E+00

-1.42E+00 8.36E+00 8.80E+00 NA NA NA 5.36E+03 1.91E+01 MW-37-57 MW-37-57 Q3-2011 023 53.2

-38.2 8/16/2011 10:55 5.11E+03 7.98E+02 4.59E+02 2.15E+01 3.27E+00 1.30E+00 1.82E+00 7.92E+00 9.16E+00

-1.34E+00 6.39E+00 6.57E+00 NA NA NA 5.36E+03 1.91E+01 MW-37-57 MW-37-57 Q4-2011 024 53.2

-38.2 11/23/2011 11:22 4.87E+03 8.16E+02 4.91E+02 1.88E+01 3.90E+00 1.81E+00

-6.08E-01 8.28E+00 1.01E+01 3.00E+00 9.12E+00 1.27E+01 NA NA NA 5.36E+03 1.91E+01 MW-37-57 MW-39-67 Q2-2011 011 67 13 4/26/2011 14:52 1.09E+04 9.64E+02 4.18E+02 1.74E+00 1.49E+00 1.50E+00

-8.12E-01 8.22E+00 8.78E+00

-4.05E+00 9.42E+00 9.00E+00 NA NA NA 7.27E+03 2.06E+00 ND ND NA MW-39-67 MW-39-67 Q2-2011 Mid 012 67 13 7/15/2011 13:42 2.24E+03 6.12E+02 4.40E+02 2.55E-01 1.16E+00 1.34E+00

-1.15E-01 8.28E+00 9.19E+00

-2.42E-02 9.72E+00 1.12E+01 NA NA NA 7.27E+03 2.06E+00 MW-39-67 MW-39-67 Q3-2011 Mid 013 67 13 8/29/2011 13:47 1.49E+04 1.24E+03 4.51E+02 1.08E+00 1.18E+00 1.20E+00 2.23E+00 7.77E+00 8.94E+00 4.82E+00 8.25E+00 1.05E+01 NA NA NA 7.27E+03 2.06E+00 MW-39-67 MW-39-67 Q4-2011 014 67 13 12/1/2011 14:04 1.03E+03 5.13E+02 4.75E+02 2.37E+00 1.90E+00 1.76E+00

-3.99E+00 9.24E+00 1.02E+01

-3.39E+00 8.07E+00 9.37E+00 NA NA NA 7.27E+03 2.06E+00 MW-39-67 MW-39-84 Q2-2011 011 83.5

-3.5 4/26/2011 14:25 4.40E+02 4.02E+02 4.13E+02

-2.03E-01 1.15E+00 1.50E+00

-9.39E-01 7.42E+00 7.84E+00

-4.02E-01 6.92E+00 7.41E+00 NA NA NA 4.40E+02 3.12E+00 ND ND NA MW-39-84 MW-39-84 Q2-2011 Mid 012 83.5

-3.5 7/15/2011 14:33 3.55E+02 4.17E+02 4.40E+02 6.54E-01 1.15E+00 1.27E+00

-1.78E+00 1.43E+01 1.71E+01

-4.89E+00 9.45E+00 8.20E+00 NA NA NA 4.40E+02 3.12E+00 MW-39-84 MW-39-84 Q3-2011 Mid 013 83.5

-3.5 8/29/2011 13:56 2.38E+02 4.14E+02 4.54E+02 8.64E-01 1.00E+00 1.00E+00 5.19E+00 1.54E+01 9.85E+00

-1.20E+00 9.99E+00 1.04E+01 NA NA NA 4.40E+02 3.12E+00 MW-39-84 MW-39-84 Q4-2011 014 83.5

-3.5 12/1/2011 14:17 1.39E+02 4.32E+02 4.88E+02 3.12E+00 2.08E+00 1.81E+00

-1.59E+00 6.48E+00 7.42E+00

-1.71E+00 8.82E+00 1.05E+01 NA NA NA 4.40E+02 3.12E+00 MW-39-84 ANALYSIS RESULTS5 YEARLY ROLLING AVERAGES4,6 Well ID1 TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

SAMPLE COLLECTION Well ID1 SAMPLING QUARTER2,8 SAMPLE ID SAMPLE ZONE CENTER Depth Ft Below Top of Casing3 SAMPLE ZONE CENTER Elevation Ft msl3

TABLE 3 FOURTH QUARTER 2011 GROUNDWATER ANALYTICAL RESULTS AND AVERAGES INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q42011 FINAL Table 3 - Forth Quarter 2011 Groundwater Analytical Results and Averages.xlsx; Q42011 Table 3 Page 2 of 7 See Page 7 for Notes TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Date Time Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Average Average Average Average Average ANALYSIS RESULTS5 YEARLY ROLLING AVERAGES4,6 Well ID1 TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

SAMPLE COLLECTION Well ID1 SAMPLING QUARTER2,8 SAMPLE ID SAMPLE ZONE CENTER Depth Ft Below Top of Casing3 SAMPLE ZONE CENTER Elevation Ft msl3 MW-39-102 Q2-2011 011 101.5

-21.5 4/26/2011 14:33 1.43E+04 1.09E+03 4.19E+02 1.08E+00 1.85E+00 2.03E+00 4.48E+01 2.08E+01 9.86E+00 6.03E+00 7.96E+00 1.07E+01 NA NA NA 1.17E+04 2.77E+00 4.48E+01 ND NA MW-39-102 MW-39-102 Q2-2011 Mid 012 101.5

-21.5 7/15/2011 14:02 1.24E+04 1.20E+03 4.36E+02 5.88E-01 1.09E+00 1.20E+00 3.70E+00 8.76E+00 1.02E+01

-6.84E-01 9.42E+00 9.35E+00 NA NA NA 1.17E+04 2.77E+00 4.48E+01 MW-39-102 MW-39-102 Q3-2011 Mid 013 101.5

-21.5 8/29/2011 14:11 1.90E+04 1.37E+03 4.41E+02

-7.38E-01 1.20E+00 1.60E+00

-3.14E+00 7.92E+00 7.72E+00 4.66E+00 7.83E+00 1.04E+01 NA NA NA 1.17E+04 2.77E+00 4.48E+01 MW-39-102 MW-39-102 Q4-2011 014 101.5

-21.5 12/1/2011 14:10 1.12E+03 5.25E+02 4.77E+02 2.77E+00 2.06E+00 1.95E+00 1.42E+00 7.68E+00 9.90E+00

-2.95E+00 6.99E+00 7.97E+00 NA NA NA 1.17E+04 2.77E+00 4.48E+01 MW-39-102 MW-39-124 Q2-2011 011 124

-44 4/26/2011 13:01 1.51E+02 3.70E+02 4.15E+02 5.20E-01 1.37E+00 1.55E+00 9.13E+00 8.56E+00 8.57E+00 3.07E+00 7.52E+00 9.27E+00 NA NA NA ND ND 9.13E+00 ND NA MW-39-124 MW-39-124 Q2-2011 Mid 012 124

-44 7/15/2011 11:44 2.30E+01 3.72E+02 4.39E+02 8.78E-01 1.19E+00 1.27E+00

-4.10E+00 1.13E+01 1.15E+01

-1.82E+00 9.51E+00 9.57E+00 NA NA NA 9.13E+00 MW-39-124 MW-39-124 Q3-2011 Mid 013 124

-44 8/29/2011 10:54

-1.02E+01 3.75E+02 4.45E+02 3.16E-01 1.12E+00 1.30E+00

-7.05E+00 1.06E+01 1.01E+01 7.76E+00 1.13E+01 1.46E+01 NA NA NA 9.13E+00 MW-39-124 MW-39-124 Q4-2011 014 124

-44 12/1/2011 11:42 1.73E+02 4.35E+02 4.89E+02

-2.58E-01 1.41E+00 1.82E+00 5.73E-01 7.95E+00 9.19E+00 2.71E+00 7.89E+00 9.85E+00 NA NA NA 9.13E+00 MW-39-124 MW-39-183 Q2-2011 011 182.5

-102.5 4/26/2011 11:35 1.15E+02 3.54E+02 4.02E+02 1.12E+00 1.56E+00 1.67E+00 6.46E+00 8.88E+00 1.09E+01

-1.52E+00 8.68E+00 8.94E+00 NA NA NA ND ND ND ND NA MW-39-183 MW-39-183 Q2-2011 Mid 012 182.5

-102.5 7/15/2011 11:49 7.02E+01 3.75E+02 4.35E+02 3.45E-01 1.03E+00 1.19E+00 2.51E+00 1.08E+01 1.22E+01

-2.37E+00 1.30E+01 1.37E+01 NA NA NA MW-39-183 MW-39-183 Q3-2011 Mid 013 182.5

-102.5 8/29/2011 10:45 1.14E+02 3.81E+02 4.33E+02 1.10E+00 1.13E+00 1.10E+00

-3.70E+00 1.05E+01 1.05E+01 5.90E+00 9.54E+00 1.22E+01 NA NA NA MW-39-183 MW-39-183 Q4-2011 014 182.5

-102.5 12/1/2011 11:26

-8.23E+01 4.11E+02 4.97E+02 1.34E-01 1.45E+00 1.80E+00

-2.81E+00 1.34E+01 1.59E+01 4.19E+00 8.16E+00 1.46E+01 NA NA NA MW-39-183 MW-39-195 Q2-2011 011 195

-115 4/26/2011 12:38 7.04E+03 8.04E+02 4.20E+02 1.88E+00 1.75E+00 1.79E+00

-2.03E+00 1.11E+01 1.28E+01 4.62E+00 8.70E+00 1.13E+01 NA NA NA 8.39E+03 1.88E+00 ND ND NA MW-39-195 MW-39-195 Q2-2011 Mid 012 195

-115 7/15/2011 11:13 4.19E+03 7.56E+02 4.35E+02 1.10E+00 1.78E+00 1.93E+00 2.79E+00 8.46E+00 9.76E+00 6.38E-01 1.01E+01 1.08E+01 NA NA NA 8.39E+03 1.88E+00 MW-39-195 MW-39-195 Q3-2011 Mid 013 195

-115 8/29/2011 10:51 1.72E+04 1.31E+03 4.43E+02 4.98E-02 7.50E-01 9.59E-01 7.98E-01 7.62E+00 8.56E+00 2.43E+00 8.19E+00 9.86E+00 NA NA NA 8.39E+03 1.88E+00 MW-39-195 MW-39-195 Q4-2011 014 195

-115 12/1/2011 11:28 5.13E+03 8.28E+02 4.87E+02 3.00E-01 1.46E+00 1.75E+00 2.12E+00 7.98E+00 1.03E+01 5.51E-01 9.48E+00 1.22E+01 NA NA NA 8.39E+03 1.88E+00 MW-39-195 MW-40-27 Q1-2011 014 26.7 46.5 3/8/2011 12:55 1.85E+02 2.56E+02 2.65E+02 1.58E-01 1.37E+00 1.61E+00 3.72E-01 6.78E+00 7.39E+00 2.83E+00 8.56E+00 9.99E+00 NA NA NA ND ND ND ND NA MW-40-27 MW-40-27 Q2-2011 015 26.7 46.5 4/29/2011 13:29 1.77E+02 3.66E+02 4.07E+02 1.18E+00 1.74E+00 1.87E+00 1.91E+00 8.40E+00 9.77E+00

-9.20E-01 9.86E+00 1.15E+01 NA NA NA MW-40-27 MW-40-27 Q2-2011 Mid 016 26.7 46.5 7/27/2011 15:12 3.69E+01 3.00E+02 3.43E+02

-4.37E-01 1.40E+00 1.93E+00

-2.18E+00 7.35E+00 7.64E+00 1.36E+00 9.03E+00 1.03E+01 NA NA NA MW-40-27 MW-40-27 Q4-2011 017 26.7 46.5 12/9/2011 11:50 2.24E+01 4.20E+02 4.90E+02 1.74E-01 1.46E+00 1.77E+00 7.86E-01 7.02E+00 8.97E+00 3.19E+00 7.14E+00 1.03E+01 NA NA NA MW-40-27 MW-40-46**

Q1-2011 015 46.2 27 3/8/2011 12:58 2.48E+02 2.74E+02 2.63E+02 1.03E-01 8.58E-01 1.07E+00 2.82E+00 8.00E+00 9.18E+00 7.99E+00 8.74E+00 1.19E+01 NA NA NA ND ND**

ND ND NA MW-40-46**

MW-40-46**

Q2-2011 016 46.2 27 4/29/2011 13:31 7.82E+01 3.54E+02 4.05E+02

-1.35E-01**

1.88E+00 1.77E+00

-9.96E-01 8.46E+00 9.00E+00

-3.98E+00 9.84E+00 9.04E+00 NA NA NA 2.83E+00 MW-40-46**

MW-40-46*

Q2-2011 Mid 017 46.2 27 7/27/2011 15:55 1.35E+02 3.09E+02 3.44E+02

-9.06E-01 1.26E+00 1.86E+00 2.28E+00 8.85E+00 1.01E+01 5.01E-01 9.30E+00 1.03E+01 NA NA NA 2.83E+00 MW-40-46*

MW-40-46*

Q4-2011 018 46.2 27 12/9/2011 12:03 9.00E+01 4.17E+02 4.77E+02 2.87E-01 1.62E+00 1.92E+00 1.26E+00 7.41E+00 9.46E+00

-9.20E-01 6.39E+00 8.16E+00 NA NA NA 2.83E+00 MW-40-46*

MW-40-81 Q1-2011 015 80.7

-7.5 3/8/2011 10:17 2.33E+02 2.68E+02 2.63E+02 8.50E-01 1.51E+00 1.67E+00 1.26E+00 1.06E+01 7.71E+00

-1.45E+00 6.08E+00 6.16E+00 NA NA NA ND ND ND ND NA MW-40-81 MW-40-81 Q2-2011 016 80.7

-7.5 4/29/2011 11:08 3.39E+02 4.12E+02 4.36E+02 1.07E+00 1.58E+00 1.70E+00 3.05E+00 6.90E+00 8.51E+00

-2.66E-01 8.04E+00 8.83E+00 NA NA NA MW-40-81 MW-40-81 Q2-2011 Mid 017 80.7

-7.5 7/27/2011 13:24

-1.18E+02 2.89E+02 3.48E+02 8.36E-01 1.70E+00 1.90E+00

-3.22E-01 6.48E+00 6.87E+00

-1.05E+00 8.67E+00 8.91E+00 NA NA NA MW-40-81 MW-40-81 Q4-2011 018 80.7

-7.5 12/9/2011 10:23

-8.05E+01 4.02E+02 4.86E+02 3.77E-01 1.51E+00 1.79E+00 4.60E-01 2.64E+01 1.18E+01 1.07E+00 1.07E+01 1.39E+01 NA NA NA MW-40-81 MW-40-100*

Q1-2011 017 100.2

-27 3/8/2011 10:27 5.17E+01 2.14E+02 2.64E+02 2.52E-02 1.30E+00 1.58E+00 2.46E+01*

1.35E+01 7.66E+00

-1.40E+00 7.88E+00 8.30E+00 NA NA NA ND ND ND*

ND NA MW-40-100*

MW-40-100*

Q2-2011 018 100.2

-27 4/29/2011 11:27 2.70E+02 4.06E+02 4.38E+02 2.46E-01 1.42E+00 1.67E+00 5.53E+00 7.14E+00 9.23E+00 2.99E+00 7.96E+00 9.80E+00 NA NA NA 2.46E+01 MW-40-100*

MW-40-100*

Q2-2011 Mid 019 100.2

-27 7/27/2011 13:29 1.07E+02 3.12E+02 3.50E+02

-9.50E-01 1.41E+00 1.98E+00 2.29E+00 9.03E+00 1.04E+01 7.10E-01 1.08E+01 1.20E+01 NA NA NA 2.46E+01 MW-40-100*

MW-40-100*

Q4-2011 020 100.2

-27 12/9/2011 10:28 4.85E+01 4.29E+02 5.00E+02 1.04E+00 1.37E+00 1.41E+00 1.85E+00 7.98E+00 9.93E+00 8.66E-01 7.77E+00 1.01E+01 NA NA NA 2.46E+01 MW-40-100*

MW-40-127*

Q1-2011 017 127.2

-54 3/8/2011 10:41 1.33E+02 2.40E+02 2.64E+02 1.03E+00 1.40E+00 1.51E+00 5.07E+01*

1.64E+01 7.63E+00 3.45E-01 7.18E+00 7.96E+00 NA NA NA ND ND ND*

ND NA MW-40-127*

MW-40-127*

Q2-2011 018 127.2

-54 4/29/2011 11:26

-2.27E+01 3.60E+02 4.32E+02 5.72E-01 1.78E+00 2.05E+00

-2.13E-01 8.26E+00 8.83E+00

-1.62E+00 9.68E+00 9.87E+00 NA NA NA 5.07E+01 MW-40-127*

MW-40-127*

Q2-2011 Mid 019 127.2

-54 7/27/2011 13:56 1.56E+02 3.15E+02 3.50E+02 4.81E-01 1.64E+00 1.92E+00 1.48E+00 9.06E+00 1.03E+01

-8.00E+00 1.02E+01 7.94E+00 NA NA NA 5.07E+01 MW-40-127*

MW-40-127*

Q4-2011 020 127.2

-54 12/9/2011 10:40 5.65E+01 4.08E+02 4.71E+02 1.27E+00 1.50E+00 1.51E+00

-1.26E+00 8.91E+00 1.04E+01

-3.35E+00 9.18E+00 1.04E+01 NA NA NA 5.07E+01 MW-40-127*

MW-40-162 Q1-2011 015 161.7

-88.5 3/8/2011 11:02 8.33E+01 2.24E+02 2.63E+02

-1.03E+00 1.07E+00 1.57E+00

-3.72E+00 6.12E+00 5.93E+00

-2.11E+00 6.42E+00 6.37E+00 NA NA NA ND ND ND ND NA MW-40-162 MW-40-162 Q2-2011 016 161.7

-88.5 4/29/2011 12:26 1.05E+02 3.78E+02 4.33E+02 8.71E-01 1.34E+00 1.46E+00 4.54E+00 1.23E+01 1.42E+01 4.43E-01 9.50E+00 1.08E+01 NA NA NA MW-40-162 MW-40-162 Q2-2011 Mid 017 161.7

-88.5 7/27/2011 14:40 5.54E+00 2.97E+02 3.44E+02

-8.61E-01 1.58E+00 1.98E+00

-2.44E+00 9.21E+00 8.54E+00

-6.93E-01 8.70E+00 9.41E+00 NA NA NA MW-40-162 MW-40-162 Q4-2011 018 161.7

-88.5 12/9/2011 11:02

-2.60E+01 3.42E+02 4.06E+02 6.89E-01 1.75E+00 1.95E+00 1.06E+00 8.43E+00 1.07E+01

-4.71E+00 1.17E+01 1.30E+01 NA NA NA MW-40-162 MW-41-40 Q1-2011 019 34.4 20.5 2/14/2011 14:05 2.03E+03 4.02E+02 2.98E+02 1.15E+01 2.68E+00 1.83E+00 4.60E+00 7.30E+00 8.61E+00 4.22E+00 7.36E+00 9.28E+00 NA NA NA 1.69E+03 5.43E+00 ND ND NA MW-41-40 MW-41-40 Q2-2011 020 34.4 20.5 4/20/2011 13:51 4.51E+03 7.36E+02 4.55E+02 2.32E+00 1.57E+00 1.44E+00 2.20E+00 9.22E+00 1.06E+01 3.02E+00 1.06E+01 1.25E+01 NA NA NA 1.69E+03 5.43E+00 MW-41-40 MW-41-40 Q2-2011 Mid 021 34.4 20.5 7/15/2011 12:30 6.99E+02 4.59E+02 4.41E+02 2.48E+00 1.35E+00 1.19E+00

-1.93E+00 1.09E+01 1.14E+01

-1.11E+00 8.94E+00 9.13E+00 NA NA NA 1.69E+03 5.43E+00 MW-41-40 MW-41-40 Q3-2011 022 34.4 20.5 8/4/2011 14:39 5.94E+02 3.57E+02 3.53E+02 1.70E+00 1.87E+00 1.93E+00 4.91E-01 5.97E+00 6.61E+00

-6.02E-02 8.16E+00 8.80E+00 NA NA NA 1.69E+03 5.43E+00 MW-41-40 MW-41-40 Q4-2011 023 34.4 20.5 11/28/2011 14:25 6.16E+02 5.13E+02 5.14E+02 6.83E-01 1.73E+00 1.95E+00 6.21E+00 8.16E+00 1.13E+01

-4.82E+00 9.81E+00 1.11E+01 NA NA NA 1.69E+03 5.43E+00 MW-41-40 MW-41-63 Q1-2011 018 59.5

-4.6 2/14/2011 13:37 1.23E+03 4.44E+02 3.80E+02 6.92E+00 2.46E+00 1.96E+00 1.24E+00 5.30E+00 6.03E+00 2.69E+00 6.06E+00 7.29E+00 NA NA NA 8.01E+02 4.98E+00 ND ND NA MW-41-63 MW-41-63 Q2-2011 019 59.5

-4.6 4/20/2011 13:13 7.58E+02 4.90E+02 4.72E+02

-7.72E-01 1.51E+00 2.03E+00 3.53E+00 8.52E+00 1.01E+01 4.02E+00 8.74E+00 1.09E+01 NA NA NA 8.01E+02 4.98E+00 MW-41-63 MW-41-63 Q2-2011 Mid 020 59.5

-4.6 7/15/2011 12:51 7.14E+02 4.56E+02 4.35E+02 3.03E+00 1.50E+00 1.30E+00 2.36E+00 7.71E+00 8.88E+00 4.47E-01 6.81E+00 7.51E+00 NA NA NA 8.01E+02 4.98E+00 MW-41-63 MW-41-63 Q3-2011 021 59.5

-4.6 8/4/2011 14:20 6.60E+02 3.60E+02 3.51E+02 1.91E+00 1.95E+00 1.96E+00 1.64E+00 7.89E+00 8.72E+00

-1.43E+00 7.29E+00 7.72E+00 NA NA NA 8.01E+02 4.98E+00 MW-41-63 MW-41-63 Q4-2011 022 59.5

-4.6 11/28/2011 14:08 6.41E+02 5.22E+02 5.22E+02 6.76E-01 1.73E+00 1.95E+00

-7.79E-01 7.20E+00 8.56E+00

-9.03E-01 7.41E+00 9.17E+00 NA NA NA 8.01E+02 4.98E+00 MW-41-63 MW-42-49 Q1-2011 024 42.6 27.1 3/4/2011 11:37 1.49E+03 5.14E+02 3.88E+02 2.32E+01 3.34E+00 1.11E+00 3.30E+04 4.42E+03 2.75E+01 1.42E+00 6.78E+00 7.87E+00 3.02E+02 3.04E+01 2.00E+01 1.34E+03 1.04E+01 1.83E+04 ND 2.07E+02 MW-42-49 MW-42-49 Q2-2011 025 42.6 27.1 4/21/2011 14:04 1.71E+03 5.88E+02 4.80E+02 5.45E+00 2.18E+00 1.45E+00 2.15E+04 2.88E+03 2.08E+01 3.41E+00 9.16E+00 1.09E+01 1.90E+02 2.72E+01 1.73E+01 1.34E+03 1.04E+01 1.83E+04 2.07E+02 MW-42-49 MW-42-49 Q3-2011 027 42.6 27.1 8/1/2011 12:50 7.78E+02 3.90E+02 3.74E+02 2.60E+00 1.92E+00 1.82E+00 1.57E+04 1.92E+03 2.16E+01 3.58E+00 8.40E+00 1.01E+01 2.80E+02 3.48E+01 2.02E+01 1.34E+03 1.04E+01 1.83E+04 2.07E+02 MW-42-49 MW-42-49 Q4-2011 028 42.6 27.1 11/3/2011 11:13 1.40E+03 5.70E+02 5.00E+02 8.98E-01 1.51E+00 1.65E+00 3.03E+03 3.90E+02 1.29E+01

-1.75E+00 7.56E+00 9.18E+00 5.77E+01 1.57E+01 1.45E+01 1.34E+03 1.04E+01 1.83E+04 2.07E+02 MW-42-49 MW-42-78 Q1-2011 019 74

-4.3 3/4/2011 10:58 5.98E+02 4.06E+02 3.84E+02 8.92E-01 1.47E+00 1.60E+00

-2.03E+00 6.72E+00 6.99E+00 8.03E-02 6.70E+00 7.41E+00 0.00E+00 1.73E+01 1.96E+01 5.40E+02 ND ND ND ND MW-42-78 MW-42-78 Q2-2011 020 74

-4.3 4/21/2011 13:45 6.26E+02 4.78E+02 4.77E+02 4.25E-01 1.13E+00 1.32E+00

-9.71E-01 9.16E+00 9.83E+00 3.58E+00 8.56E+00 1.11E+01 5.89E-01 1.49E+01 1.72E+01 5.40E+02 MW-42-78 MW-42-78 Q3-2011 022 74

-4.3 8/1/2011 12:50 3.97E+02 3.57E+02 3.72E+02

-1.16E-01 1.13E+00 1.49E+00 5.85E-01 7.98E+00 7.65E+00

-5.68E-01 9.45E+00 1.03E+01 1.02E+00 1.17E+01 1.31E+01 5.40E+02 MW-42-78 MW-42-78 Q4-2011 023 74

-4.3 11/3/2011 11:31 3.23E+02 4.65E+02 5.02E+02

-5.46E-02 1.15E+00 1.49E+00

-2.93E+00 7.32E+00 8.03E+00 1.37E-01 7.74E+00 9.98E+00

-2.26E+00 1.18E+01 1.35E+01 5.40E+02 MW-42-78 MW-43-28 Q1-2011 018 23.5 25.3 2/15/2011 13:08 2.54E+02 2.80E+02 2.99E+02

-1.06E+00 1.40E+00 2.00E+00 5.75E-02 1.26E+01 7.06E+00

-3.84E+00 6.84E+00 6.54E+00 NA NA NA ND ND ND ND NA MW-43-28 MW-43-28 Q2-2011 019 23.5 25.3 4/21/2011 11:15 2.34E+02 4.30E+02 4.72E+02 1.46E+00 1.96E+00 2.04E+00

-9.31E-01 8.74E+00 9.22E+00 4.50E+00 8.60E+00 1.09E+01 NA NA NA MW-43-28 MW-43-28 Q3-2011 020 23.5 25.3 8/4/2011 11:15 2.26E+02 3.24E+02 3.50E+02

-1.34E-01 1.42E+00 1.87E+00 4.00E+00 7.35E+00 9.02E+00

-3.51E+00 9.33E+00 9.21E+00 NA NA NA MW-43-28 MW-43-28 Q4-2011 021 23.5 25.3 11/22/2011 11:23 1.21E+02 3.60E+02 4.05E+02 1.40E+00 1.81E+00 1.95E+00

-9.87E-02 5.58E+00 7.14E+00

-3.96E+00 8.07E+00 8.55E+00 NA NA NA MW-43-28 MW-43-62 Q1-2011 018 51

-2.2 2/15/2011 13:15 1.82E+02 2.76E+02 3.00E+02 7.75E-01 1.74E+00 1.95E+00 6.59E-01 5.08E+00 5.56E+00

-2.37E-01 5.16E+00 5.52E+00 NA NA NA ND ND ND ND NA MW-43-62 MW-43-62 Q2-2011 019 51

-2.2 4/21/2011 11:00 1.05E+02 4.12E+02 4.72E+02

-4.65E-01 1.67E+00 2.18E+00

-1.90E+00 9.08E+00 9.35E+00

-2.34E+00 8.70E+00 8.43E+00 NA NA NA MW-43-62 MW-43-62 Q3-2011 021 51

-2.2 8/4/2011 11:35 1.66E+02 3.21E+02 3.55E+02

-2.14E-01 1.61E+00 1.93E+00

-1.62E+00 7.95E+00 8.00E+00

-2.98E+00 8.13E+00 8.75E+00 NA NA NA MW-43-62 MW-43-62 Q4-2011 022 51

-2.2 11/22/2011 12:22 2.01E+02 3.72E+02 4.10E+02 9.55E-01 1.78E+00 1.96E+00

-1.43E+01 1.42E+01 1.67E+01 1.94E+00 1.06E+01 1.41E+01 NA NA NA MW-43-62 MW-44-66 Q1-2011 019 62.4 31.1 2/18/2011 10:41 4.57E+02 3.90E+02 3.99E+02

-2.94E-01 1.59E+00 1.95E+00 1.74E+00 7.72E+00 8.56E+00

-1.40E+00 7.92E+00 8.46E+00 NA NA NA 8.10E+02 ND ND ND NA MW-44-66 MW-44-66 Q2-2011 020 62.4 31.1 4/26/2011 13:17 6.87E+02 4.20E+02 4.03E+02 7.05E-01 1.52E+00 1.70E+00

-1.14E-01 9.36E+00 1.03E+01 3.29E+00 1.07E+01 1.31E+01 NA NA NA 8.10E+02 MW-44-66 MW-44-66 Q2-2011 Mid 021 62.4 31.1 7/19/2011 15:39 1.62E+03 5.49E+02 4.32E+02

-7.04E-01 6.48E-01 1.06E+00 4.61E+00 9.66E+00 1.16E+01

-5.76E+00 1.11E+01 9.79E+00 NA NA NA 8.10E+02 MW-44-66 MW-44-66 Q3-2011 022 62.4 31.1 8/22/2011 12:08 4.76E+02 4.32E+02 4.45E+02 1.13E-01 9.03E-01 1.11E+00

-7.41E+00 8.73E+00 6.89E+00

-3.14E+00 9.09E+00 9.07E+00 NA NA NA 8.10E+02 MW-44-66 MW-44-66 Q4-2011 023 62.4 31.1 12/8/2011 12:00 3.70E+02 3.84E+02 4.04E+02

-8.25E-01 1.44E+00 1.94E+00 1.99E+00 7.35E+00 9.30E+00 2.32E+00 7.56E+00 1.04E+01 NA NA NA 8.10E+02 MW-44-66 MW-44-102 Q1-2011 020 80 13.5 2/18/2011 10:44 3.93E+02 2.90E+02 2.97E+02 2.63E-01 1.86E+00 2.15E+00 2.22E-01 4.96E+00 5.47E+00

-2.93E-01 6.02E+00 6.58E+00 NA NA NA 7.15E+02 ND ND ND NA MW-44-102 MW-44-102 Q2-2011 021 80 13.5 4/26/2011 12:18 6.70E+02 4.14E+02 3.99E+02 1.09E+00 1.41E+00 1.49E+00 3.59E-01 7.42E+00 8.15E+00

-2.06E+00 7.86E+00 7.82E+00 NA NA NA 7.15E+02 MW-44-102 MW-44-102 Q2-2011 Mid 022 80 13.5 7/19/2011 10:53 6.38E+02 4.50E+02 4.39E+02 2.55E-01 1.02E+00 1.19E+00 1.01E+00 6.63E+00 7.60E+00 1.28E+00 6.27E+00 7.47E+00 NA NA NA 7.15E+02 MW-44-102 MW-44-102 Q3-2011 023 80 13.5 8/22/2011 10:43 8.25E+02 4.77E+02 4.57E+02

-1.10E-01 9.69E-01 1.28E+00

-3.22E+00 6.69E+00 6.63E+00 8.99E+00 7.50E+00 1.08E+01 NA NA NA 7.15E+02 MW-44-102 MW-44-102 Q4-2011 024 80 13.5 12/1/2011 12:18 1.05E+03 4.50E+02 4.07E+02

-2.13E-01 1.52E+00 1.93E+00

-7.91E-02 8.73E+00 1.04E+01

-5.88E-01 9.33E+00 1.15E+01 NA NA NA 7.15E+02 MW-44-102 MW-45-42 Q1-2011 023 37 16.6 2/16/2011 16:58 8.12E+03 7.86E+02 3.63E+02 1.03E+00 1.39E+00 1.48E+00

-8.53E-01 5.64E+00 5.99E+00 1.42E+00 6.30E+00 7.17E+00 NA NA NA 1.70E+04 ND ND ND NA MW-45-42 MW-45-42 Q2-2011 024 37 16.6 4/20/2011 14:09 8.56E+03 1.03E+03 4.65E+02 1.45E+00 1.56E+00 1.61E+00 7.04E-01 6.50E+00 7.46E+00 7.13E+00 1.07E+01 1.29E+01 NA NA NA 1.70E+04 MW-45-42 MW-45-42 Q2-2011 Mid 025 37 16.6 7/25/2011 13:23 3.94E+04 2.07E+03 4.36E+02 1.14E+00 1.30E+00 1.37E+00 3.09E+00 7.41E+00 8.65E+00

-2.66E+00 1.01E+01 1.05E+01 NA NA NA 1.70E+04 MW-45-42 MW-45-42 Q3-2011 Mid 026 37 16.6 8/23/2011 13:58 2.72E+04 1.63E+03 4.50E+02 1.77E-01 9.15E-01 1.10E+00 8.73E-01 1.12E+01 1.05E+01

-7.52E+00 1.06E+01 8.89E+00 NA NA NA 1.70E+04 MW-45-42 MW-45-42 Q4-2011 027 37 16.6 11/28/2011 15:03 1.65E+03 6.27E+02 5.10E+02 8.10E-01 1.75E+00 1.95E+00 1.21E+00 5.94E+00 7.69E+00

-2.64E+00 6.96E+00 7.84E+00 NA NA NA 1.70E+04 MW-45-42 MW-45-61 Q1-2011 023 58

-4.4 2/16/2011 16:15 1.84E+03 5.20E+02 3.98E+02

-2.25E-01 1.64E+00 1.96E+00 1.38E+00 4.80E+00 5.41E+00 9.89E-01 5.46E+00 6.15E+00 NA NA NA 3.49E+03 ND ND ND NA MW-45-61 MW-45-61 Q2-2011 024 58

-4.4 4/20/2011 10:07 2.03E+03 6.12E+02 4.74E+02 7.22E-01 1.36E+00 1.51E+00

-4.02E+00 7.76E+00 7.55E+00

-8.47E-01 7.56E+00 7.91E+00 NA NA NA 3.49E+03 MW-45-61 MW-45-61 Q2-2011 Mid 025 58

-4.4 7/25/2011 10:00 5.63E+03 8.49E+02 4.33E+02 9.47E-01 1.19E+00 1.25E+00 1.42E+00 5.79E+00 6.69E+00 2.07E+00 8.34E+00 9.68E+00 NA NA NA 3.49E+03 MW-45-61 MW-45-61 Q3-2011 Mid 026 58

-4.4 8/23/2011 10:48 5.91E+03 8.13E+02 4.34E+02 7.01E-01 1.16E+00 1.26E+00

-8.68E-01 7.44E+00 7.90E+00 1.84E+00 6.63E+00 7.89E+00 NA NA NA 3.49E+03 MW-45-61 MW-45-61 Q4-2011 027 58

-4.4 11/28/2011 11:44 2.06E+03 6.72E+02 5.16E+02 4.76E-01 1.70E+00 1.97E+00 3.28E-01 7.41E+00 9.39E+00

-6.01E-01 9.42E+00 1.19E+01 NA NA NA 3.49E+03 MW-45-61

TABLE 3 FOURTH QUARTER 2011 GROUNDWATER ANALYTICAL RESULTS AND AVERAGES INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q42011 FINAL Table 3 - Forth Quarter 2011 Groundwater Analytical Results and Averages.xlsx; Q42011 Table 3 Page 3 of 7 See Page 7 for Notes TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Date Time Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Average Average Average Average Average ANALYSIS RESULTS5 YEARLY ROLLING AVERAGES4,6 Well ID1 TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

SAMPLE COLLECTION Well ID1 SAMPLING QUARTER2,8 SAMPLE ID SAMPLE ZONE CENTER Depth Ft Below Top of Casing3 SAMPLE ZONE CENTER Elevation Ft msl3 MW-46 Q1-2011 023 10.5 7.6 2/23/2011 12:46 2.47E+03 5.70E+02 3.98E+02 1.12E+00 1.89E+00 2.06E+00

-2.22E+00 5.28E+00 5.28E+00 5.21E-01 5.10E+00 5.66E+00 NA NA NA 3.28E+03 ND ND ND NA MW-46 MW-46 Q2-2011 024 10.5 7.6 4/25/2011 11:19 5.25E+03 7.54E+02 3.95E+02 1.48E+00 1.72E+00 1.80E+00

-2.48E+00 7.24E+00 7.06E+00

-4.44E+00 7.44E+00 6.77E+00 NA NA NA 3.28E+03 MW-46 MW-46 Q2-2011 Mid 025 10.5 7.6 7/13/2011 13:29 3.08E+03 7.17E+02 2.86E+02 8.44E-01 1.19E+00 1.26E+00 3.71E+00 8.64E+00 1.04E+01

-9.54E-01 1.02E+01 1.08E+01 NA NA NA 3.28E+03 MW-46 MW-46 Q3-2011 026 10.5 7.6 8/17/2011 11:36 3.30E+03 6.72E+02 4.50E+02 8.77E-01 1.21E+00 1.29E+00 3.43E-01 7.86E+00 8.82E+00

-1.10E+00 7.50E+00 7.97E+00 NA NA NA 3.28E+03 MW-46 MW-46 Q4-2011 027 10.5 7.6 10/20/2011 13:35 2.28E+03 4.68E+02 3.46E+02 3.95E-01 1.30E+00 1.52E+00

-4.36E+00 8.19E+00 8.94E+00

-1.03E+00 8.07E+00 1.01E+01 NA NA NA 3.28E+03 MW-46 MW-47-56 Q2-2011 Mid 006 53.2 17.1 7/6/2011 15:32 3.52E+03 6.57E+02 4.48E+02 4.63E-01 1.08E+00 1.22E+00

-1.56E+00 1.11E+01 1.20E+01 1.45E-01 7.41E+00 8.25E+00

-1.99E+01 2.17E+01 2.50E+01 3.12E+03 ND ND ND ND MW-47-56 MW-47-56 Q3-2011 Mid 007 53.2 17.1 8/18/2011 12:39 5.42E+02 2.76E+02 2.00E+02 1.03E+00 1.28E+00 1.31E+00

-8.54E-01 1.13E+01 1.25E+01 3.86E+00 8.64E+00 1.07E+01

-2.22E+00 1.75E+01 2.00E+01 3.12E+03 MW-47-56 MW-47-56 Q4-2011 008 53.2 17.1 10/28/2011 11:36 5.31E+03 8.52E+02 4.99E+02

-6.21E-01 8.79E-01 1.40E+00 1.34E+00 8.85E+00 1.07E+01 2.06E-01 1.01E+01 1.29E+01

-6.21E+00 1.24E+01 1.44E+01 3.12E+03 MW-47-56 MW-47-80 Q2-2011 Mid 005 74

-3.7 7/6/2011 14:37 1.36E+05 3.36E+03 4.50E+02 1.95E+00 1.33E+00 1.22E+00

-1.57E+00 8.37E+00 8.73E+00

-3.43E+00 7.80E+00 7.13E+00 3.07E+00 2.59E+01 2.89E+01 1.23E+05 2.04E+00 ND ND ND MW-47-80 MW-47-80 Q3-2011 Mid 006 74

-3.7 8/18/2011 11:36 1.37E+05 4.08E+03 2.18E+02 8.23E-01 1.22E+00 1.29E+00

-5.83E+00 9.30E+00 8.60E+00

-6.32E-01 8.79E+00 9.27E+00

-1.15E+00 1.88E+01 2.15E+01 1.23E+05 2.04E+00 MW-47-80 MW-47-80 Q4-2011 007 74

-3.7 10/28/2011 13:24 9.68E+04 3.21E+03 5.07E+02 2.13E+00 1.58E+00 1.38E+00

-1.35E+00 6.54E+00 7.91E+00 1.21E+00 6.45E+00 8.88E+00 3.54E+00 1.31E+01 1.46E+01 1.23E+05 2.04E+00 MW-47-80 MW-49-26 Q1-2011 023 19.1

-4.4 1/28/2011 13:37 3.17E+03 6.00E+02 4.29E+02 1.30E+01 2.86E+00 2.01E+00 3.39E-01 1.04E+01 7.00E+00

-2.43E+00 6.42E+00 6.44E+00

-4.38E+00 1.87E+01 2.20E+01 3.84E+03 1.27E+01 ND ND ND MW-49-26 MW-49-26 Q2-2011 024 19.1

-4.4 4/15/2011 11:58 3.29E+03 7.18E+02 4.80E+02 1.26E+01 3.06E+00 1.91E+00 4.75E+00 1.07E+01 1.27E+01 4.03E+00 1.20E+01 1.47E+01 1.81E+00 1.50E+01 1.72E+01 3.84E+03 1.27E+01 MW-49-26 MW-49-26 Q3-2011 025 19.1

-4.4 8/10/2011 10:46 3.97E+03 6.39E+02 2.00E+02 1.26E+01 2.89E+00 1.34E+00

-1.94E+00 9.06E+00 9.33E+00 2.94E+00 8.31E+00 1.00E+01

-1.77E+01 2.04E+01 2.57E+01 3.84E+03 1.27E+01 MW-49-26 MW-49-26 Q4-2011 026 19.1

-4.4 11/4/2011 11:50 4.92E+03 8.37E+02 5.06E+02 1.27E+01 2.95E+00 1.25E+00 2.60E+00 1.11E+01 7.92E+00 5.17E+00 8.04E+00 1.17E+01

-2.73E+00 1.26E+01 1.44E+01 3.84E+03 1.27E+01 MW-49-26 MW-49-42 Q1-2011 023 38.1

-23.4 1/28/2011 13:00 2.45E+03 5.38E+02 3.86E+02 2.30E+01 4.02E+00 2.02E+00

-1.07E+00 5.74E+00 6.21E+00

-2.45E+00 5.50E+00 5.32E+00

-3.26E+00 1.86E+01 2.18E+01 3.27E+03 1.90E+01 ND ND ND MW-49-42 MW-49-42 Q2-2011 024 38.1

-23.4 4/15/2011 11:55 1.90E+03 6.04E+02 4.78E+02 1.57E+01 3.34E+00 2.07E+00

-6.72E+00 7.62E+00 6.17E+00 1.15E-01 7.72E+00 8.33E+00 6.68E+00 1.55E+01 1.73E+01 3.27E+03 1.90E+01 MW-49-42 MW-49-42 Q3-2011 025 38.1

-23.4 8/10/2011 11:16 3.83E+03 6.21E+02 1.96E+02 1.61E+01 3.24E+00 1.64E+00

-1.22E+00 8.94E+00 9.69E+00

-3.72E+00 8.79E+00 8.23E+00

-1.40E+01 1.81E+01 2.15E+01 3.27E+03 1.90E+01 MW-49-42 MW-49-42 Q4-2011 026 38.1

-23.4 11/4/2011 11:43 4.91E+03 8.19E+02 4.90E+02 2.11E+01 3.90E+00 1.51E+00 5.99E-01 1.87E+01 1.10E+01

-3.91E+00 1.04E+01 1.20E+01 4.27E+00 1.30E+01 1.45E+01 3.27E+03 1.90E+01 MW-49-42 MW-49-65 Q1-2011 023 60

-45.4 1/28/2011 13:15 1.94E+03 5.02E+02 3.85E+02 1.15E+01 3.28E+00 2.06E+00

-6.30E-01 4.96E+00 5.21E+00 7.15E-01 5.20E+00 5.81E+00

-9.08E+00 1.83E+01 2.20E+01 2.75E+03 1.48E+01 ND ND ND MW-49-65 MW-49-65 Q2-2011 024 60

-45.4 4/15/2011 11:50 2.38E+03 6.48E+02 4.81E+02 1.62E+01 3.12E+00 1.60E+00 2.59E+00 9.66E+00 1.12E+01 4.62E-02 1.01E+01 1.10E+01 4.11E+00 1.49E+01 1.68E+01 2.75E+03 1.48E+01 MW-49-65 MW-49-65 Q3-2011 025 60

-45.4 8/10/2011 10:55 2.43E+03 5.10E+02 2.00E+02 1.14E+01 2.75E+00 1.42E+00 1.12E-01 7.77E+00 8.40E+00

-4.19E+00 9.00E+00 8.02E+00

-6.91E-01 1.81E+01 2.05E+01 2.75E+03 1.48E+01 MW-49-65 MW-49-65 Q4-2011 026 60

-45.4 11/4/2011 11:47 4.24E+03 7.23E+02 4.64E+02 2.02E+01 3.60E+00 1.47E+00

-4.27E+00 8.88E+00 9.11E+00

-6.56E-01 9.45E+00 1.15E+01 7.03E-01 1.21E+01 1.36E+01 2.75E+03 1.48E+01 MW-49-65 MW-50-42 Q1-2011 024 42

-27.1 2/25/2011 12:36 5.61E+02 3.88E+02 3.85E+02 5.42E+00 2.34E+00 1.91E+00

-1.29E-01 5.46E+00 5.88E+00

-9.07E-01 4.42E+00 4.42E+00

-7.19E+00 1.82E+01 2.18E+01 1.46E+03 1.15E+01 ND ND ND MW-50-42 MW-50-42 Q2-2011 025 42

-27.1 5/3/2011 12:05 3.77E+03 5.58E+02 3.41E+02 9.53E+00 2.20E+00 1.04E+00 1.92E+00 9.44E+00 1.07E+01 5.79E-01 1.02E+01 1.16E+01 5.86E-01 1.69E+01 1.92E+01 1.46E+03 1.15E+01 MW-50-42 MW-50-42 Q2-2011 Mid 026 42

-27.1 7/25/2011 12:18 1.03E+03 4.89E+02 4.43E+02 3.01E+00 2.09E+00 2.02E+00

-1.11E+00 7.86E+00 8.36E+00 6.63E-02 8.16E+00 9.04E+00 3.81E+00 1.71E+01 1.91E+01 1.46E+03 1.15E+01 MW-50-42 MW-50-42 Q3-2011 027 42

-27.1 8/19/2011 12:10 9.52E+02 3.42E+02 2.00E+02 9.47E+00 2.60E+00 1.31E+00 2.17E+00 8.01E+00 9.07E+00 4.72E+00 9.81E+00 1.22E+01

-7.08E+00 1.81E+01 2.10E+01 1.46E+03 1.15E+01 MW-50-42 MW-50-42 Q4-2011 028 42

-27.1 10/27/2011 10:48 9.99E+02 5.25E+02 4.92E+02 3.02E+01 4.44E+00 1.54E+00 1.76E+00 7.11E+00 9.22E+00

-2.60E+00 8.01E+00 9.51E+00

-5.76E+00 1.21E+01 1.41E+01 1.46E+03 1.15E+01 MW-50-42 MW-50-66 Q1-2011 029 60

-45.1 2/25/2011 12:36 3.76E+03 6.18E+02 3.83E+02 2.61E+01 4.02E+00 2.13E+00 2.94E+00 7.20E+00 8.24E+00 6.79E-01 8.00E+00 9.10E+00

-2.80E+00 1.81E+01 2.12E+01 5.99E+03 2.62E+01 ND ND ND MW-50-66 MW-50-66 Q2-2011 030 60

-45.1 5/3/2011 12:07 4.73E+03 6.12E+02 3.45E+02 2.63E+01 3.30E+00 1.08E+00 0.00E+00 1.77E+01 9.05E+00

-2.32E+00 9.06E+00 9.12E+00 8.43E+00 1.70E+01 1.88E+01 5.99E+03 2.62E+01 MW-50-66 MW-50-66 Q2-2011 Mid 031 60

-45.1 7/25/2011 12:26 6.50E+03 8.73E+02 4.48E+02 2.61E+01 4.08E+00 1.35E+00

-4.59E-01 7.02E+00 7.74E+00 3.81E+00 8.55E+00 1.07E+01 1.02E+01 1.66E+01 1.81E+01 5.99E+03 2.62E+01 MW-50-66 MW-50-66 Q3-2011 032 60

-45.1 8/19/2011 12:12 7.15E+03 8.49E+02 2.00E+02 2.57E+01 4.05E+00 1.65E+00 3.97E+00 8.46E+00 1.01E+01 1.73E+00 9.03E+00 1.05E+01

-8.92E+00 1.80E+01 2.11E+01 5.99E+03 2.62E+01 MW-50-66 MW-50-66 Q4-2011 033 60

-45.1 10/27/2011 10:53 7.83E+03 9.87E+02 4.94E+02 2.66E+01 4.35E+00 1.59E+00

-6.49E-01 8.64E+00 1.02E+01 1.01E+01 1.01E+01 1.49E+01

-4.90E+00 1.66E+01 1.92E+01 5.99E+03 2.62E+01 MW-50-66 MW-51-40 Q1-2011 018 39.7 28 3/8/2011 10:18 1.02E+02 2.34E+02 2.67E+02 1.07E+00 1.51E+00 1.61E+00

-7.97E+00 1.21E+01 1.36E+01 2.42E+00 7.30E+00 8.76E+00 NA NA NA ND ND ND ND NA MW-51-40 MW-51-40 Q2-2011 019 39.7 28 4/29/2011 10:41 3.63E+02 4.14E+02 4.35E+02 2.26E-01 1.37E+00 1.59E+00

-3.40E+00 9.48E+00 9.62E+00 6.20E+00 1.11E+01 1.40E+01 NA NA NA MW-51-40 MW-51-40 Q3-2011 020 39.7 28 7/28/2011 11:43 3.78E+01 3.06E+02 3.52E+02

-2.51E-01 1.37E+00 1.85E+00

-2.58E+00 1.35E+01 1.68E+01

-3.37E+00 9.33E+00 9.05E+00 NA NA NA MW-51-40 MW-51-40 Q4-2011 021 39.7 28 12/12/2011 10:43 1.86E+02 3.06E+02 3.28E+02

-7.34E-01 1.58E+00 1.94E+00

-5.53E+00 8.49E+00 9.48E+00 4.82E+00 7.89E+00 1.18E+01

-3.48E+00 1.39E+01 1.58E+01 MW-51-40 MW-51-79 Q1-2011 018 78.7

-11 3/8/2011 10:34 1.36E+02 2.46E+02 2.70E+02

-2.03E-01 1.22E+00 1.53E+00 2.42E+00 5.42E+00 6.52E+00

-2.74E+00 7.36E+00 6.45E+00 NA NA NA ND ND ND ND NA MW-51-79 MW-51-79 Q2-2011 019 78.7

-11 4/29/2011 10:57 1.17E+02 3.82E+02 4.33E+02 1.03E+00 1.67E+00 1.82E+00

-4.93E-01 7.56E+00 8.23E+00

-8.38E-01 8.08E+00 8.53E+00 NA NA NA MW-51-79 MW-51-79 Q3-2011 020 78.7

-11 7/28/2011 11:55

-1.93E+01 3.09E+02 3.60E+02 1.36E-01 1.63E+00 1.96E+00 2.20E+00 8.28E+00 9.43E+00

-5.24E-01 9.27E+00 9.93E+00 NA NA NA MW-51-79 MW-51-79 Q4-2011 021 78.7

-11 12/12/2011 11:09 1.50E+02 2.95E+02 3.29E+02

-1.38E-01 1.52E+00 1.90E+00

-3.25E+00 7.98E+00 8.95E+00

-3.01E-01 7.62E+00 9.88E+00

-1.12E+00 1.13E+01 1.27E+01 MW-51-79 MW-51-104 Q1-2011 016 103.7

-36 3/8/2011 12:10 5.76E+01 3.10E+02 3.55E+02 8.91E-01 1.47E+00 1.60E+00 2.54E+00 7.20E+00 8.14E+00 9.02E-01 5.50E+00 6.24E+00 NA NA NA ND ND ND ND NA MW-51-104 MW-51-104 Q2-2011 017 103.7

-36 4/29/2011 12:35 1.97E+02 3.90E+02 4.32E+02 1.41E+00 1.45E+00 1.48E+00

-1.90E+00 1.08E+01 1.25E+01

-6.79E-01 1.10E+01 1.20E+01 NA NA NA MW-51-104 MW-51-104 Q3-2011 018 103.7

-36 7/28/2011 9:51 1.64E+02 3.18E+02 3.51E+02

-8.86E-01 1.26E+00 1.94E+00

-1.15E-01 6.18E+00 6.84E+00

-3.12E+00 8.10E+00 7.98E+00 NA NA NA MW-51-104 MW-51-104 Q4-2011 019 103.7

-36 12/12/2011 12:12 1.48E+02 2.91E+02 3.24E+02 1.23E+00 1.76E+00 1.85E+00

-3.81E+00 9.12E+00 1.01E+01 9.25E+00 9.60E+00 1.43E+01

-3.91E+00 1.33E+01 1.51E+01 MW-51-104 MW-51-135 Q1-2011 016 135.2

-67.5 3/8/2011 12:44 8.29E+01 2.24E+02 2.62E+02 8.62E-01 1.31E+00 1.42E+00 8.60E-02 6.02E+00 6.77E+00 2.37E+00 5.96E+00 7.38E+00 NA NA NA ND ND ND ND NA MW-51-135 MW-51-135 Q2-2011 017 135.2

-67.5 4/29/2011 13:16 0.00E+00 3.66E+02 4.35E+02 1.14E+00 1.52E+00 1.63E+00 2.52E+00 1.01E+01 1.17E+01

-5.69E-01 9.00E+00 9.56E+00 NA NA NA MW-51-135 MW-51-135 Q3-2011 018 135.2

-67.5 7/28/2011 10:04

-5.63E+01 2.96E+02 3.49E+02 8.06E-01 1.71E+00 1.92E+00 4.41E+00 8.22E+00 9.83E+00 1.32E+00 9.36E+00 1.05E+01 NA NA NA MW-51-135 MW-51-135 Q4-2011 019 135.2

-67.5 12/12/2011 12:50 1.32E+02 2.93E+02 3.33E+02 2.67E-01 1.64E+00 1.94E+00 6.83E+00 9.42E+00 1.28E+01

-3.73E+00 8.40E+00 9.41E+00

-6.68E+00 1.18E+01 1.35E+01 MW-51-135 MW-51-163 Q1-2011 016 162.7

-95 3/8/2011 13:01 0.00E+00 1.96E+02 2.63E+02

-5.97E-01 1.39E+00 1.98E+00 2.81E+00 6.54E+00 7.66E+00 5.35E-01 7.76E+00 8.69E+00 NA NA NA ND ND ND ND NA MW-51-163 MW-51-163 Q2-2011 017 162.7

-95 4/29/2011 13:19 4.68E+01 3.66E+02 4.30E+02 5.27E-01 1.45E+00 1.65E+00 2.26E+00 8.40E+00 9.72E+00 9.25E-01 7.72E+00 8.87E+00 NA NA NA MW-51-163 MW-51-163 Q3-2011 018 162.7

-95 7/28/2011 10:18 1.20E+02 3.18E+02 3.54E+02

-7.15E-01 1.26E+00 1.96E+00 6.34E-01 7.71E+00 8.41E+00 3.60E+00 9.69E+00 1.17E+01 NA NA NA MW-51-163 MW-51-163 Q4-2011 019 162.7

-95 12/12/2011 12:26 1.71E+02 3.03E+02 3.32E+02 1.58E+00 1.81E+00 1.94E+00 2.25E+00 8.94E+00 1.16E+01

-8.50E-01 8.52E+00 1.08E+01

-3.59E+00 1.22E+01 1.38E+01 MW-51-163 MW-51-189*

Q1-2011 016 189.2

-121.5 3/8/2011 12:30

-1.50E+01 1.93E+02 2.68E+02

-3.06E-01 1.46E+00 1.97E+00 3.77E+01*

1.47E+01 6.28E+00 2.28E-01 5.28E+00 5.79E+00 NA NA NA ND ND ND*

ND NA MW-51-189*

MW-51-189*

Q2-2011 017 189.2

-121.5 4/29/2011 12:52 2.32E+02 3.96E+02 4.33E+02 1.28E+00 1.50E+00 1.57E+00

-8.07E-01 5.82E+00 6.25E+00

-5.07E+00 9.48E+00 8.89E+00 NA NA NA 3.77E+01 MW-51-189*

MW-51-189*

Q3-2011 018 189.2

-121.5 7/28/2011 10:42

-5.69E+00 3.03E+02 3.53E+02 3.69E-02 1.66E+00 1.95E+00 2.36E+00 1.07E+01 1.02E+01 2.52E+00 1.01E+01 1.17E+01 NA NA NA 3.77E+01 MW-51-189*

MW-51-189*

Q4-2011 019 189.2

-121.5 12/12/2011 12:23

-5.57E+01 2.30E+02 3.29E+02

-3.94E-01 1.43E+00 1.91E+00

-4.49E+00 8.10E+00 8.53E+00 1.93E+00 8.34E+00 1.13E+01

-9.34E+00 1.94E+01 2.22E+01 3.77E+01 MW-51-189*

MW-52-11 Q2-2011 006 10 6.8 4/22/2011 12:10 3.04E+02 4.08E+02 4.35E+02 1.29E-01 1.35E+00 1.60E+00 2.27E+00 1.02E+01 1.17E+01 5.08E+00 9.92E+00 1.24E+01 NA NA NA ND ND ND ND NA MW-52-11 MW-52-11 Q2-2011 Mid 007 10 6.8 7/26/2011 12:32 3.39E+02 3.99E+02 4.21E+02 1.86E-01 1.49E+00 1.74E+00 1.71E+00 8.76E+00 9.71E+00

-2.27E+00 8.43E+00 8.63E+00 NA NA NA MW-52-11 MW-52-18 Q2-2011 006 17.5

-2.6 4/22/2011 12:16 7.01E+01 3.76E+02 4.35E+02 1.37E+00 1.39E+00 1.42E+00 8.81E+00 1.29E+01 9.01E+00

-1.49E+00 9.44E+00 9.90E+00 NA NA NA ND ND ND ND NA MW-52-18 MW-52-18 Q2-2011 Mid 007 17.5

-2.6 7/26/2011 14:39 2.52E+02 3.87E+02 4.22E+02 1.06E+00 1.62E+00 1.76E+00 3.80E+00 6.45E+00 8.08E+00

-3.24E+00 8.10E+00 7.84E+00 NA NA NA MW-52-18 MW-52-48 Q2-2011 006 48

-33.1 4/22/2011 12:18 1.06E+02 3.82E+02 4.36E+02 1.69E-01 1.37E+00 1.62E+00

-4.59E+00 7.58E+00 7.31E+00 1.35E+00 7.80E+00 9.17E+00 NA NA NA ND ND ND ND NA MW-52-48 MW-52-48 Q2-2011 Mid 007 48

-33.1 7/26/2011 15:08 7.68E+01 3.66E+02 4.21E+02 2.58E-01 1.20E+00 1.46E+00 2.34E+00 9.60E+00 1.07E+01

-7.68E-01 8.73E+00 1.01E+01 NA NA NA MW-52-48 MW-52-64 Q2-2011 006 64

-49.1 4/22/2011 15:23

-2.26E+01 3.58E+02 4.32E+02 5.12E-01 1.13E+00 1.27E+00 1.87E+00 6.72E+00 7.70E+00

-8.05E+00 8.28E+00 6.18E+00 NA NA NA ND ND ND ND NA MW-52-64 MW-52-64 Q2-2011 Mid 007 64

-49.1 7/27/2011 10:45 1.35E+02 3.81E+02 4.31E+02

-4.58E-01 8.67E-01 1.27E+00 2.48E+00 7.17E+00 8.34E+00 6.66E-01 8.13E+00 9.05E+00 NA NA NA MW-52-64 MW-52-122 Q2-2011 006 122

-107.1 4/22/2011 10:45

-2.27E+01 3.60E+02 4.33E+02 1.14E+00 1.17E+00 1.17E+00 3.48E+01 2.08E+01 9.71E+00

-1.96E+00 7.96E+00 7.90E+00 NA NA NA ND ND 3.48E+01 ND NA MW-52-122 MW-52-122 Q2-2011 Mid 007 122

-107.1 7/26/2011 13:36

-2.18E+01 3.48E+02 4.19E+02 1.05E-01 1.19E+00 1.47E+00

-5.49E+00 7.92E+00 7.50E+00 8.02E-01 6.84E+00 7.89E+00 NA NA NA 3.48E+01 MW-52-122 MW-52-162 Q2-2011 006 161.5

-146.6 4/22/2011 10:18 1.85E+02 3.84E+02 4.29E+02

-7.50E-01 9.50E-01 1.42E+00 1.47E+00 8.40E+00 9.68E+00 1.95E-02 1.00E+01 1.10E+01 NA NA NA 5.16E+02 ND ND ND NA MW-52-162 MW-52-162 Q2-2011 Mid 007 161.5

-146.6 7/26/2011 11:33 5.16E+02 4.20E+02 4.22E+02 3.77E-03 1.21E+00 1.57E+00 4.29E-02 8.34E+00 9.09E+00

-2.32E+00 9.87E+00 1.00E+01 NA NA NA 5.16E+02 MW-52-162 MW-52-181 Q2-2011 006 181

-166.1 4/22/2011 10:22 2.45E+02 3.96E+02 4.33E+02 1.18E+00 1.42E+00 1.48E+00 6.46E+01 2.68E+01 1.22E+01

-1.09E+00 1.22E+01 1.30E+01 NA NA NA ND ND 6.46E+01 ND NA MW-52-181 MW-52-181 Q2-2011 Mid 007 181

-166.1 7/26/2011 11:43 2.41E+02 3.87E+02 4.22E+02 3.57E-01 1.28E+00 1.54E+00

-1.99E+00 7.50E+00 7.52E+00

-1.27E+00 9.39E+00 9.97E+00 NA NA NA 6.46E+01 MW-52-181 MW-53-82 Q1-2011 018 75

-4.7 3/3/2011 11:53 5.95E+02 3.76E+02 3.73E+02 1.61E+00 1.82E+00 1.91E+00 3.61E+00 6.18E+00 7.60E+00

-1.88E+00 7.02E+00 7.25E+00

-7.63E+00 1.59E+01 1.85E+01 6.45E+02 ND ND ND ND MW-53-82 MW-53-82 Q2-2011 019 75

-4.7 4/18/2011 12:45 6.24E+02 4.56E+02 4.50E+02 4.40E-01 1.45E+00 1.67E+00

-4.57E+00 9.82E+00 9.80E+00 3.12E+00 8.78E+00 1.07E+01

-5.86E-01 1.48E+01 1.72E+01 6.45E+02 MW-53-82 MW-53-82 Q3-2011 021 75

-4.7 8/1/2011 11:11 7.16E+02 3.84E+02 3.71E+02

-5.52E-01 7.86E-01 1.06E+00

-2.46E+00 7.38E+00 7.34E+00

-3.40E-01 8.49E+00 9.05E+00 8.23E+00 1.80E+01 1.98E+01 6.45E+02 MW-53-82 MW-53-82 Q4-2011 022 75

-4.7 11/2/2011 11:26 2.27E+02 4.50E+02 5.00E+02

-2.42E-01 1.09E+00 1.49E+00

-1.19E+00 6.78E+00 7.87E+00

-6.95E-01 8.73E+00 1.07E+01

-4.95E-01 1.24E+01 1.41E+01 6.45E+02 MW-53-82 MW-53-120 Q1-2011 022 109.8

-39.5 3/3/2011 12:00 3.84E+03 7.18E+02 3.89E+02 2.95E+01 3.76E+00 1.13E+00 2.30E+00 7.32E+00 8.49E+00

-2.43E+00 8.14E+00 8.13E+00 1.00E+01 1.70E+01 1.87E+01 5.10E+03 3.46E+01 ND ND 1.45E+01 MW-53-120 MW-53-120 Q2-2011 023 109.8

-39.5 4/18/2011 11:52 4.11E+03 7.72E+02 4.75E+02 3.55E+01 4.56E+00 1.67E+00 1.38E+00 8.82E+00 9.99E+00 4.87E-01 9.24E+00 1.02E+01 1.76E+01 1.77E+01 1.87E+01 5.10E+03 3.46E+01 1.45E+01 MW-53-120 MW-53-120 Q3-2011 025 109.8

-39.5 8/1/2011 10:00 4.44E+03 6.15E+02 3.71E+02 3.30E+01 5.22E+00 1.94E+00

-2.07E+00 8.49E+00 8.67E+00

-5.10E-01 9.36E+00 1.01E+01 1.45E+01 1.02E+01 1.07E+01 5.10E+03 3.46E+01 1.45E+01 MW-53-120 MW-53-120 Q4-2011 026 109.8

-39.5 11/2/2011 11:56 8.02E+03 9.27E+02 4.67E+02 4.05E+01 5.16E+00 1.52E+00 4.60E+00 8.52E+00 1.15E+01

-1.89E-01 7.89E+00 1.03E+01 2.58E+00 1.93E+01 2.17E+01 5.10E+03 3.46E+01 1.45E+01 MW-53-120 MW-54-37 Q1-2011 016 36.5

-23.4 2/1/2011 14:10 1.33E+03 4.86E+02 3.78E+02 4.88E+00 1.77E+00 1.26E+00

-1.42E+00 5.54E+00 5.67E+00 3.12E-01 6.42E+00 7.04E+00

-2.81E+00 1.59E+01 1.82E+01 1.59E+04 4.65E+00 ND ND ND MW-54-37 MW-54-37 Q2-2011 017 36.5

-23.4 4/12/2011 12:02 5.16E+03 8.40E+02 4.76E+02 4.91E+00 2.08E+00 1.69E+00 2.95E+00 8.26E+00 9.69E+00 2.50E+00 8.26E+00 9.96E+00 3.16E+00 1.45E+01 1.65E+01 1.59E+04 4.65E+00 MW-54-37 MW-54-37 Q2-2011 Mid 018 36.5

-23.4 7/18/2011 13:45 2.79E+04 1.67E+03 4.43E+02 4.34E+00 2.19E+00 1.85E+00

-1.17E+00 6.36E+00 6.58E+00 4.07E+00 9.21E+00 1.09E+01 1.56E+01 1.91E+01 2.07E+01 1.59E+04 4.65E+00 MW-54-37 MW-54-37 Q3-2011 019 36.5

-23.4 8/15/2011 9:25 3.13E+04 1.75E+03 1.98E+02 2.75E-01 1.60E+00 1.88E+00 5.03E-01 6.69E+00 7.58E+00 3.36E+00 7.56E+00 9.28E+00

-1.05E+01 1.66E+01 1.96E+01 1.59E+04 4.65E+00 MW-54-37 MW-54-37 Q4-2011 020 36.5

-23.4 12/6/2011 10:37 1.40E+04 1.02E+03 3.73E+02 4.48E+00 2.07E+00 1.92E+00

-6.26E+00 9.72E+00 1.03E+01 4.84E-01 8.94E+00 1.14E+01

-5.68E+00 1.25E+01 1.43E+01 1.59E+04 4.65E+00 MW-54-37

TABLE 3 FOURTH QUARTER 2011 GROUNDWATER ANALYTICAL RESULTS AND AVERAGES INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q42011 FINAL Table 3 - Forth Quarter 2011 Groundwater Analytical Results and Averages.xlsx; Q42011 Table 3 Page 4 of 7 See Page 7 for Notes TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Date Time Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Average Average Average Average Average ANALYSIS RESULTS5 YEARLY ROLLING AVERAGES4,6 Well ID1 TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

SAMPLE COLLECTION Well ID1 SAMPLING QUARTER2,8 SAMPLE ID SAMPLE ZONE CENTER Depth Ft Below Top of Casing3 SAMPLE ZONE CENTER Elevation Ft msl3 MW-54-58 Q1-2011 016 57.5

-44.4 2/1/2011 14:22 9.58E+02 4.56E+02 3.92E+02 1.68E+00 1.34E+00 1.28E+00

-4.20E-02 7.14E+00 7.94E+00

-2.21E+00 6.84E+00 6.82E+00

-4.89E+00 1.66E+01 1.92E+01 2.70E+03 1.59E+00 ND ND ND MW-54-58 MW-54-58 Q2-2011 017 57.5

-44.4 4/12/2011 12:04 9.94E+02 5.20E+02 4.79E+02 1.15E+00 1.84E+00 2.01E+00 1.70E+00 8.58E+00 9.66E+00 1.14E+00 8.74E+00 9.95E+00 5.01E+00 1.58E+01 1.78E+01 2.70E+03 1.59E+00 MW-54-58 MW-54-58 Q2-2011 Mid 018 57.5

-44.4 7/18/2011 13:33 2.48E+03 6.12E+02 4.44E+02 1.49E+00 1.21E+00 1.14E+00

-1.98E+00 8.85E+00 9.27E+00 2.35E-01 9.09E+00 1.01E+01 1.83E+01 1.97E+01 2.13E+01 2.70E+03 1.59E+00 MW-54-58 MW-54-58 Q3-2011 019 57.5

-44.4 8/15/2011 9:47 4.23E+03 6.63E+02 2.02E+02

-1.92E-01 9.75E-01 1.31E+00

-1.08E+00 8.61E+00 8.19E+00

-8.43E-01 9.45E+00 1.01E+01 2.37E+00 1.84E+01 2.07E+01 2.70E+03 1.59E+00 MW-54-58 MW-54-58 Q4-2011 020 57.5

-44.4 12/6/2011 10:23 4.83E+03 6.48E+02 3.70E+02 1.60E+00 1.80E+00 1.91E+00 9.45E-01 4.23E+00 5.14E+00 1.72E+00 4.56E+00 5.85E+00 2.66E+00 1.25E+01 1.40E+01 2.70E+03 1.59E+00 MW-54-58 MW-54-123 Q1-2011 016 123

-109.9 2/1/2011 14:11 1.08E+03 4.68E+02 3.90E+02 2.56E+00 1.39E+00 1.08E+00

-3.56E-01 6.02E+00 6.69E+00

-3.66E-03 5.16E+00 5.75E+00 2.50E+00 1.66E+01 1.87E+01 1.52E+03 3.25E+00 ND ND ND MW-54-123 MW-54-123 Q2-2011 017 123

-109.9 4/12/2011 12:22 8.24E+02 4.98E+02 4.77E+02 3.44E+00 1.96E+00 1.72E+00

-5.24E+00 8.14E+00 7.60E+00 1.86E+00 8.04E+00 9.55E+00

-3.35E+00 1.48E+01 1.75E+01 1.52E+03 3.25E+00 MW-54-123 MW-54-123 Q2-2011 Mid 018 123

-109.9 7/18/2011 14:06 5.70E+02 4.44E+02 4.46E+02 7.16E-01 1.02E+00 1.07E+00 1.92E+00 9.66E+00 1.05E+01 3.87E-02 6.30E+00 6.97E+00 6.27E+00 1.84E+01 2.04E+01 1.52E+03 3.25E+00 MW-54-123 MW-54-123 Q3-2011 019 123

-109.9 8/15/2011 9:55 1.21E+03 3.75E+02 2.00E+02 3.74E+00 2.03E+00 1.78E+00 5.50E-01 8.46E+00 9.31E+00

-5.09E-01 8.88E+00 9.49E+00

-3.43E+00 1.94E+01 2.22E+01 1.52E+03 3.25E+00 MW-54-123 MW-54-123 Q4-2011 020 123

-109.9 12/6/2011 10:37 3.92E+03 6.00E+02 3.71E+02 1.55E+00 1.86E+00 1.95E+00

-1.21E+00 4.38E+00 4.89E+00 1.04E+00 5.01E+00 6.08E+00 5.81E+00 1.28E+01 1.41E+01 1.52E+03 3.25E+00 MW-54-123 MW-54-144 Q1-2011 016 144

-130.9 2/1/2011 12:34 1.35E+03 4.96E+02 3.87E+02 9.31E+00 2.24E+00 1.06E+00

-9.04E-01 6.14E+00 6.70E+00

-6.36E-01 6.20E+00 6.74E+00

-4.27E+00 1.58E+01 1.82E+01 3.86E+03 1.05E+01 ND ND ND MW-54-144 MW-54-144 Q2-2011 017 144

-130.9 4/12/2011 9:50 1.48E+03 5.68E+02 4.79E+02 1.20E+01 2.92E+00 1.81E+00 6.43E+00 7.44E+00 9.59E+00

-4.68E+00 9.58E+00 8.86E+00

-2.75E+00 1.48E+01 1.74E+01 3.86E+03 1.05E+01 MW-54-144 MW-54-144 Q2-2011 Mid 018 144

-130.9 7/18/2011 12:38 4.34E+03 7.41E+02 4.43E+02 1.13E+01 2.44E+00 1.26E+00 3.37E+00 7.47E+00 8.78E+00

-3.49E+00 8.91E+00 8.88E+00 1.53E+01 1.87E+01 2.03E+01 3.86E+03 1.05E+01 MW-54-144 MW-54-144 Q3-2011 019 144

-130.9 8/15/2011 11:44 5.27E+03 7.23E+02 1.96E+02 1.10E+01 2.75E+00 1.62E+00 4.07E+00 9.39E+00 1.10E+01 4.25E-01 9.81E+00 1.08E+01

-5.13E+00 1.89E+01 2.18E+01 3.86E+03 1.05E+01 MW-54-144 MW-54-144 Q4-2011 020 144

-130.9 12/6/2011 13:25 6.85E+03 7.44E+02 3.71E+02 9.05E+00 2.99E+00 1.96E+00 8.64E-01 5.58E+00 6.45E+00 3.97E-01 5.58E+00 6.68E+00

-2.77E+00 1.22E+01 1.38E+01 3.86E+03 1.05E+01 MW-54-144 MW-54-173 Q1-2011 016 172.5

-159.4 2/1/2011 12:29 1.66E+03 5.26E+02 3.81E+02 5.81E+00 1.88E+00 1.10E+00

-2.87E-01 8.00E+00 8.79E+00 1.01E+00 1.06E+01 1.20E+01

-5.49E+00 1.77E+01 2.05E+01 1.64E+03 4.66E+00 ND ND ND MW-54-173 MW-54-173 Q2-2011 017 172.5

-159.4 4/12/2011 9:56 1.26E+03 5.46E+02 4.78E+02 3.91E+00 1.92E+00 1.58E+00

-1.29E+01 1.38E+01 1.53E+01 5.93E+00 9.66E+00 1.25E+01

-2.17E+00 1.50E+01 1.76E+01 1.64E+03 4.66E+00 MW-54-173 MW-54-173 Q2-2011 Mid 018 172.5

-159.4 7/18/2011 12:20 1.48E+03 5.28E+02 4.40E+02 4.54E+00 1.64E+00 1.11E+00 2.97E-01 6.84E+00 7.45E+00 1.10E+00 6.51E+00 7.50E+00

-5.43E+00 1.56E+01 1.75E+01 1.64E+03 4.66E+00 MW-54-173 MW-54-173 Q3-2011 019 172.5

-159.4 8/15/2011 11:50 1.50E+03 4.08E+02 1.97E+02 4.32E+00 1.94E+00 1.48E+00

-1.36E+00 1.01E+01 1.05E+01

-7.70E-01 1.21E+01 1.33E+01

-7.41E+00 2.05E+01 2.42E+01 1.64E+03 4.66E+00 MW-54-173 MW-54-173 Q4-2011 020 172.5

-159.4 12/6/2011 13:26 2.32E+03 6.66E+02 3.26E+02 4.72E+00 2.32E+00 1.97E+00

-8.33E-01 4.83E+00 5.47E+00 9.05E-01 5.19E+00 6.34E+00

-2.75E+00 1.24E+01 1.41E+01 1.64E+03 4.66E+00 MW-54-173 MW-54-190 Q1-2011 016 190

-176.9 2/1/2011 12:25 1.89E+03 5.56E+02 3.90E+02 1.68E+01 3.36E+00 1.28E+00 4.59E-01 6.34E+00 7.14E+00

-3.55E+00 5.96E+00 5.21E+00 1.71E+00 1.67E+01 1.89E+01 3.68E+03 1.81E+01 ND ND ND MW-54-190 MW-54-190 Q2-2011 017 190

-176.9 4/12/2011 10:01 2.07E+03 6.18E+02 4.78E+02 1.90E+01 3.38E+00 1.77E+00 3.33E+00 7.86E+00 9.23E+00 8.70E-01 9.00E+00 1.00E+01 3.35E-01 1.58E+01 1.82E+01 3.68E+03 1.81E+01 MW-54-190 MW-54-190 Q2-2011 Mid 018 190

-176.9 7/18/2011 12:14 2.37E+03 6.06E+02 4.45E+02 1.75E+01 2.85E+00 1.12E+00 2.24E+00 1.16E+01 1.29E+01

-2.72E+00 1.18E+01 1.22E+01

-3.86E+00 1.55E+01 1.74E+01 3.68E+03 1.81E+01 MW-54-190 MW-54-190 Q3-2011 019 190

-176.9 8/15/2011 12:00 3.31E+03 5.88E+02 2.00E+02 1.89E+01 3.39E+00 1.22E+00

-3.96E+00 8.61E+00 7.57E+00

-4.68E+00 8.73E+00 8.11E+00

-5.67E+00 1.96E+01 2.30E+01 3.68E+03 1.81E+01 MW-54-190 MW-54-190 Q4-2011 020 190

-176.9 12/6/2011 13:38 8.77E+03 8.22E+02 3.68E+02 1.81E+01 3.72E+00 1.90E+00 5.15E-01 3.87E+00 4.56E+00 1.47E+00 4.11E+00 5.26E+00 3.28E+00 1.21E+01 1.34E+01 3.68E+03 1.81E+01 MW-54-190 MW-55-24 Q1-2011 017 16 2.3 2/3/2011 14:13 1.02E+03 4.48E+02 4.20E+02 1.09E+01 2.82E+00 1.96E+00

-3.57E-01 4.92E+00 5.43E+00 4.75E+00 8.74E+00 7.44E+00

-5.31E+00 1.81E+01 2.14E+01 1.77E+03 1.57E+01 ND ND ND MW-55-24 MW-55-24 Q3-2011 018 16 2.3 8/12/2011 12:12 1.71E+03 4.35E+02 2.01E+02 1.29E+01 3.21E+00 1.59E+00

-4.41E+00 7.32E+00 6.86E+00 5.14E-01 7.95E+00 8.82E+00 6.75E+00 2.09E+01 2.34E+01 1.77E+03 1.57E+01 MW-55-24 MW-55-24 Q4-2011 019 16 2.3 11/14/2011 11:26 2.57E+03 6.66E+02 4.98E+02 2.33E+01 4.08E+00 1.56E+00 0.00E+00 8.49E+00 1.07E+01 3.56E+00 1.08E+01 1.50E+01

-7.45E+00 1.87E+01 2.17E+01 1.77E+03 1.57E+01 MW-55-24 MW-55-35 Q1-2011 016 32

-13.8 2/3/2011 14:16 1.70E+03 4.84E+02 3.86E+02 1.93E+01 3.42E+00 2.05E+00 8.32E-01 5.82E+00 6.45E+00 1.03E+00 6.24E+00 7.03E+00

-2.16E+00 1.86E+01 2.17E+01 2.48E+03 1.97E+01 ND ND ND MW-55-35 MW-55-35 Q3-2011 017 32

-13.8 8/12/2011 12:15 2.94E+03 5.58E+02 2.01E+02 1.63E+01 3.18E+00 1.50E+00 4.22E-01 7.50E+00 8.42E+00

-1.40E+00 8.31E+00 8.83E+00

-1.22E+01 2.17E+01 2.60E+01 2.48E+03 1.97E+01 MW-55-35 MW-55-35 Q4-2011 018 32

-13.8 11/14/2011 11:23 2.79E+03 6.84E+02 5.00E+02 2.35E+01 3.99E+00 1.60E+00 2.04E-01 7.08E+00 8.67E+00 8.98E-01 8.22E+00 1.06E+01 4.79E+00 1.87E+01 2.09E+01 2.48E+03 1.97E+01 MW-55-35 MW-55-54 Q1-2011 017 47

-28.8 2/3/2011 14:17 8.46E+03 8.58E+02 3.89E+02 1.91E+01 3.78E+00 1.95E+00 3.62E+00 5.80E+00 7.00E+00

-6.59E-01 7.44E+00 7.93E+00

-8.13E+00 1.78E+01 2.14E+01 7.65E+03 1.95E+01 ND ND ND MW-55-54 MW-55-54 Q3-2011 018 47

-28.8 8/12/2011 12:09 8.53E+03 9.24E+02 2.00E+02 2.20E+01 3.36E+00 1.17E+00 7.03E+00 8.73E+00 1.08E+01

-2.52E+00 8.07E+00 7.92E+00

-2.57E+00 1.96E+01 2.27E+01 7.65E+03 1.95E+01 MW-55-54 MW-55-54 Q4-2011 019 47

-28.8 11/14/2011 11:07 5.97E+03 8.25E+02 4.67E+02 1.75E+01 3.57E+00 1.46E+00

-2.66E+00 8.67E+00 1.04E+01 3.60E+00 6.69E+00 1.03E+01 1.62E+00 1.92E+01 2.17E+01 7.65E+03 1.95E+01 MW-55-54 MW-56-53 Q2-2011 010 52 18.3 4/27/2011 12:08 1.18E+02 3.48E+02 3.97E+02

-3.07E-02 1.23E+00 1.60E+00 3.04E+00 8.50E+00 1.01E+01

-1.64E+00 8.42E+00 8.44E+00 NA NA NA ND ND ND ND NA MW-56-53 MW-56-53 Q2-2011 Mid 011 52 18.3 7/6/2011 12:58 2.03E+02 2.75E+02 2.83E+02

-3.68E-01 7.89E-01 1.12E+00 3.72E+00 7.77E+00 9.45E+00

-4.34E+00 8.82E+00 9.56E+00

-4.67E+00 2.28E+01 2.56E+01 MW-56-53 MW-56-53 Q3-2011 Mid 012 52 18.3 8/26/2011 11:06 2.47E+02 3.96E+02 4.32E+02

-6.50E-01 7.17E-01 1.13E+00 1.31E+00 8.97E+00 1.00E+01 2.45E+00 7.50E+00 9.03E+00 NA NA NA MW-56-53 MW-56-53 Q4-2011 013 52 18.3 10/31/2011 12:13 6.15E+01 4.41E+02 5.09E+02 5.82E-02 1.09E+00 1.39E+00 4.08E+00 9.36E+00 1.24E+01 4.41E+00 8.22E+00 1.26E+01 4.96E+00 1.94E+01 2.17E+01 MW-56-53 MW-56-83 Q2-2011 012 74

-3.7 4/27/2011 13:46 7.64E+04 2.40E+03 4.19E+02 3.87E+00 1.60E+00 1.28E+00

-1.05E+00 1.14E+01 1.33E+01

-1.27E+00 9.50E+00 1.01E+01 NA NA NA 8.45E+04 2.81E+00 ND ND NA MW-56-83 MW-56-83 Q2-2011 Mid 013 74

-3.7 7/6/2011 11:58 8.42E+04 3.54E+03 2.81E+02 1.45E+00 1.27E+00 1.19E+00 2.77E+00 2.01E+01 9.44E+00 4.20E-01 8.16E+00 9.20E+00

-1.36E+01 2.15E+01 2.46E+01 8.45E+04 2.81E+00 MW-56-83 MW-56-83 Q3-2011 Mid 014 74

-3.7 8/26/2011 10:56 1.05E+05 3.12E+03 4.42E+02 3.12E+00 1.61E+00 1.37E+00

-2.12E+00 8.13E+00 8.21E+00

-6.41E-01 8.67E+00 9.15E+00 NA NA NA 8.45E+04 2.81E+00 MW-56-83 MW-56-83 Q4-2011 015 74

-3.7 10/31/2011 12:00 7.25E+04 2.80E+03 5.11E+02 9.41E-01 1.49E+00 1.61E+00 2.19E+00 7.29E+00 9.56E+00 2.43E+00 8.94E+00 1.22E+01

-3.01E+00 2.14E+01 2.44E+01 8.45E+04 2.81E+00 MW-56-83 MW-57-11 Q2-2011 007 10 5

5/4/2011 10:28 6.40E+03 6.84E+02 3.41E+02 3.11E+01 3.62E+00 1.04E+00 3.74E+00 8.32E+00 9.74E+00 2.05E+00 8.40E+00 9.72E+00 6.20E+00 1.66E+01 1.85E+01 7.01E+03 3.02E+01 ND ND ND MW-57-11 MW-57-11 Q2-2011 Mid 008 10 5

7/18/2011 11:57 7.36E+03 9.18E+02 4.45E+02 3.87E+01 5.28E+00 2.11E+00 3.27E-01 8.88E+00 9.84E+00

-2.34E+00 9.18E+00 9.39E+00

-6.76E+00 1.48E+01 1.67E+01 7.01E+03 3.02E+01 MW-57-11 MW-57-11 Q3-2011 Mid 009 10 5

8/19/2011 9:49 7.27E+03 8.58E+02 2.02E+02 2.08E+01 3.21E+00 1.24E+00 4.49E+00 7.50E+00 9.07E+00 2.31E+00 7.74E+00 9.17E+00 4.92E-01 2.06E+01 2.36E+01 7.01E+03 3.02E+01 MW-57-11 MW-57-20 Q2-2011 007 19

-4 5/4/2011 10:37 2.03E+04 1.15E+03 3.44E+02 1.74E+00 1.11E+00 9.49E-01 1.48E+00 7.52E+00 8.43E+00

-7.32E-01 9.22E+00 1.02E+01

-5.44E+00 1.64E+01 1.91E+01 2.77E+04 1.64E+00 ND ND ND MW-57-20 MW-57-20 Q2-2011 Mid 008 19

-4 7/18/2011 12:09 3.81E+04 1.94E+03 4.43E+02 1.27E+00 1.08E+00 1.01E+00

-5.13E+00 7.71E+00 7.35E+00 9.16E-01 8.67E+00 9.92E+00

-5.69E+00 1.93E+01 2.20E+01 2.77E+04 1.64E+00 MW-57-20 MW-57-20 Q3-2011 Mid 009 19

-4 8/19/2011 9:54 2.47E+04 1.55E+03 1.98E+02 1.90E+00 1.68E+00 1.56E+00

-2.01E+00 7.35E+00 7.66E+00 1.68E+00 8.07E+00 9.48E+00 3.14E+00 1.98E+01 2.25E+01 2.77E+04 1.64E+00 MW-57-20 MW-57-45 Q2-2011 008 40

-25 5/4/2011 11:03 1.35E+04 9.48E+02 3.43E+02 9.06E-01 9.74E-01 9.60E-01 7.40E+00 9.54E+00 1.21E+01

-1.84E+00 9.48E+00 9.59E+00 6.39E+00 1.78E+01 1.98E+01 2.11E+04 ND ND ND ND MW-57-45 MW-57-45 Q2-2011 Mid 009 40

-25 7/18/2011 12:36 2.53E+04 1.60E+03 4.47E+02 1.28E+00 1.32E+00 1.34E+00

-2.08E-01 8.16E+00 8.83E+00

-7.58E-01 9.39E+00 9.67E+00

-1.04E+01 1.53E+01 1.74E+01 2.11E+04 MW-57-45 MW-57-45 Q3-2011 Mid 010 40

-25 8/19/2011 10:19 2.46E+04 1.56E+03 2.02E+02 4.31E-01 1.01E+00 1.15E+00

-5.69E+00 1.03E+01 1.04E+01 2.03E+00 8.04E+00 9.53E+00 2.27E+00 2.09E+01 2.38E+01 2.11E+04 MW-57-45 MW-58-26 Q2-2011 012 20

-5.4 5/3/2011 9:58 7.22E+02 4.30E+02 4.21E+02 3.15E-01 1.13E+00 1.32E+00 2.29E+00 5.80E+00 6.89E+00

-6.42E+00 9.02E+00 8.00E+00 NA NA NA 2.46E+03 ND ND ND NA MW-58-26 MW-58-26 Q2-2011 Mid 013 20

-5.4 7/5/2011 13:29 1.86E+03 5.46E+02 4.47E+02

-3.25E-01 1.10E+00 1.41E+00 7.41E-01 6.84E+00 7.61E+00 1.22E+00 7.32E+00 8.39E+00

-1.01E+01 1.99E+01 2.25E+01 2.46E+03 MW-58-26 MW-58-26 Q3-2011 Mid 014 20

-5.4 8/26/2011 14:47 2.47E+03 5.10E+02 1.99E+02

-6.17E-02 7.95E-01 1.05E+00 2.39E-01 7.65E+00 8.47E+00 3.25E-01 8.22E+00 9.22E+00 NA NA NA 2.46E+03 MW-58-26 MW-58-26 Q4-2011 015 20

-5.4 11/15/2011 14:22 4.77E+03 7.29E+02 2.31E+02

-4.32E-01 8.28E-01 1.25E+00 1.04E+00 1.99E+01 8.90E+00 2.18E+00 9.42E+00 1.24E+01

-3.05E+00 1.22E+01 1.39E+01 2.46E+03 MW-58-26 MW-58-65***

Q2-2011 012 54

-39.4 5/3/2011 10:11 3.29E+02 3.78E+02 3.97E+02

-4.47E-01 1.03E+00 1.44E+00 1.93E+00 5.92E+00 7.00E+00

-7.81E-01 7.04E+00 7.26E+00 NA NA NA 1.19E+03 ND***

ND ND NA MW-58-65***

MW-58-65***

Q2-2011 Mid 013 54

-39.4 7/5/2011 13:30 7.26E+02 3.93E+02 2.83E+02 4.19E-01 9.12E-01 1.03E+00 5.29E+00 1.05E+01 1.25E+01 1.47E+00 7.53E+00 8.78E+00 3.44E-01 2.03E+01 2.27E+01 1.19E+03 3.64E+00 MW-58-65***

MW-58-65***

Q3-2011 Mid 014 54

-39.4 8/26/2011 14:04 1.10E+03 4.62E+02 2.61E+02 6.31E-01***

1.82E+00 1.60E+00

-1.06E+00 9.00E+00 9.65E+00

-1.54E+00 1.01E+01 1.04E+01 NA NA NA 1.19E+03 3.64E+00 MW-58-65***

MW-58-65***

Q4-2011 015 54

-39.4 11/15/2011 14:05 1.75E+03 4.32E+02 3.42E+02 3.02E-01 1.71E+00 2.03E+00

-1.89E+00 8.82E+00 9.54E+00

-7.70E-01 7.23E+00 8.96E+00 NA NA NA 1.19E+03 3.64E+00 MW-58-65***

MW-59-32 Q2-2011 Mid 005 27

-12.5 7/20/2011 9:59 1.56E+02 3.90E+02 4.38E+02 5.88E-01 1.14E+00 1.27E+00

-1.79E+00 7.92E+00 8.02E+00

-2.58E+00 9.78E+00 1.02E+01

-1.40E+01 1.82E+01 2.07E+01 4.74E+02 ND ND ND ND MW-59-32 MW-59-32 Q3-2011 Mid 006 27

-12.5 8/24/2011 14:22 4.74E+02 2.72E+02 2.17E+02 7.95E-01 1.13E+00 1.20E+00

-2.52E+00 1.05E+01 1.13E+01 2.65E+00 8.25E+00 9.93E+00

-6.65E+00 2.16E+01 2.54E+01 4.74E+02 MW-59-32 MW-59-45 Q2-2011 Mid 005 42

-27.5 7/20/2011 9:59 5.24E+02 4.35E+02 4.43E+02

-1.01E+00 1.05E+00 1.49E+00 1.81E+00 8.52E+00 9.88E+00 2.79E+00 9.48E+00 1.15E+01

-1.12E+01 1.83E+01 2.08E+01 8.82E+02 ND ND ND ND MW-59-45 MW-59-45 Q3-2011 Mid 006 42

-27.5 8/24/2011 14:32 1.24E+03 4.92E+02 2.64E+02 1.13E-01 1.11E+00 1.33E+00

-1.32E+00 8.37E+00 8.81E+00 4.22E+00 9.42E+00 1.18E+01 1.31E+00 1.07E+01 1.20E+01 8.82E+02 MW-59-45 MW-59-68 Q2-2011 Mid 005 58

-43.5 7/20/2011 10:14 1.15E+02 3.90E+02 4.42E+02 1.10E-01 7.26E-01 9.01E-01 2.83E+00 9.33E+00 1.09E+01 8.22E-01 9.87E+00 1.06E+01

-1.57E+01 2.17E+01 2.47E+01 ND ND ND ND ND MW-59-68 MW-59-68 Q3-2011 Mid 006 58

-43.5 8/24/2011 14:09 2.61E+02 2.83E+02 2.66E+02

-5.46E-01 7.35E-01 1.14E+00

-5.62E+00 8.52E+00 7.69E+00 1.56E+00 9.03E+00 1.03E+01 4.94E+00 1.28E+01 1.42E+01 MW-59-68 MW-60-35 Q1-2011 016 34.9

-22.4 2/11/2011 12:17 3.20E+02 3.72E+02 3.88E+02 9.73E-01 1.63E+00 1.78E+00 2.69E+00 6.24E+00 7.46E+00 1.22E-01 3.76E+00 4.24E+00

-1.61E+00 1.62E+01 1.84E+01 4.99E+02 ND ND ND ND MW-60-35 MW-60-35 Q2-2011 017 34.9

-22.4 4/15/2011 11:36 2.03E+02 4.32E+02 4.80E+02 3.77E-01 1.66E+00 2.00E+00 2.46E+00 1.14E+01 8.95E+00

-8.48E-01 9.58E+00 1.03E+01 2.65E+00 1.42E+01 1.61E+01 4.99E+02 MW-60-35 MW-60-35 Q3-2011 018 34.9

-22.4 8/10/2011 10:54 4.99E+02 2.69E+02 2.00E+02

-5.84E-01 7.74E-01 1.17E+00 2.11E+00 6.96E+00 8.28E+00

-1.04E+00 1.03E+01 1.10E+01 NA NA NA 4.99E+02 MW-60-35 MW-60-35 Q4-2011 019 34.9

-22.4 12/2/2011 11:21 1.74E+02 3.66E+02 4.07E+02 3.94E-01 1.72E+00 1.98E+00

-8.20E-01 9.33E+00 1.15E+01 2.63E+00 7.86E+00 1.12E+01 NA NA NA 4.99E+02 MW-60-35 MW-60-53 Q1-2011 016 53.4

-40.9 2/11/2011 10:57 3.19E+02 3.70E+02 3.87E+02 7.44E-01 1.52E+00 1.70E+00

-2.03E+00 5.88E+00 6.16E+00 1.39E+00 7.96E+00 8.33E+00

-1.39E+00 1.50E+01 1.72E+01 5.16E+02 ND ND ND ND MW-60-53 MW-60-53 Q2-2011 017 53.4

-40.9 4/15/2011 11:37

-5.87E+01 3.96E+02 4.80E+02

-1.18E-02 1.60E+00 2.04E+00 2.17E+00 9.90E+00 1.14E+01

-1.11E+00 8.68E+00 8.95E+00

-1.06E+00 1.43E+01 1.66E+01 5.16E+02 MW-60-53 MW-60-53 Q3-2011 018 53.4

-40.9 8/10/2011 11:45 5.16E+02 2.70E+02 1.99E+02 1.18E+00 1.39E+00 1.45E+00 5.77E-01 1.34E+01 8.78E+00

-5.16E-01 1.07E+01 1.15E+01 NA NA NA 5.16E+02 MW-60-53 MW-60-53 Q4-2011 019 53.4

-40.9 12/2/2011 11:46 2.65E+02 3.30E+02 3.33E+02 9.60E-02 1.69E+00 1.97E+00 4.62E-01 4.68E+00 5.62E+00

-9.95E-01 4.83E+00 5.65E+00 NA NA NA 5.16E+02 MW-60-53 MW-60-72 Q1-2011 016 72.4

-59.9 2/10/2011 12:54 3.64E+02 3.76E+02 3.84E+02 2.41E-01 1.45E+00 1.70E+00

-5.10E-02 9.12E+00 1.01E+01 2.27E+00 8.84E+00 1.07E+01 2.12E+00 1.54E+01 1.75E+01 2.91E+02 ND ND ND ND MW-60-72 MW-60-72 Q2-2011 017 72.4

-59.9 4/15/2011 13:12 2.19E+02 3.78E+02 4.13E+02 7.12E-01 1.72E+00 1.97E+00

-5.14E+00 6.54E+00 5.80E+00

-3.30E+00 1.14E+01 1.14E+01

-2.93E+00 1.39E+01 1.63E+01 2.91E+02 MW-60-72 MW-60-72 Q3-2011 018 72.4

-59.9 8/10/2011 13:25 2.91E+02 2.23E+02 1.95E+02 1.22E-01 9.33E-01 1.14E+00

-4.08E+00 9.63E+00 1.00E+01 4.20E+00 8.40E+00 1.06E+01 NA NA NA 2.91E+02 MW-60-72 MW-60-72 Q4-2011 019 72.4

-59.9 12/2/2011 10:01 3.08E+02 3.75E+02 4.01E+02 8.41E-01 1.73E+00 1.93E+00

-2.19E+00 6.99E+00 8.20E+00

-1.72E+00 8.28E+00 1.01E+01 NA NA NA 2.91E+02 MW-60-72 MW-60-135 Q1-2011 016 134.9

-122.4 2/10/2011 13:04 3.98E+02 3.78E+02 3.83E+02 1.14E+00 1.82E+00 1.98E+00 1.72E+00 6.72E+00 7.79E+00 2.24E-01 7.44E+00 8.25E+00

-3.56E+00 1.52E+01 1.76E+01 4.04E+02 ND ND ND ND MW-60-135 MW-60-135 Q2-2011 017 134.9

-122.4 4/15/2011 13:25 4.14E+02 4.02E+02 4.12E+02 6.52E-01 1.90E+00 2.16E+00

-6.83E+00 1.39E+01 1.63E+01

-2.48E+00 9.86E+00 1.01E+01 4.64E+00 1.47E+01 1.65E+01 4.04E+02 MW-60-135 MW-60-135 Q3-2011 018 134.9

-122.4 8/10/2011 13:51 4.00E+02 2.46E+02 1.96E+02

-2.08E-01 9.78E-01 1.25E+00

-7.37E+00 9.39E+00 8.24E+00

-6.27E+00 1.07E+01 9.07E+00 NA NA NA 4.04E+02 MW-60-135 MW-60-135 Q4-2011 019 134.9

-122.4 12/2/2011 10:10 3.05E+02 3.81E+02 4.08E+02

-1.48E-01 1.62E+00 1.97E+00

-1.37E-02 7.68E+00 9.43E+00 2.05E+00 8.28E+00 1.13E+01 NA NA NA 4.04E+02 MW-60-135 MW-60-154 Q1-2011 016 154.4

-141.9 2/10/2011 12:53 5.44E+02 4.02E+02 3.87E+02 2.32E-02 8.50E-01 1.07E+00

-4.12E+00 9.26E+00 8.97E+00 9.91E-01 7.86E+00 9.12E+00 4.61E+00 1.52E+01 1.71E+01 5.87E+02 ND ND ND ND MW-60-154 MW-60-154 Q2-2011 017 154.4

-141.9 4/15/2011 13:19 3.06E+02 3.96E+02 4.21E+02

-4.20E-01 1.53E+00 2.02E+00

-2.09E+00 7.62E+00 7.82E+00

-7.25E-01 6.50E+00 6.79E+00 1.62E+00 1.44E+01 1.64E+01 5.87E+02 MW-60-154 MW-60-154 Q3-2011 018 154.4

-141.9 8/10/2011 13:22 5.89E+02 2.81E+02 1.97E+02

-5.08E-02 1.13E+00 1.40E+00

-1.03E+00 8.01E+00 8.47E+00 2.98E+00 9.03E+00 1.07E+01 NA NA NA 5.87E+02 MW-60-154 MW-60-154 Q4-2011 019 154.4

-141.9 12/2/2011 10:18 6.27E+02 5.22E+02 5.23E+02

-1.97E-01 1.54E+00 1.96E+00 1.25E+00 9.33E+00 1.17E+01

-3.69E+00 1.00E+01 1.13E+01 NA NA NA 5.87E+02 MW-60-154

TABLE 3 FOURTH QUARTER 2011 GROUNDWATER ANALYTICAL RESULTS AND AVERAGES INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q42011 FINAL Table 3 - Forth Quarter 2011 Groundwater Analytical Results and Averages.xlsx; Q42011 Table 3 Page 5 of 7 See Page 7 for Notes TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Date Time Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Average Average Average Average Average ANALYSIS RESULTS5 YEARLY ROLLING AVERAGES4,6 Well ID1 TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

SAMPLE COLLECTION Well ID1 SAMPLING QUARTER2,8 SAMPLE ID SAMPLE ZONE CENTER Depth Ft Below Top of Casing3 SAMPLE ZONE CENTER Elevation Ft msl3 MW-60-176 Q1-2011 016 175.9

-163.4 2/10/2011 10:31 1.12E+03 4.68E+02 3.85E+02 2.58E-01 1.49E+00 1.74E+00 4.88E+00 1.13E+01 6.69E+00

-1.75E+00 6.70E+00 6.74E+00 7.24E+00 1.62E+01 1.79E+01 1.07E+03 ND ND ND ND MW-60-176 MW-60-176 Q2-2011 017 175.9

-163.4 4/15/2011 13:49 8.99E+02 4.66E+02 4.18E+02

-8.29E-01 1.41E+00 2.10E+00

-7.83E-02 9.90E+00 1.10E+01

-2.35E+00 1.02E+01 1.03E+01

-2.40E-01 1.40E+01 1.62E+01 1.07E+03 MW-60-176 MW-60-176 Q3-2011 018 175.9

-163.4 8/10/2011 14:12 9.72E+02 3.42E+02 2.00E+02

-1.79E-01 9.21E-01 1.22E+00

-3.87E+00 7.74E+00 7.27E+00

-1.71E-01 8.91E+00 9.60E+00 NA NA NA 1.07E+03 MW-60-176 MW-60-176 Q4-2011 019 175.9

-163.4 12/2/2011 10:27 1.30E+03 5.97E+02 5.19E+02

-1.37E+00 1.41E+00 1.95E+00 7.24E-01 9.60E+00 1.20E+01 1.35E+00 1.01E+01 1.36E+01 NA NA NA 1.07E+03 MW-60-176 MW-62-18 Q1-2011 016 13.5 1.2 2/24/2011 12:49 1.81E+02 3.60E+02 4.00E+02

-3.86E-01 1.71E+00 2.13E+00 2.12E-01 4.74E+00 5.18E+00 3.58E+00 5.46E+00 6.78E+00 NA NA NA 5.27E+02 1.26E+00 ND ND NA MW-62-18 MW-62-18 Q2-2011 017 13.5 1.2 4/13/2011 11:58 3.25E+02 4.56E+02 4.92E+02 7.82E-01 1.54E+00 1.71E+00

-4.38E+00 1.00E+01 1.09E+01

-4.07E-01 1.06E+01 1.16E+01 NA NA NA 5.27E+02 1.26E+00 MW-62-18 MW-62-18 Q2-2011 Mid 018 13.5 1.2 7/22/2011 11:35 2.00E+02 4.02E+02 4.45E+02 1.26E+00 1.24E+00 1.25E+00 4.94E+00 9.42E+00 1.14E+01

-1.79E+00 1.05E+01 1.08E+01

-3.83E+00 1.96E+01 2.20E+01 5.27E+02 1.26E+00 MW-62-18 MW-62-18 Q3-2011 019 13.5 1.2 8/3/2011 10:18 4.04E+02 3.39E+02 3.53E+02 2.03E-01 1.37E+00 1.74E+00

-1.12E+00 8.70E+00 9.13E+00 4.76E+00 9.81E+00 1.21E+01 NA NA NA 5.27E+02 1.26E+00 MW-62-18 MW-62-18 Q4-2011 020 13.5 1.2 10/21/2011 10:14 6.50E+02 3.54E+02 3.45E+02

-1.09E+00 1.66E+00 2.27E+00

-1.19E+00 6.87E+00 8.28E+00

-8.37E-01 8.82E+00 1.11E+01 NA NA NA 5.27E+02 1.26E+00 MW-62-18 MW-62-37 Q1-2011 016 34.5

-19.8 2/24/2011 12:52 3.05E+02 3.76E+02 4.00E+02 5.14E-01 1.84E+00 2.13E+00 1.07E+00 6.06E+00 6.86E+00

-2.84E+00 6.38E+00 6.28E+00 NA NA NA 3.74E+02 ND ND ND NA MW-62-37 MW-62-37 Q2-2011 017 34.5

-19.8 4/13/2011 12:10 1.56E+02 4.36E+02 4.91E+02

-1.97E-01 1.08E+00 1.37E+00

-4.48E+00 8.32E+00 7.76E+00

-1.68E+00 9.02E+00 9.05E+00 NA NA NA 3.74E+02 MW-62-37 MW-62-37 Q2-2011 Mid 018 34.5

-19.8 7/22/2011 12:28 1.15E+02 3.90E+02 4.42E+02 1.03E+00 1.60E+00 1.73E+00

-3.64E+00 7.95E+00 8.03E+00 2.96E+00 1.10E+01 1.30E+01

-8.92E+00 1.85E+01 2.09E+01 3.74E+02 MW-62-37 MW-62-37 Q3-2011 019 34.5

-19.8 8/3/2011 10:35 3.09E+02 3.33E+02 3.52E+02 1.23E+00 1.81E+00 1.96E+00 3.02E+00 6.69E+00 8.03E+00 2.71E+00 8.55E+00 1.01E+01 NA NA NA 3.74E+02 MW-62-37 MW-62-37 Q4-2011 020 34.5

-19.8 10/21/2011 10:02 3.74E+02 3.33E+02 3.47E+02

-3.24E-01 1.60E+00 2.05E+00 5.93E-01 8.19E+00 9.98E+00

-1.66E+00 8.07E+00 9.72E+00 NA NA NA 3.74E+02 MW-62-37 MW-62-53 Q1-2011 015 53.1

-40.3 2/24/2011 12:57 3.08E+02 3.78E+02 4.03E+02 8.98E-01 1.94E+00 2.18E+00

-2.62E-01 4.72E+00 5.23E+00

-1.84E+00 5.58E+00 5.81E+00 NA NA NA 4.47E+02 ND ND ND NA MW-62-53 MW-62-53 Q2-2011 016 53.1

-40.3 4/13/2011 11:32 1.57E+02 4.36E+02 4.92E+02 1.72E+00 1.79E+00 1.84E+00 5.42E-01 6.78E+00 7.51E+00

-3.00E-01 6.24E+00 6.58E+00 NA NA NA 4.47E+02 MW-62-53 MW-62-53 Q2-2011 Mid 017 53.1

-40.3 7/22/2011 10:47 1.60E+02 3.96E+02 4.45E+02

-4.83E-01 1.07E+00 1.58E+00 4.34E+00 7.86E+00 9.52E+00 1.66E+00 8.85E+00 1.02E+01

-1.60E+01 1.79E+01 2.05E+01 4.47E+02 MW-62-53 MW-62-53 Q3-2011 018 53.1

-40.3 8/3/2011 12:44 4.12E+02 3.42E+02 3.00E+02 1.52E-01 1.46E+00 1.75E+00 2.87E+00 7.59E+00 9.04E+00 3.15E+00 8.76E+00 1.06E+01 NA NA NA 4.47E+02 MW-62-53 MW-62-53 Q4-2011 019 53.1

-40.3 10/21/2011 10:17 4.82E+02 3.39E+02 3.42E+02

-1.78E-02 1.24E+00 1.61E+00 1.64E+00 6.66E+00 8.55E+00 2.49E+00 7.05E+00 1.01E+01 NA NA NA 4.47E+02 MW-62-53 MW-62-71 Q1-2011 016 71.1

-58.3 2/24/2011 12:40 5.38E+02 4.06E+02 4.03E+02 1.28E-01 1.22E+00 1.48E+00 4.10E+00 1.18E+01 6.67E+00

-2.36E-01 5.00E+00 5.47E+00 NA NA NA 5.07E+02 ND ND ND NA MW-62-71 MW-62-71 Q2-2011 017 71.1

-58.3 4/13/2011 11:15 3.39E+02 4.72E+02 5.08E+02 9.04E-01 1.45E+00 1.58E+00 2.33E+00 7.96E+00 9.27E+00

-2.38E+00 8.50E+00 8.56E+00 NA NA NA 5.07E+02 MW-62-71 MW-62-71 Q2-2011 Mid 018 71.1

-58.3 7/22/2011 10:12 4.21E+02 4.26E+02 4.44E+02

-3.90E-01 1.36E+00 1.90E+00

-7.29E-02 7.74E+00 8.31E+00

-7.90E-01 8.28E+00 8.59E+00

-6.70E+00 1.89E+01 2.13E+01 5.07E+02 MW-62-71 MW-62-71 Q3-2011 019 71.1

-58.3 8/3/2011 11:58 5.14E+02 3.69E+02 3.07E+02 3.49E-01 1.39E+00 1.65E+00

-7.31E-01 1.01E+01 1.10E+01 2.51E+00 1.04E+01 1.20E+01 NA NA NA 5.07E+02 MW-62-71 MW-62-71 Q4-2011 020 71.1

-58.3 10/21/2011 9:44 4.68E+02 3.36E+02 3.42E+02

-1.43E-01 1.29E+00 1.69E+00 8.75E-01 9.06E+00 1.13E+01 2.06E+00 9.84E+00 1.32E+01 NA NA NA 5.07E+02 MW-62-71 MW-62-92 Q1-2011 016 91.6

-78.8 2/24/2011 12:39 5.09E+02 4.00E+02 4.02E+02 9.56E-01 1.85E+00 2.06E+00 1.68E+00 5.38E+00 6.27E+00

-1.45E+00 5.68E+00 5.86E+00 NA NA NA 5.38E+02 ND ND ND NA MW-62-92 MW-62-92 Q2-2011 017 91.6

-78.8 4/13/2011 11:03 5.06E+02 4.78E+02 4.92E+02 2.87E-01 1.11E+00 1.30E+00

-2.87E+00 7.18E+00 7.31E+00

-2.10E+00 8.94E+00 8.88E+00 NA NA NA 5.38E+02 MW-62-92 MW-62-92 Q2-2011 Mid 018 91.6

-78.8 7/22/2011 10:18 5.61E+02 4.35E+02 4.39E+02

-1.12E+00 1.52E+00 2.06E+00 5.26E+00 9.42E+00 1.13E+01

-7.24E-02 9.48E+00 1.05E+01

-6.69E+00 1.76E+01 1.99E+01 5.38E+02 MW-62-92 MW-62-92 Q3-2011 019 91.6

-78.8 8/3/2011 12:10 5.61E+02 3.78E+02 3.03E+02

-3.26E-01 1.09E+00 1.52E+00 3.82E+00 1.46E+01 9.22E+00

-5.05E+00 1.17E+01 1.15E+01 NA NA NA 5.38E+02 MW-62-92 MW-62-92 Q4-2011 020 91.6

-78.8 10/21/2011 9:42 5.51E+02 3.45E+02 3.42E+02 4.45E-01 1.27E+00 1.48E+00 3.18E-01 9.39E+00 1.17E+01 1.88E-01 9.18E+00 1.22E+01 NA NA NA 5.38E+02 MW-62-92 MW-62-138 Q1-2011 016 138.1

-125.3 2/24/2011 14:54 5.17E+02 4.00E+02 4.01E+02 2.15E+00 1.77E+00 1.75E+00

-1.67E+00 4.72E+00 4.94E+00 1.88E+00 7.04E+00 8.19E+00 NA NA NA 1.21E+03 2.15E+00 ND ND NA MW-62-138 MW-62-138 Q2-2011 017 138.1

-125.3 4/13/2011 14:39 6.31E+02 5.04E+02 5.09E+02 1.22E+00 1.29E+00 1.32E+00 1.29E+00 9.08E+00 1.04E+01 1.71E+00 8.82E+00 1.02E+01 NA NA NA 1.21E+03 2.15E+00 MW-62-138 MW-62-138 Q2-2011 Mid 018 138.1

-125.3 7/22/2011 11:50 4.66E+02 4.23E+02 4.36E+02 6.72E-01 1.20E+00 1.32E+00

-5.97E-01 7.41E+00 8.13E+00 6.36E+00 9.57E+00 1.23E+01

-1.13E+01 1.79E+01 2.03E+01 1.21E+03 2.15E+00 MW-62-138 MW-62-138 Q3-2011 019 138.1

-125.3 8/3/2011 10:08 1.42E+03 5.46E+02 3.34E+02 1.53E+00 1.69E+00 1.73E+00 2.51E-01 9.48E+00 1.05E+01 1.35E+00 8.40E+00 9.73E+00 NA NA NA 1.21E+03 2.15E+00 MW-62-138 MW-62-138 Q4-2011 020 138.1

-125.3 10/21/2011 11:29 3.01E+03 5.97E+02 2.36E+02 1.24E+00 1.48E+00 1.50E+00

-5.88E+00 1.01E+01 1.10E+01 2.45E-01 1.03E+01 1.33E+01 NA NA NA 1.21E+03 2.15E+00 MW-62-138 MW-62-182 Q1-2011 016 182.1

-169.3 2/24/2011 15:07 3.55E+02 3.84E+02 4.03E+02

-1.46E-01 1.45E+00 1.94E+00

-1.95E+00 6.24E+00 6.60E+00 5.86E-01 6.60E+00 7.33E+00 NA NA NA 6.36E+02 ND ND ND NA MW-62-182 MW-62-182 Q2-2011 017 182.1

-169.3 4/13/2011 14:44 1.92E+02 4.50E+02 5.03E+02

-5.04E-01 1.05E+00 1.45E+00 5.54E+00 8.70E+00 1.09E+01

-9.44E-01 1.08E+01 1.15E+01 NA NA NA 6.36E+02 MW-62-182 MW-62-182 Q2-2011 Mid 018 182.1

-169.3 7/22/2011 12:02 2.90E+02 4.20E+02 4.54E+02 2.09E-01 1.22E+00 1.47E+00 6.48E-01 7.41E+00 8.36E+00

-5.94E-01 7.65E+00 8.31E+00

-2.27E+00 1.56E+01 1.75E+01 6.36E+02 MW-62-182 MW-62-182 Q3-2011 019 182.1

-169.3 8/3/2011 10:20 5.84E+02 3.84E+02 3.05E+02 2.04E-01 1.47E+00 1.75E+00

-5.99E+00 1.25E+01 1.14E+01

-2.96E-01 1.13E+01 1.24E+01 NA NA NA 6.36E+02 MW-62-182 MW-62-182 Q4-2011 020 182.1

-169.3 10/21/2011 11:37 6.88E+02 3.42E+02 3.27E+02

-2.48E-01 1.45E+00 1.90E+00

-4.81E+00 1.22E+01 1.34E+01

-1.67E+00 1.06E+01 1.27E+01 NA NA NA 6.36E+02 MW-62-182 MW-63-18 Q1-2011 016 14.9 0.7 3/2/2011 11:10 4.90E+02 3.58E+02 3.55E+02

-4.34E-01 1.50E+00 2.03E+00 1.82E+00 6.78E+00 7.90E+00 2.40E+00 7.38E+00 8.82E+00 NA NA NA 3.75E+02 ND ND ND NA MW-63-18 MW-63-18 Q2-2011 017 14.9 0.7 4/19/2011 10:35 7.23E+01 4.38E+02 5.05E+02

-3.13E-01 1.13E+00 1.49E+00 8.69E-01 8.04E+00 8.92E+00

-3.22E+00 8.16E+00 7.75E+00 NA NA NA 3.75E+02 MW-63-18 MW-63-18 Q2-2011 Mid 018 14.9 0.7 7/21/2011 10:26 2.96E+02 3.99E+02 4.29E+02 6.58E-02 1.19E+00 1.50E+00 2.40E+00 7.62E+00 9.09E+00 2.37E+00 7.53E+00 9.30E+00

-8.91E+00 1.69E+01 1.92E+01 3.75E+02 MW-63-18 MW-63-18 Q3-2011 019 14.9 0.7 8/3/2011 10:02 2.90E+02 3.15E+02 3.03E+02

-1.29E-01 1.20E+00 1.57E+00 1.70E+00 6.87E+00 7.90E+00 3.80E+00 8.58E+00 1.05E+01 NA NA NA 3.75E+02 MW-63-18 MW-63-18 Q4-2011 020 14.9 0.7 10/18/2011 11:34 2.59E+02 2.34E+02 2.20E+02 1.26E+00 1.74E+00 1.83E+00 1.31E+00 8.28E+00 1.07E+01 1.72E+00 1.09E+01 1.44E+01 NA NA NA 3.75E+02 MW-63-18 MW-63-34 Q1-2011 016 31.5

-17.3 3/2/2011 10:50 2.98E+02 2.86E+02 2.62E+02

-4.29E-01 1.57E+00 2.11E+00 7.43E-02 7.96E+00 8.82E+00

-2.10E+00 8.42E+00 8.59E+00 NA NA NA 3.63E+02 ND ND ND NA MW-63-34 MW-63-34 Q2-2011 017 31.5

-17.3 4/19/2011 10:25 3.94E+02 4.60E+02 4.87E+02

-1.13E+00 1.22E+00 1.83E+00 4.36E+00 8.34E+00 9.94E+00 3.72E+00 8.28E+00 1.02E+01 NA NA NA 3.63E+02 MW-63-34 MW-63-34 Q2-2011 Mid 018 31.5

-17.3 7/21/2011 10:08 3.04E+02 4.08E+02 4.39E+02 2.38E-01 1.17E+00 1.42E+00

-1.34E+00 9.03E+00 9.54E+00 1.66E-01 7.89E+00 8.63E+00

-1.26E+01 1.28E+01 1.47E+01 3.63E+02 MW-63-34 MW-63-34 Q3-2011 019 31.5

-17.3 8/3/2011 10:14 3.61E+02 3.30E+02 3.02E+02 1.90E-01 1.37E+00 1.66E+00 8.99E+00 9.09E+00 1.15E+01

-7.29E-01 8.16E+00 8.53E+00 NA NA NA 3.63E+02 MW-63-34 MW-63-34 Q4-2011 020 31.5

-17.3 10/18/2011 11:39 4.30E+02 3.36E+02 3.46E+02

-4.71E-01 1.27E+00 1.78E+00

-3.77E+00 8.31E+00 9.14E+00 2.21E+00 7.62E+00 1.11E+01 NA NA NA 3.63E+02 MW-63-34 MW-63-50 Q1-2011 016 49.5

-37.2 3/2/2011 14:21 4.35E+02 3.40E+02 3.44E+02 1.73E-01 1.62E+00 2.03E+00 1.13E+00 6.50E+00 7.48E+00 3.64E+00 7.02E+00 8.70E+00 NA NA NA 3.93E+02 ND ND ND NA MW-63-50 MW-63-50 Q2-2011 017 49.5

-37.2 4/19/2011 11:25 1.68E+02 4.36E+02 4.89E+02 7.72E-01 1.39E+00 1.53E+00

-6.46E+00 9.76E+00 9.29E+00 3.72E+00 8.18E+00 1.03E+01 NA NA NA 3.93E+02 MW-63-50 MW-63-50 Q2-2011 Mid 018 49.5

-37.2 7/21/2011 11:25 2.09E+02 3.99E+02 4.41E+02

-6.50E-01 8.58E-01 1.39E+00 2.46E-01 7.56E+00 8.55E+00 2.77E+00 8.64E+00 1.05E+01

-2.89E+00 1.51E+01 1.69E+01 3.93E+02 MW-63-50 MW-63-50 Q3-2011 019 49.5

-37.2 8/3/2011 11:38 3.50E+02 3.33E+02 3.09E+02

-8.45E-01 1.10E+00 1.60E+00 8.12E+00 1.18E+01 1.44E+01 4.49E+00 8.52E+00 1.14E+01 NA NA NA 3.93E+02 MW-63-50 MW-63-50 Q4-2011 020 49.5

-37.2 10/18/2011 13:55 3.14E+02 3.63E+02 3.85E+02 4.62E-01 1.68E+00 1.94E+00

-9.09E-01 1.09E+01 1.29E+01

-2.69E+00 1.09E+01 1.34E+01 NA NA NA 3.93E+02 MW-63-50 MW-63-93 Q1-2011 017 93

-80.7 3/2/2011 14:14 2.69E+02 3.00E+02 2.94E+02 3.30E-01 1.79E+00 2.17E+00

-1.51E+00 8.78E+00 9.05E+00 3.38E+00 7.56E+00 9.56E+00 NA NA NA 5.04E+02 ND ND ND NA MW-63-93 MW-63-93 Q2-2011 018 93

-80.7 4/19/2011 11:27 9.64E+01 4.42E+02 5.05E+02

-4.30E-02 1.14E+00 1.44E+00 3.31E+00 8.92E+00 1.03E+01

-4.35E-01 6.80E+00 7.25E+00 NA NA NA 5.04E+02 MW-63-93 MW-63-93 Q2-2011 Mid 019 93

-80.7 7/21/2011 11:32 4.17E+02 4.20E+02 4.40E+02

-4.28E-01 1.06E+00 1.48E+00

-3.58E+00 8.10E+00 7.77E+00

-6.11E+00 7.92E+00 5.51E+00 6.50E-01 1.71E+01 1.90E+01 5.04E+02 MW-63-93 MW-63-93 Q3-2011 020 93

-80.7 8/3/2011 11:50 1.84E+02 3.12E+02 3.38E+02 4.25E-02 1.31E+00 1.63E+00 1.61E+00 7.26E+00 7.83E+00

-2.65E+00 7.71E+00 8.38E+00 NA NA NA 5.04E+02 MW-63-93 MW-63-93 Q4-2011 021 93

-80.7 10/18/2011 14:14 5.04E+02 3.78E+02 3.83E+02 5.60E-01 1.37E+00 1.56E+00 7.43E-01 6.45E+00 8.33E+00 3.55E+00 6.87E+00 1.02E+01 NA NA NA 5.04E+02 MW-63-93 MW-63-112 Q1-2011 016 111.5

-99.2 3/2/2011 14:15 3.38E+02 3.18E+02 2.96E+02 1.48E-01 1.60E+00 2.00E+00

-3.72E-01 6.70E+00 7.21E+00 1.19E+00 6.36E+00 7.21E+00 NA NA NA 7.90E+02 ND ND ND NA MW-63-112 MW-63-112 Q2-2011 017 111.5

-99.2 4/19/2011 11:25 4.22E+02 4.68E+02 4.92E+02

-7.96E-01 1.00E+00 1.47E+00 4.96E+00 1.05E+01 1.25E+01 1.64E+00 1.17E+01 1.36E+01 NA NA NA 7.90E+02 MW-63-112 MW-63-112 Q2-2011 Mid 018 111.5

-99.2 7/21/2011 11:46 6.01E+02 4.44E+02 4.44E+02 2.29E-01 1.13E+00 1.37E+00

-8.46E-01 1.06E+01 1.11E+01 6.03E+00 1.21E+01 1.54E+01

-1.22E+00 1.77E+01 1.98E+01 7.90E+02 MW-63-112 MW-63-112 Q3-2011 019 111.5

-99.2 8/3/2011 12:01 8.82E+02 4.59E+02 3.36E+02

-1.83E-01 1.31E+00 1.67E+00 2.07E+00 7.35E+00 8.45E+00

-2.13E+00 7.26E+00 7.10E+00 NA NA NA 7.90E+02 MW-63-112 MW-63-112 Q4-2011 020 111.5

-99.2 10/18/2011 14:20 1.34E+03 5.43E+02 3.29E+02

-5.35E-01 1.39E+00 1.87E+00

-1.39E+00 7.53E+00 8.79E+00 1.78E+00 7.02E+00 9.82E+00 NA NA NA 7.90E+02 MW-63-112 MW-63-121 Q1-2011 016 121

-108.7 3/2/2011 11:10 5.03E+02 3.54E+02 2.94E+02

-6.82E-02 1.55E+00 2.03E+00

-6.26E-01 6.72E+00 7.20E+00 3.49E-01 6.00E+00 6.67E+00 NA NA NA 1.59E+03 ND ND ND NA MW-63-121 MW-63-121 Q2-2011 017 121

-108.7 4/19/2011 9:54 5.77E+02 4.84E+02 4.91E+02 4.12E-01 1.18E+00 1.37E+00

-1.03E+00 6.92E+00 7.17E+00

-1.09E+01 9.86E+00 5.99E+00 NA NA NA 1.59E+03 MW-63-121 MW-63-121 Q2-2011 Mid 018 121

-108.7 7/21/2011 9:58 1.33E+03 5.28E+02 4.45E+02

-3.05E-01 1.36E+00 1.74E+00 1.63E-03 7.44E+00 8.17E+00

-3.19E+00 1.05E+01 1.07E+01 1.12E+00 1.84E+01 2.05E+01 1.59E+03 MW-63-121 MW-63-121 Q3-2011 019 121

-108.7 8/3/2011 10:03 1.92E+03 6.09E+02 3.29E+02 9.09E-01 1.49E+00 1.62E+00

-6.79E+00 9.27E+00 9.08E+00 6.01E+00 8.16E+00 1.09E+01 NA NA NA 1.59E+03 MW-63-121 MW-63-121 Q4-2011 020 121

-108.7 10/18/2011 11:27 3.63E+03 8.40E+02 3.33E+02 1.49E+00 1.71E+00 1.75E+00

-6.42E+00 1.26E+01 1.62E+01 2.81E+00 9.33E+00 1.31E+01 NA NA NA 1.59E+03 MW-63-121 MW-63-163 Q1-2011 016 162.5

-150.2 3/2/2011 10:27 6.05E+02 3.76E+02 2.95E+02 1.37E+00 1.99E+00 2.12E+00 3.09E+00 5.40E+00 6.62E+00

-2.05E+00 7.72E+00 7.12E+00 NA NA NA 5.10E+02 ND ND ND NA MW-63-163 MW-63-163 Q2-2011 017 162.5

-150.2 4/19/2011 9:49 4.92E+02 4.84E+02 5.03E+02 1.11E+00 1.82E+00 2.00E+00 4.43E-01 8.94E+00 9.98E+00 4.78E+00 1.02E+01 1.26E+01 NA NA NA 5.10E+02 MW-63-163 MW-63-163 Q2-2011 Mid 018 162.5

-150.2 7/21/2011 10:09 5.08E+02 4.26E+02 4.36E+02

-6.14E-01 1.01E+00 1.48E+00

-8.47E-01 7.47E+00 8.17E+00 4.07E-01 7.53E+00 8.66E+00

-8.69E+00 1.47E+01 1.67E+01 5.10E+02 MW-63-163 MW-63-163 Q3-2011 019 162.5

-150.2 8/3/2011 10:06 4.41E+02 3.54E+02 3.08E+02 7.99E-02 1.35E+00 1.69E+00 5.51E-01 8.40E+00 9.33E+00 2.23E+00 1.03E+01 1.20E+01 NA NA NA 5.10E+02 MW-63-163 MW-63-163 Q4-2011 020 162.5

-150.2 10/18/2011 11:37 4.85E+02 3.75E+02 3.80E+02 9.47E-01 1.35E+00 1.43E+00

-4.58E+00 9.51E+00 9.82E+00

-1.98E+00 6.54E+00 7.63E+00 NA NA NA 5.10E+02 MW-63-163 MW-63-174 Q1-2011 016 174

-161.7 3/2/2011 10:26 4.13E+02 3.30E+02 2.91E+02 8.20E-01 1.80E+00 2.03E+00 3.65E+00 6.96E+00 8.18E+00 2.34E+00 7.86E+00 9.20E+00 NA NA NA 4.92E+02 ND ND ND NA MW-63-174 MW-63-174 Q2-2011 017 174

-161.7 4/19/2011 9:52 1.56E+02 4.48E+02 5.04E+02

-7.87E-01 9.72E-01 1.48E+00

-6.41E+00 8.32E+00 7.72E+00

-9.85E-01 8.58E+00 9.20E+00 NA NA NA 4.92E+02 MW-63-174 MW-63-174 Q2-2011 Mid 018 174

-161.7 7/21/2011 9:57 4.14E+02 4.17E+02 4.36E+02 6.96E-01 1.85E+00 2.10E+00

-3.57E+00 8.10E+00 8.27E+00 4.67E-01 9.36E+00 1.09E+01

-2.55E+00 1.33E+01 1.49E+01 4.92E+02 MW-63-174 MW-63-174 Q3-2011 019 174

-161.7 8/3/2011 10:18 6.09E+02 3.93E+02 3.09E+02 6.96E-01 1.49E+00 1.68E+00

-4.15E+00 9.15E+00 8.88E+00 4.51E+00 8.19E+00 1.05E+01 NA NA NA 4.92E+02 MW-63-174 MW-63-174 Q4-2011 020 174

-161.7 10/18/2011 11:42 4.53E+02 3.72E+02 3.80E+02 1.02E+00 1.71E+00 1.86E+00

-6.37E-02 8.43E+00 1.03E+01

-4.33E+00 8.13E+00 9.02E+00 NA NA NA 4.92E+02 MW-63-174 MW-65-48 Q2-2011 Mid 002 43.3 26.356 7/7/2011 12:19 8.59E+01 2.43E+02 2.85E+02 5.73E-01 1.04E+00 1.15E+00 4.10E+00 9.03E+00 1.09E+01

-1.15E+00 1.12E+01 1.18E+01

-5.93E+00 2.39E+01 2.69E+01 ND ND ND ND ND MW-65-48 MW-65-80 Q2-2011 Mid 003 71.4

-1.659 7/13/2011 10:12 8.54E+01 2.41E+02 2.84E+02 1.26E-01 9.24E-01 1.12E+00

-2.33E+00 9.12E+00 9.46E+00 2.88E+00 1.15E+01 1.34E+01

-1.27E+01 2.00E+01 2.29E+01 ND ND ND ND ND MW-65-80 MW-66-21 Q1-2011 016 14.1 0

1/31/2011 16:26 4.77E+02 4.08E+02 4.24E+02 3.48E-01 1.73E+00 2.02E+00

-2.19E-01 5.00E+00 5.33E+00 9.80E-01 6.50E+00 7.23E+00

-1.06E+00 1.84E+01 2.14E+01 6.31E+02 ND ND ND ND MW-66-21 MW-66-21 Q2-2011 017 14.1 0

4/14/2011 13:43 9.30E+01 3.88E+02 4.46E+02 6.73E-01 1.64E+00 1.85E+00

-4.70E+00 8.74E+00 8.45E+00 6.94E+00 9.82E+00 1.25E+01 1.81E+00 1.51E+01 1.72E+01 6.31E+02 MW-66-21 MW-66-21 Q3-2011 018 14.1 0

8/8/2011 10:55 7.84E+02 3.90E+02 3.73E+02 8.00E-01 1.44E+00 1.59E+00

-2.25E+00 8.16E+00 8.11E+00 3.27E-01 7.05E+00 7.73E+00 6.75E+00 9.00E+00 9.81E+00 6.31E+02 MW-66-21 MW-66-21 Q4-2011 019 14.1 0

11/29/2011 11:08 2.64E+02 3.27E+02 3.32E+02 3.54E-01 1.33E+00 1.49E+00 7.86E-01 6.60E+00 8.51E+00 1.73E+00 7.50E+00 1.01E+01

-3.27E+00 1.37E+01 1.56E+01 6.31E+02 MW-66-21

TABLE 3 FOURTH QUARTER 2011 GROUNDWATER ANALYTICAL RESULTS AND AVERAGES INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q42011 FINAL Table 3 - Forth Quarter 2011 Groundwater Analytical Results and Averages.xlsx; Q42011 Table 3 Page 6 of 7 See Page 7 for Notes TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Date Time Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Average Average Average Average Average ANALYSIS RESULTS5 YEARLY ROLLING AVERAGES4,6 Well ID1 TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

SAMPLE COLLECTION Well ID1 SAMPLING QUARTER2,8 SAMPLE ID SAMPLE ZONE CENTER Depth Ft Below Top of Casing3 SAMPLE ZONE CENTER Elevation Ft msl3 MW-66-36 Q1-2011 015 33.6

-19.5 1/31/2011 15:51 3.01E+03 6.78E+02 4.61E+02 1.55E+01 3.18E+00 2.11E+00

-1.13E+00 6.12E+00 6.49E+00

-8.31E-01 6.80E+00 7.15E+00

-4.89E+00 1.79E+01 2.12E+01 3.44E+03 1.11E+01 ND ND ND MW-66-36 MW-66-36 Q2-2011 016 33.6

-19.5 4/14/2011 12:53 3.52E+03 7.36E+02 4.79E+02 1.06E+01 2.88E+00 1.95E+00 1.50E-01 7.24E+00 8.14E+00 5.40E-01 7.92E+00 9.01E+00 6.10E-01 1.55E+01 1.79E+01 3.44E+03 1.11E+01 MW-66-36 MW-66-36 Q3-2011 017 33.6

-19.5 8/8/2011 10:49 3.90E+03 5.91E+02 3.74E+02 8.00E+00 2.60E+00 1.61E+00

-3.94E+00 1.11E+01 1.07E+01 1.48E+00 1.26E+01 1.46E+01 2.82E+00 1.53E+01 1.71E+01 3.44E+03 1.11E+01 MW-66-36 MW-66-36 Q4-2011 018 33.6

-19.5 11/29/2011 11:01 3.34E+03 6.78E+02 4.85E+02 1.02E+01 1.77E+00 1.38E+00 5.21E+00 9.78E+00 1.32E+01 1.63E+00 8.64E+00 1.21E+01 0.00E+00 1.94E+01 2.18E+01 3.44E+03 1.11E+01 MW-66-36 MW-67-39 Q1-2011 016 38.3

-25.8 2/7/2011 13:48 3.85E+03 7.60E+02 4.81E+02 1.57E+01 3.34E+00 1.83E+00 8.03E-02 6.18E+00 6.83E+00 6.64E-01 6.78E+00 7.57E+00 4.43E+00 1.97E+01 2.23E+01 3.68E+03 1.16E+01 ND ND ND MW-67-39 MW-67-39 Q2-2011 017 38.3

-25.8 4/14/2011 13:25 3.73E+03 7.14E+02 4.17E+02 1.25E+01 3.76E+00 2.10E+00 4.53E+00 8.78E+00 1.04E+01 3.71E+00 9.54E+00 1.14E+01 6.99E+00 1.47E+01 1.63E+01 3.68E+03 1.16E+01 MW-67-39 MW-67-39 Q3-2011 018 38.3

-25.8 8/8/2011 12:26 3.62E+03 5.76E+02 3.73E+02 5.31E+00 2.39E+00 1.98E+00

-3.01E+00 8.34E+00 8.17E+00

-7.13E+00 8.22E+00 7.50E+00 5.90E+00 1.71E+01 1.90E+01 3.68E+03 1.16E+01 MW-67-39 MW-67-39 Q4-2011 019 38.3

-25.8 11/29/2011 13:59 3.51E+03 8.07E+02 3.31E+02 1.30E+01 2.39E+00 1.94E+00

-1.60E+01 1.39E+01 1.60E+01

-1.78E+00 9.48E+00 1.17E+01 2.69E+00 1.24E+01 1.38E+01 3.68E+03 1.16E+01 MW-67-39 MW-67-105 Q1-2011 015 104.8

-92.3 2/7/2011 13:57 9.94E+02 4.26E+02 3.86E+02 3.37E-01 1.64E+00 1.94E+00 2.40E+00 4.84E+00 5.67E+00

-1.22E+00 4.86E+00 4.81E+00

-4.59E+00 1.96E+01 2.31E+01 1.35E+03 ND ND ND ND MW-67-105 MW-67-105 Q2-2011 016 104.8

-92.3 4/14/2011 13:43 1.10E+03 4.84E+02 4.12E+02 2.70E-01 1.72E+00 2.11E+00

-3.96E-01 9.66E+00 1.05E+01

-1.91E-01 7.24E+00 7.88E+00 5.71E+00 1.55E+01 1.73E+01 1.35E+03 MW-67-105 MW-67-105 Q3-2011 017 104.8

-92.3 8/8/2011 12:48 1.42E+03 4.38E+02 3.74E+02 7.40E-01 1.71E+00 1.92E+00

-4.93E-01 7.77E+00 8.36E+00

-6.18E+00 8.67E+00 7.26E+00 6.67E+00 1.25E+01 1.38E+01 1.35E+03 MW-67-105 MW-67-105 Q4-2011 018 104.8

-92.3 11/29/2011 14:10 1.89E+03 5.94E+02 4.78E+02 1.13E+00 1.74E+00 1.90E+00

-1.36E+00 8.73E+00 1.01E+01

-1.41E+00 8.73E+00 1.04E+01 3.65E+00 1.97E+01 2.20E+01 1.35E+03 MW-67-105 MW-67-173 Q1-2011 016 172.3

-159.8 2/7/2011 14:13 4.47E+02 4.48E+02 4.65E+02

-2.38E-01 1.68E+00 2.12E+00

-4.75E-01 5.28E+00 5.83E+00 7.55E-01 6.38E+00 5.76E+00

-7.05E-01 1.88E+01 2.18E+01 5.91E+02 ND ND ND ND MW-67-173 MW-67-173 Q2-2011 017 172.3

-159.8 4/14/2011 14:09 5.72E+02 4.20E+02 4.10E+02

-2.56E-01 1.69E+00 1.99E+00 5.04E+00 9.64E+00 1.17E+01

-9.27E+00 1.03E+01 6.85E+00 7.50E+00 1.23E+01 1.34E+01 5.91E+02 MW-67-173 MW-67-173 Q3-2011 018 172.3

-159.8 8/8/2011 12:53 6.13E+02 3.75E+02 3.72E+02

-3.44E-01 1.55E+00 1.94E+00

-1.95E+00 8.79E+00 9.16E+00 1.25E+00 8.70E+00 9.80E+00 4.91E+00 1.20E+01 1.33E+01 5.91E+02 MW-67-173 MW-67-173 Q4-2011 019 172.3

-159.8 11/29/2011 14:23 5.88E+02 4.74E+02 4.78E+02 1.13E+00 1.62E+00 1.76E+00

-1.48E+00 9.87E+00 1.14E+01

-1.48E+00 1.08E+01 1.30E+01 7.39E+00 1.18E+01 1.29E+01 5.91E+02 MW-67-173 MW-67-219 Q1-2011 015 218.8

-206.3 1/31/2011 14:48 6.41E+02 4.18E+02 4.20E+02

-1.08E+00 1.42E+00 1.97E+00 9.72E-01 5.80E+00 6.44E+00 2.44E+00 5.46E+00 6.55E+00

-4.58E+00 1.81E+01 2.14E+01 1.01E+03 ND ND ND ND MW-67-219 MW-67-219 Q2-2011 016 218.8

-206.3 4/14/2011 10:49 1.07E+03 4.78E+02 4.12E+02

-7.57E-01 9.50E-01 1.53E+00

-2.70E+00 6.62E+00 6.47E+00 4.16E+00 9.78E+00 1.20E+01 2.95E+00 1.43E+01 1.62E+01 1.01E+03 MW-67-219 MW-67-219 Q3-2011 017 218.8

-206.3 8/8/2011 10:33 1.11E+03 4.17E+02 3.73E+02 3.18E-02 1.61E+00 1.90E+00 8.34E-01 7.41E+00 8.13E+00

-6.37E+00 9.30E+00 8.11E+00 1.06E+01 1.64E+01 1.79E+01 1.01E+03 MW-67-219 MW-67-219 Q4-2011 018 218.8

-206.3 11/29/2011 10:41 1.20E+03 4.92E+02 4.45E+02 3.14E-01 1.42E+00 1.63E+00

-1.12E+01 1.14E+01 1.19E+01 1.99E+00 7.65E+00 1.12E+01 1.02E+01 1.13E+01 1.23E+01 1.01E+03 MW-67-219 MW-67-276 Q1-2011 015 275.3

-262.8 1/31/2011 14:31 8.75E+02 4.18E+02 3.87E+02

-2.57E-02 1.66E+00 2.03E+00

-2.56E+00 8.76E+00 8.16E+00 6.49E-01 6.48E+00 7.20E+00

-7.18E-01 1.92E+01 2.22E+01 9.74E+02 ND ND ND ND MW-67-276 MW-67-276 Q2-2011 016 275.3

-262.8 4/14/2011 10:53 1.06E+03 4.84E+02 4.19E+02 3.46E-01 1.22E+00 1.45E+00

-5.30E+00 6.78E+00 6.12E+00 1.62E+00 1.02E+01 1.15E+01 5.62E-01 1.42E+01 1.63E+01 9.74E+02 MW-67-276 MW-67-276 Q3-2011 017 275.3

-262.8 8/8/2011 10:45 8.99E+02 3.90E+02 3.63E+02

-3.98E-01 1.38E+00 1.82E+00

-3.35E-01 8.67E+00 9.58E+00 1.65E+00 9.24E+00 1.07E+01 1.22E+01 1.91E+01 2.10E+01 9.74E+02 MW-67-276 MW-67-276 Q4-2011 018 275.3

-262.8 11/29/2011 10:57 1.06E+03 5.25E+02 4.84E+02 1.99E-01 1.70E+00 1.95E+00

-2.95E+00 1.01E+01 1.19E+01

-7.14E-01 8.82E+00 1.11E+01 6.48E+00 1.19E+01 1.31E+01 9.74E+02 MW-67-276 MW-67-323 Q1-2011 015 322.3

-309.8 1/31/2011 15:04 3.38E+02 3.70E+02 3.90E+02 2.58E-01 1.71E+00 2.03E+00 2.47E-01 5.70E+00 6.35E+00 8.12E-03 5.80E+00 6.35E+00

-5.93E+00 1.90E+01 2.25E+01 4.26E+02 ND ND ND ND MW-67-323 MW-67-323 Q2-2011 016 322.3

-309.8 4/14/2011 11:33 4.26E+02 4.06E+02 4.13E+02 1.05E+00 1.52E+00 1.62E+00 2.02E+00 8.36E+00 9.62E+00

-1.12E+00 7.80E+00 8.21E+00

-2.21E-01 1.30E+01 1.50E+01 4.26E+02 MW-67-323 MW-67-323 Q3-2011 017 322.3

-309.8 8/8/2011 10:53 3.09E+02 3.51E+02 3.73E+02 1.75E+00 1.85E+00 1.91E+00

-6.64E-01 6.66E+00 7.23E+00 4.13E+00 8.82E+00 1.09E+01

-9.62E+00 2.15E+01 2.43E+01 4.26E+02 MW-67-323 MW-67-323 Q4-2011 018 322.3

-309.8 11/29/2011 10:57 3.62E+02 4.56E+02 4.86E+02 7.61E-01 1.71E+00 1.91E+00

-3.91E+00 9.81E+00 1.15E+01 1.58E+00 5.43E+00 8.36E+00 1.66E+01 2.34E+01 2.56E+01 4.26E+02 MW-67-323 MW-67-340 Q1-2011 015 339.8

-327.3 1/31/2011 14:53 2.75E+02 3.58E+02 3.83E+02

-7.06E-01 1.51E+00 1.99E+00 4.30E-01 6.34E+00 7.02E+00

-1.15E+00 6.54E+00 6.88E+00

-5.79E+00 1.85E+01 2.20E+01 5.46E+02 ND ND ND ND MW-67-340 MW-67-340 Q2-2011 016 339.8

-327.3 4/14/2011 11:17 6.56E+02 4.32E+02 4.13E+02 2.62E-01 1.16E+00 1.40E+00 5.89E+00 9.02E+00 1.12E+01 4.57E+00 9.02E+00 1.15E+01 7.58E+00 1.54E+01 1.71E+01 5.46E+02 MW-67-340 MW-67-340 Q3-2011 017 339.8

-327.3 8/8/2011 10:43 4.19E+02 3.60E+02 3.72E+02

-5.52E-01 1.49E+00 1.89E+00

-9.17E-01 7.92E+00 8.61E+00

-4.93E+00 1.06E+01 1.00E+01 6.17E+00 1.84E+01 2.05E+01 5.46E+02 MW-67-340 MW-67-340 Q4-2011 018 339.8

-327.3 11/29/2011 10:46 5.62E+02 4.68E+02 4.76E+02

-5.80E-01 1.53E+00 1.87E+00

-7.65E+00 7.53E+00 7.09E+00 1.23E+00 8.85E+00 1.14E+01 1.70E+00 1.06E+01 1.17E+01 5.46E+02 MW-67-340 MW-107 Q2-2011 010 32.7 110.1 5/2/2011 9:25 3.15E+02 3.76E+02 3.95E+02 8.29E-01 1.29E+00 1.40E+00

-3.56E+00 1.30E+01 1.65E+01 2.39E+00 6.84E+00 8.63E+00 NA NA NA ND ND ND ND NA MW-107 MW-108 Q2-2011 Mid 005 8.3 6.2 7/5/2011 15:08 1.24E+03 4.89E+02 2.90E+02

-9.21E-02 1.29E+00 1.55E+00 4.93E+00 9.84E+00 1.17E+01

-7.54E+00 8.49E+00 7.19E+00

-8.75E+00 2.32E+01 2.62E+01 1.51E+03 ND ND ND ND MW-108 MW-108 Q3-2011 Mid 006 8.3 6.2 8/29/2011 11:25 1.78E+03 5.73E+02 2.62E+02

-7.81E-01 7.89E-01 1.24E+00

-1.86E-01 1.19E+01 1.21E+01

-4.10E+00 1.13E+01 1.10E+01 2.65E+00 1.16E+01 1.30E+01 1.51E+03 MW-108 MW-109 Q2-2011 Mid 005 8.5 6.1 7/5/2011 12:45 2.43E+03 6.36E+02 2.79E+02 2.60E-01 1.25E+00 1.45E+00 2.23E-01 8.67E+00 9.62E+00

-3.32E+00 7.74E+00 6.65E+00 3.57E+00 3.51E+01 3.92E+01 2.85E+03 ND ND ND ND MW-109 MW-109 Q3-2011 Mid 006 8.5 6.1 8/26/2011 13:49 3.26E+03 7.50E+02 2.59E+02 5.48E-01 1.01E+00 1.12E+00 2.37E+00 7.65E+00 8.94E+00 3.72E+00 9.60E+00 1.17E+01

-8.72E-01 8.73E+00 1.00E+01 2.85E+03 MW-109 MW-111 Q4-2011 036 16.5 2.4 11/11/2011 11:30 1.11E+04 1.42E+03 3.31E+02 1.09E+00 1.53E+00 1.62E+00

-2.01E-01 7.11E+00 8.62E+00 2.75E+00 8.97E+00 1.21E+01 NA NA NA 1.11E+04 ND ND ND NA MW-111 U3-3 Q2-2011 Mid 014 7/13/2011 12:28 6.73E+02 3.81E+02 2.81E+02

-3.49E-01 8.13E-01 1.19E+00

-4.64E-01 8.01E+00 8.64E+00

-3.52E+00 8.61E+00 8.20E+00 NA NA NA 8.52E+02 ND ND ND NA U3-3 U3-3 Q3-2011 Mid 015 8/29/2011 13:09 1.03E+03 4.56E+02 2.66E+02

-5.04E-01 6.63E-01 1.06E+00

-2.50E+00 8.55E+00 7.82E+00

-3.69E+00 7.74E+00 7.12E+00 NA NA NA 8.52E+02 U3-3 U3-4D Q1-2011 027 25.6

-10.8 2/17/2011 14:41 6.28E+02 4.14E+02 4.05E+02

-8.34E-02 1.55E+00 1.95E+00 1.24E+00 4.72E+00 5.29E+00 8.61E-01 4.84E+00 5.47E+00 NA NA NA 6.81E+02 ND ND ND NA U3-4D U3-4D Q2-2011 028 25.6

-10.8 4/25/2011 14:50 7.41E+02 4.36E+02 3.98E+02 1.18E+00 1.38E+00 1.46E+00

-3.17E+00 7.58E+00 7.50E+00 4.81E-01 7.14E+00 8.11E+00 NA NA NA 6.81E+02 U3-4D U3-4D Q2-2011 Mid 029 25.6

-10.8 7/14/2011 11:55 3.88E+02 4.20E+02 4.38E+02 1.24E-01 1.06E+00 1.26E+00 4.78E+00 1.13E+01 1.32E+01 3.12E+00 1.22E+01 1.46E+01 NA NA NA 6.81E+02 U3-4D U3-4D Q3-2011 030 25.6

-10.8 7/29/2011 11:05 6.73E+02 4.02E+02 3.04E+02 1.23E-01 1.58E+00 1.90E+00 5.66E+00 8.43E+00 1.05E+01

-2.58E+00 9.30E+00 9.06E+00 NA NA NA 6.81E+02 U3-4D U3-4D Q4-2011 031 25.6

-10.8 11/16/2011 12:56 3.50E+02 3.63E+02 3.81E+02 3.17E-01 1.38E+00 1.64E+00

-9.88E-01 8.82E+00 1.07E+01

-9.21E-01 9.27E+00 1.17E+01 NA NA NA 6.81E+02 U3-4D U3-4S Q2-2011 003 4/25/2011 14:13 1.48E+02 3.78E+02 4.22E+02 6.69E-01 1.27E+00 1.41E+00 5.35E+00 8.82E+00 1.07E+01 1.75E+00 8.92E+00 1.03E+01 NA NA NA 6.10E+02 ND ND ND NA U3-4S U3-4S Q2-2011 Mid 004 7/14/2011 11:27 3.29E+02 4.11E+02 4.36E+02 1.06E+00 1.33E+00 1.40E+00

-2.41E+00 7.59E+00 7.88E+00 3.25E+00 7.65E+00 9.52E+00 NA NA NA 6.10E+02 U3-4S U3-4S Q3-2011 005 7/29/2011 10:06 4.67E+02 3.84E+02 3.43E+02 2.84E-01 1.64E+00 1.90E+00 9.19E+00 1.58E+01 9.23E+00 7.83E-01 1.02E+01 1.17E+01 NA NA NA 6.10E+02 U3-4S U3-4S Q4-2011 006 11/16/2011 11:28 7.52E+02 4.41E+02 3.32E+02 9.35E-01 1.38E+00 1.47E+00

-2.06E+00 9.27E+00 1.12E+01 1.63E+00 7.80E+00 1.08E+01 NA NA NA 6.10E+02 U3-4S U3-T1 Q1-2011 031 5.7 2.8 2/22/2011 11:11 6.55E+02 4.08E+02 3.92E+02 1.62E+00 1.96E+00 2.02E+00 1.80E+00 1.05E+01 6.14E+00 2.12E+00 6.42E+00 7.54E+00 NA NA NA 8.02E+02 ND ND ND NA U3-T1 U3-T1 Q2-2011 032 5.7 2.8 5/6/2011 10:23 7.82E+02 5.16E+02 5.03E+02

-6.43E-02 9.94E-01 1.30E+00

-3.24E+00 9.12E+00 9.22E+00 8.49E-01 1.09E+01 1.21E+01 NA NA NA 8.02E+02 U3-T1 U3-T1 Q3-2011 033 5.7 2.8 8/22/2011 14:40 1.00E+03 3.42E+02 1.95E+02

-6.26E-02 1.10E+00 1.37E+00

-4.61E-01 8.70E+00 8.45E+00

-2.62E+00 8.31E+00 8.23E+00 NA NA NA 8.02E+02 U3-T1 U3-T1 Q4-2011 034 5.7 2.8 10/19/2011 11:39 7.69E+02 4.05E+02 3.84E+02 1.59E-01 1.19E+00 1.45E+00

-3.93E-01 9.51E+00 1.17E+01 2.12E-01 9.12E+00 1.17E+01 NA NA NA 8.02E+02 U3-T1 U3-T2 Q1-2011 036 5.7 2.6 2/22/2011 14:30 2.27E+03 4.92E+02 3.62E+02 1.82E+00 2.04E+00 2.05E+00 3.65E+00 6.08E+00 7.29E+00 5.97E-01 7.12E+00 7.85E+00 NA NA NA 2.88E+03 ND ND ND NA U3-T2 U3-T2 Q2-2011 037 5.7 2.6 5/6/2011 11:41 3.83E+03 6.42E+02 4.19E+02 3.27E-01 1.32E+00 1.58E+00 2.82E+00 7.26E+00 8.74E+00 5.77E-01 9.68E+00 1.08E+01 NA NA NA 2.88E+03 U3-T2 U3-T2 Q2-2011 Mid 038 5.7 2.6 7/8/2011 10:55 2.67E+03 6.63E+02 2.80E+02 4.75E-01 1.31E+00 1.50E+00 3.77E+00 1.08E+01 1.19E+01

-1.06E+00 1.02E+01 1.07E+01 NA NA NA 2.88E+03 U3-T2 U3-T2 Q3-2011 039 5.7 2.6 7/29/2011 12:32 2.65E+03 7.02E+02 3.34E+02 1.05E+00 1.81E+00 1.99E+00

-5.43E-01 8.49E+00 9.21E+00 2.63E+00 8.91E+00 1.07E+01 NA NA NA 2.88E+03 U3-T2 U3-T2 Q4-2011 040 5.7 2.6 10/19/2011 10:20 2.98E+03 7.62E+02 3.28E+02

-8.79E-02 1.15E+00 1.47E+00

-4.88E+00 1.02E+01 1.09E+01

-5.13E+00 1.12E+01 1.23E+01 NA NA NA 2.88E+03 U3-T2 U1-CSS Q2-2011 016 14 6.1 5/4/2011 13:24 6.38E+03 6.84E+02 3.40E+02 1.61E+01 2.70E+00 1.01E+00 3.29E+00 8.36E+00 9.79E+00 7.12E+00 9.42E+00 1.24E+01

-1.05E+01 1.55E+01 1.84E+01 6.29E+03 1.00E+01 ND ND ND U1-CSS U1-CSS Q2-2011 Mid 017 14 6.1 7/8/2011 13:33 1.08E+04 1.28E+03 2.79E+02 3.90E+00 1.82E+00 1.30E+00 3.84E-02 9.18E+00 1.01E+01

-3.60E+00 9.96E+00 1.06E+01

-3.20E+00 2.09E+01 2.34E+01 6.29E+03 1.00E+01 U1-CSS U1-CSS Q4-2011 018 14 6.1 10/27/2011 13:02 1.70E+03 5.64E+02 4.77E+02 7.82E-01 1.28E+00 1.39E+00

-2.80E+00 8.07E+00 8.99E+00 1.05E+00 7.08E+00 9.69E+00

-8.01E+00 1.78E+01 2.07E+01 6.29E+03 1.00E+01 U1-CSS U1-NCD Q3-2011 011 9/15/2011 11:45 3.86E+03 6.39E+02 3.99E+02 9.08E+01 7.80E+00 1.54E+00 4.77E+03 6.42E+02 8.81E+00 3.36E+00 4.68E+00 5.97E+00 1.14E+02 2.09E+01 1.82E+01 5.83E+03 4.05E+01 6.14E+03 ND 1.49E+02 U1-NCD U1-NCD Q4-2011 012 10/3/2011 13:20 1.13E+04 1.03E+03 3.35E+02 1.58E+01 3.72E+00 1.74E+00 5.92E+03 8.04E+02 1.43E+01 1.93E+00 7.20E+00 9.97E+00 1.36E+02 2.21E+01 1.86E+01 5.83E+03 4.05E+01 6.14E+03 1.49E+02 U1-NCD U1-NCD Q4-2011 013 12/26/2011 12:45 2.32E+03 5.13E+02 3.74E+02 1.49E+01 5.52E+00 3.33E+00 7.73E+03 9.75E+02 1.84E+01

-1.01E+00 9.48E+00 1.17E+01 1.96E+02 2.79E+01 1.88E+01 5.83E+03 4.05E+01 6.14E+03 1.49E+02 U1-NCD U1-SFDS Q3-2011 013 9/15/2011 11:35 2.09E+03 5.25E+02 4.00E+02 7.79E+00 2.54E+00 1.39E+00 9.23E+00 6.72E+00 6.70E+00 1.14E+00 6.27E+00 7.16E+00

-4.97E+00 1.70E+01 1.95E+01 2.06E+03 5.33E+00 9.23E+00 ND 2.06E+01 U1-SFDS U1-SFDS Q4-2011 014 10/5/2011 9:00 2.02E+03 5.01E+02 3.35E+02 5.54E+00 2.53E+00 1.97E+00 4.27E+00 9.96E+00 1.25E+01

-6.39E+00 8.94E+00 9.49E+00 2.06E+01 1.87E+01 2.00E+01 2.06E+03 5.33E+00 9.23E+00 2.06E+01 U1-SFDS U1-SFDS Q4-2011 015 12/28/2011 8:19 1.10E+02 3.21E+02 3.61E+02 2.66E+00 2.22E+00 2.08E+00

-3.38E+00 9.87E+00 1.13E+01 3.75E-01 1.02E+01 1.33E+01

-4.44E+00 1.47E+01 1.73E+01 2.06E+03 5.33E+00 9.23E+00 2.06E+01 U1-SFDS I-2 Q3-2011 003 8/12/2011 15:13 2.34E+02 2.15E+02 2.00E+02

-5.95E-01 7.44E-01 1.16E+00 5.11E+00 1.19E+01 1.35E+01

-2.57E-01 9.24E+00 1.02E+01 NA NA NA 2.34E+02 ND ND ND NA I-2 I-2 Q4-2011 004 12/8/2011 14:15

-3.49E+01 3.45E+02 4.09E+02

-2.39E-01 1.56E+00 1.92E+00

-2.35E+00 8.76E+00 1.00E+01

-2.12E+00 8.46E+00 1.04E+01 NA NA NA 2.34E+02 I-2 MH-5 VCFD7 Q1-2011 014 2/28/2011 9:47 5.17E+03 6.58E+02 3.66E+02 1.90E+00 1.99E+00 1.94E+00 3.45E-01 5.64E+00 6.19E+00

-1.28E+00 6.18E+00 6.45E+00 NA NA NA 1.34E+04 ND ND ND NA MH-5 VCFD7 MH-5 VCFD Q2-2011 015 4/22/2011 13:37 1.25E+04 1.10E+03 4.46E+02 8.17E-01 1.85E+00 2.08E+00

-3.21E+00 8.36E+00 8.43E+00

-1.60E+00 9.06E+00 9.51E+00 NA NA NA 1.34E+04 MH-5 VCFD MH-5 VCFD Q2-2011 Mid 018 7/7/2011 14:29 2.97E+03 7.02E+02 2.83E+02

-3.05E-01 8.04E-01 1.11E+00 9.24E-01 7.95E+00 8.84E+00 5.11E-01 8.49E+00 9.13E+00 NA NA NA 1.34E+04 MH-5 VCFD MH-5 VCFD Q2-2011 Mid 019 7/12/2011 12:46 9.86E+03 1.23E+03 2.81E+02 9.15E-01 1.05E+00 1.06E+00

-1.17E+01 1.33E+01 1.52E+01

-1.19E+00 9.99E+00 1.06E+01 NA NA NA 1.34E+04 MH-5 VCFD MH-5 VCFD Q2-2011 Mid 020 7/20/2011 10:48 2.89E+03 7.32E+02 3.35E+02

-4.57E-01 1.01E+00 1.47E+00 1.79E+00 6.30E+00 7.26E+00

-2.61E+00 8.34E+00 8.34E+00 NA NA NA 1.34E+04 MH-5 VCFD MH-5 VCFD Q2-2011 Mid 021 7/26/2011 12:50 1.86E+03 6.03E+02 3.33E+02

-7.10E-01 9.45E-01 1.45E+00 2.81E+00 7.47E+00 8.99E+00

-8.33E-01 9.66E+00 1.03E+01 NA NA NA 1.34E+04 MH-5 VCFD MH-5 VCFD Q3-2011 022 8/3/2011 14:12 3.90E+03 8.31E+02 3.31E+02

-4.45E-01 1.07E+00 1.50E+00

-6.18E-01 1.01E+01 1.10E+01

-6.71E+00 1.43E+01 1.29E+01 NA NA NA 1.34E+04 MH-5 VCFD MH-5 VCFD Q3-2011 023 8/11/2011 12:39 2.74E+04 1.65E+03 2.02E+02 6.43E-01 1.19E+00 1.32E+00

-2.20E+00 7.47E+00 7.63E+00 1.85E+00 5.85E+00 7.32E+00 NA NA NA 1.34E+04 MH-5 VCFD MH-5 VCFD Q3-2011 024 8/18/2011 9:50 2.09E+04 1.87E+03 2.64E+02 9.64E-01 1.55E+00 1.70E+00 1.90E+00 7.98E+00 9.05E+00

-3.10E+00 9.60E+00 9.54E+00 NA NA NA 1.34E+04 MH-5 VCFD MH-5 VCFD Q3-2011 Mid 025 8/24/2011 11:01 1.40E+04 1.51E+03 2.58E+02 5.99E-01 1.30E+00 1.46E+00

-2.36E+00 7.86E+00 8.21E+00 3.46E+00 7.98E+00 9.92E+00 NA NA NA 1.34E+04 MH-5 VCFD MH-5 VCFD Q3-2011 Mid 026 8/30/2011 13:55 3.37E+04 1.83E+03 2.03E+02 9.19E-01 1.31E+00 1.40E+00 1.76E+00 7.23E+00 8.47E+00

-1.69E+00 7.86E+00 7.79E+00 NA NA NA 1.34E+04 MH-5 VCFD MH-5 VCFD Q4-2011 027 10/17/2011 10:07 1.48E+04 1.09E+03 3.86E+02

-5.57E-01 1.17E+00 1.65E+00 1.51E+00 7.68E+00 9.98E+00

-2.77E+00 7.92E+00 9.24E+00 NA NA NA 1.34E+04 MH-5 VCFD MH-5 VCFD Q4-2011 028 10/31/2011 14:20 2.40E+04 1.37E+03 3.89E+02 1.06E+00 1.72E+00 1.87E+00 5.56E+00 1.15E+01 1.61E+01 3.37E-01 1.09E+01 1.53E+01 NA NA NA 1.34E+04 MH-5 VCFD LAF-002 Q2-2011 015

-22.3 5/2/2011 12:50 6.69E+01 3.04E+02 3.43E+02 1.16E+00 1.55E+00 1.66E+00

-5.80E-01 7.86E+00 8.57E+00

-6.46E-01 7.24E+00 7.65E+00

-3.48E-01 1.60E+01 1.83E+01 ND ND ND ND ND LAF-002 LAF-002 Q4-2011 016

-22.3 12/13/2011 10:31 6.96E+01 4.14E+02 4.79E+02 1.65E+00 1.67E+00 1.75E+00

-3.83E+00 9.48E+00 1.11E+01 5.21E+00 8.73E+00 1.29E+01 6.36E+00 1.11E+01 1.22E+01 LAF-002

TABLE 3 FOURTH QUARTER 2011 GROUNDWATER ANALYTICAL RESULTS AND AVERAGES INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q42011 FINAL Table 3 - Forth Quarter 2011 Groundwater Analytical Results and Averages.xlsx; Q42011 Table 3 Page 7 of 7 See Page 7 for Notes TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Date Time Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Result Std. Dev.9 MDC Average Average Average Average Average ANALYSIS RESULTS5 YEARLY ROLLING AVERAGES4,6 Well ID1 TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

SAMPLE COLLECTION Well ID1 SAMPLING QUARTER2,8 SAMPLE ID SAMPLE ZONE CENTER Depth Ft Below Top of Casing3 SAMPLE ZONE CENTER Elevation Ft msl3 B-17 Q1-2011 011 2/14/2011 15:44 3.82E+03 5.88E+02 3.65E+02 5.41E-02 1.70E+00 2.14E+00 2.15E+01 1.22E+01 6.75E+00

-1.81E+00 7.00E+00 7.25E+00 NA NA NA 4.22E+03 ND 1.90E+01 ND NA B-17 B-1 Q2-2011 012 4/25/2011 10:50 8.10E+03 9.22E+02 4.53E+02

-6.21E-03 1.74E+00 2.09E+00 2.05E+01 1.33E+01 1.03E+01 3.18E+00 9.06E+00 1.11E+01 NA NA NA 4.22E+03 1.90E+01 B-1 B-1 Q3-2011 013 8/17/2011 13:17 7.36E+02 3.03E+02 1.96E+02

-6.00E-02 9.87E-01 1.25E+00 1.51E+01 1.49E+01 7.29E+00

-4.01E-01 7.02E+00 7.34E+00 NA NA NA 4.22E+03 1.90E+01 B-1 B-67 Q1-2011 011 2/28/2011 11:27 8.39E+02 3.90E+02 3.65E+02 6.28E-01 1.78E+00 2.05E+00 4.45E+00 5.82E+00 7.02E+00

-1.35E+00 6.50E+00 6.88E+00 NA NA NA 1.18E+03 ND ND ND NA B-67 B-6 Q2-2011 012 4/25/2011 9:48 2.68E+03 6.18E+02 4.53E+02

-6.69E-01 1.58E+00 2.09E+00

-1.31E-01 8.56E+00 9.08E+00 4.73E+00 1.06E+01 1.35E+01 NA NA NA 1.18E+03 B-6 B-6 Q2-2011 Mid 013 7/8/2011 11:05 5.39E+02 3.54E+02 2.82E+02 1.32E+00 1.56E+00 1.63E+00 6.09E+00 1.58E+01 8.04E+00

-2.64E+00 8.97E+00 8.84E+00 NA NA NA 1.18E+03 B-6 B-6 Q3-2011 014 7/29/2011 10:52 6.45E+02 4.14E+02 3.38E+02

-2.59E-01 1.39E+00 1.79E+00 1.60E+00 7.74E+00 8.72E+00 4.72E+00 5.07E+00 7.82E+00 NA NA NA 1.18E+03 B-6 B-6 Q4-2011 015 10/20/2011 12:01 1.70E+02 3.48E+02 3.87E+02

-1.65E-01 1.57E+00 1.98E+00

-3.07E+00 7.65E+00 8.33E+00 1.53E+00 8.34E+00 1.10E+01 NA NA NA 1.18E+03 B-6 Notes:

1. For nested multi-level monitoring wells, suffix of well ID indicates depth (rounded to nearest foot) from reference point on casing to bottom of well screen. For Waterloo multi-level systems, suffix indicates depth (rounded to nearest foot) from reference point on casing to top of sampling port. Well IDs without a suffix are open bedrock wellbores.
2. All analytical results from the last 12 months from each location are provided. Monitoring locations are sampled quarterly, bi-annually, or annually, and as necessary during the year.
3. Sampling depths within sampling intervals (i.e. location of pump intake) have been located adjacent to a transmissive zone where possible.
4. Averages provided are analytical result averages of all valid samples (including mid-quarter and confirmatory samples) collected from each monitoring location from the first quarter of 2010 (Q1-2011) to the fourth quarter of 2011 (Q4-2011) including the post Q4-2011 samples, if collected.

Monitoring locations are sampled quarterly, bi-annually, or annually and additional samples are collected when necessary. Therefore, some results provided are the average of more than 4 samples.

For quarters in which samples were reanalyzed due to potential false positives, both results were used to calculate averages if subsequent results confirmed the validity of the original sample/analysis. For cases in which reanalysis discredited the validity of the original sample result, the replacement results were used to calculate the average. If analytical results resulted in resampling, and the resample result discredited the validity of the original sample result of a particular radionuclide, the original sample results were not used for any radionuclides and only the resample result was used. For cases in which an aliquot of the original sample was reanalyzed, if the result of the aliquot confirmed the original result, then the aliquot result and the original result were averaged and the average of the two was used to calculate the rolling average. If the aliquot result indicated the original result was false, then only the aliquot result was used to calculate the rolling average.

5. NA indicates that the constituent was not analyzed.
6. ND indicates that all of the analytical results used to calculate the average were less than MDC and/or 3 times the 1 sigma uncertainty.
7. These locations are storm drains or foundation drains.
8. Mid-quarter samples were collected and analyzed to evaluate the potential effect of certain operations on groundwater quality or to further evaluate the groundwater conditions.
9. Column designated as Std. Dev. provides the three times 1 sigma uncertainty values.
  • The Q1 2011 MW-40-100, MW-40-127 and MW-51-189 Cs-137 results were verified by re-analysis. However, based on the available chemistry and Site hydrogeologic data, these values do not appear to be representative of the groundwater conditions at these sampling intervals.
    • The Q2 2011 MW-40-46 preliminary Sr-90 result was 2.83 pCi/L and exceeded the IL. However, after re-analysis, the sample was below the detection limit which suggests the preliminary result was likely a false positive. A shift in the MDC for the preliminary result could have possibly resulted from contaminated laboratory equipment, modified count time, or changes in sample preparation.
      • The Post-Q3 2011 MW-58-65 preliminary Sr-90 result was 3.64 pCi/L and exceeded the IL. However, after re-analysis, the sample was below the detection limit which suggests the preliminary result was likely a false positive. A shift in the MDC for the preliminary result could have possibly resulted from contaminated laboratory equipment, modified count time, or changes in sample preparation.

TABLE 4 2011 1st QUARTER GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERTY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q12011 FINAL Table 4 - 2011 1st Quarter Groundwater Analytical Results.xlsx; Q12011 Table 4 Page 1 of 2 See Page 2 for Notes Date Time Result Std. Dev.6 MDC I.L.3,7 Result Std. Dev.6 MDC I.L.3 Result Std. Dev.6 MDC I.L.3 Result Std. Dev.6 MDC I.L.3 Result Std. Dev.6 MDC I.L.3 MW-30-84 028 2/9/2011 12:57 9.20E+03 8.86E+02 3.79E+02 1.22E+04 1.12E+00 1.82E+00 1.98E+00 2.00E+00 5.89E-01 4.74E+00 5.22E+00 positive 1.09E+00 5.76E+00 6.49E+00 positive NA NA NA positive MW-30-84 MW-30-84 029 3/31/2011 12:03 9.04E+03 1.06E+03 4.74E+02 1.22E+04

-4.78E-01 1.66E+00 2.13E+00 2.00E+00 5.00E-01 1.12E+01 1.21E+01 positive

-3.04E+00 9.48E+00 9.12E+00 positive NA NA NA positive MW-30-84 MW-31-49 029 2/9/2011 13:12 1.06E+03 3.40E+02 2.98E+02 4.28E+04

-5.51E-01 1.76E+00 2.14E+00 2.00E+00 1.39E+00 5.22E+00 6.02E+00 positive 4.84E-01 5.26E+00 5.91E+00 positive NA NA NA positive MW-31-49 MW-31-49 030 3/30/2011 12:33 4.31E+03 7.84E+02 4.65E+02 4.28E+04 1.77E+00 2.04E+00 2.16E+00 2.00E+00

-2.34E+00 7.80E+00 8.17E+00 positive

-5.38E-01 9.18E+00 1.00E+01 positive NA NA NA positive MW-31-49 MW-31-63 029 2/9/2011 13:14 2.46E+04 1.10E+03 2.98E+02 3.99E+04 4.29E-01 1.78E+00 2.08E+00 2.00E+00

-1.42E+00 6.46E+00 6.81E+00 positive

-2.31E+00 6.42E+00 6.26E+00 positive NA NA NA positive MW-31-63 MW-31-63 030 3/30/2011 13:13 1.33E+04 1.14E+03 4.53E+02 3.99E+04 1.49E+00 1.87E+00 2.02E+00 2.00E+00 8.76E-01 9.00E+00 9.97E+00 positive

-1.92E-01 7.26E+00 7.92E+00 positive NA NA NA positive MW-31-63 MW-31-85 029 2/9/2011 13:03 4.83E+03 6.84E+02 3.82E+02 1.46E+04 3.26E-01 1.79E+00 2.18E+00 2.00E+00 3.19E+00 5.96E+00 7.08E+00 positive 3.14E+00 6.06E+00 7.39E+00 positive NA NA NA positive MW-31-85 MW-31-85 030 3/30/2011 12:55 7.75E+02 4.66E+02 4.52E+02 1.46E+04 9.37E-01 1.81E+00 2.00E+00 2.00E+00 5.90E+00 1.31E+01 8.10E+00 positive 6.43E+00 8.88E+00 1.17E+01 positive NA NA NA positive MW-31-85 MW-32-59 023 3/1/2011 11:28 4.39E+03 6.42E+02 3.59E+02 3.42E+04 1.25E+00 1.49E+00 1.55E+00 2.00E+00 6.56E-01 5.82E+00 6.63E+00 positive

-4.41E-01 7.00E+00 7.58E+00 positive NA NA NA positive MW-32-59 MW-32-59 024 3/31/2011 12:46 3.37E+04 1.96E+03 5.07E+02 3.42E+04

-2.13E-01 1.15E+00 1.51E+00 2.00E+00 8.24E-01 8.92E+00 9.96E+00 positive 1.99E-02 1.02E+01 1.11E+01 positive NA NA NA positive MW-32-59 MW-32-85 026 3/1/2011 12:05 1.34E+04 1.41E+03 2.62E+02 1.63E+04 3.81E-01 1.41E+00 1.63E+00 2.00E+00 7.79E-01 8.26E+00 9.36E+00 positive 4.73E+00 9.72E+00 1.24E+01 positive NA NA NA positive MW-32-85 MW-32-85 027 3/31/2011 13:18 1.32E+04 1.27E+03 5.07E+02 1.63E+04

-1.62E-01 1.20E+00 1.56E+00 2.00E+00

-6.56E-01 7.26E+00 7.61E+00 positive 3.80E+00 8.28E+00 1.02E+01 positive NA NA NA positive MW-32-85 MW-32-149 023 3/1/2011 13:37 1.06E+03 4.48E+02 2.68E+02 1.00E+03

-7.01E-01 1.66E+00 2.15E+00 2.00E+00 9.25E-01 5.42E+00 6.30E+00 positive 2.06E+00 6.60E+00 7.93E+00 positive NA NA NA positive MW-32-149 MW-32-149 024 3/31/2011 11:33 8.99E+02 5.34E+02 5.09E+02 1.00E+03

-2.01E-01 1.10E+00 1.49E+00 2.00E+00 2.52E+00 9.30E+00 1.09E+01 positive 2.31E+00 9.92E+00 1.18E+01 positive NA NA NA positive MW-32-149 MW-32-173 021 3/1/2011 13:13 9.02E+02 4.12E+02 2.61E+02 1.50E+03

-4.04E-01 1.12E+00 1.45E+00 2.00E+00 5.99E+00 6.06E+00 7.73E+00 positive

-2.04E+00 7.36E+00 7.55E+00 positive NA NA NA positive MW-32-173 MW-32-173 022 3/31/2011 11:35 8.41E+02 5.22E+02 5.04E+02 1.50E+03 2.46E-01 1.27E+00 1.54E+00 2.00E+00 6.51E+00 1.58E+01 8.26E+00 positive 2.19E+00 8.22E+00 9.98E+00 positive NA NA NA positive MW-32-173 MW-32-190 025 3/1/2011 13:24 1.64E+03 5.32E+02 2.64E+02 4.21E+03 7.65E-01 1.20E+00 1.29E+00 2.00E+00 2.74E+00 5.52E+00 6.57E+00 positive 4.88E+00 7.64E+00 8.75E+00 positive NA NA NA positive MW-32-190 MW-32-190 026 3/31/2011 11:47 1.41E+03 5.76E+02 5.02E+02 4.21E+03

-7.79E-01 1.15E+00 1.67E+00 2.00E+00 8.78E-01 7.96E+00 9.01E+00 positive 5.11E+00 1.04E+01 1.30E+01 positive NA NA NA positive MW-32-190 MW-36-24 020 2/28/2011 12:37 2.56E+02 3.54E+02 3.81E+02 2.56E+03

-8.87E-02 1.67E+00 2.08E+00 2.00E+00 4.53E-01 5.26E+00 5.75E+00 positive

-3.09E-01 4.74E+00 5.03E+00 positive NA NA NA positive MW-36-24 MW-36-41 021 2/28/2011 13:53 8.74E+03 6.88E+02 2.97E+02 2.10E+04 4.11E+00 1.87E+00 1.57E+00 7.99E+00 1.31E+00 5.26E+00 6.09E+00 positive 1.58E+00 5.68E+00 6.65E+00 positive NA NA NA positive MW-36-41 MW-36-52 020 2/28/2011 12:43 3.14E+03 4.92E+02 3.37E+02 1.48E+04 1.33E+00 2.00E+00 2.14E+00 8.14E+00

-6.00E+00 5.58E+00 4.80E+00 positive

-2.66E+00 5.94E+00 5.65E+00 positive NA NA NA positive MW-36-52 MW-37-22 021 1/27/2011 15:19 6.74E+03 6.18E+02 2.98E+02 9.19E+03 1.04E+01 2.52E+00 1.68E+00 2.20E+01

-2.18E+00 4.74E+00 4.94E+00 positive 2.59E+00 5.38E+00 6.55E+00 positive NA NA NA positive MW-37-22 MW-37-32 021 1/27/2011 15:09 4.57E+03 5.28E+02 2.98E+02 9.32E+03 1.49E+01 3.02E+00 1.74E+00 3.54E+01 4.20E-01 6.12E+00 6.85E+00 positive 1.72E+00 6.60E+00 7.76E+00 positive NA NA NA positive MW-37-32 MW-37-40 021 1/27/2011 13:35 5.97E+03 7.42E+02 3.82E+02 9.02E+03 1.93E+01 3.34E+00 1.85E+00 2.84E+01 1.95E+00 5.84E+00 6.78E+00 positive 2.03E+00 6.84E+00 7.92E+00 positive NA NA NA positive MW-37-40 MW-37-57 021 1/27/2011 15:26 5.63E+03 5.76E+02 2.99E+02 9.62E+03 2.02E+01 3.60E+00 1.96E+00 3.68E+01

-3.70E-01 6.34E+00 6.92E+00 positive

-1.36E+00 5.64E+00 5.68E+00 positive NA NA NA positive MW-37-57 MW-40-27 014 3/8/2011 12:55 1.85E+02 2.56E+02 2.65E+02 1.00E+03 1.58E-01 1.37E+00 1.61E+00 2.00E+00 3.72E-01 6.78E+00 7.39E+00 positive 2.83E+00 8.56E+00 9.99E+00 positive NA NA NA positive MW-40-27 MW-40-46 015 3/8/2011 12:58 2.48E+02 2.74E+02 2.63E+02 1.00E+03 1.03E-01 8.58E-01 1.07E+00 2.00E+00 2.82E+00 8.00E+00 9.18E+00 positive 7.99E+00 8.74E+00 1.19E+01 positive NA NA NA positive MW-40-46 MW-40-81 015 3/8/2011 10:17 2.33E+02 2.68E+02 2.63E+02 1.00E+03 8.50E-01 1.51E+00 1.67E+00 2.00E+00 1.26E+00 1.06E+01 7.71E+00 positive

-1.45E+00 6.08E+00 6.16E+00 positive NA NA NA positive MW-40-81 MW-40-100**

017 3/8/2011 10:27 5.17E+01 2.14E+02 2.64E+02 1.00E+03 2.52E-02 1.30E+00 1.58E+00 2.00E+00 2.46E+01**

1.35E+01 7.66E+00 positive

-1.40E+00 7.88E+00 8.30E+00 positive NA NA NA positive MW-40-100**

MW-40-127**

017 3/8/2011 10:41 1.33E+02 2.40E+02 2.64E+02 1.00E+03 1.03E+00 1.40E+00 1.51E+00 2.00E+00 5.07E+01**

1.64E+01 7.63E+00 positive 3.45E-01 7.18E+00 7.96E+00 positive NA NA NA positive MW-40-127**

MW-40-162 015 3/8/2011 11:02 8.33E+01 2.24E+02 2.63E+02 1.00E+03

-1.03E+00 1.07E+00 1.57E+00 2.00E+00

-3.72E+00 6.12E+00 5.93E+00 positive

-2.11E+00 6.42E+00 6.37E+00 positive NA NA NA positive MW-40-162 MW-41-40 019 2/14/2011 14:05 2.03E+03 4.02E+02 2.98E+02 1.00E+03 1.15E+01 2.68E+00 1.83E+00 7.28E+00 4.60E+00 7.30E+00 8.61E+00 positive 4.22E+00 7.36E+00 9.28E+00 positive NA NA NA positive MW-41-40 MW-41-63 018 2/14/2011 13:37 1.23E+03 4.44E+02 3.80E+02 1.00E+03 6.92E+00 2.46E+00 1.96E+00 7.36E+00 1.24E+00 5.30E+00 6.03E+00 positive 2.69E+00 6.06E+00 7.29E+00 positive NA NA NA positive MW-41-63 MW-42-49 024 3/4/2011 11:37 1.49E+03 5.14E+02 3.88E+02 3.16E+04 2.32E+01 3.34E+00 1.11E+00 9.00E+01 3.30E+04 4.42E+03 2.75E+01 6.58E+04 1.42E+00 6.78E+00 7.87E+00 positive 3.02E+02 3.04E+01 2.00E+01 673.5 MW-42-49 MW-42-78 019 3/4/2011 10:58 5.98E+02 4.06E+02 3.84E+02 1.00E+03 8.92E-01 1.47E+00 1.60E+00 2.00E+00

-2.03E+00 6.72E+00 6.99E+00 positive 8.03E-02 6.70E+00 7.41E+00 positive 0.00E+00 1.73E+01 1.96E+01 positive MW-42-78 MW-43-28 018 2/15/2011 13:08 2.54E+02 2.80E+02 2.99E+02 1.00E+03

-1.06E+00 1.40E+00 2.00E+00 2.00E+00 5.75E-02 1.26E+01 7.06E+00 positive

-3.84E+00 6.84E+00 6.54E+00 positive NA NA NA positive MW-43-28 MW-43-62 018 2/15/2011 13:15 1.82E+02 2.76E+02 3.00E+02 1.00E+03 7.75E-01 1.74E+00 1.95E+00 2.00E+00 6.59E-01 5.08E+00 5.56E+00 positive

-2.37E-01 5.16E+00 5.52E+00 positive NA NA NA positive MW-43-62 MW-44-66 019 2/18/2011 10:41 4.57E+02 3.90E+02 3.99E+02 1.00E+03

-2.94E-01 1.59E+00 1.95E+00 2.00E+00 1.74E+00 7.72E+00 8.56E+00 positive

-1.40E+00 7.92E+00 8.46E+00 positive NA NA NA positive MW-44-66 MW-44-102 020 2/18/2011 10:44 3.93E+02 2.90E+02 2.97E+02 1.00E+03 2.63E-01 1.86E+00 2.15E+00 2.00E+00 2.22E-01 4.96E+00 5.47E+00 positive

-2.93E-01 6.02E+00 6.58E+00 positive NA NA NA positive MW-44-102 MW-45-42 023 2/16/2011 16:58 8.12E+03 7.86E+02 3.63E+02 5.90E+03 1.03E+00 1.39E+00 1.48E+00 2.00E+00

-8.53E-01 5.64E+00 5.99E+00 positive 1.42E+00 6.30E+00 7.17E+00 positive NA NA NA positive MW-45-42 MW-45-61 023 2/16/2011 16:15 1.84E+03 5.20E+02 3.98E+02 2.65E+03

-2.25E-01 1.64E+00 1.96E+00 2.00E+00 1.38E+00 4.80E+00 5.41E+00 positive 9.89E-01 5.46E+00 6.15E+00 positive NA NA NA positive MW-45-61 MW-46 023 2/23/2011 12:46 2.47E+03 5.70E+02 3.98E+02 1.84E+03 1.12E+00 1.89E+00 2.06E+00 2.00E+00

-2.22E+00 5.28E+00 5.28E+00 positive 5.21E-01 5.10E+00 5.66E+00 positive NA NA NA positive MW-46 MW-49-26 023 1/28/2011 13:37 3.17E+03 6.00E+02 4.29E+02 6.52E+03 1.30E+01 2.86E+00 2.01E+00 2.79E+01 3.39E-01 1.04E+01 7.00E+00 positive

-2.43E+00 6.42E+00 6.44E+00 positive

-4.38E+00 1.87E+01 2.20E+01 positive MW-49-26 MW-49-42 023 1/28/2011 13:00 2.45E+03 5.38E+02 3.86E+02 4.97E+03 2.30E+01 4.02E+00 2.02E+00 3.72E+01

-1.07E+00 5.74E+00 6.21E+00 positive

-2.45E+00 5.50E+00 5.32E+00 positive

-3.26E+00 1.86E+01 2.18E+01 positive MW-49-42 MW-49-65 023 1/28/2011 13:15 1.94E+03 5.02E+02 3.85E+02 3.03E+03 1.15E+01 3.28E+00 2.06E+00 2.62E+01

-6.30E-01 4.96E+00 5.21E+00 positive 7.15E-01 5.20E+00 5.81E+00 positive

-9.08E+00 1.83E+01 2.20E+01 positive MW-49-65 MW-50-42 024 2/25/2011 12:36 5.61E+02 3.88E+02 3.85E+02 1.04E+03 5.42E+00 2.34E+00 1.91E+00 1.10E+01

-1.29E-01 5.46E+00 5.88E+00 positive

-9.07E-01 4.42E+00 4.42E+00 positive

-7.19E+00 1.82E+01 2.18E+01 positive MW-50-42 MW-50-66 029 2/25/2011 12:36 3.76E+03 6.18E+02 3.83E+02 5.90E+03 2.61E+01 4.02E+00 2.13E+00 5.24E+01 2.94E+00 7.20E+00 8.24E+00 positive 6.79E-01 8.00E+00 9.10E+00 positive

-2.80E+00 1.81E+01 2.12E+01 positive MW-50-66 MW-51-40 018 3/8/2011 10:18 1.02E+02 2.34E+02 2.67E+02 1.00E+03 1.07E+00 1.51E+00 1.61E+00 2.00E+00

-7.97E+00 1.21E+01 1.36E+01 positive 2.42E+00 7.30E+00 8.76E+00 positive NA NA NA positive MW-51-40 MW-51-79 018 3/8/2011 10:34 1.36E+02 2.46E+02 2.70E+02 1.00E+03

-2.03E-01 1.22E+00 1.53E+00 2.00E+00 2.42E+00 5.42E+00 6.52E+00 positive

-2.74E+00 7.36E+00 6.45E+00 positive NA NA NA positive MW-51-79 MW-51-104 016 3/8/2011 12:10 5.76E+01 3.10E+02 3.55E+02 1.00E+03 8.91E-01 1.47E+00 1.60E+00 2.00E+00 2.54E+00 7.20E+00 8.14E+00 positive 9.02E-01 5.50E+00 6.24E+00 positive NA NA NA positive MW-51-104 MW-51-135 016 3/8/2011 12:44 8.29E+01 2.24E+02 2.62E+02 1.00E+03 8.62E-01 1.31E+00 1.42E+00 2.00E+00 8.60E-02 6.02E+00 6.77E+00 positive 2.37E+00 5.96E+00 7.38E+00 positive NA NA NA positive MW-51-135 MW-51-163 016 3/8/2011 13:01 0.00E+00 1.96E+02 2.63E+02 1.00E+03

-5.97E-01 1.39E+00 1.98E+00 2.00E+00 2.81E+00 6.54E+00 7.66E+00 positive 5.35E-01 7.76E+00 8.69E+00 positive NA NA NA positive MW-51-163 MW-51-189**

016 3/8/2011 12:30

-1.50E+01 1.93E+02 2.68E+02 1.00E+03

-3.06E-01 1.46E+00 1.97E+00 2.00E+00 3.77E+01**

1.47E+01 6.28E+00 positive 2.28E-01 5.28E+00 5.79E+00 positive NA NA NA positive MW-51-189**

MW-53-82 018 3/3/2011 11:53 5.95E+02 3.76E+02 3.73E+02 3.83E+03 1.61E+00 1.82E+00 1.91E+00 4.46E+00 3.61E+00 6.18E+00 7.60E+00 positive

-1.88E+00 7.02E+00 7.25E+00 positive

-7.63E+00 1.59E+01 1.85E+01 positive MW-53-82 MW-53-120 022 3/3/2011 12:00 3.84E+03 7.18E+02 3.89E+02 1.05E+04 2.95E+01 3.76E+00 1.13E+00 6.60E+01 2.30E+00 7.32E+00 8.49E+00 positive

-2.43E+00 8.14E+00 8.13E+00 positive 1.00E+01 1.70E+01 1.87E+01 positive MW-53-120 MW-54-37 016 2/1/2011 14:10 1.33E+03 4.86E+02 3.78E+02 2.71E+03 4.88E+00 1.77E+00 1.26E+00 9.20E+00

-1.42E+00 5.54E+00 5.67E+00 positive 3.12E-01 6.42E+00 7.04E+00 positive

-2.81E+00 1.59E+01 1.82E+01 positive MW-54-37 MW-54-58 016 2/1/2011 14:22 9.58E+02 4.56E+02 3.92E+02 1.48E+03 1.68E+00 1.34E+00 1.28E+00 3.43E+00

-4.20E-02 7.14E+00 7.94E+00 positive

-2.21E+00 6.84E+00 6.82E+00 positive

-4.89E+00 1.66E+01 1.92E+01 positive MW-54-58 MW-54-123 016 2/1/2011 14:11 1.08E+03 4.68E+02 3.90E+02 1.30E+03 2.56E+00 1.39E+00 1.08E+00 8.14E+00

-3.56E-01 6.02E+00 6.69E+00 positive

-3.66E-03 5.16E+00 5.75E+00 positive 2.50E+00 1.66E+01 1.87E+01 positive MW-54-123 MW-54-144 016 2/1/2011 12:34 1.35E+03 4.96E+02 3.87E+02 2.64E+03 9.31E+00 2.24E+00 1.06E+00 2.53E+01

-9.04E-01 6.14E+00 6.70E+00 positive

-6.36E-01 6.20E+00 6.74E+00 positive

-4.27E+00 1.58E+01 1.82E+01 positive MW-54-144 MW-54-173 016 2/1/2011 12:29 1.66E+03 5.26E+02 3.81E+02 3.63E+03 5.81E+00 1.88E+00 1.10E+00 1.22E+01

-2.87E-01 8.00E+00 8.79E+00 positive 1.01E+00 1.06E+01 1.20E+01 positive

-5.49E+00 1.77E+01 2.05E+01 positive MW-54-173 MW-54-190 016 2/1/2011 12:25 1.89E+03 5.56E+02 3.90E+02 3.49E+03 1.68E+01 3.36E+00 1.28E+00 4.03E+01 4.59E-01 6.34E+00 7.14E+00 positive

-3.55E+00 5.96E+00 5.21E+00 positive 1.71E+00 1.67E+01 1.89E+01 positive MW-54-190 MW-55-24 017 2/3/2011 14:13 1.02E+03 4.48E+02 4.20E+02 2.58E+03 1.09E+01 2.82E+00 1.96E+00 2.97E+01

-3.57E-01 4.92E+00 5.43E+00 positive 4.75E+00 8.74E+00 7.44E+00 positive

-5.31E+00 1.81E+01 2.14E+01 positive MW-55-24 MW-55-35 016 2/3/2011 14:16 1.70E+03 4.84E+02 3.86E+02 4.38E+03 1.93E+01 3.42E+00 2.05E+00 4.26E+01 8.32E-01 5.82E+00 6.45E+00 positive 1.03E+00 6.24E+00 7.03E+00 positive

-2.16E+00 1.86E+01 2.17E+01 positive MW-55-35 MW-55-54 017 2/3/2011 14:17 8.46E+03 8.58E+02 3.89E+02 1.28E+04 1.91E+01 3.78E+00 1.95E+00 3.93E+01 3.62E+00 5.80E+00 7.00E+00 positive

-6.59E-01 7.44E+00 7.93E+00 positive

-8.13E+00 1.78E+01 2.14E+01 positive MW-55-54 MW-60-35 016 2/11/2011 12:17 3.20E+02 3.72E+02 3.88E+02 2.00E+03 9.73E-01 1.63E+00 1.78E+00 2.00E+00 2.69E+00 6.24E+00 7.46E+00 positive 1.22E-01 3.76E+00 4.24E+00 positive

-1.61E+00 1.62E+01 1.84E+01 positive MW-60-35 MW-60-53 016 2/11/2011 10:57 3.19E+02 3.70E+02 3.87E+02 2.00E+03 7.44E-01 1.52E+00 1.70E+00 2.00E+00

-2.03E+00 5.88E+00 6.16E+00 positive 1.39E+00 7.96E+00 8.33E+00 positive

-1.39E+00 1.50E+01 1.72E+01 positive MW-60-53 MW-60-72 016 2/10/2011 12:54 3.64E+02 3.76E+02 3.84E+02 2.00E+03 2.41E-01 1.45E+00 1.70E+00 2.00E+00

-5.10E-02 9.12E+00 1.01E+01 positive 2.27E+00 8.84E+00 1.07E+01 positive 2.12E+00 1.54E+01 1.75E+01 positive MW-60-72 MW-60-135 016 2/10/2011 13:04 3.98E+02 3.78E+02 3.83E+02 2.00E+03 1.14E+00 1.82E+00 1.98E+00 2.00E+00 1.72E+00 6.72E+00 7.79E+00 positive 2.24E-01 7.44E+00 8.25E+00 positive

-3.56E+00 1.52E+01 1.76E+01 positive MW-60-135 MW-60-154 016 2/10/2011 12:53 5.44E+02 4.02E+02 3.87E+02 2.00E+03 2.32E-02 8.50E-01 1.07E+00 2.00E+00

-4.12E+00 9.26E+00 8.97E+00 positive 9.91E-01 7.86E+00 9.12E+00 positive 4.61E+00 1.52E+01 1.71E+01 positive MW-60-154 MW-60-176 016 2/10/2011 10:31 1.12E+03 4.68E+02 3.85E+02 2.00E+03 2.58E-01 1.49E+00 1.74E+00 2.00E+00 4.88E+00 1.13E+01 6.69E+00 positive

-1.75E+00 6.70E+00 6.74E+00 positive 7.24E+00 1.62E+01 1.79E+01 positive MW-60-176 MW-62-18 016 2/24/2011 12:49 1.81E+02 3.60E+02 4.00E+02 2.00E+03

-3.86E-01 1.71E+00 2.13E+00 2.00E+00 2.12E-01 4.74E+00 5.18E+00 positive 3.58E+00 5.46E+00 6.78E+00 positive NA NA NA positive MW-62-18 MW-62-37 016 2/24/2011 12:52 3.05E+02 3.76E+02 4.00E+02 2.00E+03 5.14E-01 1.84E+00 2.13E+00 2.00E+00 1.07E+00 6.06E+00 6.86E+00 positive

-2.84E+00 6.38E+00 6.28E+00 positive NA NA NA positive MW-62-37 MW-62-53 015 2/24/2011 12:57 3.08E+02 3.78E+02 4.03E+02 2.00E+03 8.98E-01 1.94E+00 2.18E+00 2.00E+00

-2.62E-01 4.72E+00 5.23E+00 positive

-1.84E+00 5.58E+00 5.81E+00 positive NA NA NA positive MW-62-53 MW-62-71 016 2/24/2011 12:40 5.38E+02 4.06E+02 4.03E+02 2.00E+03 1.28E-01 1.22E+00 1.48E+00 2.00E+00 4.10E+00 1.18E+01 6.67E+00 positive

-2.36E-01 5.00E+00 5.47E+00 positive NA NA NA positive MW-62-71 MW-62-92 016 2/24/2011 12:39 5.09E+02 4.00E+02 4.02E+02 2.00E+03 9.56E-01 1.85E+00 2.06E+00 2.00E+00 1.68E+00 5.38E+00 6.27E+00 positive

-1.45E+00 5.68E+00 5.86E+00 positive NA NA NA positive MW-62-92 MW-62-138 016 2/24/2011 14:54 5.17E+02 4.00E+02 4.01E+02 2.00E+03 2.15E+00 1.77E+00 1.75E+00 2.42E+00

-1.67E+00 4.72E+00 4.94E+00 positive 1.88E+00 7.04E+00 8.19E+00 positive NA NA NA positive MW-62-138 MW-62-182 016 2/24/2011 15:07 3.55E+02 3.84E+02 4.03E+02 2.00E+03

-1.46E-01 1.45E+00 1.94E+00 2.00E+00

-1.95E+00 6.24E+00 6.60E+00 positive 5.86E-01 6.60E+00 7.33E+00 positive NA NA NA positive MW-62-182 MW-63-18 016 3/2/2011 11:10 4.90E+02 3.58E+02 3.55E+02 2.00E+03

-4.34E-01 1.50E+00 2.03E+00 2.00E+00 1.82E+00 6.78E+00 7.90E+00 positive 2.40E+00 7.38E+00 8.82E+00 positive NA NA NA positive MW-63-18 MW-63-34 016 3/2/2011 10:50 2.98E+02 2.86E+02 2.62E+02 2.00E+03

-4.29E-01 1.57E+00 2.11E+00 2.00E+00 7.43E-02 7.96E+00 8.82E+00 positive

-2.10E+00 8.42E+00 8.59E+00 positive NA NA NA positive MW-63-34 MW-63-50 016 3/2/2011 14:21 4.35E+02 3.40E+02 3.44E+02 2.00E+03 1.73E-01 1.62E+00 2.03E+00 2.00E+00 1.13E+00 6.50E+00 7.48E+00 positive 3.64E+00 7.02E+00 8.70E+00 positive NA NA NA positive MW-63-50 MW-63-93 017 3/2/2011 14:14 2.69E+02 3.00E+02 2.94E+02 2.00E+03 3.30E-01 1.79E+00 2.17E+00 2.00E+00

-1.51E+00 8.78E+00 9.05E+00 positive 3.38E+00 7.56E+00 9.56E+00 positive NA NA NA positive MW-63-93 Well ID1 SAMPLE ID SAMPLE COLLECTION ANALYSIS RESULTS4,5 Well ID TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

TABLE 4 2011 1st QUARTER GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERTY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q12011 FINAL Table 4 - 2011 1st Quarter Groundwater Analytical Results.xlsx; Q12011 Table 4 Page 2 of 2 See Page 2 for Notes Date Time Result Std. Dev.6 MDC I.L.3,7 Result Std. Dev.6 MDC I.L.3 Result Std. Dev.6 MDC I.L.3 Result Std. Dev.6 MDC I.L.3 Result Std. Dev.6 MDC I.L.3 Well ID1 SAMPLE ID SAMPLE COLLECTION ANALYSIS RESULTS4,5 Well ID TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

MW-63-112 016 3/2/2011 14:15 3.38E+02 3.18E+02 2.96E+02 2.00E+03 1.48E-01 1.60E+00 2.00E+00 2.00E+00

-3.72E-01 6.70E+00 7.21E+00 positive 1.19E+00 6.36E+00 7.21E+00 positive NA NA NA positive MW-63-112 MW-63-121 016 3/2/2011 11:10 5.03E+02 3.54E+02 2.94E+02 2.00E+03

-6.82E-02 1.55E+00 2.03E+00 2.00E+00

-6.26E-01 6.72E+00 7.20E+00 positive 3.49E-01 6.00E+00 6.67E+00 positive NA NA NA positive MW-63-121 MW-63-163 016 3/2/2011 10:27 6.05E+02 3.76E+02 2.95E+02 2.00E+03 1.37E+00 1.99E+00 2.12E+00 2.00E+00 3.09E+00 5.40E+00 6.62E+00 positive

-2.05E+00 7.72E+00 7.12E+00 positive NA NA NA positive MW-63-163 MW-63-174 016 3/2/2011 10:26 4.13E+02 3.30E+02 2.91E+02 2.00E+03 8.20E-01 1.80E+00 2.03E+00 2.00E+00 3.65E+00 6.96E+00 8.18E+00 positive 2.34E+00 7.86E+00 9.20E+00 positive NA NA NA positive MW-63-174 MW-66-21 016 1/31/2011 16:26 4.77E+02 4.08E+02 4.24E+02 1.33E+03 3.48E-01 1.73E+00 2.02E+00 2.07E+00

-2.19E-01 5.00E+00 5.33E+00 positive 9.80E-01 6.50E+00 7.23E+00 positive

-1.06E+00 1.84E+01 2.14E+01 positive MW-66-21 MW-66-36 015 1/31/2011 15:51 3.01E+03 6.78E+02 4.61E+02 7.71E+03 1.55E+01 3.18E+00 2.11E+00 1.40E+01

-1.13E+00 6.12E+00 6.49E+00 positive

-8.31E-01 6.80E+00 7.15E+00 positive

-4.89E+00 1.79E+01 2.12E+01 positive MW-66-36 MW-67-39 016 2/7/2011 13:48 3.85E+03 7.60E+02 4.81E+02 6.52E+03 1.57E+01 3.34E+00 1.83E+00 1.81E+01 8.03E-02 6.18E+00 6.83E+00 positive 6.64E-01 6.78E+00 7.57E+00 positive 4.43E+00 1.97E+01 2.23E+01 positive MW-67-39 MW-67-105 015 2/7/2011 13:57 9.94E+02 4.26E+02 3.86E+02 3.92E+03 3.37E-01 1.64E+00 1.94E+00 4.38E+00 2.40E+00 4.84E+00 5.67E+00 positive

-1.22E+00 4.86E+00 4.81E+00 positive

-4.59E+00 1.96E+01 2.31E+01 positive MW-67-105 MW-67-173 016 2/7/2011 14:13 4.47E+02 4.48E+02 4.65E+02 1.61E+03

-2.38E-01 1.68E+00 2.12E+00 2.00E+00

-4.75E-01 5.28E+00 5.83E+00 positive 7.55E-01 6.38E+00 5.76E+00 positive

-7.05E-01 1.88E+01 2.18E+01 positive MW-67-173 MW-67-219 015 1/31/2011 14:48 6.41E+02 4.18E+02 4.20E+02 2.26E+03

-1.08E+00 1.42E+00 1.97E+00 2.00E+00 9.72E-01 5.80E+00 6.44E+00 positive 2.44E+00 5.46E+00 6.55E+00 positive

-4.58E+00 1.81E+01 2.14E+01 positive MW-67-219 MW-67-276 015 1/31/2011 14:31 8.75E+02 4.18E+02 3.87E+02 2.01E+03

-2.57E-02 1.66E+00 2.03E+00 2.00E+00

-2.56E+00 8.76E+00 8.16E+00 positive 6.49E-01 6.48E+00 7.20E+00 positive

-7.18E-01 1.92E+01 2.22E+01 positive MW-67-276 MW-67-323 015 1/31/2011 15:04 3.38E+02 3.70E+02 3.90E+02 1.00E+03 2.58E-01 1.71E+00 2.03E+00 2.00E+00 2.47E-01 5.70E+00 6.35E+00 positive 8.12E-03 5.80E+00 6.35E+00 positive

-5.93E+00 1.90E+01 2.25E+01 positive MW-67-323 MW-67-340 015 1/31/2011 14:53 2.75E+02 3.58E+02 3.83E+02 1.01E+03

-7.06E-01 1.51E+00 1.99E+00 2.00E+00 4.30E-01 6.34E+00 7.02E+00 positive

-1.15E+00 6.54E+00 6.88E+00 positive

-5.79E+00 1.85E+01 2.20E+01 positive MW-67-340 U3-4D 027 2/17/2011 14:41 6.28E+02 4.14E+02 4.05E+02 1.00E+03

-8.34E-02 1.55E+00 1.95E+00 2.00E+00 1.24E+00 4.72E+00 5.29E+00 positive 8.61E-01 4.84E+00 5.47E+00 positive NA NA NA positive U3-4D U3-T1 031 2/22/2011 11:11 6.55E+02 4.08E+02 3.92E+02 1.00E+03 1.62E+00 1.96E+00 2.02E+00 2.00E+00 1.80E+00 1.05E+01 6.14E+00 positive 2.12E+00 6.42E+00 7.54E+00 positive NA NA NA positive U3-T1 U3-T2 036 2/22/2011 14:30 2.27E+03 4.92E+02 3.62E+02 2.08E+03 1.82E+00 2.04E+00 2.05E+00 2.00E+00 3.65E+00 6.08E+00 7.29E+00 positive 5.97E-01 7.12E+00 7.85E+00 positive NA NA NA positive U3-T2 MH-5 VCFD 014 2/28/2011 9:47 5.17E+03 6.58E+02 3.66E+02 1.90E+00 1.99E+00 1.94E+00 3.45E-01 5.64E+00 6.19E+00

-1.28E+00 6.18E+00 6.45E+00 NA NA NA MH-5 VCFD B-1 011 2/14/2011 15:44 3.82E+03 5.88E+02 3.65E+02 5.41E-02 1.70E+00 2.14E+00 2.15E+01 1.22E+01 6.75E+00

-1.81E+00 7.00E+00 7.25E+00 NA NA NA B-1 B-6 011 2/28/2011 11:27 8.39E+02 3.90E+02 3.65E+02 6.28E-01 1.78E+00 2.05E+00 4.45E+00 5.82E+00 7.02E+00

-1.35E+00 6.50E+00 6.88E+00 NA NA NA B-6 Notes

1. For nested multi-level monitoring wells, suffix of well ID indicates depth (rounded to nearest foot) from reference point on casing to bottom of well screen. For Waterloo multi-level systems, suffix indicates depth (rounded to nearest foot) from reference point on casing to top of sampling port.

Well IDs without a suffix are open bedrock wellbores.

2. Sampling depths within sampling intervals (location of pump intake) have been established at location of most transmissive zone to the extent possible.
3. I.L.s (Investigation Levels) are predetermined detection limits assigned to each sampling location which, if reached or exceeded, require further investigation or action. I.L.s presented here for Sr-90, CS-137, Co-60 & Ni-63 are established for 2011 based on 2010 averages. See Note #7 below for further 2011 Tritium I.L. discussion. Positive detections indicate that the the result is greater than MDC and greater than or equal to 3 times the 1 sigma uncertainty.
4. NA indicates that the constituent was not analyzed.
5. Shading indicates that the sample result exceeds the Investigation Level.
6. Column designated as Std. Dev. provides the three times 1 sigma uncertainty values.
7. To be conservative, the 2011 Tritium I.L.s were calculated using (2x the 2009 yearly average) beacuase an increased Tritium activity in multiple Unit 2 sampling intervals was observed during 2010 in response to the transient surface spill from a temporary rental RWST/R.O. processing skid.
  • Indicates storm or foundation drain sampling locations, for which investigation levels are not applicable.
    • The Q1 2011 MW-40-100, MW-40-127 and MW-51-189 Cs-137 results were verified by re-analysis. However, based on the available chemistry and Site hydrogeologic data, these values do not appear to be representative of the groundwater conditions at these sampling intervals.

TABLE 4 2011 2nd QUARTER GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERTY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q22011 FINAL Table 4 - 2011 2nd Quarter Groundwater Analytical Results.xlsx; Q22011 Table 4 Page 1 of 3 See Page 3 for Notes Date Time Result Std. Dev.6 MDC I.L.3,7 Result Std. Dev.6 MDC I.L.3 Result Std. Dev.6 MDC I.L.3 Result Std. Dev.6 MDC I.L.3 Result Std. Dev.6 MDC I.L.3 MW-30-84 Q2-2011 5/5/2011 12:58 7.57E+03 9.46E+02 3.92E+02 1.22E+04 1.64E-01 1.15E+00 1.40E+00 2.00E+00 3.00E+00 8.04E+00 9.35E+00 positive 4.65E-02 7.14E+00 7.76E+00 positive NA NA NA positive MW-30-84 MW-30-84 Q2-2011 Mid 7/11/2011 12:45 7.55E+03 1.08E+03 2.82E+02 1.22E+04

-3.75E-01 9.75E-01 1.29E+00 2.00E+00 2.17E-01 7.89E+00 8.89E+00 positive 1.39E+01 1.16E+01 1.59E+01 positive NA NA NA positive MW-30-84 MW-31-49 Q2-2011 4/18/2011 12:53 1.08E+03 5.20E+02 4.66E+02 4.28E+04 4.98E-01 1.81E+00 2.09E+00 2.00E+00

-1.82E+00 8.82E+00 9.22E+00 positive 6.17E+00 8.70E+00 1.13E+01 positive NA NA NA positive MW-31-49 MW-31-63 Q2-2011 4/18/2011 13:21 1.81E+04 1.45E+03 4.67E+02 3.99E+04 7.26E-01 1.84E+00 2.08E+00 2.00E+00

-3.10E-01 7.62E+00 8.46E+00 positive 1.76E+00 8.74E+00 1.03E+01 positive NA NA NA positive MW-31-63 MW-31-85 Q2-2011 4/18/2011 13:18 3.08E+03 6.96E+02 4.66E+02 1.46E+04

-1.09E+00 1.46E+00 2.09E+00 2.00E+00

-4.50E+00 9.34E+00 9.19E+00 positive 3.84E+00 1.01E+01 1.22E+01 positive NA NA NA positive MW-31-85 MW-32-59 Q2-2011 4/27/2011 12:26 3.31E+03 6.36E+02 4.08E+02 3.42E+04 4.03E-01 1.50E+00 1.74E+00 2.00E+00 4.77E+00 8.64E+00 1.04E+01 positive

-3.37E+00 9.58E+00 9.50E+00 positive NA NA NA positive MW-32-59 MW-32-85 Q2-2011 4/27/2011 13:04 1.14E+04 1.19E+03 5.10E+02 1.63E+04 1.58E+00 1.69E+00 1.75E+00 2.00E+00

-1.23E+00 6.80E+00 7.31E+00 positive 5.30E-01 1.02E+01 1.15E+01 positive NA NA NA positive MW-32-85 MW-32-149 Q2-2011 4/27/2011 11:12 8.69E+02 4.44E+02 4.11E+02 1.00E+03 3.00E-01 1.43E+00 1.67E+00 2.00E+00 2.12E+00 7.44E+00 8.59E+00 positive 9.88E-01 7.76E+00 8.83E+00 positive NA NA NA positive MW-32-149 MW-32-173 Q2-2011 4/27/2011 11:27 5.82E+02 4.98E+02 5.08E+02 1.50E+03 6.37E-01 1.54E+00 1.74E+00 2.00E+00 0.00E+00 2.00E+01 9.23E+00 positive 2.47E-01 9.58E+00 1.07E+01 positive NA NA NA positive MW-32-173 MW-32-190 Q2-2011 4/27/2011 11:17 1.21E+03 5.64E+02 5.10E+02 4.21E+03 7.54E-01 1.13E+00 1.20E+00 2.00E+00 8.61E-01 8.68E+00 9.74E+00 positive

-6.60E+00 8.98E+00 6.37E+00 positive NA NA NA positive MW-32-190 MW-36-24 Q2-2011 4/28/2011 14:34 3.07E+03 7.26E+02 5.19E+02 2.56E+03 1.38E+00 1.53E+00 1.59E+00 2.00E+00

-6.43E-01 7.68E+00 8.47E+00 positive 2.82E+00 7.48E+00 9.35E+00 positive NA NA NA positive MW-36-24 MW-36-41 Q2-2011 4/28/2011 15:39 8.17E+03 1.04E+03 5.14E+02 2.10E+04 3.31E+00 1.75E+00 1.36E+00 7.99E+00 2.18E+00 9.26E+00 1.07E+01 positive

-2.96E-01 1.04E+01 1.12E+01 positive NA NA NA positive MW-36-41 MW-36-52 Q2-2011 4/28/2011 14:38 5.84E+03 9.06E+02 5.15E+02 1.48E+04 3.41E+00 1.56E+00 1.11E+00 8.14E+00 4.29E+00 8.42E+00 1.03E+01 positive

-2.61E+00 8.50E+00 8.36E+00 positive NA NA NA positive MW-36-52 MW-37-22 Q2-2011 4/28/2011 12:05 6.87E+03 9.66E+02 5.14E+02 9.19E+03 8.72E+00 2.90E+00 2.05E+00 2.20E+01 7.12E-01 6.96E+00 7.67E+00 positive 5.14E-01 7.86E+00 8.62E+00 positive NA NA NA positive MW-37-22 MW-37-32 Q2-2011 4/28/2011 12:21 4.11E+03 7.98E+02 5.15E+02 9.32E+03 2.62E+01 3.76E+00 1.68E+00 3.54E+01 3.56E+00 1.20E+01 1.42E+01 positive

-1.92E+00 1.09E+01 1.09E+01 positive NA NA NA positive MW-37-32 MW-37-40 Q2-2011 4/28/2011 11:31 3.92E+03 8.02E+02 5.33E+02 9.02E+03 2.30E+01 3.66E+00 1.68E+00 2.84E+01 4.10E+00 9.02E+00 1.09E+01 positive 6.47E-01 8.94E+00 1.02E+01 positive NA NA NA positive MW-37-40 MW-37-57 Q2-2011 4/28/2011 12:17 5.81E+03 8.98E+02 5.07E+02 9.62E+03 1.58E+01 3.54E+00 2.00E+00 3.68E+01 5.18E+00 1.72E+01 8.67E+00 positive

-1.42E+00 8.36E+00 8.80E+00 positive NA NA NA positive MW-37-57 MW-39-67 Q2-2011 4/26/2011 14:52 1.09E+04 9.64E+02 4.18E+02 1.00E+03 1.74E+00 1.49E+00 1.50E+00 3.30E+00

-8.12E-01 8.22E+00 8.78E+00 positive

-4.05E+00 9.42E+00 9.00E+00 positive NA NA NA positive MW-39-67 MW-39-67 Q2-2011 Mid 7/15/2011 13:42 2.24E+03 6.12E+02 4.40E+02 1.00E+03 2.55E-01 1.16E+00 1.34E+00 3.30E+00

-1.15E-01 8.28E+00 9.19E+00 positive

-2.42E-02 9.72E+00 1.12E+01 positive NA NA NA positive MW-39-67 MW-39-84 Q2-2011 4/26/2011 14:25 4.40E+02 4.02E+02 4.13E+02 1.00E+03

-2.03E-01 1.15E+00 1.50E+00 2.10E+00

-9.39E-01 7.42E+00 7.84E+00 positive

-4.02E-01 6.92E+00 7.41E+00 positive NA NA NA positive MW-39-84 MW-39-84 Q2-2011 Mid 7/15/2011 14:33 3.55E+02 4.17E+02 4.40E+02 1.00E+03 6.54E-01 1.15E+00 1.27E+00 2.10E+00

-1.78E+00 1.43E+01 1.71E+01 positive

-4.89E+00 9.45E+00 8.20E+00 positive NA NA NA positive MW-39-84 MW-39-102 Q2-2011 4/26/2011 14:33 1.43E+04 1.09E+03 4.19E+02 1.00E+03 1.08E+00 1.85E+00 2.03E+00 8.10E+00 4.48E+01 2.08E+01 9.86E+00 positive 6.03E+00 7.96E+00 1.07E+01 positive NA NA NA positive MW-39-102 MW-39-102 Q2-2011 Mid 7/15/2011 14:02 1.24E+04 1.20E+03 4.36E+02 1.00E+03 5.88E-01 1.09E+00 1.20E+00 8.10E+00 3.70E+00 8.76E+00 1.02E+01 positive

-6.84E-01 9.42E+00 9.35E+00 positive NA NA NA positive MW-39-102 MW-39-124 Q2-2011 4/26/2011 13:01 1.51E+02 3.70E+02 4.15E+02 1.00E+03 5.20E-01 1.37E+00 1.55E+00 4.50E+00 9.13E+00 8.56E+00 8.57E+00 positive 3.07E+00 7.52E+00 9.27E+00 positive NA NA NA positive MW-39-124 MW-39-124 Q2-2011 Mid 7/15/2011 11:44 2.30E+01 3.72E+02 4.39E+02 1.00E+03 8.78E-01 1.19E+00 1.27E+00 4.50E+00

-4.10E+00 1.13E+01 1.15E+01 positive

-1.82E+00 9.51E+00 9.57E+00 positive NA NA NA positive MW-39-124 MW-39-183 Q2-2011 4/26/2011 11:35 1.15E+02 3.54E+02 4.02E+02 1.00E+03 1.12E+00 1.56E+00 1.67E+00 2.00E+00 6.46E+00 8.88E+00 1.09E+01 positive

-1.52E+00 8.68E+00 8.94E+00 positive NA NA NA positive MW-39-183 MW-39-183 Q2-2011 Mid 7/15/2011 11:49 7.02E+01 3.75E+02 4.35E+02 1.00E+03 3.45E-01 1.03E+00 1.19E+00 2.00E+00 2.51E+00 1.08E+01 1.22E+01 positive

-2.37E+00 1.30E+01 1.37E+01 positive NA NA NA positive MW-39-183 MW-39-195 Q2-2011 4/26/2011 12:38 7.04E+03 8.04E+02 4.20E+02 1.00E+03 1.88E+00 1.75E+00 1.79E+00 2.00E+00

-2.03E+00 1.11E+01 1.28E+01 positive 4.62E+00 8.70E+00 1.13E+01 positive NA NA NA positive MW-39-195 MW-39-195 Q2-2011 Mid 7/15/2011 11:13 4.19E+03 7.56E+02 4.35E+02 1.00E+03 1.10E+00 1.78E+00 1.93E+00 2.00E+00 2.79E+00 8.46E+00 9.76E+00 positive 6.38E-01 1.01E+01 1.08E+01 positive NA NA NA positive MW-39-195 MW-40-27 Q2-2011 4/29/2011 13:29 1.77E+02 3.66E+02 4.07E+02 1.00E+03 1.18E+00 1.74E+00 1.87E+00 2.00E+00 1.91E+00 8.40E+00 9.77E+00 positive

-9.20E-01 9.86E+00 1.15E+01 positive NA NA NA positive MW-40-27 MW-40-27 Q2-2011 Mid 7/27/2011 15:12 3.69E+01 3.00E+02 3.43E+02 1.00E+03

-4.37E-01 1.40E+00 1.93E+00 2.00E+00

-2.18E+00 7.35E+00 7.64E+00 positive 1.36E+00 9.03E+00 1.03E+01 positive NA NA NA positive MW-40-27 MW-40-46 Q2-2011 4/29/2011 13:31 7.82E+01 3.54E+02 4.05E+02 1.00E+03

-1.35E-01****

1.88E+00 1.77E+00 2.00E+00

-9.96E-01 8.46E+00 9.00E+00 positive

-3.98E+00 9.84E+00 9.04E+00 positive NA NA NA positive MW-40-46 MW-40-46 Q2-2011 Mid 7/27/2011 15:55 1.35E+02 3.09E+02 3.44E+02 1.00E+03

-9.06E-01 1.26E+00 1.86E+00 2.00E+00 2.28E+00 8.85E+00 1.01E+01 positive 5.01E-01 9.30E+00 1.03E+01 positive NA NA NA positive MW-40-46 MW-40-81 Q2-2011 4/29/2011 11:08 3.39E+02 4.12E+02 4.36E+02 1.00E+03 1.07E+00 1.58E+00 1.70E+00 2.00E+00 3.05E+00 6.90E+00 8.51E+00 positive

-2.66E-01 8.04E+00 8.83E+00 positive NA NA NA positive MW-40-81 MW-40-81 Q2-2011 Mid 7/27/2011 13:24

-1.18E+02 2.89E+02 3.48E+02 1.00E+03 8.36E-01 1.70E+00 1.90E+00 2.00E+00

-3.22E-01 6.48E+00 6.87E+00 positive

-1.05E+00 8.67E+00 8.91E+00 positive NA NA NA positive MW-40-81 MW-40-100 Q2-2011 4/29/2011 11:27 2.70E+02 4.06E+02 4.38E+02 1.00E+03 2.46E-01 1.42E+00 1.67E+00 2.00E+00 5.53E+00 7.14E+00 9.23E+00 positive 2.99E+00 7.96E+00 9.80E+00 positive NA NA NA positive MW-40-100 MW-40-100 Q2-2011 Mid 7/27/2011 13:29 1.07E+02 3.12E+02 3.50E+02 1.00E+03

-9.50E-01 1.41E+00 1.98E+00 2.00E+00 2.29E+00 9.03E+00 1.04E+01 positive 7.10E-01 1.08E+01 1.20E+01 positive NA NA NA positive MW-40-100 MW-40-127 Q2-2011 4/29/2011 11:26

-2.27E+01 3.60E+02 4.32E+02 1.00E+03 5.72E-01 1.78E+00 2.05E+00 2.00E+00

-2.13E-01 8.26E+00 8.83E+00 positive

-1.62E+00 9.68E+00 9.87E+00 positive NA NA NA positive MW-40-127 MW-40-127 Q2-2011 Mid 7/27/2011 13:56 1.56E+02 3.15E+02 3.50E+02 1.00E+03 4.81E-01 1.64E+00 1.92E+00 2.00E+00 1.48E+00 9.06E+00 1.03E+01 positive

-8.00E+00 1.02E+01 7.94E+00 positive NA NA NA positive MW-40-127 MW-40-162 Q2-2011 4/29/2011 12:26 1.05E+02 3.78E+02 4.33E+02 1.00E+03 8.71E-01 1.34E+00 1.46E+00 2.00E+00 4.54E+00 1.23E+01 1.42E+01 positive 4.43E-01 9.50E+00 1.08E+01 positive NA NA NA positive MW-40-162 MW-40-162 Q2-2011 Mid 7/27/2011 14:40 5.54E+00 2.97E+02 3.44E+02 1.00E+03

-8.61E-01 1.58E+00 1.98E+00 2.00E+00

-2.44E+00 9.21E+00 8.54E+00 positive

-6.93E-01 8.70E+00 9.41E+00 positive NA NA NA positive MW-40-162 MW-41-40 Q2-2011 4/20/2011 13:51 4.51E+03 7.36E+02 4.55E+02 1.00E+03 2.32E+00 1.57E+00 1.44E+00 7.28E+00 2.20E+00 9.22E+00 1.06E+01 positive 3.02E+00 1.06E+01 1.25E+01 positive NA NA NA positive MW-41-40 MW-41-40 Q2-2011 Mid 7/15/2011 12:30 6.99E+02 4.59E+02 4.41E+02 1.00E+03 2.48E+00 1.35E+00 1.19E+00 7.28E+00

-1.93E+00 1.09E+01 1.14E+01 positive

-1.11E+00 8.94E+00 9.13E+00 positive NA NA NA positive MW-41-40 MW-41-63 Q2-2011 4/20/2011 13:13 7.58E+02 4.90E+02 4.72E+02 1.00E+03

-7.72E-01 1.51E+00 2.03E+00 7.36E+00 3.53E+00 8.52E+00 1.01E+01 positive 4.02E+00 8.74E+00 1.09E+01 positive NA NA NA positive MW-41-63 MW-41-63 Q2-2011 Mid 7/15/2011 12:51 7.14E+02 4.56E+02 4.35E+02 1.00E+03 3.03E+00 1.50E+00 1.30E+00 7.36E+00 2.36E+00 7.71E+00 8.88E+00 positive 4.47E-01 6.81E+00 7.51E+00 positive NA NA NA positive MW-41-63 MW-42-49 Q2-2011 4/21/2011 14:04 1.71E+03 5.88E+02 4.80E+02 3.16E+04 5.45E+00 2.18E+00 1.45E+00 9.00E+01 2.15E+04 2.88E+03 2.08E+01 6.58E+04 3.41E+00 9.16E+00 1.09E+01 positive 1.90E+02 2.72E+01 1.73E+01 6.74E+02 MW-42-49 MW-42-78 Q2-2011 4/21/2011 13:45 6.26E+02 4.78E+02 4.77E+02 1.00E+03 4.25E-01 1.13E+00 1.32E+00 2.00E+00

-9.71E-01 9.16E+00 9.83E+00 positive 3.58E+00 8.56E+00 1.11E+01 positive 5.89E-01 1.49E+01 1.72E+01 positive MW-42-78 MW-43-28 Q2-2011 4/21/2011 11:15 2.34E+02 4.30E+02 4.72E+02 1.00E+03 1.46E+00 1.96E+00 2.04E+00 2.00E+00

-9.31E-01 8.74E+00 9.22E+00 positive 4.50E+00 8.60E+00 1.09E+01 positive NA NA NA positive MW-43-28 MW-43-62 Q2-2011 4/21/2011 11:00 1.05E+02 4.12E+02 4.72E+02 1.00E+03

-4.65E-01 1.67E+00 2.18E+00 2.00E+00

-1.90E+00 9.08E+00 9.35E+00 positive

-2.34E+00 8.70E+00 8.43E+00 positive NA NA NA positive MW-43-62 MW-44-66 Q2-2011 4/26/2011 13:17 6.87E+02 4.20E+02 4.03E+02 1.00E+03 7.05E-01 1.52E+00 1.70E+00 2.00E+00

-1.14E-01 9.36E+00 1.03E+01 positive 3.29E+00 1.07E+01 1.31E+01 positive NA NA NA positive MW-44-66 MW-44-66 Q2-2011 Mid 7/19/2011 15:39 1.62E+03 5.49E+02 4.32E+02 1.00E+03

-7.04E-01 6.48E-01 1.06E+00 2.00E+00 4.61E+00 9.66E+00 1.16E+01 positive

-5.76E+00 1.11E+01 9.79E+00 positive NA NA NA positive MW-44-66 MW-44-102 Q2-2011 4/26/2011 12:18 6.70E+02 4.14E+02 3.99E+02 1.00E+03 1.09E+00 1.41E+00 1.49E+00 2.00E+00 3.59E-01 7.42E+00 8.15E+00 positive

-2.06E+00 7.86E+00 7.82E+00 positive NA NA NA positive MW-44-102 MW-44-102 Q2-2011 Mid 7/19/2011 10:53 6.38E+02 4.50E+02 4.39E+02 1.00E+03 2.55E-01 1.02E+00 1.19E+00 2.00E+00 1.01E+00 6.63E+00 7.60E+00 positive 1.28E+00 6.27E+00 7.47E+00 positive NA NA NA positive MW-44-102 MW-45-42 Q2-2011 4/20/2011 14:09 8.56E+03 1.03E+03 4.65E+02 5.90E+03 1.45E+00 1.56E+00 1.61E+00 2.00E+00 7.04E-01 6.50E+00 7.46E+00 positive 7.13E+00 1.07E+01 1.29E+01 positive NA NA NA positive MW-45-42 MW-45-42 Q2-2011 Mid 7/25/2011 13:23 3.94E+04 2.07E+03 4.36E+02 5.90E+03 1.14E+00 1.30E+00 1.37E+00 2.00E+00 3.09E+00 7.41E+00 8.65E+00 positive

-2.66E+00 1.01E+01 1.05E+01 positive NA NA NA positive MW-45-42 MW-45-61 Q2-2011 4/20/2011 10:07 2.03E+03 6.12E+02 4.74E+02 2.65E+03 7.22E-01 1.36E+00 1.51E+00 2.00E+00

-4.02E+00 7.76E+00 7.55E+00 positive

-8.47E-01 7.56E+00 7.91E+00 positive NA NA NA positive MW-45-61 MW-45-61 Q2-2011 Mid 7/25/2011 10:00 5.63E+03 8.49E+02 4.33E+02 2.65E+03 9.47E-01 1.19E+00 1.25E+00 2.00E+00 1.42E+00 5.79E+00 6.69E+00 positive 2.07E+00 8.34E+00 9.68E+00 positive NA NA NA positive MW-45-61 MW-46 Q2-2011 4/25/2011 11:19 5.25E+03 7.54E+02 3.95E+02 1.84E+03 1.48E+00 1.72E+00 1.80E+00 2.00E+00

-2.48E+00 7.24E+00 7.06E+00 positive

-4.44E+00 7.44E+00 6.77E+00 positive NA NA NA positive MW-46 MW-46 Q2-2011 Mid 7/13/2011 13:29 3.08E+03 7.17E+02 2.86E+02 1.84E+03 8.44E-01 1.19E+00 1.26E+00 2.00E+00 3.71E+00 8.64E+00 1.04E+01 positive

-9.54E-01 1.02E+01 1.08E+01 positive NA NA NA positive MW-46 MW-47-56 Q2-2011 Mid 7/6/2011 15:32 3.52E+03 6.57E+02 4.48E+02 4.63E-01 1.08E+00 1.22E+00

-1.56E+00 1.11E+01 1.20E+01 1.45E-01 7.41E+00 8.25E+00

-1.99E+01 2.17E+01 2.50E+01 MW-47-56 MW-47-80 Q2-2011 Mid 7/6/2011 14:37 1.36E+05 3.36E+03 4.50E+02 1.95E+00 1.33E+00 1.22E+00

-1.57E+00 8.37E+00 8.73E+00

-3.43E+00 7.80E+00 7.13E+00 3.07E+00 2.59E+01 2.89E+01 MW-47-80 MW-49-26 Q2-2011 4/15/2011 11:58 3.29E+03 7.18E+02 4.80E+02 6.52E+03 1.26E+01 3.06E+00 1.91E+00 2.79E+01 4.75E+00 1.07E+01 1.27E+01 positive 4.03E+00 1.20E+01 1.47E+01 positive 1.81E+00 1.50E+01 1.72E+01 positive MW-49-26 MW-49-42 Q2-2011 4/15/2011 11:55 1.90E+03 6.04E+02 4.78E+02 4.97E+03 1.57E+01 3.34E+00 2.07E+00 3.72E+01

-6.72E+00 7.62E+00 6.17E+00 positive 1.15E-01 7.72E+00 8.33E+00 positive 6.68E+00 1.55E+01 1.73E+01 positive MW-49-42 MW-49-65 Q2-2011 4/15/2011 11:50 2.38E+03 6.48E+02 4.81E+02 3.03E+03 1.62E+01 3.12E+00 1.60E+00 2.62E+01 2.59E+00 9.66E+00 1.12E+01 positive 4.62E-02 1.01E+01 1.10E+01 positive 4.11E+00 1.49E+01 1.68E+01 positive MW-49-65 MW-50-42 Q2-2011 5/3/2011 12:05 3.77E+03 5.58E+02 3.41E+02 1.04E+03 9.53E+00 2.20E+00 1.04E+00 1.10E+01 1.92E+00 9.44E+00 1.07E+01 positive 5.79E-01 1.02E+01 1.16E+01 positive 5.86E-01 1.69E+01 1.92E+01 positive MW-50-42 MW-50-42 Q2-2011 Mid 7/25/2011 12:18 1.03E+03 4.89E+02 4.43E+02 1.04E+03 3.01E+00 2.09E+00 2.02E+00 1.10E+01

-1.11E+00 7.86E+00 8.36E+00 positive 6.63E-02 8.16E+00 9.04E+00 positive 3.81E+00 1.71E+01 1.91E+01 positive MW-50-42 MW-50-66 Q2-2011 5/3/2011 12:07 4.73E+03 6.12E+02 3.45E+02 5.90E+03 2.63E+01 3.30E+00 1.08E+00 5.24E+01 0.00E+00 1.77E+01 9.05E+00 positive

-2.32E+00 9.06E+00 9.12E+00 positive 8.43E+00 1.70E+01 1.88E+01 positive MW-50-66 MW-50-66 Q2-2011 Mid 7/25/2011 12:26 6.50E+03 8.73E+02 4.48E+02 5.90E+03 2.61E+01 4.08E+00 1.35E+00 5.24E+01

-4.59E-01 7.02E+00 7.74E+00 positive 3.81E+00 8.55E+00 1.07E+01 positive 1.02E+01 1.66E+01 1.81E+01 positive MW-50-66 MW-51-40 Q2-2011 4/29/2011 10:41 3.63E+02 4.14E+02 4.35E+02 1.00E+03 2.26E-01 1.37E+00 1.59E+00 2.00E+00

-3.40E+00 9.48E+00 9.62E+00 positive 6.20E+00 1.11E+01 1.40E+01 positive NA NA NA positive MW-51-40 MW-51-79 Q2-2011 4/29/2011 10:57 1.17E+02 3.82E+02 4.33E+02 1.00E+03 1.03E+00 1.67E+00 1.82E+00 2.00E+00

-4.93E-01 7.56E+00 8.23E+00 positive

-8.38E-01 8.08E+00 8.53E+00 positive NA NA NA positive MW-51-79 MW-51-104 Q2-2011 4/29/2011 12:35 1.97E+02 3.90E+02 4.32E+02 1.00E+03 1.41E+00 1.45E+00 1.48E+00 2.00E+00

-1.90E+00 1.08E+01 1.25E+01 positive

-6.79E-01 1.10E+01 1.20E+01 positive NA NA NA positive MW-51-104 MW-51-135 Q2-2011 4/29/2011 13:16 0.00E+00 3.66E+02 4.35E+02 1.00E+03 1.14E+00 1.52E+00 1.63E+00 2.00E+00 2.52E+00 1.01E+01 1.17E+01 positive

-5.69E-01 9.00E+00 9.56E+00 positive NA NA NA positive MW-51-135 MW-51-163 Q2-2011 4/29/2011 13:19 4.68E+01 3.66E+02 4.30E+02 1.00E+03 5.27E-01 1.45E+00 1.65E+00 2.00E+00 2.26E+00 8.40E+00 9.72E+00 positive 9.25E-01 7.72E+00 8.87E+00 positive NA NA NA positive MW-51-163 MW-51-189 Q2-2011 4/29/2011 12:52 2.32E+02 3.96E+02 4.33E+02 1.00E+03 1.28E+00 1.50E+00 1.57E+00 2.00E+00

-8.07E-01 5.82E+00 6.25E+00 positive

-5.07E+00 9.48E+00 8.89E+00 positive NA NA NA positive MW-51-189 MW-52-11 Q2-2011 4/22/2011 12:10 3.04E+02 4.08E+02 4.35E+02 1.00E+03 1.29E-01 1.35E+00 1.60E+00 2.00E+00 2.27E+00 1.02E+01 1.17E+01 positive 5.08E+00 9.92E+00 1.24E+01 positive NA NA NA positive MW-52-11 MW-52-11 Q2-2011 Mid 7/26/2011 12:32 3.39E+02 3.99E+02 4.21E+02 1.00E+03 1.86E-01 1.49E+00 1.74E+00 2.00E+00 1.71E+00 8.76E+00 9.71E+00 positive

-2.27E+00 8.43E+00 8.63E+00 positive NA NA NA positive MW-52-11 MW-52-18 Q2-2011 4/22/2011 12:16 7.01E+01 3.76E+02 4.35E+02 1.00E+03 1.37E+00 1.39E+00 1.42E+00 2.00E+00 8.81E+00 1.29E+01 9.01E+00 positive

-1.49E+00 9.44E+00 9.90E+00 positive NA NA NA positive MW-52-18 MW-52-18 Q2-2011 Mid 7/26/2011 14:39 2.52E+02 3.87E+02 4.22E+02 1.00E+03 1.06E+00 1.62E+00 1.76E+00 2.00E+00 3.80E+00 6.45E+00 8.08E+00 positive

-3.24E+00 8.10E+00 7.84E+00 positive NA NA NA positive MW-52-18 MW-52-48 Q2-2011 4/22/2011 12:18 1.06E+02 3.82E+02 4.36E+02 1.00E+03 1.69E-01 1.37E+00 1.62E+00 2.00E+00

-4.59E+00 7.58E+00 7.31E+00 positive 1.35E+00 7.80E+00 9.17E+00 positive NA NA NA positive MW-52-48 MW-52-48 Q2-2011 Mid 7/26/2011 15:08 7.68E+01 3.66E+02 4.21E+02 1.00E+03 2.58E-01 1.20E+00 1.46E+00 2.00E+00 2.34E+00 9.60E+00 1.07E+01 positive

-7.68E-01 8.73E+00 1.01E+01 positive NA NA NA positive MW-52-48 MW-52-64 Q2-2011 4/22/2011 15:23

-2.26E+01 3.58E+02 4.32E+02 1.00E+03 5.12E-01 1.13E+00 1.27E+00 2.00E+00 1.87E+00 6.72E+00 7.70E+00 positive

-8.05E+00 8.28E+00 6.18E+00 positive NA NA NA positive MW-52-64 MW-52-64 Q2-2011 Mid 7/27/2011 10:45 1.35E+02 3.81E+02 4.31E+02 1.00E+03

-4.58E-01 8.67E-01 1.27E+00 2.00E+00 2.48E+00 7.17E+00 8.34E+00 positive 6.66E-01 8.13E+00 9.05E+00 positive NA NA NA positive MW-52-64 MW-52-122 Q2-2011 4/22/2011 10:45

-2.27E+01 3.60E+02 4.33E+02 1.00E+03 1.14E+00 1.17E+00 1.17E+00 2.00E+00 3.48E+01 2.08E+01 9.71E+00 positive

-1.96E+00 7.96E+00 7.90E+00 positive NA NA NA positive MW-52-122 MW-52-122 Q2-2011 Mid 7/26/2011 13:36

-2.18E+01 3.48E+02 4.19E+02 1.00E+03 1.05E-01 1.19E+00 1.47E+00 2.00E+00

-5.49E+00 7.92E+00 7.50E+00 positive 8.02E-01 6.84E+00 7.89E+00 positive NA NA NA positive MW-52-122 MW-52-162 Q2-2011 4/22/2011 10:18 1.85E+02 3.84E+02 4.29E+02 1.00E+03

-7.50E-01 9.50E-01 1.42E+00 2.00E+00 1.47E+00 8.40E+00 9.68E+00 positive 1.95E-02 1.00E+01 1.10E+01 positive NA NA NA positive MW-52-162 MW-52-162 Q2-2011 Mid 7/26/2011 11:33 5.16E+02 4.20E+02 4.22E+02 1.00E+03 3.77E-03 1.21E+00 1.57E+00 2.00E+00 4.29E-02 8.34E+00 9.09E+00 positive

-2.32E+00 9.87E+00 1.00E+01 positive NA NA NA positive MW-52-162 MW-52-181 Q2-2011 4/22/2011 10:22 2.45E+02 3.96E+02 4.33E+02 1.00E+03 1.18E+00 1.42E+00 1.48E+00 2.00E+00 6.46E+01 2.68E+01 1.22E+01 positive

-1.09E+00 1.22E+01 1.30E+01 positive NA NA NA positive MW-52-181 MW-52-181 Q2-2011 Mid 7/26/2011 11:43 2.41E+02 3.87E+02 4.22E+02 1.00E+03 3.57E-01 1.28E+00 1.54E+00 2.00E+00

-1.99E+00 7.50E+00 7.52E+00 positive

-1.27E+00 9.39E+00 9.97E+00 positive NA NA NA positive MW-52-181 Well ID1 SAMPLE ID SAMPLE COLLECTION ANALYSIS RESULTS4,5 Well ID TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

TABLE 4 2011 2nd QUARTER GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERTY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q22011 FINAL Table 4 - 2011 2nd Quarter Groundwater Analytical Results.xlsx; Q22011 Table 4 Page 2 of 3 See Page 3 for Notes Date Time Result Std. Dev.6 MDC I.L.3,7 Result Std. Dev.6 MDC I.L.3 Result Std. Dev.6 MDC I.L.3 Result Std. Dev.6 MDC I.L.3 Result Std. Dev.6 MDC I.L.3 Well ID1 SAMPLE ID SAMPLE COLLECTION ANALYSIS RESULTS4,5 Well ID TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

MW-53-82 Q2-2011 4/18/2011 12:45 6.24E+02 4.56E+02 4.50E+02 3.83E+03 4.40E-01 1.45E+00 1.67E+00 4.46E+00

-4.57E+00 9.82E+00 9.80E+00 positive 3.12E+00 8.78E+00 1.07E+01 positive

-5.86E-01 1.48E+01 1.72E+01 positive MW-53-82 MW-53-120 Q2-2011 4/18/2011 11:52 4.11E+03 7.72E+02 4.75E+02 1.05E+04 3.55E+01 4.56E+00 1.67E+00 6.60E+01 1.38E+00 8.82E+00 9.99E+00 positive 4.87E-01 9.24E+00 1.02E+01 positive 1.76E+01 1.77E+01 1.87E+01 positive MW-53-120 MW-54-37 Q2-2011 4/12/2011 12:02 5.16E+03 8.40E+02 4.76E+02 2.71E+03 4.91E+00 2.08E+00 1.69E+00 9.20E+00 2.95E+00 8.26E+00 9.69E+00 positive 2.50E+00 8.26E+00 9.96E+00 positive 3.16E+00 1.45E+01 1.65E+01 positive MW-54-37 MW-54-37 Q2-2011 Mid 7/18/2011 13:45 2.79E+04 1.67E+03 4.43E+02 2.71E+03 4.34E+00 2.19E+00 1.85E+00 9.20E+00

-1.17E+00 6.36E+00 6.58E+00 positive 4.07E+00 9.21E+00 1.09E+01 positive 1.56E+01 1.91E+01 2.07E+01 positive MW-54-37 MW-54-58 Q2-2011 4/12/2011 12:04 9.94E+02 5.20E+02 4.79E+02 1.48E+03 1.15E+00 1.84E+00 2.01E+00 3.43E+00 1.70E+00 8.58E+00 9.66E+00 positive 1.14E+00 8.74E+00 9.95E+00 positive 5.01E+00 1.58E+01 1.78E+01 positive MW-54-58 MW-54-58 Q2-2011 Mid 7/18/2011 13:33 2.48E+03 6.12E+02 4.44E+02 1.48E+03 1.49E+00 1.21E+00 1.14E+00 3.43E+00

-1.98E+00 8.85E+00 9.27E+00 positive 2.35E-01 9.09E+00 1.01E+01 positive 1.83E+01 1.97E+01 2.13E+01 positive MW-54-58 MW-54-123 Q2-2011 4/12/2011 12:22 8.24E+02 4.98E+02 4.77E+02 1.30E+03 3.44E+00 1.96E+00 1.72E+00 8.14E+00

-5.24E+00 8.14E+00 7.60E+00 positive 1.86E+00 8.04E+00 9.55E+00 positive

-3.35E+00 1.48E+01 1.75E+01 positive MW-54-123 MW-54-123 Q2-2011 Mid 7/18/2011 14:06 5.70E+02 4.44E+02 4.46E+02 1.30E+03 7.16E-01 1.02E+00 1.07E+00 8.14E+00 1.92E+00 9.66E+00 1.05E+01 positive 3.87E-02 6.30E+00 6.97E+00 positive 6.27E+00 1.84E+01 2.04E+01 positive MW-54-123 MW-54-144 Q2-2011 4/12/2011 9:50 1.48E+03 5.68E+02 4.79E+02 2.64E+03 1.20E+01 2.92E+00 1.81E+00 2.53E+01 6.43E+00 7.44E+00 9.59E+00 positive

-4.68E+00 9.58E+00 8.86E+00 positive

-2.75E+00 1.48E+01 1.74E+01 positive MW-54-144 MW-54-144 Q2-2011 Mid 7/18/2011 12:38 4.34E+03 7.41E+02 4.43E+02 2.64E+03 1.13E+01 2.44E+00 1.26E+00 2.53E+01 3.37E+00 7.47E+00 8.78E+00 positive

-3.49E+00 8.91E+00 8.88E+00 positive 1.53E+01 1.87E+01 2.03E+01 positive MW-54-144 MW-54-173 Q2-2011 4/12/2011 9:56 1.26E+03 5.46E+02 4.78E+02 3.63E+03 3.91E+00 1.92E+00 1.58E+00 1.22E+01

-1.29E+01 1.38E+01 1.53E+01 positive 5.93E+00 9.66E+00 1.25E+01 positive

-2.17E+00 1.50E+01 1.76E+01 positive MW-54-173 MW-54-173 Q2-2011 Mid 7/18/2011 12:20 1.48E+03 5.28E+02 4.40E+02 3.63E+03 4.54E+00 1.64E+00 1.11E+00 1.22E+01 2.97E-01 6.84E+00 7.45E+00 positive 1.10E+00 6.51E+00 7.50E+00 positive

-5.43E+00 1.56E+01 1.75E+01 positive MW-54-173 MW-54-190 Q2-2011 4/12/2011 10:01 2.07E+03 6.18E+02 4.78E+02 3.49E+03 1.90E+01 3.38E+00 1.77E+00 4.03E+01 3.33E+00 7.86E+00 9.23E+00 positive 8.70E-01 9.00E+00 1.00E+01 positive 3.35E-01 1.58E+01 1.82E+01 positive MW-54-190 MW-54-190 Q2-2011 Mid 7/18/2011 12:14 2.37E+03 6.06E+02 4.45E+02 3.49E+03 1.75E+01 2.85E+00 1.12E+00 4.03E+01 2.24E+00 1.16E+01 1.29E+01 positive

-2.72E+00 1.18E+01 1.22E+01 positive

-3.86E+00 1.55E+01 1.74E+01 positive MW-54-190 MW-56-53 Q2-2011 4/27/2011 12:08 1.18E+02 3.48E+02 3.97E+02 1.19E+03

-3.07E-02 1.23E+00 1.60E+00 2.00E+00 3.04E+00 8.50E+00 1.01E+01 positive

-1.64E+00 8.42E+00 8.44E+00 positive NA NA NA positive MW-56-53 MW-56-53 Q2-2011 Mid 7/6/2011 12:58 2.03E+02 2.75E+02 2.83E+02 1.19E+03

-3.68E-01 7.89E-01 1.12E+00 2.00E+00 3.72E+00 7.77E+00 9.45E+00 positive

-4.34E+00 8.82E+00 9.56E+00 positive

-4.67E+00 2.28E+01 2.56E+01 positive MW-56-53 MW-56-83 Q2-2011 4/27/2011 13:46 7.64E+04 2.40E+03 4.19E+02 6.39E+03 3.87E+00 1.60E+00 1.28E+00 3.98E+00

-1.05E+00 1.14E+01 1.33E+01 positive

-1.27E+00 9.50E+00 1.01E+01 positive NA NA NA positive MW-56-83 MW-56-83 Q2-2011 Mid 7/6/2011 11:58 8.42E+04 3.54E+03 2.81E+02 6.39E+03 1.45E+00 1.27E+00 1.19E+00 3.98E+00 2.77E+00 2.01E+01 9.44E+00 positive 4.20E-01 8.16E+00 9.20E+00 positive

-1.36E+01 2.15E+01 2.46E+01 positive MW-56-83 MW-57-11 Q2-2011 5/4/2011 10:28 6.40E+03 6.84E+02 3.41E+02 8.44E+03 3.11E+01 3.62E+00 1.04E+00 4.92E+01 3.74E+00 8.32E+00 9.74E+00 positive 2.05E+00 8.40E+00 9.72E+00 positive 6.20E+00 1.66E+01 1.85E+01 positive MW-57-11 MW-57-11 Q2-2011 Mid 7/18/2011 11:57 7.36E+03 9.18E+02 4.45E+02 8.44E+03 3.87E+01 5.28E+00 2.11E+00 4.92E+01 3.27E-01 8.88E+00 9.84E+00 positive

-2.34E+00 9.18E+00 9.39E+00 positive

-6.76E+00 1.48E+01 1.67E+01 positive MW-57-11 MW-57-20 Q2-2011 5/4/2011 10:37 2.03E+04 1.15E+03 3.44E+02 3.04E+03 1.74E+00 1.11E+00 9.49E-01 2.24E+00 1.48E+00 7.52E+00 8.43E+00 positive

-7.32E-01 9.22E+00 1.02E+01 positive

-5.44E+00 1.64E+01 1.91E+01 positive MW-57-20 MW-57-20 Q2-2011 Mid 7/18/2011 12:09 3.81E+04 1.94E+03 4.43E+02 3.04E+03 1.27E+00 1.08E+00 1.01E+00 2.24E+00

-5.13E+00 7.71E+00 7.35E+00 positive 9.16E-01 8.67E+00 9.92E+00 positive

-5.69E+00 1.93E+01 2.20E+01 positive MW-57-20 MW-57-45 Q2-2011 5/4/2011 11:03 1.35E+04 9.48E+02 3.43E+02 2.38E+03 9.06E-01 9.74E-01 9.60E-01 2.60E+00 7.40E+00 9.54E+00 1.21E+01 positive

-1.84E+00 9.48E+00 9.59E+00 positive 6.39E+00 1.78E+01 1.98E+01 positive MW-57-45 MW-57-45 Q2-2011 Mid 7/18/2011 12:36 2.53E+04 1.60E+03 4.47E+02 2.38E+03 1.28E+00 1.32E+00 1.34E+00 2.60E+00

-2.08E-01 8.16E+00 8.83E+00 positive

-7.58E-01 9.39E+00 9.67E+00 positive

-1.04E+01 1.53E+01 1.74E+01 positive MW-57-45 MW-58-26 Q2-2011 5/3/2011 9:58 7.22E+02 4.30E+02 4.21E+02 1.00E+03 3.15E-01 1.13E+00 1.32E+00 2.00E+00 2.29E+00 5.80E+00 6.89E+00 positive

-6.42E+00 9.02E+00 8.00E+00 positive NA NA NA positive MW-58-26 MW-58-26 Q2-2011 Mid 7/5/2011 13:29 1.86E+03 5.46E+02 4.47E+02 1.00E+03

-3.25E-01 1.10E+00 1.41E+00 2.00E+00 7.41E-01 6.84E+00 7.61E+00 positive 1.22E+00 7.32E+00 8.39E+00 positive

-1.01E+01 1.99E+01 2.25E+01 positive MW-58-26 MW-58-65 Q2-2011 5/3/2011 10:11 3.29E+02 3.78E+02 3.97E+02 1.00E+03

-4.47E-01 1.03E+00 1.44E+00 2.00E+00 1.93E+00 5.92E+00 7.00E+00 positive

-7.81E-01 7.04E+00 7.26E+00 positive NA NA NA positive MW-58-65 MW-58-65 Q2-2011 Mid 7/5/2011 13:30 7.26E+02 3.93E+02 2.83E+02 1.00E+03 4.19E-01 9.12E-01 1.03E+00 2.00E+00 5.29E+00 1.05E+01 1.25E+01 positive 1.47E+00 7.53E+00 8.78E+00 positive 3.44E-01 2.03E+01 2.27E+01 positive MW-58-65 MW-59-32 Q2-2011 Mid 7/20/2011 9:59 1.56E+02 3.90E+02 4.38E+02 5.88E-01 1.14E+00 1.27E+00

-1.79E+00 7.92E+00 8.02E+00

-2.58E+00 9.78E+00 1.02E+01

-1.40E+01 1.82E+01 2.07E+01 MW-59-32 MW-59-45 Q2-2011 Mid 7/20/2011 9:59 5.24E+02 4.35E+02 4.43E+02

-1.01E+00 1.05E+00 1.49E+00 1.81E+00 8.52E+00 9.88E+00 2.79E+00 9.48E+00 1.15E+01

-1.12E+01 1.83E+01 2.08E+01 MW-59-45 MW-59-68 Q2-2011 Mid 7/20/2011 10:14 1.15E+02 3.90E+02 4.42E+02 1.10E-01 7.26E-01 9.01E-01 2.83E+00 9.33E+00 1.09E+01 8.22E-01 9.87E+00 1.06E+01

-1.57E+01 2.17E+01 2.47E+01 MW-59-68 MW-60-35 Q2-2011 4/15/2011 11:36 2.03E+02 4.32E+02 4.80E+02 2.00E+03 3.77E-01 1.66E+00 2.00E+00 2.00E+00 2.46E+00 1.14E+01 8.95E+00 positive

-8.48E-01 9.58E+00 1.03E+01 positive 2.65E+00 1.42E+01 1.61E+01 positive MW-60-35 MW-60-53 Q2-2011 4/15/2011 11:37

-5.87E+01 3.96E+02 4.80E+02 2.00E+03

-1.18E-02 1.60E+00 2.04E+00 2.00E+00 2.17E+00 9.90E+00 1.14E+01 positive

-1.11E+00 8.68E+00 8.95E+00 positive

-1.06E+00 1.43E+01 1.66E+01 positive MW-60-53 MW-60-72 Q2-2011 4/15/2011 13:12 2.19E+02 3.78E+02 4.13E+02 2.00E+03 7.12E-01 1.72E+00 1.97E+00 2.00E+00

-5.14E+00 6.54E+00 5.80E+00 positive

-3.30E+00 1.14E+01 1.14E+01 positive

-2.93E+00 1.39E+01 1.63E+01 positive MW-60-72 MW-60-135 Q2-2011 4/15/2011 13:25 4.14E+02 4.02E+02 4.12E+02 2.00E+03 6.52E-01 1.90E+00 2.16E+00 2.00E+00

-6.83E+00 1.39E+01 1.63E+01 positive

-2.48E+00 9.86E+00 1.01E+01 positive 4.64E+00 1.47E+01 1.65E+01 positive MW-60-135 MW-60-154 Q2-2011 4/15/2011 13:19 3.06E+02 3.96E+02 4.21E+02 2.00E+03

-4.20E-01 1.53E+00 2.02E+00 2.00E+00

-2.09E+00 7.62E+00 7.82E+00 positive

-7.25E-01 6.50E+00 6.79E+00 positive 1.62E+00 1.44E+01 1.64E+01 positive MW-60-154 MW-60-176 Q2-2011 4/15/2011 13:49 8.99E+02 4.66E+02 4.18E+02 2.00E+03

-8.29E-01 1.41E+00 2.10E+00 2.00E+00

-7.83E-02 9.90E+00 1.10E+01 positive

-2.35E+00 1.02E+01 1.03E+01 positive

-2.40E-01 1.40E+01 1.62E+01 positive MW-60-176 MW-62-18 Q2-2011 4/13/2011 11:58 3.25E+02 4.56E+02 4.92E+02 2.00E+03 7.82E-01 1.54E+00 1.71E+00 2.00E+00

-4.38E+00 1.00E+01 1.09E+01 positive

-4.07E-01 1.06E+01 1.16E+01 positive NA NA NA positive MW-62-18 MW-62-18 Q2-2011 Mid 7/22/2011 11:35 2.00E+02 4.02E+02 4.45E+02 2.00E+03 1.26E+00 1.24E+00 1.25E+00 2.00E+00 4.94E+00 9.42E+00 1.14E+01 positive

-1.79E+00 1.05E+01 1.08E+01 positive

-3.83E+00 1.96E+01 2.20E+01 positive MW-62-18 MW-62-37 Q2-2011 4/13/2011 12:10 1.56E+02 4.36E+02 4.91E+02 2.00E+03

-1.97E-01 1.08E+00 1.37E+00 2.00E+00

-4.48E+00 8.32E+00 7.76E+00 positive

-1.68E+00 9.02E+00 9.05E+00 positive NA NA NA positive MW-62-37 MW-62-37 Q2-2011 Mid 7/22/2011 12:28 1.15E+02 3.90E+02 4.42E+02 2.00E+03 1.03E+00 1.60E+00 1.73E+00 2.00E+00

-3.64E+00 7.95E+00 8.03E+00 positive 2.96E+00 1.10E+01 1.30E+01 positive

-8.92E+00 1.85E+01 2.09E+01 positive MW-62-37 MW-62-53 Q2-2011 4/13/2011 11:32 1.57E+02 4.36E+02 4.92E+02 2.00E+03 1.72E+00 1.79E+00 1.84E+00 2.00E+00 5.42E-01 6.78E+00 7.51E+00 positive

-3.00E-01 6.24E+00 6.58E+00 positive NA NA NA positive MW-62-53 MW-62-53 Q2-2011 Mid 7/22/2011 10:47 1.60E+02 3.96E+02 4.45E+02 2.00E+03

-4.83E-01 1.07E+00 1.58E+00 2.00E+00 4.34E+00 7.86E+00 9.52E+00 positive 1.66E+00 8.85E+00 1.02E+01 positive

-1.60E+01 1.79E+01 2.05E+01 positive MW-62-53 MW-62-71 Q2-2011 4/13/2011 11:15 3.39E+02 4.72E+02 5.08E+02 2.00E+03 9.04E-01 1.45E+00 1.58E+00 2.00E+00 2.33E+00 7.96E+00 9.27E+00 positive

-2.38E+00 8.50E+00 8.56E+00 positive NA NA NA positive MW-62-71 MW-62-71 Q2-2011 Mid 7/22/2011 10:12 4.21E+02 4.26E+02 4.44E+02 2.00E+03

-3.90E-01 1.36E+00 1.90E+00 2.00E+00

-7.29E-02 7.74E+00 8.31E+00 positive

-7.90E-01 8.28E+00 8.59E+00 positive

-6.70E+00 1.89E+01 2.13E+01 positive MW-62-71 MW-62-92 Q2-2011 4/13/2011 11:03 5.06E+02 4.78E+02 4.92E+02 2.00E+03 2.87E-01 1.11E+00 1.30E+00 2.00E+00

-2.87E+00 7.18E+00 7.31E+00 positive

-2.10E+00 8.94E+00 8.88E+00 positive NA NA NA positive MW-62-92 MW-62-92 Q2-2011 Mid 7/22/2011 10:18 5.61E+02 4.35E+02 4.39E+02 2.00E+03

-1.12E+00 1.52E+00 2.06E+00 2.00E+00 5.26E+00 9.42E+00 1.13E+01 positive

-7.24E-02 9.48E+00 1.05E+01 positive

-6.69E+00 1.76E+01 1.99E+01 positive MW-62-92 MW-62-138 Q2-2011 4/13/2011 14:39 6.31E+02 5.04E+02 5.09E+02 2.00E+03 1.22E+00 1.29E+00 1.32E+00 2.42E+00 1.29E+00 9.08E+00 1.04E+01 positive 1.71E+00 8.82E+00 1.02E+01 positive NA NA NA positive MW-62-138 MW-62-138 Q2-2011 Mid 7/22/2011 11:50 4.66E+02 4.23E+02 4.36E+02 2.00E+03 6.72E-01 1.20E+00 1.32E+00 2.42E+00

-5.97E-01 7.41E+00 8.13E+00 positive 6.36E+00 9.57E+00 1.23E+01 positive

-1.13E+01 1.79E+01 2.03E+01 positive MW-62-138 MW-62-182 Q2-2011 4/13/2011 14:44 1.92E+02 4.50E+02 5.03E+02 2.00E+03

-5.04E-01 1.05E+00 1.45E+00 2.00E+00 5.54E+00 8.70E+00 1.09E+01 positive

-9.44E-01 1.08E+01 1.15E+01 positive NA NA NA positive MW-62-182 MW-62-182 Q2-2011 Mid 7/22/2011 12:02 2.90E+02 4.20E+02 4.54E+02 2.00E+03 2.09E-01 1.22E+00 1.47E+00 2.00E+00 6.48E-01 7.41E+00 8.36E+00 positive

-5.94E-01 7.65E+00 8.31E+00 positive

-2.27E+00 1.56E+01 1.75E+01 positive MW-62-182 MW-63-18 Q2-2011 4/19/2011 10:35 7.23E+01 4.38E+02 5.05E+02 2.00E+03

-3.13E-01 1.13E+00 1.49E+00 2.00E+00 8.69E-01 8.04E+00 8.92E+00 positive

-3.22E+00 8.16E+00 7.75E+00 positive NA NA NA positive MW-63-18 MW-63-18 Q2-2011 Mid 7/21/2011 10:26 2.96E+02 3.99E+02 4.29E+02 2.00E+03 6.58E-02 1.19E+00 1.50E+00 2.00E+00 2.40E+00 7.62E+00 9.09E+00 positive 2.37E+00 7.53E+00 9.30E+00 positive

-8.91E+00 1.69E+01 1.92E+01 positive MW-63-18 MW-63-34 Q2-2011 4/19/2011 10:25 3.94E+02 4.60E+02 4.87E+02 2.00E+03

-1.13E+00 1.22E+00 1.83E+00 2.00E+00 4.36E+00 8.34E+00 9.94E+00 positive 3.72E+00 8.28E+00 1.02E+01 positive NA NA NA positive MW-63-34 MW-63-34 Q2-2011 Mid 7/21/2011 10:08 3.04E+02 4.08E+02 4.39E+02 2.00E+03 2.38E-01 1.17E+00 1.42E+00 2.00E+00

-1.34E+00 9.03E+00 9.54E+00 positive 1.66E-01 7.89E+00 8.63E+00 positive

-1.26E+01 1.28E+01 1.47E+01 positive MW-63-34 MW-63-50 Q2-2011 4/19/2011 11:25 1.68E+02 4.36E+02 4.89E+02 2.00E+03 7.72E-01 1.39E+00 1.53E+00 2.00E+00

-6.46E+00 9.76E+00 9.29E+00 positive 3.72E+00 8.18E+00 1.03E+01 positive NA NA NA positive MW-63-50 MW-63-50 Q2-2011 Mid 7/21/2011 11:25 2.09E+02 3.99E+02 4.41E+02 2.00E+03

-6.50E-01 8.58E-01 1.39E+00 2.00E+00 2.46E-01 7.56E+00 8.55E+00 positive 2.77E+00 8.64E+00 1.05E+01 positive

-2.89E+00 1.51E+01 1.69E+01 positive MW-63-50 MW-63-93 Q2-2011 4/19/2011 11:27 9.64E+01 4.42E+02 5.05E+02 2.00E+03

-4.30E-02 1.14E+00 1.44E+00 2.00E+00 3.31E+00 8.92E+00 1.03E+01 positive

-4.35E-01 6.80E+00 7.25E+00 positive NA NA NA positive MW-63-93 MW-63-93 Q2-2011 Mid 7/21/2011 11:32 4.17E+02 4.20E+02 4.40E+02 2.00E+03

-4.28E-01 1.06E+00 1.48E+00 2.00E+00

-3.58E+00 8.10E+00 7.77E+00 positive

-6.11E+00 7.92E+00 5.51E+00 positive 6.50E-01 1.71E+01 1.90E+01 positive MW-63-93 MW-63-112 Q2-2011 4/19/2011 11:25 4.22E+02 4.68E+02 4.92E+02 2.00E+03

-7.96E-01 1.00E+00 1.47E+00 2.00E+00 4.96E+00 1.05E+01 1.25E+01 positive 1.64E+00 1.17E+01 1.36E+01 positive NA NA NA positive MW-63-112 MW-63-112 Q2-2011 Mid 7/21/2011 11:46 6.01E+02 4.44E+02 4.44E+02 2.00E+03 2.29E-01 1.13E+00 1.37E+00 2.00E+00

-8.46E-01 1.06E+01 1.11E+01 positive 6.03E+00 1.21E+01 1.54E+01 positive

-1.22E+00 1.77E+01 1.98E+01 positive MW-63-112 MW-63-121 Q2-2011 4/19/2011 9:54 5.77E+02 4.84E+02 4.91E+02 2.00E+03 4.12E-01 1.18E+00 1.37E+00 2.00E+00

-1.03E+00 6.92E+00 7.17E+00 positive

-1.09E+01 9.86E+00 5.99E+00 positive NA NA NA positive MW-63-121 MW-63-121 Q2-2011 Mid 7/21/2011 9:58 1.33E+03 5.28E+02 4.45E+02 2.00E+03

-3.05E-01 1.36E+00 1.74E+00 2.00E+00 1.63E-03 7.44E+00 8.17E+00 positive

-3.19E+00 1.05E+01 1.07E+01 positive 1.12E+00 1.84E+01 2.05E+01 positive MW-63-121 MW-63-163 Q2-2011 4/19/2011 9:49 4.92E+02 4.84E+02 5.03E+02 2.00E+03 1.11E+00 1.82E+00 2.00E+00 2.00E+00 4.43E-01 8.94E+00 9.98E+00 positive 4.78E+00 1.02E+01 1.26E+01 positive NA NA NA positive MW-63-163 MW-63-163 Q2-2011 Mid 7/21/2011 10:09 5.08E+02 4.26E+02 4.36E+02 2.00E+03

-6.14E-01 1.01E+00 1.48E+00 2.00E+00

-8.47E-01 7.47E+00 8.17E+00 positive 4.07E-01 7.53E+00 8.66E+00 positive

-8.69E+00 1.47E+01 1.67E+01 positive MW-63-163 MW-63-174 Q2-2011 4/19/2011 9:52 1.56E+02 4.48E+02 5.04E+02 2.00E+03

-7.87E-01 9.72E-01 1.48E+00 2.00E+00

-6.41E+00 8.32E+00 7.72E+00 positive

-9.85E-01 8.58E+00 9.20E+00 positive NA NA NA positive MW-63-174 MW-63-174 Q2-2011 Mid 7/21/2011 9:57 4.14E+02 4.17E+02 4.36E+02 2.00E+03 6.96E-01 1.85E+00 2.10E+00 2.00E+00

-3.57E+00 8.10E+00 8.27E+00 positive 4.67E-01 9.36E+00 1.09E+01 positive

-2.55E+00 1.33E+01 1.49E+01 positive MW-63-174 MW-65-48 Q2-2011 Mid 7/7/2011 12:19 8.59E+01 2.43E+02 2.85E+02 5.73E-01 1.04E+00 1.15E+00 4.10E+00 9.03E+00 1.09E+01

-1.15E+00 1.12E+01 1.18E+01

-5.93E+00 2.39E+01 2.69E+01 MW-65-48 MW-65-80 Q2-2011 Mid 7/13/2011 10:12 8.54E+01 2.41E+02 2.84E+02 1.26E-01 9.24E-01 1.12E+00

-2.33E+00 9.12E+00 9.46E+00 2.88E+00 1.15E+01 1.34E+01

-1.27E+01 2.00E+01 2.29E+01 MW-65-80 MW-66-21 Q2-2011 4/14/2011 13:43 9.30E+01 3.88E+02 4.46E+02 1.33E+03 6.73E-01 1.64E+00 1.85E+00 2.07E+00

-4.70E+00 8.74E+00 8.45E+00 positive 6.94E+00 9.82E+00 1.25E+01 positive 1.81E+00 1.51E+01 1.72E+01 positive MW-66-21 MW-66-36 Q2-2011 4/14/2011 12:53 3.52E+03 7.36E+02 4.79E+02 7.71E+03 1.06E+01 2.88E+00 1.95E+00 1.40E+01 1.50E-01 7.24E+00 8.14E+00 positive 5.40E-01 7.92E+00 9.01E+00 positive 6.10E-01 1.55E+01 1.79E+01 positive MW-66-36 MW-67-39 Q2-2011 4/14/2011 13:25 3.73E+03 7.14E+02 4.17E+02 6.52E+03 1.25E+01 3.76E+00 2.10E+00 1.81E+01 4.53E+00 8.78E+00 1.04E+01 positive 3.71E+00 9.54E+00 1.14E+01 positive 6.99E+00 1.47E+01 1.63E+01 positive MW-67-39 MW-67-105 Q2-2011 4/14/2011 13:43 1.10E+03 4.84E+02 4.12E+02 3.92E+03 2.70E-01 1.72E+00 2.11E+00 4.38E+00

-3.96E-01 9.66E+00 1.05E+01 positive

-1.91E-01 7.24E+00 7.88E+00 positive 5.71E+00 1.55E+01 1.73E+01 positive MW-67-105 MW-67-173 Q2-2011 4/14/2011 14:09 5.72E+02 4.20E+02 4.10E+02 1.61E+03

-2.56E-01 1.69E+00 1.99E+00 2.00E+00 5.04E+00 9.64E+00 1.17E+01 positive

-9.27E+00 1.03E+01 6.85E+00 positive 7.50E+00 1.23E+01 1.34E+01 positive MW-67-173 MW-67-219 Q2-2011 4/14/2011 10:49 1.07E+03 4.78E+02 4.12E+02 2.26E+03

-7.57E-01 9.50E-01 1.53E+00 2.00E+00

-2.70E+00 6.62E+00 6.47E+00 positive 4.16E+00 9.78E+00 1.20E+01 positive 2.95E+00 1.43E+01 1.62E+01 positive MW-67-219 MW-67-276 Q2-2011 4/14/2011 10:53 1.06E+03 4.84E+02 4.19E+02 2.01E+03 3.46E-01 1.22E+00 1.45E+00 2.00E+00

-5.30E+00 6.78E+00 6.12E+00 positive 1.62E+00 1.02E+01 1.15E+01 positive 5.62E-01 1.42E+01 1.63E+01 positive MW-67-276 MW-67-323 Q2-2011 4/14/2011 11:33 4.26E+02 4.06E+02 4.13E+02 1.00E+03 1.05E+00 1.52E+00 1.62E+00 2.00E+00 2.02E+00 8.36E+00 9.62E+00 positive

-1.12E+00 7.80E+00 8.21E+00 positive

-2.21E-01 1.30E+01 1.50E+01 positive MW-67-323 MW-67-340 Q2-2011 4/14/2011 11:17 6.56E+02 4.32E+02 4.13E+02 1.01E+03 2.62E-01 1.16E+00 1.40E+00 2.00E+00 5.89E+00 9.02E+00 1.12E+01 positive 4.57E+00 9.02E+00 1.15E+01 positive 7.58E+00 1.54E+01 1.71E+01 positive MW-67-340 MW-107 Q2-2011 5/2/2011 9:25 3.15E+02 3.76E+02 3.95E+02 1.00E+03 8.29E-01 1.29E+00 1.40E+00 2.00E+00

-3.56E+00 1.30E+01 1.65E+01 positive 2.39E+00 6.84E+00 8.63E+00 positive NA NA NA positive MW-107 MW-108 Q2-2011 Mid 7/5/2011 15:08 1.24E+03 4.89E+02 2.90E+02

-9.21E-02 1.29E+00 1.55E+00 4.93E+00 9.84E+00 1.17E+01

-7.54E+00 8.49E+00 7.19E+00

-8.75E+00 2.32E+01 2.62E+01 MW-108 MW-109 Q2-2011 Mid 7/5/2011 12:45 2.43E+03 6.36E+02 2.79E+02 2.60E-01 1.25E+00 1.45E+00 2.23E-01 8.67E+00 9.62E+00

-3.32E+00 7.74E+00 6.65E+00 3.57E+00 3.51E+01 3.92E+01 MW-109 U3-3 Q2-2011 Mid 7/13/2011 12:28 6.73E+02 3.81E+02 2.81E+02

-3.49E-01 8.13E-01 1.19E+00

-4.64E-01 8.01E+00 8.64E+00

-3.52E+00 8.61E+00 8.20E+00 NA NA NA U3-3 U3-4D Q2-2011 4/25/2011 14:50 7.41E+02 4.36E+02 3.98E+02 1.00E+03 1.18E+00 1.38E+00 1.46E+00 2.00E+00

-3.17E+00 7.58E+00 7.50E+00 positive 4.81E-01 7.14E+00 8.11E+00 positive NA NA NA positive U3-4D U3-4D Q2-2011 Mid 7/14/2011 11:55 3.88E+02 4.20E+02 4.38E+02 1.00E+03 1.24E-01 1.06E+00 1.26E+00 2.00E+00 4.78E+00 1.13E+01 1.32E+01 positive 3.12E+00 1.22E+01 1.46E+01 positive NA NA NA positive U3-4D U3-4S Q2-2011 4/25/2011 14:13 1.48E+02 3.78E+02 4.22E+02 1.00E+03***

6.69E-01 1.27E+00 1.41E+00 2.00E+00 5.35E+00 8.82E+00 1.07E+01 positive 1.75E+00 8.92E+00 1.03E+01 positive NA NA NA positive U3-4S U3-4S Q2-2011 Mid 7/14/2011 11:27 3.29E+02 4.11E+02 4.36E+02 1.00E+03***

1.06E+00 1.33E+00 1.40E+00 2.00E+00

-2.41E+00 7.59E+00 7.88E+00 positive 3.25E+00 7.65E+00 9.52E+00 positive NA NA NA positive U3-4S U3-T1 Q2-2011 5/6/2011 10:23 7.82E+02 5.16E+02 5.03E+02 1.00E+03

-6.43E-02 9.94E-01 1.30E+00 2.00E+00

-3.24E+00 9.12E+00 9.22E+00 positive 8.49E-01 1.09E+01 1.21E+01 positive NA NA NA positive U3-T1 U3-T2 Q2-2011 5/6/2011 11:41 3.83E+03 6.42E+02 4.19E+02 2.08E+03 3.27E-01 1.32E+00 1.58E+00 2.00E+00 2.82E+00 7.26E+00 8.74E+00 positive 5.77E-01 9.68E+00 1.08E+01 positive NA NA NA positive U3-T2

TABLE 4 2011 2nd QUARTER GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERTY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q22011 FINAL Table 4 - 2011 2nd Quarter Groundwater Analytical Results.xlsx; Q22011 Table 4 Page 3 of 3 See Page 3 for Notes Date Time Result Std. Dev.6 MDC I.L.3,7 Result Std. Dev.6 MDC I.L.3 Result Std. Dev.6 MDC I.L.3 Result Std. Dev.6 MDC I.L.3 Result Std. Dev.6 MDC I.L.3 Well ID1 SAMPLE ID SAMPLE COLLECTION ANALYSIS RESULTS4,5 Well ID TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

U3-T2 Q2-2011 Mid 7/8/2011 10:55 2.67E+03 6.63E+02 2.80E+02 2.08E+03 4.75E-01 1.31E+00 1.50E+00 2.00E+00 3.77E+00 1.08E+01 1.19E+01 positive

-1.06E+00 1.02E+01 1.07E+01 positive NA NA NA positive U3-T2 U1-CSS Q2-2011 5/4/2011 13:24 6.38E+03 6.84E+02 3.40E+02 5.17E+03 1.61E+01 2.70E+00 1.01E+00 2.08E+01 3.29E+00 8.36E+00 9.79E+00 positive 7.12E+00 9.42E+00 1.24E+01 positive

-1.05E+01 1.55E+01 1.84E+01 positive U1-CSS U1-CSS Q2-2011 Mid 7/8/2011 13:33 1.08E+04 1.28E+03 2.79E+02 5.17E+03 3.90E+00 1.82E+00 1.30E+00 2.08E+01 3.84E-02 9.18E+00 1.01E+01 positive

-3.60E+00 9.96E+00 1.06E+01 positive

-3.20E+00 2.09E+01 2.34E+01 positive U1-CSS MH-5 VCFD Q2-2011 4/22/2011 13:37 1.25E+04 1.10E+03 4.46E+02 8.17E-01 1.85E+00 2.08E+00

-3.21E+00 8.36E+00 8.43E+00

-1.60E+00 9.06E+00 9.51E+00 NA NA NA MH-5 VCFD MH-5 VCFD Q2-2011 Mid 7/7/2011 14:29 2.97E+03 7.02E+02 2.83E+02

-3.05E-01 8.04E-01 1.11E+00 9.24E-01 7.95E+00 8.84E+00 5.11E-01 8.49E+00 9.13E+00 NA NA NA MH-5 VCFD MH-5 VCFD Q2-2011 Mid 7/12/2011 12:46 9.86E+03 1.23E+03 2.81E+02 9.15E-01 1.05E+00 1.06E+00

-1.17E+01 1.33E+01 1.52E+01

-1.19E+00 9.99E+00 1.06E+01 NA NA NA MH-5 VCFD MH-5 VCFD Q2-2011 Mid 7/20/2011 10:48 2.89E+03 7.32E+02 3.35E+02

-4.57E-01 1.01E+00 1.47E+00 1.79E+00 6.30E+00 7.26E+00

-2.61E+00 8.34E+00 8.34E+00 NA NA NA MH-5 VCFD MH-5 VCFD Q2-2011 Mid 7/26/2011 12:50 1.86E+03 6.03E+02 3.33E+02

-7.10E-01 9.45E-01 1.45E+00 2.81E+00 7.47E+00 8.99E+00

-8.33E-01 9.66E+00 1.03E+01 NA NA NA MH-5 VCFD LAF-002 Q2-2011 5/2/2011 12:50 6.69E+01 3.04E+02 3.43E+02 positive 1.16E+00 1.55E+00 1.66E+00 positive

-5.80E-01 7.86E+00 8.57E+00 positive

-6.46E-01 7.24E+00 7.65E+00 positive

-3.48E-01 1.60E+01 1.83E+01 positive LAF-002 B-1 Q2-2011 4/25/2011 10:50 8.10E+03 9.22E+02 4.53E+02

-6.21E-03 1.74E+00 2.09E+00 2.05E+01 1.33E+01 1.03E+01 3.18E+00 9.06E+00 1.11E+01 NA NA NA B-1 B-6 Q2-2011 4/25/2011 9:48 2.68E+03 6.18E+02 4.53E+02

-6.69E-01 1.58E+00 2.09E+00

-1.31E-01 8.56E+00 9.08E+00 4.73E+00 1.06E+01 1.35E+01 NA NA NA B-6 B-6 Q2-2011 Mid 7/8/2011 11:05 5.39E+02 3.54E+02 2.82E+02 1.32E+00 1.56E+00 1.63E+00 6.09E+00 1.58E+01 8.04E+00

-2.64E+00 8.97E+00 8.84E+00 NA NA NA B-6 Notes

1. For nested multi-level monitoring wells, suffix of well ID indicates depth (rounded to nearest foot) from reference point on casing to bottom of well screen. For Waterloo multi-level systems, suffix indicates depth (rounded to nearest foot) from reference point on casing to top of sampling port.

Well IDs without a suffix are open bedrock wellbores.

2. Sampling depths within sampling intervals (location of pump intake) have been established at location of most transmissive zone to the extent possible.
3. I.L.s (Investigation Levels) are predetermined detection limits assigned to each sampling location which, if reached or exceeded, require further investigation or action. I.L.s presented here for Sr-90, CS-137, Co-60 & Ni-63 are established for 2011 based on 2010 averages. See Note #7 below for further 2011 Tritium I.L. discussion. Positive detections indicate that the the result is greater than MDC and greater than or equal to 3 times the 1 sigma uncertainty.
4. NA indicates that the constituent was not analyzed.
5. Shading indicates that the sample result exceeds the Investigation Level.
6. Column designated as Std. Dev. provides the three times 1 sigma uncertainty values.
7. To be conservative, the 2011 Tritium I.L.s were calculated using (2x the 2009 yearly average) beacuase an increased Tritium activity in multiple Unit 2 sampling intervals was observed during 2010 in response to the transient surface spill from a temporary rental RWST/R.O. processing skid.
  • Indicates storm or foundation drain sampling locations, for which investigation levels are not applicable.
    • Indicates 2011 I.L.s not computed for this well due to absence of 2008 through 2010 data.
      • 2011 Tritium I.L. calculated based on the 2010 rolling average due to absence of 2009 data.
        • The Q2 2011 MW-40-46 preliminary Sr-90 result was 2.83 pCi/L and exceeded the IL. However, after re-analysis, the sample was below the detection limit which suggests the preliminary result was likely a false positive. A shift in the MDC for the preliminary result could have possibly resulted from contaminated laboratory equipment, modified count time, or changes in sample preparation.

TABLE 4 2011 3rd QUARTER GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERTY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q32011 FINAL Table 4 - 2011 3rd Quarter Groundwater Analytical Results.xlsx; Q32011 Table 4 Page 1 of 2 See Page 2 for Notes Date Time Result Std. Dev.6 MDC I.L.3,7 Result Std. Dev.6 MDC I.L.3 Result Std. Dev.6 MDC I.L.3 Result Std. Dev.6 MDC I.L.3 Result Std. Dev.6 MDC I.L.3 MW-31-49 Q3-2011 8/5/2011 10:47 4.98E+03 7.80E+02 4.16E+02 4.28E+04

-2.63E-02 1.34E+00 1.58E+00 2.00E+00 6.39E+00 8.76E+00 1.10E+01 positive 5.20E-01 1.06E+01 1.16E+01 positive NA NA NA positive MW-31-49 MW-31-63 Q3-2011 8/5/2011 11:29 1.63E+04 1.31E+03 4.18E+02 3.99E+04

-1.30E-01 1.71E+00 2.02E+00 2.00E+00

-2.83E-01 9.87E+00 1.12E+01 positive 2.13E+00 9.24E+00 1.08E+01 positive NA NA NA positive MW-31-63 MW-31-85 Q3-2011 8/5/2011 11:27 4.82E+03 7.74E+02 4.22E+02 1.46E+04 1.39E-01 1.40E+00 1.63E+00 2.00E+00

-8.79E-01 8.25E+00 8.80E+00 positive

-4.79E+00 9.57E+00 8.27E+00 positive NA NA NA positive MW-31-85 MW-32-59 Q3-2011 8/5/2011 12:30 2.06E+04 1.47E+03 4.19E+02 3.42E+04 1.64E+00 1.66E+00 1.71E+00 2.00E+00

-3.73E+00 8.34E+00 8.04E+00 positive

-1.05E+00 8.79E+00 9.24E+00 positive NA NA NA positive MW-32-59 MW-32-85 Q3-2011 8/5/2011 13:36 1.14E+04 1.12E+03 4.20E+02 1.63E+04 1.14E-01 1.64E+00 1.92E+00 2.00E+00 5.40E+00 6.87E+00 8.79E+00 positive

-1.21E+00 6.69E+00 6.57E+00 positive NA NA NA positive MW-32-85 MW-32-149 Q3-2011 8/5/2011 11:10 9.86E+02 4.71E+02 4.21E+02 1.00E+03 4.80E-01 1.81E+00 2.06E+00 2.00E+00

-9.94E-01 9.60E+00 9.39E+00 positive 2.75E+00 7.41E+00 9.28E+00 positive NA NA NA positive MW-32-149 MW-32-173 Q3-2011 8/5/2011 11:11 5.69E+02 4.17E+02 4.12E+02 1.50E+03 6.34E-01 1.48E+00 1.66E+00 2.00E+00

-9.50E-01 6.36E+00 6.56E+00 positive

-1.55E+00 1.10E+01 1.14E+01 positive NA NA NA positive MW-32-173 MW-32-190 Q3-2011 8/5/2011 11:15 1.44E+03 5.16E+02 4.20E+02 4.21E+03 7.59E-01 1.64E+00 1.82E+00 2.00E+00 2.02E+00 7.23E+00 8.43E+00 positive 1.28E+00 9.24E+00 1.06E+01 positive NA NA NA positive MW-32-190 MW-36-24 Q3-2011 8/16/2011 13:34 1.12E+03 5.01E+02 4.51E+02 2.56E+03 2.34E-01 9.96E-01 1.18E+00 2.00E+00

-2.80E+00 7.71E+00 7.54E+00 positive 7.10E-01 7.89E+00 8.75E+00 positive NA NA NA positive MW-36-24 MW-36-41 Q3-2011 8/16/2011 14:18 5.90E+03 8.37E+02 4.55E+02 2.10E+04 1.74E+00 1.26E+00 1.13E+00 7.99E+00 1.75E+00 8.91E+00 9.88E+00 positive 4.43E+00 9.15E+00 1.15E+01 positive NA NA NA positive MW-36-41 MW-36-52 Q3-2011 8/16/2011 14:52 4.69E+03 7.59E+02 4.48E+02 1.48E+04 2.93E+00 1.57E+00 1.36E+00 8.14E+00 3.59E+00 8.22E+00 9.80E+00 positive

-1.83E+00 9.33E+00 9.74E+00 positive NA NA NA positive MW-36-52 MW-37-22 Q3-2011 8/16/2011 10:35 4.52E+03 7.56E+02 4.53E+02 9.19E+03 7.59E+00 2.07E+00 1.32E+00 2.20E+01 3.10E+00 7.26E+00 8.77E+00 positive

-9.99E-01 7.35E+00 7.48E+00 positive NA NA NA positive MW-37-22 MW-37-32 Q3-2011 8/16/2011 11:00 5.23E+03 7.95E+02 4.52E+02 9.32E+03 1.68E+01 2.87E+00 1.13E+00 3.54E+01

-2.53E+00 8.34E+00 7.53E+00 positive

-6.09E+00 9.06E+00 8.10E+00 positive NA NA NA positive MW-37-32 MW-37-40 Q3-2011 8/16/2011 11:24 5.03E+03 7.86E+02 4.53E+02 9.02E+03 1.95E+01 3.18E+00 1.17E+00 2.84E+01

-2.08E+00 8.25E+00 8.54E+00 positive 1.79E+00 7.35E+00 8.59E+00 positive NA NA NA positive MW-37-40 MW-37-57 Q3-2011 8/16/2011 10:55 5.11E+03 7.98E+02 4.59E+02 9.62E+03 2.15E+01 3.27E+00 1.30E+00 3.68E+01 1.82E+00 7.92E+00 9.16E+00 positive

-1.34E+00 6.39E+00 6.57E+00 positive NA NA NA positive MW-37-57 MW-39-67 Q3-2011 Mid 8/29/2011 13:47 1.49E+04 1.24E+03 4.51E+02 1.00E+03 1.08E+00 1.18E+00 1.20E+00 3.30E+00 2.23E+00 7.77E+00 8.94E+00 positive 4.82E+00 8.25E+00 1.05E+01 positive NA NA NA positive MW-39-67 MW-39-84 Q3-2011 Mid 8/29/2011 13:56 2.38E+02 4.14E+02 4.54E+02 1.00E+03 8.64E-01 1.00E+00 1.00E+00 2.10E+00 5.19E+00 1.54E+01 9.85E+00 positive

-1.20E+00 9.99E+00 1.04E+01 positive NA NA NA positive MW-39-84 MW-39-102 Q3-2011 Mid 8/29/2011 14:11 1.90E+04 1.37E+03 4.41E+02 1.00E+03

-7.38E-01 1.20E+00 1.60E+00 8.10E+00

-3.14E+00 7.92E+00 7.72E+00 positive 4.66E+00 7.83E+00 1.04E+01 positive NA NA NA positive MW-39-102 MW-39-124 Q3-2011 Mid 8/29/2011 10:54

-1.02E+01 3.75E+02 4.45E+02 1.00E+03 3.16E-01 1.12E+00 1.30E+00 4.50E+00

-7.05E+00 1.06E+01 1.01E+01 positive 7.76E+00 1.13E+01 1.46E+01 positive NA NA NA positive MW-39-124 MW-39-183 Q3-2011 Mid 8/29/2011 10:45 1.14E+02 3.81E+02 4.33E+02 1.00E+03 1.10E+00 1.13E+00 1.10E+00 2.00E+00

-3.70E+00 1.05E+01 1.05E+01 positive 5.90E+00 9.54E+00 1.22E+01 positive NA NA NA positive MW-39-183 MW-39-195 Q3-2011 Mid 8/29/2011 10:51 1.72E+04 1.31E+03 4.43E+02 1.00E+03 4.98E-02 7.50E-01 9.59E-01 2.00E+00 7.98E-01 7.62E+00 8.56E+00 positive 2.43E+00 8.19E+00 9.86E+00 positive NA NA NA positive MW-39-195 MW-41-40 Q3-2011 8/4/2011 14:39 5.94E+02 3.57E+02 3.53E+02 1.00E+03 1.70E+00 1.87E+00 1.93E+00 7.28E+00 4.91E-01 5.97E+00 6.61E+00 positive

-6.02E-02 8.16E+00 8.80E+00 positive NA NA NA positive MW-41-40 MW-41-63 Q3-2011 8/4/2011 14:20 6.60E+02 3.60E+02 3.51E+02 1.00E+03 1.91E+00 1.95E+00 1.96E+00 7.36E+00 1.64E+00 7.89E+00 8.72E+00 positive

-1.43E+00 7.29E+00 7.72E+00 positive NA NA NA positive MW-41-63 MW-42-49 Q3-2011 8/1/2011 12:50 7.78E+02 3.90E+02 3.74E+02 3.16E+04 2.60E+00 1.92E+00 1.82E+00 9.00E+01 1.57E+04 1.92E+03 2.16E+01 65750 3.58E+00 8.40E+00 1.01E+01 positive 2.80E+02 3.48E+01 2.02E+01 673.5 MW-42-49 MW-42-78 Q3-2011 8/1/2011 12:50 3.97E+02 3.57E+02 3.72E+02 1.00E+03

-1.16E-01 1.13E+00 1.49E+00 2.00E+00 5.85E-01 7.98E+00 7.65E+00 positive

-5.68E-01 9.45E+00 1.03E+01 positive 1.02E+00 1.17E+01 1.31E+01 positive MW-42-78 MW-43-28 Q3-2011 8/4/2011 11:15 2.26E+02 3.24E+02 3.50E+02 1.00E+03

-1.34E-01 1.42E+00 1.87E+00 2.00E+00 4.00E+00 7.35E+00 9.02E+00 positive

-3.51E+00 9.33E+00 9.21E+00 positive NA NA NA positive MW-43-28 MW-43-62 Q3-2011 8/4/2011 11:35 1.66E+02 3.21E+02 3.55E+02 1.00E+03

-2.14E-01 1.61E+00 1.93E+00 2.00E+00

-1.62E+00 7.95E+00 8.00E+00 positive

-2.98E+00 8.13E+00 8.75E+00 positive NA NA NA positive MW-43-62 MW-44-66 Q3-2011 8/22/2011 12:08 4.76E+02 4.32E+02 4.45E+02 1.00E+03 1.13E-01 9.03E-01 1.11E+00 2.00E+00

-7.41E+00 8.73E+00 6.89E+00 positive

-3.14E+00 9.09E+00 9.07E+00 positive NA NA NA positive MW-44-66 MW-44-102 Q3-2011 8/22/2011 10:43 8.25E+02 4.77E+02 4.57E+02 1.00E+03

-1.10E-01 9.69E-01 1.28E+00 2.00E+00

-3.22E+00 6.69E+00 6.63E+00 positive 8.99E+00 7.50E+00 1.08E+01 positive NA NA NA positive MW-44-102 MW-45-42 Q3-2011 Mid 8/23/2011 13:58 2.72E+04 1.63E+03 4.50E+02 5.90E+03 1.77E-01 9.15E-01 1.10E+00 2.00E+00 8.73E-01 1.12E+01 1.05E+01 positive

-7.52E+00 1.06E+01 8.89E+00 positive NA NA NA positive MW-45-42 MW-45-61 Q3-2011 Mid 8/23/2011 10:48 5.91E+03 8.13E+02 4.34E+02 2.65E+03 7.01E-01 1.16E+00 1.26E+00 2.00E+00

-8.68E-01 7.44E+00 7.90E+00 positive 1.84E+00 6.63E+00 7.89E+00 positive NA NA NA positive MW-45-61 MW-46 Q3-2011 8/17/2011 11:36 3.30E+03 6.72E+02 4.50E+02 1.84E+03 8.77E-01 1.21E+00 1.29E+00 2.00E+00 3.43E-01 7.86E+00 8.82E+00 positive

-1.10E+00 7.50E+00 7.97E+00 positive NA NA NA positive MW-46 MW-47-56 Q3-2011 Mid 8/18/2011 12:39 5.42E+02 2.76E+02 2.00E+02 1.03E+00 1.28E+00 1.31E+00

-8.54E-01 1.13E+01 1.25E+01 3.86E+00 8.64E+00 1.07E+01

-2.22E+00 1.75E+01 2.00E+01 MW-47-56 MW-47-80 Q3-2011 Mid 8/18/2011 11:36 1.37E+05 4.08E+03 2.18E+02 8.23E-01 1.22E+00 1.29E+00

-5.83E+00 9.30E+00 8.60E+00

-6.32E-01 8.79E+00 9.27E+00

-1.15E+00 1.88E+01 2.15E+01 MW-47-80 MW-49-26 Q3-2011 8/10/2011 10:46 3.97E+03 6.39E+02 2.00E+02 6.52E+03 1.26E+01 2.89E+00 1.34E+00 2.79E+01

-1.94E+00 9.06E+00 9.33E+00 positive 2.94E+00 8.31E+00 1.00E+01 positive

-1.77E+01 2.04E+01 2.57E+01 positive MW-49-26 MW-49-42 Q3-2011 8/10/2011 11:16 3.83E+03 6.21E+02 1.96E+02 4.97E+03 1.61E+01 3.24E+00 1.64E+00 3.72E+01

-1.22E+00 8.94E+00 9.69E+00 positive

-3.72E+00 8.79E+00 8.23E+00 positive

-1.40E+01 1.81E+01 2.15E+01 positive MW-49-42 MW-49-65 Q3-2011 8/10/2011 10:55 2.43E+03 5.10E+02 2.00E+02 3.03E+03 1.14E+01 2.75E+00 1.42E+00 2.62E+01 1.12E-01 7.77E+00 8.40E+00 positive

-4.19E+00 9.00E+00 8.02E+00 positive

-6.91E-01 1.81E+01 2.05E+01 positive MW-49-65 MW-50-42 Q3-2011 8/19/2011 12:10 9.52E+02 3.42E+02 2.00E+02 1.04E+03 9.47E+00 2.60E+00 1.31E+00 1.10E+01 2.17E+00 8.01E+00 9.07E+00 positive 4.72E+00 9.81E+00 1.22E+01 positive

-7.08E+00 1.81E+01 2.10E+01 positive MW-50-42 MW-50-66 Q3-2011 8/19/2011 12:12 7.15E+03 8.49E+02 2.00E+02 5.90E+03 2.57E+01 4.05E+00 1.65E+00 5.24E+01 3.97E+00 8.46E+00 1.01E+01 positive 1.73E+00 9.03E+00 1.05E+01 positive

-8.92E+00 1.80E+01 2.11E+01 positive MW-50-66 MW-51-40 Q3-2011 7/28/2011 11:43 3.78E+01 3.06E+02 3.52E+02 1.00E+03

-2.51E-01 1.37E+00 1.85E+00 2.00E+00

-2.58E+00 1.35E+01 1.68E+01 positive

-3.37E+00 9.33E+00 9.05E+00 positive NA NA NA positive MW-51-40 MW-51-79 Q3-2011 7/28/2011 11:55

-1.93E+01 3.09E+02 3.60E+02 1.00E+03 1.36E-01 1.63E+00 1.96E+00 2.00E+00 2.20E+00 8.28E+00 9.43E+00 positive

-5.24E-01 9.27E+00 9.93E+00 positive NA NA NA positive MW-51-79 MW-51-104 Q3-2011 7/28/2011 9:51 1.64E+02 3.18E+02 3.51E+02 1.00E+03

-8.86E-01 1.26E+00 1.94E+00 2.00E+00

-1.15E-01 6.18E+00 6.84E+00 positive

-3.12E+00 8.10E+00 7.98E+00 positive NA NA NA positive MW-51-104 MW-51-135 Q3-2011 7/28/2011 10:04

-5.63E+01 2.96E+02 3.49E+02 1.00E+03 8.06E-01 1.71E+00 1.92E+00 2.00E+00 4.41E+00 8.22E+00 9.83E+00 positive 1.32E+00 9.36E+00 1.05E+01 positive NA NA NA positive MW-51-135 MW-51-163 Q3-2011 7/28/2011 10:18 1.20E+02 3.18E+02 3.54E+02 1.00E+03

-7.15E-01 1.26E+00 1.96E+00 2.00E+00 6.34E-01 7.71E+00 8.41E+00 positive 3.60E+00 9.69E+00 1.17E+01 positive NA NA NA positive MW-51-163 MW-51-189 Q3-2011 7/28/2011 10:42

-5.69E+00 3.03E+02 3.53E+02 1.00E+03 3.69E-02 1.66E+00 1.95E+00 2.00E+00 2.36E+00 1.07E+01 1.02E+01 positive 2.52E+00 1.01E+01 1.17E+01 positive NA NA NA positive MW-51-189 MW-53-82 Q3-2011 8/1/2011 11:11 7.16E+02 3.84E+02 3.71E+02 3.83E+03

-5.52E-01 7.86E-01 1.06E+00 4.46E+00

-2.46E+00 7.38E+00 7.34E+00 positive

-3.40E-01 8.49E+00 9.05E+00 positive 8.23E+00 1.80E+01 1.98E+01 positive MW-53-82 MW-53-120 Q3-2011 8/1/2011 10:00 4.44E+03 6.15E+02 3.71E+02 1.05E+04 3.30E+01 5.22E+00 1.94E+00 6.60E+01

-2.07E+00 8.49E+00 8.67E+00 positive

-5.10E-01 9.36E+00 1.01E+01 positive 1.45E+01 1.02E+01 1.07E+01 positive MW-53-120 MW-54-37 Q3-2011 8/15/2011 9:25 3.13E+04 1.75E+03 1.98E+02 2.71E+03 2.75E-01 1.60E+00 1.88E+00 9.20E+00 5.03E-01 6.69E+00 7.58E+00 positive 3.36E+00 7.56E+00 9.28E+00 positive

-1.05E+01 1.66E+01 1.96E+01 positive MW-54-37 MW-54-58 Q3-2011 8/15/2011 9:47 4.23E+03 6.63E+02 2.02E+02 1.48E+03

-1.92E-01 9.75E-01 1.31E+00 3.43E+00

-1.08E+00 8.61E+00 8.19E+00 positive

-8.43E-01 9.45E+00 1.01E+01 positive 2.37E+00 1.84E+01 2.07E+01 positive MW-54-58 MW-54-123 Q3-2011 8/15/2011 9:55 1.21E+03 3.75E+02 2.00E+02 1.30E+03 3.74E+00 2.03E+00 1.78E+00 8.14E+00 5.50E-01 8.46E+00 9.31E+00 positive

-5.09E-01 8.88E+00 9.49E+00 positive

-3.43E+00 1.94E+01 2.22E+01 positive MW-54-123 MW-54-144 Q3-2011 8/15/2011 11:44 5.27E+03 7.23E+02 1.96E+02 2.64E+03 1.10E+01 2.75E+00 1.62E+00 2.53E+01 4.07E+00 9.39E+00 1.10E+01 positive 4.25E-01 9.81E+00 1.08E+01 positive

-5.13E+00 1.89E+01 2.18E+01 positive MW-54-144 MW-54-173 Q3-2011 8/15/2011 11:50 1.50E+03 4.08E+02 1.97E+02 3.63E+03 4.32E+00 1.94E+00 1.48E+00 1.22E+01

-1.36E+00 1.01E+01 1.05E+01 positive

-7.70E-01 1.21E+01 1.33E+01 positive

-7.41E+00 2.05E+01 2.42E+01 positive MW-54-173 MW-54-190 Q3-2011 8/15/2011 12:00 3.31E+03 5.88E+02 2.00E+02 3.49E+03 1.89E+01 3.39E+00 1.22E+00 4.03E+01

-3.96E+00 8.61E+00 7.57E+00 positive

-4.68E+00 8.73E+00 8.11E+00 positive

-5.67E+00 1.96E+01 2.30E+01 positive MW-54-190 MW-55-24 Q3-2011 8/12/2011 12:12 1.71E+03 4.35E+02 2.01E+02 2.58E+03 1.29E+01 3.21E+00 1.59E+00 2.97E+01

-4.41E+00 7.32E+00 6.86E+00 positive 5.14E-01 7.95E+00 8.82E+00 positive 6.75E+00 2.09E+01 2.34E+01 positive MW-55-24 MW-55-35 Q3-2011 8/12/2011 12:15 2.94E+03 5.58E+02 2.01E+02 4.38E+03 1.63E+01 3.18E+00 1.50E+00 4.26E+01 4.22E-01 7.50E+00 8.42E+00 positive

-1.40E+00 8.31E+00 8.83E+00 positive

-1.22E+01 2.17E+01 2.60E+01 positive MW-55-35 MW-55-54 Q3-2011 8/12/2011 12:09 8.53E+03 9.24E+02 2.00E+02 1.28E+04 2.20E+01 3.36E+00 1.17E+00 3.93E+01 7.03E+00 8.73E+00 1.08E+01 positive

-2.52E+00 8.07E+00 7.92E+00 positive

-2.57E+00 1.96E+01 2.27E+01 positive MW-55-54 MW-56-53 Q3-2011 Mid 8/26/2011 11:06 2.47E+02 3.96E+02 4.32E+02 1.19E+03

-6.50E-01 7.17E-01 1.13E+00 2.00E+00 1.31E+00 8.97E+00 1.00E+01 positive 2.45E+00 7.50E+00 9.03E+00 positive NA NA NA positive MW-56-53 MW-56-83 Q3-2011 Mid 8/26/2011 10:56 1.05E+05 3.12E+03 4.42E+02 6.39E+03 3.12E+00 1.61E+00 1.37E+00 3.98E+00

-2.12E+00 8.13E+00 8.21E+00 positive

-6.41E-01 8.67E+00 9.15E+00 positive NA NA NA positive MW-56-83 MW-57-11 Q3-2011 Mid 8/19/2011 9:49 7.27E+03 8.58E+02 2.02E+02 8.44E+03 2.08E+01 3.21E+00 1.24E+00 4.92E+01 4.49E+00 7.50E+00 9.07E+00 positive 2.31E+00 7.74E+00 9.17E+00 positive 4.92E-01 2.06E+01 2.36E+01 positive MW-57-11 MW-57-20 Q3-2011 Mid 8/19/2011 9:54 2.47E+04 1.55E+03 1.98E+02 3.04E+03 1.90E+00 1.68E+00 1.56E+00 2.24E+00

-2.01E+00 7.35E+00 7.66E+00 positive 1.68E+00 8.07E+00 9.48E+00 positive 3.14E+00 1.98E+01 2.25E+01 positive MW-57-20 MW-57-45 Q3-2011 Mid 8/19/2011 10:19 2.46E+04 1.56E+03 2.02E+02 2.38E+03 4.31E-01 1.01E+00 1.15E+00 2.60E+00

-5.69E+00 1.03E+01 1.04E+01 positive 2.03E+00 8.04E+00 9.53E+00 positive 2.27E+00 2.09E+01 2.38E+01 positive MW-57-45 MW-58-26 Q3-2011 Mid 8/26/2011 14:47 2.47E+03 5.10E+02 1.99E+02 1.00E+03

-6.17E-02 7.95E-01 1.05E+00 2.00E+00 2.39E-01 7.65E+00 8.47E+00 positive 3.25E-01 8.22E+00 9.22E+00 positive NA NA NA positive MW-58-26 MW-58-65****

Q3-2011 Mid 8/26/2011 14:04 1.10E+03 4.62E+02 2.61E+02 1.00E+03 6.31E-01****

1.82E+00 1.60E+00 2.00E+00

-1.06E+00 9.00E+00 9.65E+00 positive

-1.54E+00 1.01E+01 1.04E+01 positive NA NA NA positive MW-58-65****

MW-59-32 Q3-2011 Mid 8/24/2011 14:22 4.74E+02 2.72E+02 2.17E+02 7.95E-01 1.13E+00 1.20E+00

-2.52E+00 1.05E+01 1.13E+01 2.65E+00 8.25E+00 9.93E+00

-6.65E+00 2.16E+01 2.54E+01 MW-59-32 MW-59-45 Q3-2011 Mid 8/24/2011 14:32 1.24E+03 4.92E+02 2.64E+02 1.13E-01 1.11E+00 1.33E+00

-1.32E+00 8.37E+00 8.81E+00 4.22E+00 9.42E+00 1.18E+01 1.31E+00 1.07E+01 1.20E+01 MW-59-45 MW-59-68 Q3-2011 Mid 8/24/2011 14:09 2.61E+02 2.83E+02 2.66E+02

-5.46E-01 7.35E-01 1.14E+00

-5.62E+00 8.52E+00 7.69E+00 1.56E+00 9.03E+00 1.03E+01 4.94E+00 1.28E+01 1.42E+01 MW-59-68 MW-60-35 Q3-2011 8/10/2011 10:54 4.99E+02 2.69E+02 2.00E+02 2.00E+03

-5.84E-01 7.74E-01 1.17E+00 2.00E+00 2.11E+00 6.96E+00 8.28E+00 positive

-1.04E+00 1.03E+01 1.10E+01 positive NA NA NA positive MW-60-35 MW-60-53 Q3-2011 8/10/2011 11:45 5.16E+02 2.70E+02 1.99E+02 2.00E+03 1.18E+00 1.39E+00 1.45E+00 2.00E+00 5.77E-01 1.34E+01 8.78E+00 positive

-5.16E-01 1.07E+01 1.15E+01 positive NA NA NA positive MW-60-53 MW-60-72 Q3-2011 8/10/2011 13:25 2.91E+02 2.23E+02 1.95E+02 2.00E+03 1.22E-01 9.33E-01 1.14E+00 2.00E+00

-4.08E+00 9.63E+00 1.00E+01 positive 4.20E+00 8.40E+00 1.06E+01 positive NA NA NA positive MW-60-72 MW-60-135 Q3-2011 8/10/2011 13:51 4.00E+02 2.46E+02 1.96E+02 2.00E+03

-2.08E-01 9.78E-01 1.25E+00 2.00E+00

-7.37E+00 9.39E+00 8.24E+00 positive

-6.27E+00 1.07E+01 9.07E+00 positive NA NA NA positive MW-60-135 MW-60-154 Q3-2011 8/10/2011 13:22 5.89E+02 2.81E+02 1.97E+02 2.00E+03

-5.08E-02 1.13E+00 1.40E+00 2.00E+00

-1.03E+00 8.01E+00 8.47E+00 positive 2.98E+00 9.03E+00 1.07E+01 positive NA NA NA positive MW-60-154 MW-60-176 Q3-2011 8/10/2011 14:12 9.72E+02 3.42E+02 2.00E+02 2.00E+03

-1.79E-01 9.21E-01 1.22E+00 2.00E+00

-3.87E+00 7.74E+00 7.27E+00 positive

-1.71E-01 8.91E+00 9.60E+00 positive NA NA NA positive MW-60-176 MW-62-18 Q3-2011 8/3/2011 10:18 4.04E+02 3.39E+02 3.53E+02 2.00E+03 2.03E-01 1.37E+00 1.74E+00 2.00E+00

-1.12E+00 8.70E+00 9.13E+00 positive 4.76E+00 9.81E+00 1.21E+01 positive NA NA NA positive MW-62-18 MW-62-37 Q3-2011 8/3/2011 10:35 3.09E+02 3.33E+02 3.52E+02 2.00E+03 1.23E+00 1.81E+00 1.96E+00 2.00E+00 3.02E+00 6.69E+00 8.03E+00 positive 2.71E+00 8.55E+00 1.01E+01 positive NA NA NA positive MW-62-37 Well ID1 SAMPLE ID SAMPLE COLLECTION ANALYSIS RESULTS4,5 Well ID TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

TABLE 4 2011 3rd QUARTER GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERTY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q32011 FINAL Table 4 - 2011 3rd Quarter Groundwater Analytical Results.xlsx; Q32011 Table 4 Page 2 of 2 See Page 2 for Notes Date Time Result Std. Dev.6 MDC I.L.3,7 Result Std. Dev.6 MDC I.L.3 Result Std. Dev.6 MDC I.L.3 Result Std. Dev.6 MDC I.L.3 Result Std. Dev.6 MDC I.L.3 Well ID1 SAMPLE ID SAMPLE COLLECTION ANALYSIS RESULTS4,5 Well ID TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

MW-62-53 Q3-2011 8/3/2011 12:44 4.12E+02 3.42E+02 3.00E+02 2.00E+03 1.52E-01 1.46E+00 1.75E+00 2.00E+00 2.87E+00 7.59E+00 9.04E+00 positive 3.15E+00 8.76E+00 1.06E+01 positive NA NA NA positive MW-62-53 MW-62-71 Q3-2011 8/3/2011 11:58 5.14E+02 3.69E+02 3.07E+02 2.00E+03 3.49E-01 1.39E+00 1.65E+00 2.00E+00

-7.31E-01 1.01E+01 1.10E+01 positive 2.51E+00 1.04E+01 1.20E+01 positive NA NA NA positive MW-62-71 MW-62-92 Q3-2011 8/3/2011 12:10 5.61E+02 3.78E+02 3.03E+02 2.00E+03

-3.26E-01 1.09E+00 1.52E+00 2.00E+00 3.82E+00 1.46E+01 9.22E+00 positive

-5.05E+00 1.17E+01 1.15E+01 positive NA NA NA positive MW-62-92 MW-62-138 Q3-2011 8/3/2011 10:08 1.42E+03 5.46E+02 3.34E+02 2.00E+03 1.53E+00 1.69E+00 1.73E+00 2.42E+00 2.51E-01 9.48E+00 1.05E+01 positive 1.35E+00 8.40E+00 9.73E+00 positive NA NA NA positive MW-62-138 MW-62-182 Q3-2011 8/3/2011 10:20 5.84E+02 3.84E+02 3.05E+02 2.00E+03 2.04E-01 1.47E+00 1.75E+00 2.00E+00

-5.99E+00 1.25E+01 1.14E+01 positive

-2.96E-01 1.13E+01 1.24E+01 positive NA NA NA positive MW-62-182 MW-63-18 Q3-2011 8/3/2011 10:02 2.90E+02 3.15E+02 3.03E+02 2.00E+03

-1.29E-01 1.20E+00 1.57E+00 2.00E+00 1.70E+00 6.87E+00 7.90E+00 positive 3.80E+00 8.58E+00 1.05E+01 positive NA NA NA positive MW-63-18 MW-63-34 Q3-2011 8/3/2011 10:14 3.61E+02 3.30E+02 3.02E+02 2.00E+03 1.90E-01 1.37E+00 1.66E+00 2.00E+00 8.99E+00 9.09E+00 1.15E+01 positive

-7.29E-01 8.16E+00 8.53E+00 positive NA NA NA positive MW-63-34 MW-63-50 Q3-2011 8/3/2011 11:38 3.50E+02 3.33E+02 3.09E+02 2.00E+03

-8.45E-01 1.10E+00 1.60E+00 2.00E+00 8.12E+00 1.18E+01 1.44E+01 positive 4.49E+00 8.52E+00 1.14E+01 positive NA NA NA positive MW-63-50 MW-63-93 Q3-2011 8/3/2011 11:50 1.84E+02 3.12E+02 3.38E+02 2.00E+03 4.25E-02 1.31E+00 1.63E+00 2.00E+00 1.61E+00 7.26E+00 7.83E+00 positive

-2.65E+00 7.71E+00 8.38E+00 positive NA NA NA positive MW-63-93 MW-63-112 Q3-2011 8/3/2011 12:01 8.82E+02 4.59E+02 3.36E+02 2.00E+03

-1.83E-01 1.31E+00 1.67E+00 2.00E+00 2.07E+00 7.35E+00 8.45E+00 positive

-2.13E+00 7.26E+00 7.10E+00 positive NA NA NA positive MW-63-112 MW-63-121 Q3-2011 8/3/2011 10:03 1.92E+03 6.09E+02 3.29E+02 2.00E+03 9.09E-01 1.49E+00 1.62E+00 2.00E+00

-6.79E+00 9.27E+00 9.08E+00 positive 6.01E+00 8.16E+00 1.09E+01 positive NA NA NA positive MW-63-121 MW-63-163 Q3-2011 8/3/2011 10:06 4.41E+02 3.54E+02 3.08E+02 2.00E+03 7.99E-02 1.35E+00 1.69E+00 2.00E+00 5.51E-01 8.40E+00 9.33E+00 positive 2.23E+00 1.03E+01 1.20E+01 positive NA NA NA positive MW-63-163 MW-63-174 Q3-2011 8/3/2011 10:18 6.09E+02 3.93E+02 3.09E+02 2.00E+03 6.96E-01 1.49E+00 1.68E+00 2.00E+00

-4.15E+00 9.15E+00 8.88E+00 positive 4.51E+00 8.19E+00 1.05E+01 positive NA NA NA positive MW-63-174 MW-66-21 Q3-2011 8/8/2011 10:55 7.84E+02 3.90E+02 3.73E+02 1.33E+03 8.00E-01 1.44E+00 1.59E+00 2.07E+00

-2.25E+00 8.16E+00 8.11E+00 positive 3.27E-01 7.05E+00 7.73E+00 positive 6.75E+00 9.00E+00 9.81E+00 positive MW-66-21 MW-66-36 Q3-2011 8/8/2011 10:49 3.90E+03 5.91E+02 3.74E+02 7.71E+03 8.00E+00 2.60E+00 1.61E+00 1.40E+01

-3.94E+00 1.11E+01 1.07E+01 positive 1.48E+00 1.26E+01 1.46E+01 positive 2.82E+00 1.53E+01 1.71E+01 positive MW-66-36 MW-67-39 Q3-2011 8/8/2011 12:26 3.62E+03 5.76E+02 3.73E+02 6.52E+03 5.31E+00 2.39E+00 1.98E+00 1.81E+01

-3.01E+00 8.34E+00 8.17E+00 positive

-7.13E+00 8.22E+00 7.50E+00 positive 5.90E+00 1.71E+01 1.90E+01 positive MW-67-39 MW-67-105 Q3-2011 8/8/2011 12:48 1.42E+03 4.38E+02 3.74E+02 3.92E+03 7.40E-01 1.71E+00 1.92E+00 4.38E+00

-4.93E-01 7.77E+00 8.36E+00 positive

-6.18E+00 8.67E+00 7.26E+00 positive 6.67E+00 1.25E+01 1.38E+01 positive MW-67-105 MW-67-173 Q3-2011 8/8/2011 12:53 6.13E+02 3.75E+02 3.72E+02 1.61E+03

-3.44E-01 1.55E+00 1.94E+00 2.00E+00

-1.95E+00 8.79E+00 9.16E+00 positive 1.25E+00 8.70E+00 9.80E+00 positive 4.91E+00 1.20E+01 1.33E+01 positive MW-67-173 MW-67-219 Q3-2011 8/8/2011 10:33 1.11E+03 4.17E+02 3.73E+02 2.26E+03 3.18E-02 1.61E+00 1.90E+00 2.00E+00 8.34E-01 7.41E+00 8.13E+00 positive

-6.37E+00 9.30E+00 8.11E+00 positive 1.06E+01 1.64E+01 1.79E+01 positive MW-67-219 MW-67-276 Q3-2011 8/8/2011 10:45 8.99E+02 3.90E+02 3.63E+02 2.01E+03

-3.98E-01 1.38E+00 1.82E+00 2.00E+00

-3.35E-01 8.67E+00 9.58E+00 positive 1.65E+00 9.24E+00 1.07E+01 positive 1.22E+01 1.91E+01 2.10E+01 positive MW-67-276 MW-67-323 Q3-2011 8/8/2011 10:53 3.09E+02 3.51E+02 3.73E+02 1.00E+03 1.75E+00 1.85E+00 1.91E+00 2.00E+00

-6.64E-01 6.66E+00 7.23E+00 positive 4.13E+00 8.82E+00 1.09E+01 positive

-9.62E+00 2.15E+01 2.43E+01 positive MW-67-323 MW-67-340 Q3-2011 8/8/2011 10:43 4.19E+02 3.60E+02 3.72E+02 1.01E+03

-5.52E-01 1.49E+00 1.89E+00 2.00E+00

-9.17E-01 7.92E+00 8.61E+00 positive

-4.93E+00 1.06E+01 1.00E+01 positive 6.17E+00 1.84E+01 2.05E+01 positive MW-67-340 MW-108 Q3-2011 Mid 8/29/2011 11:25 1.78E+03 5.73E+02 2.62E+02

-7.81E-01 7.89E-01 1.24E+00

-1.86E-01 1.19E+01 1.21E+01

-4.10E+00 1.13E+01 1.10E+01 2.65E+00 1.16E+01 1.30E+01 MW-108 MW-109 Q3-2011 Mid 8/26/2011 13:49 3.26E+03 7.50E+02 2.59E+02 5.48E-01 1.01E+00 1.12E+00 2.37E+00 7.65E+00 8.94E+00 3.72E+00 9.60E+00 1.17E+01

-8.72E-01 8.73E+00 1.00E+01 MW-109 U3-3 Q3-2011 Mid 8/29/2011 13:09 1.03E+03 4.56E+02 2.66E+02

-5.04E-01 6.63E-01 1.06E+00

-2.50E+00 8.55E+00 7.82E+00

-3.69E+00 7.74E+00 7.12E+00 NA NA NA U3-3 U3-4D Q3-2011 7/29/2011 11:05 6.73E+02 4.02E+02 3.04E+02 1.00E+03 1.23E-01 1.58E+00 1.90E+00 2.00E+00 5.66E+00 8.43E+00 1.05E+01 positive

-2.58E+00 9.30E+00 9.06E+00 positive NA NA NA positive U3-4D U3-4S Q3-2011 7/29/2011 10:06 4.67E+02 3.84E+02 3.43E+02 1.00E+03***

2.84E-01 1.64E+00 1.90E+00 2.00E+00 9.19E+00 1.58E+01 9.23E+00 positive 7.83E-01 1.02E+01 1.17E+01 positive NA NA NA positive U3-4S U3-T1 Q3-2011 8/22/2011 14:40 1.00E+03 3.42E+02 1.95E+02 1.00E+03

-6.26E-02 1.10E+00 1.37E+00 2.00E+00

-4.61E-01 8.70E+00 8.45E+00 positive

-2.62E+00 8.31E+00 8.23E+00 positive NA NA NA positive U3-T1 U3-T2 Q3-2011 7/29/2011 12:32 2.65E+03 7.02E+02 3.34E+02 2.08E+03 1.05E+00 1.81E+00 1.99E+00 2.00E+00

-5.43E-01 8.49E+00 9.21E+00 positive 2.63E+00 8.91E+00 1.07E+01 positive NA NA NA positive U3-T2 U1-NCD Q3-2011 9/15/2011 11:45 3.86E+03 6.39E+02 3.99E+02 9.08E+01 7.80E+00 1.54E+00 4.77E+03 6.42E+02 8.81E+00 3.36E+00 4.68E+00 5.97E+00 1.14E+02 2.09E+01 1.82E+01 U1-NCD U1-SFDS Q3-2011 9/15/2011 11:35 2.09E+03 5.25E+02 4.00E+02 7.79E+00 2.54E+00 1.39E+00 9.23E+00 6.72E+00 6.70E+00 1.14E+00 6.27E+00 7.16E+00

-4.97E+00 1.70E+01 1.95E+01 U1-SFDS I-2 Q3-2011 8/12/2011 15:13 2.34E+02 2.15E+02 2.00E+02 1.00E+03***

-5.95E-01 7.44E-01 1.16E+00 2.00E+00 5.11E+00 1.19E+01 1.35E+01 positive

-2.57E-01 9.24E+00 1.02E+01 positive NA NA NA positive I-2 MH-5 VCFD Q3-2011 8/3/2011 14:12 3.90E+03 8.31E+02 3.31E+02

-4.45E-01 1.07E+00 1.50E+00

-6.18E-01 1.01E+01 1.10E+01

-6.71E+00 1.43E+01 1.29E+01 NA NA NA MH-5 VCFD MH-5 VCFD Q3-2011 8/11/2011 12:39 2.74E+04 1.65E+03 2.02E+02 6.43E-01 1.19E+00 1.32E+00

-2.20E+00 7.47E+00 7.63E+00 1.85E+00 5.85E+00 7.32E+00 NA NA NA MH-5 VCFD MH-5 VCFD Q3-2011 8/18/2011 9:50 2.09E+04 1.87E+03 2.64E+02 9.64E-01 1.55E+00 1.70E+00 1.90E+00 7.98E+00 9.05E+00

-3.10E+00 9.60E+00 9.54E+00 NA NA NA MH-5 VCFD MH-5 VCFD Q3-2011 Mid 8/24/2011 11:01 1.40E+04 1.51E+03 2.58E+02 5.99E-01 1.30E+00 1.46E+00

-2.36E+00 7.86E+00 8.21E+00 3.46E+00 7.98E+00 9.92E+00 NA NA NA MH-5 VCFD MH-5 VCFD Q3-2011 Mid 8/30/2011 13:55 3.37E+04 1.83E+03 2.03E+02 9.19E-01 1.31E+00 1.40E+00 1.76E+00 7.23E+00 8.47E+00

-1.69E+00 7.86E+00 7.79E+00 NA NA NA MH-5 VCFD B-1 Q3-2011 8/17/2011 13:17 7.36E+02 3.03E+02 1.96E+02

-6.00E-02 9.87E-01 1.25E+00 1.51E+01 1.49E+01 7.29E+00

-4.01E-01 7.02E+00 7.34E+00 NA NA NA B-1 B-6 Q3-2011 7/29/2011 10:52 6.45E+02 4.14E+02 3.38E+02

-2.59E-01 1.39E+00 1.79E+00 1.60E+00 7.74E+00 8.72E+00 4.72E+00 5.07E+00 7.82E+00 NA NA NA B-6 Notes

1. For nested multi-level monitoring wells, suffix of well ID indicates depth (rounded to nearest foot) from reference point on casing to bottom of well screen. For Waterloo multi-level systems, suffix indicates depth (rounded to nearest foot) from reference point on casing to top of sampling port.

Well IDs without a suffix are open bedrock wellbores.

2. Sampling depths within sampling intervals (location of pump intake) have been established at location of most transmissive zone to the extent possible.
3. I.L.s (Investigation Levels) are predetermined detection limits assigned to each sampling location which, if reached or exceeded, require further investigation or action. I.L.s presented here for Sr-90, CS-137, Co-60 & Ni-63 are established for 2011 based on 2010 averages. See Note #7 below for further 2011 Tritium I.L. discussion. Positive detections indicate that the the result is greater than MDC and greater than or equal to 3 times the 1 sigma uncertainty.
4. NA indicates that the constituent was not analyzed.
5. Shading indicates that the sample result exceeds the Investigation Level.
6. Column designated as Std. Dev. provides the three times 1 sigma uncertainty values.
7. To be conservative, the 2011 Tritium I.L.s were calculated using (2x the 2009 yearly average) beacuase an increased Tritium activity
7. To be conservative, the 2011 Tritium investigation levels were calculated using (2x the 2009 rolling average) due to an increased Tritium activity in multiple Unit 2 sampling intervals during 2010 in response to the transient surface spill from a temporary rental RWST/R.O. processing skid.
  • Indicates storm or foundation drain sampling locations, for which investigation levels are not applicable.
    • Indicates 2011 I.L.s not computed for this well due to absence of 2008 through 2010 data.
      • 2011 Tritium I.L. calculated based on the 2010 rolling average due to absence of 2009 data.
        • The Post-Q3 2011 MW-58-65 preliminary Sr-90 result was 3.64 pCi/L and exceeded the IL. However, after re-analysis, the sample was below the detection limit which suggests the preliminary result was likely a false positive. A shift in the MDC for the preliminary result could have possibly resulted from contaminated laboratory equipment, modified count time, or changes in sample preparation.

TABLE 4 2011 4th QUARTER GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERTY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q42011 FINAL Table 4 - 2011 4th Quarter Groundwater Analytical Results.xlsx; Q42011 Table 4 Page 1 of 2 See Page 2 for Notes Date Time Result Std. Dev.6 MDC I.L.3,7 Result Std. Dev.6 MDC I.L.3 Result Std. Dev.6 MDC I.L.3 Result Std. Dev.6 MDC I.L.3 Result Std. Dev.6 MDC I.L.3 MW-31-49 Q4-2011 11/21/2011 10:32 1.54E+04 9.78E+02 3.42E+02 4.28E+04

-3.16E-01 1.08E+00 1.45E+00 2.00E+00 0.00E+00 1.14E+01 9.96E+00 positive

-3.55E+00 9.54E+00 1.08E+01 positive NA NA NA positive MW-31-49 MW-31-63 Q4-2011 11/21/2011 11:14 7.23E+03 9.00E+02 2.36E+02 3.99E+04 1.36E+00 1.42E+00 1.40E+00 2.00E+00

-2.72E+00 9.45E+00 1.09E+01 positive 2.93E+00 8.19E+00 1.20E+01 positive NA NA NA positive MW-31-63 MW-31-85 Q4-2011 11/21/2011 11:25 5.49E+03 6.33E+02 3.45E+02 1.46E+04 9.56E-01 1.41E+00 1.50E+00 2.00E+00

-3.23E+00 9.21E+00 1.04E+01 positive

-6.05E-01 9.57E+00 1.22E+01 positive NA NA NA positive MW-31-85 MW-32-59 Q4-2011 11/17/2011 14:15 2.91E+04 1.74E+03 2.26E+02 3.42E+04

-1.28E+00 1.58E+00 2.33E+00 2.00E+00

-3.91E+00 1.01E+01 1.18E+01 positive

-1.58E+00 9.84E+00 1.21E+01 positive NA NA NA positive MW-32-59 MW-32-85 Q4-2011 11/17/2011 15:08 8.88E+03 7.65E+02 3.42E+02 1.63E+04 4.57E-01 1.56E+00 1.82E+00 2.00E+00

-1.20E+00 7.38E+00 8.80E+00 positive

-1.88E+00 9.06E+00 1.09E+01 positive NA NA NA positive MW-32-85 MW-32-149 Q4-2011 11/17/2011 12:05 5.91E+02 3.45E+02 3.41E+02 1.00E+03 3.84E-01 1.46E+00 1.72E+00 2.00E+00

-5.25E+00 7.74E+00 7.86E+00 positive 2.57E+00 8.07E+00 1.12E+01 positive NA NA NA positive MW-32-149 MW-32-173 Q4-2011 11/17/2011 12:01 5.06E+02 3.33E+02 3.34E+02 1.50E+03 7.83E-02 9.63E-01 1.24E+00 2.00E+00 2.87E+00 9.12E+00 1.13E+01 positive

-1.50E-01 9.93E+00 1.26E+01 positive NA NA NA positive MW-32-173 MW-32-190 Q4-2011 11/17/2011 12:03 1.46E+03 4.05E+02 3.36E+02 4.21E+03

-7.57E-01 8.37E-01 1.41E+00 2.00E+00 1.30E+00 6.57E+00 8.59E+00 positive

-4.42E-01 6.24E+00 7.93E+00 positive NA NA NA positive MW-32-190 MW-36-24 Q4-2011 12/7/2011 11:04 0.00E+00 4.20E+02 4.96E+02 2.56E+03

-3.36E-01 1.29E+00 1.70E+00 2.00E+00 1.75E+00 7.26E+00 9.17E+00 positive

-1.38E+00 6.00E+00 7.29E+00 positive NA NA NA positive MW-36-24 MW-36-41 Q4-2011 12/7/2011 13:09 2.63E+03 6.51E+02 4.78E+02 2.10E+04 9.00E-01 1.71E+00 1.89E+00 7.99E+00 1.19E-02 7.17E+00 9.00E+00 positive

-5.23E-01 7.86E+00 1.01E+01 positive NA NA NA positive MW-36-41 MW-36-52 Q4-2011 12/7/2011 11:36 4.76E+03 8.10E+02 4.91E+02 1.48E+04 5.23E+00 1.96E+00 1.24E+00 8.14E+00 2.89E+00 7.74E+00 1.01E+01 positive 5.68E+00 9.03E+00 1.31E+01 positive NA NA NA positive MW-36-52 MW-37-22 Q4-2011 11/23/2011 11:33 4.97E+03 8.28E+02 4.96E+02 9.19E+03 8.02E+00 2.57E+00 1.38E+00 2.20E+01 2.26E+00 9.12E+00 1.19E+01 positive

-1.41E+00 7.35E+00 9.09E+00 positive NA NA NA positive MW-37-22 MW-37-32 Q4-2011 11/23/2011 11:19 4.33E+03 7.80E+02 4.91E+02 9.32E+03 1.26E+01 3.21E+00 1.52E+00 3.54E+01 7.81E+00 9.00E+00 1.28E+01 positive

-6.59E+00 8.76E+00 8.06E+00 positive NA NA NA positive MW-37-32 MW-37-40 Q4-2011 11/23/2011 11:46 5.22E+03 8.28E+02 4.83E+02 9.02E+03 1.50E+01 3.45E+00 1.47E+00 2.84E+01 1.06E+00 1.43E+01 7.71E+00 positive 9.11E-01 7.29E+00 1.00E+01 positive NA NA NA positive MW-37-40 MW-37-57 Q4-2011 11/23/2011 11:22 4.87E+03 8.16E+02 4.91E+02 9.62E+03 1.88E+01 3.90E+00 1.81E+00 3.68E+01

-6.08E-01 8.28E+00 1.01E+01 positive 3.00E+00 9.12E+00 1.27E+01 positive NA NA NA positive MW-37-57 MW-39-67 Q4-2011 12/1/2011 14:04 1.03E+03 5.13E+02 4.75E+02 1.00E+03 2.37E+00 1.90E+00 1.76E+00 3.30E+00

-3.99E+00 9.24E+00 1.02E+01 positive

-3.39E+00 8.07E+00 9.37E+00 positive NA NA NA positive MW-39-67 MW-39-84 Q4-2011 12/1/2011 14:17 1.39E+02 4.32E+02 4.88E+02 1.00E+03 3.12E+00 2.08E+00 1.81E+00 2.10E+00

-1.59E+00 6.48E+00 7.42E+00 positive

-1.71E+00 8.82E+00 1.05E+01 positive NA NA NA positive MW-39-84 MW-39-102 Q4-2011 12/1/2011 14:10 1.12E+03 5.25E+02 4.77E+02 1.00E+03 2.77E+00 2.06E+00 1.95E+00 8.10E+00 1.42E+00 7.68E+00 9.90E+00 positive

-2.95E+00 6.99E+00 7.97E+00 positive NA NA NA positive MW-39-102 MW-39-124 Q4-2011 12/1/2011 11:42 1.73E+02 4.35E+02 4.89E+02 1.00E+03

-2.58E-01 1.41E+00 1.82E+00 4.50E+00 5.73E-01 7.95E+00 9.19E+00 positive 2.71E+00 7.89E+00 9.85E+00 positive NA NA NA positive MW-39-124 MW-39-183 Q4-2011 12/1/2011 11:26

-8.23E+01 4.11E+02 4.97E+02 1.00E+03 1.34E-01 1.45E+00 1.80E+00 2.00E+00

-2.81E+00 1.34E+01 1.59E+01 positive 4.19E+00 8.16E+00 1.46E+01 positive NA NA NA positive MW-39-183 MW-39-195 Q4-2011 12/1/2011 11:28 5.13E+03 8.28E+02 4.87E+02 1.00E+03 3.00E-01 1.46E+00 1.75E+00 2.00E+00 2.12E+00 7.98E+00 1.03E+01 positive 5.51E-01 9.48E+00 1.22E+01 positive NA NA NA positive MW-39-195 MW-40-27 Q4-2011 12/9/2011 11:50 2.24E+01 4.20E+02 4.90E+02 1.00E+03 1.74E-01 1.46E+00 1.77E+00 2.00E+00 7.86E-01 7.02E+00 8.97E+00 positive 3.19E+00 7.14E+00 1.03E+01 positive NA NA NA positive MW-40-27 MW-40-46 Q4-2011 12/9/2011 12:03 9.00E+01 4.17E+02 4.77E+02 1.00E+03 2.87E-01 1.62E+00 1.92E+00 2.00E+00 1.26E+00 7.41E+00 9.46E+00 positive

-9.20E-01 6.39E+00 8.16E+00 positive NA NA NA positive MW-40-46 MW-40-81 Q4-2011 12/9/2011 10:23

-8.05E+01 4.02E+02 4.86E+02 1.00E+03 3.77E-01 1.51E+00 1.79E+00 2.00E+00 4.60E-01 2.64E+01 1.18E+01 positive 1.07E+00 1.07E+01 1.39E+01 positive NA NA NA positive MW-40-81 MW-40-100 Q4-2011 12/9/2011 10:28 4.85E+01 4.29E+02 5.00E+02 1.00E+03 1.04E+00 1.37E+00 1.41E+00 2.00E+00 1.85E+00 7.98E+00 9.93E+00 positive 8.66E-01 7.77E+00 1.01E+01 positive NA NA NA positive MW-40-100 MW-40-127 Q4-2011 12/9/2011 10:40 5.65E+01 4.08E+02 4.71E+02 1.00E+03 1.27E+00 1.50E+00 1.51E+00 2.00E+00

-1.26E+00 8.91E+00 1.04E+01 positive

-3.35E+00 9.18E+00 1.04E+01 positive NA NA NA positive MW-40-127 MW-40-162 Q4-2011 12/9/2011 11:02

-2.60E+01 3.42E+02 4.06E+02 1.00E+03 6.89E-01 1.75E+00 1.95E+00 2.00E+00 1.06E+00 8.43E+00 1.07E+01 positive

-4.71E+00 1.17E+01 1.30E+01 positive NA NA NA positive MW-40-162 MW-41-40 Q4-2011 11/28/2011 14:25 6.16E+02 5.13E+02 5.14E+02 1.00E+03 6.83E-01 1.73E+00 1.95E+00 7.28E+00 6.21E+00 8.16E+00 1.13E+01 positive

-4.82E+00 9.81E+00 1.11E+01 positive NA NA NA positive MW-41-40 MW-41-63 Q4-2011 11/28/2011 14:08 6.41E+02 5.22E+02 5.22E+02 1.00E+03 6.76E-01 1.73E+00 1.95E+00 7.36E+00

-7.79E-01 7.20E+00 8.56E+00 positive

-9.03E-01 7.41E+00 9.17E+00 positive NA NA NA positive MW-41-63 MW-42-49 Q4-2011 11/3/2011 11:13 1.40E+03 5.70E+02 5.00E+02 3.16E+04 8.98E-01 1.51E+00 1.65E+00 9.00E+01 3.03E+03 3.90E+02 1.29E+01 6.58E+04

-1.75E+00 7.56E+00 9.18E+00 positive 5.77E+01 1.57E+01 1.45E+01 6.74E+02 MW-42-49 MW-42-78 Q4-2011 11/3/2011 11:31 3.23E+02 4.65E+02 5.02E+02 1.00E+03

-5.46E-02 1.15E+00 1.49E+00 2.00E+00

-2.93E+00 7.32E+00 8.03E+00 positive 1.37E-01 7.74E+00 9.98E+00 positive

-2.26E+00 1.18E+01 1.35E+01 positive MW-42-78 MW-43-28 Q4-2011 11/22/2011 11:23 1.21E+02 3.60E+02 4.05E+02 1.00E+03 1.40E+00 1.81E+00 1.95E+00 2.00E+00

-9.87E-02 5.58E+00 7.14E+00 positive

-3.96E+00 8.07E+00 8.55E+00 positive NA NA NA positive MW-43-28 MW-43-62 Q4-2011 11/22/2011 12:22 2.01E+02 3.72E+02 4.10E+02 1.00E+03 9.55E-01 1.78E+00 1.96E+00 2.00E+00

-1.43E+01 1.42E+01 1.67E+01 positive 1.94E+00 1.06E+01 1.41E+01 positive NA NA NA positive MW-43-62 MW-44-66 Q4-2011 12/8/2011 12:00 3.70E+02 3.84E+02 4.04E+02 1.00E+03

-8.25E-01 1.44E+00 1.94E+00 2.00E+00 1.99E+00 7.35E+00 9.30E+00 positive 2.32E+00 7.56E+00 1.04E+01 positive NA NA NA positive MW-44-66 MW-44-102 Q4-2011 12/1/2011 12:18 1.05E+03 4.50E+02 4.07E+02 1.00E+03

-2.13E-01 1.52E+00 1.93E+00 2.00E+00

-7.91E-02 8.73E+00 1.04E+01 positive

-5.88E-01 9.33E+00 1.15E+01 positive NA NA NA positive MW-44-102 MW-45-42 Q4-2011 11/28/2011 15:03 1.65E+03 6.27E+02 5.10E+02 5.90E+03 8.10E-01 1.75E+00 1.95E+00 2.00E+00 1.21E+00 5.94E+00 7.69E+00 positive

-2.64E+00 6.96E+00 7.84E+00 positive NA NA NA positive MW-45-42 MW-45-61 Q4-2011 11/28/2011 11:44 2.06E+03 6.72E+02 5.16E+02 2.65E+03 4.76E-01 1.70E+00 1.97E+00 2.00E+00 3.28E-01 7.41E+00 9.39E+00 positive

-6.01E-01 9.42E+00 1.19E+01 positive NA NA NA positive MW-45-61 MW-46 Q4-2011 10/20/2011 13:35 2.28E+03 4.68E+02 3.46E+02 1.84E+03 3.95E-01 1.30E+00 1.52E+00 2.00E+00

-4.36E+00 8.19E+00 8.94E+00 positive

-1.03E+00 8.07E+00 1.01E+01 positive NA NA NA positive MW-46 MW-47-56 Q4-2011 10/28/2011 11:36 5.31E+03 8.52E+02 4.99E+02

-6.21E-01 8.79E-01 1.40E+00 1.34E+00 8.85E+00 1.07E+01 2.06E-01 1.01E+01 1.29E+01

-6.21E+00 1.24E+01 1.44E+01 MW-47-56 MW-47-80 Q4-2011 10/28/2011 13:24 9.68E+04 3.21E+03 5.07E+02 2.13E+00 1.58E+00 1.38E+00

-1.35E+00 6.54E+00 7.91E+00 1.21E+00 6.45E+00 8.88E+00 3.54E+00 1.31E+01 1.46E+01 MW-47-80 MW-49-26 Q4-2011 11/4/2011 11:50 4.92E+03 8.37E+02 5.06E+02 6.52E+03 1.27E+01 2.95E+00 1.25E+00 2.79E+01 2.60E+00 1.11E+01 7.92E+00 positive 5.17E+00 8.04E+00 1.17E+01 positive

-2.73E+00 1.26E+01 1.44E+01 positive MW-49-26 MW-49-42 Q4-2011 11/4/2011 11:43 4.91E+03 8.19E+02 4.90E+02 4.97E+03 2.11E+01 3.90E+00 1.51E+00 3.72E+01 5.99E-01 1.87E+01 1.10E+01 positive

-3.91E+00 1.04E+01 1.20E+01 positive 4.27E+00 1.30E+01 1.45E+01 positive MW-49-42 MW-49-65 Q4-2011 11/4/2011 11:47 4.24E+03 7.23E+02 4.64E+02 3.03E+03 2.02E+01 3.60E+00 1.47E+00 2.62E+01

-4.27E+00 8.88E+00 9.11E+00 positive

-6.56E-01 9.45E+00 1.15E+01 positive 7.03E-01 1.21E+01 1.36E+01 positive MW-49-65 MW-50-42 Q4-2011 10/27/2011 10:48 9.99E+02 5.25E+02 4.92E+02 1.04E+03 3.02E+01 4.44E+00 1.54E+00 1.10E+01 1.76E+00 7.11E+00 9.22E+00 positive

-2.60E+00 8.01E+00 9.51E+00 positive

-5.76E+00 1.21E+01 1.41E+01 positive MW-50-42 MW-50-66 Q4-2011 10/27/2011 10:53 7.83E+03 9.87E+02 4.94E+02 5.90E+03 2.66E+01 4.35E+00 1.59E+00 5.24E+01

-6.49E-01 8.64E+00 1.02E+01 positive 1.01E+01 1.01E+01 1.49E+01 positive

-4.90E+00 1.66E+01 1.92E+01 positive MW-50-66 MW-51-40 Q4-2011 12/12/2011 10:43 1.86E+02 3.06E+02 3.28E+02 1.00E+03

-7.34E-01 1.58E+00 1.94E+00 2.00E+00

-5.53E+00 8.49E+00 9.48E+00 positive 4.82E+00 7.89E+00 1.18E+01 positive

-3.48E+00 1.39E+01 1.58E+01 positive MW-51-40 MW-51-79 Q4-2011 12/12/2011 11:09 1.50E+02 2.95E+02 3.29E+02 1.00E+03

-1.38E-01 1.52E+00 1.90E+00 2.00E+00

-3.25E+00 7.98E+00 8.95E+00 positive

-3.01E-01 7.62E+00 9.88E+00 positive

-1.12E+00 1.13E+01 1.27E+01 positive MW-51-79 MW-51-104 Q4-2011 12/12/2011 12:12 1.48E+02 2.91E+02 3.24E+02 1.00E+03 1.23E+00 1.76E+00 1.85E+00 2.00E+00

-3.81E+00 9.12E+00 1.01E+01 positive 9.25E+00 9.60E+00 1.43E+01 positive

-3.91E+00 1.33E+01 1.51E+01 positive MW-51-104 MW-51-135 Q4-2011 12/12/2011 12:50 1.32E+02 2.93E+02 3.33E+02 1.00E+03 2.67E-01 1.64E+00 1.94E+00 2.00E+00 6.83E+00 9.42E+00 1.28E+01 positive

-3.73E+00 8.40E+00 9.41E+00 positive

-6.68E+00 1.18E+01 1.35E+01 positive MW-51-135 MW-51-163 Q4-2011 12/12/2011 12:26 1.71E+02 3.03E+02 3.32E+02 1.00E+03 1.58E+00 1.81E+00 1.94E+00 2.00E+00 2.25E+00 8.94E+00 1.16E+01 positive

-8.50E-01 8.52E+00 1.08E+01 positive

-3.59E+00 1.22E+01 1.38E+01 positive MW-51-163 MW-51-189 Q4-2011 12/12/2011 12:23

-5.57E+01 2.30E+02 3.29E+02 1.00E+03

-3.94E-01 1.43E+00 1.91E+00 2.00E+00

-4.49E+00 8.10E+00 8.53E+00 positive 1.93E+00 8.34E+00 1.13E+01 positive

-9.34E+00 1.94E+01 2.22E+01 positive MW-51-189 MW-53-82 Q4-2011 11/2/2011 11:26 2.27E+02 4.50E+02 5.00E+02 3.83E+03

-2.42E-01 1.09E+00 1.49E+00 4.46E+00

-1.19E+00 6.78E+00 7.87E+00 positive

-6.95E-01 8.73E+00 1.07E+01 positive

-4.95E-01 1.24E+01 1.41E+01 positive MW-53-82 MW-53-120 Q4-2011 11/2/2011 11:56 8.02E+03 9.27E+02 4.67E+02 1.05E+04 4.05E+01 5.16E+00 1.52E+00 6.60E+01 4.60E+00 8.52E+00 1.15E+01 positive

-1.89E-01 7.89E+00 1.03E+01 positive 2.58E+00 1.93E+01 2.17E+01 positive MW-53-120 MW-54-37 Q4-2011 12/6/2011 10:37 1.40E+04 1.02E+03 3.73E+02 2.71E+03 4.48E+00 2.07E+00 1.92E+00 9.20E+00

-6.26E+00 9.72E+00 1.03E+01 positive 4.84E-01 8.94E+00 1.14E+01 positive

-5.68E+00 1.25E+01 1.43E+01 positive MW-54-37 MW-54-58 Q4-2011 12/6/2011 10:23 4.83E+03 6.48E+02 3.70E+02 1.48E+03 1.60E+00 1.80E+00 1.91E+00 3.43E+00 9.45E-01 4.23E+00 5.14E+00 positive 1.72E+00 4.56E+00 5.85E+00 positive 2.66E+00 1.25E+01 1.40E+01 positive MW-54-58 MW-54-123 Q4-2011 12/6/2011 10:37 3.92E+03 6.00E+02 3.71E+02 1.30E+03 1.55E+00 1.86E+00 1.95E+00 8.14E+00

-1.21E+00 4.38E+00 4.89E+00 positive 1.04E+00 5.01E+00 6.08E+00 positive 5.81E+00 1.28E+01 1.41E+01 positive MW-54-123 MW-54-144 Q4-2011 12/6/2011 13:25 6.85E+03 7.44E+02 3.71E+02 2.64E+03 9.05E+00 2.99E+00 1.96E+00 2.53E+01 8.64E-01 5.58E+00 6.45E+00 positive 3.97E-01 5.58E+00 6.68E+00 positive

-2.77E+00 1.22E+01 1.38E+01 positive MW-54-144 MW-54-173 Q4-2011 12/6/2011 13:26 2.32E+03 6.66E+02 3.26E+02 3.63E+03 4.72E+00 2.32E+00 1.97E+00 1.22E+01

-8.33E-01 4.83E+00 5.47E+00 positive 9.05E-01 5.19E+00 6.34E+00 positive

-2.75E+00 1.24E+01 1.41E+01 positive MW-54-173 MW-54-190 Q4-2011 12/6/2011 13:38 8.77E+03 8.22E+02 3.68E+02 3.49E+03 1.81E+01 3.72E+00 1.90E+00 4.03E+01 5.15E-01 3.87E+00 4.56E+00 positive 1.47E+00 4.11E+00 5.26E+00 positive 3.28E+00 1.21E+01 1.34E+01 positive MW-54-190 MW-55-24 Q4-2011 11/14/2011 11:26 2.57E+03 6.66E+02 4.98E+02 2.58E+03 2.33E+01 4.08E+00 1.56E+00 2.97E+01 0.00E+00 8.49E+00 1.07E+01 positive 3.56E+00 1.08E+01 1.50E+01 positive

-7.45E+00 1.87E+01 2.17E+01 positive MW-55-24 MW-55-35 Q4-2011 11/14/2011 11:23 2.79E+03 6.84E+02 5.00E+02 4.38E+03 2.35E+01 3.99E+00 1.60E+00 4.26E+01 2.04E-01 7.08E+00 8.67E+00 positive 8.98E-01 8.22E+00 1.06E+01 positive 4.79E+00 1.87E+01 2.09E+01 positive MW-55-35 MW-55-54 Q4-2011 11/14/2011 11:07 5.97E+03 8.25E+02 4.67E+02 1.28E+04 1.75E+01 3.57E+00 1.46E+00 3.93E+01

-2.66E+00 8.67E+00 1.04E+01 positive 3.60E+00 6.69E+00 1.03E+01 positive 1.62E+00 1.92E+01 2.17E+01 positive MW-55-54 MW-56-53 Q4-2011 10/31/2011 12:13 6.15E+01 4.41E+02 5.09E+02 1.19E+03 5.82E-02 1.09E+00 1.39E+00 2.00E+00 4.08E+00 9.36E+00 1.24E+01 positive 4.41E+00 8.22E+00 1.26E+01 positive 4.96E+00 1.94E+01 2.17E+01 positive MW-56-53 MW-56-83 Q4-2011 10/31/2011 12:00 7.25E+04 2.80E+03 5.11E+02 6.39E+03 9.41E-01 1.49E+00 1.61E+00 3.98E+00 2.19E+00 7.29E+00 9.56E+00 positive 2.43E+00 8.94E+00 1.22E+01 positive

-3.01E+00 2.14E+01 2.44E+01 positive MW-56-83 MW-58-26 Q4-2011 11/15/2011 14:22 4.77E+03 7.29E+02 2.31E+02 1.00E+03

-4.32E-01 8.28E-01 1.25E+00 2.00E+00 1.04E+00 1.99E+01 8.90E+00 positive 2.18E+00 9.42E+00 1.24E+01 positive NA NA NA positive MW-58-26 MW-58-65 Q4-2011 11/15/2011 14:05 1.75E+03 4.32E+02 3.42E+02 1.00E+03 3.02E-01 1.71E+00 2.03E+00 2.00E+00

-1.89E+00 8.82E+00 9.54E+00 positive

-7.70E-01 7.23E+00 8.96E+00 positive NA NA NA positive MW-58-65 MW-60-35 Q4-2011 12/2/2011 11:21 1.74E+02 3.66E+02 4.07E+02 2.00E+03 3.94E-01 1.72E+00 1.98E+00 2.00E+00

-8.20E-01 9.33E+00 1.15E+01 positive 2.63E+00 7.86E+00 1.12E+01 positive NA NA NA positive MW-60-35 MW-60-53 Q4-2011 12/2/2011 11:46 2.65E+02 3.30E+02 3.33E+02 2.00E+03 9.60E-02 1.69E+00 1.97E+00 2.00E+00 4.62E-01 4.68E+00 5.62E+00 positive

-9.95E-01 4.83E+00 5.65E+00 positive NA NA NA positive MW-60-53 MW-60-72 Q4-2011 12/2/2011 10:01 3.08E+02 3.75E+02 4.01E+02 2.00E+03 8.41E-01 1.73E+00 1.93E+00 2.00E+00

-2.19E+00 6.99E+00 8.20E+00 positive

-1.72E+00 8.28E+00 1.01E+01 positive NA NA NA positive MW-60-72 MW-60-135 Q4-2011 12/2/2011 10:10 3.05E+02 3.81E+02 4.08E+02 2.00E+03

-1.48E-01 1.62E+00 1.97E+00 2.00E+00

-1.37E-02 7.68E+00 9.43E+00 positive 2.05E+00 8.28E+00 1.13E+01 positive NA NA NA positive MW-60-135 MW-60-154 Q4-2011 12/2/2011 10:18 6.27E+02 5.22E+02 5.23E+02 2.00E+03

-1.97E-01 1.54E+00 1.96E+00 2.00E+00 1.25E+00 9.33E+00 1.17E+01 positive

-3.69E+00 1.00E+01 1.13E+01 positive NA NA NA positive MW-60-154 MW-60-176 Q4-2011 12/2/2011 10:27 1.30E+03 5.97E+02 5.19E+02 2.00E+03

-1.37E+00 1.41E+00 1.95E+00 2.00E+00 7.24E-01 9.60E+00 1.20E+01 positive 1.35E+00 1.01E+01 1.36E+01 positive NA NA NA positive MW-60-176 MW-62-18 Q4-2011 10/21/2011 10:14 6.50E+02 3.54E+02 3.45E+02 2.00E+03

-1.09E+00 1.66E+00 2.27E+00 2.00E+00

-1.19E+00 6.87E+00 8.28E+00 positive

-8.37E-01 8.82E+00 1.11E+01 positive NA NA NA positive MW-62-18 MW-62-37 Q4-2011 10/21/2011 10:02 3.74E+02 3.33E+02 3.47E+02 2.00E+03

-3.24E-01 1.60E+00 2.05E+00 2.00E+00 5.93E-01 8.19E+00 9.98E+00 positive

-1.66E+00 8.07E+00 9.72E+00 positive NA NA NA positive MW-62-37 MW-62-53 Q4-2011 10/21/2011 10:17 4.82E+02 3.39E+02 3.42E+02 2.00E+03

-1.78E-02 1.24E+00 1.61E+00 2.00E+00 1.64E+00 6.66E+00 8.55E+00 positive 2.49E+00 7.05E+00 1.01E+01 positive NA NA NA positive MW-62-53 MW-62-71 Q4-2011 10/21/2011 9:44 4.68E+02 3.36E+02 3.42E+02 2.00E+03

-1.43E-01 1.29E+00 1.69E+00 2.00E+00 8.75E-01 9.06E+00 1.13E+01 positive 2.06E+00 9.84E+00 1.32E+01 positive NA NA NA positive MW-62-71 MW-62-92 Q4-2011 10/21/2011 9:42 5.51E+02 3.45E+02 3.42E+02 2.00E+03 4.45E-01 1.27E+00 1.48E+00 2.00E+00 3.18E-01 9.39E+00 1.17E+01 positive 1.88E-01 9.18E+00 1.22E+01 positive NA NA NA positive MW-62-92 MW-62-138 Q4-2011 10/21/2011 11:29 3.01E+03 5.97E+02 2.36E+02 2.00E+03 1.24E+00 1.48E+00 1.50E+00 2.42E+00

-5.88E+00 1.01E+01 1.10E+01 positive 2.45E-01 1.03E+01 1.33E+01 positive NA NA NA positive MW-62-138 MW-62-182 Q4-2011 10/21/2011 11:37 6.88E+02 3.42E+02 3.27E+02 2.00E+03

-2.48E-01 1.45E+00 1.90E+00 2.00E+00

-4.81E+00 1.22E+01 1.34E+01 positive

-1.67E+00 1.06E+01 1.27E+01 positive NA NA NA positive MW-62-182 MW-63-18 Q4-2011 10/18/2011 11:34 2.59E+02 2.34E+02 2.20E+02 2.00E+03 1.26E+00 1.74E+00 1.83E+00 2.00E+00 1.31E+00 8.28E+00 1.07E+01 positive 1.72E+00 1.09E+01 1.44E+01 positive NA NA NA positive MW-63-18 MW-63-34 Q4-2011 10/18/2011 11:39 4.30E+02 3.36E+02 3.46E+02 2.00E+03

-4.71E-01 1.27E+00 1.78E+00 2.00E+00

-3.77E+00 8.31E+00 9.14E+00 positive 2.21E+00 7.62E+00 1.11E+01 positive NA NA NA positive MW-63-34 MW-63-50 Q4-2011 10/18/2011 13:55 3.14E+02 3.63E+02 3.85E+02 2.00E+03 4.62E-01 1.68E+00 1.94E+00 2.00E+00

-9.09E-01 1.09E+01 1.29E+01 positive

-2.69E+00 1.09E+01 1.34E+01 positive NA NA NA positive MW-63-50 MW-63-93 Q4-2011 10/18/2011 14:14 5.04E+02 3.78E+02 3.83E+02 2.00E+03 5.60E-01 1.37E+00 1.56E+00 2.00E+00 7.43E-01 6.45E+00 8.33E+00 positive 3.55E+00 6.87E+00 1.02E+01 positive NA NA NA positive MW-63-93 MW-63-112 Q4-2011 10/18/2011 14:20 1.34E+03 5.43E+02 3.29E+02 2.00E+03

-5.35E-01 1.39E+00 1.87E+00 2.00E+00

-1.39E+00 7.53E+00 8.79E+00 positive 1.78E+00 7.02E+00 9.82E+00 positive NA NA NA positive MW-63-112 MW-63-121 Q4-2011 10/18/2011 11:27 3.63E+03 8.40E+02 3.33E+02 2.00E+03 1.49E+00 1.71E+00 1.75E+00 2.00E+00

-6.42E+00 1.26E+01 1.62E+01 positive 2.81E+00 9.33E+00 1.31E+01 positive NA NA NA positive MW-63-121 MW-63-163 Q4-2011 10/18/2011 11:37 4.85E+02 3.75E+02 3.80E+02 2.00E+03 9.47E-01 1.35E+00 1.43E+00 2.00E+00

-4.58E+00 9.51E+00 9.82E+00 positive

-1.98E+00 6.54E+00 7.63E+00 positive NA NA NA positive MW-63-163 MW-63-174 Q4-2011 10/18/2011 11:42 4.53E+02 3.72E+02 3.80E+02 2.00E+03 1.02E+00 1.71E+00 1.86E+00 2.00E+00

-6.37E-02 8.43E+00 1.03E+01 positive

-4.33E+00 8.13E+00 9.02E+00 positive NA NA NA positive MW-63-174 MW-66-21 Q4-2011 11/29/2011 11:08 2.64E+02 3.27E+02 3.32E+02 1.33E+03 3.54E-01 1.33E+00 1.49E+00 2.07E+00 7.86E-01 6.60E+00 8.51E+00 positive 1.73E+00 7.50E+00 1.01E+01 positive

-3.27E+00 1.37E+01 1.56E+01 positive MW-66-21 MW-66-36 Q4-2011 11/29/2011 11:01 3.34E+03 6.78E+02 4.85E+02 7.71E+03 1.02E+01 1.77E+00 1.38E+00 1.40E+01 5.21E+00 9.78E+00 1.32E+01 positive 1.63E+00 8.64E+00 1.21E+01 positive 0.00E+00 1.94E+01 2.18E+01 positive MW-66-36 MW-67-39 Q4-2011 11/29/2011 13:59 3.51E+03 8.07E+02 3.31E+02 6.52E+03 1.30E+01 2.39E+00 1.94E+00 1.81E+01

-1.60E+01 1.39E+01 1.60E+01 positive

-1.78E+00 9.48E+00 1.17E+01 positive 2.69E+00 1.24E+01 1.38E+01 positive MW-67-39 Well ID1 SAMPLE ID SAMPLE COLLECTION ANALYSIS RESULTS4,5 Well ID TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

TABLE 4 2011 4th QUARTER GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERTY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

Q42011 FINAL Table 4 - 2011 4th Quarter Groundwater Analytical Results.xlsx; Q42011 Table 4 Page 2 of 2 See Page 2 for Notes Date Time Result Std. Dev.6 MDC I.L.3,7 Result Std. Dev.6 MDC I.L.3 Result Std. Dev.6 MDC I.L.3 Result Std. Dev.6 MDC I.L.3 Result Std. Dev.6 MDC I.L.3 Well ID1 SAMPLE ID SAMPLE COLLECTION ANALYSIS RESULTS4,5 Well ID TRITIUM (pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

MW-67-105 Q4-2011 11/29/2011 14:10 1.89E+03 5.94E+02 4.78E+02 3.92E+03 1.13E+00 1.74E+00 1.90E+00 4.38E+00

-1.36E+00 8.73E+00 1.01E+01 positive

-1.41E+00 8.73E+00 1.04E+01 positive 3.65E+00 1.97E+01 2.20E+01 positive MW-67-105 MW-67-173 Q4-2011 11/29/2011 14:23 5.88E+02 4.74E+02 4.78E+02 1.61E+03 1.13E+00 1.62E+00 1.76E+00 2.00E+00

-1.48E+00 9.87E+00 1.14E+01 positive

-1.48E+00 1.08E+01 1.30E+01 positive 7.39E+00 1.18E+01 1.29E+01 positive MW-67-173 MW-67-219 Q4-2011 11/29/2011 10:41 1.20E+03 4.92E+02 4.45E+02 2.26E+03 3.14E-01 1.42E+00 1.63E+00 2.00E+00

-1.12E+01 1.14E+01 1.19E+01 positive 1.99E+00 7.65E+00 1.12E+01 positive 1.02E+01 1.13E+01 1.23E+01 positive MW-67-219 MW-67-276 Q4-2011 11/29/2011 10:57 1.06E+03 5.25E+02 4.84E+02 2.01E+03 1.99E-01 1.70E+00 1.95E+00 2.00E+00

-2.95E+00 1.01E+01 1.19E+01 positive

-7.14E-01 8.82E+00 1.11E+01 positive 6.48E+00 1.19E+01 1.31E+01 positive MW-67-276 MW-67-323 Q4-2011 11/29/2011 10:57 3.62E+02 4.56E+02 4.86E+02 1.00E+03 7.61E-01 1.71E+00 1.91E+00 2.00E+00

-3.91E+00 9.81E+00 1.15E+01 positive 1.58E+00 5.43E+00 8.36E+00 positive 1.66E+01 2.34E+01 2.56E+01 positive MW-67-323 MW-67-340 Q4-2011 11/29/2011 10:46 5.62E+02 4.68E+02 4.76E+02 1.01E+03

-5.80E-01 1.53E+00 1.87E+00 2.00E+00

-7.65E+00 7.53E+00 7.09E+00 positive 1.23E+00 8.85E+00 1.14E+01 positive 1.70E+00 1.06E+01 1.17E+01 positive MW-67-340 MW-111 Q4-2011 11/11/2011 11:30 1.11E+04 1.42E+03 3.31E+02 6.15E+04 1.09E+00 1.53E+00 1.62E+00 2.90E+00

-2.01E-01 7.11E+00 8.62E+00 1.36E+01 2.75E+00 8.97E+00 1.21E+01 positive NA NA NA positive MW-111 I-2 Q4-2011 12/8/2011 14:15

-3.49E+01 3.45E+02 4.09E+02 1.00E+03***

-2.39E-01 1.56E+00 1.92E+00 2.00E+00

-2.35E+00 8.76E+00 1.00E+01 positive

-2.12E+00 8.46E+00 1.04E+01 positive NA NA NA positive I-2 U3-4S Q4-2011 11/16/2011 11:28 7.52E+02 4.41E+02 3.32E+02 1.00E+03***

9.35E-01 1.38E+00 1.47E+00 2.00E+00

-2.06E+00 9.27E+00 1.12E+01 positive 1.63E+00 7.80E+00 1.08E+01 positive NA NA NA positive U3-4S U3-4D Q4-2011 11/16/2011 12:56 3.50E+02 3.63E+02 3.81E+02 1.00E+03 3.17E-01 1.38E+00 1.64E+00 2.00E+00

-9.88E-01 8.82E+00 1.07E+01 positive

-9.21E-01 9.27E+00 1.17E+01 positive NA NA NA positive U3-4D U3-T1 Q4-2011 10/19/2011 11:39 7.69E+02 4.05E+02 3.84E+02 1.00E+03 1.59E-01 1.19E+00 1.45E+00 2.00E+00

-3.93E-01 9.51E+00 1.17E+01 positive 2.12E-01 9.12E+00 1.17E+01 positive NA NA NA positive U3-T1 U3-T2 Q4-2011 10/19/2011 10:20 2.98E+03 7.62E+02 3.28E+02 2.08E+03

-8.79E-02 1.15E+00 1.47E+00 2.00E+00

-4.88E+00 1.02E+01 1.09E+01 positive

-5.13E+00 1.12E+01 1.23E+01 positive NA NA NA positive U3-T2 U1-CSS Q4-2011 10/27/2011 13:02 1.70E+03 5.64E+02 4.77E+02 5.17E+03 7.82E-01 1.28E+00 1.39E+00 2.08E+01

-2.80E+00 8.07E+00 8.99E+00 positive 1.05E+00 7.08E+00 9.69E+00 positive

-8.01E+00 1.78E+01 2.07E+01 positive U1-CSS U1-NCD Q4-2011 10/3/2011 13:20 1.13E+04 1.03E+03 3.35E+02 1.58E+01 3.72E+00 1.74E+00 5.92E+03 8.04E+02 1.43E+01 1.93E+00 7.20E+00 9.97E+00 1.36E+02 2.21E+01 1.86E+01 U1-NCD U1-NCD Q4-2011 12/26/2011 12:45 2.32E+03 5.13E+02 3.74E+02 1.49E+01 5.52E+00 3.33E+00 7.73E+03 9.75E+02 1.84E+01

-1.01E+00 9.48E+00 1.17E+01 1.96E+02 2.79E+01 1.88E+01 U1-NCD U1-SFDS Q4-2011 10/5/2011 9:00 2.02E+03 5.01E+02 3.35E+02 5.54E+00 2.53E+00 1.97E+00 4.27E+00 9.96E+00 1.25E+01

-6.39E+00 8.94E+00 9.49E+00 2.06E+01 1.87E+01 2.00E+01 U1-SFDS U1-SFDS Q4-2011 12/28/2011 8:19 1.10E+02 3.21E+02 3.61E+02 2.66E+00 2.22E+00 2.08E+00

-3.38E+00 9.87E+00 1.13E+01 3.75E-01 1.02E+01 1.33E+01

-4.44E+00 1.47E+01 1.73E+01 U1-SFDS B-6 Q4-2011 10/20/2011 12:01 1.70E+02 3.48E+02 3.87E+02

-1.65E-01 1.57E+00 1.98E+00

-3.07E+00 7.65E+00 8.33E+00 1.53E+00 8.34E+00 1.10E+01 NA NA NA B-6 MH-5 VCFD Q4-2011 10/17/2011 10:07 1.48E+04 1.09E+03 3.86E+02

-5.57E-01 1.17E+00 1.65E+00 1.51E+00 7.68E+00 9.98E+00

-2.77E+00 7.92E+00 9.24E+00 NA NA NA MH-5 VCFD MH-5 VCFD Q4-2011 10/31/2011 14:20 2.40E+04 1.37E+03 3.89E+02 1.06E+00 1.72E+00 1.87E+00 5.56E+00 1.15E+01 1.61E+01 3.37E-01 1.09E+01 1.53E+01 NA NA NA MH-5 VCFD LAF-002 Q4-2011 12/13/2011 10:31 6.96E+01 4.14E+02 4.79E+02 positive 1.65E+00 1.67E+00 1.75E+00 positive

-3.83E+00 9.48E+00 1.11E+01 positive 5.21E+00 8.73E+00 1.29E+01 positive 6.36E+00 1.11E+01 1.22E+01 positive LAF-002 Notes

1. For nested multi-level monitoring wells, suffix of well ID indicates depth (rounded to nearest foot) from reference point on casing to bottom of well screen. For Waterloo multi-level systems, suffix indicates depth (rounded to nearest foot) from reference point on casing to top of sampling port.

Well IDs without a suffix are open bedrock wellbores.

2. Sampling depths within sampling intervals (location of pump intake) have been established at location of most transmissive zone to the extent possible.
3. I.L.s (Investigation Levels) are predetermined detection limits assigned to each sampling location which, if reached or exceeded, require further investigation or action. I.L.s presented here for Sr-90, CS-137, Co-60 & Ni-63 are established for 2011 based on 2010 averages. See Note #7 below for further 2011 Tritium I.L. discussion. Positive detections indicate that the the result is greater than MDC and greater than or equal to 3 times the 1 sigma uncertainty.
4. NA indicates that the constituent was not analyzed.
5. Shading indicates that the sample result exceeds the Investigation Level.
6. Column designated as Std. Dev. provides the three times 1 sigma uncertainty values.
7. To be conservative, the 2011 Tritium I.L.s were calculated using (2x the 2009 yearly average) beacuase an increased Tritium activity in multiple Unit 2 sampling intervals was observed during 2010 in response to the transient surface spill from a temporary rental RWST/R.O. processing skid.
  • Indicates storm or foundation drain sampling locations, for which investigation levels are not applicable.
    • Indicates 2011 I.L.s not computed for this well due to absence of 2008 through 2010 data.
      • 2011 Tritium I.L. calculated based on the 2010 rolling average due to absence of 2009 data.

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 1 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC MW-30-69 004 69.3 6.4 8/18/2006 14:45 2.20E+05 4.20E+03 1.10E+03 8.14E-01 1.40E+00 1.52E+00

-7.33E+00 1.40E+01 1.41E+01 3.91E+00 1.51E+01 1.78E+01 NA NA NA MW-30-69 MW-30-69 005 69.3 6.4 11/29/2006 10:45 1.06E+05 1.86E+03 5.30E+02 2.50E+00 8.40E-01 8.10E-01 3.13E+03 3.30E+01 5.00E+00 1.20E+00 2.28E+00 2.50E+00 1.15E+01 1.26E+01 1.40E+01 MW-30-69 MW-30-69 006 69.3 6.4 1/16/2007 14:05 8.17E+04 8.73E+03 6.34E+02

-1.60E-01 1.47E+00 1.60E+00 0.00E+00 2.10E+00 2.40E+00

-4.30E-01 2.07E+00 2.50E+00 7.07E+00 1.94E+01 2.20E+01 MW-30-69 MW-30-69 007 69.3 6.4 6/12/2007 10:20 2.97E+05 8.73E+03 6.34E+02

-2.63E-01 4.19E-01 6.45E-01 3.93E-01 3.75E+00 4.09E+00 6.88E-02 4.08E+00 3.94E+00 NA NA NA MW-30-69 MW-30-69 008 69.3 6.4 7/18/2007 9:55 8.21E+04 2.46E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-30-69 MW-30-69 010 69.3 6.4 8/1/2007 11:44 1.03E+05 3.09E+03 6.40E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-30-69 MW-30-69 011 69.3 6.4 8/8/2007 10:00 9.96E+04 2.99E+03 6.32E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-30-69 MW-30-69 012 69.3 6.4 8/15/2007 11:00 2.33E+05 6.99E+03 6.33E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-30-69 MW-30-69 013 69.3 6.4 8/21/2007 9:45 1.07E+05 3.21E+03 7.05E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-30-69 MW-30-69 014 69.3 6.4 8/30/2007 11:32 9.80E+04 2.94E+03 7.03E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-30-69 MW-30-69 015 69.3 6.4 9/19/2007 11:00 9.20E+04 2.76E+03 7.02E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-30-69 MW-30-69 016 69.3 6.4 10/23/2007 11:48 1.32E+05 3.90E+03 4.24E+02 2.52E-01 6.16E-01 7.12E-01 2.42E+00 5.76E+00 4.45E+00

-5.09E-01 3.66E+00 3.86E+00 NA NA NA MW-30-69 MW-30-69 017 69.3 6.4 2/4/2008 13:00 1.87E+05 5.51E+03 3.95E+02 1.57E-01 6.98E-01 8.57E-01 1.26E+00 3.05E+00 3.56E+00

-6.00E-01 3.63E+00 3.28E+00 NA NA NA MW-30-69 MW-30-69 018 69.3 6.4 5/6/2008 11:00 1.53E+05 3.01E+03 4.06E+02 3.34E-01 3.98E-01 6.71E-01 4.94E-01 1.83E+00 3.21E+00

-5.70E-01 1.71E+00 2.73E+00 NA NA NA MW-30-69 MW-30-69 019 69.3 6.4 6/6/2008 11:01 7.36E+04 2.02E+03 5.06E+02 2.02E-01 3.20E-01 5.59E-01

-9.82E-01 2.10E+00 3.27E+00 4.91E-01 2.24E+00 3.85E+00 NA NA NA MW-30-69 MW-30-69 020 69.3 6.4 8/5/2008 11:22 1.99E+05 3.92E+03 4.95E+02 2.09E-01 3.07E-01 5.34E-01

-1.57E-01 1.42E+00 2.38E+00 1.11E+00 1.28E+00 2.33E+00 NA NA NA MW-30-69 MW-30-69 021 69.3 6.4 9/3/2008 11:29 8.53E+04 2.03E+03 5.50E+02

-3.12E-01 5.12E-01 9.72E-01

-1.89E+00 2.22E+00 3.36E+00 NA NA NA NA NA NA MW-30-69 MW-30-69 022 69.3 6.4 11/7/2008 10:27 9.55E+04 2.85E+03 3.06E+02 4.09E-01 5.53E-01 6.01E-01 7.83E-01 3.09E+00 3.66E+00

-1.07E-01 2.65E+00 2.85E+00 NA NA NA MW-30-69 MW-30-69 023 69.3 6.4 1/30/2009 11:00 1.07E+05 2.51E+03 1.98E+02

-8.74E-02 7.58E-01 9.73E-01

-1.13E+00 2.61E+00 2.66E+00 1.06E+00 2.70E+00 3.24E+00 NA NA NA MW-30-69 MW-30-69 024 69.3 6.4 4/27/2009 10:27 1.00E+05 3.65E+03 4.02E+02

-1.54E-01 4.28E-01 6.01E-01 1.49E+00 7.11E+00 4.74E+00

-2.78E-01 4.19E+00 4.60E+00 NA NA NA MW-30-69 MW-30-69 025 69.3 6.4 6/1/2009 12:02 8.20E+04 3.21E+03 3.77E+02 3.12E-01 5.63E-01 6.32E-01 2.16E+00 9.80E+00 6.53E+00 8.26E-01 6.47E+00 7.42E+00 NA NA NA MW-30-69 MW-30-69 026 69.3 6.4 8/6/2009 12:16 1.64E+05 4.77E+03 2.96E+02 6.79E-02 6.10E-01 7.41E-01

-2.09E+00 8.32E+00 7.30E+00

-2.07E+00 9.44E+00 9.70E+00 NA NA NA MW-30-69 MW-30-69 027 69.3 6.4 9/12/2009 10:45 9.91E+04 2.91E+03 2.67E+02

-3.43E-02 6.45E-01 8.50E-01

-9.52E-01 5.52E+00 6.11E+00 4.45E+00 6.13E+00 7.88E+00 NA NA NA MW-30-69 MW-30-69 028 69.3 6.4 11/9/2009 11:21 9.01E+04 2.63E+03 1.78E+02

-4.26E-01 6.63E-01 8.14E-01

-1.87E-01 5.47E+00 6.20E+00

-2.47E-01 6.03E+00 6.76E+00 NA NA NA MW-30-69 MW-30-69 029 69.3 6.4 1/27/2010 11:30 1.25E+05 3.99E+03 6.15E+02 3.42E-02 7.18E-01 8.83E-01

-3.23E-01 3.36E+00 3.68E+00 2.05E-01 3.17E+00 3.57E+00 NA NA NA MW-30-69 MW-30-69 030 69.3 6.4 2/24/2010 12:35 1.36E+05 2.01E+03 2.05E+02

-7.42E-02 3.54E-01 5.00E-01 6.84E-01 3.79E+00 4.26E+00

-1.38E+00 3.65E+00 3.73E+00 NA NA NA MW-30-69 MW-30-69 031 69.3 6.4 4/29/2010 12:55 1.61E+05 4.67E+03 2.78E+02

-1.31E-01 7.56E-01 9.40E-01

-2.29E+00 5.33E+00 5.59E+00 2.06E+00 5.37E+00 6.58E+00 NA NA NA MW-30-69 MW-30-69 032 69.3 6.4 6/8/2010 12:32 1.52E+05 4.49E+03 4.80E+02 2.56E-01 4.79E-01 5.40E-01

-1.20E+00 6.55E+00 7.22E+00

-1.72E-01 5.45E+00 5.99E+00 NA NA NA MW-30-69 MW-30-69 033 69.3 6.4 7/28/2010 12:33 1.28E+05 3.72E+03 1.80E+02 9.14E-02 5.26E-01 6.35E-01

-5.08E-01 9.69E+00 1.09E+01 1.67E+00 7.46E+00 9.20E+00 NA NA NA MW-30-69 MW-30-69 034 69.3 6.4 8/20/2010 15:08 1.11E+05 3.24E+03 2.02E+02 3.53E-01 7.80E-01 9.08E-01

-3.14E+00 5.22E+00 5.12E+00

-2.41E+00 5.25E+00 5.03E+00 NA NA NA MW-30-69 MW-30-69 035 69.3 6.4 9/8/2010 12:35 1.23E+05 3.65E+03 4.47E+02 1.93E-01 4.41E-01 5.14E-01

-1.10E+00 4.42E+00 4.87E+00 1.40E+00 4.72E+00 5.73E+00 NA NA NA MW-30-69 MW-30-69 036 69.3 6.4 11/5/2010 11:56 1.25E+05 1.88E+03 4.34E+02 9.69E-01 8.79E-01 1.94E+00

-3.68E+00 3.94E+00 7.79E+00

-5.01E+00 5.09E+00 9.47E+00 NA NA NA MW-30-69 MW-30-69 037 69.3 6.4 2/9/2011 12:17 1.01E+05 2.18E+03 2.98E+02 1.62E+00 1.93E+00 2.00E+00 1.87E+00 5.80E+00 6.74E+00

-1.13E-01 5.88E+00 6.44E+00 NA NA NA MW-30-69 MW-30-69 038 69.3 6.4 3/31/2011 11:38 1.08E+05 3.40E+03 4.72E+02

-6.11E-01 1.63E+00 2.15E+00 2.48E+00 7.96E+00 9.14E+00

-1.41E+00 6.70E+00 6.46E+00 NA NA NA MW-30-69 MW-30-69 039 69.3 6.4 5/5/2011 12:08 1.13E+05 3.48E+03 3.99E+02 2.40E+00 1.37E+00 1.23E+00 2.46E+00 8.92E+00 1.03E+01 2.21E+00 9.58E+00 1.16E+01 NA NA NA MW-30-69 MW-30-69 040 69.3 6.4 7/11/2011 12:05 1.19E+05 4.23E+03 2.83E+02

-6.14E-02 7.62E-01 1.00E+00 3.56E+00 1.07E+01 1.24E+01 2.40E+00 1.19E+01 1.40E+01 NA NA NA MW-30-69 MW-30-69 041 69.3 6.4 8/9/2011 10:49 1.14E+05 3.45E+03 4.22E+02 1.02E+00 1.76E+00 1.92E+00

-7.63E-01 1.03E+01 1.15E+01

-2.42E+00 8.58E+00 8.50E+00 NA NA NA MW-30-69 MW-30-69 042 69.3 6.4 11/30/2011 11:20 9.12E+04 3.06E+03 4.87E+02

-4.56E-01 1.51E+00 1.96E+00 1.95E+00 7.71E+00 9.97E+00 2.82E+00 7.41E+00 1.11E+01 NA NA NA MW-30-69 MW-30-84 001 83.8

-8.1 8/22/2006 13:15 1.25E+04 2.43E+03 1.61E+03

-1.60E-01 9.82E-01 1.13E+00 1.88E+00 1.09E+01 1.24E+01

-2.52E+00 1.00E+01 1.03E+01 NA NA NA MW-30-84 MW-30-84 002 83.8

-8.1 11/29/2006 14:30 1.01E+04 1.59E+03 1.10E+03

-9.40E-01 7.80E-01 8.70E-01 2.94E+02 1.68E+01 5.00E+00

-3.00E-01 3.90E+00 4.80E+00 4.10E+00 1.17E+01 1.30E+01 MW-30-84 MW-30-84 003 83.8

-8.1 1/17/2007 9:45 7.33E+03 7.50E+02 5.30E+02 4.80E-01 1.50E+00 1.60E+00 1.18E+00 2.61E+00 2.90E+00 0.00E+00 2.91E+00 3.40E+00 NA NA NA MW-30-84 MW-30-84 004 83.8

-8.1 6/12/2007 10:19 7.79E+03 9.47E+02 4.42E+02

-1.49E-01 4.44E-01 6.41E-01

-1.06E+00 2.29E+00 2.41E+00

-6.93E-01 2.38E+00 2.54E+00

-3.57E+00 1.74E+01 2.03E+01 MW-30-84 MW-30-84 005 83.8

-8.1 7/18/2007 10:25 4.80E+03 7.20E+02 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-30-84 MW-30-84 006 83.8

-8.1 7/25/2007 13:00 5.02E+03 4.49E+02 2.43E+02 1.56E-01 3.09E-01 3.48E-01 2.83E+00 3.38E+00 2.84E+00 2.03E+00 2.91E+00 3.57E+00 NA NA NA MW-30-84 MW-30-84 007 83.8

-8.1 10/23/2007 12:49 4.27E+03 7.38E+02 4.03E+02 5.95E-01 5.53E-01 5.59E-01 1.56E+00 2.81E+00 3.38E+00

-1.17E+00 3.72E+00 3.27E+00 NA NA NA MW-30-84 MW-30-84 008 83.8

-8.1 2/4/2008 14:16 4.34E+03 2.61E+02 1.32E+02

-4.08E-01 4.55E-01 7.47E-01

-1.00E+00 2.55E+00 2.73E+00

-4.32E-01 2.97E+00 2.79E+00 NA NA NA MW-30-84 MW-30-84 009 83.8

-8.1 5/6/2008 13:40 4.18E+03 2.83E+02 2.20E+02 3.26E-01 3.86E-01 6.51E-01 4.43E-01 2.37E+00 4.00E+00

-1.91E+00 2.53E+00 3.69E+00 NA NA NA MW-30-84 MW-30-84 010 83.8

-8.1 6/6/2008 12:10 3.85E+03 5.33E+02 5.04E+02 1.54E-01 2.46E-01 4.34E-01

-8.97E-01 2.16E+00 3.57E+00 2.05E+00 2.31E+00 4.29E+00 NA NA NA MW-30-84 MW-30-84 020 83.8

-8.1 8/5/2008 14:40 4.31E+03 2.28E+02 1.94E+02 2.77E-01 2.86E-01 4.67E-01

-1.87E-01 1.44E+00 2.35E+00

-1.04E-01 2.12E+00 2.66E+00 NA NA NA MW-30-84 MW-30-84 021 83.8

-8.1 9/3/2008 11:59 3.78E+03 5.13E+02 5.35E+02

-4.62E-02 4.61E-01 9.06E-01

-3.02E-01 1.73E+00 2.89E+02 NA NA NA NA NA NA MW-30-84 MW-30-84 013 83.8

-8.1 11/7/2008 10:50 5.25E+03 3.23E+02 1.64E+02 1.07E-02 5.75E-01 7.61E-01 6.64E-01 4.63E+00 5.37E+00 2.13E+00 5.34E+00 6.53E+00 NA NA NA MW-30-84 MW-30-84 014 83.8

-8.1 1/30/2009 11:21 4.69E+03 5.48E+02 1.99E+02 9.38E-02 5.97E-01 7.19E-01 8.97E+00 4.34E+00 3.02E+00

-8.43E-02 3.39E+00 3.81E+00 NA NA NA MW-30-84 MW-30-84 015 83.8

-8.1 4/27/2009 14:30 5.34E+03 9.08E+02 4.11E+02

-1.19E-01 4.70E-01 6.29E-01 1.13E+00 6.54E+00 4.36E+00 1.33E+00 3.72E+00 4.50E+00 NA NA NA MW-30-84 MW-30-84 016 83.8

-8.1 6/1/2009 13:25 5.83E+03 9.02E+02 3.76E+02 1.34E-01 7.19E-01 8.22E-01 3.90E-01 1.01E+01 6.75E+00 8.79E-02 6.06E+00 6.80E+00 NA NA NA MW-30-84 MW-30-84 017 83.8

-8.1 8/6/2009 12:38 7.76E+03 5.03E+02 1.60E+02 6.08E-02 7.47E-01 9.19E-01 1.88E+00 4.82E+00 5.65E+00

-5.55E+00 6.12E+00 4.95E+00 NA NA NA MW-30-84 MW-30-84 018 83.8

-8.1 9/12/2009 12:22 6.75E+03 3.89E+02 1.53E+02

-6.42E-02 7.28E-01 8.91E-01 1.76E+00 9.09E+00 5.02E+00

-7.70E-01 5.29E+00 5.82E+00 NA NA NA MW-30-84 MW-30-84 019 83.8

-8.1 11/9/2009 12:27 6.27E+03 3.36E+02 9.70E+01 8.84E-02 7.33E-01 8.42E-01 2.06E-01 5.92E+00 6.74E+00

-3.17E+00 5.33E+00 4.98E+00 NA NA NA MW-30-84 MW-30-84 020 83.8

-8.1 1/27/2010 12:15 6.60E+03 1.07E+03 6.37E+02

-1.64E-01 2.43E-01 4.02E-01 3.93E-01 3.06E+00 3.41E+00

-8.46E-01 3.03E+00 3.19E+00 NA NA NA MW-30-84 MW-30-84 021 83.8

-8.1 2/24/2010 12:44 6.94E+03 3.63E+02 1.68E+02 1.30E-01 4.23E-01 5.06E-01 1.17E+00 4.58E+00 5.35E+00 9.09E-01 4.74E+00 5.54E+00 NA NA NA MW-30-84 MW-30-84 022 83.8

-8.1 4/29/2010 13:46 9.56E+03 5.40E+02 1.48E+02 4.08E-01 8.33E-01 9.56E-01

-3.84E-01 5.71E+00 6.36E+00 2.19E+00 5.36E+00 6.57E+00 NA NA NA MW-30-84 MW-30-84 023 83.8

-8.1 6/8/2010 12:19 9.40E+03 4.37E+02 2.14E+02 2.01E-01 4.85E-01 5.52E-01 7.20E-01 5.49E+00 6.21E+00

-4.01E+00 6.36E+00 6.10E+00 NA NA NA MW-30-84 MW-30-84 024 83.8

-8.1 7/28/2010 13:07 9.26E+03 5.09E+02 1.01E+02 4.48E-01 7.63E-01 8.52E-01

-1.46E+00 9.30E+00 1.02E+01

-3.03E-01 9.79E+00 1.08E+01 NA NA NA MW-30-84 MW-30-84 025 83.8

-8.1 8/20/2010 16:51 1.00E+04 5.57E+02 1.29E+02 5.65E-01 8.70E-01 9.53E-01 3.22E+00 6.27E+00 7.54E+00

-3.97E+00 6.69E+00 6.20E+00 NA NA NA MW-30-84 MW-30-84 026 83.8

-8.1 9/8/2010 13:14 1.01E+04 4.32E+02 2.10E+02 3.18E-01 6.20E-01 7.05E-01

-1.48E+00 6.18E+00 6.74E+00

-4.19E-01 7.65E+00 8.58E+00 NA NA NA MW-30-84 MW-30-84 027 83.8

-8.1 11/5/2010 12:35 1.02E+04 4.80E+02 3.87E+02 5.25E-01 7.56E-01 1.70E+00

-3.07E+00 4.23E+00 8.38E+00

-5.22E+00 4.86E+00 8.20E+00 NA NA NA MW-30-84 MW-30-84 028 83.8

-8.1 2/9/2011 12:57 9.20E+03 8.86E+02 3.79E+02 1.12E+00 1.82E+00 1.98E+00 5.89E-01 4.74E+00 5.22E+00 1.09E+00 5.76E+00 6.49E+00 NA NA NA MW-30-84 MW-30-84 029 83.8

-8.1 3/31/2011 12:03 9.04E+03 1.06E+03 4.74E+02

-4.78E-01 1.66E+00 2.13E+00 5.00E-01 1.12E+01 1.21E+01

-3.04E+00 9.48E+00 9.12E+00 NA NA NA MW-30-84 MW-30-84 030 83.8

-8.1 5/5/2011 12:58 7.57E+03 9.46E+02 3.92E+02 1.64E-01 1.15E+00 1.40E+00 3.00E+00 8.04E+00 9.35E+00 4.65E-02 7.14E+00 7.76E+00 NA NA NA MW-30-84 MW-30-84 031 83.8

-8.1 7/11/2011 12:45 7.55E+03 1.08E+03 2.82E+02

-3.75E-01 9.75E-01 1.29E+00 2.17E-01 7.89E+00 8.89E+00 1.39E+01 1.16E+01 1.59E+01 NA NA NA MW-30-84 MW-30-84 032 83.8

-8.1 8/9/2011 11:16 7.06E+03 7.05E+02 3.54E+02

-1.22E+00 1.28E+00 1.92E+00

-1.67E+00 7.08E+00 7.43E+00

-3.28E+00 9.63E+00 9.46E+00 NA NA NA MW-30-84 MW-30-84 033 83.8

-8.1 11/30/2011 11:37 7.24E+03 9.39E+02 4.80E+02 5.31E-02 1.45E+00 1.81E+00

-1.63E+00 9.48E+00 1.09E+01

-1.64E+00 1.05E+01 1.26E+01 NA NA NA MW-30-84 MW-31-49 001 48.8 26.8 11/27/2006 11:45 2.98E+02 1.74E+02 1.70E+02 0.00E+00 1.29E+00 1.40E+00 NA NA NA 1.30E+00 3.60E+00 4.00E+00 1.42E+02 1.65E+02 1.80E+02 MW-31-49 MW-31-49 002 48.8 26.8 1/18/2007 9:13 1.20E+03 5.70E+02 5.30E+02 3.00E-01 1.62E+00 1.80E+00 NA NA NA

-2.10E+00 8.10E+00 9.50E+00 NA NA NA MW-31-49 MW-31-49 003 48.8 26.8 6/12/2007 14:24 1.48E+03 5.24E+02 4.37E+02

-1.51E-01 5.49E-01 7.52E-01 1.83E-01 2.12E+00 2.35E+00 1.26E-01 2.01E+00 2.26E+00 0.00E+00 1.11E+01 1.29E+01 MW-31-49 MW-31-49 004 48.8 26.8 8/2/2007 10:23 1.19E+04 1.27E+03 5.43E+02

-5.17E-01 7.89E-01 9.55E-01 8.83E+01 1.35E+01 3.31E+00 1.80E-01 3.63E+00 4.11E+00 NA NA NA MW-31-49 MW-31-49 005 48.8 26.8 9/11/2007 13:10 6.98E+03 3.27E+02 1.59E+02

-2.26E-01 4.23E-01 6.01E-01

-1.20E+00 3.04E+00 3.24E+00 0.00E+00 4.96E+00 4.75E+00 NA NA NA MW-31-49 Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 2 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-31-49 006 48.8 26.8 10/24/2007 15:50 8.77E+03 9.99E+02 4.00E+02 5.14E-02 4.26E-01 5.36E-01

-6.76E-01 3.94E+00 3.57E+00 1.35E+00 3.21E+00 3.52E+00 NA NA NA MW-31-49 MW-31-49 007 48.8 26.8 1/16/2008 10:31 3.97E+02 1.94E+02 1.77E+02

-9.14E-02 6.86E-01 8.97E-01

-1.17E+00 4.74E+00 5.07E+00

-9.76E-01 4.41E+00 4.65E+00 NA NA NA MW-31-49 MW-31-49 009 48.8 26.8 6/6/2008 15:05 3.04E+04 1.34E+03 4.69E+02 2.83E-01 3.39E-01 5.72E-01 1.11E+00 1.93E+00 3.47E+00 1.72E+00 2.01E+00 3.82E+00 NA NA NA MW-31-49 MW-31-49 010 48.8 26.8 8/7/2008 12:43 5.94E+02 1.33E+02 1.92E+02 2.39E-01 2.67E-01 4.43E-01 7.07E-01 1.30E+00 2.23E+00 7.08E-01 1.49E+00 2.56E+00 NA NA NA MW-31-49 MW-31-49 011 48.8 26.8 8/30/2008 11:55 1.36E+04 8.61E+02 5.53E+02 4.16E-01 4.80E-01 8.06E-01 1.27E+00 3.63E+00 3.09E+00 NA NA NA NA NA NA MW-31-49 MW-31-49 012 48.8 26.8 10/30/2008 11:30 6.43E+02 2.25E+02 1.71E+02 7.64E-02 1.71E-01 1.93E-01 1.39E+00 6.27E+00 7.25E+00

-9.09E-01 6.40E+00 6.88E+00 NA NA NA MW-31-49 MW-31-49 013 48.8 26.8 11/18/2008 11:15 7.77E+02 1.79E+02 1.62E+02 4.11E-01 6.30E-01 6.97E-01 1.21E+00 4.18E+00 5.03E+00 9.78E-01 4.93E+00 5.84E+00 NA NA NA MW-31-49 MW-31-49 014 48.8 26.8 2/6/2009 11:05 1.11E+04 7.86E+02 1.99E+02 1.18E-01 3.00E-01 3.57E-01

-1.67E-01 2.97E+00 3.35E+00

-4.61E-01 2.85E+00 3.14E+00 NA NA NA MW-31-49 MW-31-49 015 48.8 26.8 4/14/2009 10:36 4.84E+04 1.42E+03 1.56E+02 4.85E-01 5.63E-01 5.97E-01

-5.81E-01 6.18E+00 4.12E+00 1.44E+00 3.90E+00 4.67E+00 NA NA NA MW-31-49 MW-31-49 016 48.8 26.8 5/29/2009 11:42 9.34E+03 1.12E+03 3.77E+02 5.72E-01 5.75E-01 6.24E-01

-7.86E-01 9.50E+00 6.33E+00

-1.48E+00 6.63E+00 7.11E+00 NA NA NA MW-31-49 MW-31-49 017 48.8 26.8 7/21/2009 11:53 7.36E+02 2.61E+02 2.27E+02 1.91E-01 5.01E-01 5.96E-01

-1.36E+00 3.38E+00 3.60E+00 1.04E+00 3.92E+00 4.66E+00 NA NA NA MW-31-49 MW-31-49 019 48.8 26.8 9/14/2009 11:13 3.14E+04 9.35E+02 1.70E+02

-3.21E-02 7.29E-01 9.36E-01

-1.97E+00 5.31E+00 5.51E+00 3.23E+00 4.71E+00 6.12E+00 NA NA NA MW-31-49 MW-31-49 020 48.8 26.8 10/22/2009 12:58 4.58E+04 8.63E+02 1.63E+02 5.63E-01 8.72E-01 9.67E-01 2.29E-01 6.17E+00 6.84E+00

-4.70E-01 6.15E+00 6.61E+00 NA NA NA MW-31-49 MW-31-49 021 48.8 26.8 1/26/2010 12:07 4.46E+02 1.35E+02 1.12E+02 1.88E-01 7.59E-01 9.05E-01

-4.18E-01 5.33E+00 4.07E+00

-1.34E+00 3.84E+00 3.99E+00 NA NA NA MW-31-49 MW-31-49 022 48.8 26.8 3/5/2010 11:30 4.89E+02 1.71E+02 1.69E+02 1.47E-02 3.51E-01 4.50E-01

-4.63E-01 4.53E+00 5.10E+00 1.18E+00 4.83E+00 5.71E+00 NA NA NA MW-31-49 MW-31-49 023 48.8 26.8 4/14/2010 10:42 1.16E+04 3.90E+02 1.00E+02 1.18E-01 4.62E-01 5.72E-01

-2.95E+00 8.54E+00 9.00E+00 9.25E-03 8.91E+00 9.95E+00 NA NA NA MW-31-49 MW-31-49 024 48.8 26.8 6/7/2010 11:30 1.73E+04 5.79E+02 2.22E+02 3.41E-01 7.95E-01 9.18E-01

-3.80E+00 7.42E+00 7.51E+00 1.82E+00 6.72E+00 8.03E+00 NA NA NA MW-31-49 MW-31-49 025 48.8 26.8 7/27/2010 14:43 5.46E+04 1.59E+03 1.21E+02 3.05E-01 4.71E-01 5.22E-01 2.74E+00 1.17E+01 1.40E+01 2.23E+00 8.03E+00 9.96E+00 NA NA NA MW-31-49 MW-31-49 026 48.8 26.8 8/23/2010 12:11 4.11E+03 3.56E+02 1.23E+02 1.62E-01 7.89E-01 9.57E-01

-1.21E+00 5.42E+00 5.91E+00

-3.35E-02 5.19E+00 5.80E+00 NA NA NA MW-31-49 MW-31-49 027 48.8 26.8 9/7/2010 13:49 1.04E+05 3.02E+03 1.68E+02

-1.15E-01 2.82E-01 4.23E-01 3.35E+00 5.52E+00 6.68E+00 2.16E+00 5.97E+00 7.20E+00 NA NA NA MW-31-49 MW-31-49 028 48.8 26.8 11/3/2010 11:55 3.35E+04 9.81E+02 1.15E+02

-3.04E-02 4.26E-01 5.51E-01

-2.82E+00 8.51E+00 8.97E+00 2.22E+00 8.87E+00 1.06E+01 NA NA NA MW-31-49 MW-31-49 029 48.8 26.8 2/9/2011 13:12 1.06E+03 3.40E+02 2.98E+02

-5.51E-01 1.76E+00 2.14E+00 1.39E+00 5.22E+00 6.02E+00 4.84E-01 5.26E+00 5.91E+00 NA NA NA MW-31-49 MW-31-49 030 48.8 26.8 3/30/2011 12:33 4.31E+03 7.84E+02 4.65E+02 1.77E+00 2.04E+00 2.16E+00

-2.34E+00 7.80E+00 8.17E+00

-5.38E-01 9.18E+00 1.00E+01 NA NA NA MW-31-49 MW-31-49 031 48.8 26.8 4/18/2011 12:53 1.08E+03 5.20E+02 4.66E+02 4.98E-01 1.81E+00 2.09E+00

-1.82E+00 8.82E+00 9.22E+00 6.17E+00 8.70E+00 1.13E+01 NA NA NA MW-31-49 MW-31-49 033 48.8 26.8 8/5/2011 10:47 4.98E+03 7.80E+02 4.16E+02

-2.63E-02 1.34E+00 1.58E+00 6.39E+00 8.76E+00 1.10E+01 5.20E-01 1.06E+01 1.16E+01 NA NA NA MW-31-49 MW-31-49 034 48.8 26.8 11/21/2011 10:32 1.54E+04 9.78E+02 3.42E+02

-3.16E-01 1.08E+00 1.45E+00 0.00E+00 1.14E+01 9.96E+00

-3.55E+00 9.54E+00 1.08E+01 NA NA NA MW-31-49 MW-31-63 001 63.3 12.3 11/27/2006 12:10 6.89E+03 1.44E+03 1.10E+03 5.30E-01 1.26E+00 1.40E+00 1.99E+02 9.60E+00 3.60E+00 6.80E-01 2.94E+00 3.40E+00 4.10E+01 1.17E+02 1.30E+02 MW-31-63 MW-31-63 002 63.3 12.3 1/18/2007 9:25 1.41E+04 9.00E+02 5.20E+02

-6.50E-01 1.50E+00 1.70E+00

-4.00E-01 3.00E+00 3.50E+00

-4.50E-01 2.91E+00 3.50E+00 NA NA NA MW-31-63 MW-31-63 003 63.3 12.3 6/12/2007 14:20 5.00E+03 7.85E+02 4.38E+02 4.72E-01 6.36E-01 6.78E-01

-5.01E-01 1.92E+00 2.09E+00

-8.78E-02 1.97E+00 2.20E+00 3.37E+00 1.89E+01 2.17E+01 MW-31-63 MW-31-63 004 63.3 12.3 8/2/2007 11:15 4.06E+04 2.27E+03 5.53E+02

-1.41E-01 7.84E-01 9.53E-01 1.20E+00 3.56E+00 4.18E+00

-3.09E-02 4.41E+00 4.23E+00 NA NA NA MW-31-63 MW-31-63 005 63.3 12.3 9/11/2007 13:25 3.77E+04 1.13E+03 2.20E+02

-1.37E-01 4.52E-01 6.15E-01

-4.39E-01 3.51E+00 3.80E+00

-8.64E-01 3.92E+00 3.44E+00 NA NA NA MW-31-63 MW-31-63 006 63.3 12.3 10/24/2007 14:55 3.58E+04 1.94E+03 4.00E+02

-1.63E-01 4.58E-01 6.34E-01 1.07E+00 5.31E+00 4.01E+00 1.01E+00 3.40E+00 4.11E+00 NA NA NA MW-31-63 MW-31-63 007 63.3 12.3 1/16/2008 11:32 1.24E+04 7.35E+02 1.80E+02

-6.88E-02 5.34E-01 7.44E-01

-2.49E-01 4.04E+00 4.40E+00

-9.08E-01 4.19E+00 4.32E+00 NA NA NA MW-31-63 MW-31-63 009 63.3 12.3 6/6/2008 16:16 1.02E+04 7.92E+02 5.04E+02 1.44E-01 3.40E-01 6.17E-01

-1.15E+00 2.11E+00 3.36E+00 2.47E+00 2.31E+00 4.45E+00 NA NA NA MW-31-63 MW-31-63 010 63.3 12.3 8/7/2008 11:22 1.76E+04 4.17E+02 1.94E+02

-2.12E-01 2.61E-01 5.89E-01

-1.86E-01 1.28E+00 2.16E+00 3.73E-01 1.43E+00 2.49E+00 NA NA NA MW-31-63 MW-31-63 011 63.3 12.3 8/30/2008 12:34 2.21E+04 1.07E+03 5.49E+02

-6.34E-01 4.35E-01 9.79E-01 3.76E-01 2.35E+00 4.04E+00 NA NA NA NA NA NA MW-31-63 MW-31-63 012 63.3 12.3 10/30/2008 12:14 2.30E+04 1.08E+03 1.73E+02 2.28E-01 2.33E-01 2.52E-01 2.21E+00 6.18E+00 7.37E+00

-1.47E+00 7.26E+00 7.77E+00 NA NA NA MW-31-63 MW-31-63 013 63.3 12.3 11/18/2008 11:58 2.55E+04 8.07E+02 1.84E+02 3.95E-01 7.40E-01 8.36E-01 1.02E-02 5.89E+00 6.01E+00

-5.18E-01 6.54E+00 6.97E+00 NA NA NA MW-31-63 MW-31-63 014 63.3 12.3 2/6/2009 11:53 1.28E+04 8.39E+02 1.97E+02 6.43E-01 6.42E-01 6.82E-01

-1.32E+00 3.42E+00 3.63E+00

-7.48E-01 3.86E+00 4.17E+00 NA NA NA MW-31-63 MW-31-63 015 63.3 12.3 4/14/2009 12:07 3.24E+04 1.10E+03 1.48E+02 2.95E-01 6.81E-01 7.75E-01 1.76E+00 6.68E+00 4.45E+00 2.23E+00 3.87E+00 4.79E+00 NA NA NA MW-31-63 MW-31-63 016 63.3 12.3 5/29/2009 12:34 3.16E+04 9.51E+02 1.95E+02 5.59E-01 5.58E-01 6.07E-01 1.79E+00 1.07E+01 7.12E+00 7.44E-01 6.45E+00 7.35E+00 NA NA NA MW-31-63 MW-31-63 017 63.3 12.3 7/21/2009 12:50 1.45E+04 8.28E+02 2.31E+02 1.95E-01 7.52E-01 9.11E-01 3.48E-01 3.90E+00 4.37E+00

-1.56E+00 3.88E+00 3.75E+00 NA NA NA MW-31-63 MW-31-63 018 63.3 12.3 9/1/2009 10:50 1.41E+04 5.09E+02 2.13E+02 1.51E-01 3.55E-01 4.13E-01

-1.38E+00 6.76E+00 6.17E+00 6.92E-01 5.01E+00 5.74E+00 NA NA NA MW-31-63 MW-31-63 019 63.3 12.3 9/14/2009 12:45 1.41E+04 5.48E+02 1.55E+02 8.11E-01 8.72E-01 9.25E-01

-1.96E+00 4.75E+00 5.05E+00

-1.40E+00 5.87E+00 6.29E+00 NA NA NA MW-31-63 MW-31-63 020 63.3 12.3 10/22/2009 13:20 2.00E+04 5.85E+02 1.67E+02 1.10E+00 7.45E-01 7.37E-01 1.92E-01 5.92E+00 6.75E+00 2.27E+00 6.42E+00 7.79E+00 NA NA NA MW-31-63 MW-31-63 021 63.3 12.3 1/26/2010 13:08 3.36E+04 2.21E+03 6.66E+02 5.46E-01 8.55E-01 9.50E-01 1.63E+00 3.12E+00 3.68E+00

-1.56E+00 3.36E+00 3.52E+00 NA NA NA MW-31-63 MW-31-63 022 63.3 12.3 3/5/2010 12:17 7.35E+04 1.11E+03 1.72E+02 1.20E-01 3.38E-01 4.02E-01 2.57E+00 4.49E+00 5.38E+00

-3.85E+00 4.62E+00 4.24E+00 NA NA NA MW-31-63 MW-31-63 023 63.3 12.3 4/14/2010 13:05 1.84E+04 5.46E+02 1.08E+02

-1.50E-01 4.43E-01 6.61E-01

-4.58E+00 9.18E+00 9.12E+00 2.75E-01 9.97E+00 1.12E+01 NA NA NA MW-31-63 MW-31-63 024 63.3 12.3 6/7/2010 12:19 5.11E+04 1.53E+03 2.93E+02 3.68E-01 8.04E-01 9.11E-01 2.95E+00 5.94E+00 7.20E+00 9.47E-01 6.12E+00 7.09E+00 NA NA NA MW-31-63 MW-31-63 025 63.3 12.3 7/27/2010 15:54 6.17E+04 1.80E+03 1.27E+02 5.31E-01 6.45E-01 6.89E-01

-1.81E+00 8.27E+00 8.91E+00 1.22E+00 7.33E+00 8.70E+00 NA NA NA MW-31-63 MW-31-63 026 63.3 12.3 8/23/2010 13:11 6.69E+04 1.95E+03 1.60E+02 4.60E-01 7.62E-01 8.48E-01 1.77E+00 6.11E+00 7.13E+00

-1.67E+00 6.17E+00 6.44E+00 NA NA NA MW-31-63 MW-31-63 027 63.3 12.3 9/7/2010 15:28 4.65E+04 1.41E+03 1.46E+02 3.99E-01 7.26E-01 8.18E-01 4.05E-01 4.75E+00 5.31E+00

-1.47E+00 5.45E+00 5.56E+00 NA NA NA MW-31-63 MW-31-63 028 63.3 12.3 11/3/2010 12:32 2.95E+04 9.02E+02 1.14E+02 3.31E-01 6.30E-01 7.13E-01

-2.24E+00 9.63E+00 1.02E+01 3.44E+00 8.40E+00 1.07E+01 NA NA NA MW-31-63 MW-31-63 029 63.3 12.3 2/9/2011 13:14 2.46E+04 1.10E+03 2.98E+02 4.29E-01 1.78E+00 2.08E+00

-1.42E+00 6.46E+00 6.81E+00

-2.31E+00 6.42E+00 6.26E+00 NA NA NA MW-31-63 MW-31-63 030 63.3 12.3 3/30/2011 13:13 1.33E+04 1.14E+03 4.53E+02 1.49E+00 1.87E+00 2.02E+00 8.76E-01 9.00E+00 9.97E+00

-1.92E-01 7.26E+00 7.92E+00 NA NA NA MW-31-63 MW-31-63 031 63.3 12.3 4/18/2011 13:21 1.81E+04 1.45E+03 4.67E+02 7.26E-01 1.84E+00 2.08E+00

-3.10E-01 7.62E+00 8.46E+00 1.76E+00 8.74E+00 1.03E+01 NA NA NA MW-31-63 MW-31-63 033 63.3 12.3 8/5/2011 11:29 1.63E+04 1.31E+03 4.18E+02

-1.30E-01 1.71E+00 2.02E+00

-2.83E-01 9.87E+00 1.12E+01 2.13E+00 9.24E+00 1.08E+01 NA NA NA MW-31-63 MW-31-63 034 63.3 12.3 11/21/2011 11:14 7.23E+03 9.00E+02 2.36E+02 1.36E+00 1.42E+00 1.40E+00

-2.72E+00 9.45E+00 1.09E+01 2.93E+00 8.19E+00 1.20E+01 NA NA NA MW-31-63 MW-31-85 001 84.8

-9.2 11/27/2006 12:20 4.62E+02 1.74E+02 1.70E+02 1.50E-01 1.44E+00 1.60E+00 1.52E+02 8.40E+00 3.20E+00 2.10E-01 2.19E+00 2.50E+00 2.20E+01 9.30E+01 1.00E+02 MW-31-85 MW-31-85 002 84.8

-9.2 1/18/2007 9:16 2.66E+03 6.00E+02 5.20E+02

-5.90E-01 1.59E+00 1.80E+00

-4.90E+00 8.70E+00 1.00E+01

-6.00E-01 8.70E+00 1.00E+01 8.35E+00 2.11E+01 2.39E+01 MW-31-85 MW-31-85 003 84.8

-9.2 6/12/2007 14:05 3.17E+02 1.62E+02 1.69E+02

-3.83E-01 6.62E-01 9.31E-01 3.95E-01 2.76E+00 1.91E+00

-5.71E-01 1.69E+00 1.83E+00 NA NA NA MW-31-85 MW-31-85 004 84.8

-9.2 8/2/2007 10:58 2.69E+03 7.11E+02 5.31E+02

-7.29E-01 6.31E-01 9.31E-01

-5.01E-02 3.29E+00 3.59E+00

-1.90E+00 3.35E+00 3.31E+00 NA NA NA MW-31-85 MW-31-85 005 84.8

-9.2 9/11/2007 13:20 4.32E+03 3.32E+02 1.82E+02 6.86E-01 7.48E-01 7.93E-01

-7.04E-01 3.04E+00 3.26E+00

-3.07E+00 3.68E+00 3.24E+00 NA NA NA MW-31-85 MW-31-85 006 84.8

-9.2 10/24/2007 14:40 5.51E+03 8.15E+02 3.98E+02 2.53E-01 4.08E-01 4.51E-01 5.68E-01 2.90E+00 3.38E+00 4.76E-01 2.75E+00 3.19E+00 NA NA NA MW-31-85 MW-31-85 007 84.8

-9.2 1/16/2008 11:26 1.31E+03 2.81E+02 1.84E+02 6.97E-01 7.67E-01 7.79E-01 2.68E+00 4.05E+00 4.83E+00 1.90E+00 3.80E+00 4.62E+00 NA NA NA MW-31-85 MW-31-85 009 84.8

-9.2 6/6/2008 15:26 5.95E+03 6.30E+02 5.05E+02 1.52E-01 3.17E-01 5.69E-01

-8.07E-01 2.20E+00 3.45E+00 1.91E+00 2.45E+00 4.58E+00 NA NA NA MW-31-85 MW-31-85 010 84.8

-9.2 8/7/2008 11:13 2.30E+03 1.83E+02 1.94E+02 1.07E-01 2.87E-01 5.30E-01

-6.47E-01 1.22E+00 1.94E+00 1.63E-02 1.31E+00 2.18E+00 NA NA NA MW-31-85 MW-31-85 011 84.8

-9.2 8/30/2008 12:08 8.34E+03 7.00E+02 5.52E+02 4.46E-01 4.87E-01 8.10E-01

-5.50E-01 1.86E+00 3.07E+00 NA NA NA NA NA NA MW-31-85 MW-31-85 012 84.8

-9.2 10/30/2008 12:09 3.89E+03 4.52E+02 1.67E+02 4.08E-01 7.33E-01 8.25E-01

-5.63E+00 6.17E+00 4.73E+00

-4.82E+00 6.98E+00 6.56E+00 NA NA NA MW-31-85 MW-31-85 013 84.8

-9.2 11/18/2008 12:00 4.41E+03 2.97E+02 1.61E+02

-2.44E-01 5.37E-01 8.11E-01 2.13E+00 3.79E+00 4.76E+00 2.84E+00 3.82E+00 5.19E+00 NA NA NA MW-31-85 MW-31-85 014 84.8

-9.2 2/6/2009 11:22 7.37E+03 6.54E+02 2.02E+02 3.89E-01 5.58E-01 6.16E-01 1.22E+00 3.50E+00 4.06E+00 1.09E+00 3.57E+00 4.23E+00 NA NA NA MW-31-85 MW-31-85 015 84.8

-9.2 4/14/2009 11:41 1.88E+04 8.49E+02 1.50E+02 5.35E-01 7.01E-01 7.64E-01

-6.49E-01 5.24E+00 3.49E+00 1.11E+00 3.50E+00 4.14E+00 NA NA NA MW-31-85 MW-31-85 016 84.8

-9.2 5/29/2009 12:50 8.85E+03 1.09E+03 3.75E+02 1.84E-01 8.01E-01 9.30E-01 8.20E-01 1.04E+01 6.95E+00 6.97E-01 6.57E+00 7.51E+00 NA NA NA MW-31-85 MW-31-85 017 84.8

-9.2 7/21/2009 12:13 2.96E+03 4.10E+02 2.29E+02

-2.28E-01 5.61E-01 8.08E-01

-2.54E+00 5.04E+00 4.22E+00 2.26E+00 3.71E+00 4.75E+00 NA NA NA MW-31-85 MW-31-85 018 84.8

-9.2 9/1/2009 10:52 3.52E+03 3.00E+02 2.12E+02 4.12E-01 6.15E-01 6.81E-01

-8.48E-01 4.46E+00 4.89E+00

-5.30E-03 6.12E+00 6.86E+00 NA NA NA MW-31-85 MW-31-85 019 84.8

-9.2 9/14/2009 12:05 5.14E+03 3.48E+02 1.56E+02

-4.43E-01 4.92E-01 8.14E-01

-1.68E-01 4.96E+00 5.62E+00

-2.91E-01 5.13E+00 5.72E+00 NA NA NA MW-31-85

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 3 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-31-85 020 84.8

-9.2 10/22/2009 12:54 4.50E+03 3.06E+02 1.67E+02 5.53E-01 6.67E-01 7.18E-01 3.27E-01 6.72E+00 6.89E+00 1.12E+00 6.11E+00 7.07E+00 NA NA NA MW-31-85 MW-31-85 021 84.8

-9.2 1/26/2010 12:08 2.25E+04 1.83E+03 6.64E+02

-3.53E-01 7.18E-01 9.43E-01 5.22E-01 2.96E+00 3.33E+00 1.51E+00 2.96E+00 3.49E+00 NA NA NA MW-31-85 MW-31-85 022 84.8

-9.2 3/5/2010 11:49 2.69E+03 2.52E+02 1.68E+02 1.39E-01 3.31E-01 3.88E-01 1.93E+00 4.34E+00 5.05E+00 4.48E-01 4.46E+00 5.01E+00 NA NA NA MW-31-85 MW-31-85 023 84.8

-9.2 4/14/2010 12:09 4.85E+03 2.60E+02 9.99E+01

-1.42E-01 4.23E-01 6.36E-01 3.84E+00 6.90E+00 8.60E+00 1.40E-01 6.13E+00 6.84E+00 NA NA NA MW-31-85 MW-31-85 024 84.8

-9.2 6/7/2010 12:00 9.34E+03 4.35E+02 2.13E+02 3.29E-01 5.73E-01 6.43E-01 2.30E+00 4.86E+00 5.78E+00

-1.07E+00 4.70E+00 4.81E+00 NA NA NA MW-31-85 MW-31-85 025 84.8

-9.2 7/27/2010 15:22 6.70E+03 4.34E+02 1.00E+02 3.55E-01 4.72E-01 5.04E-01

-3.98E+00 8.82E+00 9.22E+00 2.50E+00 8.43E+00 9.93E+00 NA NA NA MW-31-85 MW-31-85 026 84.8

-9.2 8/23/2010 12:10 5.07E+03 3.96E+02 1.25E+02 6.61E-03 7.89E-01 9.16E-01 3.42E+00 4.95E+00 6.08E+00 1.52E+00 4.77E+00 5.71E+00 NA NA NA MW-31-85 MW-31-85 027 84.8

-9.2 9/7/2010 14:14 6.21E+03 5.24E+02 1.44E+02

-3.25E-01 4.45E-01 6.85E-01

-1.54E+00 5.68E+00 6.11E+00 2.71E+00 6.42E+00 7.79E+00 NA NA NA MW-31-85 MW-31-85 028 84.8

-9.2 11/3/2010 12:00 6.06E+03 4.16E+02 1.14E+02 2.41E-01 4.83E-01 5.47E-01

-1.36E+00 8.88E+00 9.62E+00

-2.66E-01 1.08E+01 1.19E+01 NA NA NA MW-31-85 MW-31-85 029 84.8

-9.2 2/9/2011 13:03 4.83E+03 6.84E+02 3.82E+02 3.26E-01 1.79E+00 2.18E+00 3.19E+00 5.96E+00 7.08E+00 3.14E+00 6.06E+00 7.39E+00 NA NA NA MW-31-85 MW-31-85 030 84.8

-9.2 3/30/2011 12:55 7.75E+02 4.66E+02 4.52E+02 9.37E-01 1.81E+00 2.00E+00 5.90E+00 1.31E+01 8.10E+00 6.43E+00 8.88E+00 1.17E+01 NA NA NA MW-31-85 MW-31-85 031 84.8

-9.2 4/18/2011 13:18 3.08E+03 6.96E+02 4.66E+02

-1.09E+00 1.46E+00 2.09E+00

-4.50E+00 9.34E+00 9.19E+00 3.84E+00 1.01E+01 1.22E+01 NA NA NA MW-31-85 MW-31-85 033 84.8

-9.2 8/5/2011 11:27 4.82E+03 7.74E+02 4.22E+02 1.39E-01 1.40E+00 1.63E+00

-8.79E-01 8.25E+00 8.80E+00

-4.79E+00 9.57E+00 8.27E+00 NA NA NA MW-31-85 MW-31-85 034 84.8

-9.2 11/21/2011 11:25 5.49E+03 6.33E+02 3.45E+02 9.56E-01 1.41E+00 1.50E+00

-3.23E+00 9.21E+00 1.04E+01

-6.05E-01 9.57E+00 1.22E+01 NA NA NA MW-31-85 MW-32-48 005 NA NA 3/4/2010 13:16 4.52E+04 7.44E+02 1.68E+02 1.02E-01 7.47E-01 9.27E-01

-1.65E-01 3.88E+00 4.41E+00

-5.57E-01 4.11E+00 4.54E+00 NA NA NA MW-32-48 MW-32-48 006 NA NA 4/28/2010 11:28 6.18E+04 1.80E+03 1.79E+02 7.51E-01 8.02E-01 8.21E-01 3.11E+00 7.80E+00 7.62E+00 1.38E+00 6.18E+00 7.26E+00 NA NA NA MW-32-48 MW-32-48 007 NA NA 7/27/2010 12:52 3.69E+03 3.26E+02 9.94E+01 3.59E-01 8.37E-01 9.60E-01 1.54E-01 7.00E+00 8.04E+00

-3.86E+00 7.74E+00 7.51E+00 NA NA NA MW-32-48 MW-32-48 008 NA NA 8/24/2010 14:03 5.90E+03 3.51E+02 2.10E+02 3.55E-01 6.33E-01 7.09E-01

-4.34E-01 4.49E+00 5.04E+00 1.96E+00 4.95E+00 5.95E+00 NA NA NA MW-32-48 MW-32-59 001 58.8 18.3 1/19/2007 9:30 7.67E+03 7.50E+02 5.20E+02 6.30E-01 1.47E+00 1.60E+00

-8.60E-01 1.98E+00 2.30E+00 4.90E-01 2.28E+00 2.60E+00 NA NA NA MW-32-59 MW-32-59 002 58.8 18.3 6/28/2007 14:25 2.40E+04 7.37E+02 1.97E+02

-1.65E-01 5.90E-01 7.97E-01

-1.74E+00 3.51E+00 3.30E+00

-1.42E+00 3.87E+00 3.34E+00 NA NA NA MW-32-59 MW-32-59 003 58.8 18.3 8/13/2007 13:07 1.42E+04 6.00E+02 1.99E+02

-2.71E-01 5.58E-01 7.58E-01 1.48E+00 2.10E+00 3.22E+00

-4.66E-01 3.30E+00 3.65E+00 NA NA NA MW-32-59 MW-32-59 001 58.8 18.3 10/26/2007 12:07 1.11E+04 4.61E+02 1.84E+02 3.22E-01 6.43E-01 7.36E-01

-1.94E-01 3.82E+00 3.87E+00 2.45E+00 3.06E+00 4.08E+00 NA NA NA MW-32-59 MW-32-59 002 58.8 18.3 1/18/2008 13:25 1.87E+04 9.11E+02 1.86E+02 4.67E-01 6.96E-01 7.57E-01 9.98E-01 4.25E+00 4.79E+00 1.99E+00 3.81E+00 4.65E+00 NA NA NA MW-32-59 MW-32-59 003 58.8 18.3 5/5/2008 15:33 4.15E+03 2.01E+02 1.82E+02 7.61E-02 5.20E-01 9.70E-01

-7.05E-01 1.89E+00 3.05E+00 1.25E+00 2.01E+00 3.77E+00 NA NA NA MW-32-59 MW-32-59 004 58.8 18.3 6/9/2008 12:10 2.85E+03 4.81E+02 5.06E+02

-3.39E-01 3.64E-01 7.61E-01

-1.22E+00 1.94E+00 2.98E+00

-7.10E-01 2.43E+00 3.91E+00 NA NA NA MW-32-59 MW-32-59 005 58.8 18.3 7/31/2008 13:23 1.54E+03 1.63E+02 1.94E+02 1.72E-01 3.81E-01 6.90E-01 4.66E-01 1.97E+00 3.33E+00

-1.08E+00 2.48E+00 3.26E+00 NA NA NA MW-32-59 MW-32-59 006 58.8 18.3 9/2/2008 13:52 2.44E+03 4.59E+02 5.53E+02 2.19E-01 5.54E-01 9.94E-01 7.77E-01 1.85E+00 3.21E+00 NA NA NA NA NA NA MW-32-59 MW-32-59 007 58.8 18.3 10/24/2008 13:59 4.13E+02 2.00E+02 1.73E+02 1.63E-01 6.06E-01 7.44E-01

-3.50E-01 7.51E+00 7.30E+00

-1.32E+00 6.29E+00 6.66E+00 NA NA NA MW-32-59 MW-32-59 008 58.8 18.3 2/4/2009 15:46 1.78E+04 1.03E+03 1.98E+02

-1.01E-01 5.73E-01 7.69E-01 1.01E-01 3.54E+00 3.41E+00 2.70E+00 3.41E+00 4.34E+00 NA NA NA MW-32-59 MW-32-59 009 58.8 18.3 4/27/2009 15:54 6.43E+04 3.00E+03 4.23E+02 4.22E-01 6.15E-01 6.76E-01

-3.21E+00 4.83E+00 3.22E+00

-5.75E-02 3.60E+00 4.11E+00 NA NA NA MW-32-59 MW-32-59 010 58.8 18.3 6/2/2009 13:59 6.69E+03 9.60E+02 3.77E+02 3.26E-01 4.73E-01 5.25E-01

-1.72E-01 9.62E+00 6.41E+00

-7.66E-01 5.63E+00 6.03E+00 NA NA NA MW-32-59 MW-32-59 011 58.8 18.3 8/3/2009 15:04 8.85E+02 2.07E+02 1.55E+02 1.87E-02 6.37E-01 7.81E-01 1.61E-01 5.47E+00 6.24E+00 9.57E-01 5.47E+00 6.44E+00 NA NA NA MW-32-59 MW-32-59 012 58.8 18.3 8/31/2009 13:24 1.86E+04 5.93E+02 2.16E+02 1.76E-02 3.29E-01 4.26E-01 4.57E-02 4.61E+00 5.09E+00

-2.25E+00 5.87E+00 5.60E+00 NA NA NA MW-32-59 MW-32-59 013 58.8 18.3 9/15/2009 14:33 5.92E+03 3.69E+02 1.55E+02

-4.42E-01 6.95E-01 9.02E-01 1.35E+00 4.70E+00 5.40E+00

-1.17E-01 5.10E+00 5.67E+00 NA NA NA MW-32-59 MW-32-59 014 58.8 18.3 10/22/2009 13:37 5.61E+03 3.33E+02 1.66E+02

-5.42E-01 6.48E-01 9.80E-01 5.15E-01 5.36E+00 6.05E+00

-3.05E+00 7.18E+00 7.04E+00 NA NA NA MW-32-59 MW-32-59 015 58.8 18.3 1/28/2010 14:01 8.92E+04 3.45E+03 6.39E+02 4.07E-02 3.15E-01 4.04E-01 1.02E+00 4.07E+00 4.72E+00 3.06E+00 3.93E+00 4.92E+00 NA NA NA MW-32-59 MW-32-59 016 58.8 18.3 3/4/2010 13:23 8.81E+04 1.03E+03 1.67E+02 1.51E-01 6.31E-01 7.80E-01 6.65E-01 5.36E+00 4.46E+00

-1.40E+00 5.22E+00 4.34E+00 NA NA NA MW-32-59 MW-32-59 017 58.8 18.3 4/28/2010 11:30 6.83E+04 2.00E+03 1.88E+02

-3.10E-01 3.61E-01 6.30E-01 4.95E+00 4.86E+00 6.21E+00 1.55E+00 4.86E+00 5.81E+00 NA NA NA MW-32-59 MW-32-59 018 58.8 18.3 6/9/2010 14:53 1.55E+05 4.58E+03 4.89E+02 4.10E-01 7.75E-01 8.75E-01

-9.71E-01 6.12E+00 6.76E+00 1.48E+00 6.66E+00 7.93E+00 NA NA NA MW-32-59 MW-32-59 019 58.8 18.3 7/27/2010 13:00 6.54E+04 1.91E+03 1.33E+02 1.50E-01 4.37E-01 5.21E-01 1.07E+00 1.02E+01 1.14E+01 3.80E+00 9.26E+00 1.21E+01 NA NA NA MW-32-59 MW-32-59 020 58.8 18.3 8/24/2010 14:22 5.78E+03 3.48E+02 2.10E+02

-9.82E-02 6.14E-01 8.32E-01 3.21E+00 5.84E+00 7.14E+00

-2.01E+00 6.60E+00 6.75E+00 NA NA NA MW-32-59 MW-32-59 021 58.8 18.3 9/9/2010 13:57 7.44E+04 2.18E+03 1.67E+02 4.21E-01 7.20E-01 8.03E-01 1.68E+00 5.43E+00 6.39E+00

-1.58E+00 5.38E+00 5.54E+00 NA NA NA MW-32-59 MW-32-59 022 58.8 18.3 11/3/2010 12:08 1.58E+04 6.66E+02 1.16E+02 2.02E-01 6.15E-01 7.14E-01 6.67E+00 7.98E+00 1.03E+01 1.19E+00 9.11E+00 1.06E+01 NA NA NA MW-32-59 MW-32-59 023 58.8 18.3 3/1/2011 11:28 4.39E+03 6.42E+02 3.59E+02 1.25E+00 1.49E+00 1.55E+00 6.56E-01 5.82E+00 6.63E+00

-4.41E-01 7.00E+00 7.58E+00 NA NA NA MW-32-59 MW-32-59 024 58.8 18.3 3/31/2011 12:46 3.37E+04 1.96E+03 5.07E+02

-2.13E-01 1.15E+00 1.51E+00 8.24E-01 8.92E+00 9.96E+00 1.99E-02 1.02E+01 1.11E+01 NA NA NA MW-32-59 MW-32-59 025 58.8 18.3 4/27/2011 12:26 3.31E+03 6.36E+02 4.08E+02 4.03E-01 1.50E+00 1.74E+00 4.77E+00 8.64E+00 1.04E+01

-3.37E+00 9.58E+00 9.50E+00 NA NA NA MW-32-59 MW-32-59 027 58.8 18.3 8/5/2011 12:30 2.06E+04 1.47E+03 4.19E+02 1.64E+00 1.66E+00 1.71E+00

-3.73E+00 8.34E+00 8.04E+00

-1.05E+00 8.79E+00 9.24E+00 NA NA NA MW-32-59 MW-32-59 028 58.8 18.3 11/17/2011 14:15 2.91E+04 1.74E+03 2.26E+02

-1.28E+00 1.58E+00 2.33E+00

-3.91E+00 1.01E+01 1.18E+01

-1.58E+00 9.84E+00 1.21E+01 NA NA NA MW-32-59 MW-32-85 001 85.3 85.3 1/19/2007 9:40 1.12E+04 8.40E+02 5.30E+02 3.20E-01 1.47E+00 1.60E+00 1.57E+00 2.82E+00 3.10E+00 9.00E-01 4.20E+00 4.80E+00 NA NA NA MW-32-85 MW-32-85 002 85.3 85.3 6/28/2007 15:05 5.42E+03 3.77E+02 1.95E+02

-4.15E-01 5.10E-01 6.75E-01

-1.70E-01 2.77E+00 3.03E+00

-3.05E-01 3.19E+00 3.21E+00 NA NA NA MW-32-85 MW-32-85 003 85.3 85.3 8/13/2007 10:48 5.70E+03 4.05E+02 2.01E+02

-2.45E-02 4.47E-01 5.75E-01 3.28E-01 2.81E+00 3.15E+00 9.90E-01 2.98E+00 3.53E+00 NA NA NA MW-32-85 MW-32-85 004 85.3 85.3 10/26/2007 11:12 1.26E+04 4.79E+02 1.79E+02

-1.17E-01 4.27E-01 6.25E-01 8.85E-01 2.97E+00 3.45E+00

-1.85E-02 3.23E+00 3.63E+00 NA NA NA MW-32-85 MW-32-85 005 85.3 85.3 1/18/2008 14:50 1.07E+04 6.90E+02 1.83E+02

-3.03E-01 4.38E-01 7.35E-01 3.57E-01 2.64E+00 2.67E+00

-5.37E-01 1.97E+00 2.13E+00 NA NA NA MW-32-85 MW-32-85 006 85.3 85.3 5/5/2008 14:10 8.36E+03 2.64E+02 1.81E+02

-6.65E-02 3.89E-01 7.59E-01 1.95E+00 2.16E+00 3.96E+00

-3.64E-01 2.06E+00 3.27E+00 NA NA NA MW-32-85 MW-32-85 007 85.3 85.3 6/9/2008 12:25 1.11E+04 8.21E+02 5.04E+02

-9.56E-02 3.57E-01 7.12E-01 1.39E+00 2.01E+00 3.68E+00

-5.47E-01 2.04E+00 3.34E+00 NA NA NA MW-32-85 MW-32-85 008 85.3 85.3 7/31/2008 14:35 7.48E+03 2.83E+02 1.93E+02 1.16E-01 3.35E-01 6.24E-01 2.14E-01 2.06E+00 3.50E+00 1.07E+00 1.88E+00 3.43E+00 NA NA NA MW-32-85 MW-32-85 009 85.3 85.3 9/2/2008 14:40 8.05E+03 6.90E+02 5.52E+02 1.42E-01 4.15E-01 7.65E-01

-1.37E+00 2.45E+00 3.52E+00 NA NA NA NA NA NA MW-32-85 MW-32-85 010 85.3 85.3 10/24/2008 14:50 8.62E+03 6.66E+02 1.72E+02 1.13E-01 4.56E-01 5.68E-01 1.39E+00 5.78E+00 6.62E+00 3.08E+00 5.89E+00 7.32E+00 NA NA NA MW-32-85 MW-32-85 011 85.3 85.3 2/4/2009 15:49 6.54E+03 6.38E+02 1.98E+02 5.26E-01 7.76E-01 8.50E-01 4.88E-01 2.85E+00 3.31E+00 2.27E+00 3.20E+00 4.15E+00 NA NA NA MW-32-85 MW-32-85 012 85.3 85.3 4/27/2009 15:34 8.87E+03 1.17E+03 4.31E+02 1.21E-01 5.33E-01 6.47E-01

-2.07E+00 6.11E+00 4.07E+00 1.69E+00 4.08E+00 4.90E+00 NA NA NA MW-32-85 MW-32-85 013 85.3 85.3 6/2/2009 15:11 8.07E+03 1.04E+03 3.76E+02

-1.55E-01 6.47E-01 7.60E-01

-1.73E+00 1.30E+01 8.65E+00 8.98E-01 8.75E+00 9.91E+00 NA NA NA MW-32-85 MW-32-85 015 85.3 85.3 8/31/2009 14:11 8.98E+03 4.22E+02 2.14E+02 4.28E-02 7.57E-01 9.24E-01 8.15E-01 5.03E+00 5.69E+00

-4.97E+00 5.84E+00 5.36E+00 NA NA NA MW-32-85 MW-32-85 016 85.3 85.3 9/15/2009 15:06 7.70E+03 4.17E+02 1.57E+02 1.08E-01 6.03E-01 7.16E-01 2.26E+00 4.83E+00 5.66E+00

-4.65E+00 5.54E+00 5.03E+00 NA NA NA MW-32-85 MW-32-85 017 85.3 85.3 10/22/2009 13:53 7.80E+03 3.83E+02 1.66E+02 1.01E-02 4.27E-01 5.44E-01 1.58E+00 1.11E+01 5.84E+00

-2.02E+00 6.51E+00 6.87E+00 NA NA NA MW-32-85 MW-32-85 018 85.3 85.3 1/28/2010 14:38 8.03E+03 1.11E+03 4.26E+02 6.86E-01 8.28E-01 8.91E-01 2.21E+00 3.65E+00 4.30E+00 2.29E+00 3.27E+00 4.05E+00 NA NA NA MW-32-85 MW-32-85 019 85.3 85.3 3/4/2010 14:44 9.31E+03 3.62E+02 1.68E+02

-2.46E-01 4.71E-01 7.01E-01 3.62E-01 3.45E+00 3.85E+00

-1.26E+00 3.88E+00 4.04E+00 NA NA NA MW-32-85 MW-32-85 020 85.3 85.3 4/28/2010 13:08 1.15E+04 5.85E+02 1.45E+02 3.95E-02 6.03E-01 7.62E-01 7.18E-01 9.07E+00 9.43E+00 1.03E+00 6.79E+00 8.05E+00 NA NA NA MW-32-85 MW-32-85 021 85.3 85.3 6/9/2010 12:03 1.20E+04 4.85E+02 2.14E+02 3.30E-01 7.56E-01 8.66E-01

-1.92E+00 5.57E+00 6.05E+00

-7.73E-01 5.68E+00 6.30E+00 NA NA NA MW-32-85 MW-32-85 022 85.3 85.3 7/27/2010 14:51 1.21E+04 5.81E+02 1.01E+02 3.80E-01 6.37E-01 7.07E-01 1.38E+00 7.47E+00 8.69E+00 2.30E+00 7.74E+00 9.52E+00 NA NA NA MW-32-85 MW-32-85 023 85.3 85.3 8/24/2010 11:03 1.38E+04 4.94E+02 2.10E+02

-3.76E-01 4.75E-01 7.02E-01

-6.66E-01 5.96E+00 6.62E+00

-1.19E+00 5.22E+00 5.48E+00 NA NA NA MW-32-85 MW-32-85 024 85.3 85.3 9/9/2010 15:29 1.44E+04 6.57E+02 1.27E+02 1.34E-01 6.77E-01 8.36E-01 1.43E+00 6.27E+00 6.90E+00

-1.25E-01 5.49E+00 6.10E+00 NA NA NA MW-32-85 MW-32-85 025 85.3 85.3 11/3/2010 12:45 1.49E+04 6.48E+02 1.16E+02 3.80E-01 4.90E-01 5.36E-01 5.89E+00 9.60E+00 1.18E+01

-5.55E+00 8.71E+00 7.61E+00 NA NA NA MW-32-85 MW-32-85 026 85.3 85.3 3/1/2011 12:05 1.34E+04 1.41E+03 2.62E+02 3.81E-01 1.41E+00 1.63E+00 7.79E-01 8.26E+00 9.36E+00 4.73E+00 9.72E+00 1.24E+01 NA NA NA MW-32-85 MW-32-85 027 85.3 85.3 3/31/2011 13:18 1.32E+04 1.27E+03 5.07E+02

-1.62E-01 1.20E+00 1.56E+00

-6.56E-01 7.26E+00 7.61E+00 3.80E+00 8.28E+00 1.02E+01 NA NA NA MW-32-85 MW-32-85 028 85.3 85.3 4/27/2011 13:04 1.14E+04 1.19E+03 5.10E+02 1.58E+00 1.69E+00 1.75E+00

-1.23E+00 6.80E+00 7.31E+00 5.30E-01 1.02E+01 1.15E+01 NA NA NA MW-32-85 MW-32-85 030 85.3 85.3 8/5/2011 13:36 1.14E+04 1.12E+03 4.20E+02 1.14E-01 1.64E+00 1.92E+00 5.40E+00 6.87E+00 8.79E+00

-1.21E+00 6.69E+00 6.57E+00 NA NA NA MW-32-85

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 4 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-32-85 031 85.3 85.3 11/17/2011 15:08 8.88E+03 7.65E+02 3.42E+02 4.57E-01 1.56E+00 1.82E+00

-1.20E+00 7.38E+00 8.80E+00

-1.88E+00 9.06E+00 1.09E+01 NA NA NA MW-32-85 MW-32-131 001 130.8

-53.7 1/19/2007 9:45 1.13E+04 8.40E+02 5.30E+02

-1.03E+00 1.47E+00 1.70E+00

-6.00E-02 2.04E+00 2.30E+00 3.00E-02 2.07E+00 2.40E+00 NA NA NA MW-32-131 MW-32-131 002 130.8

-53.7 6/28/2007 12:45 3.02E+02 1.88E+02 1.97E+02

-1.39E-01 5.13E-01 5.94E-01

-1.46E+00 5.09E+00 4.92E+00 9.88E-01 3.76E+00 4.38E+00 NA NA NA MW-32-131 MW-32-131 003 130.8

-53.7 8/13/2007 11:15 1.29E+02 1.70E+02 1.87E+02 2.69E-01 7.33E-01 8.51E-01

-8.09E-01 4.86E+00 4.85E+00

-1.19E+00 3.29E+00 3.22E+00 NA NA NA MW-32-131 MW-32-131 004 130.8

-53.7 10/26/2007 10:11 3.74E+02 2.39E+02 2.42E+02 2.47E-01 6.03E-01 7.06E-01

-1.81E-01 3.48E+00 3.82E+00

-2.55E-01 3.92E+00 3.99E+00 NA NA NA MW-32-131 MW-32-131 005 130.8

-53.7 1/18/2008 11:23 5.04E+02 2.07E+02 1.79E+02 5.14E-01 7.79E-01 8.52E-01 8.47E-01 2.19E+00 2.21E+00

-8.40E-02 1.98E+00 2.18E+00 NA NA NA MW-32-131 MW-32-131 006 130.8

-53.7 5/5/2008 12:35 1.03E+03 1.36E+02 1.83E+02

-2.89E-01 3.98E-01 7.75E-01

-1.21E+00 2.28E+00 3.55E+00

-3.26E-01 2.27E+00 3.66E+00 NA NA NA MW-32-131 MW-32-149 004 149.3

-72.2 10/26/2007 10:10 2.92E+03 2.94E+02 1.90E+02

-2.45E-01 4.89E-01 7.22E-01 1.99E-01 3.10E+00 3.51E+00 1.65E-01 3.56E+00 3.99E+00 NA NA NA MW-32-149 MW-32-149 005 149.3

-72.2 1/18/2008 11:18 1.15E+03 2.69E+02 1.85E+02 3.04E-01 8.25E-01 9.53E-01 2.94E+00 4.29E+00 3.08E+00

-8.74E-01 2.82E+00 2.93E+00 NA NA NA MW-32-149 MW-32-149 006 149.3

-72.2 5/5/2008 10:54 8.83E+02 1.31E+02 1.82E+02 7.39E-01 5.05E-01 7.94E-01

-2.99E+00 2.67E+00 3.71E+00 2.04E+00 2.12E+00 4.12E+00 NA NA NA MW-32-149 MW-32-149 007 149.3

-72.2 7/31/2008 11:10 5.32E+02 1.31E+02 1.94E+02 1.38E-02 3.46E-01 6.80E-01 1.06E+00 1.65E+00 2.87E+00 1.42E+00 1.56E+00 2.81E+00 NA NA NA MW-32-149 MW-32-149 008 149.3

-72.2 10/24/2008 10:28 5.03E+02 2.10E+02 1.72E+02 4.69E-01 6.52E-01 6.99E-01 1.80E+00 5.22E+00 6.07E+00 1.25E+00 4.96E+00 5.82E+00 NA NA NA MW-32-149 MW-32-149 009 149.3

-72.2 2/4/2009 13:50 2.65E+02 1.18E+02 1.17E+02 4.53E-01 6.75E-01 7.34E-01 5.44E-01 2.99E+00 3.38E+00 3.32E-01 2.91E+00 3.28E+00 NA NA NA MW-32-149 MW-32-149 010 149.3

-72.2 4/27/2009 13:31 3.21E+02 1.79E+02 1.87E+02 7.04E-01 8.48E-01 9.20E-01 1.35E+00 4.26E+00 2.84E+00

-4.83E-02 2.34E+00 2.57E+00 NA NA NA MW-32-149 MW-32-149 011 149.3

-72.2 6/2/2009 12:05 2.24E+02 1.53E+02 1.62E+02

-2.86E-01 6.60E-01 7.98E-01

-2.68E+00 1.02E+01 6.78E+00 2.12E+00 7.04E+00 8.40E+00 NA NA NA MW-32-149 MW-32-149 012 149.3

-72.2 8/3/2009 12:43 3.90E+02 1.70E+02 1.57E+02 9.42E-02 6.51E-01 7.80E-01 2.86E+00 6.63E+00 7.79E+00

-9.46E-01 8.14E+00 7.75E+00 NA NA NA MW-32-149 MW-32-149 013 149.3

-72.2 8/31/2009 11:29 4.57E+02 2.06E+02 2.15E+02

-2.81E-01 5.05E-01 6.80E-01

-1.45E+00 5.66E+00 6.05E+00

-1.77E-01 4.84E+00 5.32E+00 NA NA NA MW-32-149 MW-32-149 014 149.3

-72.2 9/15/2009 12:39 1.99E+02 1.46E+02 1.54E+02

-9.07E-02 7.77E-01 9.52E-01 1.03E+00 5.91E+00 6.65E+00 2.31E+00 6.12E+00 7.24E+00 NA NA NA MW-32-149 MW-32-149 015 149.3

-72.2 10/22/2009 15:39 2.95E+02 1.59E+02 1.67E+02

-9.56E-02 4.01E-01 5.33E-01

-6.75E+00 9.40E+00 7.45E+00

-5.88E-01 8.74E+00 8.40E+00 NA NA NA MW-32-149 MW-32-149 016 149.3

-72.2 1/28/2010 11:47 5.28E+03 9.24E+02 4.30E+02 2.02E-01 7.48E-01 8.83E-01 2.15E+00 3.71E+00 4.43E+00 4.50E-01 4.17E+00 4.73E+00 NA NA NA MW-32-149 MW-32-149 017 149.3

-72.2 4/28/2010 13:50 6.60E+03 4.52E+02 1.47E+02 3.03E-01 7.08E-01 8.24E-01 1.98E+00 6.88E+00 7.55E+00 9.80E-01 4.44E+00 5.36E+00 NA NA NA MW-32-149 MW-32-149 018 149.3

-72.2 6/9/2010 12:52 9.76E+03 4.44E+02 2.14E+02

-1.16E-01 6.45E-01 8.05E-01

-8.57E-01 8.36E+00 9.08E+00

-4.49E+00 6.20E+00 5.62E+00 NA NA NA MW-32-149 MW-32-149 019 149.3

-72.2 7/27/2010 15:34 3.81E+03 3.33E+02 1.01E+02 1.14E-01 3.57E-01 4.33E-01 7.24E-01 1.28E+01 1.64E+01 1.53E+00 8.88E+00 1.06E+01 NA NA NA MW-32-149 MW-32-149 020 149.3

-72.2 8/24/2010 11:27 2.60E+03 2.70E+02 2.10E+02 1.04E-01 6.64E-01 8.13E-01 1.04E-01 6.51E+00 7.44E+00 2.67E-02 5.89E+00 6.71E+00 NA NA NA MW-32-149 MW-32-149 021 149.3

-72.2 9/9/2010 11:36 2.12E+03 2.70E+02 1.27E+02 2.27E-01 7.72E-01 9.22E-01 3.68E+00 7.83E+00 9.16E+00 1.24E+00 8.52E+00 1.00E+01 NA NA NA MW-32-149 MW-32-149 022 149.3

-72.2 11/3/2010 16:09 1.55E+03 2.24E+02 1.12E+02 4.08E-01 5.02E-01 5.49E-01

-1.00E+01 1.08E+01 1.15E+01 3.36E+00 7.71E+00 9.94E+00 NA NA NA MW-32-149 MW-32-149 023 149.3

-72.2 3/1/2011 13:37 1.06E+03 4.48E+02 2.68E+02

-7.01E-01 1.66E+00 2.15E+00 9.25E-01 5.42E+00 6.30E+00 2.06E+00 6.60E+00 7.93E+00 NA NA NA MW-32-149 MW-32-149 024 149.3

-72.2 3/31/2011 11:33 8.99E+02 5.34E+02 5.09E+02

-2.01E-01 1.10E+00 1.49E+00 2.52E+00 9.30E+00 1.09E+01 2.31E+00 9.92E+00 1.18E+01 NA NA NA MW-32-149 MW-32-149 025 149.3

-72.2 4/27/2011 11:12 8.69E+02 4.44E+02 4.11E+02 3.00E-01 1.43E+00 1.67E+00 2.12E+00 7.44E+00 8.59E+00 9.88E-01 7.76E+00 8.83E+00 NA NA NA MW-32-149 MW-32-149 027 149.3

-72.2 8/5/2011 11:10 9.86E+02 4.71E+02 4.21E+02 4.80E-01 1.81E+00 2.06E+00

-9.94E-01 9.60E+00 9.39E+00 2.75E+00 7.41E+00 9.28E+00 NA NA NA MW-32-149 MW-32-149 028 149.3

-72.2 11/17/2011 12:05 5.91E+02 3.45E+02 3.41E+02 3.84E-01 1.46E+00 1.72E+00

-5.25E+00 7.74E+00 7.86E+00 2.57E+00 8.07E+00 1.12E+01 NA NA NA MW-32-149 MW-32-165 001 163

-85.9 1/19/2007 9:50 1.05E+04 8.70E+02 5.70E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-32-165 MW-32-165 002 163

-85.9 6/28/2007 13:06 5.81E+02 2.03E+02 1.97E+02

-2.82E-01 7.33E-01 9.70E-01 8.54E-01 2.85E+00 2.94E+00

-8.16E-01 2.46E+00 2.60E+00 NA NA NA MW-32-165 MW-32-165 003 163

-85.9 8/13/2007 11:35 4.93E+02 2.09E+02 2.08E+02

-6.38E-01 3.81E-01 6.52E-01

-1.42E+00 3.76E+00 3.37E+00 1.63E+00 1.69E+00 2.91E+00 NA NA NA MW-32-165 MW-32-173 001 172.8

-95.7 10/26/2007 9:55 5.89E+03 3.87E+02 1.92E+02 1.86E-02 5.87E-01 7.54E-01 6.92E-01 3.00E+00 3.51E+00

-9.97E-01 2.91E+00 3.02E+00 NA NA NA MW-32-173 MW-32-173 002 172.8

-95.7 1/18/2008 11:05 3.40E+03 4.07E+02 1.82E+02 1.13E-01 6.02E-01 7.63E-01

-3.84E-01 2.00E+00 2.18E+00

-6.14E-01 2.09E+00 2.25E+00 NA NA NA MW-32-173 MW-32-173 003 172.8

-95.7 5/5/2008 10:33 1.69E+03 1.52E+02 1.82E+02 1.11E-02 3.53E-01 7.09E-01 1.95E-01 2.18E+00 3.64E+00 5.47E-01 2.24E+00 3.91E+00 NA NA NA MW-32-173 MW-32-173 004 172.8

-95.7 7/31/2008 10:52 1.08E+03 1.48E+02 1.92E+02 6.80E-01 4.52E-01 7.11E-01

-1.17E+00 1.58E+00 2.47E+00 6.06E-01 1.65E+00 2.96E+00 NA NA NA MW-32-173 MW-32-173 005 172.8

-95.7 9/2/2008 11:30 9.72E+02 3.72E+02 5.48E+02 1.85E-01 4.64E-01 8.41E-01

-1.02E+00 2.67E+00 3.88E+00 NA NA NA NA NA NA MW-32-173 MW-32-173 006 172.8

-95.7 10/24/2008 10:25 1.03E+03 2.67E+02 1.74E+02 1.05E-01 3.60E-01 4.36E-01 8.63E-01 5.67E+00 6.61E+00 2.30E+00 6.36E+00 7.74E+00 NA NA NA MW-32-173 MW-32-173 007 172.8

-95.7 2/4/2009 13:40 7.56E+02 1.45E+02 1.17E+02 2.57E-01 4.26E-01 4.74E-01 1.79E+00 3.65E+00 4.41E+00 2.56E+00 3.47E+00 4.49E+00 NA NA NA MW-32-173 MW-32-173 008 172.8

-95.7 4/27/2009 13:32 7.86E+02 4.77E+02 4.31E+02 7.47E-02 4.43E-01 5.48E-01

-3.20E+00 6.12E+00 4.08E+00 1.19E+00 4.77E+00 5.59E+00 NA NA NA MW-32-173 MW-32-173 009 172.8

-95.7 6/2/2009 11:58 1.72E+03 2.19E+02 1.68E+02 1.05E-01 5.78E-01 6.69E-01

-1.33E+00 9.20E+00 6.13E+00

-1.40E+00 6.21E+00 6.55E+00 NA NA NA MW-32-173 MW-32-173 010 172.8

-95.7 8/3/2009 12:37 4.93E+02 1.77E+02 1.55E+02

-4.67E-02 3.89E-01 5.13E-01 3.21E+00 5.34E+00 6.46E+00

-7.71E-01 4.92E+00 5.26E+00 NA NA NA MW-32-173 MW-32-173 011 172.8

-95.7 8/31/2009 11:31 5.79E+02 2.09E+02 2.13E+02

-4.09E-04 6.06E-01 7.50E-01 1.81E+00 4.96E+00 5.93E+00 2.58E+00 6.62E+00 7.35E+00 NA NA NA MW-32-173 MW-32-173 012 172.8

-95.7 9/15/2009 12:11 4.71E+02 1.65E+02 1.55E+02

-5.93E-03 6.73E-01 8.21E-01 2.46E+00 4.92E+00 5.83E+00

-6.66E+00 7.39E+00 6.57E+00 NA NA NA MW-32-173 MW-32-173 013 172.8

-95.7 10/22/2009 15:36 4.31E+02 1.68E+02 1.68E+02

-1.01E-02 3.85E-01 4.95E-01

-2.49E-01 5.87E+00 6.61E+00 6.81E-01 5.70E+00 6.64E+00 NA NA NA MW-32-173 MW-32-173 014 172.8

-95.7 1/28/2010 11:42 1.33E+03 6.95E+02 6.63E+02 1.67E-01 7.37E-01 8.74E-01

-4.48E+00 7.32E+00 7.64E+00 2.11E+00 4.42E+00 5.30E+00 NA NA NA MW-32-173 MW-32-173 015 172.8

-95.7 4/28/2010 15:45 1.54E+03 2.45E+02 1.48E+02 4.63E-01 5.34E-01 5.49E-01 4.96E+00 5.45E+00 6.79E+00

-8.08E-01 4.93E+00 5.21E+00 NA NA NA MW-32-173 MW-32-173 016 172.8

-95.7 6/9/2010 12:23 2.34E+03 2.66E+02 2.08E+02 3.04E-01 5.97E-01 6.81E-01

-9.18E-01 6.63E+00 7.29E+00 8.09E-01 6.48E+00 7.43E+00 NA NA NA MW-32-173 MW-32-173 017 172.8

-95.7 7/27/2010 15:17 2.47E+03 2.69E+02 9.88E+01 9.64E-02 3.38E-01 4.14E-01

-1.51E+00 8.71E+00 9.65E+00

-2.29E+00 7.04E+00 7.12E+00 NA NA NA MW-32-173 MW-32-173 018 172.8

-95.7 8/24/2010 11:23 2.19E+03 2.60E+02 2.10E+02

-1.37E-01 3.98E-01 5.77E-01 2.92E+00 6.57E+00 7.82E+00 4.56E-01 6.55E+00 7.41E+00 NA NA NA MW-32-173 MW-32-173 019 172.8

-95.7 9/9/2010 11:29 1.98E+03 2.63E+02 1.28E+02 5.82E-01 8.34E-01 8.96E-01 1.67E+00 4.86E+00 5.81E+00 9.94E-01 4.84E+00 5.77E+00 NA NA NA MW-32-173 MW-32-173 020 172.8

-95.7 11/3/2010 15:53 1.40E+03 2.16E+02 1.14E+02 1.65E-02 4.38E-01 5.24E-01 3.87E+00 1.76E+01 9.62E+00

-2.94E+00 9.88E+00 1.01E+01 NA NA NA MW-32-173 MW-32-173 021 172.8

-95.7 3/1/2011 13:13 9.02E+02 4.12E+02 2.61E+02

-4.04E-01 1.12E+00 1.45E+00 5.99E+00 6.06E+00 7.73E+00

-2.04E+00 7.36E+00 7.55E+00 NA NA NA MW-32-173 MW-32-173 022 172.8

-95.7 3/31/2011 11:35 8.41E+02 5.22E+02 5.04E+02 2.46E-01 1.27E+00 1.54E+00 6.51E+00 1.58E+01 8.26E+00 2.19E+00 8.22E+00 9.98E+00 NA NA NA MW-32-173 MW-32-173 023 172.8

-95.7 4/27/2011 11:27 5.82E+02 4.98E+02 5.08E+02 6.37E-01 1.54E+00 1.74E+00 0.00E+00 2.00E+01 9.23E+00 2.47E-01 9.58E+00 1.07E+01 NA NA NA MW-32-173 MW-32-173 025 172.8

-95.7 8/5/2011 11:11 5.69E+02 4.17E+02 4.12E+02 6.34E-01 1.48E+00 1.66E+00

-9.50E-01 6.36E+00 6.56E+00

-1.55E+00 1.10E+01 1.14E+01 NA NA NA MW-32-173 MW-32-173 026 172.8

-95.7 11/17/2011 12:01 5.06E+02 3.33E+02 3.34E+02 7.83E-02 9.63E-01 1.24E+00 2.87E+00 9.12E+00 1.13E+01

-1.50E-01 9.93E+00 1.26E+01 NA NA NA MW-32-173 MW-32-190 001 190.3

-113.7 1/19/2007 9:55 1.13E+04 8.40E+02 5.20E+02 4.20E-01 1.50E+00 1.70E+00 2.60E-01 1.26E+00 1.40E+00 7.10E-01 1.50E+00 1.70E+00 NA NA NA MW-32-190 MW-32-190 002 190.3

-113.7 6/28/2007 13:07 2.41E+03 2.72E+02 1.87E+02

-5.09E-02 6.12E-01 8.20E-01 1.52E+00 3.07E+00 3.64E+00

-1.29E+00 3.27E+00 3.37E+00 NA NA NA MW-32-190 MW-32-190 003 190.3

-113.7 8/13/2007 11:25 1.72E+03 2.67E+02 2.03E+02

-3.65E-01 8.12E-01 1.04E+00 6.21E-01 2.49E+00 2.93E+00

-1.19E+00 2.38E+00 2.39E+00 NA NA NA MW-32-190 MW-32-190 004 190.3

-113.7 10/26/2007 9:53 9.76E+03 4.80E+02 1.93E+02

-5.05E-01 7.75E-01 9.73E-01

-6.17E-01 3.07E+00 3.27E+00

-1.94E-01 3.18E+00 3.57E+00 NA NA NA MW-32-190 MW-32-190 005 190.3

-113.7 1/18/2008 11:35 8.89E+03 6.32E+02 1.83E+02 4.28E-01 7.73E-01 8.69E-01 6.57E-01 1.71E+00 2.02E+00 5.18E-01 1.65E+00 1.96E+00 NA NA NA MW-32-190 MW-32-190 006 190.3

-113.7 5/5/2008 10:57 6.73E+03 2.41E+02 1.82E+02

-1.68E-01 4.28E-01 8.16E-01

-1.18E+00 2.08E+00 3.24E+00

-2.62E+00 3.16E+00 2.97E+00 NA NA NA MW-32-190 MW-32-190 007 190.3

-113.7 7/31/2008 11:24 4.71E+03 2.35E+02 1.94E+02 3.21E-01 3.35E-01 5.51E-01

-8.54E-01 1.55E+00 2.53E+00 2.22E+00 1.77E+00 3.30E+00 NA NA NA MW-32-190 MW-32-190 008 190.3

-113.7 9/2/2008 11:40 3.81E+03 5.20E+02 5.44E+02 5.92E-01 5.81E-01 9.53E-01 1.39E+00 2.82E+00 4.63E+00 NA NA NA NA NA NA MW-32-190 MW-32-190 009 190.3

-113.7 10/24/2008 10:31 3.35E+03 4.31E+02 1.73E+02 3.30E-03 5.75E-01 7.41E-01 5.89E-01 5.33E+00 5.98E+00 3.85E+00 5.68E+00 7.16E+00 NA NA NA MW-32-190 MW-32-190 010 190.3

-113.7 2/4/2009 13:45 2.69E+03 4.26E+02 1.98E+02 2.44E-01 5.57E-01 6.47E-01 3.60E-02 2.67E+00 2.95E+00 4.71E-01 3.02E+00 3.44E+00 NA NA NA MW-32-190 MW-32-190 011 190.3

-113.7 4/27/2009 13:24 2.54E+03 6.68E+02 4.09E+02

-2.51E-02 5.58E-01 6.80E-01

-6.89E-01 4.01E+00 2.67E+00 5.11E-01 2.30E+00 2.68E+00 NA NA NA MW-32-190 MW-32-190 012 190.3

-113.7 6/2/2009 12:01 1.95E+03 5.76E+02 3.78E+02 8.61E-02 5.09E-01 5.90E-01 3.64E-01 1.02E+01 6.77E+00 1.26E+00 5.70E+00 6.67E+00 NA NA NA MW-32-190 MW-32-190 013 190.3

-113.7 8/3/2009 12:45 2.03E+03 2.76E+02 1.56E+02 1.36E-01 5.64E-01 6.69E-01 9.65E-02 5.25E+00 5.81E+00

-2.59E+00 4.95E+00 4.66E+00 NA NA NA MW-32-190 MW-32-190 014 190.3

-113.7 8/31/2009 11:41 2.14E+03 2.61E+02 2.13E+02 1.65E-01 5.30E-01 6.20E-01 2.01E+00 6.21E+00 7.34E+00 2.09E+00 5.91E+00 7.13E+00 NA NA NA MW-32-190 MW-32-190 015 190.3

-113.7 9/15/2009 12:13 1.77E+03 2.28E+02 1.53E+02 3.73E-01 7.22E-01 8.16E-01 1.75E+00 4.04E+00 4.89E+00 4.08E-01 4.59E+00 5.13E+00 NA NA NA MW-32-190 MW-32-190 016 190.3

-113.7 10/22/2009 15:30 1.63E+03 2.18E+02 1.67E+02 8.62E-02 3.60E-01 4.39E-01

-1.67E+00 6.11E+00 6.45E+00 3.05E-01 5.96E+00 6.67E+00 NA NA NA MW-32-190 MW-32-190 017 190.3

-113.7 1/28/2010 11:57 1.71E+03 5.91E+02 4.25E+02 4.33E-01 4.97E-01 5.09E-01

-1.94E-02 4.23E+00 4.80E+00 1.29E+00 4.62E+00 5.46E+00 NA NA NA MW-32-190

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 5 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-32-190 018 190.3

-113.7 3/4/2010 12:42 1.98E+03 2.10E+02 1.67E+02 4.99E-03 5.73E-01 7.52E-01

-6.41E-01 3.29E+00 3.70E+00 3.53E+00 3.74E+00 4.67E+00 NA NA NA MW-32-190 MW-32-190 019 190.3

-113.7 4/28/2010 15:51 1.59E+03 2.48E+02 1.49E+02

-2.92E-01 7.01E-01 9.85E-01 1.82E+00 5.66E+00 6.65E+00

-2.37E+00 5.38E+00 5.33E+00 NA NA NA MW-32-190 MW-32-190 020 190.3

-113.7 6/9/2010 12:43 1.76E+03 2.45E+02 2.05E+02 4.69E-01 8.43E-01 9.49E-01

-3.64E+00 5.89E+00 6.02E+00 1.50E+00 5.84E+00 6.92E+00 NA NA NA MW-32-190 MW-32-190 021 190.3

-113.7 7/27/2010 15:41 1.58E+03 2.21E+02 9.83E+01

-8.57E-02 3.52E-01 5.06E-01 6.23E-01 7.98E+00 9.16E+00

-2.62E+00 7.77E+00 7.60E+00 NA NA NA MW-32-190 MW-32-190 022 190.3

-113.7 8/24/2010 11:37 1.69E+03 2.43E+02 2.09E+02 2.54E-01 7.84E-01 9.25E-01

-5.47E-01 4.84E+00 5.45E+00 9.00E-01 4.96E+00 5.87E+00 NA NA NA MW-32-190 MW-32-190 023 190.3

-113.7 9/9/2010 11:34 1.65E+03 2.48E+02 1.30E+02

-1.31E-01 5.85E-01 8.27E-01

-2.39E-01 9.87E+00 1.08E+01 2.00E+00 6.66E+00 7.98E+00 NA NA NA MW-32-190 MW-32-190 024 190.3

-113.7 11/3/2010 16:07 1.53E+03 2.28E+02 1.17E+02

-9.74E-02 4.35E-01 5.82E-01 2.12E+00 9.02E+00 1.07E+01

-2.40E+00 9.21E+00 9.36E+00 NA NA NA MW-32-190 MW-32-190 025 190.3

-113.7 3/1/2011 13:24 1.64E+03 5.32E+02 2.64E+02 7.65E-01 1.20E+00 1.29E+00 2.74E+00 5.52E+00 6.57E+00 4.88E+00 7.64E+00 8.75E+00 NA NA NA MW-32-190 MW-32-190 026 190.3

-113.7 3/31/2011 11:47 1.41E+03 5.76E+02 5.02E+02

-7.79E-01 1.15E+00 1.67E+00 8.78E-01 7.96E+00 9.01E+00 5.11E+00 1.04E+01 1.30E+01 NA NA NA MW-32-190 MW-32-190 027 190.3

-113.7 4/27/2011 11:17 1.21E+03 5.64E+02 5.10E+02 7.54E-01 1.13E+00 1.20E+00 8.61E-01 8.68E+00 9.74E+00

-6.60E+00 8.98E+00 6.37E+00 NA NA NA MW-32-190 MW-32-190 029 190.3

-113.7 8/5/2011 11:15 1.44E+03 5.16E+02 4.20E+02 7.59E-01 1.64E+00 1.82E+00 2.02E+00 7.23E+00 8.43E+00 1.28E+00 9.24E+00 1.06E+01 NA NA NA MW-32-190 MW-32-190 030 190.3

-113.7 11/17/2011 12:03 1.46E+03 4.05E+02 3.36E+02

-7.57E-01 8.37E-01 1.41E+00 1.30E+00 6.57E+00 8.59E+00

-4.42E-01 6.24E+00 7.93E+00 NA NA NA MW-32-190 MW-33 001 19.2

-0.4 12/15/2005 8:00 1.42E+05 4.26E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-33 MW-33 002 19.2

-0.4 12/19/2005 11:38 1.99E+05 5.97E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-33 MW-33 003 19.2

-0.4 12/29/2005 11:30 2.20E+05 6.60E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-33 MW-33 004 19.2

-0.4 1/6/2006 12:30 1.89E+05 5.67E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-33 MW-33 005 19.2

-0.4 1/13/2006 12:10 2.32E+05 6.96E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-33 MW-33 006 19.2

-0.4 1/20/2006 10:40 2.26E+05 6.78E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-33 MW-33 007 19.2

-0.4 1/27/2006 11:10 2.42E+05 7.26E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-33 MW-33 008 19.2

-0.4 2/3/2006 12:15 2.50E+05 2.84E+04 6.33E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-33 MW-33 009 19.2

-0.4 2/7/2006 16:00 2.14E+05 2.64E+04 6.37E+02 1.36E-01 5.06E-01 6.25E-01 NA NA NA NA NA NA NA NA NA MW-33 MW-33 010 19.2

-0.4 2/16/2006 13:55 2.61E+05 2.91E+04 6.36E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-33 MW-33 011 19.2

-0.4 3/3/2006 10:20 2.53E+05 7.59E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-33 MW-33 012 19.2

-0.4 4/7/2006 10:25 2.21E+05 6.63E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-33 MW-33 014 19.2

-0.4 5/17/2006 12:50 1.35E+05 2.01E+04 1.60E+03 7.79E-01 1.43E+00 1.47E+00 1.17E+01 1.19E+01 1.37E+01 4.62E+00 1.41E+01 1.28E+01 NA NA NA MW-33 MW-33 015 19.2

-0.4 6/7/2006 10:15 1.41E+05 1.85E+04 1.32E+03 6.74E-01 5.63E-01 6.44E-01 6.95E-01 8.72E+00 9.58E+00

-6.11E+00 8.63E+00 8.02E+00 NA NA NA MW-33 MW-33 017 19.2

-0.4 7/3/2006 9:50 2.64E+05 2.01E+04 3.85E+03 4.78E-01 1.37E+00 1.57E+00

-6.85E-01 1.17E+01 1.27E+01

-5.24E+00 1.28E+01 1.21E+01 NA NA NA MW-33 MW-33 018 19.2

-0.4 8/4/2006 8:15 1.84E+05 2.54E+04 1.87E+03 NA NA NA 3.53E+00 6.31E+00 7.84E+00

-1.14E+00 7.35E+00 8.60E+00 NA NA NA MW-33 MW-33 019 19.2

-0.4 8/30/2006 13:00 1.15E+05 1.77E+04 4.39E+03 NA NA NA

-6.99E-01 8.47E+00 8.90E+00 3.71E+00 7.21E+00 9.60E+00 NA NA NA MW-33 MW-33 020 19.2

-0.4 6/15/2007 15:48 9.06E+04 3.26E+03 3.61E+02

-2.82E-01 2.86E-01 4.85E-01

-2.78E-01 3.82E+00 3.76E+00

-1.64E+00 3.44E+00 3.39E+00

-8.12E-01 1.16E+01 1.37E+01 MW-33 MW-33 021 19.2

-0.4 8/3/2007 10:20 2.30E+04 7.08E+02 2.04E+02 5.80E-01 8.49E-01 9.33E-01 8.18E-01 2.37E+00 2.83E+00 2.45E-01 2.13E+00 2.46E+00 NA NA NA MW-33 MW-33 022 19.2

-0.4 4/28/2008 15:00 5.85E+04 1.16E+03 2.58E+02 1.69E-01 2.97E-01 5.22E-01 1.08E-01 1.87E+00 3.12E+00

-4.51E-02 2.12E+00 3.49E+00 NA NA NA MW-33 MW-33 023 19.2

-0.4 9/4/2008 14:41 6.80E+04 1.82E+03 5.47E+02 1.33E-01 4.05E-01 7.55E-01 5.46E-01 1.61E+00 2.83E+00 NA NA NA NA NA NA MW-33 MW-33 024 19.2

-0.4 4/29/2009 15:12 3.44E+04 1.30E+03 1.72E+02 2.74E-01 5.39E-01 6.09E-01

-1.06E+00 8.93E+00 5.95E+00 1.83E+00 5.72E+00 6.77E+00 NA NA NA MW-33 MW-33 025 19.2

-0.4 2/2/2010 13:15 3.20E+04 2.16E+03 4.38E+02

-1.15E-01 7.38E-01 9.21E-01 2.64E+00 3.44E+00 4.21E+00 4.59E-01 3.96E+00 4.42E+00 NA NA NA MW-33 MW-33 026 19.2

-0.4 4/15/2010 13:54 6.31E+04 1.06E+03 1.76E+02

-1.77E-01 6.60E-01 8.85E-01

-3.35E+00 7.39E+00 7.21E+00

-5.17E+00 7.74E+00 6.17E+00 NA NA NA MW-33 MW-33 027 19.2

-0.4 8/30/2010 14:29 3.69E+03 3.42E+02 1.26E+02 1.64E-01 3.24E-01 3.69E-01 7.72E-01 5.64E+00 6.38E+00

-3.08E-01 5.07E+00 5.60E+00 NA NA NA MW-33 MW-33 028 19.2

-0.4 9/11/2010 13:28 3.86E+03 3.53E+02 1.27E+02 9.96E-03 7.38E-01 9.28E-01

-1.30E+00 4.86E+00 5.14E+00 1.12E+00 5.10E+00 5.95E+00 NA NA NA MW-33 MW-34 001 18.9

-0.4 12/13/2005 13:53 6.39E+04 1.92E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-34 MW-34 002 18.9

-0.4 12/19/2005 10:35 1.21E+05 3.63E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-34 MW-34 003 18.9

-0.4 12/29/2005 10:50 1.47E+05 4.41E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-34 MW-34 004 18.9

-0.4 1/6/2006 11:35 1.59E+05 4.77E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-34 MW-34 005 18.9

-0.4 1/13/2006 11:40 1.31E+05 3.93E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-34 MW-34 006 18.9

-0.4 1/20/2006 10:00 2.11E+05 6.33E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-34 MW-34 007 18.9

-0.4 1/27/2006 10:50 2.12E+05 6.36E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-34 MW-34 008 18.9

-0.4 2/3/2006 12:20 2.24E+05 2.69E+04 6.33E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-34 MW-34 009 18.9

-0.4 2/7/2006 15:15 1.74E+05 2.38E+04 6.37E+02 9.22E-02 3.78E-01 4.67E-01 NA NA NA NA NA NA NA NA NA MW-34 MW-34 010 18.9

-0.4 2/16/2006 13:55 1.99E+05 2.55E+04 6.36E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-34 MW-34 011 18.9

-0.4 3/3/2006 9:35 2.30E+05 6.90E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-34 MW-34 012 18.9

-0.4 4/7/2006 10:05 2.76E+05 8.28E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-34 MW-34 013 18.9

-0.4 5/17/2006 13:15 3.64E+04 5.52E+03 8.35E+02 2.50E-02 6.63E-01 9.24E-01 7.84E+00 1.39E+01 1.55E+01 2.72E+00 1.31E+01 1.44E+01 NA NA NA MW-34 MW-34 014 18.9

-0.4 6/26/2006 10:20 1.05E+04 8.52E+02 3.41E+02 3.71E-01 6.49E-01 7.79E-01 1.83E+00 7.85E+00 8.96E+00 5.84E+00 7.34E+00 9.37E+00 NA NA NA MW-34 MW-34 015 18.9

-0.4 7/26/2006 10:20 4.07E+04 3.51E+03 1.57E+03 2.18E-01 8.97E-01 1.16E+00

-1.73E-01 4.87E+00 5.24E+00

-2.54E-01 5.64E+00 6.78E+00 NA NA NA MW-34 MW-34 016 18.9

-0.4 8/24/2006 12:18 6.69E+04 1.05E+04 3.39E+03 NA NA NA 1.62E+00 5.81E+00 6.78E+00

-1.60E+00 5.89E+00 5.85E+00 NA NA NA MW-34 MW-34 017 18.9

-0.4 9/21/2006 9:45 1.61E+04 2.78E+03 5.86E+02 0.00E+00 1.12E+00 1.31E+00 6.09E-02 1.69E+00 1.85E+00

-2.10E-01 1.65E+00 1.79E+00 NA NA NA MW-34 MW-34 018 18.9

-0.4 8/3/2007 10:21 2.22E+04 7.44E+02 2.13E+02 3.94E-02 7.08E-01 9.04E-01

-1.55E+00 4.53E+00 4.44E+00 2.12E+00 3.40E+00 4.01E+00 NA NA NA MW-34 MW-35 001 19

-0.4 12/13/2005 13:50 4.23E+04 3.18E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-35 MW-35 002 19

-0.4 12/19/2005 10:17 7.60E+04 2.28E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-35 MW-35 003 19

-0.4 12/29/2005 10:00 8.05E+04 2.42E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-35 MW-35 004 19

-0.4 1/6/2006 11:10 9.54E+04 2.86E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-35 MW-35 005 19

-0.4 1/13/2006 10:50 9.78E+04 2.93E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-35 MW-35 006 19

-0.4 1/20/2006 9:30 1.04E+05 3.12E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-35 MW-35 007 19

-0.4 1/27/2006 11:00 3.87E+04 1.16E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-35 MW-35 008 19

-0.4 2/3/2006 12:20 5.14E+04 1.29E+04 6.33E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-35 MW-35 009 19

-0.4 2/7/2006 14:40 8.44E+04 1.66E+04 6.37E+02 1.62E-01 4.32E-01 5.28E-01 NA NA NA NA NA NA NA NA NA MW-35 MW-35 010 19

-0.4 2/16/2006 13:30 9.04E+04 1.72E+04 6.36E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-35 MW-35 011 19

-0.4 3/3/2006 9:05 1.19E+05 3.57E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-35 MW-35 012 19

-0.4 4/7/2006 9:55 5.62E+04 1.69E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-35 MW-35 013 19

-0.4 5/17/2006 13:37 4.07E+04 6.15E+03 8.72E+02 4.70E-01 7.53E-01 7.87E-01 6.46E+00 2.07E+01 1.64E+01 3.04E+00 1.37E+01 1.53E+01 NA NA NA MW-35 MW-35 014 19

-0.4 6/26/2006 10:40 1.74E+04 1.37E+03 4.29E+02

-2.30E-01 6.66E-01 8.69E-01

-1.34E+00 1.01E+01 1.09E+01

-2.45E+00 8.92E+00 9.36E+00 NA NA NA MW-35 MW-35 015 19

-0.4 9/21/2006 9:30 4.53E+04 7.19E+03 9.12E+02 6.26E-01 1.30E+00 1.41E+00

-3.15E-01 1.96E+00 1.82E+00 2.44E-01 1.49E+00 1.69E+00 NA NA NA MW-35 MW-35 016 19

-0.4 6/15/2007 13:58 2.03E+03 5.87E+02 3.84E+02 2.26E-01 4.34E-01 4.91E-01 4.66E+01 8.82E+00 2.81E+00

-1.27E+00 2.58E+00 2.63E+00 6.18E+00 1.92E+01 2.20E+01 MW-35 MW-35 017 19

-0.4 8/3/2007 10:22 5.95E+03 5.58E+02 2.70E+02 9.45E-02 5.76E-01 6.98E-01

-9.20E-01 2.71E+00 2.82E+00 5.74E-01 2.88E+00 3.33E+00 NA NA NA MW-35 MW-35 018 19

-0.4 4/28/2008 13:38 1.04E+03 1.77E+02 2.19E+02 2.34E-01 2.96E-01 5.03E-01

-2.93E-02 2.03E+00 3.34E+00

-5.77E-02 2.36E+00 3.87E+00 NA NA NA MW-35 MW-35 019 19

-0.4 4/30/2009 11:17 1.46E+03 3.03E+02 1.74E+02

-2.75E-01 5.13E-01 6.38E-01

-1.08E+00 9.27E+00 6.18E+00

-1.87E+00 5.79E+00 6.00E+00 NA NA NA MW-35 MW-35 020 19

-0.4 5/20/2010 13:25 2.82E+03 2.87E+02 2.14E+02

-1.97E-01 4.52E-01 6.73E-01 1.51E+00 5.67E+00 6.71E+00

-1.24E+00 6.33E+00 6.84E+00 NA NA NA MW-35

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 6 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-36-24 001 16.1

-4.3 2/7/2006 17:00 NA NA NA 1.29E+00 5.48E-01 5.53E-01 NA NA NA NA NA NA NA NA NA MW-36-24 MW-36-24 002 16.1

-4.3 2/27/2006 9:45 3.04E+04 9.95E+03 6.36E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-36-24 MW-36-24 003 16.1

-4.3 3/23/2006 16:00 3.42E+04 3.81E+03 1.86E+03 9.99E-01 6.42E-01 6.42E-01

-3.86E+00 1.01E+01 1.05E+01 5.02E+00 9.33E+00 1.22E+01 6.41E+01 1.59E+01 1.53E+01 MW-36-24 MW-36-24 004 16.1

-4.3 4/5/2006 10:30 NA NA NA 1.56E+00 4.86E-01 4.35E-01 NA NA NA NA NA NA NA NA NA MW-36-24 MW-36-24 005 16.1

-4.3 6/5/2006 12:20 2.02E+02 1.59E+02 1.51E+02 3.70E-01 7.66E-01 9.31E-01 3.99E+00 1.03E+01 1.21E+01 6.90E-02 1.02E+01 1.12E+01 NA NA NA MW-36-24 MW-36-24 006 16.1

-4.3 8/28/2006 10:30 2.45E+02 1.80E+02 1.71E+02 NA NA NA

-1.04E+00 3.27E+00 3.32E+00 1.66E+00 3.06E+00 4.19E+00 NA NA NA MW-36-24 MW-36-24 007 16.1

-4.3 6/27/2007 10:40 1.54E+02 1.76E+02 1.93E+02 5.90E-01 7.92E-01 8.46E-01 3.31E-01 2.81E+00 3.17E+00 4.00E-01 3.03E+00 3.45E+00 NA NA NA MW-36-24 MW-36-24 008 16.1

-4.3 8/8/2007 13:45 1.63E+02 1.85E+02 2.04E+02

-5.35E-01 6.81E-01 9.31E-01 1.53E-01 3.40E+00 3.77E+00 3.56E+00 3.40E+00 4.17E+00

-7.46E+00 2.10E+01 2.54E+01 MW-36-24 MW-36-24 009 16.1

-4.3 10/18/2007 10:06 2.86E+02 1.91E+02 2.01E+02 8.56E-02 7.60E-01 9.26E-01 7.20E-01 2.91E+00 3.37E+00 3.11E-01 3.01E+00 3.47E+00 NA NA NA MW-36-24 MW-36-24 010 16.1

-4.3 1/23/2008 14:18 2.16E+03 2.36E+02 1.70E+02 1.03E-01 3.12E-01 3.76E-01 2.92E-02 2.39E+00 2.67E+00

-4.84E-01 2.37E+00 2.57E+00 NA NA NA MW-36-24 MW-36-24 011 16.1

-4.3 7/24/2008 13:57 1.02E+03 1.22E+02 1.63E+02 3.38E-01 3.75E-01 6.24E-01 3.97E-01 2.09E+00 3.61E+00

-5.45E-01 2.37E+00 3.85E+00 NA NA NA MW-36-24 MW-36-24 012 16.1

-4.3 11/10/2008 15:33 2.01E+02 1.50E+02 1.61E+02 5.52E-01 7.53E-01 8.04E-01 0.00E+00 6.81E+00 4.46E+00 2.72E+00 3.84E+00 5.41E+00 NA NA NA MW-36-24 MW-36-24 013 16.1

-4.3 1/22/2009 12:48 2.37E+02 1.16E+02 1.06E+02

-6.26E-01 7.37E-01 9.48E-01 5.41E-01 2.88E+00 3.34E+00 3.15E-01 3.35E+00 3.82E+00 NA NA NA MW-36-24 MW-36-24 014 16.1

-4.3 5/1/2009 13:55 4.98E+02 1.98E+02 1.62E+02

-1.28E-01 7.22E-01 8.58E-01 1.20E+00 7.73E+00 5.15E+00

-8.11E-01 4.19E+00 4.36E+00 NA NA NA MW-36-24 MW-36-24 015 16.1

-4.3 8/4/2009 16:09 2.92E+03 3.20E+02 1.55E+02 4.60E-01 6.62E-01 7.29E-01

-2.97E-01 5.12E+00 4.98E+00 7.76E-01 5.67E+00 6.40E+00 NA NA NA MW-36-24 MW-36-24 016 16.1

-4.3 10/28/2009 15:48 1.47E+03 2.00E+02 1.61E+02 6.36E-01 8.91E-01 9.78E-01

-9.30E-01 3.65E+00 4.03E+00

-3.01E-01 4.86E+00 5.04E+00 NA NA NA MW-36-24 MW-36-24 017 16.1

-4.3 2/1/2010 13:49 6.60E+02 5.97E+02 6.18E+02 7.81E-01 8.04E-01 8.46E-01 2.13E+00 3.24E+00 3.80E+00 0.00E+00 4.13E+00 4.27E+00 NA NA NA MW-36-24 MW-36-24 018 16.1

-4.3 4/28/2010 14:14 3.53E+03 3.39E+02 1.45E+02 1.91E-01 5.60E-01 6.67E-01 1.74E+00 5.87E+00 6.86E+00 2.13E+00 5.66E+00 6.86E+00 NA NA NA MW-36-24 MW-36-24 019 16.1

-4.3 7/29/2010 12:04 2.64E+02 1.17E+02 1.00E+02 2.45E-01 3.84E-01 4.23E-01 8.89E-01 9.88E+00 1.10E+01

-2.61E+00 1.19E+01 1.26E+01 NA NA NA MW-36-24 MW-36-24 020 16.1

-4.3 11/4/2010 16:15 2.62E+03 2.82E+02 1.13E+02 3.79E-01 5.81E-01 6.42E-01 3.42E+00 9.88E+00 1.17E+01

-1.80E+00 1.16E+01 1.26E+01 NA NA NA MW-36-24 MW-36-24 021 16.1

-4.3 2/28/2011 12:37 2.56E+02 3.54E+02 3.81E+02

-8.87E-02 1.67E+00 2.08E+00 4.53E-01 5.26E+00 5.75E+00

-3.09E-01 4.74E+00 5.03E+00 NA NA NA MW-36-24 MW-36-24 022 16.1

-4.3 4/28/2011 14:34 3.07E+03 7.26E+02 5.19E+02 1.38E+00 1.53E+00 1.59E+00

-6.43E-01 7.68E+00 8.47E+00 2.82E+00 7.48E+00 9.35E+00 NA NA NA MW-36-24 MW-36-24 023 16.1

-4.3 8/16/2011 13:34 1.12E+03 5.01E+02 4.51E+02 2.34E-01 9.96E-01 1.18E+00

-2.80E+00 7.71E+00 7.54E+00 7.10E-01 7.89E+00 8.75E+00 NA NA NA MW-36-24 MW-36-24 024 16.1

-4.3 12/7/2011 11:04 0.00E+00 4.20E+02 4.96E+02

-3.36E-01 1.29E+00 1.70E+00 1.75E+00 7.26E+00 9.17E+00

-1.38E+00 6.00E+00 7.29E+00 NA NA NA MW-36-24 MW-36-41 001 37

-25.2 2/10/2006 11:10 4.75E+04 1.24E+04 6.38E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-36-41 MW-36-41 002 37

-25.2 2/27/2006 13:45 4.58E+04 1.22E+04 6.36E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-36-41 MW-36-41 003 37

-25.2 3/24/2006 12:45 5.52E+04 4.65E+03 1.86E+03 3.48E+00 5.46E-01 4.16E-01

-5.91E+00 1.39E+01 1.45E+01 2.97E+00 1.53E+01 1.74E+01 4.87E+01 1.65E+01 1.65E+01 MW-36-41 MW-36-41 004 37

-25.2 4/5/2006 12:55 NA NA NA 3.53E+00 6.24E-01 5.02E-01 NA NA NA NA NA NA NA NA NA MW-36-41 MW-36-41 005 37

-25.2 6/5/2006 11:30 2.05E+04 3.17E+03 6.01E+02 2.30E+00 6.59E-01 6.10E-01

-3.37E+00 1.27E+01 1.33E+01 6.21E-02 1.03E+01 1.13E+01 NA NA NA MW-36-41 MW-36-41 006 37

-25.2 8/28/2006 10:10 2.01E+04 3.09E+03 6.45E+02 NA NA NA 1.96E+00 4.15E+00 5.22E+00

-2.78E-01 3.56E+00 3.78E+00 NA NA NA MW-36-41 MW-36-41 007 37

-25.2 6/27/2007 12:30 6.11E+03 3.50E+02 1.74E+02 2.18E+00 1.17E+00 9.85E-01 4.30E-01 4.61E+00 1.74E+00 1.36E+00 2.91E+00 3.67E+00 NA NA NA MW-36-41 MW-36-41 008 37

-25.2 5/1/2009 14:40 1.13E+04 7.20E+02 1.64E+02 4.03E+00 1.14E+00 7.31E-01

-2.59E-01 6.14E+00 4.09E+00 1.04E-01 3.03E+00 3.26E+00 NA NA NA MW-36-41 MW-36-41 009 37

-25.2 8/4/2009 14:29 1.01E+04 5.64E+02 1.57E+02 7.12E+00 1.34E+00 7.74E-01 3.04E+00 6.52E+00 7.88E+00 7.15E+00 7.15E+00 9.63E+00 NA NA NA MW-36-41 MW-36-41 010 37

-25.2 10/28/2009 16:14 1.01E+04 4.29E+02 1.67E+02 5.14E+00 1.19E+00 7.96E-01

-2.95E-01 4.17E+00 4.70E+00 1.79E+00 4.56E+00 5.37E+00 NA NA NA MW-36-41 MW-36-41 011 37

-25.2 2/1/2010 12:25 9.56E+03 1.30E+03 6.06E+02 4.60E+00 9.53E-01 4.44E-01 1.66E+00 4.23E+00 4.78E+00 0.00E+00 4.35E+00 5.71E+00 NA NA NA MW-36-41 MW-36-41 012 37

-25.2 4/28/2010 15:38 1.56E+04 6.89E+02 1.50E+02 5.95E+00 1.30E+00 5.74E-01 1.38E+00 6.43E+00 6.92E+00 8.55E-01 5.70E+00 6.68E+00 NA NA NA MW-36-41 MW-36-41 013 37

-25.2 7/29/2010 12:23 1.30E+04 7.52E+02 1.46E+02 1.88E+00 7.41E-01 5.17E-01

-1.84E+00 6.35E+00 6.48E+00 4.07E+00 6.12E+00 7.75E+00 NA NA NA MW-36-41 MW-36-41 014 37

-25.2 11/4/2010 16:55 1.22E+04 5.75E+02 1.10E+02 3.54E+00 9.13E-01 6.12E-01 7.62E-01 8.76E+00 1.01E+01 3.09E+00 8.58E+00 1.06E+01 NA NA NA MW-36-41 MW-36-41 015 37

-25.2 2/28/2011 13:53 8.74E+03 6.88E+02 2.97E+02 4.11E+00 1.87E+00 1.57E+00 1.31E+00 5.26E+00 6.09E+00 1.58E+00 5.68E+00 6.65E+00 NA NA NA MW-36-41 MW-36-41 016 37

-25.2 4/28/2011 15:39 8.17E+03 1.04E+03 5.14E+02 3.31E+00 1.75E+00 1.36E+00 2.18E+00 9.26E+00 1.07E+01

-2.96E-01 1.04E+01 1.12E+01 NA NA NA MW-36-41 MW-36-41 017 37

-25.2 8/16/2011 14:18 5.90E+03 8.37E+02 4.55E+02 1.74E+00 1.26E+00 1.13E+00 1.75E+00 8.91E+00 9.88E+00 4.43E+00 9.15E+00 1.15E+01 NA NA NA MW-36-41 MW-36-41 018 37

-25.2 12/7/2011 13:09 2.63E+03 6.51E+02 4.78E+02 9.00E-01 1.71E+00 1.89E+00 1.19E-02 7.17E+00 9.00E+00

-5.23E-01 7.86E+00 1.01E+01 NA NA NA MW-36-41 MW-36-52 001 49.7

-37.9 2/10/2006 10:30 2.24E+04 8.55E+03 6.38E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-36-52 MW-36-52 002 49.7

-37.9 2/27/2006 12:05 2.57E+04 9.14E+03 6.36E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-36-52 MW-36-52 003 49.7

-37.9 3/24/2006 16:00 2.68E+04 3.47E+03 1.87E+03 4.11E+00 5.66E-01 5.14E-01 4.47E+00 9.06E+00 1.04E+01

-2.47E+00 9.69E+00 1.03E+01 1.18E+01 1.44E+01 1.54E+01 MW-36-52 MW-36-52 004 49.7

-37.9 4/5/2006 14:30 NA NA NA 5.01E+00 7.23E-01 6.26E-01 NA NA NA NA NA NA NA NA NA MW-36-52 MW-36-52 005 49.7

-37.9 6/5/2006 11:30 2.40E+04 3.68E+03 6.40E+02 4.42E+00 8.33E-01 5.53E-01 3.49E+00 1.05E+01 1.21E+01 4.80E-01 1.04E+01 1.15E+01 NA NA NA MW-36-52 MW-36-52 006 49.7

-37.9 8/28/2006 10:00 1.41E+04 2.19E+03 5.35E+02 NA NA NA 4.06E-01 6.52E+00 7.36E+00

-2.69E-01 5.23E+00 5.69E+00 NA NA NA MW-36-52 MW-36-52 007 49.7

-37.9 6/27/2007 11:45 1.01E+04 4.89E+02 1.95E+02 2.62E+00 1.09E+00 3.28E-01

-3.82E-01 2.77E+00 2.99E+00 9.25E-01 2.61E+00 3.14E+00 NA NA NA MW-36-52 MW-36-52 008 49.7

-37.9 8/8/2007 14:15 1.25E+04 1.24E+03 4.60E+02 2.26E+00 1.00E+00 2.82E-01 1.30E+00 2.97E+00 3.51E+00

-8.82E-01 3.31E+00 3.55E+00 4.27E+00 2.14E+01 2.47E+01 MW-36-52 MW-36-52 009 49.7

-37.9 1/23/2008 14:13 1.13E+04 4.47E+02 1.71E+02 4.85E+00 9.69E-01 4.24E-01

-2.89E-01 2.01E+00 2.25E+00 4.08E-01 1.86E+00 2.20E+00 NA NA NA MW-36-52 MW-36-52 010 49.7

-37.9 7/24/2008 16:00 1.26E+04 7.66E+02 3.74E+02 5.67E+00 7.42E-01 4.73E-01

-4.79E-01 2.24E+00 3.69E+00 2.77E-02 2.11E+00 3.53E+00 NA NA NA MW-36-52 MW-36-52 011 49.7

-37.9 11/10/2008 16:53 1.10E+04 4.40E+02 1.63E+02 8.27E+00 1.24E+00 3.89E-01

-3.85E-01 3.86E+00 4.21E+00 1.36E+00 4.67E+00 5.65E+00 NA NA NA MW-36-52 MW-36-52 012 49.7

-37.9 1/22/2009 12:59 6.79E+03 6.03E+02 2.06E+02 3.37E+00 8.99E-01 6.07E-01

-6.07E-01 2.96E+00 3.24E+00 1.65E+00 3.24E+00 4.05E+00 NA NA NA MW-36-52 MW-36-52 013 49.7

-37.9 5/1/2009 15:07 6.06E+03 5.33E+02 1.63E+02 2.40E+00 7.82E-01 5.20E-01 2.41E+00 7.13E+00 4.75E+00 1.70E+00 4.26E+00 5.17E+00 NA NA NA MW-36-52 MW-36-52 014 49.7

-37.9 8/4/2009 12:02 8.61E+03 5.30E+02 1.62E+02 4.70E+00 1.05E+00 5.90E-01 1.90E-01 7.86E+00 6.96E+00

-1.37E+00 7.25E+00 7.05E+00 NA NA NA MW-36-52 MW-36-52 015 49.7

-37.9 10/28/2009 15:39 8.23E+03 3.92E+02 1.67E+02 3.51E+00 1.05E+00 6.91E-01 1.28E+00 4.38E+00 4.98E+00 3.63E+00 4.05E+00 5.13E+00 NA NA NA MW-36-52 MW-36-52 016 49.7

-37.9 2/1/2010 15:28 5.97E+03 1.03E+03 6.42E+02 2.12E+00 6.87E-01 4.50E-01

-3.34E+00 6.50E+00 6.30E+00

-1.10E+00 3.79E+00 4.07E+00 NA NA NA MW-36-52 MW-36-52 017 49.7

-37.9 4/28/2010 15:46 8.49E+03 5.09E+02 1.47E+02 5.36E+00 1.35E+00 6.85E-01 2.29E+00 5.31E+00 6.27E+00 2.98E+00 4.80E+00 6.12E+00 NA NA NA MW-36-52 MW-36-52 018 49.7

-37.9 7/29/2010 12:24 7.07E+03 4.46E+02 1.00E+02

-1.52E-01 6.33E-01 8.23E-01

-1.63E+00 7.79E+00 8.33E+00

-1.74E+00 9.63E+00 1.03E+01 NA NA NA MW-36-52 MW-36-52 019 49.7

-37.9 11/4/2010 15:55 7.08E+03 4.40E+02 1.10E+02 4.73E+00 1.11E+00 6.76E-01 1.15E-01 5.89E+00 6.52E+00

-2.28E+00 7.92E+00 7.79E+00 NA NA NA MW-36-52 MW-36-52 020 49.7

-37.9 2/28/2011 12:43 3.14E+03 4.92E+02 3.37E+02 1.33E+00 2.00E+00 2.14E+00

-6.00E+00 5.58E+00 4.80E+00

-2.66E+00 5.94E+00 5.65E+00 NA NA NA MW-36-52 MW-36-52 021 49.7

-37.9 4/28/2011 14:38 5.84E+03 9.06E+02 5.15E+02 3.41E+00 1.56E+00 1.11E+00 4.29E+00 8.42E+00 1.03E+01

-2.61E+00 8.50E+00 8.36E+00 NA NA NA MW-36-52 MW-36-52 022 49.7

-37.9 8/16/2011 14:52 4.69E+03 7.59E+02 4.48E+02 2.93E+00 1.57E+00 1.36E+00 3.59E+00 8.22E+00 9.80E+00

-1.83E+00 9.33E+00 9.74E+00 NA NA NA MW-36-52 MW-36-52 023 49.7

-37.9 12/7/2011 11:36 4.76E+03 8.10E+02 4.91E+02 5.23E+00 1.96E+00 1.24E+00 2.89E+00 7.74E+00 1.01E+01 5.68E+00 9.03E+00 1.31E+01 NA NA NA MW-36-52 MW-37-22 001 17

-2 2/24/2006 9:50 1.07E+04 5.92E+03 6.39E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-37-22 MW-37-22 002 17

-2 2/28/2006 10:20 NA NA NA 2.40E+00 9.10E-01 9.16E-01 NA NA NA NA NA NA NA NA NA MW-37-22 MW-37-22 002 17

-2 2/28/2006 10:20 1.28E+04 2.03E+03 1.31E+03 2.37E+00 8.91E-01 8.44E-01 2.41E+00 1.92E+01 1.95E+01 3.60E+00 1.58E+01 1.77E+01 4.24E+01 1.48E+01 1.47E+01 MW-37-22 MW-37-22 003 17

-2 3/10/2006 10:35 2.32E+04 2.57E+03 1.28E+03 4.70E+00 9.84E-01 7.87E-01 4.61E+00 1.46E+01 1.63E+01 5.65E+00 1.39E+01 1.57E+01 2.08E+01 1.27E+01 1.33E+01 MW-37-22 MW-37-22 004 17

-2 3/27/2006 10:35 3.49E+04 3.78E+03 1.81E+03 4.05E+00 8.76E-01 6.97E-01 9.75E-01 4.68E+00 5.21E+00 7.46E-01 4.48E+00 4.97E+00 5.43E+01 1.53E+01 1.52E+01 MW-37-22 MW-37-22 005 17

-2 6/27/2006 10:25 1.05E+04 8.55E+02 3.40E+02 9.57E+00 1.20E+00 7.87E-01 3.20E+00 6.92E+00 8.00E+00

-8.05E-01 6.94E+00 7.43E+00 NA NA NA MW-37-22 MW-37-22 006 17

-2 9/29/2006 9:30 7.37E+03 1.22E+03 3.76E+02 1.42E+01 1.80E+00 9.01E-01

-3.84E-02 8.51E+00 9.49E+00

-1.03E+00 7.63E+00 7.69E+00 NA NA NA MW-37-22 MW-37-22 007 17

-2 6/27/2007 10:50 4.05E+03 3.35E+02 1.94E+02 1.49E+01 2.13E+00 8.72E-01

-2.26E+00 4.88E+00 3.50E+00

-1.12E+00 3.24E+00 3.34E+00 NA NA NA MW-37-22 MW-37-22 008 17

-2 8/7/2007 10:55 2.79E+03 2.69E+02 1.89E+02 1.83E+01 2.07E+00 8.57E-01 2.74E+00 3.93E+00 4.22E+00 4.23E-01 3.07E+00 3.54E+00 NA NA NA MW-37-22 MW-37-22 009 17

-2 10/15/2007 14:30 2.26E+03 2.22E+02 1.69E+02 2.29E+01 2.28E+00 4.67E-01 1.33E+00 3.25E+00 3.78E+00

-1.42E+00 3.44E+00 3.44E+00 NA NA NA MW-37-22 MW-37-22 010 17

-2 1/23/2008 10:42 6.52E+03 3.54E+02 1.71E+02 8.73E+00 1.27E+00 4.63E-01

-2.09E+00 2.96E+00 2.86E+00 2.34E-01 3.08E+00 3.49E+00 NA NA NA MW-37-22

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 7 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-37-22 011 17

-2 7/24/2008 11:20 4.33E+03 2.28E+02 1.95E+02 1.22E+01 1.25E+00 7.14E-01 4.32E-01 2.13E+00 3.66E+00 2.97E+00 2.57E+00 4.83E+00 NA NA NA MW-37-22 MW-37-22 012 17

-2 11/10/2008 12:20 2.68E+03 3.92E+02 1.74E+02 1.80E+01 1.88E+00 4.08E-01 2.81E+00 4.96E+00 5.96E+00

-2.85E-01 4.53E+00 4.88E+00 NA NA NA MW-37-22 MW-37-22 013 17

-2 1/21/2009 14:27 5.27E+03 5.36E+02 2.05E+02 8.81E+00 1.33E+00 6.79E-01

-3.12E-01 3.02E+00 3.27E+00

-2.03E+00 3.09E+00 2.82E+00 NA NA NA MW-37-22 MW-37-22 014 17

-2 5/1/2009 12:16 3.85E+03 7.92E+02 4.73E+02 9.37E+00 1.37E+00 4.81E-01 1.09E+00 7.64E+00 5.09E+00

-8.00E-01 5.43E+00 5.74E+00 NA NA NA MW-37-22 MW-37-22 015 17

-2 7/23/2009 14:40 4.70E+03 4.97E+02 2.27E+02 1.21E+01 1.56E+00 4.27E-01 4.22E-02 3.86E+00 4.38E+00

-1.57E+00 3.54E+00 3.56E+00 NA NA NA MW-37-22 MW-37-22 016 17

-2 10/28/2009 11:39 4.56E+03 2.90E+02 1.62E+02 1.24E+01 1.51E+00 4.86E-01

-5.18E-02 5.66E+00 6.30E+00

-3.95E-01 6.42E+00 6.70E+00 NA NA NA MW-37-22 MW-37-22 017 17

-2 1/29/2010 15:24 5.54E+03 9.63E+02 4.47E+02 1.22E+01 1.46E+00 4.07E-01 9.10E-01 3.98E+00 4.49E+00

-4.43E-01 4.51E+00 4.99E+00 NA NA NA MW-37-22 MW-37-22 018 17

-2 4/27/2010 13:23 9.06E+03 4.26E+02 2.09E+02 1.29E+01 1.68E+00 6.44E-01

-1.08E+00 5.73E+00 5.64E+00 1.34E+00 4.41E+00 5.29E+00 NA NA NA MW-37-22 MW-37-22 019 17

-2 8/5/2010 14:06 3.70E+03 3.26E+02 9.90E+01 5.19E+00 1.39E+00 9.19E-01

-1.60E+00 7.62E+00 8.20E+00 4.53E+00 7.13E+00 9.76E+00 NA NA NA MW-37-22 MW-37-22 020 17

-2 11/4/2010 14:28 4.46E+03 3.57E+02 1.12E+02 1.38E+01 1.33E+00 5.33E-01

-2.26E+00 7.33E+00 7.68E+00

-1.24E+00 9.31E+00 1.00E+01 NA NA NA MW-37-22 MW-37-22 021 17

-2 1/27/2011 15:19 6.74E+03 6.18E+02 2.98E+02 1.04E+01 2.52E+00 1.68E+00

-2.18E+00 4.74E+00 4.94E+00 2.59E+00 5.38E+00 6.55E+00 NA NA NA MW-37-22 MW-37-22 022 17

-2 4/28/2011 12:05 6.87E+03 9.66E+02 5.14E+02 8.72E+00 2.90E+00 2.05E+00 7.12E-01 6.96E+00 7.67E+00 5.14E-01 7.86E+00 8.62E+00 NA NA NA MW-37-22 MW-37-22 023 17

-2 8/16/2011 10:35 4.52E+03 7.56E+02 4.53E+02 7.59E+00 2.07E+00 1.32E+00 3.10E+00 7.26E+00 8.77E+00

-9.99E-01 7.35E+00 7.48E+00 NA NA NA MW-37-22 MW-37-22 024 17

-2 11/23/2011 11:33 4.97E+03 8.28E+02 4.96E+02 8.02E+00 2.57E+00 1.38E+00 2.26E+00 9.12E+00 1.19E+01

-1.41E+00 7.35E+00 9.09E+00 NA NA NA MW-37-22 MW-37-32 002 29

-14 2/28/2006 12:00 2.86E+04 2.73E+03 1.32E+03 1.78E+01 1.49E+00 2.22E+00 1.27E+01 1.93E+01 2.17E+01 1.50E+01 1.90E+01 2.20E+01 3.41E+01 1.46E+01 1.48E+01 MW-37-32 MW-37-32 002 29

-14 2/28/2006 12:00 NA NA NA 1.82E+01 1.72E+00 2.28E+00 NA NA NA NA NA NA NA NA NA MW-37-32 MW-37-32 003 29

-14 3/10/2006 12:50 2.83E+04 2.79E+03 1.28E+03 1.52E+01 1.39E+00 1.90E+00 1.43E+01 1.59E+01 1.78E+01 1.51E+00 1.51E+01 1.65E+01 1.13E+01 1.26E+01 1.34E+01 MW-37-32 MW-37-32 004 29

-14 3/27/2006 11:10 1.39E+04 2.61E+03 1.72E+03 1.95E+01 1.59E+00 2.44E+00 1.10E+00 4.72E+00 5.25E+00

-8.50E-01 4.41E+00 4.80E+00 6.09E+00 1.40E+01 1.51E+01 MW-37-32 MW-37-32 005 29

-14 6/27/2006 9:15 7.92E+03 6.63E+02 2.99E+02 2.98E+01 2.64E+00 3.72E+00

-2.37E-01 5.24E+00 6.07E+00

-2.02E-01 4.75E+00 5.78E+00 NA NA NA MW-37-32 MW-37-32 006 29

-14 9/29/2006 10:15 1.15E+04 1.88E+03 4.64E+02 1.53E+01 1.80E+00 1.91E+00

-3.21E+00 8.98E+00 8.67E+00 2.51E+00 8.73E+00 1.06E+01 NA NA NA MW-37-32 MW-37-32 001 29

-14 2/24/2007 10:55 3.01E+04 9.93E+03 6.39E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-37-32 MW-37-32 007 29

-14 6/27/2007 12:20 3.13E+03 3.05E+02 1.93E+02 1.85E+01 2.37E+00 2.31E+00

-1.49E+00 3.86E+00 3.38E+00 1.63E+00 3.38E+00 4.14E+00 NA NA NA MW-37-32 MW-37-32 008 29

-14 8/7/2007 10:56 3.81E+03 2.97E+02 1.87E+02 1.89E+01 2.02E+00 2.36E+00 1.99E+00 3.18E+00 3.88E+00 1.88E+00 3.19E+00 4.01E+00 NA NA NA MW-37-32 MW-37-32 009 29

-14 10/15/2007 14:36 2.49E+03 2.30E+02 1.69E+02 2.13E+01 2.19E+00 2.66E+00 8.79E-01 4.61E+00 4.81E+00 2.53E+00 3.75E+00 4.70E+00 NA NA NA MW-37-32 MW-37-32 010 29

-14 1/23/2008 11:03 6.76E+03 3.57E+02 1.70E+02 1.52E+01 1.59E+00 3.65E-01 1.09E+00 2.70E+00 3.16E+00

-5.32E-02 2.72E+00 2.55E+00 NA NA NA MW-37-32 MW-37-32 011 29

-14 7/24/2008 12:28 5.16E+03 2.45E+02 1.95E+02 2.06E+01 1.51E+00 8.63E-01

-4.08E-01 1.58E+00 2.18E+00

-1.46E-01 2.04E+00 2.58E+00 NA NA NA MW-37-32 MW-37-32 012 29

-14 11/10/2008 12:20 2.89E+03 4.01E+02 1.71E+02 1.86E+01 1.95E+00 3.99E-01 1.71E+00 5.33E+00 6.24E+00 4.09E-01 5.37E+00 6.14E+00 NA NA NA MW-37-32 MW-37-32 013 29

-14 1/21/2009 14:30 3.76E+03 4.61E+02 2.04E+02 1.11E+01 1.49E+00 6.27E-01 1.59E+00 2.84E+00 3.40E+00

-7.12E-01 3.32E+00 3.49E+00 NA NA NA MW-37-32 MW-37-32 014 29

-14 5/1/2009 12:13 4.83E+03 8.66E+02 4.72E+02 1.72E+01 1.80E+00 6.64E-01

-2.55E+00 7.43E+00 4.95E+00 1.24E-01 3.66E+00 4.12E+00 NA NA NA MW-37-32 MW-37-32 015 29

-14 7/23/2009 15:07 5.48E+03 5.28E+02 2.25E+02 2.38E+01 2.17E+00 6.75E-01

-6.60E-01 3.35E+00 3.66E+00

-1.22E+00 3.10E+00 3.12E+00 NA NA NA MW-37-32 MW-37-32 016 29

-14 10/28/2009 11:37 4.56E+03 2.88E+02 1.61E+02 2.20E+01 2.04E+00 7.01E-01

-3.69E+00 7.75E+00 7.99E+00 2.12E-01 4.67E+00 5.38E+00 NA NA NA MW-37-32 MW-37-32 017 29

-14 1/29/2010 15:43 5.69E+03 1.05E+03 6.73E+02 2.03E+01 1.89E+00 4.73E-01 1.04E+00 3.51E+00 3.99E+00

-5.67E-01 3.75E+00 4.02E+00 NA NA NA MW-37-32 MW-37-32 018 29

-14 4/27/2010 17:25 7.24E+03 3.90E+02 2.10E+02 1.87E+01 2.28E+00 6.59E-01 6.85E-01 5.87E+00 6.72E+00

-2.27E+00 4.88E+00 4.69E+00 NA NA NA MW-37-32 MW-37-32 019 29

-14 8/5/2010 14:00 4.80E+03 3.69E+02 9.97E+01 1.41E+01 1.85E+00 5.42E-01

-5.90E+00 8.89E+00 8.07E+00

-3.93E-01 8.67E+00 9.54E+00 NA NA NA MW-37-32 MW-37-32 020 29

-14 11/4/2010 13:14 5.99E+03 4.22E+02 1.17E+02

-2.91E-01 6.15E-01 7.91E-01

-4.11E+00 7.41E+00 7.07E+00 1.54E+00 7.68E+00 9.04E+00 NA NA NA MW-37-32 MW-37-32 021 29

-14 1/27/2011 15:09 4.57E+03 5.28E+02 2.98E+02 1.49E+01 3.02E+00 1.74E+00 4.20E-01 6.12E+00 6.85E+00 1.72E+00 6.60E+00 7.76E+00 NA NA NA MW-37-32 MW-37-32 022 29

-14 4/28/2011 12:21 4.11E+03 7.98E+02 5.15E+02 2.62E+01 3.76E+00 1.68E+00 3.56E+00 1.20E+01 1.42E+01

-1.92E+00 1.09E+01 1.09E+01 NA NA NA MW-37-32 MW-37-32 023 29

-14 8/16/2011 11:00 5.23E+03 7.95E+02 4.52E+02 1.68E+01 2.87E+00 1.13E+00

-2.53E+00 8.34E+00 7.53E+00

-6.09E+00 9.06E+00 8.10E+00 NA NA NA MW-37-32 MW-37-32 024 29

-14 11/23/2011 11:19 4.33E+03 7.80E+02 4.91E+02 1.26E+01 3.21E+00 1.52E+00 7.81E+00 9.00E+00 1.28E+01

-6.59E+00 8.76E+00 8.06E+00 NA NA NA MW-37-32 MW-37-40 001 39.2

-24.2 2/24/2006 11:35 1.68E+04 7.41E+03 6.39E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-37-40 MW-37-40 002 39.2

-24.2 2/28/2006 11:40 1.47E+04 2.13E+03 1.32E+03 3.86E+00 1.23E+00 1.19E+00 1.79E+01 1.71E+01 1.96E+01 1.53E+00 1.64E+01 1.81E+01 5.65E+01 1.65E+01 1.61E+01 MW-37-40 MW-37-40 002 39.2

-24.2 2/28/2006 11:40 NA NA NA 4.91E+00 1.23E+00 1.08E+00 NA NA NA NA NA NA NA NA NA MW-37-40 MW-37-40 003 39.2

-24.2 3/10/2006 10:25 1.70E+04 2.30E+03 1.29E+03 1.35E+01 1.32E+00 7.28E-01 5.51E+00 1.45E+01 1.62E+01 1.99E+00 1.47E+01 1.62E+01 1.24E+01 1.35E+01 1.44E+01 MW-37-40 MW-37-40 004 39.2

-24.2 3/27/2006 11:55 1.56E+04 2.82E+03 1.82E+03 1.11E+01 1.12E+00 5.90E-01 3.34E+00 6.14E+00 5.43E+00 4.03E+00 4.71E+00 5.39E+00 6.37E+00 1.35E+01 1.47E+01 MW-37-40 MW-37-40 006 39.2

-24.2 6/27/2006 10:15 1.42E+04 1.13E+03 3.89E+02 2.44E+01 1.71E+00 7.03E-01 8.68E+00 7.68E+00 9.25E+00

-4.36E+00 6.70E+00 6.60E+00 NA NA NA MW-37-40 MW-37-40 007 39.2

-24.2 6/27/2007 11:00 6.35E+03 3.99E+02 1.93E+02 4.69E+00 1.14E+00 8.47E-01 5.92E-01 3.36E+00 3.91E+00

-1.07E+00 3.15E+00 3.22E+00 NA NA NA MW-37-40 MW-37-40 008 39.2

-24.2 8/7/2007 13:45 5.85E+03 3.50E+02 1.88E+02 9.76E+00 1.51E+00 6.27E-01 1.10E+00 3.12E+00 3.71E+00

-2.48E-01 3.36E+00 3.70E+00 NA NA NA MW-37-40 MW-37-40 009 39.2

-24.2 10/15/2007 15:00 5.69E+03 3.03E+02 1.69E+02 5.98E+00 1.28E+00 7.48E-01 7.63E-01 2.91E+00 3.38E+00 5.99E-01 2.82E+00 3.32E+00 NA NA NA MW-37-40 MW-37-40 010 39.2

-24.2 2/1/2008 17:20 6.73E+03 3.17E+02 1.33E+02 9.48E-01 8.54E-01 8.45E-01 3.09E-01 2.63E+00 2.95E+00

-3.70E-01 2.75E+00 2.94E+00

-4.35E+00 1.46E+01 1.76E+01 MW-37-40 MW-37-40 011 39.2

-24.2 7/24/2008 13:12 5.24E+03 2.43E+02 1.91E+02 1.31E+00 4.41E-01 5.07E-01

-1.10E+00 1.52E+00 2.48E+00

-1.35E+00 2.11E+00 2.70E+00 NA NA NA MW-37-40 MW-37-40 012 39.2

-24.2 11/10/2008 16:17 5.49E+03 5.45E+02 1.76E+02 1.13E+00 5.31E-01 3.83E-01 3.61E-01 6.03E+00 6.83E+00 5.04E+00 7.42E+00 9.22E+00 NA NA NA MW-37-40 MW-37-40 013 39.2

-24.2 1/22/2009 13:05 4.91E+03 5.13E+02 2.00E+02 3.47E+00 8.85E-01 5.69E-01

-2.64E+00 3.78E+00 3.27E+00 2.67E+00 3.14E+00 4.08E+00 NA NA NA MW-37-40 MW-37-40 014 39.2

-24.2 5/1/2009 14:15 4.38E+03 8.33E+02 4.73E+02 1.11E+00 5.15E-01 3.77E-01

-2.89E-01 7.70E+00 5.13E+00 2.74E+00 5.21E+00 6.44E+00 NA NA NA MW-37-40 MW-37-40 015 39.2

-24.2 7/23/2009 14:16 4.22E+03 4.74E+02 2.26E+02 1.19E+01 1.39E+00 3.48E-01

-1.35E-01 3.99E+00 4.50E+00

-3.89E-01 3.12E+00 3.38E+00 NA NA NA MW-37-40 MW-37-40 016 39.2

-24.2 10/28/2009 13:48 4.52E+03 2.88E+02 1.62E+02 1.69E+01 1.75E+00 7.12E-01 2.63E+00 6.40E+00 7.65E+00 3.10E+00 6.72E+00 8.29E+00 NA NA NA MW-37-40 MW-37-40 017 39.2

-24.2 1/29/2010 12:52 4.70E+03 8.82E+02 4.33E+02 1.25E+01 1.44E+00 4.29E-01 7.58E-01 5.10E+00 5.66E+00

-1.29E+00 4.93E+00 5.38E+00 NA NA NA MW-37-40 MW-37-40 018 39.2

-24.2 4/27/2010 12:43 5.37E+03 3.45E+02 2.07E+02 1.71E+01 1.81E+00 6.52E-01

-2.56E+00 4.54E+00 4.41E+00

-7.35E-02 5.03E+00 5.51E+00 NA NA NA MW-37-40 MW-37-40 019 39.2

-24.2 8/5/2010 14:25 7.00E+03 4.43E+02 9.99E+01 1.43E+01 1.74E+00 4.81E-01 3.15E-01 7.86E+00 9.00E+00 3.82E+00 7.44E+00 9.31E+00 NA NA NA MW-37-40 MW-37-40 020 39.2

-24.2 11/4/2010 12:06 6.41E+03 4.29E+02 1.15E+02 1.28E+01 1.92E+00 6.32E-01 2.77E+00 8.58E+00 1.03E+01

-2.01E+00 8.29E+00 8.39E+00 NA NA NA MW-37-40 MW-37-40 021 39.2

-24.2 1/27/2011 13:35 5.97E+03 7.42E+02 3.82E+02 1.93E+01 3.34E+00 1.85E+00 1.95E+00 5.84E+00 6.78E+00 2.03E+00 6.84E+00 7.92E+00 NA NA NA MW-37-40 MW-37-40 022 39.2

-24.2 4/28/2011 11:31 3.92E+03 8.02E+02 5.33E+02 2.30E+01 3.66E+00 1.68E+00 4.10E+00 9.02E+00 1.09E+01 6.47E-01 8.94E+00 1.02E+01 NA NA NA MW-37-40 MW-37-40 023 39.2

-24.2 8/16/2011 11:24 5.03E+03 7.86E+02 4.53E+02 1.95E+01 3.18E+00 1.17E+00

-2.08E+00 8.25E+00 8.54E+00 1.79E+00 7.35E+00 8.59E+00 NA NA NA MW-37-40 MW-37-40 024 39.2

-24.2 11/23/2011 11:46 5.22E+03 8.28E+02 4.83E+02 1.50E+01 3.45E+00 1.47E+00 1.06E+00 1.43E+01 7.71E+00 9.11E-01 7.29E+00 1.00E+01 NA NA NA MW-37-40 MW-37-57 001 53.2

-38.2 2/24/2006 10:30 1.60E+04 7.22E+03 6.39E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-37-57 MW-37-57 002 53.2

-38.2 2/28/2006 13:35 1.33E+04 2.06E+00 1.32E+03 2.22E+01 1.75E+00 1.05E+00 1.81E+00 2.14E+01 2.44E+01 5.22E+00 1.82E+01 2.14E+01 2.91E+01 1.50E+01 1.54E+01 MW-37-57 MW-37-57 002 53.2

-38.2 2/28/2006 13:35 NA NA NA 2.27E+01 2.00E+00 1.02E+00 NA NA NA NA NA NA NA NA NA MW-37-57 MW-37-57 003 53.2

-38.2 3/10/2006 11:45 1.91E+04 2.40E+03 1.29E+03 2.29E+01 1.74E+00 7.68E-01 1.46E+00 1.76E+01 1.77E+01 7.74E+00 1.53E+01 1.73E+01 1.04E+01 1.33E+01 1.43E+01 MW-37-57 MW-37-57 004 53.2

-38.2 3/27/2006 13:55 1.59E+04 2.84E+03 1.81E+03 1.65E+01 1.38E+00 6.60E-01 2.52E+00 5.25E+00 5.80E+00 3.94E+00 4.86E+00 5.53E+00 3.71E+00 1.37E+01 1.49E+01 MW-37-57 MW-37-57 005 53.2

-38.2 6/27/2006 9:35 4.48E+04 3.42E+03 6.83E+02 2.73E+01 1.89E+00 8.18E-01 NA NA NA 2.04E+00 5.77E+00 6.52E+00 NA NA NA MW-37-57 MW-37-57 006 53.2

-38.2 9/29/2006 10:40 1.05E+04 1.74E+03 4.52E+02 1.81E+01 1.88E+00 7.87E-01

-3.39E+00 8.04E+00 7.81E+00 2.60E+00 8.86E+00 1.07E+01 NA NA NA MW-37-57 MW-37-57 007 53.2

-38.2 6/27/2007 12:20 5.89E+03 3.89E+02 1.95E+02 2.42E+01 3.03E+00 8.84E-01 2.45E+00 3.51E+00 4.32E+00

-9.58E-02 4.67E+00 4.84E+00 NA NA NA MW-37-57 MW-37-57 008 53.2

-38.2 8/7/2007 12:55 6.68E+03 3.68E+02 1.88E+02 2.33E+01 2.15E+00 5.01E-01

-1.35E+00 3.27E+00 3.42E+00

-3.64E-02 3.86E+00 4.33E+00 NA NA NA MW-37-57 MW-37-57 009 53.2

-38.2 10/15/2007 15:00 4.88E+03 2.85E+02 1.68E+02 2.78E+01 2.49E+00 5.53E-01 3.62E-01 2.67E+00 2.72E+00 1.20E-01 2.40E+00 2.77E+00 NA NA NA MW-37-57 MW-37-57 010 53.2

-38.2 2/1/2008 16:31 6.63E+03 3.14E+02 1.33E+02 2.89E+01 3.20E+00 9.62E-01

-9.11E-01 3.72E+00 3.68E+00

-2.93E-01 3.12E+00 3.45E+00 8.47E-01 1.46E+01 1.71E+01 MW-37-57 MW-37-57 011 53.2

-38.2 7/24/2008 13:20 5.33E+03 2.47E+02 1.94E+02 2.12E+01 1.46E+00 5.27E-01

-7.11E-01 1.88E+00 3.07E+00

-1.17E+00 2.10E+00 3.24E+00 NA NA NA MW-37-57 MW-37-57 012 53.2

-38.2 11/10/2008 11:04 4.27E+03 4.77E+02 1.71E+02 2.40E+01 2.29E+00 6.36E-01

-1.57E-01 6.08E+00 6.80E+00 9.78E-01 7.18E+00 8.14E+00 NA NA NA MW-37-57

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 8 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-37-57 013 53.2

-38.2 1/21/2009 14:22 5.04E+03 5.21E+02 2.02E+02 1.99E+01 1.97E+00 6.68E-01 3.77E-02 3.44E+00 3.80E+00 1.05E+00 3.71E+00 4.35E+00 NA NA NA MW-37-57 MW-37-57 014 53.2

-38.2 5/1/2009 12:39 5.94E+03 5.24E+02 1.61E+02 2.49E+01 2.15E+00 5.69E-01

-2.83E-02 7.56E+00 5.04E+00 5.79E-01 4.89E+00 5.60E+00 NA NA NA MW-37-57 MW-37-57 015 53.2

-38.2 7/23/2009 15:12 4.05E+03 4.61E+02 2.22E+02 3.17E+01 2.46E+00 6.47E-01 9.63E-01 3.07E+00 3.68E+00 3.34E-01 3.17E+00 3.55E+00 NA NA NA MW-37-57 MW-37-57 016 53.2

-38.2 10/28/2009 12:00 4.20E+03 2.81E+02 1.62E+02 2.88E+01 2.58E+00 8.87E-01 1.78E+00 5.84E+00 6.92E+00

-1.29E-01 6.51E+00 7.24E+00 NA NA NA MW-37-57 MW-37-57 017 53.2

-38.2 1/29/2010 15:43 5.07E+03 9.08E+02 4.31E+02 1.76E+01 1.80E+00 4.25E-01 1.11E+00 4.16E+00 4.74E+00 5.45E-01 3.90E+00 4.50E+00 NA NA NA MW-37-57 MW-37-57 018 53.2

-38.2 4/27/2010 17:28 5.20E+03 3.50E+02 2.16E+02 1.90E+01 2.15E+00 6.60E-01

-5.08E+00 7.63E+00 7.24E+00 1.71E+00 6.43E+00 7.85E+00 NA NA NA MW-37-57 MW-37-57 019 53.2

-38.2 8/5/2010 13:59 7.30E+03 4.52E+02 9.94E+01 1.73E+01 1.69E+00 5.57E-01

-2.16E+00 7.37E+00 7.75E+00

-6.93E-01 8.96E+00 9.77E+00 NA NA NA MW-37-57 MW-37-57 020 53.2

-38.2 11/4/2010 13:49 6.72E+03 4.41E+02 1.15E+02 1.97E+01 2.15E+00 5.70E-01 6.72E+00 1.52E+01 9.04E+00

-3.60E+00 7.95E+00 7.35E+00 NA NA NA MW-37-57 MW-37-57 021 53.2

-38.2 1/27/2011 15:26 5.63E+03 5.76E+02 2.99E+02 2.02E+01 3.60E+00 1.96E+00

-3.70E-01 6.34E+00 6.92E+00

-1.36E+00 5.64E+00 5.68E+00 NA NA NA MW-37-57 MW-37-57 022 53.2

-38.2 4/28/2011 12:17 5.81E+03 8.98E+02 5.07E+02 1.58E+01 3.54E+00 2.00E+00 5.18E+00 1.72E+01 8.67E+00

-1.42E+00 8.36E+00 8.80E+00 NA NA NA MW-37-57 MW-37-57 023 53.2

-38.2 8/16/2011 10:55 5.11E+03 7.98E+02 4.59E+02 2.15E+01 3.27E+00 1.30E+00 1.82E+00 7.92E+00 9.16E+00

-1.34E+00 6.39E+00 6.57E+00 NA NA NA MW-37-57 MW-37-57 024 53.2

-38.2 11/23/2011 11:22 4.87E+03 8.16E+02 4.91E+02 1.88E+01 3.90E+00 1.81E+00

-6.08E-01 8.28E+00 1.01E+01 3.00E+00 9.12E+00 1.27E+01 NA NA NA MW-37-57 MW-38 002 25.4

-11.1 12/8/2005 10:30 9.85E+02 4.38E+02 4.54E+02

-4.38E+00 9.29E+00 1.25E+01 2.93E+00 8.80E+00 6.57E+00 2.99E+00 8.98E+00 7.06E+00 NA NA NA MW-38 MW-38 003 25.4

-11.1 12/30/2005 11:50 2.50E+02 4.29E+02 4.71E+02 NA NA NA 2.84E+00 8.51E+00 6.39E+00 2.81E+00 8.43E+00 6.71E+00 NA NA NA MW-38 MW-38 004 25.4

-11.1 1/10/2006 13:50 1.01E+03 4.50E+02 4.66E+02 NA NA NA 3.71E+00 1.11E+01 8.02E+00 3.55E+00 1.06E+01 8.02E+00 NA NA NA MW-38 MW-38 005 25.4

-11.1 1/19/2006 13:15 7.58E+02 4.29E+02 4.61E+02 NA NA NA 3.13E+00 9.38E+00 7.14E+00 3.71E+00 1.11E+01 8.77E+00 NA NA NA MW-38 MW-38 006 25.4

-11.1 1/25/2006 12:15 1.44E+03 4.59E+02 4.61E+02 NA NA NA 3.67E+00 1.10E+01 8.21E+00 4.18E+00 1.25E+01 9.71E+00 NA NA NA MW-38 MW-38 007 25.4

-11.1 2/1/2006 13:30 3.39E+02 4.23E+02 4.60E+02 NA NA NA 3.06E+00 9.19E+00 6.91E+00 3.03E+00 9.09E+00 7.30E+00 NA NA NA MW-38 MW-38 008 25.4

-11.1 2/8/2006 11:15 1.88E+02 3.30E+02 3.46E+02 1.35E-01 4.34E-01 5.15E-01 5.29E+00 1.16E+01 1.31E+01 2.41E+00 1.17E+01 1.31E+01 NA NA NA MW-38 MW-38 009 25.4

-11.1 2/16/2006 10:05 1.47E+02 4.11E+02 4.54E+02 NA NA NA 2.91E+00 8.74E+00 6.54E+00 2.48E+00 7.44E+00 6.05E+00 NA NA NA MW-38 MW-38 010 25.4

-11.1 2/23/2006 13:25 2.63E+03 4.98E+02 4.61E+02 NA NA NA 1.97E+00 5.90E+00 4.22E+00 1.88E+00 5.63E+00 4.19E+00 NA NA NA MW-38 MW-38 011 25.4

-11.1 3/3/2006 8:50 3.70E+02 4.71E+02 4.66E+02 NA NA NA 2.65E+00 7.94E+00 6.38E+00 4.53E+00 1.36E+01 1.08E+01 NA NA NA MW-38 MW-38 013 25.4

-11.1 5/22/2006 9:20 7.59E+02 4.11E+02 4.46E+02 1.52E-01 2.88E-01 3.20E-01 3.42E+00 1.03E+01 7.57E+00 3.40E+00 1.02E+01 7.93E+00 NA NA NA MW-38 MW-38 014 25.4

-11.1 6/21/2006 9:48 7.62E+02 1.77E+02 1.70E+02 NA NA NA 5.90E-01 2.10E+00 2.40E+00 1.20E+00 2.07E+00 2.20E+00 NA NA NA MW-38 MW-38 014 25.4

-11.1 6/21/2006 9:48 9.16E+02 4.38E+02 4.60E+02

-2.66E+00 2.16E+00 2.40E+00 2.52E+00 7.56E+00 5.45E+00 2.50E+00 7.49E+00 5.59E+00 1.10E+00 5.70E+00 6.40E+00 MW-38 MW-38 015 25.4

-11.1 7/6/2006 12:00 5.93E+02 4.20E+02 4.52E+02

-3.70E-01 4.50E-01 5.20E-01 3.40E+00 1.02E+01 7.70E+00 2.98E+00 8.95E+00 7.41E+00 NA NA NA MW-38 MW-38 016 25.4

-11.1 8/7/2006 13:23 2.15E+02 1.80E+02 1.74E+02 5.00E-02 6.30E-01 7.10E-01 2.29E+00 6.47E+00 9.51E+00

-7.22E-01 6.90E+00 9.33E+00 2.75E+01 2.94E+01 3.13E+01 MW-38 MW-38 017 25.4

-11.1 9/5/2006 11:30 3.53E+02 1.86E+02 1.67E+02

-5.30E-01 7.80E-01 8.70E-01 3.81E-01 7.68E+00 8.63E+00

-4.48E-01 6.20E+00 6.42E+00 NA NA NA MW-38 MW-38 018 25.4

-11.1 11/22/2006 10:38 1.78E+02 4.08E+02 4.50E+02

-7.00E-02 6.60E-01 7.30E-01 3.13E+00 9.38E+00 7.14E+00 3.08E+00 9.25E+00 7.53E+00 NA NA NA MW-38 MW-38 019 25.4

-11.1 2/12/2007 9:58 2.24E+03 6.00E+02 5.30E+02

-5.10E-01 1.32E+00 1.50E+00 2.73E+00 1.92E+00 2.00E+00

-1.03E+00 1.41E+00 1.80E+00 NA NA NA MW-38 MW-38 020 25.4

-11.1 8/16/2007 11:30 6.04E+02 1.53E+02 1.44E+02

-9.21E-02 6.92E-01 8.85E-01 1.21E+00 3.07E+00 3.65E+00 2.48E+00 3.01E+00 3.98E+00 NA NA NA MW-38 MW-38 021 25.4

-11.1 4/22/2009 10:45 2.74E+02 1.67E+02 1.77E+02 3.53E-01 7.50E-01 8.49E-01

-2.57E-01 4.41E+00 2.94E+00 6.51E-01 2.55E+00 2.94E+00 NA NA NA MW-38 MW-39-67 001 67 13 5/22/2007 9:53 4.73E+02 1.77E+02 1.31E+02 2.76E+00 8.57E-01 5.71E-01 1.23E-01 1.67E+00 1.85E+00 1.84E+00 1.88E+00 2.08E+00

-3.11E+00 1.06E+01 1.23E+01 MW-39-67 MW-39-67 002 67 13 8/7/2007 16:30 3.25E+02 1.86E+02 1.95E+02 4.78E+00 1.13E+00 6.32E-01 2.59E+00 4.62E+00 3.57E+00 2.62E-01 2.55E+00 2.96E+00 NA NA NA MW-39-67 MW-39-67 003 67 13 1/17/2008 14:35 3.57E+02 1.95E+02 1.83E+02 3.52E+00 1.29E+00 8.53E-01

-1.28E-01 3.17E+00 3.57E+00 1.76E+00 3.63E+00 4.25E+00 NA NA NA MW-39-67 MW-39-67 004 67 13 5/1/2008 13:48 3.18E+02 1.24E+02 1.96E+02 2.21E+00 6.17E-01 6.78E-01

-3.01E-01 1.58E+00 2.53E+00 3.64E-01 1.80E+00 3.11E+00 NA NA NA MW-39-67 MW-39-67 005 67 13 10/23/2008 12:53 4.15E+02 2.01E+02 1.99E+02 3.31E+00 1.12E+00 7.74E-01

-1.28E+00 5.46E+00 5.95E+00

-1.22E-01 5.38E+00 6.06E+00 NA NA NA MW-39-67 MW-39-67 006 67 13 4/9/2009 14:55 3.38E+02 1.67E+02 1.50E+02 3.35E+00 9.68E-01 6.51E-01

-8.08E-01 5.12E+00 3.41E+00 9.19E-01 3.60E+00 4.21E+00 NA NA NA MW-39-67 MW-39-67 007 67 13 11/5/2009 15:11 4.41E+02 1.20E+02 9.84E+01 2.37E+00 7.72E-01 5.02E-01

-6.24E-01 5.07E+00 5.46E+00 2.05E+00 5.21E+00 6.29E+00 NA NA NA MW-39-67 MW-39-67 008 67 13 5/4/2010 15:23 3.79E+02 2.01E+02 2.13E+02 1.26E+00 6.60E-01 6.33E-01 4.66E-01 5.42E+00 6.14E+00 1.30E+00 6.75E+00 7.87E+00 NA NA NA MW-39-67 MW-39-67 009 67 13 7/22/2010 14:26 2.86E+02 1.19E+02 9.90E+01 1.73E+00 6.00E-01 3.90E-01 2.94E+00 6.33E+00 7.80E+00

-5.65E+00 7.25E+00 5.04E+00 NA NA NA MW-39-67 MW-39-67 010 67 13 11/15/2010 16:28 3.74E+02 1.86E+02 3.88E+02 1.96E+00 9.36E-01 1.94E+00

-1.74E+00 3.99E+00 8.40E+00

-3.17E+00 4.38E+00 8.38E+00 NA NA NA MW-39-67 MW-39-67 011 67 13 4/26/2011 14:52 1.09E+04 9.64E+02 4.18E+02 1.74E+00 1.49E+00 1.50E+00

-8.12E-01 8.22E+00 8.78E+00

-4.05E+00 9.42E+00 9.00E+00 NA NA NA MW-39-67 MW-39-67 012 67 13 7/15/2011 13:42 2.24E+03 6.12E+02 4.40E+02 2.55E-01 1.16E+00 1.34E+00

-1.15E-01 8.28E+00 9.19E+00

-2.42E-02 9.72E+00 1.12E+01 NA NA NA MW-39-67 MW-39-67 013 67 13 8/29/2011 13:47 1.49E+04 1.24E+03 4.51E+02 1.08E+00 1.18E+00 1.20E+00 2.23E+00 7.77E+00 8.94E+00 4.82E+00 8.25E+00 1.05E+01 NA NA NA MW-39-67 MW-39-67 014 67 13 12/1/2011 14:04 1.03E+03 5.13E+02 4.75E+02 2.37E+00 1.90E+00 1.76E+00

-3.99E+00 9.24E+00 1.02E+01

-3.39E+00 8.07E+00 9.37E+00 NA NA NA MW-39-67 MW-39-84 001 83.5

-3.5 5/22/2007 10:38 5.91E+02 1.89E+02 1.29E+02 1.72E+00 7.22E-01 5.57E-01

-9.07E-02 1.53E+00 1.69E+00 5.61E-01 1.58E+00 1.81E+00

-1.68E+00 9.99E+00 1.15E+01 MW-39-84 MW-39-84 002 83.5

-3.5 8/7/2007 15:30 2.52E+02 1.77E+02 1.91E+02 7.97E-01 7.18E-01 7.30E-01 3.55E-01 3.07E+00 3.44E+00

-1.11E+00 3.59E+00 3.76E+00 NA NA NA MW-39-84 MW-39-84 003 83.5

-3.5 1/17/2008 13:25 1.43E+02 1.70E+02 1.84E+02 1.78E+00 9.47E-01 7.24E-01

-2.74E+00 2.99E+00 2.86E+00 8.36E-01 2.94E+00 3.50E+00 NA NA NA MW-39-84 MW-39-84 004 83.5

-3.5 5/1/2008 14:10 1.50E+02 1.18E+02 1.96E+02 2.23E+00 7.07E-01 8.93E-01

-2.12E-01 2.24E+00 3.67E+00

-2.12E-01 2.24E+00 3.67E+00 NA NA NA MW-39-84 MW-39-84 005 83.5

-3.5 10/23/2008 12:56 2.34E+02 1.88E+02 1.99E+02 1.04E+00 6.90E-01 5.86E-01 1.74E+00 5.88E+00 6.93E+00 1.12E+00 6.98E+00 8.05E+00 NA NA NA MW-39-84 MW-39-84 006 83.5

-3.5 4/9/2009 15:25 1.85E+02 1.48E+02 1.50E+02 2.05E+00 7.71E-01 6.01E-01

-3.09E-01 4.19E+00 2.79E+00 1.63E+00 2.67E+00 3.42E+00 NA NA NA MW-39-84 MW-39-84 007 83.5

-3.5 11/5/2009 15:14 2.42E+02 1.02E+02 9.56E+01 1.11E+00 6.78E-01 6.28E-01

-1.25E+00 1.06E+01 1.16E+01 3.13E+00 6.23E+00 7.74E+00 NA NA NA MW-39-84 MW-39-84 008 83.5

-3.5 5/4/2010 15:32 2.25E+02 1.95E+02 2.12E+02 1.26E+00 6.00E-01 5.62E-01 1.07E+00 5.85E+00 6.81E+00

-2.75E+00 5.78E+00 5.93E+00 NA NA NA MW-39-84 MW-39-84 009 83.5

-3.5 7/22/2010 14:42 3.70E+02 1.30E+02 1.01E+02 8.43E-01 6.21E-01 5.85E-01

-3.32E+00 6.79E+00 6.90E+00 2.43E+00 6.95E+00 8.54E+00 NA NA NA MW-39-84 MW-39-84 010 83.5

-3.5 11/15/2010 16:38 2.51E+02 2.10E+02 4.59E+02 1.80E+00 8.83E-01 1.86E+00 3.58E+00 4.41E+00 1.05E+01 7.47E+00 4.82E+00 1.24E+01 NA NA NA MW-39-84 MW-39-84 011 83.5

-3.5 4/26/2011 14:25 4.40E+02 4.02E+02 4.13E+02

-2.03E-01 1.15E+00 1.50E+00

-9.39E-01 7.42E+00 7.84E+00

-4.02E-01 6.92E+00 7.41E+00 NA NA NA MW-39-84 MW-39-84 012 83.5

-3.5 7/15/2011 14:33 3.55E+02 4.17E+02 4.40E+02 6.54E-01 1.15E+00 1.27E+00

-1.78E+00 1.43E+01 1.71E+01

-4.89E+00 9.45E+00 8.20E+00 NA NA NA MW-39-84 MW-39-84 013 83.5

-3.5 8/29/2011 13:56 2.38E+02 4.14E+02 4.54E+02 8.64E-01 1.00E+00 1.00E+00 5.19E+00 1.54E+01 9.85E+00

-1.20E+00 9.99E+00 1.04E+01 NA NA NA MW-39-84 MW-39-84 014 83.5

-3.5 12/1/2011 14:17 1.39E+02 4.32E+02 4.88E+02 3.12E+00 2.08E+00 1.81E+00

-1.59E+00 6.48E+00 7.42E+00

-1.71E+00 8.82E+00 1.05E+01 NA NA NA MW-39-84 MW-39-102 001 101.5

-21.5 5/22/2007 10:40 8.05E+02 2.13E+02 1.29E+02 1.32E+00 7.17E-01 6.21E-01

-3.99E-02 1.81E+00 1.99E+00 6.54E-01 1.78E+00 2.11E+00 6.39E-02 1.15E+01 1.32E+01 MW-39-102 MW-39-102 002 101.5

-21.5 8/7/2007 14:25 3.21E+02 1.79E+02 1.88E+02 4.71E-01 5.61E-01 5.95E-01

-7.63E-01 3.35E+00 3.60E+00

-2.47E+00 4.70E+00 4.22E+00 NA NA NA MW-39-102 MW-39-102 003 101.5

-21.5 1/17/2008 13:32 1.54E+02 1.67E+02 1.79E+02 9.88E-01 8.36E-01 7.97E-01 7.42E-01 2.37E+00 2.83E+00 7.91E-01 3.45E+00 2.98E+00 NA NA NA MW-39-102 MW-39-102 004 101.5

-21.5 4/30/2008 14:56 5.03E+02 1.69E+02 2.44E+02 8.83E-01 5.43E-01 7.95E-01

-1.02E+00 2.63E+00 4.00E+00 4.88E-01 1.90E+00 3.34E+00

-1.07E+01 1.40E+01 2.48E+01 MW-39-102 MW-39-102 005 101.5

-21.5 10/22/2008 13:56 1.68E+02 1.83E+02 2.00E+02 1.23E+00 7.18E-01 5.92E-01 6.57E-01 6.18E+00 6.75E+00

-1.90E+00 5.47E+00 5.53E+00 NA NA NA MW-39-102 MW-39-102 006 101.5

-21.5 4/9/2009 15:38 2.20E+02 1.53E+02 1.51E+02 2.40E+00 8.22E-01 6.31E-01

-8.17E-02 5.07E+00 3.38E+00 1.30E+00 3.12E+00 3.80E+00 NA NA NA MW-39-102 MW-39-102 007 101.5

-21.5 11/5/2009 15:12 2.67E+02 1.08E+02 9.93E+01 1.24E+00 1.02E+00 1.05E+00

-2.19E+00 6.51E+00 5.89E+00

-4.22E+00 7.20E+00 6.76E+00 NA NA NA MW-39-102 MW-39-102 008 101.5

-21.5 5/4/2010 15:27 3.93E+02 2.01E+02 2.13E+02 4.15E-01 6.36E-01 6.97E-01

-2.40E+00 5.49E+00 5.72E+00

-5.18E-01 6.30E+00 6.91E+00 NA NA NA MW-39-102 MW-39-102 009 101.5

-21.5 7/22/2010 14:52 2.39E+02 1.49E+02 1.49E+02 4.05E+00 9.93E-01 4.71E-01

-1.08E+00 6.35E+00 6.98E+00

-3.68E+00 5.55E+00 4.42E+00 NA NA NA MW-39-102 MW-39-102 010 101.5

-21.5 11/15/2010 16:12 3.61E+02 1.83E+02 3.84E+02 1.40E+00 9.00E-01 1.93E+00 2.98E+00 3.38E+00 8.21E+00

-4.12E+00 3.52E+00 6.23E+00 NA NA NA MW-39-102 MW-39-102 011 101.5

-21.5 4/26/2011 14:33 1.43E+04 1.09E+03 4.19E+02 1.08E+00 1.85E+00 2.03E+00 4.48E+01 2.08E+01 9.86E+00 6.03E+00 7.96E+00 1.07E+01 NA NA NA MW-39-102 MW-39-102 012 101.5

-21.5 7/15/2011 14:02 1.24E+04 1.20E+03 4.36E+02 5.88E-01 1.09E+00 1.20E+00 3.70E+00 8.76E+00 1.02E+01

-6.84E-01 9.42E+00 9.35E+00 NA NA NA MW-39-102 MW-39-102 013 101.5

-21.5 8/29/2011 14:11 1.90E+04 1.37E+03 4.41E+02

-7.38E-01 1.20E+00 1.60E+00

-3.14E+00 7.92E+00 7.72E+00 4.66E+00 7.83E+00 1.04E+01 NA NA NA MW-39-102 MW-39-102 014 101.5

-21.5 12/1/2011 14:10 1.12E+03 5.25E+02 4.77E+02 2.77E+00 2.06E+00 1.95E+00 1.42E+00 7.68E+00 9.90E+00

-2.95E+00 6.99E+00 7.97E+00 NA NA NA MW-39-102 MW-39-124 001 124

-44 5/22/2007 9:50 2.61E+02 1.49E+02 1.31E+02 9.26E-01 9.70E-01 1.00E+00

-1.15E-01 1.64E+00 1.80E+00

-5.31E-01 1.54E+00 1.63E+00 3.55E+00 1.17E+01 1.33E+01 MW-39-124 MW-39-124 002 124

-44 8/7/2007 13:40 1.92E+02 1.73E+02 1.88E+02 5.90E-01 8.57E-01 9.43E-01

-1.14E+00 2.94E+00 3.06E+00 4.97E-01 3.17E+00 3.61E+00 NA NA NA MW-39-124

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 9 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-39-124 003 124

-44 1/17/2008 15:40 1.67E+02 1.64E+02 1.73E+02 1.48E+00 9.71E-01 8.60E-01 6.55E-01 2.61E+00 3.00E+00 9.85E-01 2.03E+00 2.55E+00 NA NA NA MW-39-124 MW-39-124 004 124

-44 4/30/2008 15:24 2.15E+02 9.50E+01 1.53E+02 1.79E+00 6.60E-01 8.91E-01

-1.23E+00 2.13E+00 3.40E+00 5.87E-01 2.19E+00 3.89E+00

-1.13E+01 1.42E+01 2.52E+01 MW-39-124 MW-39-124 005 124

-44 10/22/2008 14:00 2.31E+02 1.88E+02 2.00E+02 9.42E-01 6.47E-01 5.64E-01 1.03E+00 6.64E+00 7.61E+00 1.63E+00 6.98E+00 8.11E+00 NA NA NA MW-39-124 MW-39-124 006 124

-44 4/9/2009 11:46 1.98E+02 1.50E+02 1.50E+02 9.16E-01 6.33E-01 6.09E-01

-9.45E-02 5.16E+00 3.44E+00

-1.55E-01 3.30E+00 3.67E+00 NA NA NA MW-39-124 MW-39-124 007 124

-44 11/5/2009 12:56 2.68E+02 1.09E+02 1.00E+02 1.87E+00 8.68E-01 7.66E-01

-6.47E-01 5.88E+00 6.55E+00 4.43E+00 7.04E+00 8.98E+00 NA NA NA MW-39-124 MW-39-124 008 124

-44 5/4/2010 12:32 3.08E+02 1.92E+02 2.06E+02 5.90E-01 8.18E-01 8.96E-01

-2.76E-02 5.43E+00 5.45E+00 1.35E-02 5.05E+00 5.58E+00 NA NA NA MW-39-124 MW-39-124 009 124

-44 7/22/2010 11:39 1.12E+02 1.34E+02 1.46E+02 2.25E+00 7.71E-01 5.01E-01

-1.11E+00 8.32E+00 9.28E+00

-4.37E-01 9.75E+00 1.10E+01 NA NA NA MW-39-124 MW-39-124 010 124

-44 11/15/2010 12:46 3.73E+02 1.83E+02 3.86E+02 1.17E+00 8.85E-01 1.93E+00

-6.40E+00 6.71E+00 1.61E+01

-1.31E-01 4.98E+00 1.10E+01 NA NA NA MW-39-124 MW-39-124 011 124

-44 4/26/2011 13:01 1.51E+02 3.70E+02 4.15E+02 5.20E-01 1.37E+00 1.55E+00 9.13E+00 8.56E+00 8.57E+00 3.07E+00 7.52E+00 9.27E+00 NA NA NA MW-39-124 MW-39-124 012 124

-44 7/15/2011 11:44 2.30E+01 3.72E+02 4.39E+02 8.78E-01 1.19E+00 1.27E+00

-4.10E+00 1.13E+01 1.15E+01

-1.82E+00 9.51E+00 9.57E+00 NA NA NA MW-39-124 MW-39-124 013 124

-44 8/29/2011 10:54

-1.02E+01 3.75E+02 4.45E+02 3.16E-01 1.12E+00 1.30E+00

-7.05E+00 1.06E+01 1.01E+01 7.76E+00 1.13E+01 1.46E+01 NA NA NA MW-39-124 MW-39-124 014 124

-44 12/1/2011 11:42 1.73E+02 4.35E+02 4.89E+02

-2.58E-01 1.41E+00 1.82E+00 5.73E-01 7.95E+00 9.19E+00 2.71E+00 7.89E+00 9.85E+00 NA NA NA MW-39-124 MW-39-183 001 182.5

-102.5 5/22/2007 10:08 2.47E+02 1.45E+02 1.29E+02 6.51E-01 8.82E-01 9.53E-01 6.42E-01 1.88E+00 1.89E+00 3.09E-02 1.58E+00 1.79E+00 0.00E+00 1.09E+01 1.25E+01 MW-39-183 MW-39-183 002 182.5

-102.5 8/7/2007 12:40 1.88E+02 1.73E+02 1.89E+02 7.11E-01 8.02E-01 8.32E-01 1.38E+00 5.12E+00 5.12E+00 2.34E+00 4.56E+00 5.46E+00 NA NA NA MW-39-183 MW-39-183 003 182.5

-102.5 1/17/2008 11:55 4.65E+01 1.56E+02 1.82E+02 8.29E-01 6.17E-01 5.82E-01

-3.72E-01 3.51E+00 3.92E+00 0.00E+00 2.03E+00 2.20E+00 NA NA NA MW-39-183 MW-39-183 004 182.5

-102.5 4/30/2008 15:03 1.12E+02 1.06E+02 1.77E+02 1.12E+00 5.66E-01 7.83E-01 1.45E-01 2.45E+00 4.14E+00 7.95E-01 2.60E+00 4.48E+00 1.83E+00 1.46E+01 2.50E+01 MW-39-183 MW-39-183 005 182.5

-102.5 10/22/2008 14:07 5.39E+01 1.73E+02 1.97E+02 3.45E-01 7.29E-01 8.35E-01

-4.16E+00 6.88E+00 7.09E+00

-3.08E+00 7.77E+00 7.39E+00 NA NA NA MW-39-183 MW-39-183 006 182.5

-102.5 4/9/2009 11:45 2.60E+01 1.26E+02 1.50E+02 2.13E-01 6.65E-01 7.61E-01 3.94E-01 6.71E+00 4.47E+00 6.05E-01 3.77E+00 4.33E+00 NA NA NA MW-39-183 MW-39-183 007 182.5

-102.5 11/5/2009 12:57 9.85E+01 9.25E+01 9.87E+01 3.71E-01 7.14E-01 8.05E-01 1.63E+00 9.42E+00 6.01E+00 1.94E+00 6.13E+00 7.46E+00 NA NA NA MW-39-183 MW-39-183 008 182.5

-102.5 5/4/2010 12:51 1.34E+02 1.89E+02 2.10E+02 8.20E-02 5.44E-01 6.90E-01 2.11E+00 6.52E+00 7.73E+00

-2.38E+00 7.59E+00 6.99E+00 NA NA NA MW-39-183 MW-39-183 009 182.5

-102.5 7/22/2010 11:38 1.07E+02 1.12E+02 1.19E+02 2.08E-01 4.19E-01 4.79E-01

-4.62E+00 8.88E+00 9.01E+00

-5.09E+00 9.62E+00 8.98E+00 NA NA NA MW-39-183 MW-39-183 010 182.5

-102.5 11/15/2010 12:53

-8.02E+01 1.61E+02 3.88E+02 4.19E-01 7.56E-01 1.77E+00 1.45E+00 4.83E+00 1.10E+01 3.58E+00 4.93E+00 1.19E+01 NA NA NA MW-39-183 MW-39-183 011 182.5

-102.5 4/26/2011 11:35 1.15E+02 3.54E+02 4.02E+02 1.12E+00 1.56E+00 1.67E+00 6.46E+00 8.88E+00 1.09E+01

-1.52E+00 8.68E+00 8.94E+00 NA NA NA MW-39-183 MW-39-183 012 182.5

-102.5 7/15/2011 11:49 7.02E+01 3.75E+02 4.35E+02 3.45E-01 1.03E+00 1.19E+00 2.51E+00 1.08E+01 1.22E+01

-2.37E+00 1.30E+01 1.37E+01 NA NA NA MW-39-183 MW-39-183 013 182.5

-102.5 8/29/2011 10:45 1.14E+02 3.81E+02 4.33E+02 1.10E+00 1.13E+00 1.10E+00

-3.70E+00 1.05E+01 1.05E+01 5.90E+00 9.54E+00 1.22E+01 NA NA NA MW-39-183 MW-39-183 014 182.5

-102.5 12/1/2011 11:26

-8.23E+01 4.11E+02 4.97E+02 1.34E-01 1.45E+00 1.80E+00

-2.81E+00 1.34E+01 1.59E+01 4.19E+00 8.16E+00 1.46E+01 NA NA NA MW-39-183 MW-39-195 001 195

-115 5/22/2007 12:45 2.55E+02 1.50E+02 1.33E+02 1.30E+00 6.90E-01 5.69E-01 0.00E+00 7.67E+00 4.34E+00 3.54E-01 4.16E+00 4.82E+00

-2.52E+00 9.95E+00 1.15E+01 MW-39-195 MW-39-195 002 195

-115 8/7/2007 12:00 2.00E+02 1.70E+02 1.85E+02 5.92E-01 6.23E-01 6.55E-01

-4.08E-02 4.14E+00 4.06E+00

-2.76E-01 4.56E+00 4.30E+00 NA NA NA MW-39-195 MW-39-195 003 195

-115 1/17/2008 17:28 9.63E+01 1.64E+02 1.84E+02 8.97E-01 8.51E-01 8.38E-01 7.57E-01 4.08E+00 4.05E+00 8.15E-01 3.42E+00 4.01E+00 NA NA NA MW-39-195 MW-39-195 004 195

-115 4/30/2008 16:10 2.74E+02 1.50E+02 2.36E+02 1.21E+00 5.52E-01 8.29E-01

-1.17E+00 2.28E+00 3.71E+00 2.23E-02 2.48E+00 4.21E+00

-2.59E+00 1.45E+01 2.51E+01 MW-39-195 MW-39-195 005 195

-115 10/22/2008 14:26 1.72E+02 1.83E+02 2.00E+02 8.81E-01 7.23E-01 6.88E-01 4.14E+00 5.57E+00 6.90E+00 1.81E+00 6.76E+00 7.96E+00 NA NA NA MW-39-195 MW-39-195 006 195

-115 4/9/2009 12:08 7.46E+01 1.32E+02 1.48E+02 6.89E-01 6.60E-01 7.11E-01

-2.41E-01 8.63E+00 5.75E+00

-1.04E+00 4.80E+00 5.07E+00 NA NA NA MW-39-195 MW-39-195 007 195

-115 11/5/2009 13:03 1.09E+02 9.35E+01 9.86E+01 4.36E-01 7.60E-01 8.53E-01

-2.05E+00 7.00E+00 7.38E+00

-1.01E+00 8.71E+00 9.45E+00 NA NA NA MW-39-195 MW-39-195 008 195

-115 5/4/2010 13:14 6.99E+01 1.64E+02 1.84E+02 6.21E-01 6.54E-01 6.82E-01

-1.56E+00 6.42E+00 6.86E+00

-1.59E-01 6.84E+00 7.63E+00 NA NA NA MW-39-195 MW-39-195 009 195

-115 7/22/2010 12:10 9.26E+01 1.11E+02 1.20E+02 5.61E-01 5.70E-01 5.97E-01 7.86E-01 8.64E+00 9.43E+00

-9.78E-01 8.93E+00 9.62E+00 NA NA NA MW-39-195 MW-39-195 010 195

-115 11/15/2010 13:25 2.16E+02 1.86E+02 4.09E+02 1.52E-01 7.35E-01 1.73E+00

-3.21E+00 4.09E+00 6.54E+00 8.70E+00 4.38E+00 1.20E+01 NA NA NA MW-39-195 MW-39-195 011 195

-115 4/26/2011 12:38 7.04E+03 8.04E+02 4.20E+02 1.88E+00 1.75E+00 1.79E+00

-2.03E+00 1.11E+01 1.28E+01 4.62E+00 8.70E+00 1.13E+01 NA NA NA MW-39-195 MW-39-195 012 195

-115 7/15/2011 11:13 4.19E+03 7.56E+02 4.35E+02 1.10E+00 1.78E+00 1.93E+00 2.79E+00 8.46E+00 9.76E+00 6.38E-01 1.01E+01 1.08E+01 NA NA NA MW-39-195 MW-39-195 013 195

-115 8/29/2011 10:51 1.72E+04 1.31E+03 4.43E+02 4.98E-02 7.50E-01 9.59E-01 7.98E-01 7.62E+00 8.56E+00 2.43E+00 8.19E+00 9.86E+00 NA NA NA MW-39-195 MW-39-195 014 195

-115 12/1/2011 11:28 5.13E+03 8.28E+02 4.87E+02 3.00E-01 1.46E+00 1.75E+00 2.12E+00 7.98E+00 1.03E+01 5.51E-01 9.48E+00 1.22E+01 NA NA NA MW-39-195 MW-40-27 001 26.7 46.5 6/5/2007 11:00 1.56E+02 1.58E+02 1.63E+02

-7.82E-04 6.48E-01 8.50E-01 2.70E-02 3.04E+00 3.39E+00 1.48E+00 2.90E+00 3.17E+00 NA NA NA MW-40-27 MW-40-27 002 26.7 46.5 7/23/2007 12:35 1.62E+02 1.59E+02 1.69E+02 3.32E-01 5.90E-01 6.62E-01 2.52E+00 3.39E+00 3.88E+00

-5.97E-02 3.45E+00 3.83E+00 NA NA NA MW-40-27 MW-40-27 003 26.7 46.5 1/7/2008 16:28 1.44E+02 1.70E+02 1.82E+02

-4.39E-01 4.49E-01 7.84E-01

-4.17E-01 1.74E+00 1.87E+00 6.09E-01 1.70E+00 1.99E+00 NA NA NA MW-40-27 MW-40-27 004 26.7 46.5 8/11/2008 13:19 2.22E+02 1.06E+02 1.72E+02 3.66E-01 4.20E-01 7.05E-01 6.08E-01 2.28E+00 4.00E+00

-3.72E-01 2.56E+00 3.83E+00

-7.57E+00 1.15E+01 2.05E+01 MW-40-27 MW-40-27 005 26.7 46.5 10/28/2008 14:58 1.42E+02 1.80E+02 1.95E+02 4.78E-01 5.84E-01 6.10E-01

-1.55E+00 5.73E+00 6.22E+00

-1.46E+00 6.86E+00 7.41E+00 6.28E+00 1.64E+01 1.85E+01 MW-40-27 MW-40-27 006 26.7 46.5 1/19/2009 14:29 1.20E+02 1.34E+02 1.48E+02 4.82E-01 6.36E-01 6.82E-01 6.25E-01 3.41E+00 3.86E+00 1.46E+00 2.90E+00 3.58E+00

-1.86E+00 1.80E+01 2.09E+01 MW-40-27 MW-40-27 007 26.7 46.5 4/13/2009 14:17 1.98E+02 1.45E+02 1.36E+02

-5.35E-01 7.85E-01 9.65E-01

-1.14E-01 6.86E+00 4.57E+00

-6.04E-02 3.42E+00 3.81E+00

-2.30E+00 1.82E+01 2.12E+01 MW-40-27 MW-40-27 008 26.7 46.5 7/20/2009 14:50 1.54E+02 1.94E+02 2.14E+02 2.47E-01 4.05E-01 4.49E-01 4.50E+00 8.49E+00 5.96E+00

-1.64E+00 5.54E+00 5.88E+00 NA NA NA MW-40-27 MW-40-27 009 26.7 46.5 11/19/2009 14:57 1.17E+02 9.33E+01 9.75E+01

-6.51E-01 7.14E-01 8.71E-01 1.06E+00 4.59E+00 5.44E+00

-2.53E+00 5.33E+00 5.10E+00 NA NA NA MW-40-27 MW-40-27 010 26.7 46.5 2/4/2010 14:40 1.30E+02 1.65E+02 1.83E+02 1.10E-01 4.58E-01 5.59E-01

-1.62E+00 7.83E+00 6.98E+00 2.86E+00 6.71E+00 8.30E+00 NA NA NA MW-40-27 MW-40-27 011 26.7 46.5 4/15/2010 16:00 1.48E+02 1.74E+02 1.93E+02 1.05E-01 6.29E-01 7.95E-01

-1.30E+00 4.02E+00 4.36E+00

-2.98E+00 5.64E+00 4.86E+00 NA NA NA MW-40-27 MW-40-27 012 26.7 46.5 8/26/2010 14:42 1.93E+02 1.26E+02 1.24E+02 2.23E-01 6.54E-01 7.73E-01 1.95E+00 4.50E+00 5.46E+00

-1.03E+00 4.72E+00 5.12E+00 NA NA NA MW-40-27 MW-40-27 013 26.7 46.5 11/29/2010 15:23 2.06E+02 1.49E+02 1.44E+02 1.10E-01 7.98E-01 9.63E-01 3.16E-01 3.38E+00 3.76E+00 1.01E+00 3.63E+00 4.18E+00 NA NA NA MW-40-27 MW-40-27 014 26.7 46.5 3/8/2011 12:55 1.85E+02 2.56E+02 2.65E+02 1.58E-01 1.37E+00 1.61E+00 3.72E-01 6.78E+00 7.39E+00 2.83E+00 8.56E+00 9.99E+00 NA NA NA MW-40-27 MW-40-27 015 26.7 46.5 4/29/2011 13:29 1.77E+02 3.66E+02 4.07E+02 1.18E+00 1.74E+00 1.87E+00 1.91E+00 8.40E+00 9.77E+00

-9.20E-01 9.86E+00 1.15E+01 NA NA NA MW-40-27 MW-40-27 016 26.7 46.5 7/27/2011 15:12 3.69E+01 3.00E+02 3.43E+02

-4.37E-01 1.40E+00 1.93E+00

-2.18E+00 7.35E+00 7.64E+00 1.36E+00 9.03E+00 1.03E+01 NA NA NA MW-40-27 MW-40-27 017 26.7 46.5 12/9/2011 11:50 2.24E+01 4.20E+02 4.90E+02 1.74E-01 1.46E+00 1.77E+00 7.86E-01 7.02E+00 8.97E+00 3.19E+00 7.14E+00 1.03E+01 NA NA NA MW-40-27 MW-40-46 001 46.2 27 6/5/2007 11:50 1.42E+02 1.58E+02 1.66E+02

-3.17E-01 5.82E-01 8.88E-01 7.90E-01 3.59E+00 3.39E+00

-2.35E+00 2.70E+00 2.27E+00 NA NA NA MW-40-46 MW-40-46 002 46.2 27 7/23/2007 12:15 9.48E+01 1.53E+02 1.71E+02 3.50E-01 5.61E-01 6.28E-01

-9.08E-01 3.79E+00 4.09E+00

-1.72E+00 3.07E+00 2.90E+00 NA NA NA MW-40-46 MW-40-46 003 46.2 27 10/12/2007 14:45

-1.59E+01 1.52E+02 1.74E+02

-2.14E-02 5.10E-01 6.85E-01

-3.80E-01 3.72E+00 3.59E+00 4.94E-01 3.72E+00 4.26E+00 NA NA NA MW-40-46 MW-40-46 004 46.2 27 1/7/2008 14:42

-1.96E+01 1.45E+02 1.80E+02 8.04E-01 8.55E-01 8.75E-01

-1.21E+00 2.84E+00 3.00E+00 1.16E+00 2.58E+00 2.82E+00 NA NA NA MW-40-46 MW-40-46 005 46.2 27 8/11/2008 13:35 1.68E+02 1.04E+02 1.71E+02

-3.25E-01 3.77E-01 8.09E-01 1.25E-01 1.99E+00 3.31E+00 1.09E+00 2.05E+00 3.64E+00 4.04E+00 1.17E+01 2.01E+01 MW-40-46 MW-40-46 006 46.2 27 10/28/2008 15:30 8.80E+01 1.74E+02 1.98E+02 6.53E-01 7.02E-01 7.20E-01 2.82E-01 6.58E+00 7.49E+00 1.83E+00 6.30E+00 7.48E+00 9.34E-01 1.71E+01 1.96E+01 MW-40-46 MW-40-46 007 46.2 27 1/19/2009 14:28 7.76E+01 1.33E+02 1.48E+02 2.69E-01 5.01E-01 5.67E-01 8.08E-01 2.88E+00 3.39E+00

-1.19E+00 2.78E+00 2.88E+00

-5.63E+00 1.89E+01 2.22E+01 MW-40-46 MW-40-46 008 46.2 27 4/13/2009 14:40 1.52E+02 1.37E+02 1.36E+02

-1.51E-01 5.21E-01 7.12E-01

-1.13E+00 6.89E+00 4.59E+00

-2.72E-01 4.01E+00 4.40E+00

-5.37E+00 1.97E+01 2.32E+01 MW-40-46 MW-40-46 009 46.2 27 7/20/2009 15:11 1.48E+02 1.92E+02 2.13E+02 5.87E-01 5.81E-01 6.03E-01

-1.03E+00 7.61E+00 7.32E+00

-1.38E+00 6.32E+00 6.66E+00 NA NA NA MW-40-46 MW-40-46 010 46.2 27 11/19/2009 15:07 5.74E+01 8.82E+01 9.82E+01 9.58E-02 5.13E-01 5.92E-01

-9.97E-01 4.25E+00 4.70E+00 1.09E+00 4.54E+00 5.35E+00 NA NA NA MW-40-46 MW-40-46 011 46.2 27 2/4/2010 14:59 9.28E+01 1.62E+02 1.82E+02 6.20E-01 7.56E-01 7.95E-01 2.03E+00 4.53E+00 5.36E+00 1.37E+00 4.96E+00 5.86E+00 NA NA NA MW-40-46 MW-40-46 012 46.2 27 4/15/2010 16:18 2.35E+02 1.38E+02 1.45E+02 3.98E-01 7.23E-01 8.15E-01 2.73E+00 3.30E+00 4.08E+00 1.19E+00 3.40E+00 3.95E+00 NA NA NA MW-40-46 MW-40-46 013 46.2 27 8/26/2010 14:56 1.24E+02 1.22E+02 1.29E+02

-1.83E-01 5.11E-01 7.19E-01 7.02E-01 6.01E+00 6.90E+00 5.48E+00 6.17E+00 8.30E+00 NA NA NA MW-40-46 MW-40-46 014 46.2 27 11/29/2010 16:36 1.63E+02 1.47E+02 1.48E+02 6.60E-02 7.89E-01 9.38E-01 5.82E-01 3.82E+00 4.28E+00 2.06E+00 3.99E+00 4.74E+00 NA NA NA MW-40-46 MW-40-46 015 46.2 27 3/8/2011 12:58 2.48E+02 2.74E+02 2.63E+02 1.03E-01 8.58E-01 1.07E+00 2.82E+00 8.00E+00 9.18E+00 7.99E+00 8.74E+00 1.19E+01 NA NA NA MW-40-46 MW-40-46 016 46.2 27 4/29/2011 13:31 7.82E+01 3.54E+02 4.05E+02

-1.35E-01**

1.88E+00 1.77E+00

-9.96E-01 8.46E+00 9.00E+00

-3.98E+00 9.84E+00 9.04E+00 NA NA NA MW-40-46 MW-40-46 017 46.2 27 7/27/2011 15:55 1.35E+02 3.09E+02 3.44E+02

-9.06E-01 1.26E+00 1.86E+00 2.28E+00 8.85E+00 1.01E+01 5.01E-01 9.30E+00 1.03E+01 NA NA NA MW-40-46 MW-40-46 018 46.2 27 12/9/2011 12:03 9.00E+01 4.17E+02 4.77E+02 2.87E-01 1.62E+00 1.92E+00 1.26E+00 7.41E+00 9.46E+00

-9.20E-01 6.39E+00 8.16E+00 NA NA NA MW-40-46 MW-40-81 001 80.7

-7.5 6/5/2007 12:37 1.63E+02 1.59E+02 1.63E+02

-2.93E-02 6.98E-01 9.11E-01

-1.00E+00 3.09E+00 3.22E+00

-4.70E-03 3.79E+00 3.62E+00 NA NA NA MW-40-81

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 10 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-40-81 002 80.7

-7.5 7/23/2007 13:00 6.95E+01 1.52E+02 1.72E+02 2.45E-01 6.00E-01 6.94E-01

-7.08E-01 4.95E+00 5.20E+00 2.31E+00 3.81E+00 4.95E+00 NA NA NA MW-40-81 MW-40-81 003 80.7

-7.5 10/12/2007 10:52 6.99E+01 1.53E+02 1.73E+02

-9.65E-02 5.05E-01 7.10E-01 5.47E-01 4.00E+00 4.48E+00 7.73E-01 4.02E+00 4.64E+00 NA NA NA MW-40-81 MW-40-81 004 80.7

-7.5 1/7/2008 14:35 1.09E+02 1.64E+02 1.81E+02 2.87E-01 7.05E-01 8.26E-01

-7.49E-01 2.51E+00 2.38E+00

-2.66E-01 1.77E+00 1.95E+00 NA NA NA MW-40-81 MW-40-81 005 80.7

-7.5 8/11/2008 9:43 2.42E+02 1.06E+02 1.71E+02 1.68E-01 3.65E-01 6.52E-01

-7.84E-02 1.69E+00 2.78E+00 2.60E-01 1.92E+00 3.25E+00

-2.96E+00 1.10E+01 1.92E+01 MW-40-81 MW-40-81 006 80.7

-7.5 10/28/2008 11:20 3.04E+01 1.61E+02 1.93E+02

-1.84E-01 4.17E-01 6.28E-01 2.04E+00 5.28E+00 6.24E+00

-8.66E-01 6.75E+00 7.32E+00

-2.38E+00 2.33E+01 2.69E+01 MW-40-81 MW-40-81 007 80.7

-7.5 1/19/2009 10:38 1.61E+02 1.37E+02 1.48E+02 2.92E-01 5.76E-01 6.54E-01

-4.67E-01 3.62E+00 4.01E+00

-1.41E+00 3.77E+00 3.92E+00

-7.55E+00 1.77E+01 2.09E+01 MW-40-81 MW-40-81 008 80.7

-7.5 4/13/2009 11:06 2.31E+02 1.50E+02 1.35E+02

-3.34E-02 6.47E-01 8.17E-01

-1.98E+00 7.17E+00 4.78E+00 3.78E+00 4.67E+00 6.06E+00

-1.26E+01 2.01E+01 2.42E+01 MW-40-81 MW-40-81 009 80.7

-7.5 7/20/2009 11:28 2.13E+02 1.95E+02 2.14E+02

-2.23E-02 4.35E-01 5.48E-01

-7.78E-01 4.98E+00 5.50E+00

-1.11E+00 5.54E+00 5.96E+00 NA NA NA MW-40-81 MW-40-81 010 80.7

-7.5 11/17/2009 13:51 9.11E+01 8.83E+01 9.45E+01

-1.58E-01 6.63E-01 8.17E-01

-4.31E+00 6.09E+00 5.16E+00 2.83E+00 3.76E+00 4.81E+00 NA NA NA MW-40-81 MW-40-81 011 80.7

-7.5 2/4/2010 10:56 1.47E+02 1.65E+02 1.83E+02 3.99E-02 6.37E-01 8.18E-01 1.42E+00 4.00E+00 4.69E+00

-7.18E-03 4.86E+00 5.42E+00 NA NA NA MW-40-81 MW-40-81 012 80.7

-7.5 4/15/2010 12:15 1.92E+02 1.37E+02 1.47E+02 4.25E-01 7.02E-01 7.79E-01 1.72E+00 4.20E+00 4.93E+00 1.08E-01 3.82E+00 4.36E+00 NA NA NA MW-40-81 MW-40-81 013 80.7

-7.5 8/26/2010 11:05 9.08E+01 1.14E+02 1.24E+02 2.45E-01 5.25E-01 6.06E-01

-3.95E+00 5.24E+00 4.96E+00

-2.64E+00 4.68E+00 4.20E+00 NA NA NA MW-40-81 MW-40-81 014 80.7

-7.5 11/29/2010 12:03 2.48E+02 1.58E+02 1.47E+02 1.13E-03 6.45E-01 7.85E-01

-9.67E-01 4.38E+00 4.79E+00

-4.37E-01 4.83E+00 5.28E+00 NA NA NA MW-40-81 MW-40-81 015 80.7

-7.5 3/8/2011 10:17 2.33E+02 2.68E+02 2.63E+02 8.50E-01 1.51E+00 1.67E+00 1.26E+00 1.06E+01 7.71E+00

-1.45E+00 6.08E+00 6.16E+00 NA NA NA MW-40-81 MW-40-81 016 80.7

-7.5 4/29/2011 11:08 3.39E+02 4.12E+02 4.36E+02 1.07E+00 1.58E+00 1.70E+00 3.05E+00 6.90E+00 8.51E+00

-2.66E-01 8.04E+00 8.83E+00 NA NA NA MW-40-81 MW-40-81 017 80.7

-7.5 7/27/2011 13:24

-1.18E+02 2.89E+02 3.48E+02 8.36E-01 1.70E+00 1.90E+00

-3.22E-01 6.48E+00 6.87E+00

-1.05E+00 8.67E+00 8.91E+00 NA NA NA MW-40-81 MW-40-81 018 80.7

-7.5 12/9/2011 10:23

-8.05E+01 4.02E+02 4.86E+02 3.77E-01 1.51E+00 1.79E+00 4.60E-01 2.64E+01 1.18E+01 1.07E+00 1.07E+01 1.39E+01 NA NA NA MW-40-81 MW-40-100 001 100.2

-27 6/5/2007 11:15 1.76E+02 1.61E+02 1.64E+02 3.40E-01 6.16E-01 6.94E-01

-1.92E+00 3.06E+00 3.04E+00

-1.98E+00 3.87E+00 3.59E+00 NA NA NA MW-40-100 MW-40-100 002 100.2

-27 7/23/2007 13:20 8.12E+01 1.55E+02 1.75E+02 2.91E-01 6.18E-01 6.96E-01

-4.67E-01 1.91E+00 2.10E+00 1.78E-01 1.94E+00 2.20E+00 NA NA NA MW-40-100 MW-40-100 003 100.2

-27 10/12/2007 11:03 5.95E+01 1.53E+02 1.73E+02

-7.39E-02 5.75E-01 7.69E-01 1.93E+00 3.57E+00 3.87E+00 8.90E-01 3.30E+00 3.61E+00 NA NA NA MW-40-100 MW-40-100 004 100.2

-27 1/7/2008 11:55 1.98E+01 1.52E+02 1.81E+02

-7.69E-02 5.85E-01 8.00E-01 3.13E-01 2.27E+00 2.60E+00 8.84E-02 2.75E+00 2.86E+00 NA NA NA MW-40-100 MW-40-100 006 100.2

-27 5/30/2008 12:45 1.16E+02 9.84E+01 1.60E+02 1.16E-01 5.60E-01 9.81E-01

-7.43E-01 2.12E+00 3.48E+00

-8.73E-01 2.00E+00 3.15E+00 NA NA NA MW-40-100 MW-40-100 007 100.2

-27 8/11/2008 10:10 1.93E+02 1.05E+02 1.71E+02

-3.44E-02 2.85E-01 5.83E-01

-1.18E-01 1.59E+00 2.68E+00 6.38E-01 1.52E+00 2.70E+00 0.00E+00 1.09E+01 1.89E+01 MW-40-100 MW-40-100 008 100.2

-27 10/28/2008 11:30 8.66E+01 1.73E+02 1.95E+02 1.13E-01 6.37E-01 7.83E-01

-1.25E+00 6.50E+00 7.11E+00 3.92E+00 7.02E+00 8.63E+00

-7.70E-01 1.79E+01 2.06E+01 MW-40-100 MW-40-100 009 100.2

-27 1/19/2009 11:52 4.24E+01 1.30E+02 1.48E+02 1.06E-01 6.03E-01 7.25E-01 6.13E-01 5.97E+00 3.85E+00 1.26E-01 3.15E+00 3.61E+00

-9.80E+00 1.89E+01 2.24E+01 MW-40-100 MW-40-100 010 100.2

-27 4/13/2009 11:07 2.62E+02 1.56E+02 1.35E+02 6.63E-02 5.52E-01 6.82E-01

-2.19E+00 6.60E+00 4.40E+00

-2.09E+00 4.40E+00 4.45E+00

-3.13E-01 1.86E+01 2.17E+01 MW-40-100 MW-40-100 011 100.2

-27 7/20/2009 11:31 1.65E+02 1.97E+02 2.18E+02

-1.75E-01 5.63E-01 7.24E-01 4.36E-01 5.52E+00 6.32E+00 7.15E-01 5.75E+00 6.65E+00 NA NA NA MW-40-100 MW-40-100 012 100.2

-27 11/17/2009 14:34 7.32E+01 9.03E+01 9.89E+01 9.08E-02 6.51E-01 7.90E-01

-1.00E+00 3.72E+00 4.12E+00

-4.90E-01 4.50E+00 4.99E+00 NA NA NA MW-40-100 MW-40-100 013 100.2

-27 2/4/2010 11:10 1.47E+02 1.65E+02 1.82E+02 7.06E-01 7.83E-01 8.05E-01

-7.58E-01 4.26E+00 4.60E+00

-3.34E+00 4.75E+00 4.53E+00 NA NA NA MW-40-100 MW-40-100 014 100.2

-27 4/15/2010 12:16 1.39E+02 1.33E+02 1.46E+02

-1.08E-01 5.37E-01 7.48E-01

-2.83E-01 3.54E+00 3.96E+00

-2.16E+00 5.12E+00 4.80E+00 NA NA NA MW-40-100 MW-40-100 015 100.2

-27 8/26/2010 11:09 1.24E+02 1.37E+02 1.45E+02

-2.33E-01 3.95E-01 6.21E-01 8.87E-01 6.15E+00 7.12E+00 6.51E-01 5.61E+00 6.53E+00 NA NA NA MW-40-100 MW-40-100 016 100.2

-27 11/29/2010 12:12 1.34E+02 1.40E+02 1.46E+02

-2.12E-01 6.70E-01 8.39E-01

-1.46E-01 4.05E+00 4.53E+00 3.11E-01 4.26E+00 4.81E+00 NA NA NA MW-40-100 MW-40-100 017 100.2

-27 3/8/2011 10:27 5.17E+01 2.14E+02 2.64E+02 2.52E-02 1.30E+00 1.58E+00 2.46E+01*

1.35E+01 7.66E+00

-1.40E+00 7.88E+00 8.30E+00 NA NA NA MW-40-100 MW-40-100 018 100.2

-27 4/29/2011 11:27 2.70E+02 4.06E+02 4.38E+02 2.46E-01 1.42E+00 1.67E+00 5.53E+00 7.14E+00 9.23E+00 2.99E+00 7.96E+00 9.80E+00 NA NA NA MW-40-100 MW-40-100 019 100.2

-27 7/27/2011 13:29 1.07E+02 3.12E+02 3.50E+02

-9.50E-01 1.41E+00 1.98E+00 2.29E+00 9.03E+00 1.04E+01 7.10E-01 1.08E+01 1.20E+01 NA NA NA MW-40-100 MW-40-100 020 100.2

-27 12/9/2011 10:28 4.85E+01 4.29E+02 5.00E+02 1.04E+00 1.37E+00 1.41E+00 1.85E+00 7.98E+00 9.93E+00 8.66E-01 7.77E+00 1.01E+01 NA NA NA MW-40-100 MW-40-127 001 127.2

-54 6/5/2007 12:55 1.87E+02 1.62E+02 1.63E+02 2.60E-01 5.05E-01 5.71E-01 7.57E-01 2.98E+00 3.41E+00

-5.59E-03 2.94E+00 3.26E+00 NA NA NA MW-40-127 MW-40-127 002 127.2

-54 7/23/2007 15:15 4.26E+01 1.44E+02 1.68E+02 3.83E-01 5.15E-01 5.73E-01

-1.17E+00 1.67E+00 1.76E+00 2.04E-01 1.59E+00 1.77E+00 NA NA NA MW-40-127 MW-40-127 003 127.2

-54 10/12/2007 11:30 2.83E+01 1.44E+02 1.64E+02 1.01E-01 4.97E-01 6.24E-01

-2.32E+00 3.90E+00 4.06E+00

-1.51E+00 3.72E+00 3.79E+00 NA NA NA MW-40-127 MW-40-127 004 127.2

-54 1/7/2008 12:30 9.75E+00 1.48E+02 1.79E+02 5.17E-01 6.83E-01 7.23E-01 6.45E-01 2.42E+00 2.77E+00 3.24E-01 2.28E+00 2.59E+00 NA NA NA MW-40-127 MW-40-127 006 127.2

-54 5/30/2008 13:00 3.27E+01 9.16E+01 1.63E+02

-4.84E-01 5.30E-01 9.68E-01 6.92E-01 2.23E+00 3.43E+00 1.36E+00 2.00E+00 3.62E+00 NA NA NA MW-40-127 MW-40-127 007 127.2

-54 8/11/2008 10:34 1.68E+02 1.04E+02 1.70E+02 1.65E-01 2.41E-01 4.19E-01 1.24E-01 1.65E+00 2.81E+00 7.30E-03 1.49E+00 2.51E+00

-8.77E+00 1.13E+01 2.01E+01 MW-40-127 MW-40-127 008 127.2

-54 10/28/2008 12:10 7.53E+01 1.70E+02 1.95E+02 4.36E-01 7.10E-01 7.87E-01

-2.53E+00 6.46E+00 6.88E+00

-4.33E+00 8.23E+00 7.68E+00 0.00E+00 1.66E+01 1.93E+01 MW-40-127 MW-40-127 009 127.2

-54 1/19/2009 11:25 9.22E+01 1.33E+02 1.48E+02

-7.90E-02 7.19E-01 9.00E-01

-1.20E+00 3.75E+00 3.94E+00 1.68E+00 3.66E+00 4.45E+00

-3.34E+00 1.85E+01 2.16E+01 MW-40-127 MW-40-127 010 127.2

-54 4/13/2009 11:24 1.52E+02 1.37E+02 1.36E+02 5.56E-02 6.11E-01 7.66E-01

-1.08E+00 7.16E+00 4.77E+00

-1.39E+00 4.58E+00 4.79E+00

-9.13E+00 1.86E+01 2.22E+01 MW-40-127 MW-40-127 011 127.2

-54 7/20/2009 12:09 1.77E+02 1.98E+02 2.18E+02 3.38E-01 6.30E-01 7.11E-01

-3.30E-02 6.03E+00 6.40E+00 1.15E+00 5.50E+00 6.38E+00 NA NA NA MW-40-127 MW-40-127 012 127.2

-54 11/17/2009 14:32 1.04E+02 9.33E+01 9.89E+01 2.64E-01 6.96E-01 7.95E-01 1.35E+00 5.58E+00 6.40E+00

-5.95E-01 6.08E+00 6.66E+00 NA NA NA MW-40-127 MW-40-127 013 127.2

-54 2/4/2010 11:12 8.56E+01 1.62E+02 1.82E+02 4.26E-01 6.79E-01 7.49E-01

-4.37E+00 6.12E+00 5.32E+00 1.98E+00 4.21E+00 5.14E+00 NA NA NA MW-40-127 MW-40-127 014 127.2

-54 4/15/2010 13:13 1.26E+02 1.34E+02 1.47E+02

-5.12E-03 3.50E-01 4.61E-01

-2.40E+00 9.29E+00 9.96E+00 2.32E+00 9.72E+00 1.18E+01 NA NA NA MW-40-127 MW-40-127 015 127.2

-54 8/26/2010 11:16 1.36E+02 1.40E+02 1.47E+02 2.23E-02 2.78E-01 3.67E-01

-5.02E+00 7.95E+00 8.28E+00 6.43E-01 6.48E+00 7.48E+00 NA NA NA MW-40-127 MW-40-127 016 127.2

-54 11/29/2010 12:26 1.22E+02 1.38E+02 1.45E+02 7.34E-01 9.02E-01 9.73E-01

-1.53E-01 4.82E+00 5.43E+00 1.12E+00 4.38E+00 5.06E+00 NA NA NA MW-40-127 MW-40-127 017 127.2

-54 3/8/2011 10:41 1.33E+02 2.40E+02 2.64E+02 1.03E+00 1.40E+00 1.51E+00 5.07E+01*

1.64E+01 7.63E+00 3.45E-01 7.18E+00 7.96E+00 NA NA NA MW-40-127 MW-40-127 018 127.2

-54 4/29/2011 11:26

-2.27E+01 3.60E+02 4.32E+02 5.72E-01 1.78E+00 2.05E+00

-2.13E-01 8.26E+00 8.83E+00

-1.62E+00 9.68E+00 9.87E+00 NA NA NA MW-40-127 MW-40-127 019 127.2

-54 7/27/2011 13:56 1.56E+02 3.15E+02 3.50E+02 4.81E-01 1.64E+00 1.92E+00 1.48E+00 9.06E+00 1.03E+01

-8.00E+00 1.02E+01 7.94E+00 NA NA NA MW-40-127 MW-40-127 020 127.2

-54 12/9/2011 10:40 5.65E+01 4.08E+02 4.71E+02 1.27E+00 1.50E+00 1.51E+00

-1.26E+00 8.91E+00 1.04E+01

-3.35E+00 9.18E+00 1.04E+01 NA NA NA MW-40-127 MW-40-162 001 161.7

-88.5 6/5/2007 14:45 1.40E+02 1.56E+02 1.64E+02 2.94E-01 4.53E-01 5.04E-01

-1.67E+00 5.33E+00 4.95E+00 3.85E-01 4.68E+00 4.53E+00 NA NA NA MW-40-162 MW-40-162 002 161.7

-88.5 7/23/2007 17:40 2.59E+01 1.46E+02 1.73E+02 1.19E-01 4.45E-01 5.07E-01

-2.51E-01 2.81E+00 1.75E+00 7.27E-01 1.45E+00 1.69E+00 NA NA NA MW-40-162 MW-40-162 003 161.7

-88.5 10/12/2007 12:54 4.45E+01 1.49E+02 1.69E+02

-5.48E-02 6.20E-01 8.19E-01

-1.11E+00 4.47E+00 4.05E+00

-1.01E+00 3.31E+00 3.47E+00 NA NA NA MW-40-162 MW-40-162 004 161.7

-88.5 1/7/2008 13:10 4.96E+01 1.56E+02 1.82E+02 7.93E-02 3.63E-01 4.48E-01 4.17E-01 2.52E+00 2.87E+00 3.63E-01 2.40E+00 2.72E+00 NA NA NA MW-40-162 MW-40-162 005 161.7

-88.5 8/11/2008 11:44 2.30E+02 1.08E+02 1.75E+02 7.70E-02 4.19E-01 7.81E-01 6.25E-01 2.43E+00 4.16E+00 3.15E+00 2.07E+00 4.11E+00

-5.27E+00 1.22E+01 2.16E+01 MW-40-162 MW-40-162 006 161.7

-88.5 10/28/2008 13:15 1.12E+02 1.77E+02 1.96E+02 2.80E-01 6.35E-01 7.35E-01

-2.00E+00 5.84E+00 6.26E+00 2.11E+00 6.08E+00 7.29E+00 3.75E+00 1.79E+01 2.04E+01 MW-40-162 MW-40-162 007 161.7

-88.5 1/19/2009 11:47 1.07E+02 1.33E+02 1.48E+02 1.32E-01 5.16E-01 6.16E-01

-3.98E-01 3.32E+00 3.67E+00 4.22E-01 2.96E+00 3.41E+00

-9.17E+00 1.85E+01 2.20E+01 MW-40-162 MW-40-162 008 161.7

-88.5 4/13/2009 12:25 1.42E+02 1.37E+02 1.38E+02 3.28E-01 4.94E-01 5.46E-01

-2.83E+00 5.84E+00 3.89E+00

-6.45E-01 3.81E+00 4.06E+00

-2.90E+00 1.85E+01 2.17E+01 MW-40-162 MW-40-162 009 161.7

-88.5 7/20/2009 12:57 1.24E+02 1.92E+02 2.14E+02 7.42E-02 4.26E-01 5.17E-01

-2.20E-01 5.75E+00 6.31E+00 1.54E+00 5.64E+00 6.56E+00 NA NA NA MW-40-162 MW-40-162 010 161.7

-88.5 11/17/2009 15:15 2.87E+01 8.52E+01 9.80E+01

-4.58E-01 6.48E-01 8.27E-01 9.75E-01 5.70E+00 6.47E+00 3.59E+00 5.43E+00 6.97E+00 NA NA NA MW-40-162 MW-40-162 011 161.7

-88.5 2/4/2010 11:57 2.20E+01 1.59E+02 1.82E+02 8.54E-02 5.94E-01 7.58E-01 4.31E-01 4.82E+00 5.46E+00 9.30E-01 4.44E+00 5.12E+00 NA NA NA MW-40-162 MW-40-162 012 161.7

-88.5 4/15/2010 14:50 1.03E+02 1.32E+02 1.46E+02 9.77E-02 6.63E-01 8.18E-01

-2.73E+00 8.36E+00 8.61E+00 2.35E+00 8.63E+00 1.05E+01 NA NA NA MW-40-162 MW-40-162 013 161.7

-88.5 8/26/2010 12:29 1.02E+02 1.36E+02 1.48E+02 5.09E-01 7.23E-01 7.75E-01 7.14E-01 6.23E+00 7.08E+00 3.52E+00 6.78E+00 8.38E+00 NA NA NA MW-40-162 MW-40-162 014 161.7

-88.5 11/29/2010 12:45 6.40E+01 1.27E+02 1.45E+02

-5.51E-03 6.55E-01 7.94E-01 3.60E-01 4.34E+00 4.91E+00 3.43E-01 4.47E+00 5.03E+00 NA NA NA MW-40-162 MW-40-162 015 161.7

-88.5 3/8/2011 11:02 8.33E+01 2.24E+02 2.63E+02

-1.03E+00 1.07E+00 1.57E+00

-3.72E+00 6.12E+00 5.93E+00

-2.11E+00 6.42E+00 6.37E+00 NA NA NA MW-40-162 MW-40-162 016 161.7

-88.5 4/29/2011 12:26 1.05E+02 3.78E+02 4.33E+02 8.71E-01 1.34E+00 1.46E+00 4.54E+00 1.23E+01 1.42E+01 4.43E-01 9.50E+00 1.08E+01 NA NA NA MW-40-162 MW-40-162 017 161.7

-88.5 7/27/2011 14:40 5.54E+00 2.97E+02 3.44E+02

-8.61E-01 1.58E+00 1.98E+00

-2.44E+00 9.21E+00 8.54E+00

-6.93E-01 8.70E+00 9.41E+00 NA NA NA MW-40-162 MW-40-162 018 161.7

-88.5 12/9/2011 11:02

-2.60E+01 3.42E+02 4.06E+02 6.89E-01 1.75E+00 1.95E+00 1.06E+00 8.43E+00 1.07E+01

-4.71E+00 1.17E+01 1.30E+01 NA NA NA MW-40-162 MW-41-40 002 34.4 20.5 4/12/2006 15:00 7.26E+02 2.07E+02 1.56E+02 2.63E+00 1.74E+00 1.58E+00 2.91E+00 2.62E+00 3.03E+00

-7.58E-01 2.55E+00 2.74E+00 NA NA NA MW-41-40 MW-41-40 003 34.4 20.5 5/25/2006 10:00 6.07E+02 2.22E+02 1.88E+02 5.18E+00 1.46E+00 1.07E+00 4.35E+00 1.06E+01 1.24E+01

-1.16E+00 1.07E+01 1.14E+01 NA NA NA MW-41-40 MW-41-40 004 34.4 20.5 6/12/2006 9:50 6.76E+02 2.00E+02 1.51E+02 3.58E+00 6.83E-01 5.31E-01 5.30E+00 1.02E+01 1.19E+01 9.42E-02 9.32E+00 1.02E+01 NA NA NA MW-41-40

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 11 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-41-40 005 34.4 20.5 7/14/2006 8:45 9.83E+02 2.64E+02 2.07E+02 7.02E+00 2.83E+00 2.09E+00 3.44E+00 1.29E+01 1.63E+01

-2.31E+00 1.07E+01 1.29E+01 NA NA NA MW-41-40 MW-41-40 006 34.4 20.5 8/16/2006 13:15 4.47E+02 1.95E+02 1.68E+02 NA NA NA 7.39E-01 6.84E+00 8.78E+00 1.70E-01 5.46E+00 7.51E+00 NA NA NA MW-41-40 MW-41-40 007 34.4 20.5 11/13/2006 12:55 4.25E+02 1.38E+02 1.30E+02 4.64E+00 8.70E-01 6.90E-01 5.00E-01 5.70E+00 6.90E+00 1.30E+00 6.90E+00 8.20E+00 3.10E+00 5.70E+00 6.40E+00 MW-41-40 MW-41-40 008 34.4 20.5 6/19/2007 14:45 3.91E+03 7.32E+02 3.60E+02 5.99E+00 1.15E+00 7.49E-01

-3.09E+00 4.42E+00 3.28E+00

-3.47E-01 2.81E+00 3.01E+00 2.21E-01 1.27E+01 1.49E+01 MW-41-40 MW-41-40 009 34.4 20.5 8/14/2007 14:35 3.80E+02 1.97E+02 2.00E+02 5.96E+00 1.17E+00 7.45E-01 0.00E+00 3.52E+00 3.31E+00 1.40E+00 4.08E+00 4.00E+00 NA NA NA MW-41-40 MW-41-40 010 34.4 20.5 1/24/2008 16:28 2.15E+02 1.80E+02 1.93E+02 3.05E+00 1.07E+00 7.54E-01 2.67E+00 2.55E+00 2.21E+00

-5.18E-01 2.00E+00 2.16E+00 NA NA NA MW-41-40 MW-41-40 011 34.4 20.5 10/22/2008 14:49 2.21E+03 7.26E+02 5.92E+02 5.91E+00 1.10E+00 4.21E-01 3.07E+00 6.33E+00 7.66E+00

-3.60E+00 8.64E+00 8.40E+00 NA NA NA MW-41-40 MW-41-40 012 34.4 20.5 4/7/2009 15:56 5.71E+02 1.91E+02 1.50E+02 5.38E+00 1.14E+00 6.38E-01 4.26E+00 7.29E+00 4.86E+00 4.60E-01 3.27E+00 3.76E+00 NA NA NA MW-41-40 MW-41-40 013 34.4 20.5 7/24/2009 15:33 6.17E+02 2.51E+02 2.25E+02 4.30E+00 1.05E+00 7.04E-01

-1.73E-01 3.21E+00 3.51E+00 4.32E-01 3.57E+00 3.93E+00 NA NA NA MW-41-40 MW-41-40 014 34.4 20.5 11/10/2009 13:08 3.15E+02 1.11E+02 9.85E+01 4.00E+00 1.10E+00 8.06E-01 1.79E+00 4.50E+00 5.18E+00

-2.03E+00 4.62E+00 4.72E+00 NA NA NA MW-41-40 MW-41-40 015 34.4 20.5 3/1/2010 17:28 9.35E+02 1.91E+02 1.68E+02 4.01E+00 8.98E-01 4.46E-01

-3.97E+00 8.45E+00 8.76E+00 1.01E+00 6.81E+00 6.59E+00 NA NA NA MW-41-40 MW-41-40 016 34.4 20.5 4/19/2010 14:09 4.32E+02 1.79E+02 1.50E+02 2.09E+00 1.05E+00 8.40E-01

-2.56E+00 8.09E+00 8.29E+00

-6.83E-01 8.55E+00 9.32E+00 NA NA NA MW-41-40 MW-41-40 017 34.4 20.5 7/21/2010 13:41 2.79E+03 3.02E+02 1.47E+02 4.37E+00 1.02E+00 6.33E-01 1.59E+00 5.82E+00 7.07E+00

-6.50E-01 7.18E+00 7.61E+00 NA NA NA MW-41-40 MW-41-40 018 34.4 20.5 10/25/2010 16:06 2.43E+03 2.78E+02 1.17E+02 4.08E+00 1.16E+00 6.72E-01 3.32E+00 5.63E+00 6.87E+00

-1.99E+00 6.74E+00 6.96E+00 NA NA NA MW-41-40 MW-41-40 019 34.4 20.5 2/14/2011 14:05 2.03E+03 4.02E+02 2.98E+02 1.15E+01 2.68E+00 1.83E+00 4.60E+00 7.30E+00 8.61E+00 4.22E+00 7.36E+00 9.28E+00 NA NA NA MW-41-40 MW-41-40 020 34.4 20.5 4/20/2011 13:51 4.51E+03 7.36E+02 4.55E+02 2.32E+00 1.57E+00 1.44E+00 2.20E+00 9.22E+00 1.06E+01 3.02E+00 1.06E+01 1.25E+01 NA NA NA MW-41-40 MW-41-40 021 34.4 20.5 7/15/2011 12:30 6.99E+02 4.59E+02 4.41E+02 2.48E+00 1.35E+00 1.19E+00

-1.93E+00 1.09E+01 1.14E+01

-1.11E+00 8.94E+00 9.13E+00 NA NA NA MW-41-40 MW-41-40 022 34.4 20.5 8/4/2011 14:39 5.94E+02 3.57E+02 3.53E+02 1.70E+00 1.87E+00 1.93E+00 4.91E-01 5.97E+00 6.61E+00

-6.02E-02 8.16E+00 8.80E+00 NA NA NA MW-41-40 MW-41-40 023 34.4 20.5 11/28/2011 14:25 6.16E+02 5.13E+02 5.14E+02 6.83E-01 1.73E+00 1.95E+00 6.21E+00 8.16E+00 1.13E+01

-4.82E+00 9.81E+00 1.11E+01 NA NA NA MW-41-40 MW-41-63 001 59.5

-4.6 4/12/2006 14:45 7.01E+02 2.03E+02 1.53E+02 5.49E+00 2.21E+00 1.60E+00 6.98E-01 2.27E+00 2.52E+00

-3.89E-02 2.68E+00 2.78E+00 NA NA NA MW-41-63 MW-41-63 002 59.5

-4.6 5/25/2006 10:20 3.61E+02 2.07E+02 1.92E+02 5.22E+00 1.53E+00 1.10E+00 7.91E-02 9.63E+00 1.15E+01 3.51E+00 7.87E+00 1.07E+01 NA NA NA MW-41-63 MW-41-63 003 59.5

-4.6 6/12/2006 10:05 2.68E+02 1.67E+02 1.52E+02 8.45E-01 5.28E-01 5.86E-01 8.20E-01 8.70E+00 9.55E+00 2.12E+00 7.05E+00 8.29E+00 NA NA NA MW-41-63 MW-41-63 004 59.5

-4.6 7/18/2006 13:04 2.43E+02 1.95E+02 1.92E+02 2.17E+00 9.90E-01 8.04E-01 3.04E+00 9.49E+00 1.11E+01 1.73E-01 8.00E+00 8.75E+00 NA NA NA MW-41-63 MW-41-63 005 59.5

-4.6 8/16/2006 13:00 3.56E+02 1.89E+02 1.70E+02 NA NA NA 3.69E+00 8.12E+00 1.03E+01

-1.55E+00 7.58E+00 7.11E+00 NA NA NA MW-41-63 MW-41-63 006 59.5

-4.6 11/13/2006 13:10 1.57E+02 1.35E+02 1.30E+02 2.06E+00 6.60E-01 6.60E-01

-1.60E+00 4.50E+00 5.70E+00 0.00E+00 5.40E+00 6.60E+00 3.00E+00 6.60E+00 7.30E+00 MW-41-63 MW-41-63 007 59.5

-4.6 6/20/2007 11:05 5.52E+02 1.97E+02 1.86E+02 7.08E+00 1.28E+00 6.27E-01

-3.10E-01 2.37E+00 2.65E+00

-1.06E-02 2.33E+00 2.65E+00

-4.39E-01 1.26E+01 1.48E+01 MW-41-63 MW-41-63 008 59.5

-4.6 8/14/2007 16:10 5.47E+02 2.04E+02 1.99E+02 3.55E+00 9.02E-01 5.31E-01

-2.83E+00 3.40E+00 3.20E+00 1.32E-01 3.48E+00 3.87E+00 NA NA NA MW-41-63 MW-41-63 009 59.5

-4.6 1/25/2008 10:05 3.03E+02 2.79E+02 2.93E+02 3.76E+00 1.13E+00 8.22E-01 0.00E+00 3.33E+00 1.89E+00 5.24E-02 1.64E+00 1.88E+00 NA NA NA MW-41-63 MW-41-63 010 59.5

-4.6 10/22/2008 12:34 6.91E+02 5.73E+02 5.92E+02 5.69E+00 1.13E+00 4.41E-01 2.60E+00 5.59E+00 6.71E+00 9.04E-01 6.08E+00 7.02E+00 NA NA NA MW-41-63 MW-41-63 011 59.5

-4.6 4/23/2009 11:57 5.26E+02 1.85E+02 1.83E+02 4.08E+00 8.84E-01 3.37E-01 4.19E-01 6.80E+00 4.53E+00 1.22E+00 4.19E+00 4.93E+00 NA NA NA MW-41-63 MW-41-63 012 59.5

-4.6 7/24/2009 14:13 4.40E+02 2.34E+02 2.26E+02 2.67E+00 8.02E-01 4.63E-01

-8.28E-01 3.60E+00 3.85E+00

-5.58E-01 3.12E+00 3.31E+00 NA NA NA MW-41-63 MW-41-63 013 59.5

-4.6 11/10/2009 13:30 4.50E+02 1.21E+02 9.90E+01 3.88E+00 9.58E-01 5.92E-01 1.07E+00 3.63E+00 4.24E+00

-4.65E-01 4.35E+00 4.80E+00 NA NA NA MW-41-63 MW-41-63 014 59.5

-4.6 3/1/2010 16:00 2.48E+02 1.59E+02 1.68E+02 2.01E+00 6.78E-01 4.19E-01 3.00E+00 4.84E+00 5.86E+00

-1.07E+00 5.37E+00 5.79E+00 NA NA NA MW-41-63 MW-41-63 015 59.5

-4.6 4/19/2010 14:03 4.36E+02 1.77E+02 1.49E+02 3.66E+00 1.22E+00 7.70E-01

-4.51E+00 1.22E+01 1.52E+01

-7.27E-02 6.99E+00 7.76E+00 NA NA NA MW-41-63 MW-41-63 016 59.5

-4.6 7/21/2010 13:41 5.18E+02 1.68E+02 1.43E+02 4.79E+00 1.09E+00 6.23E-01

-2.71E+00 8.29E+00 8.77E+00 1.61E+00 7.93E+00 9.59E+00 NA NA NA MW-41-63 MW-41-63 017 59.5

-4.6 10/25/2010 12:59 5.06E+02 1.50E+02 1.14E+02 4.25E+00 1.19E+00 7.17E-01 1.06E+00 6.08E+00 7.07E+00 2.87E+00 5.85E+00 7.23E+00 NA NA NA MW-41-63 MW-41-63 018 59.5

-4.6 2/14/2011 13:37 1.23E+03 4.44E+02 3.80E+02 6.92E+00 2.46E+00 1.96E+00 1.24E+00 5.30E+00 6.03E+00 2.69E+00 6.06E+00 7.29E+00 NA NA NA MW-41-63 MW-41-63 019 59.5

-4.6 4/20/2011 13:13 7.58E+02 4.90E+02 4.72E+02

-7.72E-01 1.51E+00 2.03E+00 3.53E+00 8.52E+00 1.01E+01 4.02E+00 8.74E+00 1.09E+01 NA NA NA MW-41-63 MW-41-63 020 59.5

-4.6 7/15/2011 12:51 7.14E+02 4.56E+02 4.35E+02 3.03E+00 1.50E+00 1.30E+00 2.36E+00 7.71E+00 8.88E+00 4.47E-01 6.81E+00 7.51E+00 NA NA NA MW-41-63 MW-41-63 021 59.5

-4.6 8/4/2011 14:20 6.60E+02 3.60E+02 3.51E+02 1.91E+00 1.95E+00 1.96E+00 1.64E+00 7.89E+00 8.72E+00

-1.43E+00 7.29E+00 7.72E+00 NA NA NA MW-41-63 MW-41-63 022 59.5

-4.6 11/28/2011 14:08 6.41E+02 5.22E+02 5.22E+02 6.76E-01 1.73E+00 1.95E+00

-7.79E-01 7.20E+00 8.56E+00

-9.03E-01 7.41E+00 9.17E+00 NA NA NA MW-41-63 MW-42-49 001 42.6 27.1 3/23/2006 11:15 2.63E+03 6.60E+02 5.89E+02 5.19E+01 1.72E+00 4.88E-01 1.02E+05 7.14E+02 1.00E+02 1.94E+02 2.78E+01 2.32E+01 NA NA NA MW-42-49 MW-42-49 002 42.6 27.1 3/31/2006 9:29 2.49E+03 4.49E+02 2.37E+02 2.10E+01 9.96E-01 3.67E-01 6.55E+03 1.24E+02 2.76E+01 2.29E+01 2.10E+01 2.50E+01 NA NA NA MW-42-49 MW-42-49 003 42.6 27.1 4/7/2006 17:52 2.51E+03 7.88E+02 7.37E+02 1.09E+02 2.16E+00 4.09E-01 8.11E+04 7.08E+02 1.01E+02 8.81E+01 2.52E+01 1.97E+01 2.22E+03 1.76E+02 5.84E+01 MW-42-49 MW-42-49 004 42.6 27.1 6/18/2007 15:00 1.34E+03 5.00E+02 3.74E+02 7.73E+01 4.04E+00 6.07E-01 1.90E+04 1.85E+03 1.31E+01 4.29E+00 3.71E+00 4.82E+00 1.03E+03 4.53E+01 1.44E+01 MW-42-49 MW-42-49 007 42.6 27.1 10/4/2007 12:40 2.46E+03 2.87E+02 1.93E+02 4.65E+01 3.12E+00 6.02E-01 3.69E+04 3.14E+03 1.83E+01 1.59E+01 6.25E+00 3.61E+00 1.17E+03 4.94E+01 1.88E+01 MW-42-49 MW-42-49 008 42.6 27.1 1/21/2008 16:11 1.32E+03 5.25E+02 4.15E+02 3.34E+01 3.18E+00 9.11E-01 3.38E+04 2.93E+03 2.02E+01 0.00E+00 4.13E+00 5.42E+00 5.01E+02 5.01E+01 2.68E+01 MW-42-49 MW-42-49 010 42.6 27.1 5/13/2008 13:20 3.24E+03 2.56E+02 1.44E+02 2.36E+01 1.54E+00 5.48E-01 1.41E+04 7.89E+02 1.47E+01 1.69E+01 4.47E+00 4.67E+00 7.34E+02 2.85E+01 2.19E+01 MW-42-49 MW-42-49 011 42.6 27.1 8/4/2008 14:24 3.16E+03 2.65E+02 1.91E+02 3.56E+01 1.72E+00 5.59E-01 1.06E+04 6.13E+02 1.20E+01

-8.47E-03 2.69E+00 4.52E+00 3.13E+02 2.60E+01 2.61E+01 MW-42-49 MW-42-49 012 42.6 27.1 9/5/2008 12:52 1.32E+04 8.36E+02 5.08E+02 2.96E+02 4.98E+00 4.02E-01 2.21E+04 1.38E+03 1.58E+01 NA NA NA 4.62E+02 2.17E+01 2.03E+01 MW-42-49 MW-42-49 013 42.6 27.1 10/31/2008 13:27 2.60E+03 3.77E+02 1.63E+02 9.61E+01 4.34E+00 4.16E-01 1.78E+04 1.58E+03 1.83E+01 5.88E-01 6.96E+00 7.78E+00 2.71E+02 2.73E+01 1.99E+01 MW-42-49 MW-42-49 014 42.6 27.1 11/17/2008 14:56 1.12E+03 2.01E+02 1.73E+02 1.02E+02 6.96E+00 1.28E+00 1.54E+04 1.16E+03 1.74E+01 3.26E+00 5.21E+00 6.76E+00 2.44E+02 3.00E+01 2.25E+01 MW-42-49 MW-42-49 015 42.6 27.1 1/26/2009 16:16 1.28E+03 3.03E+02 2.06E+02 6.77E+02 1.13E+01 7.44E-01 8.05E+04 8.01E+03 2.66E+01 0.00E+00 5.24E+00 5.56E+00 9.12E+02 4.50E+01 1.90E+01 MW-42-49 MW-42-49 016 42.6 27.1 3/16/2009 14:50 7.22E+04 1.03E+03 1.60E+02 5.88E+02 8.57E+00 7.24E-01 1.40E+05 3.00E+01 2.00E+01 5.23E+00 3.54E+00 2.17E+00 1.16E+03 4.95E+01 2.06E+01 MW-42-49 MW-42-49 017 42.6 27.1 4/17/2009 11:03 2.22E+03 3.29E+02 1.89E+02 2.58E+02 6.63E+00 5.69E-01 8.63E+04 4.86E+01 3.24E+01 2.68E+00 4.67E+00 5.75E+00 9.16E+02 4.11E+01 2.19E+01 MW-42-49 MW-42-49 018 42.6 27.1 8/10/2009 12:00 1.47E+03 2.25E+02 1.79E+02 4.83E+00 1.06E+00 5.30E-01 5.42E+03 4.31E+02 9.57E+00

-1.12E+00 4.84E+00 4.60E+00 7.46E+01 2.37E+01 2.35E+01 MW-42-49 MW-42-49 019 42.6 27.1 10/27/2009 15:34 1.75E+03 2.21E+02 1.67E+02 1.91E+01 2.00E+00 7.46E-01 2.44E+04 1.83E+03 1.64E+01

-1.66E-01 4.70E+00 5.17E+00 1.84E+02 3.04E+01 2.44E+01 MW-42-49 MW-42-49 020 42.6 27.1 2/16/2010 16:49 9.79E+02 1.76E+02 1.53E+02 1.24E+02 5.92E+00 7.03E-01 6.52E+04 7.07E+03 3.33E+01

-9.83E-01 6.81E+00 6.79E+00 7.10E+02 4.05E+01 2.18E+01 MW-42-49 MW-42-49 021 42.6 27.1 4/16/2010 12:59 1.30E+03 4.25E+02 3.71E+02 2.40E+01 2.31E+00 8.23E-01 2.37E+04 2.85E+03 2.92E+01 8.37E-01 1.06E+01 1.23E+01 2.36E+02 2.88E+01 2.07E+01 MW-42-49 MW-42-49 022 42.6 27.1 7/30/2010 11:38 1.69E+03 2.34E+02 1.24E+02 1.39E+01 1.53E+00 3.90E-01 1.87E+04 2.46E+03 2.50E+01 7.33E-01 6.64E+00 7.77E+00 1.77E+02 2.97E+01 2.18E+01 MW-42-49 MW-42-49 023 42.6 27.1 10/27/2010 12:23 1.28E+03 2.03E+02 1.64E+02 1.81E+01 2.31E+00 8.72E-01 2.39E+04 2.94E+03 2.93E+01

-1.67E+00 9.77E+00 1.03E+01 2.24E+02 2.66E+01 2.10E+01 MW-42-49 MW-42-49 024 42.6 27.1 3/4/2011 11:37 1.49E+03 5.14E+02 3.88E+02 2.32E+01 3.34E+00 1.11E+00 3.30E+04 4.42E+03 2.75E+01 1.42E+00 6.78E+00 7.87E+00 3.02E+02 3.04E+01 2.00E+01 MW-42-49 MW-42-49 025 42.6 27.1 4/21/2011 14:04 1.71E+03 5.88E+02 4.80E+02 5.45E+00 2.18E+00 1.45E+00 2.15E+04 2.88E+03 2.08E+01 3.41E+00 9.16E+00 1.09E+01 1.90E+02 2.72E+01 1.73E+01 MW-42-49 MW-42-49 027 42.6 27.1 8/1/2011 12:50 7.78E+02 3.90E+02 3.74E+02 2.60E+00 1.92E+00 1.82E+00 1.57E+04 1.92E+03 2.16E+01 3.58E+00 8.40E+00 1.01E+01 2.80E+02 3.48E+01 2.02E+01 MW-42-49 MW-42-49 028 42.6 27.1 11/3/2011 11:13 1.40E+03 5.70E+02 5.00E+02 8.98E-01 1.51E+00 1.65E+00 3.03E+03 3.90E+02 1.29E+01

-1.75E+00 7.56E+00 9.18E+00 5.77E+01 1.57E+01 1.45E+01 MW-42-49 MW-42-78 001 74

-4.3 3/24/2006 9:45 1.28E+03 5.87E+02 5.75E+02 3.09E-01 3.90E-01 4.08E-01 4.46E+03 1.36E+02 2.22E+01 1.08E+01 1.71E+01 2.08E+01 NA NA NA MW-42-78 MW-42-78 002 74

-4.3 4/7/2006 17:58 7.92E+02 7.04E+02 7.30E+02 1.03E-01 3.68E-01 3.98E-01 1.98E+03 1.19E+02 3.13E+01

-2.34E+00 2.35E+01 2.51E+01 3.66E+01 1.39E+01 1.43E+01 MW-42-78 MW-42-78 003 74

-4.3 6/18/2007 14:40 3.78E+02 1.88E+02 1.88E+02 3.83E-01 5.34E-01 5.78E-01 6.28E+01 1.21E+01 4.11E+00 2.31E+00 3.40E+00 4.00E+00 2.48E+00 1.32E+01 1.52E+01 MW-42-78 MW-42-78 006 74

-4.3 10/4/2007 13:25 4.34E+02 1.94E+02 1.94E+02 2.33E-01 3.09E-01 3.43E-01 3.04E+02 3.44E+01 4.71E+00 3.10E+00 4.04E+00 5.18E+00 6.86E-01 1.53E+01 1.77E+01 MW-42-78 MW-42-78 007 74

-4.3 1/21/2008 15:33 3.46E+02 1.89E+02 1.96E+02

-2.51E-01 6.81E-01 9.32E-01 1.08E+02 1.52E+01 3.35E+00 1.71E-01 3.33E+00 3.61E+00 9.73E+00 2.42E+01 2.75E+01 MW-42-78 MW-42-78 009 74

-4.3 8/4/2008 12:07 6.18E+02 1.50E+02 1.91E+02 3.91E-01 2.57E-01 3.76E-01 2.71E+00 2.02E+00 3.75E+00

-6.44E-01 2.10E+00 3.29E+00

-7.57E-01 1.52E+01 2.68E+01 MW-42-78 MW-42-78 010 74

-4.3 10/31/2008 13:34 5.62E+02 2.12E+02 1.65E+02 4.17E-02 3.01E-01 3.87E-01 3.31E-01 5.68E+00 6.34E+00 8.32E-01 6.72E+00 7.68E+00 3.69E+00 1.77E+01 2.02E+01 MW-42-78 MW-42-78 011 74

-4.3 1/30/2009 11:22 3.65E+02 2.18E+02 2.00E+02 4.40E-01 6.45E-01 7.03E-01 6.70E-01 3.32E+00 3.88E+00

-1.89E-01 3.57E+00 3.99E+00 NA NA NA MW-42-78 MW-42-78 012 74

-4.3 4/17/2009 10:49 2.74E+02 1.88E+02 1.89E+02 4.67E-01 6.74E-01 7.47E-01 1.61E+00 5.85E+00 3.90E+00 5.31E-01 3.60E+00 4.14E+00 6.58E+00 1.91E+01 2.16E+01 MW-42-78 MW-42-78 013 74

-4.3 8/10/2009 12:40 5.19E+02 1.82E+02 1.78E+02 5.90E-01 6.39E-01 6.73E-01 6.07E-01 3.40E+00 3.94E+00 8.71E-01 3.31E+00 3.94E+00

-7.92E+00 1.98E+01 2.32E+01 MW-42-78 MW-42-78 014 74

-4.3 10/27/2009 14:06 5.51E+02 1.73E+02 1.66E+02 9.06E-02 5.20E-01 6.23E-01 1.19E+00 3.54E+00 4.06E+00

-1.12E+00 3.62E+00 3.74E+00

-8.49E-01 1.94E+01 2.25E+01 MW-42-78

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 12 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-42-78 015 74

-4.3 2/16/2010 16:19 3.57E+02 1.49E+02 1.52E+02

-1.14E-01 4.87E-01 6.80E-01 3.92E+00 5.46E+00 6.70E+00

-1.84E-01 4.93E+00 5.52E+00

-9.55E+00 1.76E+01 2.08E+01 MW-42-78 MW-42-78 016 74

-4.3 4/16/2010 13:29 3.93E+02 2.91E+02 3.10E+02 1.81E-01 7.86E-01 9.23E-01 2.22E+00 8.67E+00 1.03E+01

-6.97E+00 9.24E+00 7.54E+00

-6.55E+00 1.76E+01 2.08E+01 MW-42-78 MW-42-78 017 74

-4.3 7/30/2010 12:23 6.31E+02 1.71E+02 1.31E+02 2.78E-02 3.03E-01 3.85E-01

-1.17E-01 7.56E+00 8.30E+00

-7.43E-01 7.04E+00 7.42E+00 1.96E+00 1.31E+01 1.52E+01 MW-42-78 MW-42-78 018 74

-4.3 10/27/2010 13:56 6.13E+02 1.74E+02 1.64E+02

-1.14E-01 4.79E-01 5.87E-01

-1.09E+00 8.69E+00 9.51E+00

-5.11E+00 8.41E+00 7.24E+00

-4.24E+00 1.80E+01 2.09E+01 MW-42-78 MW-42-78 019 74

-4.3 3/4/2011 10:58 5.98E+02 4.06E+02 3.84E+02 8.92E-01 1.47E+00 1.60E+00

-2.03E+00 6.72E+00 6.99E+00 8.03E-02 6.70E+00 7.41E+00 0.00E+00 1.73E+01 1.96E+01 MW-42-78 MW-42-78 020 74

-4.3 4/21/2011 13:45 6.26E+02 4.78E+02 4.77E+02 4.25E-01 1.13E+00 1.32E+00

-9.71E-01 9.16E+00 9.83E+00 3.58E+00 8.56E+00 1.11E+01 5.89E-01 1.49E+01 1.72E+01 MW-42-78 MW-42-78 022 74

-4.3 8/1/2011 12:50 3.97E+02 3.57E+02 3.72E+02

-1.16E-01 1.13E+00 1.49E+00 5.85E-01 7.98E+00 7.65E+00

-5.68E-01 9.45E+00 1.03E+01 1.02E+00 1.17E+01 1.31E+01 MW-42-78 MW-42-78 023 74

-4.3 11/3/2011 11:31 3.23E+02 4.65E+02 5.02E+02

-5.46E-02 1.15E+00 1.49E+00

-2.93E+00 7.32E+00 8.03E+00 1.37E-01 7.74E+00 9.98E+00

-2.26E+00 1.18E+01 1.35E+01 MW-42-78 MW-43-28 002 23.5 25.3 4/12/2006 12:45 3.46E+02 1.79E+02 1.59E+02 9.40E-02 7.40E-01 8.06E-01

-1.44E+00 2.52E+00 2.54E+00 1.56E+00 2.24E+00 2.56E+00 NA NA NA MW-43-28 MW-43-28 003 23.5 25.3 5/25/2006 12:10 1.20E+02 1.83E+02 1.89E+02 2.65E+00 1.89E+00 1.77E+00

-8.64E-01 9.47E+00 1.03E+01

-1.33E-01 9.42E+00 1.06E+01 NA NA NA MW-43-28 MW-43-28 004 23.5 25.3 6/12/2006 12:45 2.30E+02 1.62E+02 1.52E+02 1.39E-01 4.27E-01 5.27E-01 2.85E+00 6.93E+00 7.82E+00

-7.55E-01 5.93E+00 6.39E+00 NA NA NA MW-43-28 MW-43-28 005 23.5 25.3 7/12/2006 9:40 1.09E+02 1.88E+02 1.95E+02 1.10E+00 1.69E+00 1.72E+00 2.41E+00 9.87E+00 1.11E+01

-7.95E-01 8.58E+00 9.11E+00 NA NA NA MW-43-28 MW-43-28 006 23.5 25.3 8/16/2006 12:10 2.60E+02 1.83E+02 1.72E+02 NA NA NA 5.47E-01 8.43E-01 9.56E-01

-5.16E-01 7.70E-01 8.30E-01 NA NA NA MW-43-28 MW-43-28 007 23.5 25.3 6/18/2007 13:30 2.78E+02 1.70E+02 1.74E+02 1.07E+00 5.97E-01 4.86E-01

-3.68E-01 3.13E+00 3.39E+00

-3.72E-01 3.31E+00 3.46E+00 3.58E+00 1.50E+01 1.73E+01 MW-43-28 MW-43-28 008 23.5 25.3 8/13/2007 11:35 9.56E+01 1.71E+02 1.93E+02

-6.25E-01 7.50E-01 1.02E+00

-7.36E-01 3.57E+00 3.68E+00 2.77E-01 2.70E+00 3.12E+00 NA NA NA MW-43-28 MW-43-28 009 23.5 25.3 1/25/2008 11:11 3.06E+02 2.82E+02 2.96E+02 1.46E-01 6.06E-01 7.38E-01 1.88E+00 2.16E+00 2.66E+00 1.46E+00 2.51E+00 3.03E+00 8.44E+00 1.76E+01 1.99E+01 MW-43-28 MW-43-28 010 23.5 25.3 10/31/2008 14:17 2.65E+02 1.58E+02 1.66E+02

-1.08E-01 3.95E-01 5.66E-01 4.07E+00 5.19E+00 6.44E+00

-1.16E+00 6.21E+00 6.63E+00 NA NA NA MW-43-28 MW-43-28 011 23.5 25.3 4/7/2009 12:14 3.14E+02 1.65E+02 1.51E+02

-1.43E-01 5.66E-01 7.05E-01 5.41E-01 5.93E+00 3.95E+00

-1.31E-01 3.45E+00 3.77E+00 NA NA NA MW-43-28 MW-43-28 012 23.5 25.3 7/31/2009 13:10 1.30E+02 1.44E+02 1.56E+02

-2.45E-02 4.13E-01 5.46E-01 1.19E+00 6.04E+00 7.03E+00

-1.16E+00 6.23E+00 6.64E+00 NA NA NA MW-43-28 MW-43-28 013 23.5 25.3 11/10/2009 14:10 1.73E+02 9.72E+01 9.64E+01 1.57E-02 5.19E-01 6.53E-01

-5.72E-02 3.86E+00 4.25E+00 2.17E+00 4.13E+00 4.96E+00 NA NA NA MW-43-28 MW-43-28 014 23.5 25.3 3/2/2010 17:30 2.13E+02 1.56E+02 1.68E+02 1.48E-01 3.81E-01 4.50E-01

-9.17E-01 5.10E+00 5.60E+00 2.29E+00 5.80E+00 6.91E+00 NA NA NA MW-43-28 MW-43-28 015 23.5 25.3 4/19/2010 13:38 2.25E+02 1.39E+02 1.47E+02

-7.48E-02 5.52E-01 7.63E-01

-2.66E-01 5.61E+00 6.36E+00

-1.90E-01 5.61E+00 6.33E+00 NA NA NA MW-43-28 MW-43-28 016 23.5 25.3 7/20/2010 13:48 9.11E+01 1.33E+02 1.47E+02

-6.43E-02 3.80E-01 5.33E-01 5.80E+00 7.53E+00 9.76E+00

-1.44E+00 9.49E+00 1.01E+01 NA NA NA MW-43-28 MW-43-28 017 23.5 25.3 10/25/2010 11:29 1.95E+02 1.17E+02 1.13E+02

-1.98E-01 5.01E-01 6.94E-01 3.36E+00 5.00E+00 6.09E+00

-5.01E-01 5.43E+00 5.84E+00 NA NA NA MW-43-28 MW-43-28 018 23.5 25.3 2/15/2011 13:08 2.54E+02 2.80E+02 2.99E+02

-1.06E+00 1.40E+00 2.00E+00 5.75E-02 1.26E+01 7.06E+00

-3.84E+00 6.84E+00 6.54E+00 NA NA NA MW-43-28 MW-43-28 019 23.5 25.3 4/21/2011 11:15 2.34E+02 4.30E+02 4.72E+02 1.46E+00 1.96E+00 2.04E+00

-9.31E-01 8.74E+00 9.22E+00 4.50E+00 8.60E+00 1.09E+01 NA NA NA MW-43-28 MW-43-28 020 23.5 25.3 8/4/2011 11:15 2.26E+02 3.24E+02 3.50E+02

-1.34E-01 1.42E+00 1.87E+00 4.00E+00 7.35E+00 9.02E+00

-3.51E+00 9.33E+00 9.21E+00 NA NA NA MW-43-28 MW-43-28 021 23.5 25.3 11/22/2011 11:23 1.21E+02 3.60E+02 4.05E+02 1.40E+00 1.81E+00 1.95E+00

-9.87E-02 5.58E+00 7.14E+00

-3.96E+00 8.07E+00 8.55E+00 NA NA NA MW-43-28 MW-43-62 002 51

-2.2 4/12/2006 11:55 2.00E+02 1.65E+02 1.58E+02 4.34E-01 4.63E-01 4.83E-01 3.27E+00 4.04E+00 3.73E+00 1.82E+00 3.09E+00 3.47E+00 NA NA NA MW-43-62 MW-43-62 003 51

-2.2 5/25/2006 12:30 1.24E+02 1.77E+02 1.82E+02 3.23E-01 1.64E+00 1.77E+00

-1.21E+00 1.26E+01 1.36E+01

-2.10E+00 9.81E+00 1.02E+01 NA NA NA MW-43-62 MW-43-62 004 51

-2.2 6/12/2006 12:40 1.29E+02 1.40E+02 1.38E+02 1.25E+00 5.58E-01 5.86E-01 4.97E+00 7.02E+00 7.98E+00

-6.81E-01 7.19E+00 7.85E+00 NA NA NA MW-43-62 MW-43-62 005 51

-2.2 7/12/2006 10:05 2.04E+01 1.53E+02 1.65E+02 4.76E-01 1.46E+00 1.54E+00 1.34E+01 1.10E+01 1.36E+01 3.73E-01 1.01E+01 1.11E+01 NA NA NA MW-43-62 MW-43-62 006 51

-2.2 8/16/2006 11:55 1.08E+02 1.67E+02 1.70E+02 NA NA NA 2.23E-01 9.10E-01 1.01E+00

-1.95E-01 8.33E-01 9.13E-01 NA NA NA MW-43-62 MW-43-62 007 51

-2.2 6/19/2007 9:36 1.97E+02 1.88E+02 2.02E+02 8.55E-01 6.58E-01 6.40E-01

-6.77E-01 3.21E+00 3.42E+00

-8.52E-01 3.10E+00 3.26E+00 1.38E+00 1.33E+01 1.55E+01 MW-43-62 MW-43-62 008 51

-2.2 8/13/2007 12:42 1.14E+02 1.73E+02 1.92E+02 1.29E-01 6.90E-01 8.27E-01

-1.18E+00 3.65E+00 3.89E+00 1.53E-01 3.31E+00 3.80E+00 NA NA NA MW-43-62 MW-43-62 009 51

-2.2 1/25/2008 10:57 1.23E+02 1.74E+02 1.93E+02 1.00E+00 6.47E-01 5.52E-01 4.31E-01 2.42E+00 2.39E+00

-1.11E+00 2.07E+00 2.10E+00 3.76E+00 1.67E+01 1.91E+01 MW-43-62 MW-43-62 010 51

-2.2 10/31/2008 13:16 2.25E+02 1.56E+02 1.66E+02 1.97E-01 4.13E-01 4.74E-01

-3.65E-03 6.45E+00 6.96E+00 2.59E+00 6.30E+00 7.60E+00 NA NA NA MW-43-62 MW-43-62 011 51

-2.2 4/7/2009 13:59 1.34E+02 1.43E+02 1.52E+02 6.85E-01 5.88E-01 5.94E-01 1.18E+01 6.15E+00 4.10E+00

-4.55E-01 3.89E+00 4.22E+00 NA NA NA MW-43-62 MW-43-62 012 51

-2.2 7/31/2009 12:52 1.18E+02 1.46E+02 1.59E+02 8.83E-01 4.79E-01 3.54E-01

-8.49E-01 5.09E+00 5.49E+00

-2.26E-01 7.25E+00 6.57E+00 NA NA NA MW-43-62 MW-43-62 013 51

-2.2 11/10/2009 12:02 1.96E+02 1.01E+02 9.84E+01 1.24E+00 7.10E-01 6.57E-01 3.69E-01 5.16E+00 5.74E+00

-4.87E-01 5.54E+00 5.94E+00 NA NA NA MW-43-62 MW-43-62 014 51

-2.2 3/2/2010 14:46 1.31E+02 1.52E+02 1.68E+02 3.51E-01 3.93E-01 4.05E-01 1.64E+00 4.61E+00 5.43E+00 1.35E+00 4.75E+00 5.61E+00 NA NA NA MW-43-62 MW-43-62 015 51

-2.2 4/19/2010 13:17 2.16E+02 1.39E+02 1.47E+02 6.35E-01 7.10E-01 7.15E-01

-1.08E+00 4.44E+00 4.90E+00 1.30E+00 4.68E+00 5.52E+00 NA NA NA MW-43-62 MW-43-62 016 51

-2.2 7/20/2010 15:07 5.97E+01 1.33E+02 1.51E+02 4.41E-01 4.75E-01 4.94E-01

-1.11E+00 7.96E+00 8.85E+00

-2.40E+00 8.22E+00 8.59E+00 NA NA NA MW-43-62 MW-43-62 017 51

-2.2 10/25/2010 11:06 9.76E+01 1.05E+02 1.12E+02 3.69E-01 7.10E-01 8.03E-01 5.94E-01 6.27E+00 6.81E+00

-6.69E-01 5.37E+00 5.81E+00 NA NA NA MW-43-62 MW-43-62 018 51

-2.2 2/15/2011 13:15 1.82E+02 2.76E+02 3.00E+02 7.75E-01 1.74E+00 1.95E+00 6.59E-01 5.08E+00 5.56E+00

-2.37E-01 5.16E+00 5.52E+00 NA NA NA MW-43-62 MW-43-62 019 51

-2.2 4/21/2011 11:00 1.05E+02 4.12E+02 4.72E+02

-4.65E-01 1.67E+00 2.18E+00

-1.90E+00 9.08E+00 9.35E+00

-2.34E+00 8.70E+00 8.43E+00 NA NA NA MW-43-62 MW-43-62 021 51

-2.2 8/4/2011 11:35 1.66E+02 3.21E+02 3.55E+02

-2.14E-01 1.61E+00 1.93E+00

-1.62E+00 7.95E+00 8.00E+00

-2.98E+00 8.13E+00 8.75E+00 NA NA NA MW-43-62 MW-43-62 022 51

-2.2 11/22/2011 12:22 2.01E+02 3.72E+02 4.10E+02 9.55E-01 1.78E+00 1.96E+00

-1.43E+01 1.42E+01 1.67E+01 1.94E+00 1.06E+01 1.41E+01 NA NA NA MW-43-62 MW-44-66 001 62.4 31.1 3/28/2006 14:05 3.38E+02 1.91E+02 1.73E+02 7.38E-02 1.53E+00 1.67E+00 6.54E-01 1.05E+01 1.17E+01

-2.87E+00 1.02E+01 1.09E+01 NA NA NA MW-44-66 MW-44-66 002 62.4 31.1 5/24/2006 9:05 2.37E+02 1.97E+02 1.92E+02 7.41E-01 4.11E-01 4.45E-01

-3.07E-01 8.97E+00 9.69E+00 4.85E+00 9.06E+00 1.11E+01 NA NA NA MW-44-66 MW-44-66 003 62.4 31.1 7/20/2006 11:15 8.92E+02 2.27E+02 1.63E+02 7.55E-01 1.22E+00 1.31E+00 3.54E+01 1.74E+01 9.59E+00 6.24E-01 7.37E+00 8.48E+00 NA NA NA MW-44-66 MW-44-66 004 62.4 31.1 6/29/2007 15:00 2.68E+02 1.73E+02 1.84E+02

-4.25E-01 7.28E-01 9.04E-01 2.64E-01 3.03E+00 3.47E+00 7.78E-01 3.40E+00 3.98E+00 NA NA NA MW-44-66 MW-44-66 005 62.4 31.1 8/14/2007 13:10 4.17E+02 1.98E+02 2.00E+02 9.30E-02 4.72E-01 5.75E-01

-8.93E-01 2.91E+00 3.08E+00

-3.39E-01 3.40E+00 3.11E+00 NA NA NA MW-44-66 MW-44-66 006 62.4 31.1 10/31/2007 13:30 5.13E+02 1.82E+02 1.81E+02 3.77E-01 4.10E-01 4.21E-01 2.76E+00 4.29E+00 4.81E+00 1.91E+00 3.90E+00 4.71E+00 NA NA NA MW-44-66 MW-44-66 007 62.4 31.1 1/24/2008 12:55 2.91E+02 2.00E+02 2.12E+02 2.85E-01 4.53E-01 4.99E-01 1.73E+01 4.35E+00 2.31E+00 1.40E+00 3.17E+00 2.43E+00 NA NA NA MW-44-66 MW-44-66 008 62.4 31.1 4/30/2008 15:38 1.61E+02 1.19E+02 1.96E+02 4.11E-02 4.06E-01 7.89E-01

-8.72E-02 2.06E+00 3.38E+00 9.13E-01 2.44E+00 4.27E+00 NA NA NA MW-44-66 MW-44-66 009 62.4 31.1 7/25/2008 12:18 5.50E+02 2.55E+02 3.75E+02 3.07E-01 3.66E-01 6.17E-01

-2.33E+00 2.53E+00 3.03E+00

-2.09E-01 1.74E+00 2.85E+00 NA NA NA MW-44-66 MW-44-66 010 62.4 31.1 10/23/2008 13:17 3.18E+02 1.61E+02 1.66E+02 3.23E-01 3.83E-01 3.92E-01

-3.20E+00 5.21E+00 5.30E+00

-1.59E+00 5.73E+00 6.02E+00 NA NA NA MW-44-66 MW-44-66 011 62.4 31.1 2/3/2009 9:40 2.06E+02 1.92E+02 1.97E+02 4.52E-01 7.98E-01 8.95E-01 1.96E+00 3.53E+00 4.18E+00 3.09E+00 3.06E+00 4.12E+00 NA NA NA MW-44-66 MW-44-66 012 62.4 31.1 4/28/2009 13:32 3.10E+02 1.98E+02 2.06E+02 2.20E-01 4.85E-01 5.59E-01

-7.47E-01 6.38E+00 4.25E+00

-1.51E-01 4.49E+00 4.97E+00 NA NA NA MW-44-66 MW-44-66 013 62.4 31.1 7/29/2009 12:56 7.44E+02 2.00E+02 1.88E+02 6.54E-01 7.67E-01 8.08E-01 8.84E-02 6.04E+00 6.70E+00 1.80E+00 5.58E+00 6.69E+00 NA NA NA MW-44-66 MW-44-66 014 62.4 31.1 11/5/2009 16:27 7.15E+02 1.37E+02 9.71E+01 3.23E-01 6.00E-01 6.79E-01

-4.93E+00 8.65E+00 7.60E+00 8.01E-01 4.83E+00 5.53E+00 NA NA NA MW-44-66 MW-44-66 015 62.4 31.1 2/23/2010 16:08 4.37E+02 1.70E+02 1.70E+02 4.84E-02 3.00E-01 3.79E-01 2.33E+00 4.32E+00 5.12E+00

-7.78E-01 4.49E+00 4.87E+00 NA NA NA MW-44-66 MW-44-66 016 62.4 31.1 6/10/2010 15:30 4.75E+02 1.89E+02 1.92E+02 2.16E-01 6.77E-01 7.93E-01

-1.54E+00 5.91E+00 6.37E+00

-1.91E+00 6.06E+00 6.25E+00 NA NA NA MW-44-66 MW-44-66 017 62.4 31.1 7/22/2010 15:47 1.75E+02 1.41E+02 1.47E+02 2.76E-01 5.63E-01 6.43E-01

-3.76E+00 6.86E+00 6.84E+00 1.20E+00 8.52E+00 9.73E+00 NA NA NA MW-44-66 MW-44-66 018 62.4 31.1 10/26/2010 14:46 3.10E+02 1.29E+02 1.11E+02

-1.07E-01 4.30E-01 5.95E-01 4.23E-01 6.24E+00 7.11E+00

-3.70E+00 7.37E+00 7.27E+00 NA NA NA MW-44-66 MW-44-66 019 62.4 31.1 2/18/2011 10:41 4.57E+02 3.90E+02 3.99E+02

-2.94E-01 1.59E+00 1.95E+00 1.74E+00 7.72E+00 8.56E+00

-1.40E+00 7.92E+00 8.46E+00 NA NA NA MW-44-66 MW-44-66 020 62.4 31.1 4/26/2011 13:17 6.87E+02 4.20E+02 4.03E+02 7.05E-01 1.52E+00 1.70E+00

-1.14E-01 9.36E+00 1.03E+01 3.29E+00 1.07E+01 1.31E+01 NA NA NA MW-44-66 MW-44-66 021 62.4 31.1 7/19/2011 15:39 1.62E+03 5.49E+02 4.32E+02

-7.04E-01 6.48E-01 1.06E+00 4.61E+00 9.66E+00 1.16E+01

-5.76E+00 1.11E+01 9.79E+00 NA NA NA MW-44-66 MW-44-66 022 62.4 31.1 8/22/2011 12:08 4.76E+02 4.32E+02 4.45E+02 1.13E-01 9.03E-01 1.11E+00

-7.41E+00 8.73E+00 6.89E+00

-3.14E+00 9.09E+00 9.07E+00 NA NA NA MW-44-66 MW-44-66 023 62.4 31.1 12/8/2011 12:00 3.70E+02 3.84E+02 4.04E+02

-8.25E-01 1.44E+00 1.94E+00 1.99E+00 7.35E+00 9.30E+00 2.32E+00 7.56E+00 1.04E+01 NA NA NA MW-44-66 MW-44-102 001 80 13.5 6/13/2006 10:35 2.53E+02 2.01E+02 1.96E+02 3.53E-01 9.93E-01 1.26E+00

-3.22E+00 8.26E+00 8.67E+00

-7.71E-01 7.99E+00 8.52E+00 NA NA NA MW-44-102 MW-44-102 002 80 13.5 7/20/2006 10:50 3.16E+02 1.82E+02 1.64E+02

-3.39E-01 1.05E+00 1.29E+00

-2.99E+00 9.39E+00 9.83E+00

-2.34E+00 9.50E+00 9.39E+00 NA NA NA MW-44-102 MW-44-102 003 80 13.5 8/4/2006 9:40 7.61E+02 2.30E+02 1.81E+02 NA NA NA

-4.04E+00 8.10E+00 7.76E+00

-2.00E+00 7.01E+00 6.82E+00 NA NA NA MW-44-102 MW-44-102 004 80 13.5 9/13/2006 11:30 2.67E+02 1.94E+02 2.00E+02 NA NA NA 7.19E+00 9.68E+00 1.12E+01

-4.76E-01 8.18E+00 8.99E+00 NA NA NA MW-44-102 MW-44-102 005 80 13.5 6/19/2007 17:46 2.98E+02 1.76E+02 1.83E+02

-1.33E-01 4.81E-01 6.39E-01 1.88E+00 2.15E+00 2.63E+00 6.41E-01 2.02E+00 2.38E+00

-4.92E+00 1.31E+01 1.58E+01 MW-44-102

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 13 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-44-102 006 80 13.5 8/14/2007 14:55 2.84E+02 1.89E+02 1.99E+02 1.97E-01 7.63E-01 8.99E-01

-1.46E+00 2.76E+00 2.77E+00

-1.35E+00 2.79E+00 2.73E+00 NA NA NA MW-44-102 MW-44-102 007 80 13.5 10/31/2007 12:01 3.54E+02 1.76E+02 1.82E+02

-2.58E-01 7.75E-01 9.60E-01

-6.60E-01 2.88E+00 3.11E+00

-1.23E+00 3.60E+00 3.11E+00 NA NA NA MW-44-102 MW-44-102 008 80 13.5 1/24/2008 13:05 4.17E+02 2.94E+02 2.96E+02 2.06E-01 5.16E-01 6.04E-01 1.18E+01 4.64E+00 3.19E+00

-4.44E-03 2.85E+00 3.11E+00 NA NA NA MW-44-102 MW-44-102 009 80 13.5 4/30/2008 15:28 2.56E+02 1.22E+02 1.96E+02 7.90E-02 3.71E-01 7.13E-01 1.03E+00 2.03E+00 3.63E+00

-2.07E+00 3.04E+00 4.52E+00 NA NA NA MW-44-102 MW-44-102 010 80 13.5 7/25/2008 12:18 4.37E+02 2.46E+02 3.75E+02

-2.83E-02 1.83E-01 3.21E-01

-4.07E-01 1.78E+00 2.88E+00 1.35E+00 1.87E+00 3.41E+00 NA NA NA MW-44-102 MW-44-102 011 80 13.5 10/23/2008 13:48 4.75E+02 1.68E+02 1.65E+02 2.01E-01 4.65E-01 5.44E-01 1.72E+00 6.24E+00 7.28E+00 2.39E+00 8.12E+00 8.47E+00 NA NA NA MW-44-102 MW-44-102 012 80 13.5 2/2/2009 12:06 2.57E+02 1.94E+02 1.93E+02 4.66E-01 6.12E-01 6.71E-01 9.83E-01 3.39E+00 4.02E+00

-9.65E-01 3.53E+00 3.74E+00 NA NA NA MW-44-102 MW-44-102 013 80 13.5 4/28/2009 13:34 5.14E+02 1.82E+02 1.80E+02 3.70E-01 7.10E-01 8.03E-01 9.60E-01 8.27E+00 5.51E+00

-2.67E-01 5.18E+00 5.85E+00 NA NA NA MW-44-102 MW-44-102 014 80 13.5 7/29/2009 12:08 4.50E+02 1.86E+02 1.89E+02 4.34E-01 6.99E-01 7.73E-01

-4.62E-02 6.13E+00 6.76E+00

-3.58E-01 5.05E+00 5.49E+00 NA NA NA MW-44-102 MW-44-102 015 80 13.5 11/5/2009 15:23 5.15E+02 1.25E+02 9.78E+01 7.80E-01 7.47E-01 8.12E-01 1.01E+00 5.22E+00 4.51E+00

-4.18E+00 5.71E+00 4.65E+00 NA NA NA MW-44-102 MW-44-102 016 80 13.5 2/17/2010 16:35 5.12E+02 1.71E+02 1.69E+02 2.24E-01 3.57E-01 3.93E-01

-3.93E+00 6.67E+00 5.43E+00 1.47E+00 3.56E+00 4.34E+00 NA NA NA MW-44-102 MW-44-102 017 80 13.5 6/10/2010 13:13 4.94E+02 1.79E+02 1.83E+02

-1.79E-01 5.13E-01 6.74E-01

-2.41E+00 7.89E+00 8.11E+00

-5.22E+00 7.37E+00 6.86E+00 NA NA NA MW-44-102 MW-44-102 018 80 13.5 7/21/2010 13:20 2.76E+02 1.49E+02 1.45E+02 4.11E-01 4.70E-01 4.80E-01 2.38E+00 1.02E+01 1.18E+01

-1.83E+00 8.85E+00 9.25E+00 NA NA NA MW-44-102 MW-44-102 019 80 13.5 10/26/2010 13:32 4.47E+02 1.42E+02 1.12E+02 2.42E-01 5.47E-01 6.33E-01

-2.73E+00 5.49E+00 5.54E+00 6.85E-01 5.38E+00 6.11E+00 NA NA NA MW-44-102 MW-44-102 020 80 13.5 2/18/2011 10:44 3.93E+02 2.90E+02 2.97E+02 2.63E-01 1.86E+00 2.15E+00 2.22E-01 4.96E+00 5.47E+00

-2.93E-01 6.02E+00 6.58E+00 NA NA NA MW-44-102 MW-44-102 021 80 13.5 4/26/2011 12:18 6.70E+02 4.14E+02 3.99E+02 1.09E+00 1.41E+00 1.49E+00 3.59E-01 7.42E+00 8.15E+00

-2.06E+00 7.86E+00 7.82E+00 NA NA NA MW-44-102 MW-44-102 022 80 13.5 7/19/2011 10:53 6.38E+02 4.50E+02 4.39E+02 2.55E-01 1.02E+00 1.19E+00 1.01E+00 6.63E+00 7.60E+00 1.28E+00 6.27E+00 7.47E+00 NA NA NA MW-44-102 MW-44-102 023 80 13.5 8/22/2011 10:43 8.25E+02 4.77E+02 4.57E+02

-1.10E-01 9.69E-01 1.28E+00

-3.22E+00 6.69E+00 6.63E+00 8.99E+00 7.50E+00 1.08E+01 NA NA NA MW-44-102 MW-44-102 024 80 13.5 12/1/2011 12:18 1.05E+03 4.50E+02 4.07E+02

-2.13E-01 1.52E+00 1.93E+00

-7.91E-02 8.73E+00 1.04E+01

-5.88E-01 9.33E+00 1.15E+01 NA NA NA MW-44-102 MW-45-42 001 37 16.6 4/4/2006 17:20 5.18E+02 2.22E+02 2.17E+02 8.83E-01 5.94E-01 5.95E-01 1.41E+01 1.35E+01 1.54E+01

-4.38E-02 1.22E+01 1.34E+01 NA NA NA MW-45-42 MW-45-42 002 37 16.6 5/25/2006 9:25 1.82E+03 3.74E+02 2.45E+02 9.78E-01 1.14E+00 1.18E+00

-7.92E+00 1.21E+01 1.17E+01

-3.97E+00 1.21E+01 1.23E+01 NA NA NA MW-45-42 MW-45-42 003 37 16.6 6/12/2006 10:45 2.27E+03 4.13E+02 2.15E+02 1.02E+00 6.80E-01 7.49E-01 9.06E-02 5.68E+00 6.29E+00 2.61E+00 5.68E+00 6.70E+00 NA NA NA MW-45-42 MW-45-42 004 37 16.6 7/14/2006 9:30 4.19E+02 2.18E+02 2.00E+02 0.00E+00 1.45E+00 1.59E+00 1.22E+00 8.17E+00 9.27E+00 2.33E+00 9.82E+00 1.13E+01 NA NA NA MW-45-42 MW-45-42 005 37 16.6 8/11/2006 10:00 3.16E+03 5.51E+02 2.71E+02 NA NA NA

-1.16E-01 1.51E+00 1.64E+00

-4.26E-01 1.40E+00 1.54E+00 NA NA NA MW-45-42 MW-45-42 006 37 16.6 9/13/2006 11:50 4.15E+03 7.32E+02 3.27E+02 NA NA NA

-1.58E+00 5.85E+00 6.00E+00

-1.46E+00 5.39E+00 5.27E+00 NA NA NA MW-45-42 MW-45-42 007 37 16.6 11/13/2006 13:20 5.25E+02 1.38E+02 1.40E+02

-7.10E-01 7.50E-01 8.50E-01 3.70E+00 5.40E+00 5.60E+00 5.00E-01 6.90E+00 8.30E+00 3.00E-01 3.60E+00 4.10E+00 MW-45-42 MW-45-42 008 37 16.6 6/21/2007 15:05 2.32E+03 6.27E+02 4.36E+02

-6.08E-02 6.25E-01 7.76E-01 1.31E-01 4.14E+00 4.59E+00 2.51E+00 2.82E+00 4.08E+00 3.58E+00 1.30E+01 1.49E+01 MW-45-42 MW-45-42 009 37 16.6 8/15/2007 11:30 1.16E+03 1.80E+02 1.47E+02

-3.79E-01 7.74E-01 9.47E-01 1.92E+00 2.76E+00 3.41E+00 1.19E+00 2.60E+00 3.23E+00 NA NA NA MW-45-42 MW-45-42 010 37 16.6 10/5/2007 11:05 2.22E+03 3.05E+02 1.50E+02 3.55E-01 5.10E-01 5.56E-01 0.00E+00 4.13E+00 1.99E+00 3.65E-01 1.94E+00 2.21E+00 NA NA NA MW-45-42 MW-45-42 011 37 16.6 1/25/2008 12:15 1.44E+03 3.90E+02 2.96E+02 2.08E-01 5.15E-01 6.03E-01 1.60E+00 2.43E+00 2.88E+00 5.96E-01 2.31E+00 2.66E+00 NA NA NA MW-45-42 MW-45-42 012 37 16.6 5/1/2008 15:15 1.13E+03 1.51E+02 1.96E+02

-4.10E-02 3.11E-01 6.29E-01 6.65E-01 1.99E+00 3.47E+00

-1.17E+00 3.62E+00 4.55E+00 NA NA NA MW-45-42 MW-45-42 013 37 16.6 7/25/2008 16:40 2.32E+03 3.77E+02 3.74E+02 3.02E-01 2.75E-01 4.42E-01

-1.77E+00 1.76E+00 2.53E+00 1.09E+00 1.76E+00 3.19E+00 NA NA NA MW-45-42 MW-45-42 014 37 16.6 10/22/2008 14:55 3.14E+03 8.03E+02 5.91E+02 4.62E-01 5.15E-01 5.29E-01

-1.64E+00 5.07E+00 5.26E+00

-3.00E+00 4.93E+00 4.36E+00 NA NA NA MW-45-42 MW-45-42 015 37 16.6 2/2/2009 18:02 1.41E+03 3.27E+02 1.97E+02

-1.78E-01 4.41E-01 6.64E-01

-1.41E+00 2.57E+00 2.67E+00

-1.27E+00 2.55E+00 2.57E+00 NA NA NA MW-45-42 MW-45-42 016 37 16.6 4/23/2009 15:20 5.99E+03 9.50E+02 4.08E+02 2.63E-01 5.33E-01 6.08E-01

-4.68E-01 4.41E+00 2.94E+00

-1.42E+00 2.49E+00 2.48E+00 NA NA NA MW-45-42 MW-45-42 017 37 16.6 7/24/2009 14:30 1.90E+03 3.50E+02 2.31E+02 5.09E-02 7.67E-01 9.17E-01 4.63E-01 5.25E+00 5.40E+00 1.22E+00 3.69E+00 4.48E+00 NA NA NA MW-45-42 MW-45-42 018 37 16.6 11/10/2009 14:49 2.50E+03 2.24E+02 1.04E+02 6.11E-02 6.16E-01 7.60E-01 4.83E-01 4.44E+00 5.17E+00

-8.72E-01 5.57E+00 5.86E+00 NA NA NA MW-45-42 MW-45-42 019 37 16.6 2/17/2010 15:55 3.86E+03 2.88E+02 1.68E+02 6.43E-01 5.02E-01 4.78E-01 2.03E+00 4.29E+00 5.10E+00

-9.48E-01 4.35E+00 4.74E+00 NA NA NA MW-45-42 MW-45-42 020 37 16.6 4/20/2010 16:13 2.02E+03 3.05E+02 1.51E+02 2.96E-01 6.27E-01 7.22E-01 2.94E+00 6.79E+00 7.62E+00

-7.47E+00 8.46E+00 5.97E+00 NA NA NA MW-45-42 MW-45-42 021 37 16.6 7/19/2010 15:38 3.69E+03 3.35E+02 1.43E+02 5.08E-01 6.10E-01 6.47E-01 1.04E+00 7.75E+00 8.85E+00

-1.87E+00 7.10E+00 7.11E+00 NA NA NA MW-45-42 MW-45-42 022 37 16.6 10/22/2010 15:59 2.74E+03 2.90E+02 1.13E+02 9.55E-02 5.19E-01 6.32E-01 1.35E+00 6.04E+00 6.99E+00

-1.65E+00 5.70E+00 5.89E+00 NA NA NA MW-45-42 MW-45-42 023 37 16.6 2/16/2011 16:58 8.12E+03 7.86E+02 3.63E+02 1.03E+00 1.39E+00 1.48E+00

-8.53E-01 5.64E+00 5.99E+00 1.42E+00 6.30E+00 7.17E+00 NA NA NA MW-45-42 MW-45-42 024 37 16.6 4/20/2011 14:09 8.56E+03 1.03E+03 4.65E+02 1.45E+00 1.56E+00 1.61E+00 7.04E-01 6.50E+00 7.46E+00 7.13E+00 1.07E+01 1.29E+01 NA NA NA MW-45-42 MW-45-42 025 37 16.6 7/25/2011 13:23 3.94E+04 2.07E+03 4.36E+02 1.14E+00 1.30E+00 1.37E+00 3.09E+00 7.41E+00 8.65E+00

-2.66E+00 1.01E+01 1.05E+01 NA NA NA MW-45-42 MW-45-42 026 37 16.6 8/23/2011 13:58 2.72E+04 1.63E+03 4.50E+02 1.77E-01 9.15E-01 1.10E+00 8.73E-01 1.12E+01 1.05E+01

-7.52E+00 1.06E+01 8.89E+00 NA NA NA MW-45-42 MW-45-42 027 37 16.6 11/28/2011 15:03 1.65E+03 6.27E+02 5.10E+02 8.10E-01 1.75E+00 1.95E+00 1.21E+00 5.94E+00 7.69E+00

-2.64E+00 6.96E+00 7.84E+00 NA NA NA MW-45-42 MW-45-61 001 58

-4.4 4/4/2006 17:00 2.98E+02 2.18E+02 2.23E+02 1.82E-01 5.03E-01 5.39E-01 8.62E+00 1.14E+01 1.32E+01 1.40E+00 1.02E+01 1.17E+01 NA NA NA MW-45-61 MW-45-61 002 58

-4.4 5/25/2006 9:10 1.71E+03 3.57E+02 2.37E+02 5.63E-01 9.81E-01 1.03E+00 7.76E-01 9.14E+00 1.02E+01 5.35E+00 1.06E+01 1.31E+01 NA NA NA MW-45-61 MW-45-61 003 58

-4.4 6/12/2006 11:00 1.02E+03 2.31E+02 1.56E+02 4.81E-01 5.85E-01 6.90E-01

-4.60E+00 6.63E+00 7.11E+00 9.35E-02 6.22E+00 7.59E+00 NA NA NA MW-45-61 MW-45-61 004 58

-4.4 7/20/2006 12:50 3.72E+02 1.88E+02 1.66E+02 0.00E+00 1.36E+00 1.59E+00

-3.98E-01 5.08E+00 5.30E+00 1.33E+00 3.96E+00 5.02E+00 NA NA NA MW-45-61 MW-45-61 005 58

-4.4 8/11/2006 9:45 1.35E+03 2.88E+02 1.91E+02 NA NA NA 6.43E+00 9.17E+00 1.16E+01

-8.33E-01 9.00E+00 9.75E+00 NA NA NA MW-45-61 MW-45-61 006 58

-4.4 9/13/2006 9:30 1.45E+03 3.09E+02 2.04E+02 NA NA NA

-6.55E+00 7.21E+00 5.92E+00

-3.06E+00 7.35E+00 6.87E+00 NA NA NA MW-45-61 MW-45-61 007 58

-4.4 11/13/2006 11:20 9.57E+02 1.44E+02 1.40E+02 1.73E+00 7.50E-01 7.60E-01

-3.00E-01 4.50E+00 5.30E+00

-3.20E+00 4.50E+00 6.30E+00 2.50E+00 6.60E+00 7.30E+00 MW-45-61 MW-45-61 008 58

-4.4 6/21/2007 12:55 1.47E+03 5.42E+02 4.34E+02

-7.02E-02 7.47E-01 9.67E-01 3.52E+00 4.72E+00 3.52E+00

-7.21E-01 3.56E+00 3.69E+00 3.35E+00 1.49E+01 1.71E+01 MW-45-61 MW-45-61 009 58

-4.4 8/15/2007 11:55 1.50E+03 1.88E+02 1.41E+02 4.74E-02 7.90E-01 9.41E-01 3.33E+00 4.25E+00 4.03E+00

-6.51E-01 3.86E+00 3.59E+00 NA NA NA MW-45-61 MW-45-61 010 58

-4.4 10/5/2007 11:30 2.15E+03 3.03E+02 1.52E+02 4.87E-01 5.23E-01 5.36E-01

-1.73E-01 1.43E+00 1.56E+00 6.59E-02 1.46E+00 1.62E+00 NA NA NA MW-45-61 MW-45-61 011 58

-4.4 1/25/2008 11:55 2.66E+03 4.80E+02 2.96E+02 4.26E-01 5.76E-01 6.21E-01 2.42E+00 3.60E+00 2.52E+00

-2.05E-01 2.88E+00 3.19E+00 NA NA NA MW-45-61 MW-45-61 012 58

-4.4 5/1/2008 10:16 2.21E+03 1.80E+02 1.95E+02 6.93E-01 4.96E-01 7.66E-01 3.16E-01 2.07E+00 3.59E+00

-1.29E+00 2.25E+00 3.53E+00 NA NA NA MW-45-61 MW-45-61 013 58

-4.4 7/25/2008 13:51 1.80E+03 3.46E+02 3.76E+02 2.36E-01 2.45E-01 4.05E-01

-1.88E+00 1.91E+00 2.80E+00 7.83E-01 1.91E+00 3.40E+00 NA NA NA MW-45-61 MW-45-61 014 58

-4.4 10/22/2008 9:33 1.27E+03 6.35E+02 5.90E+02 1.99E-01 5.82E-01 6.91E-01

-1.52E+00 5.07E+00 5.32E+00 1.04E+00 5.73E+00 6.58E+00 NA NA NA MW-45-61 MW-45-61 015 58

-4.4 2/2/2009 13:13 1.36E+03 3.24E+02 1.99E+02

-1.47E-01 7.61E-01 9.47E-01 9.93E-01 3.59E+00 4.20E+00 2.30E-01 3.23E+00 3.66E+00 NA NA NA MW-45-61 MW-45-61 016 58

-4.4 4/23/2009 10:20 1.46E+03 5.45E+02 4.05E+02

-1.37E-01 6.17E-01 8.06E-01

-4.72E-01 4.17E+00 2.78E+00 1.13E+00 2.54E+00 3.01E+00 NA NA NA MW-45-61 MW-45-61 017 58

-4.4 7/24/2009 11:56 1.11E+03 2.93E+02 2.29E+02 1.01E-01 8.04E-01 9.62E-01

-5.29E-01 3.33E+00 3.69E+00 6.08E-01 3.24E+00 3.82E+00 NA NA NA MW-45-61 MW-45-61 018 58

-4.4 11/9/2009 12:53 1.37E+03 1.77E+02 1.05E+02 3.44E-01 5.20E-01 5.74E-01

-4.63E-01 5.99E+00 6.70E+00

-3.73E+00 7.04E+00 6.99E+00 NA NA NA MW-45-61 MW-45-61 019 58

-4.4 2/17/2010 12:55 1.44E+03 2.10E+02 1.68E+02 3.08E-01 3.80E-01 3.95E-01

-8.12E-01 3.86E+00 4.17E+00

-2.61E+00 4.37E+00 4.43E+00 NA NA NA MW-45-61 MW-45-61 020 58

-4.4 4/20/2010 11:13 9.89E+02 2.25E+02 1.45E+02 2.71E-01 7.70E-01 8.89E-01

-8.78E-02 7.91E+00 8.84E+00

-3.82E+00 8.70E+00 8.72E+00 NA NA NA MW-45-61 MW-45-61 021 58

-4.4 7/19/2010 13:28 1.00E+03 2.07E+02 1.48E+02 4.07E-01 5.04E-01 5.30E-01

-2.93E+00 8.29E+00 8.61E+00

-2.24E+00 8.88E+00 9.24E+00 NA NA NA MW-45-61 MW-45-61 022 58

-4.4 10/22/2010 11:54 1.51E+03 2.22E+02 1.12E+02 3.58E-01 5.53E-01 6.05E-01

-2.92E+00 5.78E+00 5.94E+00 1.19E-01 6.92E+00 7.73E+00 NA NA NA MW-45-61 MW-45-61 023 58

-4.4 2/16/2011 16:15 1.84E+03 5.20E+02 3.98E+02

-2.25E-01 1.64E+00 1.96E+00 1.38E+00 4.80E+00 5.41E+00 9.89E-01 5.46E+00 6.15E+00 NA NA NA MW-45-61 MW-45-61 024 58

-4.4 4/20/2011 10:07 2.03E+03 6.12E+02 4.74E+02 7.22E-01 1.36E+00 1.51E+00

-4.02E+00 7.76E+00 7.55E+00

-8.47E-01 7.56E+00 7.91E+00 NA NA NA MW-45-61 MW-45-61 025 58

-4.4 7/25/2011 10:00 5.63E+03 8.49E+02 4.33E+02 9.47E-01 1.19E+00 1.25E+00 1.42E+00 5.79E+00 6.69E+00 2.07E+00 8.34E+00 9.68E+00 NA NA NA MW-45-61 MW-45-61 026 58

-4.4 8/23/2011 10:48 5.91E+03 8.13E+02 4.34E+02 7.01E-01 1.16E+00 1.26E+00

-8.68E-01 7.44E+00 7.90E+00 1.84E+00 6.63E+00 7.89E+00 NA NA NA MW-45-61 MW-45-61 027 58

-4.4 11/28/2011 11:44 2.06E+03 6.72E+02 5.16E+02 4.76E-01 1.70E+00 1.97E+00 3.28E-01 7.41E+00 9.39E+00

-6.01E-01 9.42E+00 1.19E+01 NA NA NA MW-45-61 MW-46 002 10.5 7.6 4/12/2006 17:15 1.38E+03 2.81E+02 1.76E+02 6.24E-01 4.82E-01 4.89E-01 9.28E-01 2.98E+00 3.31E+00

-5.36E-01 2.67E+00 2.88E+00 NA NA NA MW-46 MW-46 003 10.5 7.6 5/24/2006 12:55 9.00E+02 1.71E+03 6.33E+02 3.07E-01 6.15E-01 7.47E-01

-7.06E-02 9.87E+00 1.18E+01 5.38E+00 8.80E+00 1.21E+01 NA NA NA MW-46 MW-46 003 10.5 7.6 5/24/2006 12:55 6.23E+02 2.24E+02 1.87E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-46

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 14 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-46 004 10.5 7.6 6/13/2006 13:10 6.79E+01 1.80E+02 1.91E+02 3.46E-01 1.04E+00 1.33E+00 2.58E+00 7.28E+00 8.29E+00

-9.79E-01 8.23E+00 8.81E+00 NA NA NA MW-46 MW-46 005 10.5 7.6 7/12/2006 13:23 7.86E+02 2.36E+02 1.92E+02 5.77E-01 1.21E+00 1.23E+00 3.98E+00 9.37E+00 1.09E+01 4.49E+00 8.68E+00 1.06E+01 NA NA NA MW-46 MW-46 006 10.5 7.6 8/4/2006 8:40 1.15E+03 2.75E+02 1.98E+02 NA NA NA 1.15E+00 5.05E+00 6.52E+00

-3.50E+00 5.84E+00 5.97E+00 NA NA NA MW-46 MW-46 007 10.5 7.6 9/13/2006 13:15 1.47E+03 3.30E+02 2.19E+02 NA NA NA 3.73E-01 6.01E+00 6.95E+00 2.75E+00 7.27E+00 6.27E+00 NA NA NA MW-46 MW-46 008 10.5 7.6 6/14/2007 13:50 3.43E+03 5.64E+02 2.95E+02 2.15E-01 4.65E-01 5.35E-01 3.08E-01 3.92E+00 4.37E+00 8.52E-02 3.65E+00 4.09E+00

-1.05E+00 1.52E+01 1.78E+01 MW-46 MW-46 009 10.5 7.6 8/1/2007 11:35 6.62E+02 3.50E+02 2.44E+02 7.89E-02 3.66E-01 4.49E-01 6.63E-01 3.52E+00 3.80E+00 6.33E-02 2.43E+00 2.77E+00 NA NA NA MW-46 MW-46 010 10.5 7.6 10/22/2007 14:20 1.67E+03 5.27E+02 4.01E+02 2.17E-01 4.72E-01 5.44E-01 4.68E-01 2.97E+00 3.34E+00

-7.20E-01 2.94E+00 3.09E+00 NA NA NA MW-46 MW-46 011 10.5 7.6 1/22/2008 12:19 5.49E+02 1.74E+02 1.70E+02 5.30E-01 7.71E-01 8.47E-01

-3.99E-01 2.64E+00 2.84E+00 1.73E+00 2.61E+00 3.31E+00 NA NA NA MW-46 MW-46 012 10.5 7.6 4/29/2008 16:00 5.21E+02 1.53E+02 2.20E+02 4.10E-01 3.51E-01 5.64E-01 7.87E-01 2.12E+00 3.75E+00 4.57E-01 2.24E+00 3.90E+00 NA NA NA MW-46 MW-46 013 10.5 7.6 7/24/2008 16:56 7.71E+02 2.75E+02 3.77E+02 2.74E-01 3.07E-01 5.10E-01 6.05E-01 1.96E+00 3.38E+00

-1.89E+00 2.10E+00 3.09E+00 NA NA NA MW-46 MW-46 014 10.5 7.6 10/20/2008 15:27 1.38E+03 6.44E+02 5.89E+02 9.33E-01 5.85E-01 5.11E-01

-2.27E+00 5.88E+00 5.91E+00

-5.88E-01 5.63E+00 6.09E+00 NA NA NA MW-46 MW-46 015 10.5 7.6 2/5/2009 13:46 1.00E+03 2.88E+02 1.96E+02

-1.30E-01 6.23E-01 7.82E-01

-1.68E+00 2.78E+00 2.71E+00 7.02E-01 2.82E+00 3.28E+00 NA NA NA MW-46 MW-46 016 10.5 7.6 4/10/2009 12:31 7.56E+02 2.07E+02 1.48E+02

-7.29E-02 5.46E-01 6.63E-01 9.83E-04 5.58E+00 3.72E+00 1.54E+00 3.68E+00 4.40E+00 NA NA NA MW-46 MW-46 017 10.5 7.6 7/14/2009 13:57 8.32E+02 2.72E+02 2.30E+02 5.25E-01 7.99E-01 8.88E-01

-1.07E-01 3.07E+00 3.40E+00 2.37E+00 4.07E+00 4.55E+00 NA NA NA MW-46 MW-46 018 10.5 7.6 11/6/2009 13:24 1.10E+03 1.67E+02 1.07E+02 8.60E-01 5.09E-01 4.14E-01 2.85E+00 6.25E+00 7.40E+00

-3.06E+00 6.12E+00 5.78E+00 NA NA NA MW-46 MW-46 019 10.5 7.6 2/12/2010 12:44 1.13E+03 2.12E+02 1.82E+02 5.09E-01 5.69E-01 5.98E-01 1.41E+00 3.98E+00 4.64E+00

-1.64E+00 5.68E+00 4.98E+00 NA NA NA MW-46 MW-46 020 10.5 7.6 4/12/2010 11:32 7.62E+02 1.92E+02 1.77E+02 8.57E-01 7.68E-01 7.39E-01

-2.73E+00 1.08E+01 1.14E+01

-2.57E+00 1.05E+01 1.13E+01 NA NA NA MW-46 MW-46 021 10.5 7.6 7/23/2010 13:10 1.92E+03 2.58E+02 1.46E+02 1.80E-01 5.63E-01 6.59E-01 1.28E-01 7.65E+00 8.12E+00

-1.36E+00 7.96E+00 8.34E+00 NA NA NA MW-46 MW-46 022 10.5 7.6 10/28/2010 13:25 3.13E+03 3.08E+02 1.13E+02 3.76E-01 5.09E-01 5.49E-01

-2.05E+00 5.85E+00 5.88E+00 2.98E+00 6.81E+00 8.22E+00 NA NA NA MW-46 MW-46 023 10.5 7.6 2/23/2011 12:46 2.47E+03 5.70E+02 3.98E+02 1.12E+00 1.89E+00 2.06E+00

-2.22E+00 5.28E+00 5.28E+00 5.21E-01 5.10E+00 5.66E+00 NA NA NA MW-46 MW-46 024 10.5 7.6 4/25/2011 11:19 5.25E+03 7.54E+02 3.95E+02 1.48E+00 1.72E+00 1.80E+00

-2.48E+00 7.24E+00 7.06E+00

-4.44E+00 7.44E+00 6.77E+00 NA NA NA MW-46 MW-46 025 10.5 7.6 7/13/2011 13:29 3.08E+03 7.17E+02 2.86E+02 8.44E-01 1.19E+00 1.26E+00 3.71E+00 8.64E+00 1.04E+01

-9.54E-01 1.02E+01 1.08E+01 NA NA NA MW-46 MW-46 026 10.5 7.6 8/17/2011 11:36 3.30E+03 6.72E+02 4.50E+02 8.77E-01 1.21E+00 1.29E+00 3.43E-01 7.86E+00 8.82E+00

-1.10E+00 7.50E+00 7.97E+00 NA NA NA MW-46 MW-46 027 10.5 7.6 10/20/2011 13:35 2.28E+03 4.68E+02 3.46E+02 3.95E-01 1.30E+00 1.52E+00

-4.36E+00 8.19E+00 8.94E+00

-1.03E+00 8.07E+00 1.01E+01 NA NA NA MW-46 MW-47-56 002 53.2 17.1 4/13/2006 12:05 7.60E+02 2.22E+02 1.67E+02 2.27E+00 7.65E-01 7.30E-01 8.27E-02 5.45E+00 5.95E+00

-4.55E-01 5.30E+00 5.77E+00 NA NA NA MW-47-56 MW-47-56 003 53.2 17.1 7/18/2006 10:13 1.54E+02 1.95E+02 1.99E+02 1.91E-01 1.47E+00 1.59E+00 3.70E+00 7.80E+00 9.34E+00 2.47E+00 1.04E+01 1.29E+01 NA NA NA MW-47-56 MW-47-56 004 53.2 17.1 6/20/2007 10:07 5.29E+02 1.95E+02 1.85E+02 5.93E-01 5.25E-01 5.10E-01 0.00E+00 6.66E+00 3.37E+00 3.57E+00 3.71E+00 4.73E+00 NA NA NA MW-47-56 MW-47-56 004 53.2 17.1 6/20/2007 10:07 NA NA NA NA NA NA 0.00E+00 4.28E+00 3.79E+00 1.63E+00 3.17E+00 3.79E+00 3.81E+00 1.32E+01 1.51E+01 MW-47-56 MW-47-56 005 53.2 17.1 8/10/2007 11:00 2.70E+02 1.88E+02 2.02E+02 5.07E-01 8.04E-01 8.91E-01

-3.84E-01 3.48E+00 3.75E+00 1.49E-01 2.94E+00 3.37E+00 NA NA NA MW-47-56 MW-47-56 006 53.2 17.1 7/6/2011 15:32 3.52E+03 6.57E+02 4.48E+02 4.63E-01 1.08E+00 1.22E+00

-1.56E+00 1.11E+01 1.20E+01 1.45E-01 7.41E+00 8.25E+00

-1.99E+01 2.17E+01 2.50E+01 MW-47-56 MW-47-56 007 53.2 17.1 8/18/2011 12:39 5.42E+02 2.76E+02 2.00E+02 1.03E+00 1.28E+00 1.31E+00

-8.54E-01 1.13E+01 1.25E+01 3.86E+00 8.64E+00 1.07E+01

-2.22E+00 1.75E+01 2.00E+01 MW-47-56 MW-47-56 008 53.2 17.1 10/28/2011 11:36 5.31E+03 8.52E+02 4.99E+02

-6.21E-01 8.79E-01 1.40E+00 1.34E+00 8.85E+00 1.07E+01 2.06E-01 1.01E+01 1.29E+01

-6.21E+00 1.24E+01 1.44E+01 MW-47-56 MW-47-80 001 74

-3.7 4/13/2006 11:45 2.33E+03 4.28E+02 2.29E+02 2.73E+00 7.35E-01 6.53E-01

-5.82E-01 4.48E+00 5.14E+00 2.25E-01 3.91E+00 4.76E+00 NA NA NA MW-47-80 MW-47-80 002 74

-3.7 7/18/2006 8:51 1.87E+03 3.87E+02 2.58E+02 2.86E+00 1.43E+00 1.14E+00 1.67E+00 1.05E+01 1.19E+01 2.39E+00 9.21E+00 1.09E+01 NA NA NA MW-47-80 MW-47-80 003 74

-3.7 6/19/2007 11:00 2.36E+03 5.94E+02 3.58E+02 3.27E+00 8.98E-01 5.28E-01 2.05E+00 3.81E+00 4.58E+00

-2.27E+00 4.82E+00 3.92E+00 4.08E-01 1.18E+01 1.38E+01 MW-47-80 MW-47-80 004 74

-3.7 8/10/2007 12:21 3.51E+03 7.25E+02 4.52E+02 3.55E+00 1.21E+00 9.05E-01

-9.39E-02 3.21E+00 3.56E+00

-8.20E-02 3.18E+00 3.50E+00 NA NA NA MW-47-80 MW-47-80 005 74

-3.7 7/6/2011 14:37 1.36E+05 3.36E+03 4.50E+02 1.95E+00 1.33E+00 1.22E+00

-1.57E+00 8.37E+00 8.73E+00

-3.43E+00 7.80E+00 7.13E+00 3.07E+00 2.59E+01 2.89E+01 MW-47-80 MW-47-80 006 74

-3.7 8/18/2011 11:36 1.37E+05 4.08E+03 2.18E+02 8.23E-01 1.22E+00 1.29E+00

-5.83E+00 9.30E+00 8.60E+00

-6.32E-01 8.79E+00 9.27E+00

-1.15E+00 1.88E+01 2.15E+01 MW-47-80 MW-47-80 007 74

-3.7 10/28/2011 13:24 9.68E+04 3.21E+03 5.07E+02 2.13E+00 1.58E+00 1.38E+00

-1.35E+00 6.54E+00 7.91E+00 1.21E+00 6.45E+00 8.88E+00 3.54E+00 1.31E+01 1.46E+01 MW-47-80 MW-48-23 001 20.4

-5 2/8/2006 10:10 1.66E+02 3.26E+02 3.42E+02 1.93E-01 5.04E-01 5.94E-01

-2.14E-01 1.04E+01 1.13E+01 1.46E+00 9.95E+00 1.12E+01 NA NA NA MW-48-23 MW-48-23 002 20.4

-5 4/12/2006 9:58 1.24E+02 4.08E+02 4.52E+02

-1.10E-01 3.90E-01 4.40E-01 3.25E+00 9.75E+00 7.26E+00 2.49E+00 7.47E+00 6.18E+00 NA NA NA MW-48-23 MW-48-23 003 20.4

-5 4/27/2006 13:42 2.38E+02 1.94E+02 2.03E+02

-2.50E-02 4.58E-01 5.04E-01

-1.88E+00 5.06E+00 5.65E+00

-1.19E-01 4.40E+00 5.27E+00 NA NA NA MW-48-23 MW-48-23 004 20.4

-5 5/22/2006 10:30 7.55E+02 4.26E+02 4.46E+02 2.42E-01 2.88E-01 3.10E-01 3.22E+00 9.67E+00 7.12E+00 4.29E+00 1.29E+01 9.62E+00 NA NA NA MW-48-23 MW-48-23 005 20.4

-5 6/9/2006 11:15 2.95E+02 4.14E+02 4.53E+02 3.10E-01 9.88E-01 1.26E+00 1.09E+00 5.21E+00 5.80E+00 3.08E+00 5.41E+00 5.96E+00 NA NA NA MW-48-23 MW-48-23 005 20.4

-5 6/9/2006 11:15 7.37E+02 2.09E+02 1.56E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-48-23 MW-48-23 005 20.4

-5 6/9/2006 11:15 6.03E+01 4.39E+02 6.24E+02 3.70E-01 3.60E-01 4.00E-01 2.59E+00 7.76E+00 5.90E+00 3.25E+00 9.74E+00 7.61E+00 1.60E+01 1.53E+01 1.62E+01 MW-48-23 MW-48-23 006 20.4

-5 7/6/2006 12:00 4.21E+02 4.17E+02 4.52E+02

-2.20E-01 4.20E-01 4.90E-01 2.55E+00 7.64E+00 5.49E+00 2.60E+00 7.79E+00 5.78E+00 NA NA NA MW-48-23 MW-48-23 007 20.4

-5 8/8/2006 10:30 1.04E+02 1.68E+02 1.72E+02 7.00E-02 6.30E-01 7.00E-01 1.93E+00 4.76E+00 5.56E+00 1.99E+00 4.41E+00 5.37E+00 NA NA NA MW-48-23 MW-48-23 008 20.4

-5 9/5/2006 10:05 2.44E+01 1.59E+02 1.72E+02

-6.00E-02 7.80E-01 8.60E-01

-2.90E+00 7.82E+00 8.12E+00 1.05E-01 8.58E+00 1.02E+01 NA NA NA MW-48-23 MW-48-23 009 20.4

-5 11/22/2006 9:23 1.67E+02 4.08E+02 4.50E+02

-7.00E-02 6.30E-01 7.10E-01 3.91E+00 1.17E+01 8.71E+00 3.22E+00 9.67E+00 7.76E+00 NA NA NA MW-48-23 MW-48-23 010 20.4

-5 2/9/2007 10:54 2.72E+02 1.68E+02 1.70E+02

-1.60E-01 1.53E+00 1.70E+00 3.70E-01 1.80E+00 2.00E+00 8.30E-01 2.07E+00 2.30E+00 NA NA NA MW-48-23 MW-48-23 011 20.4

-5 8/16/2007 11:00 3.93E+02 1.64E+02 1.61E+02

-3.94E-01 5.69E-01 8.47E-01 1.66E+00 4.92E+00 3.58E+00 5.36E-01 3.03E+00 3.55E+00 NA NA NA MW-48-23 MW-48-37 001 36

-20.6 2/10/2006 14:10 1.00E+01 4.26E+02 4.73E+02 NA NA NA 1.18E+00 3.54E+00 2.53E+00 2.07E+00 6.21E+00 4.39E+00 NA NA NA MW-48-37 MW-48-37 002 36

-20.6 4/12/2006 10:00

-5.40E+01 4.02E+02 4.52E+02 2.10E-01 3.90E-01 4.30E-01 1.70E+00 5.09E+00 3.53E+00 3.34E+00 1.00E+01 6.89E+00 NA NA NA MW-48-37 MW-48-37 003 36

-20.6 4/27/2006 13:20

-2.15E+02 1.77E+02 2.04E+02

-4.96E-02 3.79E-01 4.20E-01 7.95E+00 9.91E+00 1.01E+01

-3.17E-01 8.42E+00 9.20E+00 NA NA NA MW-48-37 MW-48-37 004 36

-20.6 5/22/2006 10:00 1.39E+02 4.02E+02 4.46E+02

-1.20E-01 3.60E-01 4.10E-01 1.35E+00 4.05E+00 2.94E+00 2.31E+00 6.94E+00 5.00E+00 NA NA NA MW-48-37 MW-48-37 005 36

-20.6 6/9/2006 11:30 5.96E+02 1.38E+03 6.24E+02 1.05E-01 7.89E-01 1.03E+00 1.50E+00 5.71E+00 6.44E+00

-1.58E+00 5.25E+00 5.52E+00 NA NA NA MW-48-37 MW-48-37 005 36

-20.6 6/9/2006 11:30 1.43E+02 1.67E+02 1.66E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-48-37 MW-48-37 005 36

-20.6 6/9/2006 11:30 1.66E+02 4.11E+02 4.53E+02 2.08E+00 4.50E-01 4.00E-01 2.40E+00 7.20E+00 4.95E+00 4.14E+00 1.24E+01 8.50E+00 4.58E+00 1.35E+01 1.46E+01 MW-48-37 MW-48-37 006 36

-20.6 7/6/2006 8:45 1.47E+02 4.08E+02 4.52E+02 1.70E-01 8.10E-01 8.80E-01 2.10E+00 6.31E+00 4.44E+00 4.21E+00 1.26E+01 8.77E+00 NA NA NA MW-48-37 MW-48-37 007 36

-20.6 8/8/2006 10:20 1.09E+01 1.55E+02 1.69E+02 6.00E-02 6.90E-01 7.80E-01 1.86E+00 5.68E+00 6.65E+00 2.95E-01 5.29E+00 5.93E+00 NA NA NA MW-48-37 MW-48-37 008 36

-20.6 9/5/2006 10:20 5.73E+02 2.12E+02 1.75E+02 0.00E+00 6.90E-01 7.70E-01

-2.86E-01 5.59E+00 6.04E+00 1.60E+00 5.35E+00 6.37E+00 NA NA NA MW-48-37 MW-48-37 009 36

-20.6 11/22/2006 9:34 2.62E+02 4.11E+02 4.50E+02 0.00E+00 6.30E-01 7.00E-01 1.60E+00 4.80E+00 3.39E+00 3.58E+00 1.07E+01 7.47E+00 NA NA NA MW-48-37 MW-48-37 010 36

-20.6 2/9/2007 10:59 2.70E+01 1.65E+02 1.70E+02

-1.40E-01 1.38E+00 1.50E+00

-6.10E-01 1.26E+00 1.50E+00

-4.70E-01 1.38E+00 1.60E+00 NA NA NA MW-48-37 MW-48-37 011 36

-20.6 8/16/2007 11:07 1.29E+02 1.59E+02 1.75E+02 4.11E-02 6.27E-01 7.94E-01 1.78E+00 4.35E+00 4.53E+00

-4.00E-01 4.51E+00 5.01E+00 NA NA NA MW-48-37 MW-49-26 001 19.1

-4.4 3/22/2006 16:50 1.54E+04 2.81E+03 1.82E+03 1.84E+01 9.96E-01 4.29E-01

-5.28E-01 9.40E+00 1.02E+01

-1.35E+00 8.98E+00 9.69E+00 NA NA NA MW-49-26 MW-49-26 003 19.1

-4.4 5/19/2006 14:55 9.40E+03 1.50E+03 4.96E+02 9.03E+00 9.40E-01 5.45E-01 2.65E+00 7.87E+00 9.09E+00 1.15E+00 5.99E+00 6.92E+00 NA NA NA MW-49-26 MW-49-26 003 19.1

-4.4 5/19/2006 14:55 1.42E+04 6.75E+03 6.29E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-49-26 MW-49-26 004 19.1

-4.4 6/6/2006 9:55 1.40E+04 2.16E+03 4.95E+02 1.41E+01 1.17E+00 5.80E-01 6.14E+00 1.18E+01 1.41E+01 2.42E+00 1.02E+01 1.21E+01 NA NA NA MW-49-26 MW-49-26 005 19.1

-4.4 7/7/2006 9:15 1.00E+04 2.06E+03 1.51E+03 1.26E+01 2.67E+00 1.51E+00 1.38E+00 8.45E+00 9.49E+00

-1.98E+00 8.42E+00 8.90E+00 NA NA NA MW-49-26 MW-49-26 006 19.1

-4.4 8/1/2006 9:28 1.37E+04 1.13E+03 6.16E+02 NA NA NA

-5.93E+00 6.06E+00 4.56E+00

-3.09E+00 5.14E+00 4.31E+00 3.67E+01 3.09E+01 3.26E+01 MW-49-26 MW-49-26 007 19.1

-4.4 8/28/2006 12:30 1.10E+04 1.12E+03 7.68E+02 NA NA NA

-2.69E+00 5.42E+00 5.50E+00

-3.57E+00 4.78E+00 3.71E+00 NA NA NA MW-49-26 MW-49-26 008 19.1

-4.4 11/15/2006 11:28 6.39E+03 1.38E+03 1.00E+03 1.55E+01 1.95E+00 7.70E-01 8.00E-01 3.00E+00 3.40E+00

-3.00E-01 4.20E+00 5.00E+00 8.40E+00 2.04E+01 2.20E+01 MW-49-26 MW-49-26 009 19.1

-4.4 6/26/2007 12:30 7.76E+03 3.48E+02 1.79E+02 1.27E+01 1.40E+00 7.13E-01 1.36E+00 2.55E+00 2.83E+00

-8.28E-01 2.23E+00 2.31E+00

-1.92E+00 1.28E+01 1.50E+01 MW-49-26 MW-49-26 010 19.1

-4.4 8/9/2007 11:17 6.72E+03 9.50E+02 4.62E+02 1.43E+01 2.16E+00 9.06E-01 4.09E-01 3.72E+00 4.23E+00 2.50E+00 3.51E+00 4.54E+00 7.93E-01 2.07E+01 2.42E+01 MW-49-26 MW-49-26 011 19.1

-4.4 1/28/2008 16:28 4.21E+03 5.76E+02 2.98E+02 2.29E+01 2.40E+00 8.52E-01

-1.19E+00 1.95E+00 2.07E+00 4.31E-01 1.97E+00 2.29E+00 5.16E+00 1.53E+01 1.75E+01 MW-49-26

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 15 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-49-26 012 19.1

-4.4 4/25/2008 12:45 5.00E+03 3.13E+02 1.44E+02 1.81E+01 1.32E+00 5.69E-01 2.68E+00 2.36E+00 4.34E+00 2.08E+00 2.22E+00 4.14E+00 1.76E+00 1.19E+01 2.05E+01 MW-49-26 MW-49-26 013 19.1

-4.4 7/30/2008 15:03 3.96E+03 1.73E+02 1.30E+02 1.62E+01 1.27E+00 8.36E-01

-9.75E-01 1.74E+00 2.74E+00 1.31E+00 2.17E+00 3.93E+00

-2.81E+00 1.64E+01 2.92E+01 MW-49-26 MW-49-26 014 19.1

-4.4 11/5/2008 15:54 3.47E+03 4.55E+02 1.91E+02 1.53E+01 2.06E+00 6.10E-01

-1.36E+00 5.03E+00 5.26E+00

-3.17E-01 4.65E+00 5.18E+00 2.96E+00 1.77E+01 2.02E+01 MW-49-26 MW-49-26 015 19.1

-4.4 2/6/2009 13:03 3.10E+03 2.66E+02 1.69E+02 1.38E+01 1.91E+00 8.59E-01 1.77E+00 4.34E+00 4.54E+00 1.26E+00 3.56E+00 4.24E+00 2.31E+01 2.21E+01 2.42E+01 MW-49-26 MW-49-26 016 19.1

-4.4 5/6/2009 10:46 3.20E+03 4.05E+02 1.80E+02 1.50E+01 1.85E+00 4.90E-01 2.93E+00 7.91E+00 5.27E+00 2.01E-01 3.78E+00 4.33E+00 7.21E-01 1.67E+01 1.91E+01 MW-49-26 MW-49-26 017 19.1

-4.4 8/7/2009 10:50 3.56E+03 2.97E+02 1.79E+02 1.23E+01 1.64E+00 6.79E-01

-9.22E-01 3.27E+00 3.47E+00

-1.44E+00 3.66E+00 3.60E+00 4.77E+00 1.95E+01 2.22E+01 MW-49-26 MW-49-26 018 19.1

-4.4 10/29/2009 13:14 3.17E+03 2.91E+02 1.88E+02 1.33E+01 1.71E+00 8.20E-01 7.51E-01 6.13E+00 6.91E+00 0.00E+00 5.38E+00 5.96E+00

-4.26E+00 1.77E+01 2.06E+01 MW-49-26 MW-49-26 019 19.1

-4.4 2/22/2010 14:35 2.82E+03 2.70E+02 1.74E+02 1.36E+01 1.92E+00 8.62E-01 2.49E+00 5.76E+00 6.86E+00

-1.91E-01 5.78E+00 6.41E+00

-6.01E+00 1.84E+01 2.16E+01 MW-49-26 MW-49-26 020 19.1

-4.4 4/23/2010 14:42 3.00E+03 3.30E+02 1.38E+02 1.55E+01 2.44E+00 8.19E-01 2.82E+00 7.32E+00 8.92E+00

-2.28E-01 9.12E+00 1.01E+01

-7.28E+00 1.95E+01 2.26E+01 MW-49-26 MW-49-26 021 19.1

-4.4 8/11/2010 11:27 3.03E+03 3.03E+02 1.27E+02 1.28E+01 1.44E+00 3.66E-01

-7.91E-01 1.14E+01 1.15E+01

-1.86E+00 1.10E+01 1.19E+01 3.27E-01 1.64E+01 1.92E+01 MW-49-26 MW-49-26 022 19.1

-4.4 11/11/2010 14:23 2.59E+03 3.00E+02 4.76E+02

-3.42E-01 9.56E-01 2.34E+00 4.62E+00 4.84E+00 1.15E+01 1.18E+00 3.96E+00 9.11E+00

-1.79E+00 1.02E+01 2.29E+01 MW-49-26 MW-49-26 023 19.1

-4.4 1/28/2011 13:37 3.17E+03 6.00E+02 4.29E+02 1.30E+01 2.86E+00 2.01E+00 3.39E-01 1.04E+01 7.00E+00

-2.43E+00 6.42E+00 6.44E+00

-4.38E+00 1.87E+01 2.20E+01 MW-49-26 MW-49-26 024 19.1

-4.4 4/15/2011 11:58 3.29E+03 7.18E+02 4.80E+02 1.26E+01 3.06E+00 1.91E+00 4.75E+00 1.07E+01 1.27E+01 4.03E+00 1.20E+01 1.47E+01 1.81E+00 1.50E+01 1.72E+01 MW-49-26 MW-49-26 025 19.1

-4.4 8/10/2011 10:46 3.97E+03 6.39E+02 2.00E+02 1.26E+01 2.89E+00 1.34E+00

-1.94E+00 9.06E+00 9.33E+00 2.94E+00 8.31E+00 1.00E+01

-1.77E+01 2.04E+01 2.57E+01 MW-49-26 MW-49-26 026 19.1

-4.4 11/4/2011 11:50 4.92E+03 8.37E+02 5.06E+02 1.27E+01 2.95E+00 1.25E+00 2.60E+00 1.11E+01 7.92E+00 5.17E+00 8.04E+00 1.17E+01

-2.73E+00 1.26E+01 1.44E+01 MW-49-26 MW-49-42 001 38.1

-23.4 3/22/2006 16:45 1.13E+04 2.55E+03 1.83E+03 1.94E+01 1.04E+00 4.30E-01 3.30E+00 1.19E+01 1.32E+01

-4.57E+00 1.11E+01 1.14E+01 NA NA NA MW-49-42 MW-49-42 003 38.1

-23.4 5/19/2006 15:07 9.39E+03 1.49E+03 4.90E+02 1.20E+01 9.57E-01 4.54E-01 2.16E+00 1.39E+01 1.56E+01 3.96E+00 1.40E+01 1.63E+01 NA NA NA MW-49-42 MW-49-42 003 38.1

-23.4 5/19/2006 15:07 8.83E+03 5.33E+03 6.29E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-49-42 MW-49-42 004 38.1

-23.4 6/6/2006 10:10 8.28E+03 1.32E+03 3.86E+02 1.63E+01 1.27E+00 5.67E-01 2.88E+00 1.37E+01 1.58E+01

-1.26E+00 1.07E+01 1.13E+01 NA NA NA MW-49-42 MW-49-42 005 38.1

-23.4 7/7/2006 9:15 5.85E+03 1.82E+03 1.52E+03 1.92E+01 3.23E+00 1.49E+00 2.01E+00 1.14E+01 1.30E+01

-1.61E+00 1.06E+01 1.11E+01 NA NA NA MW-49-42 MW-49-42 006 38.1

-23.4 8/1/2006 9:40 8.80E+03 9.68E+02 6.16E+02 NA NA NA

-4.22E+00 9.33E+00 8.64E+00

-1.94E+00 8.78E+00 8.99E+00 8.06E+00 9.86E+00 1.05E+01 MW-49-42 MW-49-42 007 38.1

-23.4 8/28/2006 12:40 8.69E+03 9.57E+02 6.10E+02 NA NA NA

-8.31E-02 1.05E+01 1.16E+01

-6.74E+00 9.40E+00 6.18E+00 NA NA NA MW-49-42 MW-49-42 008 38.1

-23.4 11/15/2006 14:21 6.19E+03 1.38E+03 1.00E+03 2.11E+01 2.46E+00 8.10E-01

-6.60E-01 2.25E+00 2.60E+00 1.18E+00 2.34E+00 2.60E+00 2.60E+00 5.70E+00 6.20E+00 MW-49-42 MW-49-42 009 38.1

-23.4 6/26/2007 12:30 4.44E+03 2.90E+02 1.86E+02 2.08E+01 1.65E+00 6.22E-01

-3.62E-01 4.56E+00 4.32E+00

-2.09E+00 3.66E+00 3.54E+00

-5.19E+00 1.30E+01 1.54E+01 MW-49-42 MW-49-42 010 38.1

-23.4 8/9/2007 12:05 4.30E+03 7.91E+02 4.59E+02 2.56E+01 2.77E+00 8.29E-01

-1.17E+00 3.27E+00 3.37E+00 2.77E+00 3.52E+00 4.56E+00 4.03E-01 2.10E+01 2.46E+01 MW-49-42 MW-49-42 011 38.1

-23.4 1/28/2008 15:49 2.81E+03 4.92E+02 2.98E+02 2.94E+01 2.57E+00 5.58E-01 8.68E-01 2.10E+00 2.43E+00 8.96E-01 2.13E+00 2.52E+00 5.79E+00 1.73E+01 1.97E+01 MW-49-42 MW-49-42 012 38.1

-23.4 4/25/2008 12:38 3.20E+03 2.54E+02 1.44E+02 2.33E+01 1.49E+00 5.24E-01 4.07E-01 1.82E+00 3.18E+00 5.91E-01 2.37E+00 4.13E+00

-1.03E+00 1.17E+01 2.04E+01 MW-49-42 MW-49-42 013 38.1

-23.4 7/30/2008 15:06 2.52E+03 1.45E+02 1.30E+02 2.16E+01 1.41E+00 6.09E-01 4.49E-01 1.59E+00 2.79E+00 7.96E-01 1.70E+00 3.09E+00

-2.73E+00 1.59E+01 2.84E+01 MW-49-42 MW-49-42 014 38.1

-23.4 11/5/2008 14:31 2.54E+03 4.04E+02 1.97E+02 2.16E+01 2.50E+00 7.01E-01

-1.27E+00 6.33E+00 6.92E+00

-1.93E+00 8.10E+00 7.46E+00 4.70E+00 1.84E+01 2.09E+01 MW-49-42 MW-49-42 015 38.1

-23.4 2/6/2009 9:57 2.25E+03 2.40E+02 1.70E+02 2.07E+01 2.37E+00 9.73E-01 1.38E+00 3.51E+00 4.09E+00

-2.43E+00 3.38E+00 3.11E+00

-2.15E+00 2.15E+01 2.48E+01 MW-49-42 MW-49-42 016 38.1

-23.4 5/6/2009 14:27 2.50E+03 3.63E+02 1.79E+02 1.75E+01 2.04E+00 4.71E-01 1.31E+00 7.25E+00 4.83E+00 1.78E-01 4.17E+00 4.49E+00

-7.29E+00 1.67E+01 1.94E+01 MW-49-42 MW-49-42 017 38.1

-23.4 8/7/2009 10:55 2.68E+03 2.69E+02 1.79E+02 1.75E+01 1.92E+00 6.96E-01

-3.65E-01 3.48E+00 3.79E+00 9.35E-01 3.35E+00 3.95E+00

-7.87E+00 1.49E+01 1.75E+01 MW-49-42 MW-49-42 018 38.1

-23.4 10/29/2009 13:04 2.51E+03 2.70E+02 1.88E+02 1.74E+01 1.91E+00 7.50E-01 6.14E-01 6.27E+00 7.22E+00

-9.32E-02 7.29E+00 8.25E+00

-9.33E+00 1.73E+01 2.03E+01 MW-49-42 MW-49-42 019 38.1

-23.4 2/22/2010 14:43 2.20E+03 2.49E+02 1.75E+02 1.85E+01 2.42E+00 7.57E-01

-2.91E-01 5.17E+00 5.65E+00 1.19E+00 5.75E+00 6.62E+00 1.66E-01 1.95E+01 2.25E+01 MW-49-42 MW-49-42 020 38.1

-23.4 4/23/2010 14:39 2.76E+03 3.26E+02 1.43E+02 1.75E+01 2.28E+00 7.01E-01

-5.63E+00 6.62E+00 6.01E+00

-1.68E+00 7.58E+00 7.64E+00

-3.23E+00 2.18E+01 2.51E+01 MW-49-42 MW-49-42 021 38.1

-23.4 8/11/2010 11:00 2.27E+03 2.72E+02 1.30E+02 1.85E+01 1.67E+00 3.91E-01 4.80E+00 7.88E+00 9.85E+00

-2.34E+00 8.76E+00 9.06E+00

-1.91E+00 1.65E+01 1.96E+01 MW-49-42 MW-49-42 022 38.1

-23.4 11/11/2010 14:13 2.39E+03 2.73E+02 4.02E+02 1.99E+01 1.65E+00 1.12E+00 8.48E-01 6.79E+00 9.79E+00 3.75E+00 5.42E+00 1.30E+01 4.00E+00 8.14E+00 1.80E+01 MW-49-42 MW-49-42 023 38.1

-23.4 1/28/2011 13:00 2.45E+03 5.38E+02 3.86E+02 2.30E+01 4.02E+00 2.02E+00

-1.07E+00 5.74E+00 6.21E+00

-2.45E+00 5.50E+00 5.32E+00

-3.26E+00 1.86E+01 2.18E+01 MW-49-42 MW-49-42 024 38.1

-23.4 4/15/2011 11:55 1.90E+03 6.04E+02 4.78E+02 1.57E+01 3.34E+00 2.07E+00

-6.72E+00 7.62E+00 6.17E+00 1.15E-01 7.72E+00 8.33E+00 6.68E+00 1.55E+01 1.73E+01 MW-49-42 MW-49-42 025 38.1

-23.4 8/10/2011 11:16 3.83E+03 6.21E+02 1.96E+02 1.61E+01 3.24E+00 1.64E+00

-1.22E+00 8.94E+00 9.69E+00

-3.72E+00 8.79E+00 8.23E+00

-1.40E+01 1.81E+01 2.15E+01 MW-49-42 MW-49-42 026 38.1

-23.4 11/4/2011 11:43 4.91E+03 8.19E+02 4.90E+02 2.11E+01 3.90E+00 1.51E+00 5.99E-01 1.87E+01 1.10E+01

-3.91E+00 1.04E+01 1.20E+01 4.27E+00 1.30E+01 1.45E+01 MW-49-42 MW-49-65 001 60

-45.4 3/22/2006 16:55 5.43E+03 2.13E+03 1.82E+03 1.85E+01 1.01E+00 4.13E-01 1.36E+00 1.43E+01 1.72E+01 5.51E+00 1.37E+01 1.81E+01 NA NA NA MW-49-65 MW-49-65 003 60

-45.4 5/19/2006 15:55 5.70E+03 9.38E+02 3.84E+02 1.13E+01 8.98E-01 4.28E-01

-2.86E+00 8.51E+00 8.67E+00

-1.43E-01 9.39E+00 1.03E+01 NA NA NA MW-49-65 MW-49-65 003 60

-45.4 5/19/2006 15:55 5.75E+03 4.30E+03 6.29E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-49-65 MW-49-65 004 60

-45.4 6/6/2006 10:40 4.32E+03 7.20E+02 2.88E+02 1.72E+01 1.30E+00 6.17E-01 4.52E+00 1.41E+01 1.63E+01 4.24E+00 1.28E+01 1.52E+01 NA NA NA MW-49-65 MW-49-65 005 60

-45.4 7/7/2006 9:10 4.63E+03 1.73E+03 1.52E+03 1.56E+01 3.24E+00 1.86E+00

-2.76E+00 6.49E+00 6.88E+00 1.84E+00 6.45E+00 7.36E+00 NA NA NA MW-49-65 MW-49-65 006 60

-45.4 8/1/2006 10:00 5.76E+03 8.48E+02 6.14E+02 NA NA NA

-1.20E+00 6.84E+00 7.48E+00

-6.55E-01 8.18E+00 9.78E+00 5.75E+00 1.06E+01 1.15E+01 MW-49-65 MW-49-65 007 60

-45.4 8/28/2006 12:35 5.54E+03 8.40E+02 6.16E+02 NA NA NA

-4.07E+00 9.28E+00 9.08E+00

-1.27E+00 7.42E+00 7.60E+00 NA NA NA MW-49-65 MW-49-65 008 60

-45.4 11/15/2006 13:46 3.04E+03 1.20E+03 1.00E+03 1.92E+01 2.31E+00 8.40E-01 2.12E+00 2.61E+00 2.80E+00 3.00E-01 2.07E+00 2.40E+00

-1.80E+00 6.90E+00 7.70E+00 MW-49-65 MW-49-65 009 60

-45.4 6/26/2007 12:30 2.62E+03 2.45E+02 1.85E+02 1.58E+01 1.58E+00 8.28E-01

-1.36E-03 3.06E+00 3.38E+00

-3.59E+00 4.30E+00 2.75E+00

-7.43E+00 1.41E+01 1.68E+01 MW-49-65 MW-49-65 010 60

-45.4 8/9/2007 11:20 2.41E+03 6.42E+02 4.60E+02 2.08E+01 2.40E+00 9.11E-01 3.44E-01 2.76E+00 3.13E+00 1.65E+00 3.03E+00 3.73E+00 3.50E+00 2.14E+01 2.49E+01 MW-49-65 MW-49-65 011 60

-45.4 1/28/2008 16:52 1.85E+03 4.22E+02 2.95E+02 2.73E+01 2.79E+00 6.29E-01 2.83E+00 3.72E+00 3.81E+00

-1.63E+00 3.17E+00 3.09E+00 1.01E+01 1.95E+01 2.20E+01 MW-49-65 MW-49-65 012 60

-45.4 4/25/2008 13:13 1.93E+03 1.86E+02 1.96E+02 1.90E+01 6.62E-01 3.64E-01

-8.45E-02 1.93E+00 3.28E+00

-1.40E-01 2.29E+00 3.84E+00 6.81E+00 9.59E+00 1.62E+01 MW-49-65 MW-49-65 013 60

-45.4 7/30/2008 13:58 1.56E+03 1.23E+02 1.30E+02 1.78E+01 1.29E+00 5.51E-01

-4.77E-01 2.20E+00 3.63E+00 8.42E-02 2.02E+00 3.39E+00

-6.53E+00 1.67E+01 2.96E+01 MW-49-65 MW-49-65 014 60

-45.4 11/5/2008 14:43 1.26E+03 3.02E+02 1.92E+02 1.72E+01 2.23E+00 5.97E-01

-4.96E+00 6.60E+00 6.62E+00 2.51E+00 6.11E+00 7.41E+00 8.42E-01 1.80E+01 2.06E+01 MW-49-65 MW-49-65 015 60

-45.4 2/6/2009 9:59 1.42E+03 2.10E+02 1.70E+02 1.73E+01 2.10E+00 9.15E-01

-9.15E-01 2.96E+00 3.20E+00 7.61E-01 2.64E+00 3.21E+00 2.70E+00 2.22E+01 2.54E+01 MW-49-65 MW-49-65 016 60

-45.4 5/6/2009 15:18 1.34E+03 2.85E+02 1.80E+02 1.28E+01 1.79E+00 7.13E-01 1.40E-01 4.37E+00 2.91E+00

-3.07E-01 2.99E+00 3.02E+00

-1.93E+00 1.79E+01 2.05E+01 MW-49-65 MW-49-65 017 60

-45.4 8/7/2009 12:48 1.64E+03 2.33E+02 1.80E+02 1.24E+01 1.62E+00 7.16E-01 5.00E-01 3.13E+00 3.54E+00 5.17E-01 3.29E+00 3.76E+00

-3.28E+00 1.86E+01 2.15E+01 MW-49-65 MW-49-65 018 60

-45.4 10/29/2009 13:15 1.66E+03 2.39E+02 1.88E+02 1.14E+01 1.58E+00 8.16E-01 1.01E+00 9.45E+00 8.96E+00 1.59E+00 8.58E+00 8.81E+00

-6.66E+00 1.71E+01 2.00E+01 MW-49-65 MW-49-65 019 60

-45.4 2/22/2010 13:57 1.42E+03 2.19E+02 1.74E+02 1.55E+01 2.34E+00 7.71E-01

-6.73E-01 5.14E+00 5.79E+00 1.50E+00 4.53E+00 5.47E+00

-6.53E+00 1.81E+01 2.13E+01 MW-49-65 MW-49-65 020 60

-45.4 4/23/2010 15:17 1.55E+03 2.63E+02 1.50E+02 1.04E+01 1.85E+00 6.37E-01 6.11E+00 1.36E+01 9.18E+00

-2.53E-01 1.17E+01 1.35E+01

-1.29E+01 1.96E+01 2.32E+01 MW-49-65 MW-49-65 021 60

-45.4 8/11/2010 11:19 1.32E+03 2.16E+02 1.28E+02 1.24E+01 1.44E+00 4.49E-01

-1.12E+01 1.22E+01 1.43E+01

-2.58E-01 9.88E+00 1.11E+01

-6.74E-01 1.80E+01 2.13E+01 MW-49-65 MW-49-65 022 60

-45.4 11/11/2010 14:18 1.37E+03 2.34E+02 3.97E+02 1.41E+01 1.45E+00 1.34E+00 6.99E+00 6.88E+00 1.07E+01 3.39E-01 5.37E+00 1.18E+01

-3.41E+00 9.31E+00 2.09E+01 MW-49-65 MW-49-65 023 60

-45.4 1/28/2011 13:15 1.94E+03 5.02E+02 3.85E+02 1.15E+01 3.28E+00 2.06E+00

-6.30E-01 4.96E+00 5.21E+00 7.15E-01 5.20E+00 5.81E+00

-9.08E+00 1.83E+01 2.20E+01 MW-49-65 MW-49-65 024 60

-45.4 4/15/2011 11:50 2.38E+03 6.48E+02 4.81E+02 1.62E+01 3.12E+00 1.60E+00 2.59E+00 9.66E+00 1.12E+01 4.62E-02 1.01E+01 1.10E+01 4.11E+00 1.49E+01 1.68E+01 MW-49-65 MW-49-65 025 60

-45.4 8/10/2011 10:55 2.43E+03 5.10E+02 2.00E+02 1.14E+01 2.75E+00 1.42E+00 1.12E-01 7.77E+00 8.40E+00

-4.19E+00 9.00E+00 8.02E+00

-6.91E-01 1.81E+01 2.05E+01 MW-49-65 MW-49-65 026 60

-45.4 11/4/2011 11:47 4.24E+03 7.23E+02 4.64E+02 2.02E+01 3.60E+00 1.47E+00

-4.27E+00 8.88E+00 9.11E+00

-6.56E-01 9.45E+00 1.15E+01 7.03E-01 1.21E+01 1.36E+01 MW-49-65 MW-50-42 001 42

-27.1 3/22/2006 14:25 9.75E+03 5.78E+02 2.14E+02 1.93E+01 1.12E+00 4.76E-01

-1.36E+00 9.90E+00 1.13E+01

-5.74E-01 8.55E+00 1.02E+01 4.01E+00 1.34E+01 1.46E+01 MW-50-42 MW-50-42 003 42

-27.1 5/19/2006 13:55 4.58E+03 3.84E+03 6.30E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-50-42 MW-50-42 003 42

-27.1 5/19/2006 13:55 4.59E+03 7.74E+02 3.53E+02 1.95E+01 1.25E+00 4.77E-01 4.84E+00 8.95E+00 1.18E+01

-4.07E-01 8.17E+00 1.02E+01 NA NA NA MW-50-42 MW-50-42 004 42

-27.1 6/7/2006 9:00 1.79E+02 1.89E+02 1.56E+02 3.94E+00 7.62E-01 6.06E-01 1.15E-01 7.81E+00 8.62E+00

-1.70E+00 7.37E+00 7.69E+00 NA NA NA MW-50-42 MW-50-42 005 42

-27.1 7/3/2006 11:35 3.98E+02 2.18E+02 2.02E+02 3.45E+00 2.00E+00 1.65E+00 6.90E+00 1.38E+01 1.65E+01 4.75E+00 1.04E+01 1.30E+01 NA NA NA MW-50-42 MW-50-42 006 42

-27.1 8/1/2006 11:20 1.41E+03 6.42E+02 6.14E+02 NA NA NA 8.99E+00 1.01E+01 1.33E+01 6.21E+00 9.26E+00 1.24E+01 1.12E+01 1.53E+01 1.64E+01 MW-50-42 MW-50-42 007 42

-27.1 8/28/2006 11:50 3.11E+02 1.89E+02 1.76E+02 NA NA NA 1.97E+00 5.84E+00 6.74E+00 3.49E+00 6.36E+00 7.93E+00 NA NA NA MW-50-42 MW-50-42 008 42

-27.1 11/15/2006 11:50 1.70E+03 1.11E+03 1.00E+03 1.13E+01 1.56E+00 8.30E-01 7.20E+00 4.20E+00 4.30E+00

-9.00E-01 3.00E+00 3.80E+00

-1.20E+00 6.00E+00 6.70E+00 MW-50-42 MW-50-42 009 42

-27.1 6/26/2007 14:30 2.15E+02 1.71E+02 1.86E+02 1.16E+01 1.35E+00 7.64E-01 1.91E+00 4.44E+00 5.12E+00

-1.64E+00 4.29E+00 3.94E+00

-6.30E+00 1.84E+01 2.19E+01 MW-50-42

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 16 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-50-42 010 42

-27.1 7/26/2007 11:20 1.45E+02 1.74E+02 1.93E+02 1.94E+01 1.81E+00 5.31E-01

-5.50E+00 4.71E+00 3.68E+00 2.53E+00 3.39E+00 4.32E+00 4.92E+00 1.91E+01 2.19E+01 MW-50-42 MW-50-42 011 42

-27.1 10/18/2007 14:08 1.01E+02 1.76E+02 1.97E+02 2.45E+01 2.52E+00 5.74E-01 3.02E-01 3.38E+00 3.87E+00 6.26E-01 3.75E+00 3.81E+00

-9.14E-01 1.62E+01 1.87E+01 MW-50-42 MW-50-42 013 42

-27.1 2/26/2008 12:19 6.13E+02 2.94E+02 2.87E+02 2.40E+00 8.61E-01 7.34E-01

-1.95E+00 4.80E+00 4.66E+00 1.77E+00 3.90E+00 4.68E+00 1.71E+01 2.40E+01 2.67E+01 MW-50-42 MW-50-42 014 42

-27.1 7/31/2008 15:43 3.73E+02 1.34E+02 1.91E+02 9.28E+00 8.66E-01 4.39E-01

-9.40E-01 1.99E+00 3.20E+00 9.53E-01 1.91E+00 3.44E+00 1.58E+01 1.76E+01 2.96E+01 MW-50-42 MW-50-42 015 42

-27.1 11/6/2008 10:44 1.29E+02 1.76E+02 1.92E+02 2.56E+00 9.87E-01 6.85E-01 1.65E+00 4.98E+00 5.77E+00 5.18E-01 5.36E+00 6.17E+00 0.00E+00 1.76E+01 2.03E+01 MW-50-42 MW-50-42 016 42

-27.1 1/22/2009 15:23 2.15E+02 1.38E+02 1.48E+02 1.96E+00 8.06E-01 6.31E-01

-1.74E+00 2.48E+00 2.37E+00

-5.18E-01 2.31E+00 2.39E+00

-3.34E+00 1.74E+01 2.03E+01 MW-50-42 MW-50-42 017 42

-27.1 5/5/2009 14:11 3.92E+02 1.95E+02 1.72E+02 2.38E+00 8.93E-01 6.96E-01 5.89E-01 9.20E+00 6.13E+00

-2.50E+00 5.75E+00 5.71E+00

-9.99E+00 2.07E+01 2.42E+01 MW-50-42 MW-50-42 018 42

-27.1 8/7/2009 13:13 1.06E+03 2.09E+02 1.79E+02 5.33E+00 1.25E+00 7.23E-01

-7.54E-02 3.66E+00 4.14E+00 3.08E-01 3.27E+00 3.73E+00

-1.25E+01 1.64E+01 1.94E+01 MW-50-42 MW-50-42 019 42

-27.1 10/26/2009 14:41 4.09E+02 1.83E+02 1.88E+02 6.73E+00 1.09E+00 4.53E-01

-3.87E+00 1.01E+01 1.12E+01 2.52E-01 6.62E+00 7.45E+00

-1.40E+01 1.86E+01 2.22E+01 MW-50-42 MW-50-42 020 42

-27.1 2/19/2010 12:52 3.73E+02 1.71E+02 1.74E+02 5.56E+00 1.42E+00 8.15E-01 2.91E+00 5.42E+00 6.46E+00 3.03E+00 6.13E+00 7.39E+00

-1.37E+01 1.88E+01 2.23E+01 MW-50-42 MW-50-42 021 42

-27.1 4/30/2010 12:34 1.36E+03 2.46E+02 1.68E+02 4.36E+00 1.33E+00 8.88E-01 8.49E-01 7.56E+00 8.38E+00

-1.97E+00 5.09E+00 5.04E+00

-1.48E+01 2.25E+01 2.61E+01 MW-50-42 MW-50-42 022 42

-27.1 8/4/2010 13:11 1.61E+02 1.25E+02 1.28E+02 8.43E+00 1.42E+00 5.63E-01

-1.94E+00 8.65E+00 9.25E+00 1.30E-01 8.05E+00 9.05E+00 0.00E+00 1.59E+01 1.88E+01 MW-50-42 MW-50-42 023 42

-27.1 11/12/2010 12:10 8.67E+02 1.83E+02 1.22E+02 3.73E+00 1.31E+00 9.89E-01 2.40E+00 5.71E+00 6.76E+00 2.73E+00 5.58E+00 6.94E+00

-7.36E+00 1.79E+01 2.15E+01 MW-50-42 MW-50-42 024 42

-27.1 2/25/2011 12:36 5.61E+02 3.88E+02 3.85E+02 5.42E+00 2.34E+00 1.91E+00

-1.29E-01 5.46E+00 5.88E+00

-9.07E-01 4.42E+00 4.42E+00

-7.19E+00 1.82E+01 2.18E+01 MW-50-42 MW-50-42 025 42

-27.1 5/3/2011 12:05 3.77E+03 5.58E+02 3.41E+02 9.53E+00 2.20E+00 1.04E+00 1.92E+00 9.44E+00 1.07E+01 5.79E-01 1.02E+01 1.16E+01 5.86E-01 1.69E+01 1.92E+01 MW-50-42 MW-50-42 026 42

-27.1 7/25/2011 12:18 1.03E+03 4.89E+02 4.43E+02 3.01E+00 2.09E+00 2.02E+00

-1.11E+00 7.86E+00 8.36E+00 6.63E-02 8.16E+00 9.04E+00 3.81E+00 1.71E+01 1.91E+01 MW-50-42 MW-50-42 027 42

-27.1 8/19/2011 12:10 9.52E+02 3.42E+02 2.00E+02 9.47E+00 2.60E+00 1.31E+00 2.17E+00 8.01E+00 9.07E+00 4.72E+00 9.81E+00 1.22E+01

-7.08E+00 1.81E+01 2.10E+01 MW-50-42 MW-50-42 028 42

-27.1 10/27/2011 10:48 9.99E+02 5.25E+02 4.92E+02 3.02E+01 4.44E+00 1.54E+00 1.76E+00 7.11E+00 9.22E+00

-2.60E+00 8.01E+00 9.51E+00

-5.76E+00 1.21E+01 1.41E+01 MW-50-42 MW-50-66 001 60

-45.1 3/22/2006 14:50 6.81E+03 4.94E+02 2.13E+02 2.55E+01 1.21E+00 4.90E-01

-7.67E+00 1.60E+01 1.66E+01

-2.18E+00 1.68E+01 1.81E+01 5.33E+00 1.35E+01 1.47E+01 MW-50-66 MW-50-66 003 60

-45.1 5/19/2006 15:20 1.08E+04 5.90E+03 6.30E+02 NA NA NA 3.23E+00 1.06E+01 1.23E+01 7.78E-01 1.12E+01 1.25E+01 NA NA NA MW-50-66 MW-50-66 003 60

-45.1 5/19/2006 15:20 9.61E+03 1.52E+03 4.94E+02 1.95E+01 1.22E+00 5.16E-01 NA NA NA NA NA NA NA NA NA MW-50-66 MW-50-66 004 60

-45.1 6/7/2006 9:20 1.05E+04 1.65E+03 4.29E+02 1.98E+01 1.18E+00 4.66E-01

-1.97E+00 8.71E+00 9.38E+00 2.49E+00 8.98E+00 1.04E+01 NA NA NA MW-50-66 MW-50-66 005 60

-45.1 7/3/2006 11:00 8.62E+03 2.00E+03 1.52E+03 2.53E+01 3.79E+00 1.67E+00

-2.04E+00 9.54E+00 1.02E+01 4.40E-01 8.34E+00 9.23E+00 NA NA NA MW-50-66 MW-50-66 006 60

-45.1 8/1/2006 9:28 7.93E+03 9.36E+02 6.16E+02 NA NA NA 5.59E-01 5.98E+00 6.68E+00

-4.31E+00 6.18E+00 5.00E+00 1.06E+01 1.06E+01 1.13E+01 MW-50-66 MW-50-66 007 60

-45.1 8/28/2006 12:05 6.77E+03 1.59E+03 1.30E+03 NA NA NA 7.66E-02 4.67E+00 5.86E+00 1.34E+00 4.23E+00 5.88E+00 NA NA NA MW-50-66 MW-50-66 008 60

-45.1 11/15/2006 10:37 5.05E+03 1.32E+03 1.00E+03 2.15E+01 2.34E+00 8.10E-01 2.00E-01 3.30E+00 3.70E+00 2.60E+00 3.30E+00 3.50E+00 1.50E+00 5.70E+00 6.30E+00 MW-50-66 MW-50-66 009 60

-45.1 6/26/2007 14:02 4.21E+03 2.85E+02 1.86E+02 2.93E+01 1.86E+00 5.25E-01

-2.19E+00 2.64E+00 2.49E+00 1.63E-01 2.36E+00 2.74E+00

-6.05E-01 1.50E+01 1.74E+01 MW-50-66 MW-50-66 010 60

-45.1 7/26/2007 11:25 4.50E+03 3.39E+02 2.04E+02 3.10E+01 2.50E+00 5.78E-01

-1.12E+00 4.54E+00 4.18E+00 1.08E-02 3.46E+00 3.94E+00 1.93E+01 1.86E+01 2.02E+01 MW-50-66 MW-50-66 011 60

-45.1 10/18/2007 14:38 3.85E+03 6.53E+02 3.62E+02 4.74E+01 3.72E+00 7.97E-01

-2.28E+00 4.61E+00 4.36E+00 1.65E+00 4.20E+00 4.96E+00

-3.71E+00 1.58E+01 1.83E+01 MW-50-66 MW-50-66 013 60

-45.1 2/26/2008 13:46 3.74E+03 7.98E+02 5.31E+02 3.58E+01 2.36E+00 7.40E-01 7.87E-01 2.69E+00 3.18E+00 2.54E-01 2.54E+00 2.96E+00 4.87E+00 1.86E+01 2.12E+01 MW-50-66 MW-50-66 015 60

-45.1 5/12/2008 15:40 2.80E+03 2.39E+02 1.44E+02 3.38E+01 1.85E+00 7.01E-01 7.08E-01 2.24E+00 3.87E+00 1.23E+00 2.13E+00 3.83E+00 7.86E+00 1.28E+01 2.17E+01 MW-50-66 MW-50-66 016 60

-45.1 7/31/2008 17:02 2.71E+03 2.48E+02 1.91E+02 3.30E+01 1.59E+00 4.02E-01 2.31E+00 1.82E+00 3.43E+00 6.64E-01 1.46E+00 2.68E+00 3.58E+00 1.40E+01 2.43E+01 MW-50-66 MW-50-66 017 60

-45.1 9/8/2008 16:21 2.08E+03 4.17E+02 5.04E+02 3.23E+01 1.66E+00 4.88E-01

-8.81E-01 2.69E+00 3.96E+00 NA NA NA 1.22E+01 1.23E+01 2.06E+01 MW-50-66 MW-50-66 018 60

-45.1 11/6/2008 12:38 2.73E+03 4.17E+02 1.98E+02 3.20E+01 3.00E+00 7.41E-01

-8.66E-01 5.97E+00 6.56E+00

-2.52E+00 8.96E+00 8.45E+00

-1.63E+00 2.07E+01 2.39E+01 MW-50-66 MW-50-66 019 60

-45.1 11/19/2008 16:29 2.43E+03 2.49E+02 1.73E+02 4.99E+01 3.75E+00 8.66E-01 2.50E+00 5.26E+00 2.61E+00 5.13E-01 2.70E+00 3.17E+00

-5.06E-01 1.98E+01 2.29E+01 MW-50-66 MW-50-66 020 60

-45.1 1/22/2009 16:01 2.30E+03 2.16E+02 1.48E+02 2.75E+01 2.28E+00 4.07E-01

-1.68E+00 4.20E+00 3.99E+00

-1.97E-01 3.32E+00 3.66E+00

-9.33E+00 1.88E+01 2.23E+01 MW-50-66 MW-50-66 021 60

-45.1 3/18/2009 15:16 3.13E+03 7.02E+02 3.88E+02 2.42E+01 2.58E+00 9.13E-01 1.95E-02 5.75E+00 3.83E+00

-9.37E-01 3.56E+00 3.65E+00 1.55E+00 1.70E+01 1.94E+01 MW-50-66 MW-50-66 022 60

-45.1 5/5/2009 16:33 3.45E+03 4.35E+02 1.74E+02 2.82E+01 2.33E+00 6.13E-01

-4.57E+00 8.96E+00 5.97E+00

-6.21E-03 5.87E+00 6.54E+00

-1.93E+00 1.85E+01 2.13E+01 MW-50-66 MW-50-66 023 60

-45.1 8/7/2009 16:12 3.00E+03 2.79E+02 1.79E+02 2.91E+01 2.54E+00 9.11E-01 2.03E-01 3.35E+00 3.82E+00 7.02E-01 3.51E+00 4.14E+00

-1.36E+01 1.83E+01 2.19E+01 MW-50-66 MW-50-66 024 60

-45.1 10/26/2009 14:49 2.86E+03 2.82E+02 1.89E+02 3.00E+01 2.34E+00 5.34E-01 4.11E-01 5.89E+00 6.75E+00 2.56E+00 6.03E+00 7.46E+00

-6.44E+00 1.86E+01 2.17E+01 MW-50-66 MW-50-66 025 60

-45.1 2/19/2010 15:51 2.84E+03 2.72E+02 1.74E+02 2.50E+01 3.04E+00 8.16E-01

-6.04E-01 4.68E+00 5.20E+00

-1.03E+00 5.01E+00 5.41E+00

-3.76E+00 1.91E+01 2.21E+01 MW-50-66 MW-50-66 026 60

-45.1 4/30/2010 14:25 2.76E+03 3.21E+02 1.68E+02 2.99E+01 3.01E+00 8.81E-01

-1.86E+00 5.84E+00 6.18E+00 3.85E-01 5.38E+00 6.13E+00

-1.14E+01 2.19E+01 2.52E+01 MW-50-66 MW-50-66 027 60

-45.1 8/4/2010 16:38 3.51E+03 3.33E+02 1.34E+02 2.65E+01 2.28E+00 4.80E-01 3.52E+00 8.29E+00 9.99E+00 9.22E-01 9.18E+00 1.06E+01 2.07E+00 1.56E+01 1.81E+01 MW-50-66 MW-50-66 028 60

-45.1 11/12/2010 12:30 3.72E+03 3.30E+02 1.20E+02 2.33E+01 2.71E+00 9.50E-01

-1.39E+00 6.21E+00 6.79E+00

-1.67E+00 6.95E+00 7.30E+00 3.25E-01 1.88E+01 2.18E+01 MW-50-66 MW-50-66 029 60

-45.1 2/25/2011 12:36 3.76E+03 6.18E+02 3.83E+02 2.61E+01 4.02E+00 2.13E+00 2.94E+00 7.20E+00 8.24E+00 6.79E-01 8.00E+00 9.10E+00

-2.80E+00 1.81E+01 2.12E+01 MW-50-66 MW-50-66 030 60

-45.1 5/3/2011 12:07 4.73E+03 6.12E+02 3.45E+02 2.63E+01 3.30E+00 1.08E+00 0.00E+00 1.77E+01 9.05E+00

-2.32E+00 9.06E+00 9.12E+00 8.43E+00 1.70E+01 1.88E+01 MW-50-66 MW-50-66 031 60

-45.1 7/25/2011 12:26 6.50E+03 8.73E+02 4.48E+02 2.61E+01 4.08E+00 1.35E+00

-4.59E-01 7.02E+00 7.74E+00 3.81E+00 8.55E+00 1.07E+01 1.02E+01 1.66E+01 1.81E+01 MW-50-66 MW-50-66 032 60

-45.1 8/19/2011 12:12 7.15E+03 8.49E+02 2.00E+02 2.57E+01 4.05E+00 1.65E+00 3.97E+00 8.46E+00 1.01E+01 1.73E+00 9.03E+00 1.05E+01

-8.92E+00 1.80E+01 2.11E+01 MW-50-66 MW-50-66 033 60

-45.1 10/27/2011 10:53 7.83E+03 9.87E+02 4.94E+02 2.66E+01 4.35E+00 1.59E+00

-6.49E-01 8.64E+00 1.02E+01 1.01E+01 1.01E+01 1.49E+01

-4.90E+00 1.66E+01 1.92E+01 MW-50-66 MW-51-40 001 39.7 28 5/30/2007 11:45 1.98E+02 1.65E+02 1.68E+02

-5.30E-01 6.73E-01 9.82E-01 1.04E-01 3.48E+00 3.77E+00 1.61E+00 3.23E+00 3.77E+00 NA NA NA MW-51-40 MW-51-40 002 39.7 28 7/24/2007 15:30 2.23E+02 1.59E+02 1.60E+02 7.09E-02 4.71E-01 5.38E-01 1.65E-02 3.39E+00 3.85E+00

-1.32E+00 4.02E+00 4.13E+00 NA NA NA MW-51-40 MW-51-40 004 39.7 28 11/9/2007 15:40 1.47E+02 1.55E+02 1.70E+02

-8.16E-02 3.87E-01 4.52E-01 1.68E+00 2.96E+00 3.52E+00

-5.71E-02 3.15E+00 3.49E+00 NA NA NA MW-51-40 MW-51-40 005 39.7 28 1/8/2008 10:47 5.86E+01 1.56E+02 1.79E+02 1.57E-01 6.77E-01 8.32E-01 1.83E-02 2.66E+00 2.93E+00 7.71E-01 2.75E+00 2.87E+00 NA NA NA MW-51-40 MW-51-40 007 39.7 28 5/30/2008 10:27 1.41E+02 1.01E+02 1.60E+02 3.71E-01 5.67E-01 9.67E-01 3.19E-01 2.03E+00 3.41E+00 2.18E+00 2.36E+00 3.50E+00 NA NA NA MW-51-40 MW-51-40 008 39.7 28 8/8/2008 14:40 3.29E+02 1.60E+02 2.03E+02 3.74E-01 4.02E-01 6.70E-01 1.59E+00 2.19E+00 3.98E+00

-1.99E-01 1.79E+00 2.99E+00

-8.33E+00 1.02E+01 1.83E+01 MW-51-40 MW-51-40 009 39.7 28 10/27/2008 13:11 1.68E+02 1.85E+02 1.95E+02 1.84E-02 4.26E-01 5.67E-01 4.51E-01 4.28E+00 4.88E+00

-1.93E+00 6.35E+00 6.59E+00

-5.03E+00 2.11E+01 2.46E+01 MW-51-40 MW-51-40 010 39.7 28 1/20/2009 14:50 2.37E+01 1.68E+02 1.92E+02 1.92E-01 7.95E-01 9.70E-01 9.89E-01 2.81E+00 3.26E+00 1.05E+00 2.75E+00 3.30E+00 8.95E+00 1.67E+01 1.87E+01 MW-51-40 MW-51-40 011 39.7 28 5/7/2009 14:27 2.03E+02 1.76E+02 1.81E+02 1.02E-01 6.81E-01 8.27E-01 1.18E+00 7.08E+00 4.72E+00

-1.14E+00 5.00E+00 5.08E+00

-1.06E+00 1.83E+01 2.11E+01 MW-51-40 MW-51-40 012 39.7 28 8/12/2009 13:42 2.67E+02 1.70E+02 1.79E+02 6.39E-02 5.69E-01 6.89E-01 2.93E-01 3.35E+00 3.41E+00 1.00E+00 3.01E+00 3.56E+00

-5.55E+00 1.95E+01 2.27E+01 MW-51-40 MW-51-40 013 39.7 28 11/18/2009 14:26 1.55E+02 1.32E+02 1.41E+02

-2.16E-01 6.35E-01 8.09E-01

-1.42E+00 5.66E+00 6.00E+00

-1.14E+00 6.45E+00 6.92E+00

-5.68E+00 1.98E+01 2.30E+01 MW-51-40 MW-51-40 014 39.7 28 2/5/2010 14:31 7.54E+01 1.74E+02 1.98E+02

-5.43E-02 6.58E-01 8.64E-01 1.75E+00 4.09E+00 4.72E+00

-2.91E+00 5.31E+00 4.42E+00 NA NA NA MW-51-40 MW-51-40 015 39.7 28 4/8/2010 13:58 9.55E+01 1.32E+02 1.44E+02

-1.04E-01 7.30E-01 8.98E-01 8.94E-01 8.25E+00 9.56E+00

-1.94E+00 9.18E+00 9.55E+00 NA NA NA MW-51-40 MW-51-40 016 39.7 28 8/25/2010 16:29 1.70E+02 1.07E+02 1.03E+02

-4.31E-02 3.11E-01 4.19E-01

-2.48E+00 6.17E+00 6.53E+00 1.46E+00 5.21E+00 6.37E+00 NA NA NA MW-51-40 MW-51-40 017 39.7 28 11/30/2010 12:54 1.48E+02 1.41E+02 1.44E+02 1.46E-01 6.05E-01 7.12E-01 1.54E+00 4.28E+00 4.95E+00 1.72E+00 4.17E+00 4.95E+00 NA NA NA MW-51-40 MW-51-40 018 39.7 28 3/8/2011 10:18 1.02E+02 2.34E+02 2.67E+02 1.07E+00 1.51E+00 1.61E+00

-7.97E+00 1.21E+01 1.36E+01 2.42E+00 7.30E+00 8.76E+00 NA NA NA MW-51-40 MW-51-40 019 39.7 28 4/29/2011 10:41 3.63E+02 4.14E+02 4.35E+02 2.26E-01 1.37E+00 1.59E+00

-3.40E+00 9.48E+00 9.62E+00 6.20E+00 1.11E+01 1.40E+01 NA NA NA MW-51-40 MW-51-40 020 39.7 28 7/28/2011 11:43 3.78E+01 3.06E+02 3.52E+02

-2.51E-01 1.37E+00 1.85E+00

-2.58E+00 1.35E+01 1.68E+01

-3.37E+00 9.33E+00 9.05E+00 NA NA NA MW-51-40 MW-51-40 021 39.7 28 12/12/2011 10:43 1.86E+02 3.06E+02 3.28E+02

-7.34E-01 1.58E+00 1.94E+00

-5.53E+00 8.49E+00 9.48E+00 4.82E+00 7.89E+00 1.18E+01

-3.48E+00 1.39E+01 1.58E+01 MW-51-40 MW-51-79 001 78.7

-11 5/30/2007 12:42 9.89E+01 1.55E+02 1.72E+02

-2.36E-01 6.98E-01 9.58E-01 2.20E+00 3.63E+00 3.90E+00 3.52E-01 3.31E+00 3.76E+00 NA NA NA MW-51-79 MW-51-79 002 78.7

-11 7/24/2007 17:00 4.24E+01 1.43E+02 1.67E+02 8.02E-03 5.35E-01 6.15E-01

-6.37E-01 3.88E+00 4.21E+00

-2.83E-01 4.51E+00 4.93E+00 NA NA NA MW-51-79 MW-51-79 004 78.7

-11 11/9/2007 16:18 5.00E+01 1.50E+02 1.71E+02

-4.97E-02 2.99E-01 3.52E-01 2.66E+00 2.97E+00 3.56E+00

-2.43E-01 4.02E+00 4.45E+00 NA NA NA MW-51-79 MW-51-79 005 78.7

-11 1/8/2008 10:08 9.26E+01 1.59E+02 1.79E+02

-4.64E-01 7.01E-01 9.74E-01

-7.91E-01 2.22E+00 2.42E+00 2.58E-01 2.37E+00 2.70E+00 NA NA NA MW-51-79 MW-51-79 007 78.7

-11 5/30/2008 10:55 6.70E+01 9.41E+01 1.61E+02 2.46E-02 4.94E-01 9.94E-01

-1.14E+00 3.43E+00 4.80E+00

-5.13E-01 2.70E+00 4.31E+00 NA NA NA MW-51-79 MW-51-79 008 78.7

-11 8/8/2008 12:55 1.61E+02 1.31E+02 2.01E+02 2.03E-01 2.99E-01 5.18E-01 9.63E-01 2.17E+00 3.82E+00 5.64E-01 2.30E+00 3.98E+00

-1.07E+01 1.07E+01 1.93E+01 MW-51-79 MW-51-79 009 78.7

-11 10/27/2008 13:30 1.14E+01 1.62E+02 1.99E+02 3.14E-03 6.14E-01 7.85E-01 8.42E-01 5.07E+00 5.75E+00 2.41E+00 5.21E+00 6.37E+00 3.72E+00 1.77E+01 2.02E+01 MW-51-79 MW-51-79 010 78.7

-11 1/20/2009 15:21 1.01E+02 1.33E+02 1.48E+02

-1.71E-01 3.15E-01 5.02E-01 5.93E-01 5.57E+00 3.65E+00

-2.94E-01 3.21E+00 3.56E+00 1.58E+01 1.73E+01 1.90E+01 MW-51-79

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 17 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-51-79 011 78.7

-11 5/7/2009 15:10 6.19E+01 1.58E+02 1.81E+02 6.97E-01 7.58E-01 8.29E-01 5.17E-01 7.68E+00 5.12E+00 2.33E+00 5.79E+00 6.97E+00

-6.40E+00 1.73E+01 2.00E+01 MW-51-79 MW-51-79 012 78.7

-11 8/12/2009 11:11 1.99E+02 1.67E+02 1.80E+02 7.34E-02 4.50E-01 5.53E-01

-4.76E-01 4.82E+00 4.34E+00

-1.34E+00 4.29E+00 4.21E+00

-1.73E+01 1.83E+01 2.19E+01 MW-51-79 MW-51-79 013 78.7

-11 11/18/2009 14:31 1.15E+02 1.86E+02 2.08E+02

-4.50E-02 6.87E-01 8.44E-01

-8.05E-01 5.79E+00 6.45E+00 2.78E+00 6.58E+00 8.07E+00 2.96E-01 1.68E+01 1.94E+01 MW-51-79 MW-51-79 014 78.7

-11 2/5/2010 14:40 1.37E+02 1.80E+02 1.99E+02

-1.36E-01 6.10E-01 8.44E-01 3.61E-02 3.39E+00 3.74E+00 7.57E-01 3.57E+00 4.08E+00 NA NA NA MW-51-79 MW-51-79 015 78.7

-11 4/8/2010 14:21 6.44E+01 1.33E+02 1.51E+02 4.88E-01 8.07E-01 9.02E-01 4.35E+00 8.89E+00 1.11E+01 4.52E+00 1.00E+01 1.28E+01 NA NA NA MW-51-79 MW-51-79 016 78.7

-11 8/25/2010 16:47 1.10E+02 9.84E+01 1.01E+02 5.81E-01 8.23E-01 8.92E-01 5.29E+00 6.13E+00 7.76E+00 1.58E+00 6.71E+00 7.88E+00 NA NA NA MW-51-79 MW-51-79 017 78.7

-11 11/30/2010 13:08 3.11E+01 1.21E+02 1.44E+02

-1.22E-01 4.32E-01 5.24E-01

-8.30E-01 4.13E+00 4.54E+00 9.98E-01 4.02E+00 4.66E+00 NA NA NA MW-51-79 MW-51-79 018 78.7

-11 3/8/2011 10:34 1.36E+02 2.46E+02 2.70E+02

-2.03E-01 1.22E+00 1.53E+00 2.42E+00 5.42E+00 6.52E+00

-2.74E+00 7.36E+00 6.45E+00 NA NA NA MW-51-79 MW-51-79 019 78.7

-11 4/29/2011 10:57 1.17E+02 3.82E+02 4.33E+02 1.03E+00 1.67E+00 1.82E+00

-4.93E-01 7.56E+00 8.23E+00

-8.38E-01 8.08E+00 8.53E+00 NA NA NA MW-51-79 MW-51-79 020 78.7

-11 7/28/2011 11:55

-1.93E+01 3.09E+02 3.60E+02 1.36E-01 1.63E+00 1.96E+00 2.20E+00 8.28E+00 9.43E+00

-5.24E-01 9.27E+00 9.93E+00 NA NA NA MW-51-79 MW-51-79 021 78.7

-11 12/12/2011 11:09 1.50E+02 2.95E+02 3.29E+02

-1.38E-01 1.52E+00 1.90E+00

-3.25E+00 7.98E+00 8.95E+00

-3.01E-01 7.62E+00 9.88E+00

-1.12E+00 1.13E+01 1.27E+01 MW-51-79 MW-51-104 001 103.7

-36 5/30/2007 11:05 5.71E+01 1.48E+02 1.71E+02

-6.74E-02 7.59E-01 9.90E-01 1.25E+00 3.27E+00 3.35E+00 7.70E-02 3.25E+00 3.62E+00 NA NA NA MW-51-104 MW-51-104 002 103.7

-36 7/24/2007 17:06 9.07E+01 1.47E+02 1.64E+02 3.62E-01 4.86E-01 5.41E-01

-4.20E+00 4.62E+00 3.92E+00 1.42E+00 4.44E+00 5.33E+00 NA NA NA MW-51-104 MW-51-104 004 103.7

-36 11/9/2007 14:35 5.17E+01 1.50E+02 1.70E+02

-2.40E-01 3.18E-01 3.86E-01

-1.26E+00 2.85E+00 2.92E+00 1.15E+00 2.61E+00 3.18E+00 NA NA NA MW-51-104 MW-51-104 005 103.7

-36 1/8/2008 12:15

-4.84E+00 1.45E+02 1.78E+02

-6.19E-02 7.22E-01 9.34E-01

-9.37E-01 2.09E+00 2.26E+00

-3.84E-01 2.54E+00 2.50E+00 NA NA NA MW-51-104 MW-51-104 006 103.7

-36 8/8/2008 10:50 2.82E+02 1.55E+02 2.08E+02

-2.66E-01 4.00E-01 7.92E-01 1.56E+00 2.03E+00 3.60E+00

-1.21E-01 2.07E+00 3.38E+00

-4.19E+00 1.34E+01 2.36E+01 MW-51-104 MW-51-104 007 103.7

-36 10/27/2008 10:07 1.21E+02 1.39E+02 1.49E+02 1.19E-01 4.97E-01 6.13E-01 5.61E+00 6.81E+00 8.52E+00

-5.72E+00 8.93E+00 8.26E+00

-1.01E+00 1.84E+01 2.12E+01 MW-51-104 MW-51-104 008 103.7

-36 1/20/2009 10:46 9.95E+01 1.33E+02 1.48E+02 9.07E-03 3.78E-01 5.04E-01

-1.33E+00 2.87E+00 3.03E+00

-1.01E+00 2.37E+00 2.42E+00

-2.06E+00 2.00E+01 2.33E+01 MW-51-104 MW-51-104 009 103.7

-36 5/7/2009 11:48 1.11E+02 1.61E+02 1.78E+02

-1.53E-01 6.36E-01 7.99E-01

-8.75E-01 5.79E+00 3.86E+00 4.67E-01 3.51E+00 4.01E+00

-1.35E+01 2.36E+01 2.71E+01 MW-51-104 MW-51-104 010 103.7

-36 8/12/2009 11:14 2.91E+02 1.71E+02 1.80E+02 1.27E-01 3.65E-01 4.36E-01 8.06E-01 6.58E+00 3.82E+00 1.09E-01 3.93E+00 4.36E+00

-2.40E+00 1.86E+01 2.16E+01 MW-51-104 MW-51-104 011 103.7

-36 11/18/2009 11:34 1.44E+02 1.33E+02 1.43E+02 5.67E-01 7.29E-01 7.97E-01

-9.34E+00 1.07E+01 1.08E+01

-7.19E-01 6.11E+00 6.60E+00 3.03E+00 1.62E+01 1.84E+01 MW-51-104 MW-51-104 012 103.7

-36 2/5/2010 11:44

-1.96E+01 1.70E+02 1.99E+02 3.73E-03 6.18E-01 8.24E-01 3.36E-03 7.17E+00 6.23E+00 1.95E+00 5.38E+00 6.49E+00 NA NA NA MW-51-104 MW-51-104 013 103.7

-36 4/8/2010 10:42 1.10E+02 1.34E+02 1.45E+02 1.26E-01 7.62E-01 8.99E-01

-5.36E-01 8.43E+00 9.34E+00 2.15E+00 7.96E+00 9.79E+00 NA NA NA MW-51-104 MW-51-104 014 103.7

-36 8/25/2010 13:18 1.33E+02 1.37E+02 1.44E+02 7.62E-01 8.15E-01 8.20E-01 8.90E-01 5.75E+00 6.63E+00

-2.70E-01 4.96E+00 5.47E+00 NA NA NA MW-51-104 MW-51-104 015 103.7

-36 11/30/2010 9:55 8.54E+01 1.33E+02 1.47E+02 3.74E-01 7.18E-01 8.12E-01

-1.43E-01 3.99E+00 4.55E+00 2.19E-01 4.56E+00 5.05E+00 NA NA NA MW-51-104 MW-51-104 016 103.7

-36 3/8/2011 12:10 5.76E+01 3.10E+02 3.55E+02 8.91E-01 1.47E+00 1.60E+00 2.54E+00 7.20E+00 8.14E+00 9.02E-01 5.50E+00 6.24E+00 NA NA NA MW-51-104 MW-51-104 017 103.7

-36 4/29/2011 12:35 1.97E+02 3.90E+02 4.32E+02 1.41E+00 1.45E+00 1.48E+00

-1.90E+00 1.08E+01 1.25E+01

-6.79E-01 1.10E+01 1.20E+01 NA NA NA MW-51-104 MW-51-104 018 103.7

-36 7/28/2011 9:51 1.64E+02 3.18E+02 3.51E+02

-8.86E-01 1.26E+00 1.94E+00

-1.15E-01 6.18E+00 6.84E+00

-3.12E+00 8.10E+00 7.98E+00 NA NA NA MW-51-104 MW-51-104 019 103.7

-36 12/12/2011 12:12 1.48E+02 2.91E+02 3.24E+02 1.23E+00 1.76E+00 1.85E+00

-3.81E+00 9.12E+00 1.01E+01 9.25E+00 9.60E+00 1.43E+01

-3.91E+00 1.33E+01 1.51E+01 MW-51-104 MW-51-135 001 135.2

-67.5 5/30/2007 13:00 8.24E+01 1.50E+02 1.70E+02

-4.68E-01 5.53E-01 8.40E-01

-4.01E-01 3.62E+00 4.03E+00 2.56E+00 3.84E+00 4.48E+00 NA NA NA MW-51-135 MW-51-135 002 135.2

-67.5 7/24/2007 12:40 9.51E+01 1.43E+02 1.59E+02 5.33E-02 5.04E-01 5.76E-01

-4.56E-01 4.07E+00 4.36E+00 3.42E-01 3.30E+00 3.84E+00 NA NA NA MW-51-135 MW-51-135 004 135.2

-67.5 11/9/2007 11:55 9.83E+01 1.53E+02 1.72E+02

-2.42E-01 2.54E-01 3.18E-01

-7.27E-01 3.46E+00 3.70E+00

-3.14E-01 3.29E+00 3.66E+00 NA NA NA MW-51-135 MW-51-135 005 135.2

-67.5 1/8/2008 13:20 4.91E+01 1.55E+02 1.80E+02 3.47E-02 7.04E-01 8.79E-01 6.30E-02 1.88E+00 2.09E+00 1.43E-02 1.71E+00 1.90E+00 NA NA NA MW-51-135 MW-51-135 006 135.2

-67.5 8/8/2008 11:50 2.09E+02 1.39E+02 1.99E+02 5.09E-02 2.40E-01 4.57E-01

-1.03E+00 2.08E+00 3.29E+00 1.01E-02 2.01E+00 3.34E+00

-6.78E+00 1.14E+01 2.02E+01 MW-51-135 MW-51-135 007 135.2

-67.5 10/27/2008 10:05 7.68E+01 1.73E+02 1.99E+02 2.72E-04 5.05E-01 6.63E-01

-1.74E+00 5.26E+00 5.63E+00 3.92E+00 6.09E+00 7.69E+00

-2.05E-01 1.74E+01 2.01E+01 MW-51-135 MW-51-135 008 135.2

-67.5 1/20/2009 11:02 1.31E+02 1.35E+02 1.48E+02

-3.04E-01 3.41E-01 5.84E-01

-6.92E-01 3.89E+00 4.31E+00 9.34E-01 3.06E+00 3.66E+00

-1.08E+01 1.76E+01 2.10E+01 MW-51-135 MW-51-135 009 135.2

-67.5 5/7/2009 11:53 2.44E+01 1.43E+02 1.71E+02 8.54E-02 4.71E-01 5.79E-01 3.06E+00 7.04E+00 4.69E+00

-7.33E-01 3.77E+00 4.00E+00

-2.11E+01 2.24E+01 2.60E+01 MW-51-135 MW-51-135 010 135.2

-67.5 8/12/2009 11:22 9.84E+01 1.61E+02 1.79E+02

-1.62E-01 4.93E-01 6.57E-01

-1.17E+00 3.75E+00 3.74E+00 2.68E+00 3.30E+00 4.29E+00

-1.50E+01 1.81E+01 2.17E+01 MW-51-135 MW-51-135 011 135.2

-67.5 11/18/2009 11:35 1.30E+02 1.32E+02 1.43E+02

-5.62E-01 6.06E-01 8.17E-01

-1.52E-01 4.53E+00 5.17E+00 2.08E+00 5.09E+00 6.12E+00 1.08E+00 1.64E+01 1.88E+01 MW-51-135 MW-51-135 012 135.2

-67.5 2/5/2010 11:48 4.89E+00 1.71E+02 1.98E+02 7.14E-02 6.50E-01 8.21E-01

-1.07E-02 3.90E+00 4.35E+00

-4.54E-02 4.51E+00 5.10E+00 NA NA NA MW-51-135 MW-51-135 013 135.2

-67.5 4/8/2010 11:06 5.86E+01 1.31E+02 1.50E+02

-2.09E-02 5.99E-01 7.85E-01

-7.04E-03 8.73E+00 9.88E+00

-4.95E-01 1.04E+01 1.19E+01 NA NA NA MW-51-135 MW-51-135 014 135.2

-67.5 8/25/2010 13:21 1.36E+02 1.41E+02 1.47E+02

-2.33E-01 4.44E-01 6.70E-01

-6.64E-01 6.15E+00 6.80E+00 1.74E+00 6.62E+00 7.77E+00 NA NA NA MW-51-135 MW-51-135 015 135.2

-67.5 11/30/2010 9:57 9.53E+01 1.33E+02 1.45E+02 4.21E-01 7.13E-01 7.98E-01

-5.11E-01 4.18E+00 4.61E+00

-2.98E-01 4.20E+00 4.58E+00 NA NA NA MW-51-135 MW-51-135 016 135.2

-67.5 3/8/2011 12:44 8.29E+01 2.24E+02 2.62E+02 8.62E-01 1.31E+00 1.42E+00 8.60E-02 6.02E+00 6.77E+00 2.37E+00 5.96E+00 7.38E+00 NA NA NA MW-51-135 MW-51-135 017 135.2

-67.5 4/29/2011 13:16 0.00E+00 3.66E+02 4.35E+02 1.14E+00 1.52E+00 1.63E+00 2.52E+00 1.01E+01 1.17E+01

-5.69E-01 9.00E+00 9.56E+00 NA NA NA MW-51-135 MW-51-135 018 135.2

-67.5 7/28/2011 10:04

-5.63E+01 2.96E+02 3.49E+02 8.06E-01 1.71E+00 1.92E+00 4.41E+00 8.22E+00 9.83E+00 1.32E+00 9.36E+00 1.05E+01 NA NA NA MW-51-135 MW-51-135 019 135.2

-67.5 12/12/2011 12:50 1.32E+02 2.93E+02 3.33E+02 2.67E-01 1.64E+00 1.94E+00 6.83E+00 9.42E+00 1.28E+01

-3.73E+00 8.40E+00 9.41E+00

-6.68E+00 1.18E+01 1.35E+01 MW-51-135 MW-51-163 001 162.7

-95 5/30/2007 14:40 1.18E+02 1.56E+02 1.69E+02 3.29E-01 1.16E+00 1.36E+00

-2.81E-01 3.09E+00 3.45E+00 1.77E-01 2.82E+00 3.20E+00 NA NA NA MW-51-163 MW-51-163 002 162.7

-95 7/24/2007 14:05 4.98E+01 1.44E+02 1.66E+02 1.05E-01 4.58E-01 5.21E-01

-2.43E-01 3.44E+00 3.78E+00 8.64E-02 3.25E+00 3.63E+00 NA NA NA MW-51-163 MW-51-163 004 162.7

-95 11/9/2007 13:32 7.30E+01 1.52E+02 1.71E+02 2.08E-01 2.82E-01 3.12E-01 1.41E-01 3.54E+00 3.51E+00

-1.11E+00 3.01E+00 3.11E+00 NA NA NA MW-51-163 MW-51-163 005 162.7

-95 1/8/2008 13:57

-1.99E+01 1.47E+02 1.82E+02 4.40E-01 8.22E-01 9.29E-01

-1.74E+00 2.66E+00 2.46E+00 8.69E-02 2.15E+00 2.44E+00 NA NA NA MW-51-163 MW-51-163 006 162.7

-95 8/8/2008 11:16 6.92E+01 8.27E+01 1.40E+02

-1.22E-01 2.63E-01 5.44E-01

-1.54E+00 2.25E+00 3.56E+00 3.78E-01 1.97E+00 3.39E+00 4.33E+00 1.26E+01 2.15E+01 MW-51-163 MW-51-163 007 162.7

-95 10/27/2008 10:20 5.58E+01 1.67E+02 1.95E+02 2.55E-01 5.76E-01 6.67E-01

-1.70E+00 6.18E+00 6.74E+00 5.42E-01 5.38E+00 6.25E+00 2.11E+00 1.88E+01 2.14E+01 MW-51-163 MW-51-163 008 162.7

-95 1/20/2009 11:44 4.60E+01 1.30E+02 1.48E+02

-1.98E-01 4.97E-01 6.98E-01

-9.70E-01 3.14E+00 3.27E+00

-7.70E-02 3.24E+00 3.54E+00

-1.01E+01 1.80E+01 2.14E+01 MW-51-163 MW-51-163 009 162.7

-95 5/7/2009 12:09 5.68E+01 1.56E+02 1.81E+02

-5.45E-02 4.61E-01 6.13E-01

-7.96E-01 5.09E+00 3.39E+00 1.08E+00 3.63E+00 3.83E+00 4.18E+00 1.89E+01 2.15E+01 MW-51-163 MW-51-163 010 162.7

-95 8/12/2009 11:28 1.41E+02 1.62E+02 1.79E+02 7.24E-02 5.76E-01 6.99E-01 7.50E-01 3.74E+00 4.26E+00

-2.23E+00 3.23E+00 3.06E+00

-3.79E+00 1.80E+01 2.08E+01 MW-51-163 MW-51-163 011 162.7

-95 11/18/2009 11:33 9.48E+01 1.29E+02 1.43E+02 6.98E-02 6.64E-01 7.96E-01

-2.63E+00 5.89E+00 6.04E+00 2.61E+00 5.33E+00 6.54E+00

-2.21E+00 1.66E+01 1.93E+01 MW-51-163 MW-51-163 012 162.7

-95 2/5/2010 11:46 6.10E+01 1.74E+02 1.98E+02

-1.82E-01 5.76E-01 8.21E-01

-8.29E-01 8.12E+00 7.94E+00

-1.95E+00 6.88E+00 6.07E+00 NA NA NA MW-51-163 MW-51-163 013 162.7

-95 4/8/2010 11:31 5.35E+01 1.27E+02 1.46E+02

-7.65E-02 6.06E-01 8.13E-01

-2.95E+00 8.55E+00 8.74E+00

-1.50E+00 1.04E+01 1.10E+01 NA NA NA MW-51-163 MW-51-163 014 162.7

-95 8/25/2010 13:51 8.26E+01 9.75E+01 1.05E+02

-1.08E-01 3.98E-01 5.31E-01 3.91E+00 6.72E+00 8.11E+00 8.67E-01 6.32E+00 7.26E+00 NA NA NA MW-51-163 MW-51-163 015 162.7

-95 11/30/2010 10:02 9.01E+01 1.31E+02 1.44E+02

-3.11E-01 6.98E-01 9.94E-01 1.23E+00 8.07E+00 4.14E+00 3.30E-01 3.94E+00 4.43E+00 NA NA NA MW-51-163 MW-51-163 016 162.7

-95 3/8/2011 13:01 0.00E+00 1.96E+02 2.63E+02

-5.97E-01 1.39E+00 1.98E+00 2.81E+00 6.54E+00 7.66E+00 5.35E-01 7.76E+00 8.69E+00 NA NA NA MW-51-163 MW-51-163 017 162.7

-95 4/29/2011 13:19 4.68E+01 3.66E+02 4.30E+02 5.27E-01 1.45E+00 1.65E+00 2.26E+00 8.40E+00 9.72E+00 9.25E-01 7.72E+00 8.87E+00 NA NA NA MW-51-163 MW-51-163 018 162.7

-95 7/28/2011 10:18 1.20E+02 3.18E+02 3.54E+02

-7.15E-01 1.26E+00 1.96E+00 6.34E-01 7.71E+00 8.41E+00 3.60E+00 9.69E+00 1.17E+01 NA NA NA MW-51-163 MW-51-163 019 162.7

-95 12/12/2011 12:26 1.71E+02 3.03E+02 3.32E+02 1.58E+00 1.81E+00 1.94E+00 2.25E+00 8.94E+00 1.16E+01

-8.50E-01 8.52E+00 1.08E+01

-3.59E+00 1.22E+01 1.38E+01 MW-51-163 MW-51-189 001 189.2

-121.5 5/30/2007 14:00 1.87E+02 1.67E+02 1.71E+02

-2.88E-02 8.90E-01 1.11E+00

-3.62E-02 3.98E+00 3.82E+00 4.56E+00 3.57E+00 4.63E+00 NA NA NA MW-51-189 MW-51-189 002 189.2

-121.5 7/24/2007 13:15 9.49E+01 1.46E+02 1.63E+02 3.93E-01 4.08E-01 4.48E-01

-8.87E-01 4.11E+00 3.58E+00 1.57E+00 4.02E+00 4.31E+00 NA NA NA MW-51-189 MW-51-189 003 189.2

-121.5 10/2/2007 12:20 8.45E+00 1.70E+02 1.96E+02

-5.06E-02 2.16E-01 2.58E-01 1.38E+01 5.45E+00 2.92E+00

-4.14E-01 2.79E+00 3.04E+00 NA NA NA MW-51-189 MW-51-189 004 189.2

-121.5 11/9/2007 13:05

-6.26E+00 1.48E+02 1.71E+02 1.93E-01 3.61E-01 4.08E-01 3.04E+00 3.27E+00 4.07E+00

-8.07E-02 3.65E+00 4.05E+00 NA NA NA MW-51-189 MW-51-189 005 189.2

-121.5 1/8/2008 13:10

-4.82E+00 1.44E+02 1.77E+02

-3.17E-02 7.01E-01 8.92E-01 1.35E+00 2.13E+00 2.49E+00 1.42E+00 1.98E+00 2.41E+00 NA NA NA MW-51-189 MW-51-189 006 189.2

-121.5 8/8/2008 11:17 1.10E+02 8.97E+01 1.43E+02

-1.43E-01 3.38E-01 6.60E-01

-2.27E+00 2.13E+00 3.12E+00

-1.79E+00 2.70E+00 3.57E+00

-5.89E+00 1.15E+01 2.04E+01 MW-51-189 MW-51-189 007 189.2

-121.5 10/27/2008 10:11 7.69E+01 1.74E+02 1.99E+02 5.61E-01 7.16E-01 7.51E-01 6.11E-01 6.38E+00 7.30E+00 3.04E+00 6.13E+00 7.60E+00

-6.95E+00 1.84E+01 2.17E+01 MW-51-189 MW-51-189 008 189.2

-121.5 1/20/2009 11:33 3.32E+01 1.30E+02 1.48E+02

-2.14E-01 3.45E-01 5.59E-01

-2.05E+00 3.48E+00 3.62E+00 1.91E+00 3.32E+00 4.20E+00

-8.33E+00 1.79E+01 2.11E+01 MW-51-189 MW-51-189 009 189.2

-121.5 5/7/2009 11:55 2.06E+01 1.52E+02 1.81E+02 1.44E-01 5.33E-01 6.41E-01 1.70E+00 9.39E+00 6.26E+00

-1.22E+00 5.79E+00 6.11E+00

-3.36E+00 1.86E+01 2.14E+01 MW-51-189 MW-51-189 010 189.2

-121.5 8/12/2009 11:11 2.75E+01 1.39E+02 1.60E+02 7.76E-01 8.83E-01 9.41E-01 9.35E-01 3.82E+00 4.47E+00 1.47E+00 3.84E+00 4.60E+00

-1.98E+00 2.14E+01 2.47E+01 MW-51-189 MW-51-189 011 189.2

-121.5 11/18/2009 11:31 8.88E+01 1.35E+02 1.51E+02 3.60E-01 5.90E-01 6.58E-01 2.96E+00 5.58E+00 6.76E+00

-2.88E-01 5.82E+00 6.43E+00

-9.17E+00 1.92E+01 2.26E+01 MW-51-189

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 18 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-51-189 012 189.2

-121.5 2/5/2010 11:35 3.42E+01 1.73E+02 1.98E+02 3.21E-01 6.03E-01 6.83E-01 1.25E+00 5.70E+00 6.64E+00

-2.35E+00 6.75E+00 6.51E+00 NA NA NA MW-51-189 MW-51-189 013 189.2

-121.5 4/8/2010 11:16 5.35E+01 1.27E+02 1.46E+02 3.25E-01 7.35E-01 8.47E-01

-2.07E+00 8.19E+00 8.51E+00 3.45E-01 7.39E+00 8.29E+00 NA NA NA MW-51-189 MW-51-189 014 189.2

-121.5 8/25/2010 13:13 5.86E+01 9.38E+01 1.04E+02 4.40E-02 5.97E-01 7.65E-01 2.87E+00 5.64E+00 6.69E+00

-8.01E-01 5.85E+00 6.25E+00 NA NA NA MW-51-189 MW-51-189 015 189.2

-121.5 11/30/2010 9:56 6.91E+01 1.29E+02 1.46E+02 1.93E-01 7.99E-01 9.81E-01

-7.45E-01 4.51E+00 4.98E+00

-3.16E-01 4.61E+00 5.06E+00 NA NA NA MW-51-189 MW-51-189 016 189.2

-121.5 3/8/2011 12:30

-1.50E+01 1.93E+02 2.68E+02

-3.06E-01 1.46E+00 1.97E+00 3.77E+01*

1.47E+01 6.28E+00 2.28E-01 5.28E+00 5.79E+00 NA NA NA MW-51-189 MW-51-189 017 189.2

-121.5 4/29/2011 12:52 2.32E+02 3.96E+02 4.33E+02 1.28E+00 1.50E+00 1.57E+00

-8.07E-01 5.82E+00 6.25E+00

-5.07E+00 9.48E+00 8.89E+00 NA NA NA MW-51-189 MW-51-189 018 189.2

-121.5 7/28/2011 10:42

-5.69E+00 3.03E+02 3.53E+02 3.69E-02 1.66E+00 1.95E+00 2.36E+00 1.07E+01 1.02E+01 2.52E+00 1.01E+01 1.17E+01 NA NA NA MW-51-189 MW-51-189 019 189.2

-121.5 12/12/2011 12:23

-5.57E+01 2.30E+02 3.29E+02

-3.94E-01 1.43E+00 1.91E+00

-4.49E+00 8.10E+00 8.53E+00 1.93E+00 8.34E+00 1.13E+01

-9.34E+00 1.94E+01 2.22E+01 MW-51-189 MW-52-11 001 10 6.8 6/20/2007 12:35 1.47E+02 1.68E+02 1.84E+02

-3.58E-01 6.33E-01 8.33E-01 1.96E+00 2.54E+00 2.99E+00 6.12E-01 2.29E+00 2.65E+00

-4.56E+00 1.28E+01 1.54E+01 MW-52-11 MW-52-11 002 10 6.8 8/6/2007 16:18 7.71E+01 1.73E+02 1.94E+02

-5.43E-01 6.12E-01 9.38E-01

-2.16E+00 3.42E+00 3.23E+00 3.39E-02 2.79E+00 3.12E+00 NA NA NA MW-52-11 MW-52-11 003 10 6.8 4/28/2008 13:23 1.13E+03 1.53E+02 1.96E+02 1.97E-01 4.73E-01 8.46E-01 5.19E-01 1.93E+00 3.36E+00

-2.15E+00 3.52E+00 4.08E+00 NA NA NA MW-52-11 MW-52-11 004 10 6.8 4/30/2009 14:27 5.19E+02 4.61E+02 4.72E+02 4.52E-02 5.64E-01 7.17E-01 2.98E-01 7.52E+00 5.01E+00 1.41E+00 5.07E+00 6.04E+00 NA NA NA MW-52-11 MW-52-11 005 10 6.8 5/5/2010 12:26 3.73E+02 1.74E+02 1.83E+02 1.89E-01 4.77E-01 5.62E-01 2.14E+00 5.99E+00 6.97E+00

-2.04E+00 5.91E+00 6.08E+00 NA NA NA MW-52-11 MW-52-11 006 10 6.8 4/22/2011 12:10 3.04E+02 4.08E+02 4.35E+02 1.29E-01 1.35E+00 1.60E+00 2.27E+00 1.02E+01 1.17E+01 5.08E+00 9.92E+00 1.24E+01 NA NA NA MW-52-11 MW-52-11 007 10 6.8 7/26/2011 12:32 3.39E+02 3.99E+02 4.21E+02 1.86E-01 1.49E+00 1.74E+00 1.71E+00 8.76E+00 9.71E+00

-2.27E+00 8.43E+00 8.63E+00 NA NA NA MW-52-11 MW-52-18 001 17.5

-2.6 5/24/2007 10:44 1.62E+02 1.52E+02 1.65E+02

-2.20E-01 4.98E-01 7.30E-01 6.53E-01 3.19E+00 3.74E+00 3.13E+00 3.30E+00 4.22E+00

-1.09E+00 9.82E+00 1.14E+01 MW-52-18 MW-52-18 002 17.5

-2.6 8/6/2007 13:45 6.73E+01 1.74E+02 1.96E+02

-7.91E-02 6.92E-01 8.93E-01

-1.43E+00 3.54E+00 3.67E+00 1.11E-01 3.15E+00 3.54E+00 NA NA NA MW-52-18 MW-52-18 004 17.5

-2.6 4/30/2009 16:15 2.29E+02 2.01E+02 2.17E+02

-6.52E-02 5.55E-01 7.37E-01

-1.47E-02 7.89E+00 5.26E+00 8.60E-01 4.49E+00 5.24E+00 NA NA NA MW-52-18 MW-52-18 005 17.5

-2.6 5/5/2010 16:19 3.01E+02 1.71E+02 1.83E+02 8.08E-02 4.19E-01 5.26E-01 1.60E+00 5.61E+00 6.44E+00 9.40E-01 5.42E+00 6.22E+00 NA NA NA MW-52-18 MW-52-18 006 17.5

-2.6 4/22/2011 12:16 7.01E+01 3.76E+02 4.35E+02 1.37E+00 1.39E+00 1.42E+00 8.81E+00 1.29E+01 9.01E+00

-1.49E+00 9.44E+00 9.90E+00 NA NA NA MW-52-18 MW-52-18 007 17.5

-2.6 7/26/2011 14:39 2.52E+02 3.87E+02 4.22E+02 1.06E+00 1.62E+00 1.76E+00 3.80E+00 6.45E+00 8.08E+00

-3.24E+00 8.10E+00 7.84E+00 NA NA NA MW-52-18 MW-52-48 001 48

-33.1 5/24/2007 11:35 7.02E+01 1.48E+02 1.67E+02

-3.61E-01 7.44E-01 1.01E+00 3.66E-01 2.94E+00 3.39E+00

-9.91E-01 3.03E+00 3.11E+00

-2.74E+00 8.16E+00 9.55E+00 MW-52-48 MW-52-48 002 48

-33.1 8/6/2007 14:00 1.15E+02 1.76E+02 1.96E+02

-5.59E-01 4.83E-01 7.33E-01 7.85E-01 3.24E+00 3.75E+00 4.31E-01 3.29E+00 3.75E+00 NA NA NA MW-52-48 MW-52-48 004 48

-33.1 5/1/2009 11:35 1.43E+02 9.84E+01 1.00E+02 4.55E-02 6.02E-01 7.02E-01 1.19E+00 7.61E+00 5.07E+00

-2.32E+00 4.41E+00 4.29E+00 NA NA NA MW-52-48 MW-52-48 005 48

-33.1 5/5/2010 16:43 1.60E+02 1.65E+02 1.82E+02 6.40E-01 6.58E-01 6.90E-01

-6.17E-01 6.04E+00 6.70E+00

-1.90E-01 5.13E+00 5.67E+00 NA NA NA MW-52-48 MW-52-48 006 48

-33.1 4/22/2011 12:18 1.06E+02 3.82E+02 4.36E+02 1.69E-01 1.37E+00 1.62E+00

-4.59E+00 7.58E+00 7.31E+00 1.35E+00 7.80E+00 9.17E+00 NA NA NA MW-52-48 MW-52-48 007 48

-33.1 7/26/2011 15:08 7.68E+01 3.66E+02 4.21E+02 2.58E-01 1.20E+00 1.46E+00 2.34E+00 9.60E+00 1.07E+01

-7.68E-01 8.73E+00 1.01E+01 NA NA NA MW-52-48 MW-52-64 001 64

-49.1 5/24/2007 14:44 3.82E+00 1.70E+02 1.98E+02

-3.20E-01 7.68E-01 9.77E-01

-1.03E+00 3.25E+00 3.45E+00 8.00E-01 3.54E+00 4.11E+00

-2.85E+00 9.12E+00 1.07E+01 MW-52-64 MW-52-64 002 64

-49.1 8/6/2007 15:50 3.72E+01 1.71E+02 1.96E+02

-1.70E-02 7.22E-01 9.23E-01 5.10E-01 3.50E+00 3.68E+00 1.80E+00 6.08E+00 4.12E+00 NA NA NA MW-52-64 MW-52-64 004 64

-49.1 5/1/2009 13:50

-1.02E+01 8.27E+01 1.00E+02 4.33E-01 7.01E-01 7.72E-01 1.82E+00 6.54E+00 4.36E+00 1.24E+00 4.25E+00 4.80E+00 NA NA NA MW-52-64 MW-52-64 005 64

-49.1 5/5/2010 12:52 7.62E+01 1.61E+02 1.81E+02

-2.23E-01 7.02E-01 9.13E-01

-1.12E+00 5.21E+00 4.96E+00 1.49E+00 4.05E+00 4.98E+00 NA NA NA MW-52-64 MW-52-64 006 64

-49.1 4/22/2011 15:23

-2.26E+01 3.58E+02 4.32E+02 5.12E-01 1.13E+00 1.27E+00 1.87E+00 6.72E+00 7.70E+00

-8.05E+00 8.28E+00 6.18E+00 NA NA NA MW-52-64 MW-52-64 007 64

-49.1 7/27/2011 10:45 1.35E+02 3.81E+02 4.31E+02

-4.58E-01 8.67E-01 1.27E+00 2.48E+00 7.17E+00 8.34E+00 6.66E-01 8.13E+00 9.05E+00 NA NA NA MW-52-64 MW-52-118 004 NA NA 4/30/2009 12:03 1.15E+02 1.00E+02 1.06E+02

-3.34E-01 4.29E-01 6.89E-01 2.00E+00 8.58E+00 5.72E+00 1.27E+00 4.68E+00 5.65E+00 NA NA NA MW-52-118 MW-52-122 001 122

-107.1 5/24/2007 14:55 6.78E+01 1.47E+02 1.66E+02

-4.24E-01 6.62E-01 9.64E-01 2.52E+00 3.59E+00 3.62E+00

-1.76E+00 3.38E+00 3.29E+00

-1.94E+00 9.68E+00 1.13E+01 MW-52-122 MW-52-122 002 122

-107.1 8/6/2007 12:05 4.42E+01 1.71E+02 1.96E+02

-4.19E-01 7.10E-01 9.60E-01 1.99E+00 4.09E+00 4.34E+00 2.10E-01 4.13E+00 4.70E+00 NA NA NA MW-52-122 MW-52-122 003 122

-107.1 4/28/2008 15:23 8.87E+01 8.60E+01 1.44E+02 1.21E-01 2.92E-01 5.22E-01

-1.25E+00 2.05E+00 3.24E+00 2.72E+00 2.38E+00 4.52E+00 NA NA NA MW-52-122 MW-52-122 005 122

-107.1 5/5/2010 14:57 6.46E+01 1.64E+02 1.84E+02 1.59E-01 4.66E-01 5.60E-01 3.04E-02 5.33E+00 6.01E+00

-3.25E+00 6.25E+00 6.14E+00 NA NA NA MW-52-122 MW-52-122 007 122

-107.1 7/26/2011 13:36

-2.18E+01 3.48E+02 4.19E+02 1.05E-01 1.19E+00 1.47E+00

-5.49E+00 7.92E+00 7.50E+00 8.02E-01 6.84E+00 7.89E+00 NA NA NA MW-52-122 MW-52-162 001 161.5

-146.6 5/24/2007 11:55 2.82E+02 1.95E+02 2.03E+02

-5.15E-01 4.87E-01 8.12E-01

-5.80E-01 3.59E+00 3.29E+00 1.59E+00 3.15E+00 3.88E+00

-7.54E-01 9.75E+00 1.13E+01 MW-52-162 MW-52-162 002 161.5

-146.6 8/6/2007 11:30 2.11E+02 1.80E+02 1.95E+02 1.53E-02 4.79E-01 6.03E-01 3.61E-02 3.44E+00 3.77E+00

-3.73E-02 3.12E+00 3.52E+00 NA NA NA MW-52-162 MW-52-162 003 161.5

-146.6 4/28/2008 10:22 1.45E+02 8.73E+01 1.43E+02 1.03E+00 3.62E-01 4.43E-01

-9.14E-01 2.03E+00 3.31E+00 2.33E+00 2.13E+00 4.14E+00 NA NA NA MW-52-162 MW-52-162 004 161.5

-146.6 4/30/2009 12:06 4.92E+02 4.58E+02 4.73E+02

-1.49E-01 5.60E-01 7.37E-01

-5.43E-01 8.54E+00 5.69E+00

-1.26E+00 5.06E+00 5.17E+00 NA NA NA MW-52-162 MW-52-162 005 161.5

-146.6 5/5/2010 12:39 2.60E+02 1.70E+02 1.83E+02

-7.86E-02 4.15E-01 5.66E-01

-1.54E+00 5.52E+00 5.96E+00 3.03E+00 5.68E+00 7.13E+00 NA NA NA MW-52-162 MW-52-162 006 161.5

-146.6 4/22/2011 10:18 1.85E+02 3.84E+02 4.29E+02

-7.50E-01 9.50E-01 1.42E+00 1.47E+00 8.40E+00 9.68E+00 1.95E-02 1.00E+01 1.10E+01 NA NA NA MW-52-162 MW-52-162 007 161.5

-146.6 7/26/2011 11:33 5.16E+02 4.20E+02 4.22E+02 3.77E-03 1.21E+00 1.57E+00 4.29E-02 8.34E+00 9.09E+00

-2.32E+00 9.87E+00 1.00E+01 NA NA NA MW-52-162 MW-52-181 001 181

-166.1 5/24/2007 12:06 2.48E+02 1.94E+02 2.04E+02

-3.19E-01 5.07E-01 7.58E-01

-5.99E-01 3.30E+00 3.52E+00

-2.81E-01 3.74E+00 4.19E+00

-2.23E-01 1.01E+01 1.17E+01 MW-52-181 MW-52-181 002 181

-166.1 8/6/2007 11:40 1.19E+02 1.77E+02 1.97E+02 5.84E-02 5.56E-01 6.77E-01

-1.21E+00 2.87E+00 2.97E+00 1.28E+00 2.96E+00 3.57E+00 NA NA NA MW-52-181 MW-52-181 003 181

-166.1 4/29/2008 10:24 1.56E+02 8.77E+01 1.44E+02 1.62E-01 2.46E-01 4.28E-01 1.08E+00 2.25E+00 3.96E+00 4.11E-01 2.12E+00 3.63E+00 NA NA NA MW-52-181 MW-52-181 004 181

-166.1 4/30/2009 12:07 1.47E+02 9.95E+01 1.01E+02

-4.95E-02 5.36E-01 7.43E-01

-2.57E+00 5.82E+00 3.88E+00

-1.51E+00 4.17E+00 4.27E+00 NA NA NA MW-52-181 MW-52-181 005 181

-166.1 5/5/2010 12:47 2.18E+02 1.70E+02 1.84E+02 2.80E-01 4.29E-01 4.67E-01

-2.64E-01 5.64E+00 6.37E+00

-2.38E+00 6.40E+00 6.61E+00 NA NA NA MW-52-181 MW-52-181 006 181

-166.1 4/22/2011 10:22 2.45E+02 3.96E+02 4.33E+02 1.18E+00 1.42E+00 1.48E+00 6.46E+01 2.68E+01 1.22E+01

-1.09E+00 1.22E+01 1.30E+01 NA NA NA MW-52-181 MW-52-181 007 181

-166.1 7/26/2011 11:43 2.41E+02 3.87E+02 4.22E+02 3.57E-01 1.28E+00 1.54E+00

-1.99E+00 7.50E+00 7.52E+00

-1.27E+00 9.39E+00 9.97E+00 NA NA NA MW-52-181 MW-53-82 001 75

-4.7 8/23/2006 12:50 1.18E+04 1.85E+03 5.02E+02 6.68E+00 3.10E+00 2.74E+00

-3.52E+00 7.20E+00 6.64E+00 1.30E+00 1.02E+01 1.16E+01 4.44E+00 9.39E+00 1.02E+01 MW-53-82 MW-53-82 001 75

-4.7 8/23/2006 12:50 1.32E+04 1.11E+03 6.12E+02 NA NA NA 9.35E-01 5.78E+00 6.37E+00 1.36E+00 5.70E+00 6.30E+00 NA NA NA MW-53-82 MW-53-82 002 75

-4.7 11/9/2006 11:15 4.54E+02 1.38E+02 1.40E+02 8.00E-02 8.10E-01 9.00E-01

-1.20E+00 3.00E+00 3.60E+00

-1.30E+00 3.30E+00 4.00E+00 1.30E+00 4.20E+00 4.60E+00 MW-53-82 MW-53-82 003 75

-4.7 6/22/2007 15:30 8.68E+03 1.05E+03 4.31E+02 3.98E+00 1.45E+00 1.04E+00 3.81E+00 3.78E+00 4.53E+00 1.95E+00 3.62E+00 4.63E+00 4.53E+00 1.54E+01 1.77E+01 MW-53-82 MW-53-82 004 75

-4.7 8/9/2007 11:31 7.76E+02 2.06E+02 2.04E+02

-3.41E-02 6.87E-01 8.82E-01 6.29E-01 2.33E+00 2.76E+00

-1.05E+00 2.17E+00 2.17E+00

-2.21E+00 1.99E+01 2.36E+01 MW-53-82 MW-53-82 005 75

-4.7 10/24/2007 13:53 1.11E+03 4.71E+02 4.03E+02 2.35E-01 3.11E-01 3.43E-01 3.07E-01 2.71E+00 3.05E+00

-1.06E+00 2.44E+00 2.38E+00

-1.59E+00 2.09E+01 2.41E+01 MW-53-82 MW-53-82 006 75

-4.7 1/21/2008 12:52 9.42E+02 1.86E+02 1.71E+02 2.19E-01 4.28E-01 4.87E-01 0.00E+00 5.42E+00 3.23E+00

-1.36E+00 2.84E+00 2.84E+00 3.84E+00 1.85E+01 2.11E+01 MW-53-82 MW-53-82 008 75

-4.7 8/4/2008 12:25 1.21E+03 1.84E+02 1.91E+02 6.95E-01 3.04E-01 3.94E-01 2.79E+00 2.26E+00 4.16E+00 2.55E-02 2.14E+00 3.58E+00 1.15E+01 1.24E+01 2.09E+01 MW-53-82 MW-53-82 009 75

-4.7 10/30/2008 15:52 7.94E+02 2.37E+02 1.65E+02

-4.79E-02 2.99E-01 4.19E-01 3.66E+00 6.21E+00 7.56E+00

-1.78E+00 6.33E+00 6.63E+00

-4.83E+00 1.65E+01 1.92E+01 MW-53-82 MW-53-82 010 75

-4.7 1/26/2009 12:00 4.26E+03 3.06E+02 1.92E+02 2.30E+00 1.07E+00 9.76E-01 1.10E+00 3.96E+00 4.51E+00

-2.25E-01 3.59E+00 3.88E+00 8.04E+00 1.64E+01 1.84E+01 MW-53-82 MW-53-82 011 75

-4.7 4/14/2009 14:58 1.75E+03 3.14E+02 1.36E+02

-3.03E-01 7.29E-01 8.97E-01 7.76E+00 6.60E+00 4.40E+00 1.28E-01 4.34E+00 4.84E+00

-1.09E+00 1.85E+01 2.16E+01 MW-53-82 MW-53-82 012 75

-4.7 7/21/2009 16:26 9.82E+02 2.67E+02 2.04E+02 1.67E-01 8.37E-01 9.81E-01 3.71E+00 3.87E+00 4.87E+00 3.14E+00 4.38E+00 5.53E+00

-9.93E-01 1.81E+01 2.07E+01 MW-53-82 MW-53-82 013 75

-4.7 10/27/2009 12:01 6.64E+02 1.95E+02 1.87E+02

-1.89E-01 3.36E-01 4.96E-01 1.31E+00 2.90E+00 3.49E+00 2.42E+00 4.13E+00 4.89E+00

-9.46E+00 1.79E+01 2.10E+01 MW-53-82 MW-53-82 014 75

-4.7 2/16/2010 12:04 7.14E+03 3.41E+02 1.53E+02 2.23E+00 9.77E-01 7.74E-01 0.00E+00 5.43E+00 7.23E+00

-9.98E-01 4.75E+00 4.91E+00

-1.24E+01 1.76E+01 2.09E+01 MW-53-82 MW-53-82 015 75

-4.7 4/15/2010 15:14 4.71E+03 6.56E+02 3.96E+02 4.06E-01 7.37E-01 8.29E-01 4.40E+00 1.27E+01 1.51E+01

-4.95E+00 1.13E+01 1.13E+01 1.39E+00 1.89E+01 2.19E+01 MW-53-82 MW-53-82 016 75

-4.7 7/30/2010 12:32 2.25E+03 2.66E+02 1.27E+02 3.34E-01 3.83E-01 4.00E-01

-3.03E+00 8.36E+00 8.46E+00

-1.90E+00 8.00E+00 8.03E+00

-1.45E+01 1.77E+01 2.23E+01 MW-53-82 MW-53-82 017 75

-4.7 10/27/2010 12:07 2.59E+03 2.79E+02 1.10E+02 8.07E-01 7.90E-01 8.26E-01

-3.74E-02 5.82E+00 6.57E+00 1.14E-01 6.23E+00 7.00E+00 NA NA NA MW-53-82 MW-53-82 018 75

-4.7 3/3/2011 11:53 5.95E+02 3.76E+02 3.73E+02 1.61E+00 1.82E+00 1.91E+00 3.61E+00 6.18E+00 7.60E+00

-1.88E+00 7.02E+00 7.25E+00

-7.63E+00 1.59E+01 1.85E+01 MW-53-82 MW-53-82 019 75

-4.7 4/18/2011 12:45 6.24E+02 4.56E+02 4.50E+02 4.40E-01 1.45E+00 1.67E+00

-4.57E+00 9.82E+00 9.80E+00 3.12E+00 8.78E+00 1.07E+01

-5.86E-01 1.48E+01 1.72E+01 MW-53-82 MW-53-82 021 75

-4.7 8/1/2011 11:11 7.16E+02 3.84E+02 3.71E+02

-5.52E-01 7.86E-01 1.06E+00

-2.46E+00 7.38E+00 7.34E+00

-3.40E-01 8.49E+00 9.05E+00 8.23E+00 1.80E+01 1.98E+01 MW-53-82 MW-53-82 022 75

-4.7 11/2/2011 11:26 2.27E+02 4.50E+02 5.00E+02

-2.42E-01 1.09E+00 1.49E+00

-1.19E+00 6.78E+00 7.87E+00

-6.95E-01 8.73E+00 1.07E+01

-4.95E-01 1.24E+01 1.41E+01 MW-53-82 MW-53-120 001 109.8

-39.5 8/30/2006 11:30 4.42E+03 1.25E+03 1.12E+03 NA NA NA

-6.13E+00 9.49E+00 9.40E+00 4.98E-01 8.96E+00 9.83E+00 NA NA NA MW-53-120 MW-53-120 002 109.8

-39.5 11/9/2006 11:20 7.90E+03 1.47E+03 1.00E+03 2.47E+01 1.83E+00 7.90E-01

-4.60E-01 2.70E+00 3.10E+00

-3.50E-01 2.76E+00 3.30E+00 2.71E+01 1.32E+01 1.30E+01 MW-53-120

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 19 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-53-120 003 109.8

-39.5 6/22/2007 14:22 9.61E+03 1.10E+03 4.32E+02 3.57E+01 3.69E+00 1.04E+00 7.93E+00 5.09E+00 2.84E+00 9.47E-01 3.15E+00 3.72E+00 1.73E+01 1.38E+01 1.47E+01 MW-53-120 MW-53-120 004 109.8

-39.5 8/9/2007 12:45 8.05E+03 1.02E+03 4.59E+02 3.70E+01 3.18E+00 9.24E-01 1.37E+00 3.62E+00 4.27E+00

-1.59E-01 3.74E+00 4.17E+00 1.95E+01 2.14E+01 2.35E+01 MW-53-120 MW-53-120 005 109.8

-39.5 10/24/2007 13:38 7.40E+03 9.29E+02 4.02E+02 3.81E+01 2.27E+00 4.82E-01

-5.34E-01 3.51E+00 3.29E+00

-2.23E-01 3.35E+00 3.72E+00 7.06E+00 2.10E+01 2.38E+01 MW-53-120 MW-53-120 006 109.8

-39.5 1/21/2008 10:43 7.48E+03 3.48E+02 1.72E+02 3.12E+01 2.40E+00 6.46E-01 1.38E+00 3.02E+00 3.18E+00 1.14E-01 3.30E+00 3.71E+00 1.71E+01 1.85E+01 2.02E+01 MW-53-120 MW-53-120 008 109.8

-39.5 5/13/2008 10:10 5.91E+03 3.38E+02 1.43E+02 3.11E+01 1.73E+00 6.73E-01

-1.39E+00 1.98E+00 3.10E+00 1.33E+00 2.15E+00 3.99E+00 2.22E+01 1.28E+01 2.08E+01 MW-53-120 MW-53-120 009 109.8

-39.5 8/4/2008 10:15 5.80E+03 3.46E+02 1.91E+02 3.03E+01 1.52E+00 3.11E-01

-9.74E-01 1.93E+00 3.02E+00

-1.15E-01 2.33E+00 3.20E+00 2.65E+01 1.30E+01 2.11E+01 MW-53-120 MW-53-120 010 109.8

-39.5 9/5/2008 10:55 5.76E+03 5.90E+02 5.07E+02 3.10E+01 1.59E+00 4.10E-01

-3.34E-01 2.41E+00 3.94E+00 NA NA NA 1.94E+01 1.19E+01 3.88E-01 MW-53-120 MW-53-120 011 109.8

-39.5 10/30/2008 13:00 5.57E+03 5.39E+02 1.66E+02 2.53E+01 2.04E+00 3.80E-01 2.73E+00 4.75E+00 5.74E+00 0.00E+00 9.13E+00 9.26E+00 5.82E+00 1.69E+01 1.93E+01 MW-53-120 MW-53-120 012 109.8

-39.5 11/17/2008 10:31 5.04E+03 3.23E+02 1.72E+02 4.25E+01 3.63E+00 6.74E-01 3.25E-01 4.72E+00 5.28E+00

-1.96E-02 4.09E+00 4.49E+00 2.12E+01 2.03E+01 2.21E+01 MW-53-120 MW-53-120 013 109.8

-39.5 1/26/2009 12:43 5.06E+03 3.26E+02 1.92E+02 2.64E+01 2.37E+00 7.50E-01

-3.60E-01 4.53E+00 5.10E+00 2.32E+00 4.34E+00 5.39E+00 1.27E+01 2.22E+01 2.49E+01 MW-53-120 MW-53-120 014 109.8

-39.5 3/16/2009 9:40 5.07E+03 8.51E+02 3.81E+02 2.37E+01 2.07E+00 7.32E-01

-9.24E-02 2.48E+00 1.65E+00

-7.85E-01 1.86E+00 1.58E+00 1.34E+01 1.73E+01 1.91E+01 MW-53-120 MW-53-120 015 109.8

-39.5 4/14/2009 13:08 5.65E+03 5.40E+02 1.36E+02 2.96E+01 2.19E+00 5.66E-01

-2.26E+00 6.15E+00 4.10E+00

-6.33E-01 3.86E+00 4.10E+00 8.66E+00 1.83E+01 2.07E+01 MW-53-120 MW-53-120 016 109.8

-39.5 7/21/2009 13:18 5.40E+03 5.18E+02 2.07E+02 4.00E-01 5.46E-01 5.93E-01

-1.68E+00 3.42E+00 3.59E+00 3.12E+00 3.86E+00 5.03E+00 4.59E+00 1.66E+01 1.88E+01 MW-53-120 MW-53-120 017 109.8

-39.5 10/27/2009 11:57 5.05E+03 3.47E+02 1.88E+02 3.10E+01 2.44E+00 7.18E-01

-1.77E-01 5.80E+00 6.55E+00

-2.13E+00 6.67E+00 7.01E+00 6.81E+00 1.86E+01 2.10E+01 MW-53-120 MW-53-120 018 109.8

-39.5 2/16/2010 11:51 4.66E+03 2.87E+02 1.53E+02 3.94E+01 3.39E+00 7.41E-01

-4.00E-01 5.82E+00 6.54E+00

-3.20E-01 6.23E+00 6.98E+00 6.73E+00 1.91E+01 2.16E+01 MW-53-120 MW-53-120 019 109.8

-39.5 4/15/2010 14:36 4.10E+03 6.14E+02 3.86E+02 3.32E+01 2.69E+00 9.06E-01

-6.92E+00 8.73E+00 8.19E+00 2.24E-01 8.74E+00 9.97E+00 7.53E+00 1.96E+01 2.22E+01 MW-53-120 MW-53-120 020 109.8

-39.5 7/30/2010 14:36 3.81E+03 3.38E+02 1.28E+02 2.97E+01 2.22E+00 4.77E-01 2.09E+00 1.27E+01 1.37E+01

-4.76E-01 8.04E+00 8.95E+00 3.59E+00 1.91E+01 2.21E+01 MW-53-120 MW-53-120 021 109.8

-39.5 10/27/2010 12:48 3.91E+03 3.38E+02 1.11E+02 2.96E+01 2.91E+00 7.02E-01 2.32E+00 5.07E+00 6.00E+00

-9.52E-01 5.46E+00 5.76E+00 NA NA NA MW-53-120 MW-53-120 022 109.8

-39.5 3/3/2011 12:00 3.84E+03 7.18E+02 3.89E+02 2.95E+01 3.76E+00 1.13E+00 2.30E+00 7.32E+00 8.49E+00

-2.43E+00 8.14E+00 8.13E+00 1.00E+01 1.70E+01 1.87E+01 MW-53-120 MW-53-120 023 109.8

-39.5 4/18/2011 11:52 4.11E+03 7.72E+02 4.75E+02 3.55E+01 4.56E+00 1.67E+00 1.38E+00 8.82E+00 9.99E+00 4.87E-01 9.24E+00 1.02E+01 1.76E+01 1.77E+01 1.87E+01 MW-53-120 MW-53-120 025 109.8

-39.5 8/1/2011 10:00 4.44E+03 6.15E+02 3.71E+02 3.30E+01 5.22E+00 1.94E+00

-2.07E+00 8.49E+00 8.67E+00

-5.10E-01 9.36E+00 1.01E+01 1.45E+01 1.02E+01 1.07E+01 MW-53-120 MW-53-120 026 109.8

-39.5 11/2/2011 11:56 8.02E+03 9.27E+02 4.67E+02 4.05E+01 5.16E+00 1.52E+00 4.60E+00 8.52E+00 1.15E+01

-1.89E-01 7.89E+00 1.03E+01 2.58E+00 1.93E+01 2.17E+01 MW-53-120 MW-54-37 001 36.5

-23.4 5/3/2007 16:19 8.01E+02 3.14E+02 3.02E+02 1.25E+01 2.12E+00 7.94E-01 2.44E+00 3.63E+00 4.42E+00

-1.43E+00 2.71E+00 2.51E+00 6.09E+00 1.98E+01 2.27E+01 MW-54-37 MW-54-37 002 36.5

-23.4 7/31/2007 10:30 8.88E+02 4.14E+02 2.68E+02 5.30E+00 1.11E+00 6.26E-01 1.46E+00 2.54E+00 3.03E+00

-2.64E-02 2.82E+00 3.13E+00

-4.74E+00 1.83E+01 2.14E+01 MW-54-37 MW-54-37 003 36.5

-23.4 10/19/2007 13:25 1.04E+03 4.26E+02 3.66E+02 6.19E+00 1.37E+00 6.14E-01 6.04E-01 3.30E+00 3.84E+00 6.61E-01 3.54E+00 4.19E+00 1.04E+01 1.59E+01 1.77E+01 MW-54-37 MW-54-37 004 36.5

-23.4 1/15/2008 13:18 1.07E+03 4.97E+02 4.18E+02 5.79E+00 1.47E+00 7.26E-01 7.48E-02 2.81E+00 3.11E+00 1.03E+00 2.79E+00 3.00E+00

-1.88E-01 2.06E+01 2.43E+01 MW-54-37 MW-54-37 005 36.5

-23.4 5/2/2008 13:59 8.70E+02 1.47E+02 1.43E+02 5.08E+00 7.44E-01 5.59E-01

-9.28E-01 2.12E+00 3.29E+00

-8.38E-01 2.56E+00 4.06E+00 3.37E+00 1.24E+01 2.12E+01 MW-54-37 MW-54-37 006 36.5

-23.4 7/22/2008 17:00 9.50E+02 1.08E+02 1.31E+02 6.20E+00 7.50E-01 4.63E-01 1.34E+00 2.22E+00 3.94E+00

-4.43E-01 2.09E+00 3.34E+00 1.42E+00 1.68E+01 2.95E+01 MW-54-37 MW-54-37 007 36.5

-23.4 11/11/2008 13:16 1.25E+03 2.07E+02 1.73E+02 7.33E+00 1.45E+00 5.76E-01

-2.50E+00 6.27E+00 6.87E+00 2.81E+00 5.14E+00 6.50E+00 2.49E+00 1.92E+01 2.21E+01 MW-54-37 MW-54-37 008 36.5

-23.4 2/3/2009 15:34 1.16E+03 1.86E+02 1.64E+02 5.93E+00 1.16E+00 6.66E-01 1.70E+00 3.33E+00 3.92E+00

-1.15E+00 3.24E+00 3.14E+00

-3.14E+00 2.16E+01 2.50E+01 MW-54-37 MW-54-37 009 36.5

-23.4 5/6/2009 11:51 1.24E+03 2.78E+02 1.81E+02 6.35E+00 1.20E+00 4.75E-01

-1.81E-02 4.22E+00 2.81E+00

-1.16E+00 2.75E+00 2.61E+00 4.33E+00 1.91E+01 2.16E+01 MW-54-37 MW-54-37 010 36.5

-23.4 8/4/2009 14:35 1.42E+03 3.26E+02 2.37E+02 5.53E+00 1.18E+00 6.88E-01

-3.76E-01 3.94E+00 4.29E+00 8.01E-01 4.42E+00 4.53E+00 5.80E+00 2.11E+01 2.41E+01 MW-54-37 MW-54-37 011 36.5

-23.4 11/13/2009 14:35 1.60E+03 2.99E+02 2.00E+02 5.77E+00 1.09E+00 4.66E-01

-6.22E-01 5.64E+00 6.28E+00

-2.24E+00 6.15E+00 6.31E+00 1.36E+01 1.80E+01 1.99E+01 MW-54-37 MW-54-37 012 36.5

-23.4 2/11/2010 11:16 1.31E+03 1.89E+02 1.53E+02 5.17E+00 1.43E+00 7.17E-01

-8.12E-01 5.16E+00 5.56E+00

-1.85E+00 5.78E+00 5.93E+00

-5.60E-01 1.86E+01 2.15E+01 MW-54-37 MW-54-37 013 36.5

-23.4 5/3/2010 14:09 1.18E+03 2.25E+02 1.38E+02 4.71E+00 1.26E+00 6.67E-01

-3.67E+00 8.43E+00 8.56E+00 1.69E+00 9.49E+00 1.14E+01 3.61E+00 2.07E+01 2.36E+01 MW-54-37 MW-54-37 014 36.5

-23.4 8/4/2010 14:32 1.21E+03 2.10E+02 1.30E+02 4.00E+00 8.07E-01 3.32E-01

-4.96E-01 7.38E+00 8.14E+00

-3.97E+00 9.63E+00 9.58E+00

-3.50E+00 1.50E+01 1.80E+01 MW-54-37 MW-54-37 015 36.5

-23.4 11/23/2010 14:47 1.45E+03 2.27E+02 1.26E+02 4.51E+00 1.42E+00 9.84E-01

-2.09E+00 5.46E+00 5.80E+00

-6.89E-01 6.35E+00 6.93E+00

-2.56E+00 1.81E+01 2.15E+01 MW-54-37 MW-54-37 016 36.5

-23.4 2/1/2011 14:10 1.33E+03 4.86E+02 3.78E+02 4.88E+00 1.77E+00 1.26E+00

-1.42E+00 5.54E+00 5.67E+00 3.12E-01 6.42E+00 7.04E+00

-2.81E+00 1.59E+01 1.82E+01 MW-54-37 MW-54-37 017 36.5

-23.4 4/12/2011 12:02 5.16E+03 8.40E+02 4.76E+02 4.91E+00 2.08E+00 1.69E+00 2.95E+00 8.26E+00 9.69E+00 2.50E+00 8.26E+00 9.96E+00 3.16E+00 1.45E+01 1.65E+01 MW-54-37 MW-54-37 018 36.5

-23.4 7/18/2011 13:45 2.79E+04 1.67E+03 4.43E+02 4.34E+00 2.19E+00 1.85E+00

-1.17E+00 6.36E+00 6.58E+00 4.07E+00 9.21E+00 1.09E+01 1.56E+01 1.91E+01 2.07E+01 MW-54-37 MW-54-37 019 36.5

-23.4 8/15/2011 9:25 3.13E+04 1.75E+03 1.98E+02 2.75E-01 1.60E+00 1.88E+00 5.03E-01 6.69E+00 7.58E+00 3.36E+00 7.56E+00 9.28E+00

-1.05E+01 1.66E+01 1.96E+01 MW-54-37 MW-54-37 020 36.5

-23.4 12/6/2011 10:37 1.40E+04 1.02E+03 3.73E+02 4.48E+00 2.07E+00 1.92E+00

-6.26E+00 9.72E+00 1.03E+01 4.84E-01 8.94E+00 1.14E+01

-5.68E+00 1.25E+01 1.43E+01 MW-54-37 MW-54-58 001 57.5

-44.4 5/3/2007 16:45 7.60E+02 3.11E+02 3.02E+02 2.22E+00 9.99E-01 7.02E-01

-3.77E-01 2.81E+00 3.07E+00 1.15E-01 2.71E+00 3.09E+00 7.50E+00 1.88E+01 2.12E+01 MW-54-58 MW-54-58 002 57.5

-44.4 7/31/2007 9:55 6.93E+02 3.72E+02 2.62E+02 1.76E+00 8.53E-01 7.52E-01

-1.32E+00 3.12E+00 3.23E+00 8.17E-03 3.01E+00 3.35E+00 1.97E-01 1.80E+01 2.08E+01 MW-54-58 MW-54-58 003 57.5

-44.4 10/19/2007 13:35 5.61E+02 2.00E+02 1.94E+02 4.38E-01 8.43E-01 9.56E-01

-2.08E-01 3.03E+00 3.40E+00 3.56E-01 2.96E+00 3.39E+00 2.09E+00 1.59E+01 1.81E+01 MW-54-58 MW-54-58 004 57.5

-44.4 1/15/2008 13:45 6.47E+02 4.40E+02 4.18E+02 2.32E+00 1.09E+00 8.13E-01 2.16E+00 4.59E+00 3.18E+00

-7.34E-01 3.06E+00 3.27E+00 4.41E+00 2.34E+01 2.71E+01 MW-54-58 MW-54-58 005 57.5

-44.4 5/2/2008 14:15 7.33E+02 1.39E+02 1.43E+02 1.69E+00 4.97E-01 5.77E-01 8.65E-01 2.13E+00 3.75E+00 1.63E+00 2.46E+00 4.54E+00 9.78E-01 1.27E+01 2.20E+01 MW-54-58 MW-54-58 006 57.5

-44.4 7/22/2008 17:05 5.78E+02 9.64E+01 1.31E+02 1.71E+00 5.24E-01 6.47E-01 3.78E-01 2.07E+00 3.59E+00

-1.41E-01 2.67E+00 4.23E+00 1.37E+01 1.69E+01 2.85E+01 MW-54-58 MW-54-58 007 57.5

-44.4 11/11/2008 13:02 6.98E+02 1.85E+02 1.74E+02 9.02E+00 1.65E+00 5.87E-01

-7.43E-01 3.71E+00 3.89E+00

-1.72E+00 3.50E+00 3.31E+00 3.01E+00 1.91E+01 2.18E+01 MW-54-58 MW-54-58 008 57.5

-44.4 2/3/2009 14:53 6.82E+02 1.71E+02 1.66E+02 1.98E+00 8.52E-01 7.24E-01 9.58E-01 2.78E+00 3.29E+00 4.22E-01 2.94E+00 3.39E+00

-3.05E+00 1.95E+01 2.27E+01 MW-54-58 MW-54-58 009 57.5

-44.4 5/6/2009 12:13 6.58E+02 2.24E+02 1.78E+02 2.00E+00 8.60E-01 6.94E-01 2.19E+00 6.09E+00 4.06E+00

-2.90E+00 3.63E+00 3.32E+00

-1.92E+01 2.15E+01 2.50E+01 MW-54-58 MW-54-58 010 57.5

-44.4 8/4/2009 14:30 7.81E+02 2.73E+02 2.34E+02 1.41E+00 8.04E-01 7.44E-01

-1.71E+00 3.25E+00 3.37E+00

-9.96E-01 3.62E+00 3.83E+00 8.34E-01 2.26E+01 2.60E+01 MW-54-58 MW-54-58 011 57.5

-44.4 11/13/2009 14:54 8.38E+02 2.48E+02 2.03E+02 1.91E+00 7.62E-01 6.03E-01 3.24E+00 5.67E+00 6.89E+00

-1.36E+00 5.29E+00 5.52E+00 7.05E+00 1.83E+01 2.07E+01 MW-54-58 MW-54-58 012 57.5

-44.4 2/11/2010 11:48 9.04E+02 1.74E+02 1.53E+02 1.38E+00 8.76E-01 7.99E-01 3.86E-01 5.50E+00 6.29E+00 1.08E+00 7.15E+00 7.82E+00

-1.32E+01 1.88E+01 2.23E+01 MW-54-58 MW-54-58 013 57.5

-44.4 5/3/2010 14:23 1.11E+03 2.25E+02 1.42E+02 1.44E+00 8.33E-01 6.81E-01 6.00E-01 1.10E+01 1.30E+01

-4.85E-01 8.46E+00 9.38E+00 6.55E+00 1.99E+01 2.26E+01 MW-54-58 MW-54-58 014 57.5

-44.4 8/4/2010 14:35 7.67E+02 1.79E+02 1.28E+02 1.36E+00 6.88E-01 6.20E-01

-3.95E+00 9.51E+00 9.85E+00 8.15E-01 1.14E+01 1.32E+01

-5.38E-01 1.44E+01 1.70E+01 MW-54-58 MW-54-58 015 57.5

-44.4 11/23/2010 14:55 8.21E+02 1.80E+02 1.23E+02 2.67E+00 1.13E+00 9.76E-01 3.83E+00 6.50E+00 7.88E+00 2.75E+00 6.57E+00 8.00E+00

-3.94E+00 1.86E+01 2.21E+01 MW-54-58 MW-54-58 016 57.5

-44.4 2/1/2011 14:22 9.58E+02 4.56E+02 3.92E+02 1.68E+00 1.34E+00 1.28E+00

-4.20E-02 7.14E+00 7.94E+00

-2.21E+00 6.84E+00 6.82E+00

-4.89E+00 1.66E+01 1.92E+01 MW-54-58 MW-54-58 017 57.5

-44.4 4/12/2011 12:04 9.94E+02 5.20E+02 4.79E+02 1.15E+00 1.84E+00 2.01E+00 1.70E+00 8.58E+00 9.66E+00 1.14E+00 8.74E+00 9.95E+00 5.01E+00 1.58E+01 1.78E+01 MW-54-58 MW-54-58 018 57.5

-44.4 7/18/2011 13:33 2.48E+03 6.12E+02 4.44E+02 1.49E+00 1.21E+00 1.14E+00

-1.98E+00 8.85E+00 9.27E+00 2.35E-01 9.09E+00 1.01E+01 1.83E+01 1.97E+01 2.13E+01 MW-54-58 MW-54-58 019 57.5

-44.4 8/15/2011 9:47 4.23E+03 6.63E+02 2.02E+02

-1.92E-01 9.75E-01 1.31E+00

-1.08E+00 8.61E+00 8.19E+00

-8.43E-01 9.45E+00 1.01E+01 2.37E+00 1.84E+01 2.07E+01 MW-54-58 MW-54-58 020 57.5

-44.4 12/6/2011 10:23 4.83E+03 6.48E+02 3.70E+02 1.60E+00 1.80E+00 1.91E+00 9.45E-01 4.23E+00 5.14E+00 1.72E+00 4.56E+00 5.85E+00 2.66E+00 1.25E+01 1.40E+01 MW-54-58 MW-54-123 001 123

-109.9 5/3/2007 14:18 1.11E+03 3.75E+02 3.36E+02 2.19E+01 2.71E+00 8.06E-01 4.21E+00 3.50E+00 3.67E+00

-2.65E+00 7.07E+00 3.31E+00 7.45E+00 1.79E+01 2.03E+01 MW-54-123 MW-54-123 002 123

-109.9 7/31/2007 11:10 9.63E+02 4.29E+02 3.69E+02 1.35E+01 1.47E+00 8.87E-01 0.00E+00 4.68E+00 4.49E+00 2.96E+00 4.02E+00 5.06E+00

-3.63E+00 1.86E+01 2.17E+01 MW-54-123 MW-54-123 003 123

-109.9 10/19/2007 12:09 7.01E+02 3.87E+02 3.62E+02 1.16E+01 1.88E+00 8.13E-01 4.02E-02 3.51E+00 3.88E+00

-1.72E+00 3.65E+00 3.68E+00

-4.31E-01 2.19E+01 2.51E+01 MW-54-123 MW-54-123 004 123

-109.9 1/15/2008 10:52 5.33E+02 4.23E+02 4.18E+02 9.56E+00 1.92E+00 7.51E-01 8.25E-01 3.48E+00 3.94E+00 4.41E-01 3.00E+00 3.42E+00 6.86E+00 2.25E+01 2.58E+01 MW-54-123 MW-54-123 005 123

-109.9 5/2/2008 10:06 6.98E+02 1.34E+02 1.39E+02 6.45E+00 8.46E-01 5.98E-01

-1.28E+00 2.22E+00 3.42E+00 4.12E+00 2.63E+00 5.24E+00

-3.04E+00 1.19E+01 2.08E+01 MW-54-123 MW-54-123 006 123

-109.9 7/22/2008 15:30 6.12E+02 9.77E+01 1.32E+02 6.52E+00 8.15E-01 5.56E-01

-2.82E-01 2.22E+00 3.72E+00

-2.93E+00 2.52E+00 3.55E+00 4.33E+00 1.57E+01 2.73E+01 MW-54-123 MW-54-123 007 123

-109.9 11/11/2008 11:03 5.80E+02 1.77E+02 1.71E+02 1.26E+01 2.10E+00 7.26E-01

-6.72E-01 5.14E+00 5.51E+00 2.63E+00 4.29E+00 5.62E+00

-4.68E+00 1.83E+01 2.15E+01 MW-54-123 MW-54-123 008 123

-109.9 2/3/2009 11:55 5.31E+02 1.64E+02 1.64E+02 5.91E+00 1.15E+00 5.70E-01 9.03E-01 3.03E+00 3.59E+00 5.33E-02 3.09E+00 3.52E+00 9.09E-01 2.00E+01 2.30E+01 MW-54-123 MW-54-123 009 123

-109.9 5/6/2009 12:40 6.94E+02 2.28E+02 1.78E+02 3.94E+00 1.00E+00 5.36E-01

-1.73E+00 5.94E+00 3.96E+00 2.06E+00 3.18E+00 3.94E+00 2.67E-01 1.86E+01 2.13E+01 MW-54-123 MW-54-123 010 123

-109.9 8/4/2009 14:10 6.29E+02 2.63E+02 2.38E+02 4.53E+00 1.24E+00 7.76E-01 6.28E-01 3.50E+00 4.06E+00 2.36E-01 3.27E+00 3.76E+00 1.79E+00 2.11E+01 2.41E+01 MW-54-123 MW-54-123 011 123

-109.9 11/13/2009 14:59 7.49E+02 2.40E+02 2.04E+02 3.77E+00 1.13E+00 8.78E-01 1.12E-01 1.25E+01 7.48E+00 6.15E+00 9.53E+00 7.53E+00

-1.31E+01 2.18E+01 2.59E+01 MW-54-123 MW-54-123 012 123

-109.9 2/11/2010 11:32 8.57E+02 1.71E+02 1.53E+02 3.40E+00 1.13E+00 7.64E-01 1.87E+00 5.45E+00 6.32E+00 8.01E-01 5.33E+00 6.09E+00

-3.75E+00 1.77E+01 2.06E+01 MW-54-123 MW-54-123 013 123

-109.9 5/3/2010 15:08 9.16E+02 2.04E+02 1.37E+02 2.25E+00 1.12E+00 8.35E-01

-3.24E+00 8.00E+00 8.03E+00 5.74E-01 9.62E+00 1.09E+01

-6.51E+00 1.94E+01 2.25E+01 MW-54-123 MW-54-123 014 123

-109.9 8/4/2010 14:49 7.83E+02 1.80E+02 1.28E+02 2.98E+00 7.55E-01 4.15E-01 1.53E+00 9.99E+00 1.16E+01

-9.37E-01 8.21E+00 8.72E+00

-5.12E+00 1.64E+01 1.97E+01 MW-54-123

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 20 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-54-123 015 123

-109.9 11/23/2010 15:12 8.12E+02 1.80E+02 1.22E+02 7.65E+00 1.46E+00 9.15E-01 2.19E+00 6.74E+00 7.78E+00

-1.25E+00 6.18E+00 6.62E+00 9.26E+00 1.91E+01 2.15E+01 MW-54-123 MW-54-123 016 123

-109.9 2/1/2011 14:11 1.08E+03 4.68E+02 3.90E+02 2.56E+00 1.39E+00 1.08E+00

-3.56E-01 6.02E+00 6.69E+00

-3.66E-03 5.16E+00 5.75E+00 2.50E+00 1.66E+01 1.87E+01 MW-54-123 MW-54-123 017 123

-109.9 4/12/2011 12:22 8.24E+02 4.98E+02 4.77E+02 3.44E+00 1.96E+00 1.72E+00

-5.24E+00 8.14E+00 7.60E+00 1.86E+00 8.04E+00 9.55E+00

-3.35E+00 1.48E+01 1.75E+01 MW-54-123 MW-54-123 018 123

-109.9 7/18/2011 14:06 5.70E+02 4.44E+02 4.46E+02 7.16E-01 1.02E+00 1.07E+00 1.92E+00 9.66E+00 1.05E+01 3.87E-02 6.30E+00 6.97E+00 6.27E+00 1.84E+01 2.04E+01 MW-54-123 MW-54-123 019 123

-109.9 8/15/2011 9:55 1.21E+03 3.75E+02 2.00E+02 3.74E+00 2.03E+00 1.78E+00 5.50E-01 8.46E+00 9.31E+00

-5.09E-01 8.88E+00 9.49E+00

-3.43E+00 1.94E+01 2.22E+01 MW-54-123 MW-54-123 020 123

-109.9 12/6/2011 10:37 3.92E+03 6.00E+02 3.71E+02 1.55E+00 1.86E+00 1.95E+00

-1.21E+00 4.38E+00 4.89E+00 1.04E+00 5.01E+00 6.08E+00 5.81E+00 1.28E+01 1.41E+01 MW-54-123 MW-54-144 001 144

-130.9 5/3/2007 14:31 1.34E+03 5.64E+02 4.68E+02 1.61E+01 2.42E+00 6.97E-01

-1.34E+00 3.62E+00 3.78E+00 5.23E-01 3.36E+00 3.84E+00 4.64E+00 1.68E+01 1.93E+01 MW-54-144 MW-54-144 002 144

-130.9 7/31/2007 13:33 1.89E+03 5.67E+02 2.66E+02 1.92E+01 1.98E+00 6.71E-01

-1.19E+00 2.90E+00 3.03E+00 5.02E-02 3.33E+00 3.77E+00

-6.13E+00 1.89E+01 2.23E+01 MW-54-144 MW-54-144 003 144

-130.9 10/19/2007 12:12 1.54E+03 4.73E+02 3.62E+02 1.58E+01 2.15E+00 7.69E-01 8.53E-01 2.85E+00 3.35E+00

-4.41E-01 3.18E+00 3.39E+00 4.35E-01 1.54E+01 1.78E+01 MW-54-144 MW-54-144 004 144

-130.9 1/15/2008 11:22 1.40E+03 5.34E+02 4.16E+02 1.53E+01 2.34E+00 8.48E-01 3.67E+00 5.04E+00 4.39E+00 4.86E-02 3.96E+00 4.34E+00 9.81E+00 2.24E+01 2.54E+01 MW-54-144 MW-54-144 005 144

-130.9 5/2/2008 10:20 1.15E+03 1.64E+02 1.43E+02 1.59E+01 1.31E+00 7.05E-01

-9.63E-01 2.26E+00 3.61E+00

-1.06E+00 2.37E+00 3.65E+00

-2.00E+00 1.21E+01 2.11E+01 MW-54-144 MW-54-144 006 144

-130.9 7/22/2008 15:35 1.13E+03 1.13E+02 1.31E+02 1.69E+01 1.23E+00 5.01E-01 1.57E+00 1.91E+00 3.48E+00

-4.98E-01 2.43E+00 3.49E+00 1.11E+01 1.69E+01 2.87E+01 MW-54-144 MW-54-144 007 144

-130.9 11/11/2008 11:06 1.14E+03 2.03E+02 1.72E+02 2.02E+01 2.27E+00 4.69E-01

-6.18E-01 3.90E+00 4.30E+00 5.67E-01 5.17E+00 5.96E+00 4.08E+00 2.09E+01 2.39E+01 MW-54-144 MW-54-144 008 144

-130.9 2/3/2009 12:41 1.13E+03 2.03E+02 1.77E+02 1.44E+01 1.76E+00 6.51E-01

-5.38E-03 3.15E+00 3.46E+00

-2.00E-02 2.91E+00 3.20E+00 2.21E+00 2.37E+01 2.76E+01 MW-54-144 MW-54-144 009 144

-130.9 5/6/2009 10:23 1.45E+03 2.91E+02 1.78E+02 1.46E+01 1.89E+00 5.95E-01

-1.95E+00 4.97E+00 3.31E+00 9.27E-01 3.35E+00 3.90E+00

-5.83E+00 1.91E+01 2.21E+01 MW-54-144 MW-54-144 010 144

-130.9 8/4/2009 11:10 1.29E+03 3.18E+02 2.39E+02 1.43E+01 1.74E+00 7.92E-01 6.70E-01 2.91E+00 3.33E+00

-1.51E+00 3.72E+00 3.66E+00 1.41E+01 2.24E+01 2.50E+01 MW-54-144 MW-54-144 011 144

-130.9 11/13/2009 12:13 1.40E+03 2.88E+02 2.03E+02 1.51E+01 1.83E+00 7.72E-01

-1.68E+00 4.38E+00 4.54E+00

-1.71E+00 3.12E+00 2.42E+00

-5.64E+00 1.92E+01 2.24E+01 MW-54-144 MW-54-144 012 144

-130.9 2/10/2010 10:37 1.20E+03 1.85E+02 1.53E+02 1.44E+01 2.07E+00 7.00E-01

-5.02E-01 9.22E+00 1.01E+01

-1.77E+00 7.62E+00 7.26E+00

-1.11E+01 1.88E+01 2.23E+01 MW-54-144 MW-54-144 013 144

-130.9 5/3/2010 11:41 1.28E+03 2.40E+02 1.45E+02 1.37E+01 2.04E+00 6.93E-01

-3.08E+00 7.11E+00 7.03E+00

-4.60E+00 8.03E+00 6.97E+00

-6.93E+00 2.11E+01 2.46E+01 MW-54-144 MW-54-144 014 144

-130.9 8/4/2010 11:44 1.44E+03 2.28E+02 1.33E+02 1.17E+01 1.42E+00 4.70E-01 8.96E+00 1.13E+01 1.44E+01 1.72E+00 8.79E+00 1.06E+01 1.78E+00 1.89E+01 2.21E+01 MW-54-144 MW-54-144 015 144

-130.9 11/23/2010 12:30 1.34E+03 2.15E+02 1.21E+02 1.08E+01 1.36E+00 5.83E-01 1.02E+00 7.82E+00 8.59E+00

-3.87E+00 6.48E+00 5.93E+00 2.30E+00 1.91E+01 2.21E+01 MW-54-144 MW-54-144 016 144

-130.9 2/1/2011 12:34 1.35E+03 4.96E+02 3.87E+02 9.31E+00 2.24E+00 1.06E+00

-9.04E-01 6.14E+00 6.70E+00

-6.36E-01 6.20E+00 6.74E+00

-4.27E+00 1.58E+01 1.82E+01 MW-54-144 MW-54-144 017 144

-130.9 4/12/2011 9:50 1.48E+03 5.68E+02 4.79E+02 1.20E+01 2.92E+00 1.81E+00 6.43E+00 7.44E+00 9.59E+00

-4.68E+00 9.58E+00 8.86E+00

-2.75E+00 1.48E+01 1.74E+01 MW-54-144 MW-54-144 018 144

-130.9 7/18/2011 12:38 4.34E+03 7.41E+02 4.43E+02 1.13E+01 2.44E+00 1.26E+00 3.37E+00 7.47E+00 8.78E+00

-3.49E+00 8.91E+00 8.88E+00 1.53E+01 1.87E+01 2.03E+01 MW-54-144 MW-54-144 019 144

-130.9 8/15/2011 11:44 5.27E+03 7.23E+02 1.96E+02 1.10E+01 2.75E+00 1.62E+00 4.07E+00 9.39E+00 1.10E+01 4.25E-01 9.81E+00 1.08E+01

-5.13E+00 1.89E+01 2.18E+01 MW-54-144 MW-54-144 020 144

-130.9 12/6/2011 13:25 6.85E+03 7.44E+02 3.71E+02 9.05E+00 2.99E+00 1.96E+00 8.64E-01 5.58E+00 6.45E+00 3.97E-01 5.58E+00 6.68E+00

-2.77E+00 1.22E+01 1.38E+01 MW-54-144 MW-54-173 001 172.5

-159.4 5/3/2007 14:43 1.90E+03 6.27E+02 4.71E+02 2.09E+01 2.64E+00 8.31E-01

-4.52E-01 3.82E+00 4.16E+00 1.92E+00 3.46E+00 4.27E+00 5.00E+00 1.94E+01 2.21E+01 MW-54-173 MW-54-173 002 172.5

-159.4 7/31/2007 13:40 2.08E+03 5.94E+02 2.68E+02 1.45E+01 1.85E+00 8.29E-01 7.90E-01 2.63E+00 3.10E+00 7.75E-01 2.22E+00 2.74E+00 3.92E+00 1.81E+01 2.07E+01 MW-54-173 MW-54-173 003 172.5

-159.4 10/19/2007 12:14 1.91E+03 5.07E+02 3.63E+02 1.49E+01 2.07E+00 6.21E-01 1.05E+00 3.29E+00 3.79E+00

-3.08E-01 2.87E+00 3.18E+00 1.37E+00 1.49E+01 1.70E+01 MW-54-173 MW-54-173 004 172.5

-159.4 1/15/2008 11:15 1.84E+03 5.84E+02 4.16E+02 1.41E+01 1.80E+00 9.29E-01

-3.68E-01 2.81E+00 3.08E+00 5.21E-01 3.00E+00 3.49E+00 4.79E+00 2.30E+01 2.65E+01 MW-54-173 MW-54-173 005 172.5

-159.4 5/2/2008 10:35 2.11E+03 2.10E+02 1.42E+02 1.22E+01 1.18E+00 9.06E-01

-6.44E-01 2.22E+00 3.66E+00 1.71E+00 2.10E+00 4.01E+00 4.47E+00 1.23E+01 2.10E+01 MW-54-173 MW-54-173 006 172.5

-159.4 7/22/2008 15:51 2.05E+03 1.35E+02 1.30E+02 1.29E+01 1.08E+00 5.25E-01

-6.92E-02 2.07E+00 3.52E+00

-1.62E+00 2.11E+00 3.15E+00 7.86E+00 1.59E+01 2.72E+01 MW-54-173 MW-54-173 007 172.5

-159.4 11/11/2008 11:07 1.66E+03 2.24E+02 1.75E+02 1.61E+01 2.12E+00 7.21E-01 1.51E-01 4.23E+00 4.77E+00

-5.84E-01 3.93E+00 4.19E+00 3.04E+00 1.92E+01 2.20E+01 MW-54-173 MW-54-173 008 172.5

-159.4 2/3/2009 12:19 1.98E+03 5.45E+02 3.85E+02 1.02E+01 1.45E+00 5.93E-01

-1.52E+00 3.03E+00 3.08E+00

-2.37E+00 3.20E+00 2.94E+00 4.01E+00 2.37E+01 2.76E+01 MW-54-173 MW-54-173 009 172.5

-159.4 5/6/2009 10:24 1.57E+03 3.03E+02 1.80E+02 8.59E+00 1.46E+00 7.75E-01 3.40E-01 5.16E+00 3.44E+00 1.02E+00 2.63E+00 3.14E+00

-1.38E+00 1.92E+01 2.20E+01 MW-54-173 MW-54-173 010 172.5

-159.4 8/4/2009 11:15 1.87E+03 3.56E+02 2.34E+02 9.19E+00 1.51E+00 7.94E-01 1.49E+00 3.33E+00 3.92E+00

-6.51E-01 2.98E+00 3.14E+00 3.69E+00 2.19E+01 2.49E+01 MW-54-173 MW-54-173 011 172.5

-159.4 11/13/2009 12:04 1.83E+03 3.15E+02 2.03E+02 7.42E+00 1.29E+00 7.36E-01 7.30E-01 6.35E+00 7.30E+00

-1.25E+00 7.27E+00 6.86E+00

-1.70E+00 1.91E+01 2.20E+01 MW-54-173 MW-54-173 012 172.5

-159.4 2/10/2010 10:34 1.61E+03 2.00E+02 1.53E+02 7.51E+00 1.53E+00 7.44E-01 2.09E+00 5.21E+00 6.19E+00 1.33E+00 5.76E+00 6.72E+00

-9.09E+00 2.13E+01 2.50E+01 MW-54-173 MW-54-173 013 172.5

-159.4 5/3/2010 11:47 2.03E+03 2.84E+02 1.42E+02 6.28E+00 1.42E+00 5.94E-01

-3.87E-01 8.87E+00 9.74E+00 2.77E+00 7.82E+00 9.75E+00

-1.68E+00 2.03E+01 2.33E+01 MW-54-173 MW-54-173 014 172.5

-159.4 8/4/2010 12:09 1.53E+03 2.31E+02 1.30E+02 5.97E+00 1.02E+00 3.24E-01

-7.48E+00 8.07E+00 7.10E+00 4.86E-01 9.46E+00 1.08E+01

-1.31E+00 1.68E+01 1.99E+01 MW-54-173 MW-54-173 015 172.5

-159.4 11/23/2010 12:25 1.51E+03 2.28E+02 1.24E+02 4.65E+00 1.28E+00 8.17E-01

-1.84E+00 7.05E+00 7.31E+00

-1.82E+00 6.23E+00 6.51E+00 2.22E+00 1.84E+01 2.14E+01 MW-54-173 MW-54-173 016 172.5

-159.4 2/1/2011 12:29 1.66E+03 5.26E+02 3.81E+02 5.81E+00 1.88E+00 1.10E+00

-2.87E-01 8.00E+00 8.79E+00 1.01E+00 1.06E+01 1.20E+01

-5.49E+00 1.77E+01 2.05E+01 MW-54-173 MW-54-173 017 172.5

-159.4 4/12/2011 9:56 1.26E+03 5.46E+02 4.78E+02 3.91E+00 1.92E+00 1.58E+00

-1.29E+01 1.38E+01 1.53E+01 5.93E+00 9.66E+00 1.25E+01

-2.17E+00 1.50E+01 1.76E+01 MW-54-173 MW-54-173 018 172.5

-159.4 7/18/2011 12:20 1.48E+03 5.28E+02 4.40E+02 4.54E+00 1.64E+00 1.11E+00 2.97E-01 6.84E+00 7.45E+00 1.10E+00 6.51E+00 7.50E+00

-5.43E+00 1.56E+01 1.75E+01 MW-54-173 MW-54-173 019 172.5

-159.4 8/15/2011 11:50 1.50E+03 4.08E+02 1.97E+02 4.32E+00 1.94E+00 1.48E+00

-1.36E+00 1.01E+01 1.05E+01

-7.70E-01 1.21E+01 1.33E+01

-7.41E+00 2.05E+01 2.42E+01 MW-54-173 MW-54-173 020 172.5

-159.4 12/6/2011 13:26 2.32E+03 6.66E+02 3.26E+02 4.72E+00 2.32E+00 1.97E+00

-8.33E-01 4.83E+00 5.47E+00 9.05E-01 5.19E+00 6.34E+00

-2.75E+00 1.24E+01 1.41E+01 MW-54-173 MW-54-190 001 190

-176.9 5/3/2007 15:00 1.87E+03 6.23E+02 4.71E+02 1.95E+01 2.56E+00 7.00E-01 1.82E+00 3.23E+00 3.90E+00 3.32E-01 2.90E+00 3.30E+00 1.54E+00 1.88E+01 2.18E+01 MW-54-190 MW-54-190 002 190

-176.9 7/31/2007 13:45 2.25E+03 6.12E+02 2.66E+02 1.79E+01 2.15E+00 7.59E-01

-2.13E+00 3.35E+00 3.12E+00 9.32E-01 3.09E+00 3.67E+00

-3.07E+00 1.66E+01 1.94E+01 MW-54-190 MW-54-190 003 190

-176.9 10/19/2007 12:20 2.13E+03 5.24E+02 3.60E+02 2.04E+01 2.46E+00 7.97E-01

-1.04E+00 3.45E+00 3.07E+00 7.41E-01 4.05E+00 3.33E+00

-3.38E+00 1.71E+01 1.97E+01 MW-54-190 MW-54-190 004 190

-176.9 1/15/2008 11:37 2.24E+03 6.26E+02 4.16E+02 1.93E+01 2.54E+00 8.15E-01 6.45E-01 2.64E+00 3.11E+00

-3.88E-01 2.28E+00 2.50E+00 9.23E+00 2.42E+01 2.75E+01 MW-54-190 MW-54-190 005 190

-176.9 5/2/2008 10:30 1.84E+03 1.98E+02 1.43E+02 1.95E+01 1.40E+00 7.88E-01 8.19E-01 1.98E+00 3.46E+00 8.81E-01 1.95E+00 3.51E+00 6.07E+00 1.25E+01 2.13E+01 MW-54-190 MW-54-190 006 190

-176.9 7/22/2008 15:50 1.25E+03 1.15E+02 1.30E+02 2.13E+01 1.37E+00 5.60E-01 8.45E-01 1.98E+00 3.41E+00

-1.64E+00 2.06E+00 3.02E+00

-8.42E+00 1.61E+01 2.92E+01 MW-54-190 MW-54-190 007 190

-176.9 11/11/2008 11:09 1.44E+03 2.10E+02 1.69E+02 3.38E+01 3.12E+00 6.14E-01

-5.41E-01 5.00E+00 5.54E+00

-6.47E-01 3.54E+00 3.63E+00 4.86E-01 1.91E+01 2.20E+01 MW-54-190 MW-54-190 008 190

-176.9 2/3/2009 12:35 1.43E+03 4.88E+02 3.80E+02 1.90E+01 1.85E+00 3.85E-01

-1.18E+00 3.48E+00 3.74E+00 7.39E-01 3.08E+00 3.70E+00

-5.10E+00 2.37E+01 2.84E+01 MW-54-190 MW-54-190 009 190

-176.9 5/6/2009 10:27 1.60E+03 3.05E+02 1.80E+02 1.98E+01 2.07E+00 4.19E-01 2.31E+00 7.22E+00 4.81E+00

-8.94E-01 3.86E+00 4.04E+00

-2.80E+00 1.94E+01 2.23E+01 MW-54-190 MW-54-190 010 190

-176.9 8/4/2009 11:20 1.94E+03 3.62E+02 2.36E+02 1.98E+01 2.00E+00 6.71E-01

-7.49E-01 3.31E+00 3.53E+00 9.28E-01 3.99E+00 4.59E+00

-1.51E+00 2.14E+01 2.47E+01 MW-54-190 MW-54-190 011 190

-176.9 11/13/2009 12:17 2.01E+03 3.27E+02 2.03E+02 1.98E+01 1.94E+00 4.40E-01 1.55E+00 8.64E+00 5.62E+00 3.18E+00 5.42E+00 7.03E+00 1.33E+00 1.96E+01 2.26E+01 MW-54-190 MW-54-190 012 190

-176.9 2/10/2010 10:32 1.57E+03 1.98E+02 1.54E+02 2.35E+01 2.67E+00 6.73E-01 2.84E+00 4.98E+00 6.01E+00 1.64E-01 5.19E+00 5.77E+00

-9.59E+00 1.68E+01 1.99E+01 MW-54-190 MW-54-190 013 190

-176.9 5/3/2010 12:01 1.71E+03 2.67E+02 1.44E+02 2.22E+01 2.61E+00 6.32E-01 3.80E+00 1.05E+01 1.25E+01

-3.30E+00 1.11E+01 1.14E+01

-6.89E+00 2.24E+01 2.60E+01 MW-54-190 MW-54-190 014 190

-176.9 8/4/2010 12:34 1.60E+03 2.33E+02 1.28E+02 1.57E+01 1.51E+00 2.87E-01

-1.62E+00 8.25E+00 8.88E+00

-1.20E+00 8.80E+00 9.41E+00

-3.22E+00 1.84E+01 2.21E+01 MW-54-190 MW-54-190 015 190

-176.9 11/23/2010 12:22 1.93E+03 2.55E+02 1.27E+02 1.92E+01 1.89E+00 7.12E-01

-9.64E-01 6.04E+00 6.61E+00

-2.29E+00 6.71E+00 6.79E+00

-3.18E-01 1.81E+01 2.14E+01 MW-54-190 MW-54-190 016 190

-176.9 2/1/2011 12:25 1.89E+03 5.56E+02 3.90E+02 1.68E+01 3.36E+00 1.28E+00 4.59E-01 6.34E+00 7.14E+00

-3.55E+00 5.96E+00 5.21E+00 1.71E+00 1.67E+01 1.89E+01 MW-54-190 MW-54-190 017 190

-176.9 4/12/2011 10:01 2.07E+03 6.18E+02 4.78E+02 1.90E+01 3.38E+00 1.77E+00 3.33E+00 7.86E+00 9.23E+00 8.70E-01 9.00E+00 1.00E+01 3.35E-01 1.58E+01 1.82E+01 MW-54-190 MW-54-190 018 190

-176.9 7/18/2011 12:14 2.37E+03 6.06E+02 4.45E+02 1.75E+01 2.85E+00 1.12E+00 2.24E+00 1.16E+01 1.29E+01

-2.72E+00 1.18E+01 1.22E+01

-3.86E+00 1.55E+01 1.74E+01 MW-54-190 MW-54-190 019 190

-176.9 8/15/2011 12:00 3.31E+03 5.88E+02 2.00E+02 1.89E+01 3.39E+00 1.22E+00

-3.96E+00 8.61E+00 7.57E+00

-4.68E+00 8.73E+00 8.11E+00

-5.67E+00 1.96E+01 2.30E+01 MW-54-190 MW-54-190 020 190

-176.9 12/6/2011 13:38 8.77E+03 8.22E+02 3.68E+02 1.81E+01 3.72E+00 1.90E+00 5.15E-01 3.87E+00 4.56E+00 1.47E+00 4.11E+00 5.26E+00 3.28E+00 1.21E+01 1.34E+01 MW-54-190 MW-55-24 001 16 2.3 11/9/2006 13:20 2.00E+03 1.11E+03 1.00E+03 1.66E+01 2.40E+00 1.90E+00

-7.00E-01 4.50E+00 5.80E+00 4.00E-01 5.40E+00 6.70E+00 1.10E+00 5.40E+00 6.00E+00 MW-55-24 MW-55-24 002 16 2.3 6/28/2007 11:20 3.08E+03 2.96E+02 1.87E+02 3.25E+01 3.51E+00 1.06E+00 0.00E+00 4.00E+00 3.70E+00 1.16E+00 3.81E+00 4.60E+00 NA NA NA MW-55-24 MW-55-24 003 16 2.3 8/2/2007 11:17 2.71E+03 7.28E+02 5.47E+02 2.31E+01 2.67E+00 9.19E-01

-4.91E-01 2.79E+00 3.02E+00 1.40E+00 2.94E+00 3.47E+00

-7.94E+00 1.91E+01 2.31E+01 MW-55-24 MW-55-24 004 16 2.3 10/16/2007 10:15 2.20E+03 5.36E+02 3.68E+02 2.29E+01 2.61E+00 8.43E-01 6.26E-01 3.63E+00 4.21E+00 7.46E-01 3.29E+00 3.47E+00 NA NA NA MW-55-24 MW-55-24 005 16 2.3 1/28/2008 12:57 1.14E+03 3.65E+02 2.96E+02 2.26E+01 2.46E+00 9.24E-01 3.33E+00 3.26E+00 2.50E+00 1.04E+00 1.55E+00 2.51E+00 1.44E+01 1.82E+01 2.00E+01 MW-55-24 MW-55-24 006 16 2.3 4/25/2008 14:15 1.05E+03 1.59E+02 1.44E+02 2.55E+01 1.57E+00 4.89E-01 1.08E+00 2.31E+00 4.02E+00

-9.33E-01 2.55E+00 4.02E+00 1.25E+00 1.14E+01 1.97E+01 MW-55-24 MW-55-24 007 16 2.3 8/1/2008 13:15 1.40E+03 1.93E+02 1.91E+02 2.22E+01 1.36E+00 5.73E-01

-7.37E-03 2.19E+00 3.69E+00 2.85E+00 2.34E+00 4.16E+00 6.11E+00 1.24E+01 2.11E+01 MW-55-24 MW-55-24 008 16 2.3 10/21/2008 13:19 7.82E+02 2.57E+02 1.93E+02 1.08E+01 1.80E+00 5.55E-01 1.30E+00 5.13E+00 5.92E+00

-3.49E+00 6.66E+00 6.59E+00 4.77E+00 1.79E+01 2.03E+01 MW-55-24 MW-55-24 009 16 2.3 2/11/2009 12:55 1.04E+03 4.49E+02 3.84E+02 1.69E+01 1.74E+00 3.85E-01 1.90E+00 2.88E+00 3.50E+00 1.35E+00 3.14E+00 3.76E+00

-1.21E+01 2.45E+01 2.99E+01 MW-55-24 MW-55-24 010 16 2.3 4/29/2009 11:28 1.14E+03 2.69E+02 1.80E+02 1.55E+01 1.88E+00 6.50E-01

-1.81E-01 1.02E+01 6.77E+00

-9.81E-01 4.91E+00 5.14E+00 4.88E+00 1.95E+01 2.22E+01 MW-55-24

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 21 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-55-24 011 16 2.3 8/5/2009 13:52 1.59E+03 3.39E+02 2.37E+02 3.07E+01 2.52E+00 7.22E-01

-7.90E-01 3.74E+00 3.61E+00 1.05E+00 2.92E+00 3.52E+00 4.83E+00 2.28E+01 2.59E+01 MW-55-24 MW-55-24 012 16 2.3 11/2/2009 13:01 1.38E+03 2.27E+02 1.88E+02 1.93E+01 1.95E+00 7.59E-01 1.03E+01 9.51E+00 5.59E+00 3.87E+00 5.63E+00 7.18E+00

-7.44E+00 1.53E+01 1.80E+01 MW-55-24 MW-55-24 013 16 2.3 2/18/2010 14:01 2.21E+03 2.49E+02 1.74E+02 2.06E+01 2.46E+00 7.08E-01 4.99E+00 4.18E+00 5.27E+00 7.07E-01 4.32E+00 4.92E+00

-8.06E+00 1.86E+01 2.18E+01 MW-55-24 MW-55-24 014 16 2.3 4/21/2010 14:08 1.62E+03 4.65E+02 3.90E+02 1.94E+01 2.09E+00 8.38E-01

-1.91E+00 7.13E+00 7.46E+00 6.66E-01 9.22E+00 1.03E+01

-7.52E-01 1.79E+01 2.07E+01 MW-55-24 MW-55-24 015 16 2.3 8/6/2010 13:11 1.21E+03 2.12E+02 1.30E+02 8.64E+00 1.22E+00 4.51E-01 1.13E+00 8.94E+00 1.04E+01 8.02E-01 8.22E+00 9.59E+00 1.17E+01 1.64E+01 1.81E+01 MW-55-24 MW-55-24 016 16 2.3 11/1/2010 14:10 1.39E+03 2.09E+02 1.65E+02 1.08E+01 1.98E+00 9.92E-01

-2.29E-01 8.10E+00 9.04E+00

-4.71E+00 7.93E+00 6.54E+00 7.56E+00 1.88E+01 2.12E+01 MW-55-24 MW-55-24 017 16 2.3 2/3/2011 14:13 1.02E+03 4.48E+02 4.20E+02 1.09E+01 2.82E+00 1.96E+00

-3.57E-01 4.92E+00 5.43E+00 4.75E+00 8.74E+00 7.44E+00

-5.31E+00 1.81E+01 2.14E+01 MW-55-24 MW-55-24 018 16 2.3 8/12/2011 12:12 1.71E+03 4.35E+02 2.01E+02 1.29E+01 3.21E+00 1.59E+00

-4.41E+00 7.32E+00 6.86E+00 5.14E-01 7.95E+00 8.82E+00 6.75E+00 2.09E+01 2.34E+01 MW-55-24 MW-55-24 019 16 2.3 11/14/2011 11:26 2.57E+03 6.66E+02 4.98E+02 2.33E+01 4.08E+00 1.56E+00 0.00E+00 8.49E+00 1.07E+01 3.56E+00 1.08E+01 1.50E+01

-7.45E+00 1.87E+01 2.17E+01 MW-55-24 MW-55-35 001 32

-13.8 11/9/2006 13:40 9.04E+03 1.50E+03 1.00E+03 4.04E+01 4.80E+00 3.30E+00

-1.10E+00 3.30E+00 3.90E+00

-5.00E-01 3.30E+00 4.10E+00 4.30E+00 5.40E+00 5.80E+00 MW-55-35 MW-55-35 002 32

-13.8 6/28/2007 11:50 3.09E+03 2.93E+02 1.84E+02 3.25E+01 3.31E+00 9.74E-01

-4.64E-01 3.46E+00 3.78E+00

-1.00E+00 3.62E+00 3.75E+00 NA NA NA MW-55-35 MW-55-35 003 32

-13.8 8/2/2007 11:20 3.68E+03 7.91E+02 5.33E+02 3.40E+01 3.45E+00 8.95E-01 9.35E-01 3.19E+00 3.24E+00 7.69E-01 2.23E+00 2.70E+00 2.90E+00 1.96E+01 2.28E+01 MW-55-35 MW-55-35 004 32

-13.8 10/16/2007 10:02 5.09E+03 7.34E+02 3.63E+02 3.16E+01 3.04E+00 1.04E+00 2.62E+00 3.36E+00 3.58E+00 1.44E+00 3.44E+00 4.20E+00 NA NA NA MW-55-35 MW-55-35 005 32

-13.8 1/28/2008 11:46 2.33E+03 4.59E+02 2.97E+02 2.64E+01 2.60E+00 5.21E-01

-5.28E-01 2.12E+00 2.26E+00

-6.90E-01 2.19E+00 2.32E+00 1.12E+01 1.76E+01 1.96E+01 MW-55-35 MW-55-35 006 32

-13.8 4/25/2008 12:07 1.60E+03 1.86E+02 1.42E+02 3.44E+01 1.86E+00 6.11E-01 1.46E+00 2.26E+00 4.06E+00 2.34E+00 2.40E+00 4.61E+00 5.22E+00 1.25E+01 2.14E+01 MW-55-35 MW-55-35 007 32

-13.8 8/1/2008 10:47 1.73E+03 2.08E+02 1.91E+02 2.54E+01 1.42E+00 4.28E-01 3.51E-01 2.17E+00 3.74E+00 2.59E-01 2.33E+00 3.99E+00 1.26E+01 1.23E+01 2.05E+01 MW-55-35 MW-55-35 008 32

-13.8 2/4/2009 13:46 8.53E+02 4.28E+02 3.84E+02 1.71E+01 1.82E+00 4.39E-01 1.01E+00 3.14E+00 3.69E+00 1.58E-01 2.78E+00 3.15E+00 8.49E-01 2.30E+01 2.69E+01 MW-55-35 MW-55-35 009 32

-13.8 4/29/2009 11:26 2.70E+03 3.77E+02 1.80E+02 3.51E+01 2.79E+00 6.05E-01

-4.06E+00 6.72E+00 4.48E+00 7.97E-01 4.28E+00 5.04E+00 7.31E+00 2.03E+01 2.28E+01 MW-55-35 MW-55-35 010 32

-13.8 8/5/2009 13:40 2.83E+03 4.19E+02 2.38E+02 4.14E+01 2.88E+00 7.28E-01

-1.22E+00 3.52E+00 3.46E+00 2.68E-01 3.35E+00 3.79E+00

-2.68E+00 2.26E+01 2.61E+01 MW-55-35 MW-55-35 011 32

-13.8 11/2/2009 12:34 2.37E+03 2.64E+02 1.88E+02 2.86E+01 2.40E+00 7.17E-01 6.51E-01 4.23E+00 4.96E+00 2.97E+00 4.46E+00 5.72E+00

-9.10E+00 1.73E+01 2.02E+01 MW-55-35 MW-55-35 012 32

-13.8 2/18/2010 14:03 2.49E+03 2.60E+02 1.74E+02 3.10E+01 3.29E+00 7.35E-01

-2.47E+00 4.86E+00 5.03E+00 1.05E+00 4.83E+00 5.63E+00

-5.22E+00 1.83E+01 2.13E+01 MW-55-35 MW-55-35 013 32

-13.8 4/21/2010 14:31 2.01E+03 4.92E+02 3.90E+02 2.63E+01 2.44E+00 7.84E-01

-4.26E+00 8.04E+00 7.79E+00 2.77E+00 7.27E+00 9.17E+00

-4.98E-01 1.77E+01 2.06E+01 MW-55-35 MW-55-35 014 32

-13.8 8/6/2010 13:15 1.89E+03 2.46E+02 1.25E+02 1.66E+01 1.65E+00 3.57E-01

-4.27E-01 8.60E+00 9.69E+00 4.31E+00 9.66E+00 1.22E+01 9.65E+00 1.62E+01 1.81E+01 MW-55-35 MW-55-35 015 32

-13.8 11/1/2010 14:26 1.57E+03 2.12E+02 1.62E+02 1.13E+01 1.97E+00 9.17E-01

-2.41E+00 8.88E+00 9.46E+00 5.36E-01 8.18E+00 9.32E+00 6.22E+00 1.79E+01 2.03E+01 MW-55-35 MW-55-35 016 32

-13.8 2/3/2011 14:16 1.70E+03 4.84E+02 3.86E+02 1.93E+01 3.42E+00 2.05E+00 8.32E-01 5.82E+00 6.45E+00 1.03E+00 6.24E+00 7.03E+00

-2.16E+00 1.86E+01 2.17E+01 MW-55-35 MW-55-35 017 32

-13.8 8/12/2011 12:15 2.94E+03 5.58E+02 2.01E+02 1.63E+01 3.18E+00 1.50E+00 4.22E-01 7.50E+00 8.42E+00

-1.40E+00 8.31E+00 8.83E+00

-1.22E+01 2.17E+01 2.60E+01 MW-55-35 MW-55-35 018 32

-13.8 11/14/2011 11:23 2.79E+03 6.84E+02 5.00E+02 2.35E+01 3.99E+00 1.60E+00 2.04E-01 7.08E+00 8.67E+00 8.98E-01 8.22E+00 1.06E+01 4.79E+00 1.87E+01 2.09E+01 MW-55-35 MW-55-54 001 47

-28.8 11/9/2006 13:30 1.31E+04 1.68E+03 1.00E+03 2.28E+01 1.35E+00 8.10E-01 1.00E+00 3.30E+00 3.80E+00

-3.20E+00 4.50E+00 5.70E+00 1.70E+00 4.80E+00 5.40E+00 MW-55-54 MW-55-54 002 47

-28.8 6/28/2007 11:40 1.04E+04 4.79E+02 1.84E+02 2.47E+01 2.88E+00 9.85E-01 1.30E-01 3.09E+00 3.43E+00

-4.69E-01 3.27E+00 3.48E+00 NA NA NA MW-55-54 MW-55-54 003 47

-28.8 8/2/2007 12:00 9.91E+03 1.19E+03 5.51E+02 2.22E+01 2.38E+00 9.10E-01

-1.09E+00 3.69E+00 3.80E+00 1.46E+00 2.87E+00 3.56E+00 6.13E+00 1.99E+01 2.28E+01 MW-55-54 MW-55-54 004 47

-28.8 10/16/2007 10:05 1.03E+04 9.96E+02 3.61E+02 2.23E+01 2.49E+00 6.15E-01

-9.80E-01 2.82E+00 3.02E+00 8.80E-01 3.65E+00 2.99E+00 NA NA NA MW-55-54 MW-55-54 005 47

-28.8 1/28/2008 11:42 7.48E+03 7.35E+02 2.97E+02 2.28E+01 2.40E+00 5.39E-01

-8.47E-01 2.16E+00 2.30E+00

-1.29E+00 2.81E+00 2.20E+00 1.09E+01 1.86E+01 2.09E+01 MW-55-54 MW-55-54 006 47

-28.8 4/25/2008 10:35 5.96E+03 3.39E+02 1.44E+02 2.67E+01 1.62E+00 6.56E-01 1.74E+00 2.35E+00 4.25E+00 1.63E+00 2.59E+00 4.75E+00 7.69E+00 1.25E+01 2.13E+01 MW-55-54 MW-55-54 007 47

-28.8 8/1/2008 10:38 6.31E+03 3.59E+02 1.91E+02 2.32E+01 1.30E+00 3.56E-01 6.53E-01 2.07E+00 3.52E+00 1.29E+00 1.79E+00 3.30E+00 1.82E+01 1.26E+01 2.08E+01 MW-55-54 MW-55-54 008 47

-28.8 10/21/2008 10:21 7.76E+03 6.65E+02 1.96E+02 1.94E+01 2.37E+00 6.25E-01

-3.17E+00 5.29E+00 5.27E+00

-1.63E+00 5.43E+00 5.54E+00

-9.99E+00 1.69E+01 2.01E+01 MW-55-54 MW-55-54 009 47

-28.8 2/4/2009 12:42 7.33E+03 9.09E+02 3.82E+02 2.11E+01 2.01E+00 3.69E-01

-3.34E-01 3.11E+00 3.46E+00

-3.64E-01 3.35E+00 3.69E+00 5.24E+00 2.34E+01 2.70E+01 MW-55-54 MW-55-54 010 47

-28.8 4/29/2009 10:55 7.00E+03 5.76E+02 1.80E+02 3.27E+01 2.55E+00 6.48E-01 3.95E-01 6.93E+00 4.62E+00

-1.58E+00 4.23E+00 4.33E+00 2.56E+00 1.79E+01 2.04E+01 MW-55-54 MW-55-54 011 47

-28.8 8/5/2009 13:25 5.47E+03 5.45E+02 2.35E+02 2.85E+01 2.43E+00 6.15E-01

-1.05E-01 2.76E+00 3.04E+00

-1.85E+00 3.19E+00 3.17E+00 8.36E+00 2.34E+01 2.65E+01 MW-55-54 MW-55-54 012 47

-28.8 11/2/2009 12:33 5.82E+03 3.65E+02 1.87E+02 2.33E+01 2.12E+00 4.76E-01 1.23E+00 5.73E+00 6.54E+00 2.82E+00 6.20E+00 7.55E+00

-2.77E+00 1.91E+01 2.20E+01 MW-55-54 MW-55-54 013 47

-28.8 2/18/2010 14:05 8.23E+03 4.13E+02 1.74E+02 1.67E+01 2.22E+00 7.61E-01

-1.16E+00 3.60E+00 3.94E+00 6.65E-01 4.04E+00 4.57E+00

-1.58E+01 1.80E+01 2.15E+01 MW-55-54 MW-55-54 014 47

-28.8 4/21/2010 13:56 1.13E+04 9.27E+02 3.88E+02 2.32E+01 2.31E+00 8.38E-01

-5.23E+00 1.21E+01 1.49E+01

-4.30E+00 1.11E+01 1.10E+01

-3.67E+00 1.79E+01 2.09E+01 MW-55-54 MW-55-54 015 47

-28.8 8/6/2010 12:50 9.74E+03 5.22E+02 1.28E+02 1.93E+01 1.88E+00 3.96E-01

-1.51E+00 7.77E+00 8.26E+00 1.82E+00 7.26E+00 8.71E+00

-1.77E-01 1.41E+01 1.65E+01 MW-55-54 MW-55-54 016 47

-28.8 11/1/2010 13:36 8.68E+03 3.95E+02 1.57E+02 1.93E+01 1.72E+00 6.48E-01

-3.03E+00 7.29E+00 7.24E+00 9.59E-01 7.50E+00 8.63E+00 1.12E-01 1.77E+01 2.04E+01 MW-55-54 MW-55-54 017 47

-28.8 2/3/2011 14:17 8.46E+03 8.58E+02 3.89E+02 1.91E+01 3.78E+00 1.95E+00 3.62E+00 5.80E+00 7.00E+00

-6.59E-01 7.44E+00 7.93E+00

-8.13E+00 1.78E+01 2.14E+01 MW-55-54 MW-55-54 018 47

-28.8 8/12/2011 12:09 8.53E+03 9.24E+02 2.00E+02 2.20E+01 3.36E+00 1.17E+00 7.03E+00 8.73E+00 1.08E+01

-2.52E+00 8.07E+00 7.92E+00

-2.57E+00 1.96E+01 2.27E+01 MW-55-54 MW-55-54 019 47

-28.8 11/14/2011 11:07 5.97E+03 8.25E+02 4.67E+02 1.75E+01 3.57E+00 1.46E+00

-2.66E+00 8.67E+00 1.04E+01 3.60E+00 6.69E+00 1.03E+01 1.62E+00 1.92E+01 2.17E+01 MW-55-54 MW-56-53 001 52 18.3 1/4/2007 9:39 7.80E+02 5.40E+02 5.10E+02

-9.00E-02 7.80E-01 8.80E-01 1.36E+01 4.80E+00 4.20E+00 2.00E+00 3.60E+00 3.80E+00

-3.70E+00 6.60E+00 7.80E+00 MW-56-53 MW-56-53 002 52 18.3 6/26/2007 10:51 2.89E+02 1.70E+02 1.82E+02

-4.49E-02 5.50E-01 6.66E-01

-5.30E-01 4.46E+00 4.11E+00 2.93E+00 4.88E+00 4.84E+00 1.30E+00 1.41E+01 1.62E+01 MW-56-53 MW-56-53 003 52 18.3 8/10/2007 12:25 2.16E+02 1.86E+02 2.03E+02

-5.66E-01 6.10E-01 9.04E-01 8.31E-01 2.79E+00 3.21E+00 3.99E-02 2.56E+00 2.85E+00 NA NA NA MW-56-53 MW-56-53 004 52 18.3 1/31/2008 12:30 2.63E+02 1.27E+02 1.31E+02 5.70E-01 8.81E-01 9.77E-01 3.38E-01 3.69E+00 3.87E+00 5.97E-01 3.48E+00 3.99E+00 1.74E+00 1.55E+01 1.80E+01 MW-56-53 MW-56-53 005 52 18.3 10/24/2008 12:21 3.99E+02 1.64E+02 1.65E+02 5.40E-01 5.47E-01 5.45E-01

-7.92E-02 5.88E+00 6.64E+00

-5.42E+00 7.44E+00 6.23E+00 NA NA NA MW-56-53 MW-56-53 006 52 18.3 4/16/2009 11:43 5.00E+02 1.95E+02 1.96E+02

-8.46E-02 6.21E-01 7.53E-01 6.63E-01 6.14E+00 4.09E+00 2.86E+00 3.41E+00 4.34E+00 NA NA NA MW-56-53 MW-56-53 007 52 18.3 11/4/2009 14:09 6.86E+02 1.38E+02 1.03E+02 2.94E-01 6.00E-01 6.81E-01 5.47E-01 6.74E+00 7.50E+00 2.77E+00 6.21E+00 7.63E+00 NA NA NA MW-56-53 MW-56-53 008 52 18.3 4/20/2010 15:23 2.58E+02 1.65E+02 1.75E+02

-1.49E-01 5.35E-01 7.58E-01 3.61E+00 7.63E+00 9.44E+00

-1.55E+00 8.91E+00 9.68E+00 NA NA NA MW-56-53 MW-56-53 009 52 18.3 11/15/2010 12:48 4.64E+02 1.88E+02 3.82E+02 1.27E+00 8.67E-01 1.86E+00 3.71E+00 4.39E+00 1.06E+01

-1.74E+00 4.89E+00 9.96E+00 NA NA NA MW-56-53 MW-56-53 010 52 18.3 4/27/2011 12:08 1.18E+02 3.48E+02 3.97E+02

-3.07E-02 1.23E+00 1.60E+00 3.04E+00 8.50E+00 1.01E+01

-1.64E+00 8.42E+00 8.44E+00 NA NA NA MW-56-53 MW-56-53 011 52 18.3 7/6/2011 12:58 2.03E+02 2.75E+02 2.83E+02

-3.68E-01 7.89E-01 1.12E+00 3.72E+00 7.77E+00 9.45E+00

-4.34E+00 8.82E+00 9.56E+00

-4.67E+00 2.28E+01 2.56E+01 MW-56-53 MW-56-53 012 52 18.3 8/26/2011 11:06 2.47E+02 3.96E+02 4.32E+02

-6.50E-01 7.17E-01 1.13E+00 1.31E+00 8.97E+00 1.00E+01 2.45E+00 7.50E+00 9.03E+00 NA NA NA MW-56-53 MW-56-53 013 52 18.3 10/31/2011 12:13 6.15E+01 4.41E+02 5.09E+02 5.82E-02 1.09E+00 1.39E+00 4.08E+00 9.36E+00 1.24E+01 4.41E+00 8.22E+00 1.26E+01 4.96E+00 1.94E+01 2.17E+01 MW-56-53 MW-56-83 001 74

-3.7 9/8/2006 11:15 5.40E+02 1.62E+02 1.26E+02 2.70E+00 1.12E+00 9.59E-01 1.82E+00 6.51E+00 8.45E+00

-2.15E-01 5.23E+00 6.87E+00 NA NA NA MW-56-83 MW-56-83 002 74

-3.7 11/9/2006 10:20 1.65E+02 1.35E+02 1.40E+02 7.00E-02 7.20E-01 8.10E-01 7.70E-01 2.70E+00 3.10E+00

-2.20E-01 2.91E+00 3.50E+00 3.30E+00 5.40E+00 5.80E+00 MW-56-83 MW-56-83 003 74

-3.7 1/4/2007 13:20 1.28E+03 5.70E+02 5.20E+02 2.30E+00 9.00E-01 8.90E-01 1.18E+01 4.80E+00 4.40E+00 1.00E-01 3.00E+00 3.60E+00

-7.00E-01 7.80E+00 8.80E+00 MW-56-83 MW-56-83 004 74

-3.7 6/22/2007 10:44 1.85E+03 5.76E+02 4.30E+02 1.87E+00 1.15E+00 1.09E+00 1.47E-01 3.39E+00 3.85E+00

-1.87E+00 2.82E+00 2.46E+00 3.95E+00 1.27E+01 1.46E+01 MW-56-83 MW-56-83 005 74

-3.7 8/10/2007 11:10 1.49E+03 5.52E+02 4.55E+02 2.43E+00 1.05E+00 9.23E-01

-9.15E-01 3.86E+00 4.02E+00 1.87E-01 2.75E+00 3.15E+00 NA NA NA MW-56-83 MW-56-83 006 74

-3.7 1/31/2008 9:30 1.94E+03 1.97E+02 1.34E+02 3.56E+00 1.34E+00 9.49E-01

-8.03E-01 3.69E+00 3.23E+00 1.60E+00 2.78E+00 3.51E+00 6.57E-01 1.59E+01 1.85E+01 MW-56-83 MW-56-83 007 74

-3.7 10/24/2008 12:22 2.98E+03 7.91E+02 5.91E+02 2.13E+00 7.32E-01 4.94E-01

-1.15E+00 4.62E+00 4.98E+00 3.29E+00 5.58E+00 8.07E+00 NA NA NA MW-56-83 MW-56-83 008 74

-3.7 4/16/2009 11:49 3.24E+03 7.61E+02 4.34E+02 2.71E+00 7.59E-01 4.21E-01 6.03E-03 5.39E+00 3.59E+00 1.38E+00 4.11E+00 4.92E+00 NA NA NA MW-56-83 MW-56-83 009 74

-3.7 11/4/2009 15:47 3.15E+03 2.46E+02 1.02E+02 2.78E+00 8.12E-01 4.70E-01 2.01E+00 5.22E+00 6.13E+00

-1.15E+00 5.96E+00 6.35E+00 NA NA NA MW-56-83 MW-56-83 010 74

-3.7 4/20/2010 14:51 1.93E+03 2.96E+02 1.48E+02 1.99E+00 1.05E+00 8.74E-01 2.04E+00 8.03E+00 9.48E+00

-1.05E+00 8.71E+00 9.04E+00 NA NA NA MW-56-83 MW-56-83 011 74

-3.7 11/15/2010 14:37 2.74E+03 2.63E+02 3.84E+02 1.02E+00 7.08E-01 1.50E+00

-2.51E+00 3.87E+00 7.83E+00

-2.67E+00 3.90E+00 7.34E+00 NA NA NA MW-56-83 MW-56-83 012 74

-3.7 4/27/2011 13:46 7.64E+04 2.40E+03 4.19E+02 3.87E+00 1.60E+00 1.28E+00

-1.05E+00 1.14E+01 1.33E+01

-1.27E+00 9.50E+00 1.01E+01 NA NA NA MW-56-83 MW-56-83 013 74

-3.7 7/6/2011 11:58 8.42E+04 3.54E+03 2.81E+02 1.45E+00 1.27E+00 1.19E+00 2.77E+00 2.01E+01 9.44E+00 4.20E-01 8.16E+00 9.20E+00

-1.36E+01 2.15E+01 2.46E+01 MW-56-83 MW-56-83 014 74

-3.7 8/26/2011 10:56 1.05E+05 3.12E+03 4.42E+02 3.12E+00 1.61E+00 1.37E+00

-2.12E+00 8.13E+00 8.21E+00

-6.41E-01 8.67E+00 9.15E+00 NA NA NA MW-56-83 MW-56-83 015 74

-3.7 10/31/2011 12:00 7.25E+04 2.80E+03 5.11E+02 9.41E-01 1.49E+00 1.61E+00 2.19E+00 7.29E+00 9.56E+00 2.43E+00 8.94E+00 1.22E+01

-3.01E+00 2.14E+01 2.44E+01 MW-56-83 MW-57-11 001 10 5

6/22/2007 12:17 4.61E+03 8.10E+02 4.36E+02 4.55E+01 3.96E+00 7.97E-01 2.29E+00 6.04E+00 4.31E+00 3.69E-02 3.87E+00 4.37E+00 2.24E+01 1.79E+01 1.91E+01 MW-57-11 MW-57-11 002 10 5

8/6/2007 12:30 4.09E+03 3.21E+06 1.97E+02 3.79E+01 2.77E+00 5.36E-01 1.15E+00 3.78E+00 4.16E+00 3.95E-03 3.01E+00 3.41E+00

-5.75E-01 2.16E+01 2.50E+01 MW-57-11

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 22 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-57-11 003 10 5

5/5/2008 12:43 2.17E+03 2.29E+02 2.65E+02 2.27E+01 1.95E+00 9.08E-01 8.71E-01 2.21E+00 3.83E+00 2.87E+00 2.26E+00 4.47E+00

-1.12E+00 1.35E+01 2.34E+01 MW-57-11 MW-57-11 004 10 5

11/12/2008 10:55 3.28E+03 2.76E+02 1.73E+02 4.16E+01 3.39E+00 7.64E-01 3.34E+00 7.25E+00 4.76E+00 1.81E+00 3.78E+00 5.03E+00

-5.18E-01 2.03E+01 2.35E+01 MW-57-11 MW-57-11 005 10 5

4/21/2009 12:08 4.22E+03 4.29E+02 1.90E+02 4.72E+01 2.97E+00 5.57E-01 3.89E+00 6.71E+00 4.47E+00 1.11E+00 2.76E+00 3.35E+00 4.47E+00 1.98E+01 2.25E+01 MW-57-11 MW-57-11 006 10 5

5/4/2010 12:36 3.27E+03 3.48E+02 1.72E+02 2.46E+01 3.00E+00 8.46E-01 8.07E-01 6.20E+00 6.51E+00 1.85E-01 5.09E+00 5.67E+00

-1.79E+01 2.21E+01 2.56E+01 MW-57-11 MW-57-11 007 10 5

5/4/2011 10:28 6.40E+03 6.84E+02 3.41E+02 3.11E+01 3.62E+00 1.04E+00 3.74E+00 8.32E+00 9.74E+00 2.05E+00 8.40E+00 9.72E+00 6.20E+00 1.66E+01 1.85E+01 MW-57-11 MW-57-11 008 10 5

7/18/2011 11:57 7.36E+03 9.18E+02 4.45E+02 3.87E+01 5.28E+00 2.11E+00 3.27E-01 8.88E+00 9.84E+00

-2.34E+00 9.18E+00 9.39E+00

-6.76E+00 1.48E+01 1.67E+01 MW-57-11 MW-57-11 009 10 5

8/19/2011 9:49 7.27E+03 8.58E+02 2.02E+02 2.08E+01 3.21E+00 1.24E+00 4.49E+00 7.50E+00 9.07E+00 2.31E+00 7.74E+00 9.17E+00 4.92E-01 2.06E+01 2.36E+01 MW-57-11 MW-57-20 001 19

-4 6/22/2007 12:30 1.65E+03 5.58E+02 4.32E+02 1.96E+00 1.07E+00 9.67E-01

-1.33E+00 3.69E+00 3.90E+00

-9.51E-01 3.65E+00 3.84E+00 4.77E-01 1.36E+01 1.59E+01 MW-57-20 MW-57-20 002 19

-4 8/6/2007 12:15 9.96E+02 2.15E+02 1.96E+02 1.23E+00 6.67E-01 5.78E-01 1.21E+00 3.59E+00 3.64E+00 6.05E-01 2.75E+00 3.22E+00

-1.19E+01 2.06E+01 2.46E+01 MW-57-20 MW-57-20 003 19

-4 5/5/2008 13:18 7.27E+02 1.45E+02 1.97E+02 1.23E+00 2.16E-01 2.85E-01

-2.17E+00 1.99E+00 2.84E+00

-9.61E-01 3.60E+00 4.56E+00

-6.89E+00 9.27E+00 1.62E+01 MW-57-20 MW-57-20 004 19

-4 11/12/2008 11:30 1.51E+03 2.16E+02 1.72E+02 3.06E+00 1.30E+00 1.14E+00

-1.91E+00 3.94E+00 3.82E+00

-4.35E-01 3.52E+00 3.67E+00

-5.58E-01 1.94E+01 2.25E+01 MW-57-20 MW-57-20 005 19

-4 4/21/2009 12:22 1.52E+03 2.87E+02 1.90E+02 2.77E+00 1.02E+00 8.57E-01

-2.08E+00 5.76E+00 3.84E+00 2.32E+00 3.15E+00 4.06E+00 1.34E+01 2.16E+01 2.41E+01 MW-57-20 MW-57-20 006 19

-4 5/4/2010 12:45 8.07E+02 2.04E+02 1.61E+02 1.12E+00 9.05E-01 8.77E-01

-2.11E+00 7.95E+00 8.24E+00

-2.23E-01 7.54E+00 8.56E+00

-6.07E+00 2.19E+01 2.51E+01 MW-57-20 MW-57-20 007 19

-4 5/4/2011 10:37 2.03E+04 1.15E+03 3.44E+02 1.74E+00 1.11E+00 9.49E-01 1.48E+00 7.52E+00 8.43E+00

-7.32E-01 9.22E+00 1.02E+01

-5.44E+00 1.64E+01 1.91E+01 MW-57-20 MW-57-20 008 19

-4 7/18/2011 12:09 3.81E+04 1.94E+03 4.43E+02 1.27E+00 1.08E+00 1.01E+00

-5.13E+00 7.71E+00 7.35E+00 9.16E-01 8.67E+00 9.92E+00

-5.69E+00 1.93E+01 2.20E+01 MW-57-20 MW-57-20 009 19

-4 8/19/2011 9:54 2.47E+04 1.55E+03 1.98E+02 1.90E+00 1.68E+00 1.56E+00

-2.01E+00 7.35E+00 7.66E+00 1.68E+00 8.07E+00 9.48E+00 3.14E+00 1.98E+01 2.25E+01 MW-57-20 MW-57-45 001 40

-25 8/24/2006 9:30 4.00E+03 6.98E+02 3.17E+02 1.88E+01 3.51E+00 2.11E+00

-5.40E-01 6.75E+00 7.36E+00 1.19E+00 6.35E+00 7.50E+00 8.29E+00 9.09E+00 9.70E+00 MW-57-45 MW-57-45 001 40

-25 8/24/2006 9:30 4.06E+03 8.82E+02 7.71E+02 NA NA NA

-2.85E-01 4.41E+00 4.80E+00

-1.81E-01 3.89E+00 4.37E+00 NA NA NA MW-57-45 MW-57-45 002 40

-25 6/22/2007 12:55 9.55E+02 4.85E+02 4.35E+02 1.90E+00 1.05E+00 8.65E-01

-1.97E-01 3.40E+00 3.82E+00

-8.51E-01 3.50E+00 3.65E+00 6.46E-01 1.23E+01 1.43E+01 MW-57-45 MW-57-45 003 40

-25 8/6/2007 12:17 7.40E+02 2.07E+02 1.98E+02 2.55E+00 8.77E-01 6.09E-01

-3.91E-01 3.15E+00 3.42E+00

-1.89E-01 3.59E+00 3.35E+00

-1.15E+01 2.09E+01 2.49E+01 MW-57-45 MW-57-45 004 40

-25 5/5/2008 14:59 5.65E+02 1.38E+02 1.97E+02 2.26E+00 2.91E-01 3.68E-01

-1.35E-01 1.68E+00 2.84E+00

-4.61E-01 1.66E+00 2.69E+00

-3.60E+00 9.38E+00 1.62E+01 MW-57-45 MW-57-45 005 40

-25 11/12/2008 13:22 1.13E+03 2.01E+02 1.73E+02 1.20E+00 6.79E-01 5.97E-01 1.72E-01 3.63E+00 4.05E+00 9.15E-01 4.42E+00 5.17E+00

-2.81E+00 1.91E+01 2.22E+01 MW-57-45 MW-57-45 006 40

-25 4/21/2009 13:34 1.19E+03 2.64E+02 1.90E+02 2.25E+00 8.36E-01 6.44E-01 1.80E-01 5.64E+00 3.76E+00

-1.30E+00 3.95E+00 4.12E+00 8.26E+00 2.09E+01 2.35E+01 MW-57-45 MW-57-45 007 40

-25 5/4/2010 13:24 8.79E+02 2.19E+02 1.72E+02 1.30E+00 9.43E-01 8.65E-01 6.16E-02 5.31E+00 5.86E+00

-2.99E-01 4.77E+00 5.16E+00 7.57E-01 2.26E+01 2.58E+01 MW-57-45 MW-57-45 008 40

-25 5/4/2011 11:03 1.35E+04 9.48E+02 3.43E+02 9.06E-01 9.74E-01 9.60E-01 7.40E+00 9.54E+00 1.21E+01

-1.84E+00 9.48E+00 9.59E+00 6.39E+00 1.78E+01 1.98E+01 MW-57-45 MW-57-45 009 40

-25 7/18/2011 12:36 2.53E+04 1.60E+03 4.47E+02 1.28E+00 1.32E+00 1.34E+00

-2.08E-01 8.16E+00 8.83E+00

-7.58E-01 9.39E+00 9.67E+00

-1.04E+01 1.53E+01 1.74E+01 MW-57-45 MW-57-45 010 40

-25 8/19/2011 10:19 2.46E+04 1.56E+03 2.02E+02 4.31E-01 1.01E+00 1.15E+00

-5.69E+00 1.03E+01 1.04E+01 2.03E+00 8.04E+00 9.53E+00 2.27E+00 2.09E+01 2.38E+01 MW-57-45 MW-58-26 001 20

-5.4 11/16/2006 13:25

-2.60E+01 1.59E+02 1.60E+02 3.70E-01 7.50E-01 8.20E-01 7.27E+01 8.40E+00 4.50E+00

-9.00E-01 3.30E+00 4.30E+00

-3.20E+00 5.70E+00 6.40E+00 MW-58-26 MW-58-26 002 20

-5.4 1/5/2007 8:57 2.60E+02 1.80E+02 1.80E+02

-8.00E-02 7.50E-01 8.50E-01 2.34E+00 2.97E+00 3.20E+00 9.50E-01 2.73E+00 3.10E+00

-3.90E+00 6.30E+00 7.40E+00 MW-58-26 MW-58-26 003 20

-5.4 6/21/2007 11:10 5.97E+02 2.00E+02 1.86E+02 1.04E+00 6.09E-01 5.25E-01 1.62E+00 2.42E+00 2.86E+00

-3.94E-01 2.42E+00 2.60E+00 1.07E+00 1.24E+01 1.45E+01 MW-58-26 MW-58-26 004 20

-5.4 7/31/2007 11:00 8.56E+02 3.99E+02 2.58E+02 1.02E+00 6.33E-01 5.78E-01 1.18E+00 3.31E+00 3.83E+00 4.20E-01 3.01E+00 3.51E+00 NA NA NA MW-58-26 MW-58-26 005 20

-5.4 1/22/2008 13:20 2.95E+02 1.62E+02 1.70E+02

-1.43E-01 4.65E-01 6.60E-01 9.19E-01 2.31E+00 2.67E+00

-5.41E-02 2.57E+00 2.61E+00 NA NA NA MW-58-26 MW-58-26 006 20

-5.4 11/7/2008 13:39 2.38E+02 1.55E+02 1.63E+02 2.31E-01 6.60E-01 7.90E-01

-3.38E+00 6.24E+00 5.49E+00

-3.23E-01 4.58E+00 4.84E+00 NA NA NA MW-58-26 MW-58-26 007 20

-5.4 2/3/2009 12:49 5.19E+02 2.36E+02 1.98E+02

-8.35E-03 5.27E-01 6.83E-01 1.40E+00 2.76E+00 3.29E+00 1.45E-01 3.09E+00 3.31E+00 NA NA NA MW-58-26 MW-58-26 008 20

-5.4 4/24/2009 12:21 4.13E+02 1.48E+02 1.47E+02

-5.74E-02 4.53E-01 5.97E-01 1.26E+00 4.28E+00 2.85E+00 1.02E-01 2.31E+00 2.57E+00 NA NA NA MW-58-26 MW-58-26 009 20

-5.4 10/23/2009 13:10 4.23E+02 1.67E+02 1.68E+02 4.74E-01 6.36E-01 6.95E-01 1.68E+00 5.05E+00 5.98E+00 2.49E+00 5.68E+00 6.94E+00 NA NA NA MW-58-26 MW-58-26 010 20

-5.4 4/30/2010 14:12 5.75E+02 1.80E+02 1.82E+02 2.92E-01 5.47E-01 6.20E-01 4.25E-01 5.59E+00 6.27E+00 9.40E-01 5.75E+00 6.68E+00 NA NA NA MW-58-26 MW-58-26 011 20

-5.4 11/11/2010 15:12 3.66E+02 1.73E+02 1.44E+02 4.13E-01 7.89E-01 8.92E-01 1.98E+00 3.81E+00 4.51E+00 2.98E+00 3.75E+00 4.70E+00 NA NA NA MW-58-26 MW-58-26 012 20

-5.4 5/3/2011 9:58 7.22E+02 4.30E+02 4.21E+02 3.15E-01 1.13E+00 1.32E+00 2.29E+00 5.80E+00 6.89E+00

-6.42E+00 9.02E+00 8.00E+00 NA NA NA MW-58-26 MW-58-26 013 20

-5.4 7/5/2011 13:29 1.86E+03 5.46E+02 4.47E+02

-3.25E-01 1.10E+00 1.41E+00 7.41E-01 6.84E+00 7.61E+00 1.22E+00 7.32E+00 8.39E+00

-1.01E+01 1.99E+01 2.25E+01 MW-58-26 MW-58-26 014 20

-5.4 8/26/2011 14:47 2.47E+03 5.10E+02 1.99E+02

-6.17E-02 7.95E-01 1.05E+00 2.39E-01 7.65E+00 8.47E+00 3.25E-01 8.22E+00 9.22E+00 NA NA NA MW-58-26 MW-58-26 015 20

-5.4 11/15/2011 14:22 4.77E+03 7.29E+02 2.31E+02

-4.32E-01 8.28E-01 1.25E+00 1.04E+00 1.99E+01 8.90E+00 2.18E+00 9.42E+00 1.24E+01

-3.05E+00 1.22E+01 1.39E+01 MW-58-26 MW-58-65 001 54

-39.4 11/16/2006 13:18

-9.60E+01 1.59E+02 1.60E+02

-6.00E-02 7.20E-01 8.10E-01 2.20E+00 3.00E+00 3.30E+00

-9.00E-01 4.20E+00 4.90E+00

-3.40E+00 6.90E+00 7.80E+00 MW-58-65 MW-58-65 002 54

-39.4 1/5/2007 9:25 5.50E+02 5.40E+02 5.20E+02 1.60E-01 8.10E-01 8.80E-01

-1.95E+00 2.52E+00 3.00E+00

-1.30E-01 2.73E+00 3.20E+00

-1.40E+00 7.80E+00 8.70E+00 MW-58-65 MW-58-65 003 54

-39.4 6/21/2007 11:10 3.15E+02 1.77E+02 1.81E+02

-1.90E-01 3.96E-01 5.60E-01

-2.19E-01 2.37E+00 2.65E+00

-2.89E+00 3.17E+00 2.36E+00 2.80E+00 1.26E+01 1.45E+01 MW-58-65 MW-58-65 004 54

-39.4 7/31/2007 11:00 3.42E+02 3.02E+02 2.72E+02 6.20E-03 5.19E-01 6.52E-01 2.18E+00 3.39E+00 3.37E+00 1.02E+00 3.24E+00 3.39E+00 NA NA NA MW-58-65 MW-58-65 005 54

-39.4 1/22/2008 12:00 3.13E+02 1.62E+02 1.69E+02 1.21E-01 5.85E-01 7.22E-01 5.54E-01 3.93E+00 3.92E+00

-1.23E-01 3.29E+00 3.05E+00 NA NA NA MW-58-65 MW-58-65 006 54

-39.4 11/7/2008 13:55 2.81E+02 1.55E+02 1.62E+02 8.19E-01 8.77E-01 8.82E-01 9.13E-02 3.38E+00 3.86E+00

-1.58E+00 3.21E+00 2.98E+00 NA NA NA MW-58-65 MW-58-65 007 54

-39.4 2/3/2009 12:05 2.75E+02 2.03E+02 1.98E+02 6.60E-01 8.00E-01 8.56E-01

-8.45E-01 3.21E+00 3.41E+00 1.91E+00 3.09E+00 3.89E+00 NA NA NA MW-58-65 MW-58-65 008 54

-39.4 4/24/2009 11:52 2.33E+02 1.67E+02 1.78E+02

-2.36E-01 4.62E-01 6.58E-01 9.67E-02 3.86E+00 2.57E+00

-1.84E-01 2.46E+00 2.72E+00 NA NA NA MW-58-65 MW-58-65 009 54

-39.4 10/23/2009 12:53 2.37E+02 1.56E+02 1.65E+02 6.33E-01 6.12E-01 6.29E-01 7.13E-01 5.70E+00 6.42E+00 2.46E+00 5.97E+00 7.18E+00 NA NA NA MW-58-65 MW-58-65 010 54

-39.4 4/30/2010 13:51 3.59E+02 1.64E+02 1.72E+02 7.38E-02 5.17E-01 6.40E-01 1.50E+00 8.09E+00 9.07E+00 3.34E-01 5.75E+00 6.60E+00 NA NA NA MW-58-65 MW-58-65 011 54

-39.4 11/11/2010 13:53 4.81E+02 1.88E+02 1.45E+02 7.15E-01 7.72E-01 8.31E-01 2.61E-01 3.71E+00 4.18E+00 3.74E+00 4.41E+00 5.49E+00 NA NA NA MW-58-65 MW-58-65 012 54

-39.4 5/3/2011 10:11 3.29E+02 3.78E+02 3.97E+02

-4.47E-01 1.03E+00 1.44E+00 1.93E+00 5.92E+00 7.00E+00

-7.81E-01 7.04E+00 7.26E+00 NA NA NA MW-58-65 MW-58-65 013 54

-39.4 7/5/2011 13:30 7.26E+02 3.93E+02 2.83E+02 4.19E-01 9.12E-01 1.03E+00 5.29E+00 1.05E+01 1.25E+01 1.47E+00 7.53E+00 8.78E+00 3.44E-01 2.03E+01 2.27E+01 MW-58-65 MW-58-65 014 54

-39.4 8/26/2011 14:04 1.10E+03 4.62E+02 2.61E+02 6.31E-01***

1.82E+00 1.60E+00

-1.06E+00 9.00E+00 9.65E+00

-1.54E+00 1.01E+01 1.04E+01 NA NA NA MW-58-65 MW-58-65 015 54

-39.4 11/15/2011 14:05 1.75E+03 4.32E+02 3.42E+02 3.02E-01 1.71E+00 2.03E+00

-1.89E+00 8.82E+00 9.54E+00

-7.70E-01 7.23E+00 8.96E+00 NA NA NA MW-58-65 MW-59-32 001 27

-12.5 11/16/2006 11:05 2.80E+01 1.77E+02 1.80E+02

-6.00E-02 7.20E-01 7.90E-01 8.60E-01 2.91E+00 3.30E+00 3.00E-01 4.20E+00 4.90E+00

-2.60E+00 6.60E+00 7.50E+00 MW-59-32 MW-59-32 002 27

-12.5 1/5/2007 9:41 1.35E+02 1.77E+02 1.80E+02 3.00E-01 7.50E-01 8.20E-01 1.50E+00 3.60E+00 4.10E+00 1.30E+00 3.90E+00 4.40E+00

-1.90E+00 6.90E+00 8.10E+00 MW-59-32 MW-59-32 003 27

-12.5 6/21/2007 15:25 4.67E+02 4.23E+02 4.36E+02

-6.68E-02 6.78E-01 9.11E-01 6.01E-01 3.96E+00 4.59E+00

-4.19E-01 4.46E+00 4.71E+00

-4.37E-01 1.24E+01 1.45E+01 MW-59-32 MW-59-32 004 27

-12.5 7/31/2007 14:35 1.69E+02 1.59E+02 1.63E+02 2.00E-01 6.72E-01 7.96E-01 2.26E-01 3.30E+00 3.73E+00 7.97E-01 3.19E+00 3.75E+00 NA NA NA MW-59-32 MW-59-32 005 27

-12.5 7/20/2011 9:59 1.56E+02 3.90E+02 4.38E+02 5.88E-01 1.14E+00 1.27E+00

-1.79E+00 7.92E+00 8.02E+00

-2.58E+00 9.78E+00 1.02E+01

-1.40E+01 1.82E+01 2.07E+01 MW-59-32 MW-59-32 006 27

-12.5 8/24/2011 14:22 4.74E+02 2.72E+02 2.17E+02 7.95E-01 1.13E+00 1.20E+00

-2.52E+00 1.05E+01 1.13E+01 2.65E+00 8.25E+00 9.93E+00

-6.65E+00 2.16E+01 2.54E+01 MW-59-32 MW-59-45 001 42

-27.5 11/16/2006 11:18 5.50E+01 1.74E+02 1.70E+02 2.40E-01 7.20E-01 8.00E-01 3.74E+01 8.70E+00 6.20E+00 2.60E+00 4.20E+00 4.50E+00

-1.60E+00 5.70E+00 6.60E+00 MW-59-45 MW-59-45 002 42

-27.5 1/5/2007 9:48 8.80E+01 1.80E+02 1.80E+02 0.00E+00 7.80E-01 8.70E-01 1.49E+02 1.26E+01 4.90E+00 2.00E-01 3.90E+00 4.60E+00

-2.50E+00 7.50E+00 8.60E+00 MW-59-45 MW-59-45 003 42

-27.5 6/21/2007 15:25 7.54E+02 4.59E+02 4.34E+02

-2.74E-01 6.86E-01 9.10E-01

-1.10E-01 2.50E+00 2.83E+00 8.14E-02 2.16E+00 2.49E+00 7.74E-01 1.47E+01 1.71E+01 MW-59-45 MW-59-45 004 42

-27.5 7/31/2007 13:58 2.49E+02 1.74E+02 1.65E+02 1.64E-01 5.90E-01 7.05E-01 4.48E-01 3.52E+00 3.70E+00 7.64E-01 3.35E+00 3.94E+00 NA NA NA MW-59-45 MW-59-45 005 42

-27.5 7/20/2011 9:59 5.24E+02 4.35E+02 4.43E+02

-1.01E+00 1.05E+00 1.49E+00 1.81E+00 8.52E+00 9.88E+00 2.79E+00 9.48E+00 1.15E+01

-1.12E+01 1.83E+01 2.08E+01 MW-59-45 MW-59-45 006 42

-27.5 8/24/2011 14:32 1.24E+03 4.92E+02 2.64E+02 1.13E-01 1.11E+00 1.33E+00

-1.32E+00 8.37E+00 8.81E+00 4.22E+00 9.42E+00 1.18E+01 1.31E+00 1.07E+01 1.20E+01 MW-59-45 MW-59-68 001 58

-43.5 11/16/2006 11:30 5.50E+01 1.74E+02 1.80E+02 1.20E-01 7.20E-01 8.10E-01 1.15E+02 1.11E+01 5.60E+00 1.00E+00 3.00E+00 3.60E+00

-2.30E+00 5.70E+00 6.40E+00 MW-59-68 MW-59-68 002 58

-43.5 1/5/2007 10:05 1.56E+02 1.83E+02 1.80E+02 3.30E-01 8.10E-01 8.90E-01 6.76E+01 6.60E+00 4.10E+00

-8.00E-01 3.60E+00 4.10E+00 1.90E+00 7.50E+00 8.40E+00 MW-59-68 MW-59-68 003 58

-43.5 6/21/2007 15:25 5.90E+02 4.41E+02 4.39E+02 2.97E-01 8.79E-01 1.03E+00 6.26E-01 3.50E+00 3.80E+00 1.27E+00 2.91E+00 3.62E+00

-4.23E+00 1.30E+01 1.56E+01 MW-59-68 MW-59-68 004 58

-43.5 7/31/2007 13:58 8.19E+02 4.02E+02 2.68E+02 3.66E-01 7.08E-01 7.98E-01 9.02E-01 2.88E+00 2.95E+00 3.72E-01 2.77E+00 3.17E+00 NA NA NA MW-59-68 MW-59-68 005 58

-43.5 7/20/2011 10:14 1.15E+02 3.90E+02 4.42E+02 1.10E-01 7.26E-01 9.01E-01 2.83E+00 9.33E+00 1.09E+01 8.22E-01 9.87E+00 1.06E+01

-1.57E+01 2.17E+01 2.47E+01 MW-59-68 MW-59-68 006 58

-43.5 8/24/2011 14:09 2.61E+02 2.83E+02 2.66E+02

-5.46E-01 7.35E-01 1.14E+00

-5.62E+00 8.52E+00 7.69E+00 1.56E+00 9.03E+00 1.03E+01 4.94E+00 1.28E+01 1.42E+01 MW-59-68 MW-60-35 001 34.9

-22.4 5/8/2007 13:27

-9.12E+00 1.49E+02 1.79E+02

-1.79E-01 5.28E-01 7.62E-01 1.41E+00 4.84E+00 3.30E+00 2.45E+00 3.72E+00 4.67E+00 0.00E+00 1.81E+01 2.12E+01 MW-60-35

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 23 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-60-35 002 34.9

-22.4 7/27/2007 13:07 7.61E+02 2.40E+02 1.78E+02 6.48E-02 3.80E-01 4.66E-01 5.95E-01 4.26E+00 3.23E+00

-3.31E-01 3.07E+00 3.39E+00 NA NA NA MW-60-35 MW-60-35 003 34.9

-22.4 10/9/2007 13:20 1.84E+02 1.48E+02 1.51E+02 3.01E-01 5.97E-01 6.78E-01 1.51E+00 6.06E+00 3.54E+00 0.00E+00 2.64E+00 2.61E+00 NA NA NA MW-60-35 MW-60-35 004 34.9

-22.4 1/14/2008 17:05 7.78E+01 1.58E+02 1.78E+02 5.05E-01 8.10E-01 8.98E-01 1.11E+00 3.21E+00 3.79E+00

-9.16E-01 3.36E+00 3.54E+00 NA NA NA MW-60-35 MW-60-35 005 34.9

-22.4 4/24/2008 15:30 5.51E+01 1.14E+02 1.95E+02 3.45E-01 4.83E-01 8.34E-01

-8.41E-01 2.06E+00 3.37E+00

-8.73E-01 1.68E+00 2.56E+00 NA NA NA MW-60-35 MW-60-35 006 34.9

-22.4 7/30/2008 16:10 1.95E+02 1.21E+02 1.91E+02 2.85E-01 3.50E-01 5.92E-01 1.81E+00 1.93E+00 3.50E+00

-1.19E+00 2.07E+00 3.20E+00 NA NA NA MW-60-35 MW-60-35 007 34.9

-22.4 11/5/2008 15:03 1.42E+02 1.80E+02 1.99E+02 1.62E-01 5.01E-01 6.09E-01

-2.38E+00 5.87E+00 6.17E+00

-3.83E+00 8.52E+00 7.56E+00 NA NA NA MW-60-35 MW-60-35 008 34.9

-22.4 2/9/2009 16:12 2.00E+02 1.83E+02 1.98E+02 3.81E-01 8.27E-01 9.42E-01

-1.20E+00 3.09E+00 3.19E+00

-3.23E-01 3.00E+00 3.22E+00

-3.26E+00 2.39E+01 2.82E+01 MW-60-35 MW-60-35 009 34.9

-22.4 5/5/2009 14:06 1.54E+02 1.64E+02 1.71E+02 2.06E-01 6.48E-01 7.50E-01 1.11E+00 8.76E+00 5.84E+00 7.57E-01 5.60E+00 6.58E+00 NA NA NA MW-60-35 MW-60-35 010 34.9

-22.4 8/11/2009 14:41 2.60E+02 1.49E+02 1.53E+02 3.16E-01 4.41E-01 4.71E-01 2.47E+00 5.67E+00 6.63E+00 3.46E+00 6.18E+00 7.58E+00 5.77E+00 1.79E+01 2.03E+01 MW-60-35 MW-60-35 011 34.9

-22.4 10/30/2009 15:10 2.29E+02 1.52E+02 1.61E+02 2.24E-01 6.33E-01 7.51E-01

-3.67E+00 1.00E+01 1.12E+01 4.15E+00 6.72E+00 8.44E+00 NA NA NA MW-60-35 MW-60-35 012 34.9

-22.4 3/1/2010 11:18 2.48E+02 1.64E+02 1.74E+02 5.08E-01 6.83E-01 7.32E-01

-1.38E+00 6.15E+00 5.99E+00

-1.00E+00 3.76E+00 4.07E+00

-1.11E+01 1.88E+01 2.21E+01 MW-60-35 MW-60-35 013 34.9

-22.4 5/10/2010 15:58 2.85E+02 1.46E+02 1.35E+02 2.89E-02 5.05E-01 6.56E-01

-1.78E+00 7.56E+00 8.03E+00

-1.43E+00 9.12E+00 9.76E+00 4.12E-01 2.24E+01 2.56E+01 MW-60-35 MW-60-35 014 34.9

-22.4 8/16/2010 14:43 2.35E+02 1.42E+02 1.41E+02 3.19E-01 6.48E-01 7.39E-01 3.02E-01 5.73E+00 6.47E+00

-1.36E+00 6.23E+00 6.68E+00

-4.52E+00 2.14E+01 2.52E+01 MW-60-35 MW-60-35 015 34.9

-22.4 11/18/2010 13:25 2.44E+02 1.85E+02 4.00E+02

-5.33E-01 6.54E-01 1.73E+00 9.47E-01 4.80E+00 1.08E+01

-4.28E-01 4.56E+00 9.75E+00

-1.11E+01 8.47E+00 1.92E+01 MW-60-35 MW-60-35 016 34.9

-22.4 2/11/2011 12:17 3.20E+02 3.72E+02 3.88E+02 9.73E-01 1.63E+00 1.78E+00 2.69E+00 6.24E+00 7.46E+00 1.22E-01 3.76E+00 4.24E+00

-1.61E+00 1.62E+01 1.84E+01 MW-60-35 MW-60-35 017 34.9

-22.4 4/15/2011 11:36 2.03E+02 4.32E+02 4.80E+02 3.77E-01 1.66E+00 2.00E+00 2.46E+00 1.14E+01 8.95E+00

-8.48E-01 9.58E+00 1.03E+01 2.65E+00 1.42E+01 1.61E+01 MW-60-35 MW-60-35 018 34.9

-22.4 8/10/2011 10:54 4.99E+02 2.69E+02 2.00E+02

-5.84E-01 7.74E-01 1.17E+00 2.11E+00 6.96E+00 8.28E+00

-1.04E+00 1.03E+01 1.10E+01 NA NA NA MW-60-35 MW-60-35 019 34.9

-22.4 12/2/2011 11:21 1.74E+02 3.66E+02 4.07E+02 3.94E-01 1.72E+00 1.98E+00

-8.20E-01 9.33E+00 1.15E+01 2.63E+00 7.86E+00 1.12E+01 NA NA NA MW-60-35 MW-60-53 001 53.4

-40.9 5/8/2007 11:52 5.32E+01 1.58E+02 1.82E+02

-4.92E-01 5.52E-01 8.96E-01

-2.83E+00 4.86E+00 4.07E+00 2.15E-01 3.59E+00 4.12E+00 3.58E+00 1.84E+01 2.12E+01 MW-60-53 MW-60-53 002 53.4

-40.9 7/27/2007 12:50 1.25E+02 1.71E+02 1.87E+02

-4.72E-01 5.26E-01 7.31E-01 1.46E-01 3.01E+00 3.34E+00 7.87E-01 3.25E+00 3.79E+00 NA NA NA MW-60-53 MW-60-53 003 53.4

-40.9 10/9/2007 12:22 1.13E+02 1.44E+02 1.56E+02 6.19E-01 6.50E-01 6.79E-01

-2.11E+00 3.39E+00 3.51E+00 3.62E-01 2.79E+00 3.21E+00 NA NA NA MW-60-53 MW-60-53 004 53.4

-40.9 1/14/2008 15:40 5.35E+01 1.55E+02 1.78E+02

-1.69E-01 5.28E-01 7.59E-01

-1.10E+00 2.78E+00 2.88E+00

-1.89E+00 2.94E+00 2.76E+00 NA NA NA MW-60-53 MW-60-53 005 53.4

-40.9 4/24/2008 12:18

-1.77E+01 1.12E+02 1.96E+02 5.27E-01 5.19E-01 8.52E-01

-4.84E-01 2.47E+00 4.13E+00

-1.36E+00 2.50E+00 3.95E+00 NA NA NA MW-60-53 MW-60-53 006 53.4

-40.9 7/30/2008 13:23 1.28E+02 9.80E+01 1.63E+02 6.53E-01 5.33E-01 8.58E-01

-1.68E-01 2.09E+00 3.43E+00 1.05E+00 2.04E+00 3.65E+00 NA NA NA MW-60-53 MW-60-53 007 53.4

-40.9 11/5/2008 14:32 1.38E+02 1.80E+02 1.99E+02

-1.95E-01 5.82E-01 8.17E-01 8.77E-01 4.58E+00 5.22E+00 1.30E+00 5.78E+00 6.68E+00 NA NA NA MW-60-53 MW-60-53 008 53.4

-40.9 2/9/2009 11:28 1.31E+02 1.79E+02 1.98E+02 4.81E-01 8.09E-01 9.06E-01

-1.28E+00 3.80E+00 3.55E+00 5.34E-01 2.78E+00 3.22E+00

-1.24E+00 2.43E+01 2.85E+01 MW-60-53 MW-60-53 009 53.4

-40.9 5/5/2009 10:08 4.99E+02 2.12E+02 1.75E+02 6.40E-02 6.75E-01 8.02E-01 7.73E-01 1.18E+01 7.89E+00

-3.04E+00 8.30E+00 7.85E+00 0.00E+00 2.39E+01 2.81E+01 MW-60-53 MW-60-53 010 53.4

-40.9 8/11/2009 14:26 2.03E+02 1.56E+02 1.69E+02 1.35E-01 7.18E-01 8.69E-01 1.11E+00 4.86E+00 5.53E+00 4.62E-02 4.88E+00 5.44E+00

-3.23E+00 1.71E+01 2.00E+01 MW-60-53 MW-60-53 011 53.4

-40.9 10/30/2009 14:19 1.47E+02 1.47E+02 1.61E+02 1.24E-01 4.95E-01 6.12E-01

-2.86E-01 6.88E+00 7.53E+00

-3.34E-02 6.96E+00 7.65E+00 NA NA NA MW-60-53 MW-60-53 012 53.4

-40.9 3/1/2010 11:07 1.37E+02 1.59E+02 1.75E+02 1.14E-01 5.66E-01 7.00E-01

-1.22E+00 4.51E+00 4.92E+00

-8.72E-01 4.93E+00 5.33E+00

-5.31E+00 1.95E+01 2.27E+01 MW-60-53 MW-60-53 013 53.4

-40.9 5/10/2010 16:31 3.45E+02 1.58E+02 1.41E+02

-9.87E-02 4.95E-01 6.82E-01 8.10E-01 7.58E+00 8.81E+00

-2.08E+00 8.49E+00 9.02E+00

-5.02E+00 2.07E+01 2.40E+01 MW-60-53 MW-60-53 014 53.4

-40.9 8/16/2010 15:34 2.58E+02 1.50E+02 1.60E+02

-2.84E-02 4.87E-01 6.04E-01

-8.42E+00 7.92E+00 7.70E+00

-2.64E+00 6.03E+00 6.02E+00

-8.48E+00 1.98E+01 2.37E+01 MW-60-53 MW-60-53 015 53.4

-40.9 11/18/2010 12:22 2.49E+02 1.83E+02 3.96E+02

-4.58E-01 4.20E-01 1.32E+00 4.54E-01 4.11E+00 9.15E+00 2.23E+00 3.57E+00 8.75E+00 1.10E+01 8.93E+00 1.96E+01 MW-60-53 MW-60-53 016 53.4

-40.9 2/11/2011 10:57 3.19E+02 3.70E+02 3.87E+02 7.44E-01 1.52E+00 1.70E+00

-2.03E+00 5.88E+00 6.16E+00 1.39E+00 7.96E+00 8.33E+00

-1.39E+00 1.50E+01 1.72E+01 MW-60-53 MW-60-53 017 53.4

-40.9 4/15/2011 11:37

-5.87E+01 3.96E+02 4.80E+02

-1.18E-02 1.60E+00 2.04E+00 2.17E+00 9.90E+00 1.14E+01

-1.11E+00 8.68E+00 8.95E+00

-1.06E+00 1.43E+01 1.66E+01 MW-60-53 MW-60-53 018 53.4

-40.9 8/10/2011 11:45 5.16E+02 2.70E+02 1.99E+02 1.18E+00 1.39E+00 1.45E+00 5.77E-01 1.34E+01 8.78E+00

-5.16E-01 1.07E+01 1.15E+01 NA NA NA MW-60-53 MW-60-53 019 53.4

-40.9 12/2/2011 11:46 2.65E+02 3.30E+02 3.33E+02 9.60E-02 1.69E+00 1.97E+00 4.62E-01 4.68E+00 5.62E+00

-9.95E-01 4.83E+00 5.65E+00 NA NA NA MW-60-53 MW-60-72 001 72.4

-59.9 5/8/2007 12:17

-9.26E+00 1.52E+02 1.82E+02 2.87E-01 8.13E-01 9.71E-01 1.61E+00 4.72E+00 3.33E+00 9.40E-01 3.21E+00 3.82E+00 8.28E-01 1.69E+01 1.97E+01 MW-60-72 MW-60-72 002 72.4

-59.9 7/27/2007 13:22 1.10E+02 1.64E+02 1.81E+02

-3.27E-01 4.92E-01 5.76E-01 4.79E-01 3.96E+00 4.51E+00

-1.10E+00 3.94E+00 4.17E+00 NA NA NA MW-60-72 MW-60-72 003 72.4

-59.9 10/9/2007 14:15 1.24E+02 1.43E+02 1.54E+02 1.64E-01 6.00E-01 7.12E-01 7.48E-01 3.78E+00 4.27E+00 6.12E-01 3.76E+00 4.33E+00 NA NA NA MW-60-72 MW-60-72 004 72.4

-59.9 1/14/2008 14:12 1.36E+02 1.65E+02 1.78E+02 1.58E-01 5.93E-01 7.23E-01 5.42E-03 3.33E+00 3.56E+00 8.47E-01 2.97E+00 3.54E+00 NA NA NA MW-60-72 MW-60-72 005 72.4

-59.9 4/24/2008 12:20 1.65E+02 1.17E+02 1.93E+02 3.08E-01 4.82E-01 8.38E-01

-5.33E-01 2.37E+00 3.92E+00 1.80E-01 2.23E+00 3.75E+00 NA NA NA MW-60-72 MW-60-72 006 72.4

-59.9 7/30/2008 13:25 8.27E+01 9.69E+01 1.63E+02 1.73E-01 1.41E-01 2.33E-01

-8.79E-01 2.39E+00 3.91E+00

-1.11E+00 2.47E+00 3.96E+00 NA NA NA MW-60-72 MW-60-72 007 72.4

-59.9 11/5/2008 14:58 1.94E+02 1.64E+02 1.78E+02 2.09E-01 6.54E-01 7.78E-01

-9.53E-01 5.68E+00 6.09E+00

-1.43E+00 5.36E+00 5.64E+00 NA NA NA MW-60-72 MW-60-72 008 72.4

-59.9 2/9/2009 11:25 1.67E+02 1.55E+02 1.69E+02

-4.16E-01 7.19E-01 9.60E-01

-6.54E-01 3.00E+00 3.30E+00 7.83E-01 3.09E+00 3.69E+00

-9.25E+00 2.24E+01 2.66E+01 MW-60-72 MW-60-72 009 72.4

-59.9 5/5/2009 10:32 1.57E+02 1.67E+02 1.75E+02 6.32E-02 6.66E-01 7.71E-01 2.29E+00 1.10E+01 7.32E+00 1.75E+00 6.02E+00 7.24E+00 NA NA NA MW-60-72 MW-60-72 010 72.4

-59.9 8/11/2009 10:40 1.73E+02 1.55E+02 1.69E+02 6.31E-02 5.38E-01 6.80E-01 2.68E+00 3.88E+00 4.62E+00 4.36E+00 6.15E+00 5.86E+00

-2.42E+00 1.76E+01 2.04E+01 MW-60-72 MW-60-72 011 72.4

-59.9 10/30/2009 11:08 1.73E+02 1.48E+02 1.61E+02 4.02E-02 3.89E-01 4.83E-01

-3.13E+00 5.89E+00 5.96E+00 2.57E+00 7.02E+00 8.35E+00 NA NA NA MW-60-72 MW-60-72 012 72.4

-59.9 2/25/2010 11:31 1.27E+02 1.58E+02 1.74E+02

-5.98E-02 5.52E-01 7.30E-01

-6.83E+00 8.12E+00 7.73E+00

-1.09E+00 4.88E+00 5.26E+00

-4.85E+00 1.94E+01 2.26E+01 MW-60-72 MW-60-72 013 72.4

-59.9 5/10/2010 12:11 3.01E+02 1.52E+02 1.40E+02 1.57E-02 5.49E-01 7.10E-01

-3.66E+00 1.29E+01 1.58E+01

-7.77E+00 1.16E+01 1.10E+01

-6.97E+00 2.07E+01 2.41E+01 MW-60-72 MW-60-72 014 72.4

-59.9 8/17/2010 11:59 2.33E+01 1.23E+02 1.44E+02 1.97E-01 5.90E-01 6.91E-01

-5.91E-01 5.40E+00 6.06E+00

-1.59E+00 6.08E+00 6.57E+00 1.19E+00 2.04E+01 2.37E+01 MW-60-72 MW-60-72 015 72.4

-59.9 11/16/2010 13:17

-2.51E+01 1.68E+02 3.98E+02 5.83E-02 5.15E-01 1.33E+00 2.12E+00 5.34E+00 1.26E+01

-3.92E+00 5.67E+00 1.09E+01

-1.14E+01 8.32E+00 1.89E+01 MW-60-72 MW-60-72 016 72.4

-59.9 2/10/2011 12:54 3.64E+02 3.76E+02 3.84E+02 2.41E-01 1.45E+00 1.70E+00

-5.10E-02 9.12E+00 1.01E+01 2.27E+00 8.84E+00 1.07E+01 2.12E+00 1.54E+01 1.75E+01 MW-60-72 MW-60-72 017 72.4

-59.9 4/15/2011 13:12 2.19E+02 3.78E+02 4.13E+02 7.12E-01 1.72E+00 1.97E+00

-5.14E+00 6.54E+00 5.80E+00

-3.30E+00 1.14E+01 1.14E+01

-2.93E+00 1.39E+01 1.63E+01 MW-60-72 MW-60-72 018 72.4

-59.9 8/10/2011 13:25 2.91E+02 2.23E+02 1.95E+02 1.22E-01 9.33E-01 1.14E+00

-4.08E+00 9.63E+00 1.00E+01 4.20E+00 8.40E+00 1.06E+01 NA NA NA MW-60-72 MW-60-72 019 72.4

-59.9 12/2/2011 10:01 3.08E+02 3.75E+02 4.01E+02 8.41E-01 1.73E+00 1.93E+00

-2.19E+00 6.99E+00 8.20E+00

-1.72E+00 8.28E+00 1.01E+01 NA NA NA MW-60-72 MW-60-135 001 134.9

-122.4 5/8/2007 12:03 2.54E+01 1.55E+02 1.81E+02 3.35E-01 6.77E-01 7.74E-01

-1.05E+00 3.50E+00 3.08E+00 1.74E-01 3.12E+00 3.52E+00 4.54E+00 1.77E+01 2.02E+01 MW-60-135 MW-60-135 002 134.9

-122.4 7/27/2007 16:00 3.92E+02 2.03E+02 1.81E+02

-2.13E-01 3.09E-01 4.69E-01 2.78E-02 2.70E+00 3.07E+00 1.78E-01 2.63E+00 3.04E+00 NA NA NA MW-60-135 MW-60-135 003 134.9

-122.4 10/9/2007 14:20 5.20E+02 1.83E+02 1.50E+02

-2.59E-01 4.46E-01 6.31E-01

-1.55E+00 3.40E+00 3.52E+00

-8.88E-02 3.57E+00 3.94E+00 NA NA NA MW-60-135 MW-60-135 004 134.9

-122.4 1/14/2008 14:19 3.79E+02 1.89E+02 1.74E+02

-1.70E-01 6.17E-01 8.52E-01

-1.33E+00 3.14E+00 3.25E+00 4.22E-01 3.17E+00 3.59E+00 NA NA NA MW-60-135 MW-60-135 005 134.9

-122.4 4/24/2008 12:31 5.85E+02 1.33E+02 1.93E+02

-1.98E-02 3.17E-01 6.59E-01 1.16E+00 2.24E+00 3.93E+00

-1.70E+00 2.67E+00 3.93E+00 NA NA NA MW-60-135 MW-60-135 006 134.9

-122.4 7/30/2008 13:33 4.91E+02 1.42E+02 1.91E+02 1.70E-01 3.44E-01 6.18E-01

-4.68E-01 1.79E+00 2.88E+00 1.43E+00 2.00E+00 3.61E+00 NA NA NA MW-60-135 MW-60-135 007 134.9

-122.4 11/6/2008 10:49 4.25E+02 2.01E+02 1.99E+02

-1.71E-01 5.01E-01 7.18E-01

-2.18E-02 5.71E+00 6.40E+00

-3.93E+00 6.25E+00 5.99E+00 NA NA NA MW-60-135 MW-60-135 008 134.9

-122.4 2/9/2009 12:04 3.83E+02 1.67E+02 1.69E+02 5.52E-01 5.96E-01 6.39E-01 1.42E+00 2.96E+00 3.48E+00 4.24E-01 3.05E+00 3.35E+00 3.74E+00 2.27E+01 2.58E+01 MW-60-135 MW-60-135 009 134.9

-122.4 5/5/2009 10:54 3.17E+02 1.85E+02 1.71E+02

-1.77E-01 6.12E-01 7.45E-01

-3.22E+00 1.31E+01 8.76E+00 3.12E-01 6.81E+00 7.64E+00 NA NA NA MW-60-135 MW-60-135 010 134.9

-122.4 8/11/2009 10:52 3.46E+02 1.64E+02 1.69E+02 4.65E-01 5.88E-01 6.16E-01 1.76E+00 3.36E+00 4.03E+00 4.56E-01 3.51E+00 3.93E+00

-3.72E+00 1.77E+01 2.07E+01 MW-60-135 MW-60-135 011 134.9

-122.4 10/30/2009 10:55 3.17E+02 1.55E+02 1.61E+02

-1.77E-01 5.93E-01 7.61E-01 1.75E+00 6.83E+00 7.81E+00

-2.32E+00 6.58E+00 6.63E+00 NA NA NA MW-60-135 MW-60-135 012 134.9

-122.4 2/25/2010 11:43 3.14E+02 1.68E+02 1.75E+02 1.21E-01 5.95E-01 7.32E-01 6.09E-01 4.11E+00 4.72E+00

-5.16E+00 7.25E+00 5.27E+00

-1.29E+00 1.89E+01 2.18E+01 MW-60-135 MW-60-135 013 134.9

-122.4 5/10/2010 12:21 4.18E+02 1.80E+02 1.65E+02

-9.46E-02 6.05E-01 8.55E-01 1.55E+00 7.70E+00 9.03E+00 6.68E-03 8.37E+00 9.36E+00

-8.62E+00 2.04E+01 2.38E+01 MW-60-135 MW-60-135 014 134.9

-122.4 8/17/2010 12:09 1.87E+02 1.39E+02 1.43E+02

-2.74E-01 5.38E-01 7.27E-01

-3.46E+00 8.41E+00 9.07E+00

-1.52E+00 6.30E+00 6.70E+00 8.77E-01 2.11E+01 2.45E+01 MW-60-135 MW-60-135 015 134.9

-122.4 11/16/2010 13:22 2.41E+02 1.82E+02 3.96E+02

-4.96E-02 7.62E-01 1.88E+00 9.16E-01 5.37E+00 1.20E+01 1.02E+00 4.53E+00 1.03E+01 8.67E-01 8.52E+00 1.90E+01 MW-60-135 MW-60-135 016 134.9

-122.4 2/10/2011 13:04 3.98E+02 3.78E+02 3.83E+02 1.14E+00 1.82E+00 1.98E+00 1.72E+00 6.72E+00 7.79E+00 2.24E-01 7.44E+00 8.25E+00

-3.56E+00 1.52E+01 1.76E+01 MW-60-135 MW-60-135 017 134.9

-122.4 4/15/2011 13:25 4.14E+02 4.02E+02 4.12E+02 6.52E-01 1.90E+00 2.16E+00

-6.83E+00 1.39E+01 1.63E+01

-2.48E+00 9.86E+00 1.01E+01 4.64E+00 1.47E+01 1.65E+01 MW-60-135 MW-60-135 018 134.9

-122.4 8/10/2011 13:51 4.00E+02 2.46E+02 1.96E+02

-2.08E-01 9.78E-01 1.25E+00

-7.37E+00 9.39E+00 8.24E+00

-6.27E+00 1.07E+01 9.07E+00 NA NA NA MW-60-135 MW-60-135 019 134.9

-122.4 12/2/2011 10:10 3.05E+02 3.81E+02 4.08E+02

-1.48E-01 1.62E+00 1.97E+00

-1.37E-02 7.68E+00 9.43E+00 2.05E+00 8.28E+00 1.13E+01 NA NA NA MW-60-135 MW-60-154 001 154.4

-141.9 5/8/2007 12:33 4.13E+01 1.55E+02 1.80E+02 3.06E-01 8.13E-01 9.50E-01 1.97E-01 3.46E+00 3.86E+00 1.46E+00 3.75E+00 4.46E+00 5.52E-01 1.68E+01 1.97E+01 MW-60-154

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 24 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-60-154 002 154.4

-141.9 7/27/2007 16:18 4.62E+02 2.09E+02 1.79E+02

-1.53E-01 3.46E-01 4.09E-01 8.09E-01 4.23E+00 4.60E+00 3.74E+00 2.42E+00 3.80E+00 NA NA NA MW-60-154 MW-60-154 003 154.4

-141.9 10/9/2007 14:23 5.80E+02 1.88E+02 1.50E+02

-1.92E-02 4.98E-01 6.33E-01

-1.63E+00 3.50E+00 3.68E+00 2.20E-01 3.30E+00 3.76E+00 NA NA NA MW-60-154 MW-60-154 004 154.4

-141.9 1/14/2008 12:35 5.59E+02 2.13E+02 1.79E+02 1.10E+00 1.17E+00 1.24E+00 1.59E+00 3.84E+00 4.46E+00 2.92E-01 4.35E+00 4.82E+00 NA NA NA MW-60-154 MW-60-154 005 154.4

-141.9 4/24/2008 12:36 4.53E+02 1.28E+02 1.94E+02

-2.44E-01 3.65E-01 7.77E-01

-1.25E+00 2.37E+00 3.69E+00 1.29E+00 2.06E+00 3.79E+00 NA NA NA MW-60-154 MW-60-154 006 154.4

-141.9 7/30/2008 13:35 5.16E+02 1.44E+02 1.91E+02 5.10E-01 2.50E-01 3.30E-01

-8.80E-01 2.67E+00 3.58E+00 4.30E-01 1.89E+00 3.25E+00 NA NA NA MW-60-154 MW-60-154 007 154.4

-141.9 11/6/2008 11:19 6.87E+02 4.16E+02 3.86E+02 4.32E-01 6.57E-01 7.19E-01 2.47E+00 4.96E+00 5.91E+00 5.49E-01 5.87E+00 6.61E+00 NA NA NA MW-60-154 MW-60-154 008 154.4

-141.9 2/9/2009 12:23 4.15E+02 1.65E+02 1.67E+02 4.63E-01 7.98E-01 8.96E-01 7.14E-01 3.02E+00 3.45E+00 1.01E+00 3.54E+00 4.13E+00

-3.74E+00 2.09E+01 2.42E+01 MW-60-154 MW-60-154 009 154.4

-141.9 5/5/2009 11:15 4.39E+02 2.01E+02 1.72E+02 7.36E-02 5.70E-01 6.88E-01

-2.52E-01 6.89E+00 4.59E+00

-1.47E+00 5.07E+00 5.42E+00 NA NA NA MW-60-154 MW-60-154 010 154.4

-141.9 8/11/2009 11:14 5.13E+02 1.71E+02 1.69E+02

-3.52E-01 7.18E-01 9.69E-01

-3.93E-01 5.04E+00 5.67E+00

-2.99E+00 6.06E+00 5.34E+00 1.97E+00 1.80E+01 2.08E+01 MW-60-154 MW-60-154 011 154.4

-141.9 10/30/2009 10:56 4.09E+02 1.59E+02 1.61E+02 4.48E-01 8.40E-01 9.50E-01 1.34E+01 7.70E+00 6.69E+00

-1.32E-01 6.27E+00 7.01E+00 NA NA NA MW-60-154 MW-60-154 012 154.4

-141.9 2/25/2010 11:45 3.78E+02 1.71E+02 1.74E+02 1.97E-01 6.63E-01 7.90E-01 1.32E+00 4.72E+00 5.42E+00

-4.38E-04 4.86E+00 5.45E+00

-1.32E+01 1.84E+01 2.19E+01 MW-60-154 MW-60-154 013 154.4

-141.9 5/10/2010 12:32 4.38E+02 1.85E+02 1.69E+02 3.52E-01 6.25E-01 7.01E-01

-1.33E+00 8.40E+00 9.22E+00 1.61E-01 7.65E+00 8.61E+00

-5.15E+00 2.13E+01 2.46E+01 MW-60-154 MW-60-154 014 154.4

-141.9 8/17/2010 12:18 2.93E+02 1.50E+02 1.45E+02

-2.33E-01 5.00E-01 6.61E-01

-4.41E-01 6.04E+00 6.67E+00 1.95E+00 6.78E+00 8.02E+00

-1.16E+00 2.13E+01 2.48E+01 MW-60-154 MW-60-154 015 154.4

-141.9 11/16/2010 13:40 4.68E+02 1.94E+02 3.98E+02 3.29E-01 8.30E-01 1.94E+00

-5.28E+00 4.02E+00 7.52E+00

-2.29E-01 5.09E+00 1.11E+01

-4.54E+00 7.93E+00 1.78E+01 MW-60-154 MW-60-154 016 154.4

-141.9 2/10/2011 12:53 5.44E+02 4.02E+02 3.87E+02 2.32E-02 8.50E-01 1.07E+00

-4.12E+00 9.26E+00 8.97E+00 9.91E-01 7.86E+00 9.12E+00 4.61E+00 1.52E+01 1.71E+01 MW-60-154 MW-60-154 017 154.4

-141.9 4/15/2011 13:19 3.06E+02 3.96E+02 4.21E+02

-4.20E-01 1.53E+00 2.02E+00

-2.09E+00 7.62E+00 7.82E+00

-7.25E-01 6.50E+00 6.79E+00 1.62E+00 1.44E+01 1.64E+01 MW-60-154 MW-60-154 018 154.4

-141.9 8/10/2011 13:22 5.89E+02 2.81E+02 1.97E+02

-5.08E-02 1.13E+00 1.40E+00

-1.03E+00 8.01E+00 8.47E+00 2.98E+00 9.03E+00 1.07E+01 NA NA NA MW-60-154 MW-60-154 019 154.4

-141.9 12/2/2011 10:18 6.27E+02 5.22E+02 5.23E+02

-1.97E-01 1.54E+00 1.96E+00 1.25E+00 9.33E+00 1.17E+01

-3.69E+00 1.00E+01 1.13E+01 NA NA NA MW-60-154 MW-60-176 001 175.9

-163.4 5/8/2007 15:16 5.30E+02 2.01E+02 1.80E+02 6.88E-02 5.66E-01 7.29E-01 3.49E-01 4.54E+00 4.38E+00 1.14E+00 3.90E+00 3.98E+00 7.69E+00 1.73E+01 1.96E+01 MW-60-176 MW-60-176 002 175.9

-163.4 7/27/2007 17:35 8.49E+02 2.49E+02 1.78E+02

-4.60E-01 5.84E-01 7.87E-01 2.00E+00 3.29E+00 4.00E+00

-1.76E+00 3.15E+00 3.03E+00 NA NA NA MW-60-176 MW-60-176 003 175.9

-163.4 10/9/2007 14:57 7.02E+02 2.01E+02 1.53E+02

-5.93E-02 5.11E-01 6.64E-01

-2.68E-01 2.63E+00 2.85E+00 3.91E-01 2.71E+00 3.09E+00 NA NA NA MW-60-176 MW-60-176 004 175.9

-163.4 1/14/2008 12:25 6.68E+02 2.25E+02 1.83E+02

-7.68E-02 7.89E-01 1.04E+00 2.22E-01 3.99E+00 4.52E+00 5.49E-01 3.54E+00 4.09E+00 NA NA NA MW-60-176 MW-60-176 005 175.9

-163.4 4/24/2008 13:10 7.77E+02 2.04E+02 2.73E+02 2.68E-01 4.91E-01 8.54E-01

-1.81E+00 2.70E+00 4.00E+00

-9.94E-01 2.53E+00 3.95E+00 NA NA NA MW-60-176 MW-60-176 006 175.9

-163.4 7/30/2008 14:08 8.95E+02 1.67E+02 1.91E+02

-2.08E-02 2.96E-01 5.88E-01

-3.15E-01 2.12E+00 3.44E+00

-2.05E-01 2.03E+00 3.34E+00 NA NA NA MW-60-176 MW-60-176 007 175.9

-163.4 11/6/2008 11:55 8.32E+02 4.35E+02 3.86E+02 2.17E-01 4.71E-01 5.45E-01

-2.63E+00 5.09E+00 5.07E+00

-1.06E-01 5.66E+00 6.33E+00 NA NA NA MW-60-176 MW-60-176 008 175.9

-163.4 2/9/2009 13:08 9.16E+02 1.91E+02 1.70E+02 4.25E-01 6.80E-01 7.58E-01

-2.42E-01 3.27E+00 3.56E+00 5.10E-01 3.29E+00 3.74E+00

-1.22E+01 2.06E+01 2.44E+01 MW-60-176 MW-60-176 009 175.9

-163.4 5/5/2009 11:18 1.04E+03 2.64E+02 1.72E+02 2.40E-01 6.00E-01 6.90E-01

-4.10E+00 8.45E+00 5.63E+00 1.23E+00 5.69E+00 6.59E+00 NA NA NA MW-60-176 MW-60-176 010 175.9

-163.4 8/11/2009 11:49 1.03E+03 1.94E+02 1.69E+02

-2.36E-02 3.44E-01 4.63E-01 1.75E+00 4.84E+00 5.71E+00 2.25E+00 4.89E+00 5.91E+00

-2.65E+00 1.77E+01 2.07E+01 MW-60-176 MW-60-176 011 175.9

-163.4 10/30/2009 11:26 1.02E+03 1.83E+02 1.61E+02

-2.27E-01 4.68E-01 6.97E-01 8.58E-01 5.25E+00 5.95E+00 2.31E+00 5.37E+00 6.52E+00 NA NA NA MW-60-176 MW-60-176 012 175.9

-163.4 2/25/2010 12:24 9.90E+02 2.01E+02 1.74E+02 7.56E-02 3.36E-01 4.10E-01 2.82E+00 6.03E+00 6.92E+00

-3.93E-01 7.93E+00 7.20E+00

-1.79E+00 1.99E+01 2.30E+01 MW-60-176 MW-60-176 013 175.9

-163.4 5/10/2010 13:29 9.93E+02 2.24E+02 1.63E+02

-3.09E-01 4.52E-01 6.99E-01

-5.66E-01 8.13E+00 9.07E+00 9.92E-01 8.25E+00 9.76E+00 0.00E+00 2.04E+01 2.34E+01 MW-60-176 MW-60-176 014 175.9

-163.4 8/17/2010 12:51 8.13E+02 1.91E+02 1.44E+02

-6.59E-01 6.48E-01 9.01E-01 1.23E-01 6.43E+00 7.32E+00 1.35E+00 5.80E+00 6.97E+00 0.00E+00 2.13E+01 2.48E+01 MW-60-176 MW-60-176 015 175.9

-163.4 11/16/2010 14:06 8.33E+02 2.10E+02 3.97E+02 9.07E-01 9.42E-01 2.10E+00

-1.97E+00 4.38E+00 9.04E+00 2.85E+00 4.70E+00 1.12E+01

-6.40E+00 7.91E+00 1.78E+01 MW-60-176 MW-60-176 016 175.9

-163.4 2/10/2011 10:31 1.12E+03 4.68E+02 3.85E+02 2.58E-01 1.49E+00 1.74E+00 4.88E+00 1.13E+01 6.69E+00

-1.75E+00 6.70E+00 6.74E+00 7.24E+00 1.62E+01 1.79E+01 MW-60-176 MW-60-176 017 175.9

-163.4 4/15/2011 13:49 8.99E+02 4.66E+02 4.18E+02

-8.29E-01 1.41E+00 2.10E+00

-7.83E-02 9.90E+00 1.10E+01

-2.35E+00 1.02E+01 1.03E+01

-2.40E-01 1.40E+01 1.62E+01 MW-60-176 MW-60-176 018 175.9

-163.4 8/10/2011 14:12 9.72E+02 3.42E+02 2.00E+02

-1.79E-01 9.21E-01 1.22E+00

-3.87E+00 7.74E+00 7.27E+00

-1.71E-01 8.91E+00 9.60E+00 NA NA NA MW-60-176 MW-60-176 019 175.9

-163.4 12/2/2011 10:27 1.30E+03 5.97E+02 5.19E+02

-1.37E+00 1.41E+00 1.95E+00 7.24E-01 9.60E+00 1.20E+01 1.35E+00 1.01E+01 1.36E+01 NA NA NA MW-60-176 MW-62-18 001 13.5 1.2 5/17/2007 13:10 4.52E+02 1.83E+02 1.55E+02 2.98E-02 5.53E-01 7.27E-01

-5.10E-01 2.61E+00 2.89E+00 1.00E-01 2.79E+00 3.19E+00 4.61E+00 1.52E+01 1.74E+01 MW-62-18 MW-62-18 002 13.5 1.2 7/26/2007 15:45 5.08E+02 2.13E+02 1.78E+02 4.68E-01 4.93E-01 5.35E-01 9.04E-01 3.75E+00 4.35E+00

-2.80E+00 4.88E+00 3.80E+00 NA NA NA MW-62-18 MW-62-18 003 13.5 1.2 10/10/2007 13:50 3.76E+02 1.73E+02 1.55E+02 1.80E+00 6.67E-01 4.87E-01 0.00E+00 3.39E+00 1.87E+00

-7.14E-02 1.71E+00 1.92E+00 NA NA NA MW-62-18 MW-62-18 004 13.5 1.2 1/31/2008 15:15 3.50E+02 1.34E+02 1.34E+02 4.95E-01 7.55E-01 8.27E-01 1.18E+00 4.23E+00 4.46E+00 5.24E-01 3.38E+00 3.96E+00 NA NA NA MW-62-18 MW-62-18 006 13.5 1.2 8/6/2008 12:55 2.69E+02 1.41E+02 2.25E+02 5.31E-01 3.30E-01 4.89E-01 9.69E-02 1.67E+00 2.82E+00

-1.26E-01 1.99E+00 3.33E+00 NA NA NA MW-62-18 MW-62-18 007 13.5 1.2 10/29/2008 13:20 4.08E+02 1.65E+02 1.66E+02 5.23E-01 6.03E-01 6.37E-01

-3.09E-02 5.10E+00 5.60E+00

-3.91E+00 5.25E+00 4.70E+00 NA NA NA MW-62-18 MW-62-18 008 13.5 1.2 1/23/2009 11:55 4.64E+02 1.39E+02 1.07E+02 1.09E+00 6.47E-01 6.00E-01 9.88E-01 2.55E+00 3.06E+00

-3.42E-01 2.48E+00 2.74E+00 NA NA NA MW-62-18 MW-62-18 009 13.5 1.2 4/15/2009 13:18 4.56E+02 1.85E+02 1.36E+02 1.76E-01 5.99E-01 7.14E-01

-3.54E-01 5.81E+00 3.87E+00 1.91E+00 3.29E+00 4.20E+00

-1.88E+00 1.86E+01 2.17E+01 MW-62-18 MW-62-18 010 13.5 1.2 7/22/2009 14:24 2.36E+02 2.16E+02 2.29E+02 1.04E-01 6.42E-01 7.94E-01

-8.49E-01 2.94E+00 3.08E+00

-2.70E+00 3.66E+00 3.28E+00 NA NA NA MW-62-18 MW-62-18 011 13.5 1.2 11/12/2009 15:36 2.83E+02 1.13E+02 1.05E+02 3.30E-01 7.05E-01 8.04E-01

-1.84E+00 6.40E+00 5.80E+00

-4.63E+00 7.20E+00 6.68E+00 NA NA NA MW-62-18 MW-62-18 012 13.5 1.2 2/9/2010 15:19 2.87E+02 1.88E+02 1.98E+02 5.26E-01 6.40E-01 6.64E-01

-1.57E+00 5.87E+00 6.19E+00

-2.90E+00 7.82E+00 7.61E+00 NA NA NA MW-62-18 MW-62-18 013 13.5 1.2 4/13/2010 15:17 2.04E+02 1.34E+02 1.42E+02 2.74E-02 6.16E-01 7.97E-01

-1.48E+00 4.05E+00 4.37E+00 6.69E-01 5.38E+00 4.96E+00 NA NA NA MW-62-18 MW-62-18 014 13.5 1.2 8/3/2010 13:00 1.14E+02 1.32E+02 1.44E+02 6.60E-01 6.55E-01 6.80E-01 3.08E+00 8.40E+00 1.03E+01 5.07E+00 1.02E+01 1.32E+01 NA NA NA MW-62-18 MW-62-18 015 13.5 1.2 11/9/2010 11:57 7.48E+01 1.71E+02 3.86E+02

-1.05E-02 6.10E-01 1.54E+00 2.87E+00 4.59E+00 1.07E+01

-6.86E-01 4.79E+00 1.01E+01 NA NA NA MW-62-18 MW-62-18 016 13.5 1.2 2/24/2011 12:49 1.81E+02 3.60E+02 4.00E+02

-3.86E-01 1.71E+00 2.13E+00 2.12E-01 4.74E+00 5.18E+00 3.58E+00 5.46E+00 6.78E+00 NA NA NA MW-62-18 MW-62-18 017 13.5 1.2 4/13/2011 11:58 3.25E+02 4.56E+02 4.92E+02 7.82E-01 1.54E+00 1.71E+00

-4.38E+00 1.00E+01 1.09E+01

-4.07E-01 1.06E+01 1.16E+01 NA NA NA MW-62-18 MW-62-18 018 13.5 1.2 7/22/2011 11:35 2.00E+02 4.02E+02 4.45E+02 1.26E+00 1.24E+00 1.25E+00 4.94E+00 9.42E+00 1.14E+01

-1.79E+00 1.05E+01 1.08E+01

-3.83E+00 1.96E+01 2.20E+01 MW-62-18 MW-62-18 019 13.5 1.2 8/3/2011 10:18 4.04E+02 3.39E+02 3.53E+02 2.03E-01 1.37E+00 1.74E+00

-1.12E+00 8.70E+00 9.13E+00 4.76E+00 9.81E+00 1.21E+01 NA NA NA MW-62-18 MW-62-18 020 13.5 1.2 10/21/2011 10:14 6.50E+02 3.54E+02 3.45E+02

-1.09E+00 1.66E+00 2.27E+00

-1.19E+00 6.87E+00 8.28E+00

-8.37E-01 8.82E+00 1.11E+01 NA NA NA MW-62-18 MW-62-37 001 34.5

-19.8 5/17/2007 11:10 2.97E+02 1.70E+02 1.59E+02 3.30E-01 8.28E-01 9.66E-01 9.81E-01 2.00E+00 2.37E+00

-1.12E+00 2.25E+00 2.31E+00 1.01E+01 1.81E+01 2.04E+01 MW-62-37 MW-62-37 002 34.5

-19.8 7/26/2007 15:35 2.50E+02 1.79E+02 1.75E+02

-2.57E-01 4.14E-01 5.18E-01

-6.88E-02 2.64E+00 2.94E+00

-4.23E-01 2.60E+00 2.81E+00 NA NA NA MW-62-37 MW-62-37 003 34.5

-19.8 10/10/2007 14:50 3.02E+02 1.58E+02 1.47E+02

-1.67E-01 4.44E-01 6.10E-01 2.12E-01 1.81E+00 2.02E+00

-7.67E-01 1.74E+00 1.83E+00 NA NA NA MW-62-37 MW-62-37 004 34.5

-19.8 1/10/2008 13:55 3.97E+02 1.68E+02 1.71E+02 1.34E-01 6.05E-01 7.24E-01 8.35E-01 4.43E+00 4.62E+00

-2.10E-01 3.87E+00 4.19E+00 NA NA NA MW-62-37 MW-62-37 006 34.5

-19.8 8/6/2008 12:00 3.94E+02 1.19E+02 1.45E+02 2.23E-01 2.69E-01 4.54E-01

-2.55E+00 1.52E+00 2.06E+00

-1.08E+00 1.56E+00 2.38E+00 NA NA NA MW-62-37 MW-62-37 007 34.5

-19.8 10/29/2008 13:57 5.35E+02 1.71E+02 1.66E+02 1.36E+00 6.57E-01 5.24E-01 4.20E-01 4.77E+00 5.33E+00

-2.20E+00 5.19E+00 5.20E+00 NA NA NA MW-62-37 MW-62-37 008 34.5

-19.8 1/23/2009 12:20 4.87E+02 1.42E+02 1.08E+02 1.28E-01 7.41E-01 9.02E-01

-7.69E-01 3.12E+00 3.43E+00

-6.49E-01 3.14E+00 3.36E+00 NA NA NA MW-62-37 MW-62-37 009 34.5

-19.8 4/15/2009 13:13 4.39E+02 1.82E+02 1.35E+02

-3.16E-01 6.68E-01 8.49E-01

-1.73E-01 5.94E+00 3.96E+00

-6.46E-01 4.44E+00 4.81E+00

-1.65E+01 1.74E+01 2.14E+01 MW-62-37 MW-62-37 010 34.5

-19.8 7/22/2009 16:02 2.82E+02 2.22E+02 2.30E+02

-3.68E-01 6.77E-01 8.81E-01

-1.79E+00 3.66E+00 3.82E+00

-1.61E+00 3.56E+00 3.57E+00 NA NA NA MW-62-37 MW-62-37 011 34.5

-19.8 11/12/2009 15:27 2.17E+02 1.07E+02 1.05E+02

-3.41E-01 7.05E-01 8.68E-01

-8.33E+00 1.00E+01 1.01E+01

-1.08E+00 7.15E+00 7.72E+00 NA NA NA MW-62-37 MW-62-37 012 34.5

-19.8 2/9/2010 15:40 3.93E+02 1.95E+02 1.98E+02

-1.80E-01 4.98E-01 6.66E-01

-2.99E+00 4.96E+00 4.83E+00

-2.54E-01 5.97E+00 6.51E+00 NA NA NA MW-62-37 MW-62-37 013 34.5

-19.8 4/13/2010 15:22 2.59E+02 2.07E+02 2.26E+02 5.46E-01 7.33E-01 7.81E-01

-2.42E+00 3.86E+00 4.07E+00 1.34E+00 4.04E+00 4.80E+00 NA NA NA MW-62-37 MW-62-37 014 34.5

-19.8 8/3/2010 12:52 1.91E+02 1.43E+02 1.47E+02

-1.52E-02 5.47E-01 6.85E-01

-9.69E-01 8.78E+00 9.70E+00

-5.33E+00 9.12E+00 7.92E+00 NA NA NA MW-62-37 MW-62-37 015 34.5

-19.8 11/9/2010 11:56 6.09E+01 1.70E+02 3.85E+02 7.62E-01 6.69E-01 1.47E+00

-8.46E-02 4.49E+00 9.91E+00 3.83E+00 4.28E+00 1.07E+01 NA NA NA MW-62-37 MW-62-37 016 34.5

-19.8 2/24/2011 12:52 3.05E+02 3.76E+02 4.00E+02 5.14E-01 1.84E+00 2.13E+00 1.07E+00 6.06E+00 6.86E+00

-2.84E+00 6.38E+00 6.28E+00 NA NA NA MW-62-37 MW-62-37 017 34.5

-19.8 4/13/2011 12:10 1.56E+02 4.36E+02 4.91E+02

-1.97E-01 1.08E+00 1.37E+00

-4.48E+00 8.32E+00 7.76E+00

-1.68E+00 9.02E+00 9.05E+00 NA NA NA MW-62-37 MW-62-37 018 34.5

-19.8 7/22/2011 12:28 1.15E+02 3.90E+02 4.42E+02 1.03E+00 1.60E+00 1.73E+00

-3.64E+00 7.95E+00 8.03E+00 2.96E+00 1.10E+01 1.30E+01

-8.92E+00 1.85E+01 2.09E+01 MW-62-37 MW-62-37 019 34.5

-19.8 8/3/2011 10:35 3.09E+02 3.33E+02 3.52E+02 1.23E+00 1.81E+00 1.96E+00 3.02E+00 6.69E+00 8.03E+00 2.71E+00 8.55E+00 1.01E+01 NA NA NA MW-62-37 MW-62-37 020 34.5

-19.8 10/21/2011 10:02 3.74E+02 3.33E+02 3.47E+02

-3.24E-01 1.60E+00 2.05E+00 5.93E-01 8.19E+00 9.98E+00

-1.66E+00 8.07E+00 9.72E+00 NA NA NA MW-62-37 MW-62-53 001 53.1

-40.3 5/10/2007 15:00 3.93E+02 1.91E+02 1.72E+02 4.41E-01 7.97E-01 8.96E-01 6.50E-01 3.40E+00 3.86E+00

-9.12E-01 3.52E+00 3.74E+00

-5.00E+00 1.40E+01 1.68E+01 MW-62-53

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 25 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-62-53 002 53.1

-40.3 7/26/2007 15:34 3.45E+02 1.94E+02 1.78E+02 3.56E-01 6.98E-01 7.85E-01 0.00E+00 4.62E+00 2.53E+00

-8.44E-01 2.77E+00 2.45E+00 NA NA NA MW-62-53 MW-62-53 003 53.1

-40.3 1/10/2008 15:37 3.48E+02 1.67E+02 1.71E+02 4.45E-02 6.72E-01 8.15E-01

-7.91E-01 2.75E+00 2.93E+00 7.68E-01 2.88E+00 3.43E+00 NA NA NA MW-62-53 MW-62-53 005 53.1

-40.3 8/6/2008 12:35 3.52E+02 1.54E+02 2.41E+02 9.52E-03 2.54E-01 4.95E-01 1.38E+00 2.24E+00 3.98E+00 3.02E-01 2.30E+00 3.87E+00 NA NA NA MW-62-53 MW-62-53 006 53.1

-40.3 10/29/2008 13:51 4.08E+02 1.67E+02 1.67E+02 6.63E-02 3.87E-01 4.94E-01

-3.99E-01 5.85E+00 6.51E+00

-2.87E+00 8.09E+00 7.19E+00 NA NA NA MW-62-53 MW-62-53 007 53.1

-40.3 1/23/2009 12:44 3.56E+02 2.16E+02 2.08E+02 4.53E-01 7.68E-01 8.60E-01 2.27E-01 3.30E+00 3.77E+00

-1.27E+00 3.56E+00 3.71E+00 NA NA NA MW-62-53 MW-62-53 008 53.1

-40.3 4/15/2009 13:29 4.33E+02 1.82E+02 1.36E+02

-5.89E-01 6.65E-01 9.09E-01

-4.92E-01 5.30E+00 3.53E+00 2.83E-01 2.82E+00 3.31E+00

-6.14E+00 1.79E+01 2.12E+01 MW-62-53 MW-62-53 009 53.1

-40.3 7/22/2009 14:01 2.40E+02 2.21E+02 2.33E+02 7.09E-01 7.95E-01 8.34E-01 3.00E-02 3.13E+00 3.55E+00 3.78E-01 3.24E+00 3.73E+00 NA NA NA MW-62-53 MW-62-53 010 53.1

-40.3 11/12/2009 13:38 2.81E+02 1.09E+02 1.01E+02 3.54E-01 6.45E-01 7.27E-01 2.51E-01 2.88E+00 3.32E+00

-6.92E-01 3.25E+00 3.51E+00 NA NA NA MW-62-53 MW-62-53 011 53.1

-40.3 2/9/2010 14:00 3.46E+02 1.92E+02 1.98E+02

-1.50E-01 4.35E-01 6.61E-01

-9.19E-01 5.87E+00 6.39E+00 1.34E+00 6.06E+00 7.13E+00 NA NA NA MW-62-53 MW-62-53 012 53.1

-40.3 4/13/2010 15:27 3.25E+02 1.44E+02 1.47E+02

-1.84E-02 5.67E-01 7.67E-01 1.33E+00 3.35E+00 3.87E+00

-1.52E+00 5.03E+00 4.08E+00 NA NA NA MW-62-53 MW-62-53 013 53.1

-40.3 8/3/2010 12:20 1.59E+02 1.40E+02 1.47E+02 3.13E-01 5.61E-01 6.32E-01 2.99E+00 1.11E+01 1.33E+01 2.39E-01 7.18E+00 8.24E+00 NA NA NA MW-62-53 MW-62-53 014 53.1

-40.3 11/9/2010 12:49 2.05E+02 1.77E+02 3.88E+02 8.32E-02 6.79E-01 1.59E+00

-4.23E+00 4.83E+00 9.52E+00

-2.68E+00 5.26E+00 1.04E+01 NA NA NA MW-62-53 MW-62-53 015 53.1

-40.3 2/24/2011 12:57 3.08E+02 3.78E+02 4.03E+02 8.98E-01 1.94E+00 2.18E+00

-2.62E-01 4.72E+00 5.23E+00

-1.84E+00 5.58E+00 5.81E+00 NA NA NA MW-62-53 MW-62-53 016 53.1

-40.3 4/13/2011 11:32 1.57E+02 4.36E+02 4.92E+02 1.72E+00 1.79E+00 1.84E+00 5.42E-01 6.78E+00 7.51E+00

-3.00E-01 6.24E+00 6.58E+00 NA NA NA MW-62-53 MW-62-53 017 53.1

-40.3 7/22/2011 10:47 1.60E+02 3.96E+02 4.45E+02

-4.83E-01 1.07E+00 1.58E+00 4.34E+00 7.86E+00 9.52E+00 1.66E+00 8.85E+00 1.02E+01

-1.60E+01 1.79E+01 2.05E+01 MW-62-53 MW-62-53 018 53.1

-40.3 8/3/2011 12:44 4.12E+02 3.42E+02 3.00E+02 1.52E-01 1.46E+00 1.75E+00 2.87E+00 7.59E+00 9.04E+00 3.15E+00 8.76E+00 1.06E+01 NA NA NA MW-62-53 MW-62-53 019 53.1

-40.3 10/21/2011 10:17 4.82E+02 3.39E+02 3.42E+02

-1.78E-02 1.24E+00 1.61E+00 1.64E+00 6.66E+00 8.55E+00 2.49E+00 7.05E+00 1.01E+01 NA NA NA MW-62-53 MW-62-71 001 71.1

-58.3 5/10/2007 11:35 5.02E+02 2.00E+02 1.71E+02 6.16E-01 8.34E-01 8.92E-01

-8.78E-01 3.51E+00 3.75E+00 1.37E-01 3.21E+00 3.59E+00 4.93E+00 1.29E+01 1.48E+01 MW-62-71 MW-62-71 002 71.1

-58.3 7/26/2007 12:20 1.51E+02 1.65E+02 1.74E+02 2.15E-01 7.26E-01 8.29E-01 1.11E+00 3.36E+00 3.91E+00

-2.39E-01 3.48E+00 3.90E+00 NA NA NA MW-62-71 MW-62-71 003 71.1

-58.3 10/10/2007 12:23 2.69E+02 1.61E+02 1.55E+02 1.15E-01 5.22E-01 6.30E-01 1.18E+00 2.43E+00 2.45E+00 1.54E+00 2.10E+00 2.55E+00 NA NA NA MW-62-71 MW-62-71 004 71.1

-58.3 1/10/2008 14:04 3.53E+02 1.89E+02 1.94E+02 3.78E-01 5.85E-01 6.46E-01

-7.82E-01 2.51E+00 2.72E+00 3.78E-02 2.22E+00 2.55E+00 NA NA NA MW-62-71 MW-62-71 006 71.1

-58.3 8/6/2008 11:42 4.64E+02 1.66E+02 2.53E+02 3.31E-01 2.60E-01 3.94E-01 5.85E-01 2.01E+00 3.53E+00

-4.96E-01 2.23E+00 3.66E+00 NA NA NA MW-62-71 MW-62-71 007 71.1

-58.3 10/29/2008 12:00 5.12E+02 1.70E+02 1.66E+02 3.70E-01 4.81E-01 5.03E-01

-2.34E+00 5.97E+00 6.37E+00

-1.31E+00 6.46E+00 7.00E+00 NA NA NA MW-62-71 MW-62-71 008 71.1

-58.3 1/23/2009 12:12 2.99E+02 2.07E+02 2.04E+02 2.47E-01 7.35E-01 8.56E-01 1.92E+00 3.53E+00 4.25E+00

-4.84E-01 3.87E+00 4.22E+00 NA NA NA MW-62-71 MW-62-71 009 71.1

-58.3 4/15/2009 12:06 4.78E+02 1.89E+02 1.38E+02 2.78E-01 6.38E-01 7.30E-01 1.27E+00 6.32E+00 4.21E+00 1.21E+00 3.48E+00 4.20E+00

-3.18E+00 1.88E+01 2.20E+01 MW-62-71 MW-62-71 010 71.1

-58.3 7/22/2009 12:52 3.52E+02 2.31E+02 2.32E+02 5.54E-01 7.87E-01 8.69E-01

-1.08E+00 3.46E+00 3.75E+00 8.91E-01 3.86E+00 4.50E+00 NA NA NA MW-62-71 MW-62-71 011 71.1

-58.3 11/12/2009 12:40 4.68E+02 1.24E+02 1.02E+02 3.02E-01 6.66E-01 7.57E-01 2.35E+00 5.28E+00 6.35E+00

-1.57E+00 6.35E+00 6.71E+00 NA NA NA MW-62-71 MW-62-71 012 71.1

-58.3 2/9/2010 13:20 4.56E+02 2.00E+02 1.99E+02 4.07E-01 4.74E-01 4.89E-01 4.29E+00 5.40E+00 6.65E+00

-2.86E+00 5.37E+00 5.09E+00 NA NA NA MW-62-71 MW-62-71 013 71.1

-58.3 4/13/2010 13:45 3.77E+02 2.16E+02 2.30E+02

-2.24E-01 5.64E-01 8.12E-01

-6.51E-01 4.44E+00 4.86E+00

-3.24E+00 5.89E+00 4.62E+00 NA NA NA MW-62-71 MW-62-71 014 71.1

-58.3 8/3/2010 11:30 3.25E+02 1.70E+02 1.77E+02 2.44E-01 3.75E-01 4.12E-01

-2.03E+00 8.37E+00 8.99E+00 1.86E+00 9.87E+00 1.16E+01 NA NA NA MW-62-71 MW-62-71 015 71.1

-58.3 11/9/2010 11:02 4.17E+02 1.83E+02 3.82E+02

-6.74E-02 6.02E-01 1.52E+00

-6.58E-01 3.90E+00 8.41E+00

-4.59E+00 5.63E+00 1.09E+01 NA NA NA MW-62-71 MW-62-71 016 71.1

-58.3 2/24/2011 12:40 5.38E+02 4.06E+02 4.03E+02 1.28E-01 1.22E+00 1.48E+00 4.10E+00 1.18E+01 6.67E+00

-2.36E-01 5.00E+00 5.47E+00 NA NA NA MW-62-71 MW-62-71 017 71.1

-58.3 4/13/2011 11:15 3.39E+02 4.72E+02 5.08E+02 9.04E-01 1.45E+00 1.58E+00 2.33E+00 7.96E+00 9.27E+00

-2.38E+00 8.50E+00 8.56E+00 NA NA NA MW-62-71 MW-62-71 018 71.1

-58.3 7/22/2011 10:12 4.21E+02 4.26E+02 4.44E+02

-3.90E-01 1.36E+00 1.90E+00

-7.29E-02 7.74E+00 8.31E+00

-7.90E-01 8.28E+00 8.59E+00

-6.70E+00 1.89E+01 2.13E+01 MW-62-71 MW-62-71 019 71.1

-58.3 8/3/2011 11:58 5.14E+02 3.69E+02 3.07E+02 3.49E-01 1.39E+00 1.65E+00

-7.31E-01 1.01E+01 1.10E+01 2.51E+00 1.04E+01 1.20E+01 NA NA NA MW-62-71 MW-62-71 020 71.1

-58.3 10/21/2011 9:44 4.68E+02 3.36E+02 3.42E+02

-1.43E-01 1.29E+00 1.69E+00 8.75E-01 9.06E+00 1.13E+01 2.06E+00 9.84E+00 1.32E+01 NA NA NA MW-62-71 MW-62-92 001 91.6

-78.8 5/10/2007 11:18 7.00E+02 2.16E+02 1.68E+02 7.11E-01 9.21E-01 9.85E-01

-1.58E+00 4.63E+00 3.30E+00 7.45E-01 3.12E+00 3.72E+00

-7.73E+00 1.30E+01 1.65E+01 MW-62-92 MW-62-92 002 91.6

-78.8 7/26/2007 12:35 4.37E+02 2.07E+02 1.80E+02

-2.28E-02 3.39E-01 3.94E-01 6.50E-01 3.15E+00 3.63E+00 8.32E-01 3.38E+00 3.95E+00 NA NA NA MW-62-92 MW-62-92 003 91.6

-78.8 10/10/2007 12:15 4.28E+02 1.73E+02 1.50E+02

-1.91E-01 4.77E-01 6.54E-01 6.23E-01 1.88E+00 2.01E+00 1.85E+00 1.80E+00 2.21E+00 NA NA NA MW-62-92 MW-62-92 004 91.6

-78.8 1/10/2008 11:09 3.94E+02 1.92E+02 1.94E+02 1.38E-01 6.59E-01 7.90E-01 3.75E-01 2.94E+00 3.39E+00 9.37E-01 3.47E+00 3.62E+00 NA NA NA MW-62-92 MW-62-92 006 91.6

-78.8 8/6/2008 11:49 4.95E+02 1.59E+02 2.38E+02 2.43E-01 3.29E-01 5.64E-01 1.51E+00 2.29E+00 4.11E+00 5.16E+00 2.59E+00 5.35E+00 NA NA NA MW-62-92 MW-62-92 007 91.6

-78.8 10/29/2008 12:10 4.82E+02 1.68E+02 1.66E+02

-4.52E-02 5.40E-01 7.12E-01 1.64E+00 6.57E+00 7.61E+00 2.71E+00 6.33E+00 7.68E+00 NA NA NA MW-62-92 MW-62-92 008 91.6

-78.8 1/23/2009 12:28 5.25E+02 2.33E+02 2.05E+02

-1.59E-01 6.86E-01 8.73E-01 2.90E-01 4.58E+00 4.83E+00 1.88E+00 3.83E+00 4.74E+00 NA NA NA MW-62-92 MW-62-92 009 91.6

-78.8 4/15/2009 12:15 6.08E+02 2.06E+02 1.38E+02 1.09E-01 5.42E-01 6.60E-01 3.15E-01 6.21E+00 4.14E+00

-9.11E-01 3.36E+00 3.56E+00

-1.28E+01 1.83E+01 2.22E+01 MW-62-92 MW-62-92 010 91.6

-78.8 7/22/2009 11:37 2.80E+02 2.24E+02 2.32E+02 3.44E-02 6.37E-01 8.10E-01 8.43E-01 3.39E+00 3.96E+00

-9.42E-01 3.40E+00 3.57E+00 NA NA NA MW-62-92 MW-62-92 011 91.6

-78.8 11/12/2009 12:43 4.83E+02 1.25E+02 1.02E+02 3.91E-01 7.75E-01 8.76E-01 6.13E-01 5.25E+00 5.91E+00 2.98E-01 5.25E+00 5.86E+00 NA NA NA MW-62-92 MW-62-92 012 91.6

-78.8 2/9/2010 13:20 5.27E+02 2.03E+02 1.98E+02 4.06E-01 6.20E-01 6.83E-01

-2.81E+00 7.35E+00 6.45E+00 2.57E+00 6.50E+00 7.81E+00 NA NA NA MW-62-92 MW-62-92 013 91.6

-78.8 4/13/2010 13:38 5.96E+02 1.55E+02 1.44E+02 1.77E-01 6.88E-01 8.34E-01 1.16E+00 3.72E+00 4.24E+00 7.23E-03 3.75E+00 4.13E+00 NA NA NA MW-62-92 MW-62-92 014 91.6

-78.8 8/3/2010 11:32 3.18E+02 1.68E+02 1.76E+02 4.11E-01 5.37E-01 5.80E-01

-3.42E+00 8.13E+00 8.38E+00

-4.99E-01 7.59E+00 8.36E+00 NA NA NA MW-62-92 MW-62-92 015 91.6

-78.8 11/9/2010 11:15 4.82E+02 1.88E+02 3.86E+02

-9.75E-01 7.72E-01 1.95E+00

-2.96E+00 5.42E+00 1.17E+01 1.77E+00 4.84E+00 1.12E+01 NA NA NA MW-62-92 MW-62-92 016 91.6

-78.8 2/24/2011 12:39 5.09E+02 4.00E+02 4.02E+02 9.56E-01 1.85E+00 2.06E+00 1.68E+00 5.38E+00 6.27E+00

-1.45E+00 5.68E+00 5.86E+00 NA NA NA MW-62-92 MW-62-92 017 91.6

-78.8 4/13/2011 11:03 5.06E+02 4.78E+02 4.92E+02 2.87E-01 1.11E+00 1.30E+00

-2.87E+00 7.18E+00 7.31E+00

-2.10E+00 8.94E+00 8.88E+00 NA NA NA MW-62-92 MW-62-92 018 91.6

-78.8 7/22/2011 10:18 5.61E+02 4.35E+02 4.39E+02

-1.12E+00 1.52E+00 2.06E+00 5.26E+00 9.42E+00 1.13E+01

-7.24E-02 9.48E+00 1.05E+01

-6.69E+00 1.76E+01 1.99E+01 MW-62-92 MW-62-92 019 91.6

-78.8 8/3/2011 12:10 5.61E+02 3.78E+02 3.03E+02

-3.26E-01 1.09E+00 1.52E+00 3.82E+00 1.46E+01 9.22E+00

-5.05E+00 1.17E+01 1.15E+01 NA NA NA MW-62-92 MW-62-92 020 91.6

-78.8 10/21/2011 9:42 5.51E+02 3.45E+02 3.42E+02 4.45E-01 1.27E+00 1.48E+00 3.18E-01 9.39E+00 1.17E+01 1.88E-01 9.18E+00 1.22E+01 NA NA NA MW-62-92 MW-62-138 001 138.1

-125.3 5/10/2007 10:22 4.55E+02 1.98E+02 1.74E+02 8.19E-01 8.16E-01 8.00E-01 1.73E+00 4.17E+00 3.28E+00

-1.40E+00 3.42E+00 3.55E+00

-4.93E+00 1.32E+01 1.64E+01 MW-62-138 MW-62-138 002 138.1

-125.3 7/26/2007 15:55 5.38E+02 2.19E+02 1.82E+02 5.26E-01 5.79E-01 6.09E-01 6.88E-02 3.51E+00 3.98E+00 6.39E-01 3.93E+00 4.54E+00 NA NA NA MW-62-138 MW-62-138 003 138.1

-125.3 10/10/2007 14:46 7.78E+02 2.09E+02 1.54E+02 8.37E-01 8.30E-01 8.69E-01 0.00E+00 2.67E+00 2.90E+00

-1.19E+00 2.44E+00 2.50E+00 NA NA NA MW-62-138 MW-62-138 004 138.1

-125.3 1/10/2008 10:05 7.69E+02 1.82E+02 1.74E+02 7.34E-01 4.32E-01 3.52E-01 4.30E-01 3.36E+00 3.88E+00 1.05E-01 3.47E+00 3.91E+00 NA NA NA MW-62-138 MW-62-138 006 138.1

-125.3 8/6/2008 11:41 5.33E+02 1.55E+02 2.28E+02 1.21E+00 4.18E-01 5.01E-01 8.24E-01 2.44E+00 4.27E+00 3.85E-01 2.41E+00 4.20E+00 NA NA NA MW-62-138 MW-62-138 007 138.1

-125.3 10/29/2008 12:25 7.50E+02 1.82E+02 1.66E+02 1.24E+00 5.53E-01 3.58E-01 1.40E+00 6.06E+00 7.05E+00 2.04E+00 8.28E+00 8.60E+00 NA NA NA MW-62-138 MW-62-138 008 138.1

-125.3 1/23/2009 12:50 6.26E+02 2.43E+02 2.04E+02 2.46E+00 8.27E-01 6.23E-01

-4.23E-01 2.40E+00 2.67E+00 5.99E-01 2.24E+00 2.64E+00 NA NA NA MW-62-138 MW-62-138 009 138.1

-125.3 4/15/2009 12:38 7.72E+02 2.18E+02 1.32E+02 1.78E+00 8.70E-01 7.93E-01

-7.43E-01 6.18E+00 4.12E+00 4.95E-01 3.20E+00 3.73E+00 1.23E+00 1.83E+01 2.12E+01 MW-62-138 MW-62-138 010 138.1

-125.3 7/22/2009 16:55 6.31E+02 2.54E+02 2.29E+02 1.31E+00 7.83E-01 7.15E-01 1.86E+00 3.81E+00 4.50E+00 3.36E-01 3.63E+00 4.18E+00 NA NA NA MW-62-138 MW-62-138 011 138.1

-125.3 11/12/2009 15:11 5.76E+02 1.35E+02 1.07E+02 2.83E+00 7.98E-01 4.82E-01 1.05E+00 7.42E+00 8.36E+00 7.24E-02 7.92E+00 8.71E+00 NA NA NA MW-62-138 MW-62-138 012 138.1

-125.3 2/9/2010 15:54 7.81E+02 2.18E+02 1.99E+02 8.78E-01 6.50E-01 6.24E-01 2.22E+00 5.03E+00 6.09E+00

-3.56E+00 4.79E+00 4.02E+00 NA NA NA MW-62-138 MW-62-138 013 138.1

-125.3 4/13/2010 18:02 6.54E+02 1.59E+02 1.46E+02 1.28E+00 7.41E-01 6.91E-01

-7.33E-01 6.39E+00 5.98E+00

-2.36E+00 6.71E+00 5.83E+00 NA NA NA MW-62-138 MW-62-138 014 138.1

-125.3 8/3/2010 14:09 5.91E+02 1.82E+02 1.76E+02 1.47E+00 7.40E-01 6.56E-01 3.83E+00 7.26E+00 8.95E+00

-1.73E+00 7.35E+00 7.39E+00 NA NA NA MW-62-138 MW-62-138 015 138.1

-125.3 11/9/2010 14:31 3.31E+02 2.07E+02 4.46E+02

-1.05E-01 6.18E-01 1.57E+00

-1.42E+00 4.04E+00 8.57E+00 2.51E+00 4.68E+00 1.11E+01 NA NA NA MW-62-138 MW-62-138 016 138.1

-125.3 2/24/2011 14:54 5.17E+02 4.00E+02 4.01E+02 2.15E+00 1.77E+00 1.75E+00

-1.67E+00 4.72E+00 4.94E+00 1.88E+00 7.04E+00 8.19E+00 NA NA NA MW-62-138 MW-62-138 017 138.1

-125.3 4/13/2011 14:39 6.31E+02 5.04E+02 5.09E+02 1.22E+00 1.29E+00 1.32E+00 1.29E+00 9.08E+00 1.04E+01 1.71E+00 8.82E+00 1.02E+01 NA NA NA MW-62-138 MW-62-138 018 138.1

-125.3 7/22/2011 11:50 4.66E+02 4.23E+02 4.36E+02 6.72E-01 1.20E+00 1.32E+00

-5.97E-01 7.41E+00 8.13E+00 6.36E+00 9.57E+00 1.23E+01

-1.13E+01 1.79E+01 2.03E+01 MW-62-138 MW-62-138 019 138.1

-125.3 8/3/2011 10:08 1.42E+03 5.46E+02 3.34E+02 1.53E+00 1.69E+00 1.73E+00 2.51E-01 9.48E+00 1.05E+01 1.35E+00 8.40E+00 9.73E+00 NA NA NA MW-62-138 MW-62-138 020 138.1

-125.3 10/21/2011 11:29 3.01E+03 5.97E+02 2.36E+02 1.24E+00 1.48E+00 1.50E+00

-5.88E+00 1.01E+01 1.10E+01 2.45E-01 1.03E+01 1.33E+01 NA NA NA MW-62-138 MW-62-182 001 182.1

-169.3 5/10/2007 10:43 5.41E+02 2.09E+02 1.76E+02 1.22E-01 7.18E-01 8.90E-01 3.74E-02 3.50E+00 3.33E+00

-2.40E-01 3.23E+00 3.53E+00

-1.76E+00 1.24E+01 1.50E+01 MW-62-182 MW-62-182 002 182.1

-169.3 7/26/2007 16:20 4.17E+02 2.06E+02 1.82E+02

-9.56E-02 2.73E-01 3.26E-01

-1.16E+00 3.10E+00 3.25E+00 6.21E-01 2.70E+00 3.15E+00 NA NA NA MW-62-182

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 26 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-62-182 003 182.1

-169.3 10/10/2007 14:42 4.94E+02 1.83E+02 1.54E+02

-1.48E-01 4.40E-01 5.99E-01 6.04E-01 1.91E+00 1.91E+00 5.45E-01 1.92E+00 2.23E+00 NA NA NA MW-62-182 MW-62-182 004 182.1

-169.3 1/10/2008 11:15 4.70E+02 1.68E+02 1.71E+02 8.15E-02 5.13E-01 6.33E-01

-1.17E-01 2.96E+00 2.99E+00 9.22E-01 1.31E+00 2.33E+00 NA NA NA MW-62-182 MW-62-182 006 182.1

-169.3 8/6/2008 13:54 3.99E+02 1.52E+02 2.34E+02 5.30E-02 3.33E-01 6.16E-01 8.48E-01 2.19E+00 3.85E+00

-2.67E-01 2.40E+00 3.97E+00 NA NA NA MW-62-182 MW-62-182 007 182.1

-169.3 10/29/2008 15:52 4.98E+02 1.70E+02 1.66E+02 4.40E-02 7.13E-01 9.16E-01 1.60E+00 6.21E+00 6.92E+00 2.99E-01 5.82E+00 6.54E+00 NA NA NA MW-62-182 MW-62-182 008 182.1

-169.3 1/23/2009 13:49 4.98E+02 2.28E+02 2.03E+02

-1.85E-01 4.56E-01 6.98E-01

-1.91E+00 2.55E+00 2.68E+00

-1.03E+00 2.43E+00 2.55E+00 NA NA NA MW-62-182 MW-62-182 009 182.1

-169.3 4/15/2009 14:53 7.36E+02 2.21E+02 1.37E+02

-6.26E-01 7.43E-01 9.46E-01 2.06E-01 6.32E+00 4.21E+00 2.09E-01 4.55E+00 5.11E+00

-6.59E+00 1.83E+01 2.17E+01 MW-62-182 MW-62-182 010 182.1

-169.3 7/22/2009 17:00 4.66E+02 2.43E+02 2.33E+02 2.73E-01 8.22E-01 9.71E-01 5.02E-01 2.96E+00 3.47E+00

-9.12E-01 2.73E+00 2.70E+00 NA NA NA MW-62-182 MW-62-182 011 182.1

-169.3 11/12/2009 15:15 5.10E+02 1.27E+02 1.03E+02 1.53E-01 5.44E-01 6.32E-01

-3.06E+00 7.80E+00 8.09E+00 2.77E+00 6.00E+00 7.53E+00 NA NA NA MW-62-182 MW-62-182 012 182.1

-169.3 2/9/2010 16:07 4.69E+02 2.10E+02 2.10E+02

-2.03E-01 3.12E-01 4.91E-01 9.56E-01 5.40E+00 6.26E+00

-2.02E-01 5.46E+00 6.05E+00 NA NA NA MW-62-182 MW-62-182 013 182.1

-169.3 4/13/2010 18:18 4.77E+02 1.52E+02 1.46E+02 2.86E-01 6.55E-01 7.61E-01 9.81E-01 3.93E+00 4.57E+00 3.69E-01 4.09E+00 4.65E+00 NA NA NA MW-62-182 MW-62-182 014 182.1

-169.3 8/3/2010 14:02 2.78E+02 1.65E+02 1.75E+02 2.87E-01 7.05E-01 8.30E-01

-5.53E+00 1.24E+01 1.51E+01

-9.25E-01 8.00E+00 8.64E+00 NA NA NA MW-62-182 MW-62-182 015 182.1

-169.3 11/9/2010 14:43 4.76E+02 1.88E+02 3.87E+02 1.02E+00 6.77E-01 1.46E+00

-2.35E+00 4.16E+00 8.56E+00 1.99E+00 5.26E+00 1.21E+01 NA NA NA MW-62-182 MW-62-182 016 182.1

-169.3 2/24/2011 15:07 3.55E+02 3.84E+02 4.03E+02

-1.46E-01 1.45E+00 1.94E+00

-1.95E+00 6.24E+00 6.60E+00 5.86E-01 6.60E+00 7.33E+00 NA NA NA MW-62-182 MW-62-182 017 182.1

-169.3 4/13/2011 14:44 1.92E+02 4.50E+02 5.03E+02

-5.04E-01 1.05E+00 1.45E+00 5.54E+00 8.70E+00 1.09E+01

-9.44E-01 1.08E+01 1.15E+01 NA NA NA MW-62-182 MW-62-182 018 182.1

-169.3 7/22/2011 12:02 2.90E+02 4.20E+02 4.54E+02 2.09E-01 1.22E+00 1.47E+00 6.48E-01 7.41E+00 8.36E+00

-5.94E-01 7.65E+00 8.31E+00

-2.27E+00 1.56E+01 1.75E+01 MW-62-182 MW-62-182 019 182.1

-169.3 8/3/2011 10:20 5.84E+02 3.84E+02 3.05E+02 2.04E-01 1.47E+00 1.75E+00

-5.99E+00 1.25E+01 1.14E+01

-2.96E-01 1.13E+01 1.24E+01 NA NA NA MW-62-182 MW-62-182 020 182.1

-169.3 10/21/2011 11:37 6.88E+02 3.42E+02 3.27E+02

-2.48E-01 1.45E+00 1.90E+00

-4.81E+00 1.22E+01 1.34E+01

-1.67E+00 1.06E+01 1.27E+01 NA NA NA MW-62-182 MW-63-18 001 14.9 0.7 5/18/2007 10:35 2.30E+02 1.59E+02 1.57E+02 4.75E-02 5.37E-01 6.95E-01 8.56E-01 2.44E+00 2.67E+00 1.11E+00 2.65E+00 2.74E+00 7.36E+00 1.61E+01 1.82E+01 MW-63-18 MW-63-18 002 14.9 0.7 7/30/2007 13:10 2.00E+02 1.74E+02 1.89E+02

-2.18E-01 3.91E-01 4.68E-01 1.98E+00 2.65E+00 3.03E+00

-1.31E+00 2.50E+00 2.53E+00 NA NA NA MW-63-18 MW-63-18 003 14.9 0.7 10/11/2007 12:43 1.49E+02 1.56E+02 1.71E+02 3.08E-01 6.23E-01 7.12E-01 1.52E+00 2.63E+00 3.16E+00

-1.41E-01 2.52E+00 2.74E+00 NA NA NA MW-63-18 MW-63-18 004 14.9 0.7 1/9/2008 14:55 1.23E+02 1.56E+02 1.73E+02

-6.34E-02 5.55E-01 7.38E-01 2.55E+00 3.29E+00 3.42E+00 1.97E+00 2.94E+00 3.75E+00 NA NA NA MW-63-18 MW-63-18 005 14.9 0.7 4/23/2008 14:50 2.57E+02 1.53E+02 2.43E+02 2.31E-02 4.68E-01 8.62E-01 8.04E-01 2.35E+00 4.03E+00 7.68E-01 2.06E+00 3.69E+00 8.53E+00 1.43E+01 2.42E+01 MW-63-18 MW-63-18 006 14.9 0.7 7/30/2008 11:13 1.79E+02 1.20E+02 1.91E+02 3.29E+00 5.61E-01 4.68E-01

-1.71E-02 1.75E+00 2.97E+00

-1.16E+00 2.04E+00 2.49E+00 NA NA NA MW-63-18 MW-63-18 007 14.9 0.7 11/5/2008 10:53 3.20E+02 1.59E+02 1.65E+02 3.25E-01 6.20E-01 7.03E-01 1.31E-01 5.91E+00 6.75E+00

-1.52E+00 5.73E+00 6.04E+00 NA NA NA MW-63-18 MW-63-18 008 14.9 0.7 1/29/2009 13:46 1.54E+02 1.85E+02 1.98E+02

-2.22E-01 6.74E-01 8.57E-01 9.78E-02 2.64E+00 3.01E+00 1.02E+00 3.20E+00 3.87E+00 NA NA NA MW-63-18 MW-63-18 009 14.9 0.7 5/4/2009 12:29 1.97E+02 1.62E+02 1.64E+02 1.26E-01 6.00E-01 6.93E-01

-2.37E+00 6.86E+00 4.57E+00 8.34E-01 4.26E+00 4.94E+00 NA NA NA MW-63-18 MW-63-18 010 14.9 0.7 7/30/2009 14:26 3.80E+02 1.83E+02 1.89E+02

-2.47E-01 2.76E-01 4.70E-01 2.06E+00 5.42E+00 6.37E+00 4.32E-01 5.99E+00 6.85E+00 NA NA NA MW-63-18 MW-63-18 011 14.9 0.7 11/3/2009 12:19 1.24E+02 1.46E+02 1.61E+02

-2.75E-02 5.64E-01 7.37E-01

-6.29E-01 5.29E+00 5.78E+00 1.74E+00 7.20E+00 8.06E+00 NA NA NA MW-63-18 MW-63-18 012 14.9 0.7 2/8/2010 13:40 3.38E+02 1.68E+02 1.78E+02 5.39E-01 7.74E-01 8.34E-01 5.09E+00 4.35E+00 5.44E+00 4.46E-01 4.41E+00 5.00E+00 NA NA NA MW-63-18 MW-63-18 013 14.9 0.7 4/26/2010 13:22 3.16E+02 1.55E+02 1.47E+02

-7.37E-02 6.62E-01 8.66E-01 3.73E-01 5.22E+00 5.91E+00 3.24E+00 6.03E+00 7.50E+00 NA NA NA MW-63-18 MW-63-18 014 14.9 0.7 8/10/2010 12:08 1.62E+02 1.58E+02 1.73E+02

-1.55E-02 3.48E-01 4.72E-01

-6.04E-01 7.20E+00 8.11E+00

-2.17E+00 6.42E+00 6.45E+00 NA NA NA MW-63-18 MW-63-18 015 14.9 0.7 11/2/2010 12:22 1.97E+02 1.18E+02 1.13E+02 1.31E-01 6.87E-01 8.18E-01 1.81E+00 5.46E+00 6.40E+00 3.45E+00 6.55E+00 8.07E+00 NA NA NA MW-63-18 MW-63-18 016 14.9 0.7 3/2/2011 11:10 4.90E+02 3.58E+02 3.55E+02

-4.34E-01 1.50E+00 2.03E+00 1.82E+00 6.78E+00 7.90E+00 2.40E+00 7.38E+00 8.82E+00 NA NA NA MW-63-18 MW-63-18 017 14.9 0.7 4/19/2011 10:35 7.23E+01 4.38E+02 5.05E+02

-3.13E-01 1.13E+00 1.49E+00 8.69E-01 8.04E+00 8.92E+00

-3.22E+00 8.16E+00 7.75E+00 NA NA NA MW-63-18 MW-63-18 018 14.9 0.7 7/21/2011 10:26 2.96E+02 3.99E+02 4.29E+02 6.58E-02 1.19E+00 1.50E+00 2.40E+00 7.62E+00 9.09E+00 2.37E+00 7.53E+00 9.30E+00

-8.91E+00 1.69E+01 1.92E+01 MW-63-18 MW-63-18 019 14.9 0.7 8/3/2011 10:02 2.90E+02 3.15E+02 3.03E+02

-1.29E-01 1.20E+00 1.57E+00 1.70E+00 6.87E+00 7.90E+00 3.80E+00 8.58E+00 1.05E+01 NA NA NA MW-63-18 MW-63-18 020 14.9 0.7 10/18/2011 11:34 2.59E+02 2.34E+02 2.20E+02 1.26E+00 1.74E+00 1.83E+00 1.31E+00 8.28E+00 1.07E+01 1.72E+00 1.09E+01 1.44E+01 NA NA NA MW-63-18 MW-63-34 001 31.5

-17.3 5/18/2007 13:03 2.28E+02 1.58E+02 1.55E+02

-1.62E-01 5.43E-01 7.77E-01 4.10E-01 2.21E+00 2.51E+00

-3.25E-01 2.65E+00 2.44E+00 1.57E+00 1.54E+01 1.80E+01 MW-63-34 MW-63-34 002 31.5

-17.3 7/30/2007 13:28 2.80E+02 1.77E+02 1.90E+02

-1.64E-01 3.36E-01 4.03E-01 1.73E-01 3.66E+00 3.56E+00 3.98E-01 3.66E+00 4.24E+00 NA NA NA MW-63-34 MW-63-34 003 31.5

-17.3 10/11/2007 12:50 2.31E+02 1.61E+02 1.74E+02

-2.75E-01 4.44E-01 6.73E-01

-6.24E-01 3.60E+00 3.58E+00 3.81E-01 2.65E+00 3.10E+00 NA NA NA MW-63-34 MW-63-34 004 31.5

-17.3 1/9/2008 14:20 3.26E+02 1.65E+02 1.71E+02 1.24E-01 5.57E-01 6.84E-01 1.83E+00 3.63E+00 4.44E+00 3.53E-01 3.90E+00 4.35E+00 NA NA NA MW-63-34 MW-63-34 005 31.5

-17.3 4/23/2008 13:55 4.90E+02 1.68E+02 2.45E+02 3.82E-01 5.68E-01 9.89E-01 1.71E+00 2.05E+00 3.78E+00

-1.77E+00 3.53E+00 4.19E+00 5.77E+00 1.46E+01 2.49E+01 MW-63-34 MW-63-34 006 31.5

-17.3 7/30/2008 11:12 4.41E+02 1.39E+02 1.91E+02 1.15E+00 4.60E-01 6.45E-01

-1.48E-02 2.26E+00 3.87E+00

-7.91E-01 2.52E+00 3.65E+00 NA NA NA MW-63-34 MW-63-34 007 31.5

-17.3 11/5/2008 11:03 4.14E+02 3.77E+02 3.85E+02 3.15E-01 6.77E-01 7.78E-01 5.73E-01 5.43E+00 6.10E+00

-1.40E-01 5.17E+00 5.67E+00 NA NA NA MW-63-34 MW-63-34 008 31.5

-17.3 1/29/2009 12:22 4.20E+02 2.22E+02 1.96E+02 2.20E-01 6.87E-01 8.13E-01 1.41E+00 2.91E+00 3.45E+00

-2.64E-01 2.96E+00 3.23E+00 NA NA NA MW-63-34 MW-63-34 009 31.5

-17.3 5/4/2009 12:10 3.23E+02 1.76E+02 1.59E+02 2.16E-01 6.03E-01 6.89E-01 6.53E-01 7.29E+00 4.86E+00 1.92E+00 3.42E+00 4.32E+00 NA NA NA MW-63-34 MW-63-34 010 31.5

-17.3 7/30/2009 14:00 3.37E+02 1.80E+02 1.88E+02 2.57E-01 5.50E-01 6.37E-01 6.62E-01 5.50E+00 5.65E+00 1.70E+00 5.49E+00 6.42E+00 NA NA NA MW-63-34 MW-63-34 011 31.5

-17.3 11/3/2009 11:02 3.10E+02 1.55E+02 1.62E+02

-3.73E-01 4.06E-01 6.81E-01

-6.69E-02 8.31E+00 9.16E+00 8.03E-01 5.76E+00 6.76E+00 NA NA NA MW-63-34 MW-63-34 012 31.5

-17.3 2/8/2010 13:19 3.96E+02 1.70E+02 1.78E+02 2.26E-01 6.78E-01 8.09E-01

-6.36E-01 3.94E+00 4.33E+00

-8.85E-01 4.26E+00 4.66E+00 NA NA NA MW-63-34 MW-63-34 013 31.5

-17.3 4/26/2010 13:21 2.89E+02 1.53E+02 1.47E+02

-3.04E-01 7.18E-01 9.93E-01

-5.64E-01 5.55E+00 5.88E+00

-1.09E+00 5.19E+00 5.37E+00 NA NA NA MW-63-34 MW-63-34 014 31.5

-17.3 8/10/2010 11:44 1.89E+02 1.64E+02 1.78E+02 2.21E-01 3.59E-01 3.95E-01 2.60E+00 9.29E+00 1.06E+01 3.10E+00 7.21E+00 9.27E+00 NA NA NA MW-63-34 MW-63-34 015 31.5

-17.3 11/2/2010 13:04 3.41E+02 1.35E+02 1.14E+02 3.11E-01 5.72E-01 6.45E-01 1.16E-01 5.66E+00 6.29E+00

-2.31E+00 6.33E+00 6.51E+00 NA NA NA MW-63-34 MW-63-34 016 31.5

-17.3 3/2/2011 10:50 2.98E+02 2.86E+02 2.62E+02

-4.29E-01 1.57E+00 2.11E+00 7.43E-02 7.96E+00 8.82E+00

-2.10E+00 8.42E+00 8.59E+00 NA NA NA MW-63-34 MW-63-34 017 31.5

-17.3 4/19/2011 10:25 3.94E+02 4.60E+02 4.87E+02

-1.13E+00 1.22E+00 1.83E+00 4.36E+00 8.34E+00 9.94E+00 3.72E+00 8.28E+00 1.02E+01 NA NA NA MW-63-34 MW-63-34 018 31.5

-17.3 7/21/2011 10:08 3.04E+02 4.08E+02 4.39E+02 2.38E-01 1.17E+00 1.42E+00

-1.34E+00 9.03E+00 9.54E+00 1.66E-01 7.89E+00 8.63E+00

-1.26E+01 1.28E+01 1.47E+01 MW-63-34 MW-63-34 019 31.5

-17.3 8/3/2011 10:14 3.61E+02 3.30E+02 3.02E+02 1.90E-01 1.37E+00 1.66E+00 8.99E+00 9.09E+00 1.15E+01

-7.29E-01 8.16E+00 8.53E+00 NA NA NA MW-63-34 MW-63-34 020 31.5

-17.3 10/18/2011 11:39 4.30E+02 3.36E+02 3.46E+02

-4.71E-01 1.27E+00 1.78E+00

-3.77E+00 8.31E+00 9.14E+00 2.21E+00 7.62E+00 1.11E+01 NA NA NA MW-63-34 MW-63-50 001 49.5

-37.2 5/15/2007 11:48 3.26E+02 1.83E+02 1.73E+02

-9.70E-02 6.15E-01 8.32E-01

-1.33E-01 5.28E+00 5.01E+00 6.64E-01 4.23E+00 4.81E+00

-2.41E+00 1.24E+01 1.51E+01 MW-63-50 MW-63-50 002 49.5

-37.2 7/25/2007 14:00 2.25E+02 1.80E+02 1.95E+02 1.29E-01 6.03E-01 6.84E-01 2.08E+00 3.18E+00 3.90E+00

-1.58E-01 3.19E+00 3.54E+00 NA NA NA MW-63-50 MW-63-50 003 49.5

-37.2 10/11/2007 11:10 2.89E+02 1.62E+02 1.73E+02

-3.41E-01 5.10E-01 7.67E-01 6.21E-01 2.98E+00 3.39E+00 1.56E+00 3.17E+00 3.86E+00 NA NA NA MW-63-50 MW-63-50 004 49.5

-37.2 1/9/2008 12:32 3.56E+02 1.67E+02 1.72E+02 4.48E-01 7.41E-01 8.26E-01 3.37E-01 2.66E+00 3.02E+00

-1.42E+00 3.14E+00 3.20E+00 NA NA NA MW-63-50 MW-63-50 005 49.5

-37.2 4/23/2008 13:04 2.70E+02 1.63E+02 2.65E+02 4.27E-01 5.45E-01 9.26E-01

-1.10E+00 1.85E+00 2.93E+00 9.01E-01 1.75E+00 3.27E+00 2.43E+00 1.40E+01 2.41E+01 MW-63-50 MW-63-50 006 49.5

-37.2 7/30/2008 10:29 3.35E+02 1.32E+02 1.91E+02 6.10E-01 4.97E-01 8.02E-01

-1.77E+00 1.83E+00 2.66E+00

-1.22E+00 1.91E+00 2.80E+00 NA NA NA MW-63-50 MW-63-50 007 49.5

-37.2 11/5/2008 9:39 3.17E+02 1.94E+02 1.99E+02 5.67E-01 6.58E-01 6.79E-01 1.26E+00 6.36E+00 7.04E+00

-7.21E-01 6.52E+00 7.08E+00 NA NA NA MW-63-50 MW-63-50 008 49.5

-37.2 1/29/2009 14:06 2.98E+02 2.04E+02 1.96E+02 5.67E-01 8.00E-01 8.76E-01 8.89E-02 3.09E+00 3.51E+00 1.37E+00 3.41E+00 4.19E+00 NA NA NA MW-63-50 MW-63-50 009 49.5

-37.2 5/4/2009 11:31 3.30E+02 1.80E+02 1.65E+02 1.58E-01 5.73E-01 6.59E-01 1.22E+00 6.27E+00 4.18E+00

-2.49E-01 3.98E+00 4.34E+00 NA NA NA MW-63-50 MW-63-50 010 49.5

-37.2 7/30/2009 11:05 3.35E+02 1.80E+02 1.87E+02 5.40E-01 5.84E-01 5.81E-01 2.00E+00 6.27E+00 7.39E+00 1.36E+00 6.63E+00 7.71E+00 NA NA NA MW-63-50 MW-63-50 011 49.5

-37.2 11/3/2009 10:42 3.60E+02 1.58E+02 1.61E+02

-5.37E-03 5.31E-01 6.94E-01 2.14E-01 6.81E+00 7.54E+00

-1.30E+00 7.20E+00 7.57E+00 NA NA NA MW-63-50 MW-63-50 012 49.5

-37.2 2/8/2010 12:45 3.34E+02 1.67E+02 1.77E+02 5.42E-01 7.40E-01 7.92E-01

-1.46E+00 3.25E+00 3.55E+00 7.99E-01 3.33E+00 3.81E+00 NA NA NA MW-63-50 MW-63-50 013 49.5

-37.2 4/26/2010 12:06 4.13E+02 1.62E+02 1.45E+02 2.38E-01 5.82E-01 6.82E-01

-5.57E+00 1.01E+01 1.12E+01

-4.30E+00 6.74E+00 6.45E+00 NA NA NA MW-63-50 MW-63-50 014 49.5

-37.2 8/10/2010 14:32 2.72E+02 1.65E+02 1.75E+02

-2.47E-02 5.47E-01 6.90E-01

-1.32E+00 7.10E+00 7.82E+00 7.73E-01 7.74E+00 8.96E+00 NA NA NA MW-63-50 MW-63-50 015 49.5

-37.2 11/2/2010 15:07 3.29E+02 1.31E+02 1.12E+02 2.27E-01 6.23E-01 7.23E-01

-2.98E-02 7.72E+00 8.42E+00 2.76E+00 8.00E+00 9.78E+00 NA NA NA MW-63-50 MW-63-50 016 49.5

-37.2 3/2/2011 14:21 4.35E+02 3.40E+02 3.44E+02 1.73E-01 1.62E+00 2.03E+00 1.13E+00 6.50E+00 7.48E+00 3.64E+00 7.02E+00 8.70E+00 NA NA NA MW-63-50 MW-63-50 017 49.5

-37.2 4/19/2011 11:25 1.68E+02 4.36E+02 4.89E+02 7.72E-01 1.39E+00 1.53E+00

-6.46E+00 9.76E+00 9.29E+00 3.72E+00 8.18E+00 1.03E+01 NA NA NA MW-63-50 MW-63-50 018 49.5

-37.2 7/21/2011 11:25 2.09E+02 3.99E+02 4.41E+02

-6.50E-01 8.58E-01 1.39E+00 2.46E-01 7.56E+00 8.55E+00 2.77E+00 8.64E+00 1.05E+01

-2.89E+00 1.51E+01 1.69E+01 MW-63-50 MW-63-50 019 49.5

-37.2 8/3/2011 11:38 3.50E+02 3.33E+02 3.09E+02

-8.45E-01 1.10E+00 1.60E+00 8.12E+00 1.18E+01 1.44E+01 4.49E+00 8.52E+00 1.14E+01 NA NA NA MW-63-50

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 27 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-63-50 020 49.5

-37.2 10/18/2011 13:55 3.14E+02 3.63E+02 3.85E+02 4.62E-01 1.68E+00 1.94E+00

-9.09E-01 1.09E+01 1.29E+01

-2.69E+00 1.09E+01 1.34E+01 NA NA NA MW-63-50 MW-63-93 001 93

-80.7 10/2/2006 13:10 5.16E+02 1.95E+02 5.70E+01 7.81E-02 6.73E-01 7.32E-01 5.46E-01 1.43E+01 1.59E+01

-4.42E+00 1.67E+01 2.03E+01

-5.31E+00 1.23E+01 1.54E+01 MW-63-93 MW-63-93 002 93

-80.7 5/15/2007 12:45 2.81E+02 1.80E+02 1.75E+02 8.20E-02 7.29E-01 9.24E-01 1.87E-01 4.80E+00 4.60E+00 9.57E-01 4.54E+00 4.51E+00 NA NA NA MW-63-93 MW-63-93 003 93

-80.7 7/25/2007 14:34 2.37E+02 1.82E+02 1.97E+02

-4.43E-01 4.41E-01 5.29E-01 1.24E+00 3.31E+00 3.90E+00 9.28E-03 3.75E+00 4.16E+00 NA NA NA MW-63-93 MW-63-93 004 93

-80.7 10/11/2007 11:17 1.15E+02 1.55E+02 1.72E+02 8.19E-01 8.90E-01 9.47E-01

-6.98E-01 2.97E+00 3.16E+00

-1.77E+00 3.33E+00 3.23E+00 NA NA NA MW-63-93 MW-63-93 005 93

-80.7 1/9/2008 12:46 2.15E+02 1.59E+02 1.71E+02 1.86E-01 7.08E-01 8.45E-01 7.74E-01 3.06E+00 3.56E+00 1.05E-01 3.20E+00 3.58E+00 NA NA NA MW-63-93 MW-63-93 005 93

-80.7 4/23/2008 11:23 3.02E+02 1.65E+02 2.65E+02 2.93E-01 5.46E-01 9.39E-01 3.49E-01 2.27E+00 3.88E+00 7.04E-01 2.41E+00 4.14E+00

-3.72E+00 1.41E+01 2.46E+01 MW-63-93 MW-63-93 007 93

-80.7 7/29/2008 14:17 2.38E+02 1.25E+02 1.92E+02 2.28E-03 2.21E-01 3.86E-01

-4.02E-01 2.01E+00 3.36E+00

-3.19E-01 1.96E+00 3.23E+00 NA NA NA MW-63-93 MW-63-93 008 93

-80.7 11/5/2008 10:14 3.90E+02 3.75E+02 3.86E+02

-9.77E-02 1.94E-01 2.36E-01 1.53E+00 5.10E+00 5.92E+00 2.80E+00 6.24E+00 7.60E+00 NA NA NA MW-63-93 MW-63-93 009 93

-80.7 1/29/2009 14:20 3.40E+02 2.09E+02 1.93E+02 1.18E-01 6.33E-01 7.75E-01

-9.44E-01 3.17E+00 3.42E+00

-8.17E-01 3.63E+00 3.88E+00 NA NA NA MW-63-93 MW-63-93 010 93

-80.7 5/4/2009 12:00 1.66E+02 1.59E+02 1.64E+02 5.44E-01 5.13E-01 5.53E-01 2.00E+00 6.72E+00 4.48E+00

-1.69E+00 3.63E+00 3.63E+00 NA NA NA MW-63-93 MW-63-93 011 93

-80.7 7/30/2009 11:30 2.64E+02 1.77E+02 1.88E+02 1.81E-01 3.63E-01 4.15E-01 2.45E+00 5.54E+00 6.51E+00 3.68E-01 5.66E+00 6.36E+00 NA NA NA MW-63-93 MW-63-93 012 93

-80.7 11/3/2009 10:55 3.01E+02 1.53E+02 1.61E+02 7.11E-01 7.17E-01 7.57E-01

-2.46E+00 4.82E+00 5.00E+00 5.40E-01 4.70E+00 5.26E+00 NA NA NA MW-63-93 MW-63-93 013 93

-80.7 2/8/2010 13:00 2.90E+02 1.65E+02 1.77E+02 1.78E-01 6.63E-01 8.06E-01

-1.10E+00 4.41E+00 4.71E+00 5.93E-01 4.54E+00 5.11E+00 NA NA NA MW-63-93 MW-63-93 014 93

-80.7 4/26/2010 12:42 3.03E+02 1.55E+02 1.47E+02

-2.90E-02 5.61E-01 7.42E-01

-6.91E-01 5.55E+00 6.23E+00

-3.69E+00 5.52E+00 5.35E+00 NA NA NA MW-63-93 MW-63-93 015 93

-80.7 8/10/2010 15:10 1.95E+02 1.61E+02 1.74E+02

-1.91E-01 4.38E-01 6.16E-01 1.24E+00 6.64E+00 7.70E+00 2.61E-01 7.58E+00 8.46E+00 NA NA NA MW-63-93 MW-63-93 016 93

-80.7 11/2/2010 15:08 2.39E+02 1.21E+02 1.11E+02 3.29E-01 5.72E-01 6.42E-01

-4.18E-02 4.95E+00 5.64E+00 3.38E+00 5.80E+00 7.11E+00 NA NA NA MW-63-93 MW-63-93 017 93

-80.7 3/2/2011 14:14 2.69E+02 3.00E+02 2.94E+02 3.30E-01 1.79E+00 2.17E+00

-1.51E+00 8.78E+00 9.05E+00 3.38E+00 7.56E+00 9.56E+00 NA NA NA MW-63-93 MW-63-93 018 93

-80.7 4/19/2011 11:27 9.64E+01 4.42E+02 5.05E+02

-4.30E-02 1.14E+00 1.44E+00 3.31E+00 8.92E+00 1.03E+01

-4.35E-01 6.80E+00 7.25E+00 NA NA NA MW-63-93 MW-63-93 019 93

-80.7 7/21/2011 11:32 4.17E+02 4.20E+02 4.40E+02

-4.28E-01 1.06E+00 1.48E+00

-3.58E+00 8.10E+00 7.77E+00

-6.11E+00 7.92E+00 5.51E+00 6.50E-01 1.71E+01 1.90E+01 MW-63-93 MW-63-93 020 93

-80.7 8/3/2011 11:50 1.84E+02 3.12E+02 3.38E+02 4.25E-02 1.31E+00 1.63E+00 1.61E+00 7.26E+00 7.83E+00

-2.65E+00 7.71E+00 8.38E+00 NA NA NA MW-63-93 MW-63-93 021 93

-80.7 10/18/2011 14:14 5.04E+02 3.78E+02 3.83E+02 5.60E-01 1.37E+00 1.56E+00 7.43E-01 6.45E+00 8.33E+00 3.55E+00 6.87E+00 1.02E+01 NA NA NA MW-63-93 MW-63-112 001 111.5

-99.2 5/15/2007 13:10 4.24E+02 1.95E+02 1.75E+02

-5.27E-02 7.50E-01 9.42E-01 2.58E+00 3.90E+00 3.59E+00 9.59E-01 3.72E+00 4.19E+00

-5.14E+00 1.34E+01 1.55E+01 MW-63-112 MW-63-112 002 111.5

-99.2 7/25/2007 14:52 2.69E+02 1.83E+02 1.97E+02 6.32E-02 3.46E-01 3.99E-01 6.92E-01 4.14E+00 4.19E+00

-6.35E-01 3.94E+00 4.34E+00 NA NA NA MW-63-112 MW-63-112 003 111.5

-99.2 10/11/2007 13:45 2.78E+02 1.62E+02 1.72E+02

-7.94E-02 6.73E-01 8.71E-01

-3.04E+00 5.49E+00 4.52E+00 7.65E-01 3.50E+00 4.15E+00 NA NA NA MW-63-112 MW-63-112 004 111.5

-99.2 1/9/2008 10:20 4.69E+02 1.73E+02 1.72E+02 2.19E-01 5.07E-01 5.92E-01 3.90E-01 3.30E+00 3.34E+00 2.87E-01 3.56E+00 3.75E+00 NA NA NA MW-63-112 MW-63-112 005 111.5

-99.2 4/23/2008 11:08 3.72E+02 1.68E+02 2.65E+02

-3.90E-02 3.96E-01 7.94E-01 4.77E-01 2.30E+00 3.89E+00 1.75E+00 2.78E+00 4.52E+00

-5.00E-01 1.43E+01 2.48E+01 MW-63-112 MW-63-112 006 111.5

-99.2 7/29/2008 14:20 2.07E+02 1.01E+02 1.63E+02 7.08E-01 5.39E-01 8.66E-01 6.61E-01 2.23E+00 3.89E+00 1.07E+00 2.46E+00 4.41E+00 NA NA NA MW-63-112 MW-63-112 007 111.5

-99.2 11/4/2008 12:41 2.75E+02 1.92E+02 2.01E+02 4.72E-01 5.88E-01 6.17E-01 1.89E-01 5.68E+00 6.43E+00

-2.75E+00 8.34E+00 7.58E+00 NA NA NA MW-63-112 MW-63-112 008 111.5

-99.2 1/30/2009 14:39 4.37E+02 2.21E+02 1.97E+02 2.43E-02 7.80E-01 9.24E-01

-1.10E+00 2.81E+00 2.86E+00 1.77E+00 3.41E+00 4.13E+00 NA NA NA MW-63-112 MW-63-112 009 111.5

-99.2 5/4/2009 14:30 4.42E+02 1.94E+02 1.64E+02 1.54E-01 5.99E-01 7.38E-01

-2.30E+00 6.18E+00 4.12E+00 1.38E+00 3.93E+00 4.71E+00 NA NA NA MW-63-112 MW-63-112 010 111.5

-99.2 7/30/2009 13:54 4.64E+02 1.88E+02 1.89E+02 1.50E-01 5.70E-01 6.78E-01

-5.23E+00 7.61E+00 7.36E+00 4.44E+00 6.98E+00 8.68E+00 NA NA NA MW-63-112 MW-63-112 011 111.5

-99.2 11/3/2009 11:17 4.96E+02 1.62E+02 1.61E+02 5.07E-01 8.31E-01 9.25E-01 4.38E-01 6.15E+00 6.86E+00

-4.82E+00 7.04E+00 6.72E+00 NA NA NA MW-63-112 MW-63-112 012 111.5

-99.2 2/8/2010 13:14 3.80E+02 1.70E+02 1.79E+02 6.50E-01 7.23E-01 7.33E-01

-6.93E-01 3.86E+00 4.28E+00

-2.22E+00 5.70E+00 4.89E+00 NA NA NA MW-63-112 MW-63-112 013 111.5

-99.2 4/26/2010 12:39 4.47E+02 1.64E+02 1.42E+02 4.81E-01 5.84E-01 6.06E-01 4.15E+00 6.75E+00 8.37E+00 4.44E+00 7.86E+00 9.87E+00 NA NA NA MW-63-112 MW-63-112 014 111.5

-99.2 8/10/2010 14:52 3.71E+02 1.73E+02 1.78E+02 2.83E-01 4.37E-01 4.78E-01

-3.00E+00 7.68E+00 7.90E+00

-5.28E+00 9.73E+00 9.11E+00 NA NA NA MW-63-112 MW-63-112 015 111.5

-99.2 11/2/2010 15:05 3.01E+02 1.29E+02 1.13E+02 6.02E-02 5.25E-01 6.51E-01

-2.54E+00 6.29E+00 6.56E+00 1.96E+00 6.72E+00 7.95E+00 NA NA NA MW-63-112 MW-63-112 016 111.5

-99.2 3/2/2011 14:15 3.38E+02 3.18E+02 2.96E+02 1.48E-01 1.60E+00 2.00E+00

-3.72E-01 6.70E+00 7.21E+00 1.19E+00 6.36E+00 7.21E+00 NA NA NA MW-63-112 MW-63-112 017 111.5

-99.2 4/19/2011 11:25 4.22E+02 4.68E+02 4.92E+02

-7.96E-01 1.00E+00 1.47E+00 4.96E+00 1.05E+01 1.25E+01 1.64E+00 1.17E+01 1.36E+01 NA NA NA MW-63-112 MW-63-112 018 111.5

-99.2 7/21/2011 11:46 6.01E+02 4.44E+02 4.44E+02 2.29E-01 1.13E+00 1.37E+00

-8.46E-01 1.06E+01 1.11E+01 6.03E+00 1.21E+01 1.54E+01

-1.22E+00 1.77E+01 1.98E+01 MW-63-112 MW-63-112 019 111.5

-99.2 8/3/2011 12:01 8.82E+02 4.59E+02 3.36E+02

-1.83E-01 1.31E+00 1.67E+00 2.07E+00 7.35E+00 8.45E+00

-2.13E+00 7.26E+00 7.10E+00 NA NA NA MW-63-112 MW-63-112 020 111.5

-99.2 10/18/2011 14:20 1.34E+03 5.43E+02 3.29E+02

-5.35E-01 1.39E+00 1.87E+00

-1.39E+00 7.53E+00 8.79E+00 1.78E+00 7.02E+00 9.82E+00 NA NA NA MW-63-112 MW-63-121 001 121

-108.7 5/15/2007 13:42 3.11E+02 1.83E+02 1.75E+02 3.00E-01 7.97E-01 9.37E-01 6.30E-01 4.25E+00 4.20E+00

-1.19E+00 3.65E+00 3.87E+00 2.29E+00 1.52E+01 1.77E+01 MW-63-121 MW-63-121 002 121

-108.7 7/25/2007 11:50 2.96E+02 1.82E+02 1.94E+02 3.19E-01 5.31E-01 5.93E-01

-1.31E+00 3.29E+00 3.46E+00 1.70E-01 3.46E+00 3.87E+00 NA NA NA MW-63-121 MW-63-121 003 121

-108.7 10/11/2007 13:51 4.62E+02 1.70E+02 1.74E+02 2.39E-01 6.25E-01 7.37E-01 2.48E+00 4.51E+00 4.94E+00 1.54E+00 4.00E+00 4.54E+00 NA NA NA MW-63-121 MW-63-121 004 121

-108.7 1/9/2008 10:42 5.40E+02 1.74E+02 1.71E+02 2.06E-02 4.70E-01 6.09E-01 2.54E+00 3.38E+00 4.15E+00 1.09E+00 3.41E+00 4.02E+00 NA NA NA MW-63-121 MW-63-121 005 121

-108.7 4/23/2008 11:17 4.54E+02 1.34E+02 1.98E+02 5.36E-01 4.94E-01 8.04E-01

-3.56E-01 9.40E-01 1.55E+00

-1.33E+00 2.71E+00 1.81E+00

-3.22E+00 1.41E+01 2.46E+01 MW-63-121 MW-63-121 006 121

-108.7 7/29/2008 14:30 3.44E+02 1.04E+02 1.61E+02 7.60E-01 3.83E-01 5.73E-01 2.86E-01 2.08E+00 3.57E+00 1.23E+00 2.30E+00 4.11E+00 NA NA NA MW-63-121 MW-63-121 007 121

-108.7 11/4/2008 12:43 4.95E+02 2.06E+02 1.98E+02 3.81E-01 7.52E-01 8.55E-01

-7.97E-01 5.42E+00 5.97E+00 1.20E+00 6.38E+00 7.41E+00 NA NA NA MW-63-121 MW-63-121 008 121

-108.7 1/30/2009 14:41 6.23E+02 2.42E+02 1.97E+02 7.30E-01 5.09E-01 4.47E-01 1.91E+00 3.18E+00 3.92E+00 9.14E-01 2.84E+00 3.45E+00 NA NA NA MW-63-121 MW-63-121 009 121

-108.7 5/4/2009 14:35 5.38E+02 2.04E+02 1.65E+02 7.71E-01 8.55E-01 9.23E-01

-6.65E-02 8.16E+00 5.44E+00 2.35E+00 4.29E+00 5.35E+00 NA NA NA MW-63-121 MW-63-121 010 121

-108.7 7/30/2009 14:03 4.66E+02 1.88E+02 1.89E+02 5.21E-01 5.49E-01 5.66E-01 1.05E+00 4.89E+00 5.53E+00

-2.66E+00 6.67E+00 5.19E+00 NA NA NA MW-63-121 MW-63-121 011 121

-108.7 11/3/2009 11:46 5.01E+02 1.64E+02 1.61E+02 5.66E-01 8.73E-01 9.67E-01

-5.33E+00 9.88E+00 8.44E+00

-2.07E+00 9.35E+00 8.77E+00 NA NA NA MW-63-121 MW-63-121 012 121

-108.7 2/8/2010 13:18 5.15E+02 1.74E+02 1.77E+02 3.18E-01 6.45E-01 7.40E-01

-2.07E-01 3.92E+00 4.30E+00

-2.48E-01 5.33E+00 4.92E+00 NA NA NA MW-63-121 MW-63-121 013 121

-108.7 4/26/2010 12:59 6.06E+02 1.80E+02 1.46E+02 4.17E-01 6.09E-01 6.57E-01 3.57E+00 6.06E+00 7.40E+00 1.16E+00 6.13E+00 7.15E+00 NA NA NA MW-63-121 MW-63-121 014 121

-108.7 8/10/2010 11:28 5.39E+02 1.80E+02 1.77E+02 3.67E-01 5.93E-01 6.58E-01

-9.48E-01 8.12E+00 8.95E+00

-6.58E-01 8.76E+00 9.58E+00 NA NA NA MW-63-121 MW-63-121 015 121

-108.7 11/2/2010 11:46 5.20E+02 1.49E+02 1.10E+02 6.38E-01 7.57E-01 8.11E-01 1.17E+00 6.66E+00 7.68E+00

-4.06E+00 7.17E+00 6.83E+00 NA NA NA MW-63-121 MW-63-121 016 121

-108.7 3/2/2011 11:10 5.03E+02 3.54E+02 2.94E+02

-6.82E-02 1.55E+00 2.03E+00

-6.26E-01 6.72E+00 7.20E+00 3.49E-01 6.00E+00 6.67E+00 NA NA NA MW-63-121 MW-63-121 017 121

-108.7 4/19/2011 9:54 5.77E+02 4.84E+02 4.91E+02 4.12E-01 1.18E+00 1.37E+00

-1.03E+00 6.92E+00 7.17E+00

-1.09E+01 9.86E+00 5.99E+00 NA NA NA MW-63-121 MW-63-121 018 121

-108.7 7/21/2011 9:58 1.33E+03 5.28E+02 4.45E+02

-3.05E-01 1.36E+00 1.74E+00 1.63E-03 7.44E+00 8.17E+00

-3.19E+00 1.05E+01 1.07E+01 1.12E+00 1.84E+01 2.05E+01 MW-63-121 MW-63-121 019 121

-108.7 8/3/2011 10:03 1.92E+03 6.09E+02 3.29E+02 9.09E-01 1.49E+00 1.62E+00

-6.79E+00 9.27E+00 9.08E+00 6.01E+00 8.16E+00 1.09E+01 NA NA NA MW-63-121 MW-63-121 020 121

-108.7 10/18/2011 11:27 3.63E+03 8.40E+02 3.33E+02 1.49E+00 1.71E+00 1.75E+00

-6.42E+00 1.26E+01 1.62E+01 2.81E+00 9.33E+00 1.31E+01 NA NA NA MW-63-121 MW-63-163 001 162.5

-150.2 5/15/2007 11:38 5.78E+02 2.10E+02 1.73E+02

-6.43E-02 6.50E-01 8.74E-01

-8.04E-01 2.84E+00 2.59E+00 9.51E-01 2.25E+00 2.64E+00

-9.58E-01 1.44E+01 1.73E+01 MW-63-163 MW-63-163 002 162.5

-150.2 7/25/2007 12:13 4.79E+02 1.91E+02 1.96E+02

-7.20E-01 3.46E-01 6.26E-01

-3.18E+00 5.16E+00 4.39E+00

-4.54E-01 3.75E+00 3.99E+00 NA NA NA MW-63-163 MW-63-163 003 162.5

-150.2 10/11/2007 14:18 3.49E+02 1.65E+02 1.73E+02 7.93E-03 7.98E-01 9.60E-01

-4.46E-01 3.00E+00 3.28E+00

-1.91E-02 2.94E+00 3.30E+00 NA NA NA MW-63-163 MW-63-163 004 162.5

-150.2 1/9/2008 10:51 5.68E+02 1.77E+02 1.72E+02 3.19E-03 5.55E-01 7.17E-01

-4.52E-01 3.50E+00 3.89E+00 2.23E+00 6.11E+00 4.38E+00 NA NA NA MW-63-163 MW-63-163 005 162.5

-150.2 4/23/2008 11:23 4.44E+02 1.70E+02 2.65E+02 1.82E-01 4.33E-01 7.87E-01 8.04E-01 1.06E+00 1.84E+00 6.60E-01 1.13E+00 1.94E+00 5.30E+00 1.52E+01 2.60E+01 MW-63-163 MW-63-163 006 162.5

-150.2 7/29/2008 14:56 4.48E+02 1.07E+02 1.63E+02

-8.79E-02 2.50E-01 4.37E-01

-2.09E+00 2.34E+00 3.61E+00 9.03E-01 2.59E+00 4.48E+00 NA NA NA MW-63-163 MW-63-163 007 162.5

-150.2 11/4/2008 12:45 6.85E+02 1.86E+02 1.76E+02

-1.44E-01 5.53E-01 7.46E-01 1.77E-01 5.37E+00 6.12E+00 7.78E-01 6.21E+00 7.23E+00 NA NA NA MW-63-163 MW-63-163 008 162.5

-150.2 1/29/2009 11:57 5.81E+02 2.40E+02 1.95E+02 2.86E-01 5.64E-01 6.42E-01 5.82E+00 7.23E+00 3.42E+00

-1.73E-01 2.81E+00 3.03E+00 NA NA NA MW-63-163 MW-63-163 009 162.5

-150.2 5/4/2009 14:39 4.36E+02 1.94E+02 1.66E+02

-1.10E-02 6.03E-01 7.41E-01

-2.88E-01 5.57E+00 3.71E+00

-4.47E+00 4.50E+00 3.64E+00 NA NA NA MW-63-163 MW-63-163 010 162.5

-150.2 7/30/2009 13:45 6.96E+02 1.98E+02 1.89E+02

-1.33E-01 3.60E-01 5.06E-01

-2.87E+00 5.47E+00 5.52E+00

-1.49E-01 5.80E+00 6.40E+00 NA NA NA MW-63-163 MW-63-163 011 162.5

-150.2 11/3/2009 13:47 5.22E+02 1.64E+02 1.61E+02 4.30E-01 8.28E-01 9.38E-01 5.72E-01 4.56E+00 5.33E+00 6.80E+00 4.98E+00 7.07E+00 NA NA NA MW-63-163 MW-63-163 012 162.5

-150.2 2/8/2010 15:36 5.94E+02 1.77E+02 1.78E+02

-1.49E-01 5.64E-01 7.92E-01

-8.47E-02 6.87E+00 5.81E+00 9.37E-01 4.95E+00 5.83E+00 NA NA NA MW-63-163 MW-63-163 013 162.5

-150.2 4/26/2010 14:30 5.29E+02 1.70E+02 1.43E+02 1.98E-01 5.64E-01 6.75E-01

-1.45E+00 7.71E+00 8.86E+00

-2.98E+00 6.17E+00 5.91E+00 NA NA NA MW-63-163 MW-63-163 014 162.5

-150.2 8/10/2010 11:21 4.13E+02 1.74E+02 1.78E+02 2.45E-01 4.43E-01 4.98E-01

-6.87E-01 8.55E+00 9.17E+00

-5.25E-01 8.23E+00 9.24E+00 NA NA NA MW-63-163

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 28 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-63-163 015 162.5

-150.2 11/2/2010 11:49 4.44E+02 1.41E+02 1.10E+02 7.71E-01 8.38E-01 8.77E-01

-3.99E+00 9.88E+00 1.10E+01 2.94E+00 6.12E+00 7.63E+00 NA NA NA MW-63-163 MW-63-163 016 162.5

-150.2 3/2/2011 10:27 6.05E+02 3.76E+02 2.95E+02 1.37E+00 1.99E+00 2.12E+00 3.09E+00 5.40E+00 6.62E+00

-2.05E+00 7.72E+00 7.12E+00 NA NA NA MW-63-163 MW-63-163 017 162.5

-150.2 4/19/2011 9:49 4.92E+02 4.84E+02 5.03E+02 1.11E+00 1.82E+00 2.00E+00 4.43E-01 8.94E+00 9.98E+00 4.78E+00 1.02E+01 1.26E+01 NA NA NA MW-63-163 MW-63-163 018 162.5

-150.2 7/21/2011 10:09 5.08E+02 4.26E+02 4.36E+02

-6.14E-01 1.01E+00 1.48E+00

-8.47E-01 7.47E+00 8.17E+00 4.07E-01 7.53E+00 8.66E+00

-8.69E+00 1.47E+01 1.67E+01 MW-63-163 MW-63-163 019 162.5

-150.2 8/3/2011 10:06 4.41E+02 3.54E+02 3.08E+02 7.99E-02 1.35E+00 1.69E+00 5.51E-01 8.40E+00 9.33E+00 2.23E+00 1.03E+01 1.20E+01 NA NA NA MW-63-163 MW-63-163 020 162.5

-150.2 10/18/2011 11:37 4.85E+02 3.75E+02 3.80E+02 9.47E-01 1.35E+00 1.43E+00

-4.58E+00 9.51E+00 9.82E+00

-1.98E+00 6.54E+00 7.63E+00 NA NA NA MW-63-163 MW-63-174 001 174

-161.7 5/15/2007 11:54 5.93E+02 2.12E+02 1.73E+02 2.64E-01 7.62E-01 9.04E-01

-6.91E-01 2.52E+00 2.70E+00 8.16E-03 2.49E+00 2.76E+00 1.30E+00 1.28E+01 1.51E+01 MW-63-174 MW-63-174 002 174

-161.7 7/25/2007 12:00 5.28E+02 1.94E+02 1.97E+02

-2.78E-01 4.41E-01 6.59E-01 6.28E-01 3.98E+00 4.55E+00

-3.03E-01 3.45E+00 3.80E+00 NA NA NA MW-63-174 MW-63-174 003 174

-161.7 10/11/2007 14:22 3.70E+02 1.65E+02 1.72E+02

-2.85E-01 7.14E-01 9.39E-01 1.94E+00 2.90E+00 2.70E+00

-8.59E-01 2.56E+00 2.71E+00 NA NA NA MW-63-174 MW-63-174 004 174

-161.7 1/9/2008 10:45 6.23E+02 1.79E+02 1.72E+02 6.16E-01 6.95E-01 7.24E-01

-1.24E+00 3.14E+00 3.33E+00 1.48E+00 3.03E+00 3.77E+00 NA NA NA MW-63-174 MW-63-174 005 174

-161.7 4/23/2008 11:21 4.89E+02 1.72E+02 2.65E+02

-6.82E-02 3.65E-01 7.48E-01

-5.74E-01 2.01E+00 3.30E+00 3.66E-01 2.43E+00 4.19E+00

-2.14E+00 1.44E+01 2.50E+01 MW-63-174 MW-63-174 006 174

-161.7 7/29/2008 14:40 4.49E+02 1.40E+02 1.92E+02 6.56E-02 2.76E-01 4.80E-01

-3.76E-01 2.23E+00 3.71E+00

-1.72E+00 2.65E+00 3.79E+00 NA NA NA MW-63-174 MW-63-174 007 174

-161.7 11/4/2008 12:44 4.77E+02 2.04E+02 1.99E+02

-2.76E-01 5.52E-01 7.83E-01

-2.68E+00 4.83E+00 4.74E+00 1.18E+00 5.45E+00 6.30E+00 NA NA NA MW-63-174 MW-63-174 008 174

-161.7 1/29/2009 11:55 4.92E+02 2.28E+02 1.97E+02 4.27E-01 5.96E-01 6.57E-01

-4.53E-01 3.81E+00 3.67E+00

-1.34E+00 3.29E+00 3.32E+00 NA NA NA MW-63-174 MW-63-174 009 174

-161.7 5/4/2009 14:28 4.57E+02 1.94E+02 1.63E+02

-2.15E-01 6.62E-01 7.87E-01 1.98E-01 4.58E+00 3.05E+00

-2.66E+00 3.11E+00 2.63E+00 NA NA NA MW-63-174 MW-63-174 010 174

-161.7 7/30/2009 13:05 4.22E+02 1.86E+02 1.89E+02

-1.74E-01 5.20E-01 6.82E-01 1.48E-01 5.52E+00 6.18E+00 1.22E+00 5.79E+00 6.83E+00 NA NA NA MW-63-174 MW-63-174 011 174

-161.7 11/3/2009 13:53 4.98E+02 1.64E+02 1.61E+02

-1.04E-02 7.92E-01 9.91E-01 1.30E+00 6.69E+00 7.80E+00 5.41E+00 6.04E+00 8.21E+00 NA NA NA MW-63-174 MW-63-174 012 174

-161.7 2/8/2010 15:32 5.05E+02 1.74E+02 1.78E+02 3.28E-02 6.25E-01 8.03E-01

-9.48E-02 3.76E+00 4.18E+00

-2.02E+00 3.76E+00 3.88E+00 NA NA NA MW-63-174 MW-63-174 013 174

-161.7 4/26/2010 14:28 4.98E+02 1.71E+02 1.46E+02

-1.69E-02 5.53E-01 7.24E-01 2.68E+00 4.74E+00 5.86E+00

-4.68E+00 5.26E+00 4.32E+00 NA NA NA MW-63-174 MW-63-174 014 174

-161.7 8/10/2010 11:40 3.33E+02 1.65E+02 1.71E+02 3.54E-01 5.43E-01 6.01E-01

-3.32E+00 7.07E+00 6.89E+00

-1.41E+00 7.84E+00 8.11E+00 NA NA NA MW-63-174 MW-63-174 015 174

-161.7 11/2/2010 11:50 2.63E+02 1.26E+02 1.13E+02

-1.42E-01 4.59E-01 6.06E-01

-6.01E-01 6.03E+00 6.82E+00 2.17E-01 6.42E+00 7.11E+00 NA NA NA MW-63-174 MW-63-174 016 174

-161.7 3/2/2011 10:26 4.13E+02 3.30E+02 2.91E+02 8.20E-01 1.80E+00 2.03E+00 3.65E+00 6.96E+00 8.18E+00 2.34E+00 7.86E+00 9.20E+00 NA NA NA MW-63-174 MW-63-174 017 174

-161.7 4/19/2011 9:52 1.56E+02 4.48E+02 5.04E+02

-7.87E-01 9.72E-01 1.48E+00

-6.41E+00 8.32E+00 7.72E+00

-9.85E-01 8.58E+00 9.20E+00 NA NA NA MW-63-174 MW-63-174 018 174

-161.7 7/21/2011 9:57 4.14E+02 4.17E+02 4.36E+02 6.96E-01 1.85E+00 2.10E+00

-3.57E+00 8.10E+00 8.27E+00 4.67E-01 9.36E+00 1.09E+01

-2.55E+00 1.33E+01 1.49E+01 MW-63-174 MW-63-174 019 174

-161.7 8/3/2011 10:18 6.09E+02 3.93E+02 3.09E+02 6.96E-01 1.49E+00 1.68E+00

-4.15E+00 9.15E+00 8.88E+00 4.51E+00 8.19E+00 1.05E+01 NA NA NA MW-63-174 MW-63-174 020 174

-161.7 10/18/2011 11:42 4.53E+02 3.72E+02 3.80E+02 1.02E+00 1.71E+00 1.86E+00

-6.37E-02 8.43E+00 1.03E+01

-4.33E+00 8.13E+00 9.02E+00 NA NA NA MW-63-174 MW-65-48 001 43.3 26.356 1/4/2007 12:00 2.08E+02 1.83E+02 1.80E+02 0.00E+00 7.80E-01 8.60E-01 1.60E+00 3.60E+00 3.90E+00

-5.00E-01 3.00E+00 3.70E+00

-2.20E+00 6.30E+00 7.30E+00 MW-65-48 MW-65-48 002 43.3 26.356 7/7/2011 12:19 8.59E+01 2.43E+02 2.85E+02 5.73E-01 1.04E+00 1.15E+00 4.10E+00 9.03E+00 1.09E+01

-1.15E+00 1.12E+01 1.18E+01

-5.93E+00 2.39E+01 2.69E+01 MW-65-48 MW-65-80 001 71.4

-1.659 9/8/2006 9:40 3.29E+01 1.62E+02 1.74E+02 4.72E-01 9.80E-01 1.04E+00

-5.15E-01 1.99E+00 2.18E+00

-2.34E-01 1.81E+00 1.98E+00 NA NA NA MW-65-80 MW-65-80 002 71.4

-1.659 1/4/2007 12:35 1.83E+02 1.80E+02 1.80E+02 1.60E-01 7.80E-01 8.70E-01

-2.50E-01 2.22E+00 2.50E+00

-1.13E+00 2.31E+00 2.80E+00

-1.90E+00 6.60E+00 7.40E+00 MW-65-80 MW-65-80 003 71.4

-1.659 7/13/2011 10:12 8.54E+01 2.41E+02 2.84E+02 1.26E-01 9.24E-01 1.12E+00

-2.33E+00 9.12E+00 9.46E+00 2.88E+00 1.15E+01 1.34E+01

-1.27E+01 2.00E+01 2.29E+01 MW-65-80 MW-66-21 001 14.1 0

7/30/2007 13:45 3.57E+03 2.91E+02 1.96E+02 1.79E+00 7.08E-01 2.08E+03 1.77E-01 3.07E+00 3.51E+00 2.21E+00 3.27E+00 4.20E+00 NA NA NA MW-66-21 MW-66-21 002 14.1 0

10/15/2007 10:45 1.04E+03 2.24E+02 1.95E+02 2.42E+00 7.97E-01 5.30E-01

-8.32E-01 3.03E+00 2.74E+00 1.01E-01 2.79E+00 3.18E+00 1.48E+01 2.06E+01 2.28E+01 MW-66-21 MW-66-21 003 14.1 0

1/14/2008 11:33 8.18E+02 4.62E+02 4.16E+02 1.09E+00 8.96E-01 8.19E-01 1.68E+00 3.14E+00 3.77E+00 2.35E+00 3.86E+00 4.26E+00

-5.07E+00 2.12E+01 2.55E+01 MW-66-21 MW-66-21 004 14.1 0

4/21/2008 14:10 9.53E+02 1.51E+02 1.93E+02 1.01E+00 2.05E-01 2.82E-01 6.53E-01 2.36E+00 4.07E+00 1.86E-02 2.26E+00 3.74E+00

-7.28E+00 8.88E+00 1.55E+01 MW-66-21 MW-66-21 005 14.1 0

7/29/2008 11:48 7.83E+02 1.02E+02 1.30E+02 9.07E-01 3.56E-01 4.39E-01

-1.01E+00 1.88E+00 2.92E+00 1.71E+00 2.17E+00 3.99E+00

-6.26E+00 1.66E+01 2.99E+01 MW-66-21 MW-66-21 006 14.1 0

11/4/2008 10:30 5.34E+02 2.07E+02 1.64E+02 1.03E+00 6.96E-01 6.69E-01 1.44E+00 4.67E+00 5.42E+00 2.98E+00 5.17E+00 6.47E+00

-5.68E+00 1.79E+01 2.09E+01 MW-66-21 MW-66-21 007 14.1 0

1/27/2009 13:52 4.61E+02 1.74E+02 1.75E+02 2.91E-01 7.50E-01 8.72E-01 1.60E-01 5.45E+00 3.11E+00

-1.87E+00 2.90E+00 2.71E+00 1.29E+01 1.74E+01 1.93E+01 MW-66-21 MW-66-21 008 14.1 0

3/17/2009 12:00 4.29E+02 3.80E+02 3.81E+02 3.49E-01 6.45E-01 7.29E-01 1.60E-01 6.36E+00 4.24E+00 1.72E+00 3.84E+00 4.65E+00

-4.98E+00 1.70E+01 1.99E+01 MW-66-21 MW-66-21 009 14.1 0

4/20/2009 17:00 8.28E+01 1.65E+02 1.87E+02 1.93E-01 5.55E-01 6.50E-01 1.27E+00 7.23E+00 4.82E+00 9.73E-01 4.11E+00 4.84E+00

-1.86E+00 1.94E+01 2.22E+01 MW-66-21 MW-66-21 010 14.1 0

7/28/2009 14:10 8.23E+02 2.52E+02 2.01E+02 4.51E-01 6.90E-01 7.54E-01

-4.32E-01 4.04E+00 4.51E+00 8.39E-01 3.65E+00 4.34E+00 8.48E+00 2.07E+01 2.33E+01 MW-66-21 MW-66-21 011 14.1 0

11/11/2009 13:46 9.51E+02 2.57E+02 2.04E+02 3.59E-01 8.07E-01 9.17E-01

-2.53E-01 5.70E+00 6.26E+00 1.12E+00 5.73E+00 6.68E+00

-1.49E-01 1.65E+01 1.90E+01 MW-66-21 MW-66-21 012 14.1 0

2/22/2010 14:36 9.60E+02 2.00E+02 1.75E+02 8.97E-01 7.30E-01 7.14E-01 4.96E-01 4.72E+00 5.31E+00

-1.35E+00 5.07E+00 5.41E+00

-5.33E+00 1.96E+01 2.28E+01 MW-66-21 MW-66-21 013 14.1 0

4/9/2010 15:27 9.50E+02 4.07E+02 3.82E+02 1.12E-02 4.34E-01 5.44E-01 3.09E+00 6.75E+00 8.43E+00 3.15E+00 5.19E+00 7.18E+00

-2.25E+00 1.92E+01 2.25E+01 MW-66-21 MW-66-21 014 14.1 0

8/9/2010 12:30 1.07E+03 2.01E+02 1.29E+02 1.17E+00 5.52E-01 4.41E-01

-5.85E+00 9.45E+00 9.34E+00

-9.97E-01 8.07E+00 8.65E+00 3.11E+00 1.19E+01 1.37E+01 MW-66-21 MW-66-21 015 14.1 0

11/10/2010 15:13 3.22E+02 1.64E+02 3.46E+02 2.57E-01 7.74E-01 1.84E+00 6.04E+00 5.26E+00 1.28E+01

-1.91E-01 5.67E+00 1.26E+01 9.56E+00 8.45E+00 1.85E+01 MW-66-21 MW-66-21 016 14.1 0

1/31/2011 16:26 4.77E+02 4.08E+02 4.24E+02 3.48E-01 1.73E+00 2.02E+00

-2.19E-01 5.00E+00 5.33E+00 9.80E-01 6.50E+00 7.23E+00

-1.06E+00 1.84E+01 2.14E+01 MW-66-21 MW-66-21 017 14.1 0

4/14/2011 13:43 9.30E+01 3.88E+02 4.46E+02 6.73E-01 1.64E+00 1.85E+00

-4.70E+00 8.74E+00 8.45E+00 6.94E+00 9.82E+00 1.25E+01 1.81E+00 1.51E+01 1.72E+01 MW-66-21 MW-66-21 018 14.1 0

8/8/2011 10:55 7.84E+02 3.90E+02 3.73E+02 8.00E-01 1.44E+00 1.59E+00

-2.25E+00 8.16E+00 8.11E+00 3.27E-01 7.05E+00 7.73E+00 6.75E+00 9.00E+00 9.81E+00 MW-66-21 MW-66-21 019 14.1 0

11/29/2011 11:08 2.64E+02 3.27E+02 3.32E+02 3.54E-01 1.33E+00 1.49E+00 7.86E-01 6.60E+00 8.51E+00 1.73E+00 7.50E+00 1.01E+01

-3.27E+00 1.37E+01 1.56E+01 MW-66-21 MW-66-36 001 33.6

-19.5 7/30/2007 12:49 9.10E+03 4.13E+02 1.94E+02 6.20E+00 1.19E+00 6.05E-01

-9.84E-01 2.67E+00 2.76E+00

-5.59E-01 2.90E+00 3.06E+00 NA NA NA MW-66-36 MW-66-36 002 33.6

-19.5 10/15/2007 10:16 8.95E+03 4.61E+02 1.92E+02 1.12E+01 1.61E+00 5.63E-01 0.00E+00 8.34E+00 4.32E+00

-2.92E-01 4.34E+00 4.68E+00 1.17E+01 1.88E+01 2.09E+01 MW-66-36 MW-66-36 003 33.6

-19.5 1/14/2008 11:40 7.26E+03 1.01E+03 4.16E+02 1.51E+01 2.40E+00 8.34E-01 2.34E+00 3.38E+00 4.14E+00

-1.08E+00 3.78E+00 3.39E+00 7.19E+00 2.36E+01 2.71E+01 MW-66-36 MW-66-36 004 33.6

-19.5 4/21/2008 13:25 6.09E+03 2.89E+02 1.97E+02 1.32E+01 5.27E-01 3.65E-01

-2.89E-01 2.09E+00 3.46E+00

-2.09E+00 3.54E+00 4.13E+00

-3.35E-01 8.98E+00 1.54E+01 MW-66-36 MW-66-36 005 33.6

-19.5 7/29/2008 12:05 5.01E+03 1.91E+02 1.30E+02 1.20E+01 1.06E+00 6.20E-01 2.07E-01 1.66E+00 2.82E+00

-1.05E+00 1.93E+00 3.00E+00

-1.00E+00 1.69E+01 2.98E+01 MW-66-36 MW-66-36 006 33.6

-19.5 11/4/2008 10:40 5.44E+03 5.34E+02 1.67E+02 1.38E+01 1.71E+00 5.23E-01 6.91E-01 4.32E+00 4.90E+00 1.78E+00 5.24E+00 6.23E+00 9.57E-01 1.64E+01 1.88E+01 MW-66-36 MW-66-36 007 33.6

-19.5 1/27/2009 13:07 3.65E+03 7.62E+02 4.41E+02 1.22E+01 1.56E+00 6.15E-01

-1.04E+00 2.88E+00 3.06E+00 6.35E-02 3.27E+00 3.72E+00 1.45E+01 1.70E+01 1.87E+01 MW-66-36 MW-66-36 008 33.6

-19.5 4/20/2009 15:26 4.39E+03 4.34E+02 1.87E+02 1.07E+01 1.42E+00 5.97E-01 5.54E-02 6.44E+00 4.29E+00

-1.13E+00 4.05E+00 4.20E+00 8.95E+00 1.97E+01 2.21E+01 MW-66-36 MW-66-36 009 33.6

-19.5 7/28/2009 13:41 3.05E+03 4.10E+02 2.10E+02 7.51E+00 1.21E+00 3.95E-01 3.19E+00 6.23E+00 3.54E+00

-6.56E-01 3.65E+00 3.98E+00 6.22E+00 1.92E+01 2.16E+01 MW-66-36 MW-66-36 010 33.6

-19.5 11/11/2009 13:18 4.32E+03 4.44E+02 2.04E+02 6.82E+00 1.24E+00 6.70E-01 3.75E+00 6.95E+00 8.31E+00

-8.32E-01 7.47E+00 7.95E+00

-3.91E+00 1.77E+01 2.08E+01 MW-66-36 MW-66-36 011 33.6

-19.5 2/22/2010 14:04 3.43E+03 2.91E+02 1.75E+02 7.03E+00 1.53E+00 7.17E-01 4.16E-01 4.70E+00 5.29E+00 4.35E-01 5.42E+00 6.09E+00

-8.21E+00 1.94E+01 2.26E+01 MW-66-36 MW-66-36 012 33.6

-19.5 4/9/2010 15:17 3.64E+03 5.90E+02 3.87E+02 7.05E+00 1.36E+00 7.54E-01 1.79E+00 7.65E+00 9.10E+00 6.63E+00 8.54E+00 1.20E+01

-7.64E+00 1.69E+01 2.02E+01 MW-66-36 MW-66-36 013 33.6

-19.5 8/9/2010 11:47 3.08E+03 3.06E+02 1.24E+02 6.40E+00 1.07E+00 3.74E-01

-1.53E+00 8.82E+00 9.41E+00 4.62E+00 7.61E+00 1.02E+01 4.59E+00 1.58E+01 1.80E+01 MW-66-36 MW-66-36 014 33.6

-19.5 11/10/2010 12:33 3.13E+03 2.96E+02 3.96E+02 7.43E+00 1.03E+00 1.13E+00 5.42E+00 3.87E+00 9.67E+00 7.18E-01 4.34E+00 9.81E+00

-4.23E+00 9.63E+00 2.16E+01 MW-66-36 MW-66-36 015 33.6

-19.5 1/31/2011 15:51 3.01E+03 6.78E+02 4.61E+02 1.55E+01 3.18E+00 2.11E+00

-1.13E+00 6.12E+00 6.49E+00

-8.31E-01 6.80E+00 7.15E+00

-4.89E+00 1.79E+01 2.12E+01 MW-66-36 MW-66-36 016 33.6

-19.5 4/14/2011 12:53 3.52E+03 7.36E+02 4.79E+02 1.06E+01 2.88E+00 1.95E+00 1.50E-01 7.24E+00 8.14E+00 5.40E-01 7.92E+00 9.01E+00 6.10E-01 1.55E+01 1.79E+01 MW-66-36 MW-66-36 017 33.6

-19.5 8/8/2011 10:49 3.90E+03 5.91E+02 3.74E+02 8.00E+00 2.60E+00 1.61E+00

-3.94E+00 1.11E+01 1.07E+01 1.48E+00 1.26E+01 1.46E+01 2.82E+00 1.53E+01 1.71E+01 MW-66-36 MW-66-36 018 33.6

-19.5 11/29/2011 11:01 3.34E+03 6.78E+02 4.85E+02 1.02E+01 1.77E+00 1.38E+00 5.21E+00 9.78E+00 1.32E+01 1.63E+00 8.64E+00 1.21E+01 0.00E+00 1.94E+01 2.18E+01 MW-66-36 MW-67-39 001 38.3

-25.8 8/31/2007 12:05 4.86E+03 4.34E+02 1.92E+02 1.86E+01 1.86E+00 4.73E-01

-1.93E-01 2.02E+00 2.24E+00

-9.45E-01 2.00E+00 2.09E+00 NA NA NA MW-67-39 MW-67-39 002 38.3

-25.8 10/1/2007 11:30 5.07E+03 3.75E+02 1.95E+02 2.71E+01 2.44E+00 6.21E-01 1.02E+01 4.11E+00 1.98E+00 3.69E-01 2.07E+00 2.39E+00 2.51E+00 1.68E+01 1.93E+01 MW-67-39 MW-67-39 004 38.3

-25.8 2/25/2008 15:38 4.17E+03 8.28E+02 5.29E+02 2.05E+01 1.77E+00 6.97E-01

-1.15E+00 3.44E+00 3.73E+00 1.99E+00 4.39E+00 3.98E+00

-5.41E-01 2.26E+01 2.63E+01 MW-67-39 MW-67-39 005 38.3

-25.8 7/28/2008 14:07 3.87E+03 1.72E+02 1.30E+02 1.37E+01 1.11E+00 3.97E-01

-1.03E+00 2.60E+00 3.42E+00 4.47E-01 2.15E+00 3.68E+00 6.34E+00 1.67E+01 2.88E+01 MW-67-39 MW-67-39 007 38.3

-25.8 12/18/2008 11:30 3.18E+03 2.66E+02 1.71E+02 1.62E+01 1.69E+00 1.00E+00 1.18E+00 4.61E+00 5.40E+00 7.33E-01 5.04E+00 5.81E+00 8.37E-01 1.68E+01 1.94E+01 MW-67-39 MW-67-39 008 38.3

-25.8 1/27/2009 16:15 3.67E+03 2.91E+02 1.92E+02 1.42E+01 1.71E+00 7.62E-01

-8.03E-01 2.04E+00 2.15E+00

-1.11E-01 2.06E+00 2.25E+00 1.12E+01 1.68E+01 1.87E+01 MW-67-39 MW-67-39 009 38.3

-25.8 4/20/2009 15:02 3.88E+03 4.14E+02 1.90E+02 1.13E+01 1.56E+00 5.49E-01

-2.66E-01 7.17E+00 4.78E+00 1.31E-01 3.74E+00 4.21E+00 1.36E+01 2.06E+01 2.29E+01 MW-67-39 MW-67-39 010 38.3

-25.8 7/28/2009 15:04 2.69E+03 3.87E+02 2.08E+02 6.37E+00 1.11E+00 3.98E-01 1.90E-01 3.01E+00 3.45E+00 2.33E-01 3.24E+00 3.70E+00

-3.64E+00 1.79E+01 2.06E+01 MW-67-39

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 29 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-67-39 011 38.3

-25.8 11/11/2009 14:09 2.80E+03 2.43E+02 1.65E+02 1.35E+01 1.83E+00 7.82E-01

-1.20E+00 8.07E+00 8.84E+00

-1.94E+00 1.00E+01 1.07E+01

-3.83E+00 1.49E+01 1.73E+01 MW-67-39 MW-67-39 012 38.3

-25.8 3/3/2010 13:54 2.55E+03 2.63E+02 1.75E+02 1.24E+01 1.89E+00 6.63E-01

-9.37E-01 5.29E+00 5.81E+00 2.05E+00 6.38E+00 7.62E+00

-9.06E+00 2.03E+01 2.37E+01 MW-67-39 MW-67-39 013 38.3

-25.8 5/6/2010 15:38 3.30E+03 3.60E+02 1.70E+02 9.77E+00 1.69E+00 5.74E-01

-1.53E+00 9.44E+00 1.08E+01

-1.11E+00 7.71E+00 8.22E+00

-1.04E+01 2.13E+01 2.48E+01 MW-67-39 MW-67-39 014 38.3

-25.8 8/9/2010 10:43 3.37E+03 3.15E+02 1.22E+02 8.52E+00 1.21E+00 5.69E-01

-9.27E+00 1.08E+01 1.30E+01

-1.39E+00 8.28E+00 8.77E+00

-2.31E+00 1.43E+01 1.69E+01 MW-67-39 MW-67-39 015 38.3

-25.8 11/10/2010 11:49 3.56E+03 3.09E+02 3.95E+02 5.43E+00 8.85E-01 1.10E+00 1.04E+00 3.96E+00 8.88E+00 2.82E+00 4.30E+00 1.04E+01

-1.86E+00 9.87E+00 2.21E+01 MW-67-39 MW-67-39 016 38.3

-25.8 2/7/2011 13:48 3.85E+03 7.60E+02 4.81E+02 1.57E+01 3.34E+00 1.83E+00 8.03E-02 6.18E+00 6.83E+00 6.64E-01 6.78E+00 7.57E+00 4.43E+00 1.97E+01 2.23E+01 MW-67-39 MW-67-39 017 38.3

-25.8 4/14/2011 13:25 3.73E+03 7.14E+02 4.17E+02 1.25E+01 3.76E+00 2.10E+00 4.53E+00 8.78E+00 1.04E+01 3.71E+00 9.54E+00 1.14E+01 6.99E+00 1.47E+01 1.63E+01 MW-67-39 MW-67-39 018 38.3

-25.8 8/8/2011 12:26 3.62E+03 5.76E+02 3.73E+02 5.31E+00 2.39E+00 1.98E+00

-3.01E+00 8.34E+00 8.17E+00

-7.13E+00 8.22E+00 7.50E+00 5.90E+00 1.71E+01 1.90E+01 MW-67-39 MW-67-39 019 38.3

-25.8 11/29/2011 13:59 3.51E+03 8.07E+02 3.31E+02 1.30E+01 2.39E+00 1.94E+00

-1.60E+01 1.39E+01 1.60E+01

-1.78E+00 9.48E+00 1.17E+01 2.69E+00 1.24E+01 1.38E+01 MW-67-39 MW-67-105 001 104.8

-92.3 8/31/2007 12:35 1.86E+03 5.16E+02 3.34E+02 1.11E+00 6.12E-01 5.26E-01 2.26E-01 2.00E+00 2.00E+00

-3.08E-01 1.68E+00 1.86E+00 NA NA NA MW-67-105 MW-67-105 002 104.8

-92.3 10/1/2007 11:40 2.64E+03 2.96E+02 1.95E+02 4.12E-01 8.28E-01 9.46E-01 0.00E+00 6.11E+00 3.77E+00

-4.57E-01 3.63E+00 3.96E+00 1.05E+01 1.58E+01 1.76E+01 MW-67-105 MW-67-105 003 104.8

-92.3 1/11/2008 15:15 2.43E+03 6.42E+02 4.15E+02 7.58E-01 9.98E-01 1.07E+00 9.32E+00 5.13E+00 2.83E+00 7.44E-01 3.60E+00 3.70E+00 1.81E+01 2.42E+01 2.67E+01 MW-67-105 MW-67-105 004 104.8

-92.3 2/25/2008 13:44 2.38E+03 6.89E+02 5.30E+02 1.13E+00 7.89E-01 8.12E-01

-1.27E+00 3.25E+00 3.38E+00

-4.79E-02 2.97E+00 3.25E+00 1.24E+01 1.74E+01 1.93E+01 MW-67-105 MW-67-105 005 104.8

-92.3 7/28/2008 14:25 2.16E+03 1.40E+02 1.37E+02 9.63E-01 3.54E-01 4.16E-01 4.17E-01 1.59E+00 2.78E+00 7.65E-01 1.51E+00 2.78E+00 7.25E+00 1.65E+01 2.85E+01 MW-67-105 MW-67-105 006 104.8

-92.3 11/3/2008 14:21 2.93E+03 4.02E+02 1.66E+02 1.11E+00 5.60E-01 4.64E-01

-2.48E-01 6.36E+00 7.11E+00 7.75E-02 6.87E+00 7.59E+00 6.32E+00 1.68E+01 1.90E+01 MW-67-105 MW-67-105 007 104.8

-92.3 1/27/2009 16:45 1.96E+03 2.42E+02 1.92E+02 4.08E-01 8.30E-01 9.49E-01

-1.13E+00 3.32E+00 2.71E+00

-3.40E-02 2.39E+00 2.66E+00 1.21E+01 1.64E+01 1.81E+01 MW-67-105 MW-67-105 008 104.8

-92.3 4/20/2009 16:00 1.98E+03 3.15E+02 1.88E+02 6.38E-01 6.92E-01 7.12E-01

-1.78E+00 4.89E+00 3.26E+00 3.61E-01 3.35E+00 3.92E+00 1.01E+01 1.97E+01 2.20E+01 MW-67-105 MW-67-105 009 104.8

-92.3 7/28/2009 15:15 1.77E+03 3.30E+02 2.09E+02 5.33E-01 4.15E-01 3.68E-01 1.59E+00 2.85E+00 3.42E+00

-7.22E-01 3.54E+00 3.64E+00 1.17E+01 1.83E+01 2.04E+01 MW-67-105 MW-67-105 010 104.8

-92.3 11/11/2009 14:31 2.12E+03 3.32E+02 2.03E+02 8.49E-01 5.43E-01 4.85E-01 1.63E-01 5.89E+00 6.71E+00 4.21E-01 7.59E+00 7.67E+00

-2.17E+00 1.71E+01 1.99E+01 MW-67-105 MW-67-105 011 104.8

-92.3 3/3/2010 14:01 1.59E+03 2.28E+02 1.79E+02 5.90E-01 7.56E-01 8.05E-01

-2.99E-01 4.00E+00 4.38E+00

-1.50E+00 4.14E+00 4.26E+00

-4.08E+00 1.91E+01 2.23E+01 MW-67-105 MW-67-105 012 104.8

-92.3 5/6/2010 15:46 1.54E+03 2.60E+02 1.64E+02 1.77E+00 1.01E+00 7.88E-01 4.33E-01 8.65E+00 9.84E+00 3.51E+00 1.01E+01 1.24E+01

-6.18E+00 2.07E+01 2.40E+01 MW-67-105 MW-67-105 013 104.8

-92.3 8/9/2010 10:37 1.26E+03 2.10E+02 1.24E+02 2.61E+00 8.16E-01 6.26E-01 1.46E+00 6.24E+00 7.48E+00 1.75E+00 5.78E+00 7.28E+00 9.56E+00 1.69E+01 1.90E+01 MW-67-105 MW-67-105 014 104.8

-92.3 11/10/2010 11:42 1.14E+03 2.24E+02 3.95E+02 1.41E+00 8.12E-01 1.69E+00

-1.68E+00 3.59E+00 7.64E+00

-3.12E+00 4.14E+00 8.26E+00 1.24E+00 8.56E+00 1.90E+01 MW-67-105 MW-67-105 015 104.8

-92.3 2/7/2011 13:57 9.94E+02 4.26E+02 3.86E+02 3.37E-01 1.64E+00 1.94E+00 2.40E+00 4.84E+00 5.67E+00

-1.22E+00 4.86E+00 4.81E+00

-4.59E+00 1.96E+01 2.31E+01 MW-67-105 MW-67-105 016 104.8

-92.3 4/14/2011 13:43 1.10E+03 4.84E+02 4.12E+02 2.70E-01 1.72E+00 2.11E+00

-3.96E-01 9.66E+00 1.05E+01

-1.91E-01 7.24E+00 7.88E+00 5.71E+00 1.55E+01 1.73E+01 MW-67-105 MW-67-105 017 104.8

-92.3 8/8/2011 12:48 1.42E+03 4.38E+02 3.74E+02 7.40E-01 1.71E+00 1.92E+00

-4.93E-01 7.77E+00 8.36E+00

-6.18E+00 8.67E+00 7.26E+00 6.67E+00 1.25E+01 1.38E+01 MW-67-105 MW-67-105 018 104.8

-92.3 11/29/2011 14:10 1.89E+03 5.94E+02 4.78E+02 1.13E+00 1.74E+00 1.90E+00

-1.36E+00 8.73E+00 1.01E+01

-1.41E+00 8.73E+00 1.04E+01 3.65E+00 1.97E+01 2.20E+01 MW-67-105 MW-67-173 001 172.3

-159.8 8/31/2007 13:04 1.05E+03 4.28E+02 3.37E+02 3.73E-01 3.77E-01 4.12E-01

-1.46E+00 3.56E+00 3.68E+00 1.19E-02 3.75E+00 4.15E+00 NA NA NA MW-67-173 MW-67-173 002 172.3

-159.8 10/1/2007 12:30 1.01E+03 2.25E+02 1.95E+02 1.48E-01 8.62E-01 1.07E+00

-1.34E+00 3.79E+00 4.01E+00 2.82E+00 3.25E+00 3.77E+00 4.12E+00 1.71E+01 1.96E+01 MW-67-173 MW-67-173 004 172.3

-159.8 2/25/2008 14:00 9.51E+02 5.51E+02 5.30E+02

-4.12E-01 6.06E-01 7.76E-01 6.65E-01 2.82E+00 3.23E+00

-3.63E-01 2.54E+00 2.70E+00

-5.95E+00 2.37E+01 2.82E+01 MW-67-173 MW-67-173 005 172.3

-159.8 7/28/2008 14:42 9.12E+02 1.09E+02 1.36E+02 1.05E-01 2.66E-01 4.85E-01

-1.22E+00 2.06E+00 3.19E+00

-3.63E-01 2.14E+00 3.49E+00 5.88E+00 1.64E+01 2.84E+01 MW-67-173 MW-67-173 006 172.3

-159.8 11/3/2008 14:37 9.93E+02 2.58E+02 1.66E+02

-3.48E-02 2.59E-01 3.02E-01

-1.41E+00 6.69E+00 6.32E+00 1.49E+00 6.66E+00 7.65E+00

-1.40E+00 1.69E+01 1.97E+01 MW-67-173 MW-67-173 007 172.3

-159.8 1/27/2009 16:33 7.57E+02 2.00E+02 1.92E+02 4.35E-01 5.94E-01 6.32E-01

-1.51E+00 3.86E+00 3.90E+00

-1.24E+00 2.58E+00 2.73E+00 1.48E+01 1.79E+01 1.96E+01 MW-67-173 MW-67-173 008 172.3

-159.8 3/17/2009 14:00 6.73E+02 4.19E+02 3.81E+02

-5.07E-01 5.72E-01 6.95E-01

-1.51E+00 5.85E+00 3.90E+00 8.14E-01 3.41E+00 4.00E+00

-3.42E+00 1.71E+01 2.00E+01 MW-67-173 MW-67-173 009 172.3

-159.8 4/20/2009 15:50 7.47E+02 2.28E+02 1.87E+02 2.33E-01 6.84E-01 7.84E-01

-2.70E+00 7.05E+00 4.70E+00 9.39E-01 3.60E+00 4.24E+00 8.40E+01 2.45E+01 2.47E+01 MW-67-173 MW-67-173 010 172.3

-159.8 7/28/2009 15:24 1.05E+03 2.76E+02 2.07E+02 1.59E-01 5.58E-01 6.83E-01 6.46E-01 2.91E+00 3.45E+00

-6.41E-01 3.06E+00 3.17E+00 7.63E-01 1.74E+01 1.99E+01 MW-67-173 MW-67-173 011 172.3

-159.8 11/11/2009 14:50 8.10E+02 2.46E+02 2.04E+02 1.67E-01 6.98E-01 8.18E-01 2.06E-01 9.81E+00 6.60E+00

-1.52E+00 6.95E+00 7.53E+00

-2.17E+00 1.86E+01 2.16E+01 MW-67-173 MW-67-173 012 172.3

-159.8 3/3/2010 14:21 8.70E+02 1.98E+02 1.80E+02

-5.05E-01 5.66E-01 9.10E-01

-3.74E+00 5.84E+00 5.23E+00 3.45E-01 3.84E+00 4.42E+00

-1.67E+00 1.95E+01 2.26E+01 MW-67-173 MW-67-173 013 172.3

-159.8 5/6/2010 16:03 6.78E+02 2.03E+02 1.66E+02

-1.35E-01 4.87E-01 7.07E-01

-3.30E+00 9.64E+00 1.02E+01

-8.48E-01 1.00E+01 1.11E+01

-7.30E+00 2.01E+01 2.37E+01 MW-67-173 MW-67-173 014 172.3

-159.8 8/9/2010 11:07 6.72E+02 1.71E+02 1.27E+02 7.70E-02 4.44E-01 5.35E-01

-7.06E-01 1.34E+01 1.68E+01 6.44E-01 8.97E+00 1.04E+01

-1.44E+00 1.14E+01 1.34E+01 MW-67-173 MW-67-173 015 172.3

-159.8 11/10/2010 12:04 6.25E+02 2.01E+02 3.97E+02

-9.99E-01 6.33E-01 1.86E+00 4.02E-01 7.80E+00 1.12E+01

-1.17E+00 4.83E+00 1.03E+01

-1.65E+00 8.09E+00 1.81E+01 MW-67-173 MW-67-173 016 172.3

-159.8 2/7/2011 14:13 4.47E+02 4.48E+02 4.65E+02

-2.38E-01 1.68E+00 2.12E+00

-4.75E-01 5.28E+00 5.83E+00 7.55E-01 6.38E+00 5.76E+00

-7.05E-01 1.88E+01 2.18E+01 MW-67-173 MW-67-173 017 172.3

-159.8 4/14/2011 14:09 5.72E+02 4.20E+02 4.10E+02

-2.56E-01 1.69E+00 1.99E+00 5.04E+00 9.64E+00 1.17E+01

-9.27E+00 1.03E+01 6.85E+00 7.50E+00 1.23E+01 1.34E+01 MW-67-173 MW-67-173 018 172.3

-159.8 8/8/2011 12:53 6.13E+02 3.75E+02 3.72E+02

-3.44E-01 1.55E+00 1.94E+00

-1.95E+00 8.79E+00 9.16E+00 1.25E+00 8.70E+00 9.80E+00 4.91E+00 1.20E+01 1.33E+01 MW-67-173 MW-67-173 019 172.3

-159.8 11/29/2011 14:23 5.88E+02 4.74E+02 4.78E+02 1.13E+00 1.62E+00 1.76E+00

-1.48E+00 9.87E+00 1.14E+01

-1.48E+00 1.08E+01 1.30E+01 7.39E+00 1.18E+01 1.29E+01 MW-67-173 MW-67-219 001 218.8

-206.3 8/31/2007 13:43 1.25E+03 4.46E+02 3.30E+02 3.27E-02 3.00E-01 3.47E-01

-1.58E-01 3.04E+00 3.32E+00 9.02E-01 3.09E+00 3.68E+00 NA NA NA MW-67-219 MW-67-219 002 218.8

-206.3 10/1/2007 12:53 9.46E+02 2.22E+02 1.95E+02

-2.27E-01 7.50E-01 1.03E+00 1.48E-01 2.60E+00 2.90E+00 1.38E-01 2.37E+00 2.65E+00 1.21E+01 2.64E+01 2.99E+01 MW-67-219 MW-67-219 004 218.8

-206.3 2/25/2008 11:43 1.23E+03 5.81E+02 5.31E+02

-7.61E-02 4.93E-01 6.12E-01

-1.33E+00 3.03E+00 3.18E+00 1.08E+00 3.15E+00 3.78E+00 1.23E+01 1.81E+01 2.03E+01 MW-67-219 MW-67-219 005 218.8

-206.3 7/28/2008 11:00 1.17E+03 1.16E+02 1.36E+02

-7.49E-02 2.34E-01 4.85E-01

-2.91E-01 1.98E+00 3.33E+00

-2.64E-01 1.92E+00 3.18E+00 5.99E+00 1.68E+01 2.90E+01 MW-67-219 MW-67-219 006 218.8

-206.3 11/3/2008 11:31 1.37E+03 2.93E+02 1.68E+02 8.78E-02 1.69E-01 1.91E-01 1.32E+00 4.93E+00 5.86E+00 4.00E+00 6.30E+00 8.05E+00 2.30E+00 1.65E+01 1.88E+01 MW-67-219 MW-67-219 007 218.8

-206.3 1/27/2009 12:34 9.68E+02 2.81E+02 2.50E+02

-7.56E-02 5.30E-01 7.13E-01

-3.58E-01 1.89E+00 2.10E+00 7.86E-02 1.83E+00 2.09E+00 1.14E+01 2.16E+01 2.43E+01 MW-67-219 MW-67-219 008 218.8

-206.3 4/20/2009 12:09 1.18E+03 2.63E+02 1.89E+02 3.27E-01 6.63E-01 7.50E-01

-2.03E+00 6.20E+00 4.13E+00 4.77E-01 4.26E+00 4.84E+00 9.52E+00 1.85E+01 2.08E+01 MW-67-219 MW-67-219 009 218.8

-206.3 7/28/2009 11:11 9.22E+02 2.61E+02 2.03E+02 1.81E-01 8.09E-01 9.66E-01 2.89E+00 3.99E+00 4.97E+00 1.63E+00 3.76E+00 4.67E+00 1.14E+01 1.66E+01 1.85E+01 MW-67-219 MW-67-219 010 218.8

-206.3 11/11/2009 11:16 1.44E+03 2.88E+02 2.00E+02

-1.39E-01 6.37E-01 7.86E-01 1.78E+00 4.86E+00 5.82E+00

-4.94E-01 6.25E+00 6.90E+00 6.03E+00 1.74E+01 1.97E+01 MW-67-219 MW-67-219 011 218.8

-206.3 3/3/2010 11:23 1.09E+03 2.07E+02 1.79E+02 3.26E-01 7.37E-01 8.53E-01

-2.20E+00 3.00E+00 3.18E+00 1.81E+00 3.13E+00 3.73E+00 4.96E+00 1.89E+01 2.15E+01 MW-67-219 MW-67-219 012 218.8

-206.3 5/6/2010 11:51 1.20E+03 2.40E+02 1.66E+02 1.78E-01 6.31E-01 7.71E-01 2.27E+00 8.87E+00 1.05E+01 2.35E+00 7.38E+00 9.29E+00

-7.98E+00 1.95E+01 2.31E+01 MW-67-219 MW-67-219 013 218.8

-206.3 8/9/2010 13:33 1.11E+03 2.01E+02 1.25E+02 9.94E-02 5.32E-01 6.41E-01

-7.99E-01 8.14E+00 9.12E+00

-6.19E+00 9.03E+00 8.33E+00 2.34E+00 1.21E+01 1.39E+01 MW-67-219 MW-67-219 014 218.8

-206.3 11/10/2010 13:40 1.15E+03 2.24E+02 3.96E+02 3.53E-01 7.28E-01 1.78E+00

-2.80E-01 3.60E+00 7.62E+00 2.49E-01 3.62E+00 7.89E+00

-4.41E+00 8.84E+00 1.98E+01 MW-67-219 MW-67-219 015 218.8

-206.3 1/31/2011 14:48 6.41E+02 4.18E+02 4.20E+02

-1.08E+00 1.42E+00 1.97E+00 9.72E-01 5.80E+00 6.44E+00 2.44E+00 5.46E+00 6.55E+00

-4.58E+00 1.81E+01 2.14E+01 MW-67-219 MW-67-219 016 218.8

-206.3 4/14/2011 10:49 1.07E+03 4.78E+02 4.12E+02

-7.57E-01 9.50E-01 1.53E+00

-2.70E+00 6.62E+00 6.47E+00 4.16E+00 9.78E+00 1.20E+01 2.95E+00 1.43E+01 1.62E+01 MW-67-219 MW-67-219 017 218.8

-206.3 8/8/2011 10:33 1.11E+03 4.17E+02 3.73E+02 3.18E-02 1.61E+00 1.90E+00 8.34E-01 7.41E+00 8.13E+00

-6.37E+00 9.30E+00 8.11E+00 1.06E+01 1.64E+01 1.79E+01 MW-67-219 MW-67-219 018 218.8

-206.3 11/29/2011 10:41 1.20E+03 4.92E+02 4.45E+02 3.14E-01 1.42E+00 1.63E+00

-1.12E+01 1.14E+01 1.19E+01 1.99E+00 7.65E+00 1.12E+01 1.02E+01 1.13E+01 1.23E+01 MW-67-219 MW-67-276 001 275.3

-262.8 8/31/2007 12:20 6.79E+02 3.83E+02 3.41E+02

-3.34E-01 3.57E-01 4.29E-01 1.36E+00 3.82E+00 4.02E+00

-9.09E-01 3.75E+00 4.00E+00 NA NA NA MW-67-276 MW-67-276 002 275.3

-262.8 10/1/2007 13:04 1.11E+03 2.30E+02 1.96E+02 3.82E-02 8.36E-01 9.91E-01

-3.32E+00 3.63E+00 3.34E+00

-3.17E-01 3.51E+00 3.31E+00 5.04E-01 1.59E+01 1.84E+01 MW-67-276 MW-67-276 004 275.3

-262.8 2/25/2008 11:48 1.07E+03 5.64E+02 5.29E+02 4.43E-01 7.06E-01 7.88E-01 2.00E+00 3.45E+00 4.21E+00 1.79E+00 4.11E+00 4.33E+00 1.08E+01 1.89E+01 2.11E+01 MW-67-276 MW-67-276 005 275.3

-262.8 7/28/2008 11:09 1.16E+03 1.16E+02 1.36E+02

-5.05E-02 2.76E-01 5.47E-01

-8.94E-01 1.98E+00 3.18E+00 5.92E-01 1.97E+00 3.45E+00 7.55E+00 1.62E+01 2.77E+01 MW-67-276 MW-67-276 006 275.3

-262.8 11/3/2008 11:39 1.18E+03 2.75E+02 1.66E+02

-5.08E-02 1.81E-01 2.16E-01 3.75E-01 5.63E+00 6.29E+00

-7.43E-01 6.00E+00 6.50E+00 7.29E+00 1.73E+01 1.95E+01 MW-67-276 MW-67-276 007 275.3

-262.8 1/27/2009 13:01 1.10E+03 5.12E+02 4.39E+02 3.32E-01 5.93E-01 6.66E-01 2.35E-01 3.24E+00 3.70E+00

-1.19E+00 3.74E+00 3.96E+00 1.15E+01 1.68E+01 1.87E+01 MW-67-276 MW-67-276 008 275.3

-262.8 4/20/2009 12:15 9.46E+02 2.43E+02 1.86E+02 7.29E-03 5.33E-01 6.74E-01 1.18E+00 5.45E+00 3.63E+00

-2.84E-01 3.63E+00 4.04E+00 2.21E+01 2.07E+01 2.28E+01 MW-67-276 MW-67-276 009 275.3

-262.8 7/28/2009 11:15 9.17E+02 2.63E+02 2.04E+02 2.23E-01 3.98E-01 4.46E-01

-6.84E-01 5.00E+00 4.61E+00 2.18E+00 3.71E+00 4.70E+00 7.04E+00 1.76E+01 1.99E+01 MW-67-276 MW-67-276 010 275.3

-262.8 11/11/2009 11:23 1.05E+03 1.88E+02 1.65E+02 2.35E-01 8.09E-01 9.59E-01 9.81E-01 8.21E+00 9.54E+00 4.26E+00 9.15E+00 1.17E+01 1.80E+00 1.66E+01 1.91E+01 MW-67-276 MW-67-276 011 275.3

-262.8 3/3/2010 11:25 1.11E+03 2.10E+02 1.80E+02

-1.30E-01 5.78E-01 8.23E-01 1.09E+00 3.92E+00 4.54E+00

-3.85E+00 6.67E+00 4.49E+00 1.73E+00 1.92E+01 2.21E+01 MW-67-276 MW-67-276 012 275.3

-262.8 5/6/2010 12:20 1.09E+03 2.33E+02 1.65E+02

-1.16E-01 5.38E-01 7.47E-01

-1.34E+00 7.98E+00 8.70E+00 2.02E+00 9.16E+00 1.09E+01 9.78E+00 2.03E+01 2.27E+01 MW-67-276 MW-67-276 013 275.3

-262.8 8/9/2010 13:36 9.33E+02 1.86E+02 1.22E+02 4.00E-01 4.66E-01 4.98E-01 2.56E+00 7.23E+00 8.80E+00

-2.39E+00 8.22E+00 8.27E+00 9.94E+00 1.28E+01 1.42E+01 MW-67-276 MW-67-276 014 275.3

-262.8 11/10/2010 14:16 1.01E+03 2.18E+02 3.96E+02

-7.85E-01 5.64E-01 1.77E+00 1.94E+00 4.26E+00 9.92E+00

-5.48E+00 4.42E+00 7.40E+00 5.46E+00 8.55E+00 1.89E+01 MW-67-276 MW-67-276 015 275.3

-262.8 1/31/2011 14:31 8.75E+02 4.18E+02 3.87E+02

-2.57E-02 1.66E+00 2.03E+00

-2.56E+00 8.76E+00 8.16E+00 6.49E-01 6.48E+00 7.20E+00

-7.18E-01 1.92E+01 2.22E+01 MW-67-276

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 30 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-67-276 016 275.3

-262.8 4/14/2011 10:53 1.06E+03 4.84E+02 4.19E+02 3.46E-01 1.22E+00 1.45E+00

-5.30E+00 6.78E+00 6.12E+00 1.62E+00 1.02E+01 1.15E+01 5.62E-01 1.42E+01 1.63E+01 MW-67-276 MW-67-276 017 275.3

-262.8 8/8/2011 10:45 8.99E+02 3.90E+02 3.63E+02

-3.98E-01 1.38E+00 1.82E+00

-3.35E-01 8.67E+00 9.58E+00 1.65E+00 9.24E+00 1.07E+01 1.22E+01 1.91E+01 2.10E+01 MW-67-276 MW-67-276 018 275.3

-262.8 11/29/2011 10:57 1.06E+03 5.25E+02 4.84E+02 1.99E-01 1.70E+00 1.95E+00

-2.95E+00 1.01E+01 1.19E+01

-7.14E-01 8.82E+00 1.11E+01 6.48E+00 1.19E+01 1.31E+01 MW-67-276 MW-67-323 001 322.3

-309.8 8/31/2007 13:20 3.13E+02 1.55E+02 1.57E+02

-2.41E-01 3.06E-01 3.74E-01 1.14E+00 3.71E+00 4.33E+00 1.29E-01 3.76E+00 4.32E+00 NA NA NA MW-67-323 MW-67-323 002 322.3

-309.8 10/1/2007 14:08 1.29E+03 2.40E+02 1.96E+02 5.67E-01 8.58E-01 9.37E-01

-5.77E-01 3.04E+00 3.24E+00

-6.19E-01 3.35E+00 3.58E+00 5.25E-01 1.65E+01 1.92E+01 MW-67-323 MW-67-323 004 322.3

-309.8 2/25/2008 11:59 3.72E+02 2.75E+02 2.87E+02 3.61E-01 7.60E-01 8.62E-01

-2.08E-01 2.97E+00 3.32E+00 1.29E+00 3.50E+00 4.18E+00 6.85E+00 1.88E+01 2.13E+01 MW-67-323 MW-67-323 005 322.3

-309.8 7/28/2008 11:25 3.38E+02 9.08E+01 1.36E+02

-2.38E-01 3.66E-01 7.29E-01 8.29E-01 2.30E+00 3.99E+00 2.24E-01 2.04E+00 3.46E+00

-5.98E+00 1.59E+01 2.86E+01 MW-67-323 MW-67-323 006 322.3

-309.8 11/3/2008 11:44 6.84E+02 2.24E+02 1.64E+02 4.20E-02 3.40E-01 4.37E-01

-3.56E+00 5.21E+00 5.18E+00 4.29E-01 5.12E+00 5.87E+00

-7.38E+00 1.59E+01 1.87E+01 MW-67-323 MW-67-323 007 322.3

-309.8 1/27/2009 13:50 3.65E+02 1.70E+02 1.76E+02

-1.15E-01 4.05E-01 5.85E-01 4.74E-01 3.86E+00 4.42E+00 3.47E-01 3.38E+00 3.86E+00 9.84E+00 1.32E+01 1.47E+01 MW-67-323 MW-67-323 008 322.3

-309.8 4/20/2009 12:20 3.97E+02 1.98E+02 1.87E+02 2.21E-01 7.17E-01 8.23E-01

-5.22E-01 6.86E+00 4.57E+00

-2.70E+00 4.50E+00 4.33E+00

-5.56E+00 2.10E+01 2.43E+01 MW-67-323 MW-67-323 009 322.3

-309.8 7/28/2009 11:25 3.94E+02 2.16E+02 2.07E+02 5.31E-02 3.21E-01 4.07E-01

-1.54E+00 3.31E+00 3.45E+00 7.30E-01 3.72E+00 4.34E+00 2.93E-01 1.79E+01 2.04E+01 MW-67-323 MW-67-323 010 322.3

-309.8 11/11/2009 11:34 4.21E+02 1.62E+02 1.65E+02

-3.92E-01 4.86E-01 7.25E-01

-3.01E+00 8.12E+00 8.50E+00

-1.44E+00 8.10E+00 8.57E+00 2.91E+00 1.53E+01 1.74E+01 MW-67-323 MW-67-323 011 322.3

-309.8 3/3/2010 11:31 4.71E+02 1.80E+02 1.80E+02 3.29E-01 7.45E-01 8.63E-01

-5.78E-01 3.68E+00 4.08E+00

-1.86E-01 3.66E+00 4.06E+00 8.96E+00 1.96E+01 2.21E+01 MW-67-323 MW-67-323 012 322.3

-309.8 5/6/2010 12:30 4.44E+02 1.83E+02 1.67E+02

-1.63E-01 4.58E-01 6.67E-01

-2.50E+00 7.72E+00 7.87E+00 2.97E-01 8.21E+00 9.30E+00

-1.13E+01 1.96E+01 2.33E+01 MW-67-323 MW-67-323 013 322.3

-309.8 8/9/2010 13:23 4.32E+02 1.48E+02 1.23E+02 6.38E-01 6.31E-01 6.53E-01 1.47E+00 6.88E+00 8.02E+00 3.28E-01 6.72E+00 7.56E+00

-4.51E+00 1.37E+01 1.63E+01 MW-67-323 MW-67-323 014 322.3

-309.8 11/10/2010 14:03 3.88E+02 1.89E+02 3.94E+02 1.89E-01 8.21E-01 2.01E+00 2.70E+00 4.61E+00 1.06E+01 3.11E-01 5.07E+00 1.12E+01

-3.22E+00 7.93E+00 1.78E+01 MW-67-323 MW-67-323 015 322.3

-309.8 1/31/2011 15:04 3.38E+02 3.70E+02 3.90E+02 2.58E-01 1.71E+00 2.03E+00 2.47E-01 5.70E+00 6.35E+00 8.12E-03 5.80E+00 6.35E+00

-5.93E+00 1.90E+01 2.25E+01 MW-67-323 MW-67-323 016 322.3

-309.8 4/14/2011 11:33 4.26E+02 4.06E+02 4.13E+02 1.05E+00 1.52E+00 1.62E+00 2.02E+00 8.36E+00 9.62E+00

-1.12E+00 7.80E+00 8.21E+00

-2.21E-01 1.30E+01 1.50E+01 MW-67-323 MW-67-323 017 322.3

-309.8 8/8/2011 10:53 3.09E+02 3.51E+02 3.73E+02 1.75E+00 1.85E+00 1.91E+00

-6.64E-01 6.66E+00 7.23E+00 4.13E+00 8.82E+00 1.09E+01

-9.62E+00 2.15E+01 2.43E+01 MW-67-323 MW-67-323 018 322.3

-309.8 11/29/2011 10:57 3.62E+02 4.56E+02 4.86E+02 7.61E-01 1.71E+00 1.91E+00

-3.91E+00 9.81E+00 1.15E+01 1.58E+00 5.43E+00 8.36E+00 1.66E+01 2.34E+01 2.56E+01 MW-67-323 MW-67-340 001 339.8

-327.3 8/31/2007 12:54 3.69E+02 1.61E+02 1.60E+02 1.69E-01 2.71E-01 3.04E-01 6.52E-01 4.61E+00 5.13E+00 4.53E+00 5.43E+00 5.20E+00 NA NA NA MW-67-340 MW-67-340 002 339.8

-327.3 10/1/2007 14:00 3.90E+02 1.92E+02 1.96E+02 1.42E-01 3.71E-01 4.20E-01 7.29E-01 3.46E+00 3.96E+00

-1.22E+00 3.33E+00 3.50E+00 3.89E+00 1.54E+01 1.76E+01 MW-67-340 MW-67-340 004 339.8

-327.3 2/25/2008 12:00 4.78E+02 2.82E+02 2.86E+02

-2.17E-01 5.53E-01 6.94E-01

-1.58E+00 3.99E+00 3.94E+00

-7.62E-01 3.19E+00 3.43E+00 5.72E+00 1.83E+01 2.09E+01 MW-67-340 MW-67-340 005 339.8

-327.3 7/28/2008 11:18 5.11E+02 9.36E+01 1.30E+02

-3.39E-01 2.28E-01 5.49E-01 3.13E-01 2.21E+00 3.81E+00 9.03E-01 2.25E+00 3.68E+00

-6.94E+00 1.57E+01 2.78E+01 MW-67-340 MW-67-340 006 339.8

-327.3 11/3/2008 11:54 6.69E+02 2.22E+02 1.63E+02 8.08E-02 4.26E-01 5.43E-01 2.23E+00 6.25E+00 7.45E+00 3.65E+00 6.76E+00 8.47E+00

-8.34E+00 1.59E+01 1.88E+01 MW-67-340 MW-67-340 007 339.8

-327.3 1/27/2009 12:44 5.23E+02 4.37E+02 4.39E+02 2.57E-01 5.48E-01 6.31E-01 4.72E-01 3.72E+00 4.19E+00

-4.00E-01 3.41E+00 3.67E+00 7.78E+00 1.68E+01 1.90E+01 MW-67-340 MW-67-340 008 339.8

-327.3 4/20/2009 12:25 4.96E+02 2.07E+02 1.88E+02 4.35E-01 5.64E-01 6.05E-01 3.18E+00 7.19E+00 4.79E+00

-1.37E-01 3.53E+00 3.83E+00 8.03E+00 2.03E+01 2.29E+01 MW-67-340 MW-67-340 009 339.8

-327.3 7/28/2009 11:20 4.70E+02 2.25E+02 2.08E+02 2.02E-01 6.29E-01 7.50E-01 5.88E-01 3.75E+00 4.34E+00

-3.76E-01 3.06E+00 3.30E+00

-6.20E-01 1.89E+01 2.16E+01 MW-67-340 MW-67-340 010 339.8

-327.3 11/11/2009 11:28 5.37E+02 1.68E+02 1.65E+02

-2.77E-01 7.77E-01 9.54E-01

-3.00E-01 5.63E+00 6.15E+00 2.49E+00 6.63E+00 8.33E+00

-9.81E+00 1.49E+01 1.77E+01 MW-67-340 MW-67-340 011 339.8

-327.3 3/3/2010 11:49 5.97E+02 1.85E+02 1.79E+02 1.19E-01 5.07E-01 6.26E-01 4.02E-01 4.41E+00 5.05E+00 2.42E+00 4.80E+00 5.86E+00 2.20E+00 1.91E+01 2.19E+01 MW-67-340 MW-67-340 012 339.8

-327.3 5/6/2010 12:24 6.57E+02 2.00E+02 1.65E+02

-2.13E-01 4.66E-01 7.01E-01

-2.61E+00 7.77E+00 8.17E+00 3.62E-01 8.78E+00 1.00E+01

-5.47E+00 1.94E+01 2.28E+01 MW-67-340 MW-67-340 013 339.8

-327.3 8/9/2010 13:20 4.86E+02 1.55E+02 1.25E+02

-3.81E-02 5.00E-01 6.29E-01 1.20E+00 7.44E+00 8.75E+00

-2.42E+00 6.98E+00 7.06E+00 2.60E+00 1.45E+01 1.67E+01 MW-67-340 MW-67-340 014 339.8

-327.3 11/10/2010 13:53 5.31E+02 1.97E+02 3.95E+02

-8.93E-01 5.00E-01 1.64E+00 1.72E+00 4.50E+00 1.03E+01

-2.97E+00 3.90E+00 7.25E+00 2.25E+00 8.84E+00 1.97E+01 MW-67-340 MW-67-340 015 339.8

-327.3 1/31/2011 14:53 2.75E+02 3.58E+02 3.83E+02

-7.06E-01 1.51E+00 1.99E+00 4.30E-01 6.34E+00 7.02E+00

-1.15E+00 6.54E+00 6.88E+00

-5.79E+00 1.85E+01 2.20E+01 MW-67-340 MW-67-340 016 339.8

-327.3 4/14/2011 11:17 6.56E+02 4.32E+02 4.13E+02 2.62E-01 1.16E+00 1.40E+00 5.89E+00 9.02E+00 1.12E+01 4.57E+00 9.02E+00 1.15E+01 7.58E+00 1.54E+01 1.71E+01 MW-67-340 MW-67-340 017 339.8

-327.3 8/8/2011 10:43 4.19E+02 3.60E+02 3.72E+02

-5.52E-01 1.49E+00 1.89E+00

-9.17E-01 7.92E+00 8.61E+00

-4.93E+00 1.06E+01 1.00E+01 6.17E+00 1.84E+01 2.05E+01 MW-67-340 MW-67-340 018 339.8

-327.3 11/29/2011 10:46 5.62E+02 4.68E+02 4.76E+02

-5.80E-01 1.53E+00 1.87E+00

-7.65E+00 7.53E+00 7.09E+00 1.23E+00 8.85E+00 1.14E+01 1.70E+00 1.06E+01 1.17E+01 MW-67-340 MW-107 004 32.7 110.1 9/28/2005 12:00 3.09E+02 3.87E+02 4.20E+02 NA NA NA 3.86E+00 1.16E+01 8.53E+00 NA NA NA NA NA NA MW-107 MW-107 001 32.7 110.1 12/8/2005 11:15 1.28E+02 4.11E+02 4.54E+02 7.65E+00 1.53E+01 1.33E+01 2.55E+00 7.64E+00 5.59E+00 4.11E+00 1.23E+01 8.97E+00 NA NA NA MW-107 MW-107 002 32.7 110.1 4/18/2006 11:15 1.27E+02 4.11E+02 4.51E+02 0.00E+00 3.90E-01 4.40E-01 2.65E+00 7.94E+00 5.62E+00 4.36E+00 1.31E+01 9.21E+00 NA NA NA MW-107 MW-107 003 32.7 110.1 6/6/2006 13:30 1.05E+02 1.53E+02 1.56E+02

-2.07E-01 5.43E-01 7.13E-01 1.65E+00 8.31E+00 9.24E+00

-3.66E-01 8.36E+00 9.05E+00 NA NA NA MW-107 MW-107 005 32.7 110.1 7/23/2007 14:18 8.92E+01 1.52E+02 1.70E+02 1.66E-01 5.19E-01 5.87E-01 8.13E-01 2.73E+00 1.60E+00 1.03E-01 1.41E+00 1.60E+00 NA NA NA MW-107 MW-107 006 32.7 110.1 4/24/2008 15:41 1.91E+02 8.90E+01 1.44E+02

-6.22E-02 2.21E-01 4.42E-01

-2.03E+00 2.78E+00 4.11E+00

-1.38E+00 2.12E+00 3.07E+00 NA NA NA MW-107 MW-107 007 32.7 110.1 5/30/2008 15:25 4.62E+01 9.02E+01 1.58E+02 6.62E-02 5.51E-01 9.60E-01 1.22E+00 1.88E+00 3.36E+00 5.48E-01 2.20E+00 3.57E+00 NA NA NA MW-107 MW-107 008 32.7 110.1 4/22/2009 12:30 1.96E+02 1.71E+02 1.86E+02 9.02E-03 4.34E-01 5.52E-01

-2.11E-01 3.86E+00 2.57E+00 1.54E+00 2.61E+00 3.19E+00 NA NA NA MW-107 MW-107 009 32.7 110.1 4/22/2010 10:11 9.67E+01 1.64E+02 1.83E+02

-7.61E-02 5.23E-01 6.74E-01 9.25E-01 6.08E+00 6.99E+00

-1.88E+00 7.25E+00 7.56E+00 NA NA NA MW-107 MW-107 010 32.7 110.1 5/2/2011 9:25 3.15E+02 3.76E+02 3.95E+02 8.29E-01 1.29E+00 1.40E+00

-3.56E+00 1.30E+01 1.65E+01 2.39E+00 6.84E+00 8.63E+00 NA NA NA MW-107 MW-108 003 8.3 6.2 9/29/2005 12:00 3.32E+02 3.84E+02 4.20E+02 NA NA NA 3.23E+00 9.70E+00 7.39E+00 3.21E+00 9.64E+00 7.84E+00 NA NA NA MW-108 MW-108 004 8.3 6.2 11/3/2005 12:00 1.97E+02 4.26E+02 4.76E+02 NA NA NA 3.41E+00 1.02E+01 7.53E+00 2.65E+00 7.95E+00 6.39E+00 NA NA NA MW-108 MW-108 002 8.3 6.2 5/13/2006 10:53 2.78E+02 1.82E+02 1.68E+02 6.89E-01 8.26E-01 8.08E-01 3.12E+00 8.86E+00 1.05E+01

-1.45E-01 1.23E+01 1.34E+01 NA NA NA MW-108 MW-108 005 8.3 6.2 7/5/2011 15:08 1.24E+03 4.89E+02 2.90E+02

-9.21E-02 1.29E+00 1.55E+00 4.93E+00 9.84E+00 1.17E+01

-7.54E+00 8.49E+00 7.19E+00

-8.75E+00 2.32E+01 2.62E+01 MW-108 MW-108 006 8.3 6.2 8/29/2011 11:25 1.78E+03 5.73E+02 2.62E+02

-7.81E-01 7.89E-01 1.24E+00

-1.86E-01 1.19E+01 1.21E+01

-4.10E+00 1.13E+01 1.10E+01 2.65E+00 1.16E+01 1.30E+01 MW-108 MW-109 003 8.5 6.1 9/29/2005 12:00 1.54E+02 3.81E+02 4.20E+02 NA NA NA 3.74E+00 1.12E+01 8.45E+00 3.19E+00 9.57E+00 7.88E+00 NA NA NA MW-109 MW-109 004 8.5 6.1 11/3/2005 12:00 1.01E+02 4.23E+02 4.76E+02 NA NA NA 3.59E+00 1.08E+01 7.89E+00 2.59E+00 7.78E+00 6.26E+00 NA NA NA MW-109 MW-109 002 8.5 6.1 5/13/2006 10:10 3.39E+02 1.89E+02 1.70E+02 2.98E-01 8.24E-01 9.27E-01 2.00E-01 5.68E+00 6.24E+00

-2.50E+00 6.12E+00 6.08E+00 NA NA NA MW-109 MW-109 005 8.5 6.1 7/5/2011 12:45 2.43E+03 6.36E+02 2.79E+02 2.60E-01 1.25E+00 1.45E+00 2.23E-01 8.67E+00 9.62E+00

-3.32E+00 7.74E+00 6.65E+00 3.57E+00 3.51E+01 3.92E+01 MW-109 MW-109 006 8.5 6.1 8/26/2011 13:49 3.26E+03 7.50E+02 2.59E+02 5.48E-01 1.01E+00 1.12E+00 2.37E+00 7.65E+00 8.94E+00 3.72E+00 9.60E+00 1.17E+01

-8.72E-01 8.73E+00 1.00E+01 MW-109 MW-111 001 16.5 2.4 9/29/2005 10:00 2.15E+05 2.26E+03 4.20E+02 NA NA NA 4.48E+00 1.34E+01 1.02E+01 1.81E+00 5.42E+00 5.57E+00 NA NA NA MW-111 MW-111 001 16.5 2.4 9/29/2005 10:00 2.05E+05 2.56E+04 6.24E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-111 MW-111 002 16.5 2.4 10/14/2005 10:00 6.81E+03 4.73E+03 6.41E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-111 MW-111 003 16.5 2.4 10/21/2005 10:00 2.84E+05 3.05E+04 6.41E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-111 MW-111 004 16.5 2.4 10/28/2005 8:30 2.18E+05 6.54E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-111 MW-111 005 16.5 2.4 11/4/2005 9:00 3.02E+05 9.06E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-111 MW-111 006 16.5 2.4 11/22/2005 10:00 1.80E+05 5.40E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-111 MW-111 007 16.5 2.4 12/2/2005 10:15 1.25E+05 3.75E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-111 MW-111 008 16.5 2.4 12/8/2005 16:50 2.71E+05 8.13E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-111 MW-111 009 16.5 2.4 12/15/2005 11:00 2.96E+05 8.88E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-111 MW-111 010 16.5 2.4 12/19/2005 9:45 1.92E+05 5.76E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-111 MW-111 011 16.5 2.4 12/29/2005 10:00 2.12E+05 6.36E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-111 MW-111 012 16.5 2.4 1/6/2006 10:45 1.13E+05 3.39E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-111 MW-111 013 16.5 2.4 1/13/2006 10:30 1.99E+05 5.97E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-111 MW-111 014 16.5 2.4 1/20/2006 9:30 1.19E+05 3.57E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-111 MW-111 015 16.5 2.4 1/27/2006 10:05 5.78E+05 1.73E+02 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-111 MW-111 016 16.5 2.4 2/3/2006 12:20 2.95E+05 3.09E+04 6.33E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-111 MW-111 017 16.5 2.4 2/7/2006 16:10 2.38E+05 2.78E+04 6.37E+02 1.17E+00 6.03E-01 6.31E-01 NA NA NA NA NA NA NA NA NA MW-111 MW-111 018 16.5 2.4 2/16/2006 13:40 2.94E+05 3.09E+04 6.36E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-111

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 31 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 MW-111 019 16.5 2.4 3/3/2006 9:00 2.36E+05 7.08E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-111 MW-111 020 16.5 2.4 4/7/2006 9:50 1.45E+05 4.35E+03 7.00E+02 NA NA NA NA NA NA NA NA NA NA NA NA MW-111 MW-111 021 16.5 2.4 5/17/2006 14:05 4.31E+04 6.51E+03 9.10E+02 2.49E+00 1.40E+00 1.24E+00

-2.32E-01 1.34E+01 1.51E+01 4.25E+00 1.30E+01 1.49E+01 NA NA NA MW-111 MW-111 022 16.5 2.4 6/23/2006 8:35 2.62E+05 3.92E+04 2.35E+03 6.23E-01 1.07E+00 1.32E+00

-4.18E+00 1.40E+01 1.46E+01

-1.60E-01 1.38E+01 1.52E+01 NA NA NA MW-111 MW-111 023 16.5 2.4 9/21/2006 10:25 1.59E+05 2.07E+04 1.42E+03 8.79E-01 1.25E+00 1.33E+00 9.50E-02 1.13E+00 1.26E+00

-6.26E-02 1.15E+00 1.24E+00 NA NA NA MW-111 MW-111 024 16.5 2.4 6/15/2007 14:17 1.19E+05 3.69E+03 3.52E+02 9.74E-01 6.30E-01 5.76E-01

-7.53E-01 3.27E+00 3.00E+00 1.21E-01 2.79E+00 3.17E+00 6.34E+00 1.26E+01 1.43E+01 MW-111 MW-111 025 16.5 2.4 8/3/2007 9:53 9.88E+04 2.93E+03 3.68E+02 9.74E-01 6.73E-01 6.27E-01 4.24E-01 2.75E+00 3.15E+00 3.95E-01 2.60E+00 3.02E+00 NA NA NA MW-111 MW-111 026 16.5 2.4 1/28/2008 11:38 4.77E+04 1.77E+03 2.97E+02 2.56E+00 9.45E-01 6.18E-01 2.60E+00 4.05E+00 3.90E+00

-6.32E-01 2.55E+00 2.63E+00 1.33E+01 1.58E+01 1.73E+01 MW-111 MW-111 027 16.5 2.4 9/4/2008 14:00 7.39E+04 1.89E+03 5.47E+02 1.02E+00 3.62E-01 4.21E-01

-8.16E-01 2.22E+00 3.61E+01 NA NA NA NA NA NA MW-111 MW-111 028 16.5 2.4 10/21/2008 14:20 6.64E+04 2.00E+03 2.60E+02 9.08E-01 9.32E-01 9.72E-01

-9.35E-01 3.60E+00 3.79E+00 5.10E-01 4.32E+00 5.03E+00 NA NA NA MW-111 MW-111 029 16.5 2.4 4/30/2009 12:36 3.89E+04 1.38E+03 1.71E+02 2.17E+00 8.97E-01 7.67E-01 1.51E+00 1.04E+01 6.92E+00

-3.30E+00 6.45E+00 6.44E+00 NA NA NA MW-111 MW-111 030 16.5 2.4 11/2/2009 15:48 2.26E+04 6.93E+02 1.80E+02 8.46E-01 5.72E-01 5.25E-01 5.61E-02 5.91E+00 6.73E+00

-1.39E-01 6.92E+00 7.69E+00 NA NA NA MW-111 MW-111 031 16.5 2.4 2/2/2010 14:27 2.63E+04 1.94E+03 4.29E+02 1.07E+00 5.60E-01 4.40E-01 1.87E+00 3.62E+00 4.27E+00

-1.55E-01 3.90E+00 4.40E+00 NA NA NA MW-111 MW-111 032 16.5 2.4 4/21/2010 14:48 3.35E+04 1.07E+03 1.91E+02 1.48E+00 7.26E-01 6.28E-01 6.79E+00 6.54E+00 4.32E+00 1.70E+00 4.37E+00 5.18E+00 NA NA NA MW-111 MW-111 033 16.5 2.4 8/27/2010 15:21 3.86E+04 1.13E+03 1.28E+02 6.44E-01 8.07E-01 8.55E-01

-8.83E-01 6.30E+00 6.59E+00 1.88E+00 5.70E+00 6.84E+00 NA NA NA MW-111 MW-111 034 16.5 2.4 9/10/2010 14:09 4.69E+04 1.37E+03 1.40E+02 1.80E+00 1.00E+00 8.02E-01

-5.04E+00 6.84E+00 6.88E+00

-5.62E-01 6.84E+00 7.62E+00 NA NA NA MW-111 MW-111 035 16.5 2.4 11/1/2010 14:55 4.59E+04 1.34E+03 1.27E+02 3.47E-01 5.90E-01 6.60E-01

-1.99E-01 5.63E+00 6.38E+00 5.49E+00 5.91E+00 7.75E+00 NA NA NA MW-111 MW-111 036 16.5 2.4 11/11/2011 11:30 1.11E+04 1.42E+03 3.31E+02 1.09E+00 1.53E+00 1.62E+00

-2.01E-01 7.11E+00 8.62E+00 2.75E+00 8.97E+00 1.21E+01 NA NA NA MW-111 U3-3 014 NA NA 7/13/2011 12:28 6.73E+02 3.81E+02 2.81E+02

-3.49E-01 8.13E-01 1.19E+00

-4.64E-01 8.01E+00 8.64E+00

-3.52E+00 8.61E+00 8.20E+00 NA NA NA U3-3 U3-3 015 NA NA 8/29/2011 13:09 1.03E+03 4.56E+02 2.66E+02

-5.04E-01 6.63E-01 1.06E+00

-2.50E+00 8.55E+00 7.82E+00

-3.69E+00 7.74E+00 7.12E+00 NA NA NA U3-3 U3-4D 007 25.6

-10.8 10/16/2005 12:00 3.70E+02 4.05E+02 4.38E+02 NA NA NA 4.72E+00 1.41E+01 1.01E+01 3.72E+00 1.12E+01 8.50E+00 NA NA NA U3-4D U3-4D 008 25.6

-10.8 10/21/2005 12:00 3.99E+02 3.90E+02 4.27E+02 NA NA NA 3.11E+00 9.34E+00 6.58E+00 2.98E+00 8.95E+00 6.58E+00 NA NA NA U3-4D U3-4D 009 25.6

-10.8 10/28/2005 12:00 4.05E+02 4.29E+02 4.72E+02 NA NA NA 3.91E+00 1.17E+01 8.54E+00 4.36E+00 1.31E+01 9.84E+00 NA NA NA U3-4D U3-4D 012 25.6

-10.8 11/18/2005 12:00 1.10E+02 4.35E+02 4.81E+02 NA NA NA 3.04E+00 9.13E+00 6.67E+00 2.04E+00 6.11E+00 4.97E+00 NA NA NA U3-4D U3-4D 013 25.6

-10.8 12/2/2005 12:00 2.73E+02 4.23E+02 4.64E+02 NA NA NA 2.97E+00 8.92E+00 6.62E+00 2.00E+00 6.01E+00 5.05E+00 NA NA NA U3-4D U3-4D 001 25.6

-10.8 12/15/2005 13:10 3.99E+02 4.32E+02 4.70E+02 NA NA NA 2.73E+00 8.20E+00 6.05E+00 2.88E+00 8.64E+00 6.66E+00 NA NA NA U3-4D U3-4D 002 25.6

-10.8 12/30/2005 9:25 4.42E+02 4.35E+02 4.71E+02 NA NA NA 3.53E+00 1.06E+01 7.76E+00 3.96E+00 1.19E+01 8.99E+00 NA NA NA U3-4D U3-4D 003 25.6

-10.8 1/12/2006 11:00 5.73E+02 4.38E+02 4.72E+02 NA NA NA 3.29E+00 9.86E+00 7.12E+00 3.42E+00 1.03E+01 7.75E+00 NA NA NA U3-4D U3-4D 004 25.6

-10.8 2/15/2006 13:45 2.71E+02 9.39E+02 6.36E+02 NA NA NA NA NA NA NA NA NA NA NA NA U3-4D U3-4D 006 25.6

-10.8 4/26/2006 14:20 5.75E+02 2.19E+02 1.87E+02

-1.48E-01 6.11E-01 7.91E-01

-3.01E-01 8.38E+00 9.11E+00

-3.10E+00 8.21E+00 8.71E+00 NA NA NA U3-4D U3-4D 014 25.6

-10.8 6/22/2006 10:20 7.10E+02 2.15E+02 1.68E+02 1.27E-01 5.73E-01 7.39E-01

-2.41E+00 1.15E+01 1.21E+01

-2.08E+00 8.42E+00 8.34E+00 NA NA NA U3-4D U3-4D 015 25.6

-10.8 2/1/2008 12:40 3.75E+02 1.36E+02 1.35E+02

-1.78E-01 7.83E-01 9.77E-01 2.83E-01 2.69E+00 3.10E+00 1.41E+00 3.26E+00 3.97E+00 NA NA NA U3-4D U3-4D 016 25.6

-10.8 4/29/2008 13:27 3.19E+02 1.43E+02 2.22E+02 1.44E-01 2.76E-01 4.94E-01 5.15E-01 1.91E+00 3.36E+00

-1.53E-01 1.73E+00 2.91E+00 NA NA NA U3-4D U3-4D 017 25.6

-10.8 7/28/2008 16:46 4.66E+02 2.50E+02 3.79E+02

-3.57E-01 4.96E-01 9.81E-01 2.89E-01 2.08E+00 3.62E+00 4.78E-01 2.36E+00 3.69E+00 NA NA NA U3-4D U3-4D 018 25.6

-10.8 10/20/2008 14:40 5.68E+02 1.71E+02 1.64E+02

-8.59E-02 8.61E-01 1.11E+00 3.53E-01 4.62E+00 5.17E+00 7.12E-01 4.13E+00 4.79E+00 NA NA NA U3-4D U3-4D 010 25.6

-10.8 11/4/2008 12:00 1.18E+02 4.23E+02 4.76E+02 NA NA NA 3.17E+00 9.51E+00 6.90E+00 3.34E+00 1.00E+01 7.54E+00 NA NA NA U3-4D U3-4D 011 25.6

-10.8 11/10/2008 12:00 3.16E+02 4.14E+02 4.61E+02 NA NA NA 4.10E+00 1.23E+01 8.95E+00 4.07E+00 1.22E+01 9.41E+00 NA NA NA U3-4D U3-4D 019 25.6

-10.8 2/10/2009 14:15 4.82E+02 2.31E+02 1.97E+02 1.00E-01 5.16E-01 6.41E-01 3.86E-01 2.66E+00 3.00E+00 7.53E-01 3.02E+00 3.39E+00 NA NA NA U3-4D U3-4D 020 25.6

-10.8 4/17/2009 15:57 3.82E+02 1.83E+02 1.89E+02

-1.17E-01 3.51E-01 5.11E-01

-9.67E-01 6.92E+00 4.61E+00 4.01E-01 3.32E+00 3.82E+00 NA NA NA U3-4D U3-4D 021 25.6

-10.8 8/5/2009 14:06 4.82E+02 1.88E+02 1.89E+02

-1.59E-01 5.17E-01 7.34E-01

-2.04E+00 5.43E+00 5.08E+00 1.93E+00 5.66E+00 6.65E+00 NA NA NA U3-4D U3-4D 022 25.6

-10.8 11/6/2009 13:15 4.73E+02 1.28E+02 1.06E+02

-8.06E-02 5.49E-01 6.68E-01 1.02E+00 5.84E+00 6.77E+00 3.35E-01 6.20E+00 7.03E+00 NA NA NA U3-4D U3-4D 023 25.6

-10.8 2/12/2010 14:15 8.65E+02 1.85E+02 1.77E+02

-1.60E-02 6.00E-01 7.86E-01 7.15E-01 3.15E+00 3.69E+00 1.91E+00 3.66E+00 4.34E+00 NA NA NA U3-4D U3-4D 024 25.6

-10.8 4/12/2010 12:49 1.07E+03 2.06E+02 1.77E+02

-4.68E-02 5.46E-01 7.39E-01

-5.85E+00 9.33E+00 8.95E+00

-2.13E+00 8.04E+00 7.89E+00 NA NA NA U3-4D U3-4D 025 25.6

-10.8 7/23/2010 13:21 6.84E+02 1.86E+02 1.77E+02

-1.56E-01 4.60E-01 6.46E-01 2.21E+00 7.56E+00 8.91E+00

-1.01E+00 7.61E+00 8.14E+00 NA NA NA U3-4D U3-4D 026 25.6

-10.8 10/28/2010 14:04 7.12E+02 1.68E+02 1.13E+02 2.26E-01 4.89E-01 5.61E-01 2.75E+00 5.75E+00 6.97E+00 1.33E+00 7.82E+00 9.00E+00 NA NA NA U3-4D U3-4D 027 25.6

-10.8 2/17/2011 14:41 6.28E+02 4.14E+02 4.05E+02

-8.34E-02 1.55E+00 1.95E+00 1.24E+00 4.72E+00 5.29E+00 8.61E-01 4.84E+00 5.47E+00 NA NA NA U3-4D U3-4D 028 25.6

-10.8 4/25/2011 14:50 7.41E+02 4.36E+02 3.98E+02 1.18E+00 1.38E+00 1.46E+00

-3.17E+00 7.58E+00 7.50E+00 4.81E-01 7.14E+00 8.11E+00 NA NA NA U3-4D U3-4D 029 25.6

-10.8 7/14/2011 11:55 3.88E+02 4.20E+02 4.38E+02 1.24E-01 1.06E+00 1.26E+00 4.78E+00 1.13E+01 1.32E+01 3.12E+00 1.22E+01 1.46E+01 NA NA NA U3-4D U3-4D 030 25.6

-10.8 7/29/2011 11:05 6.73E+02 4.02E+02 3.04E+02 1.23E-01 1.58E+00 1.90E+00 5.66E+00 8.43E+00 1.05E+01

-2.58E+00 9.30E+00 9.06E+00 NA NA NA U3-4D U3-4D 031 25.6

-10.8 11/16/2011 12:56 3.50E+02 3.63E+02 3.81E+02 3.17E-01 1.38E+00 1.64E+00

-9.88E-01 8.82E+00 1.07E+01

-9.21E-01 9.27E+00 1.17E+01 NA NA NA U3-4D U3-4S 001 NA NA 7/23/2010 14:12 3.74E+02 1.74E+02 1.79E+02 3.76E-01 4.15E-01 4.21E-01 9.00E-01 8.51E+00 9.30E+00 1.89E+00 7.75E+00 9.37E+00 NA NA NA U3-4S U3-4S 002 NA NA 10/29/2010 11:40 3.51E+02 1.32E+02 1.10E+02 3.86E-01 5.82E-01 6.43E-01 1.64E+00 5.59E+00 6.52E+00

-2.02E+00 5.91E+00 6.14E+00 NA NA NA U3-4S U3-4S 003 NA NA 4/25/2011 14:13 1.48E+02 3.78E+02 4.22E+02 6.69E-01 1.27E+00 1.41E+00 5.35E+00 8.82E+00 1.07E+01 1.75E+00 8.92E+00 1.03E+01 NA NA NA U3-4S U3-4S 004 NA NA 7/14/2011 11:27 3.29E+02 4.11E+02 4.36E+02 1.06E+00 1.33E+00 1.40E+00

-2.41E+00 7.59E+00 7.88E+00 3.25E+00 7.65E+00 9.52E+00 NA NA NA U3-4S U3-4S 005 NA NA 7/29/2011 10:06 4.67E+02 3.84E+02 3.43E+02 2.84E-01 1.64E+00 1.90E+00 9.19E+00 1.58E+01 9.23E+00 7.83E-01 1.02E+01 1.17E+01 NA NA NA U3-4S U3-4S 006 NA NA 11/16/2011 11:28 7.52E+02 4.41E+02 3.32E+02 9.35E-01 1.38E+00 1.47E+00

-2.06E+00 9.27E+00 1.12E+01 1.63E+00 7.80E+00 1.08E+01 NA NA NA U3-4S U3-T1 007 5.7 2.8 10/7/2005 12:00 1.59E+03 4.20E+02 4.15E+02 NA NA NA 2.71E+00 8.14E+00 6.09E+00 2.77E+00 8.30E+00 6.55E+00 NA NA NA U3-T1 U3-T1 008 5.7 2.8 10/21/2005 12:00 3.09E+02 3.87E+02 4.27E+02 NA NA NA 3.92E+00 1.18E+01 8.66E+00 3.87E+00 1.16E+01 9.03E+00 NA NA NA U3-T1 U3-T1 009 5.7 2.8 10/28/2005 12:00 3.40E+02 4.29E+02 4.72E+02 NA NA NA 3.55E+00 1.06E+01 8.06E+00 5.35E+00 1.61E+01 1.23E+01 NA NA NA U3-T1 U3-T1 010 5.7 2.8 11/4/2005 12:00 1.97E+02 4.29E+02 4.76E+02 NA NA NA 4.01E+00 1.20E+01 8.86E+00 3.90E+00 1.17E+01 9.13E+00 NA NA NA U3-T1 U3-T1 011 5.7 2.8 11/10/2005 12:00 5.63E+02 4.26E+02 4.61E+02 NA NA NA 3.11E+00 9.32E+00 6.89E+00 2.97E+00 8.92E+00 6.99E+00 NA NA NA U3-T1 U3-T1 012 5.7 2.8 11/18/2005 12:00 0.00E+00 4.29E+02 4.81E+02 NA NA NA 3.90E+00 1.17E+01 8.39E+00 3.40E+00 1.02E+01 7.71E+00 NA NA NA U3-T1 U3-T1 013 5.7 2.8 12/2/2005 12:00 4.98E+02 4.29E+02 4.64E+02 NA NA NA 2.80E+00 8.39E+00 6.23E+00 2.94E+00 8.83E+00 6.86E+00 NA NA NA U3-T1 U3-T1 001 5.7 2.8 12/15/2005 13:15 3.40E+02 4.29E+02 4.70E+02 NA NA NA 2.53E+00 7.60E+00 5.63E+00 2.89E+00 8.67E+00 6.65E+00 NA NA NA U3-T1 U3-T1 002 5.7 2.8 12/30/2005 10:40 5.29E+02 4.38E+02 4.71E+02 NA NA NA 4.02E+00 1.21E+01 8.71E+00 4.07E+00 1.22E+01 9.17E+00 NA NA NA U3-T1 U3-T1 003 5.7 2.8 1/12/2006 9:50 7.87E+02 4.47E+02 4.72E+02 NA NA NA 3.10E+00 9.31E+00 6.88E+00 2.83E+00 8.49E+00 6.70E+00 NA NA NA U3-T1 U3-T1 004 5.7 2.8 2/15/2006 13:15 8.35E+02 1.65E+03 6.36E+02 NA NA NA NA NA NA NA NA NA NA NA NA U3-T1 U3-T1 005 5.7 2.8 3/16/2006 11:50 1.26E+03 2.79E+02 1.85E+02 6.55E-01 8.43E-01 8.29E-01 1.06E+00 5.49E+00 6.18E+00

-1.81E-01 5.63E+00 6.14E+00 NA NA NA U3-T1 U3-T1 006 5.7 2.8 5/26/2006 13:30 7.32E+02 2.33E+02 1.89E+02 1.27E+00 1.02E+00 1.01E+00 1.21E+00 8.34E+00 9.42E+00 5.99E+00 8.98E+00 1.15E+01 NA NA NA U3-T1 U3-T1 014 5.7 2.8 7/12/2006 12:50 6.84E+02 2.36E+02 1.98E+02 3.36E-01 1.36E+00 1.44E+00 1.15E+00 1.13E+01 1.18E+01

-1.14E+00 1.18E+01 1.26E+01 NA NA NA U3-T1 U3-T1 015 5.7 2.8 8/15/2006 11:30 7.66E+02 2.25E+02 1.73E+02 NA NA NA

-4.04E+00 6.82E+00 6.33E+00 2.15E+00 6.84E+00 8.29E+00 NA NA NA U3-T1 U3-T1 016 5.7 2.8 6/12/2007 12:54 5.06E+02 4.25E+02 4.39E+02 6.25E-01 8.75E-01 9.54E-01

-8.51E-02 2.94E+00 2.22E+00 7.17E-01 2.00E+00 2.33E+00

-1.46E+00 1.40E+01 1.63E+01 U3-T1 U3-T1 017 5.7 2.8 8/1/2007 13:20 4.90E+02 3.38E+02 2.73E+02 5.21E-02 5.13E-01 6.47E-01 8.49E-01 3.57E+00 4.15E+00 2.88E-01 3.42E+00 3.92E+00 NA NA NA U3-T1 U3-T1 018 5.7 2.8 10/22/2007 16:13 5.30E+02 4.01E+02 4.01E+02 3.41E-01 5.49E-01 6.09E-01

-1.08E+00 3.44E+00 3.64E+00

-1.34E+00 3.52E+00 3.68E+00 NA NA NA U3-T1 U3-T1 019 5.7 2.8 1/22/2008 16:11 6.05E+02 3.15E+02 2.97E+02 6.43E-01 7.41E-01 7.79E-01 1.11E+00 2.75E+00 3.21E+00 2.38E-01 2.51E+00 2.75E+00 1.14E+01 1.65E+01 1.84E+01 U3-T1 U3-T1 019 5.7 2.8 1/22/2008 16:11 7.29E+02 3.27E+02 2.96E+02 6.26E-01 7.26E-01 7.69E-01 1.21E+00 3.14E+00 3.76E+00

-1.79E-01 3.56E+00 3.93E+00 8.87E+00 1.85E+01 2.09E+01 U3-T1

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 32 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 U3-T15 020 5.7 2.8 5/2/2008 15:24 7.09E+02 1.63E+02 2.22E+02 7.24E-01 5.19E-01 8.26E-01 2.85E-01 1.84E+00 3.19E+00

-1.15E+00 1.87E+00 2.82E+00 NA NA NA U3-TI5 U3-T15 021 5.7 2.8 7/23/2008 11:16 5.56E+02 2.58E+02 3.79E+02 6.40E-01 5.19E-01 8.37E-01 2.41E+00 2.24E+00 4.18E+00 6.54E-01 2.44E+00 4.01E+00 NA NA NA U3-T15 U3-T15 022 5.7 2.8 10/20/2008 10:19 5.99E+02 5.63E+02 5.91E+02 7.01E-01 5.47E-01 5.20E-01 2.51E+00 6.27E+00 7.46E+00 1.51E+00 6.24E+00 7.35E+00 NA NA NA U3-T15 U3-T15 023 5.7 2.8 1/28/2009 12:00 6.75E+02 2.48E+02 2.04E+02 1.04E+00 7.47E-01 7.44E-01

-1.53E+00 3.59E+00 2.95E+00

-6.63E-01 2.30E+00 2.48E+00 NA NA NA U3-T15 U3-T15 024 5.7 2.8 4/10/2009 15:22 3.28E+02 1.65E+02 1.49E+02 3.23E-01 6.69E-01 7.61E-01 1.68E-01 6.03E+00 4.02E+00 1.24E+00 3.39E+00 4.14E+00 NA NA NA U3-T15 U3-T15 025 5.7 2.8 7/14/2009 11:08 3.99E+02 2.36E+02 2.32E+02 4.77E-02 7.47E-01 8.96E-01 2.51E+00 5.24E+00 5.65E+00 9.47E-01 3.72E+00 4.45E+00 NA NA NA U3-T15 U3-T15 026 5.7 2.8 11/13/2009 16:35 3.79E+02 1.18E+02 1.03E+02 3.87E-01 5.95E-01 6.63E-01

-6.81E-01 5.33E+00 5.76E+00 1.33E+00 6.33E+00 7.37E+00 NA NA NA U3-T15 U3-T15 027 5.7 2.8 2/10/2010 12:02 4.76E+02 1.73E+02 1.78E+02 2.19E-01 6.55E-01 7.88E-01

-1.28E+00 6.23E+00 5.80E+00 2.78E+00 3.74E+00 4.78E+00 NA NA NA U3-T15 U3-T15 028 5.7 2.8 5/5/2010 16:54 5.00E+02 1.79E+02 1.84E+02 6.48E-02 4.95E-01 5.97E-01

-3.25E+00 8.98E+00 1.04E+01

-8.61E-01 6.62E+00 7.16E+00 NA NA NA U3-T15 U3-T15 029 5.7 2.8 7/26/2010 12:15 3.84E+02 1.74E+02 1.78E+02 1.20E-02 3.91E-01 4.99E-01 5.07E+00 7.68E+00 9.77E+00

-6.61E-01 6.96E+00 7.49E+00 NA NA NA U3-T15 U3-T15 030 5.7 2.8 10/29/2010 16:04 3.04E+02 1.28E+02 1.10E+02 4.84E-02 6.36E-01 7.68E-01

-8.56E-01 6.04E+00 6.70E+00 1.59E+00 5.73E+00 6.79E+00 NA NA NA U3-T15 U3-T15 031 5.7 2.8 2/22/2011 11:11 6.55E+02 4.08E+02 3.92E+02 1.62E+00 1.96E+00 2.02E+00 1.80E+00 1.05E+01 6.14E+00 2.12E+00 6.42E+00 7.54E+00 NA NA NA U3-T15 U3-T15 032 5.7 2.8 5/6/2011 10:23 7.82E+02 5.16E+02 5.03E+02

-6.43E-02 9.94E-01 1.30E+00

-3.24E+00 9.12E+00 9.22E+00 8.49E-01 1.09E+01 1.21E+01 NA NA NA U3-T15 U3-T15 033 5.7 2.8 8/22/2011 14:40 1.00E+03 3.42E+02 1.95E+02

-6.26E-02 1.10E+00 1.37E+00

-4.61E-01 8.70E+00 8.45E+00

-2.62E+00 8.31E+00 8.23E+00 NA NA NA U3-T15 U3-T15 034 5.7 2.8 10/19/2011 11:39 7.69E+02 4.05E+02 3.84E+02 1.59E-01 1.19E+00 1.45E+00

-3.93E-01 9.51E+00 1.17E+01 2.12E-01 9.12E+00 1.17E+01 NA NA NA U3-T15 U3-T2 012 5.7 2.6 10/7/2005 12:00 7.03E+02 3.93E+02 4.15E+02 NA NA NA 3.67E+00 1.10E+01 8.06E+00 4.13E+00 1.24E+01 9.39E+00 NA NA NA U3-T2 U3-T2 013 5.7 2.6 10/21/2005 12:00 1.47E+03 3.63E+02 4.27E+02 NA NA NA 3.33E+00 1.00E+01 7.23E+00 3.00E+00 9.00E+00 6.90E+00 NA NA NA U3-T2 U3-T2 014 5.7 2.6 10/28/2005 12:00 1.28E+03 4.56E+02 4.72E+02 NA NA NA 3.44E+00 1.03E+01 7.67E+00 4.28E+00 1.28E+01 9.89E+00 NA NA NA U3-T2 U3-T2 015 5.7 2.6 11/4/2005 12:00 1.19E+03 4.59E+02 4.76E+02 NA NA NA 3.41E+00 1.02E+01 7.53E+00 3.86E+00 1.16E+01 8.81E+00 NA NA NA U3-T2 U3-T2 016 5.7 2.6 11/10/2005 12:00 1.64E+03 4.59E+02 4.61E+02 NA NA NA 3.81E+00 1.14E+01 8.34E+00 3.98E+00 1.19E+01 9.09E+00 NA NA NA U3-T2 U3-T2 017 5.7 2.6 11/18/2005 12:00 1.13E+03 4.65E+02 4.81E+02 NA NA NA 3.97E+00 1.19E+01 8.70E+00 4.15E+00 1.25E+01 9.55E+00 NA NA NA U3-T2 U3-T2 018 5.7 2.6 12/2/2005 12:00 1.33E+03 4.56E+02 4.64E+02 NA NA NA 2.31E+00 6.92E+00 5.23E+00 2.58E+00 7.74E+00 6.11E+00 NA NA NA U3-T2 U3-T2 001 5.7 2.6 12/15/2005 13:30 1.29E+03 4.62E+02 4.70E+02 NA NA NA 2.77E+00 8.30E+00 6.09E+00 2.85E+00 8.55E+00 6.57E+00 NA NA NA U3-T2 U3-T2 002 5.7 2.6 12/30/2005 10:50 1.69E+03 4.74E+02 4.71E+02 NA NA NA 3.81E+00 1.14E+01 8.46E+00 3.49E+00 1.05E+01 8.31E+00 NA NA NA U3-T2 U3-T2 003 5.7 2.6 1/6/2006 8:45 2.42E+03 4.92E+02 4.66E+02 NA NA NA 2.86E+00 8.57E+00 6.56E+00 4.04E+00 1.21E+01 9.38E+00 NA NA NA U3-T2 U3-T2 004 5.7 2.6 1/13/2006 13:20 1.78E+03 4.77E+02 4.72E+02 NA NA NA 4.01E+00 1.20E+01 8.74E+00 3.41E+00 1.02E+01 7.94E+00 NA NA NA U3-T2 U3-T2 005 5.7 2.6 1/20/2006 11:00 1.75E+03 4.56E+02 4.61E+02 NA NA NA 3.40E+00 1.02E+01 7.71E+00 3.27E+00 9.82E+00 7.99E+00 NA NA NA U3-T2 U3-T2 006 5.7 2.6 1/25/2006 11:10 2.32E+03 4.86E+02 4.61E+02 NA NA NA 3.96E+00 1.19E+01 8.77E+00 3.17E+00 9.50E+00 7.64E+00 NA NA NA U3-T2 U3-T2 007 5.7 2.6 2/1/2006 11:15 2.13E+03 4.80E+02 4.60E+02 NA NA NA 3.17E+00 9.51E+00 7.02E+00 3.47E+00 1.04E+01 7.99E+00 NA NA NA U3-T2 U3-T2 009 5.7 2.6 2/17/2006 9:20 1.92E+03 2.50E+03 6.36E+02 NA NA NA NA NA NA NA NA NA NA NA NA U3-T2 U3-T2 010 5.7 2.6 3/16/2006 12:00 1.69E+03 3.36E+02 2.04E+02 5.87E-01 9.21E-01 1.00E+00

-7.43E-01 6.36E+00 6.83E+00

-1.22E-01 6.33E+00 6.88E+00 NA NA NA U3-T2 U3-T2 011 5.7 2.6 5/26/2006 13:15 1.90E+03 3.86E+02 2.48E+02 1.49E+00 1.11E+00 1.01E+00 1.64E+00 1.01E+01 1.22E+01 5.67E+00 9.40E+00 1.25E+01 NA NA NA U3-T2 U3-T2 019 5.7 2.6 7/12/2006 12:25 1.83E+03 3.78E+02 2.54E+02 7.24E-01 1.72E+00 1.80E+00 2.58E+00 6.90E+00 8.07E+00 1.30E+00 6.69E+00 7.74E+00 NA NA NA U3-T2 U3-T2 020 5.7 2.6 8/15/2006 10:30 1.58E+03 7.79E+02 7.72E+02 NA NA NA

-8.87E-01 7.17E+00 7.64E+00 3.29E+00 9.10E+00 1.14E+01 NA NA NA U3-T2 U3-T2 021 5.7 2.6 6/12/2007 9:25 1.45E+03 5.19E+02 4.36E+02

-3.89E-01 7.05E-01 9.59E-01 2.03E-01 2.29E+00 2.54E+00

-1.00E-01 2.42E+00 2.74E+00 5.88E+00 1.39E+01 1.57E+01 U3-T2 U3-T2 022 5.7 2.6 8/1/2007 14:14 1.25E+03 4.62E+02 2.55E+02

-4.84E-02 5.37E-01 7.11E-01

-1.75E+00 3.23E+00 3.20E+00 1.99E-02 3.54E+00 4.00E+00 NA NA NA U3-T2 U3-T2 023 5.7 2.6 10/22/2007 15:07 1.17E+03 4.76E+02 4.02E+02 2.36E-01 5.28E-01 6.08E-01

-7.13E-02 2.82E+00 3.11E+00 2.53E+00 3.50E+02 3.81E+00 NA NA NA U3-T2 U3-T2 024 5.7 2.6 1/22/2008 16:16 1.33E+03 3.83E+02 2.97E+02 4.31E-01 8.54E-01 9.63E-01 7.39E-01 2.97E+00 3.39E+00

-1.14E+00 3.39E+00 2.86E+00 2.78E+00 1.62E+01 1.89E+01 U3-T2 U3-T2 025 5.7 2.6 5/2/2008 14:44 1.02E+03 1.77E+02 2.22E+02 6.52E-01 3.31E-01 4.70E-01 5.80E-01 2.06E+00 3.53E+00 7.90E-01 1.63E+00 3.00E+00 NA NA NA U3-T2 U3-T2 026 5.7 2.6 7/23/2008 13:40 9.97E+02 2.85E+02 3.64E+02 5.90E-01 5.19E-01 8.44E-01 3.57E-02 1.72E+00 2.93E+00

-1.02E+00 2.44E+00 3.39E+00 NA NA NA U3-T2 U3-T2 027 5.7 2.6 10/20/2008 10:36 9.28E+02 5.97E+02 5.90E+02 4.73E-01 4.95E-01 4.85E-01

-4.68E-01 4.82E+00 5.31E+00

-5.02E+00 6.54E+00 6.06E+00 NA NA NA U3-T2 U3-T2 028 5.7 2.6 1/28/2009 11:40 1.11E+03 2.87E+02 2.04E+02 6.04E-01 6.41E-01 6.75E-01 7.10E-01 2.42E+00 2.74E+00 4.09E-01 2.30E+00 2.61E+00 NA NA NA U3-T2 U3-T2 029 5.7 2.6 4/24/2009 11:24 1.03E+03 4.97E+02 4.14E+02 1.76E+00 6.54E-01 4.11E-01 1.62E+00 6.65E+00 4.43E+00 3.29E-01 4.16E+00 4.69E+00 NA NA NA U3-T2 U3-T2 030 5.7 2.6 7/14/2009 13:04 1.12E+03 2.94E+02 2.30E+02 5.50E-01 8.61E-01 9.58E-01 1.31E-01 3.69E+00 4.23E+00

-6.32E-01 3.72E+00 4.05E+00 NA NA NA U3-T2 U3-T2 031 5.7 2.6 11/16/2009 12:53 8.94E+02 1.52E+02 1.03E+02 3.24E-01 6.54E-01 7.43E-01 3.94E-01 6.63E+00 6.48E+00

-2.09E+00 6.95E+00 6.93E+00 NA NA NA U3-T2 U3-T2 032 5.7 2.6 2/11/2010 12:43 9.41E+02 1.88E+02 1.78E+02 5.85E-01 7.72E-01 8.17E-01

-8.06E-01 3.38E+00 3.63E+00 7.20E-02 3.71E+00 4.10E+00 NA NA NA U3-T2 U3-T2 033 5.7 2.6 5/7/2010 13:05 9.75E+02 1.95E+02 1.83E+02 6.31E-01 6.31E-01 6.58E-01

-2.27E+00 5.70E+00 5.99E+00

-1.66E+00 6.62E+00 6.97E+00 NA NA NA U3-T2 U3-T2 034 5.7 2.6 7/26/2010 14:26 8.76E+02 1.92E+02 1.74E+02 5.34E-01 6.12E-01 6.47E-01

-2.12E+00 7.50E+00 7.69E+00 2.29E+00 7.21E+00 8.84E+00 NA NA NA U3-T2 U3-T2 035 5.7 2.6 10/29/2010 11:22 1.47E+03 2.19E+02 1.11E+02 4.22E-01 6.79E-01 7.56E-01

-6.11E-02 5.42E+00 6.11E+00 3.00E+00 5.47E+00 6.89E+00 NA NA NA U3-T2 U3-T2 036 5.7 2.6 2/22/2011 14:30 2.27E+03 4.92E+02 3.62E+02 1.82E+00 2.04E+00 2.05E+00 3.65E+00 6.08E+00 7.29E+00 5.97E-01 7.12E+00 7.85E+00 NA NA NA U3-T2 U3-T2 037 5.7 2.6 5/6/2011 11:41 3.83E+03 6.42E+02 4.19E+02 3.27E-01 1.32E+00 1.58E+00 2.82E+00 7.26E+00 8.74E+00 5.77E-01 9.68E+00 1.08E+01 NA NA NA U3-T2 U3-T2 038 5.7 2.6 7/8/2011 10:55 2.67E+03 6.63E+02 2.80E+02 4.75E-01 1.31E+00 1.50E+00 3.77E+00 1.08E+01 1.19E+01

-1.06E+00 1.02E+01 1.07E+01 NA NA NA U3-T2 U3-T2 039 5.7 2.6 7/29/2011 12:32 2.65E+03 7.02E+02 3.34E+02 1.05E+00 1.81E+00 1.99E+00

-5.43E-01 8.49E+00 9.21E+00 2.63E+00 8.91E+00 1.07E+01 NA NA NA U3-T2 U3-T2 040 5.7 2.6 10/19/2011 10:20 2.98E+03 7.62E+02 3.28E+02

-8.79E-02 1.15E+00 1.47E+00

-4.88E+00 1.02E+01 1.09E+01

-5.13E+00 1.12E+01 1.23E+01 NA NA NA U3-T2 U1-CSS 001 14 6.1 1/30/2007 11:45 1.76E+03 6.00E+02 5.70E+02 1.95E+01 2.19E+00 1.70E+00 7.00E-01 1.32E+00 1.40E+00

-3.20E-01 1.38E+00 1.60E+00 1.64E+01 2.67E+01 2.90E+01 U1-CSS U1-CSS 002 14 6.1 2/27/2007 11:24 4.32E+03 6.90E+02 5.70E+02 1.38E+01 2.31E+00 2.10E+00 1.11E+00 1.95E+00 2.10E+00 7.00E-01 1.95E+00 2.20E+00

-1.30E+00 2.55E+01 2.90E+01 U1-CSS U1-CSS 003 14 6.1 6/13/2007 11:39 1.53E+03 5.25E+02 4.35E+02 1.45E+01 1.91E+00 6.24E-01 8.50E-01 3.57E+00 4.15E+00 2.82E+00 4.28E+00 4.93E+00 4.42E+00 1.95E+01 2.22E+01 U1-CSS U1-CSS 004 14 6.1 8/6/2007 15:55 2.80E+03 2.81E+02 1.95E+02 2.68E+01 2.33E+00 5.71E-01 2.53E+00 4.30E+00 4.61E+00 2.48E+00 6.84E+00 4.17E+00 NA NA NA U1-CSS U1-CSS 005 14 6.1 1/15/2008 14:54 4.95E+02 2.04E+02 1.76E+02 7.73E+00 1.31E+00 6.91E-01 2.85E+00 6.56E+00 3.36E+00

-6.88E-02 3.33E+00 3.71E+00 NA NA NA U1-CSS U1-CSS 006 14 6.1 4/23/2008 15:25 1.77E+03 1.96E+02 1.44E+02 6.74E+00 9.01E-01 7.19E-01

-1.36E+00 2.12E+00 3.20E+00

-7.61E-01 2.08E+00 3.16E+00 NA NA NA U1-CSS U1-CSS 007 14 6.1 5/12/2008 14:05 6.88E+02 1.35E+02 1.42E+02 4.83E+00 8.35E-01 9.25E-01 2.59E+00 2.30E+00 4.25E+00 3.09E-01 2.58E+00 3.96E+00

-2.18E+00 1.19E+01 2.08E+01 U1-CSS U1-CSS 008 14 6.1 9/8/2008 10:24 1.45E+03 3.77E+02 4.98E+02 9.38E+00 9.40E-01 5.43E-01 1.90E+00 2.07E+00 3.76E+00 NA NA NA NA NA NA U1-CSS U1-CSS 009 14 6.1 11/6/2008 14:48 2.66E+03 3.86E+02 1.66E+02 6.74E+00 1.20E+00 5.33E-01 3.52E+00 6.01E+00 7.29E+00

-1.94E+00 6.45E+00 6.67E+00 1.02E+01 1.65E+01 1.85E+01 U1-CSS U1-CSS 010 14 6.1 11/19/2008 13:50 2.20E+03 2.33E+02 1.62E+02 9.08E+00 1.38E+00 5.80E-01 2.35E+00 4.04E+00 4.98E+00 8.56E-01 4.63E+00 5.37E+00 NA NA NA U1-CSS U1-CSS 011 14 6.1 3/18/2009 13:05 1.57E+03 5.36E+02 3.81E+02 1.41E+01 2.04E+00 9.24E-01 2.00E+00 5.93E+00 3.95E+00 2.86E-01 3.03E+00 3.42E+00 6.46E-01 1.94E+01 2.22E+01 U1-CSS U1-CSS 012 14 6.1 4/21/2009 13:07 3.28E+03 3.87E+02 1.91E+02 3.56E+01 2.64E+00 7.19E-01 5.75E-01 5.28E+00 3.52E+00 1.36E+00 3.02E+00 3.74E+00 1.79E+01 1.92E+01 2.11E+01 U1-CSS U1-CSS 013 14 6.1 10/26/2009 14:07 2.91E+03 2.81E+02 1.86E+02 1.75E+01 1.88E+00 5.38E-01

-1.10E-01 5.94E+00 6.71E+00

-4.96E+00 5.91E+00 5.17E+00 0.00E+00 2.04E+01 2.34E+01 U1-CSS U1-CSS 014 14 6.1 5/3/2010 15:58 1.88E+03 2.79E+02 1.70E+02 8.95E+00 1.81E+00 8.92E-01 4.61E-01 5.87E+00 6.66E+00 3.94E+00 5.22E+00 6.88E+00

-1.79E+01 2.18E+01 2.53E+01 U1-CSS U1-CSS 015 14 6.1 11/8/2010 14:56 2.26E+03 2.72E+02 1.26E+02 1.18E+01 1.45E+00 6.84E-01 2.29E+00 5.01E+00 5.93E+00 2.07E+00 5.61E+00 6.70E+00 3.16E-01 1.81E+01 2.13E+01 U1-CSS U1-CSS 016 14 6.1 5/4/2011 13:24 6.38E+03 6.84E+02 3.40E+02 1.61E+01 2.70E+00 1.01E+00 3.29E+00 8.36E+00 9.79E+00 7.12E+00 9.42E+00 1.24E+01

-1.05E+01 1.55E+01 1.84E+01 U1-CSS U1-CSS 017 14 6.1 7/8/2011 13:33 1.08E+04 1.28E+03 2.79E+02 3.90E+00 1.82E+00 1.30E+00 3.84E-02 9.18E+00 1.01E+01

-3.60E+00 9.96E+00 1.06E+01

-3.20E+00 2.09E+01 2.34E+01 U1-CSS U1-CSS 018 14 6.1 10/27/2011 13:02 1.70E+03 5.64E+02 4.77E+02 7.82E-01 1.28E+00 1.39E+00

-2.80E+00 8.07E+00 8.99E+00 1.05E+00 7.08E+00 9.69E+00

-8.01E+00 1.78E+01 2.07E+01 U1-CSS U1-NCD 001 NA NA 5/8/2008 9:45 9.50E+03 3.49E+02 1.96E+02 3.97E+02 2.58E+00 3.57E-01 NA NA NA NA NA NA NA NA NA U1-NCD U1-NCD 002 NA NA 10/15/2008 12:35 6.19E+03 3.71E+02 1.61E+02 4.35E+02 5.89E+00 3.33E-01 NA NA NA NA NA NA NA NA NA U1-NCD U1-NCD 003 NA NA 1/12/2009 13:45 2.13E+03 2.48E+02 1.92E+02 4.64E+02 8.90E+00 6.61E-01 2.84E+04 2.63E+03 1.22E+01 7.66E-01 2.37E+00 2.80E+00 6.41E+02 4.11E+01 1.89E+01 U1-NCD U1-NCD 004 NA NA 4/13/2009 12:15 5.21E+03 5.18E+02 1.35E+02 3.22E+02 7.74E+00 8.42E-01 2.70E+04 2.66E+01 1.77E+01 2.70E+00 4.46E+00 5.13E+00 5.09E+02 6.05E+01 4.30E+01 U1-NCD

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 33 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 U1-NCD 005 NA NA 7/13/2009 12:30 2.66E+03 3.86E+02 2.08E+02 1.30E+02 4.98E+00 5.04E-01 1.78E+04 1.36E+03 1.39E+01 7.71E-01 3.71E+00 4.30E+00 2.91E+02 2.72E+01 2.12E+01 U1-NCD U1-NCD 006 NA NA 10/12/2009 9:40 3.11E+03 2.90E+02 1.88E+02 8.37E+01 3.94E+00 5.22E-01 1.32E+04 9.90E+02 1.60E+01 1.87E+00 6.39E+00 7.72E+00 3.13E+02 3.09E+01 2.30E+01 U1-NCD U1-NCD 007 NA NA 1/4/2010 9:00 5.47E+03 3.48E+02 1.81E+02 6.40E+01 3.33E+00 4.39E-01 1.14E+04 1.58E+03 6.64E+00 8.50E-01 2.52E+00 2.89E+00 2.31E+02 2.85E+01 2.15E+01 U1-NCD U1-NCD 008 NA NA 7/15/2010 9:10 1.35E+04 4.41E+02 1.58E+02 5.06E+01 3.21E+00 7.59E-01 1.14E+04 1.42E+03 1.40E+01 7.51E-01 5.21E+00 6.03E+00 2.90E+02 3.39E+01 2.40E+01 U1-NCD U1-NCD 009 NA NA 10/20/2010 13:40 3.34E+03 3.23E+02 1.27E+02 3.88E+01 2.31E+00 6.39E-01 1.20E+04 1.47E+03 9.98E+00

-1.14E+00 4.96E+00 5.42E+00 2.31E+02 3.19E+01 2.23E+01 U1-NCD U1-NCD 011 NA NA 9/15/2011 11:45 3.86E+03 6.39E+02 3.99E+02 9.08E+01 7.80E+00 1.54E+00 4.77E+03 6.42E+02 8.81E+00 3.36E+00 4.68E+00 5.97E+00 1.14E+02 2.09E+01 1.82E+01 U1-NCD U1-NCD 012 NA NA 10/3/2011 13:20 1.13E+04 1.03E+03 3.35E+02 1.58E+01 3.72E+00 1.74E+00 5.92E+03 8.04E+02 1.43E+01 1.93E+00 7.20E+00 9.97E+00 1.36E+02 2.21E+01 1.86E+01 U1-NCD U1-NCD 013 NA NA 12/26/2011 12:45 2.32E+03 5.13E+02 3.74E+02 1.49E+01 5.52E+00 3.33E+00 7.73E+03 9.75E+02 1.84E+01

-1.01E+00 9.48E+00 1.17E+01 1.96E+02 2.79E+01 1.88E+01 U1-NCD U1-SFDS 001 NA NA 4/9/2008 8:55 6.28E+02 1.41E+02 1.97E+02 9.98E+00 4.86E-01 4.31E-01 NA NA NA NA NA NA NA NA NA U1-SFDS U1-SFDS 002 NA NA 5/8/2008 9:10 8.81E+02 1.50E+02 1.96E+02 1.40E+01 5.18E-01 3.69E-01 NA NA NA NA NA NA NA NA NA U1-SFDS U1-SFDS 003 NA NA 10/15/2008 12:45 1.09E+03 1.79E+02 1.67E+02 1.85E+01 1.26E+00 4.56E-01 NA NA NA NA NA NA NA NA NA U1-SFDS U1-SFDS 004 NA NA 1/14/2009 9:15 3.11E+02 1.82E+02 1.93E+02 1.22E+01 1.67E+00 8.15E-01 6.39E+00 3.47E+00 2.22E+00 1.03E+00 1.91E+00 2.27E+00 7.26E+00 1.62E+01 1.83E+01 U1-SFDS U1-SFDS 005 NA NA 4/13/2009 12:30 1.52E+03 2.96E+02 1.37E+02 4.93E+01 3.03E+00 6.15E-01 8.09E+00 5.87E+00 3.91E+00 2.45E+00 3.80E+00 4.79E+00

-9.47E+00 1.92E+01 2.30E+01 U1-SFDS U1-SFDS 006 NA NA 7/15/2009 8:30 7.33E+02 2.73E+02 2.39E+02 3.54E+01 2.67E+00 4.79E-01 9.41E+00 7.41E+00 3.60E+00

-9.93E-02 4.44E+00 4.64E+00 5.10E+00 2.14E+01 2.44E+01 U1-SFDS U1-SFDS 007 NA NA 10/14/2009 9:50 7.04E+02 1.98E+02 1.88E+02 2.91E+01 2.31E+00 5.00E-01 1.22E+01 8.32E+00 6.38E+00 6.68E-01 5.80E+00 6.68E+00

-5.49E+00 1.69E+01 1.97E+01 U1-SFDS U1-SFDS 008 NA NA 1/6/2010 8:50 5.10E+02 1.83E+02 1.81E+02 1.25E+01 1.46E+00 4.47E-01 8.18E+00 4.07E+00 2.98E+00

-5.94E-01 2.91E+00 3.18E+00

-2.06E+00 1.84E+01 2.15E+01 U1-SFDS U1-SFDS 009 NA NA 7/7/2010 8:45 6.44E+02 1.80E+02 1.45E+02 1.88E+01 2.10E+00 6.82E-01 2.09E+01 1.26E+01 7.48E+00 1.64E+00 7.91E+00 9.44E+00 3.42E+00 2.24E+01 2.58E+01 U1-SFDS U1-SFDS 010 NA NA 10/20/2010 8:45 4.82E+02 1.56E+02 1.26E+02 1.17E+01 1.83E+00 8.74E-01 7.99E+00 7.54E+00 5.78E+00

-8.31E-01 5.24E+00 5.67E+00 9.71E-01 1.86E+01 2.18E+01 U1-SFDS U1-SFDS 013 NA NA 9/15/2011 11:35 2.09E+03 5.25E+02 4.00E+02 7.79E+00 2.54E+00 1.39E+00 9.23E+00 6.72E+00 6.70E+00 1.14E+00 6.27E+00 7.16E+00

-4.97E+00 1.70E+01 1.95E+01 U1-SFDS U1-SFDS 014 NA NA 10/5/2011 9:00 2.02E+03 5.01E+02 3.35E+02 5.54E+00 2.53E+00 1.97E+00 4.27E+00 9.96E+00 1.25E+01

-6.39E+00 8.94E+00 9.49E+00 2.06E+01 1.87E+01 2.00E+01 U1-SFDS U1-SFDS 015 NA NA 12/28/2011 8:19 1.10E+02 3.21E+02 3.61E+02 2.66E+00 2.22E+00 2.08E+00

-3.38E+00 9.87E+00 1.13E+01 3.75E-01 1.02E+01 1.33E+01

-4.44E+00 1.47E+01 1.73E+01 U1-SFDS I-2 001 NA NA 8/2/2010 14:39 6.21E+01 1.53E+02 1.73E+02

-2.56E-01 3.72E-01 5.25E-01 7.04E+00 7.80E+00 1.02E+01 9.34E-02 6.54E+00 7.19E+00 NA NA NA I-2 I-2 002 NA NA 11/17/2010 14:25 1.74E+02 1.71E+02 3.78E+02 2.25E-01 6.25E-01 1.50E+00

-4.50E-01 5.04E+00 1.10E+01 3.35E+00 5.94E+00 1.40E+01 NA NA NA I-2 I-2 003 NA NA 8/12/2011 15:13 2.34E+02 2.15E+02 2.00E+02

-5.95E-01 7.44E-01 1.16E+00 5.11E+00 1.19E+01 1.35E+01

-2.57E-01 9.24E+00 1.02E+01 NA NA NA I-2 I-2 004 NA NA 12/8/2011 14:15

-3.49E+01 3.45E+02 4.09E+02

-2.39E-01 1.56E+00 1.92E+00

-2.35E+00 8.76E+00 1.00E+01

-2.12E+00 8.46E+00 1.04E+01 NA NA NA I-2 RW-1 002 107.5

-30 10/25/2006 14:15 2.95E+04 2.28E+03 5.85E+02 3.10E-01 8.79E-01 9.23E-01 1.99E+00 5.23E+00 5.98E+00 4.31E-01 4.74E+00 5.22E+00 NA NA NA RW-1 RW-1 001 107.5

-30 10/25/2006 11:37 6.41E+04 4.88E+03 8.52E+02

-8.44E-01 1.29E+00 1.52E+00 9.50E-01 4.75E+00 5.45E+00 8.01E-01 4.62E+00 5.32E+00 NA NA NA RW-1 RW-1 005 107.5

-30 10/31/2006 20:00 1.89E+04 1.49E+03 4.73E+02 9.06E-01 1.15E+00 1.14E+00 5.93E-01 4.51E+00 5.21E+00 1.65E+00 5.31E+00 6.60E+00 NA NA NA RW-1 RW-1 003 107.5

-30 10/31/2006 12:27 1.07E+05 8.06E+03 1.10E+03

-3.70E-01 9.51E-01 1.09E+00 7.18E-01 4.23E+00 4.71E+00 7.34E-01 3.04E+00 3.61E+00 NA NA NA RW-1 RW-1 004 107.5

-30 10/31/2006 15:55 2.63E+04 2.04E+03 5.51E+02

-1.06E+00 1.15E+00 1.39E+00

-2.26E-01 3.86E+00 3.99E+00

-6.22E-03 2.86E+00 3.21E+00 NA NA NA RW-1 RW-1 006 107.5

-30 11/1/2006 12:00 1.84E+04 1.45E+03 4.66E+02 3.64E-01 1.03E+00 1.08E+00

-3.39E+00 4.14E+00 3.90E+00

-5.25E-01 4.01E+00 4.19E+00 NA NA NA RW-1 RW-1 007 107.5

-30 11/2/2006 12:00 2.40E+04 2.13E+03 1.00E+03 1.50E-01 6.00E-01 6.70E-01 1.12E+00 2.37E+00 2.60E+00

-8.50E-01 2.37E+00 2.90E+00 NA NA NA RW-1 RW-1 008 107.5

-30 11/3/2006 9:00 3.06E+04 2.34E+03 1.00E+03 4.80E-01 7.20E-01 7.80E-01

-1.05E+00 2.19E+00 2.60E+00 8.20E-01 2.40E+00 2.70E+00 NA NA NA RW-1 MH-5 VCFD6 001 NA NA 6/29/2007 12:15 1.41E+03 2.33E+02 1.87E+02

-3.26E-01 6.21E-01 9.20E-01

-9.57E-01 3.40E+00 3.60E+00 6.39E-02 3.13E+00 3.49E+00 NA NA NA MH-5 VCFD6 MH-5 VCFD6 002 NA NA 8/10/2007 15:15 1.17E+03 5.21E+02 4.56E+02 3.17E-02 7.84E-01 9.38E-01

-5.40E-01 3.17E+00 2.87E+00

-8.50E-01 2.84E+00 2.93E+00 NA NA NA MH-5 VCFD6 MH-5 VCFD6 003 NA NA 10/26/2007 13:30 1.62E+03 2.30E+02 1.84E+02 1.60E-01 6.06E-01 7.10E-01 2.15E-01 2.64E+00 2.95E+00

-6.20E-01 2.90E+00 3.06E+00 NA NA NA MH-5 VCFD6 MH-5 VCFD6 004 NA NA 1/16/2008 12:30 9.28E+02 2.45E+02 1.77E+02 4.62E-01 8.33E-01 9.37E-01 5.23E-01 2.78E+00 3.09E+00 5.97E-01 2.55E+00 2.90E+00 NA NA NA MH-5 VCFD6 MH-5 VCFD6 005 NA NA 6/3/2009 14:45 1.20E+03 1.95E+02 1.62E+02

-5.27E-01 6.72E-01 8.48E-01 3.34E+00 9.21E+00 6.14E+00 7.60E-01 4.83E+00 5.73E+00 NA NA NA MH-5 VCFD6 MH-5 VCFD6 006 NA NA 8/24/2009 10:15 1.50E+03 2.46E+02 2.18E+02 5.16E-01 5.64E-01 5.97E-01 8.69E-02 5.58E+00 6.23E+00 2.70E+00 6.51E+00 7.43E+00 NA NA NA MH-5 VCFD6 MH-5 VCFD6 007 NA NA 11/16/2009 11:10 6.28E+02 1.39E+02 1.07E+02 3.95E-01 6.57E-01 7.36E-01

-5.36E-01 1.07E+01 1.17E+01 2.75E+00 6.29E+00 7.70E+00 NA NA NA MH-5 VCFD6 MH-5 VCFD6 008 NA NA 2/18/2010 13:46 2.08E+02 1.59E+02 1.71E+02 6.25E-02 3.27E-01 4.08E-01

-1.18E+00 4.41E+00 4.80E+00

-1.81E+00 4.11E+00 4.15E+00 NA NA NA MH-5 VCFD6 MH-5 VCFD6 009 NA NA 5/17/2010 10:15 4.33E+02 1.73E+02 1.79E+02 3.66E-01 5.84E-01 6.48E-01 2.13E+00 6.00E+00 7.18E+00 4.52E-01 6.63E+00 7.65E+00 NA NA NA MH-5 VCFD6 MH-5 VCFD6 010 NA NA 8/5/2010 14:45 7.32E+02 1.89E+02 1.77E+02 5.37E-01 5.67E-01 5.84E-01 7.26E-01 7.72E+00 8.69E+00

-2.26E+00 6.93E+00 7.07E+00 NA NA NA MH-5 VCFD6 MH-5 VCFD6 011 NA NA 8/30/2010 13:30 9.96E+03 5.48E+02 1.26E+02 1.25E-01 3.21E-01 3.81E-01 1.50E+00 5.58E+00 6.48E+00 8.08E-01 6.51E+00 7.50E+00 NA NA NA MH-5 VCFD6 MH-5 VCFD6 012 NA NA 9/10/2010 15:30 8.80E+02 1.89E+02 1.25E+02 3.60E-01 6.35E-01 7.11E-01 7.21E-01 6.45E+00 7.44E+00 1.23E+00 5.71E+00 6.85E+00 NA NA NA MH-5 VCFD6 MH-5 VCFD6 013 NA NA 11/24/2010 11:10 4.60E+02 1.86E+02 1.47E+02 1.36E-01 7.57E-01 8.85E-01 1.75E+00 3.45E+00 4.02E+00 5.48E-01 3.79E+00 4.28E+00 NA NA NA MH-5 VCFD6 MH-5 VCFD6 014 NA NA 2/28/2011 9:47 5.17E+03 6.58E+02 3.66E+02 1.90E+00 1.99E+00 1.94E+00 3.45E-01 5.64E+00 6.19E+00

-1.28E+00 6.18E+00 6.45E+00 NA NA NA MH-5 VCFD6 MH-5 VCFD6 015 NA NA 4/22/2011 13:37 1.25E+04 1.10E+03 4.46E+02 8.17E-01 1.85E+00 2.08E+00

-3.21E+00 8.36E+00 8.43E+00

-1.60E+00 9.06E+00 9.51E+00 NA NA NA MH-5 VCFD6 MH-5 VCFD6 018 NA NA 7/7/2011 14:29 2.97E+03 7.02E+02 2.83E+02

-3.05E-01 8.04E-01 1.11E+00 9.24E-01 7.95E+00 8.84E+00 5.11E-01 8.49E+00 9.13E+00 NA NA NA MH-5 VCFD6 MH-5 VCFD6 019 NA NA 7/12/2011 12:46 9.86E+03 1.23E+03 2.81E+02 9.15E-01 1.05E+00 1.06E+00

-1.17E+01 1.33E+01 1.52E+01

-1.19E+00 9.99E+00 1.06E+01 NA NA NA MH-5 VCFD6 MH-5 VCFD6 020 NA NA 7/20/2011 10:48 2.89E+03 7.32E+02 3.35E+02

-4.57E-01 1.01E+00 1.47E+00 1.79E+00 6.30E+00 7.26E+00

-2.61E+00 8.34E+00 8.34E+00 NA NA NA MH-5 VCFD6 MH-5 VCFD6 021 NA NA 7/26/2011 12:50 1.86E+03 6.03E+02 3.33E+02

-7.10E-01 9.45E-01 1.45E+00 2.81E+00 7.47E+00 8.99E+00

-8.33E-01 9.66E+00 1.03E+01 NA NA NA MH-5 VCFD6 MH-5 VCFD6 022 NA NA 8/3/2011 14:12 3.90E+03 8.31E+02 3.31E+02

-4.45E-01 1.07E+00 1.50E+00

-6.18E-01 1.01E+01 1.10E+01

-6.71E+00 1.43E+01 1.29E+01 NA NA NA MH-5 VCFD6 MH-5 VCFD6 023 NA NA 8/11/2011 12:39 2.74E+04 1.65E+03 2.02E+02 6.43E-01 1.19E+00 1.32E+00

-2.20E+00 7.47E+00 7.63E+00 1.85E+00 5.85E+00 7.32E+00 NA NA NA MH-5 VCFD6 MH-5 VCFD6 024 NA NA 8/18/2011 9:50 2.09E+04 1.87E+03 2.64E+02 9.64E-01 1.55E+00 1.70E+00 1.90E+00 7.98E+00 9.05E+00

-3.10E+00 9.60E+00 9.54E+00 NA NA NA MH-5 VCFD6 MH-5 VCFD6 025 NA NA 8/24/2011 11:01 1.40E+04 1.51E+03 2.58E+02 5.99E-01 1.30E+00 1.46E+00

-2.36E+00 7.86E+00 8.21E+00 3.46E+00 7.98E+00 9.92E+00 NA NA NA MH-5 VCFD6 MH-5 VCFD6 026 NA NA 8/30/2011 13:55 3.37E+04 1.83E+03 2.03E+02 9.19E-01 1.31E+00 1.40E+00 1.76E+00 7.23E+00 8.47E+00

-1.69E+00 7.86E+00 7.79E+00 NA NA NA MH-5 VCFD6 MH-5 VCFD6 027 NA NA 10/17/2011 10:07 1.48E+04 1.09E+03 3.86E+02

-5.57E-01 1.17E+00 1.65E+00 1.51E+00 7.68E+00 9.98E+00

-2.77E+00 7.92E+00 9.24E+00 NA NA NA MH-5 VCFD6 MH-5 VCFD6 028 NA NA 10/31/2011 14:20 2.40E+04 1.37E+03 3.89E+02 1.06E+00 1.72E+00 1.87E+00 5.56E+00 1.15E+01 1.61E+01 3.37E-01 1.09E+01 1.53E+01 NA NA NA MH-5 VCFD6 LAF-002 001 NA

-22.3 6/6/2006 12:47 5.20E+01 1.71E+02 1.83E+02 NA NA NA NA NA NA NA NA NA NA NA NA LAF-002 LAF-002 001 NA

-22.3 6/6/2006 12:47 3.98E+01 3.60E+02 6.98E+02 1.38E+00 1.85E+00 1.93E+00

-3.88E+00 1.53E+00 1.59E+00

-2.24E+00 1.25E+01 1.34E+01

-2.84E-01 2.13E+01 2.34E+01 LAF-002 LAF-002 003 NA

-22.3 9/19/2006 13:14

-4.71E+01 1.50E+02 1.70E+02

-5.08E-01 8.90E-01 1.07E+00 6.45E-02 9.05E+00 1.01E+00

-2.76E+00 6.35E+00 4.99E+00 NA NA NA LAF-002 LAF-002 004 NA

-22.3 12/4/2006 13:38

-1.20E+01 1.62E+02 1.60E+02

-1.20E-01 7.80E-01 8.50E-01 NA NA NA 9.00E-01 5.40E+00 6.30E+00

-2.50E+00 7.20E+00 8.10E+00 LAF-002 LAF-002 005 NA

-22.3 3/7/2007 14:45

-8.30E+01 1.56E+02 1.60E+02 8.20E-01 1.50E+00 1.60E+00 3.10E+00 4.80E+00 5.10E+00

-1.20E+00 5.40E+00 7.30E+00 NA NA NA LAF-002 LAF-002 006 NA

-22.3 6/7/2007 13:18

-6.85E+00 1.33E+02 1.54E+02 3.19E-01 6.02E-01 6.79E-01 7.80E-01 2.63E+00 3.04E+00 6.55E-01 2.60E+00 3.04E+00 NA NA NA LAF-002 LAF-002 007 NA

-22.3 10/9/2007 9:35 7.46E+01 1.37E+02 1.55E+02 4.43E-01 4.98E-01 5.18E-01

-5.45E-01 2.10E+00 1.69E+00

-1.44E+00 1.78E+00 1.39E+00 NA NA NA LAF-002 LAF-002 008 NA

-22.3 12/4/2007 10:50 9.00E+01 1.46E+02 1.62E+02 4.89E-01 6.20E-01 6.62E-01

-6.91E-01 4.59E+00 4.37E+00

-2.35E+00 3.72E+00 3.39E+00 NA NA NA LAF-002 LAF-002 009 NA

-22.3 4/10/2008 0:00 4.65E+01 8.46E+01 1.44E+02 4.73E-01 3.02E-01 4.56E-01 1.91E+00 2.14E+00 3.95E+00 1.61E+00 2.46E+00 4.56E+00 NA NA NA LAF-002 LAF-002 010 NA

-22.3 10/17/2008 10:32 8.19E+01 1.55E+02 1.74E+02 4.05E-01 7.90E-01 9.01E-01 2.36E-01 2.76E+00 3.16E+00

-3.08E-02 3.09E+00 3.46E+00

-4.61E+00 2.01E+01 2.35E+01 LAF-002 LAF-002 011 NA

-22.3 4/21/2009 14:24 1.80E+02 1.77E+02 1.89E+02 1.77E-01 5.70E-01 6.58E-01

-1.74E+00 5.94E+00 3.96E+00 3.37E-01 3.99E+00 4.50E+00 2.34E+00 1.92E+01 2.19E+01 LAF-002 LAF-002 012 NA

-22.3 11/19/2009 12:35

-7.51E+01 1.40E+02 1.65E+02

-1.84E-02 5.43E-01 7.29E-01 4.01E-01 8.91E+00 1.02E+01 6.99E+00 9.51E+00 1.27E+01 2.20E+00 1.47E+01 1.68E+01 LAF-002 LAF-002 013 NA

-22.3 5/11/2010 13:44

-4.21E+01 1.32E+02 1.63E+02 6.55E-01 7.37E-01 7.78E-01

-1.49E+00 6.90E+00 7.60E+00 1.64E+00 6.08E+00 7.34E+00

-6.88E+00 2.21E+01 2.54E+01 LAF-002 LAF-002 014 NA

-22.3 11/22/2010 14:41 1.02E+02 1.13E+02 1.21E+02 1.96E-01 4.62E-01 5.40E-01

-6.13E-01 6.13E+00 6.83E+00

-1.60E+00 5.88E+00 6.15E+00 3.65E+00 1.77E+01 2.05E+01 LAF-002 LAF-002 015 NA

-22.3 5/2/2011 12:50 6.69E+01 3.04E+02 3.43E+02 1.16E+00 1.55E+00 1.66E+00

-5.80E-01 7.86E+00 8.57E+00

-6.46E-01 7.24E+00 7.65E+00

-3.48E-01 1.60E+01 1.83E+01 LAF-002 LAF-002 016 NA

-22.3 12/13/2011 10:31 6.96E+01 4.14E+02 4.79E+02 1.65E+00 1.67E+00 1.75E+00

-3.83E+00 9.48E+00 1.11E+01 5.21E+00 8.73E+00 1.29E+01 6.36E+00 1.11E+01 1.22E+01 LAF-002 B-16 001 NA NA 6/29/2007 12:35 7.93E+02 2.07E+02 1.89E+02

-3.83E-01 6.75E-01 9.80E-01 0.00E+00 7.04E+00 4.44E+00

-9.13E-01 3.30E+00 3.40E+00 NA NA NA B-16

TABLE 5 HISTORIC GROUNDWATER ANALYTICAL RESULTS INDIAN POINT ENERGY CENTER BUCHANAN, NY J:\\17,000-18,999\\17869\\17869-92.MG\\Q4-2011\\FINAL\\Tables\\;

2011 FINAL Table 5 - Historic Groundwater Analtycial Results.xlsx; 2011 Table 5 Page 34 of 34 See Page 34 for Notes Date Time Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Result Std. Dev.7 MDC Well ID1 TRITIUM ( pCi/L)

Sr-90 (pCi/L)

Cs-137 (pCi/L)

Co-60 (pCi/L)

Ni-63 (pCi/L)

Well ID1, 4 SAMPLE ID SAMPLE ZONE CENTER, depth ft below top of casing2 SAMPLE ZONE CENTER, elevation ft msl2 SAMPLE COLLECTION ANALYSIS RESULTS3 B-16 002 NA NA 8/14/2007 11:30 1.10E+03 2.25E+02 1.90E+02 1.29E-02 5.93E-01 7.38E-01 0.00E+00 6.71E+00 3.93E+00 9.94E-01 3.54E+00 4.16E+00 NA NA NA B-16 B-16 003 NA NA 10/22/2007 14:49 1.10E+03 4.68E+02 4.01E+02

-1.56E-01 3.72E-01 5.51E-01 1.68E+01 5.82E+00 3.82E+00 1.33E+00 3.23E+00 3.53E+00 NA NA NA B-16 B-16 004 NA NA 1/22/2008 13:08 2.27E+02 1.61E+02 1.71E+02 1.29E-01 5.00E-01 6.12E-01 3.13E-01 2.54E+00 2.83E+00

-9.46E-02 2.72E+00 3.01E+00 NA NA NA B-16 B-16 005 NA NA 4/18/2008 18:25 1.17E+03 1.57E+02 2.01E+02

-1.14E-01 3.81E-01 7.82E-01 2.00E+01 3.70E+00 3.07E+00

-2.48E-01 1.76E+00 2.97E+00 NA NA NA B-16 B-16 006 NA NA 6/3/2009 13:30 8.81E+02 1.83E+02 1.62E+02 7.01E-02 7.89E-01 9.15E-01 9.21E+00 1.11E+01 7.41E+00

-3.25E+00 6.23E+00 5.86E+00 NA NA NA B-16 B-16 007 NA NA 2/23/2010 14:10 1.49E+03 2.13E+02 1.69E+02 4.61E-02 3.00E-01 3.80E-01 4.53E+00 5.45E+00 6.44E+00

-6.69E-01 7.14E+00 5.88E+00 NA NA NA B-16 B-16 008 NA NA 4/23/2010 16:44 8.15E+02 1.91E+02 1.85E+02 2.22E-01 5.20E-01 6.03E-01 9.79E+00 7.91E+00 6.38E+00 5.59E-01 6.24E+00 7.21E+00 NA NA NA B-16 B-16 009 NA NA 8/17/2010 15:40 1.40E+04 6.48E+02 1.27E+02 1.25E-01 6.43E-01 7.91E-01 2.27E+01 1.06E+01 5.87E+00 2.96E+00 6.00E+00 7.45E+00 NA NA NA B-16 B-16 010 NA NA 11/17/2010 11:10 2.37E+03 2.72E+02 3.86E+02 6.87E-01 7.68E-01 1.72E+00 1.89E+01 6.46E+00 7.93E+00 8.39E-01 4.32E+00 9.74E+00 NA NA NA B-16 B-16 011 NA NA 2/14/2011 15:44 3.82E+03 5.88E+02 3.65E+02 5.41E-02 1.70E+00 2.14E+00 2.15E+01 1.22E+01 6.75E+00

-1.81E+00 7.00E+00 7.25E+00 NA NA NA B-16 B-16 012 NA NA 4/25/2011 10:50 8.10E+03 9.22E+02 4.53E+02

-6.21E-03 1.74E+00 2.09E+00 2.05E+01 1.33E+01 1.03E+01 3.18E+00 9.06E+00 1.11E+01 NA NA NA B-16 B-16 013 NA NA 8/17/2011 13:17 7.36E+02 3.03E+02 1.96E+02

-6.00E-02 9.87E-01 1.25E+00 1.51E+01 1.49E+01 7.29E+00

-4.01E-01 7.02E+00 7.34E+00 NA NA NA B-16 B-66 001 NA NA 7/5/2007 9:00 4.03E+02 1.67E+02 1.69E+02 1.01E-01 4.97E-01 5.67E-01 1.29E+00 3.46E+00 4.04E+00 1.09E+00 3.51E+00 4.15E+00 NA NA NA B-66 B-66 002 NA NA 8/14/2007 8:30 5.46E+01 1.68E+02 1.92E+02

-3.06E-01 6.20E-01 8.32E-01 5.63E-01 2.97E+00 3.42E+00

-2.88E+00 3.31E+00 2.35E+00 NA NA NA B-66 B-66 003 NA NA 10/22/2007 11:30 1.07E+02 1.70E+02 1.90E+02

-7.54E-02 4.34E-01 5.83E-01 2.39E+00 2.33E+00 3.04E+00 1.04E+00 2.46E+00 3.05E+00 NA NA NA B-66 B-66 004 NA NA 1/16/2008 16:50 4.72E+02 2.04E+02 1.79E+02 1.05E-01 7.05E-01 8.83E-01 3.96E+00 4.41E+00 3.32E+00 1.29E+00 3.15E+00 3.66E+00 NA NA NA B-66 B-66 005 NA NA 4/25/2008 14:15 5.23E+01 8.45E+01 1.43E+02

-1.20E-01 2.59E-01 5.25E-01

-2.89E-01 1.96E+00 3.24E+00

-7.50E-01 3.43E+00 4.21E+00 NA NA NA B-66 B-66 006 NA NA 6/3/2009 9:40 1.08E+02 1.46E+02 1.63E+02 1.71E-01 7.08E-01 8.14E-01 1.50E-01 1.19E+01 7.94E+00 1.26E+00 5.79E+00 6.80E+00 NA NA NA B-66 B-66 007 NA NA 2/19/2010 9:56 3.78E+02 1.65E+02 1.68E+02 1.14E-02 3.57E-01 4.59E-01 1.43E+00 4.13E+00 4.84E+00 2.21E-01 3.96E+00 4.54E+00 NA NA NA B-66 B-66 008 NA NA 5/18/2010 9:40 4.48E+01 1.62E+02 1.84E+02

-1.02E-01 4.47E-01 5.71E-01 5.39E-01 5.58E+00 6.34E+00 2.39E-01 5.50E+00 6.27E+00 NA NA NA B-66 B-66 009 NA NA 8/5/2010 13:43 1.49E+02 1.62E+02 1.79E+02 1.12E-01 8.02E-01 9.78E-01 2.32E+00 6.57E+00 8.03E+00

-9.21E-02 8.23E+00 9.37E+00 NA NA NA B-66 B-66 010 NA NA 11/8/2010 11:45 1.05E+02 1.33E+02 1.43E+02 1.43E-01 6.60E-01 7.68E-01 0.00E+00 5.04E+00 6.20E+00

-3.20E-01 4.70E+00 5.29E+00 NA NA NA B-66 B-66 011 NA NA 2/28/2011 11:27 8.39E+02 3.90E+02 3.65E+02 6.28E-01 1.78E+00 2.05E+00 4.45E+00 5.82E+00 7.02E+00

-1.35E+00 6.50E+00 6.88E+00 NA NA NA B-66 B-66 012 NA NA 4/25/2011 9:48 2.68E+03 6.18E+02 4.53E+02

-6.69E-01 1.58E+00 2.09E+00

-1.31E-01 8.56E+00 9.08E+00 4.73E+00 1.06E+01 1.35E+01 NA NA NA B-66 B-66 013 NA NA 7/8/2011 11:05 5.39E+02 3.54E+02 2.82E+02 1.32E+00 1.56E+00 1.63E+00 6.09E+00 1.58E+01 8.04E+00

-2.64E+00 8.97E+00 8.84E+00 NA NA NA B-66 B-66 014 NA NA 7/29/2011 10:52 6.45E+02 4.14E+02 3.38E+02

-2.59E-01 1.39E+00 1.79E+00 1.60E+00 7.74E+00 8.72E+00 4.72E+00 5.07E+00 7.82E+00 NA NA NA B-66 B-66 015 NA NA 10/20/2011 12:01 1.70E+02 3.48E+02 3.87E+02

-1.65E-01 1.57E+00 1.98E+00

-3.07E+00 7.65E+00 8.33E+00 1.53E+00 8.34E+00 1.10E+01 NA NA NA B-66 Notes:

1. For nested multi-level monitoring wells, suffix of well ID indicates depth (rounded to nearest foot) from reference point on casing to bottom of well screen. For Waterloo multi-level systems, suffix indicates depth (rounded to nearest foot) from reference point on casing to top of sampling port. Well IDs without a suffix are open bedrock wellbores.
2. Sampling depths within sampling intervals (location of pump intake) have been established at location of most transmissive zone to the extent possible.
3. NA indicates that the constituent was not analyzed.
4. Current well identifications are shown for each location. Minor name changes have been made based on altered transducer installations.
5. At monitoring well U3-T1, sample IDs 019-B, 019-D, and 019-S were collected for laboratory and field QA/QC (B=Blind, D=Duplicate, S-Spike). Only the duplicate sample results were included in the calculations for rolling averages.
6. These locations are storm drains or foundation drains, not monitoring wells.
7. Column designated as Std. Dev. provides the three times 1 sigma uncertainty values.
  • The Q1 2011 MW-40-100, MW-40-127 and MW-51-189 Cs-137 results were verified by re-analysis. However, based on the available chemistry and Site hydrogeologic data, these values do not appear to be representative of the groundwater conditions at these sampling intervals.
    • The Q2 2011 MW-40-46 preliminary Sr-90 result was 2.83 pCi/L and exceeded the IL. However, after re-analysis, the sample was below the detection limit which suggests the preliminary result was likely a false positive. A shift in the MDC for the preliminary result could have possibly resulted from contaminated laboratory equipment, modified count time, or changes in sample preparation.
      • The Post-Q3 2011 MW-58-65 preliminary Sr-90 result was 3.64 pCi/L and exceeded the IL. However, after re-analysis, the sample was below the detection limit which suggests the preliminary result was likely a false positive. A shift in the MDC for the preliminary result could have possibly resulted from contaminated laboratory equipment, modified count time, or changes in sample preparation.

FINAL QUARTERLY LONG-TERM GROUNDWATER MONITORING REPORT Q1 THROUGH Q4 2011 (REPORT NO. 13)

FIGURES Figure 1 Site Location Plan Figure 2 Site Plan Figure 3 Lower Hudson Valley Geologic Map Figure 4 4th Quarter 2011 Current and Potential Future SSC Source Locations Figure 5A-Q1 1st Quarter 2011 Longterm Transducer Monitoring Evaluation Map Figure 5A-Q2 2nd Quarter 2011 Longterm Transducer Monitoring Evaluation Map Figure 5A-Q3 3rd Quarter 2011 Longterm Transducer Monitoring Evaluation Map Figure 5A-Q4 4th Quarter 2011 Longterm Transducer Monitoring Evaluation Map Figure 6-Q1 1st Quarter 2011 Rolling Average Tritium Activity Map Figure 6-Q2 2nd Quarter 2011 Rolling Average Tritium Activity Map Figure 6-Q3 3rd Quarter 2011 Rolling Average Tritium Activity Map Figure 6-Q4 4th Quarter 2011 Rolling Average Tritium Activity Map Figure 6A Temporal Trends in Unit 2 Rolling Average Tritium Activity Maps Figure 6B Unit 2 Leak Collection Device Evaluation 4th Quarter 2011 Figure 7-Q1 1st Quarter 2011 Rolling Average Strontium-90 Activity Map Figure 7-Q2 2nd Quarter 2011 Rolling Average Strontium-90 Activity Map Figure 7-Q3 3rd Quarter 2011 Rolling Average Strontium-90 Activity Map Figure 7-Q4 4th Quarter 2011 Rolling Average Strontium-90 Activity Map Figure 7A Sr-90 Baseline Analysis-Unit 1 Defueling Evaluation 4thQuarter 2011 Figure 8-Q1 1st Quarter 2011 Rolling Average Cesium, Cobalt, and Nickel Activity Map Figure 8-Q2 2nd Quarter 2011 Rolling Average Cesium, Cobalt, and Nickel Activity Map Figure 8-Q3 3rd Quarter 2011 Rolling Average Cesium, Cobalt, and Nickel Activity Map Figure 8-Q4 4th Quarter 2011 Rolling Average Cesium, Cobalt, and Nickel Activity Map

Site Location Dwg. Date:

Figure No.:

Job No.:

Proj. Mgr.: MJB Designed By: MJB Reviewed By: MJB Operator: GAS/EMD 09-13-2012 1

INDIAN POINT ENERGY CENTER BUCHANAN, NEW YORK GZA GeoEnvironmental, Inc.

One Edgewater Drive Norwood, MA 02062 Phone: (781) 278-3700 Fax: (781) 278-5701 SITE LOCATION PLAN 0

2,000 4,000 6,000 1,000 Feet 4

© 2012 - GZA GeoEnvironmental, Inc. \\\\gzanor\\Jobs\\17,000-18,999\\17869\\17869-91.MG\\Figures\\GIS\\MXD Documents\\2011-comb\\12-08-30 F01 Site Location Plan 17869-92_final.mxd, 9/13/2012, 12:52:26 PM, jennifer.pisani 01.0017869.92

Tr ans.

Tr ansform er area and s witch gear Tank Tr ansform er yard Tan k 30 30 70 80 90 80 70 90 80 Tan k Tan k Tan k Condensate Tank Tr ansform ers on rais ed Concrete Pad Tr ans.

Tr ansform ers Concrete slab Tank Tr ansform ers on rais ed Concrete Pad Tan k Storage Tank Tr ansform er Subs tation "H" Tr ailer Tr ans Tan k St orag e Tan k Tank Pit Tr ans Tr ans Tr ans St orag e Ta nks Tr ansform ers Yard (Gravel)

DISCHARGE OUTFALL CANAL Turbine Generator Building 2 Turbine Generator Building 1 Turbine Generator Building 3 Transformer Yard Primary Auxilliary Building UNIT 2 UNIT 1 UNIT 3 Hudson River Discharge Canal Unit 1 Screenwell House Condensate Polisher Building Intake Structure Heater Bay Aux.

Boiler Building Administration Building Discharge Canal Transformer Yard Primary Auxilliary Building Superheater / Admin. Building Nuclear Service Building Fuel Storage Building Chem. Service Fuel Pool Fuel Storage Building Outfall MOB Curtain Drain Stack Sphere Foundation Drain Sump Tank Pit FPT Curtain Drain Annulus Fuel Pool Fuel Pool Containment Spray Sump FPT Chem. Sys.

Foundation Drain SCD NCD Utility Tunnel Utility Tunnel Pressure Water Storage Tank Reactor Water Storage Tank Passive Water Storage Tank Reactor Water Storage Tank LEGEND 50 0

50 100 150 25 Feet Plant North N

N Storm Drain Storm Drain - Connection Terminated Footing / Curtain Drain Figure No.:

Job No.:

Dwg. Date:

Proj. Mgr.: DMW Designed By: MJB/DMW Reviewed By: DMW Operator: GAS/EMD 01.0017869.92 2

INDIAN POINT ENERGY CENTER BUCHANAN, NEW YORK GZA GeoEnvironmental, Inc.

One Edgewater Drive Norwood, MA 02062 Phone: (781) 278-3700 Fax: (781) 278-5701 SITE PLAN 09-13-2012

© 2012 - GZA GeoEnvironmental, Inc. \\\\gzanor\\Jobs\\17,000-18,999\\17869\\17869-91.MG\\Figures\\GIS\\MXD Documents\\2011-comb\\12-08-30 F02 Site Plan 17869-92_DRAFT.mxd, 9/13/2012, 12:54:42 PM, jennifer.pisani

G

^

XY XY XYXY XYXY XY XYXY XYXY XYXY XY XYXY XY XY XYXY XY XY XYXYXY XY XYXY XY XY XY XY XYXY XY XYXY XYXY XYXY XYXY XY XYXY XYXY XY XYXY XYXY XYXY XY XYXY XYXY XY XYXY XYXY XYXY XY XYXY XYXY XYXY XYXY XYXY XY XYXY XYXY XY XYXY XYXY XYXY XY XYXY XY XY XYXY XY XY XY XY XYXY XYXY XY XYXY XY XY XYXY XYXY XY XYXY XYXY XYXY XY XYXY XYXY XY XYXY XYXY XYXY XY XYXY XYXY XY XYXY XYXY XY XYXY XYXY XYXY XY XYXY XY X

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

? @

?

?

? @

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

I-2 U3-3 U3-2 U3-1 RW-1 MW-67 MW-66 MW-37 MW-36 MW-35 MW-34 MW-33 U3-4S U3-4D MW-52 MW-51 MW-50 MW-49 MW-47 MW-46 MW-45 MW-44 MW-42 MW-41 MW-38 MW-32 MW-31 MW-40 MW-48 MW-43 MW-39 U3-T2 U3-T1 MW-65 MW-62 MW-60 MW-59 MW-57 MW-56 MW-55 MW-54 MW-53 MW-30 MW-64 MW-61 MW-63 U1-CSS MW-105 MW-101 MW-110 MW-111 MW-112 MW-108 MW-107 MW-58 MW-109 Storage storage Gravel Gravel Storage No Access Grass Earth Parking Asphalt Asphalt curb Asphalt parking Asphalt Concrete curbs Sign Concrete curb Concrete Concrete sidewalk Concrete curb Wooden curb Concrete sidewalk Concrete sidewalk Grass Concrete sidewalk Concrete sidewalk A/C UNIT Handicap ramp Concrete sidewalk Concrete sidewalk A/C unit on concrete Concrete sidewalk Conc. sidewalk Concrete sidewalk Stone curbs Asphalt drive Asphalt parking Asphalt parking Asphalt parking Asphalt parking Asphalt curb Asphalt sidewalk Shrubs Trans.

Asphalt Concrete sidewalk Concrete sidewalk Transformer area and switch gear Storage Containers A/C Units Grass Concrete curb Grass Shrubs Concrete sidewalk Conc. sidewalk Wooden walk Open gr ate Asphalt drive Asphalt Asphalt Asphalt Asphalt Asphalt Asphalt Asphalt Asphalt drive Asphalt Asphalt Drive Sidewalk Gravel Gravel Transformer yard Asphalt Drive this Area No Access Asphalt Conc rete Retaining Wa ll Stone retaining wall oncrete sidewalk Gravel parking Concrete sidewalk Gravel parking Gravel parking Gravel parking Stone curbs Stone curbs Asphalt parking Concrete curb Asphalt parking Concrete curb Concrete sidewalk curb pad Asphalt curb Asphalt curb Asphalt parking Grass Asphalt curb Asphalt curb Grass Asphalt curb Asphalt parking sidewalk Concrete Gravel parking Storage Grass Asphalt drive Storage units Gravel Parking lot Asphalt Concrete sidewalk Overhead walkway Concrete curb Asphalt parking Concrete walk Asphalt parking Asphalt Asphalt Asphalt Wood walk Asphalt Concrete walk Concrete pier Courtyard Asphalt Rip-rap Sidewalk Concrete 110 140 120 130 30 30 40 50 30 40 50 90 70 70 80 90 80 80 90 100 110 110 110 110 120 120 100 70 60 70 80 90 60 80 90 100 100 0

110 140 140 Transformer Gravel Covered Concrete Asphalt parking Transformers on raised Concrete Pad Trans.

Transformers Concrete slab Grass Transformers on raised Concrete Pad Concrete Bridge Concrete Bridge Transformer Substation "H" Trailer Trans Asphalt Trans Trans Trans Concrete sidewalk Asphalt Grass Vent pit Mach.

stand Transformers Yard (Gravel)

DISCHARGE OUTFALL CANAL Gravel Shrubs Shrubs Shrubs Overhead Crane Grass FUEL TRAN SFE R PO O L STO RA GE PO O L STO RA GE PO O L FA IL ED FU EL AUX. PO O L DIS ASS EM B LY PO O L CAS K L O AD PO O L CAS K W AS H &

DIS ASS EM B LY ISO L ATIO N PI T PU MP SU CTI ON WELL WATER STO RA GE PO O L ROOF DRAIN ELEVATION 65' 43.8' 43.8' 43.8' 21.75' 22.75' (EL.=0.0) 33' 13' 43.8' 33' 33' 33' 33' 33' 42.5' 42.5' MH-4 MH-4A MH-5 MH-6 MH-2 B6 B6A B5 B4 B4A B3 B3A B2A B2 B1 A2 A1 U3-MH-14 F5 A2A CB-B CB-E CB-F C-1 C-3 D2 B7 B8 CB-33 CB-34 CB-15 CB-14 CB-13 CB-32 CB-31 CB-30 A7 U1-CB-22 U3-CB (U1-CB-10)

CB-29 U3-CB (U1-CB-9)

U1-CB-21 U1-CB-20 CB-28 CB-24 CB-27 E16 E16 E16A CB-6 CB-5A (CB-6)

CB-5B CB-7 CB-5 MH16 CB-3B CB3A CB4 CB-2C CB3 CB-2B CB-2A CB-2 CB-1 MH18 MH8 MH17 MH7 MH23A CB-16 MH9 MH10 MH11 MH22 MH21 MH13 MH3 MH12 MH1 CB-18 MH15 CB-19 CB-23 MH14 C2 E7 E6 E8 E9 E10 E11 E5 E5A E4 E4 E4A E3B E3 E3A F3 F4 CB E2 E2A F6 F7 E2B E2C E1 A6 A5 A3A A3 A4 E14 E15 E15A (U1-CB-8)

AB E13 E12 D1 CB-17 F2 F1 CB-12 MH-23 MH-19 MH-20 ROOF DRAIN Turbine Generator Building 2 Turbine Generator Building 1 Turbine Generator Building 3 Transformer Yard PAB FUEL POOL UNIT 2 1,015' 640' WEST FUEL POOL UNIT 1 UNIT 3 U2-C1 HR-1 U3-C1 OUT-1 4

4 33' UTILITY TUNNEL 33' UTILITY TUNNEL CSS CSS TRENCH NORTHERN CLEAN ZONE UNIT 1/2 UNIT 2 NORTH UNIT 3 NORTH UNIT 3 SOUTH SOUTHERN CLEAN ZONE 50 40 30 20 10 5

E12 50 40 30 20 10 5

20 13 6

5 7

1 1

1 1

1 1

1 1

1 1

1 1

1 1

MH-5 VCFD U1-NCD U1-SFDS B-1 B-6 8

MW-68 H U D S O N R I V E R Plant North N

N 4th QUARTER 2011 CURRENT AND POTENTIAL FUTURE SSC SOURCE LOCATIONS

?

?

? LAF-03 LAF-02 LAF-01 H U D S O N R I V E R EASTERN IP1-CB FLOW PATH SOUTH WESTERN IP1-CB FLOW PATH PRIMAR Y

IP1 FL OW P ATH LEGACY IP1 STORM DRAIN FLOW PATH IP1-CSS TRENCH FLOW PATH 50 0

50 100 150 25 Feet Figure No.:

Job No.:

Dwg. Date:

Proj. Mgr.: MJB Designed By: MJB Reviewed By: MJB Operator: GAS 01.0017869.92 4

INDIAN POINT ENERGY CENTER BUCHANAN, NEW YORK GZA GeoEnvironmental, Inc.

One Edgewater Drive Norwood, MA 02062 Phone: (781) 278-3700 Fax: (781) 278-5701 4th QUARTER 2011 CURRENT AND POTENTIAL FUTURE SSC SOURCE LOCATIONS 1,557.1' LAFARGE WELLS Data Notes:

1. Illustration of contaminant plume is a schematic representation only. In reality, the geologic bedrock formation is over 99% solid, crystalline rock, with the contaminated water contained only in the remaining (less than 1%) interstitial space (i.e. fractures).
2. The H3 bounding isopleth encompasses upper bound values measured over both depth and time through the current quarter. As such, the "plume" is an overstatement of contaminant levels actually existing on-site at any one time. Compare bounding plume to current plume on Figure 6.
3. The Sr-90 bounding isopleth encompasses upper bound values measured over both depth and time through the current quarter.

As such, the "plume" is an overstatement of contaminant levels actually existing on-site at any one time. Compare bounding plume to current plume on Figure 7.

4. Two discrete isopleths have been drawn around MW-39 and 41 given measured Sr90 concentrations greater than 2 pCi/L. It is expected that similar concentrations exist at other locations along the legacy piping alignment in addition to the locations shown.
5. Historically elevated tritium levels in MW-42-49 observed during Q1 2009 were consistent with leakage visually identified on 03/07/2009 (and terminated immediately thereafter) from the waste distillate tank valves located within the Unit 1 fuel storage building. Elevated tritium levels not seen in MW-53; therefore, this transient leakage was likely to have been generally confined to, and contained by, the Unit 1 North Curtain Drain.
6. Historically elevated Tritium levels in MW-45-42 observed during Q2 2009 were consistent with an increased activity observed in Unit 3 Manhole A2. This release was initially detected in a storm drain sample collected 03/25/2009 under the 80-10 Effluents Program. This Tritium peak dissipated prior to samples taken during the subsequent quarter. Additionally, transient Tritium peaks have been recently detected in MH-A2 from Q3 2010 to Q3 2011. These increases are consistent with elevated Tritium levels in MW-41-40, MW-46 and B-1. Based on investigations initiated in, and ongoing since, 2009 and the more recent sampling of the Unit 3 Fuel Storage Building (FSB) roof drains, it has been concluded that these increases in storm drain and monitoring well Tritium activity are due to condensation of SFP evaporation on the FSB roof (Washout) when the exhaust fan is not operating, which then enters the roof drains and discharges directly into MH-A2 during rainfall events. As such, Entergy placed the FSB vent fan back in service on 7-21-2011 and the Tritium activity in MH-A2 returned to baseline conditions within 2 weeks.
7. Elevated levels of Tritium detected in MH-9 and MH-10a during routine 80-10 Effluents Program sampling on 1/15/2010 appears to have originated from a November 21, 2009 transient leak in temporary RWST / R.O. skid connection hoses, which flowed into MH-
9. It also appears that this release entered the well vault for MW-32, and may have penetrated the well casings and entered the subsurface around the monitoring installation.
8. Elevated levels of Tritium initially detected in U1-CSS, MW-39, MW-46, MW-54, MW-56 and MW-57 during the Q2-2011 sampling event appear to have originated from a Q2 2011 sample sink overflow and subsequent floor flooding in a Unit 1 Chemical Systems Building sample room on the 53 elevation.

LEGEND Potential Future Source Locations Activity Data Isopleth Probable Legacy Release SSCs Groundwater Elevation Contours General Notes:

Unit 2 and Unit 3 Potential H3 Sources

1. Base map was developed from an untitled electronic file provided by Badey & Watson Surveying and Engineering, P.C.,

Dated 2/3/06; CAD file name : "GZA.dwg".

2. Additional Long Term Monitoring Plan information is provided in the Hydrogeologic Site Investigation Report, GZA GeoEnvironmental, Inc. January 7, 2008.

0 200 400 100 Feet Notes:

1. Groundwater contours drawn from Q4 2008 groundwater data to show groundwater conditions used for recalibration of the Precipitation Mass Balance Model (see Q2 2009 LTM Report). These contours developed from limited data recorded on 11/11/2008. Actual elevations may vary from conditions shown and the actual distribution of piezometric heads is likely more complex than indicated.

09-13-2012

© 2012 - GZA GeoEnvironmental, Inc. \\\\gzanor\\Jobs\\17,000-18,999\\17869\\17869-91.MG\\Figures\\GIS\\MXD Documents\\2011-comb\\12-08-30 F04 Q4 2011 Current and Potential Future SSC Source Locations 17869-92_final.mxd, 9/13/2012, 1:40:20 PM, jennifer.pisani

^

Transient Spill from Temporary R.O. Skid Piping -

Entered MW-32 Vault and MH 11/21/2009 7

Transient Distillate Tank Valve Leak in Unit 1 Fuel Storage Building - 03/07/2009 5

Terminated Connection To Storm Drain Drain Exfiltration Inter-Structure Joint / Mud Mat Containment Spray Sump Pipe Trench 20 Ambient "Watertable" Contours for Q4 2008 (11/11/2008) 1 1

Contours Other Than 10' Interval 5

Streamtubes Bounding Activity H3 2

> 5,000 pCi/L 1,

3 Bounding Activity SR90

> 2 pCi/L 1,

MW-30 Boring / Monitoring Installation Designation Longterm Radionuclide Monitoring Installation

?

Standby Radionuclide Monitoring Installation

?

6 G

Unit 3 SFP Evap. Washout to MH-A2 - 3/25/09 (initial)

(Surface Spills and Washout)

Localized Transient Releases Unit 2 Fuel Pool (All identified leaks repaired as of December 2007)

Unit 1 West Fuel Pool (All U1-SFPs drained and inactive as of October 2008)

Sample Sink Overflow - Unit 1 Chemical Systems Building Q2 2011 8XXXX

G

^

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

?

? @

?

?

? @

?

?

?

?

?

?

?

?

?

?

?

?

?

?

I-2 U3-3 U3-2 U3-1 RW-1 MW-67 MW-66 MW-37 MW-36 MW-35 MW-34 MW-33 U3-4S U3-4D MW-52 MW-51 MW-50 MW-49 MW-47 MW-46 MW-45 MW-44 MW-42 MW-41 MW-38 MW-32 MW-31 MW-40 MW-48 MW-43 MW-39 U3-T2 U3-T1 MW-65 MW-62 MW-60 MW-59 MW-57 MW-56 MW-55 MW-54 MW-53 MW-30 MW-64 MW-61 MW-63 U1-CSS MW-105 MW-101 MW-110 MW-111 MW-112 MW-108 MW-107 MW-58 MW-109 Storage storage Gravel Gravel Storage No Access Grass Earth Parking Asphalt Asphalt curb Asphalt parking Asphalt Concrete curbs Sign Concrete curb Concrete Concrete sidewalk Concrete curb Wooden curb Concrete sidewalk Concrete sidewalk Grass Concrete sidewalk Concrete sidewalk A/C UNIT Handicap ramp Concrete sidewalk Concrete sidewalk A/C unit on concrete Concrete sidewalk Conc. sidewalk Concrete sidewalk Stone curbs Asphalt drive Asphalt parking Asphalt parking Asphalt parking Asphalt parking Asphalt curb Asphalt sidewalk Shrubs Trans.

Asphalt Concrete sidewalk Concrete sidewalk Transformer area and switch gear Storage Containers A/C Units Grass Concrete curb Grass Shrubs Concrete sidewalk Conc. sidewalk Wooden walk Open gr ate Asphalt drive Asphalt Asphalt Asphalt Asphalt Asphalt Asphalt Asphalt Asphalt drive Asphalt Asphalt Drive Sidewalk Gravel Gravel Transformer yard Asphalt Drive this Area No Access Asphalt Conc rete Retaining Wa ll Stone retaining wall Concrete sidewalk Gravel parking Concrete sidewalk Gravel parking Gravel parking Gravel parking curbs Stone curbs Stone curbs Asphalt parking Concrete curb Asphalt parking Concrete curb Concrete sidewalk curb pad Asphalt curb Asphalt curb Asphalt parking Grass Asphalt curb Asphalt curb Grass Asphalt curb Asphalt parking sidewalk Concrete Gravel parking Storage Grass Asphalt drive Storage units Gravel Parking lot Asphalt Concrete sidewalk Overhead walkway Concrete curb Asphalt parking Concrete walk Asphalt parking Asphalt Asphalt Asphalt Wood walk Asphalt Concrete walk Concrete pier Courtyard Asphalt Rip-rap Sidewalk Concrete 110 140 120 130 30 30 40 50 30 40 50 90 70 70 80 90 80 80 90 100 110 110 110 110 120 120 100 70 60 70 80 90 60 80 90 100 100 110 140 140 Transformer Gravel Covered Concrete Asphalt parking Transformers on raised Concrete Pad Trans.

Transformers Concrete slab Grass Transformers on raised Concrete Pad Concrete Bridge Concrete Bridge Transformer Substation "H" Trailer Trans Asphalt Trans Trans Trans Concrete sidewalk Asphalt Grass Vent pit Mach.

stand Transformers Yard (Gravel)

DISCHARGE OUTFALL CANAL Gravel Shrubs Shrubs Shrubs Overhead Crane Grass FUEL TRAN SFE R PO O L STO RA GE PO O L STO RA GE PO O L FA IL ED FU EL AUX. PO O L DIS ASS EM B LY PO O L CAS K L O AD PO O L CAS K W AS H &

DIS ASS EM B LY ISO L ATIO N PI T PU MP SU CTI ON WELL WATER STO RA GE PO O L ROOF DRAIN ELEVATION 65' 43.8' 43.8' 43.8' 21.75' 22.75' (EL.=0.0) 33' 13' 43.8' 33' 33' 33' 33' 33' 42.5' 42.5' MH-4 MH-4A MH-5 MH-6 MH-2 B6 B6A B5 B4 B4A B3 B3A B2A B2 B1 A2 A1 U3-MH-14 F5 A2A CB-B CB-E CB-F C-1 C-3 D2 B7 B8 CB-33 CB-34 CB-15 CB-14 CB-13 CB-32 CB-31 CB-30 A7 U1-CB-22 U3-CB (U1-CB-10)

CB-29 U3-CB (U1-CB-9)

U1-CB-21 U1-CB-20 CB-28 CB-24 CB-27 E16 E16 E16A CB-6 CB-5A (CB-6)

CB-5B CB-7 CB-5 MH16 CB-3B CB3A CB4 CB-2C CB3 CB-2B CB-2A CB-2 CB-1 MH18 MH8 MH17 MH7 MH23A CB-16 MH9 MH10 MH11 MH22 MH21 MH13 MH3 MH12 MH1 CB-18 MH15 CB-19 CB-23 MH14 C2 E7 E6 E8 E9 E10 E11 E5 E5A E4 E4 E4A E3B E3 E3A F3 F4 CB E2 E2A F6 F7 E2B E2C E1 A6 A5 A3A A3 A4 E14 E15 E15A (U1-CB-8)

AB E13 E12 D1 CB-17 F2 F1 CB-12 MH-23 MH-19 MH-20 ROOF DRAIN Turbine Generator Building 2 Turbine Generator Building 1 Turbine Generator Building 3 Transformer Yard PAB FUEL POOL UNIT 2 1,015' 640' WEST FUEL POOL UNIT 1 UNIT 3 U2-C1 HR-1 U3-C1 OUT-1 4

4 33' UTILITY TUNNEL 33' UTILITY TUNNEL CSS CSS TRENCH 5

6 7

MH-5 U1-NCD U1-SFDS B-1 B-6 8.05 9.92 0.41 0.67 5.25 5.96 7.08 8.63 9.20 0.81 0.50 4.51 4.33 3.58 9.25 5.34 4.20 4.25 4.31 3.01 1.31 0.64 5.08 5.17 8.85 5.69 6.86 6.41 8.12 8.22 8.82 9.49 9.02 3.71 7.24 7.36 8.32 7.20 5.55 6.83 5.64 1.04 1.02 1.01 0.88 0.70 1.41 0.03 0.55 0.86 0.51 0.32 7.93 9.23 1.06 1.40 1.07 0.89 0.95 0.61 0.25 0.18 1.61 0.74 0.75 1.39 1.02 0.63 0.94 3.07 0.08 0.74 48.81 15.05 43.19 36.63 34.96 45.52 47.50 10.20 25.01 13.30 47.99 53.73 10.07 10.12

-0.08 31.79 36.77 40.71 39.02 44.17 52.35 50.49 53.61 54.10 56.06 59.35 60.39 34.97 48.19 28.89 29.83 30.67 31.34 31.94 32.20 33.31 36.57 34.13 33.95 37.16 32.91 37.99 29.93 28.35 31.53 30.88 30.15 11.24 11.66 12.03 12.06 11.49 13.13 12.33 10.71 12.07 11.11

-0.86

-0.33

-0.48

-0.63 121.79 6.26 8.81 8.18 4.11 4.89 5.95 5.78 5.61 3.67 3.76 8.61 0.64 6.52 5.34 4.20 2.69 3.74 4.95 1.22 0.76 9.47 9.80 6.71 9.67 8.98 9.59 9.18 2.00 2.19 5.89 2.99 5.17 5.75 6.29 8.22 6.85 7.65 7.29 7.82 9.08 9.38 8.83 1.95 5.24 6.03 6.49 6.07 4.18 5.40 4.05 0.42 0.31 0.82 42.12 11.95 39.59 35.07 34.43 41.21 44.09 11.06 10.27 41.44 48.62

-2.38

-2.07

-0.86

-0.74

-0.50

-1.14 29.33 33.79 37.42 36.03 39.92 45.15 36.67 38.89 39.47 41.65 47.27 54.22 32.72 36.98 22.70 22.33 24.43 24.79 25.12 25.21 25.94 29.87 30.48 31.08 24.82 23.25 33.36 20.16 21.08 20.77 23.10 29.05 12.36 11.53

-0.62

-0.44

-0.08

-1.97

-2.46

-1.49

-3.14

-1.68

-2.08

-0.74

-0.64

-5.66

-3.28

-2.66

-1.33

-1.68

-2.15

-2.03

-1.13

-0.82

-2.86

-1.03

-1.87

-1.62

-0.67

-0.56

-2.42

-1.72

-3.41

-2.99

-1.43

-2.70 113.87

45 NA NA NA 7.9 0.59 0.74 8.88 13.01 50.74 29.48 41.25 56.35 31.43 37.47 12.29 11.23

-1.42

-3.47 H U D S O N R I V E R 3.28 10.59 10.35 8.05 9.92 0.41 0.67 5.25 5.96 7.08 8.63 9.20 0.81 0.50 4.51 4.33 3.58 9.25 5.34 4.20 4.25 4.31 3.01 1.31 0.64 5.08 5.17 8.85 5.69 6.86 6.41 8.12 8.22 9.05 8.82 9.49 9.02 3.71 7.24 7.36 8.32 7.20 5.55 6.83 5.64 1.04 1.02 1.01 0.88 0.70 1.41 0.03 0.55 0.86 0.51 0.32 7.93 9.23 1.06 1.40 1.07 0.89 0.95 0.61 0.25 0.18 1.61 0.74 0.75 1.39 1.02 0.63 0.94 3.07 0.08 0.74 15.05 43.19 36.63 34.96 45.52 47.50 10.20 25.01 13.30 47.99 53.73 10.07 10.12

-0.08 31.79 36.77 40.71 39.02 44.17 52.35 50.49 53.61 54.10 56.06 59.35 60.39 34.97 48.19 28.89 29.83 30.67 31.34 31.94 32.20 33.31 36.57 34.13 33.95 37.16 32.91 37.99 29.16 29.93 28.35 31.53 30.88 30.15 11.24 11.66 12.03 12.06 20.46 12.60 11.49 13.13 12.33 10.71 12.07 11.11

-0.86

-0.33

-0.48

-0.63 121.79 Plant North N

N 1st QUARTER 2011 LONGTERM TRANSDUCER MONITORING EVALUATION MAP

?

?

? LAF-03 LAF-02 LAF-01 H U D S O N R I V E R EASTERN IP1-CB FLOW PATH SOUTH WESTERN IP1-CB FLOW PATH PRIMAR Y

IP1 FL OW P ATH LEGACY IP1 STORM DRAIN FLOW PATH IP1-CSS TRENCH FLOW PATH 50 0

50 100 150 25 Feet 1,557.1' 0

200 400 100 Feet Figure No.:

Job No.:

Dwg. Date:

Proj. Mgr.: MJB Designed By: MJB Reviewed By: MJB Operator: GAS 01.0017869.92 5A INDIAN POINT ENERGY CENTER BUCHANAN, NEW YORK GZA GeoEnvironmental, Inc.

One Edgewater Drive Norwood, MA 02062 Phone: (781) 278-3700 Fax: (781) 278-5701 1st QUARTER 2011 LONGTERM TRANSDUCER MONITORING EVALUATION MAP LAFARGE WELLS Transducer Notes:

Potential Future Source Locations Unit 2 and Unit 3 Potential H3 Source

  • - For locations with multilevel depth monitoring, redundancy provided by monitoring more than one depth at same location.

- Redundant transducer data not available for Q1 2011.

Probable Legacy Release SSCs Containment Spray Sump Pipe Trench Terminated Connection To Storm Drain Drain Exfiltration Inter-Structure Joint / Mud Mat Unit 1 West Fuel Pool (All U1-SFPs drained and inactive as of October 2008)

Unit 2 Fuel Pool (All identified leaks repaired as of December 2007)

LEGEND Monitoring Installations MW-30 Boring / Monitoring Installation Designation Longterm Radionuclide Monitoring Installation

?

Standby Radionuclide Monitoring Installation

?

Transducer Monitored Interval Interval no longer monitored with Transducer 32.5 36.8 Quarterly groundwater elevation at time of low river tide on 1-22-2011 33.3 32.4 Single level monitoring location with duplicate Transducers for redundancy*

35.6 33.1 34.7 39.2 38.1 35.2 Multiple Screened Intervals w/ Depth Maximum quarterly groundwater elevation at time of low river tide measured between Q2 2007 and Q2 2009, inclusive.

Minimum quarterly groundwater elevation at time of low river tide measured between Q2 2007 and Q2 2009, inclusive.

Activity Data Isopleth Bounding Activity H3 Bounding Activity SR90

> 5,000 pCi/L

> 2 pCi/L 1,

1, 2

3 (Data from primary trans. shown) 5 Transient Distillate Tank Valve Leak in Unit 1 Fuel Storage Building - 3/07/2009 Unit 3 SFP Evap. Washout to MH-A2 - 3/25/09 6

G Transient Spill from Temporary R.O. Skid Piping -

Entered MW-32 Vault and MH 11/21/2009 7

^

Data Notes:

1. Illustration of contaminant plume is a schematic representation only. In reality, the geologic bedrock formation is over 99% solid, crystalline rock, with the contaminated water contained only in the remaining (less than 1%) interstitial space (i.e. fractures).
2. The H3 bounding isopleth encompasses upper bound values measured over both depth and time through the current quarter. As such, the "plume" is an overstatement of contaminant levels actually existing on-site at any time. Compare bounding plume to current plume on Figure 6.
3. The Sr-90 bounding isopleth encompasses upper bound values measured over both depth and time through the current quarter. As such, the "plume" is an overstatement of contaminant levels actually existing on-site at any time. Compare bounding plume to current plume on Figure 7.
4. Two discrete isopleths have been drawn around MW-39 and 41 given measured Sr90 concentrations greater than 2 pCi/L. It is expected that similar concentrations exist at other locations along the legacy piping alignment in addition to the locations shown.
5. Historically elevated Tritium levels in MW-42-49 observed during Q1 2009 were consistent with leakage visually identified on 03/07/2009 (and terminated immediately thereafter) from the waste distillate tank valves located within the Unit 1 fuel storage building. Data trends through Q1 2010 indicate that the observed Tritium peaks in MW-42-49 and downgrading wells associated with this release have dissipated through the groundwater flow system.
6. Historically elevated Tritium levels in MW-45-42 observed during Q2 2009 were consistent with an increased activity observed in Unit 3 Manhole A2. This release was initially detected in a storm drain sample collected 03/25/2009 under the 80-10 Effluents Program. This Tritium peak dissipated prior to samples taken during the subsequent quarter. Additionally, transient Tritium peaks have been recently detected in MH-A2 from Q3 2010 to Q1 2011. These increases are consistent with elevated Tritium levels in MW-41-40, MW-46 and B-1. Based on investigations initiated in, and ongoing since, 2009 and the more recent sampling of the Unit 3 Fuel Storage Building (FSB) roof drains, it has been concluded that these increases in storm drain and monitoring well Tritium activity are due to condensation of SFP evaporation on the FSB roof (Washout) when the exhaust fan is not operating, which then enters the roof drains and discharges directly into MH-A2 during rainfall events.
7. Elevated levels of Tritium detected in MH-9 and MH-10a during routine 80-10 Effluents Program sampling on 1/15/2010 appears to have originated from a November 21, 2009 transient leak in temporary RWST / R.O. skid connection hoses, which flowed into MH-9. It also appears that this release entered the well vault for MW-32, and may have penetrated the well casings and entered the subsurface around the monitoring installation.

General Notes

1. Base map was developed from an untitled electronic file provided by Badey and Watson Surveying and Engineering, P.C., Dated 2/3/06; CAD file name : "GZA.dwg".

09-17-2012

© 2012 - GZA GeoEnvironmental, Inc. \\\\gzanor\\Jobs\\17,000-18,999\\17869\\17869-91.MG\\Figures\\GIS\\MXD Documents\\2011-comb\\base Q1 F05A Longterm Transducer Monitoring Evaluation Map 17869-92.mxd, 9/17/2012, 12:53:35 PM, jennifer.pisani Low River Tide Elevation Q1-11 (Feet msl)

(Quarter)

(Feet msl)

(Quarter)

(Feet msl)

HR1

-3.28 Q1-09

-0.86 Q3-07 NA I2 48.62 Q3-07 53.73 Q1-08 50.74 MW-30-69 11.53 Q3-07 12.33 Q1-09 11.23 MW-30-84 12.36 Q4-08 13.13 Q1-09 12.29 MW-40-27 54.22 Q4-08 60.39 Q1-08 56.35 MW-40-162 36.67 Q3-07 50.49 Q1-08 45.00 MW-43-28 31.08 Q3-07 33.95 Q2-08 37.47 MW-43-62 30.48 Q3-08 34.13 Q1-09 31.43 MW-46 11.95 Q3-07 15.05 Q1-08 13.01 MW-51-40 45.15 Q2-09 52.35 Q2-08 41.25 MW-51-189 29.33 Q3-07 31.79 Q2-08 29.48 MW-53-82 9.59 Q3-07 12.60 Q2-08 10.59 MW-53-120 9.18 Q3-07 11.49 Q2-08 10.35 MW-55-24 7.82 Q3-07 9.02 Q4-08 8.88 MW-55-54 7.65 Q3-07 8.82 Q4-08 7.90 MW-65-48 36.98 Q2-09 48.19 Q1-09 NA MW-65-80 32.72 Q4-08 34.97 Q2-08 NA MW-66-21

-0.74 Q1-08 0.50 Q2-09 0.74 MW-66-36

-0.86 Q1-09 0.81 Q2-07 0.59 MW-67-39

-0.56 Q2-09 1.02 Q3-07

-1.42 MW-67-340

-2.42 Q1-09 0.63 Q3-07

-3.47 U3-C1 0.64 Q1-09 3.58 Q4-07 3.28 Notes:

1. Quarter 2, 2007 groundwater elevations were measured on 6/1/07 at 6:20 am.

11.23

2. Quarter 3, 2007 groundwater elevations were measured on 9/25/07 at 4:32 am.

between Q2-2007 and Q2-2009, inclusive.

3. Quarter 4, 2007 groundwater elevations were measured on 12/9/07 at 4:15 am.
4. Quarter 1, 2008 groundwater elevations were measured on 1/3/08 at 1:14 a.m.
5. Quarter 2, 2008 groundwater elevations were measured on 4/4/08 at 5:14 pm.
6. Quarter 3, 2008 groundwater elevations were measured on 7/10/08 at 11:35 am.
7. Quarter 4, 2008 groundwater elevations were measured on 11/11/08 at 2:54 am.
8. Quarter 1, 2009 groundwater elevations were measured on 1/9/09 at 2:42.
9. Quarter 2, 2009 groundwater elevations were measured on 5/22/09 at 2:41 pm.
10. Quarter 3, 2009 groundwater elevations were measured on 8/9/09 at 8:18 am.
11. Quarter 4, 2009 groundwater elevations were measured on 11/28/09 at 3:45 pm.
12. Quarter 1, 2010 groundwater elevations were measured on 1/30/10 at 6:00 am.
13. Quarter 2, 2010 groundwater elevations were measured on 4/09/10 at 12:06 pm.
14. Quarter 3, 2010 groundwater elevations were measured on 7/31/10 at 12:30 am.
15. Quarter 4, 2010 groundwater elevations were measured on 10/16/10 at 1:36 am.
16. Quarter 1, 2011 groundwater elevations were measured on 1/22/11 at 8:20 pm.

NA - data not available.

Highlighted box indicates that data falls >30% outside of range Maximum Low River Tide Elevation Q2-2007 through Q2-2009 Q2-2007 through Q2-2009 Well ID Minimum Low River Tide Elevation Localized Transient Releases (Surface Spills and Washout)

(initial)