ML113640120

From kanterella
Jump to navigation Jump to search
Initial Exam 2011-302 Final Simulator Scenarios
ML113640120
Person / Time
Site: Saint Lucie  NextEra Energy icon.png
Issue date: 12/14/2011
From:
NRC/RGN-II
To:
Florida Power & Light Co
References
50-335/11-302, 50-389/11-302
Download: ML113640120 (74)


Text

1 Facility:

St. Lucie Scenario No.:

1 Op Test No.:

HLC 20A Examiners:

Operators:

SRO:

RO:

BOP:

Initial Conditions:

100% power MOL. Reduce power to 45% to remove the 2A Main Feedwater pump from service due to a oil leak.

Turnover:

2A High Pressure safety injection pump is out of service to repair a motor oil leak. Taken out of service 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> ago. B train protected, OLRM: Yellow Critical Tasks:

Close 2B Diesel Generator output breaker Start 2B HPSI pump Event Malf.

Event Event No.

No.

Type*

Description 1

RlRO, Reduce power to 45% to remove the 2A Main Feedwater pump.

N/BOP 2

1 C/BOP 2A MFRV fails to respond to downpower.

3 2

CIRO Pressurizer level channel L T -111 OX fails as is.

4 3

CIRO Letdown isolation valves fails closed which results in letdown line rupture in Containment.

5 4

M/ALL Small Break LOCA, manual trip. Loss of oftsite power.

6 5

C/BOP 2B Diesel Generator output breaker does not close on LOOP.

7 6

CIRO 2B HPSI pump does not start when 2B Diesel Generator breaker closes after SIAS actuation.

(N)ormal, (R)eactivity, (I)nstrument, (C)omponent, (M)ajor RO NA NA Event 3 & 4 were not ran due to a manual Rx trip being inserted by the RO during the attempt to control the SG level with the 2A MFRV in manual.

2 SCENARIO EVENT DESCRIPTION SCENARIO 1 Unit will be turned over at 100% power MOL. Directions are to reduce power to approximately 45% to remove the 2A Main Feedwater pump from service due to motor oil leak.

As the downpower progresses the 2A Main feedwater reg. valve (MFRV) is not responding to the reduced steam flow. To control the 2A Steam Generator level the BOP must take manual control of the 2A MFRV.

Pressurizer level channel LT-1110X is failed as is. Because the level setpoint is failed as is and the reference setpoint is lowering, this will result is increasing letdown flow when letdown should be decreasing for the power reduction. The crew should swap to Pressurizer level channel U-1110Y to mitigate the failure.

Letdown isolation valve V2515 fails closed. The RO should stop all running Charging pumps. Shortly after the letdown valve fails closed, RCS leakage will increase indicating a ruptured non-isolable letdown line. This will result is a small break LOCA. The crew should manually trip the unit and enter 2-EOP-03, Loss of coolant accident.

On the trip a Loss of offsite power will occur with the 2B Diesel generator output breaker failing to close. The BOP should manually close the 2B Diesel generator output breaker.

At this point, RCS pressure is still above SIAS setpoint, however later when SIAS is reached the Diesel output breakers will open and re-close to sequence SIAS loads. The 2B HPSI pump will not start on SIAS and should be manually started by the RO.

Recommended termination is when both Diesel generators are loaded on their busses, the 2B HPSI pump has been started and the crew is performing a controlled cooldown.

Scenario 1 Rev. 1

3 Appendix D Operator Action Form ES-D-2 Op Test No.:

....;....- Scenario #

Event #

_____ Page 3

of 13 Event

Description:

Reduce power to remove 2B MFW pump from service.

Time I

Position I

Applicant's Actions or Behavior Booth Operator Instructions: For setup, place placard for 'B' protected train and OLRM YELLOW. Place clearance tag on 2A HPSI pp. Place Myler over HPSI annunciators.

NOTE: If surrogate SRO I RO used, brief the SRO I RO on MFRV failure, PZR level channel and HSPI pp fail to start. Stress: do not cue RO I BOP on trends related to these failures.

Handout 2-GOP-123, 'Turbine Shutdown-Full Load To Zero Load' and 2-GOP-101,

'Reactor Operating Guidelines During Steady State and Scheduled Load Changes' for crew to review in briefing room while simulator is being setup. Make copy for I/F.

NOTE: The 2A MFRV fail to respond is a manual trigger. Trigger when directed by examiner.

Control Room Indications Available:

RO/BOP Prepare the Unit for load reduction lAW 2-GOP-101 section 6.2 (attached page 4)

RO When directed by SRO perform steps 6.3 and 6.4 of 2-GOP-123 for CEA insertion. (attached page 5)

BOP When directed by SRO perform section 6.6, attached, of 2-GOP-123, DEH setup for downpower. (attached page 6)

RO Place Pressurizer on recirc lAW 2-GOP-101 Appendix A (attached page 7) when directed by SRO.

Start additional Charging pump lAW 2-NOP-02.02, section 4.3.

RO Charging and Letdown. (attached page 8,9) when directed by SRO.

When directed, align and commence boration lAW 2-NOP-RO 02.24, Boron Concentration Control, section 6.6, (attached page 10,11)

BOP Communicating with RO, hit 'GO' on Turbine control panel.

Scenario 1 Rev. 1

4 REVISION NO.:

PROCEDURE TITLE:

PAGE:

11 REACTOR OPERATING GUIDELINES DURING STEADY 8 of 16' PROCEDURE NO.:

STATE AND SCHEDULED LOAD CHANGES 2-GOP-101 ST. LUCIE UNIT 2 6.2 Power Level Reductions

1.

At or above 50% power:

A.

All planned reactivity additions should be made by boration or dilution in accordance with 2-NOP-02.24, Boron Concentration Control.

B.

USE CEAs for ASI control, CONSIDER the reactivity effect of CEAs when adjusting boron concentration.

C.

REFER to NOP-100.02, Axial Shape Index Control, for specific instructions regarding ASI control during planned or unplanned load reductions.

2.

!f available, Then ENSURE two Charging Pumps are operating.

If necessary, START an additional Charging Pump in accordance with 2-NOP-02.02, Charging and Letdown.

3.

PLACE the Pressurizer on recirculation in accordance with Appendix A, Pressurizer Recirculation Guidelines.

4.

UNLOAD the Main Generator in accordance with 2-GOP-123, Turbine Shutdown - Full to Zero Load.

5.

SECURE Zinc Injection per 2-NOP-02.26, before reducing power by more than 20%.

END OF SECTION 6.2

5 REVISION NO.:

PROCEDURE TITLE:

PAGE:

38 PROCEDURE NO.:

TURBINE SHUTDOWN - FULL LOAD TO ZERO LOAD 10 of 46 2-GOP-123 ST. LUCIE UNIT 2 6.0 INSTRUCTIONS INITIAL NOTE Steps in this procedure may be performed out of sequence provided:

  • All applicable conditions necessary to perform the step are satisfied and,
  • The performance of the out of sequence steps do not change an operational mode and
  • Permission is granted from SM/US 6.1 PREPARE the unit for the load reduction in accordance with 2-GOP-101, Reactor Operating Guidelines During Steady State and Scheduled Load Changes.

NOTE The following step is based on a reactor trip being desired, but NOT reauired based on plant parameters.

6.2 If desired by SM/US to trip the reactor at a different power level then planned, Then BRIEF the crew and GO TO step 6.28 6.3 PREPARE the CEA Control Panel for the load reduction by performing the following:

1.

PLACE the Mode Select switch in MS.

AND

2.

VERIFY the Manual Sequential Reg light is LIT.

6.4 If Group 5 CEAs are fully withdrawn, Then VERIFY CEA operability by INSERTING Group 5 just until the upper electrical limit (UEL) lights clear for all the CEAs in that group or until all the CEAs in that group have been inserted approximately one inch.

6.5

!f CEA motion is unavailable at any time during the load reduction, Then PERFORM the following:

1.

STOP the load reduction and refer to 2-AOP-66.01, Dropped or Misaligned CEA Abnormal Operations OR

2.

!f the load reduction can NOT be stopped, Then CONTACT Reactor Engineering for recommendation on ASI control.

6 REVISION NO.:

PROCEDURE TITLE:

PAGE:

38 PROCEDURE NO.:

2-GOP-123 TURBINE SHUTDOWN - FULL LOAD TO ZERO LOAD 11 of 46 ST. LUCIE UNIT 2 6.6 11 the DEH is NOT in Turbine Manual, Then PROGRAM the DEH System for the load reduction by performing the following on the Turbine DEH Cont Panel:

1.

DEPRESS the Ref pushbutton.

NOTE In the event an error is made in depressing a numerical pushbutton, the number in the Demand display can be removed by depressing the Cancel pushbutton.

2.

ENTER the desired load by DEPRESSING the numerical pushbuttons on the keyboard. VERIFY the desired number appears in the Demand display.

3.

DEPRESS the Enter pushbutton.

4.

VERIFY the Hold pushbutton illuminates.

5.

DEPRESS the Load Rate MW/Min pushbutton.

6.

ENTER the desired load rate by DEPRESSING the numerical pushbuttons on the keyboard. VERIFY the desired number appears in the Demand display.

7.

DEPRESS the Enter pushbutton. VERIFY the desired load rate appears in the Reference display.

8.

DEPRESS the Ref pushbutton.

6.7 11 a rapid load reduction is necessary, Then GO TO 2-AOP-22.01, Rapid Down Power.

6.8

.If a rapid load reduction is NOT required, Then PERFORM the following:

1.

BEGIN borating the RCS to reduce RCS temperature in accordance with 2-NOP-02.24, Boron Concentration Control.

INITIAL

7 REVISION NO.:

PROCEDURE TITLE:

11 REACTOR OPERATING GUIDELINES DURING STEADY P-RO-C-ED-U-R-E-NO.... :--....

STATE AND SCHEDULED LOAD CHANGES 2-GOP-101 ST. LUCIE UNIT 2 APPENDIX A PRESSURIZER RECIRCULATION GUIDELINES (Page 1 of 2)

NOTE PAGE:

12 of 16 The purpose of placing the Pressurizer on recirculation is to keep the Pressurizer and RCS boron concentration within 25 ppm when changing RCS boron concentration.

From measured data, the estimated time in minutes to correct a greater than or equal to 25 ppm boron mismatch by operating 6 Backup Bank heaters may be determined as follows:

Time (in minutes) to correct mismatch = [(pzr ppm - RCS ppm)-

25 ppm] x 3

1.

To place the Pressurizer on recirculation:

A.

PLACE all available Backup Bank heater control switches to ON.

B.

Slowly REDUCE the AUTO setpoint on PIC-1100X or PIC-1100Y, the selected "Pressurizer Pressure" controller, to maintain normal operating pressure.

C.

OBSERVE HIC-11 00, "Pressurizer Spray" output and PCV-11 00E/11 OOF, "Pressurizer Spray Valve" position indication to verify Main Spray flow.

NOTE Normally, the required number of Backup Bank heaters in service is dependent upon:

1. The magnitude of thermal losses from the system, including leakage to the Quench Tank.
2. The number of heater elements out of service.

The normal configuration is to have enough Backup Bank heaters in service to keep the Proportional Bank heaters at approximately 50% output.

2.

To take the Pressurizer off recirculation:

A.

REMOVE the additional Backup Bank heaters from service one at a time by returning the control switch to AUTO.

B.

ADJUST the AUTO setpoint on PIC-1100X or PIC-1100Y, the selected "Pressurizer Pressure" controller, to maintain normal operating pressure.

8 REVISION NO.:

51 PROCEDURE TITLE:

PAGE:

PROCEDURE NO.:

2-NOP-02.02 CHARGING AND LETDOWN ST. LUCIE UNIT 2 4.3 Start Additional Charging Pump's) to Raise Flow WARNING 17 of 80 Placing a second or third charging pump in service will increase letdown flow.

which may cause general area dose rates in vicinity of letdown line in the 19.5' Pipe Penetration room or 19.5' Letdown Cubicle room to exceed 1000 mr/hr (Locked High Radiation Area limit) due to reduced transport time of short-lived radioactive isotopes.

1.

NOTIFY RP at least 15 minutes prior to starting a charging pump.

2.

DIRECT SNPO to perform a local inspection and verify charging pump to be started is ready to operate.

3.

IF in MODE 1 or 2. THEN PLACE V2520. ION EXCHANGER BYPASS VALVE. in BYPASS RESET to minimize reactivity effects of changing letdown temperature.

4.

IF associated charging pump recirculation valve is OPERABLE.

THEN ENSURE the valve is OPEN prior to starting the pump.

5.

START charging pump by placing its control switch in START.

6.

WHEN 3 minutes has elapsed since pump start, THEN ENSURE associated recirc valve is CLOSED.

7.

ADJUST upper BIAS control knob on HIC-111 O. LEVEL. to control letdown flow to maintain actual Pressurizer level to program RRS Pressurizer level for current plant conditions. as required.

8.

VERIFY proper charging header flow by ~

of the following methods:

IF FIA-2212. CHARGING TO REGEN HX. is in service. THEN VERIFY indication raises and stabilizes for number of running charging pumps.

IF FIA-2212 is NOT in service. THEN VERIFY the following:

Letdown flow rises Pressurizer level rises in response to starting the additional charging pump

9 REVISION NO.:

51 PROCEDURE TITLE:

PAGE:

PROCEDURE NO.:

2-NOP-02.02 CHARGING AND LETDOWN ST. LUCIE UNIT2 4.3 Start Additional Charging Pump(s) to Raise Flow (continued)

9.

PLACE CHRG PUMP SEL RUNNING - BtU PP switch in proper position per Attachment 2, Charging Pump Combinations VS. Selector Switch Position.

10.

WHEN letdown temperature stabilizes, THEN ENSURE V2520, ION EXCHANGER BYPASS VALVE, control switch is returned to AUTO.

18 of 80

10 REVISION NO.:

PROCEDURE TITLE:

PAGE:

23 of 76 PROCEDURE NO.:

25A BORON CONCENTRATION CONTROL 2-NOP-02.24 ST. LUCIE UNIT 2 6.6 Aligning for MANUAL Boration CHECK NOTE The Operations Supervisor SHALL be notified and a CR submitted of any unexplained or unplanned Reactivity change (Le., >.5 deg Tcold

~

change or >.5% power change).

J>

If a Reactivity management issue occurs, refer to procedure ADM-09.11, Reactivity Management.

Engineering Assessment of FIC-2210Y Boric Acid Flow, show that there could be an error up to -+/- 0.1 GPM. Recommended minimum Boric Acid Flow is 0.75 gpm.

1.

ENSURE Section 3.0, Prerequisites is completed at least once per shift.

2.

ENSURE Section 4.0, Precautions I Limitations, has been reviewed at least once per shift.

3.

DETERMINE the desired volume of boric acid to be added.

4.

IF necessary to re-zero boric acid totalizer, THEN PRESS STOP I RESET on FQIS-2210Y.

5.

ENSURE Makeup Mode Selector switch in MANUAL.

6.

ENSURE FIC-2210X, Reactor Water Flow, in MANUAL and REDUCE the controller output to ZERO.

7.

ENSURE FCV-2210X, Primary Makeup Water. control switch is in CLOSED.

8.

ENSURE FIC-2210Y, Boric Acid Flow, in MANUAL and REDUCE the controller output to ZERO.

9.

ENSURE FCV-2210Y, Boric Acid, control switch is in CLOSED.

10.

ENSURE one of the Primary Makeup Water Pumps 2A or 2B is running.

11.

START either BA Pump 2A or 2B.

12.

PLACE FCV-2210Y control switch in AUTO.

13.

!f borating to the VCT, Then OPEN V-2512, Reactor Makeup Water Stop Vlv.

11 PROCEDURE TITLE:

PAGE:

REVISION NO.:

25A PROCEDURE NO.:

BORON CONCENTRATION CONTROL 24 of 76 2-NOP-02.24 ST. LUCIE UNIT 2 6.6 Aligning for MANUAL Boration (continued)

14.

If borating to the Charging Pump suction, Then OPEN V2525, Boron Load Control Valve.

15.

ADJUST FIC-2210Y Boric Acid Flow in AUTO or MANUAL to the desired flowrate.

NOTE Ensure a minimum of 10 gpm boric acid flow at all times with the BAM pump recirc valve closed.

16.

If desired to maximize the boric acid flow rate CLOSE the running BAM pump recirc valve.

17.

MAINTAIN VCT pressure less than or equal to 30 psig by opening and closing V2513, VCT Vent, as needed.

18.

If necessary to maintain the desired VCT level, It:llID DIVERT the letdown flow to the Waste Management System by placing V2500, VCT Divert Valve, in the WMS position.

19.

When the desired VCT level is reached, Then PERFORM the following:

A.

PLACE V2500 to the AUTO position.

B.

ENSURE V2500 indicates CLOSED.

20.

When the desired amount of boric acid has been added, Then OPEN the BAM pump recirc valve if closed previously.

21.

When the desired amount of boric acid has been added, ~

CLOSE FCV-2210Y, Boric Acid.

22.

If additional Borations are desired, or if the expected changes to Tave, or Boron concentration are NOT achieved, Then REPEAT Steps 6.6.1 through 6.6.20.

CAUTION

~1 Stopping either BAM pump with the Makeup Mode Selector switch in any position other than MANUAL could cause the pump breaker to trip.

23.

STOP the running Boric Acid Pump by PLACING the control switch in AUTO.

CHECK

12 Appendix D Operator Action Form ES-D-2 Op Test No.:

....;.._ Scenario #

1 Event #

.....;2=--____ Page 4

of _1.... 3--t Event

Description:

2A MFRV fails to respond to down power Time I

Position i

Applicant's Actions or Behavior Booth Operator Instructions: Trigger 2A MFRV fails to respond when directed by examiner.

NOTE: When MFRV is in manual and controlled, call as NPO and state Main Feed pump oil leak is getting worse.

Control Room Indications Available: 2A SG level rising as downpower progresses. Steam flow Feed flow mismatch. 2A High SG level alarm if not noticed in a timely manner.

lOA from 2-AOP-09.01, Feedwater Control System Abnormal BOP Operations, If SG levels are not between 60-70% NR and not stable, take manual control of feed flow and stabilize SG levels to 60-70% NR.

NOTE: manual trip criteria is S 50% and 2: 70% narrow range.

BOP Place the 2A MFRV in manual to control 2A SG level to 60-70% NR.

When directed by SRO operate 2A MFW control system lAW 2-AOP-09.01 steps 4.2.2.2.1 through 2.5. (attached page 13)

RO/BOP When 2A SG level in manual control and controlling within band continue with downpower as directed by SRO.

RO When directed by SRO begin rapid downpower boration per Operator aid. (attached page 14,15)

BOP Program DEH for desired load reduction RO When directed insert CEA lead group 6 inches RO When Tave lowering, notify SRO I BOP to press go on Turbine Scenario 1 Rev. 1

13 REVISION NO.:

PROCEDURE TITLE:

PAGE:

1

'0 FEEDWATER CONTROL SYSTEM ABNORMAL OPERATIONS 90f57 PROCEDURE NO.:

2-AOP-09.01 ST. LUCIE UNIT 2 I INSTRUCTIONS I I CONTINGENCY ACTIONS I 4.2.2 S/G Level, Feed Flow, or Steam Flow Anomalies 0

1.

PERFORM applicable step(s) in any order per Table 2.

Table 2 Level or Feedwater Control Malfunctions Suspected Malfunction Step HPFRV Section 4.2.2 Step 2 MFW pump recirculation valve Section 4.2.2 Step 3 FCV-12-1. Condensate Hdr Recirc To Cndsr Section 4.2.2 Step 4 DCS FW inputs Section 4.2.2 Step 5 LPFRV Section 4.2.2 Step 6

~

The HPFRV and its associated LPFRV have flow-compensation logic such that operating one in manual with the other in auto may cause the valve in auto to reposition in an attempt to keep the feed flow rate constant.

D

2.

VERIFY HPFRV controllers are 2.1 ENSURE affected LOW PWR MIA controlling SIG levels in normal STA is in A (auto).

band:

2.2 PLACE affected HIGH PWR MIA FIC-9011. SIG 2A FLOW STA in M (manual).

CNTL (HPFRV 2A) 2.3 CLOSE affected HPFRV using FIC-9021. SIG 28 FLOW HIGH PWR MIA STA until LPFRV CNTL (HPFRV 28) is 20% to 50% open.

2.4 MAINTAIN SIG level in normal band.

2.5 MAINTAIN LPFRV between 20%

to 50% open by adjusting HPFRV as required.

14 REVISION NO.:

4 PROCEDURE NO.:

2-AOP-22.01 PROCEDURE TITLE:

RAPID DOWNPOWER ST. LUCIE UNIT 2 ATTACHMENT 1 RCS Boration Guidance (Page 1 of 2)

NOTE PAGE:

31 of 39 Step 1 in this attachment is applicable when the CVCS is normally aligned, with no RCS boration or dilution in progress. If other than normal alignment, use guidance of 2-NOP-02.24, Boron Concentration Control.

An Operator Aid has been placed at RTGB-205. Any revision to this section of the procedure shall verify the validity of the Operator Aid and, if changes are necessary, a Label Request shall be initiated to incorporate these changes on a new Operator Aid Placard.

1.

BORATE the RCS by the following:

A.

START either Boric Acid Pump 2A or 2B.

B.

PLACE FCV-2210Y, BORIC ACID (RTGB-205), control switch in AUTO.

C.

IF borating to the Charging Pump suction, THEN OPEN V2525, BORON LOAD CONTROL VALVE (RTGB-205).

D.

IF borating to the VCT, THEN OPEN V2512, REACTOR MAKEUP WATER STOP VLV (RTGB-205).

E.

ADJUST FIC-221 OY, BORIC ACID, to the desired flowrate.

F.

IF desired to maximize the boric acid flow rate, THEN CLOSE the running BAM pump recirc valve.

V2650, TANK 2A RECIRC VALVE (RTGB-205)

V2651, TANK 2B RECIRC VALVE (RTGB-205)

G.

CYCLE V2513, VENT VALVE (RTGB-205) to maintain VCT pressure less than or equal to 30 psig.

H.

CYCLE V2500, DIVERT VALVE (RTGB-205) to WMS if necessary to maintain the desired VCT level.

15 REVISION NO.:

4 PROCEDURE NO.:

2-AOP-22.01 PROCEDURE TITLE:

RAPID DOWNPOWER ST. LUCIE UNIT 2 ATTACHMENT 1 RCS Boration Guidance (Page 2 of 2)

2.

SECURE boration as follows:

A.

ENSURE BAM pump recirc valves, OPEN V2650, TANK 2A RECIRC VALVE (RTGB-205)

V2651, TANK 2B RECIRC VALVE (RTGB-205)

B.

CLOSE FCV-2210Y, BORIC ACID (RTGB 205).

C.

ADJUST FIC-221 OY, BORIC ACID, to zero (RTGB 205).

D.

STOP running Boric Acid Pump.

PAGE:

32 of 39 E.

ENSURE CLOSED V2512, REACTOR MAKEUP WATER STOP VLV (RTGB-205).

F.

ENSURE CLOSED V2525, BORON LOAD CONTROL VALVE (RTGB-205).

G.

ENSURE CLOSED V2513, VENT VALVE (RTGB-205)

H.

ENSURE V2500, DIVERT VALVE, in AUTO (RTGB 205).

16 Appendix D Operator Action Form ES-D-2 Op Test No.:

.....;...._ Scenario#

Event #

_3;;..... ____ Page 5

of 13 Event

Description:

Pressurizer Level Channel L T-1110X fails as is Time I

Position I

~plicant's Actions or Behavior Booth Operator Instructions: Trigger L T *111 OX fail as is when directed by examiner.

Control Room Indications Available: Letdown flow not lowering as expected for downpower. Pressurizer level deviation from setpoint as downpower progresses.

Annunciator H*18 'Pzr. Channel Y level High/Low' (if failure not realized in timely manner)

Examiners note: This is a subtle failure in that the applicant should recognize letdown flow should be substantially lower than charging flow due to the downpower. As the downpower progresses Pressurizer level will deviate low from setpoint.

Recognizes letdown flow is not constant (i.e. to high) for downpower.

lOA of 2-AOP-01.10, Pressurizer Pressure and Level. VERIFY RO selected Pressurizer level control channel LlC-111 OX(Y),

LEVEL, NORMAL.

CONTINGENCY ACTIONS: PLACE LEVEL CONTROL CHANNEL selector switch to non-affected control channel.

Swap Pressurizer level channel to LlC-1110Y Verifies letdown flow lowering and Pressurizer level recovering to setpoint.

When Pressurizer level reaches setpoint communicates to SRO.

Scenario 1 Rev. 1

17 Appendix D Operator Action Form ES-D-2 Op Test No.:

Scenario #

Event #

_4.;...-.____ Page.2....- of.....;.,;13;""'-1 Event

Description:

Letdown Isolation valve V2515 fails closed. Letdown line leak.

Time I

Position I

Applicant's Actions or Behavior Booth Operator Instructions: Trigger Letdown Isolation valve V2515 fail closed when directed.

Control Room Indications Available: M-5 Letdown Press High/Low. No letdown flow indication.

Examiners Note: One minute after Letdown valve fails closed a letdown line break in Containment occurs resulting in approximately 200 gpm non-isolable leak.

Recognize and communicate letdown valve V2515 failed RO closed. Stops all running Charging pumps and places control switches in AUTO. lOA's from 2-AOP-02.03, Charging and Letdown.

Recognize and communicate RCS leakage alarm. RCS leak rate recorder indicates full scale. Pressurizer level and pressure lowering.

When directed by SRO, start all available Charging Pumps.

Recognize and communicate Pressurizer level lowering and cannot be maintained on setpoint with all charging pumps running. Recommend tripping the Reactor.

RO When Pressure reaches ONB T.S. setpoint (2225 psia) communicate to SRO 'entered ONB T.S.'

SRO May elect to perform a quick T.S. brief on RCS T.S. leakage.

RO/BOP When directed by SRO trip the Reactor.

Scenario 1 Rev. 1

18 Appendix D Op Test No.:

Event

Description:

Operator Action Form ES-D-2 Scenario #

Event #

_5;.:.,,6;...... ___ Page ?...- of _1;,.;;.3--1 SBLOCA manual trip, Loss of Offsite Power, 2B Diesel Breaker fails to close on LOOP Time I

Position I

Applicant's Actions or Behavior Booth Operator Instructions:

Control Room Indications Available: LOOP. 2B Diesel Generator Breaker does not close.

Examiners note: due to small break SIAS will probably not occur while crew is in EOP-01 Manually trips reactor prior to auto trip. Performs EOP-01 RO Safety Functions as directed for Reactivity Control, Inventory Control, Pressure Control, Core Heat removal.

Reactivity Control

  • Verify Reactor power is lowering.
  • Verify startup rate is negative.
  • Verify all CEAs are fully inserted.

Inventory Control

  • Verify Pressurizer level is between 10 and 68%
  • Pressurizer level is trending to 30 - 35%.

Pressure Control

  • Verifies RCS pressure is between 1800-2300 psia.
  • Verifies RCS pressure is trending 2225-2275 psia.
  • Verifies RCS subcooling is ~20°F.

Core Heat Removal

  • Verifies at least one RCP running with CCW. (no RCP's running due to LOOP)
  • Verifies loop delta T is <10°F. (loop delta T will be higher than 10°F due to nat. circ. Developing)

Scenario 1 Rev. 1

19 Appendix D Op Test No.: -----

Event

Description:

Operator Action Form ES-D-2 Scenario #

Event #

_5..:.,,6 ____ Page L-of --.,;13;"""'-1 SBLOCA manual trip, Loss of Offsite Power, 2B Diesel Breaker fails to close on LOOP Time I

Position I

Applicant's Actions or Behavior Booth Operator Instructions:

Control Room Indications Available:

Verifies turbine trip on reactor trip. Performs EOP-01 Safety BOP functions as directed for: Vital Auxiliaries, RCS Heat Removal, Containment Conditions.

BOP Recognize and communicate 2B Diesel output breaker did not Critical close. Insert Sync. Plug into 2B Diesel breaker and close Diesel Output breaker. Monitor and verify load sequencing on Task the 2B Diesel.

Closes MSR reheat Block TCV's due to loss of power to MSR block valves.

Notifies NPO to perform Appendix X section 1 of EOP-99.

(outside CR actions)

Notify SNPO to check SFP inventory and temperature.

Maintenance of Vital Auxiliaries

  • Verifies turbine governor and throttle valves closed.
  • Verifies GEN Brk open (East breaker, Mid Breaker and Exciter Breaker.)
  • Verifies all vital and non vital AC Buses energized.
  • Verifies all vital and non vital DC Buses energized.

RCS Heat Removal

  • Verify at least one SG has BOTH:

SG Level 20-83% NR Feedwater available, level being restored to 60-70% NR

  • Verify RCS Tavg is between 525 and 535 0 F
  • SG pressure between 850-930 psia via ADV's Scenario 1 Rev. 1

20

---.-.---~~~~

Appendix D Op Test No.:

Event

Description:

Operator Action Form ES-D-2 Scenario #

Event #

...,;5;;.:,,6;...... ___ Page

_9 _

of _1;..;.3---4 SBLOCA manual trip, Loss of Offsite Power, 2B Diesel Breaker fails to close on LOOP Time I

Position I

Applicant's Actions or Behavior Booth Operator Instructions:

Control Room Indications Available:

BOP Place ADV's in AUTO/AUTO to maintain 900 psia SG pressures.

Containment Conditions

  • Verifies Containment pressure <2 psig. (Pressure is increasing ensures 4 Containment Cooling fans on.)

BOP

  • Verifies NO Containment radiation monitors in alarm.
  • Verifies Containment temperature is less than 120°F.

(Temperature is increasing)

  • Verifies NO secondary plant radiation alarms.

SRO should exit 2-EOP-01, Standard Post Trip Actions to 2-EOP-03, Loss of Coolant Accident. ST A should perform Safety Function Status Check Sheets for 2-EOP-03.

NOTE: on AFAS, AFAS -1 may lockout due to 2A Diesel breaker closing before the manual closure of 2B Diesel breaker. (2B AFW pump start delay). The BOP should recognize this condition and recommend to SRO that AFAS-1 should be manually actuated.

Scenario 1 Rev. 1

21


~.. ~-----~----

Appendix D Operator Action Form ES-D-2 Op Test No.:

.....;....- Scenario #

1 Event #

_7~ ____ Page 10 of _1~3---1 Event

Description:

2B HPSI fails to automatically start Time I

Position I

Applicant's Actions or Behavior Booth Operator Instructions: Trigger Appendix H when directed.

Control Room Indications Available:

Perform Appendix A, (step 4) Sampling Steam generators when directed (attached page 22) NOTE: CCW cannot be BOP restored to the "N' header for SG blowdown sample cooling. As a result HP will need to be called for local surveys. (step 4 of Appendix A)

When directed place the four CCW valves to/from the RCP's to BOP CLOSE. Place the two RCP Bleedoff valves to CLOSE. (step 8.A.3)

BOP When SIAS received, verify ESFAS pumps and valves actuate as designed. (step 6)

RO Critical Recognize 2B HPSI did not start on SIAS. Communicates and starts the 2B HPSI pump.

Step EXAMINER NOTE: The above Critical Task is applicable if RCS pressure lowers to

<HPSI shutoff head (-1200 psia) and the 2B HPSI pump has not been started.

BOP Close the MISV's and SGBD valves when directed. (step 13)

Perform Appendix X section 2 when directed (step 13B).

(attached page 23-26)

When directed, coordinate with NPO to restore Instrument Air BOP (step 14) lAW Appendix H. When NPO called stating alignment complete, BOP should reset the 2A and or 2B Instrument air compressors from the control board.

Scenario 1 Rev. 1

22 REVISION NO.:

PROCEDURE TITLE:

PAGE:

40 PROCEDURE NO.:

2-EOP-99

2. (continued)

APPENDICES I FIGURES I TABLES I DATA SHEETS ST. LUCIE UNIT 2 APPENDIX A SAMPLING STEAM GENERATORS (Page 2 of 2) o B.!f CIAS or high radiation has closed the SGBD Sample Valves, Then OPEN FCV-23-7 and FCV-23-9 by PLACING the control switch to CLOSE I OVERRIDE and then to OPEN.

o 3. !f..S/Gs can be sampled, Then:

A.

ENSURE OPEN FCV-23-7 and FCV-23-9, SGBD Sample Valves.

B.

DIRECT Chemistry to perform S/G samples for activity and boron.

o 4. !f S/Gs cannot be sampled, Then DIRECT Health Physics to conduct secondary plant local area radiation surveys.

END OF APPENDIX A 4 of 159

23 REVISION NO.:

40 PROCEDURE NO.:

2-EOP-99 PROCEDURE TITLE:

APPENDICES I FIGURES I TABLES I DATA SHEETS ST. LUCIE UNIT 2 APPENDIX X SECONDARY POST TRIP ACTIONS (Page 5 of 8)

Section 2: CONTROL ROOM ACTIONS PAGE:

118 of 159 INSTRUCTIONS CONTINGENCY ACTIONS o 1. ENSURE ONLY ONE MFW Pump is RUNNING, with the control switch in RECIRC.

o 2. ENSURE ONLY ONE Condensate Pump is RUNNING.

o 3. !f AFAS has actuated, and use of Main Feedwater is

desired, Then PERFORM ALL of the following:

o A. ENSURE AFAS is RESET.

o B. ENSURE BOTH SIG [Main FRV] Block valves CLOSED.

1. MV-09-5
2. MV-09-6 o C. ENSURE BOTH Low Power MIA Stations in MANUAL.

o D. For EACH MFW header to be placed in service, ENSURE the associated MFIVs are OPEN.

o E. DEPRESS BOTH pushbuttons to RESET the Low Power Feedwater Valves.

o F. ADJUST the Low Power MIA Stations AS NECESSARY to control SIG levels.

o G. RESTORE AFW to the standby alignment.

24 REVISION NO.:

40 PROCEDURE NO.:

2-EOP-99 PROCEDURE TITLE:

APPENDICES I FIGURES I TABLES I DATA SHEETS ST. LUCIE UNIT 2 APPENDIX X SECONDARY POST TRIP ACTIONS (Page 6 of 8)

Section 2: CONTROL ROOM ACTIONS (continued)

PAGE:

1190f159 INSTRUCTIONS CONTINGENCY ACTIONS o 4. !f AFAS has NOT actuated and use of Main Feedwater is

desired, Then PERFORM ALL of the following:

o A. ENSURE BOTH S/G [Main FRY] Block valves CLOSED.

0 B. For EACH MFW header to be placed in service, ENSURE the associated MFIVs are OPEN.

0 C. ENSURE BOTH Low Power MIA Stations in MANUAL.

0 D. DEPRESS BOTH push buttons to RESET the Low Power Feedwater Valves.

0 E. ADJUST the Low Power MIA Stations AS NECESSARY to control S/G levels.

o 5. ENSURE BOTH Heater Drain Pumps are STOPPED.

o 6. ENSURE BOTH of the following:

o A. Bearing Oil Pump DA.1 ENSURE Emergency Bearing Oil and Seal Oil Backup Pump Pump RUNNING.

RUNNING.

0 B. When the turbine reaches 600 rpm, Then Bearing Oil Lift Pump RUNNING.

25 REVISION NO.:

PROCEDURE TITLE:

PAGE:

40 PROCEDURE NO.:

APPENDICES I FIGURES I TABLES I DATA SHEETS 120 of 159 2-EOP-99 ST. LUCIE UNIT 2 APPENDIX X SECONDARY POST TRIP ACTIONS (Page 7 of 8)

Section 2: CONTROL ROOM ACTIONS (continued)

INSTRUCTIONS o 7. ENSURE the Turbine Drain Valves are OPEN.

o 8. ENSURE ONLY ONE Turbine Cooling Water Pump is RUNNING.

o 9. VERIFY Turbine Generator Bearing Oil temperature between 11 0 to 120°F.

CONTINGENCY ACTIONS o 9.1 DIRECT a field operator to adjust TCW to the in-service TLO Cooler to maintain outlet Oil temperature between 11 0 to 120°F.

o 10. When Turbine speed reaches ZERO 010.1 PERFORM ALL of the following:

rpm, Then VERIFY the turning gear automatically ENGAGES.

o 11.!f Reactor power history is low, Then CONSIDER reducing steam generator blowdown flow to maintain RCS temperature.

o A. PLACE Turning Gear in MANUAL.

o B. VERIFY the Turning Gear Permissive Light is ON.

o C. Locally ENSURE the Turning Gear is ENGAGED.

o D. Locally START the Turning Gear.

26 REVISION NO.:

40 PROCEDURE NO.:

2-EOP-99 PROCEDURE TITLE:

APPENDICES I FIGURES I TABLES I DATA SHEETS ST. LUCIE UNIT 2 APPENDIX X SECONDARY POST TRIP ACTIONS (Page 8 of 8)

Section 2: CONTROL ROOM ACTIONS (continued)

PAGE:

121 of 159 INSTRUCTIONS CONTINGENCY ACTIONS o 12. Place Boron Dilution Alarm System in Operation.

When indicated Reactor power is less than 10-5%,

Then PERFORM BOTH of the following:

o A. ENERGIZE BOTH channels of Startup Nuclear Instrumentation to place the Boron Dilution Alarm System in operation.

o B. VERIFY BOTH Boron Dilution Alarm System Channels are operating.

012.1 !f BOTH Boron Dilution Alarm System chanr'iels are NOT operating, Then PERFORM applicable actions of 2-AOP-02.01, Boron Concentration Control System (BCCS) Abnormal Operations.

NOTE Excessive moisture can build up in CEDMC's room, and impact equipment reliability if 15 KW heaters are not energized after plant shutdown.

o 13. NOTIFY SNPO to energize 15 KW heater located in the CEDMC's room to minimize humidity build-up per 2-NOP-25.10, CEDMCS Air Conditioning System Operation.

o 14.CONSIDER contacting the Division Load Dispatcher for a switching order to OPEN the Main Generator disconnects.

END OF APPENDIX X

27 Appendix D Operator Action Form ES-D-2 Op Test No.:

.......;....- Scenario #

Event #

_7.;...... ____ Page 11 of 13 Event

Description:

2B HPSI fails to automatically start Time I

Position I

Applicant's Actions or Behavior Booth Operator Instructions: Trigger Appendix H when directed.

Control Room Indications Available:

When directed, cooldown (step 18) the RCS using the ADV's RO not to exceed 50°F in anyone hour period. Up to 100°F in any one hour period is allowed to regain or maintain subcooling.

RO When directed depressurize the RCS using Aux. Spray (step

19) to maintain subcooling at the lower limits of Figure 1 A.

Suggested termination point is when the 2B HPSI pump has been started, Instrument air has been restored and a controlled cooldown and depressurization is in progress.

Scenario 1 Rev. 1

28 OPERATIONS SHIFT TURNOVER REPORT UNIT 2 CONTROL ROOM Day: Today Desk RCO:

Board RCO:

Protected Train: B Unit 2 Identified RCS Leakage:

o Unit 2 Unidentified RCS Leakage: 0.012 Unit 2 Scheduled Activities per the OSP: Reduce power to 45% to remove the 2A Main feedwater pump from service due to oil leak on oil cooler.

Upcoming ECOs to Hang or Release:

Tech Spec Action Statement: 2A HPSI Pump Out of Service for motor oil leak.

OPS 513's:

Locked in Annunciators:

Current Status: 100% power MOe Equipment Problems: 2A Main Feedwater pump motor oil leak.

Scenario 1 Rev. 1

29 Applicable Procedures 2-GOP-123, Turbine Shutdown-Full Load To Zero Load' 2-GOP-101, 'Reactor Operating Guidelines During Steady State and Scheduled Load Changes' 2-AOP-09.01, 'Feedwater Control System Abnormal Operations' 2-AOP-O 1.10, 'Pressurizer Pressure and Level' 2-AOP-02.03, 'Charging and Letdown' 2-EOP-01, 'Standard Post Trip Actions' 2-EOP-03, 'Loss of Coolant Accident' Scenario 1 Rev. 1

1 Facility:

St. Lucie Scenario No.:

2 Op Test No.:

HLC 20A Examiners:

Operators:

SRO:

RO:

BOP:

Initial Conditions:

45% power, Xenon building in, 16 gpm dilution rate I/C #3, MOC.

Turnover: Unit was down powered to remove the 2A Main feedwater pump to repair a motor oil leak.

Repairs have been made and both Main Feedwater pumps are running. 2A High Pressure safety injection pump is out of service to repair a motor oil leak. Taken out of service 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> ago. B train protected, OLRM: Yellow Critical Tasks:

Direct to locally close 2B MSIV Stop all RCP's within 10 minutes of loss of CCW Event Malf.

Event Event No.

No.

Type*

Description 1

RlRO, Raise power to 100%

RlBOP 2

1 C/BOP CEDM Fan 21 A sheared shaft 3

2 C/RO Letdown flow controller HIC-1110 goes to maximum flow.

4 3

C/BOP 2B Intake cooling water pump failed motor bearing, increasing AMPS.

5 4

N/BOP 2B Steam Generator 10 GPM SGTL.

6 5

MIAII 2B Steam Generator tube rupture 200 GPM 7

6 C/BOP 2B Main Steam isolation valve (MSIV) fails to close on isolation of 2B Steam Generator. Locally close 2B MSIV.

8 7

C/RO Auxiliary spray valve SE-02-3 fails to close after opening to lower subcooling.

9 Cooldown and isolate the 2B Steam Generator (N)ormal, (R)eactivity, (I)nstrument, (C)omponent, (M)ajor BOP

/N

2 SCENARIO EVENT DESCRIPTION SCENARIO 2 The Unit will be turned over at 45% power with directions to raise power to 100%.

During the up-power CEDM cooling fan 21A experiences a sheared shaft. The Standby fan HVE-21 B will not automatically start and should be manually started. Failure to have one fan running requires a plant shutdown.

Letdown flow controller HIC-1110 will fail causing maximum letdown flow. Actions should be taken to manually control letdown to match charging flow and maintain Pressurizer level at setpoint.

The 2B Intake Cooling water pump will experience a failed motor bearing resulting in increasing motor amps. If not identified within a few minutes, the pump will trip on overcurrent. This will require the 2C Intake cooling water pump to be electrically and mechanically aligned to replace the 2B A Steam Generator tube leak of approximately 10 gallons per minute will occur on the 2B Steam Generator. Secondary radiation should cue the crew into the proper diagnoses. Because letdown flow control is in manual, a mis-match between charging and letdown will not occur. Manual reduction of letdown should be performed to maintain Pressurization level on setpoint. The up power should be terminated and a rapid down power should be started. As the down power progresses, the tube leak will ramp to a 200 gallon per minute tube rupture. The crew should manually trip the plant and enter 2-EOP-01, Standard Post Trip actions.

After 2-EOP-01 is complete the crew should enter 2-EOP-04, Steam Generator Tube Rupture. Major mitigating actions are to cooldown and isolate the 2B Steam Generator.

Subcooling should be controlled at the minimum values to limit leak flow. Because all RCP's will be turned off due to procedure requirements, lowering RCS pressure will be accomplished by cycling the Auxiliary spray valves and closing the charging loop isolation valves. When SE-02-3 is opened and attempted to be closed, the valve will not close. Proper actions are to re-open the charging loop isolation valves. This will limit the spray flow through the failed open Aux. spray valve to a controllable level and subcooling will be maintained.

When isolation criteria is met for the 2B Steam Generator the crew should isolate the Steam Generator. When attempting to close the 2B MSIV, the valve will not close from the control room. 2-EOP-99 Appendix I should be implemented to locally close the 2B MSIV.

Suggested termination point is when the crew has isolated the 2B Steam Generator and controlled cooldown and RCS depressurization is occurring.

Scenario 2 Rev. 1

3 Appendix D Operator Action Form ES-D-2 Op Test No.:

......;...- Scenario #

2 Event #

_1~ ____ Page 3

of 16 Event

Description:

Raise power to 100%

Time I

Position I

Applicant's Actions or Behavior Booth Operator Instructions: Place placard for 'B' protected train and OLRM YELLOW. Place clearance tag on 2A HPSI pp. Place Myler over HPSI annunciators.

Start the 2B Main Feedwater pump. With crew in briefing room hand out 2-GOP-101 and 2-GOP-201 signed off up to 6.136. Crew to perform a brief while simulator is being setup. Also sign off 6.136 step 4 as RE, Nuc. Delta T not required and N/A steps 5 and 6.

NOTE: If surrogate SRO I RO used, brief the SRO I RO on HIC-111 0 failure and 2B ICW pp failure. Do not cue RO I BOP on observed trends related to these failures.

Control Room Indications Available:

RO Raise dilution rate for power increase lAW 2-NOP-02.24, Boron Concentration Control, step 6.5.13 (attached page 4)

Withdraw CEA's to control Rx power and ASI lAW 2-GOP-101 Rx Operating Guidelines step 6.1 (attached page 5)

  • CEA Withdrawal, select MS on the CEDMCS Control Switch
  • Move the IN/HOLD/OUT Switch to the OUT direction Divert letdown to WMS by placing V2500 to WMS to maintain VCT level within normal band.

Program DEH for power increase

  • Set reference by ensuring REF selected and then BOP depress desired MW endpoint, select ENTER
  • Depress LOAD RATE type in desired load rate and select ENTER
  • Depress GO pushbutton Scenario 2 Rev. 1

4 REVISION NO.:

PROCEDURE TITLE:

PAGE:

25A BORON CONCENTRATION CONTROL PROCEDURE NO.:

2-NOP-02.24 ST. LUCIE UNIT 2 21 of 76 6.5 Aligning for MANUAL Dilution (continued)

12.

DDDD!f diluting to the Charging Pump suction, Then OPEN V-2525, Boron Load Control Valve.

CAUTION To preclude lifting the VCT relief valve while using V-2525, do NOT allow PMW flowrate to exceed the running Charging pump(s) capacity.

13.

DODD ADJUST FIC-2210X PMW Flow in AUTO or MANUAL to desired flowrate (and if using V-2525 do NOT exceed the flowrate for the number of running Charging Pumps).

14.

DODD MAINTAIN VCT pressure less than or equal to 30 psig by opening and closing V2513, VCT Vent, as needed.

15.

DDDD!f necessary to maintain the desired VCT level, Then DIVERT the letdown flow to the Waste Management System by placing V2500, VCT Divert Valve, in the WMS position:

A.

0 0 0 0 ENSURE V2500 VCT Divert Valve indicates OPEN.

B.

DODD When the desired VCT level is reached, PLACE V2500 in AUTO.

C.

0 0 0 0 ENSURE V2500 indicates CLOSED.

16.

DODD When the desired amount of primary water has been added, Then CLOSE FCV-221 OX, Primary Makeup Water.

17.

DODD !fV-2512 Reactor Makeup Water Stop Vlv was opened, Then PLACE V-2512 in CLOSE and ENSURE it indicates CLOSED.

18.

DODD !fV-2525 Boron Load Control Valve was opened, Then PLACE V-2525 in CLOSE and ENSURE it indicates CLOSED.

19.

0 0 0 0 ENSURE FIC-2210X, PMW Flow controller is in MANUAL and RECUCE output to MINIMUM.

20.

DODD MONITOR for any abnormal change in Taw.

21.

0 0 0 0

§1 RECORD on Data Sheet 1, Boration I Dilution Log, the number of gallons of Primary Makeup Water added as indicated on FQI-2210X, PMW Flow Totalizer.

22.

0 0 0 0 !f additional dilutions are desired, or if the expected changes to Taw or Boron concentration are NOT achieved, Then REPEAT Steps 6.5.1 through 6.5.20.

5 REVISION NO.:

PROCEDURE TITLE:

PAGE:

11 REACTOR OPERATING GUIDELI NES DURING STEADY

""P-ROC-ED-U-R-E....

NO-.:---4 STATE AND SCHEDULED LOAD CHANGES 6 of 16 2-GOP-101 ST. LUCIE UNIT 2 6.0 INSTRUCTIONS NOTE Steps in this procedure may be performed out of sequence provided:

  • All applicable conditions necessary to perform the step are satisfied and,
  • The performance of the out of sequence steps do not change an operational mode and
  • Permission is granted from SM/US 6.1 Power Level Escalations NOTE CEAs should be above the Long-term Steady State Insertion Limit (102 inches withdrawn on Group 5) before reaching 20% core power and at a position to begin controlling ASI at the ESI between 20% and 50% power.

Refer to NOP-100.02, Axial Shape Index Control, for furtherguidance.

1.

As Main Generator loading commences, MAINTAIN T -avg at T -ref by:

A.

CEA withdrawal in Manual Sequential.

AND/OR B.

Boron concentration changes in accordance with 2-NOP-02.24, Boron Concentration Control.

NOTE Contact Reactor Engineering if further assistance is required when using Appendix B.

2.

At or above 50% power (or 30% if a shape annealing factor test is performed), refer to Appendix B for power escalation rates.

3.

At or above 50% power:

A.

All planned reactivity additions should be made by boration or dilution in accordance with 2-NOP-02.24, Boron Concentration Control.

B.

USE CEAs for ASI control, CONSIDER the reactivity effect of CEAs when adjusting AS1.

C.

REFER to NOP-100.02, Axial Shape Index Control, for specific instructions regarding ASI control during power escalations.

a

~------------------------------------------~ =

6 Appendix D Operator Action Form ES-D-2 Op Test No.:

1 Scenario #

2 Event #

...,;2;;...... ____ Page 4

of 16 Event

Description:

CEDM Fan 21 A sheared shaft Time L

Position 1 Applicant's Actions or Behavior Booth Operator Instructions: As soon as turnover is complete, trigger CEDM 21A sheared shaft.

Control Room Indications Available: HVE-21A AMP meter (AM-507) indicating low.

Annunciator X-8 CEDM Fan Flow I Low. Five minutes later X-2, CEDM Air Cooler Temp. Hi.

BOP Recognize annunciator X-8 and identifies no CEDM cooling fans are running. (low amps on HVE-21 B)

Recognize TR-25-3 PT07 increasing temperature Places HVE-21A to STOP Start HVE-21B when directed. (Note: procedure requires a 10 minute delay to start backup fan after stopping running fan)

Step 4.2.2.1, 2-AOP-25.01, Loss of RCB Cooling Fans (attached page 7) If not started within 45 minutes of loss of HVE-21A, a Reactor trip must be manually initiated.

Scenario 2 Rev. 1

7 REVISION NO.:

o PROCEDURE TITLE:

LOSS OF RCB COOLING FANS PAGE:

70f21 PROCEDURE NO.:

2-AOP-25.01 ST. LUCIE UNIT 2 I INSTRUCTIONS I I CONTINGENCY ACTIONS I 4.2.2 Loss of CEOM Cooling Fan CAUTION At least one CEDM Cooling Fan must be operating to maintain the reactor vessel support structure within its design basis. Operator action is required within 45 minutes to restore a CEDM Cooling Fan OR initiate reactor trip and cooldown to at least Hot Shutdown. The total time allowed from the loss of a CEDM Cooling Fan to Hot Shutdown is 5 hours5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br />.

(Section 6.2 Commitment 1, Section 6.2 Commitment 2)

To ensure motor is NOT started while rotating in reverse, a time delay of approximately 10 minutes shall be observed before starting a CEDM

~ooling Fan to limit starting current.

D

1.

WHEN 10 minutes from time of CEDM Cooling Fan trip has

elapsed, THEN START standby CEDM Cooling Fan.

HVE-21A HVE-21B 1.1 PERFORM Attachment 1, CEDM Cooling Fan Local Breaker Operations.

1.2 PERFORM one start attempt of any available CEDM COOling Fan.

1.3 IF NO CEDM Cooling Fan is

running, THEN PERFORM the following:

A.

IMPLEMENT 2-AOP-22.01,

Rapid Downpower.

B.

NOTIFY EM.

1.4 IF NO CEDM Cooling Fan is running at 45 minutes from fan

trip, THEN PERFORM the following (Section 6.2 Commitment 1, Section 6.2 Commitment 2):

A.

TRIP reactor.

B.

IMPLEMENT 2-EOP-01, Standard Post Trip Actions.

8 Appendix D Operator Action Form ES-D-2 Op Test No.:

......;..,- Scenario #

2 Event #

_3~ ____ Page 2..- of

...;..;16~-I Event

Description:

Letdown flow controller HIC-1110 goes to maximum flow Time I

Position I

Applicant's Actions or Behavior Booth Operator Instructions: When directed trigger HIC*111 0 maximum flow Control Room Indications Available: Annunciator M*5 Letdown Press High/Low Letdown flow indicates full scale high Recognize and communicate letdown flow >128 gpm and HIC-1110 controller output to full scale high.

Perform step 4.2.6.1.A.1 through A.3 of 2-AOP-02.03, Charging RO and Letdown, to control letdown (attached page 9)

NOTE: due to the nature of this failure, previewing manual (step A.1.1 in procedure) will show the same output as automatic. Matching manual to auto cannot be accomplished.

Scenario 2 Rev. 1

9 REVISION NO.:

PROCEDURE TITLE:

PAGE:

0 PROCEDURE NO.:

CHARGING AND LETDOWN 14 of 39 2-AOP-02.03 ST. LUCIE UNIT 2 I INSTRUCTIONS I I CONTINGENCY ACTIONS I 4.2.6 Letdown Level Control Malfunction D

1.

IF letdown level control is malfunctioning, THEN PERFORM the following:

A.

VERIFY the output of A.1 PLACE HIC-1110, LEVEL, HIC-1110, LEVEL, (Letdown Level Controller) in (Letdown Level Controller)

MANUAL by performing the is responding as expected following:

to current plant conditions.

1.

BALANCE HIC-1110 MANUAL to AUTO controller output signals by previewing and using the MANUAL control knob to match the manual and auto controller output signals.

2.

PLACE HIC-1110 in MANUAL.

3.

ADJUST letdown flow to a value consistent with the current plant conditions.

4.

PERFORM a system walkdown observing for leaks or lifting relief valves.

B.

VERIFY the selected level B.1 PLACE the alternate level control control valve is responding valve in service per 2-NOP-02.02, as expected to HIC-111 0 Charging and Letdown.

output.

10 Appendix D Operator Action Form ES-D-2 Op Test No.:

Scenario #

2 Event #

_4..;.....-____ Page 6

of 16 Event

Description:

2B Intake cooling water pump motor bearing failure Time I

Position I

Applicant's Actions or Behavior Booth Operator Instructions: Trigger 2B ICW pp motor failure when directed.

Trigger align 2C ICW to 2B header when called from Control room.

Call as NPO five minutes after notified to align 2C to 2B header, 2C ICW pump is ready to start. Three minutes after pump has started, inform the control room 2C ICW pump discharge valve is fully opened.

Control Room Indications Available: Increasing amps on AM-833. When pumps trips annunciator E-30 ICW Headers Press low BOP Recognize increasing amps on 2B ICW pump. Recommends tripping pump prior to overcurrent trip.

Perform section 4.2.2 contingency actions 1.1 and 1.2.B of 2-AOP-21.03B 2B Intake Cooling Water System Header (attached page 11) as directed Monitor Main Generator cold gas temperatures. Step 6 of.

Performs Attachment 1 section 2.0 (attached page 12-14) to align and start 2C ICW pump on the 2B header as directed RO Bypass CVCS Ion Exchanger by placing V2520 to BYPASS when directed. (Attachment 1 step 2.0.5)

Note: crew will probably stop up power at this time until two ICW pumps are in service.

BOP When directed place turbine on hold.

When directed stop dilution lAW 2-NOP-02.24, Boron RO Concentration Control, step 6.5.16 through 6.5.20 (attached page 4)

RO When 2C ICW pump alignment and venting complete, place CVCS Ion Exchanger V2520 back to Ion Exchanger.

Scenario 2 Rev. 1

11 REVISION NO.:

3 PROCEDURE NO.:

PROCEDURE TITLE:

28 INTAKE COOLING WATER SYSTEM HEADER PAGE:

7 of 45 2-AOP-21.038 ST. LUCIE UNIT 2 I INSTRUCTIONS I 4.2.2 2B ICW Pump OvrldfTrip o

1.

VERIFY 28 lew pump amps normal.

I CONTINGENCY ACTIONS I 1.1 IF 28 lew pump indicates abnormally high amps, THEN PERFORM the following:

A.

PLACE 28 lew pump control switch to PULL TO LOCK position.

B.

PERFORM Section 2.0.

1.2 IF 28 lew pump TRIPPED, THEN PERFORM the following:

A.

IF health and safety of the public is in jeopardy, THEN ATTEMPT one restart only.

(Section 6.1.3 Management Directive 1)

B.

IF 28 lew pump was NOT restarted, THEN PERFORM Section 2.0.

12 REVISION NO.:

3 PROCEDURE TITLE:

PAGE:

28 INTAKE COOLING WATER SYSTEM HEADER PROCEDURE NO.:

2-AOP-21.038 ST. LUCIE UNIT 2 ATTACHMENT 1 Start Standby Pump On 2B ICW Header With Header Depressurized (Page 3 of 5) 2.0 STARTING 2C ICW PUMP FROM STANDBY CONDITION

1.

ENSURE 2B ICW Pump Control Switch in PULL TO LOCK position.

2.

ENSURE 2C ICW Pump control switch in PULL TO LOCK position.

3.

ENSURE 2C ICW Pump aligned to 2B ICW header.

28 of 45 A.

LOCK CLOSED SB21165, 2C ICW PUMP X-TIE DISCH TO 'A' TRAIN ISOL.

(I NTKl9/N-4IW-C)

B.

LOCK OPEN SB21211, 2C ICW PUMP X-TIE DISCH TO 'B' TRAIN ISOL.

(I NTKl9/N-4IW-C)

4.

THROTTLE 2C ICW PUMP DISCH ISOL, approximately 10 turns OPEN, SB21206.

(I NTKl18/N-31W-C)

5.

BYPASS CVCS Ion Exchangers by placing V2520, ION EXCHANGER BYPASS VALVE, to BYPASS.

(RTGB-205)

6.

MONITOR Generator Average Cold Gas temperature.

IF Average Cold Gas Temperature rises to 47°C, THEN REDUCE MVARS to minimum, but NOT less than (unity) 0 MVARS.

(Section 6.1.3 Management Directive 2)

IF Average Cold Gas Temperature rises to 50.7°C, THEN IMPLEMENT 2-AOP-22.01, Rapid Downpower to REDUCE power as necessary to stabilize main generator cold gas temperature.

7.

IF 2C COMPONENT COOLING WATER Pump is NOT running, THEN ENSURE AB 4.16kv bus ALIGNED to B side.

A.

ENSURE 2C COMPONENT COOLING WATER Pump control switch in PULL TO LOCK position.

B.

OPEN Bkr 2-20505, 4.16KV BUS TIE 2AB - 2A3. (RTGB-201)

C.

OPEN Bkr 2-20208, 4.16KV BUS TIE 2A3 - 2AB. (RTGB-201)

D.

CLOSE Bkr 2-20409, 4.16KV BUS TIE 2B3 - 2AB. (RTGB-201)

E.

CLOSE Bkr 2-20504, 4.16KV BUS TIE 2AB - 2B3. (RTGB-201)

13 REVISION NO.:

3 PROCEDURE TITLE:

PAGE:

2B INTAKE COOLING WATER SYSTEM HEADER PROCEDURE NO.:

2-AOP-21.03B ST. LUCIE UNIT 2 ATTACHMENT 1 Start Standby Pump On 2B ICW Header With Header Depressurized (Page 4 of 5) 2.0 STARTING 2C ICW PUMP FROM STANDBY CONDITION (continued)

8.

WHEN 2C ICW Pump alignment is complete, THEN START 2C ICW Pump.

29 of 45

9.

IF 2C ICW pump start was NOT successful, THEN GO TO Attachment 2, Contingency Action With 2B ICW Header Depressurized.

10.

As pressure begins to rise in 2B ICW Header as indicated by PI-21-5C, 2C ICW PUMP DISCH PRESS (INTKl26/N-3/E-B), SLOWLY OPEN, SB21206, 2C ICW PUMP DISCH ISOL, until valve is fully OPEN.

11.

LOCK OPEN, SB21206, 2C ICW PUMP DISCH ISOL.

12.

IF 2C COMPONENT COOLING WATER Pump OR 2C ICW Pump are operating and supplying the applicable header, THEN ENSURE Tech Spec requirements of Section 3.7.3 and 3.7.4 are satisfied.

NQ!.E The following step will require a ladder at CCW platform for access to HX vent valves and a pipe wrench to remove vent caps.

13.

VENT 2B ICW Header until a steady stream of water issues by opening and closing each of the following valves individually:

A.

SH21337, SS-21-1B VENT (CCW/28/N-ElW-4)

B.

SH212050, SS-21-1B BACKWASH OUTLET VENT (CCW/31/N-EIW-4)

C.

SH21244, 2B CCW HX TUBE SIDE INLET HEAD VENT (CCW/32/S-DIW-4)

D.

SH21245, 2B CCW HX ICW OUTLET VENT (CCW/38/N-ElW-2)

E.

SH21363, SS-21-4B VENT (GB/26/S-211W-G)

F.

SH21218, 2B TCW HX TUBE SIDE OUTLET HEAD VENT (TGB/26/N-22/E-K)

G.

SH21219, 2B TCW HX TUBE SIDE INLET HEAD VENT (TGB/26/N-221W-D)

14 REVISION NO.:

3 PROCEDURE TITLE:

PAGE:

26 INTAKE COOLING WATER SYSTEM HEADER PROCEDURE NO.:

2-AOP-21.036 ST. LUCIE UNIT 2 ATTACHMENT 1 Start Standby Pump On 2B ICW Header With Header Depressurized (Page 5 of 5) 2.0 STARTING 2C ICW PUMP FROM STANDBY CONDITION (continued)

14.

ENSURE SH40077, 2C ICW HYPO HDR ACID RETURN ISOL, OPEN (I NTKl17/N-3/E-C).

15.

ENSURE SH40078, 2B ICW HYPO HDR ACID RETURN ISOL, CLOSED (INTKl18/S-3/E-C).

30 of 45

15 Appendix D Operator Action Form ES-D-2 Op Test No.: ----

Scenario #

2 Event #

...,;5;;...... ____ Page 7

of 16 Event

Description:

2B SG tube leak 10 GPM Time I

Position I

Applicant's Actions or Behavior Booth Operator Instructions: Trigger 2B SGTL, when directed Control Room Indications Available: Five minutes after trigger, SJAE radiation alarm on PC-11.

NOTE: due to letdown flow control in manual, Charging and letdown mismatch will not be evident until letdown is manually reduced due to SG tube leakage.

Recognize Pressurizer level lowering. Carry out actions as RO directed by SRO lAW 2-AOP-08.02, Steam Generator Tube Leak' (attached page 17-24)

When recognized SGTL >75 GPD, commence a rapid down power at 10 MW/min per 2-AOP-22.01, Rapid Downpower, to attain the following: (attached page 25-28)

Power equal to or less than 50% in 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />

. Mode 3 within next 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> Manually control letdown to maintain Pressurizer level. When letdown controlled to maintain Pressurizer level, estimate leak rate of approximately 10 gpm.

Acknowledge and communicate PC-11 SJAE radiation alarm.

BOP Carry out actions as directed by SRO lAW 2-AOP-08.02, Steam Generator Tube Leak' (attached page 17-24)

Recognize SG blowdown radiation trending up.

Program DEH for rapid downpower lAW 2-AOP-22.01, Rapid Downpower. When Tave lowering depress 'GO' on DEH.

Scenario 2 Rev. 1

16


~-.-----

Appendix D Operator Action Form ES-D-2 Op Test No.:

.......;.-- Scenario #

2 Event #

___.5 _____ Page 8

of 16 Event

Description:

2B SG tube leak 10 GPM Time I

Position I

Applicant's Actions or Behavior Booth Operator Instructions:

Control Room Indications Available:

BOP When directed commence Turbine downpower at 10 MW/min When directed, notify field operator to verify:

SGBTF truck bay door closed

  • HVS-10A or B running HVE-41 A or B running
  • SGBD Ventilation Process monitor in service Scenario 2 Rev. 1

17 PROCEDURE TITLE:

PAGE:

REVISION NO.:

o STEAM GENERATOR TUBE LEAK 6 of 46 PROCEDURE NO.:

2-AOP-08.02 I INSTRUCTIONS I 4.0 OPERATOR ACTIONS 4.1 Immediate Operator Actions None 4.2 Subsequent Operator Actions 4.2.1 General Actions ST. LUCIE UNIT 2 I CONTINGENCY ACTIONS I

1.

VERIFY pressurizer level stable or 1.1 OPERATE charging pumps per. Charging Pump Guidance. as required to stabilize or raise pressurizer level.

rising and pressure norma\\.

1.2 IF pressurizer heaters are NOT operating automatically, THEN manually OPERATE pressurizer heaters to maintain pressure at 2250 psia (2225 to 2275 psia) or as directed by US.

1.3 IF all available charging pumps are running AND pressurizer level is still dropping, THEN ISOLATE letdown as follows:

A.

CLOSE V2516.

CONTAINMENT ISOL VALVE -IC.

B.

CLOSE V2522, CONTAINMENT ISOL VALVE-OC.

C.

CLOSE V2515, STOP VALVE-IC.

18

--"""----~-------------------

PROCEDURE TITLE:

PAGE:

REVISION NO.:

o STEAM GENERATOR TUBE LEAK 70f46 PROCEDURE NO.:

2-AOP-OS.02 I INSTRUCTIONS I 4.2.1 General Actions (continued)

1.

(continued)

ST. LUCIE UNIT 2 I CONTINGENCY ACTIONS I 1.4 I F the following conditions are

met, All available charging pumps are running Letdown is isolated Pressurizer level is lowering THEN PERFORM one of the following:

A.

IF in Mode 1 or 2, THEN TRIP reactor and GO TO 2-EOP-01, Standard Post Trip Actions.

B.

IF in Mode 3, SIAS NOT blocked THEN GO TO 2-EOP-04, Steam Generator Tube Rupture.

C.

IF in Mode 3, SIAS

blocked, THEN IMPLEMENT Low Mode AOP for current plant conditions.

19 PROCEDURE TiTlE:

PAGE:

REVISION NO.:

o STEAM GENERATOR TUBE LEAK 80f46 PROCEDURE NO.:

2-AOP-08.02 ST. LUCIE UNIT 2 I INSTRUCTIONS I I CONTINGENCY ACTIONS I 4.2.1 General Actions (continued)

NOTE A full isotopic analysis of steam generator water activity could take up to an hour. If an expeditious indication of gross activity is required, a frisk in the Secondary Lab or a quick count gamma analysis in the Hot Lab will yield the necessary information to determine the gross magnitude and source of leak.

o

2.

o

3.
4.

G

5.

NOTIFY Chemistry of probable SIG tube leakage and to begin sampling for activity.

REQUEST Radiation Protection conduct secondary area radiation surveys.

IF Air Ejector or Steam Generator Blowdown monitor is NOT spiking, THEN ESTIMATE leakage by comparing Air Ejector Monitor or Steam Generator Blowdown Monitor reading with Daily Chemistry Report.

IF unable to estimate primary to secondary leakage or the radiation monitors are out of

service, THEN ESTIMATE leak rate from Chemistry sample.

4.1 IF Air Ejector or Steam Generator Blowdown monitor is spiking, THEN USE the maximum monitor readings and ANNOTATE estimated leakage as "spiking".

4.2 REFER TO Attachment 1, General Information for discussion of spiking characteristics.

20 REVISION NO.:

o PROCEDURE TITLE:

PAGE:

STEAM GENERATOR TUBE LEAK PROCEDURE NO.:

2-AOP-OS.02 ST. LUCIE UNIT 2 I INSTRUCTIONS I I CONTINGENCY ACTIONS I 4.2.1 General Actions (continued)

NOTE A prompt determination of the leak rate takes precedence over fulfilling the 2-hour time requirement of 2-0SP-01.03, Reactor Coolant System Inventory Balance.

GJ

6.

DETERMINE primary to secondary leak rate by one of the following methods:

Charging I letdown mismatch 2-0SP-01.03, Reactor Coolant System Inventory Balance NOTE A time delay may exist between an increase in SJAE Monitor reading and Steam Generator Blowdown Monitor readings.

GJ

7.

IF sample flow is available to the radiation monitors, THEN LOG Air Ejector monitor or Steam Generator Blowdown Radiation Monitor readings every 15 minutes on Attachment 6, Steam Jet Air Ejector/Steam Generator Blowdown Monitoring.

9 of 46

21 REVISION NO.:

o PROCEDURE TITLE:

PAGE:

STEAM GENERATOR TUBE LEAK PROCEDURE NO.:

2-AOP-OS.02 ST. LUCIE UNIT 2 10 of 46

'INSTRUCTIONS I I CONTINGENCY ACTIONS I 4.2.1 General Actions (continued)

GJ NOTE Quick diagnosis of a tube leak and subsequent rapid isolation of the affected S/G will minimize secondary contamination and radiation exposure. (Section 6.1.3 Management Directive 1)

All available radiation monitors should be monitored to confirm and quantify leakage. (Section 6.1.3 Management Directive 1)

Prior to confirmation of a tube leak, planning and preparation for unit shutdown and mitigating the affects should commence by performing notifications, procedure reviews, crew briefings, and ensuring resources are available to support unit conditions.

(Section 6.1.3 Management Directive 1)

8.

CONFIRM S/G tube leakage using any of the following:

Plant response (pressurizer level dropping, letdown lowering, lower Feedwater flow to affected SIG, etc.)

Secondary radiation monitors rising High activity or rising trends on any of the following radiation monitors:

SIG liquid sample Main steam line S/G blowdown Chemistry analysis Rising SIG water level 8.1 IF radiation monitor is determined to be failed AND NO S/G tube leakage exists, THEN PERFORM the following:

A.

NOTIFY RP.

B.

NOTIFY Chemistry.

C.

EXIT this procedure.

22 REVISION NO.:

PROCEDURE TITLE:

PAGE:

0 STEAM GENERATOR TUBE LEAK PROCEDURE NO.:

11 of 46 2-AOP-08.02 ST. LUCIE UNIT 2

'INSTRUCTIONS,

I CONTINGENCY ACTIONS,

4.2.1 General Actions (continued)

G

9.

IF at any time S/G blowdown sample flow isolates on high radiation, THEN PERFORM the following as necessary to support S/G sampling by Chemistry:

PLACE FCV-23-7, 9, SAMPLE, in CLOSE I OVRD OPEN FCV-23-7, 9, SAMPLE 0

10.

DISPATCH a field operator to the SGBTF to perform the following:

A.

VERIFY SGBTF Truck Bay A.1 CLOSE SGBTF Truck Bay (roll-up) door is CLOSED.

(roll up) door.

B.

VERIFY the following B.1 PLACE SGBTF ventilation SGBTF ventilation systems systems in service per are in operation:

NOP-25.01, SGBTF Ventilation System.

Supply Fans HVS 10A or HVS-10B Exhaust Fans HVE 41A or HVE-41B SGBTF Ventilation Process Monitor

23 REVISION NO.:

o PROCEDURE TITLE:

STEAM GENERATOR TUBE LEAK PAGE:

12 of 46 PROCEDURE NO.:

2-AOP-OS.02 ST. LUCIE UNIT 2 I INSTRUCTIONS I I CONTINGENCY ACTIONS I 4.2.1 General Actions (continued)

D D

D D

11.

EVALUATE isolating blowdown and vacuum drag on Unit 1.

12.

VERIFY steam generator blowdown aligned to Monitor Storage Tanks.

NOTE 12.1 ALIGN steam generator blowdown to the Monitor Storage Tanks per 2-NOP-23.02, Steam Generator Slowdown System Operations.

If conditions or steam generator tube leakage change, rediagnosis of shutdown conditions is required to ensure compliance with EPRI guidelines and Technical Specifications.

Leak rate changes should be evaluated over a minimum of 30 minutes.

  • , General Information, provides a basic summary of EPRI Action Levels and recommendations for minimizing the likelihood of tube rupture.
13.

IF in MODE 1 through 3 and SIAS is NOT blocked, THEN GO TO Section 4.2.2.

14.

IF in MODE 3 through 6 and SIAS is blocked, THEN GO TO Section 4.2.3.

24 REVISION NO.:

PROCEDURE TITLE:

PAGE:

0 STEAM GENERATOR TUBE LEAK PROCEDURE NO.:

13 of 46 2-AOP-OB.02 ST. LUCIE UNIT 2 I INSTRUCTIONS I I CONTINGENCY ACTIONS I 4.2.2 Mode 1 through 3 - SIAS Not Blocked 0

1.

VERIFY leak rate is less than 1.1 IMPLEMENT a rapid downpower 75 gpd.

at 10 MW/min per 2-AOP-22.01, Rapid Downpower, to attain the following:

Power equal to or less than 50% in 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> Mode 3 within next 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> 1.2 GO TO Section 4.2.2 Step 6.

0

2.

IF leak rate is less than 75 gpd and greater than 30 gpd, THEN PERFORM the following:

A.

ENSURE RMS monitoring is performed at 15 minute intervals.

B.

IF leak rate has been stable for 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or greater, THEN REDUCE sampling interval to 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />.

25 REVISION NO.:

4 PROCEDURE TITLE:

PAGE:

RAPID DOWNPOWER PROCEDURE NO.:

2-AOP-22.01 ST. LUCIE UNIT 2 I INSTRUCTIONS I I CONTINGENCY ACTIONS I 4.0 OPERATOR ACTIONS NOTE OPS-530, Pre-Planned Power Change Guidance, delineates operations department policy for the use of pre-planned down power profiles provided by the Plant Physics Curve Book.

4.1 Immediate Operator Actions o

1.

o

2.

o

3.

BEGIN boration per operator aid.

PERFORM the following:

A.

PROGRAM the turbine DEH for the desired load reduction rate.

B.

SET DEMAND to desired power level.

INSERT the Lead CEA Group approximately 6 inches to initially lower RCS temperature.

5 of 39

26 PROCEDURE TITLE:

PAGE:

REVISION NO.:

4 RAPID DOWNPOWER 6 of 39 PROCEDURE NO.:

2-AOP-22.01 ST. LUCIE UNIT 2 I INSTRUCTIONS I 4.2 Subsequent Operator Actions

1.

D

2.

D

3.

D

4.

D

5.

WHEN a Tavg lowering is noted, THEN PRESS the GO pushbutton on the turbine DEH control panel.

IF reducing power by more than 20%, THEN NOTIFY SNPO to secure Zinc Injection per 2-NOP-02.26, Zinc Addition.

NOTIFY plant personnel using Gai-tronics and boost function as follows:

"Attention all personnel, Unit 2 has commenced a Rapid Downpower due to (reason)

NOTIFY System of the rapid downpower load reduction.

PLACE Pressurizer on recirculation per Attachment 5, Pressurizer Recirculation Guidelines.

I CONTINGENCY ACTIONS I 1.1 IF in turbine MANUAL, THEN PRESS and RELEASE the GV LOWER pushbutton as necessary to reduce I control the load reduction rate.

27 REVISION NO.:

4 PROCEDURE NO.:

PROCEDURE TITLE:

PAGE:

RAPID DOWNPOWER 70f39 2-AOP-22.01 ST. LUCIE UNIT 2 I INSTRUCTIONS I I CONTINGENCY ACTIONS I 4.2 Subsequent Operator Actions (continued) o

6.

START additional charging pump as required per guidance from, Charging Pump Guidance.

NOTE O-NOP-100.02, Axial Shape Index Control, provides additional guidance on ASI Control.

US may direct temporary operation outside of ASI limit.

o

7.

MAINTAIN Axial Shape Index

+/-O.5 of ESI using CEAs.

7.1 IF operation outside ASllimit is unavoidable, THEN PERFORM the following:

A.

NOTIFY US.

B.

MAINTAIN ASI within RPS LPD pre-trip limits.

C.

RESTORE ASI to within limits as soon as practical.

7.2 IF ASI CANNOT be maintained within transient band due to the inoperability of CEA( s},

THEN CONTACT Reactor Engineering to assist in determining the load reduction rate to minimize effects of operation outside of transient limits.

28

~--.. ~~~~-------~--------------------------

PROCEDURE TITLE:

PAGe:

REVISION NO.:

4 RAPID DOWNPOWER 8of39 PROCEDURE NO.:

2-AOP-22.01 ST. LUCIE UNIT 2 I INSTRUCTIONS I I CONTINGENCY ACTIONS I 4.2 Subsequent Operator Actions (continued)

8.

MAINTAIN T ref and T avg within 6.6°F.

9.

VERIFY boration lineup per, RCS Boration Guidance 8.1 VERIFY boration flow path to RCS.

8.2 ESTABLISH T ref and Tavg within 6.6 OF using any of the following:

RCS Boration Rate CEA Position Turbine Load 8.3 IF Tref and Tavg can NOT be maintained within 6.6 of, THEN NOTIFY US AND:

A.

TRIP reactor.

B.

GO TO 2-EOP-01,

Standard Post Trip Actions.

29 Appendix D Operator Action Form ES-D-2 Op Test No.: -----

Scenario #

2 Event #

6 Page 9

of 16 Event

Description:

SGTR 200 gpm Time I

Position I

Applicant's Actions or Behavior Booth Operator Instructions: When directed trigger SGTR 2B SG Control Room Indications Available: Pressurizer pressure and level lowering.

RO Recognize rapidly lowering Pressurizer level. Recommend isolating Letdown and starting third charging pump.

BOP Identifies increasing trends on SJAE, Main Steam monitors and SG Blowdown monitors.

RO/BOP Trip the Reactor when directed and carry out 2-EOP-01, Standard Post Trip Actions.

Scenario 2 Rev. 1

30 Appendix D Operator Action Form ES-D-2 Op Test No.:

Scenario #

2 Event #

6 Page 10 of 16

~--------

-=~

Event

Description:

SGTR200 gpm Time I

Position I

Applicant's Actions or Behavior Booth Operator Instructions:

Control Room Indications Available:

Manually trips reactor prior to auto trip. Performs EOP-01 RO Safety Functions as directed for Reactivity Control, Inventory Control, Pressure Control, Core Heat removal NOTE: due to the size of the SGTR, SIAS will not be received until the crew is in EOP-04 Reactivity Control

  • Verify Reactor power is lowering.
  • Verify startup rate is negative.
  • Verify all CEAs are fully inserted.

Inventory Control

  • Verify Pressurizer level is between 10 and 68%
  • Pressurizer level is trending to 30 - 35%.

Pressure Control

  • Verifies RCS pressure is between 1800-2300 psia.
  • Verifies RCS pressure is trending 2225-2275 psia.
  • Verifies RCS subcooling is ~20°F.

Core Heat Removal

  • Verifies at least one RCP running with CCW. ( if >10 minutes with no CCW must secure)
  • Verifies loop delta T is <1 O°F.

Scenario 2 Rev. 1

31 Appendix D Operator Action Form ES-D-2 Op Test No.: ----

Scenario #

2 Event #

_6;...... ____ Page 11 of 16 Event

Description:

SGTR200 gpm Time I

Position I

Applicant's Actions or Behavior Booth Operator Instructions:

Control Room Indications Available:

Verifies turbine trip on reactor trip. Performs EOP-01 Safety BOP functions as directed for: Vital Auxiliaries, RCS Heat Removal, Containment Conditions.

Closes MSR reheat Block valves Notifies NPO to perform Appendix X section 1 of EOP-99.

(outside CR actions) Notify SNPO to check SFP inventory and temperature.

Maintenance of Vital Auxiliaries

  • Verifies turbine governor and throttle valves closed.
  • Verifies GEN Brk open (East breaker, Mid Breaker and Exciter Breaker.)
  • Verifies all vital and non vital AC Buses energized.
  • Verifies all vital and non vital DC Buses energized.

RCS Heat Removal

  • Verify at least one SG has BOTH:

SG Level 20-83% NR Feedwater available, level being restored to 60-70% NR

  • Verify RCS Tavg is between 525 and 535 0 F SG pressure between 850-930 psia via SBCS Scenario 2 Rev. 1

32 Appendix D Operator Action Form ES-D-2 Op Test No.:

.....;...- Scenario #

2 Event #

_6.;..... ____ Page 12 of 16 Event

Description:

SGTR200 gpm Time I

Position 1 Applicant's Actions or Behavior Booth Operator Instructions:

Control Room Indications Available:

Containment Conditions

  • Verifies Containment pressure <2 psig.

BOP

  • Verifies NO Containment radiation monitors in alarm.
  • Verifies Containment temperature is less than 120°F.
  • Verifies NO secondary plant radiation alarms.

(secondary radiation increasing)

SRO should exit 2-EOP-01, Standard Post Trip Actions to 2-EOP-04, Steam Generator Tube rupture. STA should perform Safety Function Status Check Sheets for 2-EOP-04 Scenario 2 Rev. 1

33 Appendix D Operator Action Form ES-D-2 Op Test No.:

......;....- Scenario #

2 Event #

_7.;..l.,8';':",;..9 ___ Page 1l....- of _1;..;;.6---1 Event

Description:

2B MSIV fails to close, Aux. Spray SE-02-3 fails to close, Cooldown and Isolate the 2B SG Time I

Position i

Applicant's Actions or Behavior Booth Operator Instructions:

Control Room Indications Available:

BOP When directed perform 2-EOP-99 Appendix A, sampling SG's (attached page 34,35)

RO Critical On SIAS, when CCW has isolated to the RCP's stop ALL RCP's within 10 minutes.

Task BOP On SIAS, verify available HPSI, LPSI pumps start and associated ECCS injection valves open.

BOP/RO Place all four CCW valves to/from RCP's to CLOSE when CCW lost for greater than 30 minutes.

BOP/RO Place two RCP bleedoff valves to close when CCW lost to RCP's for greater than 30 minutes.

When directed, cooldown the RCS to a THaT less than 510°F using SBCS. NOTE: the RO should place SBCS 8801 to full RO 100% open unit THaT less than 510°F then throttle closed 8801 to obtain a 30°F cooldown in anyone hour period. This is the limit if no RCP's are operating.

When directed depressurize (using Aux. Spray) the RCS to:

  • Within the limits of Fig. 1A RO
  • Less than 930 psia
  • Approximately equal (within 50 psia) to the 2B SG.

NOTE: Aux. spray is ineffective with the Charging loop isolation valves open. When using Aux. spray, both Charging loop isolation valves should be closed.

Recognize Aux. Spray valve SE-02-3 failed to close when RO switch taken to close. Communicate to SRO and re-open Charging loop isolation valves to control de-pressurization.

Scenario 2 Rev. 1

34 REVISION NO.:

PROCEDURE TITLE:

40 PROCEDURE NO.:

APPENDICES I FIGURES I TABLES I DATA SHEETS 2-EOP-99 ST. lUCIE UNIT 2 APPENDIX A SAMPLING STEAM GENERATORS (Page 1 of 2) o 1. !f a lOOP has occurred, Then PERFORM BOTH of the following:

o A. ENSURE 2AB 480V Load Center is aligned to an energized bus.

o B. DISPATCH an operator to restore Instrument Air.

REFER TO Appendix H, Operation of the 2A and 2B Instrument Air Compressors.

CAUTION A Train (...J)

PAGE:

3 of 159 B Train (...J)

If a VALID SIAS occurs, the CCW 'N' header shall NOT be aligned to ANY essential header. This will maintain train separation while safeguards signals are still ~resent.

NOTE HCV-14-9 (HCV-14-10) will open 5 seconds after HCV-14-8A (HCV-14-8B) starts to open When SIAS is present, placing the control switches in CLOSE and then OVERRIDE will open the CCW 'N' header valves, until SIAS is reset o 2..If an INADVERTENT SIAS has closed the 'N' Header

valves, Then PERFORM the following:

o A RESTORE flow from EITHER 'A' or 'B' CCW Header by placing the control switches for the desired train to CLOSE and then to OPEN:

HCV-14-8A HCV-14-9 OR HCV-14-8B HCV-14-10

35 REVISION NO.:

PROCEDURE TITLE:

PAGE:

40 PROCEDURE NO.:

2-EOP-99

2. (continued)

APPENDICES I FIGURES I TABLES I DATA SHEETS ST. LUCIE UNIT 2 APPENDIX A SAMPLING STEAM GENERATORS (Page 2 of 2) o B.!f CIAS or high radiation has closed the SGBD Sample Valves, Then OPEN FCV-23-7 and FCV-23-9 by PLACING the control switch to CLOSE I OVERRIDE and then to OPEN.

o 3. !f..S/Gs can be sampled, Then:

A.

ENSURE OPEN FCV-23-7 and FCV-23-9, SGBD Sample Valves.

B.

DIRECT Chemistry to perform S/G samples for activity and boron.

o 4. Jf S/Gs cannot be sampled, Then DIRECT Health Physics to conduct secondary plant local area radiation surveys.

END OF APPENDIX A 4 of 159

36 REVISION NO.:

40 PROCEDURE NO.:

2-EOP-99 PROCEDURE TITLE:

APPENDICES I FIGURES I TABLES I DATA SHEETS ST. LUCIE UNIT 2 APPENDIX X SECONDARY POST TRIP ACTIONS (Page 5 of 8)

Section 2: CONTROL ROOM ACTIONS PAGE:

118of159 INSTRUCTIONS CONTINGENCY ACTIONS o 1. ENSURE ONLY ONE MFW Pump is RUNNING, with the control switch in RECIRC.

o 2. ENSURE ONLY ONE Condensate Pump is RUNNING.

o 3. !f AFAS has actuated, and use of Main Feedwater is

desired, Then PERFORM ALL of the following:

o A. ENSURE AFAS is RESET.

o B. ENSURE BOTH SIG [Main FRV] Block valves CLOSED.

1. MV-09-5
2. MV-09-6 o C. ENSURE BOTH Low Power MIA Stations in MANUAL.

o D. For EACH MFW header to be placed in service, ENSURE the associated MFIVs are OPEN.

o E. DEPRESS BOTH push buttons to RESET the Low Power Feedwater Valves.

o F. ADJUST the Low Power MIA Stations AS NECESSARY to control SIG levels.

o G. RESTORE AFW to the standby alignment.

37 REVISION NO.:

40 PROCEDURE NO.:

2-EOP-99 PROCEDURE TITLE:

APPENDICES I FIGURES I TABLES I DATA SHEETS ST. LUCIE UNIT 2 APPENDIX X SECONDARY POST TRIP ACTIONS (Page 6 of 8)

Section 2: CONTROL ROOM ACTIONS (continued)

PAGE:

119 of 159 INSTRUCTIONS CONTINGENCY ACTIONS o 4. If AFAS has NOT actuated and use of Main Feedwater is

desired, Then PERFORM ALL of the following:

o A. ENSURE BOTH SIG [Main FRV] Block valves CLOSED.

o B. For EACH MFW header to be placed in service, ENSURE the associated MFIVs are OPEN.

o C. ENSURE BOTH Low Power MIA Stations in MANUAL.

o D. DEPRESS BOTH pushbuttons to RESET the Low Power Feedwater Valves.

o E. ADJUST the Low Power MIA Stations AS NECESSARY to control SIG levels.

o 5. ENSURE BOTH Heater Drain Pumps are STOPPED.

o 6. ENSURE BOTH of the following:

o A. Bearing Oil Pump and Seal Oil Backup Pump RUNNING.

o B. When the turbine reaches 600 rpm, Then Bearing Oil Lift Pump RUNNING.

o A.1 ENSURE Emergency Bearing Oil Pump RUNNING.

38 REVISION NO.:

PROCEDURE TITLE:

PAGE:

40 PROCEDURE NO.:

APPENDICES I FIGURES I TABLES I DATA SHEETS 120 of 159 2-EOP-99 ST. LUCIE UNIT 2 APPENDIX X SECONDARY POST TRIP ACTIONS (Page 7 of 8)

Section 2: CONTROL ROOM ACTIONS (continued)

INSTRUCTIONS o 7. ENSURE the Turbine Drain Valves are OPEN.

o 8. ENSURE ONLY ONE Turbine Cooling Water Pump is RUNNING.

o 9. VERIFY Turbine Generator Bearing Oil temperature between 110 to 120°F.

CONTINGENCY ACTIONS o 9.1 DIRECT a field operator to adjust TCW to the in-service TLO Cooler to maintain outlet Oil temperature between 110 to 120°F.

o 10. When Turbine speed reaches ZERO 010.1 PERFORM ALL of the following:

rpm, Then VERIFY the turning gear automatically ENGAGES.

o 11.!f Reactor power history is low, Then CONSIDER reducing steam generator blowdown flow to maintain RCS temperature.

o A. PLACE Turning Gear in MANUAL.

o B. VERIFY the Turning Gear Permissive Light is ON.

o C. Locally ENSURE the Turning Gear is ENGAGED.

o D. Locally START the Turning Gear.

39

~.~~---~~--~~~~~~~~~-------------

REVISION NO.:

40 PROCEDURE NO.:

2-EOP-99 PROCEDURE TITLE:

APPENDICES I FIGURES I TABLES I DATA SHEETS ST. LUCIE UNIT 2 APPENDIX X SECONDARY POST TRIP ACTIONS (Page 8 of 8)

Section 2: CONTROL ROOM ACTIONS (continued)

PAGE:

121 of 159 INSTRUCTIONS CONTINGENCY ACTIONS o 12. Place Boron Dilution Alarm System in Operation.

When indicated Reactor power is less than 10-5%,

Then PERFORM BOTH of the following:

o A. ENERGIZE BOTH channels of Startup Nuclear Instrumentation to place the Boron Dilution Alarm System in operation.

o B. VERIFY BOTH Boron Dilution Alarm System Channels are operating.

012.1 11 BOTH Boron Dilution Alarm System channels are NOT operating, Then PERFORM applicable actions of 2-AOP-02.01, Boron Concentration Control System (BCCS) Abnormal Operations.

HQIg Excessive moisture can build up in CEDMC's room, and impact equipment reliability if 15 KW heaters are not energized after plant shutdown.

o 13. NOTIFY SNPO to energize 15 KW heater located in the CEDMC's room to minimize humidity build-up per 2-NOP-25.10, CEDMCS Air Conditioning System Operation.

o 14.CONSIDER contacting the Division Load Dispatcher for a switching order to OPEN the Main Generator disconnects.

END OF APPENDIX X

40 Appendix D Op Test No.:

Event

Description:

Operator Action Form ES-D-2 Scenario #

2 Event #

_7;..:.,8;;;.:,,9;;...... ___ Page ~

of.......;..;16;.........,

2B MSIV fails to close, Aux. Spray SE-02-3 fails to close, Cooldown and Isolate the 2B SG Time I

Position I

Applicant's Actions or Behavior Booth Operator Instructions:

Control Room Indications Available:

BOP When directed perform Appendix X, section 2 (attached page 36-39)

BOP When directed (T HOT less than 510°F) isolate the 2B SG per 2-EOP-99 Appendix R (attached page 41-43)

BOP Recognize and communicate to SRO, the 2B MSIV, HCV Critical 1 B, failed to close from the Control Room. Recommend to SRO Task perform EOP-99 Appendix I to locally close HCV-08-1 B.

When 2B SG isolated, cooldown to obtain a 30°F cooldown in anyone hour period and depressurization to:

RO

  • Within the limits of Fig. 1A
  • Less than 930 psia
  • Approximately equal (within 50 psia) to the 2B SG.

Suggested termination point;

  • 2B SG isolated including local closure of 2B MSIV, HCV-08-1 B.

Cooldown and depressurization controlled to the above limits.

Scenario 2 Rev. 1

41 REVISION NO.:

PROCEDURE TITLE:

PAGE:

40 PROCEDURE NO.:

2-EOP-99 APPENDICES I FIGURES I TABLES I DATA SHEETS ST. LUCIE UNIT 2 APPENDIX R STEAM GENERATOR ISOLATION (Page 4 of 6)

Section 2: 2B Steam Generator Isolation CAUTION 96 of 159 If SIG isolation is due to a SGTR the secondary plant may have higher than normal radiation levels. Contact Health Physics for area accessibility instructions.

D 1. ENSURE HCV-08-1B, Main Steam Header 'B' Isolation Valve (MSIV), is CLOSED.

D 2. !f HCV-08-1 B did not close remotely, Then PERFORM local closure.

REFER TO Appendix I, MSIV Local Closure.

D 3. ENSURE MV-08-1 B, MSIV Header 'B' Bypass Valve, is CLOSED.

NOTE Instrument air must be available to close MFIVs using RTGB control switch.

If instrument air is NOT available when MFIV closure is required, then manual initiation of MSIS should be considered.

D 4. ENSURE HCV-09-2A, Main Feedwater Header 'B' Isolation Valve, is CLOSED.

D 5. ENSURE HCV-09-2B, Main Feedwater Header 'B' Isolation Valve, is CLOSED.

D 6. !f BOTH HCV-09-2A and HCV-09-2B, Main Feedwater Isolation Valves to SIG 2B, are NOT CLOSED or suspected of leaking, Then PERFORM ANY of the following AS NECESSARY:

D A. ENSURE ALL of the following valves are CLOSED:

D MV-09-6, Stm Gen 2B Reg Block Valve D LCV-9006, 2B 15% Bypass D MV-09-4, 2B 100% Bypass D B. STOP BOTH Main Feedwater Pumps.

D 7. ENSURE FCV-23-5, 2B SG Blowdown, is CLOSED.

42 REVISION NO.:

PROCEDURE TITLE:

PAGE:

40 PROCEDURE NO.:

2-EOP-99 APPENDICES I FIGURES I TABLES I DATA SHEETS ST. LUCIE UNIT 2 APPENDIX R STEAM GENERATOR ISOLATION (Page 5 of 6)

Section 2: 2B Steam Generator Isolation (continued) o 8. ENSURE FCV-23-6, 2B SG Blowdown, is CLOSED.

o 9. ENSURE MV-08-19B, 2B SIG Atmos Dump VI v, is CLOSED.

D 10.CLOSE MV-08-17, 2B SIG ADV Isol.

o 11.PLACE the control switch for auxiliary feed, Pump 2B, in STOP.

o 12.ENSURE MV-09-10, Pump 2B Disch to SG 2B Valve, is CLOSED.

D 13.ENSURE MV-09-12, Pump 2C to SG 2B, is CLOSED.

D 14. PLACE MV-08-12, SG 2B Stm to AFW PP 2C, in CLOSE.

D 15.ENSURE MV-08-18B, 2B SIG Atmos Dump Vlv, is CLOSED.

D 16.CLOSE MV-08-16, 2B SIG ADV Isol.

D 17. PERFORM the following LOCAL operations:

D A. UNLOCK and CLOSE V09158, 2C AFW Pump to 2B SIG Isolation.

o B. UNLOCK and CLOSE V09136, 2B AFW Pump to 2B SIG Isolation.

97 of 159 o C. CLOSE SE-08-1, Main Steam to 2C AFW Pump Warm-up Valve Solenoid.

D D. !f SE-08-1, Main Steam to 2C AFW Pump Warm-up Valve Solenoid is NOT CLOSED or suspected of leaking, Then CLOSE V08883, SE-06-1 Inlet Isolation.

(continued on next page)

43 REVISION NO.:

40 PROCEDURE NO.:

2-EOP-99 PROCEDURE TITLE:

APPENDICES I FIGURES I TABLES I DATA SHEETS ST. LUCIE UNIT 2 APPENDIX R STEAM GENERATOR ISOLATION (Page 6 of 6)

Section 2: 28 Steam Generator Isolation (continued) 17.(continued)

PAGE:

98 of 159 o E. !f MV-08-12, S/G 2B Steam to AFW Pump 2C, is NOT CLOSED or suspected of leaking, Then PERFORM ANY of the following AS NECESSARY:

o 1. Locally CLOSE MV-08-12 using the handwheel.

o 2. ISOLATE steam to 2C AFW Pump as follows:

o a. CLOSE MV-08-3, 2C Pump.

o b. Locally CLOSE the following valves:

o V08622, CB #67 Drain o V08618, Drain off MV-08-3 1501 o V08619, Drain off MV-08-3 1501 End of Section 2 END OF APPENDIX R

44 OPERATIONS SHIFT TURNOVER REPORT UNIT 2 CONTROL ROOM Day: Today Desk RCO:

Board RCO:

Protected Train:

B Unit 2 Identified RCS Leakage:

o Unit 2 Unidentified RCS Leakage: 0.012 Unit 2 Scheduled Activities per the OSP: Raise power to 100%

Upcoming ECOs to Hang or Release:

Tech Spec Action Statement: 2A HPSI Pump OPS 513's:

Locked in Annunciators:

Current Status: Unit was down powered to remove the 2A Main feedwater pump to repair a motor oil leak. Repairs have been made and both Main Feedwater pumps and Heater Drain Pumps are running. 2A High Pressure safety injection pump is out of service to repair a motor oil leak, Taken out of service 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> ago. 2-GOP-201 is complete up to step 6.136. Step 6.136 step 4, Nuclear Delta T Power Calibration is NOT required. Step 5 and 6 are N/A.

Equipment Problems:

2A HPSI pump oil leak. Taken out of service 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> ago.

Scenario 2 Rev. 1

45 Applicable Procedures 2-GOP-201, 'Reactor Plant Start-up Mode 2 to Mode l' 2-GOP-1 01, 'Reactor Operating Guidelines During Steady State and Scheduled Load Changes' 2-NOP-02.24, 'Boron Concentration Control' 2-AOP-2S.01, 'Loss of RCB Cooling Fans' 2-AOP-02.03, 'Charging and Letdown' 2-AOP-21.03B, '2B Intake Cooling Water System Header' 2-AOP-OB.02, 'Steam Generator Tube Leak' 2-AOP-22.01, 'Rapid Downpower' 2-EOP-01, 'Standard Post Trip Actions' 2-EOP-04, 'Steam Generator Tube Rupture' Scenario 2 Rev. 1